EFCOG Best Practice #159 Best Practice Title: Adoption of NFPA 70 2008 in place of NFPA 70 2005 Facility: DOE Complex Point of Contact: Michael Hicks NE-ID, 208-526-3724, hicksmd@id.doe.gov John McAlhaney SRS, 803-557-9002, jackie.mcalhaney@srs.gov Mark McNellis SNL, 505-845-4895, msmcnel@sandia.gov Lloyd Gordon LANL, 505-667-0778, lbgordon@lanl.gov Brief Description of Best Practice: NFPA 70 2008 is recommended for approval across the DOE Complex as an upgrade to NFPA 70 2005 in 10 CFR 851 Worker Safety and Health Plans (WSHP). Why the best practice was used: 10 CFR 851 lists safety and health consensus standards with which the contractor must comply when applicable with site hazards (851.23). Only the versions of consensus standards that were in effect on February 9, 2006 were promulgated pursuant to rulemaking therefore only those specifically cited versions are required by the Rule. Contractors may include successor versions of the consensus standards that provide equal or greater worker protection if included in their DOE-approved worker safety and health program. What are the benefits of the best practice: The use of NFPA 70 2008 is at least as protective as the 2005 edition, and even more protective in some areas, such that the new edition should be considered for DOE Complex wide acceptance. NFPA 70 2008 is recommended for approval across the DOE Complex as an upgrade to NFPA 70 2005. What problems/issues were associated with the best practice: There were no issues associated with this gap analysis. Adoption of the 2008 Edition of NFPA 70 provides a level of protection “As Safe or Safer” than the 2005 version. How the success of the Best Practice was measured: N/A Description of process experience using the Best Practice: At the time this analysis was performed, process experience did not exist. . Page 1 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety Article 90 90.2 Scope. (A) Covered. This Code covers the installation of electrical conductors, equipment, and raceways; signaling and communications conductors, equipment, and raceways; and optical fiber cables and raceways for the following: (1) Public and private premises, including buildings, structures, mobile homes, recreational vehicles, and floating buildings (2) Yards, lots, parking lots, carnivals, and industrial substations FPN to (2): For additional information concerning such installations in an industrial or multibuilding complex, see ANSI C2-2002, National Electrical Safety Code. 90.2 Scope. (A) Covered. This Code covers the installation of electrical conductors, equipment, and raceways; signaling and communications conductors, equipment, and raceways; and optical fiber cables and raceways for the following: (1) Public and private premises, including buildings, structures, mobile homes, recreational vehicles, and floating buildings (2) Yards, lots, parking lots, carnivals, and industrial substations (3) Installations of conductors and equipment that connect to the supply of electricity (4) Installations used by the electric utility, such as office buildings, warehouses, garages, machine shops, and recreational buildings, that are not an integral part of a generating plant, substation, or control center. (3) Installations of conductors and equipment that connect to the supply of electricity (4) Installations used by the electric utility, such as office buildings, warehouses, garages, machine shops, and recreational buildings, that are not an integral part of a generating plant, substation, or control center. Bonding (Bonded). The permanent joining of metallic parts to form an electrically conductive path that Article 100 Definitions Bonded (Bonding). Connected to establish electrical continuity and conductivity. Page 2 of 361 Deleted fine print note referencing ANSI C2-2002, National Electrical Safety Code with respect to industrial substations. No direct safety impact. Simplified definition. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety ensures electrical continuity and the capacity to conduct safely any current likely to be imposed. Device. A unit of an electrical system that is intended to carry or control but not utilize electric energy. Ground. A conducting connection, whether intentional or accidental, between an electrical circuit or equipment and the earth or to some Branch-Circuit Overcurrent Device. A device capable of providing protection for service, feeder, and branch circuits and equipment over the full range of overcurrents between its rated current and its interrupting rating. Branchcircuit overcurrent protective devices are provided with interrupting ratings appropriate for the intended use but no less than 5,000 amperes. Clothes Closet. A non-habitable room or space intended primarily for storage of garments and apparel. Device. A unit of an electrical system that carries or controls electric energy as its principal function. Electric Power Production and Distribution Network. Power production, distribution, and utilization equipment and facilities, such as electric utility systems that deliver electric power to the connected loads, that are external to and not controlled by an interactive system. Ground. The earth. New definition. As Safe or Safer. New definition. As Safe or Safer. Revised definition. As Safe or Safer. New definition. As Safe or Safer. Simplified definition. As Safe or Safer. Page 3 of 361 70 2008 851 Evaluation 2005 NEC conducting body that serves in place of the earth. Grounded. Connected to earth or to some conducting body that serves in place of the earth. Grounding Conductor, Equipment. The conductor used to connect the non– current-carrying metal parts of equipment, raceways, and other enclosures to the system grounded conductor, the grounding electrode conductor, or both, at the service equipment or at the source of a separately derived system. Grounding Electrode. A device that establishes an electrical connection to the earth. Grounding Electrode Conductor. The conductor used to connect the grounding electrode(s) to the equipment grounding conductor, to the grounded conductor, or to both, at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at the source of a separately derived system. 2008 NEC Change Description and Impact to Worker Safety Grounded (Grounding). Connected (connecting) to ground or to a conductive body that extends the ground connection. Grounding Conductor, Equipment (EGC). The conductive path installed to connect normally non currentcarrying metal parts of equipment together and to the system grounded conductor or to the grounding electrode conductor, or both. Simplified definition. Grounding Electrode. A conducting object through which a direct connection to earth is established. Grounding Electrode Conductor. A conductor used to connect the system grounded conductor or the equipment to a grounding electrode or to a point on the grounding electrode system. Eliminated “device” to differentiate from the definition of device. As Safe or Safer. Simplified definition removing service and separately derived system reference. Intersystem Bonding Termination. A device that provides a means for connecting communications system(s) New definition. Page 4 of 361 As Safe or Safer. Customized definition removing service and separately derived system reference and added fine print notes. As Safe or Safer. As Safe or Safer. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC grounding conductor(s) and bonding conductor(s) at the service equipment or at the disconnecting means for buildings or structures supplied by a feeder or branch circuit. Kitchen. An area with a sink and permanent facilities for food preparation and cooking. Luminaire. A complete lighting unit Luminaire. A complete lighting unit consisting of a lamp or lamps together consisting of a light source such as a with the parts designed to distribute the lamp or lamps, together with the parts light, to position and protect the lamps designed to position the light source and ballast (where applicable), and to and connect it to the power supply. It connect the lamps to the power supply. may also include parts to protect the light source or the ballast or to distribute the light. A lampholder itself is not a luminaire. Metal-Enclosed Power Switchgear. A Metal-Enclosed Power Switchgear. A switchgear assembly completely switchgear assembly completely enclosed on all sides and top with enclosed on all sides and top with sheet metal (except for ventilating sheet metal (except for ventilating openings and inspection windows) openings and inspection windows) and containing primary power circuit containing primary power circuit switching, interrupting devices, or both, switching, interrupting devices, or both, with buses and connections. The with buses and connections. The assembly may include control and assembly may include control and auxiliary devices. Access to the interior auxiliary devices. Access to the interior of the enclosure is provided by doors, of the enclosure is provided by doors, removable covers, or both. removable covers, or both. Metalenclosed power switchgear is available in non-arc-resistant or arc-resistant Page 5 of 361 Change Description and Impact to Worker Safety Not previously defined. Needed for applicability of devices. As Safe or Safer. Enhanced definition to establish luminaire as the complete lighting apparatus. As Safe or Safer. Added “Metal-enclosed power switchgear is available in non-arcresistant or arc-resistant constructions.” to identify that equipment is now available as arc resistant. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC Premises Wiring (System). That interior and exterior wiring, including power, lighting, control, and signal circuit wiring together with all their associated hardware, fittings, and wiring devices, both permanently and temporarily installed, that extends from the service point or source of power, such as a battery, a solar photovoltaic system, or a generator, transformer, or converter windings, to the outlet(s). Such wiring does not include wiring internal to appliances, luminaires (fixtures), motors, controllers, motor control centers, and similar equipment. Qualified Person. One who has skills and knowledge related to the construction and operation of the electrical equipment and installations 2008 NEC constructions. Neutral Conductor. The conductor connected to the neutral point of a system that is intended to carry current under normal conditions. Neutral Point. The common point on a wye-connection in a polyphase system or midpoint on a single-phase, 3-wire system, or midpoint of a single-phase portion of a 3-phase delta system, or a midpoint of a 3-wire, direct-current system. Premises Wiring (System). Interior and exterior wiring, including power, lighting, control, and signal circuit wiring together with all their associated hardware, fittings, and wiring devices, both permanently and temporarily installed. This includes (a) wiring from the service point or power source to the outlets or (b) wiring from and including the power source to the outlets where there is no service point. Qualified Person. One who has skills and knowledge related to the construction and operation of the electrical equipment and installations Page 6 of 361 Change Description and Impact to Worker Safety New definition finally defines the neutral conductor and calls it out accordingly. As Safe or Safer. New definition. As Safe or Safer. Simplified definition. As Safe or Safer. Emphasized need to “recognize and avoid” the hazards. Improved safety position. 70 2008 851 Evaluation 2005 NEC 2008 NEC and has received safety training on the hazards involved. and has received safety training to recognize and avoid the hazards involved. Short-Circuit Current Rating. The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding defined acceptance criteria. Surge Arrester. A protective device for limiting surge voltages by discharging or bypassing surge current; it also prevents continued flow of follow current while remaining capable of repeating these functions. Surge-Protective Device (SPD). A protective device for limiting transient voltages by diverting or limiting surge current; it also prevents continued flow of follow current while remaining capable of repeating these functions and is designated as follows: Type 1: Permanently connected SPDs intended for installation between the secondary of the service transformer and the line side of the service disconnect overcurrent device. Type 2: Permanently connected SPDs intended for installation on the load side of the service disconnect overcurrent device, including SPDs Page 7 of 361 Change Description and Impact to Worker Safety New definition to accommodate new requirements in other articles. As Safe or Safer. New definition to accommodate wider use of surge arresters. As Safe or Safer. New definition to accommodate wider use of surge protective devices. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC located at the branch panel. Type 3: Point of utilization SPDs. Type 4: Component SPDs, including discrete components, as well as assemblies. Ungrounded. Not connected to ground or to a conductive body that extends the ground connection. Utility-Interactive Inverter. An inverter intended for use in parallel with an electric utility to supply common loads that may deliver power to the utility. Article 110 110.7 Insulation Integrity. Completed 110.7 Wiring Integrity. Completed wiring installations shall be free from wiring installations shall be free from short circuits and from grounds other short circuits, ground faults, or any than as required or permitted in Article connections to ground other than as 250. required or permitted elsewhere in this Code. 110.12 Mechanical Execution of Work. 110.12 Mechanical Execution of Work. (A) Unused Openings. Unused cable (A) Unused Openings. Unused or raceway openings in boxes, openings, other than those intended for raceways, auxiliary gutters, cabinets, the operation of equipment, those cutout boxes, meter socket enclosures, intended for mounting purposes, or equipment cases, or housings shall be those permitted as part of the design effectively closed to afford protection for listed equipment, shall be closed to substantially equivalent to the wall of afford protection substantially the equipment. Where metallic plugs or equivalent to the wall of the equipment. plates are used with nonmetallic Where metallic plugs or plates are enclosures, they shall be recessed at used with nonmetallic enclosures, they least 6 mm (1⁄4 in.) from the outer shall be recessed at least 6 mm (1⁄4 Page 8 of 361 Change Description and Impact to Worker Safety New definition to accommodate use of ungrounded parts in other articles. As Safe or Safer. New definition to accommodate wider use of this equipment type. As Safe or Safer. Changed to comply with NEC Style Manual and better address the possibilities in more than one article. As Safe or Safer. Improved readability. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC in.) from the outer surface of the enclosure. 110.16 Flash Protection. Switchboards, 110.16 Flash Protection. Electrical panelboards, industrial control panels, equipment, such as switchboards, meter socket enclosures, and motor panelboards, industrial control panels, control centers that are in other than meter socket enclosures, and motor dwelling occupancies and are likely to control centers, that are in other than require examination, adjustment, dwelling occupancies, and are likely to servicing, or maintenance while require examination, adjustment, energized shall be field marked to warn servicing, or maintenance while qualified persons of potential electric energized shall be field marked to warn arc flash hazards. The marking shall qualified persons of potential electric be located so as to be clearly visible to arc flash hazards. The marking shall qualified persons before examination, be located so as to be clearly visible to adjustment, servicing, or maintenance qualified persons before of the equipment. examination, adjustment, servicing, or maintenance of the equipment. 110.20 Enclosure Types. Enclosures (other than surrounding fences or walls) of switchboards, panelboards, industrial control panels, motor control centers, meter sockets, and motor controllers, rated not over 600 volts nominal and intended for such locations, shall be marked with an enclosure-type number as shown in Table 110.20. Table 110.20 shall be used for selecting these enclosures for use in specific locations other than hazardous (classified) locations. The enclosures Change Description and Impact to Worker Safety surface of the enclosure. Page 9 of 361 Clarifies that equipment similar to the types mentioned are also subject to the requirement. No impact since we already included similar equipment in our evaluations. New section covering enclosure types and the NEMA designation applicability moved from 430.91. Table 430.91 was also moved to make it clear which enclosure type is needed for the environment in which it will be operated and that it applies to more than motor controllers. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC are not intended to protect against conditions such as condensation, icing, corrosion, or contamination that may occur within the enclosure or enter via the conduit or unsealed openings. 110.22 Identification of Disconnecting Means. (B) Engineered Series Combination Systems. Where circuit breakers or fuses are applied in compliance with series combination ratings selected under engineering supervision and marked on the equipment as directed by the engineer, the equipment enclosure(s) shall be legibly marked in the field to indicate the equipment has been applied with a series combination rating. The marking shall be readily visible and state the following: 110.26 (C) Entrance to Working Space. (1) Minimum Required. At least one entrance of sufficient area shall be provided to give access to working space about electrical equipment. CAUTION — ENGINEERED SERIES COMBINATION SYSTEM RATED _______ AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED. 110.26 (C) Entrance to and Egress from Working Space. (1) Minimum Required. At least one entrance of sufficient area shall be provided to give access to and egress from working space about electrical Page 10 of 361 Change Description and Impact to Worker Safety New section to identify series combination ratings by engineering and the associated marking requirements. As Safe or Safer. Added egress wording for clarification that personnel egress is the important item here. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 110.26 (C) Entrance to Working Space. 2008 NEC Change Description and Impact to Worker Safety equipment. 110.26 (C) Entrance to and Egress from Working Space. The change makes this requirement only applicable to rooms with equipment over 1.8 m wide reducing (2) Large Equipment. For equipment (2) Large Equipment. For equipment the somewhat over burdensome rated 1200 amperes or more that rated 1200 amperes or more and over requirement when the equipment does contains overcurrent devices, switching 1.8 m (6 ft) wide that contains not pose a threat to worker egress. devices, or control devices, there shall overcurrent devices, switching devices, Wording changed to be consistent with be one entrance to the required or control devices, there shall be one life safety terminology. working space not less than 610 mm entrance to and egress from the (24 in.) wide and 2.0 m (61⁄2 ft) high at required working space not less than As Safe or Safer. each end of the working space. 610 mm (24 in.) wide and 2.0 m (61⁄2 Where the entrance has a personnel ft) high at each end of the working door(s), the door(s) shall open in the space. A single entrance to and egress direction of egress and be equipped from the required working space shall with panic bars, pressure plates, or be permitted where either of the other devices that are normally latched conditions in 110.26(C)(2)(a) or but open under simple pressure. A (C)(2)(b) is met. single entrance to the required working space shall be permitted where either of the conditions in 110.26(C)(2)(a) or (C)(2)(b) is met. (a) Unobstructed Exit. Where the location permits a continuous and unobstructed way of exit travel, a single entrance to the working space shall be permitted. (a) Unobstructed Egress. Where the location permits a continuous and unobstructed way of egress travel, a single entrance to the working space shall be permitted. 110.26(C)(3) Personnel Doors. Where New section extracted from (C)(2) and equipment rated 1200 A or more that added here to address the situation of contains overcurrent devices, switching egress during an arc flash or similar Page 11 of 361 70 2008 851 Evaluation 2005 NEC 110.33 Entrance and Access to Work Space. (A) Entrance. At least one entrance not less than 610 mm (24 in.) wide and 2.0 m (61⁄2 ft) high shall be provided to give access to the working space about electric equipment. Where the entrance has a personnel door(s), the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates, or other devices that are normally latched but open under simple pressure. 2008 NEC devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 7.6 m (25 ft) from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates, or other devices that are normally latched but open under simple pressure. 110.26(G) Locked Electrical Equipment Rooms or Enclosures. Electrical equipment rooms or enclosures housing electrical apparatus that are controlled by a lock(s) shall be considered accessible to qualified persons. 110.33 Entrance to Enclosures and Access to Working Space. (A) Entrance. At least one entrance to enclosures for electrical installations as described in 110.31 not less than 610 mm (24 in.) wide and 2.0 m (61⁄2 ft) high shall be provided to give access to the working space about electrical equipment. Page 12 of 361 Change Description and Impact to Worker Safety event. Actually provides added worker safety. New section to clarify that locked doors do not constitute inaccessibility to qualified persons. As Safe or Safer. Revised to move information into new section 110.33(A)(3) and to clarify just where the requirement applies. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 110.34 Work Space and Guarding. (A) Working Space. Except as elsewhere required or permitted in this Code, the minimum clear working space in the direction of access to live parts of electrical equipment shall not be less than specified in Table 110.34(A). Distances shall be measured from the live parts, if such are exposed, or from the enclosure front or opening if such are enclosed. 110.33 (A)(3) Personnel Doors. Where there is a personnel door(s) intended for entrance to and egress from the working space less than 7.6 m (25 ft) from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates, or other devices that are normally latched but open under simple pressure. 110.34 Work Space and Guarding. (A) Working Space. Except as elsewhere required or permitted in this Code, equipment likely to require examination, adjustment, servicing, or maintenance while energized shall have clear working space in the direction of access to live parts of the electrical equipment and shall be not less than specified in Table 110.34(A). Distances shall be measured from the live parts, if such are exposed, or from the enclosure front or opening if such are enclosed. Article 200 200.2 General. All premises wiring systems, other than circuits and systems exempted or prohibited by 210.10, 215.7, 250.21, 250.22, 250.162, 503.155, 517.63, 668.11, 668.21, and 690.41, Exception, shall 200.2 General. All premises wiring systems, other than circuits and systems exempted or prohibited by 210.10, 215.7, 250.21, 250.22, 250.162, 503.155, 517.63, 668.11, 668.21, and 690.41 Exception, shall Page 13 of 361 Change Description and Impact to Worker Safety New section with information relocated from main section 110.33(A). As Safe or Safer. Added “equipment likely to require examination, adjustment, servicing, or maintenance while energized” to address only the equipment required to have working space. As Safe or Safer. Shortened original section and refers to two new sections with information from the original section. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC have a grounded conductor that is identified in accordance with 200.6. The grounded conductor, where insulated, shall have insulation that is (1) suitable, other than color, for any ungrounded conductor of the same circuit on circuits of less than 1000 volts or impedance grounded neutral systems of 1 kV and over, or (2) rated not less than 600 volts for solidly grounded neutral systems of 1 kV and over as described in 250.184(A). 2008 NEC Change Description and Impact to Worker Safety have a grounded conductor that is identified in accordance with 200.6. The grounded conductor shall comply with 200.2(A) and (B). 200.2(A) Insulation. The grounded conductor, where insulated, shall have insulation that is (1) suitable, other than color, for any ungrounded conductor of the same circuit on circuits of less than 1000 volts or impedance grounded neutral systems of 1 kV and over, or (2) rated not less than 600 volts for solidly grounded neutral systems of 1 kV and over as described in 250.184(A). 200.2(B) Continuity. The continuity of a grounded conductor shall not depend on a connection to a metallic enclosure, raceway, or cable armor. 200.3 Connection to Grounded System. Exception: Listed utility-interactive Page 14 of 361 Relocated and renamed from original. As Safe or Safer. New section improving ground continuity. As Safe or Safer. New exception added to address increased use of photovoltaic equipment and fuel cells. 70 2008 851 Evaluation 2005 NEC 2008 NEC inverters identified for use in distributed resource generation systems such as photovoltaic and fuel cell power systems shall be permitted to be connected to premises wiring without a grounded conductor where the connected premises wiring or utility system includes a grounded conductor. Article 210 210.4 Multiwire Branch Circuits. 210.4 Multiwire Branch Circuits. (A) General. Branch circuits (A) General. Branch circuits recognized by this article shall be recognized by this article shall be permitted as multiwire circuits. A permitted as multiwire circuits. A multiwire circuit shall be permitted to multiwire circuit shall be permitted to be considered as multiple circuits. All be considered as multiple circuits. All conductors shall originate from the conductors of a multiwire branch circuit same panelboard or similar distribution shall originate from the same equipment. panelboard or similar distribution equipment. 210.4(B) Devices or Equipment. Where 210.4(B) Disconnecting Means. Each a multiwire branch circuit supplies multiwire branch circuit shall be more than one device or equipment on provided with a means that will the same yoke, a means shall be simultaneously disconnect all provided to disconnect simultaneously ungrounded conductors at the point all ungrounded conductors supplying where the branch circuit originates. those devices or equipment at the point where the branch circuit originates. 210.4(D) Grouping. The ungrounded and grounded conductors of each multiwire branch circuit shall be Page 15 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Clarification of conductors in a multiwire branch circuit. As Safe or Safer. Clarification, that actually will help reduce the common neutral situation even more than previous Code improvements. New section that imposes requirements that will also assist in reducing the risk of common neutral 70 2008 851 Evaluation 2005 NEC 210.5 Identification for Branch Circuits. (C) Ungrounded Conductors. Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by system. The means of identification shall be permitted to be by separate color coding, marking tape, tagging, or other approved means and shall be permanently posted at each branch-circuit panelboard or similar branch-circuit distribution equipment. 2008 NEC grouped by wire ties or similar means in at least one location within the panelboard or other point of origination. Exception: The requirement for grouping shall not apply if the circuit enters from a cable or raceway unique to the circuit that makes the grouping obvious. 210.5 Identification for Branch Circuits. (C) Ungrounded Conductors. Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit shall be identified by phase or line and system at all termination, connection, and splice points. The means of identification shall be permitted to be by separate color coding, marking tape, tagging, or other approved means. The method utilized for conductors originating within each branch circuit panelboard or similar branch circuit distribution equipment shall be documented in a manner that is readily available or shall be permanently posted at each branch circuit panelboard or similar branch circuit distribution equipment. 210.6 Branch-Circuit Voltage Page 16 of 361 Change Description and Impact to Worker Safety encounters. Clarifies identification requirements for branch circuits to include any point where there is a connection and it now requires documentation. Improves worker safety. New section adding luminaires to the 70 2008 851 Evaluation 2005 NEC 2008 NEC Limitations. (D) 600 Volts Between Conductors. (3) Luminaires powered from directcurrent systems where the luminaire contains a listed, dc-rated ballast that provides isolation between the dc power source and the lamp circuit and protection from electric shock when changing lamps. 210.8 Ground-Fault Circuit-Interrupter 210.8 Ground-Fault Circuit-Interrupter Protection for Personnel. Protection for Personnel. (B) Other Than Dwelling Units. All 125- (B) Other Than Dwelling Units. All 125volt, single phase, 15- and 20-ampere volt, single phase, 15- and 20-ampere receptacles installed in the locations receptacles installed in the locations specified in (1) through (5) shall have specified in (1) through (5) shall have ground-fault circuit-interrupter ground-fault circuit-interrupter protection for personnel: protection for personnel: (1) Bathrooms (1) Bathrooms (2) Commercial and institutional (2) Kitchens kitchens—for the purposes of this (3) Rooftops section, a kitchen is an area with a sink (4) Outdoors and permanent facilities for food preparation and cooking Exception No. 2 to (4): In industrial (3) Rooftops establishments only, where the (4) Outdoors in public spaces—for the conditions of maintenance and purpose of this section a public space supervision ensure that only qualified is defined as any space that is for personnel are involved, an assured use by, or is accessible to, the public equipment grounding conductor program as specified in 590.6(B)(2) Exception to (3) and (4): Receptacles shall be permitted for only those that are not readily accessible and are receptacle outlets used to supply Page 17 of 361 Change Description and Impact to Worker Safety types of equipment allowed to be fed from circuits over 277 volts but less than 600 volts. As Safe or Safer. Simplified by moving the definition of kitchen to Article 100 and removing the caveats about outdoors in public spaces as well as adding sinks as a specific location. Exceptions were added to eliminate the requirement in areas that would not benefit from GFCI installation. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC supplied from a dedicated branch circuit for electric snow-melting or deicing equipment shall be permitted to be installed in accordance with the applicable provisions of Article 426. equipment that would create a greater hazard if power is interrupted or having a design that is not compatible with GFCI protection. Change Description and Impact to Worker Safety (5) Sinks — where receptacles are (5) Outdoors, where installed to comply installed within 1.8 m (6 ft) of the with 210.63 outside edge of the sink. Exception No 1 to (5): In industrial laboratories, receptacles used to supply equipment where removal of power would introduce a greater hazard shall be permitted to be installed without GFCI protection. Exception No 2 to (5): For receptacles located in patient care areas of health care facilities other than those covered under 210.8(B)(1), GFCI protection shall not be required. II. Branch-Circuit Ratings 210.19 Conductors — Minimum Ampacity and Size. (A) Branch Circuits Not More Than 600 Volts. (1) General Exception No. 2: Grounded conductors that are not connected to an overcurrent device shall be permitted Page 18 of 361 New exception added to allow the grounded conductor (neutral) to be sized at 100% vs. 125%. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC to be sized at 100 percent of the continuous and noncontinuous load. Article 215 215.2 Minimum Rating and Size. (A) Feeders Not More Than 600 Volts. (1) General. Exception No. 2: Grounded conductors that are not connected to an overcurrent device shall be permitted to be sized at 100 percent of the continuous and noncontinuous load. 215.6 Feeder Conductor Grounding 215.6 Feeder Equipment Grounding Means. Where a feeder supplies Conductor. Where a feeder supplies branch circuits in which equipment branch circuits in which equipment grounding conductors are required, the grounding conductors are required, the feeder shall include or provide a feeder shall include or provide an grounding means, in accordance with equipment grounding conductor in the provisions of 250.134, to which the accordance with the provisions of equipment grounding conductors of the 250.134, to which the equipment branch circuits shall be connected. grounding conductors of the branch circuits shall be connected. Where the feeder supplies a separate building or structure, the requirements of 250.32(B) shall apply. 215.12 Identification for Feeders. 215.12 Identification for Feeders. (C) Ungrounded Conductors. Where (C) Ungrounded Conductors. Where the premises wiring system has the premises wiring system has feeders supplied from more than one feeders supplied from more than one nominal voltage system, each nominal voltage system, each ungrounded conductor of a feeder, ungrounded conductor of a feeder shall Page 19 of 361 Change Description and Impact to Worker Safety New exception added to allow the grounded conductor (neutral) to be sized at 100% vs. 125%. As Safe or Safer. Modified section to address the term equipment grounding conductor with respect to feeder installations as well as address feeders supplying buildings. As Safe or Safer. Clarifies identification requirements for feeder circuits to include any point where there is a connection and it now requires documentation. Improves worker safety. 70 2008 851 Evaluation 2005 NEC where accessible, shall be identified by system. The means of identification shall be permitted to be by separate color coding, marking tape, tagging, or other approved means and shall be permanently posted at each feeder panelboard or similar feeder distribution equipment. 225.39 Rating of Disconnect. The feeder or branch-circuit disconnecting means shall have a rating of not less than the load to be supplied, determined in accordance with Parts I and II of Article 220 for branch circuits, Parts III or IV of Article 220 for feeders, or Part V of Article 220 for farm loads. In no case shall the rating be lower than specified in 225.39(A), (B), (C), or (D). 2008 NEC Change Description and Impact to Worker Safety be identified by phase or line and system at all termination, connection, and splice points. The means of identification shall be permitted to be by separate color coding, marking tape, tagging, or other approved means. The method utilized for conductors originating within each feeder panelboard or similar feeder distribution equipment shall be documented in a manner that is readily available or shall be permanently posted at each feeder panelboard or similar feeder distribution equipment. Article 225 225.39 Rating of Disconnect. The Provides alternate method for feeder or branch-circuit disconnecting determining rating. means shall have a rating of not less than the calculated load to be supplied, As Safe or Safer. determined in accordance with Parts I and II of Article 220 for branch circuits, Part III or IV of Article 220 for feeders, or Part V of Article 220 for farm loads. Where the branch circuit or feeder disconnecting means consists of more than one switch or circuit breaker, as permitted by 225.33, combining the ratings of all the switches or circuit breakers for determining the rating of the disconnecting means shall be permitted. In no case shall the rating Page 20 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC be lower than specified in 225.39(A), (B), (C), or (D). Article 230 230.42 Minimum Size and Rating. 230.42 Minimum Size and Rating. (A) General. The ampacity of the (A) General. The ampacity of the service-entrance conductors before the service-entrance conductors before the application of any adjustment or application of any adjustment or correction factors shall not be less than correction factors shall not be less than either (A)(1) or (A)(2). Loads shall be either (A)(1) or (A)(2). Loads shall be determined in accordance with Article determined in accordance with Part III, 220. Ampacity shall be determined IV, or V of Article 220, as applicable. from 310.15. The maximum allowable Ampacity shall be determined from current of busways shall be that value 310.15. The maximum allowable for which the busway has been listed current of busways shall be that value or labeled. for which the busway has been listed or labeled. 230.44 Cable Trays. 230.44 Cable Trays. Exception: Conductors other than Exception: Conductors, other than service-entrance conductors shall be service-entrance conductors, shall be permitted to be installed in a cable tray permitted to be installed in a cable tray with service-entrance conductors, with service-entrance conductors, provided a solid fixed barrier of a provided a solid fixed barrier of a material compatible with the cable tray material compatible with the cable tray is installed to separate the serviceis installed to separate the serviceentrance conductors from other entrance conductors from other conductors installed in the cable tray. conductors installed in the cable tray. Cable trays shall be identified with permanently affıxed labels with the wording “Service-Entrance Conductors.” The labels shall be located so as to be visible after Page 21 of 361 Change Description and Impact to Worker Safety Clarifies the intent of applicable parts of Article 220. As Safe or Safer. Added identification requirements for service-entrance conductors. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC installation and placed so that the service-entrance conductors may be readily traced through the entire length of the cable tray. 230.50 Protection of Open Conductors 230.50 Protection Against Physical and Cables Against Damage — Above Damage. Ground. Service-entrance conductors (A) Underground Service-Entrance installed above ground shall be Conductors. Underground serviceprotected against physical damage as entrance conductors shall be protected specified in 230.50(A) or (B). against physical damage in accordance with 300.5. (B) All Other Service-Entrance Conductors. All other service-entrance conductors, other than underground service entrance conductors, shall be protected against physical damage as specified in 230.50(B)(1) or (B)(2). 230.53 Raceways to Drain. Where 230.53 Raceways to Drain. Where exposed to the weather, raceways exposed to the weather, raceways enclosing service-entrance conductors enclosing service-entrance conductors shall be raintight and arranged to drain. shall be suitable for use in wet Where embedded in masonry, locations and arranged to drain. Where raceways shall be arranged to drain. embedded in masonry, raceways shall be arranged to drain. Exception: As permitted in 348.12(1). 230.54 Overhead Service Locations. 230.54 Overhead Service Locations. (A) Raintight Service Head. Service (A) Service Head. Service raceways raceways shall be equipped with a shall be equipped with a service head raintight service head at the point of at the point of connection to service connection to service-drop conductors. drop conductors. The service head shall comply with the requirement for Page 22 of 361 Change Description and Impact to Worker Safety Modified to address specific requirements for underground service entrance conductors and impose the same requirements for installation as other underground conductors. As Safe or Safer. Clarified to address broader requirements of wet locations and eliminated the exception. As Safe or Safer. Eliminated “raintight” to be consistent with terminology used for wet locations. Added location of requirements for the service head. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC (B) Service Cable Equipped with Raintight Service Head or Gooseneck. Service cables shall be equipped with a raintight service head. 230.71 Maximum Number of Disconnects. (A) General. For the purpose of this section, disconnecting means used solely for power monitoring equipment, transient voltage surge suppressors, or the control circuit of the ground-fault protection system or power-operable service disconnecting means, installed as part of the listed equipment, shall not be considered a service disconnecting means. 230.79 Rating of Service Disconnecting Means. The service disconnecting means shall have a rating not less than the load to be carried, determined in accordance with Article 220. In no case shall the rating be lower than specified in 230.79(A), (B), (C), or (D). 2008 NEC fittings in 314.15. (B) Service Cable Equipped with Service Head or Gooseneck. Service cables shall be equipped with a service head. The service head shall comply with the requirement for fittings in 314.15. 230.71 Maximum Number of Disconnects. (A) General. For the purpose of this section, disconnecting means installed as part of listed equipment and used solely for the following shall not be considered a service disconnecting means: (1) Power monitoring equipment (2) Surge-protective device(s) (3) Control circuit of the ground-fault protection system (4) Power-operable service disconnecting means 230.79 Rating of Service Disconnecting Means. The service disconnecting means shall have a rating not less than the calculated load to be carried, determined in accordance with Part III, IV, or V of Article 220, as applicable. In no case shall the rating be lower than specified in 230.79(A), (B), (C), or (D). Page 23 of 361 Change Description and Impact to Worker Safety Eliminated “raintight” to be consistent with terminology used for wet locations. Added location of requirements for the service head. As Safe or Safer. Clarified the intent that when installed as part of listed equipment and used for the specific items the disconnecting means is not service disconnect. As Safe or Safer. Clarifies the intent of applicable parts of Article 220. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 230.82 Equipment Connected to the Supply Side of Service Disconnect. Only the following equipment shall be permitted to be connected to the supply side of the service disconnecting means: (1) Cable limiters or other currentlimiting devices (2) Meters and meter sockets nominally rated not in excess of 600 volts, provided all metal housings and service enclosures are grounded (3) Meter disconnect switches nominally rated not in excess of 600 volts that have a short-circuit current rating equal to or greater than the available short circuit current, provided all metal housings and service enclosures are grounded (4) Instrument transformers (current and voltage), impedance shunts, load management devices, and arresters 230.82 Equipment Connected to the Supply Side of Service Disconnect. Only the following equipment shall be permitted to be connected to the supply side of the service disconnecting means: (1) Cable limiters or other currentlimiting devices. (2) Meters and meter sockets nominally rated not in excess of 600 volts, provided all metal housings and service enclosures are grounded in accordance with Part VII and bonded in accordance with Part V of Article 250. (3) Meter disconnect switches nominally rated not in excess of 600 volts that have a short-circuit current rating equal to or greater than the available short-circuit current, provided all metal housings and service enclosures are grounded in accordance with Part VII and bonded in accordance with Part V of Article 250. A meter disconnect switch shall be capable of interrupting the load served. (4) Instrument transformers (current and voltage), impedance shunts, load management devices, surge arresters, and Type 1 surge-protective devices. (8) Ground-fault protection systems or transient voltage surge suppressors, where installed as part of listed equipment, if suitable overcurrent protection and disconnecting means are provided Page 24 of 361 Change Description and Impact to Worker Safety Adds specific reference to the requirements for grounding and clarifies arrester types. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 230.95 Ground-Fault Protection of Equipment. Ground fault protection of equipment shall be provided for solidly grounded wye electrical services of more than 150 volts to ground but not exceeding 600 volts phase-to-phase for each service disconnect rated 1000 amperes or more. The grounded conductor for the solidly grounded wye system shall be connected directly to ground without inserting any resistor or impedance device. The rating of the service disconnect shall be considered to be the rating of the largest fuse that can be installed or the highest continuous current trip setting for which the actual overcurrent device installed in a circuit breaker is rated or can be adjusted. Exception No. 1: The ground-fault protection provisions of this section shall not apply to a service disconnect for a continuous industrial process where a nonorderly shutdown will 2008 NEC (8) Ground-fault protection systems or Type 2 surge protective devices, where installed as part of listed equipment, if suitable overcurrent protection and disconnecting means are provided. 230.95 Ground-Fault Protection of Equipment. Ground fault protection of equipment shall be provided for solidly grounded wye electric services of more than 150 volts to ground but not exceeding 600 volts phase-to-phase for each service disconnect rated 1000 amperes or more. The grounded conductor for the solidly grounded wye system shall be connected directly to ground through a grounding electrode system, as specified in 250.50, without inserting any resistor or impedance device. Exception: The ground-fault protection provisions of this section shall not apply to a service disconnect for a continuous industrial process where a nonorderly shutdown will introduce additional or increased hazards. Page 25 of 361 Change Description and Impact to Worker Safety Specifies the grounding requirements to remove any doubts. Removed exception for fire pumps. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety introduce additional or increased hazards. Exception No. 2: The ground-fault protection provisions of this section shall not apply to fire pumps. 230.204 Isolating Switches. (D) Grounding Connection. Isolating switches shall be provided with a means for readily connecting the load side conductors to ground when disconnected from the source of supply. A means for grounding the load side conductors shall not be required for any duplicate isolating switch installed and maintained by the electric supply company. 230.205 Disconnecting Means. (A) Location. The service disconnecting means shall be located in accordance with 230.70. 