Contents Menu Bussmann® Ferrule Introduction Table of Contents Catalog Symbol General Information Ampere Range Page FWA 150V 5-60A 80 FWX 250V 1-30A 81 FWH 500V 0.25-30A 82-83 FWC 600V 6-32A 84 FWP 660V/700V 1-100A 85-86 FWK 750V 5-60A 87 FWJ 1000V 20-30A 88 FWL/FWS 1250V/1500V 2-30A 89 Accessories Fuseholders 90 Curves Time-Current & Peak Let-Through Voltage 150 250 500 600 700 700 750 800 1000 1000 1250 1500 91-96 AC X X X X X — — — X — X X DC — X X — — X X X — X — — Ampere Range 5-60 1-30 0.25-30 6-32 1-100 1-30 5-60 20-30 20-30 2-30 20-30 2-15 Select fuses designed and tested to: • IEC 269: Part 4 • U.L. Recognized Bussmann offers a full line of ferrule style (cylindrical and clip-mounted) fuses, designed and tested to meet standards and requirements in various locations around the world. Their unique design and construction provide: • Superior cycling capability • Low energy let-through (I2t) Ferrule fuses provide an excellent solution for small UPS, small AC drives and other low power applications where space is at a premium. Voltage Rating All Bussmann ferrule fuses — except 660 volt — have been tested at their rated voltage. The 660 volt ferrule fuse has been tested to the IEC 269 standard, which requires clearing at the rated voltage +10%. Accessories Ferrule fuses may be mounted in fuseclips, fuseholders, fuseblocks or fused switches. A variety of products are available to suit most end-use requirements. For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 79 Contents Menu Bussmann® Ferrule FWA 150V 5-60A ® Electrical Characteristics I2t (A2S) Clearing Pre-arc at 150V Ordering Information Rated Current RMS-Amps Size 5 1.6 10 3.6 10 ≈ 38mm 15 14 (⁄‹Ω£™∑) 20 33 25 58 30 100 35 75 40 100 21 ≈ 51mm 45 130 (⁄‹Ω¡§∑) 50 170 60 250 䡲 Interrupting rating 100kA RMS Symmetrical. 䡲 Watts loss provided at rated current. 䡲 Consult Bussmann for DC ratings. 䡲 See accessories on page 90. Watts Loss Part Number 1 2.7 3.3 3.8 4.9 4.9 4.5 5.1 6 7.3 8.0 FWA-5A10F FWA-10A10F FWA-15A10F FWA-20A10F FWA-25A10F FWA-30A10F FWA-35A21F FWA-40A21F FWA-45A21F FWA-50A21F FWA-60A21F 8 16 55 130 220 400 800 1000 1300 1600 2400 Dimensions Curves Carton Qty. Carton Weight (kg) Figure Number See Page or (BIF #) 10 0.100 Fig. 1 page 91 (35785317) 10 0.600 Fig. 1 page 91 (35785305) 1 kg = 2.2 lbs. 1 lb = 0.45 kg Dimensions Fig. 1: 5-60 Amp Range A C Part Number FWA 5A10F-30A10F FWA 35A21F-60A21F A 38.1 50.8 Metric B C 9.5 10.3 15.9 20.6 A 1.5 2.0 Inches B C 0.375 0.406 0.625 0.811 Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm B Electrical Characteristics Total Clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g , (RMS). Arc Voltage This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (RMS) at a power factor of 15%. 1.5 K 1.0 Kp 0.8 UL 1.0 0.6 0.5 300 1) 0.5 0.4 200 0.3 0.2 0.3 0.2 2) 100 Eg Eg 0.15 22 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current . The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 70 102 150 50 100 150 0.1 30 40 50 Ib 60 70 80 90 100% 1) 5-30 Amp Range 2) 35-60 Amp Range BIF document: 720003 80 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 Contents Menu Bussmann® Ferrule FWX 250V (U.L.) Size 1-30A Electrical Characteristics I2t (A2S) Rated Current Clearing RMS-Amps Pre-arc at 250V ® Ordering Information Watts Loss Part Number Carton Qty. 1 — — — FWX-1A14F 2 — — — FWX-2A14F 3 — — — FWX-3A14F 4 — — — FWX-4A14F 14 ≈ 51mm 5 1.6 13 1.3 FWX-5A14F 10 (·Ω¡§∑) 10 3.6 24 3.4 FWX-10A14F 15 14 83 3.8 FWX-15A14F 20 33 200 4.6 FWX-20A14F 25 58 300 5.3 FWX-25A14F 30 100 500 5.9 FWX-30A14F 䡲 Interrupting rating 200kA RMS Symmetrical. 