Transformer Terminal Buyer’s Guide RET 541, RET 543, RET 545 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Issued: February 2005 Status: Updated Version: C/15.06.2005 Data subject to change without notice Features • Transformer terminal for protection, control, measurement and supervision of two-winding power transformers and generatortransformer blocks in distribution networks • Designed to withstand harsh environments e.g. in heavy industry, marine and offshore applications • Three-phase current differential protection with stabilized and instantaneous stages for fast and selective winding short-circuit and interturn fault protection as main protection • Fast and reliable operation even with saturating CTs • Numerical implementation of vector group matching allows wye-connection of measuring CTs as standard without interposing CTs, irrespective of transformer vector group • Restricted earth-fault protection with the conventional high impedance principle or the stabilized numerical principle • Three-phase overcurrent and earth-fault back-up protection with definite time and IDMT characteristics for both windings • Optional automatic on-load tap-changer control function for single or parallel transformers using the Master-Follower, Negative Reactance or Minimizing Circulating Current principles • Supports several methods to interface tapchanger position information to differential protection and voltage regulator • Measurement of two sets of three-phase currents, phase-to-phase or phase to neutral voltages, neutral current, residual voltage, frequency, power factor, active and reactive power and energy • Condition monitoring including circuitbreaker condition monitoring, trip circuit supervision and internal self-supervision of the transformer terminal • Extensive set of integrated communication protocols: SPA, LON, IEC 60870-5-103, Modbus RTU/ASCII, DNP 3.0 • Interface to Profibus DP and IEC 61850 based systems via adapters • Part of ABB’s substation automation system • Thermal overload and negative phase sequence protection • Additional protection functions available in the Multi –version terminal: overexcitation, overvoltage, undervoltage, residual overvoltage, directional overcurrent and earthfault, overfrequency, underfrequency and underimpedance line back-up protection • Large graphic display, either integrated or as an external module • Control functions including local and remote control of switching objects, including object status indication and interlockings on bay and substation level Fig. 1 ret54_mimic_co180dpi Mimic view of RET 54_ transformer terminal. 3 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Application The RET 541/543/545 transformer terminals are designed to be used for the protection, control, measurement and supervision of twowinding power transformers and generatortransformer blocks in distribution networks. RET 54_ terminals can also be used in harsh environments e.g. in heavy industry, marine and offshore applications. The main protection function is three-phase current differential protection with stabilized and instantaneous stages for fast and selective winding short-circuit and interturn protection. Besides 2nd and 5th harmonic restraints, the stabilized stage also includes a waveform recognition-based blocking-deblocking feature. Reliable operation even with partially saturated current transformers, that is, short operate times at faults occurring in the zone to be protected and high stability at external faults are achieved. Increased sensitivity can be obtained by automatic adaptation to the position changes of the on load tap changer. Interposing current transformers are not needed: Any vector group matching and CT ratio corrections in a wide range are numerically implemented as well as zero-sequence current elimination, which prevents unwanted trips at earth faults occurring outside the protected area. In addition to the differential protection, the Basic version terminals incorporate the following protections: Restricted earth fault protection with stabilized numerical or high impedance principle, unbalance and thermal overload protections, three phase overcurrent and non-directional earth fault back-up protection with definite and IDMT characteristics on both sides of the transformer. The Multi-version terminals, further including overvoltage and undervoltage, residual overvoltage, underfrequency and overfrequency, overexcitation, directional earthfault, directional overcurrent and underimpedance line back-up protections fulfill the most demanding application requirements. Enhanced with the optional automatic voltage regulation function, the RET 54_ terminal can be applied as a comprehensive integrated transformer management terminal. The voltage regulator can be applied for a single transformer or for parallel transformers with Master-Follower, Negative Reactance or Minimizing Circulating Current principles. A special control version terminal with voltage regulator and control functions can be applied, when integration of voltage regulation and protection is not allowed. 4 The graphical configuration tool, based on the IEC 61131-3 standard, enables easy creation of application-specific configurations and MIMIC pictures corresponding to different switchgear systems. The process status is shown on a dynamic large graphical display. Detailed information, for instance, measured values, events and application-specific alarms, are presented in the display views. The RET 54_ terminals can measure two sets of three phase currents, phase-to-phase or phase-to-earth voltages, neutral current, residual voltage, frequency and power factor. Active and reactive power is calculated from the measured currents and voltages. Energy can be calculated on the basis of the measured power. The measured values can be indicated locally and remotely as scaled primary values. With the condition monitoring functions the RET 54_ transformer terminal monitors e.g. trip circuits, gas pressure of the breaker and breaker wear and provides scheduled time intervals for maintenance. The RTD1 card, available as an option to the RET 541 and RET 543 terminals, provides versatile analog inputs enabling e.g. tap position supervision of the on load tap changer, RTD inputs for top and bottom oil temperature monitoring, and ambient temperature biasing for accurate thermal overload protection. The mA outputs allow transfer of any measurement data e.g. to PLCs. By means of the graphic HMI display, the control functions in the transformer terminal indicate the position of disconnectors, circuit breakers and tap changer locally. Local control of these objects is possible via the push buttons on the front panel of the terminal. Furthermore, the terminal allows position information of the objects to be transmitted to the remote control system. Controllable objects, such as CBs, can also be opened and closed over the remote control system. Supporting a wide range of communication protocols, including SPA, LON, IEC 608705-103, DNP 3.0 and Modbus RTU/ASCII, commonly used by utilities and industries, the terminals are flexibly integrated into different control systems. Connection to Profibus DP or IEC 61850 based system is possible via the interface adapters SPA-ZC 302 or SPA-ZC 400, respectively. Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Design The transformer terminals RET 541, RET 543 and RET 545 differ from each other regarding the number of digital inputs and outputs available. Please, refer to section “Ordering” for more details. The functions of the RET 54_ transformer terminal are categorized as: • protection functions • measurement functions • control functions • condition monitoring functions • communication functions • general functions • standard functions The functions are further divided to three subsets that correspond to different functionality levels, refer to section “Ordering Information” Protection functions Protection is one of the most important functions of the RET 54_ transformer terminal. The protection function blocks (e.g. NOC3Low) are independent of each other and have e.g. their own setting groups and data recording. The protection function blocks are documented on the CD-ROM “Technical Descriptions of Functions” (1MRS750889-MCD) Measurement functions The measurement function blocks are documented on the CD-ROM “Technical Descriptions of Functions” (1MRS750889-MCD) Control functions The control functions are used to indicate the position of switching devices, i.e. circuit breakers and disconnectors, and to execute open and close commands for controllable switching devices in the switchgear. Furthermore, there are supplementary functions for control logic purposes, e.g. on/off switches, MIMIC alarm, LED control, numerical data for the MIMIC and logic controlled position selection. The control functions configured using the Relay Configuration Tool can be associated with position indicators that are part of the MIMIC configuration picture displayed on the HMI. Position indicators are used to indicate the position of switching devices via the MIMIC picture and to control them locally. The control function blocks are documented on the CD-ROM “Technical Descriptions of Functions” (1MRS750889-MCD) Condition monitoring functions The condition monitoring function blocks are documented on the CD-ROM “Technical Descriptions of Functions” (1MRS750889MCD) General functions Additional functions are available for different general purposes to be used in logics such as activation of HMI backlight, switchgroups, and resetting of operation indications, latched output signals, registers and disturbance recorder. Communication functions The RET 54_ transformer terminal provides the IEC_103, Modbus, DNP 3.0, SPA and LON serial communication protocols. In a customer-specific transformer terminal configuration, special events can be generated via an EVENT230 event function. EVENT230 is documented on the CD-ROM “Technical descriptions of Functions” (1MRS750889-MCD). Standard functions Standard functions are used for logics, such as interlocking, alarming and control sequencing. The use of logic functions is not limited and the functions can be interconnected with each other as well as with protection, measurement, power quality, control, condition monitoring and general functions. In addition, the digital inputs and outputs as well as LON inputs and outputs can be connected to standard functions by using the Relay Configuration Tool. The standard function blocks are documented on the CD-ROM “Technical descriptions of Functions” (1MRS750889-MCD). Other functions Low auxiliary voltage indication The RET 54_ transformer terminal is provided with a low auxiliary voltage indication feature. The power supply module issues an internal alarm signal when a drop in the power supply voltage is detected (ACFail, active low). The alarm signal is activated if the power supply voltage falls about 10% below the lowest rated DC input voltage of the power supply module. 5 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Design (cont´d) The indication of a low auxiliary voltage is available in the transformer terminal configuration and can be connected to any signal output of the RET 54_. tion of a digital input can be inverted. The programmable filter time removes debounces and short disturbances on a digital input. The filter time can be set for each digital input separately. Overtemperature indication The RET 54_ transformer terminal includes an internal temperature supervision function. The power supply module issues an internal alarm signal when overtemperature has been detected inside the terminal enclosure. The alarm signal will be activated once the temperature inside the terminal enclosure increases to +78°C (+75°...