BFOU (c) - TELE

advertisement
BFOU (c) 150/250(300)V
S4/S8
MGT/EPR/EPR/TCWB/EVA
Fire resistant, flame retardant halogen-free instrumentation cable
Mud resistant
Applicable standards:
NEK TS 606 Code S4/S8, IEC 60092-376- Design guidelines
IEC 60228 conductor
IEC 60092-351 Insulating material, IEC 60092-359 Sheathing materials
IEC 60332-1, IEC 60332-3-22 Flame retardant, IEC 60331 Fire resistant
IEC 60754-1,2 Halogen free, IEC 61034-1,2 Low Smoke
CONSTRUCTION
Code
Letter
Conductors
Insulation
Tinned annealed circular stranded copper according to IEC 60228 class 2
B
Mica tape EP rubber thermosetting compound ,IEC 60092-351 (EPR)
Inner covering
F
Color coded cores twisted together and wrapped with polyester tape. Pairs/
Triples are laid up collectively and screened by copper backed polyester tape
with tinned copper drain wire .Pairs/ triples are identified by numbers printed
directly on the insulated conductors.
Flame retardand and halogen free thermosetting compound
Armour/screen
O
Tinned annealed copper wire braid
Pair, Triple, Quad
twisting
Separator
Outer sheath
Separator, suitable tape between the braid and outer sheath
U
Flame retardand, halogen free and mud resistant thermosetting compound
SHF2 (IEC 60092-359)
Colour of outer
sheath
Grey or Blue
Standard marking
E.g. TF KABLE 3 BFOU (c) 250V S4/S8 2 PAIR 0,75mm2 IEC 60331-21 IEC 603323-22 IEC 60092-376
TELE-FONIKA Kable S.A.
www.tfkable.com
BFOU_C_250V_AJ/KHB 04-02-15
BFOU (c) 150/250(300)V
S4/S8
MGT/EPR/EPR/TCWB/EVA
FEATURES
Maximum conductor operating temperature: +90°C
Maximum conductor temperature during short circuit: +250oC
Lowest ambient temperature for fixed installation: -40°C
Lowest installation temperature: -15°C
Minimum bending radius: 6 D
D – overall diameter of cable
Flame retardant: IEC 60332-3-22 (Category A)
Fire resistant: IEC 60331
Smoke emission: IEC 61034-2
Corrosive gas emission: IEC 60754-1
Oil resistance: IEC 60092-359 SHF2, IRM 902 (100⁰C/24h)
Mud resistance: NEK 606 (SHF MUD, SHF2)
APPLICATIONS
Fixed installation for instrumentation ,communication, control and alarm system in both EX -and
safe areas emergency and critical systems where requirements for fire resistance exists.
Meets the MUD resistance requirement in NEK TS 606
Other industrial applications
Standard length cable packing
1000m on drums. Other forms of packing and delivery are available on
request
TELE-FONIKA Kable S.A.
www.tfkable.com
BFOU_C_250V_AJ/KHB 04-02-15
BFOU (c) 150/250(300)V
S4/S8
MGT/EPR/EPR/TCWB/EVA
Size
N x 2 x mm2
2x2x0,75
4x2x0,75
8x2x0,75
12x2x0,75
16x2x0,75
19x2x0,75
24x2x0,75
N x 3 x mm2
2x3x0,75
4x3x0,75
8x3x0,75
12x3x0,75
16x3x0,75
N x 2 x mm2
3x2x1,0
4x2x1,0
N x 2 x mm2
2x2x1,5
4x2x1,5
8x2x1,5
12x2x1,5
16x2x1,5
N x 3 x mm2
2x3x1,5
4x3x1,5
8x3x1,5
12x3x1,5
N x 2 x mm2
2x2x2,5
4x2x2,5
8x2x2,5
16x2x2,5
N x 3 x mm2
4x3x2,5
8x3x2,5
Class
of
conductor
Insulation
Thickness
Thickness of
inner sheath
Thickness of
outer sheath
Approximate Approximate
overall
net weight
diameter
of cable
2
2
2
2
2
2
2
mm
0,6
0,6
0,6
0,6
0,6
0,6
0,6
mm
1,1
1,1
1,1
1,4
1,9
1,9
2,3
mm
1,3
1,4
1,5
1,6
1,7
1,8
2
mm
13,7
19,0
23,4
28,0
32,3
34,6
39,0
kg/km
258
416
612
842
1104
1247
1561
2
2
2
2
2
0,6
0,6
0,6
0,6
0,6
1,1
1,1
1,1
1,4
2,1
1,3
1,4
1,6
1,8
1,9
18,2
20,5
22,7
31,5
36,8
372
497
703
1091
1463
2
2
0,7
0,7
1,1
1,1
1,4
1,4
19,0
20,6
418
482
2
2
2
2
2
0,7
0,7
0,7
0,7
0,7
1,1
1,1
1,1
1,4
1,9
1,4
1,4
1,7
1,8
1,9
15,5
21,8
27,5
32,9
38,0
337
551
868
1207
1580
2
2
2
2
0,7
0,7
0,7
0,7
1,1
1,1
1,1
1,4
1,4
1,5
1,8
1,9
21,0
23,8
31,4
36,9
492
687
1139
1578
2
2
2
2
0,7
0,7
0,7
0,7
1,1
1,1
1,1
2,3
1,4
1,5
1,8
2,1
16,6
23,7
30,1
42,9
402
683
1103
2228
2
2
0,7
0,7
1,1
1,1
1,6
1,9
26,0
34,4
929
1472
TELE-FONIKA Kable S.A.
www.tfkable.com
BFOU_C_250V_AJ/KHB 04-02-15
BFOU (c) 150/250(300)V
S4/S8
MGT/EPR/EPR/TCWB/EVA
All the information contained in this document - including tables and diagrams - is given in good faith and believed to be correct at
the time of publication. The information does not constitute a warranty nor representation for which TELE-FONIKA Kable assumes
legal responsibility. TELE-FONIKA Kable reserves rights to introduce changes to the document at any time
TELE-FONIKA Kable S.A.
www.tfkable.com
BFOU_C_250V_AJ/KHB 04-02-15
Download