XLS80e Intelligent Fire Alarm Control Panel

advertisement
XLS80e Intelligent
Fire Alarm Control Panel
SPECIFICATION DATA
FEATURES
• Certified to EN54 parts 2 and 4
• Drift compensation
• Automatic or Manual “Loop Learn” options
• “Walk Test” function by zone for efficient
commissioning
• On screen “test” tally (tested/untested count) for
devices in zone walk test
• Auto-program option
• Automatic time control functions by day of week for
“Control-by-Event” (CBE)
•
255 Zone capacity per panel
•
Full configuration edit capability from panel or PC
DESCRIPTION
The XLS80E Intelligent Fire Alarm Control Panel provides a
cost-effective platform for a fire alarm system that is both
flexible and expandable. The panel offers system designers
and end users a technically sophisticated range of facilities
and functions whilst maintaining ease of programming,
installation, and operation.
The XLS80E control panel is fully compatible with the full
range of Honeywell’s TC800 Series analogue addressable
sensors, control and monitor modules. This makes the
XLS80E the perfect solution for retrofit jobs as well as for
new projects.
Each panel can support up to 8 analogue addressable
loops and each loop can support up to 99 TC800 Series
analogue sensors and 99 TC800 Series modules. This
gives the XLS80e a panel a maximum capacity of 1584
points..
Full function repeater panels complements the XLS80E
product range.
System
The XLS80E fire panel will control a combination of up to 99
heat, smoke or multi-criteria sensors on each loop and a
combination of 99 call points, monitor, control and
conventional zone interface modules and sounders per
Honeywell TC800 Series loop.
Depending on the arrangement of user specified zones,
isolation modules may also be added to the system
although they are not required at loop ends.
The XLS80e controllers, peripheral devices and all the
system fields components e.g. sensors and modules are
approved to meet with the requirements of EN54
The XLS80E can also be networked with other XLS80E
controllers and repeaters in a “Peer to Peer” architecture.
Furthermore, if a graphic based PC front end (GUI) is
required, the XLS80e panels can be connected to
Honeywell's Enterprise Building Integrator (EBI).
Each panel supervises its own detection system and is
designed to function independently of all others in the “Peer
to Peer” network in case of a communication failure.
XLS80E_1.doc
XLS50 INTELLIGENT FIRE ALARM CONTROL PANEL
XLS80E FIRE CONTROL PANEL
XLS60
Communication
8
0
A
ToResetPanelAfterAlarm:
1..Si
Siw
lelence/
esound:
2
Mleunce
tePSounders
anelbypreby
ssipressi
ngAcnkgno
dgeR
/M
ute:
3.PressSystemReset:
To initiate Manual Evacuation Press Evacuate:
FIRE
XLS80e controllers may be networked together using the
XLSNET “Peer to Peer” communication boards. The boards
plug directly into the processor PCB in the XLS80E. (One
XLSNET board is required per XLS80e). The “Peer to Peer”
network supports up to 100 nodes with a maximum of 32
XLS80e controllers can be included in the network.
1
N
B
4
5
ER
FS
2
O C
8
9
I V
JW
3
P
D
T
H
6
G
>
K
F1
Q
F2
7
U
F3
<
X
LY
M
Z
FAULT ACK'DDS
I ABLE GR
ND
PU
PL
ES
RO
RD
R
SIE
AD
YE
EDC
SY
EA
MU
/SLIL
A
LN
AR
SPOWER
FO
AUU
LT SU
FA
LY
TSO
FU
AN
UD
LT
DU
ISN
AD
BE
LE
SL
AA
BY
LS
ED TEST DE
MLO
PS
UTF
TE
CM
ED
FIRE
- ZONEINDICATORS-
FAULT/TES/D
TISABLED
BSEN5-24:1998 Analogue Addressable Fire Panel
BSEN
-44:1998
230V
0.75A
50Hz Integral Power Supply
MANUAL
CALL POINT
The XLSNET provides both a high speed and robust
communication path, enabling “cause and effects” to be
programmed across the complete XLS80e controller
network.
BREAK GLASS
PRESSHERE
honeywell
DOOR
HOLDER
CONTROL
RELAY
MODULE
CM
HEAT
SENSOR
DUCT TYPE
SMOKE SENSOR
IONISATION
SENSOR
The XLS80e is also compatible with the Honeywell
Enterprise Buildings Integrator (EBI) Graphic User Interface
(GUI) communicating via OPC open communication
protocol. The XLS80e “OPC2net” interface link to the
Honeywell EBI allows for both alarm and fault annunciation
of each individual sensor/module to be displayed on the EBI
operator station in either (or both) text and graphic format/s.
OPTICAL
SENSOR
CM
ISOLATOR
MODULE
FI
LOOP
POWERED
SOUNDER
LOOP
POWERED
BASE
SOUNDER
CONV. ZONE
INTERFACE
MODULE
Peripheral Devices
CONTROL
MODULE
ISOLATOR
MODULE
FI
FI
FI
CONVENTIONAL
DETECTOR I/F
MODULE
BREAK GLASS
PR
ESSHERE
honeywell
BEAM DETECTOR
A full range of repeater panels and serial peripheral devices
complements the XLS80E.