䡲 Watts loss provided at rated current. 䡲 250 Vdc U.L. Recognition on 5 through 30 amperes only. Consult Bussmann for additional ratings. 䡲 See accessories on page 90. Dimensions Curves Carton Weight (kg) Figure Number See Page or (BIF #) 0.225 Fig. 1 page 92 (35785302) 1 kg = 2.2 lbs. 1 lb = 0.45 kg Dimensions Fig. 1: 1-30 Amp Range 50.8 (2.000") 14.3 (0.563") Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm 15.5 (0.610") Electrical Characteristics Total Clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g , (RMS). Arc Voltage This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (RMS) at a power factor of 15%. 1.4 1.2 1.5 K 1.0 Kp 0.8 UL 103 1.0 0.6 0.5 800 0.4 600 500 0.5 0.3 400 0.3 0.2 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 0.2 300 Eg 0.15 75 125 200 250 300 Eg 200 50 100 150 200 250VRMS 0.1 30 40 50 Ib 60 70 80 90 100% BIF document: 720006 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 81 Contents Menu Bussmann® Ferrule FWH 500V Size 䡲 䡲 䡲 䡲 0.25-30A Electrical Characteristics I2t (A2S) Rated Current Clearing RMS-Amps Pre-arc at 500V ® Ordering Information Watts Loss 0.25 0.01 0.05 2.7 0.5 0.05 0.25 1.2 1 0.4 2 1.7 2 1.3 3.5 3.2 3.15 3.1 7.7 2.9 5 15 40 2.1 6.3 36 90 2.3 6 ≈ 32mm 7 50 125 2.5 (⁄Ω¢∑ ≈ 1⁄Ω¢∑) 10 — — — 12.5 20 — 3.53 15 44 146 3.08 16 48 177 4.48 20 75 259 4.26 25 — — — 30 — — — 0.25-7A 300% minimum opening current at rated voltage. 10-30A 200% minimum opening current at rated voltage. Interrupting rating: 0.25-20A 50kA at ≥ 20% pf 25-30A 20kA at Consult Bussmann for DC ratings. See accessories on page 90. Blow Times Current Ratings 150% 0.25-7A > 30 min. 10-30A < 30 min. 200% < 30 min. < 30 min. Part Number FWH-.250A6F FWH-.500A6F FWH-001A6F FWH-002A6F FWH-3.15A6F FWH-005A6F FWH-6.30A6F FWH-007A6F FWH-010A6F FWH-12.5A6F FWH-015A6F FWH-016A6F FWH-020A6F FWH-025A6F FWH-030A6F Carton Qty. Carton Weight (kg) Dimensions Curves Figure Number See Page or (BIF #) page 92 (35785256) 10 0.03 Fig. 1 page 93 (50955) 1 kg = 2.2 lbs. ≥ 20% pf. 300% ≤ 10 sec. ≤ 10 sec. Dimensions Fig. 1: 0.25-30 Amp Range 31.8 (1.25") 6.4 (0.25") 3.2 (0.125") Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm BIF document: 720038 82 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 1 lb = 0.45 kg Contents Menu Bussmann® Ferrule FWH 500V Size 1-30A ® Electrical Characteristics I2t (A2S) Rated Current Clearing RMS-Amps Pre-arc at 500V Ordering Information Watts Loss Part Number Carton Qty. 1 — — — FWH-1A14F 2 — — — FWH-2A14F 3 — — 2.3 FWH-3A14F 4 — — — FWH-4A14F 5 1.6 6.4 1.5 FWH-5A14F 14 ≈ 51mm 6 1.6 6.4 1.5 FWH-6A14F 10 (·Ω¡§∑) 10 3.6 13 4 FWH-10A14F 12 — — — FWH-12A14F 15 10 40 5.5 FWH-15A14F 20 26 96 6 FWH-20A14F 25 49 191 7 FWH-25A14F 30 58 232 9 FWH-30A14F 䡲 Interrupting rating 200kA RMS Symmetrical. 䡲 Watts loss provided at rated current. 䡲 500 Vdc U.L. Recognition on 5 through 30 amperes only. Consult Bussmann for additional ratings. 䡲 See accessories on page 90. Dimensions Curves Carton Weight (kg) Figure Number See Page or (BIF #) 0.250 Fig. 1 page 93 (35785298) 1 kg = 2.2 lbs. 1 lb = 0.45 kg Dimensions Fig. 1: 1-30 Amp Range 50.8 (2.000") 14.3 (0.563") 15.5 (0.610") Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm Electrical Characteristics Total Clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g , (RMS). 