TECHNICAL SPECIFICATION FOR ELECTRICAL/DATA WORK TO BE CARRIED OUT AT JIVAPAR BRANCH FOR BANK OF INDIA Sr. No. Description 1.0 ELECTRICAL WIRING: 1 Supply, Installation, Testing and Commissioning of following point wiring as per the specifications and drawings. The unit rate for the switch board and further to point outlet including all hardware, connector strips, fan hook, outlet boxes, switch boards, switch plates, switches, wire conduits etc. A point shall include in addition to phase and neutral wire, a PVC insulated earth-continuing wire from L.P. to the final termination at outlet points. All the wiring should be done in concealed/semi concealed open manner or slab/ wall/false ceiling. The wiring should be done with rigid PVC conduits/Casing-capping having minimum of 1.6 mm wall thickness and minimum 19mm dia with 440V grade PVC insulated. ISI approved copper conductor wire, with crabtree/ROMA make switches and accessories with company boxes for point outlet and SB and with all required hardware accessories to complete the wiring. No junction boxes are allowed anywhere in the wiring. All joints shall be done at point outlet on switchboards only. In between joints are not allowed anywhere. The wiring shall be done as per IS 732 and IS 4648. THE COST OF ALL POINTS ARE INCLUDING OF WIRING MAINS (A) Making Zari in the wall & sami finishing the surface. (B) Ball and socket joint wherever required. (C) Earthing of Fittings. (D) Electrical connections from the outlet points to the fixture with 3 core flexible wire. (E) The size of the wire will be as follows normal point wiring from SB to point outlet boxes. Phase-neutral: 1.5 sq. mm. Earth: 1.0 sq. mm. SB mains from I.p. to SB from I.p to 5 Amp. Plug point for freeze/geyser etc. Phase-neutral: 2.5 sq. mm. Earth: 1.5 sq. mm. Wiring for 15 Amp. Plug point for freeze/geyser etc. Phase-neutral: 4.0 sq. mm. Earth: 2.5 sq. mm. Wiring for 20 Amp. Plug point for A.C. Phase-neutral: 4.0 sq. mm. Earth: 2.5 sq. mm. Two parallel 15 Amp. Plug points for first point Phase-neutral: 4.0 sq. mm. Earth: 2.5 sq. mm. For second point looping Phase-neutral: 4.0 sq. mm. Earth: 2.5 sq. mm. 1.1 One light point controlled by one 5 Amp. Switch 1.2 Two light point controlled by one 5 Amp. Switch 1.3 One 5 Amp. 5 pin socket outlet controlled by one 5 Amp. Switch looped on switch board. 1.4 Two 5 Amp. 5 pin socket & One 15 Amp. 5 pin socket controlled by one 15 Amp. Switch at other convenient location for computer. Qty. Rate Unit 28 8 No. No. 10 No. 12 No. Amount 1.5 Two 5 Amp. 5 pin socket outlet controlled by one 5 Amp. Switch at other convenient location for Raw Power. 1.6 One 5 Amp. 5 pin socket outlet controlled by one 5 Amp. Switch at other convenient location for wall/Ex. fans./Sep. Points 1.7 One Ceiling fan point controlled by one 5 Amp. Switch with electronic type fan Regulator 1.8 One buzzer/bell point controlled by one bell push, with electric type buzzer/bell. 1.9 One 15 Amp. 6 pin socket outlet controlled by one 15 Amp. Switch with indicator 1.10 SITC of 20 A, 230 V, the satisfaction of E.I.C. For SPLIT AC 1.5TR /2.0 TR unit with necessory require wiring from DB of 2 no of 4.0 sqmm wires and 1 no of 2.5 sqmm PVC Insulated copper conductor wire laying in with 20 mm/25 mm dia PVC rigid conduits 1.5 mm thick ISI mark. These will be used with point wiring of A.C. points, etc 1.11 One 25 Amp. Cyclic Timer for ATM AC Units, complete with required connectors and lugs etc (In Server Room) 1.12 20 Amp power point for Glowsign board with L & T time switch & with 20 Amp. SP MCB 2.0 CABLES & CABLE TERMINATIONS: 2.1 Supplying & Laying PVC armoured cable of 1100 V grade of copper/conductor (as specified) of following sizes in ready made trench mounted on wall with necessary clamping arrangement or in prelaid