+83°C). Overtemperature indication is available in the transformer terminal configuration and can be connected to any signal output of the RET 54_. Analog channels The transformer terminal measures the analog signals needed for protection, measuring, etc. via galvanically separated matching transformers. RET 54_ transformer terminals have 9 analog channels. Furthermore, the transformer terminal includes virtual analog channels for calculating the residual current and residual voltage from phase currents and voltages. Both the amplitude and the phase angle are calculated for the virtual channels. Note! When sensitive earth-fault protection is needed, core balance transformers are not recommended to be replaced with the numerically derived sum of phase currents. Normally, an earth-fault setting below 10% of the rated value requires the use of a core balance transformer. Analog channels of the transformer terminal are configured with the CAP 505 Relay Product Engineering Tools. A separate scaling factor can be set for each analog channel. The factors enable differences between the ratings of the protected unit and those of the measuring device (CT and VT ratio corrections). The setting value 1.00 means that the rated value of the protected unit is exactly the same as that of the measuring device. Digital inputs The digital inputs of the transformer terminals are voltage controlled and optically isolated with three treshold voltages defined by the order, see chapter “Ordering”. The func- 6 Some specific digital inputs can be programmed to operate either as digital inputs, as pulse counters or as used for time synchronization. When a digital input operates as a pulse counter, pulse counting frequency can be up to100 Hz. Oscillation suppression The transformer terminals have two global parameters for the suppression of digital input oscillation. The settings of these parameters determine the oscillation level and hysteresis for all digital inputs. Event is generated in case oscillation is detected. Attributes of a digital input for transformer terminal configuration For each digital input, the status of the input (value), the time tag for the status change (time) and the validity of the digital input (invalidity) can be issued by the attributes. These attributes are available in the transformer terminal configuration and can be used for various purposes. RTD/analog inputs The RET 541 and RET 543 transformer terminals equipped with an RTD/analog module (RTD1) have eight general purpose analog inputs for DC measurement. The RTD/analog inputs are galvanically isolated from the transformer terminal power supply and enclosure. However, the inputs have a common ground. The general purpose RTD/analog inputs accept voltage-, current- or resistancetype signals. For each measuring mode, a separate parameter is provided for choosing between the available measurement ranges. RTD/analog inputs can be applied for e.g. temperature measurement. Digital outputs The outputs of the transformer terminal are categorized as follows: • HSPO: High-speed power output, doublepole contact, preferred for tripping purposes and for circuit breaker and disconnector control • PO: Power output, either single-pole or double-pole contact, preferred for circuit breaker and disconnector control Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 • SO: Signal output, either NO (Normally Open) or NO/NC (Normally Open/Normally Closed) contact. The output contact is a normal-duty contact and cannot be used for controlling a heavy load such as a circuit breaker. Analog outputs The RET 541 and RET 543 transformer terminals equipped with an RTD/analog module have four general purpose 0...20 mA analog current outputs. All outputs are galvanically isolated from the supply and enclosure of the transformer terminal and from each other. Analog outputs can be utilized for transferring any measured or calculated information to panel meters or e.g. PLCs. Alarm LED indicators The transformer terminal offers eight alarm LED indicators to be configured with the Relay Mimic Editor. The LED colours (green, yellow, red), their use, and the ON and OFF state texts can be freely defined. Three basic Display panel The transformer terminal is provided with either a fixed display or an external display module. The external display module requires a separate voltage supply from a common source with the main unit. The display consists of 19 rows divided into two windows: a main window (17 rows) and an assisting window (2 rows). The graphic display presents detailed information on MIMIC, objects, events, measurements, control alarms, and parameters. The assisting window is used for terminal-dependent indications/alarms and help messages. Additionally, the panel includes the following HMI items: • three push-buttons for object control (I, O, object selection) Serial communication The transformer terminal has three serial communication ports, one on the front panel and two on the rear panel. The standard optical ABB connector The standard optical ABB connector (RS-232 connection) on the front panel is intended for the connection of a PC for configuring the transformer terminal with the CAP 50_ tools. The front interface uses the SPA bus protocol. operation modes are supported: non-latched, latched-steady and latched flashflashing. Alarms can be acknowledged remotely, locally or by using logic of the transformer terminal. The alarm channels include time tagging for detected alarms. The time tagging principle used depends on the operation mode. Interlocking LED indicator The interlocking LED indicates that control operation has been interlocked or that the interlocking is in bybass mode, e.g. when control is possible despite of interlocking. Trip Circuit Supervision The purpose of this function is to supervise the tripping circuitry of the circuit breaker. An alarm will be generated in case a faulty tripping circuit, e.g. a circuit is not able to perform a trip, is detected. The supervision is based on the constant-current injection through the tripping circuitry. • eight freely programmable alarm LEDs with different colours and modes according to the configuration • LED indicator for control interlocking • three protection LED indicators • HMI push-button section with four arrow buttons and buttons for clear and enter • optically isolated serial communication port • backlight and contrast control • freely programmable button (F) which can be used in the configuration of the transformer terminal • a button for remote/local control HMI has two main levels, the user level and the technical level. The user level is for “everyday” measurements and monitoring whereas the technical level is intended for advanced transformer terminal programming. Unauthorized access can be prevented with passwords. SPA/IEC_103/DNP 3.0/Modbus communication on the rear connector X3.2 The 9-pin D-type subminiature male connector (RS-232 connection) on the rear panel connects the transformer terminal to the distribution automation system via the SPA bus, IEC_103, DNP 3.0 or Modbus. The fibreoptic interface module type RER 123 is used to connect the transformer terminal to the fibre-optic communication bus for SPA and 7 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 IEC_103 protocols. RS-485 interface module RER 133 is used to connect the transformer terminal to the RS-485 communication bus for DNP 3.0 and Modbus. LON/SPA bus communication on the rear connector X3.3 The 9-pin D-type subminiature female connector (RS-485 connection) on the rear panel connects the transformer terminal to the substation automation system via the SPA bus or the LON bus. The fibre-optic interface module type RER 103 is used to connect the transformer terminal to the fibre-optic communication bus. The RER 103 module supports both SPA bus and LON bus communication. The SPA-ZC 302 is an interface module that provides connectivity to the Profibus DP fieldbus and SPA-ZC 400 interface module provides connectivity to the IEC 61850-8-1 Station bus. Transformer terminal configuration The Relay Configuration Tool, based on the IEC 61131-3 standard and included in the CAP 505 Relay Product Engineering Tools, is used for configuring the basic terminal, protection and logic function blocks, control and measurement functions, timers and other functional elements included in the logic functions category. The programmable system of RET 54_ transformer terminals allows the output contacts to be operated in accordance with the state of the logic inputs and the outputs of the protection, control, measurement and condition monitoring functions. The PLC functions (e.g. interlocking and alarm logic) are programmed with Boolean functions, timers, counters, comparators and flip-flops. The program is written in a graphic function block diagram language by using the configuration software. Mimic configuration with Relay Mimic Editor The Relay Mimic Editor, which is included in the CAP 505 Relay Product Engineering Tools, is used for configuring the graphic display and the alarm channels of the transformer terminal. The mimic configuration may include circuit breakers, disconnectors, indicators, measurement data objects and user-defined texts and explanations. Any configuration can be saved for later use. 8 Self-supervision The transformer terminal RET 54_ is provided with an extensive self-supervision system. The self-supervision system handles run-time fault situations and informs the user of faults via the HMI and LON/SPA bus communication. When a fault has been detected, the green Ready indicator starts flashing, a fault indication text is displayed on the HMI and an event 0/E57 is generated. The fault indication text on the HMI consists of two rows: a general message ‘internal fault’, followed by the generated IRF code of the fault. The relay will try to recover from a fault either by restarting the module (I/O module or HMI) that reported the fault, or by restarting the whole relay. During restarting the IRF state will remain active until the internal selfsupervision program has determined that the relay is operating normally. If the fault is still persistent after restarting three times, the relay will be in permanent IRF state. All of the eight alarm function blocks can be configured in the same alarm view of the mimic editor. ON and OFF state texts (only one language version at a time can be supported for the alarm) and LED colours can be defined. Three different colours can be used to define the ON and OFF state. Three basic modes are available: • non-latched • latched-steady • latched flashing Interlocking LED texts can also be defined in the same alarm view but the colour of the interlocking LED cannot be changed. LON network configuration The LON Network Tool is used for binding network variables between the transformer terminal units. Typically, LON horizontal communication is used for transferring object status data (open, close, undefined) between units for interlocking purposes. Additionally, LON horizontal communication is used to transfer measured current amplitude and phase angle information between terminals, when parallel control with MCC principle is to be applied. DNP 3.0 and Modbus configuration The Protocol Mapping Tool is used for configuring the DNP 3.0 and Modbus interfaces of the transformer terminal. Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Transformer terminal parameterization The parameters of the transformer terminal units can be set either locally over the HMI or externally via the serial communication using the Relay Engineering Tools CAP 501/505. Local parameterization When the parameters are set locally, the setting parameters can be chosen from the hierarchical menu structure. The desired language for parameter description can be selected. External parameterization The Relay Setting Tool is used for parameterizing and setting the transformer terminals externally. The parameters can be set off-line on a PC and downloaded to the transformer terminal over a communication port. The menu structure of the setting tool, including views for parameterization and settings, is the same as the menu structure of the transformer terminal. Auxiliary voltage For its operation, the RET 54_ terminal, including the external display module, requires a secured auxiliary voltage supply. The terminal’s internal power supply module forms the voltages required by the terminal electronics. The power supply module is a galvanically isolated (fly-back type) dc/dc converter. A green protection LED indicator on the front panel is lit when the power supply module is in operation. Power supply modules Terminal connections All external circuits are connected to the terminal blocks on the rear panel, see figures 2...4. The terminal block for the measuring transformers consists of fixed screw terminals. The serial interface RS-485 on the rear panel is used for connecting the transformer terminal to the SPA bus or the LON bus. The SPA/LON bus is connected via a connection module type RER 103 fitted to the 9-pin Dtype subminiature connector and screwed to the rear panel. The serial interface RS-232 on the rear panel is used for connecting the transformer terminal to the SPA bus, the IEC_103, DNP 3.0 or Modbus. The SPA/IEC_103 is connected via a connection module type RER 123 fitted to the 9-pin D-type subminiature connector and screwed to the rear panel. DNP 3.0/Modbus is connected via a connection module, type RER 133. There are two basic types of power supply modules available for the RET 54_: type PS1/_ and type PS2/_. The operating range of digital inputs depends on the type of the power supply module. See Technical data. The digital input and output contacts of the transformer terminal are connected to the multi-pole connectors. Protective earth is connected to the screw marked with the earth symbol. 