Last updated: 12 Sep 2016

advertisement
Last updated: 27 Sep 2016
VOLUME 2 LIST OF APPROVED PRODUCTS AND SERVICES
Foreword by the United Arab Emirates (UAE) Acting Commander in Chief, Major
General Rashid Thani Al Matrooshi
As the dynamic environment in our Region progresses, we the UAE Civil Defence Authority, has set forth a
number of strategic goals for the delivery of public safety. Our strategic goals observe both the national and
Ministry of Interior’s strategic plan by;
“Providing an effective firefighting and emergency response system delivered by qualified and well trained
people using the latest technologies to ensure lives and properties are safeguarded”
As a result, the UAE can be ‘benchmarked’ with other Countries that are witnessing a decline in fires and
incidents when compared to the density of population. As an example, the number of fire incidents has been
reduced by 39% in 2011 compared to 2010, with a marked reduction in small and medium fire incidents,
together with a high percentage achievement of a 9 minute response time for first attendance at incidents.
“Providing excellent performance and support during disasters and crises”
Confirmation of performance and support are achieved during disasters and crisis situations. Civil Defence
Departments conduct a range of joint fire safety and evacuation drills in association with other safety agencies
for both the public and private sectors. Evacuation drills carried out in Dubai during 2011 was estimated at
356 drills, which targeted 178,530 persons. Customer satisfaction percentage achieved was 97.2%. The
number of drills carried out has increased by 142.4% compared to the target number set out in our annual
plan.
“Spreading a fire safety and awareness culture across the community “
In this regard, a National Safety campaign was launched targeting ‘domestic safety’ with an achieved target of
50% of homes in UAE being visited during a six month period. This was aimed at preventive awareness and
removing violations which threaten public safety. During the campaign, 206,490 houses (61.4% of the total
dwellings) were visited, again with a marked customer satisfaction percentage of 92%.
Similarly a National Safety campaign was also executed at industrial areas, with teams visiting industrial
facilities at different industrial areas across the country. 31,647 facilities were inspected. The teams also
managed to correct violation situations in 13,400 facilities and 53,426 people were trained in the basic skills of
firefighting and awareness.
“Equipping operations with the best and appropriate equipment and technologies”
The latest state of the art technologies have been introduced for various services such as, ‘e-engineering’ for
online drawing approval and the ’24 x 7 smart system’ for building electronic monitoring and protection.
Currently 61.7% of buildings are connected to the system and 95.7% surveyed for connection.
In addition, the ‘UAE Fire and Life Safety Code of Practice’ with our Standard Operating Procedures (SOPs) is
considered a first in the region. This will contribute to reduced costs and effort. Ultimately this will result in a
decrease in accidents and improve command and control mechanisms.
“Achieving Strategic Partnership with Public/Private and Voluntary Organizations”
By ensuring, through careful selection, that products, systems and installers are approved with a listing by
Civil Defence, following rigorous third party certification. This ensures that locally we receive the best
performance of fire safety products, systems and technologies.
ii
27 Sep 2016
VOLUME 2 LIST OF APPROVED PRODUCTS AND SERVICES
LPCB is widely recognised as an independent reference for all fire and security safety experts. Their testing
laboratories and approvals services together with their leading team of highly qualified expert scientists and
engineers, guides us all impeccably towards a qualified framework.
Major General Rashid Thani Al Matrooshi
Introduction
BRE Global Ltd, based in the UK near London, is an independent third party organisation offering certification
of fire, security and sustainability products and services to an international market. LPCB is the certification
brand used for fire and security products and services. The LPCB mark is accepted worldwide. We have
representative offices in China, India and Malaysia. We are owned by the BRE Trust, a not-for-profit
organisation.
LPCB listings can be accessed, free of charge, at www.redbooklive.com or via apps from Apple, Google and
Windows.
BRE Global Ltd is also a Notified Certification Body and Notified Test Laboratory for:



Construction Products Regulation
Pressure Equipment Directive
Marine Equipment Directive
Transport Pressure Equipment Directive
BRE Global additionally carries out:





Fire Investigation
Fire Risk Assessment
Fire Safety Engineering
Research
Training
27 Sep 2016
iii
VOLUME 2 LIST OF APPROVED PRODUCTS AND SERVICES
LPCB Listings
Listings are given in sections which list related groups of products and services such as suppression, security
and so on. Each section also summarises the technical basis for the certification of each product or service.
The Red Book listings should always be used in conjunction with rules, regulations and design specifications
required by the relevant Authority having jurisdiction.
2015 Listings comprise:
Volume 1:
 Fire detection and alarm products, systems, and cables
 Manual fire extinguishing equipment
 Automatic sprinkler, water spray and deluge systems
 Fixed fire fighting products and systems
 Related installers
Volume 2: (This Volume)
 Passive fire protection products
 Security protection products
 Fire doors and shutters
 Smoke and fire ventilation systems
 Related installers
 Management Systems
 Construction products
Listings are given in the name of the manufacturer or service provider, in alphabetical order. They can be
downloaded free of charge from our website at www.redbooklive.com and also via an App that is available
free from Apple iStore (for iPhone and iPad), from Google Play, (for Android phones and tablets) and
Windows Store (for Windows 8 phones).
Updates
Certification of products and services are updated regularly. To ensure that you are using the most up to date
information please refer to <<www.redbooklive.com>> or download the App.
What is Third Party Certification?
A frequent concern of stakeholders is in knowing whether a product will perform in accordance with the stated
specifications. These concerns can involve such product attributes as safety, health or environmental impacts,
durability, compatibility, suitability for intended purposes or for stated conditions, and other similar
considerations. These issues can all be addressed through product certification.
Third party certification is a conformity assessment process, carried out by a body that is independent of both
supplier and customer organisations. It provides confirmation that products and services have met and will
continue to meet the requirements of specified standards and other normative documents.
iv
27 Sep 2016
VOLUME 2 LIST OF APPROVED PRODUCTS AND SERVICES
LPCB third party product certification schemes are quality assurance schemes and comprise initial type
testing and technical evaluation, assessment and surveillance of the manufacturer’s quality system and
factory production procedures, regular audit testing, labelling and listing.
Similarly, LPCB schemes for suppliers of services (installers) are also quality assurance schemes comprising
a technical assessment of an installer’s capability, assessment and surveillance of the installer’s quality
system and production procedures, regular inspection of completed installations and listing.
Benefits of Third Party Certification
For specifiers, regulators, insurers, manufacturers and installers, the benefits of an LPCB approval are:
For specifiers and regulators:
 Risk reduction - specifying LPCB approved products and services demonstrates due-diligence and
best endeavour and mitigates against possible accusations of negligence.
 Avoidance of costly mistakes - you can trust LPCB approved products and services to conform each
and every time.
 Time - using Red Book Live to search for and assess products and services can save you time.
For manufacturers and installers:
 Increased global sales - LPCB approval is recognised and specified widely throughout the world. In
some territories LPCB approval is a mandatory requirement.
 Added value of the product or service - LPCB approved products and services are recognised as
providing added value given their ability to conform each and every time.
 Reduced liability - LPCB approved products and services demonstrate due-diligence which can
reduce liability for both you and your customers.
What does LPCB Certification offer?
LPCB certification is carried out against Loss Prevention Standards (LPS’s). These LPS’s include reference to
BS, EN or ISO standards as appropriate. LPCB certification are level 5 schemes as detailed in ISO/ IEC
17067 with the added requirement to have a quality system certificated to ISO 9001.
The technical requirements of LPCB schemes are given in the Loss Prevention Standards (LPSs). These
documents are drafted by LPCB technical experts in conjunction with appropriate external experts. They are
then peer reviewed by representatives from trade bodies, regulators, insurers, specifiers, manufacturers and
other suppliers. Finally these documents are approved for use by the BRE Global Governing Body; the Body
that oversees all of the certification activities of BRE Global.
Product schemes comprise:
 Initial type testing and evaluation of product.
 Approval and surveillance of the manufacturer’s (or supplier’s) quality management system to ISO
9001
 Assessment and surveillance of the manufacturer’s (or supplier) factory production control system
(FPC).
 Periodic audit testing of the product from either the factory or marketplace.
 Labelling or marking as appropriate.
 Listing on Red Book Live
27 Sep 2016
v
VOLUME 2 LIST OF APPROVED PRODUCTS AND SERVICES
Installer schemes comprise:
 Technical assessment of the installation contractor’s capability.
 Approval and surveillance of the contractor’s quality management system to ISO 9001 or assessment
against the requirements of the relevant Loss Prevention Standard where ISO 9001 is not
appropriate.
 Regular surveillance inspections of on-going installations.
 The issue of Certificates of Conformity by the installer to demonstrate compliance for each installation.
 Listing in the Red Book.
The LPCB Mark - the Mark you can trust
After certification of a product or service the manufacturer or service provider may place the LPCB certification
mark, as shown below, on the product, packaging and literature etc.
Where LPCB holds accreditation through the United Kingdom Accreditation Service (UKAS), the certified
company may include the UKAS symbol (the Crown and Tick) alongside the LPCB mark for certain
applications e.g. promotional literature or material and stationery, as shown below.
(Full details of LPCB accreditation can be found on the UKAS website at www.ukas.com)
Where for reasons of space or cost the use of the above full mark is not practical, then the following simplified
mark may be applied directly to the product (for some schemes only). The LPCB scheme rules define how
and where the marks can be used.
The products listed in Volume 2: Part 5 - Construction Products, are approved under our BRE Global
Certification brand - the certification mark for this brand is changing.
vi
27 Sep 2016
VOLUME 2 LIST OF APPROVED PRODUCTS AND SERVICES
To this
from
(discontinued for new certificates
from 1 January 2014)
A transition period of up to three years is being allowed for the change and the ‘old’ mark remains valid where
the certificate was issued before 1 January 2014.
27 Sep 2016
vii
CONTENTS
2 Fire doors, shutters and installers of fire and security doors
1
SECTION 1.1 Firebreak doors and shutters
3
SECTION 1.2 Lift landing doors
16
SECTION 2 Fire and security door and shutter installers
17
SECTION 3 Inspection, repair and maintenance of fire and security doors and shutters 21
viii
27 Sep 2016
INDEX
1
123 Fire (a division of MB Plant Limited)
21
A
Ascot Doors Limited
3, 21
Assa Abloy Entrance Systems Limited
21
Attenborough Doors Limited
3
Avert Fire (UK) Ltd
17, 22
C
Checkmate Fire Solutions Ltd
17, 22
Clark Door Limited
4, 17
D
DoorCheck Limited
23
Ductclean (UK) Limited
18
F
Fire Safety Services (UK) Limited
23
G
Grange Door Systems
18, 23
gte Brandschutz AG
4
Gunfire Trading Divison of Gunite (Eastern)
Limited
18
H
Hart Door Systems
5, 18
Hoermann (Beijing) Door Production Co. Limited 5
Hörmann KG Freisen
6
I
Industrial Door Engineering Limited
7, 18, 24
K
Kone Corporation
8
Kone PLC
19, 24
27 Sep 2016
Konecranes Industrial Door Services
24
L
LBS Security Services Limited T/A LBS Group 8,
25
Lincs Doors Limited
8
M
Manning Construction Limited
19
Mercian Shutters Limited
9, 19, 25
Middle East Insulation
9
N
Nene Valley Fire and Acoustic Limited
19, 25
P
Prestige Fire Door Services Limited
20
R
R Lewis & Co. (UK) Ltd
20
Rite Industrial Doors Ltd
26
S
Safe Partnership
20
Saudi Factory for Fire Equipment Co.
10
Stanair Industrial Door Services Limited
26
Stobich Brandschutz GmbH
10
Sunray Engineering Limited
12, 20
T
Technocover Limited (incorporating TechnoRail
and Strataform)
14
TEK Interiors Limited
20, 26
Tyco Fire and Integrated Solutions (the trading
company for Tyco Fire and Integrated Solutions
(UK) Limited)
27
ix
Part
2
FIRE DOORS, SHUTTERS
AND INSTALLERS OF FIRE
AND SECURITY DOORS
PART 2: FIRE DOORS, SHUTTERS AND INSTALLERS OF FIRE AND
SECURITY DOORS
INTRODUCTION
Fire doors and shutters contribute to the passive fire protection of buildings by maintaining the:
 fire separation of compartment walls, while allowing the passage of persons or objects
 fire separation in shafts or service ducts that penetrate compartment floors
 protection provided by walls forming protected routes for means of escape.
In addition to careful design and product selection, it is recommended that all products are installed and
maintained by LPCB approved contractors who have demonstrated their competence.
Products
Doors and shutter assemblies are approved in accordance with: LPS 1056: Test and Evaluation
Requirements for the Approval and Listing of Fire Doorsets, Lift Landing Doors and Shutter Assemblies.
The fire testing element of this LPS is based on BS 476:Part 20 - Method for determination of the fire
resistance of elements of construction (general principles) or EN 1634-1 Fire resistance test for doors and
shutter assemblies- Part 1: Fire doors and shutters and EN 81-58 Landing doors fire resistance test.
LPS 1056 also includes requirements for the reliability testing of the door and shutter assemblies, and
assessment procedures for doors and shutters that are too big to be directly fire tested.
Installation contractors
LPCB approved installation contractors are assessed in accordance with: LPS 1271: Requirements for LPCB
Approval and Listing of companies installing fire and security doors, doorsets, shutters and active fire/smoke
barriers.
Maintenance contractors
LPCB approved maintenance contractors who repair and maintain fire doors and shutters are approved in
accordance with: LPS 1197: Requirements for LPCB Approval and Listing of companies inspecting, repairing
and maintaining fire and security doors, doorsets, shutters and active fire/smoke barriers.
2
27 Sep 2016
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
This section lists firebreak doorsets and shutters approved to:


LPS 1056 Test and Evaluation requirements for the LPCB Approval and Listing of Fire Doorsets, Lift
Landing Doors and Shutter Assemblies. LPS 1056 is based upon relevant BS or European test
criteria and not only looks at the fire integrity and insulation (where applicable) but also includes
reliability cyclic tests and grading, or
EN 81-58 Landing doors fire resistance test, and/or
EN 1634-1 Fire resistance and smoke control tests for door and shutter assemblies, openable
windows and elements of building hardware. Fire resistance test for door and shutter assemblies and
openable windows
For details of the specific fire resistance required for firebreak doors and shutters for different building types,
see the LPC Design Guide for the Fire Protection of Buildings:2000.
Where insulation is marked as 0, this denotes that the insulation was not measured or that it could not be
measured in accordance with the relevant standard.
Ascot Doors Limited
Britannia Way Industrial Park, Union Road, Bolton BL2 2HE, United Kingdom
Tel: +44 (0)1204 545801 • Fax: +44 (0)1204 545800
E-mail: sales@ascotdoors.co.uk • Website: www.ascotdoors.co.uk
Certificate No: 131a to LPS 1056: Issue 6
Product Name
Spec.
Door Type
Max
Height
(m)
Max
Width
(m)
Max
Area
(m2 )
A200 Series
4
Rolling Shutter
6.00
9.00
54.00
Fire Resistance
(min)
BS 476: Part 22
Integrity / Insulation
240 / 0
LPCB Ref. No.
131a/01
Notes:
1. LPCB Ref No. 131a/01 - for a list of the sizes for the shutter dimensions up to the stated please refer to BRE Global Assessment
Report CC200913 Review 1.
Attenborough Doors Limited
Merlin Way, Quarry Hill Industrial Estate, Ilkeston, Derbyshire DE7 4RA, United Kingdom
Tel: +44 (0)115 9300815 • Fax: +44 (0)115 9448930
E-mail: information@attenboroughdoor.co.uk • Website: www.attenboroughdoor.co.uk
Certificate No: 145b to LPS 1056: Issue 5
Product Name
Spec.
Door Type
Max
Height
(m)
Max
Width
(m)
Max
Area
(m2 )
Attenborough Fire
Shutter
4
Rolling
shutter
7.00
7.00
49.00
27 Sep 2016
Fire
Resistance
(min)
BS 476: Part
22
Integrity
240
Fire
Resistance
(min)
BS 476: Part
22
Insulation
0
LPCB Ref.
No.
145b/01
3
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
Clark Door Limited
Unit F Central, Kingmoor Park, Carlisle, Cumbria CA6 4SJ, United Kingdom
Tel: +44 (0)1228 522321 • Fax: +44 (0)1228 401854
E-mail: mail@clarkdoor.com • Website: www.clarkdoor.com
Certificate No: 106a to LPS 1056: Issue 6
Fireman
Product
Name
Door Type
Max
Height
(m)
Max
Width
(m)
Max
Area
(m2)
16.00
Fire
Resistance
(min)
BS 476: Part
22
Integrity
240
Fire
Resistance
(min)
BS 476: Part
22
Insulation
0
Fireman
Sliding door
4.0
4.0
Single leaf
hinged door
Double leaf
hinged door
2.76
1.423
3.57
240
0
2.76
2.845
7.15
240
0
Reliability
(self closing
durability Ref. LPS
1056 Clause 3.6)
LPCB Ref.
No.
No performance
determined
No performance
determined
No performance
determined
106a/01
106a/02
106a/03
Notes:
1. Clark Door Ltd are also approved under LPS 1271 for installation of Fireman series of fire rated doorsets.
2. 106a/02 & 106a/03 - Vision panels, 6.5mm thick Pyroshield clear glass with maximum dimensions 1000mm wide x 1000mm high.
Maximum area 1m²
3. 106a/03 - Double leaf doors, passive leaf must be fitted with a 3-point latching mechanism that engages in the top of frame, sill and
the active leaf, and the active leaf must be fitted with a full length astragal that overlaps the passive leaf by at least 25mm.
4. 106a/01, 106a/02, & 106a/03 - Door leaf skins can be fabricated from galvanised mild steel or grade 316 stainless steel.
5. 106a/01, 106a/02, & 106a/03 - The doorsets can be installed in a rigid supporting construction such as brick, blockwork or concrete.
The doorsets can also be installed in a composite wall panel system which provides equal or greater fire resistance than the doorset,
when installed in a composite wall panel system the minimum fixing detail described in assessment report CC213834 shall be
provided.
gte Brandschutz AG
Hamburger Straße 2, D-14532 Stahnsdorf, Germany
Tel: +49 3329 6359-0 • Fax: +49 3329 6359-25
E-mail: philip.capellen@gte.ag • Website: www.gte.ag
Certificate No: 735a to LPS 1056: Issue 6.1
Product Name
Door Type
Max
Height
(m)
Max
Width
(m)
Max
Area
(m2)
Fire
Resistance
(m)
BS 476: Part 22
Insulation
90
LPCB Ref. No.
1.82
Fire
Resistance
(m)
BS 476: Part 22
Integrity
90
CSS
Vertical sliding
conveyor
system shutter
Horizontal
sliding
conveyor
system shutter
Flap type
conveyor
system shutter
(Single)
Flap type
conveyor
system shutter
(Stacked)
1.3
1.4
1.3
1.4
1.82
90
90
735a/02
1.3
1.1
1.43
90
90
735a/03
0.85
1.1
0.935
90
90
735a/04
735a/01
Notes:
4
27 Sep 2016
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
1. LPCB Product Ref. No’s 735a/01, /02, /03 & /04 suitable for installation into masonry walls and Durasteel partitions as described in
Assessment report No. CC221812.
2. CSS conveyor system shutters must be regularly maintained in line with the gte Brandschutz recommendations.
Hart Door Systems
Redburn Road, Westerhope Industrial Estate, Westerhope, Newcastle upon Tyne NE5 1PJ, United Kingdom
Tel: +44 (0)191 214 0404 • Fax: +44 (0)191 271 1611
E-mail: info@hartdoors.com • Website: www.hartdoors.com
Certificate No: 016a to LPS 1056: Issue 6
Product
Name
Door Type
Max Height
(m)
Max Width
(m)
Max
Area
(m 2)
Firebrand
Face-fixed
Rolling shutter
Face-fixed
Rolling shutter
7.0
7.0
49.0
Fire resistance
(min)
BS 476 Part 22
Integrity /
Insulation
240/0
3.250
2.750
8.937
60/0
Reliability
(self closing
durability ref.
LPS 1056 clause
3.6)
No performance
determined
No performance
determined
LPCB Ref.
No.
016a/01
016a/02
Notes
1. LPCB ref. 016a/01 and 016a/02 for a list of detailed specification and component sizes for the shutter dimensions up to the
maximum stated please refer to BRE Global assessment CC92909 review 2.
2. LPCB ref. 016a/01 The Firebrand shutter is approved for use when built into masonry/concrete or steel supporting constructions
having a fire resistance greater or equal to that required of the doorset itself as detailed in BRE Global assessment CC92909 review
2.
3. LPCB ref. 016a/02 The Firebrand shutter is approved for use when built into a non-loadbearing drywall partition system having a fire
resistance greater or equal to that required of the doorset itself as detailed in BRE Global assessment CC92909 review 2.
4. Hart Door Systems Ltd are also approved under LPS 1271 for installation of Firebrand rolling shutters.
Hoermann (Beijing) Door Production Co. Limited
No. 13 Zhong He Street, BDA, Beijing 100176, China
Tel: +86 (0) 10 87223 400
E-mail: sascha.weckesser.bj@hoermann.cn • Website: www.hoermann.cn
Certificate No: 1101a to LPS 1056
Product
Name
Maximum
Leaf Size
Height
(mm)
Maximum
Leaf Size
Width
(mm)
Maximum
Leaf Size
Area (m 2)
VisionPanel
GlassType
VisionPanel
Maximumclear
viewheight
(mm)
VisionPanelMaximumclear
viewwidith (mm)
VisionPanel
Maximumclear
view
area (m 2 )
0.24
EN 16341:2008 Fire
Resistance
(minutes)
Integrity
60
EN 16341:2008 Fire
Resistance
(minutes)
Insulation
30
HFE601G
Single
leaf
doorset
HFE602G
Double
leaf
doorset
2450
1114
2.73
Pilkington
Glass
600
400
2450
1040
2.55
Pilkington
Glass
600
400
LPCB
Ref. No.
1101a/01
0.24
60
30
1101a/02
Notes:
1. The approved doorsets have been approved for use with the following hardware types:
a. Hinges - three Yin shi model 3D- 160ZW stainless steel 3D hinges (160mm x 111mm x 3.5mm thick). Fixed using five M5 x 18mm
long screws per hinge.
b. Locking mechanism - Steel Model ECO an ECO100 lockset, size 235mm long x 97mm wide x 24mm thick.
c. Door furniture - all door furniture shall be manufactured from Stainless steel.
d. Door closer - Steel GEZE TS4000 size 287mm long x 60mm wide x 24mm thick for use with single and double leaf doorsets.
e. Each door leaf incorporates a 23mm thick Pilkington insulated glass vision panel fitted using a beading of 1.5mm thick G.M.S,
insulated with 25mm by 2mm thick fire seal. Fixed using M5 x 60mm long screws.
27 Sep 2016
5
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
2. LPCB Ref. Nos. 1101a/01 and 1101a/02, doorsets have been tested in a concrete line surround and are approved when installed in
masonry or concrete wall surround with 1.5mm thick G.M.S. frame. Fixed using two M8 x 60mm long anchor bolts welded to 105mm x
47mm x 3mm thick steel plate at maximum 850 mm centres. The door frame gap is filled / insulated with cement sand mortar.
Hörmann KG Freisen
Bahnhofstrasse 43, D-66629 Freisen, Germany
Tel: +49 (0) 6855 9930 • Fax: +49 (0)6855 993 197
E-mail: k.schmitt.frs@hoermann.de • Website: www.hoermann.de
Certificate No: 655a to LPS 1056: Issue 6.2
Product
Name
HBS 60
C-1
HBS 60
C-2
HBS 90
C-1
HBS 90
C-2
HBS 120
C-1
HBS 120
C-2
HBS 30
D-1
HBS 60
D-1
HBS 90
D-1
HBS 30
F-2
HBS 60
F-2
HBS 90
F-2
Door
Type
Single
leaf
hinged
door
Double
leaf
hinged
door
Single
leaf
hinged
door
Single
leaf
hinged
door
Double
leaf
hinged
door
double
leaf
hinged
door
Single
leaf
hinged
door
Double
leaf
hinged
door
Single
leaf
hinged
door
Single
leaf
hinged
door
Single
leaf
hinged
door
Double
leaf
hinged
door
Double
leaf
hinged
door
Double
leaf
hinged
door
Vision
Panel Glass
Type
Maximum
leaf size
Maximum
leaf size
Maximum
leaf size
(see note 10)
(see note 10)
(see note 10)
Vision
Panel
max
clear
view
widith
(mm)
522
Vision
Panel
max
clear
view
area
(m²)
0.40
Transom
paneloption
available
3.088
Vision
Panel
max
clear
view
height
(mm)
937
LPCB
Ref. No.
(see note 5)
Fire
Resistance
(min BS 476
Part 22
Integrity /
Insulation
Height
(mm)
Widith
(mm)
Area (m²)
6.5mm
Georgianwired
2487
1242
Yes
60 / 0
655a/07