1.5 Arc Voltage This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (RMS) at a power factor of 15%. 2.0 K 1.6 1.0 1.0 Kp 0.8 UL 0.6 0.5 1.2 103 0.5 0.4 800 0.3 600 500 0.3 0.2 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 0.2 400 0.15 100 Eg 250 400 500 300 100 Eg 200 300 400 500 0.1 30 40 50 Ib 60 70 80 90 100% BIF document: 720008 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 83 Contents Menu Bussmann® Ferrule FWC 600V Size 6-32A ® Electrical Characteristics I2t (A2S) Rated Current Clearing RMS-Amps Pre-arc at 600V 6 4 8 6 10 9 10 ≈ 38mm 12 15 (⁄‹Ω£™∑) 16 25 20 34 25 60 32 95 䡲 Interrupting rating 200kA RMS Symmetrical. 䡲 Watts loss provided at rated current. 䡲 Consult Bussmann for DC ratings. 䡲 See accessories on page 90. Ordering Information Watts Loss Part Number 1.5 2.0 2.5 3.0 3.5 4.8 6.0 7.5 FWC-6A10F FWC-8A10F FWC-10A10F FWC-12A10F FWC-16A10F FWC-20A10F FWC-25A10F FWC-32A10F 30 50 70 120 150 260 390 600 Carton Qty. 10 Dimensions Curves Carton Weight (kg) Figure Number See Page or (BIF #) 0.100 Fig. 1 page 94 (35785306) 1 kg = 2.2 lbs. 1 lb = 0.45 kg Dimensions Fig. 1: 6-32 Amp Range 38.1 (1.500") 10.3 (0.406") 9.5 (0.375") Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm Electrical Characteristics Total Clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g , (RMS). Arc Voltage This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (RMS) at a power factor of 15%. 2.0 1.5 K 1.6 1.0 0.5 0.3 0.2 0.15 100 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current . The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 1.0 Kp 0.8 UL 1.2 0.6 0.5 103 0.4 800 0.3 600 500 0.2 400 Eg 250 400 500 600 300 200 Eg 300 400 500 600 0.1 30 40 50 Ib 60 70 80 90 100% BIF document: 720011 84 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 Contents Menu Bussmann® Ferrule FWP 660V/700V (IEC/U.L.) Size Electrical Characteristics I2t (A2S) Rated Current Clearing RMS-Amps Pre-arc at 660V 1-50A ® Ordering Information Watts Loss 1 — — — 2 — — — 3 — — — 4 — — — 5 1.6 11 1.5 6 — — — 14 ≈ 51mm 10 3.6 22 4 (·Ω¡§∑) 15 10 75 5.5 20 26 180 6 25 44 320 7 30 58 450 9 32 68 600 7.6 40 84 750 8 50 200 1800 9 䡲 Interrupting rating 200kA RMS Symmetrical. 䡲 Watts loss provided at rated current. 䡲 700 Vdc ratings for 5 through 30 amperes only. Consult Bussmann for 䡲 See accessories on page 90. Part Number Carton Qty. Carton Weight (kg) FWP-1A14F FWP-2A14F FWP-3A14F FWP-4A14F FWP-5A14F FWP-6A14F FWP-10A14F FWP-15A14F FWP-20A14F FWP-25A14F FWP-30A14F FWP-32A14F FWP-40A14F FWP-50A14F 10 0.225 Dimensions Curves Figure Number See Page or (BIF #) Fig. 1 page 94 (35785307) 1 kg = 2.2 lbs. 1 lb = 0.45 kg other ratings. Dimensions Fig. 1: 1-50 Amp Range 50.8 (2.000") 14.3 (0.563") 15.5 (0.610") Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm Electrical Characteristics Total Clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g , (RMS). 