Hybrid Multiconverter Conditioner Topology for High-Power Applications María Isabel Milanés-Montero, Member, IEEE, Enrique Romero-Cadaval, Senior Member, IEEE, and Fermín Barrero-González, Senior Member, IEEE Abstract—A novel multiconverter conditioner topology and its control stage are proposed in this paper. It is formed by an active conditioner in parallel with a hybrid conditioner composed of an active filter in series with one or more passive filters. This topology allows the reduction of the inverter ratings, constituting an effective solution at high-power levels. Collaborative control strategies are developed for the new topology, which share the compensation objectives between the two converters. These control strategies and the tracking techniques are based on estimating the load current, achieving new algorithms with a reduction in the number of meters in the control stage. The conditioner operates properly in three-phase four-wire systems reducing the harmonic distortion and/or imbalance and attaining the unity displacement power factor. Experimental results are included for the testing of the topology and its control. Index Terms—Active filter (AF), hybrid filter, multiconverter topology, power conditioner. I. I NTRODUCTION T HE use of nonlinear loads injecting harmonic and reactive current components into the electrical power system has undergone rapid growth in recent years. The reduction or elimination of these components can be achieved by using compensation equipment installed at the point of common coupling (PCC). Conventional topologies, such as passive filters, active or hybrid conditioners, or universal conditioners, have been developed for this purpose [1]–[11]. However, these topologies have restrictions to be used in high-power applications due to the semiconductor technology limits regarding the inverter rating [12], [13]. A solution to this drawback is the employment of two or more devices to collaborate in the compensation. Seriesconnected active multiconverter conditioners [14]–[16], a thyristor binary compensator in parallel with an active conditioner [17], and parallel-connected active multiconverter conditioners sharing the dc link [13], [17] or with the independent dc bus [14], [19]–[22], have been developed using different collaborative strategies. In this paper, a new parallel-connected multiconverter topology, in which one of the equipment is a hybrid conditioner, is proposed. We call it the parallel active Fig. 1. Block diagram of the parallel-connected multiconverter topology: two power stages (active filter in parallel with a hybrid filter, sharing the dc bus) and one collaborative control stage. with parallel Hybrid conditioner (pApH). It is formed by two converters connected in parallel, sharing the dc bus (see Fig. 1). One of the converters, termed slow because it operates with a low switching frequency, is responsible for the fundamental and dominant harmonic components in the load current. This device is aided by the fast conditioner, which operates at a higher frequency, compensating the higher harmonic components. The main advantage of this topology is the separation of the correction which leads to a reduction in the inverter ratings, making this equipment viable at high-power levels. Another advantage, whose demonstration is out of the scope of this paper, is the reduction in volume, losses, and price of the conditioner due to the possibility of using ferromagnetic core filter inductors for the slow converter [18]. The sharing strategy between the two conditioners and their respective principles of operation are explained in Section II. The hybrid multiconverter topology is described in Section III. The novel control stage, based on the load current estimation by means of the source current measurement, is explained in Section IV. Experimental results for a 1.2-kVA laboratory prototype are presented in Section V. Finally, in Section VI, a comparison between a hybrid multiconverter conditioner and a classical shunt active monoconverter conditioner is carried out by a simulation to calculate the design rate power of the inverters in each topology. It is demonstrated that the novel topology achieves a decrease in the inverter ratings, making it useful for high-power applications. II. S HARING S TRATEGY AND P RINCIPLES OF O PERATION Manuscript received November 15, 2009; revised April 16, 2010 and July 1, 2010; accepted July 8, 2010. Date of publication July 29, 2010; date of current version May 13, 2011. This work was supported by the Junta de Extremadura (Regional Government), Spain, under project PDT08A046. The authors are with the Power Electrical and Electronic Systems Research Group, School of Industrial Engineering, University of Extremadura, 06006 Badajoz, Spain (e-mail: milanes@unex.es). The hybrid filter topology chosen for the multiconverter pApH conditioner is the Active filter in series to Passive filter (AsP) because