Insulation Monitor PGR-3200 PGR-3200 MANUAL INSULATION MONITOR REVISION 3-D-111915 NITOR INSULATION MO Copyright © 2015 by Littelfuse, Inc. All rights reserved. Document Number: PM-1025-EN Printed in Canada PGR-3200 Insulation Monitor This page intentionally left blank. Page i Rev. 3-D-111915 PGR-3200 Insulation Monitor TABLE OF CONTENTS PAGE SECTION General....................................................................... 1 Operation................................................................... 1 2.1 Relay Operating Mode ............................................... 1 2.2 Front-Panel Controls .................................................. 1 2.2.1 Reset................................................................ 1 2.2.2 Test.................................................................. 1 2.3 Front-Panel Indication ................................................ 1 2.3.1 Power .............................................................. 1 2.3.2 Insulation Warning ......................................... 1 2.3.3 Active .............................................................. 1 2.3.4 Insulation Alarm ............................................. 1 2.4 Analog Output ............................................................ 1 2.5 Remote Reset .............................................................. 1 2.6 Remote Test ................................................................ 1 3 Installation................................................................. 3 3.1 PGH-5000 and PGH-6000 ......................................... 4 4 Technical Specifications .......................................... 6 4.1 PGR-3200 ................................................................... 6 4.2 PGH High-Tension Couplers..................................... 7 5 Ordering Information.............................................. 7 6 Performance Test ..................................................... 7 6.1 Insulation Test ............................................................ 7 Appendix A PGR-3200 Revision History .......................... 8 1 2 LIST OF FIGURES FIGURE 1 2 3 4 5 6 PAGE PGR-3200 Outline and Mounting Details ................. 2 Connection Diagram for Ungrounded Systems Under 1.3 kV .............................................................. 3 Connection Diagram for Ungrounded 5-kV Systems.............................................................. 3 PGH-5000 Outline and Mounting Details ......................................................................... 4 PGH-6000 Outline and Mounting Details ......................................................................... 5 PGA-0510 Analog Ohm Meter ................................. 5 DISCLAIMER Specifications are subject to change without notice. Littelfuse, Inc. is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction. Page ii Rev. 3-D-111915 PGR-3200 Insulation Monitor This page intentionally left blank. Page iii Rev. 3-D-111915 PGR-3200 Insulation Monitor 1. GENERAL The PGR-3200 Insulation Monitor measures phase-toground resistance to detect electrical-insulation failure in an ungrounded power utilization system. It provides three levels of detection with a 50-k warning with an LED and output contact indication, a 30-k warning with LED indication, and a 10-k alarm with LED and output contact indication. An analog output is provided for predictive maintenance trending. The PGR-3200 can be used to detect faults in ungrounded systems up to 6 kV. It can be directly connected to a system up to 1.3 kV, single or three phase, 50 or 60 Hz. A PGH-series high-tension coupler is required for 5- and 6-kV systems. 2. OPERATION The PGR-3200 actively monitors insulation resistance when it is connected to the supply voltage. All conductors connected to the monitored circuit are included in the insulation measurement. See Fig. 2. 2.1 RELAY OPERATING MODE The PGR-3200 output relays operate in the non-failsafe mode; they energize when an insulation warning or alarm occurs. 