9 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Terminal diagrams + PS1_4_ACFail 1 - 2 PS1_4_TempAlarm X1.1 27 25 24 22 21 19 18 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 100V 1A 5A 1A 5A 1A 5A 100V 1A 5A 1A 5A 1A 5A 1A 5A Ch 10, VT2 SERIAL BUS Ch 9, CT7 SERIAL BUS Ch 8, CT6 X3.2 X3.3 X4.1 3 4 IRF Ch 7, CT5 X4.1 Mains Ch 6, VT1 5 6 + Ch 5, CT4 Ch 4, CT3 PS1_4_HSPO3 7 9 8 PS1_4_HSPO1 PS1_4_TCS1 11 13 12 10 Ch 3, CT2 Ch 2, CT1 TCS + 15 PS1_4_HSPO2 PS1_4_TCS2 TCS 16 18 17 X4.2 8 - X4.2 1 2 PS1_4_HSPO4 PS1_4_BI1 - 4 5 PS1_4_BI2 - 6 7 PS1_4_BI3 X5.1 1 2 3 BIO1_5_BI1 - - 4 5 6 - 7 8 9 - 10 11 12 PS1_4_HSPO5 - - 13 14 15 16 17 18 PS1_4_SO1 1 2 18 BIO1_5_BI2 BIO1_5_BI3 X5.2 3 BIO1_5_BI4 BIO1_5_BI5 BIO1_5_SO1 BIO1_5_BI7 BIO1_5_SO2 BIO1_5_BI9 BIO1_5_SO3 BIO1_5_BI10 BIO1_5_BI11 BIO1_5_BI12 4 5 6 7 9 BIO1_5_BI8 BIO1_5_SO4 8 10 12 11 13 15 X5.2 - 13 15 14 16 17 BIO1_5_BI6 - 9 11 10 12 BIO1_5_SO5 BIO1_5_SO6 14 16 18 17 RET 541 CD541 Fig. 2 10 Sample connection diagram of RET 541 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 + PS1_4_ACFail 1 - 2 PS1_4_TempAlarm X1.1 27 25 24 22 21 19 18 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 100V 1A 5A 1A 5A 1A 5A 100V 1A 5A 1A 5A 1A 5A 1A 5A Ch 10, VT2 SERIAL BUS Ch 9, CT7 SERIAL BUS Ch 8, CT6 X3.2 X3.3 X4.1 3 4 IRF Ch 7, CT5 X4.1 Mains Ch 6, VT1 5 6 + Ch 5, CT4 Ch 4, CT3 PS1_4_HSPO3 7 9 8 PS1_4_HSPO1 PS1_4_TCS1 TCS 11 13 12 TCS 16 18 17 10 Ch 3, CT2 Ch 2, CT1 + 15 PS1_4_HSPO2 PS1_4_TCS2 X4.2 8 - X4.2 1 2 PS1_4_HSPO4 PS1_4_BI1 - 4 5 PS1_4_BI2 - 6 7 PS1_4_BI3 X5.1 1 2 3 BIO1_5_BI1 - - 4 5 6 - 7 8 9 PS1_4_HSPO5 - 10 11 12 13 14 15 16 17 18 PS1_4_SO1 1 2 18 BIO1_5_BI2 BIO1_5_BI3 X5.2 3 BIO1_5_BI4 BIO1_5_BI5 BIO1_5_SO1 BIO1_5_BI7 BIO1_5_SO2 BIO1_5_BI9 BIO1_5_SO3 BIO1_5_BI10 BIO1_5_BI11 BIO1_5_BI12 4 5 6 7 9 BIO1_5_BI8 BIO1_5_SO4 8 10 12 11 13 15 X5.2 - 13 15 14 16 17 BIO1_5_BI6 - 9 11 10 12 BIO1_5_SO5 BIO1_5_SO6 14 16 18 17 X7.1 BIO2_7_PO1 17 18 X7.2 X7.1 1 2 3 4 5 6 7 8 9 10 11 12 BIO2_7_BI1 BIO2_7_PO2 1 2 BIO2_7_PO3 4 5 6 BIO2_7_PO4 8 9 10 BIO2_7_PO5 12 13 14 BIO2_7_PO6 16 17 18 3 BIO2_7_BI2 BIO2_7_BI3 7 BIO2_7_BI4 BIO2_7_BI5 BIO2_7_BI6 BIO2_7_BI7 11 BIO2_7_BI8 13 14 BIO2_7_BI9 15 16 BIO2_7_BI10 15 RET 543 CD543 Fig. 3 Sample connection diagram of RET 543 11 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 X4.1 + PS2_4_ACFail Mains - PS2_4_TempAlarm X1.1 27 25 24 22 21 19 18 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 100V Ch 10, VT2 1A 5A Ch 9, CT7 1A 5A 1A 5A 100V 1A 5A 1A 5A 1A 5A 1A 5A SERIAL BUS SERIAL BUS Ch 8, CT6 2 X3.2 X3.3 X4.1 3 4 IRF Ch 7, CT5 1 Ch 6, VT1 5 6 + Ch 5, CT4 Ch 4, CT3 PS2_4_HSPO3 7 9 8 PS2_4_HSPO1 PS2_4_TCS1 11 13 12 10 Ch 3, CT2 Ch 2, CT1 TCS + 15 PS2_4_HSPO2 PS2_4_TCS2 TCS 16 18 17 X4.2 1 PS2_4_HSPO4 PS2_4_HSPO5 - - - X5.1 1 2 3 4 5 6 7 8 9 PS2_4_HSPO6 BIO1_5_BI1 BIO1_5_BI2 PS2_4_HSPO7 BIO1_5_BI3 - 10 11 12 13 14 15 16 17 18 BIO1_5_BI5 PS2_4_HSPO8 - 10 12 11 13 14 16 15 17 18 X5.2 3 BIO1_5_BI7 BIO1_5_SO1 BIO1_5_BI8 BIO1_5_BI9 BIO1_5_SO2 BIO1_5_BI11 BIO1_5_SO3 BIO1_5_BI12 4 5 6 7 9 BIO1_5_BI10 X5.2 1 2 6 8 7 9 BIO1_5_BI4 BIO1_5_BI6 - 2 4 3 5 BIO1_5_SO4 8 10 12 11 13 15 BIO1_5_SO5 X6.1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 BIO1_6_BI1 BIO1_5_SO6 BIO1_6_BI2 BIO1_6_BI3 BIO1_6_SO1 BIO1_6_BI5 BIO1_6_BI6 BIO1_6_SO2 BIO1_6_BI7 BIO1_6_BI8 BIO1_6_SO3 BIO1_6_BI9 BIO1_6_BI10 BIO1_6_SO4 BIO1_6_BI11 BIO1_6_SO5 BIO1_6_BI12 X7.1 4 5 6 7 8 9 10 11 12 17 3 BIO1_6_BI4 BIO1_6_SO6 1 2 3 16 18 X6.2 X6.2 1 2 14 4 5 6 7 9 8 10 12 11 13 15 14 16 18 17 X7.1 BIO2_7_BI1 BIO2_7_PO1 BIO2_7_BI2 BIO2_7_PO2 BIO2_7_BI4 BIO2_7_PO3 BIO2_7_BI6 BIO2_7_BI7 BIO2_7_BI8 BIO2_7_BI9 15 16 BIO2_7_BI10 1 2 3 BIO2_7_BI5 13 14 17 18 X7.2 BIO2_7_BI3 BIO2_7_PO4 BIO2_7_PO5 BIO2_7_PO6 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 RET 545 CD545_b Fig. 4 12 Sample connection diagram of RET 545 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Technical data Table 1: General functions available for the RET 54_ Function Description INDRESET Resetting of operation indicators, latched output signals, registers and waveforms i.e. the disturbance recorder MMIWAKE Activation of HMI backlight SWGRP1 Switchgroup SWGRP1 SWGRP2 Switchgroup SWGRP2 SWGRP3 Switchgroup SWGRP3 ...... SWGRP20 Switchgroup SWGRP20 Table 2: Standard functions available for the RET 54_ Function Description ABS Absolute value ACOS Principal arc cosine ADD Extensible adder AND Extensible AND connection ASIN Principal arc sine ATAN Principal arc tangent BCD2INT Type conversion from BCD coded input to SINT (Tap changer) BITGET Get one bit BITSET Set one bit BOOL_TO_* Type conversion from BOOL to WORD / USINT / UINT / UDINT / SINT / REAL / INT / DWORD / DINT / BYTE BOOL2INT Type conversion from BOOL inputs to INT output BYTE_TO_* Type conversion from BYTE to WORD / DWORD COMH Hysteresis comparator COS Cosine in radians CTD Down-counter CTUD Up-down counter CTU Up-counter DATE_TO_UDINT Type conversion from DATE to UDINT DINT_TO_* Type conversion from DINT to SINT / REAL / INT DIV Divider DWORD_TO_* Type conversion from DWORD to WORD / BYTE EQ Extensible comparison to equal EXP Natural exponential EXPT Exponentiation F_TRIG Falling edge detector GE Extensible comparison to greater or equal GRAY2INT Type conversion from GRAY coded input to SINT (Tap changer) GT Extensible comparison to greater INT_TO_* Type conversion from INT to REAL / DINT INT2BOOL Type conversion from INT input to BOOL outputs LE Extensible comparison to less or equal LIMIT Limitation LN Natural logarithm LOG Logarithm base 10 LT Extensible comparison to less MAX Extensible maximum MIN Extensible minimum MOD Modulo MOVE Move 13 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 2: Standard functions available for the RET 54_ Function Description MUL Extensible multiplier MUX Extensible multiplexer NAT2INT Type conversion from natural binary coded input to SINT (Tap changer) NE Comparison to greater or less NOT Complement OR Extensible OR connection R_TRIG Rising edge detector REAL_TO_* Type conversion from REAL to USINT / UINT / UDINT / SINT / INT / DINT ROL Rotate to left ROR Rotate to right RS Reset dominant bistable function block RS_D Reset dominant bistable function block with data input SEL Binary selection SHL Bit-shift to left SHR Bit-shift to right SIN Sine in radians SINT_TO_* Type conversion from SINT to REAL / INT / DINT SUB Subtractor SQRT Square root SR Set dominant bistable function block XOR Extensible exclusive OR connection TAN Tangent in radians TIME_TO_* Type conversion from TIME to UDINT / TOD / REAL TOD_TO_* Type conversion from TOD to UDINT / TIME / REAL TOF Off-delay timer TON On-delay timer TP Pulse TRUNC_REAL_TO* Truncation toward zero from REAL to DINT / INT / SINT / UDINT / UINT / USINT UDINT_TO_* Type conversion from UDINT to USINT / UINT / REAL UINT_TO_* Type conversion from UINT to USINT / UDINT / REAL / BOOL USINT_TO_* Type conversion from USINT to UINT / UDINT / REAL WORD_TO_* Type conversion from WORD to DWORD / BYTE Table 3: Conditioning monitoring functions available for the RET 54_ 14 Function Description CMBWEAR1 Circuit-breaker electric wear 1 CMBWEAR2 Circuit-breaker electric wear 2 CMCU3 Supervision function of the energizing current input circuit CMGAS1 Gas pressure monitoring CMGAS3 Three-pole gas pressure monitoring CMSCHED Scheduled maintenance CMSPRC1 Spring charging control 1 CMTCS1 Trip circuit supervision 1 CMTCS2 Trip circuit supervision 2 CMTIME1 Operate time counter 1 for the operate time used (e.g. motors) CMTIME2 Operate time counter 2 for the operate time used (e.g. motors) CMTRAV1 Breaker travel time 1 CMVO3 Supervision function of the energizing voltage input circuit Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 4: Control functions available for the RET 54_ Function Description CO3DC1 Three-state disconnector 1 with indication CO3DC2 Three-state disconnector 2 with indication COCB1 Circuit breaker 1 control with indication COCB2 Circuit breaker 2 control with indication COCBDIR Direct open for CBs via HMI CODC1 Disconnector 1 control with indication CODC2 Disconnector 2 control with indication CODC3 Disconnector 3 control with indication CODC4 Disconnector 4 control with indication CODC5 Disconnector 5 control with indication COIND1 Switching device 1 indication COIND2 Switching device 2 indication COIND3 Switching device 3 indication COIND4 Switching device 4 indication COIND5 Switching device 5 indication COIND6 Switching device 6 indication COIND7 Switching device 7 indication COIND8 Switching device 8 indication COLOCAT Logic-controlled control position selector COLTC On-load tap changer controller (voltage regulator) COSW1 On/off switch 1 COSW2 On/off switch 2 COSW3 On/off switch 3 COSW4 On/off switch 4 MMIALAR1 Alarm channel 1, LED indicator MMIALAR2 Alarm channel 2, LED indicator MMIALAR3 Alarm channel 3, LED indicator MMIALAR4 Alarm channel 4, LED indicator MMIALAR5 Alarm channel 5, LED indicator MMIALAR6 Alarm channel 6, LED indicator MMIALAR7 Alarm channel 7, LED indicator MMIALAR8 Alarm channel 8, LED indicator MMIDATA1 MIMIC data monitoring point 1 MMIDATA2 MIMIC data monitoring point 2 MMIDATA3 MIMIC data monitoring point 3 MMIDATA4 MIMIC data monitoring point 4 MMIDATA5 MIMIC data monitoring point 5 15 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 5: On-load tap changer controller function block On load tap changer control function (voltage regulator), COLTC Reference voltage 0.000 ... 2.000 xUn Delay time for the 1st control pulse 1.0 ... 300.0 s Delay time for the 2nd control pulse 1.0 ... 300.0 s Resistive line-drop compens. factor (Ur) 0.0 ... 25.0 %Un Reactive line-drop compens. factor (Ux) 0.0 ... 25.0 %Un Load phase angle (in NRP mode) -89 ... +89 deg Stability factor in parallel operation 0.0 ... 70.0 %Un Operation mode Not in use Manual Automatic single Automatic master Automatic follower Negative Reactance Principle Minimizing Circulating Current Controlled via op.mode inputs Delay mode Definite time Inverse time Raise and lower pulse duration 0.5 ... 10.0 s Bandwith 0.60 ... 9.00 %Un Overcurrent blocking limit 0.10 ... 5.00 xIn Undervoltage blocking limit 0.10 ... 1.20 xUn Overvoltage blocking limit 0.80 ... 1.60 xUn High circ. current blocking limit 0.10 ... 5.00 xIn Max limit for LDC term 0.00 ... 2.00 xUn Reduce Set Voltage step 0.00 ... 9.00 %Un Max volt tap -36 ... 36 Min volt tap -36 ... 36 Max parallel trafos in MCC mode 4 Operation accuracies - voltage measurement: - lower and raise output pulse duration: Depends on the frequency of the voltage measured: f/fn = 0.95 ... 1.05: +1.0% of the set value or +0.01xUn +1% of the set value or +250 ms 250ms and an inaccuracy which occurs when voltage varies +0.5% +100 ms Reset ratio (hysteresis) 20% of the set Bandwith - operation time DT mode: - operation time IDMT mode: Table 6: Measurement function blocks General measurement/ analog input on RTD/analog module, MEAI1...8 The general measurement function blocks can be used to measure general purpose dc or ac voltage signals with a sensor input. They also include a REAL type input which can be used to monitor any internal REAL type IEC 61131-3 based signal, e.g. input data from the RTD/analog module. GE1…3 (V dc/ac) General REAL type input -10000.00000...10000.00000 -10000.00000...10000.00000 Analog output on RTD/analog module, MEAO1...4 The analog output function blocks handle the scaling of any internal REAL type IEC 61131-3 based signal to fit a selectable 0…20 mA or 4…20 mA range for use with the outputs on the RTD/analog module. General REAL type input -10000.00000...10000.00000 Neutral current measurement, MECU1A and MECU1B Io (A) Io (%) 16 0.0…20000.0 A 0.0…80.0% In Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Three-phase current measurement, MECU3A and MECU3B IL1 IL2 IL3 IL1 IL2 IL3 IL1 demand IL2 demand IL3 demand IL1 demand IL2 demand IL3 demand 0.0…20000.0 A 0.0…20000.0 A 0.0…20000.0 A 0.0…1000.0% In 0.0…1000.0% In 0.0…1000.0% In 0.0…20000.0 A 0.0…20000.0 A 0.0…20000.0 A 0.0…1000.0% In 0.0…1000.0% In 0.0…1000.0% In Transient disturbance recorder for 16 analog channels, MEDREC16 The transient disturbance recorder MEDREC16 is used for recording the current and voltage waveforms, as well as the status data of internal IEC 61131-3 based logic signals and digital inputs connected to the transformer terminals. Maximum 16 analog inputs and 16 logic signal inputs are available. One fundamental cycle contains 40 samples. Operation mode Pre-trg time Over limit ILx Over limit Io Over limit Iob Over limit Uo Over limit Ux Over limit Uxy Over limit U12b Over limit ILxb Under limit Ux Under limit Uxy AI filter time Saturation Overwrite Extension 0…100% 0.00…40.00 x In 0.00…40.00 x In 0.00…40.00 x In 0.00…2.00 x Un 0.00…2.00 x Un 0.00…2.00 x Un 0.00…2.00 x Un 0.00…40.00 x In 0.00…2.00 x Un 0.00…2.00 x Un 0.000…60.000 s The recording can be triggered by any (or several) of the alternatives listed below: • triggering on the rising or falling edge of any (or several) of the digital inputs • triggering on overcurrent, overvoltage or undervoltage • manual triggering via the menu or with the push-button F on the front panel (if configured) • triggering via serial communication • periodic triggering The recording length depends on the number of recordings and inputs used. For example, the following combination of recording length, number of recordings and number of inputs is available at 50 Hz (60 Hz): # recordings \ # inputs 1 3 10 1 1163 cyc. 23.3 s (19.4 s) 412 cyc. 8.2 s (6.9 s) 126 cyc. 2.5 s (2.1 s) 5 232 cyc. 4.6 s (3.9 s) 82 cyc. 1.6 s (1.4 s) 25 cyc. 0.5 s (0.4 s) 10 115 cyc. 2.3 s (1.9 s) 41 cyc. 0.8 s (0.7 s) 12 cyc. 0.24 s (0.2 s) System frequency measurement, MEFR1 Frequency Average Freq. Voltage U 10.00…75.00 Hz 10.00…75.00 Hz 0.0…2.0 x Un 17 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Three-phase power and energy measurement, MEPE7 P3 (kW) Q3 (kvar) Power factor DPF Power factor PF P3 demand (kW) Q3 demand (kvar) Energy kWh Reverse kWh Energy kvarh Reverse kvarh -999999…999999 kW -999999…999999 kvar -1.00…1.00 -1.00…1.00 -999999…999999 kW -999999…999999 kvar 0…999999999 kWh 0…999999999 kWh 0…999999999 kvarh 0…999999999 kvarh Residual voltage measurement, MEVO1A and MEVO1B Uo Uo 0…150000 V 0.0…120.0% Un Three-phase voltage measurement, MEVO3A and MEVO3B UL1_U12 UL2_U23 UL3_U31 UL1_U12 UL2_U23 UL3_U31 UL1_U12 average UL2_U23 average UL3_U31 average UL1_U12 average UL2_U23 average UL3_U31 average 18 0.00…999.99 kV 0.00…999.99 kV 0.00…999.99 kV 0.00…2.00 x Un 0.00…2.00 x Un 0.00…2.00 x Un 0.00…999.99 kV 0.00…999.99 kV 0.00…999.99 kV 0.00…2.00 x Un 0.00…2.00 x Un 0.00…2.00 x Un Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 7: Protection function blocks Three-phase non-directional overcurrent protection, low-set stages, NOC3Low, 3I>, NOC3LowB,3I> Start current Operate time at DT mode Time multiplier at IDMT mode Operation mode Measuring mode Drop-off time of the operate time counter Operation accuracy Start time: - Injected currents - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy at DT mode Accuracy class index E at IDMT mode 0.10…5.00 x In 0.05…300.00 s 0.05…1.00 Not in use Definite time Extremely inverse Very inverse Normal inverse Long time inverse RI-type inverse RD-type inverse IEEE curves Peak-to-peak Fundamental frequency 0...1000 ms Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value or ±0.01 x In >2.0 x start current: <32 ms <40 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.95 < 45 ms ±2% of set value or ±20 ms Class index E = 5.0 or ±20 ms Three-phase non-directional overcurrent protection, high-set stage, NOC3High, 3I>>, and instantaneous stage, NOC3Inst, 3I>>> Start