eLAN Fire Alarm Product Guide

advertisement

FIRE

DETECTION

SYSTEMS

eLAN Fire Alarm Product Guide

eLAN System

The unique, VES eLAN system is a total hardware and software solution that can provide dealers with a complete set of tools and products to grow and manage the fire alarm installation, maintenance and monitoring business. The eLAN product range and software tools provide real added value and cost benefits for installers and their customers along with professional, consistent and accurate reporting of the service history for the entire life of the installation.

Product range: eSP Business Suite -

Full suite of software applications eLAN Panel -

Analog Addressable Fire Control Panel (2 or 4 SLC loops) eLAN RS Panel -

Analog Addressable Fire Control Panel (1 or 2 SLC loops)

VESNet -

Communication cards eVIEW -

Analog Addressable Serial Annunciator eMATRIX -

Configurable floor plan Graphical Annunciators

SLC Devices -

Optical, heat and multi sensors. Pull stations and I/O modules

Annunciation Devices -

Full line of Horns & Strobes, Wall & Ceiling

Ancillary Items -

Fire Document Enclosure and Ancillary Enclosure

VoiceAlert -

Voice evacuation system

eSP Business Suite

The unique eSP Business Suite is the most powerful differentiator between VES and other manufacturers. eSP is a web-based service, allowing for complete control of your installations. The VES Dealer can use eSP for quoting, ordering and programming the system from start to finish.

Quick Quote ™

An embedded module of eSP, Quick Quote is your bidding, tracking, financial analysis and parts ordering tool. Quick Quote keeps all of your information – parts, people, prices and more – in one secure location. Like every other module of eSP, Quick Quote is available to your employees from anywhere with an ordinary web browser.

eSP Discovery

Discover the ease, power and savings of remote programming with eSP Discovery. From a web browser, anywhere in the world, you can configure the eLAN panel or network with easy “Drag & Drop” style programming. All of your systems programming is safe, secure and backed-up in a centralized location, with redundant internet pathways. No more lost programs. No more cables or modems to maintain. You can even collaborate with co-workers anywhere in the world, via the web, to program a system. When you’re ready to download, just queue it up from anywhere with internet access. eSP Discovery now also supports Upload from an auto learned or existing location

Virtual Panel

With Virtual Panel, you’re never out of touch with your eLAN system.

A singular achievement in the industry, Virtual Panel shows you the exact display from the front of the panel with a Media Gateway®.

Virtual Panel works over a standard web browser from anywhere on the Local Network. This makes it an ideal solution for command centers, security offices and facilities managers. Media Gateway or

Ether/DACT.

eLAN System with eSP Business Suite

Overview

The eLAN system from VES is a complete, UL 9th edition and FM listed range of hardware and software tools that enables dealers to design, bid, install, service and maintain fire alarm systems using the unique and powerful eSP software suite eLAN systems are scalable from stand-alone, singlepanel systems with 126+ devices, to fully supervised, fault tolerant networked systems utilizing up to 127 panels and over 100,000 points of protection.

Because of the technological advances of our selfconfiguring VESNet network, you can now program a complete networked system as if it’s a single panel.

Easy “Plug & Play” networking allows the network to be programmed remotely with no special software or onsite computer.

The VES eSP Business Suite breaks the technological and training barrier to simple and secure fire systems.

All of your data: quotes, programming, event logs, device sensitivity readings” and much more is available anytime, on the web, from anywhere. No software or special hardware to maintain and upgrade.

eLAN™ System Hardware

eLAN Analogue Addressable Panels with support for

1, 2 or 4 SLC loops for over 500 points per panel with a single hazard networked releasing capability. SLC loop communication uses standard cable. Twisted pair or shielded is not required. Inter-panel networking uses standard CAT-5 cabling or optional Fiber Optics.

World class UL Listed range of detection devices include self-calibrating optical and multisensors, heat sensors, pull stations and input/output modules.

Notification devices include a full line of synchronized horns and strobes.

VESNet networking allows for easy-to-install Class A communications between up to 127 control panels and remote LCD annunciators.

VESNet™ Networking – The Power of Communication

Each eLAN panel can be configured with one of three communications cards:

Media Gateway®, the nerve center of the networked system.