1.4 1.2 1.0 0.9 0.8 0.7 0.6 0.5 0.4 1.4 1.2 103 9 8 7 6 K Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 1.0 Kp 0.8 UL 0.6 0.5 0.4 0.3 5 1) 0.2 4 2) 0.3 200 Arc Voltage This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (RMS) at a power factor of 15%. Eg Eg 3 300 400 500 600 700 200 300 400 500 600 700 1) 5-30 Amp Range 2) 32-50 Amp Range For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 0.1 30 40 50 Ib 60 70 80 90 100% BIF document: 720025 85 Contents Menu Bussmann® Ferrule FWP 660V/700V (IEC/U.L.) Size Electrical Characteristics I2t (A2S) Rated Current Clearing RMS-Amps Pre-arc at 660V 20 23 25 37 32 55 22 ≈ 58mm 40 68 (‡Ω•∑) 50 155 63 280 80 600 100 1100 䡲 Interrupting rating 200kA RMS Symmetrical. 䡲 Watts loss provided at rated current. 䡲 Consult Bussmann for DC ratings. 䡲 See accessories on page 90. 20-100A ® Ordering Information 260 410 605 750 1600 3080 6600 12500 Watts Loss Part Number Carton Qty. Carton Weight (kg) 4.6 5.6 7.0 8.5 9.5 11 13.5 16 FWP-20A22F FWP-25A22F FWP-32A22F FWP-40A22F FWP-50A22F FWP-63A22F FWP-80A22F FWP-100A22F 10 0.450 Dimensions Curves Figure Number See Page or (BIF #) page 95 (35785291) Fig. 1 1 kg = 2.2 lbs. 1 lb = 0.45 kg Dimensions Fig. 1: 20-100 Amp Range 58.0 (2.283") 22.2 (0.875") 15.0 (0.591") Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm Electrical Characteristics Total Clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g , (RMS). 1.4 1.2 1.0 0.9 0.8 0.7 0.6 Arc Voltage This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (RMS) at a power factor of 15%. 1.4 1.2 103 9 8 7 6 K 0.5 5 0.4 4 0.3 200 300 400 500 600 1.0 Kp 0.8 UL 0.6 0.5 0.4 0.3 0.2 Eg Eg 3 700 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current . The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 200 300 400 500 600 700 0.1 30 40 50 Ib 60 70 80 90 100% BIF document: 720026 86 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 Contents Menu Bussmann® Ferrule FWK 750V Size 5-60A Electrical Characteristics I2t (A2S) Rated Current Clearing RMS-Amps Pre-arc at 750 Vdc Ordering Information Watts Loss Part Number Dimensions Curves Figure Number See Page or (BIF #) Carton Qty. Carton Weight (kg) 10 0.95 Fig. 1 page 95 (35785031) 10 1.65 Fig. 2 page 95 (35785031) 5 8.5 16 — FWK-5A20F 8 50 100 — FWK-8A20F 10 95 200 — FWK-10A20F 20 ≈ 127mm 15 100 240 — FWK-15A20F (⁄‹Ω¡§∑) 20 125 315 — FWK-20A20F 25 400 1100 — FWK-25A20F 30 800 2600 — FWK-30A20F 35 1300 4300 — FWK-35A25F 25 ≈ 146mm 40 1600 5300 — FWK-40A25F (1∑) 50 3100 12000 — FWK-50A25F 60 5900 24000 — FWK-60A25F 䡲 Interrupting rating 45kA RMS symmetrical. 䡲 750 Vdc rating for 5 through 60 amperes (Time constant = 10-15 mS). 1 kg = 2.2 lbs. 1 lb = 0.45 kg Dimensions Fig. 1: 5-30 Amp Range 127.0 (5.000") 20.5 (0.807") 16.0 (0.630") Fig. 2: 35-60 Amp Range 146.05 (5.75") 25.4 (1") 20.64 (0.813") Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm BIF document: 720039 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 87 Contents Menu Bussmann® Ferrule FWJ 1000V 20-30A Electrical Characteristics I2t (A2S) Rated Current Clearing RMS-Amps Pre-arc at 1000V Size 20 25 25 33 30 52 Interrupting rating 200kA RMS Symmetrical. Watts loss provided at rated current. 800 Vdc U.L. Recognized. See accessories on page 90. 14 ≈ 67mm (·Ω¡§∑) 䡲 䡲 䡲 䡲 ® Ordering Information Watts Loss Part Number Carton Qty. Carton Weight (kg) 9 11 14 FWJ-20A14F FWJ-25A14F FWJ-30A14F 10 0.300 220 350 450 Dimensions Curves Figure Number See Page or (BIF #) Fig. 1 page 96 (35785315) 1 kg = 2.2 lbs. 1 lb = 0.45 kg Dimensions Fig. 1: 20-30 Amp Range 66.7 (2.626") 14.5 (0.571") 15.9 (0.625") Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm Electrical Characteristics Total Clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g , (RMS). Arc Voltage This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (RMS) at a power factor of 15%. 