2.2 FRONT-PANEL CONTROLS 2.2.1 RESET The front-panel RESET switch is used to reset latching trips. Cycling the supply voltage will also reset the PGR3200. See Section 2.5. 2.2.2 TEST All LED’s will light and output relays will energize when the TEST button is pressed for at least 8 s. 2.3 FRONT-PANEL INDICATION 2.3.1 POWER The green LED’s labelled PWR indicates presence of supply voltage. 2.3.2 INSULATION WARNING The red LED’s labelled 50 k and 30 k will light when those respective insulation resistance values, or lower are measured. 2.3.3 ACTIVE The red LED labelled ACTIVE indicates the monitor is enabled. Page 1 Rev. 3-D-111915 2.3.4 INSULATION ALARM When insulation resistance measures 10 k or less, the red LED labelled <10 k will light. 2.4 ANALOG OUTPUT A non-isolated, 0- to 1-mA output (terminals 25 and 26) indicates insulation resistance. The metering output relates to an insulation-resistance range of 0 to infinity using optional meter PGA-0510. See Figs. 2, 3, and 6. 2.5 REMOTE RESET When remote-reset terminals 18 and 19 (alarm) or 21 and 22 (warning) are connected, a warning or alarm remains latched until the RESET switch is pressed or the remotereset terminals are momentarily opened. If the remote-reset terminals are not connected, the PGR-3200 operates in non-latching mode; a warning or alarm will reset when the fault is removed. 2.6 REMOTE TEST When terminal 29 is connected to ground the monitor will alarm. See Figs. 2 and 3. Response to a test input can take several seconds. Page 2 Rev. 3-D-111915 PGR-3200 Insulation Monitor NOTES: INSULATION MONITOR 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M4 x 13 OR 8-32 x 0.50. 3. OVERALL DIMENSION WHEN MOUNTED ON DIN EN50022 35 mm x 7.5 mm TOP-HAT RAIL. 4. 24 V INPUT IS AVAILABLE ONLY FOR THE PGR-3200-120 ORDERING OPTION. L2/N L1 PHASE <1.3 KV 1 2 3 4 5 6 24 V 7 8 9 10 k INSULATION 10 11 12 50 k INSULATION 13 14 15 TOP 99.80 113.0 (NOTE 3) (3.93) (4.45) POWR-GARD TEST PGR-3200 SERIES RESET PWR INSULATION WARNING 75.0 PUSH 8 s INSULATION ALARM 50 K (2.95) INSULATION MONITOR ACTIVE 30 K <10 K SIDE FRONT 7.4 17 18 19 50 k REMOTE RESET 20 21 22 10 k REMOTE RESET 23 24 25 26 ANALOG OUTPUT 27 28 ENABLE 29 30 PGH >1.3 KV 61.2 (2.41) 75.0 (2.95) 16 (0.29) 99.80 (3.93) 85.0 (3.35) FIGURE 1. PGR-3200 Outline and Mounting Details. 6.9 MOUNTING DETAIL (0.27) BOTTOM Page 3 Rev. 3-D-111915 PGR-3200 Insulation Monitor 3. INSTALLATION NOTE: Mounting, terminal-block connections, and wiring must conform to applicable local electrical codes. Check all applicable codes prior to installation. 24 Vac SUPPLY (SEE NOTE) The PGR-3200 can be surface or DIN-rail mounted. See Fig. 1. Use terminal 6 (L1) as the line terminal and terminal 5 (L2/N) as the neutral terminal. Connect terminal 30 to ground. For systems up to 1.3 kV, connect terminal 2 to one phase on the load side of the starter. Connect terminals for latching operation, remote reset, and remote test as required. See Sections 2.5 and 2.6 and Figs. 2 and 3. Connect an optional PGA-0510 Analog Ohm Meter to terminals 25 and 26. Meter outline, dimensions, and cutout size are shown in Fig. 6. 24 Vac SUPPLY (SEE NOTE) 1 3 2 PHASE <1.3 KV 4 5 6 L2/N L1 7 8 9 11 10 12 10 k INSULATION (Alarm) INSULATION MONITOR 13 14 15 50 k INSULATION (Warning) PGR-3200 SERIES Remote Reset or Latching Mode 10 K REMOTE RESET 50 K REMOTE RESET 16 17 18 19 20 21 22 23 Optional links to latch fault condition. 18 21 Optional Remote Reset ANALOG OUTPUT 24 25 26 PGH >1.3 KV ENABLE 27 28 29 30 Optional External Test M PGA-0510 19 NOTE: 120/24 OR 240 VAC 50/60 HZ ARE ORDERING OPTIONS. 22 USE SPECIFIED SUPPLY VOLTAGE. FIGURE 2. Connection Diagram for Ungrounded Systems Under 1.3 kV. A 1 3 2 PHASE <1.3 KV 7 5 6 L2/N L1 24 V 4 8 9 11 10 12 10 k INSULATION (Alarm) INSULATION MONITOR 13 14 PGH-5000 15 M 50 k INSULATION (Warning) PGR-3200 SERIES Remote Reset or Latching Mode 10 K REMOTE RESET 50 K REMOTE RESET 16 17 18 19 20 21 22 23 Optional links to latch fault condition. 18 21 Optional Remote Reset ANALOG OUTPUT 24 25 26 PGH >1.3 KV ENABLE 27 28 29 30 Optional External Test M PGA-0510 19 NOTE: 120/24 OR 240 VAC 50/60 HZ ARE ORDERING OPTIONS. 