230.204 Isolating Switches. (D) Connection to Ground. Isolating switches shall be provided with a means for readily connecting the load side conductors to a grounding electrode system, equipment ground busbar, or grounded steel structure when disconnected from the source of supply. A means for grounding the load side conductors to a grounding electrode system, equipment grounding busbar, or grounded structural steel shall not be required for any duplicate isolating switch installed and maintained by the electric supply company. 230.205 Disconnecting Means. (A) Location. The service disconnecting means shall be located in accordance with 230.70. For either overhead or underground primary distribution systems on private property, the service disconnect shall be permitted to be located in a location that is not readily accessible. Page 26 of 361 Specifies the grounding requirements to remove any doubts. As Safe or Safer. Allows private property owners some relief. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety Article 240 240.4 Protection of Conductors. 240.4 Protection of Conductors. Provides specific criteria for (D) Small Conductors. Unless (D) Small Conductors. Unless conductors smaller than 14 AWG. specifically permitted in 240.4(E) or specifically permitted in 240.4(E) or 240.4(G), the overcurrent protection (G), the overcurrent protection shall not As Safe or Safer. shall not exceed 15 amperes for 14 exceed that required by (D)(1) through AWG, 20 amperes for 12 AWG, and 30 (D)(7) after any correction factors for amperes for 10 AWG copper; or 15 ambient temperature and number of amperes for 12 AWG and 25 amperes conductors have been applied. for 10 AWG aluminum and copper-clad (1) 18 AWG Copper. 7 amperes, aluminum after any correction factors provided all the following conditions for ambient temperature and number of are met: conductors have been applied. (1) Continuous loads do not exceed 5.6 amperes. (2) Overcurrent protection is provided by one of the following: a. Branch-circuit-rated circuit breakers listed and marked for use with 18 AWG copper wire b. Branch-circuit-rated fuses listed and marked for use with 18 AWG copper wire c. Class CC, Class J, or Class T fuses (2) 16 AWG Copper. 10 amperes, provided all the following conditions are met: (1) Continuous loads do not exceed 8 amperes. (2) Overcurrent protection is provided by one of the following: Page 27 of 361 70 2008 851 Evaluation 2005 NEC 240.5 Protection of Flexible Cords, Flexible Cables, and Fixture Wires. (B) Branch Circuit Overcurrent Device. Flexible cord shall be protected where supplied by a branch circuit in accordance with one of the methods described in 240.5(B)(1), (B)(2), (B)(3), or (B)(4). (1) Supply Cord of Listed Appliance or Portable Lamps. Where flexible cord or tinsel cord is approved for and used with a specific listed appliance or portable lamp, it shall be considered to 2008 NEC a. Branch-circuit-rated circuit breakers listed and marked for use with 16 AWG copper wire b. Branch-circuit-rated fuses listed and marked for use with 16 AWG copper wire c. Class CC, Class J, or Class T fuses (3) 14 AWG Copper. 15 amperes (4) 12 AWG Aluminum and CopperClad Aluminum. 15 amperes (5) 12 AWG Copper. 20 amperes (6) 10 AWG Aluminum and CopperClad Aluminum. 25 amperes (7) 10 AWG Copper. 30 amperes 240.5 Protection of Flexible Cords, Flexible Cables, and Fixture Wires. (B) Branch-Circuit Overcurrent Device. Flexible cord shall be protected, where supplied by a branch circuit, in accordance with one of the methods described in 240.5(B)(1), (B)(3), or (B)(4). Fixture wire shall be protected, where supplied by a branch circuit, in accordance with 240.5(B)(2). (1) Supply Cord of Listed Appliance or Luminaire. Where flexible cord or tinsel cord is approved for and used with a specific listed appliance or luminaire, it shall be Page 28 of 361 Change Description and Impact to Worker Safety Provides specific requirements for protection of fixture wire. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC considered to be protected when applied within the appliance or luminaire listing requirements. For the purposes of this section, a luminaire may be either portable or permanent. 240.21 Location in Circuit. 240.21 Location in Circuit. (C) Transformer Secondary (C) Transformer Secondary Conductors. Each set of conductors Conductors. A set of conductors feeding separate loads shall be feeding a single load, or each set of permitted to be connected to a conductors feeding separate loads, transformer secondary, without shall be permitted to be connected to a overcurrent protection at the transformer secondary, without secondary, as specified in overcurrent protection at the 240.21(C)(1) through (C)(6). The secondary, as specified in provisions of 240.4(B) shall not be 240.21(C)(1) through (C)(6). The permitted for transformer secondary provisions of 240.4(B) shall not be conductors. permitted for transformer secondary conductors. 240.21 Location in Circuit. 240.21 Location in Circuit. (C) Transformer Secondary (C) Transformer Secondary Conductors. Conductors. (2) Transformer Secondary Conductors (2) Transformer Secondary Conductors Not Over 3 m (10 ft) Long. Not Over 3 m (10 ft) Long. (4) For field installations where the secondary conductors leave the enclosure or vault in which the supply connection is made, the rating of the overcurrent device protecting the primary of the transformer, multiplied by the primary to secondary transformer voltage ratio, shall not exceed 10 times the ampacity Change Description and Impact to Worker Safety be protected when applied within the appliance or portable lamp listing requirements. Page 29 of 361 Clarified intent to address single loads as well as multiple load arrangements. As Safe or Safer. New section to address situations where the primary device rating may be too high to adequately protect the tap conductors. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 240.21 Location in Circuit. (C) Transformer Secondary Conductors. (3) Industrial Installation Secondary Conductors Not Over 7.5 m (25 ft) Long. For industrial installations only, where the length of the secondary conductors does not exceed 7.5 m (25 ft) and complies with all of the following: 240.21 Location in Circuit. 240.24 Location in or on Premises. (B) Occupancy. Each occupant shall have ready access to all overcurrent devices protecting the conductors supplying that occupancy. Exception No. 1: Where electric 2008 NEC of the secondary conductor. 240.21 Location in Circuit. (C) Transformer Secondary Conductors. (3) Industrial Installation Secondary Conductors Not over 7.5 m (25 ft) Long. For industrial installations only, where the length of the secondary conductors does not exceed 7.5 m (25 ft) and complies with all of the following: (1) Conditions of maintenance and supervision ensure that only qualified persons service the systems. 240.21 Location in Circuit. (H) Battery Conductors. Overcurrent protection shall be permitted to be installed as close as practicable to the storage battery terminals in a nonhazardous location. Installation of the overcurrent protection within a hazardous location shall also be permitted. 240.24 Location in or on Premises. (B) Occupancy. Each occupant shall have ready access to all overcurrent devices protecting the conductors supplying that occupancy, unless otherwise permitted in 240.24(B)(1) and (B)(2). Page 30 of 361 Change Description and Impact to Worker Safety New requirement inserted ahead of the three existing requirements to assure that only qualified personnel work on the system. As Safe or Safer. New section added to address hazardous locations and overcurrent protective device location. As Safe or Safer. Converts governing by exception into positive Code language in keeping with NEC Style Manual and to clarify the intent that only overcurrent protective devices for permanent cooking appliances require guest access. 70 2008 851 Evaluation 2005 NEC service and electrical maintenance are provided by the building management and where these are under continuous building management supervision, the service overcurrent devices and feeder overcurrent devices supplying more than one occupancy shall be permitted to be accessible to only authorized management personnel in the following: (1) Multiple-occupancy buildings (2) Guest rooms or guest suites of hotels and motels that are intended for transient occupancy Exception No. 2: Where electric service and electrical maintenance are provided by the building management and where these are under continuous building management supervision, the branch circuit overcurrent devices supplying any guest rooms or guest suites shall be permitted to be accessible to only authorized management personnel for guest rooms of hotels and motels that are intended for transient occupancy. 240.24 Location in or on Premises. 2008 NEC Change Description and Impact to Worker Safety As Safe or Safer. (1) Service and Feeder Overcurrent Devices. Where electric service and electrical maintenance are provided by the building management and where these are under continuous building management supervision, the service overcurrent devices and feeder overcurrent devices supplying more than one occupancy shall be permitted to be accessible only to authorized management personnel in the following: (1) Multiple-occupancy buildings (2) Guest rooms or guest suites (2) Branch-Circuit Overcurrent Devices. Where electric service and electrical maintenance are provided by the building management and where these are under continuous building management supervision, the branchcircuit overcurrent devices supplying any guest rooms or guest suites without permanent provisions for cooking shall be permitted to be accessible only to authorized management personnel. 240.24 Location in or on Premises. (F) Not Located over Steps. Overcurrent devices shall not be Page 31 of 361 New section to eliminate panels being installed over steps. 70 2008 851 Evaluation 2005 NEC 2008 NEC located over steps of a stairway. 240.86 Series Ratings. (A) Selected Under Engineering Supervision in Existing Installations. The series rated combination devices shall be selected by a licensed professional engineer engaged primarily in the design or maintenance of electrical installations. The selection shall be documented and stamped by the professional engineer. This documentation shall be available to those authorized to design, install, inspect, maintain, and operate the system. This series combination rating, including identification of the upstream device, shall be field marked on the end use equipment. VIII. Supervised Industrial Installations 240.92 Location in Circuit. An overcurrent device shall be connected in each ungrounded circuit conductor as required in 240.92(A) through (D). 240.86 Series Ratings. (A) Selected Under Engineering Supervision in Existing Installations. The series rated combination devices shall be selected by a licensed professional engineer engaged primarily in the design or maintenance of electrical installations. The selection shall be documented and stamped by the professional engineer. This documentation shall be available to those authorized to design, install, inspect, maintain, and operate the system. This series combination rating, including identification of the upstream device, shall be field marked on the end use equipment. For calculated applications, the engineer shall ensure that the downstream circuit breaker(s) that are part of the series combination remain passive during the interruption period of the line side fully rated, currentlimiting device. VIII. Supervised Industrial Installations 240.92 Location in Circuit. An overcurrent device shall be connected in each ungrounded circuit conductor as required in 240.92(A) through (E). Page 32 of 361 Change Description and Impact to Worker Safety Improves safety by reducing obstacles to access to electrical panels. Added section to address the need to assure that the downstream device does not operate during the fault clearing operation. As Safe or Safer. New section inserted to address the need for sizing information for feeder taps not previously provided. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC (A) Feeder and Branch-Circuit Conductors. Feeder and branch-circuit conductors shall be protected at the point the conductors receive their supply as permitted in 240.21 or as otherwise permitted in 240.92(B), (C), or (D). (A) Feeder and Branch-Circuit Conductors. Feeder and branch-circuit conductors shall be protected at the point the conductors receive their supply as permitted in 240.21 or as otherwise permitted in 240.92(B), (C), or (D). (B) Feeder Taps. For feeder taps specified in 240.21(B)(2), (B)(3), and (B)(4), the tap conductors shall be permitted to be sized in accordance with Table 240.92(B). (C) Transformer Secondary Conductors of Separately Derived Systems. Conductors shall be permitted to be connected to a transformer secondary of a separately derived system, without overcurrent protection at the connection, where the conditions of 240.92(C)(1), (C)(2), and (C)(3) are met. Article 250 250.4 General Requirements for Grounding and Bonding. (B) Ungrounded Systems. (4) Path for Fault Current. Electrical equipment, wiring, and other electrically conductive material likely to become energized shall be installed in a manner that creates a low (B) Transformer Secondary Conductors of Separately Derived Systems. Conductors shall be permitted to be connected to a transformer secondary of a separately derived system, without overcurrent protection at the connection, where the conditions of 240.92(B)(1), (B)(2), and (B)(3) are met. 250.4 General Requirements for Grounding and Bonding. (B) Ungrounded Systems. (4) Path for Fault Current. Electrical equipment, wiring, and other electrically conductive material likely to become energized shall be installed in a manner that creates a permanent, Page 33 of 361 Change Description and Impact to Worker Safety Modified to eliminate the “permanent” circuit reference and to clarify that it is specifically a ground fault from another phase that is the real concern. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC impedance circuit from any point on the wiring system to the electrical supply source to facilitate the operation of overcurrent devices should a second ground fault from a different phase occur on the wiring system. The earth shall not be considered as an effective fault-current path. 250.6 Objectionable Current over 250.6 Objectionable Current. Grounding Conductors. (A) Arrangement to Prevent (A) Arrangement to Prevent Objectionable Current. Objectionable Current. The grounding of electrical systems, The grounding of electrical systems, circuit conductors, surge arresters, circuit conductors, surge arresters, and surge-protective devices, and conductive non–current-carrying conductive normally non–currentmaterials and equipment shall be carrying metal parts of equipment shall installed and arranged in a manner that be installed and arranged in a manner will prevent objectionable current over that will prevent objectionable current. the grounding conductors or grounding paths. 250.6 Objectionable Current. 250.6 Objectionable Current. (B) Alterations to Stop Objectionable (B) Alterations to Stop Objectionable Current. If the use of multiple Current. If the use of multiple grounding connections results in grounding connections results in objectionable current, one or more of objectionable current, one or more of the following alterations shall be the following alterations shall be permitted to be made, provided that permitted to be made, provided that the requirements of 250.4(A)(5) or the requirements of 250.4(A)(5) or (B)(4) are met: (B)(4) are met: (1) Discontinue one or more but not all (1) Discontinue one or more but not all of such grounding connections. of such grounding connections. Change Description and Impact to Worker Safety low-impedance circuit from any point on the wiring system to the electrical supply source to facilitate the operation of overcurrent devices should a second fault occur on the wiring system. The earth shall not be considered as an effective fault-current path. Page 34 of 361 Modified to simplify wording and to clarify that it is the metal parts of equipment not normally carrying current that must meet the grounding requirements for objectionable current. As Safe or Safer. Clarified to specifically address the conductive path causing the objectionable current and not just any interconnecting grounding conductors. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC (2) Change the locations of the grounding connections. (3) Interrupt the continuity of the conductor or conductive path interconnecting the grounding connections. (4) Take other suitable remedial and approved action. 250.6 Objectionable Current. (D) Limitations to Permissible Alterations. The provisions of this section shall not be considered as permitting electronic equipment from being operated on ac systems or branch circuits that are not grounded as required by this article. Currents that introduce noise or data errors in electronic equipment shall not be considered the objectionable currents addressed in this section. 250.8 Connection of Grounding and Bonding Equipment. Grounding conductors and bonding jumpers shall be connected by exothermic welding, listed pressure connectors, listed clamps, or other listed means. Connection devices or fittings that depend solely on solder shall not be used. Sheet metal screws shall not be used to connect grounding conductors 2008 NEC Change Description and Impact to Worker Safety (2) Change the locations of the grounding connections. (3) Interrupt the continuity of the conductor or conductive path causing the objectionable current. (4) Take other suitable remedial and approved action. 250.6 Objectionable Current. (D) Limitations to Permissible Alterations. The provisions of this section shall not be considered as permitting electronic equipment from being operated on ac systems or branch circuits that are not connected to an equipment grounding conductor as required by this article. Currents that introduce noise or data errors in electronic equipment shall not be considered the objectionable currents addressed in this section. 250.8 Connection of Grounding and Bonding Equipment. (A) Permitted Methods. Grounding conductors and bonding jumpers shall be connected by one of the following means: (1) Listed pressure connectors (2) Terminal bars (3) Pressure connectors listed as grounding and bonding equipment Page 35 of 361 Clarifies the distinction of grounded versus connected to an equipment grounding conductor. As Safe or Safer. Reworked section to delineate the specific methods acceptable for connection of grounding conductors and to allow any listed means to be used. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC or connection devices to enclosures. II. System Grounding 250.20 Alternating-Current Systems to Be Grounded. (D) Separately Derived Systems. Separately derived systems, as covered in 250.20(A) or (B), shall be grounded as specified in 250.30. 2008 NEC Change Description and Impact to Worker Safety (4) Exothermic welding process (5) Machine screw-type fasteners that engage not less than two threads or are secured with a nut (6) Thread-forming machine screws that engage not less than two threads in the enclosure (7) Connections that are part of a listed assembly (8) Other listed means (B) Methods Not Permitted. Connection devices or fittings that depend solely on solder shall not be used. II. System Grounding 250.20 Alternating-Current Systems to Be Grounded. (D) Separately Derived Systems. Separately derived systems, as covered in 250.20(A) or (B), shall be grounded as specified in 250.30(A). Where an alternate source such as an on-site generator is provided with transfer equipment that includes a grounded conductor that is not solidly interconnected to the service-supplied grounded conductor, the alternate source (derived system) shall be grounded in accordance with 250.30(A). Page 36 of 361 Added section to address specific case of the separately derived system grounding when alternate source is a generator through a transfer operation. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 250.21 Alternating-Current Systems of 50 Volts to 1000 Volts Not Required to Be Grounded. 250.21 Alternating-Current Systems of 50 Volts to 1000 Volts Not Required to Be Grounded. The following ac systems of 50 volts to 1000 volts shall be permitted to be grounded but shall not be required to be grounded: (1) Electric systems used exclusively to supply industrial electric furnaces for melting, refining, tempering, and the like (2) Separately derived systems used exclusively for rectifiers that supply only adjustable-speed industrial drives (3) Separately derived systems supplied by transformers that have a primary voltage rating less than 1000 volts, provided that all the following conditions are met: a. The system is used exclusively for control circuits. b. The conditions of maintenance and supervision ensure that only qualified persons service the installation. c. Continuity of control power is required. d. Ground detectors are installed on the control system. (4) Other systems that are not required to be grounded in accordance with the (A) General. The following ac systems of 50 volts to 1000 volts shall be permitted to be grounded but shall not be required to be grounded: (1) Electrical systems used exclusively to supply industrial electric furnaces for melting, refining, tempering, and the like (2) Separately derived systems used exclusively for rectifiers that supply only adjustable-speed industrial drives (3) Separately derived systems supplied by transformers that have a primary voltage rating less than 1000 volts, provided that all the following conditions are met: a. The system is used exclusively for control circuits. b. The conditions of maintenance and supervision ensure that only qualified persons service the installation. c. Continuity of control power is required. (4) Other systems that are not required to be grounded in accordance with the requirements of 250.20(B) Page 37 of 361 Change Description and Impact to Worker Safety Modified to clarify the intent of requiring ground detectors and to specify which systems must have them installed. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC requirements of 250.20(B). Where an alternating-current system is not grounded as permitted in 250.21(1) through (4), ground detectors shall be installed on the system. (B) Ground Detectors. Ungrounded alternating current systems as permitted in 250.21(A)(1) through (A)(4) operating at not less than 120 volts and not exceeding 1000 volts shall have ground detectors installed on the system. 250.22 Circuits Not to Be Grounded. The following circuits shall not be grounded: (1) Circuits for electric cranes operating over combustible fibers in Class III locations, as provided in 503.155 (2) Circuits in health care facilities as provided in 517.61 and 517.160 (3) Circuits for equipment within electrolytic cell working zone as provided in Article 668 (4) Secondary circuits of lighting systems as provided in 411.5(A) (5) Secondary circuits of lighting systems as provided in 680.23(A)(2). 250.24 Grounding Service-Supplied Alternating-Current Systems. (A) System Grounding Connections. (1) General. The grounding electrode conductor connection shall be made at any accessible point from the load end of the service drop or service lateral to and including the terminal or bus to 250.22 Circuits Not to Be Grounded. The following circuits shall not be grounded: (1) Circuits for electric cranes operating over combustible fibers in Class III locations, as provided in 503.155 (2) Circuits in health care facilities as provided in 517.61 and 517.160 (3) Circuits for equipment within electrolytic cell working zone as provided in Article 668 (4) Secondary circuits of lighting systems as provided in 411.5(A) 250.24 Grounding Service-Supplied Alternating-Current Systems. (A) System Grounding Connections. (1) General. The connection shall be made at any accessible point from the load end of the service drop or service lateral to and including the terminal or bus to which the grounded service Page 38 of 361 Change Description and Impact to Worker Safety Added exemption for transformers for lighting systems covered in 680.23 Underwater Luminaires. As Safe or Safer. Clarifies that it is specifically the grounding electrode conductor connection addressed by this section. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC conductor is connected at the service disconnecting means. 250.24 Grounding Service-Supplied Alternating-Current Systems. (A) System Grounding Connections. (5) Load-Side Grounding Connections. A grounding connection shall not be made to any grounded conductor on the load side of the service disconnecting means except as otherwise permitted in this article. 250.24 Grounding Service-Supplied Alternating-Current Systems. (C) Grounded Conductor Brought to Service Equipment. Where an ac system operating at less than 1000 volts is grounded at any point, the grounded conductor(s) shall be run to each service disconnecting means and shall be bonded to each disconnecting means enclosure. The grounded conductor(s) shall be installed in accordance with 250.24(C)(1) through (C)(3). Exception: Where more than one service disconnecting means are 2008 NEC which the grounded service conductor is connected at the service disconnecting means. 250.24 Grounding Service-Supplied Alternating-Current Systems. (A) System Grounding Connections. (5) Load-Side Grounding Connections. A grounded conductor shall not be connected to normally non–current carrying metal parts of equipment, to equipment grounding conductor(s), or be reconnected to ground on the load side of the service disconnecting means except as otherwise permitted in this article. 250.24 Grounding Service-Supplied Alternating-Current Systems. (C) Grounded Conductor Brought to Service Equipment. Where an ac system operating at less than 1000 volts is grounded at any point, the grounded conductor(s) shall be run to each service disconnecting means and shall be connected to each disconnecting means grounded conductor(s) terminal or bus. A main bonding jumper shall connect the grounded conductor(s) to each service disconnecting means enclosure. The grounded conductor(s) shall be installed in accordance with Page 39 of 361 Change Description and Impact to Worker Safety Clarifies that the grounded conductor (neutral) is not to be grounded to anything other than the proper connection at the service point. As Safe or Safer. Clarified the connection requirements for the grounded conductor at the service point disconnect enclosure. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC located in an assembly listed for use as service equipment, it shall be permitted to run the grounded conductor(s) to the assembly, and the conductor(s) shall be bonded to the assembly enclosure. 2008 NEC 250.24(C)(1) through (C)(3). 250.28 Main Bonding Jumper and System Bonding Jumper. Exception: Where more than one service disconnecting means are located in a single assembly listed for use as service equipment, it shall be permitted to run the grounded conductor(s) to the assembly common grounded conductor(s) terminal or bus. The assembly shall include a main bonding jumper for connecting the grounded conductor(s) to the assembly enclosure. 250.24 Grounding Service-Supplied Alternating-Current Systems. (D) Grounding Electrode Conductor. A grounding electrode conductor shall be used to connect the equipment grounding conductors, the serviceequipment enclosures, and, where the system is grounded, the grounded service conductor to the grounding electrode(s) required by Part III of this article. This conductor shall be sized in accordance with 250.66. 250.28 Main Bonding Jumper and System Bonding Jumper. (C) Attachment. Main bonding jumpers and system bonding jumpers shall be attached in the manner specified by (C) Attachment. Main bonding jumpers and system bonding jumpers shall be connected in the manner specified by 250.24 Grounding Service-Supplied Alternating-Current Systems. (D) Grounding Electrode Conductor. A grounding electrode conductor shall be used to connect the equipment grounding conductors, the serviceequipment enclosures, and, where the system is grounded, the grounded service conductor to the grounding electrode(s) required by Part III of this article. Change Description and Impact to Worker Safety Page 40 of 361 Added sizing requirement for the grounding electrode conductor. As Safe or Safer. Modified to emphasize “connected” versus just attached to assure good electrical path. Added new sections (2) and (3) to specifically address the needs for bonding in services or separately derived systems with more 70 2008 851 Evaluation 2005 NEC 2008 NEC the applicable provisions of 250.8. the applicable provisions of 250.8. (D) Size. Main bonding jumpers and system bonding jumpers shall not be smaller than the sizes shown in Table 250.66. Where the supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the bonding jumper shall have an area that is not less than 121⁄2 percent of the area of the largest phase conductor except that, where the phase conductors and the bonding jumper are of different materials (copper or aluminum), the minimum size of the bonding jumper shall be based on the assumed use of phase conductors of the same material as the bonding jumper and with an ampacity equivalent to that of the installed phase conductors. (D) Size. Main bonding jumpers and system bonding jumpers shall be sized in accordance with 250.28(D)(1) through (D)(3). (1) General. Main bonding jumpers and system bonding jumpers shall not be smaller than the sizes shown in Table 250.66. Where the supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the bonding jumper shall have an area that is not less than 121⁄2 percent of the area of the largest phase conductor except that, where the phase conductors and the bonding jumper are of different materials (copper or aluminum), the minimum size of the bonding jumper shall be based on the assumed use of phase conductors of the same material as the bonding jumper and with an ampacity equivalent to that of the installed phase conductors. (2) Main Bonding Jumper for Service with More Than One Enclosure. Where a service consists of more than a single enclosure as permitted in Page 41 of 361 Change Description and Impact to Worker Safety than one enclosure. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety 230.71(A), the main bonding jumper for each enclosure shall be sized in accordance with 250.28(D)(1) based on the largest ungrounded service conductor serving that enclosure. 250.30 Grounding Separately Derived Alternating-Current Systems. (A) Grounded Systems. A separately derived ac system that is grounded shall comply with 250.30(A)(1) through (A)(8). A grounding connection shall not be made to any grounded circuit conductor on the load side of the point of grounding of the separately derived (3) Separately Derived System with More Than One Enclosure. Where a separately derived system supplies more than a single enclosure, the system bonding jumper for each enclosure shall be sized in accordance with 250.28(D)(1) based on the largest ungrounded feeder conductor serving that enclosure, or a single system bonding jumper shall be installed at the source and sized in accordance with 250.28(D)(1) based on the equivalent size of the largest supply conductor determined by the largest sum of the areas of the corresponding conductors of each set. 250.30 Grounding Separately Derived Alternating-Current Systems. (A) Grounded Systems. A separately derived ac system that is grounded shall comply with 250.30(A)(1) through (A)(8). Except as otherwise permitted in this article, a grounded conductor shall not be connected to normally non current-carrying metal parts of Page 42 of 361 Modified to clarify that the grounded conductor is not to be connected to any grounded non current-carrying metal part whether it is a conductor or not. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC system except as otherwise permitted in this article. 250.30 Grounding Separately Derived Alternating-Current Systems. (A) Grounded Systems. (4) Grounding Electrode Conductor, Multiple Separately Derived Systems. Where more than one separately derived system is installed, it shall be permissible to connect a tap from each separately derived system to a common grounding electrode conductor. Each tap conductor shall connect the grounded conductor of the separately derived system to the common grounding electrode conductor. The grounding electrode conductors and taps shall comply with 250.30(A)(4)(a) through (A)(4)(c). 250.30 Grounding Separately Derived Alternating-Current Systems. (A) Grounded Systems. 2008 NEC equipment, to equipment grounding conductors, or be reconnected to ground on the load side of the point of grounding of a separately derived system. 250.30 Grounding Separately Derived Alternating-Current Systems. (A) Grounded Systems. (4) Grounding Electrode Conductor, Multiple Separately Derived Systems. Where more than one separately derived system is installed, it shall be permissible to connect a tap from each separately derived system to a common grounding electrode conductor. Each tap conductor shall connect the grounded conductor of the separately derived system to the common grounding electrode conductor. The grounding electrode conductors and taps shall comply with 250.30(A)(4)(a) through (A)(4)(c). This connection shall be made at the same point on the separately derived system where the system bonding jumper is installed. 250.30 Grounding Separately Derived Alternating-Current Systems. (A) Grounded Systems. Page 43 of 361 Change Description and Impact to Worker Safety Added specific connection requirements for the connection of the separately derived system grounding electrode conductors. As Safe or Safer. Specifies connection to grounded conductor which effectively bonds the building steel to the system as originally intended. 70 2008 851 Evaluation 2005 NEC 2008 NEC (6) Bonding. Structural steel and metal piping shall be bonded in accordance with 250.104(D). (6) Bonding. Structural steel and metal piping shall be connected to the grounded conductor of a separately derived system in accordance with 250.104(D). 250.32 Buildings or Structures Supplied by a Feeder(s) or Branch Circuit(s). 250.32 Buildings or Structures Supplied by a Feeder(s) or Branch Circuit(s). (B) Grounded Systems. For a grounded system at the separate building or structure, the connection to the grounding electrode and grounding or bonding of equipment, structures, or frames required to be grounded or bonded shall comply with either 250.32(B)(1) or (B)(2). (B) Grounded Systems. For a grounded system at the separate building or structure, an equipment grounding conductor as described in 250.118 shall be run with the supply conductors and be connected to the building or structure disconnecting means and to the grounding electrode(s). The equipment grounding conductor shall be used for grounding or bonding of equipment, structures, or frames required to be grounded or bonded. The equipment grounding conductor shall be sized in accordance with 250.122. Any installed grounded conductor shall not be connected to the equipment grounding conductor or to the grounding electrode(s). (1) Equipment Grounding Conductor. An equipment grounding conductor as described in 250.118 shall be run with the supply conductors and connected to the building or structure disconnecting means and to the grounding electrode(s). The equipment grounding conductor shall be used for grounding or bonding of equipment, structures, or frames required to be grounded or bonded. The equipment Exception: For existing premises wiring grounding conductor shall be sized in systems only, the grounded conductor accordance with 250.122. Any installed run with the supply to the building or Page 44 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Modified to specifically address the requirement for an equipment grounding conductor to be installed and change the section to only allow the grounded conductor to be connected for situations meeting the exception criteria. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC grounded conductor shall not be connected to the equipment grounding conductor or to the grounding electrode(s). (2) Grounded Conductor. Where (1) an equipment grounding conductor is not run with the supply to the building or structure, (2) there are no continuous metallic paths bonded to the grounding system in each building or structure involved, and (3) ground-fault protection of equipment has not been installed on the supply side of the feeder(s), the grounded conductor run with the supply to the building or structure shall be connected to the building or structure disconnecting means and to the grounding electrode(s) and shall be used for grounding or bonding of equipment, structures, or frames required to be grounded or bonded. The size of the grounded conductor shall not be smaller than the larger of either of the following: (1) That required by 220.61 (2) That required by 250.122 250.32 Buildings or Structures Supplied by a Feeder(s) or Branch Circuit(s). 2008 NEC Change Description and Impact to Worker Safety structure shall be permitted to be connected to the building or structure disconnecting means and to the grounding electrode(s) and shall be used for grounding or bonding of equipment, structures, or frames required to be grounded or bonded where all the requirements of (1), (2), and (3) are met: (1) An equipment grounding conductor is not run with the supply to the building or structure. (2) There are no continuous metallic paths bonded to the grounding system in each building or structure involved. (3) Ground-fault protection of equipment has not been installed on the supply side of the feeder(s). Where the grounded conductor is used for grounding in accordance with the provision of this exception, the size of the grounded conductor shall not be smaller than the larger of either of the following: (1) That required by 220.61 (2) That required by 250.122 250.32 Buildings or Structures Supplied by a Feeder(s) or Branch Circuit(s). Page 45 of 361 Modified to assure that the grounded conductor is not connected to any grounded metal part other than at the 70 2008 851 Evaluation 2005 NEC 2008 NEC (D) Disconnecting Means Located in Separate Building or Structure on the Same Premises. Where one or more disconnecting means supply one or more additional buildings or structures under single management, and where these disconnecting means are located remote from those buildings or structures in accordance with the provisions of 225.32, Exception Nos. 1 and 2, all of the following conditions shall be met: Change Description and Impact to Worker Safety grounding electrode connection and that the term connection is used to reinforce the idea of good electrical continuity. (D) Disconnecting Means Located in Separate Building or Structure on the Same Premises. Where one or more disconnecting means supply one or more additional buildings or structures As Safe or Safer. under single management, and where these disconnecting means are located remote from those buildings or structures in accordance with the provisions of 225.32, Exception No. 1 and No. 2, 700.12(B)(6), 701.11(B)(5), or 702.11, all of the following conditions shall be met: (1) The connection of the grounded (1) The connection of the grounded conductor to the grounding electrode at conductor to the grounding electrode, a separate building or structure shall to normally non-current-carrying metal not be made. parts of equipment, or to the equipment grounding conductor at a separate building or structure shall not be made. (2) An equipment grounding conductor for grounding any non-current-carrying equipment, interior metal piping systems, and building or structural metal frames is run with the circuit conductors to a separate building or structure and bonded to existing grounding electrode(s) required in Part III of this article, or, where there are no (2) An equipment grounding conductor for grounding and bonding any normally non-current-carrying metal parts of equipment, interior metal piping systems, and building or structural metal frames is run with the circuit conductors to a separate building or structure and connected to existing grounding electrode(s) Page 46 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC existing electrodes, the grounding electrode(s) required in Part III of this article shall be installed where a separate building or structure is supplied by more than one branch circuit. required in Part III of this article, or, where there are no existing electrodes, the grounding electrode(s) required in Part III of this article shall be installed where a separate building or structure is supplied by more than one branch circuit. (3) Bonding the equipment grounding conductor to the grounding electrode at a separate building or structure shall be made in a junction box, panelboard, or similar enclosure located immediately inside or outside the separate building or structure. (3) The connection between the equipment grounding conductor and the grounding electrode at a separate building or structure shall be made in a junction box, panelboard, or similar enclosure located immediately inside or outside the separate building or structure. 250.34 Portable and Vehicle-Mounted Generators. (A) Portable Generators. The frame of a portable generator shall not be required to be connected to a grounding electrode as defined in 250.52 for a system supplied by the generator under the following conditions: (1) The generator supplies only equipment mounted on the generator, cord-and-plug-connected equipment through receptacles mounted on the generator, or both, and (2) The normally non–current-carrying 250.34 Portable and Vehicle-Mounted Generators. (A) Portable Generators. The frame of a portable generator shall not be required to be connected to a grounding electrode as defined in 250.52 for a system supplied by the generator under the following conditions: (1) The generator supplies only equipment mounted on the generator, cord-and-plug-connected equipment through receptacles mounted on the generator, or both, and (2) The non–current-carrying metal Page 47 of 361 Change Description and Impact to Worker Safety Modified to address and emphasize “normally” non-current carrying metal parts as throughout the Code and to reiterate “connected” instead of “bonded”. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC parts of equipment and the equipment grounding conductor terminals of the receptacles are bonded to the generator frame. 250.34 Portable and Vehicle-Mounted Generators. (B) Vehicle-Mounted Generators. The frame of a vehicle shall not be required to be connected to a grounding electrode as defined in 250.52 for a system supplied by a generator located on this vehicle under the following conditions: (1) The frame of the generator is bonded to the vehicle frame, and (2) The generator supplies only equipment located on the vehicle or cord-and-plug-connected equipment through receptacles mounted on the vehicle, or both equipment located on the vehicle and cord-and-plugconnected equipment through receptacles mounted on the vehicle or on the generator, and (3) The non–current-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are bonded to the generator frame. 250.34 Portable and Vehicle-Mounted Generators. metal parts of equipment and the equipment grounding conductor terminals of the receptacles are connected to the generator frame. 250.34 Portable and Vehicle-Mounted Generators. (B) Vehicle-Mounted Generators. The frame of a vehicle shall not be required to be connected to a grounding electrode as defined in 250.52 for a system supplied by a generator located on this vehicle under the following conditions: (1) The frame of the generator is bonded to the vehicle frame, and (2) The generator supplies only equipment located on the vehicle or cord-and-plug-connected equipment through receptacles mounted on the vehicle, or both equipment located on the vehicle and cord-and-plugconnected equipment through receptacles mounted on the vehicle or on the generator, and (3) The normally non–current-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are connected to the generator frame. 250.34 Portable and Vehicle-Mounted Generators. Page 48 of 361 Change Description and Impact to Worker Safety Modified to address and emphasize “normally” non-current carrying metal parts as throughout the Code and to reiterate “connected” instead of “bonded”. As Safe or Safer. Modified to reiterate “connected” instead of “bonded”. 70 2008 851 Evaluation 2005 NEC 2008 NEC (C) Grounded Conductor Bonding. A system conductor that is required to be grounded by 250.26 shall be bonded to the generator frame where the generator is a component of a separately derived system. (C) Grounded Conductor Bonding. A system conductor that is required to be grounded by 250.26 shall be connected to the generator frame where the generator is a component of a separately derived system. 250.35 Permanently Installed Generators. A conductor that provides an effective ground-fault current path shall be installed with the supply conductors from a permanently installed generator(s) to the first disconnecting mean(s) in accordance with (A) or (B). (A) Separately Derived System. Where the generator is installed as a separately derived system, the requirements in 250.30 shall apply. (B) Non-separately Derived System. Where the generator is not installed as a separately derived system, an equipment bonding jumper shall be installed between the generator equipment grounding terminal and the equipment grounding terminal or bus of the enclosure of supplied disconnecting mean(s) in accordance with (B)(1) or (B)(2). Page 49 of 361 Change Description and Impact to Worker Safety As Safe or Safer. New section created to answer concerns about the specific grounding and bonding requirements for permanently installed generators previously not addressed. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety (1) Supply Side of Generator Overcurrent Device. The equipment bonding jumper on the supply side of each generator overcurrent device shall be sized in accordance with 250.102(C) based on the size of the conductors supplied by the generator. 250.36 High-Impedance Grounded Neutral Systems. High-impedance grounded neutral systems in which a grounding impedance, usually a resistor, limits the ground fault current to a low value shall be permitted for 3-phase ac systems of 480 volts to 1000 volts where all the following conditions are met: (1) The conditions of maintenance and supervision ensure that only qualified persons service the installation. (2) Continuity of power is required. (3) Ground detectors are installed on the system. (2) Load Side of Generator Overcurrent Device. The equipment grounding conductor on the load side of each generator overcurrent device shall be sized in accordance with 250.102(D) based on the rating of the overcurrent device supplied. 250.36 High-Impedance Grounded Neutral Systems. High-impedance grounded neutral systems in which a grounding impedance, usually a resistor, limits the ground fault current to a low value shall be permitted for 3-phase ac systems of 480 volts to 1000 volts where all the following conditions are met: (1) The conditions of maintenance and supervision ensure that only qualified persons service the installation. (2) Ground detectors are installed on the system. Page 50 of 361 Removed the stipulation that “continuity of power is required” as a criteria for use of a high impedance grounding system since the answer to this question would most certainly be yes, continuity is required. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC (4) Line-to-neutral loads are not served. 250.36 High-Impedance Grounded Neutral Systems. (3) Line-to-neutral loads are not served. 