for high-power loads it constitutes the most economic solution due to the reduction attained in the inverter power [12], [23]. If this hybrid filter is designed and controlled TABLE I F UNCTIONS OF THE ACTIVE E QUIPMENT OF E ACH C ONDITIONER Fig. 2. Correction using a hybrid multiconverter pApH conditioner. to behave as a dominant harmonic filter (DHF) [24] it will be formed by an active filter (AF) in series with one or more parallel passive filters (PFs) tuned to the dominant harmonic frequencies in the load current, that are usually of low order. These components would be mainly filtered passively, while the AF, which will have a low rating, will collaborate in overcoming the drawbacks of passive filters working alone. Also, the hybrid filter could compensate dynamically the displacement power factor, dPF. As the harmonics in the reference current for this filter are of low order, a low switching frequency could be used for the inverter of this device, which is called the slow conditioner. The other parallel active (pA) conditioner will then be responsible for the higher order harmonics, which usually have lower amplitudes, so the inverter rating will be smaller. The tuned harmonic components left uncompensated by the slow equipment to avoid passive filter overload and the switching harmonics of the hybrid conditioner are also potential tasks for this equipment. As high harmonic components will be entrusted to this conditioner, a higher switching frequency would be needed, and it would act as the fast device. This sharing strategy demonstrates the advantage of this topology compared to a hybrid monoconverter AsP conditioner [9]. If reactive power is proposed as a compensation objective, the passive filters have to be designed with a narrow bandwidth. It means that the hybrid equipment could filter out only the lower order frequencies in the load current if an admissible inverter rating for high-power applications is looked for. The hybrid filter attains a selective but not global compensation. The proposed multiconverter topology avoids this drawback, since the fast conditioner compensates the higher harmonic components in the load current, achieving an overall compensation. If both filters operate as current-controlled sources, the single-phase equivalent circuit of the multiconverter topology is the one shown in Fig. 2, where iAFs and iAFf are the currents injected by the inverters of the slow and fast conditioners, respectively. The reference current for the hybrid filter, iHF,ref , behaving as a DHF is as follows: lim iHF,ref = iAFs,ref = iL1 − i+ L1d + iLhPF (1) where iL1 is the fundamental load current; i+ L1d is the active positive-sequence fundamental load current component; and ilim LhPF is the limit tuned load current allowed by the conditioner to avoid passive filter overload, calculated as follows: ilim LhPF = lim if ILhPF ≤ IFPh PF iLhPF , iLhPF ILhPF lim · IPFh , PF lim if ILhPF > IPFh PF (2) with ILhPF being the rms value of a tuned harmonic component lim being the maximum rms value in the load current and IPFh PF of each tuned harmonic current in the passive filter(s). One can notice that with this reference current, the hybrid filter avoids reactive power overcompensation in case of loads with lower lagging reactive power than the fixed installed passive filter reactive power. The reference current for the fast conditioner will be needed, collaborating with the slow device, to attain the desired source current, iS,ref , which depends on the compensation objectives. This current will be calculated as follows: iAFf,ref = iL − iS,ref − iHF,meas (3) where iHF,meas is the measured hybrid filter current. If a perfect harmonic cancellation (PHC) global control strategy [25], [26] is selected for the multiconverter equipment, aiming for the source current to be in phase with the positivesequence fundamental component of the voltage at the PCC, the functions of the active equipment of each conditioner are the ones summarized in Table I. There is no type of interaction between both converters because the hybrid filter operates as a DHF with the precise reference current proposed in (1). Possible interaction in terms of zero-sequence components between both converters is avoided since the slow converter is responsible for fundamental and dominant harmonic frequencies. Only zero-sequence components at these frequencies due to unbalanced load current would flow through the slow converter. Other possible zero-sequence components (triplen harmonics or imbalance at other frequencies) will only circulate through the fast converter. For the same reason, the reference current of the hybrid filter assures that the current at the fast converter switching frequency does not circulate through the slow one. On the other hand, the current at the slow converter switching frequency is proposed as one of the compensation goals of the fast converter (see Table I). Fig. 3. Three-phase