22 USE SPECIFIED SUPPLY VOLTAGE. FIGURE 3. Connection Diagram for Ungrounded 5-kV Systems. E Page 4 Rev. 3-D-111915 PGR-3200 Insulation Monitor 95.2 (3.75) 44.5 (1.75) 9.5 (0.38) NOTE 2 POWR-GARD PGH-5000 PGH-5000 Æ 5 KV HIGH TENSION COUPLER Æ HT Coupling Voltage: 5,000 Vac Max. Current to Ground: 2.5 mA Max. A DANGER HIGH VOLTAGE Impedance to Ground: E >2M M RELAY Revision: Serial No: 1-800-TEC-FUSE (1-800-832-3873) Made in Saskatoon, Canada Formerly HTC 5000 165.1 (6.50) PGH-5000 E ATTENTION! 150.0 (5.91) E E M 5kV HIGHTENSION COUPLER BOTH GROUND CONNECTIONS MUST BE MADE AND SECURED BEFORE CONNECTIONS TO THE RELAY AND THE HIGH VOLTAGE LINE MAXIMUM VOLTAGE AC 5000V A A 915.0 (36.00) FRONT SIDE MOUNTING DETAIL NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING HOLES: 5.00 (0.20). 3. ALL GROUND CONNECTIONS MUST BE MADE AND SECURED BEFORE CONNECTION TO RELAY AND HIGH VOLTAGE LINE. 4. CORD PROVIDED IS APPROXIMATELY 915.0 (36.00) LONG. FIGURE 4. PGH-5000 Outline and Mounting Details. 3.1 PGH-5000 AND PGH-6000 For 5-kV and 6-kV systems, connect the PGR-3200 to the monitored circuit with a PGH-5000 and PGH-6000 respectively. See Fig. 4 for PGH-5000 outline and mounting details. See Fig. 5 for PGH-6000 outline and mounting details. Connect protective-ground terminal ( ) to ground. Connect terminal E to ground or to PGR-3200 terminal 30, which must be grounded. Connect terminal M to PGR-3200 terminal 29. (PGR-3200 terminal 2 is not used.) For PGR-3200 to PGH-5000/PGH-6000 distances greater than 10 m (30’), use shielded cable, and connect the cable shield to the second PGH-5000/PGH-6000 terminal E. Connect terminal A to one phase on the load side of the motor starter. See Fig. 3. The PGH-5000/PHG-6000 includes 915 mm (36”) of highvoltage conductor. Page 5 Rev. 3-D-111915 PGR-3200 Insulation Monitor 145.0 (5.71) 120.0 (4.72) 98.5 (3.88) 12.50 (0.49) 12.50 (0.49) POWR-GARD POWR-GARD A E E M 6kV HIGHTENSION COUPLER PGH-6000 6kV HIGHTENSION COUPLER PGH-6000 PGH-6000 Æ 6 KV HIGH TENSION COUPLER Æ Coupling Voltage: 6,000 Vac Max. Current to Ground: 2.5 mA Max. HT A DANGER DANGER HIGH VOLTAGE ATTENTION! 175.0 (6.89) 200.0 (7.87) HIGH VOLTAGE Impedance to Ground: ATTENTION! BOTH GROUND CONNECTIONS MUST BE MADE AND SECURED BEFORE CONNECTIONS TO THE RELAY AND THE HIGH VOLTAGE LINE >2M PGH-6000 E E M RELAY Revision: Serial No: Formerly HTC 6000 1-800-TEC-FUSE (1-800-832-3873) Made in Saskatoon, Canada BOTH GROUND CONNECTIONS MUST BE MADE AND SECURED BEFORE CONNECTIONS TO THE RELAY AND THE HIGH VOLTAGE LINE MAXIMUM VOLTAGE MAXIMUM VOLTAGE (0.49) AC 6000V 12.50 AC 6000V 915.0 (36.00) LONG SIDE FRONT NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING HOLES: 6.35 (0.25). 3. ALL GROUND CONNECTIONS MUST BE MADE AND SECURED BEFORE CONNECTION TO RELAY AND HIGH VOLTAGE LINE. 4. CORD PROVIDED IS APPROXIMATELY 915.0 (36.00) LONG. FIGURE 5. PGH-6000 Outline and Mounting Details. 67.5 (2.657) 67.5 (2.657) 48.0 (1.890) 66.0 (2.598) R1.25(0.049) MAXIMUM NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). TOP FRONT 65.0 (2.559) 71.0 (2.795) MOUNTING CUTOUT SIDE FIGURE 6. PGA-0510 Analog Ohm Meter. REAR Page 6 Rev. 3-D-111915 PGR-3200 Insulation Monitor 4. TECHNICAL SPECIFICATIONS 4.1 PGR-3200 Supply 120 V option ............................... 5 VA, 120 Vac, 24 Vac (+10, -15%) 50/60 Hz 240 V option ..........................5 VA, 240 Vac, (+10, -15%) 50/60 Hz Maximum System Voltage: Direct Connection: UL Rating ........................600 Vac Maximum.........................1,300 Vac With PGH-5000.....................5,000 Vac With PGH-6000.....................6,000 Vac Measuring Voltage ......................12 Vdc Measuring Current.......................20 A maximum DC Resistance..............................600 k AC impedance at 50-60 Hz .........