CONVENTIONAL DEVICES
XLS80E Configuration
The XLS80E Full Repeater is a compact repeater unit, which
mimics all the main indications and controls on the XLS80e
panel and when connected as a part of the “Peer to Peer”
network alarms from any other device on the network may
be mapped to the repeater panel (default = all). The XLS80e
repeater panel has an LCD display, 6 general status LEDs
and four control switches for Acknowledge, Silence,
Evacuate and Reset.
Displays and Printer
The XLS80E panel has 14 general panel status information
warning LEDs and a alphanumeric liquid crystal display with
2 lines by 40 characters. The display is illuminated to assist
viewing under dim ambient light conditions.
If a graphic based PC front end is required, the XLS80E (or
Network of XLS80E controllers can be connected via a OPC
interface to Honeywell's Enterprise Buildings Integrator
(EBI).
In addition to the general status LEDs and the LCD display,
the panel comes with 20 pairs of zone status indicators as
standard ("FIRE" and "FAULT/DISABLED" indications).
User definable text messages can be read directly from the
LCD to give details of fire and fault event locations. Optional
panel functions and more detail about events and devices
can be accessed using the numeric keypad and following
the menu driven user level options on the LCD. Additionally,
when the optional printer is used, this information can be
printed out to provide a hard copy.
System Configuration
The XLS80E controller can be programmed on-site using
either the panel control features or the Microsoft Windows
PC based programming tool.
Note: The PC based programming software allows for the
engineer to connect a laptop PC to the control panel through
a dedicated serial port and upload panel configuration,
make alterations in the installation information, and finally
download the new configuration into the panel. This is
particularly convenient for large panels or distributed
systems when large amounts of location text, or complex
cause and effect patterns are required.
The LCD serves as the primary user interface when using
the manual programming option. When the numeric keypad
is not in use, the display reverts to automatically scrolling
through any fire alarm or fault conditions present on the
panel.
Protection
User controls on the front panel are password protected.
Pressing any key on the panel will prompt for the
appropriate level password to be entered. Authorised
access to higher level functions including device isolation
and configuration data entry is available through the panel
keyboard and is again password protected.
All configuration data and event logging is retained by nonvolatile memory and is, therefore, protected against
corruption or complete failure of all external power supplies.
The system reliability can be optimised by running the
XLS80e “fault diagnosis program”. This enables the
identification of any problems that may not be found during
normal system testing.
2
XLS80E_1.doc
XLS50 INTELLIGENT FIRE ALARM CONTROL PANEL
SPECIFICATIONS
Operating Voltage:
20v DC Sensor Circuits
24v DC Sounder Circuits
Internal Sounder:
Intermittent buzzer indicates a fault condition
High-pitched continuous buzzer indicates a fire condition
User Controls:
MUTE BUZZER
EXTEND DELAY
END DELAY/EVACUATE
SILENCE/RESOUND
RESET
DAY MODE
FIRE OUTPUT DISABLE
CHANGE TABS
ZONES IN ALARM
Battery Space
•
12Ah with standard back box
•
38Ah with extended deep/double-extended deep
back box
•
78Ah with Remote Battery/PSU Enclosure
Primary Input Power
230V 50Hz AC (Fused at 5Amp.
Recommended 5Amp mains spur)
Sounder Outputs
2 Sounder outputs @ 1A each
Programming Controls:
Alphanumeric multi-level keypad with 10 keys and
Navigation arrows ÛÝÞÜ plus three push buttons:
Sounder/Volt-free Outputs
2 Sounder/Volt-free output contacts rated 30V 1A
ýþß
Relay Outputs
Fire Relay Output @ 30V 1A
Fault Relay Output @ 30V
Indicators:
LED status indicators:
•
FIRE
•
FAULT
•
PRE-ALARM
•
SYSTEM FAULT
•
SOUNDER FAULT/DISABLED
•
FIRE O/P FAULT/DISABLED
•
FIRE O/P ACTIVE
•
DISABLEMENT
•
TEST
•
POWER
•
DAY MODE
•
DELAYS ACTIVE
•
NON-FIRE ACTIVE
Auxiliary Power Output
2 Auxiliary Outputs rated @26-28V 1A each
Total Auxiliary Output
Total Sounder and auxiliary power dependent on power
supply option selected (please refer to the XLS80e PSU
Specifications)
Dimensions:
Standard Back Box: 500mm W x 400mm H x 153mm D
Extended Back Box: 500mm W x 620mm H x 251mm D
Standard Extension Back Box: 500mm W x 220mm H x
251mm D
LCD Display:
Graphic 240 x 64 pixel back-lit display (6 x 40 characters)
Environmental Operating Limits:
Temperature: 0°C to +49°C
Humidity:
85% rh (non-condensing)
Serial Interface:
Dedicated serial port for software Upload/ Download
Construction:
Sheet steel painted, sealed to IP30.
Optional recess mount bezel available.
System Capacity
Up to 100 nodes
32 XLS80e intelligent fire alarm panels
8160 zones
25344 intelligent sensors
25344 addressable monitor/control modules
170km of network cabling
Cable Entry:
20mm knock-outs in top and bottom of the cabinet
Panel Capacity:
2 to 8 loops per panel
255 Software zones per panel
64, 128 or 255 Zone LED indication options on Extended
Panel cabinets
99 Intelligent Sensors per loop
99 Addressable Monitor/Control Modules per loop
Key Operated Switch
Level 2 access code keyswitch
Approvals:
EN54, CE
Zones:
Up to 255 zone with individual LED indicators when using
the extended panel option.
3
XLS80E_1.doc