6.5mm
Georgianwired
2487
1242
3.088
937
522
0.40
Yes
60 / 0
655a/08
6.0mm
Pyran S
2487
1242
3.088
1002
264
0.22
Yes
90/ 0
655a/09
6.5mm
Georgianwired
2487
1242
3.088
781
435
0.34
Yes
90 / 0
6.0mm
Pyran S
2487
1242
3.088
1002
264
0.22
Yes
90 / 0
6.5mm
Georgianwired
2487
1242
3.088
781
435
0.34
Yes
90 / 0
6.0mm
Pyran S
2487
1242
3.088
1002
264
0.22
Yes
120 / 0
655a/11
6.0mm
Pyran S
2487
1242
3.088
1002
264
0.22
Yes
120 / 0
655a/12
Promaglas
90/35 Type
1.0
4225
1950
6.580
2085
1080
2.25
No
30 / 0
655a/13
Promaglas
90/35 Type
1.0
4062
1875
6.330
2085
1080
2.25
No
60 / 0
655a/14
Promaglas
90/35 Type
1.0
3770
1740
5.850
2085
1080
2.25
No
90 / 0
655a/15
-
3700
1694
5.69
-
-
-
No
30 / 30
655a/16
-
3700
1694
5.69
-
-
-
No
60 / 30
655a/17
-
3458
1583
5.21
-
-
-
No
90 / 30
655a/18
655a/10
Notes:
1. LPCB ref No. 655a/07 & 08 for alternative approved thin/thick rebated doorsets, frame profiles, sill arrangements & door furniture
please refer to BRE assessment report CC 94538 Review 4.
2. LPCB ref No. 655a/09, 10, 11 & 12 for alternative approved thin/thick rebated doorsets, frame profiles, sill arrangements & door
furniture please refer to BRE assessment report CC 292106.
6
27 Sep 2016
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
3.
a.
b.
c.
d.
4.
a.
b.
c.
d.
5.
6.
a.
b.
c.
7.
8.
9.
10.
11.
LPCB ref No. 655a/13, 14 & 15 doorsets are approved with the following hardware only.
Hinges - 3 x Schwarte
Locking mechanism - A BKS 6065 lock with an additional BKS6138 lock
Door closer - Geze TS 4000
Door furniture - Eco Schulte 0432-EN 179-DO 20.3 plastic-coated steel lever handles, four dog bolts along the hinge edge.
LPCB ref No. 655a/16, 17 & 18 doorsets are approved with the following hardware only
Hinges - 2 pairs (4) Schwarte FH-615-20-KO on each leaf (passive/active leaf)
Door closer - GEZE TS 4000 (active/passive leaf)
Locking mechanism - BKS 6065 lock with additional BKS 6138 catch lock (active leaf), and BKS 1899 rebate locking bolt (passive
leaf)
Door furniture - ECO Shulte DIN 18273-FS-SG-BB-PZ lever handles (active/passive leaf) along with ECO Shulte SR Basis-1 door
selector and three security bolts.
Where a doorset is fitted with a transom panel, the transom shall be up to a maximum height of 1000mm and not exceeding the
maximum permitted height of the doorset, and be of the same construction as the door leaf which is fastened to the door frame with
security bolts at the top and steel screws at the bottom at maximum 500mm centres. The transom panel may be fitted into the frame
type either with or without flexible perimeter seals. For LPCB ref no 655a/07, 08, 09, 10, 11 & 12 a vision panel may be fitted within
the transom panel in the same way as for the door leaf, see note 6.
LPCB ref No. 655a/07, 08, 09, 10, 11 & 12 Vision panel frames, steel channel spacers, minimum 1.0mm thick are welded to the leaf
and connected together through the door leaf with M5 steel screws and threaded sockets at 250mm nominal centres. LPCB ref No.
655a/07 and 08 frame depth which holds the 6.5mm-thick Georgian-wired glass is 15 mm. For LPCB ref No. 655a/09, 10 & 11 the
depth which holds the 6.5mm-thick Georgian-wired glass and the 6.0mm-thick Pyran S glass is 15mm For LPCB Ref No. 655a/12 the
depth which holds only the 6.0mm-thick Pyan S glass is 15mm.. Ceramic fibre tape, nominally 4mm thick, is fitted between the glass
and the frame. The single and double leaf doorsets may be fitted with one or more vision panels providing the following requirements
are met
Where more than one panel is fitted the max total vision area must not exceed 0.34m2 and each vision panel must be separated by
at least 165mm
The vision panel must be a minimum of 165mm from the leaf edge.
The arrangement of the vision panels in double leaf doorsets shall be the same in both leaves.
LPCB ref No. 655a/13, 14 & 15 Vision panel frames, comprising of 2mm-thick T-profiles, 30mm x 30mm, which are connected via
2mm fillet welds, the tail of the T-profiles are covered on both sides with strips of Promatect-L board, 30mm x 15mm. The vision panel
Promaglas 90/35 Type 1.0 is held in place by a 2mm-thick steel glazing bead 44.5mm x 20.5mm fixed back to the glazing support
frame with 4.2mm diameter x 50mm long self tapping screws. The perimeter on both sides is sealed against the glazing beads using
EPDM seals.
LPCB ref No. 655a /07, 08, 09, 10,11 & 12 doorsets may be installed in either Masonry minimum 215mm-thick, Concrete/concrete
block minimum 150mm-thick, autoclaved aerated concrete block walls minimum 215mm -thick / 400kg/m2 or Steel stud with
plasterboard or calcium silicate board partitions. Where the doorset is installed in a plasterboard or calcium silicate board partition, the
inside of the aperture to which the doorset is being fixed is lined with 2mm thick steel stud channel section, with flanges at least
40mm wide. The vertical studs either side of the aperture are fixed top and bottom to either a masonry or concrete supporting
construction, and the horizontal stud along the top of the aperture is fixed to the vertical studs at either end. The door frame shall also
be filled with fire resisting board and fixed to the partition using 5mm diameter self-tapping self-drilling screws.
LPCB ref No. 655a/13, 14, 15, 16, 17 & 18 doorsets may be installed in masonry or concrete walls minimum 240mm-thick.
The dimensions quoted are the individual door-leaf dimensions, not including the frame or overall clear opening.
LPCB ref No. 655a/07, 08, 09, 10,11,12, 13, 14, 15, 16, 17 & 18 doorsets the reliability (self-closing durability Ref. LPS 1056 clause
3.6) has no performance determined.
Industrial Door Engineering Limited
Winnington Avenue, Winnington, Northwich, Cheshire CW8 4EQ, United Kingdom
Tel: +44 (0)1606 871832 • Fax: +44 (0)1606 871482
E-mail: sales@industrial-door-eng.co.uk • Website: www.industrial-door-eng.co.uk
Certificate No: 165a to LPS 1056: Issue 6
Product Name
Door Type
Max
Height
(m)
Max
Width
(m)
Max
Area
(m2)
Sentry
Rolling
shutter
7.0
7.0
Sentry 2
Rolling
shutter
7.0
Sentry 1
Compact
Rolling
shutter
2.20
27 Sep 2016
49.0
Fire
Resistance
(min)
BS 476: Part
22
Integrity
240
Fire
Resistance
(min)
BS 476: Part
22
Insulation
0
7.0
49.0
120
0
3.40
7.48
60
0
Reliability
(self closing
Durability
Ref
LPS 1056
Clause 3.6)
No
performance
determined
No
performance
determined
No
performance
determined
LPCB Ref.
No.
165a/01
165a/02
165a/03
7
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
Product Name
Door Type
Max
Height
(m)
Max
Width
(m)
Max
Area
(m2)
Sentry 1
Rolling
shutter
2.20
2.20
4.84
Fire
Resistance
(min)
BS 476: Part
22
Integrity
60
Fire
Resistance
(min)
BS 476: Part
22
Insulation
0
Reliability
(self closing
Durability
Ref
LPS 1056
Clause 3.6)
No
performance
determined
LPCB Ref.
No.
165a/04
Notes:
1. LPCB Ref No. 165a/03 - Sentry 1 Compact rolling shutter can be fitted with either the flat or curved lath.
2. Industrial Door Engineering Limited are also Certified for the installation of fire rated Sentry rolling shutters against the requirements
of LPS 1271.
Kone Corporation
Kartanontie 1, Helsinki FI00330, Finland
Tel: +39 02 3395 2505
Website: www.kone.com
Certificate No: C1209a/C1210a to EN 81-58, EN 1634-3
KES201 and KES600
Product Name
KES201 (AMDL/V2.0)
KES600 (AMDL/V2.0)
LPCB Ref. No.
1209a/01 & 1210a/01
1209a/02 & 1210a/02
LBS Security Services Limited T/A LBS Group
Unit 6, Sterling Trading Estate, Rainham Road South, Dagenham, Essex RM10 8TX, United Kingdom
Tel: +44 (0)208 526 8572 • Fax: +44 (0)208 984 0378
E-mail: sales@lbsgroup.co.uk • Website: www.lbsgroup.co.uk
Certificate No: 247b to LPS 1056: Issue 5
Fireguard
Product
Name
Fireguard
Door Type
Rolling
shutter
Max Height
(m)
7.0
Max Width
(m)
10.0
Max Area
(m2
49.0
Fire ResistanceIntegrity/Insulation
(min)
240/0
LPCB Ref.
No.
247b/01
Notes:
1. LPCB Ref 247b/01 - for a list of the component's and sizes for the shutter dimensions up to the maximum stated please refer to BRE
Global assessment CC203994 Rev 2.
Lincs Doors Limited
Innovation Way, Europarc, Grimsby, North East Lincolnshire DN37 9TT, United Kingdom
Tel: +44 (0)1472 311057 • Fax: +44 (0)1472 311058
E-mail: enquiries@lincsdoors.co.uk • Website: www.lincsdoors.co.uk
Certificate No: 777a to LPS 1056: Issue 6
8
27 Sep 2016
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
Product
Name
Door Type
Max
Height
(m)
Max
Width
(m)
Max
Area
(m 2)
1.99
Fire
Resistance
(min)
BS 476: Part
22
Integrity
120
Fire
Resistance
(min)
BS 476: Part
22
Insulation
0
Pyroshield
Single leaf hinged
without vision panel
Single leaf hinged
without vision panel
Single leaf hinged
with vision panel
Single leaf hinged
with vision panel
Double leaf hinged
without vision panel
Double leaf hinged
without vision panel
Double leaf hinged
with vision panel
Double leaf hinged
with vision panel
2.114
0.942
2.536
1.130
2.48
60
0
2.114
0.942
1.99
90
0
2.536
1.130
2.48
60
0
2.114
1.884
3.98
120
0
2.536
2.260
4.96
60
0
2.114
1.884
3.98
90
0
2.536
2.260
4.96
60
0
Reliability
(self closing
durability
Ref. LPS 1056
Clause 3.6)
LPCB
Ref. No.
No performance
determined
No performance
determined
No performance
determined
No performance
determined
No performance
determined
No performance
determined
No performance
determined
No performance
determined
777a/01
777a/02
777a/03
777a/04
Notes:
1. LPCB Ref Nos. 777a/02 & 777a/04 - Vision panels, 10mm thick Pyrodur glass with maximum dimensions 245mm wide x 350mm
high.
2. LPCB Ref Nos. 777a/03 & 777a/04 - Double leaf doors, passive leaf must be fitted with a 3-point latching mechanism that engages in