> 1 M Frequency Range .........................50 – 20,000 Hz Response-Level Settings .............10, 30, and 50 k (fixed) Response Delay: Warning, 10 k relay output: Insulation Resistance < 5 k ................................4 s Insulation Resistance = 10 k ...............................5 s Alarm, 50 k relay output: Insulation Resistance < 25 k ..............................2.5 s Insulation Resistance = 50 k ..............................4.5 s Analog Output: Mode ......................................Self Powered Range .....................................0 to 1 mA Impedance ..............................6 k maximum Parameter ...............................0 to ∞ Ω Insulation Resistance Output Relays; Warning and Alarm: Configuration .........................N.O. and N.C. (Form C) Operating Mode.....................Non-Fail-Safe UL Contact Rating.................5 A, 240 Vac resistive, 0.28 A, 30 Vdc resistive Switching Capacity................1,200 VA Supplemental Contact Ratings: Carry Continuous ...............5 A, maximum Trip Mode ....................................Latching or Autoreset Reset .............................................Front-Panel Button and Remote N.C. Contacts Test ...............................................Front-Panel Button and Remote N.O. Contact Terminals .....................................Wire Clamping, 22 to 12 AWG (0.3 to 3.3 mm2) conductors Tightening Torque .............. 0.40 N·m (3.54 lbf·in) Dimensions: Height .....................................75 mm (3.0”) Width......................................100 mm (3.9”) Depth ......................................113 mm (4.4”) Including DIN rail ..............115 mm (4.5”) Shipping Weight ......................... 0.45 kg (1 lb) Environment: Operating Temperature..........-10 to 60°C (14 to 140°F) Storage Temperature .............-40 to 80°C (-40 to 176°F) Humidity ................................85% Non-Condensing Certification .................................UL Listed LISTED SWITCHES, IND CONT 19PF NRNT, NRNT7, E183688 UL508 Industrial Control Equipment FCC PGR-3200 Insulation Monitor 4.2 PGH HIGH-TENSION COUPLERS Maximum Line Voltage: PGH-5000 ..............................5,000 Vac PGH-6000 ........................... 6,000 Vac Current to Ground .................... 2.5 mA maximum Terminal M Maximum Voltage ..................................... 50 Vac Terminals: E, E, and M ......................... Wire Clamping, 26 to 12 AWG (0.13 to 3.3 mm2) conductors Tightening Torque ........... 0.50 N·m (4.43 lbf·in) ...................................... Wire Clamping, 10 AWG (5.3 mm2) maximum High Tension Lead A ............... 8 AWG (8.4 mm2), 40 kVdc, 915 mm (36”) 5. ORDERING INFORMATION PGR-3200- Supply: Blank – 240 V Supply(1) 120 – 120- or 24- Vac Supply PGA-0510 ....................................Analog Ohm Meter PGH-5000 ....................................5 kV High Tension Coupler PGH-6000 ....................................6 kV High Tension Coupler NOTES: (1) UL not available for this supply option. Page 7 Rev. 3-D-111915 6. PERFORMANCE TEST 6.1 INSULATION TEST Perform this test with the starter open and appropriate lock-out procedures. Connect a 20 k resistor between one phase and ground at the line side of the starter or motor terminal box. Select a phase that is not connected to PGR-3200 terminal 2 (or the PGH-5000 or PGH-6000). The PGR-3200 will indicate a warning by lighting the 50 k and 30 k LED’s and energizing the 50 k insulation relay. Replace the 20-k resistor with an 8 k resistor. The PGR-3200 will indicate an alarm by lighting the < 10 k LED and energizing the 10 k insulation relay. Page 8 Rev. 3-D-111915 PGR-3200 Insulation Monitor MANUAL RELEASE DATE APPENDIX A PGR-3200 REVISION HISTORY MANUAL PRODUCT REVISION REVISION (REVISION NUMBER ON PRODUCT LABEL) November 19, 2015 3-D-111915 August 4, 2015 3-C-080415 MANUAL REVISION HISTORY REVISION 3-D-111915 SECTION 4 Terminal torque specifications added. SECTION 5 Ordering information updated. REVISION 3-C-080415 Model name changed to Insulation Monitor. SECTION 3 Figs. 4, 5, and 6 updated. SECTION 4 Output relay, dimension, and environment specifications updated. Certifications updated. Section 4.2 added. SECTION 5 Ordering information updated. APPENDIX A Revision history added. PRODUCT REVISION HISTORY PRODUCT REVISION 01 UL Certification. 01