XLS80e Intelligent Fire Alarm Control Panel SPECIFICATION DATA FEATURES • Certified to EN54 parts 2 and 4 • Drift compensation • Automatic or Manual “Loop Learn” options • “Walk Test” function by zone for efficient commissioning • On screen “test” tally (tested/untested count) for devices in zone walk test • Auto-program option • Automatic time control functions by day of week for “Control-by-Event” (CBE) • 255 Zone capacity per panel • Full configuration edit capability from panel or PC DESCRIPTION The XLS80E Intelligent Fire Alarm Control Panel provides a cost-effective platform for a fire alarm system that is both flexible and expandable. The panel offers system designers and end users a technically sophisticated range of facilities and functions whilst maintaining ease of programming, installation, and operation. The XLS80E control panel is fully compatible with the full range of Honeywell’s TC800 Series analogue addressable sensors, control and monitor modules. This makes the XLS80E the perfect solution for retrofit jobs as well as for new projects. Each panel can support up to 8 analogue addressable loops and each loop can support up to 99 TC800 Series analogue sensors and 99 TC800 Series modules. This gives the XLS80e a panel a maximum capacity of 1584 points.. Full function repeater panels complements the XLS80E product range. System The XLS80E fire panel will control a combination of up to 99 heat, smoke or multi-criteria sensors on each loop and a combination of 99 call points, monitor, control and conventional zone interface modules and sounders per Honeywell TC800 Series loop. Depending on the arrangement of user specified zones, isolation modules may also be added to the system although they are not required at loop ends. The XLS80e controllers, peripheral devices and all the system fields components e.g. sensors and modules are approved to meet with the requirements of EN54 The XLS80E can also be networked with other XLS80E controllers and repeaters in a “Peer to Peer” architecture. Furthermore, if a graphic based PC front end (GUI) is required, the XLS80e panels can be connected to Honeywell's Enterprise Building Integrator (EBI). Each panel supervises its own detection system and is designed to function independently of all others in the “Peer to Peer” network in case of a communication failure. XLS80E_1.doc XLS50 INTELLIGENT FIRE ALARM CONTROL PANEL XLS80E FIRE CONTROL PANEL XLS60 Communication 8 0 A ToResetPanelAfterAlarm: 1..Si Siw lelence/ esound: 2 Mleunce tePSounders anelbypreby ssipressi ngAcnkgno dgeR /M ute: 3.PressSystemReset: To initiate Manual Evacuation Press Evacuate: FIRE XLS80e controllers may be networked together using the XLSNET “Peer to Peer” communication boards. The boards plug directly into the processor PCB in the XLS80E. (One XLSNET board is required per XLS80e). The “Peer to Peer” network supports up to 100 nodes with a maximum of 32 XLS80e controllers can be included in the network. 1 N B 4 5 ER FS 2 O C 8 9 I V JW 3 P D T H 6 G > K F1 Q F2 7 U F3 < X LY M Z FAULT ACK'DDS I ABLE GR ND PU PL ES RO RD R SIE AD YE EDC SY EA MU /SLIL A LN AR SPOWER FO AUU LT SU FA LY TSO FU AN UD LT DU ISN AD BE LE SL AA BY LS ED TEST DE MLO PS UTF TE CM ED FIRE - ZONEINDICATORS- FAULT/TES/D TISABLED BSEN5-24:1998 Analogue Addressable Fire Panel BSEN -44:1998 230V 0.75A 50Hz Integral Power Supply MANUAL CALL POINT The XLSNET provides both a high speed and robust communication path, enabling “cause and effects” to be programmed across the complete XLS80e controller network. BREAK GLASS PRESSHERE honeywell DOOR HOLDER CONTROL RELAY MODULE CM HEAT SENSOR DUCT TYPE SMOKE SENSOR IONISATION SENSOR The XLS80e is also compatible with the Honeywell Enterprise Buildings Integrator (EBI) Graphic User Interface (GUI) communicating via OPC open communication protocol. The XLS80e “OPC2net” interface link to the Honeywell EBI allows for both alarm and fault annunciation of each individual sensor/module to be displayed on the EBI operator station in either (or both) text and graphic format/s. OPTICAL SENSOR CM ISOLATOR MODULE FI LOOP POWERED SOUNDER LOOP POWERED BASE SOUNDER CONV. ZONE INTERFACE MODULE Peripheral Devices CONTROL MODULE ISOLATOR MODULE FI FI FI CONVENTIONAL DETECTOR I/F MODULE BREAK GLASS PR ESSHERE honeywell BEAM DETECTOR A full range of repeater panels and serial peripheral devices complements the XLS80E. CONVENTIONAL DEVICES XLS80E Configuration The XLS80E Full Repeater is a compact repeater unit, which mimics all the main indications and controls on the XLS80e panel and when connected as a part of the “Peer to Peer” network alarms from any other device on the network may be mapped to the repeater panel (default = all). The XLS80e repeater panel has an LCD display, 6 general status LEDs and four control switches for Acknowledge, Silence, Evacuate and Reset. Displays and Printer The XLS80E panel has 14 general panel status