the top of frame, sill and the active leaf, and the active leaf must be fitted with a full length astragal that overlaps the passive leaf by at
least 25mm.
3. LPCB Ref Nos. 777a/01, 777a/02, 777a/03 & 777a/04 - Door leaf skins can be fabricated from galvanised mild steel or grade 316
stainless steel.
4. LPCB Ref Nos. 777a/01, 777a/02, 777a/03 & 777a/04 - The doorsets can be installed in a rigid supporting construction such as brick,
blockwork or concrete. The doorsets can also be installed in a composite wall panel system which provides equal or greater fire
resistance than the doorset, when installed in a composite wall panel system the minimum fixing detail described in assessment
report CC223023 shall be provided.
Mercian Shutters Limited
Pearsall Drive, Brades Road Industrial Estate, Oldbury, West Midlands B69 2RA, United Kingdom
Tel: +44 (0)121 544 6124 • Fax: +44 (0)121 552 6793
E-mail: info@merciandoors.co.uk • Website: www.merciandoors.co.uk
Certificate No: 355b to LPS 1056: Issue 5 excluding installation
Product Name
Spec.
Door Type
Max
Height
(m)
Max
Width
(m)
Max
Area
(m2 )
SF Series
4
Rolling shutter
Rolling shutter
7.00
5.00
7.00
10.0
49.00
50.00
Fire
Resistance
(min)
BS 476: Part 22
Integrity
60, 120 & 240
60 & 120
Fire
Resistance
(min)
BS 476: Part 22
Insulation
0
0
LPCB Ref. No.
355b/01
Notes:
1. SF series rolling shutters ref 355b/01 - Reference must be made to assessment report no CC242948 issue 2 dated 11 June 2008 to
confirm component dimensions relevant to the system size and fire resistance required.
2. Mercian Shutters Ltd are also approved under LPS 1271 for installation of SF Series fire rated rolling shutters.
Middle East Insulation
P O Box 14225, Dubai, United Arab Emirates
Tel: +971 48801600 • Fax: +971 48801700
E-mail: contact@mei-uae.com
Certificate No: 708a to LPS 1056: Issue 6.1
27 Sep 2016
9
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
Product
Name
Maximum
leaf size
Height
(mm)
Maximum
leaf size
Width
(mm)
Maximum
leaf size
Area (m²)
Vision
Panel
Glass
type
FORT/HC
single leaf
doorset
2967
1196
3.22
N/A
2968
1056
2.84
2968
1056
2.84
2968
1056
2.84
2968
1056
2.84
2968
1056
2.84
2337
1017
2.16
2337
1017
2.16
2337
1017
2.16
2337
1017
2.16
2337
1017
2.16
2682
1196
2682
FORT/HC
double leaf
doorset
Vison
panel
Maximum
clear view
height
(mm)
-
Vision
Panel
Maximum
clear view
width
(mm)
-
Vision
panel
Maximum
clear view
area (m²)
BS 476:
Part 22
Fire
Resistance
(minutes)
Integrity
180
BS 476:
Part 22
Fire
Resistance
(minutes)
Insulation
0
LPCB
Ref. No.
-
Transom
Panel
Option
Available
(see note
2)
NO
6mm
Pyran S
6mm
Pyran S
6mm
Pyroshield
6mm
Pyroshield
N/A
500
805
200
0.10
YES
120
0
708a/03
230
0.17
YES
90
0
700
200
0.14
YES
90
0
805
230
0.17
YES
60
0
-
-
-
YES
120
0
6mm
Pyran S
6mm
Pyran S
6mm
Pyroshield
6mm
Pyroshield
N/A
700
200
0.14
YES
120
0
805
230
0.17
YES
90
0
700
200
0.14
YES
90
0
805
230
0.17
YES
60
0
-
-
-
YES
120
0
2.91
6mm
Pyran S
254
254
0.065
YES
120
0
1196
2.91
700
200
0.140
YES
90
0
2682
1196
2.91
700
200
0.140
YES
90
0
2682
1196
2.91
6mm
Pyran S
6mm
Pyroshield
6mm
Pyroshield
805
230
0.168
YES
60
0
708a/01
708a/05
708a/06
A copy of the certificate, confirming the full scope of approval including notes relating to the superscript references in the above table,
may be viewed online by clicking certificate link in the associated entry on www.RedBookLive.com
Saudi Factory for Fire Equipment Co.
Al-Kharj Road, 2nd Industrial Area, PO Box 4441, Riyadh 14334, Kingdom of Saudi Arabia
Tel: +966 1 265 0070 • Fax: +966 1 265 2190
E-mail: qa@sffeco.com.sa • Website: www.sffeco.com
Certificate No: 403c to LPS 1056 Issue 6.1
Product Name
Door
Type
Max
Height
(mm)
Max
Width
(mm)
Max
Area
(m²)
SFFECO FIRE DOOR
Single
leaf,
hinged
steel
doorset
2197
1092
2.399
Fire
Resistance
(minutes)
BS 476:
Part 22
Integrity
180
Fire
Resistance
(minutes)
BS 476:
Part 22
Insulation
0
Relibility
(self closing
durability
Ref. LPS
1056 Clause
3.6)
No
Performance
Determined
LPCB Ref. No.
403c/01
Notes.
1. LPCB Ref. No. 403c/01 The SFFECO FIRE DOOR doorset is approved to withstand a fire exposure from the opening side only, as
detailed in BRE Assessment report CC225304.
Stobich Brandschutz GmbH
Pracherstieg 6, D - 38644, Goslar, Germany
Tel: 00 49 532 157080 • Fax: 00 49 532 157080
E-mail: info@stobich.de • Website: www.stobich.com
Certificate No: 1064a to LPS 1056: Issue 6.1
10
27 Sep 2016
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
Product Name
Supporting
construction
Penetration
sealing
Max leaf
height
(m)
ECClos-Q conveyor
system closure
160mm thick
Plasterboard
partition
(see note 1)
200mm
blockwork wall
(see note 4)
200mm aerated
concrete
See note 2
ECClos-S conveyor
system closure
(horizontally closing)
ECClos-S conveyor
system closure
(vertically closing)
ECClos-Flex
conveyor system
closure (vertically
closing)
200mm aerated
concrete
160mm thick
Plasterboard
partition
(see note 1)
160mm thick
Plasterboard
partition
(see note 1)
240mm masonry
200mm aerated
concrete
200mm aerated
concrete
200mm aerated
concrete
Max leaf
area
(m²)
1.377
(note 3)
Max
leaf
width
(m)
1.940
(note 3)
Fire Resistance
(Min)
EN 1366-7
Integrity/Insulation
120/120
1064a/01
See note 5
See note 6
1.377
(note 3)
1.940
(note 3)
2.343
(note 3)
240/120
1064a/02
See note 7
3.177
3.374
10.719
120/90
1064a/03
See note 7
4.765
5.061
16.079
120/0
See note 8
3.187
3.374
10.753
120/120
See note 8
4.780
5.061
16.129
120/0
See note 9
See note 11
4.780
3100
5.061
3652
16.129
11.321
120/90
90/0
See note 12
3100
3852
11.321
60/0
See note 13
3100
3652
11.321
60/0
2.343
(note 3)
LPCB
Ref. No.
1064a/04
1064a/05
1064a/06
Notes:
1. LPCB Ref 1064a/01 - Standard flexible supporting construction according to BS EN 1366-7, table no 3, giving a fire resistance of 120
minutes, a cross bar type steel frame consisting of two uprights spanning from the floor to ceiling with a horizontal steel spanning
between the sections (all 100mm x 100mm x 4mm thick) is located within the partition, around the structual opening to bear the load
of the conveyor system. The conveyor system closure shall be face fixed and may be located on the exposed or unexposed side.
2. LPCB Ref 1064a/01 where the conveyor track penetrates the 160mm thick structural opening 1700mm (w) x 1500mm (h) a blockwork
wall/panel is formed below (built from the finsihed floor level), minimum density 350kg/m3, 150mm thick, 800mm high and 2060mm
wide, the top of the wall/panel is lined with a 20mm thick layer of Promatect-H board with the vertical edges protected with 100mm x
25mm x 3mm thick steel angles through fixed to the cross bar steel frame uprights (within the partition) at 200mm centres. A nominal
175mm opening is left around the conveyor track and blockwork wall/panel, this is built up with layers of Promatect-H25/H20/H15/H12
and H10, Promaseal-PL boards and Tenmat Firefly 102. Two 35mm lateral gaps are left between the boards and blockwork wall
which are friction fitted with Rockwool type RPB9 minimum density 90kg/m3 to allow movement/expansion.
3. LPCB Ref 1064a/01 and 1064a/02 The closure leaf is 'T' shaped and may be increased by a maximum of 15% in height and/or 15%
in width provided the surface area of the leaf is not increased by more than 20% from the dimensions given in the table above. The
leaf may not be reduced by more than 50% in width and 75% in height.
4. LPCB Ref 1064a/02 - Standard low density rigid wall construction according to BS EN 1366-7, table no 2, with a minimum density of
613kg/m3. The conveyor system closure shall be face to face fixed and may be located on the exposed or unexposed side.
5. LPCB Ref 1064a/02 where the conveyor track penetrates the 200mm thick structural opening 1700mm (w) x 1500mm (h), a
blockwork wall/panel is formed below minimum density 350kg/m3, 150mm thick and supported 300mm above the finished floor level
with 4 x 300mm and 1 x 500mm L profile fixing brackets 150mm x 100mm x 10mm thick with threaded rods and nuts (M10). The top
of the wall/panel is lined with a 20mm thick layer of Promatect-H board with the vertical edges protected with 100mm x 25mm x 3mm
thick steel angles though fixed back to the 200mm thick wall at 200mm centres. A nominal 175mm opening is left around the
conveyor track and blockwork wall/panel, this is built up with layers of Promatect-H25/H20/H15/H12 and H10, Promaseal-PL boards
and Tenmat Firefly 102. Two 35mm lateral gaps are left between the boards and blockwork wall which are friction fitted with
Rockwool type RPB9 minimum density 90kg/m3 to allow movement/expansion.
6. LPCB Ref 1064a/02 the penetration seal may incorporate a cable penetration, with maximum penetration size of 60mm x 220mm x
175mm (thickness x height x depth). The penetration must be lined with 20mm Promatect-H boards and the perimeter of the opening
sealed with one layer of Tenmat Firefly 102, all control cables must then individually pass through a mineral wool batt (Rockwool
RPB9 minimum density 90kg/m3) which is held in place within the penetration with EMPE glue.
7. LPCB ref No. 1064a/03 where the conveyor track penetrates the 200mm thick supporting construction a recess 175mm deep is
formed in the base of the 3000mm x 3000mm structural opening, a blockwork wall/panel 150mm thick is formed supported 260mm
below the structural opening with 5 x 500mm and 2 x 300mm L profile fixing brackets 150mm x100mm x 10mm thick with threaded
rods and nuts (M10).The top of the wall/panel is lined with a 20mm thick layer of Promatect-H board with the vertical edges protected
with 100mm x 25mm x 3mm thick steel angles through fixed back to the 200mm thick supporting construction. A nominal 60mm gap
