Le Thien Telecom Address: 18/A20 Quach Van Tuan Street, Ward 12, Tan Binh District, HCM city, Viet nam Tel: +848. 2938293 Fax: +848. 2938292 Website:www.lethientelecom.com Email: sales@lethientelecom.com TECHNICAL SUMMARY SHEET HAC240 – Series Doc ref hac-tss2(240V) Issue 2 Date Jan 2005 240V SINGLE PHASE 50/60Hz AC LOAD BANKS HAC240 Series load banks for single phase gen-set and UPS testing Type ref HAC240-5 HAC240-8 HAC240-11 HAC240-14 Max Volts 1 ph 50/60hz 240V 240V 240V 240V Max watts 5451W 8251W 11050W 13851W Max amps 22A 33A 45A 57A Case size (mm) length width height 710mm 330mm 425mm 710mm 330mm 425mm 710mm 330mm 425mm 710mm 330mm 425mm approx. weight 19 kgs 21 kgs 25 kgs 27 kgs Notes : 1. The load bank cooling fan is powered from the gen-set or UPS under test and does not require an external auxiliary supply. 2. The load bank can operate at 200V, 220V & 230V with proportional reduction in load current. 3. HAC load banks are for AC operation only 4. The load banks include an earth leakage isolation circuit breaker, load isolation contactors and fan failure protection. Hillstone Products Ltd Unit D2 Greenbrook Business Park Greenbrook Street Bury Lancashire England BL9 6LZ Tel. +44 (0) 161 763 3100 Fax. +44 (0) 161 763 3158 e-mail sales@hillstone.co.uk web www.hillstone.co.uk TECHNICAL SUMMARY SHEET HAC415 – Series Doc ref hac-tss5(415V) Issue 5 Date Jan 2005 415V THREE PHASE 50/60Hz AC LOAD BANKS HAC415 Series load banks for three phase gen-set and UPS testing Type ref HAC415-10 HAC415-20 HAC415-30 HAC415-40 HAC415-50 HAC415-60 HAC415-70 HAC415-80 HAC415-90 HAC415-100 Max Volts 3ph 50/60hz 415V 415V 415V 415V 415V 415V 415V 415V 415V 415V Max watts 10KW 20KW 30KW 40KW 50KW 60KW 70KW 80KW 90KW 100KW Case size (mm) length width height 900mm 450mm 600mm 900mm 450mm 650mm 900mm 450mm 700mm 900mm 450mm 750mm 1000mm 450mm 1000mm 1000mm 450mm 1000mm 1000mm 450mm 1200mm 1000mm 450mm 1200mm 1000mm 450mm 1500mm 1000mm 450mm 1500mm approx. weight 35 kgs 42 kgs 48 kgs 55 kgs 65 kgs 70 kgs 85 kgs 95 kgs 110 kgs 125 kgs Notes : 1. The load bank cooling fan is powered from the gen-set or UPS under test and does not require an external auxiliary supply. Separate aux supply available as optional extra. 2. The load bank can operate at 380V & 400V with proportional reduction in load current. 3. HAC load banks are for AC operation only 4. The load banks include load isolation contactors and fan failure protection. Hillstone Products Ltd Unit D2 Greenbrook Business Park Greenbrook Street Bury Lancashire England BL9 6LZ Tel. +44 (0) 161 763 3100 Fax. +44 (0) 161 763 3158 e-mail sales@hillstone.co.uk web www.hillstone.co.uk