1.5 2000 K 1.0 Kp 0.8 UL 1.0 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current . The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 1600 0.6 0.5 1200 0.4 0.5 0.3 800 0.3 0.2 0.2 400 Eg Eg 0.15 680 800 1000 200 600 1000 1400 1800 0.1 30 40 50 Ib 60 70 80 90 100% BIF document: 720028 88 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 Contents Menu Bussmann® Ferrule FWL/FWS 1250V/1500V Size Electrical Characteristics I2t (A2S) Rated Current Clearing RMS-Amps Pre-arc at 1000 Vdc †2 0.8 †6 27 20 ≈ 127mm †15 300 (·Ω¡§∑) ‡20 675 ‡30 1850 䡲 Interrupting rating 45kA RMS Symmetrical. 䡲 Rated voltage (IEC) †1500V ‡1250V 䡲 1000 Vdc rating. 䡲 See accessories on page 90. 2.4 81 700 1550 4300 2-30A Ordering Information Watts Loss Part Number Carton Qty. Carton Weight (kg) 4.4 6.7 5 5.9 7.5 FWS-2A20F FWS-6A20F FWS-15A20F FWL-20A20F FWL-30A20F 10 1.00 Dimensions Curves Figure Number See Page or (BIF #) Fig. 1 page 96 (35785109) 1 kg = 2.2 lbs. 1 lb = 0.45 kg Dimensions Fig. 1: 2-30 Amp Range 127.0 (5.000") 20.5 (0.807") 16.0 (0.630") Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm BIF document: 720040 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 89 Contents Menu Bussmann® Ferrule – Accessories Fuseholders ® Catalog Symbol: CH Series Features: • 10 ≈ 38 Dovetail design provides maximum flexibility in assembling multiple poles • Touchsafe design - No exposed contacts • DIN rail mount (35mm) • Optional open fuse indication lights • Excellent for switchboard panel, control consoles, small motors, transformers, and similar applications • Handle/fusepuller to install and remove fuses easily • Available in single and multi-pole configurations • Circuit marking system (P/N CH10CL and CH10CM) • Wire ready: Saves time as terminals are ready to accept wires. • CE marking Standards: North American 10 ≈ 38 Class CC Listed U.L. 512, Guide IZLT, File E14853 Certified CSA Std. C22.2 No. 39, Class 6225 01, File 47235 North American 10 ≈ 38 Midget Recognized U.L. 512, Guide IZLT2, File E14853 Certified CSA Std. C22.2 No. 39, Class 6225 01, File 47235 European 10 ≈ 38 IEC 269-2-1 14 ≈ 51 IEC 269-2 22 ≈ 58 IEC 269-2 Recommended Buss® Fuse Types: 10 ≈ 38 North American Class CC Fuses - LP-CC, FNQ-R, KTK-R 10 ≈ 38 North American Midget Fuses - FNQ, KTK, AGU, BAF, BAN, FNM, FWA, & FWC 14 ≈ 51 Fuses - FWX, FWH, FWP & NON 22 ≈ 58 Fuses - FWP BIF document: 1151 Catalog Symbol: J70100 Ampere Rating: 100 Amperes Voltage Rating: 700 Volts AC Agency Approvals: UL Recognized, Guide IZLT2, File E14853 Withstand Rating: 200,000 RMS Sym. Amps For use with 22 ≈ 58mm fuses (FWP-40A22F, FWP-100A22F, etc.) Materials: Thermoplastic UL Flammability: 94 VO Amps 100 Poles 1 2 3 Catalog Numbers Box Lug w/ Retaining Clip J70100-1CR J70100-2CR J70100-3CR Max. Wire Size #2 #2 #2 BIF document: 1211 90 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 Contents Menu Bussmann® Ferrule Curves FWA 150V 5-30A (10 ≈ 38mm) FWA 150V 35-60A (21 ≈ 51mm) Time-Current Curve Time-Current Curve 104 104 6 4 6 4 2 2 6 4 103 6 4 103 2 2 6 4 102 6 4 Virtual Pre-Arcing Time In Seconds 102 Virtual Pre-Arcing Time In Seconds 2 101 FWA-5A10F FWA-10A10F FWA-15A10F FWA-20A10F FWA-25A10F FWA-30A10F 6 4 2 