is left around the vertical sides with a nominal 120mm gap left on the underside of the conveyor track and blockwork wall, this is built
up with layers of Promatect-H25/H20/H15, Promaseal-PL boards and Tenmat Firefly 102. Two 35mm lateral gaps are left between
the boards and blockwork wall which are friction fitted with Rockwool type RPB9 minimum density 90kg/m3 to allow movement
/expansion. The conveyor system closure shall be face fixed and may be located on the exposed side only.
27 Sep 2016
11
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
8. LPCB ref No. 1064a/04 where the conveyor track penetrates the 160mm thick supporting construction 3000mm (w) x 3000mm (h) a
blockwork wall/panel is formed below (built from the finished floor level), minimum density 350kg/m3, 150mm thick, 1240mm high and
3545mm wide, the top of the wall/panel is lined with a 20mm thick layer of Promatect-H board with the vertical edges protected with
100mm x 25mm x 3mm thick steel angles through fixed to the cross bar steel frame uprights (within the partition) at 100mm centres.
A recess positioned centrally 388mm deep x 1066mm long is formed on the top of the wall to accommodate the conveyor. A nominal
200mm opening is left around the conveyor track and blockwork wall/panel, this is built up with layers of Promatect-H25/H20/H15/H12
and H10, Promaseal-PL boards and Tenmat Firefly 102. Two 35mm lateral gaps are left between the boards and blockwork wall
which are friction fitted with Rockwool type RPB9 minimum density 90kg/m3 to allow movement /expansion. The conveyor system
closure shall be face fixed and may be located on the un-exposed side only.
9. LPCB ref No. 1064a/05 where the conveyor track penetrates the 240mm thick supporting construction a recess 110mm deep x
695mm long is formed in the base of the 3000mm x 3000mm structural opening, a blockwork wall/panel 150mm thick is formed and
supported 480mm below the structural opening with 5 x 500mm and 2 x 300mm L profile fixing brackets 150mm x100mm x 10mm
thick with threaded rods and nuts (M10).The top of the wall/panel is lined with a 20mm thick layer of Promatect-H board with the
vertical edges protected with 100mm x 25mm x 3mm thick steel angles through fixed back to the 240mm supporting construction. A
nominal 60mm gap is left around the vertical sides and underside of the conveyor track and blockwork wall, this is built up with layers
of Promatect-H25/H20/H15/H12/H10, Promaseal-PL boards and Tenmat Firefly 102. Two 35mm lateral gaps are left between the
boards and blockwork wall which are friction fitted with Rockwool type RPB9 minimum density 90kg/m3 to allow movement
/expansion. The conveyor system closure shall be face fixed and may be located on the exposed side only.
10. LPCB ref No. 1064a/06 The locking mechanism for the ECClos-Flex system is located at the base of the structural opening and is
fixed to the supporting construction via a Z section and continuous 10mm-thick x 268mm high Durasteel plate section. The conveyor
system closure shall be face fixed and may be located on the exposed side only.
11. LPCB ref No. 1064a/06 The chain conveyor track system where it penetrates the locking mechanism (see note 10) consists of a C
profile 105 x 56 x 3mm surrounded on three sides with 12.5mm fireproof gypsum plaster board through fixed to Durasteel board using
brackets and 5mm blind steel rivets, the inside of the C section is packed with layers of intumescent fabric (Heliotex EW 120), or
alternatively a C profile 105 x 56 x 3mm surrounded by two layers of intumescent fabric (Heliotex EW 120), fixed using metal strips to
the Durasteel board.
12. LPCB ref No. 1064a/06 The belt conveyor track system (450mm x 105mm) where it penetrates the locking mechanism (see note 10)
is protected up to a depth of 70mm with calcium silicate boards which are fastened to the Durasteel locking mechanism using
brackets and 5mm thick blind steel rivets. Where there are gaps between the conveyor track and the calcium silicate boards (approx
4mm) they are lined with a layer of Tenmat firefly 102.
13. LPCB ref No. 1064a/06 The chain conveyor track system where it penetrates the locking mechanism (see note 10) consists of a C
profile 105 x 56 x 3mm surrounded on three sides with mineral wool minimum density 150kg/m3, the mineral wool has a 20mm deep
channel cut out and is inserted tightly onto the Durasteel board, the inside of the C section is packed with mineral wool, where there
are gaps between the conveyor track and mineral wool (approx 4mm) they are lined with a layer of Tenmat firefly 102.
To view the applicable drawing, please click on the product name in the entry on www.RedBookLive.com
Sunray Engineering Limited
Kingsnorth Industrial Estate, Wotton Road, Ashford, Kent TN23 6LL, United Kingdom
Tel: +44 (0)1233 639039 • Fax: +44 (0)1233 625137
E-mail: sales@sunraydoors.co.uk • Website: www.sunraydoors.co.uk
Certificate No: 234b to LPS 1056: Issue 6.1
Product
Name
Door Type
Max
Height
(m)
Max
Width
(m)
Max
Area
(m 2)
Vision
panel glass
type
Vision panel
maximum
clear view
height (mm 2)
-
Vision panel
maximum
clear view
width (mm 2)
-
Vision panel
maximum
clear view
area (m 2)
-
Fire resistance (min)
BS 476: Part 22
Integrity/Insulation
LPCB
Ref. No.
ExcluDoor
4
ExcluDoor
4 Mk2 FR
Single-leaf
hinged door
Single-leaf
hinged door
2.250
1.050
2.400
-
2.702
1.328
3.25
30 / 0
234b/01
ExcluGlass
4 Vision
Panel
-
-
-
-
180 / 0
234b/02
Single-leaf
hinged door
Single-leaf
hinged door
2.350
1.155
2.71
2.702
1.328
3.25
-
-
-
240 / 0
ExcluGlass
4 Vision
Panel
ExcluGlass
4 Vision
Panel
-
280
380
0.1064
60 / 0
Double-leaf
hinged door
2.702
1.328
3.25
280
380
0.1064
60 / 0
Double-leaf
hinged door
Unequal
width
Double-leaf
hinged door
Unequal
width
Double-leaf
hinged door
2.702
1.328
3.25
-
-
-
240 / 0
2.702
1.328
3.25
ExcluGlass
4 Vision
Panel
280
380
0.1064
60 / 0
2.702
1.328
3.25
-
-
-
-
240 / 0
234b/03
Notes:
For BS 476: Part 22 applications
1. LPCB Ref 234b/01, 234b/02 and 234b/03 are also certified to Security Rating 4 against the requirements of LPS 1175.
2. Sunray Engineering Ltd is also approved to LPS 1271 for installation of fire and security doors, see approval listing for details.
12
27 Sep 2016
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
3. LPCB Ref No. 234b/02 and 234b/03, Doorsets are approved to withstand a fire exposure to the closing side only as detailed in BRE
Assessment CC 285805B
4. LPCB Ref No. 234b/02 and 234b/03, may be fitted with one or more Eurospec SWE1010 stainless steel door viewers.
5. LPCB Ref No 234b/02 and 234b/03, the ExcluDoor 4 Mk2, double leaf doorset, may have a vision panel installed in either the passive
or the active leaf.
Certificate No: 234b to LPS 1056: Issue 6.1
Product
Name
Door Type
Max leaf
Height
(m)
Max
leaf
Width
(m)
Max
leaf
Area
(m 2 )
Vision panel
glass type
Vision panel
maximum clear
view height
(mm 2)
Vision panel
maximum clear
view width
(mm 2)
Vision panel
maximum
clear view area
(m 2)
ExcluDoor
4, Mk2 FR
ExcluDoor
4 Mk2 FR
Single-leaf
hinged door
Single-leaf
hinged door
Single-leaf
hinged door
Double-leaf
hinged door
Double-leaf
hinged door
Unequal
width
Double-leaf
hinged door
Unequal
width
Double-leaf
hinged door
Single-leaf
hinged door
Single-leaf
hinged door
Single-leaf
hinged door
Double-leaf
hinged door
Double-leaf
hinged door
Unequal
width
Dobule-leaf
hinged door
Unequal
width
Double-leaf
hinged door
2.702
1.328
3.25
-
-
-
2.350
1.155
2.71
ExcluGlass 4
Vision Panel
-
Fire
resistance
(min) EN
1634-1:2008
Integrity /
Insulation
180 / 0
-
-
-
240 / 0
2.702
1.328
3.25
280
380
0.1064
60 / 0
2.702
1.328
3.25
280
380
0.1064
60 / 0
2.702
1.328
3.25
ExcluGlass 4
Vision Panel
ExcluGlass 4
Vision Panel
-
-
-
-
240 / 0
2.702
1.328
3.25
ExcluGlass 4
Vision Panel
280
380
0.1064
60 / 0
2.702
1.328
3.25
-
-
-
-
240 / 0
2.702
1.328
3.25
-
-
-
-
180 / 0
2.350
1.155
2.71
-
-
-
-
240 / 0
2.702
1.328
3.25
280
380
0.1064
240 / 0
2.702
1.328
3.25
ExcluGlass 4
Vision Panel
-
-
-
-
340 / 0
2.702
1.328
3.25
280
380
0.1064
60 / 0
2.702
1.328
3.25
ExcluGlass 4
Vision Panel
-
-
-
-
240 / 0
2.702
1.328
3.25
ExcluGlass 4
Vision Panel
280
380
0.1064
60 / 0
ExcluDoor
3 Mk3 FR
LPCB
Ref. No.
234b/02
234b/03
234b/04
234b/05
Notes:
For EN 1634-1:2008 applications
1. LPCB Ref: 234b/02, 234b/03, 234b/04 and 234b/05 Doorsets may be fitted with a plain outer face so that there is no method of
external access.
2. LPCB Ref: 234b/02, 234b/03, 264b/04 and 234b/05 are also certificated to Security Rating 4 against the requirements of LPS 1175.
3. Sunray Engineering Ltd is also approved to LPS 1271 for installation of fire and security doors, see approval listing for details.
4. LPCB ref no 234b/02, 234b/03, 234b/04 and 234b/05, Doorsets are approved to withstand a fire exposure to the closing side only as
detailed in BRE Assessment CC 285805A
5. LPCB ref no 234b/02, 234b/03, 234b/04 and 234b/05 may be fitted with one or more Eurospec SWE1010 stainless steel door
viewers.
6. LPCB ref no 234b/02, 234b/03, 234b/04 and 234b/05, the ExcluDoor 4 MK2, double leaf doorsets, may only have the vision panel
installed in the active leaf.
7. LPCB Ref: 234b/02, 234b/03, 234b/04 and 234b/05, Doorsets are approved with the following Surelock Slimline three-point lock
system as shown below.
27 Sep 2016
13
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
Entry
Description
Code
Key
3-point bolting
3-point bolting
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
3-point
deadlocking
SL304
SL305
*
*
SL301