NIC, for networked remote panels.

Ether/DACT, for stand-alone, single panels.

All inputs and outputs on all eLAN panels are fully programmable, enabling an entirely integrated fire system over very large areas.

Integrated Modem/DACT on the eLAN RS panel.

Complex “Cause & Effect” relationships are easily programmed, even between panels.

No need to visit each panel on the network to configure it. The entire VESNet network is programmed at the same time, saving hours of on-site programming time.

The powerful communications capability of the eLAN system can cut the everincreasing costs of service calls by allowing the entire system to be diagnosed remotely.

Any number (up to the maximum number of nodes) of discrete VESNet LCD

Networked Displays can be added, providing comprehensive indication at convenient locations.

eLAN System Schematic

eLAN

Control

Panel eLAN RS

Control

Panel

Annunciator eLAN

Control

Panel

Loop 1

Loop 2

Loop 3

Loop 4

Monitoring Center

Reduced

Costs

Internet Access to eSP Business Suite and

Access to all Installations

Annunciator

Telc o eLAN

Control

Panel

Media

Gateway eVIEW

Annunciator

24V DC eMATRIX

Office Buildings

Hospitals

Schools / Universities

Hotels

Improved

Service

Dealer

Quoting

Parts Ordering

Maintain Customers

View Service Schedules

View Inspection History

Produce and Store Site Configurations

Configure Systems

Virtual Panel

Retrieve Event Log

View Analog Value of Devices

Apartment Complexes

eLAN

Control

Panel eLAN RS

Control

Panel

Annunciator eLAN

Control

Panel

Loop 1

Loop 2

Loop 3

Loop 4

Monitoring Center

Reduced

Costs

Internet Access to eSP Business Suite and

Access to all Installations

Annunciator

Telc o eLAN

Control

Panel

Media

Gateway eVIEW

Annunciator

24V DC eMATRIX

Office Buildings

Hospitals

Schools / Universities

Hotels

Improved

Service

Dealer

Quoting

Parts Ordering

Maintain Customers

View Service Schedules

View Inspection History

Produce and Store Site Configurations

Configure Systems

Virtual Panel

Retrieve Event Log

View Analog Value of Devices

Apartment Complexes

eLAN

Analog Addressable Fire Control Panels

(2 or 4 Loops)

2 Loops

VF1220

No Communicator

VF1221

W/ Media Gateway

VF1222

W/ NIC Card

VF1223

W/ Ether/ DACT

4 Loops

VF1240

No Communicator

VF1241 W/ Media Gateway

VF1242

W/ NIC Card

VF1243 W/ Ether/ DACT

The VF1240 and VF1220 analog addressable FACP with networked releasing, supports 2 or 4 SLC loops for a total of 500 points with a single hazard releasing capability. SLC loop communications uses standard cable– twisted pair or shielded is not necessary while inter-panel networking

(VESNet) uses standard CAT5 cabling.

The panel may be configured with various communication cards; VF1241 and VF1221 include a

Media Gateway®, VF1244 and VF1224 include an Ether DACT or VF1242 and VF1222 include a NIC

(Network Interface Card). Communications options support remote programming, central station monitoring, Virtual Panel, and networking.

The Panel can be configured as a stand alone panel with just a few devices for a small building or

Releasing System.It can also operate as the building system and Releasing System and can be part of a network with a total of 127 nodes serving a multiple building campus or a very large facility.

Auto Learn capability provides a convenient method to troubleshoot new installations before final programming is loaded and remote manufacturer assistance is also available to diagnose and help correct configuration options.

UL 864 9th Edition listed

Multi-loop (4) analog-addressable

126 primary points per loop

500 relationships per network with 2,000 inputs and 2,000 outputs

500 primary points per panel expandable up to 800 points per panel when using devices with sub-points

Up to 10,000 ft. wiring length on SLC loop

127 Panels on a Media Gateway®/ NIC system programmed as a single network

Configurable through keypad or remotely, via eSP

Programmable Inputs – 3

Programmable relays – 5

Supervised Powered Outputs – 3

Programmable Notification Appliance

Circuits: 4

Power per NAC: 1.6 Amps Max

Programmable outputs on SLC loop

Programmable Function button on front display

Fire Drill button on front display

Day and night sensitivity settings

Power Supply: 5.25 Amp, regulated & integrated LCD Display: 8x40

Zonal Mode: Annunciation by zone w/o individual relationships

Panel Ring Modes: Common, Zonal, Stage 2

NAC Outputs programmable as Continuous,

March, Temporal

Program Zones as AND, OR, or Any Two

(Cross Zone)

Battery size: Up to 17 Ah in standard enclosure; up to 52 Ah with external cabinet

Access levels: 3

Access key switch: Yes

Recognized for use in High Rise

One man walk test – Fire Test Mode

Available with semi flush trim ring

Available in Red (RAL 3002) or Gray

(RAL 7035)

All VES controls are

UL 9th Edition listed and FM approved

APPROVED

eLAN RS

Analog Addressable Fire Control Panels

(1 or 2 Loops)

1 Loop

VF0950

No Communicator

VF0951

W/ Media Gateway

VF0952

W/ NIC Card

VF0953

W/ Ether/ DACT

VF0954

W/ Integrated Modem/ DACT

2 Loops

VF0960

No Communicator

VF0961

W/ Media Gateway

VF0962

W/ NIC Card

VF0963

W/ Ether/ DACT

VF0964

W/ Integrated Modem/ DACT eLAN RS is a versatile range of open protocol fire alarm control panels compatible with existing eLAN fire alarm panel technology.

Available with one or two detection loops capable of hosting up to 250 devices. eLAN RS uses leading edge microprocessor based electronics to provide a flexible control system with high reliability and integrity.

Suitable for all small to medium sized fire detection systems, eLAN RS control panels can be expanded and networked to become part of much larger systems if the need arises, therefore providing a future proof solution for any installation.

With its large graphical display and ergonomic button and indicator layout, the eLAN RS control panel is simple and straightforward to understand for installers, commissioning engineers and end users alike.

Available in Red or Gray

2 programmable NAC circuits

3 programmable relays

5.25A power supply

Large graphic display

Real time clock

Up to 512 additional programmable I/O via I/O modules

Powerful, network wide cause and effects

Sensitivity adjustment and Drift Compensation

Can be networked with eLAN control panels

Compatible with eVIEW Annunciator

Same look and feel as eLAN range

Stores 1000 last events in event log

DACT connection available

Compact, stylish enclosure

VESNet

Communication and

Network Options

Communications

Installation

One Communications Card per Panel

1 Plug-in Ribbon Cable, 2 CAT5 wired to

RJ-45 VESNet connectors

2 RJ-11 Telephone Jacks

1 RS-232 cable to panel

Ethernet RJ-45 on Media Gateway®

Powered from Panel

VESNet communication is only available on the Media Gateway® and NIC.

Telephone jacks are only available on the Media Gateway® and Ether/DACT.

SIGNALING

LISTED

FIRE ALARM SUBASSEMBLY

3PBS

LBL-000133

A

B

Heartbeat

J8

POWER

Ethernet

VNet A

VNet B

Comm Active

Comm Fault

REFER TO MEDIA GATEWAY INSTALLATION

MANUAL WITH RELEASING VF1627-00

Rev. E02.XX

J7

DATA

VF1150 Media Gateway® with Releasing

Supports networking, remote monitoring, virtual display and remote programming and remote displays.

000AFD0002FB

VES, LLC

620 ALLENDALE ROAD, SUITE 175

KING OF PRUSSIA, PA 19406

610-992-0400

MAXIMUM POWER REQUIREMENT: 24VDC @ 115mA

FOR INDOOR DRY USE ONLY

JACK J3 VESNet IS SUPERVISED AND POWER- LIMITED

JACK J5 ETHERNET IS UNSUPERVISED AND POWER- LIMITED

THE MEDIA GATEWAY WITH RELEASING CONTAINS

A DACT AT JACK 1 TELCO LINE 1 AND LINE 2.

JACK 1 TELCO LINE 1 AND LINE 2 ARE SUPERVISED

TESTED TO COMPLY WITH FCC STANDARDS

THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.

OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:

(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND

(2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,

INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.

Industry Canada Electromagnetic Compatibility, ICES-003:

THIS CLASS A DIGITAL APPARATUS COMPLIES WITH CANADIAN ICES-003.

CET APPAREIL NUMERIQUE DE LA CLASSE A EST CONFORME A LA NORME

THIS DEVICE COMPLIES WITH PART 68 RULES

FCC REG. NO.: VESAL00BVF10xx-xx

REN = 00B

JACK TYPE: RJ11C

TELCO

PRI

Line 1

SEC

Line 2

SIGNALING

LISTED

FIRE ALARM SUBASSEMBLY

3PBS

LBL-000133

A

B

Heartbeat

J8

POWER

VNet A

VNet B

Comm Active

Comm Fault

REFER TO NETWORK INTERFACE CARD

(NIC) INSTALLATION MANUAL WITH

RELEASING VF1629-00 Rev. E02.XX

VF1151 Network Interface Card

(NIC) with Releasing

Used for inter-panel networking and interfaces to other systems.

000AFD0002FB

VES, LLC

620 ALLENDALE ROAD, SUITE 175

KING OF PRUSSIA, PA 19406

610-992-0400

MODEL NO.: VF1151-00

NETWORK INTERFACE CARD (NIC)

WITH RELEASING

MAXIMUM POWER REQUIREMENT: 24 VDC @ 80 mA

FOR INDOOR DRY USE ONLY

JACK J3 VESNet IS SUPERVISED AND POWER- LIMITED

THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.

OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:

(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND

(2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,

INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.

Industry Canada Electromagnetic Compatibility, ICES-003:

THIS CLASS A DIGITAL APPARATUS COMPLIES WITH CANADIAN ICES-003.

CET APPAREIL NUMERIQUE DE LA CLASSE A EST CONFORME A LA NORME

NMB-003 DU CANADA.

THIS DEVICE COMPLIES WITH PART 68 RULES

FCC REG. NO.: VESAL00BVF10xx-xx

REN = 00B

JACK TYPE: RJ11C

SIGNALING

LISTED

FIRE ALARM SUBASSEMBLY

3PBS

LBL-000133

Heartbeat

J8

POWER

Ethernet

VNet A

VNet B

Comm Active

Comm Fault

REFER TO MODEM-DACT ETHERNET

INSTALLATION MANUAL WITH RELEASING

VF1628-00, Rev. E02.XX AND

MODEM-DACT CONFIGURATION AND

REPAIR MANUAL VF1624-00, Rev.E02.XX

J7

DATA

000AFD0002FB

VES, LLC

620 ALLENDALE ROAD, SUITE 175

KING OF PRUSSIA, PA 19406

610-992-0400

MODEL NO.: VF1153-00

MODEM-DACT ETHERNET

WITH RELEASING

MAXIMUM POWER REQUIREMENT: 24 VDC @ 115 mA

FOR INDOOR DRY USE ONLY

JACK J5 ETHERNET IS UNSUPERVISED AND POWER- LIMITED

JACK 1 TELCO LINE 1 AND LINE 2 ARE SUPERVISED

TESTED TO COMPLY WITH FCC STANDARDS

THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.

OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:

(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND

THIS CLASS A DIGITAL APPARATUS COMPLIES WITH CANADIAN ICES-003.

CET APPAREIL NUMERIQUE DE LA CLASSE A EST CONFORME A LA NORME

NMB-003 DU CANADA.

THIS DEVICE COMPLIES WITH PART 68 RULES

FCC REG. NO.: VESAL00BVF10xx-xx

REN = 00B

JACK TYPE: RJ11C

TELCO

PRI

Line 1

SEC

Line 2

VF1153 Ether/DACT

Used for single panel installations.

Supports remote monitoring, virtual display, and remote programming.

Standard Features

Dual-line digital communicator with line seizure on Media Gateway® and

Modem DACT

33.6 Kbps modem for panel downloading

Provides network-wide programming with remote and local management

Remote programming via eSP

Discovery

Transmits in SIA (SIA 8 and SIA 20)

Digital Communications standard (300 bps) and Contact ID communication format

All nodes report through a single Media

Gateway® to a central station and data center

VESNet configurable for Class A or B networking

Communication speed of 115 Kbps on VESNet™ and 10BaseT Ethernet interface

Built-in Firewall with messaging through LAN connections always from within VESNet

Maintenance message logging

Virtual Panel ready with Media

Gateway®

Built-in Web Server in the Media

Gateway® for displaying Virtual Panel

Installation diagnostics at startup through eSP

Onboard Motorola 32 bit, 66 MHz

RISC processor

RJ-45 (Ethernet) port for LAN connection

2 RJ-45 VESNet™ ports for network connections using standard CAT

3,5,5e,6 cable

2 RJ-11 Telco ports for phone lines for connection to RJ-31X or RJ-38

Up to 126 Fire Nodes can be installed on VESNet™

Up to 2,000 feet between nodes on

VESNet™

Installation diagnostics at startup

eVIEW

Serial LCD Annunciator

VF1172-10 Red

VF1172-40 Gray

The eVIEW fire alarm annunciator provides a simple and convenient method of extending the controls and indications of the Elite fire alarm control panel to other locations.

The large, graphic LCD display and high brightness LED indicators duplicate the indications on the Elite fire alarm control panel at up to 15 additional locations via a simple, two-wire serial data connection.

Available in Red or Gray

Up to 15 annunciators can be connected to each eLAN or eLAN RS fire control panel

Large 320 Character graphic display

High brightness LED indications

Internal Sounder

Replicates all panel controls

Simple, two-wire serial connection plus 24VDC

Low power consumption

Multi language options

Connection supervised by eLAN fire control panel

Flush Mounting Kit available (VF1173-10 Red, VF1173-40 Gray)

eMATRIX

Configurable Floor Plan

Mimic Annunciator

The eMATRIX system uses flexible, optic light guides to illuminate areas on a floor plan, laid over a high resolution grid. This unique system dispenses completely with wiring and enables indicators to be moved, removed or added on site without the need for any wiring.

All indicators can be configured to operate upon any event type and at point, zone or group level via the powerful and intuitive eSP Discovery.

Available in Red or Gray

Up to 504 LED’s can be controlled from any eLAN panel

Select up to 12 printed colors (not including background and building outline)

Available in a range of standard enclosures to suit any applications

Custom sized units can be made upon request

Choice of Red, Green or Yellow LED’s eMATRIX can easily be re-configured or upgraded on site with minimal cost and effort

Special Order Item

Enclosure sizes:

AM2: 14.5” Wide x 12.2” High x 3.5” Deep, Max. number of LED’s = 40

AM3: 14.5” Wide x 18.9” High x 4.25” Deep, Max. number of LED’s = 72

AM4: 14.5” Wide x 24” High x 5” Deep, Max. number of LED’s = 88

VF1171

16 Channel Input/Output Board

To add more I/O capablity to the extensive options already offered by the eLAN control panel, up to thirty two, sixteen channel I/O boards may be connected.

When using a simple two wire RS485 communications protocol, these boards may be mounted locally to the control panel or distibuted on a bus up to 3,900 feet long by using a suitable cable.

The flexibility of these boards is further enhanced by the fact that each of the channels is configurable as either an input or and output.

16 channels

Each channel configurable as input or output

Inputs opto-isolated

Outputs open collector transistor

Simple 2 wire connection to control panel

Up to 32 boards supported per panel (512 Input/Output Channels)

Inputs and outputs configurable as per field devices

Full cause and effects on all inputs and outputs

Multi drop RS485 communications

Can be used with other eLAN I/O modules on the same panel

VF3033/ VF3034

Single Action and Dual Action

Addressable Pull Station

The VF3033 and VF3034 series pull stations are operated by pulling the handle marked “PULL” on the front of the station as far down as it will go. At that point, the station will lock in place and is easily visible from up to

50 feet. The activation handle is reset by opening the station with the key, placing the handle in the normal upright position and relocking the station.

On the dual action, the push bar rotates inward allowing the “PULL” handle to be grasped and operated by a single hand. A VF5608 Mini Switch Monitor is an integrated component of this assembly allowing user flexibility in assigning its own unique Signaling Line Circuit (SLC) loop address.

Single or Dual Action

Gold Plated Alarm Contacts

Surface or Weatherproof back boxes available.