four-wire source with nonlinear load and shunt hybrid multiconverter conditioner. III. D ESCRIPTION OF THE T OPOLOGY In this paper, a particular topology of the one presented in Section II is used, which only has one passive branch (Fig. 3). The active part of this topology is formed by a neutral-pointedclamped voltage-source inverter with six branches. The three fast conditioner branches are connected to each phase of the utility by a filter inductor, while the slow conditioner branches are connected in series to the passive filter impedances. The inductor of the passive filter will also filter the slow inverter switching harmonics. To tune the passive filters, a controlled rectifier supplying a resistive load was considered as a nonlinear load since in high-power applications, such as adjustable speed ac drives of 1000 hp and larger, or for dc drive applications to supply the dc directly to the dc motor, phase-controlled rectifiers instead of diode rectifiers, are typically used [27]. This load requires fundamental reactive power compensation to maintain unity dPF, and its dominant harmonics are the fifth and seventh orders. As one passive branch has been selected for the hybrid conditioner, it is possible to tune the passive filter to a lower, higher, or intermediate order. After studying these options, the tuning to the lowest harmonic (fifth order) was finally selected because of the following: – – – The filter impedance at the higher dominant harmonic will be inductive, eliminating the possibilities of resonances, as opposed to tuning to the 6th or 7th orders, which could produce resonances between the filter and the source impedance near the 5th harmonic frequency. As the amplitude of the harmonics in the load current decreases as the harmonic order increases, the voltage that the active filter has to generate to make the 7th order harmonic component to circulate across the hybrid filter will be reduced. The passive filter will provide a higher impedance at higher and non-dominant harmonic orders (h > 7), reducing the voltage provided by the active filter to avoid the derivation of these harmonics through the hybrid branch. IV. C ONTROL S TAGE The global compensation objectives of the conditioner are as follows: – dPF correction for every firing angle in the controlled rectifier. – Harmonic reduction in the source current. – Imbalance elimination in the source current. The control stage is formed by collaborative control strategies to achieve these global compensation objectives and tracking techniques. Collaborative control strategies have been developed with capabilities to do the following: – Split the compensation objectives between the two converters (Table I), – Guarantee an efficient overall performance, avoiding interferences between the two converters, – Allow that one converter could help the other one in anomalous situations, as overload. As the resulting collaborative strategies are complex, special attention has been paid to develop algorithms with a number of measurements as minimum as possible. A. Collaborative Control Strategies If control strategies based on the load current detection are employed, as was previously proposed in Section II, in threephase four-wire systems, three load currents (iLa , iLb , and iLc ), six compensating currents (iHFa , iHFb , iHFc , iAFfa , iAFfb , and iAFfc ), three phase-to-neutral PCC voltages (uPCCa , uPCCb , and uPCCc ), and the dc bus voltage (Udc ) need to be sensed. This implies thirteen measurements to control the multiconverter conditioner. An improvement is proposed so that the control strategies will be based on the load current estimation to minimize the number of sensors. Fig. 4. Block diagram of the hybrid multiconverter conditioner control strategies. The multiconverter conditioner uses a sinusoidal source current (SSC) global control strategy. The collaboration between the two converters is based on a frequency sharing operation: the slow converter employs a selective harmonic compensation control algorithm using harmonic load current extractors, while the fast converter cooperates with it to comply with the global compensation objectives. Also, the control is implemented so that the converter responsible for the dc bus control loop can be chosen. These collaborative control strategies assure that there is no type of interaction between the two conditioners. The control block diagram of the hybrid multiconverter conditioner is shown in Fig. 4. It is composed of two parts which are explained in the following sections. Extraction of the Reference Source Current: The block diagram for the extraction of the reference source current is displayed in the upper signal path in Fig. 4. The reference source current using an SSC strategy operating as PHC [21], but based on the measurement of the source current in 0–d–q coordinates, can be calculated as follows: ⎤ ⎡ ⎤ 0 iS0,ref ⎦ ⎣ iSd,ref ⎦ = K ⎣ u+ PCC1d + iSq,ref uPCC1q ⎡ = + p+ S1 + Δp1(Udc) 2 u+ PCC1d + 2 u+ PCC1q ⎡ 0 ⎤ ⎣ u+ ⎦ PCC1d u+ PCC1q (4) where the term Δp+ 1(Udc) is the positive-sequence fundamental active power absorbed from the grid for controlling the dc bus voltage. This term is obtained from the output of a proportionalintegral (PI) controller whose input is the error between the reference dc bus voltage and its measurement. The positivesequence fundamental PCC voltage is obtained by an autoadjustable synchronous reference frame (ASRF) [28]. Calculation of the Reference Hybrid Conditioner Current: The calculation of the reference current for the hybrid filter proposed in (1) has to be changed because the load currents are not measured. A new control method which estimates these variables from the measurement of the source currents will be used, resulting in the following reference current for the slow converter: ∗ ∗lim + i∗lim (5) iHF,ref = iL1 − i+ L5 + iL7 L1d where the superfix “∗” means that this variable is not measured, but estimated. The harmonic terms in (5) are obtained using two blocks called the hth harmonic load current extractor (hLCE), one for the fifth and another for the seventh harmonic orders (see lower signal path in Fig. 4). In Fig. 5, the block diagram of an hLCE is displayed, where the inputs are the source current and the positive-sequence harmonic angle (calculated by multiplying the output angle of the ASRF, θ1+ , by the harmonic order), and the output is the estimated harmonic load current. The principle of operation of this module is the following: If a dominant harmonic load current iLh is to be absorbed by the hybrid filter, this component has to be null in the source current. Two synchronous reference frames (positive- and negative-sequence) and one one-phase ASRF [28] (zero-sequence) are used to Fig. 5. hLCE using control strategies based on the source current measurement. Fig. 6. Fundamental compensating load current extraction (1LCE) using control strategies based on the source current measurement, with the addition of a dc bus control loop. calculate the source current components in 0–d–q coordinates. A PI controller for each component is used to estimate this component in the load current. Also, to avoid the fifth passive filter overload, (2) is particularized as follows: i∗lim Lh = i∗Lh , i∗ Lh ∗ ILh h lim · IPF5 , ∗ h lim if ILh IPF5 ∗ h lim if ILh > IPF5 (6) ∗ where it must be highlighted that ILh is the rms value of the tuned harmonic component in the estimated load current; h lim is the maximum rms value of each tuned harmonic and IFP5 current in the fifth passive filter. It is necessary to add an additional block for the dc bus voltage control in the fundamental harmonic term in (5). For this voltage to be constant and near its reference, the hybrid filter has to absorb fundamental positive-sequence active power from the utility. Hence, a new term, Δi+ 1d(Udc) , has to be included, resulting finally in the following: ∗ ∗lim ∗lim + Δi+ iHF,ref = iL1 − i+ L1d 1d(Udc) + iL5 + iL7 . (7) This term is obtained from the output of a PI controller whose input is the error between the reference dc bus voltage and its measurement. The PI controller has been designed with an enable signal to choose whether the slow conditioner is in charge of the dc bus control (enabling the PI) or whether this function is left to the fast conditioner (disabling the PI or not turning on the slow converter). It also improves the reliability of the multiconverter conditioner, since in case of failure of one converter, the other one could continue operating. The control block diagram for the fundamental component is shown in Fig. 6. In Fig. 4, one observes that seven measurements only are needed for the control strategies (three source currents, the dc bus voltage, and three PCC voltages). Fig. 7. Duty cycle determination for the hybrid conditioner (slow). Fig. 9. Experimental prototype: 1: Slow (hybrid) conditioner, 2: Fast conditioner, 3: Ferromagnetic core inductors (passive filter), 4: Capacitors (passive filter), 5: Air core inductors, 6: DC bus capacitors. TABLE II PASSIVE F ILTER PARAMETERS Fig. 8. Duty cycle determination for the active conditioner (fast). B. Tracking Technique The tracking technique determines the duty cycle for the conditioner aimed at eliminating the error between the reference and the measured currents e in a switching period TS , namely: D = 0.5 − e uAF LAF − TS Udc Udc (8) where uAF is the voltage on the ac side of the active filter. In the slow conditioner, the hybrid filter current is measured, so e will be determined from the difference between the reference and the measured currents. The voltage uAF can be calculated as follows: uAF = uPCC + iHF,meas · ZCPF5 (9) where ZCPF5 is the impedance of the passive filter without inductance. Fig. 7 shows the block diagram of the dead-beat technique for the slow conditioner, in which TSs is its switching period. As the fast conditioner current is not measured, a strategy which allows the estimation of the error between the reference and the measured currents is needed. If the hybrid filter is turned on from the fast converter point of view, the set formed by the load plus the slow conditioner behaves as a new load without first, fifth, and seventh order components to correct. In a fastswitching period TSf , the new load current can be considered approximately constant, so: ΔiS + ΔiAFf = (ΔiL − ΔiHF ) ≈ 0 → ΔiS = −ΔiAFf (10) which means that the error can be calculated as the difference between the reference and the measured source currents changing the sign. Fig. 8 shows the dead-beat technique for the fast conditioner. In this converter, uAF is equal to the PCC voltage. The tracking technique requires the measurement of three additional signals, the hybrid filter currents, resulting finally in ten variables necessary for the control stage of the novel topology. V. E XPERIMENTAL R ESULTS The novel topology and control were tested on a 1.2-kVA laboratory prototype (Fig. 3). A three-phase four-wire system √was used, 50 Hz, and nominal base parameters UBL−L = 100 3 V 3φ and SB = 1200 VA, from which the base values of current, IB = 4 A, and impedance, ZB = 25 Ω, can be obtained. The nonlinear load is formed by a three-phase controlled rectifier with resistive load, RL = 48 Ω, selected so that the maximum power demanded, namely, the nominal power of the load (SL max = 1170 VA), is lower than the basis power of the system. Fig. 9 shows a photograph of the experimental multiconverter conditioner prototype, highlighting its components. The capacitance and inductance of the passive filter have been calculated so that at the fundamental frequency (equivalent capacitive behavior) the reactive power equals the maximum reactive power demand, QL1 max = 561.21 VAr (when the firing angle is 45.26◦ ), and at the fifth harmonic, the inductive and capacitive reactances are equal. Afterwards, as the inductor of the passive filter has to operate as a filter inductor in the active equipment, it has been checked that the value of LPF5 was between the design limits of LAFs , taking into account the double criteria, namely: the ripple and maximum current derivatives. The quality factor of the filter was selected so that the resistance of the filter was lower than the source impedance at the tuned frequencies. The values of the passive filter parameters are indicated in Table II, while Table III gives the parameters used in the experimental conditioner. The values of the capacitances C1 and C2 are calculated assigning a maximum ripple in the dc voltage of 3%. The control algorithms are implemented using a real-time control system DS1104 (dSPACE), composed of a Power TABLE III PARAMETERS OF THE E XPERIMENTAL C ONDITIONER Fig. 11. Operation of the multiconverter conditioner. From top to bottom: waveforms of iL , iS , iAF , iHF (5 A/div), and frequency spectra of these currents (400 mA/div; 125 Hz/div) in the same order. (a) α = 0◦ ; (b) α = 45◦ . Fig. 10. Operation of the multiconverter conditioner. From top to bottom: waveforms of iL , iS , iAF , iHF (5 A/div), and frequency spectra of these currents (400 mA/div; 125 Hz/div) in the same order. (a) α = 0◦ ; (b) α = 45◦ . PC603e/250 MHz processor and a Texas Instruments DSP TMS320F240. This platform has four multiplexed A/D inputs of 16 bits (2 μs sampling time) and four A/D inputs of 12 bits (8 ns sampling time). With this control platform, we can carry out experimental tests which only need eight inputs, (iSa , iSb , iSc , iHFa , iHFb , uPCCab , uPCCcb , and Udc ). The control strategies and tracking techniques in detail are provided in the previous two sections. For the generation of the switching signals of the inverters, two symmetric pulse width modulations were employed. These are generated by the slave DSP of the DS1104 platform from the duty cycles calculated in the tracking techniques. The switching frequency of the slow and fast conditioners was fixed to 4 and 10 kHz, respectively. The experimental results when the fast conditioner is turned on first, so that it is responsible for the dc bus control (the PI is disabled), are shown in Fig. 10 for different firing angle values. In Fig. 10(a), there is no fundamental reactive power, so the fundamental hybrid current component is null appearing only the fifth and seventh compensating currents which fully eliminate these components in the load current. The active conditioner demands fundamental current for the dc bus control and reduces the high-order components in the load current. However, in Fig. 10(b), the firing angle of the rectifier is not zero, so fundamental reactive power is demanded by the load. This power term is delivered by the slow conditioner, so that the hybrid filter current contains a fundamental component in this situation. In Fig. 11, similar experiments have been conducted, but turning on the slow conditioner first, so that the dc bus control is the task of this equipment (the PI is enabled). This is the reason why the fundamental component appears in the hybrid conditioner although no fundamental reactive power is demanded by the load [see Fig. 11(a)]. Total harmonic distortion (THD) values of the load and source currents obtained in these experimental tests are summarized in Table IV. The results fulfill the standard IEEE519 (SCR < 50) except in Fig. 10(b) due to the ripple at TABLE IV THD VALUES OF C URRENTS IN THE E XPERIMENTAL T ESTS Fig. 13. Single-phase equivalent circuits of the systems analyzed by simulation: (a) active monoconverter conditioning and (b) proposed hybrid multiconverter conditioning. VI. D ISCUSSION The hybrid multiconverter topology proposed in this paper involves an increase in the number of active and passive elements and control algorithms with more complexity, so the employment of this conditioner makes sense only if lower inverter ratings are attained, allowing its use for high-power applications. The design rate power of the inverter can be calculated as Sinv = 3Uinv Iinv Fig. 12. Operation of the multiconverter conditioner under unbalanced PCC voltages. From top to bottom: waveforms of the currents for phases a, b and c (5 A/div) and frequency spectra of these currents (400 mA/div; 125 Hz/div) in the same order. (a) iL and (b) iS . 4 kHz (switching frequency of the slow converter), which cannot be compensated by the fast converter since its switching frequency has had to be reduced to 10 kHz due to computational limitations of the control platform. To test the operation of the conditioner under unbalanced PCC voltage conditions, the phase c conductor is connected to the neutral conductor of the utility, causing + − /UPCC1 = inverse- and zero-sequence components (UPCC1 + 0 UPCC1 /UPCC1 = 50%). The load currents for each phase are shown in Fig. 12(a), while the three source currents are presented using the same axis in Fig. 12(b) so that balanced and sinusoidal source currents can be appreciated. The source current THD is improved to 2%, fulfilling the IEEE 519 limits. (11) where Uinv and Iinv are the rms values of the voltage and the current in the ac side of the inverter, respectively. It has to be noted that Uinv is not the voltage in the output of the active equipment (after the filter inductor), but the voltage in the ac terminals of the inverter. A simulation analysis was carried out to compare the inverter ratings of a conventional active monoconverter conditioner injecting the global reference compensation current, iAF,ref = iL − iS,ref (12) and a hybrid multiconverter conditioner with the reference currents proposed in (1) for the slow conditioner and in (3) and (4) for the fast one. The single-phase equivalent circuits of the two systems under comparison are shown in Fig. 13. One observes that the active filters are displayed as voltage sources in phase with an inductor, which is equivalent to the current sources in Fig. 2. Also, the inductor in the hybrid conditioner [see Fig. 13(b)] takes part in both the active and the passive filters, since it was designed for that purpose. TABLE V PARAMETERS U SED IN THE S IMULATION T EST voltage in the ac side of the inverter (since the semiconductor devices depend on this value), and this voltage is higher than the PCC voltage in the active equipment (active monoconverter and active multiconverter) due to the voltage drop in the filter inductor. TABLE VI S IMULATION R ESULTS : M AXIMUM A PPARENT P OWER OF THE I NVERTER IN THE L EAST FAVORABLE F IRING A NGLE S ITUATION R ELATIVE TO THE M AXIMUM L OAD P OWER VII. C ONCLUSION Since at high-power levels phase-controlled rectifiers are typically used in large adjustable speed drives, we selected the same load proposed in the experimental tests, a controlled rectifier supplying a resistive load, varying the firing angle of the rectifier, so that variable fundamental reactive power compensation is needed. The passive filter in the hybrid conditioner was also tuned to the fifth order. The values of the parameters used in the simulation analysis, listed in Table V, are the same as the ones collected in Tables II and III for the experimental tests, since the system and load are equal. The filter inductance of the monoconverter conditioner has been selected with the same criterion explained for the multiconverter conditioner. The study was performed under sinusoidal and balanced source voltages. For each firing angle value between 0◦ and 60◦ , the inverter ratings were calculated using (11) and drawn as a curve versus the firing angle. Since a variable load has been selected, the inverter ratings depend on the specific load conditions for each firing angle. Then, we determined the ratio between the maximum apparent power of the inverter in the least favorable firing angle situation and the maximum load power, Sinv /SL . The load power is calculated as SL = 3UPCC IL (13) being UPCC the rms value of the PCC voltage and IL the rms value of the load current. The results are summarized in Table VI. For a conventional active conditioner, this ratio is greater than 90%. With a hybrid multiconverter topology, the fast conditioner inverter ratio is below 16% and approximately 20% for the slow conditioner inverter. These results validate the usefulness of the topology for high-power levels due to the decrease in the inverter rating. The size of a classical stand-alone active filter is typically considered about the value of the THD of the load current. For example, for a load current of 40% THD, the active filter is rated 40% of the power size of the load. This low value of power ratio is due to the fact that the conditioner does not compensate variable fundamental reactive power (for example, in case of diode rectifier loads), and the rating of the active filter is calculated with the voltage, not in the ac side of the inverter, Uinv , but after the filter inductor (so the voltage equals UPCC ). However, the rating of the inverter should be calculated with the A novel hybrid multiconverter topology composed of a hybrid conditioner in parallel with an active one has been proposed in this paper. The main advantage of the topology is the decrease attained in the rating of the inverters. A simulation analysis demonstrated the proper performance of this topology at high-power levels due to the lower inverter ratings obtained as compared with the classical shunt active monoconverter topology. Collaborative control strategies were developed to split the compensation objectives between the two converters, to guarantee an efficient overall performance avoiding interferences between the two converters and to allow that one converter could help the other one in anomalous situations. Control strategies and tracking techniques for the global conditioner without the measurement of the load current were presented. Some experiments have been conducted with a 1.2-kVA laboratory prototype under different load conditions and under unbalanced voltages. R EFERENCES [1] H. Akagi, “New trends in active filters for power conditioning,” IEEE Trans. Ind. Appl., vol. 32, no. 6, pp. 1312–1322, Nov./Dec. 1996. [2] B. Singh, K. Al-Haddad, and A. Chandra, “A review of active filters for power quality improvement,” IEEE Trans. Ind. Electron., vol. 46, no. 5, pp. 960–971, Oct. 1999. [3] F. Barrero, S. Martínez, F. Yeves, F. Mur, and P. M. Martínez, “Universal and reconfigurable to UPS active power filter for line conditioning,” IEEE Trans. Power Del., vol. 18, no. 1, pp. 319–325, Jan. 2003. [4] C. Lascu, L. Asiminoaei, I. Boldea, and F. Blaabjerg, “Frequency response analysis of current controllers for selective harmonic compensation in active power filters,” IEEE Trans. Ind. Electron., vol. 56, no. 2, pp. 337– 347, Feb. 2009. [5] B. Singh and J. Solanki, “An implementation of an adaptive control algorithm for a three-phase shunt active filter,” IEEE Trans. Ind. Electron., vol. 56, no. 8, pp. 2811–2820, Aug. 2009. [6] S. Orts-Grau, F. J. Gimeno-Sales, S. Segui-Chilet, A. Abellan-Garcia, M. Alcaniz-Fillol, and R. Masot-Peris, “Selective compensation in fourwire electric systems based on a new equivalent conductance approach,” IEEE Trans. Ind. Electron., vol. 56, no. 8, pp. 2862–2874, Aug. 2009. [7] D. C. Patel, R. R. Sawant, and M. C. Chandorkar, “Three-dimensional flux vector modulation of four-leg sine-wave output inverters,” IEEE Trans. Ind. Electron., vol. 57, no. 4, pp. 1261–1269, Apr. 2010. [8] J. Miret, L. Garcia de Vicuna, M. Castilla, J. Matas, and J. M. Guerrero, “Design of an analog quasi-steady-state nonlinear current-mode controller for single-phase active power filter,” IEEE Trans. Ind. Electron., vol. 56, no. 12, pp. 4872–4881, Dec. 2009. [9] S. Srianthumrong and H. Akagi, “A medium-voltage transformerless AC/DC power conversion system consisting of a diode rectifier and a shunt hybrid filter,” IEEE Trans. Ind. Appl., vol. 39, no. 3, pp. 874–882, May/Jun. 2003. [10] S. Rahmani, A. Hamadi, N. Mendalek, and K. Al-Haddad, “A new control technique for three-phase shunt hybrid power filter,” IEEE Trans. Ind. Electron., vol. 56, no. 8, pp. 2904–2915, Aug. 2009. [11] V. F. Corasaniti, M. B. Barbieri, P. L. Arnera, and M. I. Valla, “Hybrid active filter for reactive and harmonics compensation in a distribution network,” IEEE Trans. Ind. Electron., vol. 56, no. 3, pp. 670–677, Mar. 2009. [12] S. Bhattacharya, P.