RCC hume pipe with necessary cable identification lugs at both ends, digging of trench and its filing with second call bricks, send. The cable shall ISI mark and conforming to latest ISS. All the cable shall be terminated with suitable sizes of Lugs. & Gland a b c d e 3.0 3.1 3.2 3.3 3.4 3.5 3.6 4.0 2 x 6 sq. mm. + 1 x 4 sq. mm. Copper Fle. Wire (for UPS Input/Output) 4c x 6 sq. mm. Copper armoured cable (Panel to UPS & POWER DB) 4c x 10 sq. mm. Copper armoured cable (Panel to LT & AC DB) 4c x 25 sq. mm. Alu. armoured cable (Panel to Generator) 3.5 x 50 sq. mm. Alu. armoured cable (Panel to Main SFU) EARTHING: Providing & erecting earthing as per drawing complete earth copper plate size 600 x 600 x 3.15 mm at the technically lly respective position with digging of earth & refilling with charcoal & salt complete with masonry enclose made of cast-iron cover plate having lockable arrangement & watering pipe & guide pipe of suitable size to earth pit. (For UPS) Same as above but G.I. Plate size 600 x 600 x 3.15 mm (For Lighting) Supply and Laying of 8 SWG Copper wire thick with proper saddling with minimum distance at 1.5 feet. Supply and Laying of 8 SWG G.I. wire thick with proper saddling with minimum distance at 1.5 feet. 25*3 mm G.I. strip-FromG.I. Earthpit to main Pannel + From Cu. Earthpit to Ups I/P DB 25*3 mm Cu. Strip FIXTURES AND FITTINGS: Supply, installation, testing and commissioning of the following fixtures and fittings. The fixtures shall be installed on wall, false ceiling etc. and as per the manufacture instructions. The job also includes the connection of the fixture with outlet point using 3 core flexible wire Wherever the lighting fixtures are there./Crompton/Wipro 11 No. 8 No. 4 No. 1 No. 8 No. 8 No. 1 No. 1 No. 15 15 12 0 10 Mtr. Mtr. Mtr. Mtr. Mtr. 1 1 No. No. 20 Mtr. 25 40 Mtr. Mtr. 0 Mtr. 4.1 4.2 4.3 4.4 4.5 4.6 4.7 5.0 5.1 5.2 5.3 5.4 5.5 5.6 2 x 36 W Compact Flourecent recess mounying Light Fitting 2 x 18W Down Light Fitting 1 x 36W Mirolta Type Fitting 16" Wall Fan 12" Ceiling Fan (Energy Sever model) 300mm Exhaust Fan(heavy duty) 1 x 11W Mirolta Type Fitting PANEL BOARD/DISTRIBUTION BOARDS Supplying & erecting complete with 14/16 SWG complete floor/ wall mountain type with required compartment including cables end box and gland/termination as required. S.F.U. (HRC type) 200 A -1 no. Supplying & erecting complete with 14/16 SWG complete floor/ wall mountain type with required compartment including meters & lamps with following materials: Incoming Feeder: S.F.U.(HRC type)125 A -1 No. 63A Change Over Switch - 1 No. 160 A TPN, 440 V, 50 Hz., Cu. Busbar. Outgoing Feeder: * Timer of L & T make Cat. No. 67DDTO digicom Timer with 16A. 4P contactor / Theben make Cat no. SUL 180 a - T180 0 001 ANALOG Timer with L & T make contactor MNX 18 (operating coil voltage 230V, 50 Hz). (24 Hrs.) 1 No. for signage light 63A FP MCB - 6 Nos. (For LTDB- 1, AC DB - 2, PDB- 1, ATM -1 & SPARE- 1) & 40A DP MCB - 1 No. (For Glow Sign Board) AVF Digital Meter of Trinity/Enercon Make with load balance ratio R Y B Lamp with indicator and required cable glands etc. Supplying & Installing, Testing & Commissioning of DB with following: (For Lighting Purpose)-6 WAY TPN DB Incoming: 63 A FP MCB-1No. Outgoing: 40 A DP ELCB-3 Nos. 16/10/25 Amp. SP MCB -12 Nos. Supplying, installing, testing & commission of Distribution Board with following: (For A.C. Units)-4 WAY TPN DB Incoming: 63 A FP MCB-1No. Outgoing: 25 A DP MCB-6 Nos. Supplying, installing, testing & commission of Distribution Board with following: (For 15A Power Points & Raw Power Points) 4 WAY TPN DB Incoming: 63 A FP MCB-1No. Outgoing: 10/16 A SP MCB - 12 Nos. Supplying, installing, testing & commission of Distribution Board with following: (For UPS Units)-8 WAY SPN DB Incoming: 63 A