current Operate time Operation mode 0.10…40.00 x In 0.05…300.00 s Not in use Definite time Instantaneous Measuring mode Peak-to-peak Fundamental frequency 0...1000 ms Drop-off time of the operate time counter Operation accuracy Start time: - injected currents - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy at DT mode Note! The values below apply when f/fn = 0.95...1.05 0.1...10 x In: ±2.5% of set value or ±0.01 x In 10...40 x In: ±5.0% of set value >2.0 x start current: <32 ms <40 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.95 < 45 ms ±2% of set value or ±20 ms 19 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Three-phase directional overcurrent function, low-set stage, DOC6Low, I>→ Operation mode Start current Operate time Time multiplier Basic angle ϕb Operation direction Earth-fault protection Measuring mode Drop-off time of the operate time counter Operation accuracy Start time: - injected currents - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy at DT mode Accuracy class index E at IDMT mode Not in use Definite time Extremely inverse Very inverse Normal inverse Long-time inverse RI-type inverse RD-type inverse 0.05…40.00 x In 0.05…300.00 s 0.05…1.00 0…90° Forward Reverse Disabled Enabled Phase-to-phase voltages, peak-to-peak measurement Phase-to-phase voltages, fundamental freq. measurement Phase-to-earth voltages, peak-to-peak measurement Phase-to-earth voltages, fundamental freq. measurement 0...1000 ms Note! The values below apply when f/fn = 0.95...1.05 0.1...10 x In: ±2.5% of set value or ±0.01 x In 10...40 x In: ±5.0% of set value ±2.5% of measured voltage or ±0.01 x Un ±2° >2.0 x start current: <42 ms <50 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.95 < 45 ms ±2% of set value or ±20 ms Class index E = 5.0 or ±20 ms Three-phase directional overcurrent function, high-set stage, DOC6High, I>>→, and instantaneous stage, DOC6Inst, I>>>→ Operation mode Start current Operate time Basic angle ϕb Operation direction Earth-fault protection Non-directional operation (when the direction cannot be determined) Measuring mode Drop-off time of the operate time counter 20 Not in use Definite time Instantaneous 0.05…40.00 x In 0.05…300.00 s 0…90° Forward Reverse Disabled Enabled Disabled Enabled Phase-to-phase voltages, peak-to-peak measurement Phase-to-phase voltages, fundamental freq. measurement Phase-to-earth voltages, peak-to-peak measurement Phase-to-earth voltages, fundamental freq. measurement 0...1000 ms Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Operation accuracy Start time: - injected currents - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy at DT mode Note! The values below apply when f/fn = 0.95...1.05 0.1...10 x In: ±2.5% of set value or ±0.01 x In 10...40 x In: ±5.0% of set value ±2.5% of measured voltage or ±0.01 x Un ±2° >2.0 x start current: <42 ms <50 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.95 < 45 ms ±2% of set value or ±20 ms Three-phase underimpedance protection, low-set stage UI6Low, Z<, and high-set stage UI6High, Z<< Z-setting Operate time UI6High Meas. signals (phase selection) Measuring mode Operation accuracy Start time: - injected impedance - internal time - total time Reset time Reset ratio Retardation time Operate time accuracy 0.01…60.00 p.u. 0.04…300.00 s Not in use; In use 4 selections for ph-e voltages 7 selections for ph-ph voltages (depends on the signals available) Peak-to peak; Fund.freq. Note! The values below apply when f/fn = 0.95...1.05 ± 3.0% of set value or ± 0.02 p.u. = 0.50 x Z-setting <42 ms <50 ms 70...1030 ms (depends on the minimum pulse width set for the TRIP output) Typ. 1.03 < 45 ms ± 2% of set value or ± 20 ms Stabilized and instantaneous differential protection for transformers, Diff6T, 3∆Ι>,3∆Ι>> Basic setting; the lowest ratio of differential and nominal current to cause a trip Starting ratio; slope of the 2nd line of the operating characteristics Turn-point 1; turnpoint between the 1st and 2nd line of the operating characteristics Turn-point 2; turnpoint between the 2nd and 3rd line of the operating characteristics Tripping value of the instantaneous stage Operation accuracy Trip time: - Injected currents - internal time - total time Reset time Reset ratio, typically Retardation time 5...50% 10...50% 0.5 x In 1.0...3.0 x In 5...30 x In Note! The values below apply when f/fn = 0.95...1.05 Phase difference measurement: ±4° Stabilized stage: ±4% of set value or ±2% x In Instantaneous stage: ±4% of set value or ±2% x In >2.0 x operating current <35 ms <45 ms 60...1020 ms (depends on the minimum pulse width set for the trip output) 0.98 < 40 ms 21 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Non-directional earth-fault protection, low-set stage, NEF1Low, I0> Start current Operate time at DT mode Time multiplier at IDMT mode Operation mode Measuring mode Drop-off time of the operate time counter Operation accuracy Start time: - Injected currents - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy at DT mode Accuracy class index E at IDMT mode 1.0…100.0% of In 0.05…300.00 s 0.05…1.00 Not in use Definite time Extremely inverse Very inverse Normal inverse Long time inverse RI-type inverse RD-type inverse IEEE curves Peak-to-peak Fundamental frequency 0...1000 ms Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value + 0.0005 x In >2.0 x start current: <32 ms <40 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.95 <45 ms ±2% of set value or ±20 ms Class index E = 5.0 or ±20 ms Non-directional earth-fault protection, high-set stage, NEF1High, I0>>, and instantaneous stage, NEF1Inst, I0>>> Start current Operate time Operation mode Measuring mode Drop-off time of the operate time counter Operation accuracy Start time: - Injected currents - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy at DT mode 22 0.10…12.00 x In 0.05…300.00 s Not in use Definite time Instantaneous Peak-to-peak Fundamental frequency 0...1000 ms Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value or + 0.01 x In >2.0 x start current <32 ms <40 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.95 < 45 ms ±2% of set value or ±20 ms Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Directional earth-fault protection, low-set stage, DEF2Low, I0>→ Start current Start voltage Operate time at DT mode Time multiplier at IDMT mode Operation mode Operation criteria Operation direction Basic angle ϕb Operation characteristic Intermittent E/F Measuring mode Drop-off time of the operate time counter Operation accuracy 1.0…25.0% of In 2.0…100.0% of Un 0.1…300.0 s 0.05…1.00 Not in use Definite time Extremely inverse Very inverse Normal inverse Long time inverse Basic angle & Uo Basic angle IoSin/Cos & Uo IoSin/Cos Non-directional Io Non-directional Uo Forward Reverse -90° -60° -30° 0° IoSin(ϕ) IoCos(ϕ) Not active Active Peak-to-peak Fundamental frequency 0...1000 ms Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value + 0.0005 x In ±2.5% of set value or + 0.01 x Un Phase angle ±2° Start time: - Injected neutral current and residual voltage >2.0 x start current and residual voltage >2.0 x start voltage - internal time <72 ms - total time < 80 ms Reset time 40...1000 ms (depends on the minimum pulse width set for the trip output) Reset ratio, typically 0.95 Retardation time < 50 ms Operate time accuracy at DT mode ±2% of set value or ±20 ms Accuracy class index E at IDMT mode Class index E = 5.0 or ±20 ms 23 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Directional earth-fault protection, high-set stage, DEF2High, I0>>→, and instantaneous stage, DEF2Inst, I0>>>→ Start current Start voltage Operate time Operation mode Operation criteria Operation direction Basic angle ϕb Operation characteristic Intermittent E/F Measuring mode Drop-off time of the operate time counter Operation accuracy Start time, injected neutral current and residual voltage - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy at DT mode 1.0…200.0% of In 2.0…100.0% of Un 0.1…300.0 s Not in use Definite time Instantaneous Basic angle & Uo Basic angle IoSin/Cos & Uo IoSin/Cos Non-directional Io Non-directional Uo Forward Reverse -90° -60° -30° 0° IoSin(ϕ) IoCos(ϕ) Not active Active Peak-to-peak Fundamental frequency 0...1000 ms Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value + 0.0005 x In ±2.5% of set value or + 0.01 x Un Phase angle ±2° Injected neutral current >2.0 x start current and residual voltage >2.0 x start voltage <72 ms <80 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.95 <50 ms ±2% of set value or ±20 ms High-impedance based restricted earth-fault protection, REF1A, ∆I0> Basic setting; the lowest ratio of differential and nominal current to cause a trip Operation accuracy Trip time - injected currents - internal time - total time Reset time Reset ratio Retardation time 24 0.5...50% Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value or ±0.004 x In >2.0 x operating current: <20 ms <30 ms 60...1020 ms (depends on the minimum pulse width set for the trip output) 0.80...0.98 This function block cannot be retarded but trips once the current exceeds the operate value Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Stabilized restricted earth-fault protection, REF4A, ∆I0> and REF4B, ∆I0> Basic setting Operate time Ratio I2f/I1f> 2nd harmonic blocking Operation accuracy of differential current measurement Operation accuracy of phase angle measurement Start time: -injected currents - internal time - total time Reset time Reset ratio, typically Retardation time (Total retardation time when the current drops below the start value) Operation time accuracy at definite time mode 0.5...50% 0.04...300.00 s 10...50 % Not in use / In use Note! The values below apply when f/fn = 0.95...1.05 ±4% of set value or ±0.02 x In ±2% >2.0 x operating current: <30 ms <40 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.98 (0.90...0.98) <50 ms ±2% of set value or ±20 ms Residual overvoltage protection, low-set stage, ROV1Low, U0> Start voltage Operate time Operation mode Measuring mode Operation accuracy Start time: -injected voltages - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy at DT mode 2.0…20.0% of Un 0.05…300.00 s Not in use Definite time Peak-to-peak Fundamental frequency Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value or ±0.01 x Un >2 x start voltage: <32 ms <40 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.95 Total time for blocking: < 25 ms Total time when voltage drops below start value: < 50 ms ±2% of set value or ±20 ms 25 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Residual overvoltage protection, high-set stage, ROV1High, U0>>, and instantaneous stage, ROV1Inst, U0>>> Start voltage Operate time Operation mode Measuring mode Operation accuracy Start time - injected voltages - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy at DT mode 26 2.0…80.0% of Un 0.05…300.00 s Not in use Definite time Peak-to-peak Fundamental frequency Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value or ±0.01 x Un >2 x start voltage <32 ms <40 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.95 Total time for blocking: < 25 ms Total time when voltage drops below start value: < 50 ms ±2% of set value or ±20 ms Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Three-phase thermal overload protection for motors, generators and transformers, TOL3Dev, 3 BASIC SETTINGS: Starting current of the motor Max. starting time permitted for the motor Number of starts allowed from cold state Type of device to be protected Trip temperature Prior alarm temperature Restart inhibit (temperature limit for successful restarting) Ambient temperature Cooling time-constant Heating time-constant for generator or transformer ADVANCED SETTINGS: Short time-constant for stator Long time-constant for stator Weighting factor of the short time-constant for stator Temperature rise of stator at rated current Maximum temperature of stator Short time-constant for rotor Long time-constant for rotor Weighting factor of the short time-constant for rotor Temperature rise of rotor at rated current Maximum temperature of rotor Operation mode (principle of ambient temperature compensation) Waiting time for a successful restart (Readonly parameter) Estimated time to the trip (Read-only parameter) Operation accuracy Reset ratio: - trip - start - restart 0.10...10.00 x In 0.1...120.0 s 1...3 Motor; through-ventilated, rated power < 1500 kW Motor; through-ventilated, rated power > 1500 kW Motor; surface cooling, rated power < 500 kW Motor; surface cooling, rated power > 500 kW Generator; hydro or small air-cooled turbine generators Generator; large turbine generators Transformer 80.0…120.0% 40.0…100.0% 40.0…100.0% -50.0…100.0°C 1.0...10.0 x time constant 1...999 min 0.0...999.0 min 0.0...999.0 min 0.00...1.00 0.0...350.0 °C 0.0...350.0 °C 0.0...999.0 min 0.0...999.0 min 0.00...1.00 0.0...350.0 °C 0.0...350.0 °C Not in use No sensors; the set ambient temperature 1 sensor used 2 sensors used 0...86400 s 0...86400 s Note! The values below apply when f/fn = 0.95...1.05 ±1.0%, I = 0.1...10.0 x In (Calculated temp. rise - 0.1) / Trip temperature (Calculated temp. rise - 0.1) / Prior alarm temperature (Calculated temp. rise - 0.1) / Restart inhibit temperature limit 27 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Negative phase-sequence protection, low-set stage, NPS3Low, I2>, and high-set stage, NPS3High, I2>> Operation mode Start value of negative-sequence current I2 Operate time Operating characteristic constant K (corresponds to the machine constant, equal to the I22t constant of the machine as stated by machine manufacturer) Definite start time at inverse-time mode Definite minimum operate time Maximum operate time Cooling time of the machine Number of phases to be measured