Status LED to indicate device operational state

SLC wiring easily attached with screw compression plates

VF5600

Ionization Smoke Sensor Head

5 programmable response modes

Drift compensation

Address is set by X-Pert card and is stored in base

Two Status LEDs for 360° visibility of alarm status

VF5601

Photoelectric Smoke Sensor Head

5 programmable response modes

Drift compensation

Two Status LEDs for 360° visibility of alarm status

Address is set by X-Pert card and is stored in base

VF5602

Heat Detector Head

5 programmable response modes

Address is set by X-Pert card and is stored in base

Fixed point or rate of rise function

Two Status LEDs for 360° visibility of alarm status

Programmable Range 135° - 190° (F)

VF5603

Multisensor Detector Head

5 programmable response modes

Combines photo smoke and heat value for enhanced detection performance and false alarm reduction

Address is set by X-Pert addressing and is stored in the sensor base

Rate of rise heat option

Drift compensation

Two Status LEDs for 360° visibility of alarm status

VF5632

E-Z Fit Base

The E-Z fit base is a low profile 6” mounting base for detectors

High degree of protection against unauthorized removal

VF4990

Aux Powered Sounder Base

Compatible panel silence functions

Sync network “self tests” to ensure synchronized output if “upstream” sync signal is lost

Sounders will operate in “failsafe” mode if the sync network is compromised

Continuous or Temporal output with Sync module available to sync multiple temporal units

VF5635

Low Power Relay Base

The VF5635 Low Power Relay Base incorporates a low power relay to control field equipment such as automatic door closers

Gives a set of voltage free contacts controlled by the remote output of a detector

Draws negligible current

VF5633

Isolating Base

The VF5633 Isolating Base sense and detects short circuit faults on SLC loops

Up to 20 devices may be installed between isolating bases

XPERT addressing

Accommodates a sensor head.

VF5640

Blank XPERT Card

A Universal address card supplied with all bases. Using a coding guide, pips are removed to set the address of the inserted detector.

Simplifies and speed up installation and commissioning

Used patented, proven technology

Address remains the same, no matter how often detectors are replaced

VF5663

Input Module

Three input states - “normal”, “fault” and “alarm”

One visible LED

Fast response time

Mounts on 2-gang or 4x4 box

VF5664

Dual Input Module

Three input states per input - “normal”, “fault” and “alarm”

Two visible LEDs

Fast response time

Mounts on 2-gang or 4x4 box

2 Individual inputs on one module.

VF5665

Input/ Output Module

Provides a single-pole output, supervised input and a non-supervised input

Visible LED

Fast response time

Mounts on 2-gang or 4x4 box

VF5666

Supervised Output Module

Allows sounders to be operated continuously or be pulsed, 1 second on, 1 second off

Can also be used for public address speakers

Visible LED

Can be used for remote NAC circuits or boosters.

VF5667

Relay Output Module

The Relay Output Module provides a single 2-pole changeover relay

Can be placed anywhere on loop

Visible LED

VF5608

Mini Input Module

Designed for use where space is limited

LED status indication (Yellow - Fault, Green - Polling, Red - Alarm)

DIN Rail Mountable

VF5660

Pigtail Input Module

Three input states - “normal”, “fault” and “alarm”

LED depicting module status condition

Designed to fit into equipment with limited space

Monitors equipment where a fast response is required

Class A or Class B input capability

VF5605

Isolator

The VF5605 Isolator is placed at intervals on the loop and ensures that, in the case of a short circuit, only the section between the isolators will be affected. When the short circuit is removed, the isolators automatically restore power and data to the isolated section.

Detects wiring short circuits using patented technology

Minimizes disruption from short circuits

Automatic de-isolation on short circuit removal

Up to 20 devices may be installed between isolators

VF5634

Isolator Base

The VF5634 Isolator Base is unique and designed to only accept the Isolator

Only accepts Isolators

VF4992

Duct Smoke Detector

Patent pending “Test Port Valve” allows for aerosol smoke testing without cover removal

Clear cover fitted with four captive “No-Tools Required” thumbscrews

In-line terminal block for easier wiring

More wiring space than competitive models

Built in alarm relay test switch Unit includes green pilot and red alarm visual indicators

External mounting tabs do not require cover removal to install

One set of 15A form “C” alarm contacts

VF4672-30

VF4670-10

VF4674-10

VF4675-30

Horns and Strobes

The VES series of notification appliances feature a sleek modern design that will please building owners with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes, voltage test points,

12/24 VDC operation, universal mounting base and multiple mounting options for both new and retrofit construction.