DP 100mA ELCB - 1 No. Outgoing: 10/16 A SP MCB - 6 Nos. Supplying, installing, testing & commission of Distribution Board with following: (For UPS Input DB) -12 WAY SPN DB Incoming: 63 A FP MCB - 1 No. & 40A DP MCB -1No. Outgoing: 40 DP MCB -2 No. 15 35 8 8 3 2 4 Nos. Nos. Nos. Nos. Nos. Nos. 1 No. 1 No. 1 No. 1 No. 1 No. 1 No. 1 No. 6.0 INTERCOM TELEPHONE 6.1 SITC telephone point with Telephine socket outlets of RJ 11 with concealed boxes in walls/furniture's etc. SITC of 2 pair of 0.51 cross section pvc insulated copper conductor telephone wire of ITI approved with 20/25 dia. PVC conduits with accessories duly burried under floor with necessary chasing / breaking in floor and to be refinished with all necessary civil material etc. or to be cleated on wall / ceiling with saddles / spacer etc. necessary termination etc. for intercom Tele. facility (9nos.) + Fax Tele. facility (2 nos.) + for Direct Tele. facility (2 nos.) 6.2 Supply & installation of 20 pair crone terminal DP Box. Krone make 7.0 LAN/STRUCTURE CABLING WORK: 7.1 Supplying and installation of computer data cable CAT-6 of D-Link Brand Make including PVC pipe 25mm dia. 1.5mm thick, recessed in counter necessary, ceiling, wall or shorting in concealled way in during cutting and plastering as required. including connection with RJ-45 on both end. with Cable (Including 1 for LCD, 2 for IP Phone,2 for ATM) 7.2 Supply & testing at patch cord. (Factory Built) a Length 1 Meter (Make D-Link) (If Required) b Length 2 Meter (Make D-Link) (If Required) 7.3 Supply, installation & testing of 12U Rack with 1 fan & power point having one shelf in the rack 7.4 Supply & Crimping of RJ-45 Connector with proper testing 7.5 Providing, installing, testing, commissioning of CAT 6 UTP pvc insulated copper conductor data cable of D - Link with 20/25 dia. PVC conduits with accessories duly burried under floor with necessary chasing / breaking in floor and to be refinished with all necessary civil material etc. or to be cleated on wall / ceiling with saddles / spacer etc. necessary termination etc. with ferrule numbering at both ends of each piece of cable complete.[ 2 Lines from BSNL Krone to new krone]. 7.6 S & I of 300 x 300 x 40 mm size GI box including the top cover duly fabricated from 18 SWG m. s. Sheet complete with necessary knock outs at all the sides of box for conduit entries duly fixed in floor, incl. breaking in floor & re-finished the same etc. complete (Wire Draw Box) 7.7 S & I of 150 x 150 x 25 mm size GI box including the top cover duly fabricated from 18 SWG m. s. Sheet complete with necessary knock outs at all the sides of box for conduit entries duly fixed in floor, incl. breaking in floor & re-finished the same etc. complete (Wire Draw Box) 7.8 SITC of 1.5 sq. mm. 3 core flexible cable of approved make (4mtr. Length) with M.S. flexible pipe & 15amp. 3 pin top of approved make for the supply of locker room. 7.8 SITC of CABLE TV cable line with proper fixing & connecting with modular CoAxial TV Socket 8 MUSIC SYSTEM 1 Supplying & Providing of 0.75 Sqmm Twin same as clouse No. 1 of Internal Wiring From Music Amplifier to various speakers as per the requirement complete in all respect as per the drwaing and Architect or Consulatant (Rate are inclusive of conduits) 2 Supply & installation of 6 inch round AHUJA/BOSCH make concealed/wall type speaker connected with computer network/PC which will play music with necessary attachment as per requriment. GRAND TOTAL OF ELECTRICAL AMOUNT 7 2 Nos. Nos. 12 Nos. 12 12 No. No. 1 12 No. Nos. 60 Mtr. 8 Nos 8 Nos 2 Nos 1 No. 120 Mtr 5 No GRAND TOTAL OF FURNISHING / CIVIL AMOUNT Rs Rs GRAND TOTAL OF FURNITURE-CIVIL & ELECTRICAL ITEMS AMOUNT Rs RUPEES IN WORDS : RUPEES IN WORDS : SIGNATURE OF THE CONTRACTOR NAME OF THE CONTRACTOR ADDRESS: PLACE: