Hands-On Relay Testing Session Restricted Earth Fault (REF) Element Settings Exercise Objectives After completing this exercise, you should be able to do the following: • Identify REF settings and protection requirements. • Define REF settings recommendations. • Calculate effective settings for the hands-on activities. • Validate relay settings. In this exercise, you will determine protection settings for the REF function for the example transformer data provided. You will perform calculations and then enter protection settings into ACSELERATOR QuickSet® SEL-5030 Software. Finally, after sending your settings to the relay, you will validate element assertion and relay operation. REF Protection REF protection is a technique for sensitive detection of ground faults in a grounded wye-connected transformer winding. Because it employs a neutral current transformer (CT) at one end of the winding and a normal set of three CTs at the line end of the winding, REF protection can detect only ground faults within that particular wye-connected winding. For REF to function, the line-end CTs must also be connected in wye because the technique uses a comparison of zero-sequence currents. Delta-connected CTs cancel out all zero-sequence components of the currents, eliminating one of the quantities the REF element needs for comparison. SEL-387A REF Implementation The REF implementation in the SEL-387A Current Differential and Overcurrent Relay uses a directional element (32I) that compares the direction of an operating current derived from the line-end CTs with the polarizing current obtained from the neutral CT. A zero-sequence current threshold and positive-sequence restraint supervise tripping. Because the SEL-387A has two REF elements, you can apply separate elements to each of the wye windings of a wye-wye-connected transformer. The neutral CT connects to one of the relay inputs (wye-delta with no grounding bank) or two relay inputs (wye-wye or wye-delta with grounding bank). The three current inputs are labeled IN1, IN2, and IN3. The directional element compares the polarizing current (neutral CT current) to the operating current (IRW1 or IRW2) and indicates forward (internal) fault location or reverse (external) fault location. The forward (internal) indication occurs if the fault is within the protected winding, between the line-end CTs and the neutral CT. Restricted Earth Fault (REF) Element Settings Page 1 of 6 20120723 The element operate time is determined by an extremely inverse-time overcurrent curve (Curve U4) at the time dial (TD) setting 0.5 and with 50GPn as the pickup setting (see Figure 1). Relay Word bit 32IF (forward fault) torque-controls the timing curve, and IN1 operates the timing function. The curve resets in one cycle if the current drops below the pickup or if 32IF deasserts. When the curve times out, Relay Word bit REFP asserts. Figure 1 REF Protection Output (Extremely Inverse-Time Overcurrent) Data Requirements You will need the following information to calculate the REF setting: • Transformer Winding 1 and Winding 2 CT ratios • Transformer neutral CT ratio Hands-On Activity 1: Calculate REF Element Settings In this hands-on activity, you will determine the settings for applying the REF element to transformer Winding 2. The relay uses the residual currents from a single winding to calculate the polarizing quantity (see Figure 2). Figure 2 Two-Winding Transformer Application Single-Line Diagram System Data Transformer rated MVA is 50 Winding 1 phase CT is 200:5, wye connected Winding 2 phase CT is 2000:5, wye connected Neutral CT is 1200:5 A Restricted Earth Fault (REF) Element Settings Page 2 of 6 20120723 Step 1 In ACSELERATOR QuickSet, select Group 1 > Set 1 > REFn. Step 2 Determine and enter the Polarizing Quantity REFn (n = 1 or 2) setting. REFn = __________________ Step 3 In ACSELERATOR QuickSet, select the Group 1 > Set 1 > General Data settings. Step 4 Determine and enter the Neutral (IWN2) CT Ratio. CTRN2 = __________________ Step 5 Select the Restricted Earth Fault settings. Step 6 Verify that the Restricted Earth Fault Torque Control setting is at the default setting of 1. Step 7 Determine and enter the REFn Current Sensitivity Level. 50GP1 = __________________ 50GP2 = _________________ Note: For this application, enable both Winding 1 and Winding 2 REF functions. The neutral current sensitivity threshold can be set as low as 0.25 times nominal current (0.25 A for a 5 A nominal CT current), the minimum neutral current sensitivity of the relay. However, the minimum acceptable value of 50GP must meet the following two criteria: • 50GPn must be greater than the highest unbalance expected by load conditions. • 50GPn must be greater than a minimum value determined by the relationship of the CTRn values used in the REF function. ⎡ CTRMAX ⎤ 50GPn = ≥ 0.05 • Inom • ⎢ ⎥ ⎣ CTRNn ⎦ In this example, n = 2, representing transformer Winding 2. Restricted Earth Fault (REF) Element Settings Page 3 of 6 20120723 Step 8 Use the Sequential Events Recorder (SER) to capture the operation of the REF elements under test. Select the Report > SER > SER Trigger Lists settings. Step 9 Add the following Relay Word bits to SER 4: 32IE1 and 32IE2: REF logic enabled 32IR1 and 32IR2: external ground fault 32IF1 and 32IF2: internal ground fault 50GN1 and 50GN2: neutral current pickup REFP1 and REFP2: REF inverse-time overcurrent Step 10 Save your settings, and send them to the relay. Hands-On Activity 2: Validate REF Element In this hands-on activity, you will validate the REF element enable logic, fault direction logic, and inverse-time overcurrent logic. You will use Relay Word bits to monitor the following conditions: • External ground fault • Internal ground fault • Inverse-time overcurrent Set Up Monitoring To monitor element Relay Word bits, you will set up user-defined target light-emitting diodes (LEDs) in the ACSELERATOR QuickSet human-machine interface (HMI). Step 1 Select Tools > HMI > HMI. Step 2 In the Device Overview panel, from the HMI categories to the left, select Targets, and scroll down to Target Rows 50 and 51. Monitor the REF Relay Word bits found in each target row. 49 LB9 LB10 LB11 LB12 LB13 LB14 50 50GC1 50GN1 32IE1 32IR1 32IF1 REFP1 51 50GC2 50GN2 32IE2 32IR2 32IF2 REFP2 52 * * * * * * Figure 3 Restricted Earth Fault (REF) Element Settings REF Targets in SEL-387A HMI Page 4 of 6 20120723 REF Enabled Logic In this test, you will verify that the REF Relay Word bit asserts for the following current values: |IN1| ≥ 50G • INOM1 Step 1 Reset the target LEDs. The instructor will inject the current into the IN current input. Step 2 Verify the following HMI targets: • The 32IE1 Relay Word bit asserts. • The 50GN1 Relay Word bit asserts. Fault Direction Logic In this test, you will verify the REF directional pickup as follows: • For an external fault, IN is at 0 degrees. • For an internal fault, IN is at 180 degrees. Step 1 Reset all relay targets. The instructor will inject an external fault, followed by an internal fault. Step 2 Verify the following HMI target LEDs: • The 32IR1 target LED asserts for an external fault. • The 32IF1 target LED asserts for an internal fault. Inverse-Time Test In this test, you will verify the time characteristic of the inverse-time overcurrent element. From Figure 1, you can see that the curve shape is U4 with a TD of 0.5. Step 1 Calculate the expected operate time (tp) for IWn = 2 • 50GPn • (CTRNn/CTRn) at 0 degrees using the following equation or the TOC_Calculator.xls spreadsheet: 5.67 ⎞ ⎛ tp = TD • ⎜ 0.0352 + 2 ⎟ M −1 ⎠ ⎝ Restricted Earth Fault (REF) Element Settings Page 5 of 6 20120723 Step 2 Clear the SER using the SER C serial port command or the ACSELERATOR QuickSet HMI menu. The instructor will inject the current magnitude for the test. Step 3 Issue the SER serial port command, or select SER from the ACSELERATOR QuickSet HMI menu. Step 4 Verify the following: • 50GNn is asserted. • 32IEn is asserted. • 32IFn is asserted. • REFPn is asserted. • The operate time is as expected (the difference between 50GNn and REFPn). I-44 HANDS ON Date: 05/31/12 161/14.4 KV SUBSTATION FID=SEL-387A-R606-V0-Z004003-D20040628 # DATE TIME ELEMENT STATE 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 05/31/12 09:06:41.704 09:06:41.727 09:06:44.047 09:06:47.577 09:06:47.577 09:06:47.596 09:08:17.450 09:08:17.473 09:08:17.829 09:08:22.328 09:08:22.328 09:08:22.345 09:15:28.946 09:15:28.969 09:15:29.323 50GN1 INTERNAL REFP1 INTERNAL 50GN2 REFP1 50GN2 INTERNAL REFP2 INTERNAL 50GN2 REFP2 50GN2 INTERNAL REFP2 Restricted Earth Fault (REF) Element Settings FAULT FAULT FAULT FAULT FAULT Time: 09:19:57.654 Asserted Asserted Asserted Deasserted Deasserted Deasserted Asserted Asserted Asserted Deasserted Deasserted Deasserted Asserted Asserted Asserted Page 6 of 6 20120723