250.36 High-Impedance Grounded Neutral Systems. (A) Grounding Impedance Location. The grounding impedance shall be installed between the grounding electrode conductor and the system neutral. Where a neutral is not available, the grounding impedance shall be installed between the grounding electrode conductor and the neutral derived from a grounding transformer. 250.36 High-Impedance Grounded Neutral Systems. (A) Grounding Impedance Location. The grounding impedance shall be installed between the grounding electrode conductor and the system neutral point. Where a neutral point is not available, the grounding impedance shall be installed between the grounding electrode conductor and the neutral point derived from a grounding transformer. 250.36 High-Impedance Grounded Neutral Systems. (B) Neutral Conductor. The neutral conductor from the neutral point of the transformer or generator to its connection point to the grounding impedance shall be fully insulated. The neutral conductor shall have an ampacity of not less than the maximum current rating of the grounding impedance. In no case shall the neutral conductor be smaller than 8 AWG copper or 6 AWG aluminum or copperclad aluminum. (B) Grounded System Conductor. The grounded system conductor from the neutral point of the transformer or generator to its connection point to the grounding impedance shall be fully insulated. The grounded system conductor shall have an ampacity of not less than the maximum current rating of the grounding impedance. In no case shall the grounded system conductor be smaller than 8 AWG copper or 6 AWG aluminum or copper-clad aluminum. Page 51 of 361 Change Description and Impact to Worker Safety Added “point” to emphasize the specific point to which the grounding impedance is connected. The definition of neutral point narrows to options to assure proper location. As Safe or Safer. Replaced “neutral” with “grounded system” to properly identify the role of the conductor. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 250.36 High-Impedance Grounded Neutral Systems. 250.36 High-Impedance Grounded Neutral Systems. (C) System Neutral Connection. The system neutral conductor shall not be connected to ground except through the grounding impedance. 250.36 High-Impedance Grounded Neutral Systems. (C) System Grounding Connection. The system shall not be connected to ground except through the grounding impedance. 250.36 High-Impedance Grounded Neutral Systems. (D) Neutral Conductor Routing. The conductor connecting the neutral point of the transformer or generator to the grounding impedance shall be permitted to be installed in a separate raceway. It shall not be required to run this conductor with the phase conductors to the first system disconnecting means or overcurrent device. 250.52 Grounding Electrodes. (A) Electrodes Permitted for Grounding. (D) Neutral Point to Grounding Impedance Conductor Routing. The conductor connecting the neutral point of the transformer or generator to the grounding impedance shall be permitted to be installed in a separate raceway from the ungrounded conductors. It shall not be required to run this conductor with the phase conductors to the first system disconnecting means or overcurrent device. 250.52 Grounding Electrodes. (A) Electrodes Permitted for Grounding. (2) Metal Frame of the Building or Structure. The metal frame of the building or structure, where any of the following methods are used to make an earth connection: (2) Metal Frame of the Building or Structure. The metal frame of the building or structure that is connected to the earth by any of the following methods: Page 52 of 361 Change Description and Impact to Worker Safety Replaced “neutral” with “grounding” to properly identify the role of the conductor. As Safe or Safer. Modified wording to properly identify the role of the conductor. As Safe or Safer. Modified to address the specific actions taken to make the connection to earth and to reinforce the connection requirements. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC (1) 3.0 m (10 ft) or more of a single structural metal member in direct contact with the earth or encased in concrete that is in direct contact with the earth (2) The structural metal frame is bonded to one or more of the grounding electrodes as defined in 250.52(A)(1), (A)(3), or (A)(4) (3) The structural metal frame is bonded to one or more of the grounding electrodes as defined in 250.52(A)(5) or (A)(6) that comply with 250.56, or (4) Other approved means of establishing a connection to earth. 250.52 Grounding Electrodes. (A) Electrodes Permitted for Grounding. (3) Concrete-Encased Electrode. An electrode encased by at least 50 mm (2 in.) of concrete, located within and near the bottom of a concrete foundation or footing that is in direct contact with the earth, consisting of at least 6.0 m (20 ft) of one or more bare or zinc galvanized or other electrically conductive coated steel reinforcing bars or rods of not less than 13 mm 2008 NEC (1) 3.0 m (10 ft) or more of a single structural metal member in direct contact with the earth or encased in concrete that is in direct contact with the earth (2) Connecting the structural metal frame to the reinforcing bars of a concrete-encased electrode as provided in 250.52(A)(3) or ground ring as provided in 250.52(A)(4) (3) Bonding the structural metal frame to one or more of the grounding electrodes as defined in 250.52(A)(5) or (A)(7) that comply with 250.56 (4) Other approved means of establishing a connection to earth 250.52 Grounding Electrodes. (A) Electrodes Permitted for Grounding. Change Description and Impact to Worker Safety Modified to clarify intent and to allow more than just the bottom of the concrete encased electrode to qualify as the section in direct contact with the (3) Concrete-Encased Electrode. An earth. In addition, there is no need to electrode encased by at least 50 mm connect all of the concrete-encased (2 in.) of concrete, located horizontally electrodes to the grounding electrode near the bottom or vertically, and within system as was inferred previously. that portion of a concrete foundation or footing that is in direct contact with the As Safe or Safer. earth, consisting of at least 6.0 m (20 ft) of one or more bare or zinc galvanized or other electrically conductive coated steel reinforcing Page 53 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC (1⁄2 in.) in diameter, or consisting of at least 6.0 m (20 ft) of bare copper conductor not smaller than 4 AWG. Reinforcing bars shall be permitted to be bonded together by the usual steel tie wires or other effective means. bars or rods of not less than 13 mm (1⁄2 in.) in diameter, or consisting of at least 6.0 m (20 ft) of bare copper conductor not smaller than 4 AWG. Reinforcing bars shall be permitted to be bonded together by the usual steel tie wires or other effective means. Where multiple concrete-encased electrodes are present at a building or structure, it shall be permissible to bond only one into the grounding electrode system. 250.52 Grounding Electrodes. (A) Electrodes Permitted for Grounding. 250.52 Grounding Electrodes. (A) Electrodes Permitted for Grounding. (5) Rod and Pipe Electrodes. Rod and pipe electrodes shall not be less than 2.5 m (8 ft) in length and shall consist of the following materials. (a) Electrodes of pipe or conduit shall not be smaller than metric designator 21 (trade size 3⁄4) and, where of iron or steel, shall have the outer surface galvanized or otherwise metal-coated for corrosion protection. (b) Electrodes of rods of iron or steel shall be at least 15.87 mm (5⁄8 in.) in diameter. Stainless steel rods less than 16 mm (5⁄8 in.) in diameter, nonferrous rods, or their equivalent shall be listed (5) Rod and Pipe Electrodes. Rod and pipe electrodes shall not be less than 2.44 m (8 ft) in length and shall consist of the following materials. (a) Grounding electrodes of pipe or conduit shall not be smaller than metric designator 21 (trade size 3⁄4) and, where of steel, shall have the outer surface galvanized or otherwise metalcoated for corrosion protection. (b) Grounding electrodes of stainless steel and copper or zinc coated steel shall be at least 15.87 mm (5⁄8 in.) in diameter, unless listed and not less than 12.70 mm (1⁄2 in.) in diameter. Page 54 of 361 Change Description and Impact to Worker Safety Modified dimensions to more precisely indicate the metric equivalents. Specifically addresses the term grounding electrode in (b) to rule out other interpretations and cleared up the listed equivalent issue surrounding the minimum size allowed. No direct impact, but long term provides longer lasting grounding electrodes for personnel and equipment protection. 70 2008 851 Evaluation 2005 NEC 2008 NEC and shall not be less than 13 mm (1⁄2 in.) in diameter. 250.52 Grounding Electrodes. (A) Electrodes Permitted for Grounding. 250.52 Grounding Electrodes. (A) Electrodes Permitted for Grounding. 250.52 Grounding Electrodes. (6) Other Listed Electrodes. Other listed grounding electrodes shall be permitted. 250.52 Grounding Electrodes. (B) Electrodes Not Permitted for Grounding. The following shall not be used as grounding electrodes: (1) Metal underground gas piping system (2) Aluminum electrodes (B) Not Permitted for Use as Grounding Electrodes. The following systems and materials shall not be used as grounding electrodes: (1) Metal underground gas piping systems (2) Aluminum 250.54 Supplementary Grounding 250.54 Auxiliary Grounding Electrodes. Electrodes. Supplementary grounding One or more grounding electrodes electrodes shall be permitted to be shall be permitted to be connected to connected to the equipment grounding the equipment grounding conductors conductors specified in 250.118 and specified in 250.118 and shall not be shall not be required to comply with the required to comply with the electrode electrode bonding requirements of bonding requirements of 250.50 or 250.50 or 250.53(C) or the resistance 250.53(C) or the resistance requirements of 250.56, but the earth requirements of 250.56, but the earth shall not be used as an effective shall not be used as an effective ground-fault current path as specified ground-fault current path as specified in 250.4(A)(5) and 250.4(B)(4). in 250.4(A)(5) and 250.4(B)(4). 250.64 Grounding Electrode Conductor 250.64 Grounding Electrode Conductor Page 55 of 361 Change Description and Impact to Worker Safety Inserted new (6) to allow any other listed grounding electrodes to be used to allow improvements in manufacturing techniques and new listings. As Safe or Safer. Modified to reinforce the intent that grounding electrodes is the subject matter and that the materials or systems identified are not to be used, regardless if they are called electrodes or not. As Safe or Safer. Clarified intent since no definition of supplementary electrodes is presented and that any additional grounding electrodes beyond those required top be connected do not have to meet the same requirements. This change allows for easier installations and additions. As Safe or Safer. Inserted specific locations where 70 2008 851 Evaluation 2005 NEC 2008 NEC Installation. Grounding electrode conductors shall be installed as specified in 250.64(A) through (F). Change Description and Impact to Worker Safety grounding electrode conductors must comply with the requirements of the section. Installation. Grounding electrode conductors at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at a separately derived system shall be As Safe or Safer. installed as specified in 250.64(A) through (F). 250.64 Grounding Electrode Conductor 250.64 Grounding Electrode Conductor Total rewrite to address the specific Installation. Installation. requirements and to more accurately identify the equipment and materials (D) Grounding Electrode Conductor (D) Service with Multiple Disconnecting involved. The wording regarding taps Taps. Where a service consists of Means Enclosures. Where a service was reinforced with specific reference more than a single enclosure as consists of more than a single to grounding electrodes throughout to permitted in 230.71(A), it shall be enclosure as permitted in 230.71(A), eliminate confusion with other permitted to connect taps to the grounding electrode connections shall ungrounded conductor taps in Section common grounding electrode be made in accordance with (D)(1), 240.21. conductor. Each such tap conductor (D)(2), or (D)(3). shall extend to the inside of each such As Safe or Safer. enclosure. The common grounding (1) Grounding Electrode Conductor electrode conductor shall be sized in Taps. Where the service is installed as accordance with 250.66, based on the permitted by 230.40, Exception No. 2, sum of the circular mil area of the a common grounding electrode largest ungrounded service entrance conductor and grounding electrode conductors. Where more than one set conductor taps shall be installed. The of service entrance conductors as common grounding electrode permitted by 230.40, Exception No. 2 conductor shall be sized in accordance connect directly to a service drop or with 250.66, based on the sum of the lateral, the common grounding circular mil area of the largest electrode conductor shall be sized in ungrounded service-entrance accordance with Table 250.66 Note 1. conductor(s). Where the serviceThe tap conductors shall be permitted entrance conductors connect directly to Page 56 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC to be sized in accordance with the grounding electrode conductors specified in 250.66 for the largest conductor serving the respective enclosures. The tap conductors shall be connected to the common grounding electrode conductor in such a manner that the common grounding electrode conductor remains without a splice or joint. a service drop or service lateral, the common grounding electrode conductor shall be sized in accordance with Table 250.66, Note 1. A tap conductor shall extend to the inside of each service disconnecting means enclosure. The grounding electrode conductor taps shall be sized in accordance with 250.66 for the largest conductor serving the individual enclosure. The tap conductors shall be connected to the common grounding electrode conductor by exothermic welding or with connectors listed as grounding and bonding equipment in such a manner that the common grounding electrode conductor remains without a splice or joint. (2) Individual Grounding Electrode Conductors. A grounding electrode conductor shall be connected between the grounded conductor in each service equipment disconnecting means enclosure and the grounding electrode system. Each grounding electrode conductor shall be sized in accordance with 250.66 based on the service-entrance conductor(s) supplying the individual service disconnecting means. Page 57 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety (3) Common Location. A grounding electrode conductor shall be connected to the grounded service conductor(s) in a wireway or other accessible enclosure on the supply side of the service disconnecting means. The connection shall be made with exothermic welding or a connector listed as grounding and bonding equipment. The grounding electrode conductor shall be sized in accordance with 250.66 based on the serviceentrance conductor(s) at the common location where the connection is made. 250.64 Grounding Electrode Conductor 250.64 Grounding Electrode Conductor Elimination of service broadens the Installation. Installation. locations that require bonding per this section to include those supplied via (E) Enclosures for Grounding (E) Enclosures for Grounding other means such as separately Electrode Conductors. Ferrous metal Electrode Conductors. Ferrous metal derived systems, feeders and branch enclosures for grounding electrode enclosures for grounding electrode circuits. conductors shall be electrically conductors shall be electrically continuous from the point of continuous from the point of As Safe or Safer. attachment to cabinets or equipment to attachment to cabinets or equipment to the grounding electrode and shall be the grounding electrode and shall be securely fastened to the ground clamp securely fastened to the ground clamp or fitting. Nonferrous metal enclosures or fitting. Nonferrous metal enclosures shall not be required to be electrically shall not be required to be electrically continuous. Ferrous metal enclosures continuous. Ferrous metal enclosures that are not physically continuous from that are not physically continuous from cabinets or equipment to the grounding cabinets or equipment to the grounding Page 58 of 361 70 2008 851 Evaluation 2005 NEC electrode shall be made electrically continuous by bonding each end of the raceway or enclosure to the grounding electrode conductor. Bonding shall apply at each end and to all intervening ferrous raceways, boxes, and enclosures between the service equipment and the grounding electrode. The bonding jumper for a grounding electrode conductor raceway or cable armor shall be the same size as, or larger than, the required enclosed grounding electrode conductor. Where a raceway is used as protection for a grounding electrode conductor, the installation shall comply with the requirements of the appropriate raceway article. 250.64 Grounding Electrode Conductor Installation. (F) To Electrode(s). A grounding electrode conductor shall be permitted to be run to any convenient grounding electrode available in the grounding electrode system, or to one or more grounding electrode(s) individually, or to the aluminum or copper busbar as permitted in 250.64(C). The grounding electrode conductor shall be sized for the largest grounding electrode 2008 NEC Change Description and Impact to Worker Safety electrode shall be made electrically continuous by bonding each end of the raceway or enclosure to the grounding electrode conductor. Bonding shall apply at each end and to all intervening ferrous raceways, boxes, and enclosures between the cabinets or equipment and the grounding electrode. The bonding jumper for a grounding electrode conductor raceway or cable armor shall be the same size as, or larger than, the enclosed grounding electrode conductor. Where a raceway is used as protection for a grounding electrode conductor, the installation shall comply with the requirements of the appropriate raceway article. 250.64 Grounding Electrode Conductor Modified to place specific requirements Installation. on the installation of grounding electrode conductors and to allow for (F) Installation to Electrode(s). use of a listed means for connection to Grounding electrode conductor(s) and enclosures. bonding jumpers interconnecting grounding electrodes shall be installed As Safe or Safer. in accordance with (1), (2), or (3). The grounding electrode conductor shall be sized for the largest grounding electrode conductor required among all the electrodes connected to it. Page 59 of 361 70 2008 851 Evaluation 2005 NEC conductor required among all the electrodes connected to it. 2008 NEC Change Description and Impact to Worker Safety (1) The grounding electrode conductor shall be permitted to be run to any convenient grounding electrode available in the grounding electrode system where the other electrode(s), if any, are connected by bonding jumpers per 250.53(C). (2) Grounding electrode conductor(s) shall be permitted to be run to one or more grounding electrode(s) individually. 250.66 Size of Alternating-Current Grounding Electrode Conductor. The size of the grounding electrode conductor of a grounded or (3) Bonding jumper(s) from grounding electrode(s) shall be permitted to be connected to an aluminum or copper busbar not less than 6 mm × 50 mm (1⁄4 in. × 2 in.). The busbar shall be securely fastened and shall be installed in an accessible location. Connections shall be made by a listed connector or by the exothermic welding process. The grounding electrode conductor shall be permitted to be run to the busbar. Where aluminum busbars are used, the installation shall comply with 250.64(A). 250.66 Size of Alternating-Current Grounding Electrode Conductor. The size of the grounding electrode conductor at the service, at each Page 60 of 361 Modified to eliminate the confusion and misinterpretation of where grounding electrode conductors need to be installed in accordance with the 70 2008 851 Evaluation 2005 NEC 2008 NEC ungrounded ac system shall not be building or structure where supplied by less than given in Table 250.66, except a feeder(s) or branch circuit(s), or at a as permitted in 250.66(A) through (C). separately derived system of a grounded or ungrounded ac system shall not be less than given in Table 250.66, except as permitted in 250.66(A) through (C). 250.68 Grounding Electrode Conductor 250.68 Grounding Electrode Conductor and Bonding Jumper Connection to and Bonding Jumper Connection to Grounding Electrodes. Grounding Electrodes. The connection of a grounding electrode conductor at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at a separately derived system and associated bonding jumper(s) shall be made as specified 250.68(A) and (B). Change Description and Impact to Worker Safety requirements of this section. As Safe or Safer. Modified to eliminate the confusion and misinterpretation of where grounding electrode conductors need to be installed in accordance with the requirements of this section. Exception No. 2 modified to better explain the requirements. As Safe or Safer. (A) Accessibility. The connection of a grounding electrode conductor or bonding jumper to a grounding electrode shall be accessible. (A) Accessibility. All mechanical elements used to terminate a grounding electrode conductor or bonding jumper to a grounding electrode shall be accessible. Exception No. 1: An encased or buried connection to a concrete-encased, driven, or buried grounding electrode shall not be required to be accessible. Exception No. 1: An encased or buried connection to a concrete-encased, driven, or buried grounding electrode shall not be required to be accessible. Exception No. 2: An exothermic or irreversible compression connection to Exception No. 2: Exothermic or irreversible compression connections Page 61 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC fire-proofed structural metal shall not be required to be accessible. Change Description and Impact to Worker Safety used at terminations, together with the mechanical means used to attach such terminations to fireproofed structural metal whether or not the mechanical means is reversible, shall not be required to be accessible. 250.68 Grounding Electrode Conductor 250.68 Grounding Electrode Conductor Removed “permanent” and reworded and Bonding Jumper Connection to and Bonding Jumper Connection to slightly to specifically address that Grounding Electrodes. Grounding Electrodes. there are bonding jumpers not conductors and that the grounding (B) Effective Grounding Path. The (B) Effective Grounding Path. The path is the important component to connection of a grounding electrode connection of a grounding electrode maintain. conductor or bonding jumper to a conductor or bonding jumper to a grounding electrode shall be made in a grounding electrode shall be made in a Actually improves worker safety by manner that will ensure a permanent manner that will ensure an effective assuring a continuous ground path. and effective grounding path. Where grounding path. Where necessary to necessary to ensure the grounding ensure the grounding path for a metal path for a metal piping system used as piping system used as a grounding a grounding electrode, effective electrode, bonding shall be provided bonding shall be provided around around insulated joints and around any insulated joints and around any equipment likely to be disconnected for equipment likely to be disconnected for repairs or replacement. Bonding repairs or replacement. Bonding jumpers shall be of sufficient length to conductors shall be of sufficient length permit removal of such equipment to permit removal of such equipment while retaining the integrity of the while retaining the integrity of the bond. grounding path. IV. Enclosure, Raceway, and Service IV. Enclosure, Raceway, and Service Modified to differentiate “connected to Cable Grounding Cable Connections the grounded system conductor” from simply “grounding” which had been 250.80 Service Raceways and 250.80 Service Raceways and misinterpreted and inconsistently Enclosures. Metal enclosures and Enclosures. Metal enclosures and applied. Page 62 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC raceways for service conductors and equipment shall be grounded. raceways for service conductors and equipment shall be connected to the grounded system conductor if the electrical system is grounded or to the grounding electrode conductor for electrical systems that are not grounded. Exception: A metal elbow that is installed in an underground installation of rigid nonmetallic conduit and is isolated from possible contact by a minimum cover of 450 mm (18 in.) to any part of the elbow shall not be required to be grounded. Exception: A metal elbow that is installed in an underground installation of rigid nonmetallic conduit and is isolated from possible contact by a minimum cover of 450 mm (18 in.) to any part of the elbow shall not be required to be connected to the grounded system conductor or grounding electrode conductor. 