Rotation direction Drop-off time of the operate time counter Operation accuracy Start time: - injected negative-seq. current - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy at DT mode Accuracy class index E at IDMT mode, typically Not in use Definite time Inverse time 0.01...0.50 x In 0.1....120.0 s 5.0...100.0 0.1...60.0 s 0.1...120.0 s 500...10000 s 5...10000 s 2 or 3 Forward Reverse 0...1000 ms Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value or ±0.01 x In = 2.00 x start value <32 ms <40 ms 70...1030 ms (depends on the minimum pulse width set for the trip output) 0.96 <45 ms ±2% of set value or ±20 ms ±2% of the calculated ideal operate time or ±20 ms Three-phase overvoltage protection, low-set stage, OV3Low, 3U> Start voltage Operate time Time multiplier Operation mode Measuring mode Operation hysteresis Operation accuracy Start time: -injected voltages - internal time - total time Reset time Reset ratio Retardation time Operate time accuracy at DT mode Accuracy class index E at IDMT mode, typically 28 0.10…1.60 x Un 0.05…300.0 s 0.05…1.00 Not in use Definite time A curve B curve Phase-to-phase voltages; peak-to-peak measurement Phase-to-phase voltages; fundamental freq. measurement Phase-to-earth voltages; fundamental freq. measurement 1.0...5.0% Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value = 1.1 x start voltage <42 ms <50 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.96 (range 0.95...0.99) < 50 ms ±2% of set value or ±20 ms ±20 ms Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Three-phase overvoltage protection, high-set stage, OV3High, 3U>> Start voltage Operate time Operation mode Measuring mode Operation hysteresis Operation accuracy Start time: - injected voltages - internal time - total time Reset time Reset ratio Retardation time Operate time accuracy at DT mode 0.10…1.60 x Un 0.05…300.0 s Not in use Definite time Phase-to-phase voltages; peak-to-peak measurement Phase-to-phase voltages; fundamental freq. measurement Phase-to-earth voltages; fundamental freq. measurement 1.0...5.0% Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value = 1.1 x start voltage <42 ms <50 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 0.96 (range 0.95...0.99) < 50 ms ±2% of set value or ±20 ms Three-phase undervoltage protection, low-set stage, UV3Low, 3U< Start voltage Operate time Time multiplier Operation mode Measuring mode Operation hysteresis Operation accuracy Start time: - injected voltages - internal time - total time Reset time Reset ratio Retardation time Operate time accuracy at DT mode Accuracy class index E at IDMT mode, typically 0.10…1.20 x Un 0.1…300.0 s 0.1…1.0 Not in use Definite time C curve Phase-to-phase voltages; peak-to-peak measurement Phase-to-phase voltages; fundamental freq. measurement Phase-to-earth voltages; fundamental freq. measurement 1.0...5.0% Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value or ±0.01 x Un <0.5 x start voltage: <32 ms <40 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 1.04 (range 1.01...1.05) < 60 ms ±2.5% of set value ±35 ms 29 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Three-phase undervoltage protection, high-set stage, UV3High, 3U<< Start voltage Operate time Operation mode Measuring mode Operation hysteresis Operation accuracy Start time: - injected voltages - internal time - total time Reset time Reset ratio Retardation time Operate time accuracy at DT mode 0.10…1.20 x Un 0.1…300.0 s Not in use Definite time Phase-to-phase voltages; peak-to-peak measurement Phase-to-phase voltages; fundamental freq. measurement Phase-to-earth voltages; fundamental freq. measurement 1.0...5.0% Note! The values below apply when f/fn = 0.95...1.05 ±2.5% of set value or ±0.01 x Un <0.5 x start voltage: <32 ms <40 ms 40...1000 ms (depends on the minimum pulse width set for the trip output) 1.04 (range 1.01...1.05) <60 ms ±2.5% of set value Phase-sequence voltage protection, PSV3St1 and PSV3St2, U1<, U2>, U1> Start value U2> Start value U1< Start value U1> Operate time U2> Operate time U1< Operate time U1> Operation mode Rotation direction selection Operation accuracy Trip time, U2> operation: - Injected negative-sequency voltage - internal time - total time Trip time, U1< operation: - injected positive-sequency voltage - internal time - total time Trip time, U1> operation: - Injected positive-sequency voltage - internal time - total time Reset time Reset ratio, typically Retardation time Operate time accuracy 30 0.01…1.00 x Un 0.01…1.20 x Un 0.80…1.60 x Un 0.04…60.00 s 0.04…60.00 s 0.04…60.00 s Not in use; U1< & U2> & U1>; U1< & U2>; U2> & U1>; U1< & U1>; U2>; U1<; U1> Forward; Reverse; Input ROT_DIR Note! The values below apply when f/fn = 0.95...1.05 ± 2.5% of set value or ± 0.01 x Un = 1.1 x start value <42 ms <50 ms = 0.50 x start value <32 ms <40 ms = 1.1 x start value <42 ms <50 ms 70...1030 ms (depends on the minimum pulse width set for the TRIP output) U2> operation: 0.96 U1< operation: 1.04 U1> operation: 0.99 <45 ms (for all operations) ± 2% of set value or ± 20 ms Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Underfrequency or overfrequency protection, 5 stages, Freq1St1… Freq1St5, f</f>, df/dt Operation mode Undervoltage limit for blocking Start value for under-/overfrequency prot. Operate time for under-/overfrequency prot. Start value for df/dt protection Operate time for df/dt protection Operation accuracy - Frequency rate of change (df/dt): - real df/dt - real df/dt - Undervoltage blocking Start time: - total start times at fn = 50 Hz: - frequency measurement - df/dt measurement Reset time Operate time accuracy Not in use f</f> 1 timer f</f> 2 timers f</f> OR df/dt> f</f> AND df/dt> f</f> OR df/dt< f</f> AND df/dt< 0.30…0.90 x Un 25.00…75.00 Hz 0.10…120.00 s 0.2…10.0 Hz/s 0.12…120.00 s Under-/overfrequency (f</f>): ±10 mHz <±5 Hz/s: ±100 mHz/s <±15 Hz/s: ±2.0% of real df/dt ±1.0% of set value <100 ms <120 ms 140...1000 ms (depends on the minimum pulse width set for the trip output) ±2% of set value or ±30 ms Overexcitation protection, low-set stage, OE1Low, U/f>, and high-set stage, OE1High, U/f>> U/f start (DT mode) U/f start (IDMT mode) U max cont. Operate time k Maximum time Constant delay Cooling time Operation mode 1.00...2.00 x U/f 1.00...2.00 x U/f 0.80...1.60 x Un 0.10...600.00 s 0.1...100.0 500...10000 s 0.1...120.0 s 5...10000 s Not in use; Definite time; Curve#1; Curve#2 Operation accuracies Start time: - Injected U/f - internal time - total time Reset time 20...40 Hz: ±4% of set value; 40...80 Hz: ±2% of set value Reset ratio: - 20...40 Hz - 40...80 Hz Retardation time Operate time accuracy at definite-time mode Operate time accuracy at inverse-time modes >2.0 x Un/fn <60 ms, <70 ms 100…1060 ms (depends on the set minimum pulse width for the TRIP output) typ. 0.99 typ 0.97 <105 ms 20...80 Hz: ±4% of set value or ±40 ms ±100 ms or the accuracy appearing when the measured voltage varies ±1.0% 31 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Three-phase transformer inrush and motor start-up current detector Inrush3, 3I2f> Ratio I2f/I1f> Start current Operation mode 5…50% 0.10…5.00 x In Not in use Inrush mode Start-up mode Note! The values below apply when f/fn = 0.95...1.05 Operation accuracy: - current measurement - ratio I2f/I1f measurement Start time: - internal time - total time ±2.5% of set value or ±0.01 x In ±5.0% of set value <32 ms <40 ms Fuse failure supervision, FuseFail, FUSEF Ratio U2/U1> Ratio I2/I1< 10...50% 10...50% Operation accuracy: - when f/fn = 0.98...1.02: - when f/fn = 0.95...1.05: - injected negative-sequence voltage BSOUT activation time: - f/fn=0.98...1.02 Reset time Reset ratio: - for Ratio U2/U1> - for Ratio I2/I1< ±2.0 percentage units (of settings Ratio U2/U1> and Ratio I2/I1<) ±4.0 percentage units (of settings Ratio U2/U1> and Ratio I2/I1<) = 2.00 x Ratio U2/U1> < 35 ms (within the same task and when the task interval is 10 ms) 20 ms (within the same task) 0.8...0.96 1.04...1.2 Table 8: Energizing inputs Rated frequency Current inputs 50.0/60.0 Hz rated current 1 A/5 A thermal withstand capability Voltage inputs continuously 4 A/20 A for 1 s 100 A/500 A dynamic current withstand, half-wave value 250 A/1250 A input impedance <100 mΩ/<20 mΩ rated voltage (parameterization) 100 V/110 V/115 V/120 V voltage withstand, continuously 2 x Un (240 V) burden at rated voltage <0.5 VA Table 9: Auxiliary power supplies Type PS1/240V (RET 541, RET 543) PS2/240V (RET 545 only) Input voltage, ac 110/120/220/240 V - Input voltage, dc 110/125/220 V 24/48/60 V Voltage variation ac 85…110%, dc 80…120% of rated value dc 80…120% of rated value Burden <50 W Ripple in dc auxiliary voltage max. 12% of the dc value Interruption time in auxiliary dc <40 ms, 110 V and voltage without resetting <100 ms, 200 V Internal overtemperature indication 32 +78°C (+75…+83°C) External display module PS1/48V (RET 541, RET 543) PS2/48V (RET 545 only) <60 ms, 48 V and <100 ms, 60 V Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 10: Digital inputs Power supply version PS1/240 V (High) PS1/240 V (Medium), PS2/240 V PS1/48 V (Low), PS2/48V Input voltage, dc 220 V 110/125/220 V 24/48/60/110/125/ 220 V Nominal treshold voltage, dc - operating range, dc 155 V 155…265 V 80 V 80...265 V 18 V 18...265 V Current drain ~2…25 mA Power consumption/input <0.8 W Pulse counting (specific digital inputs), 0…100 Hz frequency range Time synchronization (specific digital inputs) synchronization rate once per minute or once per second Table 11: RTD/analog inputs Supported RTD sensors 100 Ω Platinum TCR 0.00385 (DIN 43760) 250 Ω Platinum TCR 0.00385 1000 Ω Platinum TCR 0.00385 100 Ω Nickel TCR 0.00618 (DIN 43760) 120 Ω Nickel TCR 0.00618 250 Ω Nickel TCR 0.00618 1000 Ω Nickel TCR 0.00618 10 Ω Copper TCR 0.00427 120 Ω Nickel TCR 0.00672 (MIL-T-24388C) Max lead resistance 200 Ω per lead (three-wire measurement) Accuracy ±0.5% of full scale ±1.0% of full scale for 10 Ω Copper RTD Isolation 2 kV (inputs to outputs and inputs to protective earth) Sampling frequency 5 Hz Response time ≤ Filter time + 30 ms (430 ms...5.03 s) RTD/ Resistance sensing max 4.2 mA RMS current 6.2 mA RMS for 10 Ω Copper Current input impedance 274 Ω ±0.1% Table 12: Analog outputs Output range 0...20 mA Accuracy ±0.5% of full scale Max load 600 Ω Isolation 2 kV (output to output, output to inputs and output to protective earth) Response time ≤ 85 ms Table 13: Signal outputs Max system voltage 250 V ac/dc Continuous carry 5A Make and carry for 0.5 s 10 A Make and carry for 3 s 8A Breaking capacity when control circuit time-constant 1 A/0.25 A/0.15 A L/R <40 ms, at 48/110/220 V dc 33 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 14: Power outputs Max system voltage 250 V ac/dc Continuous carry 5A Make and carry for 0.5 s 30 A Make and carry for 3 s 15 A Breaking capacity when control circuit time constant 5 A/3 A/1 A L/R <40 ms, at 48/110/220 V dc Minimum contact load TCS (Trip Circuit Supervision) 100 mA, 24 V ac/dc (2.4 VA) Control voltage range 20…265 V ac/dc Current drain through the approx. 1.5 mA (0.99…1.72 mA) supervision circuit Minimum voltage 20 V ac/dc (15…20 V) (threshold) over a contact Table 15: Environmental conditions Specified service temperature range -10…+55°C Transport and storage temperature range -40…+70°C Degree of protection by enclosure Front side, flush-mounted IP 54 Rear side, connection terminals IP 20 Dry heat test according to IEC 60068-2-2 Dry cold test according to IEC 60068-2-1 Damp heat test, cyclic according to IEC 60068-2-30 r.h. = 95%, T = 20°…55°C Storage temperature tests according to IEC 60068-2-48 Table 16: Standard tests Insulation tests Mechanical tests Dielectric test IEC 60255-5 Test voltage 2 kV, 50 Hz, 1 min. Impulse voltage test IEC 60255-5 Test voltage 5 kV, unipolar impulses, waveform 1.2/50 µs, source energy 0.5 J Insulation resistance measurements IEC 60255-5 Insulation resistance > 100 MΩ, 500 V dc Vibration tests (sinusoidal) IEC 60255-21-1, class I Shock and bump test IEC 60255-21-2, class I Seismic test IEC 60255-21-3, class 2 Table 17: Electromagnetic compatibility tests The EMC immunity test level fulfills the requirements listed below 34 1 MHz burst disturbance test, class common mode III, IEC 60255-22-1 differential mode 2.5 kV Electrostatic discharge test, class III, IEC 61000-4-2 and IEC 60255-22-2 for contact discharge 6 kV for air discharge 8 kV Radio frequency interference test conducted, common mode IEC 61000-4-6 10 V (rms), f = 150 kHz…80 MHz radiated, amplitude-modulated IEC 61000-4-3 10 V/m (rms), f = 80…1000 MHz radiated, pulse-modulated ENV 50204 10 V/m, f = 900 MHz radiated, test with a portable transmitter IEC 60255-22-3, method C f = 77.2 MHz, P = 6 W; f = 172.25 MHz, P = 5 W 1.0 kV Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 17: Electromagnetic compatibility tests Fast transient disturbance test (IEC 60255-22-4 and IEC 61000-4-4) power supply 4 kV I/O ports 2 kV Surge immunity test (IEC 61000-4-5) power supply 4 kV, common mode 2 kV, differential mode I/O ports 2 kV, common mode 1 kV, differential mode Power frequency (50 Hz) magnetic 100 A/m field, IEC 61000-4-8 Voltage dips and short interruptions, IEC 61000-4-11 30%, 10 ms >90%, 5000 ms Electromagnetic emission tests EN 55011 and EN 50081-2 conducted RF emission (mains terminal) EN 55011, class A radiated RF emission EN 55011, class A CE approval Complies with the EMC directive 89/336/EEC and the LV directive 73/23/EEC Table 18: Data communication Rear interface, connector X3.1 not used, reserved for future purposes Rear interface, connector X3.2 RS-232 connection the fibre-optic interface module RER 123 for SPA and IEC_103 protocol SPA, IEC_103 RS-485 connection the RS-485 interface module RER 133 for DNP 3.0 and Modbus Rear interface, connector