-T. Cheng, and D. Divan, “Hybrid solutions for improving passive filter performance in high power applications,” IEEE Trans. Ind. Appl., vol. 33, no. 3, pp. 732–747, May/Jun. 1997. [13] L. Asiminoaei, E. Aeloiza, P. N. Enjeti, and F. Blaabjerg, “Shunt activepower-filter topology based on parallel interleaved inverters,” IEEE Trans. Ind. Electron., vol. 55, no. 3, pp. 1175–1189, Mar. 2008. [14] S. Kim and P. N. Enjeti, “A new hybrid active power filter (APF) topology,” IEEE Trans. Power Electron., vol. 17, no. 1, pp. 48–54, Jan. 2002. [15] M. D. Manjrekar, P. K. Steimer, and T. A. Lipo, “Hybrid multilevel power conversion system: A competitive solution for high-power applications,” IEEE Trans. Ind. Appl., vol. 36, no. 3, pp. 834–841, May/Jun. 2000. [16] G. R. Kamath and N. Mohan, “Series-connected, all-hybrid converters for utility interactive applications,” in Proc. IECON, 1997, pp. 726–731. [17] J. Dixon, Y. del Valle, M. Orchard, M. Ortúzar, L. Morán, and C. Maffrand, “A full compensating system for general loads, based on a combination of thyristor binary compensator and a PWM-IGBT active power filter,” IEEE Trans. Ind. Electron., vol. 50, no. 5, pp. 982–989, Oct. 2003. [18] E. Romero-Cadaval, M. I. Milanes-Montero, E. Gonzalez-Romera, and F. Barrero-Gonzalez, “Power injection system for grid-connected photovoltaic generation systems based on two collaborative voltage source invert,” IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4389–4398, Nov. 2009. [19] S. Ogasawara, J. Takagaki, H. Akagi, and A. Nabae, “A novel control scheme of a parallel current-controlled PWM inverter,” IEEE Trans. Ind. Appl., vol. 28, no. 5, pp. 1023–1030, Sep./Oct. 1992. [20] Y. Sato, T. Kawase, M. Akiyama, and T. Kataoka, “A control strategy for general-purpose active filters based on voltage detection,” IEEE Trans. Ind. Appl., vol. 36, no. 5, pp. 1405–1412, Sep./Oct. 2000. [21] L. Asiminoaei, C. Lascu, F. Blaabjerg, and I. Boldea, “Performance improvement of shunt active power filter with dual parallel topology,” IEEE Trans. Power Electron., vol. 22, no. 1, pp. 247–259, Jan. 2007. [22] L.-P. Wong, D. K.-W. Cheng, M. H. L. Chow, and Y.-S. Lee, “Interleaved three-phase forward converter using integrated transformer,” IEEE Trans. Ind. Electron., vol. 52, no. 5, pp. 1246–1260, Oct. 2005. [23] P.-T. Cheng, S. Bhattacharya, and D. Divan, “Control of square-wave inverters in high-power hybrid active filter systems,” IEEE Trans. Ind. Appl., vol. 34, no. 3, pp. 458–472, May/Jun. 1998. [24] P.-T. Cheng, S. Bhattacharya, and D. Divan, “Operations of the dominant harmonic active filter (DHAF) under realistic utility conditions,” IEEE Trans. Ind. Appl., vol. 37, no. 4, pp. 1037–1044, Jul./Aug. 2001. [25] M.-R. Rafiei, H. A. Toliyat, R. Ghazi, and T. Gopalarathanam, “An optimal and flexible control strategy for active filtering and power factor correction under non-sinusoidal line voltages,” IEEE Trans. Power Del., vol. 16, no. 2, pp. 297–305, Apr. 2001. [26] M. I. Milanés, E. Romero, and F. Barrero, “Comparison of control strategies for shunt active power filters in three-phase four-wire systems,” IEEE Trans. Power Electron., vol. 22, no. 1, pp. 229–236, Jan. 2007. [27] Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std. 519-1992, 1993. [28] M. I. Milanés, E. Romero, A. Rico, V. Miñambres, and F. Barrero, “Novel method for synchronization to disturbed three-phase and single-phase systems,” in Proc. ISIE, 2007, pp. 860–865. María Isabel Milanés-Montero (S’03–M’06) was born in Badajoz, Spain, in 1974. She received the M.Sc. degree in industrial engineering and the Ph.D. degree from Universidad de Extremadura, Badajoz, Spain, in 1997 and 2005, respectively. In November 1998, she joined Universidad de Extremadura as an Assistant Professor. She is currently with the Power Electrical and Electronic Systems Research Group. Her major fields of interest include power quality, active and hybrid power filters, renewable energy sources control, and electrical machine drives. Enrique Romero-Cadaval (S’03–M’05–SM’10) was born in Villafranca de los Barros, Badajoz, Spain, in 1968. He received the M.Sc. degree in electronic industrial engineering from Escuela Técnica Superior de Ingeniería, Universidad Pontificia de Comillas, Madrid, Spain, in 1992 and the Ph.D. degree from Universidad de Extremadura, Badajoz, Spain, in 2004. He is a full Professor in power electronics at Universidad de Extremadura. He is currently with the Power Electrical and Electronic Systems Research Group. His research interests are power electronics, power quality, electromagnetic inference, active power filters, and renewable energy sources control. Fermín Barrero-González (M’95–SM’10) was born in Puebla de la Reina, Badajoz, Spain, in 1959. He received the M.Sc. degree in electrical engineering from Universidad Politécnica de Madrid, Madrid, Spain, in 1984 and the Ph.D. degree from The Universidad Nacional de Educación a Distancia, Madrid, in 1995. He is a full Professor in electrical engineering at Universidad de Extremadura, Badajoz. He is currently coordinating the Power Electrical and Electronic Systems Research Group. His research interest areas are power electronics in the power system, flexible ac transmission systems, active power filters, and electrical machine drives. Dr. Barrero-González is a member of the IEEE IAS Industrial Static Converters Committee, European Working Group.