250.84 Underground Service Cable or Raceway. 250.84 Underground Service Cable or Raceway. (A) Underground Service Cable. The sheath or armor of a continuous underground metal-sheathed or armored service cable system that is bonded to the grounded underground system shall not be required to be grounded at the building or structure. The sheath or armor shall be permitted to be insulated from the interior metal raceway conduit or piping. (A) Underground Service Cable. The sheath or armor of a continuous underground metal-sheathed or armored service cable system that is connected to the grounded system conductor on the supply side shall not be required to be connected to the grounded system conductor at the building or structure. The sheath or armor shall be permitted to be insulated from the interior metal Page 63 of 361 Change Description and Impact to Worker Safety Actually improves worker safety by assuring a continuous ground path. Modified to differentiate “connected to the grounded system conductor” from simply “grounding” which had been misinterpreted and inconsistently applied. Actually improves worker safety by assuring a continuous ground path. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety raceway or piping. (B) Underground Service Raceway Containing Cable. An underground metal service raceway that contains a metal-sheathed or armored cable bonded to the grounded underground system shall not be required to be grounded at the building or structure. The sheath or armor shall be permitted to be insulated from the interior metal raceway or piping. 250.86 Other Conductor Enclosures and Raceways. Except as permitted by 250.112(I), metal enclosures and raceways for other than service conductors shall be grounded. Exception No. 1: Metal enclosures and raceways for conductors added to existing installations of open wire, knob and tube wiring, and nonmetallicsheathed cable shall not be required to be grounded where these enclosures or wiring methods comply with (1) through (4) as follows: (1) Do not provide an equipment (B) Underground Service Raceway Containing Cable. An underground metal service raceway that contains a metal-sheathed or armored cable connected to the grounded system conductor shall not be required to be connected to the grounded system conductor at the building or structure. The sheath or armor shall be permitted to be insulated from the interior metal raceway or piping. 250.86 Other Conductor Enclosures and Raceways. Except as permitted by 250.112(I), metal enclosures and raceways for other than service conductors shall be connected to the equipment grounding conductor. Exception No. 1: Metal enclosures and raceways for conductors added to existing installations of open wire, knob and tube wiring, and nonmetallicsheathed cable shall not be required to be connected to the equipment grounding conductor where these enclosures or wiring methods comply with (1) through (4) as follows: (1) Do not provide an equipment Page 64 of 361 Inserted “connected to the equipment grounding conductor” in lieu of “grounded” which had been misinterpreted and inconsistently applied. Actually improves worker safety by assuring a continuous ground path. 70 2008 851 Evaluation 2005 NEC ground (2) Are in runs of less than 7.5 m (25 ft) (3) Are free from probable contact with ground, grounded metal, metal lath, or other conductive material (4) Are guarded against contact by persons Exception No. 2: Short sections of metal enclosures or raceways used to provide support or protection of cable assemblies from physical damage shall not be required to be grounded. Exception No. 3: A metal elbow shall not be required to be grounded where it is installed in a nonmetallic raceway and is isolated from possible contact by a minimum cover of 450 mm (18 in.) to any part of the elbow or is encased in not less than 50 mm (2 in.) of concrete. 250.94 Bonding for Other Systems. An accessible means external to enclosures for connecting intersystem bonding and grounding electrode conductors shall be provided at the service equipment and at the 2008 NEC Change Description and Impact to Worker Safety ground (2) Are in runs of less than 7.5 m (25 ft) (3) Are free from probable contact with ground, grounded metal, metal lath, or other conductive material (4) Are guarded against contact by persons Exception No. 2: Short sections of metal enclosures or raceways used to provide support or protection of cable assemblies from physical damage shall not be required to be connected to the equipment grounding conductor. Exception No. 3: A metal elbow shall not be required to be connected to the equipment grounding conductor where it is installed in a nonmetallic raceway and is isolated from possible contact by a minimum cover of 450 mm (18 in.) to any part of the elbow or is encased in not less than 50 mm (2 in.) of concrete. 250.94 Bonding for Other Systems. An intersystem bonding termination for connecting intersystem bonding and grounding conductors required for other systems shall be provided external to enclosures at the service Page 65 of 361 Modified to address the specific requirements for intersystem connections and to eliminate confusion and misapplication of the requirements intended. 70 2008 851 Evaluation 2005 NEC 2008 NEC disconnecting means for any additional buildings or structures by at least one of the following means: equipment and at the disconnecting means for any additional buildings or structures. The intersystem bonding termination shall be accessible for connection and inspection. The intersystem bonding termination shall have the capacity for connection of not less than three intersystem bonding conductors. The intersystem bonding termination device shall not interfere with opening a service or metering equipment enclosure. The intersystem bonding termination shall be one of the following: (1) Exposed nonflexible metallic raceways (2) Exposed grounding electrode conductor (3) Approved means for the external connection of a copper or other corrosion-resistant bonding or grounding conductor to the grounded raceway or equipment (1) A set of terminals securely mounted to the meter enclosure and electrically connected to the meter enclosure. The terminals shall be listed as grounding and bonding equipment. (2) A bonding bar near the service equipment enclosure, meter enclosure, or raceway for service conductors. The bonding bar shall be connected with a minimum 6 AWG copper conductor to an equipment grounding conductor(s) in the service equipment enclosure, meter enclosure, or exposed nonflexible metallic raceway. (3) A bonding bar near the grounding Page 66 of 361 Change Description and Impact to Worker Safety Actually improves worker safety by assuring a continuous ground path. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety electrode conductor. The bonding bar shall be connected to the grounding electrode conductor with a minimum 6 AWG copper conductor. 250.104 Bonding of Piping Systems Exception: In existing buildings or structures where any of the intersystem bonding and grounding conductors required by 770.93, 800.100(B), 810.21(F), 820.100(B), 830.100(B) exist, installation of the intersystem bonding termination is not required. An accessible means external to enclosures for connecting intersystem bonding and grounding electrode conductors shall be permitted at the service equipment and at the disconnecting means for any additional buildings or structures by at least one of the following means: (1) Exposed nonflexible metallic raceways (2) An exposed grounding electrode conductor (3) Approved means for the external connection of a copper or other corrosion-resistant bonding or grounding conductor to the grounded raceway or equipment 250.104 Bonding of Piping Systems Page 67 of 361 Added “based on the rating of the 70 2008 851 Evaluation 2005 NEC 2008 NEC and Exposed Structural Steel. (A) Metal Water Piping. and Exposed Structural Steel. (A) Metal Water Piping. (2) Buildings of Multiple Occupancy. In buildings of multiple occupancy where the metal water piping system(s) installed in or attached to a building or structure for the individual occupancies is metallically isolated from all other occupancies by use of nonmetallic water piping, the metal water piping system(s) for each occupancy shall be permitted to be bonded to the equipment grounding terminal of the panelboard or switchboard enclosure (other than service equipment) supplying that occupancy. The bonding jumper shall be sized in accordance with Table 250.122. VI. Equipment Grounding and Equipment Grounding Conductors (2) Buildings of Multiple Occupancy. In buildings of multiple occupancy where the metal water piping system(s) installed in or attached to a building or structure for the individual occupancies is metallically isolated from all other occupancies by use of nonmetallic water piping, the metal water piping system(s) for each occupancy shall be permitted to be bonded to the equipment grounding terminal of the panelboard or switchboard enclosure (other than service equipment) supplying that occupancy. The bonding jumper shall be sized in accordance with Table 250.122, based on the rating of the overcurrent protective device for the circuit supplying the occupancy. VI. Equipment Grounding and Equipment Grounding Conductors 250.110 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed). Exposed non– current-carrying metal parts of fixed equipment likely to become energized shall be grounded under any of the 250.110 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed). Exposed non– current-carrying metal parts of fixed equipment likely to become energized shall be connected to the equipment Page 68 of 361 Change Description and Impact to Worker Safety overcurrent protective device for the circuit supplying the occupancy” to clarify the intent to use the supply conductor overcurrent protective device rating for sizing the bonding jumper. Actually improves worker safety by assuring a continuous ground path. Replaced “grounded” with “connected to the equipment grounding conductor” in keeping with the overall emphasis on the connection for the grounding conductors and where the connection is to be made. Actually improves worker safety by assuring a continuous ground path. 70 2008 851 Evaluation 2005 NEC 2008 NEC grounding conductor under any of the following conditions: 250.112 Fastened in Place or 250.112 Fastened in Place or Connected by Permanent Wiring Connected by Permanent Wiring Methods (Fixed) — Specific. Exposed, Methods (Fixed) — Specific. Except as non current-carrying metal parts of the permitted in 250.112(I), exposed, non kinds of equipment described in current-carrying metal parts of the 250.112(A) through (K), and non– kinds of equipment described in current-carrying metal parts of 250.112(A) through (K), and non– equipment and enclosures described in current-carrying metal parts of 250.112(L) and (M), shall be grounded equipment and enclosures described in regardless of voltage. 250.112(L) and (M), shall be connected to the equipment grounding conductor regardless of voltage. Change Description and Impact to Worker Safety following conditions: 250.112 Fastened in Place or Connected by Permanent Wiring Methods (Fixed) — Specific. (I) Power-Limited Remote-Control, Signaling, and Fire Alarm Circuits. Equipment supplied by Class 1 power limited circuits and Class 1, Class 2, and Class 3 remote control and signaling circuits, and by fire alarm circuits, shall be grounded where system grounding is required by Part II or Part VIII of this article. 250.112 Fastened in Place or Connected by Permanent Wiring Methods (Fixed) — Specific. (I) Remote-Control, Signaling, and Fire Alarm Circuits. Equipment supplied by Class 1 circuits shall be grounded unless operating at less than 50 volts. Equipment supplied by Class 1 powerlimited circuits, by Class 2 and Class 3 remote-control and signaling circuits, and by fire alarm circuits shall be grounded where system grounding is required by Part II or Part VIII of this article. Page 69 of 361 Replaced “grounded” with “connected to the equipment grounding conductor” in keeping with the overall emphasis on the connection for the grounding conductors and where the connection is to be made. The addition of the exception in 250.112(I) refers to Remote-Control, Signaling, and Fire Alarm Circuits and the less than 50 volts exception to grounding requirements. Actually improves worker safety by assuring a continuous ground path. Inserted the qualifier for Class 1 circuit grounding requirements and to separate the power limited Class 1 circuit requirements from other Class 1 circuits. The 50 volt threshold to align with system voltage levels requiring system grounding. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 250.112 Fastened in Place or Connected by Permanent Wiring Methods (Fixed) — Specific. 250.112 Fastened in Place or Connected by Permanent Wiring Methods (Fixed) — Specific. (K) Skid Mounted Equipment. Permanently mounted electrical equipment and skids shall be grounded with an equipment bonding jumper sized as required by 250.122. (K) Skid-Mounted Equipment. Permanently mounted electrical equipment and skids shall be connected to the equipment grounding conductor sized as required by 250.122. 250.112 Fastened in Place or Connected by Permanent Wiring Methods (Fixed) — Specific. 250.112 Fastened in Place or Connected by Permanent Wiring Methods (Fixed) — Specific. (M) Metal Well Casings. Where a submersible pump is used in a metal well casing, the well casing shall be bonded to the pump circuit equipment grounding conductor. 250.114 Equipment Connected by Cord and Plug. Under any of the conditions described in 250.114(1) through (4), exposed non–currentcarrying metal parts of cord-and plugconnected equipment likely to become energized shall be grounded. 250.116 Non electric Equipment. The metal parts of non electric equipment (M) Metal Well Casings. Where a submersible pump is used in a metal well casing, the well casing shall be connected to the pump circuit equipment grounding conductor. 250.114 Equipment Connected by Cord and Plug. Under any of the conditions described in 250.114(1) through (4), exposed non–currentcarrying metal parts of cord-and plugconnected equipment likely to become energized shall be connected to the equipment grounding conductor. 250.116 Non electrical Equipment. The metal parts of the following non Page 70 of 361 Change Description and Impact to Worker Safety Replaced “grounded” with “connected to the equipment grounding conductor” in keeping with the overall emphasis on the connection for the grounding conductors and where the connection is to be made. Actually improves worker safety by assuring a continuous ground path. Differentiates connected from bonding to continue the emphasis on making the proper connection. As Safe or Safer. Replaced “grounded” with “connected to the equipment grounding conductor” in keeping with the overall emphasis on the connection for the grounding conductors and where the connection is to be made. This phrase was added to each of the exceptions as well. Actually improves worker safety by assuring a continuous ground path. Replaced “grounded” with “connected to the equipment grounding conductor” 70 2008 851 Evaluation 2005 NEC 2008 NEC described in this section shall be grounded. electrical equipment described in this section shall be connected to the equipment grounding conductor: (1) Frames and tracks of electrically operated cranes and hoists (2) Frames of non electrically driven elevator cars to which electric conductors are attached (3) Hand-operated metal shifting ropes or cables of electric elevators 250.119 Identification of Equipment Grounding Conductors. Unless required elsewhere in this Code, equipment grounding conductors shall be permitted to be bare, covered, or insulated. Individually covered or insulated equipment grounding conductors shall have a continuous outer finish that is either green or green with one or more yellow stripes except as permitted in this section. Conductors with insulation or individual covering that is green, green with one or more yellow stripes, or otherwise identified as permitted by this section shall not be used for ungrounded or grounded circuit conductors. (1) Frames and tracks of electrically operated cranes and hoists (2) Frames of non electrically driven elevator cars to which electrical conductors are attached (3) Hand-operated metal shifting ropes or cables of electric elevators 250.119 Identification of Equipment Grounding Conductors. Unless required elsewhere in this Code, equipment grounding conductors shall be permitted to be bare, covered, or insulated. Individually covered or insulated equipment grounding conductors shall have a continuous outer finish that is either green or green with one or more yellow stripes except as permitted in this section. Conductors with insulation or individual covering that is green, green with one or more yellow stripes, or otherwise identified as permitted by this section shall not be used for ungrounded or grounded circuit conductors. Exception: Power-limited, Class 2 or Class 3 circuit cables containing only Page 71 of 361 Change Description and Impact to Worker Safety in keeping with the overall emphasis on the connection for the grounding conductors and where the connection is to be made. Actually improves worker safety by assuring a continuous ground path. Exception added to allow for the use of green insulation within cables for Power Limited Class 2 or Class 3 circuits. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 250.119 Identification of Equipment Grounding Conductors. circuits operating at less than 50 volts shall be permitted to use a conductor with green insulation for other than equipment grounding purposes. 250.119 Identification of Equipment Grounding Conductors. (A) Conductors Larger Than 6 AWG. Equipment grounding conductors larger than 6 AWG shall comply with 250.119(A)(1) and (A)(2). (A) Conductors Larger Than 6 AWG. Equipment grounding conductors larger than 6 AWG shall comply with 250.119(A)(1) and (A)(2). (2) Identification shall encircle the conductor and shall be accomplished by one of the following: a. Stripping the insulation or covering from the entire exposed length b. Coloring the exposed insulation or covering green c. Marking the exposed insulation or covering with green tape or green adhesive labels 250.122 Size of Equipment Grounding Conductors. (2) Identification shall encircle the conductor and shall be accomplished by one of the following: a. Stripping the insulation or covering from the entire exposed length b. Coloring the insulation or covering green at the termination c. Marking the insulation or covering with green tape or green adhesive labels at the termination 250.122 Size of Equipment Grounding Conductors. (A) General. Copper, aluminum, or copper-clad aluminum equipment grounding conductors of the wire type shall not be smaller than shown in Table 250.122 but shall not be required (A) General. Copper, aluminum, or copper-clad aluminum equipment grounding conductors of the wire type shall not be smaller than shown in Table 250.122, but in no case shall Page 72 of 361 Change Description and Impact to Worker Safety Added “at the termination” to specifically identify where the coloring is required. As Safe or Safer. Emphasizes the size limitation to the circuit conductor size and adds cable tray to the equipment grounding conductor allowances. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC to be larger than the circuit conductors supplying the equipment. Where a raceway or a cable armor or sheath is used as the equipment grounding conductor, as provided in 250.118 and 250.134(A), it shall comply with 250.4(A)(5) or (B)(4). they be required to be larger than the circuit conductors supplying the equipment. Where a cable tray, a raceway, or a cable armor or sheath is used as the equipment grounding conductor, as provided in 250.118 and 250.134(A), it shall comply with 250.4(A)(5) or (B)(4). 250.122 Size of Equipment Grounding Conductors. 250.122 Size of Equipment Grounding Conductors. (C) Multiple Circuits. Where a single equipment grounding conductor is run with multiple circuits in the same raceway or cable, it shall be sized for the largest overcurrent device protecting conductors in the raceway or cable. 250.122 Size of Equipment Grounding Conductors. (D) Motor Circuits. Where the overcurrent device consists of an instantaneous trip circuit breaker or a motor short-circuit protector, as allowed in 430.52, the equipment grounding conductor size shall be (C) Multiple Circuits. Where a single equipment grounding conductor is run with multiple circuits in the same raceway, cable, or cable tray, it shall be sized for the largest overcurrent device protecting conductors in the raceway, cable, or cable tray. Equipment grounding conductors installed in cable trays shall meet the minimum requirements of 392.3(B)(1)(c). 250.122 Size of Equipment Grounding Conductors. (D) Motor Circuits. Equipment grounding conductors for motor circuits shall be sized in accordance with (D)(1) or (D)(2). (1) General. The equipment grounding Page 73 of 361 Change Description and Impact to Worker Safety Provides specific requirements for sizing equipment grounding conductor for multiple circuits and adds cable trays as a method for routing multiple circuits. As Safe or Safer. Provides specific requirements for sizing equipment grounding conductors for motor circuits and eliminates the previous confusion levels. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC permitted to be based on the rating of the motor overload protective device but shall not be less than the size shown in Table 250.122. 2008 NEC Change Description and Impact to Worker Safety conductor size shall not be smaller than determined by 250.122(A) based on the rating of the branch-circuit short-circuit and ground fault protective device. (2) Instantaneous-Trip Circuit Breaker and Motor Short-Circuit Protector. Where the overcurrent device is an instantaneous-trip circuit breaker or a motor short-circuit protector, the equipment grounding conductor shall be sized not smaller than that given by 250.122(A) using the maximum permitted rating of a dual element timedelay fuse selected for branch-circuit short-circuit and ground-fault protection in accordance with 430.52(C)(1), Exception No. 1. 