X3.3 protocol DNP 3.0, Modbus data transfer rates DNP 3.0 and Modbus: 300 bps...19.2 kbps, selectable RS-485 connection LON bus or SPA bus, selectable the fibre-optic interface module RER 103 is needed for galvanic isolation Rear interface, connector X3.4 data transfer rates SPA bus: 4.8/9.6/19.2 kbps LON bus: 78.0 kbps/1.2 Mbps protocol SPA, LON RJ45 connection galvanically isolated RJ45 connection for an external display module communication cable Front panel 1MRS 120511.001 (1 m) 1MRS 120511.003 (3 m) optical connection protocol SPA serial communication cable 1MRS 120511.001 (1 m) baud rates 4.8/9.6/19.2 kbps start bits 1 data bits 7 parity even stop bits 1 LON protocol bit rates 78.0 kbps/1.2 Mbps IEC_103 protocol baud rates 9.6/19.2 kbps data bits 8 parity even stop bits 1 bit rates 300, 600, 1200, 2400, 4800, 9600, 19200 bps data bits 8 stop bits 1, 2 parity none, odd, even SPA protocol DNP 3.0 35 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 18: Data communication Modbus RTU/ASCII bit rates 300, 600, 1200, 2400, 4800, 9600, 19200 bps data bits 5, 6, 7, 8 stop bits 1, 2 parity none, odd, even Table 19: General Toolboxes CAP 501 CAP 505 LNT 505 Event recording all events are recorded in higher level syntax: reason, time, date the last 100 events are recorded Data recording records operate values Protection functions Control functions Condition monitoring functions Measurement functions see Technical Descriptions of Functions, CD-ROM (1MRS 750889-MCD) Self-supervision RAMs ROMs EEPROMs all analog reference voltages automatic test sequences for I/Os and HMI modules output contact condition monitoring (all contacts) Mechanical dimensions Width: 223.7 mm (1/2 of a 19” rack) Height, frame: 265.9 mm (6U) Height, box: 249.8 mm Depth: 235 mm External display module Weight of the unit 36 ~8 kg Width: 223.7 mm Height: 265.9 mm Depth: 74 mm Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Ordering The following is to be specified when ordering RET 54_ transformer terminals: • Order number (see figure below) • Display language combination (e.g. English-German) • Quantity of transformer terminals Each RET 54_ transformer terminal has a specific order number that identifies the transformer terminal type as well as the hardware and the software as described in the figure below. The order number is printed on the marking strip on the front panel of the transformer terminal delivered, e.g. Order No: RET543AB230AAAA. RET54_AB230AAAA A = fixed display, B = external display module Reserved for future use Reserved for future use Auxiliary voltage range of the power supply module and voltage range of the digital inputs A: power supply: PS1/240 V (Medium) or PS2/240 V Ur = 110/120/220/240 V AC; 110/125/220 V DC digital inputs: Ur = 110/125/220 V DC threshold voltage: Ut = 80 V DC B: power supply: PS1/240 V (High) or PS2/240 V Ur = 110/120/220/240 V AC; 110/125/220 V DC digital inputs: Ur = 220 V DC threshold voltage: Ut = 155 V DC C: power supply: PS1/48 V (Low) or PS2/48 V Ur = 24/48/60 V DC digital inputs: Ur = 24/48/60/110/125/220 V DC Hardware number: 230, 231, 232, 233, 234, 235, 240, 241, 242, 243, 244, 245, 250, 251, 252 Functionality level: C = Control, B = Basic, M = Multi Software revision: A Transformer terminal type: RET 541, RET 543, RET 545 ret54_ordernumber_ Fig. 5 Order number of RET 54_ transformer terminal. Language combinations The display language combination (see table below) is identified by a three-digit suf- fix in the software number labelled on the front panel of the transformer terminal, e.g. Software 1MRS110028-0_. Suffix Language combination 001 English-German 002 English-Swedish 003 English-Finnish 007 English-Portuguese 008 English-Polish 009 English-Russian 010 English-Spanish Number of digital inputs/outputs The RET 541, RET 543 and RET 545 transformer terminals differ from each other as to Number of inputs/outputs Digital inputs Trip circuit supervision inputs Power outputs (NO single-pole) Power outputs (NO double-pole) Signal outputs (NO) Signal outputs (NO/NC) Self-supervision outputs RET 541 15 2 0 5 2 5 1 the number of digital inputs and outputs as follows: RET 543 25 2 2 9 2 5 1 RET 545 34 2 3 11 4 8 1 37 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Functionality levels The functionality level determines the extent of the selection of function blocks available for the transformer terminal. For more detail- ed information on the separate function blocks included in each selection, please consult your relay supplier. Functionality level Selection of function blocks C (Control) All control1, condition monitoring and measurement functions B (Basic) All control1, condition monitoring and measurement functions, basic protection functions M (Multi) All control1, condition monitoring, measurement and protection functions 1) The COLTC Tap Changer control function block comes as standard in the Control version. In the Basic and the Multi versions, COLTC is available as an option. Table 20: Transformer terminal functionality levels 87T 3∆I >, 3∆I >> 51 50 / 51 / 51B 50 / 51B 3I > 3I >> 3I >>> 67 67 67 21G 21G 3I > -> 3I >> -> 3I >>> -> Z< Z<< 51N 50N / 51N 50N 67N / 51N 67N 67N 59N 59N 59N 87N 87N 87N Io > / SEF Io >> Io >>> Io > / SEF -> Io >> -> Io >>> -> Uo > Uo >> Uo >>> ∆ Io > ∆ Io > ∆ Io >, REF 49T 46 46 3 I2 > I2 >> 59 59 27 27 47 47 3U > 3U >> 3U < 3U << U1< & U2> & U1> U1< & U2> & U1> 81U / 81O 81U / 81O 81U / 81O 81U / 81O 81U / 81O 24 24 68 60 62BF f</ f</ f</ f</ f</ f > / df/dt f > / df/dt f > / df/dt f > / df/dt f > / df/dt U/f> U/f>> 3I2f > FUSEF CBFP 3I 3I Io Io 3U 3U Uo Uo E / P / Q / pf f 38 Functions available in RET 541/543/545 Transformer Terminals. Processor capacity to be checked with "CPU load" tool Short circuit and overcurrent Three-phase differential protection for transformers, stabilized and instantaneous stages Three-phase non-directional overcurrent, low-set stage Three-phase non-dir. overcurrent, high-set stage / blockable overcurrent Three-phase non-dir. overcurrent, inst. stage / blockable overcurrent Three-phase non-directional overcurrent function, low-set stage (B) Three-phase directional o/c, low-set stage Three-phase directional o/c, high-set stage / blockable overcurrent Three-phase directional o/c, high-set stage / blockable overcurrent Three-Phase Underimpedance Protection, Low-Set Stage Three-Phase Underimpedance Protection, High-Set Stage Earth-fault Non-directional earth-fault, low-set stage Non-directional earth-fault, high-set stage Non-directional earth-fault, instantaneous stage Directional earth-fault, low-set stage Directional earth-fault, high-set stage Directional earth-fault, instantaneous stage Residual overvoltage, low-set stage Residual overvoltage, high-set stage Residual overvoltage, instantaneous stage Stabilized restricted earth-fault protection (high voltage side) Stabilized restricted earth-fault protection (low voltage side) High-impedance based restricted earth-fault protection Overload / unbalanced load Three-phase thermal overload protection Negative-phase-sequence (NPS) protection, low-set stage Negative phase sequence (NPS) protection, high-set stage Over / undervoltage Three-phase overvoltage, low-set stage Three-phase overvoltage, high-set stage Three-phase undervoltage, low-set stage Three-phase undervoltage, high-set stage Three-phase phase sequency voltage protection, stage 1 Three-phase phase sequency voltage protection, stage 2 Over/under frequency Underfrequency or overfrequency inc. rate of change, stage 1 Underfrequency or overfrequency inc. rate of change, stage 2 Underfrequency or overfrequency inc. rate of change, stage 3 Underfrequency or overfrequency inc. rate of change, stage 4 Underfrequency or overfrequency inc. rate of change, stage 5 Over / under excitation Overexcitation Protection, Low-Set Stage U/f> Overexcitation Protection, High-Set Stage U/f>> Additional functions Three-phase inrush detector Fuse failure supervision Circuit breaker failure Measurement function Current Three-phase current Three-phase current, B -stage Neutral current Neutral current, B -stage Voltage Three-phase voltage Three-phase voltage, B -stage Residual voltage Residual voltage, B -stage Energy / Power Three-phase power and energy (incl. cos ϕ) Frequency System frequency Recording Transient disturbance recorder In versions with RTD1 -card Measurement of RTD/analog -inputs, general measurement Control of analog -outputs Code Diff6T NOC3Low NOC3High NOC3Inst NOC3LowB DOC6Low DOC6High DOC6Inst UI6Low UI6High REF541/3/5 MULTI IEC Symbol RET541/3/5 BASIC IEEE Code RET541/3/5 CONTROL FUNCTIONALITY LEVELS X X X X X X NEF1Low NEF1High NEF1Inst DEF2Low DEF2High DEF2Inst ROV1Low ROV1High ROV1Inst REF4A REF4B REF1A X X X TOL3Dev NPS3Low NPS3High X X X X X X OV3Low OV3High UV3Low UV3High PSV3St1 PSV3St2 X X X Freq1St1 Freq1St2 Freq1St3 Freq1St4 Freq1St5 X OE1Low OE1High X Inrush3 FuseFail - MECU3A MECU3B MECU1A MECU1B MEVO3A MEVO3B MEVO1A MEVO1B X X X X X X X X X X X X MEPE7 X X X MEFR1 X X X MEDREC16 X X X MEAI1…8 MEAO1…4 X X X Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Transformer Terminals functionality levels, cont. IEEE Code IEC Symbol CBCM CBCM CBCM CBCM CBCM CBCM CBCM CBCM CBCM TCS TCS MCS MCS Condition monitoring function Circuit breaker CB electric wear 1 CB electric wear 2 Operation Time Counter 1 (e.g. motors) Operation Time Counter 2 (e.g. motors) Gas density supervision Gas density supervision for three poles Spring charging control 1 Breaker travel time 1 Scheduled maintenance Trip circuit Trip Circuit Supervision 1 Trip Circuit Supervision 2 Measuring circuit Supervision of the energizing current input circuit Supervision of the energizing voltage input circuit Control function Circuit breakers, disconnectors / earthing switch Circuit breaker 1, 2 (2 state inputs / 2 control outputs) Disconnector 1….5 (2 state inputs / 2 control outputs) Three state disconnector 1, 2 (3 state inputs / 4 control outputs) Object indication 1…8 (2 state inputs) MIMIC dynamic data point 1…5 on MMI (single line diagram) Alarm 1…8 on MMI (alarm view) On/off switch 1…4 on MMI (single line diagram) Direct open for CBs via MMI Logic control position selector Additional functions Interlocking Command control Standard functions Operation indication, relay and register reset Activation of MMI backlight Switchgroups SWGRP1...SWGRP20 PLC logics (AND, OR, timers etc.) acc. to IEC 1131-3 Data communication Event to be defined by the customer, E0...E63 SPA bus LON bus General functions Main / secondary setting Remote setting Selfsupervision Annunciating, event generating and value recording Measurement, parameter and switching device status display Remote-end binary signal transfer Binary signal interbay transfer Code CMBWEAR1 CMBWEAR2 CMTIME1 CMTIME2 CMGAS1 CMGAS3 CMSPRC1 CMTRAV1 CMSCHED X X X CMTCS1 CMTCS2 X X X CMCU3 CMVO3 X X X X X X X X X X X X X X X X X X COCB1...2 CODC1…5 CO3DC1...2 COIND1…8 MMIDATA1…5 MMIALAR1…8 COSW1…4 COCBDIR COLOCAT INDRESET MMIWAKE SWGRP1....20 EVENT230 - Options Dual HMI language, desired language combination must be stated in the purchase order On-load tap changer controller (voltage regulator), to be ordered as a COLTC separate item (1MRS 100144) O O O X O O RET54_ Functionality2.xls Hardware versions of RET 541, RET 543 and RET 545 For the number of digital inputs and outputs of RET 54_ transformer terminals, refer to section “Order number” above. The number of matching transformers and analog inputs and outputs, and the auxiliary voltage range vary between the different hardware versions of RET 54_. Moreover, RET 541 and RET 543 can be supplied with an RTD/analog module. For more detailed information about the hardware of RET 54_, refer to the tables 20...28 below. 