information warning LEDs and a alphanumeric liquid crystal display with 2 lines by 40 characters. The display is illuminated to assist viewing under dim ambient light conditions. If a graphic based PC front end is required, the XLS80E (or Network of XLS80E controllers can be connected via a OPC interface to Honeywell's Enterprise Buildings Integrator (EBI). In addition to the general status LEDs and the LCD display, the panel comes with 20 pairs of zone status indicators as standard ("FIRE" and "FAULT/DISABLED" indications). User definable text messages can be read directly from the LCD to give details of fire and fault event locations. Optional panel functions and more detail about events and devices can be accessed using the numeric keypad and following the menu driven user level options on the LCD. Additionally, when the optional printer is used, this information can be printed out to provide a hard copy. System Configuration The XLS80E controller can be programmed on-site using either the panel control features or the Microsoft Windows PC based programming tool. Note: The PC based programming software allows for the engineer to connect a laptop PC to the control panel through a dedicated serial port and upload panel configuration, make alterations in the installation information, and finally download the new configuration into the panel. This is particularly convenient for large panels or distributed systems when large amounts of location text, or complex cause and effect patterns are required. The LCD serves as the primary user interface when using the manual programming option. When the numeric keypad is not in use, the display reverts to automatically scrolling through any fire alarm or fault conditions present on the panel. Protection User controls on the front panel are password protected. Pressing any key on the panel will prompt for the appropriate level password to be entered. Authorised access to higher level functions including device isolation and configuration data entry is available through the panel keyboard and is again password protected. All configuration data and event logging is retained by nonvolatile memory and is, therefore, protected against corruption or complete failure of all external power supplies. The system reliability can be optimised by running the XLS80e “fault diagnosis program”. This enables the identification of any problems that may not be found during normal system testing. 2 XLS80E_1.doc XLS50 INTELLIGENT FIRE ALARM CONTROL PANEL SPECIFICATIONS Operating Voltage: 20v DC Sensor Circuits 24v DC Sounder Circuits Internal Sounder: Intermittent buzzer indicates a fault condition High-pitched continuous buzzer indicates a fire condition User Controls: MUTE BUZZER EXTEND DELAY END DELAY/EVACUATE SILENCE/RESOUND RESET DAY MODE FIRE OUTPUT DISABLE CHANGE TABS ZONES IN ALARM Battery Space • 12Ah with standard back box • 38Ah with extended deep/double-extended deep back box • 78Ah with Remote Battery/PSU Enclosure Primary Input Power 230V 50Hz AC (Fused at 5Amp. Recommended 5Amp mains spur) Sounder Outputs 2 Sounder outputs @ 1A each Programming Controls: Alphanumeric multi-level keypad with 10 keys and Navigation arrows ÛÝÞÜ plus three push buttons: Sounder/Volt-free Outputs 2 Sounder/Volt-free output contacts rated 30V 1A ýþß Relay Outputs Fire Relay Output @ 30V 1A Fault Relay Output @ 30V Indicators: LED status indicators: • FIRE • FAULT • PRE-ALARM • SYSTEM FAULT • SOUNDER FAULT/DISABLED • FIRE O/P FAULT/DISABLED • FIRE O/P ACTIVE • DISABLEMENT • TEST • POWER • DAY MODE • DELAYS ACTIVE • NON-FIRE ACTIVE Auxiliary Power Output 2 Auxiliary Outputs rated @26-28V 1A each Total Auxiliary Output Total Sounder and auxiliary power dependent on power supply option selected (please refer to the XLS80e PSU Specifications) Dimensions: Standard Back Box: 500mm W x 400mm H x 153mm D Extended Back Box: 500mm W x 620mm H x 251mm D Standard Extension Back Box: 500mm W x 220mm H x 251mm D LCD Display: Graphic 240 x 64 pixel back-lit display (6 x 40 characters) Environmental Operating Limits: Temperature: 0°C to +49°C Humidity: 85% rh (non-condensing) Serial Interface: Dedicated serial port for software Upload/ Download Construction: Sheet steel painted, sealed to IP30. Optional recess mount bezel available. System Capacity Up to 100 nodes 32 XLS80e intelligent fire alarm panels 8160 zones 25344 intelligent sensors 25344 addressable monitor/control modules 170km of network cabling Cable Entry: 20mm knock-outs in top and bottom of the cabinet Panel Capacity: 2 to 8 loops per panel 255 Software zones per panel 64, 128 or 255 Zone LED indication options on Extended Panel cabinets 99 Intelligent Sensors per loop 99 Addressable Monitor/Control Modules per loop Key Operated Switch Level 2 access code keyswitch Approvals: EN54, CE Zones: Up to 255 zone with individual LED indicators when using the extended panel option. 3 XLS80E_1.doc