250.122 Size of Equipment Grounding 250.122 Size of Equipment Grounding Deleted the portions of this section that Conductors. Conductors. presented qualifiers that were misinterpreted and introduced (F) Conductors in Parallel. Where (F) Conductors in Parallel. Where confusion into equipment grounding conductors are run in parallel in conductors are run in parallel in conductor sizing. It simply points to multiple raceways or cables as multiple raceways or cables as Table 250.122 for all cases. permitted in 310.4, the equipment permitted in 310.4, the equipment grounding conductors, where used, grounding conductors, where used, As Safe or Safer. shall be run in parallel in each raceway shall be run in parallel in each raceway or cable. or cable. One of the methods in 250.122(F)(1) or (F)(2) shall be used to ensure the Page 74 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC equipment grounding conductors are protected. (1) Based on Rating of Overcurrent Protective Device. Each parallel equipment grounding conductor shall be sized on the basis of the ampere rating of the overcurrent device protecting the circuit conductors in the raceway or cable in accordance with Table 250.122. Each parallel equipment grounding conductor shall be sized on the basis of the ampere rating of the overcurrent device protecting the circuit conductors in the raceway or cable in accordance with Table 250.122. (2) Ground-Fault Protection of Equipment Installed. Where groundfault protection of equipment is installed, each parallel equipment grounding conductor in a multiconductor cable shall be permitted to be sized in accordance with Table 250.122 on the basis of the trip rating of the ground-fault protection where the following conditions are met: (1) Conditions of maintenance and supervision ensure that only qualified persons will service the installation. (2) The ground-fault protection equipment is set to trip at not more than the ampacity of a single ungrounded conductor of one of the cables in parallel. Page 75 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC (3) The ground-fault protection is listed for the purpose of protecting the equipment grounding conductor. 250.132 Short Sections of Raceway. Isolated sections of metal raceway or cable armor, where required to be grounded, shall be grounded in accordance with 250.134. 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) — Grounding. Unless grounded by connection to the grounded circuit conductor as permitted by 250.32, 250.140, and 250.142, non-current-carrying metal parts of equipment, raceways, and other enclosures, if grounded, shall be grounded by one of the following methods. 2008 NEC 250.132 Short Sections of Raceway. Isolated sections of metal raceway or cable armor, where required to be grounded, shall be connected to an equipment grounding conductor in accordance with 250.134. 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) — Grounding. 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) — Grounding. Unless grounded by connection to the grounded circuit conductor as permitted by 250.32, 250.140, and 250.142, non-current-carrying metal parts of equipment, raceways, and other enclosures, if grounded, shall be connected to an equipment grounding conductor by one of the methods specified in 250.134(A) or (B). 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) — Grounding. (A) Equipment Grounding Conductor Types. By any of the equipment grounding conductors permitted by (A) Equipment Grounding Conductor Types. By connecting to any of the equipment grounding conductors Page 76 of 361 Change Description and Impact to Worker Safety Replaced “grounded” with “connected to an equipment grounding conductor” in keeping with the overall emphasis on the connection for the grounding conductors and where the connection is to be made. Actually improves worker safety by assuring a continuous ground path. Replaced “grounded” with “connected to an equipment grounding conductor” in keeping with the overall emphasis on the connection for the grounding conductors and where the connection is to be made. Actually improves worker safety by assuring a continuous ground path. Continuing the emphasis on the connection to an equipment grounding conductor versus simply grounding. Actually improves worker safety by assuring a continuous ground path. 70 2008 851 Evaluation 2005 NEC 2008 NEC 250.118. permitted by 250.118. (B) With Circuit Conductors. By an equipment grounding conductor contained within the same raceway, cable, or otherwise run with the circuit conductors. 250.136 Equipment Considered Effectively Grounded. Under the conditions specified in 250.136(A) and (B), the non–current-carrying metal parts of the equipment shall be considered effectively grounded. (B) With Circuit Conductors. By connecting to an equipment grounding conductor contained within the same raceway, cable, or otherwise run with the circuit conductors. 250.136 Equipment Considered Grounded. Under the conditions specified in 250.136(A) and (B), the normally non–current-carrying metal parts of the equipment shall be considered grounded. (A) Equipment Secured to Grounded Metal Supports. Electrical equipment secured to and in electrical contact with a metal rack or structure provided for its support and grounded by one of the means indicated in 250.134. The structural metal frame of a building shall not be used as the required equipment grounding conductor for ac equipment. (A) Equipment Secured to Grounded Metal Supports. Electrical equipment secured to and in electrical contact with a metal rack or structure provided for its support and connected to an equipment grounding conductor by one of the means indicated in 250.134. The structural metal frame of a building shall not be used as the required equipment grounding conductor for ac equipment. (B) Metal Car Frames. Metal car frames supported by metal hoisting cables attached to or running over metal sheaves or drums of elevator machines that are grounded by one of (B) Metal Car Frames. Metal car frames supported by metal hoisting cables attached to or running over metal sheaves or drums of elevator machines that are connected to an Page 77 of 361 Change Description and Impact to Worker Safety Removed the term “effectively” and continues the emphasis on the connection to an equipment grounding conductor versus simply grounding. Actually improves worker safety by assuring a continuous ground path. 70 2008 851 Evaluation 2005 NEC the methods indicated in 250.134. 250.138 Cord-and-Plug-Connected Equipment. Non–current-carrying metal parts of cord-and-plugconnected equipment, if grounded, shall be grounded by one of the methods in 250.138(A) or (B). (B) By Means of a Separate Flexible Wire or Strap. By means of a separate flexible wire or strap, insulated or bare, protected as well as practicable against physical damage, where part of equipment. 2008 NEC equipment grounding conductor by one of the methods indicated in 250.134. 250.138 Cord-and-Plug-Connected Equipment. Non–current-carrying metal parts of cord-and-plugconnected equipment, if grounded, shall be connected to an equipment grounding conductor by one of the methods in 250.138(A) or (B). 250.144 Multiple Circuit Connections. Where equipment is required to be grounded and is supplied by separate connection to more than one circuit or grounded premises wiring system, a means for grounding shall be provided for each such connection as specified in 250.134 and 250.138. (B) By Means of a Separate Flexible Wire or Strap. By means of a separate flexible wire or strap, insulated or bare, connected to an equipment grounding conductor, and protected as well as practicable against physical damage, where part of equipment. 250.144 Multiple Circuit Connections. Where equipment is grounded and is supplied by separate connection to more than one circuit or grounded premises wiring system, an equipment grounding conductor termination shall be provided for each such connection as specified in 250.134 and 250.138. 250.146 Connecting Receptacle Grounding Terminal to Box. An equipment bonding jumper shall be used to connect the grounding terminal of a grounding-type receptacle to a 250.146 Connecting Receptacle Grounding Terminal to Box. An equipment bonding jumper shall be used to connect the grounding terminal of a grounding-type receptacle to a Page 78 of 361 Change Description and Impact to Worker Safety Continuing the emphasis on the connection to an equipment grounding conductor versus simply grounding. Actually improves worker safety by assuring a continuous ground path. Replaced “a means for grounding“ with “an equipment grounding conductor termination” to continue the emphasis of connections to the equipment grounding conductor versus just “grounding.” Actually improves worker safety by assuring a continuous ground path. Added the sizing requirements for the equipment bonding jumper. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC grounded box unless grounded as in 250.146(A) through (D). 250.146 Connecting Receptacle Grounding Terminal to Box. (A) Surface Mounted Box. Where the box is mounted on the surface, direct metal-to-metal contact between the device yoke and the box or a contact yoke or device that complies with 250.146(B) shall be permitted to ground the receptacle to the box. At least one of the insulating washers shall be removed from receptacles that do not have a contact yoke or device that complies with 250.146(B) to ensure direct metal-to-metal contact. This provision shall not apply to covermounted receptacles unless the box and cover combination are listed as providing satisfactory ground continuity between the box and the receptacle. 2008 NEC grounded box unless grounded as in 250.146(A) through (D). The equipment bonding jumper shall be sized in accordance with Table 250.122 based on the rating of the overcurrent device protecting the circuit conductors. 250.146 Connecting Receptacle Grounding Terminal to Box. (A) Surface-Mounted Box. Where the box is mounted on the surface, direct metal-to-metal contact between the device yoke and the box or a contact yoke or device that complies with 250.146(B) shall be permitted to ground the receptacle to the box. At least one of the insulating washers shall be removed from receptacles that do not have a contact yoke or device that complies with 250.146(B) to ensure direct metal-to-metal contact. This provision shall not apply to covermounted receptacles unless the box and cover combination are listed as providing satisfactory ground continuity between the box and the receptacle. A listed exposed work cover shall be permitted to be the grounding and bonding means when (1) the device is attached to the cover with at least two Page 79 of 361 Change Description and Impact to Worker Safety Added the use of listed covers as the grounding and bonding means. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 250.146 Connecting Receptacle Grounding Terminal to Box. 2008 NEC fasteners that are permanent (such as a rivet) or have a thread locking or screw locking means and (2) when the cover mounting holes are located on a flat non-raised portion of the cover. 250.146 Connecting Receptacle Grounding Terminal to Box. Change Description and Impact to Worker Safety Continuing the emphasis on the connection to an equipment grounding conductor versus simply grounding. (D) Isolated Receptacles. Where (D) Isolated Receptacles. Where For isolated receptacles, the required for the reduction of electrical installed for the reduction of electrical installation of the equipment grounding noise (electromagnetic interference) on noise (electromagnetic interference) on conductor meeting the requirements of the grounding circuit, a receptacle in the grounding circuit, a receptacle in this section will be allowed to pass which the grounding terminal is which the grounding terminal is through unconnected. purposely insulated from the purposely insulated from the receptacle mounting means shall be receptacle mounting means shall be Actually improves worker safety by permitted. The receptacle grounding permitted. The receptacle grounding assuring a continuous ground path. terminal shall be grounded by an terminal shall be connected to an insulated equipment grounding insulated equipment grounding conductor run with the circuit conductor run with the circuit conductors. This grounding conductor conductors. This equipment grounding shall be permitted to pass through one conductor shall be permitted to pass or more panelboards without through one or more panelboards connection to the panelboard without a connection to the panelboard grounding terminal as permitted in grounding terminal bar as permitted in 408.40, Exception, so as to terminate 408.40, Exception, so as to terminate within the same building or structure within the same building or structure directly at an equipment grounding directly at an equipment grounding conductor terminal of the applicable conductor terminal of the applicable derived system or service. derived system or service. Where installed in accordance with the provisions of this section, this Page 80 of 361 70 2008 851 Evaluation 2005 NEC 250.148 Continuity and Attachment of Equipment Grounding Conductors to Boxes. Where circuit conductors are spliced within a box, or terminated on equipment within or supported by a box, any equipment grounding conductor(s) associated with those circuit conductors shall be spliced or joined within the box or to the box with devices suitable for the use in accordance with 250.148(A) through (E). 250.148 Continuity and Attachment of Equipment Grounding Conductors to Boxes. (C) Metal Boxes. A connection shall be made between the one or more equipment grounding conductors and a metal box by means of a grounding screw that shall be used for no other purpose or a listed grounding device. 250.166 Size of Direct-Current Grounding Electrode Conductor. The 2008 NEC equipment grounding conductor shall also be permitted to pass through boxes, wireways, or other enclosures without being connected to such enclosures. 250.148 Continuity and Attachment of Equipment Grounding Conductors to Boxes. Where circuit conductors are spliced within a box, or terminated on equipment within or supported by a box, any equipment grounding conductor(s) associated with those circuit conductors shall be connected within the box or to the box with devices suitable for the use in accordance with 250.148(A) through (E). 250.148 Continuity and Attachment of Equipment Grounding Conductors to Boxes. Change Description and Impact to Worker Safety Emphasis on connection. Actually improves worker safety by assuring a continuous ground path. Added “equipment listed for grounding” to the approved methods to allow for the listing of new equipment. (C) Metal Boxes. A connection shall be As Safe or Safer. made between the one or more equipment grounding conductors and a metal box by means of a grounding screw that shall be used for no other purpose, equipment listed for grounding, or a listed grounding device. 250.166 Size of the Direct-Current Separates the requirements from the Grounding Electrode Conductor. The permitted variations. Page 81 of 361 70 2008 851 Evaluation 2005 NEC size of the grounding electrode conductor for a dc system shall be as specified in 250.166(A) through (E). 2008 NEC IX. Instruments, Meters, and Relays size of the grounding electrode conductor for a dc system shall be as specified in 250.166(A) and (B), except as permitted by 250.166(C) through (E). 250.168 Direct-Current System Bonding Jumper. For direct-current systems that are to be grounded, an unspliced bonding jumper shall be used to connect the equipment grounding conductor(s) to the grounded conductor at the source or the first system disconnecting means where the system is grounded. The size of the bonding jumper shall not be smaller than the system grounding electrode conductor specified in 250.166 and shall comply with the provisions of 250.28(A), (B), and (C). IX. Instruments, Meters, and Relays 250.170 Instrument Transformer Circuits. Secondary circuits of current and potential instrument transformers shall be grounded where the primary windings are connected to circuits of 300 volts or more to ground and, where on switchboards, shall be grounded irrespective of voltage. 250.170 Instrument Transformer Circuits. Secondary circuits of current and potential instrument transformers shall be grounded where the primary windings are connected to circuits of 300 volts or more to ground and, where on switchboards, shall be grounded irrespective of voltage. Exception: Circuits where the primary Exception No. 1: Circuits where the 250.168 Direct-Current Bonding Jumper. For dc systems, the size of the bonding jumper shall not be smaller than the system grounding electrode conductor specified in 250.166. Page 82 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Specifically targets the requirements for the system bonding conductor to eliminate confusion as to just what or where the connection is to be made. Actually improves worker safety by assuring a continuous ground path. Added exception for the three phase systems connected in delta where there would be no need for grounding. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC windings are connected to circuits of less than 1000 volts with no live parts or wiring exposed or accessible to other than qualified persons. 250.172 Instrument Transformer Cases. Cases or frames of instrument transformers shall be grounded where accessible to other than qualified persons. 250.174 Cases of Instruments, Meters, and Relays Operating at Less Than 1000 Volts. Instruments, meters, and relays operating with windings or working parts at less than 1000 volts shall be grounded as specified in 250.174(A), (B), or (C). (A) Not on Switchboards. Instruments, meters, and relays not located on switchboards, operating with windings 2008 NEC Change Description and Impact to Worker Safety primary windings are connected to circuits of less than 1000 volts with no live parts or wiring exposed or accessible to other than qualified persons. Exception No. 2: Current transformer secondaries connected in a threephase delta configuration shall not be required to be grounded. 250.172 Instrument Transformer Cases. Cases or frames of instrument transformers shall be connected to the equipment grounding conductor where accessible to other than qualified persons. 250.174 Cases of Instruments, Meters, and Relays Operating at Less Than 1000 Volts. Instruments, meters, and relays operating with windings or working parts at less than 1000 volts shall be connected to the equipment grounding conductor as specified in 250.174(A), (B), or (C). (A) Not on Switchboards. Instruments, meters, and relays not located on switchboards, operating with windings Page 83 of 361 Replaced “grounded“ with “connected to the equipment grounding conductor” to continue the emphasis of connections to the equipment grounding conductor versus just “grounding.” Actually improves worker safety by assuring a continuous ground path. Replaced “grounded“ with “connected to the equipment grounding conductor” to continue the emphasis of connections to the equipment grounding conductor versus just “grounding.” Actually improves worker safety by assuring a continuous ground path. 70 2008 851 Evaluation 2005 NEC 2008 NEC or working parts at 300 volts or more to ground, and accessible to other than qualified persons, shall have the cases and other exposed metal parts grounded. or working parts at 300 volts or more to ground, and accessible to other than qualified persons, shall have the cases and other exposed metal parts connected to the equipment grounding conductor. (B) On Dead-Front Switchboards. Instruments, meters, and relays (whether operated from current and potential transformers or connected directly in the circuit) on switchboards having no live parts on the front of the panels shall have the cases grounded. (B) On Dead-Front Switchboards. Instruments, meters, and relays (whether operated from current and potential transformers or connected directly in the circuit) on switchboards having no live parts on the front of the panels shall have the cases connected to the equipment grounding conductor. (C) On Live-Front Switchboards. Instruments, meters, and relays (whether operated from current and potential transformers or connected directly in the circuit) on switchboards having exposed live parts on the front of panels shall not have their cases grounded. Mats of insulating rubber or other suitable floor insulation shall be provided for the operator where the voltage to ground exceeds 150. (C) On Live-Front Switchboards. Instruments, meters, and relays (whether operated from current and potential transformers or connected directly in the circuit) on switchboards having exposed live parts on the front of panels shall not have their cases connected to the equipment grounding conductor. Mats of insulating rubber or other suitable floor insulation shall be provided for the operator where the voltage to ground exceeds 150. 250.176 Cases of Instruments, Meters, and Relays — Operating Voltage 1 kV and Over. Where instruments, meters, 250.176 Cases of Instruments, Meters, and Relays — Operating Voltage 1 kV and Over. Where instruments, meters, Page 84 of 361 Change Description and Impact to Worker Safety Replaced “grounded“ with “connected to the equipment grounding conductor”. 70 2008 851 Evaluation 2005 NEC 2008 NEC and relays have current-carrying parts of 1 kV and over to ground, they shall be isolated by elevation or protected by suitable barriers, grounded metal, or insulating covers or guards. Their cases shall not be grounded. and relays have current-carrying parts of 1 kV and over to ground, they shall be isolated by elevation or protected by suitable barriers, grounded metal, or insulating covers or guards. Their cases shall not be connected to the equipment grounding conductor. 250.184 Solidly Grounded Neutral 250.184 Solidly Grounded Neutral Systems. Solidly grounded neutral Systems. Solidly grounded neutral systems shall be permitted to be either systems shall be permitted to be either single point grounded or multigrounded single point grounded or multigrounded neutral. neutral. (A) Neutral Conductor. (A) Neutral Conductor. (1) Insulation Level. The minimum insulation level for neutral conductors of solidly grounded systems shall be 600 volts. (1) Insulation Level. The minimum insulation level for neutral conductors of solidly grounded systems shall be 600 volts. Exception No. 1: Bare copper conductors shall be permitted to be used for the neutral of service entrances and the neutral of directburied portions of feeders. Exception No. 1: Bare copper conductors shall be permitted to be used for the neutral conductor of the following: (1) Service-entrance conductors (2) Service laterals (3) Direct-buried portions of feeders. Exception No. 2: Bare conductors shall be permitted for the neutral conductor of overhead portions installed outdoors. Exception No. 2: Bare conductors shall be permitted for the neutral of overhead portions installed outdoors. Page 85 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Emphasizes neutral conductor and provides specific requirements for use of bare copper conductors. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Exception No. 3: The neutral grounded conductor shall be permitted to be a bare conductor if isolated from phase conductors and protected from physical damage. 250.184 Solidly Grounded Neutral Systems. Exception No. 3: The grounded neutral conductor shall be permitted to be a bare conductor if isolated from phase conductors and protected from physical damage. 