100 6 4 2 10–1 2 101 6 4 2 100 6 4 2 10–1 6 4 6 4 2 2 10–2 10–2 6 4 6 4 2 2 10–3 10–3 6 4 6 4 2 10–4 FWA-35A21F FWA-40A21F FWA-45A21F FWA-50A21F FWA-60A21F 2 2 4 6 8 2 101 4 6 8 2 102 4 6 8 103 10–4 Prospective Current In Amperes RMS 2 101 4 6 8 2 102 4 6 8 103 Prospective Current In Amperes RMS Peak Let-Through Curve Peak Let-Through Curve 104 104 6 6 4 4 FWA-30A10F FWA-25A10F FWA-20A10F FWA-15A10F 10 2 103 Peak Let-Through Current Peak Let-Through Current 2 3 FWA-60A21F FWA-50A21F FWA-45A21F FWA-40A21F FWA-35A21F 6 4 2 FWA-12A10F FWA-10A10F FWA-5A10F 102 6 4 2 102 6 6 4 4 2 2 101 101 101 2 4 6 102 2 4 6 103 2 4 6 104 2 4 6 105 2 101 2 4 6 102 Prospective Short-Circuit Current Symmetrical RMS BIF document: 35785317 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 2 4 6 103 2 4 6 104 2 4 6 105 2 Prospective Short-Circuit Current Symmetrical RMS BIF document: 35785305 91 Contents Menu Bussmann® Ferrule Curves FWX 250V 1-30A (14 ≈ 51mm) FWH 500V 0.25-7A (6 ≈ 32mm) Time-Current Curve Time-Current Curve 104 104 6 4 6 4 FWH-3.15A6F FWH-005A6F 3 FWH-6.30A6F 10 103 6 4 FWH-007A6F 6 4 2 2 102 102 6 4 Virtual Pre-Arcing Time In Seconds 6 4 Virtual Pre-Arcing Time In Seconds FWH-002A6F 2 2 2 101 6 4 FWX-5A14F FWX-10A14F FWX-15A14F FWX-20A14F FWX-25A14F FWX-30A14F 2 100 6 4 2 101 6 4 2 100 6 4 2 2 10–1 6 FWH-.250A6F 4 FWH-.500A6F FWH-001A6F 2 10–1 6 4 2 10–2 10–2 4x10–3 .2 6 4 .4 .6 .8 100 2 4 6 8 101 2 4 Prospective Current In Amperes RMS 2 10–3 6 4 2 10–4 2 4 6 8 2 101 4 6 8 102 2 4 6 8 103 Prospective Current In Amperes RMS Peak Let-Through Curve 104 6 4 FWX-30A14F FWX-25A14F FWX-20A14F FWX-15A14F FWX-10A14F FWX-5A14F Peak Let-Through Current 2 103 6 4 2 102 6 4 2 101 101 2 4 6 102 2 4 6 103 2 4 6 104 4 6 105 2 Prospective Short-Circuit Current Symmetrical RMS BIF document: 35785302 92 BIF document: 35785256 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 6 8 102 2 Contents Menu Bussmann® Ferrule Curves FWH 500V 10-30A (6 ≈ 32mm) FWH 500V 1-30A (14 ≈ 51mm) Time-Current Curve Time-Current Curve 104 104 6 4 2 10 103 6 4 3 2 102 6 4 Virtual Pre-Arcing Time In Seconds FWH-12.5A6F FWH-016A6F FWH-020A6F FWH-025A6F 101 100 FWH-5A14F FWH-10A14F FWH-15A14F FWH-20A14F FWH-25A14F FWH-30A14F 2 101 6 4 2 100 6 4 2 10–1 6 4 2 10–1 10–2 6 4 2 10–2 10–3 6 4 2 10–3 1 10 10–4 102 103 104 2 105 4 6 8 2 101 4 6 8 2 102 4 6 105 2 8 103 Prospective Current In Amperes RMS Prospective Current In Amperes RMS Peak Let-Through Curve 104 6 4 2 FWH-30A14F FWH-25A14F 103 Peak Let-Through Current Virtual Pre-Arcing Time In Seconds 102 6 4 2 FWH-20A14F FWH-15A14F FWH-10A14F FWH-5A14F 102 6 4 2 101 101 2 4 6 102 2 4 6 103 2 4 6 104 2 4 6 Prospective Short-Circuit Current Symmetrical RMS BIF document: 50955 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 BIF document: 35785298 93 Contents Menu Bussmann® Ferrule Curves FWC 600V 6-32A (10 ≈ 38mm) FWP 660V/700V 1-50A (14 ≈ 51mm) Time-Current Curve Time-Current Curve 4 104 10 6 4 6 4 2 2 103 103 10 6 4 2 FWP-25A14F FWP-30A14F FWP-32A14F FWP-40A14F FWP-50A14F 102 6 4 Virtual Pre-Arcing Time In Seconds 2 2 Virtual Pre-Arcing Time In Seconds 6 4 FWC-6A10F FWC-8A10F FWC-10A10F FWC-12A10F FWC-16A10F FWC-20A10F FWC-25A10F FWC-30A10F & FWC-32A10F 6 4 2 101 6 4 2 100 6 4 2 101 6 4 2 100 6 4 FWP-5A14F FWP-10A14F FWP-15A14F FWP-20A14F 2 10–1 2 6 4 10–1 2 6 4 10–2 6 4 2 –2 10 2 6 4 10–3 6 4 2 2 10–3 10–4 6 4 2 4 