39 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 21: Hardware versions of RET 541, 6I/3U transformers RET541A_230BAAA RET541A_230CAAA RET541A_230AAAB RET541A_230BAAB RET541A_233AAAA RET541A_233BAAA RET541A_233CAAA RET541A_233AAAB RET541A_233BAAB Order number RET541A_230AAAA HW modules 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 1 1 1 1 1 1 1 1 1 1 Analog interface Current rafo 1/5 A Voltage trafo 100 V Main processor boards CPU module Power supply boards 1 PS1: 80...265 VDC/AC (High) PS1: 80...265 VDC /AC (Medium) 1 1 1 1 1 1 1 PS1: 18...80 VDC/AC (Low) 1 1 PS2: 80...265 VDC PS2: 18...80 VDC Digital I/O boards 1 BIO1:Threshold voltage 155 VDC BIO1: threshold voltage 80 VDC 1 1 1 1 1 1 BIO1: threshold voltage 18 VDC 1 1 1 BIO2: Threshold voltage 155 VDC BIO2: threshold voltage 80 VDC BIO2: threshold voltage 18 VDC Analog I/O board RTD/analog module 1 1 1 1 1 1 1 1 Display boards Graphic HMI display, fixed 1 1 1 Graphic HMI display, external 1 1 1 1 1 1 1 1 Mechanic 1/2 enclosure 1 1 1 1 1 15 15 Power outputs, single pole 0 0 Power outputs, double pole 5 5 Signal outputs (NO) 2 2 Signal outputs (NO/NC) 5 5 Supervised trip circuits 2 2 IRF outputs 1 1 RTD/analog inputs 0 8 Analog outputs 0 4 Digital inputs 40 1 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 22: Hardware versions of RET 541, 7I/2U transformers RET541A_231BAAA RET541A_231CAAA RET541A_231AAAB RET541A_231BAAB RET541A_234AAAA RET541A_234BAAA RET541A_234CAAA RET541A_234AAAB RET541A_234BAAB Order number RET541A_231AAAA HW modules 7 2 7 2 7 2 7 2 7 2 7 2 7 7 7 7 2 2 2 2 1 1 1 1 1 1 1 1 1 1 Analog interface Current trafo 1/5 A Voltage trafo 100 V Main processor boards CPU module Power supply boards 1 PS1: 80...265 VDC/AC (High) PS1: 80...265 VDC /AC (Medium) 1 1 1 1 1 1 1 PS1: 18...80 VDC/AC (Low) 1 1 PS2: 80...265 VDC PS2: 18...80 VDC Digital I/O boards 1 BIO1:threshold voltage 155 VDC BIO1: threshold voltage 80 VDC 1 1 1 1 1 1 BIO1: threshold voltage 18 VDC 1 1 1 BIO2: threshold voltage 155 VDC BIO2: threshold voltage 80 VDC BIO2: threshold voltage 18 VDC Analog I/O board RTD/analog module 1 1 1 1 1 1 1 1 1 1 1 1 Display boards Graphic HMI display, fixed 1 1 1 Graphic HMI display, external 1 1 1 1 Mechanic 1/2 enclosure 1 1 1 1 1 1 15 15 Power outputs, single pole 0 0 Power outputs, double pole 5 5 Signal outputs (NO) 2 2 Signal outputs (NO/NC) 5 5 Supervised trip circuits 2 2 IRF outputs 1 1 RTD/analog inputs 0 8 Analog outputs 0 4 Digital inputs 41 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 23: Hardware versions of RET 541, 8I/1U transformers RET541A_232BAAA RET541A_232CAAA RET541A_232AAAB RET541A_232BAAB RET541A_235AAAA RET541A_235BAAA RET541A_235CAAA RET541A_235AAAB RET541A_235BAAB Order number RET541A_232AAAA HW modules 8 1 8 1 8 1 8 1 8 1 8 1 8 1 8 1 8 1 8 1 1 1 1 1 1 1 1 1 1 1 Analog interface Current rafo 1/5 A Voltage trafo 100 V Main processor boards CPU module Power supply boards 1 PS1: 80...265 VDC/AC (High) PS1: 80...265 VDC /AC (Medium) 1 1 1 1 1 1 1 PS1: 18...80 VDC/AC (Low) 1 1 PS2: 80...265 VDC PS2: 18...80 VDC Digital I/O boards 1 BIO1: threshold voltage 155 VDC BIO1: threshold voltage 80 VDC 1 1 1 1 1 1 BIO1: threshold voltage 18 VDC 1 1 1 BIO2: threshold voltage 155 VDC BIO2: threshold voltage 80 VDC BIO2: threshold voltage 18 VDC Analog I/O board RTD/analog module 1 1 1 1 1 1 1 1 1 1 1 1 Display boards Graphic HMI display, fixed 1 1 1 Graphic HMI display, external 1 1 1 1 Mechanic 1/2 enclosure 1 1 1 1 1 15 15 Power outputs, single pole 0 0 Power outputs, double pole 5 5 Signal outputs (NO) 2 2 Signal outputs (NO/NC) 5 5 Supervised trip circuits 2 2 IRF outputs 1 1 RTD/analog inputs 0 8 Analog outputs 0 4 Digital inputs 42 1 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 24: Hardware versions of RET 543, 6I/3U transformers RET543A_240BAAA RET543A_240CAAA RET543A_240AAAB RET543A_240BAAB RET543A_243AAAA RET543A_243BAAA RET543A_243CAAA RET543A_243AAAB RET543A_243BAAB Order number RET543A_240AAAA HW modules 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 1 1 1 1 1 1 1 1 1 1 Analog interface Current trafo 1/5 A Voltage trafo 100 V Main processor boards CPU module Power supply boards 1 PS1: 80...265 VDC/AC (High) PS1: 80...265 VDC/AC (Medium) 1 1 1 1 1 1 PS1: 18...80 VDC/AC (Low) 1 1 1 PS2: 80...265 VDC PS2: 18...80 VDC Digital I/O boards 1 BIO1: threshold voltage 155 VDC BIO1: threshold voltage 80 VDC 1 1 1 1 1 BIO2: threshold voltage 155 VDC 1 1 1 1 1 1 1 1 BIO2: threshold voltage 18 VDC 1 1 1 BIO1: threshold voltage 18 VDC BIO2: threshold voltage 80 VDC 1 1 1 Analog I/O board RTD/analog module 1 1 1 1 1 1 1 1 1 1 1 1 Display boards Graphic HMI display, fixed 1 1 1 Graphic HMI display external 1 1 1 1 Mechanic 1/2 enclosure 1 1 1 1 1 1 25 25 Power outputs, single pole 2 2 Power outputs, double pole 9 9 Signal outputs (NO) 2 2 Signal outputs (NO/NC) 5 5 Supervised trip circuits 2 2 IRF outputs 1 1 RTD/analog inputs 0 8 Analog outputs 0 4 Digital inputs 43 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 25: Hardware versions of RET 543, 7I/2U transformers RET543A_241BAAA RET543A_241CAAA RET543A_241AAAB RET543A_241BAAB RET543A_244AAAA RET543A_244BAAA RET543A_244CAAA RET543A_244AAAB RET543A_244BAAB Order number RET543A_241AAAA HW modules 7 2 7 2 7 2 7 2 7 2 7 2 7 2 7 2 7 2 7 2 1 1 1 1 1 1 1 1 1 1 Analog interface Current trafo 1/5 A Voltage trafo 100 V Main processor boards CPU module Power supply boards 1 PS1: 80...265 VDC/AC (High) PS1: 80...265 VDC/AC (Medium) 1 1 1 1 1 1 1 PS1: 18...80 VDC/AC (Low) 1 1 PS2: 80...265 VDC PS2: 18...80 VDC Digital I/O boards 1 BIO1: threshold voltage 155 VDC BIO1: threshold voltage 80 VDC 1 1 1 1 1 BIO2: threshold voltage 155 VDC 1 1 1 1 1 1 1 1 BIO2: threshold voltage 18 VDC 1 1 1 BIO1: threshold voltage 18 VDC BIO2: threshold voltage 80 VDC 1 1 1 Analog I/O board RTD/analog module 1 1 1 1 1 1 1 1 1 1 1 1 Display boards Graphic HMI display, fixed 1 1 1 Graphic HMI display, external 1 1 1 1 Mechanic 1/2 enclosure 1 1 1 1 1 25 25 Power outputs, single pole 2 2 Power outputs, double pole 9 9 Signal outputs (NO) 2 2 Signal outputs (NO/NC) 5 5 Supervised trip circuits 2 2 IRF outputs 1 1 RTD/analog inputs 0 8 Analog outputs 0 4 Digital inputs 44 1 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 26: Hardware versions of RET 543, 8I/1U transformers RET543A_242BAAA RET543A_242CAAA RET543A_242AAAB RET543A_242BAAB RET543A_245AAAA RET543A_245BAAA RET543A_245CAAA RET543A_245AAAB RET543A_245BAAB Order number RET543A_242AAAA HW modules 8 1 8 1 8 1 8 1 8 1 8 1 8 1 8 1 8 8 1 1 1 1 1 1 1 1 1 1 1 1 Analog interface Current trafo 1/5 A Voltage trafo 100 V Main processor boards CPU module Power supply boards 1 PS1: 80...265 VDC/AC (High) PS1: 80...265 VDC/AC (Medium) 1 1 1 1 1 1 1 PS1: 18...80 VDC/AC (Low) 1 1 PS2: 80...265 VDC PS2: 18...80 VDC Digital I/O boards 1 BIO1: threshold voltage 155 VDC BIO1: threshold voltage 80 VDC 1 1 1 1 1 BIO2: threshold voltage 155 VDC 1 1 1 1 1 1 1 1 BIO2: threshold voltage 18 VDC 1 1 1 BIO1: threshold voltage 18 VDC BIO2: threshold voltage 80 VDC 1 1 1 Analog I/O board RTD/analog module 1 1 1 1 1 1 1 1 1 1 1 1 Display boards Graphic HMI display, fixed 1 1 1 Graphic HMI display external 1 1 1 1 Mechanic 1/2 enclosure 1 1 1 1 1 1 25 25 Power outputs, single pole 2 2 Power outputs, double pole 9 9 Signal outputs (NO) 2 2 Signal outputs (NO/NC) 5 5 Supervised trip circuits 2 2 IRF outputs 1 1 RTD/analog inputs 0 8 Analog outputs 0 4 Digital inputs 45 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 27: Hardware versions of RET 545, 6I/3U transformers RET545A_250BAAA RET545A_250CAAA RET545A_250AAAB RET545A_250BAAB Order number RET545A_250AAAA HW modules 6 3 6 3 6 3 6 3 6 3 1 1 1 1 1 1 1 1 1 Analog interface Current trafo 1/5 A Voltage trafo 100 V Main processor boards CPU module Power supply boards PS1: 80...265 VDC/AC (High) PS1: 80...265 VDC/AC (Medium) PS1: 18...80 VDC/AC (Low) PS2: 80...265 VDC 1 PS2: 18...80 VDC Digital I/O boards 2 BIO1: threshold voltage 155 VDC BIO1: threshold voltage 80 VDC 2 2 BIO1: threshold voltage 18 VDC 1 BIO2: threshold voltage 155 VDC BIO2: threshold voltage 80 VDC 2 2 1 1 1 1 BIO2: threshold voltage 18 VDC Analog I/O board RTD/analog module Display boards Graphic HMI display, fixed 1 1 1 Graphic HMI display, external 1 1 1 1 Mechanic 1/2 enclosure Digital inputs 46 1 1 1 34 Power outputs, single pole 3 Power outputs, double pole 11 Signal outputs (NO) 4 Signal outputs (NO/NC) 8 Supervised trip circuits 2 IRF outputs 1 RTD/analog inputs 0 Analog outputs 0 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 28: Hardware versions of RET 545, 7I/2U transformers RET545A_251BAAA RET545A_251CAAA RET545A_251AAAB RET545A_251BAAB Order number RET545A_251AAAA HW modules 7 2 7 2 7 2 7 2 7 2 1 1 1 1 1 1 1 1 1 Analog interface Current trafo 1/5 A Voltage trafo 100 V Main processor boards CPU module Power supply boards PS1: 80...265 VDC/AC (High) PS1: 80...265 VDC/AC (Medium) PS1: 18...80 VDC/AC (Low) PS2: 80...265 VDC 1 PS2: 18...80 VDC Digital I/O boards 2 BIO1: threshold voltage 155 VDC BIO1: threshold voltage 80 VDC 2 2 BIO1: threshold voltage 18 VDC 1 BIO2: threshold voltage 155 VDC BIO2: threshold voltage 80 VDC 2 2 1 1 1 1 BIO2: threshold voltage 18 VDC Analog I/O board RTD/analog module Display boards Graphic HMI display, fixed 1 1 1 Graphic HMI display, external 1 1 1 1 Mechanic 1/2 enclosure Digital inputs 1 1 1 34 Power outputs, single pole 3 Power outputs, double pole 11 Signal outputs (NO) 4 Signal outputs (NO/NC) 8 Supervised trip circuits 2 IRF outputs 1 RTD/analog inputs 0 Analog outputs 0 47 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 29: Hardware versions of RET 545, 8I/1U transformers RET545A_252BAAA RET545A_252CAAA RET545A_252AAAB RET545A_252BAAB Order number RET545A_252AAAA HW modules 8 1 8 1 8 1 8 1 8 1 1 1 1 1 1 1 1 1 1 Analog interface Current trafo 1/5 A Voltage trafo 100 V Main processor boards CPU module Power supply boards PS1: 80...265 VDC/AC (High) PS1: 80...265 VDC/AC (Medium) PS1: 18...80 VDC/AC (Low) PS2: 80...265 VDC 1 PS2: 18...80 VDC Digital I/O boards 2 BIO1: threshold voltage 155 VDC BIO1: threshold voltage 80 VDC 2 2 BIO1: threshold voltage 18 VDC 1 BIO2: threshold voltage 155 VDC BIO2: threshold voltage 80 VDC 2 2 1 1 1 1 BIO2: threshold voltage 18 VDC Analog I/O board RTD/analog module Display boards Graphic HMI display, fixed 1 1 1 Graphic HMI display, external 1 1 1 1 Mechanic 1/2 enclosure Digital inputs 48 1 1 1 34 Power outputs, single pole 3 Power outputs, double pole 11 Signal outputs (NO) 4 Signal outputs (NO/NC) 8 Supervised trip circuits 2 IRF outputs 1 RTD/analog inputs 0 Analog outputs 0 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Software configuration Each RET 54_ transformer terminal allows various software configurations based on separate functions. Functions included in the selected functionality level can be activated within the scope of the I/O connections and considering the total CPU load of the functions. Parts and assembly descriptions To achieve the best possible operation accuracy, all parts of a RET 54_ product have been calibrated together. Thus, each product forms a whole for which no separate spare parts can be supplied. In the event of malfunction, please consult your transformer terminal supplier. 49 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 RET/1U Application examples MF RET/4I Q p> 3DI> 87TG 3I> HV 51 50 3 HV 49T 3I> LV 51 50 I2> 46 I0> HV 51N 50N 3I2f> 68 CBFP 62BF LV RET/RTD Q RET 54_ RET/1U 3I> 51 50 CBFP 62BF REF/3I, REA 101/3I RET/31 CBFP 62BF HV 3U> 59 3U< 27 U0> 59N 000 000 U 3I Io Q P 3I U TO Tw R TCS CBCM 000 3I> & 3I R 3U Q P TCS REA 101 E MF REF/3U REF/1U REF 54_ Yd transformer Fig. 6 50 Protection, control and supervision functions of a Yd-connected power transformer, implemented with RET 543 transformer terminal, REF543 feeder terminal and REA 101 arc protection. Position indication of the on-load tap changer is used to increase the sensitivity of the differential function of the transformer. In this example, the voltage controller is not included in the RET 543 transformer terminal. Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 MF RET/3I REF/4I p> Q RET/1I REF/1I Q RET/RTD 3DI> 87T 3I> HV 51 50 DI0> LV 87TN 3I> LV 51 50 3 49T I 0> HV 51N 50N I2> HV 46 I0> LV 51N 50N 3I2f > HV 68 CBFP 62BF HV I0 3I U 3I R I0 o o TO Tw TCS U U CBFP 62BF LV RET 54_ 000 000 3I> 51 50 I0> 51N 50N LO 86 3I I0 000 R TCS CBFP 62BF REF 610 90 RET/1U REF/3U REF/3I 3I> 51 50 3U> 59 I0> 51N 50N 3U< 27 RET/3I CBFP 62BF 000 3I I0 R 3U P Q TCS REF 54_ MF Dyn-trafo_impEarthedLVn Fig. 7 Protection, control, measurement and supervision functions of an Dyn-connected power transformer, implemented with RET 543 transformer terminal and an REF 543 feeder terminal. The neutral point of the low-voltage network is earthed via a high impedance. REF 610 is used as a backup relay on the high-voltage side. This sceme can be applied also for parallel connected transformers. 51 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 M REF/3U REF/3U M MF 3I> 51 50 3U> 59 3I 2f > 68 3U< 27 I 0> 51N 50N RET/3I 000 I0 3I R 3U TCS CBFP 62BF REF/3I REF 54_ M RET/1I REF/1I M M Θ Θ P> M M RET/1U REF/1I 3I> HV 51 50 ∆I0> HV 87TN 3I> LV 51 50 3I I0 ∆I0> LV 87TN I 0> HV 51N 50N 3I U 3 49T I 0> LV 51N 50N 3I 2f > HV 68 RET/3I R I0 TO Tw CBFP 62BF LV 67 3U> 59 I 0> 51N 50N 3U< 27 CBFP 62BF f> 81O df/dt 81O-R TCS U CBFP 62BF HV 3I> REF,REA/3I RET/1I 000 87T RET 54_ M 000 3∆I> U 90 000 3I> & 3I I0 3U pf Q P 3I-harm R TCS REA 101 f REF/3U REF/3U 3U-harm REF 54_ MF M E M YNd transformer with earthing transformer on LV side Fig. 8 52 Protection, control, measurement and supervision functions of a YNd-connected power transformer, implemented with an RET 543 transformer terminal, REF 543 feeder terminals and REA 101 arc protection. The low-voltage network is earthed via a zig-zag earthing transformer. Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 MF REF/3U M REF/3U M 3I> 51 50 3U> 59 3I 2f > 68 3U< 27 I0> 51N 50N RET/3I REF/3I 000 3I I0 R 3U TCS CBFP 62BF REF 54_ M Θ REF/1I P> Θ M RET/RTD 3I> HV 51 50 ∆I0 > 87TN HV 3I> LV 51 50 3I I0 ∆I0> LV 87TN I0> HV 51N 50N 3I U 3 49T I0> LV 51N 50N 3I 2f > HV 68 R I0 REF/1I RET/1I TO Tw REF/3U RET/1U 3I> 67 3U> 59 I0> 51N 50N 3U< 27 TCS U CBFP 62BF LV CBFP 62BF HV RET 54_ REF, REA/3I 000 000 3∆I > 87T RET/1I U 90 000 3I> & RET/3I MF CBFP 62BF REF 54_ f> 81O df/dt 81O-R 3I I0 3U pf R TCS f REA 101 CBCM E MCS YNyn transformers impedance earthed LV neutral Fig. 9 Protection, control, measurement and supervision functions of YNyn-connected power transformers, implemented with RET 543 transformer terminals, REF 543 feeder terminals and REA 101 arc protection. The neutral point of the low-voltage network is earthed via a low resistance. The scheme is also applicable to other types of low-impedance earthed networks, where the neutral point is earthed effectively or via a low reactance. This sceme can be applied also for parallel connected transformers. 