Access
control
Exit
Combination
Key
Turnknob
Access
control
Panic
Emergency





SL303
SL310

SL311

SL313

SL314

SL315

SL320
*

SL321
*

SL322
*

SL323
*

SL324
*

SL325
*


















SL330

SL335


 - included as standard
* - optional enhancement
Technocover Limited (incorporating TechnoRail and Strataform)
Henfaes Lane, Welshpool, Powys SY21 7BE, United Kingdom
Tel: +44 (0)1938 555511 • Fax: +44 (0)1938 555527
E-mail: techadvice@technocover.co.uk • Website: www.technocover.co.uk
Certificate No: 450g to LPS 1056: Issue 6
Product
Name
Door Type
Maximum
Leaf Size
Height
(mm)
Maximum
Leaf Size
Width
(mm)
Maximum
Leaf Size
(m2 )
Door Hardware
Variations
Sentinel
UltraSecure
DS1/LV
Single leaf
outward
opening
hinged
doorset
uninsulated
2200
940
2.06
SM3,SM4,SM6,SM7,
SM8,SM10,SM13,SM14,
SM16,SM17,SM18,SM20
SM23,SM24,SM26,SM27,
SM28 & SM30.
14
BS476:
Part 22
Fire
resistance
(minutes)
Integrity
240
BS476:
Part 22
Fire
resistance
(minutes)
Insulation
0
LPCB
Ref.
No.
450g/01
27 Sep 2016
PART 2: SECTION 1.1
FIREBREAK DOORS AND SHUTTERS
Product
Name
Door Type
Maximum
Leaf Size
Height
(mm)
Maximum
Leaf Size
Width
(mm)
Maximum
Leaf Size
(m2 )
Door Hardware
Variations
BS476:
Part 22
Fire
resistance
(minutes)
Integrity
120
BS476:
Part 22
Fire
resistance
(minutes)
Insulation
0
LPCB
Ref.
No.
DS1/LV
Single leaf
outward
opening
hinged
doorset
uninsulated
DS2/LV
Double leaf
outward
opening
hinged
doorset
uninsulated
DS2/LV
Double leaf
outward
opening
hinged
doorset
uninsulated
2640
1128
2.58
SM3,SM4,SM6,SM7,
SM8,SM10,SM13,SM14,
SM16,SM17,SM18,SM20
SM23,SM24,SM26,SM27,
SM28 & SM30.
2768
1218
2.80
SM3,SM4,SM6,SM7,
SM8,SM10,SM13,SM14,
SM16,SM17,SM18,SM20
SM23,SM24,SM26,SM27,
SM28 & SM30.
120
0
450g/02
2215
975
2.15
SM3,SM4,SM6,SM7,
SM8,SM10,SM13,SM14,
SM16,SM17,SM18,SM20
SM23,SM24,SM26,SM27,
SM28 & SM30.
240
0
Notes:
1. The Sentinel UltraSecure Doorsets are also certified to Security Level 3 & 4 against the requirements of LPS1175: Issue 6.
2. LPCB ref 450g/01 & 450g/02, for approved Door Hardware Variations please refer to Manufacturer's Technical Literature.
3. LPCB ref 450g/01 & 450g/02, the Sentinel UltraSecure Doorsets are approved when installed in concrete/masonry walls or drywall
partitions.
27 Sep 2016
15
PART 2: SECTION 1.2
LIFT LANDING DOORS
This section lists lift landing doors approved to LPS 1056 Test and Evaluation requirements for the LPCB
Approval and Listing of Fire Doorsets, Lift Landing Doors and Shutter Assemblies. LPS 1056 is based upon
relevant BS or European test criteria and not only looks at the fire integrity and insulation (where applicable)
but also includes reliability cyclic tests and grading.
Currently there are no products listed in this section.
16
27 Sep 2016
PART 2: SECTION 2
FIRE AND SECURITY DOOR AND SHUTTER INSTALLERS
This section lists companies approved to LPS 1271 Requirements for LPCB Approval and Listing of
companies installing fire and security doors, doorsets, shutters and smoke/fire barriers. This standard was
developed to ensure that the product performance is not compromised by poor installation of the fire or
security door or shutter. This section includes manufacturers installing doors and independent installation
companies.
The latest version is LPS 1271: Issue 2.
Information regarding the security of doors is available in Part 4: Section 5.
Avert Fire (UK) Ltd
P O Box 248, Dawes lane, Scunthorpe DN16 1DW, United Kingdom
Tel: +44 (0)1724 853712 • Fax: +44 (0)1724 278848
E-mail: admin@avertfire.co.uk; • Website: www.avertfire.co.uk
Certificate No. 850PIa to LPS 1271: Issue 2
Approved installer of:
- Fire Doors and Doorsets
Checkmate Fire Solutions Ltd
Unit B9, Lowfields Close, Lowfields Business Park, Elland, West Yorkshire HX5 9DX, United Kingdom
Tel: +44 (0) 1279 850021 • Fax: +44 (0) 1279 850061
E-mail: info@checkmatefire.com • Website: www.checkmatefire.com
Certificate No. 860PIb to LPS 1271: Issue 2
Approved installer of:
- Fire Doors and Doorsets
Checkmate Fire Solutions Ltd
Unit 1, Woodgates Farm, Woodgates End, Dunmow, Essex CM6 2BN, United Kingdom
Tel: +44 (0) 1279 850021
E-mail: info@checkmatefire.com • Website: www.checkmatefire.com
Certificate No. 860PIb to LPS 1271: Issue 2
Approved installer of:
- Fire Doors and Doorsets
Clark Door Limited
Unit F Central, Kingmoor Park, Carlisle, Cumbria CA6 4SJ, United Kingdom
Tel: +44 (0)1228 522321 • Fax: +44 (0)1228 401854
E-mail: mail@clarkdoor.com • Website: www.clarkdoor.com
Certificate No. 106b to LPS 1271: Issue 1
Approved installer of Fireman series of fire rated doorsets.
27 Sep 2016
17
PART 2: SECTION 2
FIRE AND SECURITY DOOR AND SHUTTER INSTALLERS
Ductclean (UK) Limited
1 Woodfield Road, Welwyn Garden City, Hertfordshire AL7 1JQ, United Kingdom
Tel: 0870 1129196 • Fax: 0870 112 9197
E-mail: jamie.carraher@ductclean.co.uk • Website: www.ductclean.co.uk
Certificate No. 1276PI to LPS 1271: Issue 2
Approved installer of:
- Fire Doors and Doorsets
Grange Door Systems
Unit 18/8 Dryden Road, Bilston Glen Industrial Estate, Edinburgh EH20 9LZ, United Kingdom
Tel: +44 (0)131 440 7000
E-mail: sales@grangedoor.com • Website: www.grangedoor.com
Certificate No. 573b to LPS 1271: Issue 2
Approved installer of:
- Fire Doors and Doorsets
Gunfire Trading Divison of Gunite (Eastern) Limited
Endeavour House, Compass Point, St Ives, Cambridgeshire PE27 5JL, United Kingdom
Tel: +44 (0)1480 466880 • Fax: +44 (0)1480 308999
E-mail: admin@gunite.co.uk • Website: www.gunite.co.uk
Certificate No. 848PIa to LPS 1271: Issue 1
Approved installer of certified fire doors and doorsets
Hart Door Systems
Redburn Road, Westerhope Industrial Estate, Westerhope, Newcastle upon Tyne NE5 1PJ, United Kingdom
Tel: +44 (0)191 214 0404 • Fax: +44 (0)191 271 1611
E-mail: info@hartdoors.com • Website: www.hartdoors.com
Certificate No. 016b to LPS 1271: Issue 1
Approved installer of Firebrand fire rated rolling shutters.
Industrial Door Engineering Limited
Winnington Avenue, Winnington, Northwich, Cheshire CW8 4EQ, United Kingdom
Tel: +44 (0)1606 871832 • Fax: +44 (0)1606 871482
E-mail: sales@industrial-door-eng.co.uk • Website: www.industrial-door-eng.co.uk
Certificate No. 165c to LPS 1271: Issue 1
Approved installer of Sentry, Sentry 1, Sentry 1 Compact and Sentry 2 fire rated rolling shutters.
18
27 Sep 2016
PART 2: SECTION 2
FIRE AND SECURITY DOOR AND SHUTTER INSTALLERS
Kone PLC
Global House, Station Place, Chertsey, Surrey KT16 9HW, United Kingdom
Tel: +44 (0)8451 999 999 • Fax: +44 (0)870 7701144
E-mail: sales.marketinguk@kone.com • Website: www.kone.co.uk
Helpdesk KONE ONE
KONE PLC, Global House, Station Place, Chertsey, Surrey KT16 9HW, United Kingdom
Tel: +44 (0)8451 999 999 • Fax: +44 (0)870 770 114
E-mail: sales.marketinguk@kone.com • Website: www.kone.co.uk
Certificate No. 122P to LPS 1271: Issue 1
Installation of Certified fire rated Rolling Shutters, Hinged Doorsets and Lift Landing Sliding Folding Shutters
Full UK Coverage
Manning Construction Limited
Brodawel, Coychurch, Bridgend CF35 5BU, United Kingdom
Tel: 01656 862333 • Fax: 01656 861439