6 8 2 101 4 6 8 102 2 4 6 6 105 8 103 Prospective Current In Amperes RMS 2 10–4 2 102 4 6 8 103 2 4 6 8 104 Prospective Current In Amperes RMS Peak Let-Through Curve Peak Let-Through Curve 104 104 6 4 4 2 2 103 Peak Let-Through Current Peak Let-Through Current FWP-50A14F FWP-40A14F FWP-32A14F FWP-30A14F FWP-25A14F 6 FWC-30A10F & FWC-32A10F FWC-25A10F FWC-20A10F FWC-16A10F 6 4 2 FWC-12A10F FWC-10A10F FWC-8A10F FWC-6A10F 102 103 6 4 2 6 6 4 4 2 FWP-20A14F FWP-15A14F FWP-10A14F FWP-5A14F 102 2 101 101 101 2 4 6 102 2 4 6 103 2 4 6 104 Prospective Short-Circuit Current Symmetrical RMS BIF document: 35785306 94 4 6 105 2 101 2 4 6 102 2 4 6 103 2 4 6 104 2 4 Prospective Short-Circuit Current Symmetrical RMS BIF document: 35785307 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 2 Contents Menu Bussmann® Ferrule Curves FWP 660V/700V 20-100A (22 ≈ 58mm) Time-Current Curve FWK 750V 5-30A (20 ≈ 127mm) FWK 750V 35-60A (25 ≈ 146mm) Time-Current Curve 104 104 6 4 6 4 2 FWK-15A20F 2 FWK-20A20F 3 103 10 6 FWK-30A20F 4 FWK-40A25F 2 2 6 4 102 6 Virtual Pre-Arcing Time In Seconds 10 2 101 6 4 2 100 6 4 FWK-50A25F FWK-60A25F FWP-50A22F FWP-63A22F FWP-80A22F FWP-100A22F 2 Virtual Pre-Arcing Time In Seconds FWK-25A20F 6 4 FWP-20A22F FWP-25A22F FWP-32A22F FWP-40A22F 4 2 101 6 4 2 100 6 4 FWK-5A20F FWK-8A20F 2 2 FWK-10A20F —1 10 10–1 6 4 6 4 2 2 —2 10 –2 10 6 4 —3 4x10 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103 Prospective Current In Amperes RMS 2 10–3 6 4 2 10–4 2 101 4 6 8 2 102 4 6 8 103 Prospective Current In Amperes RMS Peak Let-Through Curve 104 FWP-100A22F FWP-80A22F 6 FWP-63A22F Peak Let-Through Current 4 FWP-50A22F 2 103 6 FWP-40A22F FWP-32A22F 4 FWP-25A22F FWP-20A22F 2 102 102 2 4 6 103 2 4 6 104 2 4 6 105 2 Prospective Short-Circuit Current Symmetrical RMS BIF document: 35785291 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 BIF document: 35785031 95 Contents Menu Bussmann® Ferrule Curves FWJ 1000V 20-30A (14 ≈ 67mm) Time-Current Curve FWL/FWS 1250V/1500V 2-30A (20 ≈ 127mm) Time-Current Curve 104 104 6 4 FWS-15A20F 6 4 FWL-20A20F FWL-30A20F 2 2 103 103 6 4 6 4 2 2 102 Virtual Pre-Arcing Time In Seconds 102 6 4 Virtual Pre-Arcing Time In Seconds 2 101 6 4 FWJ-20A14F FWJ-25A14F FWJ-30A14F 2 100 6 4 2 101 6 4 2 100 6 4 2 6 4 10–1 6 4 2 FWS-2A20F FWS-6A20F 10–1 2 6 4 10–2 4x10–3 2 100 10–2 2 4 6 8 101 2 4 6 8 102 Prospective Current In Amperes RMS 6 4 2 10–3 6 4 2 10–4 2 101 4 6 8 102 2 4 6 8 103 Prospective Current In Amperes RMS Peak Let-Through Curve 104 6 4 FWJ-30A14F FWJ-25A14F FWJ-20A14F Peak Let-Through Current 2 103 6 4 2 102 6 4 2 101 101 2 4 6 102 2 4 6 103 2 4 6 104 2 4 6 105 2 Prospective Short-Circuit Current Symmetrical RMS BIF document: 35785315 96 BIF document: 35785109 For complete specification data, visit our Web site at www.bussmann.com or call Bussmann Information Fax ~ 314.527.1450 2 4 6 8 103 Bussmann ® Worldwide Circuit Protection Solutions Bussmann North America’s leading supplier of fuses and fusible protection systems, Bussmann continues its 80-year history of blazing new trails of innovative technologies. Maker of the industry’s first truly global product line, each item is backed by an efficient worldwide network of distribution, customer service and technical support. Bussmann products include the most extensive circuit protection solutions that are built and tested to a variety of