53 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 3U< 27 3U> 59 U0 > 59N 3U U0 000 RET/2U (Multi) REX/3U REX/1U M MF CBCM R TCS RET/4I (Basic) MCS RET/3I (Multi) REX 521 H06 M M Q p> M Q RET/1I (Basic) REF/1I 81O 81O-R f< df/dt 81U 81U-R U/f> 24 CBFP 62BF HV Z< 21 CBFP 62BF LV U< 27 I0> HV 51N 50N 3I I0 DI0 > LV 87TN I0> LV 51N 50N 3I I0 3I> HV 51 50 3 49T 3I> LV 51 50 3I2f > HV 68 000 R TCS REF/3I, REA 101/3I R U f TO TTC U U RET 54_ (Multi) 3I> 51 50 3U> 59 I0> 51N 50N 3U< 27 CBFP 62BF U0> 59N 000 3I 3U 3I> & I0 R TCS REA 101 REF/3U RET/3I (Basic) 000 000 T RET 54_ (Basic) RET/1U (Multi) MF f> df/dt 3DI > 87TG REF 54_ Yyn-trafo_highresEarthedLV Fig. 10 54 Protection, control, measurement and supervision functions of an Yyn-connected industrial power transformer, implemented with RET 543 transformer terminals, an REF 543 feeder terminal, an REX 521 protection relay and REA 101 arc protection. The neutral point of the low-voltage network is earthed via a high resistance. Transformer Terminal RET 541, RET 543, RET 545 MF REX521/1U REX521/3U 1MRS755543 RET_/3I 3DI> 87TG 3I> HV 51 50 DI0> LV 87TN 3I> LV 51 50 3I I0 3 49T I0> HV 51N 50N 3I U I0> LV 51N 50N I2> HV 46 CBFP 62BF HV RET_/1I 000 R TCS I0 o Q P> REM_/3I REM_/3U REM_/1U G 3~ REM/RTD REM_/3I RET_/3I 27 3U> 59 U0> 59N f> 81U o TO Tw 3U U0 000 f CBCM R TCS MCS REX 521 H06 RET 54_ Q 3U< 000 3DI> 87G X< 40 3I> 51 50 P> 32 3I P I(U)> 51V I2> 46 Q U I0> 50N 51N 3 49G U0 pf TCS o MCS 3U> 59 3U< 27 U 0> 59N T f F 60 Q> 49 38 R E CBFP 62BF REM 54_ gener_blockconn-trafo1 Fig. 11 Transformer in block connection with a generator. The transformer terminal RET 543 is used for overall differential protection. An earthing resistor is recommended for the generator. The REX 521 protection relay is used for abnormal voltage and frequency supervision and protection of the network and the machine. 55 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 3DI> 87TG MF RET_/3I RET_/1U RET_/1U 51 3I> HV 50 000 DI0 > LV 87TN 3I> LV 51 50 3I 3 49T I0> HV 51N 50N 3I 46 I0> LV 51N 50N U> 59N I2> HV RET_/1I I0 R U TCS I0 o o TO Tw CBFP 62BF RET 54_ Q Q P> REM_/3I (A) REM_/3I (B) REM_/2U(A)/3U(B) REM_/1U (A) 3DI> 87G f>/f< 81O 81U Ios> 64S X< 40 P> 32 I> 2 46 CBFP 62BF 000 3I P Q U f pf R TCS MCS E G 3~ REM_/3I (A) RET_/3I REK 510 REM/I0R (B) REM_/1I (A) REM 54_ (A) 3I> 51 50 P> 32 Z< 21G 3 49G 3I P U/f> 24 F 60 Q 3U IOR > 64R 3U> 59 U0 pf 3U< 27 CBFP 62BF U0 > 59N 000 R TCS MCS f E REM 54_ (B) gen_blockconn-trafo2 Fig. 12 56 Transformer in block connection with a generator. The transformer terminal RET 543 is used for overall differential protection. An earthing resistor is recommended for the generator. Generator protection functions are divided for two REM 543 machine terminals (A and B). The current injection device REK 510 is used in the rotor earth-fault protection scheme. Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 3I > 3I> I0> 50/51 67 = multiple-stage three-phase overcurrent protection, double low-set, high-set and instantaneous stages available (NOC3_) = multiple-stage three-phase directional overcurrent protection, low-set, high-set and instantaneous stage available (DOC6_) 50N/51N = multiple-stage earth-fault protection, low-set, high-set and instantaneous stage available (NEF1_) I2 > 46 = negative phase sequence (NPS) protection, low-set and high-set stages available (NPS3_) 3I2f > 68 = inrush detection based on the 2nd harmonic content of phase currents, applied for preventing possible unnecessary operation of overcurrent or earth-fault protection during transformer switching-in or to start cold load pick-up logic (Inrush3_) 3D I > 87T 3D I > 87TG = overall differential protection for generator and transformer blocks, stabilized and instantaneous stages (Diff6T) DI0> 87TN = restricted earth-fault (REF) protection, low- or high-impedance type (Diff3) I(U)> 51V = voltage-dependent overcurrent protection, low-set and high-set stages available (VOC6_) I 0S> 64S = stator earth-fault protection (NEF1_) I 0R> 64R = rotor earth-fault protection (NEF1_) U/f 24 = overexcitation protection, low-set and high-set stages available (OE1_) U< 27 = undervoltage protection, low-set and high-set stage available (UV3_) 3U < 27 = three-phase undervoltage protection, low-set and high-set stage available (UV3_) 3U > 59 = three-phase overvoltage protection, low-set and high-set stage available (OV3_) U0> 59N = multiple-stage residual overvoltage protection, low-set, high-set and instantaneous stage available (ROV1_) f> 81U = overfrequency protection (incl. in Freq1St_) f> df/dt 81U = overfrequency protection and frequency rate of change function (incl. in Freq1St_) 81U-R f< df/dt 81O = underfrequency protection and frequency rate of change function (incl. in Freq1St_) 81O-R f>/f< 81O 81U = over/underfrequency protection (incl. in Freq1St_) 3 49G = three-phase thermal overload protection for generator (TOL3Dev) 3 49T = three-phase thermal overload protection for transformers (TOL3Dev) Q> 49 38 = thermal supervision for generator windings and bearings with RTDs (MEAI_) 62BF = circuit-breaker failure protection (included in all current-based short circuit and earth-fault protection function blocks) CBFP = three phase differential protection for transformers, stabilized and instantaneous stages (Diff3) SYMNOT1_RET Fig. 13 Symbol notations, part I 57 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Z< 21G = underimpedance protection for generator, low-set and high-set stages (UI6_) 3Z< 21 = three-phase underimpedance protection, low-set and high-set stages (UI6_) X< 40 = underexcitation protection, low-set and high-set stages (UE6_) P> 32 F = underpower, low-forward power or reverse power protection, stages 1, 2 and 3 available (UPOW6St_) 60 = fuse failure supervision (FuseFail) 3I > & = arc protection with REA 101 MCS = measuring circuit supervision TCS = trip circuit supervision CBCM U U = circuit-breaker condition monitoring 90V = automatic voltage regulation (COLTC) = manual voltage regulation (COLTC) P = active power measurement, indication and supervision Q = reactive power measurement, indication and supervision 3I = 3-phase current measurement, indication and supervision 3U = 3-phase voltage or phase-to-phase voltage measurement, indication and supervision f = frequency measurement, indication and supervision pf = power factor measurement, indication and supervision I0 = residual current measurement, indication and supervision U0 = residual voltage measurement, indication and supervision SYMNOT2_RET Fig. 14 58 Symbol notations, part II Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 U = phase voltage or phase-to-phase voltage measurement, indication and supervision oT = oil temperature measurement, indication and supervision o oT W = transformer winding temperature measurement, indication and supervision oT TC = tap changer temperature measurement, indication and supervision oT = ambient temperature measurement, indication and supervision = energy counter, forward or reverse active / reactive energy (MEPE7) E 3I-harm = current waveform distortion measurement (PQCU3H) 3U-harm = voltage waveform distortion measurement (PQVU3H) = annunciating, event generating and value recording functions R = disturbance recorder (MEDREC16) 000 = digital value indication 000 = HMI/MIMIC display 000 = tap changer position display 0 I = local and remote control interface = bay-oriented interlocking logic SYMNOT3_RET Fig. 15 Symbol notations, part III 59 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Application selection tables for RET 541, RET 543 and RET 545 functions Table 30: Protection functions Types of fault IEEE Device No. IEC Symbol Protection function Function block code Differential protection 87T 3∆I>, 3∆I>> Stabilized and instantaneous differential protection for transformers Diff6T Short circuit and overcurrent 51 3I> Three-phase nondirectional overcurrent, low-set stage NOC3Low 51 3I> Three-phase nondirectional overcurrent, low-set stage NOC3LowB 50/51/51B 3I>> Three-phase nondirectional overcurrent, high-set stage NOC3High 50/51B 3I>>> Three-phase nondirectional overcurrent, instantaneous stage NOC3Inst 67 3I>→ Three-phase directional o/c, low-set stage DOC6Low 67 3I>>→ Three-phase directional o/c, high-set stage DOC6High 67 3I>>>→ Three-phase directional o/c, instantaneous stage DOC6Inst 21 Z< Three-phase underimpedance,low-set stage UI6Low 21 Z<< Three-phase underimpedance, highset stage UI6High 51N Io>/SEF Non-directional earthfault, low-set stage (or SEF = sensitive earthfault protection) NEF1Low 50N/51N Io>> Non-directional earthfault, high-set stage NEF1High 50N Io>>> Non-directional earthNEF1Inst fault, instantaneous stage 67N/51N Io>→/SEF Directional earth-fault, low-set stage (or SEF = sensitive earth-fault protection) DEF2Low 67N Io>>→ Directional earth-fault, high-set stage DEF2High 67N Io>>>→ Directional earth-fault, instantaneous stage DEF2Inst 59N Uo> Residual overvoltage, low-set stage ROV1Low 59N Uo>> Residual overvoltage, high-set stage ROV1High 59N Uo>>> Residual overvoltage, instantaneous stage ROV1Inst 87N ∆Io> High-impedance based restricted earth-fault protection REF1A Underimpedance Earth fault 60 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 30: Protection functions Types of fault IEEE Device No. IEC Symbol Protection function Function block code Earth-fault 87TN ∆Io> Stabilized restricted earth-fault protection REF4A 87TN ∆Io> Stabilized restricted earth-fault protection REF4B Overload 49M/49G/49T 3 Three-phase thermal protection for devices (motors, generators and transformers) TOL3Dev Negative phaseseguence 46 I2 > Negative phaseseguence protection, low-set stage NPS3Low 46 I2>> Negative phaseseguence protection, high-set stage NPS3High 59 3U> Three-phase overvoltage, low-set stage OV3Low 59 3U>> Three-phase overvoltage, high-set stage OV3High 27 3U< Three-phase undervoltage, low-set stage UV3Low 27 3U<< Three-phase undervoltage, high-set stage UV3High 27, 47, 59 U1< U2> U1> Phase-sequence voltage protection, stage 1 PSV3St1 27, 47, 59 U1< U2> U1> Phase-sequence voltage protection, stage 2 PSV3St2 81U/81O f</f>, df/dt Underfrequency or overfrequency, stage 1 (incl. rate of change) Freq1St1 81U/81O f</f>, df/dt Underfrequency or overfrequency, stage 2 (incl. rate of change) Freq1St2 81U/81O f</f>, df/dt Underfrequency or overfrequency, stage 3 (incl. rate of change) Freq1St3 81U/81O f</f>, df/dt Underfrequency or overfrequency, stage 4 (incl. rate of change) Freq1St4 81U/81O f</f>, df/dt Underfrequency or overfrequency, stage 5 (incl. rate of change) Freq1St5 24 U/f> Overexcitation protection, OE1Low low-set stage 24 U/f>> Overexcitation protection, OE1High high-set stage 68 3I2f> Three-phase transformer Inrush3 inrush and motor start-up current detector 60 FUSEF Fuse failure supervision Overvoltage/ undervoltage Overfrequency/ underfrequency Overexcitation Additional functions FuseFail 61 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 31: Measurement functions Types of measurement IEC Symbol Measurement function Function block code General measurement/ analog input or analog output mA/V/°C/Ω General measurement/ analog input on RTD/analog module MEAI1...8 mA Analog output on RTD/analog module MEAO1...4 3I Three-phase current measurement, stage A MECU3A 3I Three-phase current measurement, stage B MECU3B Io Neutral current measurement, stage A MECU1A Io Neutral current measurement, stage B MECU1B 3U Three-phase voltage measurement, stage A MEVO3A 3U Three-phase voltage measurement, stage B MEVO3B Uo Residual voltage measurement, stage A MEVO1A Uo Residual voltage measurement, stage B MEVO1B Energy / Power E, P, Q, pf Three-phase power and energy measurement MEPE7 Frequency f System frequency measurement MEFR1 Transient disturbance recorder MEDREC16 Control function Function block code Current Voltage Recording Table 32: Control functions Types of control Symbol Circuit breaker 0↔ 1 0↔ 1 0↔ 1 Disconnector 0↔ 1 0↔ 1 0↔ 1 62 Circuit breaker 1 (2 state COCB1 inputs / 2 control outputs) Circuit breaker 2 (2 state COCB2 inputs / 2 control outputs) Direct open for CBs via HMI COCBDIR Disconnector 1...5 CODC1...CODC5 (2 state inputs / 2 control outputs) Three state disconnector CO3DC1 1 (3 state inputs/ 4 control outputs) Three-state disconnector CO3DC2 2 (3 state inputs/ 4 control outputs) Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 Table 32: Control functions Types of control Symbol Other control functions Control function Function block code Object indication 1...8 (2 state inputs) COIND1...COIND8 On/off switch 1...4 (1 output) COSW1...COSW4 Logic control position selector COLOCAT On-load tap changer COLTC controller (voltage regul.) MIMIC dynamic data point 1...5 MMIDATA1...MMIDATA5 Alarm 1...8 (HMI, remote) MMIALAR1...MMIALAR8 Table 33: Condition monitoring functions Types of condition monitoring Symbol Condition monitoring function Function block code Circuit breaker CBCM CB electric wear 1 CMBWEAR1 CBCM CB electric wear 2 CMBWEAR2 CBCM Operate time counter 1 for used operate time (motors) CMTIME1 CBCM Operate time counter 2 for used operate time (motors) CMTIME2 CBCM Gas pressure monitoring CMGAS1 CBCM Three-pole gas pressure CMGAS3 monitoring CBCM Spring charging control 1 CMSPRC1 CBCM Breaker travel time 1 CMTRAV1 CBCM Scheduled maintenance CMSCHED TCS Trip Circuit Supervision 1 CMTCS1 TCS Trip Circuit Supervision 2 CMTCS2 MCS Supervision function of the energizing current input circuit CMCU3 MCS Supervision function of the energizing voltage input circuit CMVO3 Trip circuit Measuring circuit 63 Transformer Terminal RET 541, RET 543, RET 545 1MRS755543 References Additional information Transformer Terminal RET 54_ Technical Reference 1MRS755225 Manual, General Technical Descriptions of Functions 1MRS750889-MCD (CD-ROM only) Installation Manual 1MR 750526-MUM Operator’s Manual 1MR 750500-MUM Technical Reference Manual RER 103 1MRS750532-MUM Technical Reference Manual RER 123 1MRS751143-MUM Protection & Control Terminals REF 54_, REM 54_, RET 54_ and REC 523 Configuration Guideline 1MRS750745-MUM Bus Connection Module RER 133 Technical Description 1MRS755163 Echelon, LON and LonTalk are registered trademarks of Echelon Corporation. All other product names or brands are trademarks, registered trademarks, or service marks of their respective owners. Document changes 64 Version Date Changes C Table 7: Reset ratio of OV3Low and OV3High changed from 0.96 to 1.04 15.06.2005 ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa, FINLAND Tel +358 10 22 11 Fax +358 10 224 1094 www.abb.com/substationautomation