Sleek modern aesthetics

Finger slide switches

Voltage test points

Multiple voltages

3 audible settings 90, 95, 99 dB

8 Candela settings:

Wall - 15 / 1575 / 30 / 75 / 95 / 110 / 135 / 185

Ceiling - 15 / 30 / 60 / 75 / 95 / 115 / 150 / 177

Universal mounting base -

Ceiling and wall mounts to 5 backbox types

Environmentally friendly - Low current draw

Compatible with UL “Regulated Voltage” using

VF4670-10 Horn Strobe - Wall - Red

VF4670-30 Horn Strobe - Wall - White

VF4671-10 Horn Strobe - Ceiling - Red

VF4671-30 Horn Strobe - Ceiling - White

VF4672-10 Strobe - Wall - Red

VF4672-30 Strobe - Wall - White

VF4673-10 Strobe - Ceiling - Red

VF4673-30 Strobe - Ceiling - White

VF4674-10 Horn - Wall - Red

VF4674-30 Horn - Wall - White

VF4675-10 Horn - Ceiling - Red

VF4675-30 Horn - Ceiling - White filtered DC or unfiltered VRMS input voltage

VF071x

Fire Document Enclosure

Matches design and color scheme for standard Elite control panels

Standard enclosure holds 50 sheets of paper, deep version holds 100 sheets

Key lockable, Tamper included

Designed for versatility

Choice of small or large capacity enclosure in Red or Gray

The “Doc Box” also doubles up as a Key Box, providing 7 easily accessible formed key hooks

VF0710-xx* Standard

VF0711-xx* Deep

VF0712-xx* Standard w/Tamper

VF0713-xx* Deep w/Tamper

*xx = 10 (Red) or 40 (Gray)

VF073x

Ancillary Enclosure

The Ancillary Enclosure is designed to provide an organized and secure mounting enclosure for I/O cards and SLC devices. The Ancillary Enclosure is manufactured in three different sizes, two different colours and with a tamper option.

The Ancillary Enclosure is customized with mounting requirements and multiple conduit entries to fit module configurations depicted in the table below.

A combination of SLC devices, I/O boards, din rail and PSU can be achieved.

Available in Red (-10) or Gray (-40).

VF0730-xx* 14.5”W x 12.2”H x 3.4”D

VF0731-xx* 14.5”W x 18.9”H x 4.25”D

VF0732-xx* 14.5”W x 24”H x 5”D

* xx = 10 (Red) or 40 (Gray)

Chassis plate part number:

VF0752-00 Auxiliary Enclosure Device Plate, Large Enclosure

VF0751-00 Auxiliary Enclosure Device Plate, Medium Enclosure

VF0750-00 Auxiliary Enclosure Device Plate, Small Enclosure

VoiceAlert

Voice Evacuation System

VF9700 Master Panel

The VES VoiceAlert High Rise Evacuation System operates in conjunction with the eLAN Fire Alarm

Control Panel (FACP) in a building to provide automatic response to life safety emergencies. The

VoiceAlert system includes all necessary features to provide an effective voice evacuation system. The

VoiceAlert can be custom configured to satisfy the needs of any high rise application.

True Multiplex 6 Channel Distributed Audio

Modular System - components added as needed

Integrated 2 Channel Digital Message Repeater

Live Microphone Page to any zone

Fast RS-485 Communication Protocol

Easy Installation and Operation

Natural Sound Voice Recordings

Built in Alarm and Alert Signals

Up to 4 Minute Message Capacity

Works with 12VDC or 24VDC Fire Alarm Panel

Listed with for use with the eLAN FACP

3 Minute Message Restart on Microphone Key

Fully Supervised

Operation -

Basic System includes

Master Panel (VF9700)