major standards: U.L., CSA, IEC, ISO. . . Additionally, both European (DIN, British Standard) and North American styled fuses are used for a wide range of applications: industrial motor protection, power conversion, medium voltage power distribution, telecommunications network equipment, electronics, and automotive. Manufacturing operations in the U.S., Denmark, and the United Kingdom have earned ISO 9000 certification, assuring Bussmann customers only the utmost quality across every product line. Knowledgeable. Responsive. Customer focused. Bussmann continues to set the standard for circuit protection solutions in the global marketplace. Bussmann—The Source For Global Solutions In Semiconductor Protection Today’s power electronics market knows no international boundaries – so neither should the high speed fuses that are used to protect semiconductor devices. Only one fuse maker – Bussmann – has the resources required to meet all of the power conversion industry’s principle needs: • Knowledgeable technical support • Cutting-edge application design • Global sourcing & manufacturing (certified to ISO 9000 standards) Contents Bussmann offers a comprehensive range of high speed fuselinks, specifically designed for semiconductor device protection. These products use advanced materials and technology to deliver unsurpassed performance. All high speed fuses carry the quality assurance of the Bussmann name – the recognized world leader in circuit protection. Headquarters Cooper Industries Bussmann Division P.O. Box 14460 St. Louis, Missouri 63178-4460, USA Telephone: 314-394-2877 Facsimile: 800-544-2570 Bussmann Circuit Components 7300 West Wilson Avenue Chicago, IL 60656-4793, USA Telephone: 708-867-4600 Facsimile: 708-867-2211 European Headquarters Bussmann Division Cooper (UK) Limited Burton-on-the-Wolds Leicestershire LE12 5th, England Telephone: 44 1509 882737 Facsimile: 44 1509 882786 Bussmann Asia Pacific 331 North Bridge Road #03-02 Odeon Towers Singapore 188720 Republic of Singapore Telephone: 65 336 3610 Facsimile: 65 336 4810 Bussmann Australia Block X 391 Park Road P.O. Box 257 Regents Park, Sydney NSW 2143, Australia Telephone: 61 2 9743 8333 Facsimile: 61 2 9743 8070 Bussmann Brasil Bussmann do Brasil Ltda. Rodovia Santos Dumont, Km 23 13 300-000 Cruz das Almas Caixa Postal 95-Itu Sao Paulo-Brasil Telephone: 55 11 7824 1722 Facsimile: 55 11 7824 1721 Bussmann Denmark 5 Literbuen DK-2740 Skovlunde Copenhagen, Denmark Telephone: 45 4485 0900 Facsimile: 45 4485 0901 Bussmann India 2nd Floor, Unit #5 White House 23-29, St. Marks Road Bangalore – 560-001 India Telephone: 91-80-227-0893 Facsimile: 91-80-224-0124 Bussmann Mexico Arrow-Hart S.A. de C.V. Poniente 148, No. 933 02300 Mexico, D.F. Mexico Telephone: 52 5 587 0211 Facsimile: 52 5 567 4049 This brochure summarizes the features and benefits of the following high speed fuses that Bussmann manufactures for the power electronics market: • North American • British • European (DIN) • Ferrule This catalog is intended to present product data and provide technical information that will help the end user with design application. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this catalog. Once a product has been selected, it should be tested by the user in all possible applications. ©1998 Cooper Industries, Bussmann Division Printed in the U.S.A. http://www.bussmann.com