E-mail: seuston@manning-online.com • Website: www.manning-online.com
Certificate No. 1141PI to LPS 1271: Issue 1
Approved installer of certified fire doors and shutters
Mercian Shutters Limited
Pearsall Drive, Brades Road Industrial Estate, Oldbury, West Midlands B69 2RA, United Kingdom
Tel: +44 (0)121 544 6124 • Fax: +44 (0)121 552 6793
E-mail: info@merciandoors.co.uk • Website: www.merciandoors.co.uk
Also at:
Mercian Industrial Doors (Southern) Limited, t/a Mercian Industrial Doors Southern, 10-12 Galleymead Road,
Colnbrook, Slough, Berkshire SL3 0EN, United Kingdom
Certificate No. 355c to LPS 1271: Issue 1
Approved installer of SF series of fire rated rolling shutters.
Nene Valley Fire and Acoustic Limited
2a New Street, Irthlingborough, Northamptonshire NN9 5UG, United Kingdom
Tel: +44 (0) 1933 650650 • Fax: +44 (0) 1933 650001
E-mail: enquiries@nenevalleyfire.com • Website: www.nenevalleyfireandacoustic.com
Certificate No. 1021PIb to LPS 1271: Issue 2
Approved installer of:
- Fire Doors and Doorsets
27 Sep 2016
19
PART 2: SECTION 2
FIRE AND SECURITY DOOR AND SHUTTER INSTALLERS
Prestige Fire Door Services Limited
15 Kings Road, Fleet, Hampshire GU51 3DH, United Kingdom
Tel: +44 (0)1252 645534 • Fax: +44 (0)1252 678742
E-mail: admin@prestigefiredoorservices.com • Website: www.prestigefiredoorservices.com
Certificate No. 1066PI to LPS 1271: Issue 1
Approved Installer of certified fire doors and doorsets
R Lewis & Co. (UK) Ltd
Unit 7 and 8, Parklands Industrial Estate, East Moors Road, Cardiff CF24 5JP, United Kingdom
Tel: +44 (0) 2920 215716
E-mail: craig@rlewisandcoukltd.com • Website: www.rlewisandcoukltd.com
Certificate No. 1006PIa to LPS 1271: Issue 2.0
Company assessed and approved for installation of passive fire protection products under the following scope.
Appendix 2 - Fire Doors & Doorsets
Safe Partnership
3 East Street, Wareham, Dorset BH20 4NN, United Kingdom
Tel: +44 (0)1929 551100 • Fax: +44 (0)1929 553300
E-mail: safe@safepartnership.org • Website: www.safepartnership.co.uk
Certificate No. 835c to LPS 1271: Issue 1
Approved installer of Safe Partnership Ltd Safe Door timber security doors as approved under LPS 1175 (Ref Certificate 835a).
Sunray Engineering Limited
Kingsnorth Industrial Estate, Wotton Road, Ashford, Kent TN23 6LL, United Kingdom
Tel: +44 (0)1233 639039 • Fax: +44 (0)1233 625137
E-mail: sales@sunraydoors.co.uk • Website: www.sunraydoors.co.uk
Certificate No. 234e to LPS 1271: Issue 1
Approved installer of certified Sunray, ExecDoor 1, ExecDoor 2, ExcluDoor 3, ExcluDoor 3 Mk2, ExcluDoor 3 Mk2 FR, ExcluDoor 3 Mk3
FR, ExcluDoor 4. ExcluDoor 4 Mk2 FR. ExcluDoor4 Mk3, ExcluDoor 5 and ExcluDoor 6
(Ref product certificates 234b, 234c and 234d)
TEK Interiors Limited
Unit 10A Beehive Business Centre, Beehive Lane, Great Baddon, Chelmsford, Essex CM2 9TE, United
Kingdom
Tel: 01245 250657
E-mail: Neil@tekfiredoorservices.co.uk • Website: www.tekfiredoorservices.co.uk
Certificate No. 1300PIb to LPS 1271: Issue 2
Approved installer of:
- Fire Doors and Doorsets
20
27 Sep 2016
PART 2: SECTION 3
INSPECTION, REPAIR AND MAINTENANCE OF FIRE AND SECURITY DOORS AND SHUTTERS
This section lists companies approved to LPS 1197 Requirements for LPCB Approval and Listing of
companies inspecting, repairing and maintaining fire and security doors, doorsets, shutter and active
smoke/fire barriers.
The long term performance of products covered in this standard is dependent upon regular inspection, repair
and maintenance in accordance with the manufacturer’s recommendations. Companies approved to LPS
1197 have demonstrated their ability to carry out this work effectively. The listings include the geographical
areas and products covered by the companies and the level of service provided.
The latest version is LPS 1197: Issue 4.2.
123 Fire (a division of MB Plant Limited)
Swift House Business Centre, 16 High Street S43 3UX, United Kingdom
Tel: 0114 360 3213
E-mail: andrewbell@123fire.co.uk • Website: www.123fire.co.uk
Certificate No. 1133PIa to LPS 1197 : Issue 4
Company assessed and approved for:
- Inspection
- Maintenance services and 'one off' general repair
Of:
Fire resistant doors and doorsets
Product groups:
Hinged and pivoted timber doorsets
Ascot Doors Limited
Britannia Way Industrial Park, Union Road, Bolton BL2 2HE, United Kingdom
Tel: +44 (0)1204 545801 • Fax: +44 (0)1204 545800
E-mail: sales@ascotdoors.co.uk • Website: www.ascotdoors.co.uk
Certificate No. 131c to LPS 1197 Issue 3
General servicing/maintenance
Maintenance contracts
24 hour answering service
24 hour emergency service
Yes
Yes
Yes
Yes
On site within 4 hours of all of England, Scotland and Wales.
Assa Abloy Entrance Systems Limited
7 Churchill Way, 35A Business Park, Chapeltown, Sheffield, South Yorkshire S35 2PY, United Kingdom
Tel: +44 (0)870 609 4474 • Fax: +44 (0)114 257 4397
E-mail: service.uk.aaes@assaabloy.com • Website: www.assaabloyentrance.co.uk
Certificate No. 001c to LPS 1197: Issue 4
Company assessed and approved for:
- Inspection
- Maintenance services and 'one off' general repair
- Inspection, maintenance services and repair, term contracts
Of:
Fire resistant shutters
27 Sep 2016
21
PART 2: SECTION 3
INSPECTION, REPAIR AND MAINTENANCE OF FIRE AND SECURITY DOORS AND SHUTTERS
Product groups:
Steel rolling shutters
Avert Fire (UK) Ltd
P O Box 248, Dawes lane, Scunthorpe DN16 1DW, United Kingdom
Tel: +44 (0)1724 853712 • Fax: +44 (0)1724 278848
E-mail: admin@avertfire.co.uk; • Website: www.avertfire.co.uk
Certificate No. 850PIb to LPS 1197 : Issue 4
Approved installer of certified fire doors and doorsets.
Company assessed and approved for:
- Inspection
- Maintenance services and 'one off' general repair
Of:
Fire resistant doors and doorsets
Product groups:
Hinged and pivoted steel doorsets
Hinged and pivoted timber doorsets
Checkmate Fire Solutions Ltd
Unit 1, Woodgates Farm, Woodgates End, Dunmow, Essex CM6 2BN, United Kingdom
Tel: +44 (0) 1279 850021
E-mail: info@checkmatefire.com • Website: www.checkmatefire.com
Certificate No. 860PIa to LPS 1197 : Issue 4
Company assessed and approved for:
- Inspection
- Maintenance services and 'one off' general repair
Of:
Fire resistant doors and doorsets
Checkmate Fire Solutions Ltd
Unit B9, Lowfields Close, Lowfields Business Park, Elland, West Yorkshire HX5 9DX, United Kingdom
Tel: +44 (0) 1279 850021 • Fax: +44 (0) 1279 850061
E-mail: info@checkmatefire.com • Website: www.checkmatefire.com
E-mail: info@checkmatefire.co
Certificate No. 860PIa to LPS 1197 : Issue 4
Company assessed and approved for:
- Inspection
- Maintenance services and 'one off' general repair
Of:
Fire resistant doors and doorsets
Product groups:
Hinged and pivoted timber doorsets
22
27 Sep 2016
PART 2: SECTION 3
INSPECTION, REPAIR AND MAINTENANCE OF FIRE AND SECURITY DOORS AND SHUTTERS
DoorCheck Limited
192b Balfour Road, Ilford, Essex IG1 4JA, United Kingdom
Tel: 0208 553 3307
E-mail: info@door-check.co.uk • Website: www.door-check.co.uk
Certificate No. 1119PI to LPS 1197: Issue 4
General servicing and maintenance of fire doors and fire doorsets
Company assessed and approved for:
- Inspection
- Maintenance services and 'one off' general repair
Of:
Fire resistant doors and doorsets
Product groups:
Hinged and pivoted timber doorsets
Fire Safety Services (UK) Limited
Progress House, 15 Railton Road, Woburn Road Industrial Estate, Kempston, Bedford MK42 7PW, United
Kingdom
Tel: 01234 854100 • Fax: 01234 840777
E-mail: enquiries@firesafetyservices.co.uk • Website: www.firesafetyservices.co.uk
Certificate No. 1145PIb to LPS 1197:4
Company assessed and approved for:
- Inspection
- Maintenance services and 'one off' general repair
- Inspection, maintenance services and repair, term contracts
Of:
Fire resistant doors and doorsets
Smoke fire barriers
Fire resistant shutters
Product groups:
Hinged and pivoted timber doorsets
Grange Door Systems
Unit 18/8 Dryden Road, Bilston Glen Industrial Estate, Edinburgh EH20 9LZ, United Kingdom
Tel: +44 (0)131 440 7000
E-mail: sales@grangedoor.com • Website: www.grangedoor.com
Certificate No. 573a to LPS 1197: Issue 4
Company assessed and approved for:
- Inspection
- Inspection, maintenance services and repair, term contracts
Of:
Fire resistant shutters
Product groups:
Steel rolling shutters
27 Sep 2016
23
PART 2: SECTION 3
INSPECTION, REPAIR AND MAINTENANCE OF FIRE AND SECURITY DOORS AND SHUTTERS
Industrial Door Engineering Limited
Winnington Avenue, Winnington, Northwich, Cheshire CW8 4EQ, United Kingdom
Tel: +44 (0)1606 871832 • Fax: +44 (0)1606 871482
E-mail: sales@industrial-door-eng.co.uk • Website: www.industrial-door-eng.co.uk
Certificate No. 165b to LPS 1197: Issue 3
General servicing/maintenance
Maintenance contracts
24 hour answering service
24 hour emergency service
Yes
Yes
Yes
Yes
On site within 4 hours of call in Cheshire, Clwyd, Derbyshire, Greater Manchester, Gwynedd, Lancashire, Merseyside and Yorkshire.
Kone PLC
Global House, Station Place, Chertsey, Surrey KT16 9HW, United Kingdom
Tel: +44 (0)8451 999 999 • Fax: +44 (0)870 7701144
E-mail: sales.marketinguk@kone.com • Website: www.kone.co.uk
Helpdesk KONE ONE
KONE PLC, Global House, Station Place, Chertsey, Surrey KT16 9HW, United Kingdom
Tel: +44 (0)8451 999 999 • Fax: +44(0)870 770 1144
E-mail: sales.marketinguk@kone.com • Website: www.kone.co.uk
Certificate No. 122n to LPS 1197
General servicing/maintenance
Maintenance contracts
24 hour answering service
24 hour emergency service
Yes
Yes
Yes
Yes
Onsite within 4 hours of call, Full UK Coverage
Konecranes Industrial Door Services
Unit 1B, Sills Road, Willow Farm Business Park, Castle Donnington, Leicestershire DE74 2US, United
Kingdom
Tel: 0844 5611 007 • Fax: 01332 5697781
E-mail: glen.gurney@konecranes.com • Website: www.konecranes.com
Certificate No. 908a to LPS 1197: Issue 3
General servicing/maintenance
Maintenance contracts
24 hour answering service
24 hour emergency service
Yes
Yes
Yes
Yes
On site within 4 hours of call in West Midlands, Staffordshire, Hereford, Worcester, Warwickshire, Milton Keynes, Northamptonshire,
Peterborough, Lincolnshire, Nottinghamshire, Derbyshire, South Yorkshire and Leicestershire.
24
27 Sep 2016
PART 2: SECTION 3
INSPECTION, REPAIR AND MAINTENANCE OF FIRE AND SECURITY DOORS AND SHUTTERS
LBS Security Services Limited T/A LBS Group
Unit 6, Sterling Trading Estate, Rainham Road South, Dagenham, Essex RM10 8TX, United Kingdom
Tel: +44 (0)208 526 8572 • Fax: +44 (0)208 984 0378
E-mail: sales@lbsgroup.co.uk • Website: www.lbsgroup.co.uk
Certificate No. 247a to LPS 1197: Issue 4
Company assessed and approved for:
- Inspection
- Maintenance services and 'one off' general repair
- Inspection, maintenance services and repair, term contracts
- Emergency repair and response services
Of:
Fire resistant shutters
Product groups:
Steel rolling shutters
Mercian Shutters Limited
Pearsall Drive, Brades Road Industrial Estate, Oldbury, West Midlands B69 2RA, United Kingdom
Tel: +44 (0)121 544 6124 • Fax: +44 (0)121 552 6793
E-mail: info@merciandoors.co.uk • Website: www.merciandoors.co.uk
also at:
Mercian Industrial Doors (Southern) Limited, t/a Mercian Industrial Doors Southern, 10-12 Gallymead Road,
Colnbrook, Slough, Berkshire SL3 0EN, United Kingdom
Certificate No. 355a to LPS 1197: Issue 3
General servicing/maintenance
Maintenance contracts
24 hour answering service
24 hour emergency service
Yes
Yes
Yes
Yes
On site within 4 hours of call in Hereford and Worcestershire, Shropshire, Staffordshire, Warwickshire and West Midlands.
Nene Valley Fire and Acoustic Limited
2a New Street, Irthlingborough, Northamptonshire NN9 5UG, United Kingdom
Tel: +44 (0) 1933 650650 • Fax: +44 (0) 1933 650001
E-mail: enquiries@nenevalleyfire.com • Website: www.nenevalleyfireandacoustic.com
Certificate No. 1021PIa to LPS 1197: Issue 4
Company assessed and approved for:
- Inspection
- Maintenance services and 'one off' general repair
Of:
Fire resistant doors and doorsets
Product groups:
Hinged and pivoted timber doorsets
27 Sep 2016
25
PART 2: SECTION 3
INSPECTION, REPAIR AND MAINTENANCE OF FIRE AND SECURITY DOORS AND SHUTTERS
Rite Industrial Doors Ltd
9H Longbrooks, Knowel Road, Brenchley, Kent TN12 7DJ, United Kingdom
Tel: 01892 7251000 • Fax: 01892 725105
E-mail: ray@ritedoors.co.uk • Website: www.ritedoors.co.uk
Certificate No. 1306PI to LPS 1197 : Issue 4
Company assessed and approved for:
- Inspection, maintenance services and repair, term contracts
Of:
Fire resistant shutters
Product groups:
Steel rolling shutters
Stanair Industrial Door Services Limited
2 Henson Way, Telford Way Industrial Estate, Kettering, Northamptonshire NN16 8PX, United Kingdom
Tel: +44 (0)1536 482187 • Fax: +44 (0)1536 411799
E-mail: info@stanair.co.uk • Website: www.stanair.co.uk
Subsidiary Office(s)
Unit 11, Blundells Road, Bradville, Milton Keynes MK13 7HA
Certificate No. 141a to LPS 1197 Issue 4
Company assessed and approved for:
- Maintenance services and 'one off' general repair
- Inspection, maintenance services and repair, term contracts
- Emergency repair and response services
Of:
Fire resistant shutters
Product groups:
Steel rolling shutters
TEK Interiors Limited
Unit 10A Beehive Business Centre, Beehive Lane, Great Baddon, Chelmsford, Essex CM2 9TE, United
Kingdom
Tel: 01245 250657
E-mail: Neil@tekfiredoorservices.co.uk • Website: www.tekfiredoorservices.co.uk
Certificate No. 1300PIa to LPS 1197 : Issue 4
Company assessed and approved for:
- Inspection, maintenance services and repair, term contracts
Of:
Fire resistant doors and doorsets
Product groups:
Hinged and pivoted timber doorsets
26
27 Sep 2016
PART 2: SECTION 3
INSPECTION, REPAIR AND MAINTENANCE OF FIRE AND SECURITY DOORS AND SHUTTERS
Tyco Fire and Integrated Solutions (the trading company for Tyco Fire and Integrated
Solutions (UK) Limited)
Tyco Park, Grimshaw Lane, Newton Heath, Manchester M40 2WL, United Kingdom
Tel: +44 (0)161 205 2321 • Fax: +44 (0)161 455 4459
Website: www.tycofis.com
Certificate No. 014c to LPS 1197: Issue 3
General servicing/maintenance
Maintenance contracts
Yes
24 hour answering service
Yes
24 hour emergency service
Yes
Yes
On site within 4 hours of call in mainland UK.
27 Sep 2016
27
Download