Master Mic Control

16 switch control points

Dual Channel DMR

High speed communication loop

Distributed Panel (VF9755)*

4 Output Zones (may be configured for 8)

Dual Channel Audio Interface

Dual Channel Amplification

Optional

Integrated Fire Phone

Maximum System Configuration

Up to 256 Distributed Panels (VF9755)

Up to 2028 monitor and control points

VF9775 Distributed Panel

Master Panels

VF9720 16 Zones

VF9740 16 Zones with Fire Phone

VF9722 32 Zones

VF9742 32 Zones with Fire Phone

VF9724 48 Zones

VF9744 48 Zones with Fire Phone

VF9726 64 Zones

VF9746 64 Zones with Fire Phone

VF9728 80 Zones

VF9748 80 Zones with Fire Phone

VF9730 96 Zones

VF9750 96 Zones with Fire Phone

VF9751 112 Zones

VF9752 128 Zones

*

Number of distributed panels to be determined by building specifications

Distributed Panels - Single Channel

VF9760 25Watt

VF9778 25Watt with Fire Phone

VF9762 50Watt

VF9768 50Watt with Fire Phone

VF9764 100Watt

VF9770 100Watt with Fire Phone

VF9788 100Watt, 16 Audio Channels with Fire Phone

Distributed Panels - Dual Channel

VF9774 50Watt

VF9780 50Watt with Fire Phone

VF9776 100Watt

VF9782 100Watt with Fire Phone

VF9798 200Watt , 4 Audio Channels with Fire Phone

VF9793 200Watt, 16 Audio Channels with Fire Phone

VoiceAlert

Fire Phone Equipment

Fire Phone accessories give the VMX system two-way communication capability. Fire Phone jacks are mounted on a single gang plate. Fixed telephone and warden stations are available in surface/ semi-flush mount cabinet with a thumb-turn-latch.

VF9512

Telephone Jack

VF9511

Portable Handset

Brushed Stainless Steel

Single Gang Plate

VF9514

Fire Phone Station

Coil cord / Thumb Turn Latch

Available in Red or Gray

Size: Surface / Semi-Flush Mount

12-3/4 x 7-1/4 x 3-3/4” h-w-d

Color - Red

6 mount in VF9510 cabinet

Can be used with telephone jack plate (VF9512)

VF9517

Warden Station

Armored cable / Thumb Turn Latch

Available in Red or Gray

Size: Surface / Semi-Flush Mount

12-3/4 x 7-1/4 x 3-3/4” h-w-d

VF9510

Telephone Cabinet

Holds 6 VF9511

Available in Red or Gray

Size: Surface / Semi-Flush Mount /

Key Lock 27 x 14-1/2 x 4” h-w-d

Speakers and Speaker/Strobes

VES offer a comprehensive range of speakers and speaker strobes including wall mounted, ceiling mounted and vandal resistant versions. All models feature high efficiency sound output, with dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 2 watts. They are designed to provide a sleek, aesthetic appearance for emergency voice/alarm communications systems. VES speakers and speaker strobes mount to standard electrical boxes for ease of installation, they are also available as a surface mounted option.

Approvals: UL, FM, MEA, CSFM, BFP

ADA/NFPA/ANSI compliant

Field selectable candela settings

Field selectable taps for 25 or 70

VRMS operation from 1/8 - 2 watts

High efficiency design for maximum output at minimum wattage

Fast IN/OUT screw terminals

Available in Red or Off White

VF4405-10 Wall Speaker 2 Watt Red

VF4405-30 Wall Speaker 2 Watt White

VF4409-10 Ceiling Mount Speaker 2 Watt Red

VF4409-30 Ceiling Mount Speaker 2 Watt White

VF4820-10 Wall Speaker/Strobe 2 Watt Red

VF4820-30 Wall Speaker/Strobe 2 Watt White

VF4829-10 Ceiling Speaker/Strobe 2 Watt Red

VF4829-30 Ceiling Speaker/Strobe 2 Watt White

For a full list of units please see individual data sheets

Distributed by:

FIRE

DETECTION

SYSTEMS

VES LLC , 620 Allendale Road, King of Prussia, PA. 19406

Tel: 800.270.3066 (Toll free) Fax: 610.992.3380

E-mail: info@ves-network.com Web: www.ves-network.com

Version 1.01 1/2010.

Download