250.184 Solidly Grounded Neutral Systems. (B) Single Point Grounded System. Where a single point grounded neutral system is used, the following shall apply: (B) Single-Point Grounded Neutral System. Where a single-point grounded neutral system is used, the following shall apply: (1) A single point grounded system shall be permitted to be supplied from (a) or (b): a. A separately derived system b. A multigrounded neutral system with an equipment grounding conductor connected to the multigrounded neutral at the source of the single point grounded system (1) A single-point grounded neutral system shall be permitted to be supplied from (a) or (b): a. A separately derived system b. A multigrounded neutral system with an equipment grounding conductor connected to the multigrounded neutral conductor at the source of the single-point grounded neutral system (2) A grounding electrode shall be provided for the system. (2) A grounding electrode shall be provided for the system. (3) A grounding electrode conductor shall connect the grounding electrode to the system neutral. (3) A grounding electrode conductor shall connect the grounding electrode to the system neutral conductor. Page 86 of 361 Change Description and Impact to Worker Safety Inserted “conductor” and “neutral” to emphasize that it is the conductor connection required for the system. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC (4) A bonding jumper shall connect the equipment grounding conductor to the grounding electrode conductor. (4) A bonding jumper shall connect the equipment grounding conductor to the grounding electrode conductor. (5) An equipment bonding conductor shall be provided to each building, structure, and equipment enclosure. (5) An equipment grounding conductor shall be provided to each building, structure, and equipment enclosure. (6) A neutral shall only be required where phase to neutral loads are supplied. (6) A neutral conductor shall only be required where phase-to-neutral loads are supplied. (7) The neutral, where provided, shall be insulated and isolated from earth except at one location. (7) The neutral conductor, where provided, shall be insulated and isolated from earth except at one location. (8) An equipment grounding conductor shall be run with the phase conductors and shall comply with (a), (b), and (c): a. Shall not carry continuous load b. May be bare or insulated c. Shall have sufficient ampacity for fault current duty 250.186 Impedance Grounded Neutral Systems. (8) An equipment grounding conductor shall be run with the phase conductors and shall comply with (a), (b), and (c): a. Shall not carry continuous load b. May be bare or insulated c. Shall have sufficient ampacity for fault current duty 250.186 Impedance Grounded Neutral Systems. (C) System Neutral Connection. The system neutral shall not be connected to ground, except through the neutral (C) System Neutral Conductor Connection. The system neutral conductor shall not be connected to Page 87 of 361 Change Description and Impact to Worker Safety Inserted “conductor” to emphasize that it is the conductor connection required for the system. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC grounding impedance. 250.188 Grounding of Systems Supplying Portable or Mobile Equipment. Systems supplying portable or mobile high-voltage equipment, other than substations installed on a temporary basis, shall comply with 250.188(A) through (F). (A) Portable or Mobile Equipment. Portable or mobile high-voltage equipment shall be supplied from a system having its neutral grounded through an impedance. Where a deltaconnected high-voltage system is used to supply portable or mobile equipment, a system neutral shall be derived. I. General 280.1 Scope. This article covers general requirements, installation requirements, and connection requirements for surge arresters installed on premises wiring systems. 280.2 Definition. Surge Arrester. A protective device for 2008 NEC ground, except through the neutral grounding impedance. 250.188 Grounding of Systems Supplying Portable or Mobile Equipment. Systems supplying portable or mobile high-voltage equipment, other than substations installed on a temporary basis, shall comply with 250.188(A) through (F). (A) Portable or Mobile Equipment. Portable or mobile high-voltage equipment shall be supplied from a system having its neutral conductor grounded through an impedance. Where a delta-connected high-voltage system is used to supply portable or mobile equipment, a system neutral point and associated neutral conductor shall be derived. Article 280 I. General 280.1 Scope. This article covers general requirements, installation requirements, and connection requirements for surge arresters installed on premises wiring systems over 1 kV. Page 88 of 361 Change Description and Impact to Worker Safety Inserted “conductor” and “point and associated neutral conductor” to emphasize that it is the conductor connection required for the system. As Safe or Safer. Redefinition of scope of the article to only apply to systems over 1kV. Actually provides increased worker safety by requiring application of surge protectors where they will not catastrophically fail endangering workers. Definition moved to Article 100. 70 2008 851 Evaluation 2005 NEC 2008 NEC limiting surge voltages by discharging or bypassing surge current, and it also prevents continued flow of follow current while remaining capable of repeating these functions. 280.2 Uses Not Permitted. A surge arrester shall not be installed where the rating of the surge arrester is less than the maximum continuous phaseto-ground power frequency voltage available at the point of application. 280.4 Surge Arrester Selection. (A) Circuits of Less Than 1000 Volts. Surge arresters installed on a circuit of less than 1000 volts shall comply with all of the following: 280.4 Surge Arrester Selection. The surge arresters shall comply with 280.4(A) and (B). (1) The rating of the surge arrester shall be equal to or greater than the maximum continuous phase-toground power frequency voltage available at the point of application. (2) Surge arresters installed on circuits of less than 1000 volts shall be listed. (3) Surge arresters shall be marked with a short circuit current rating and shall not be installed at a point on the system where the available fault current is in excess of that rating. (A) Rating. The rating of a surge arrester shall be equal to or greater than the maximum continuous operating voltage available at the point of application. (1) Solidly Grounded Systems. The maximum continuous operating voltage shall be the phase-toground voltage of the system. (2) Impedance or Ungrounded System. The maximum continuous operating voltage shall be the phase-to-phase voltage of the system. Page 89 of 361 Change Description and Impact to Worker Safety Uses not permitted added to specifically address the limitations of surge arrester installations. Actually provides increased worker safety by requiring application of surge protectors where they will not catastrophically fail endangering workers. Changes necessitated by the redefinition of the scope of the article. Actually provides increased worker safety by requiring application of surge protectors where they will not catastrophically fail endangering workers. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety (4) Surge arresters shall not be installed on ungrounded systems, impedance grounded systems, or corner grounded delta systems unless listed specifically for use on these systems. (B) Circuits of 1 kV and Over— Silicon Carbide Types. The rating of a silicon carbide-type surge arrester shall be not less than 125 percent of the maximum continuous phase-to-ground voltage available at the point of application. (B) Silicon Carbide Types. The rating of a silicon carbide-type surge arrester shall be not less than 125 percent of the rating specified in 280.4(A). 280.5 Listing. A surge arrester shall be a listed device. 280.12 Routing of Surge Arrester Connections. The conductor used to connect the surge arrester to line or bus and to ground shall not be any longer than necessary and shall avoid unnecessary bends. 280.21 Installed at Services of Less Than 1000 Volts. Line and ground connecting 280.12 Routing of Surge Arrester Grounding Conductors. The conductor used to connect the surge arrester to line, bus, or equipment and to a grounding conductor connection point as provided in 280.21 shall not be any longer than necessary and shall avoid unnecessary bends. 280.21 Connection. New section developed as an outfall of rewording 280.4. Actually provides increased worker safety. Modified to specifically state the requirements for connection of the surge arrester to a specific grounding conductor point versus just “ground.” Actually provides increased worker safety. Reworded based on the redefinition of Article 280 to only over 1kV systems. As Safe or Safer. Page 90 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety conductors shall not be smaller than 14 AWG copper or 12 AWG aluminum. The arrester grounding conductor shall be connected to one of the following: (1) Grounded service conductor (2) Grounding electrode conductor (3) Grounding electrode for the service (4) Equipment grounding terminal in the service equipment 280.22 Installed on the Load Side Services of Less Than 1000 Volts. Line and ground connecting conductors shall not be smaller than 14 AWG copper or 12 AWG aluminum. A surge arrester shall be permitted to be connected between any two conductors — ungrounded conductor(s), grounded conductor, grounding conductor. The grounded conductor and the grounding conductor shall be interconnected only by the normal operation of the surge arrester during a surge. 280.23 Circuits of 1 kV and Over — Surge-Arrester Conductors. The conductor between the surge arrester and the line and the surge arrester and the grounding connection shall not be smaller than 6 AWG copper or aluminum. The arrester grounding conductor shall be connected to one of the following: (1) Grounded service conductor (2) Grounding electrode conductor (3) Grounding electrode for the service (4) Equipment grounding terminal in the service equipment Deleted based on the redefinition of Article 280 to only over 1kV systems. As Safe or Safer. 280.23 Surge-Arrester Conductors. The conductor between the surge arrester and the line and the surge arrester and the grounding connection shall not be smaller than 6 AWG copper or aluminum. Page 91 of 361 Reworded based on the redefinition of Article 280 to only over 1kV systems. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 280.24 Circuits of 1 kV and Over — Interconnections. The grounding conductor of a surge arrester protecting a transformer that supplies a secondary distribution system shall be interconnected as specified in 280.24(A), (B), or (C). 280.24 Circuits of 1 kV and Over — Interconnections. 280.24 Interconnections. The grounding conductor of a surge arrester protecting a transformer that supplies a secondary distribution system shall be interconnected as specified in 280.24(A), (B), or (C). (A) Metallic Interconnections. A metallic interconnection shall be made to the secondary grounded circuit conductor or the secondary circuit grounding conductor provided that, in addition to the direct grounding connection at the surge arrester, the following occurs: (A) Metallic Interconnections. (1) The grounded conductor of the secondary has elsewhere a grounding connection to a continuous metal underground water piping system. However, in urban water-pipe areas where there are at least four water-pipe connections on the neutral and not fewer than four such connections in each mile of neutral, the metallic interconnection shall be permitted to be made to the secondary 280.24 Interconnections. Change Description and Impact to Worker Safety Reworded based on the redefinition of Article 280 to only over 1kV systems. As Safe or Safer. Modified to specifically address the neutral conductor and that the connection needs to comply with the requirements set forth in the article. (1) Additional Grounding As Safe or Safer. Connection. The grounded conductor of the secondary has elsewhere a grounding connection to a continuous metal underground water piping system. In urban waterpipe areas where there are at least four water-pipe connections on the neutral conductor and not fewer than four such connections in each mile of neutral conductor, the metallic interconnection shall be permitted to be made to the secondary neutral conductor with omission of the direct grounding connection at the surge arrester. (2) Multigrounded Neutral System Connection. The grounded Page 92 of 361 70 2008 851 Evaluation 2005 NEC neutral with omission of the direct grounding connection at the surge arrester. (2) The grounded conductor of the secondary system is a part of a multiground neutral system or static wire of which the primary neutral or static wire has at least four ground connections in each mile of line in addition to a ground at each service. 280.25 Grounding. Except as indicated in this article, surge arrester grounding connections shall be made as specified in Article 250. Grounding conductors shall not be run in metal enclosures unless bonded to both ends of such enclosure. 2008 NEC Change Description and Impact to Worker Safety conductor of the secondary system is a part of a multigrounded neutral system or static wire of which the primary neutral conductor or static wire has at least four grounding connections in each mile of line in addition to a grounding connection at each service. I. General 280.25 Grounding Conductor Connections and Enclosures. Except as indicated in this article, surgearrester grounding conductor connections shall be made as specified in Article 250, Parts III and X. Grounding conductors installed in metal enclosures shall comply with 250.64(E). Article 285 I. General 285.1 Scope. This article covers general requirements, installation requirements, and connection requirements for transient voltage surge suppressors (TVSSs) permanently installed on premises wiring systems. 285.1 Scope. This article covers general requirements, installation requirements, and connection As Safe or Safer. requirements for SPDs [surge arresters and transient voltage surge suppressors (TVSSs)] permanently installed on premises wiring systems 1 Page 93 of 361 Modified to address the importance of the conductor connection and to point to the specific requirements in Article 250 instead of the article in general. This is partially due to the effort to have all references to other articles comply with the NFPA Style Manual. As Safe or Safer. Reworded based on the redefinition of Article 285 to only less than 1kV systems. 70 2008 851 Evaluation 2005 NEC 285.2 Definition. Transient Voltage Surge Suppressor (TVSS). A protective device for limiting transient voltages by diverting or limiting surge current; it also prevents continued flow of follow current while remaining capable of repeating these functions. 285.3 Uses Not Permitted. A TVSS device shall not be installed in the following: (1) Circuits exceeding 600 volts (2) On ungrounded systems, impedance grounded systems, or corner grounded delta systems unless listed specifically for use on these systems. (3) Where the rating of the TVSS is less than the maximum continuous phase-to-ground power frequency voltage available at the point of application 285.4 Number Required. Where used at a point on a circuit, the TVSS shall be connected to each ungrounded conductor. 2008 NEC kV or less. Change Description and Impact to Worker Safety Definition incorporated into Article 100 Surge Protective Device (SPD). As Safe or Safer. 285.3 Uses Not Permitted. An SPD (surge arrester or TVSS) device shall not be installed in the following: (1) Circuits exceeding 1 kV (2) On ungrounded systems, impedance grounded systems, or corner grounded delta systems unless listed specifically for use on these systems. (3) Where the rating of the SPD (surge arrester or TVSS) is less than the maximum continuous phase-to-ground power frequency voltage available at the point of application 285.4 Number Required. Where used at a point on a circuit, the SPD (surge arrester or TVSS) shall be connected to each ungrounded conductor. Reworded based on the redefinition of Article 285 to only less than 1kV systems. As Safe or Safer. Reworded based on the redefinition of Article 285 to only less than 1kV systems. As Safe or Safer. 285.5 Listing. A TVSS shall be a listed device. 285.5 Listing. An SPD (surge arrester or TVSS) shall be a listed device. Page 94 of 361 Reworded based on the redefinition of Article 285 to only less than 1kV systems. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety As Safe or Safer. 285.6 Short Circuit Current Rating. The TVSS shall be marked with a short circuit current rating and shall not be installed at a point on the system where the available fault current is in excess of that rating. This marking requirement shall not apply to receptacles. II. Installation 285.6 Short-Circuit Current Rating. The SPD (surge arrester or TVSS) shall be marked with a short-circuit current rating and shall not be installed at a point on the system where the available fault current is in excess of that rating. This marking requirement shall not apply to receptacles. II. Installation 285.11 Location. TVSSs shall be permitted to be located indoors or outdoors and shall be made inaccessible to unqualified persons, unless listed for installation in accessible locations. 285.12 Routing of Connections. The conductors used to connect the TVSS to the line or bus and to ground shall not be any longer than necessary and shall avoid unnecessary bends. 285.11 Location. SPDs (surge arresters or TVSSs) shall be permitted to be located indoors or outdoors and shall be made inaccessible to unqualified persons, unless listed for installation in accessible locations. 285.12 Routing of Connections. The conductors used to connect the SPD (surge arrester or TVSS) to the line or bus and to ground shall not be any longer than necessary and shall avoid unnecessary bends. III. Connecting SPDs. III. Connecting Transient Voltage Surge Suppressors 285.21 Connection. Where a TVSS is installed, it shall comply with 285.21(A) through (C). 285.21 Connection. Where an SPD (surge arrester or TVSS) device is installed, it shall comply with 285.23 Page 95 of 361 Reworded based on the redefinition of Article 285 to only less than 1kV systems. As Safe or Safer. Reworded based on the redefinition of Article 285 to only less than 1kV systems. As Safe or Safer. Reworded based on the redefinition of Article 285 to only less than 1kV systems. As Safe or Safer. Total rewrite based on the redefinition of Article 285 to only less than 1kV systems and to include SPD’s. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC through 285.28. 285.23 Type 1 SPDs (Surge Arresters). Type 1 SPDs shall be installed in accordance with 285.23(A) and (B). (A) Installation. Type 1 SPDs (surge arresters) shall be installed as follows: (1) Type 1 SPDs (surge arresters) shall be permitted to be connected to the supply side of the service disconnect as permitted in 230.82(4) or (2) Type 1 SPDs (surge arresters) shall be permitted to be connected as specified in 285.24. (B) At the Service. When installed at services, the grounding conductor of a Type 1 SPD shall be connected to one of the following: (1) Grounded service conductor (2) Grounding electrode conductor (3) Grounding electrode for the service (4) Equipment grounding terminal in the service equipment 285.24 Type 2 SPDs (TVSSs). Type 2 SPDs (TVSSs) shall be installed in Page 96 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC accordance with 285.24(A) through (C). (A) Location. (1) Service Supplied Building or Structure. The transient voltage surge suppressor shall be connected on the load side of a service disconnect overcurrent device required in 230.91, unless installed in accordance with 230.82(8). (A) Service-Supplied Building or Structure. Type 2 SPDs (TVSSs) shall be connected anywhere on the load side of a service disconnect overcurrent device required in 230.91, unless installed in accordance with 230.82(8). (2) Feeder Supplied Building or Structure. The transient voltage surge suppressor shall be connected on the load side of the first overcurrent device at the building or structure. (B) Feeder-Supplied Building or Structure. Type 2 SPDs (TVSSs) shall be connected at the building or structure anywhere on the load side of the first overcurrent device at the building or structure. Exception to (1) and (2): Where the TVSS is also listed as a surge arrester, the connection shall be as permitted by Article 280. (3) Separately Derived System. The TVSS shall be connected on the load side of the first overcurrent device in a separately derived system. (C) Separately Derived System. The SPD (TVSS) shall be connected on the load side of the first overcurrent device in a separately derived system. 285.25 Type 3 SPDs. Type 3 SPDs Page 97 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC (TVSSs) shall be permitted to be installed anywhere on the load side of branch circuit overcurrent protection up to the equipment served, provided the connection is a minimum 10 m (30 ft) of conductor distance from the service or separately derived system disconnect. (B) Conductor Size. Line and ground connecting conductors shall not be smaller than 14 AWG copper or 12 AWG aluminum. 285.26 Conductor Size. Line and grounding conductors shall not be smaller than 14 AWG copper or 12 AWG aluminum. (C) Connection Between Conductors. A TVSS shall be permitted to be connected between any two conductors — ungrounded conductor(s), grounded conductor, grounding conductor. The grounded conductor and the grounding conductor shall be interconnected only by the normal operation of the TVSS during a surge. 285.27 Connection Between Conductors. An SPD (surge arrester or TVSS) shall be permitted to be connected between any two conductors — ungrounded conductor(s), grounded conductor, grounding conductor. The grounded conductor and the grounding conductor shall be interconnected only by the normal operation of the SPD (surge arrester or TVSS) during a surge. 285.28 Grounding Conductor Connections and Enclosures. Except as indicated in this article, SPD grounding connections shall be made as specified in Article 250, Part III. Page 98 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 300.4 Protection Against Physical Damage. Where subject to physical damage, conductors shall be protected. 2008 NEC Grounding conductors installed in metal enclosures shall comply with 250.64(E). Article 300 300.4 Protection Against Physical Damage. Where subject to physical damage, conductors shall be protected. (E) Cables and Raceways Installed Under Roof Decking. A cable- or raceway-type wiring method, installed in exposed or concealed locations under metal-corrugated sheet roof decking, shall be installed and supported so the nearest outside surface of the cable or raceway is not less than 38 mm (11⁄2 in.) from the nearest surface of the roof decking. Exception: Rigid metal conduit and intermediate metal conduit shall not be required to comply with 300.4(E). (G) Insulated Fittings. Where raceways contain 4 AWG or larger insulated circuit conductors and these conductors enter a cabinet, box, enclosure, or raceway, the conductors shall be protected by a substantial fitting providing a smoothly rounded Page 99 of 361 Change Description and Impact to Worker Safety Added new section E to address a growing problem with roof decking replacement or installation where the roof decking screws penetrate electrical metallic tubing and some conduits or cables installed in the rafter cavity. Some of these screws are over 6 inches long and require significant torque to install. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC (F) Insulated Fittings. Where raceways containing ungrounded conductors 4 AWG or larger enter a cabinet, box enclosure, or raceway, the conductors shall be protected by a substantial fitting providing a smoothly rounded insulating surface, unless the conductors are separated from the fitting or raceway by substantial insulating material that is securely fastened in place. 300.5 Underground Installations. (B) Listing. Cables and insulated conductors installed in enclosures or raceways in underground installations shall be listed for use in wet locations. 2008 NEC insulating surface, unless the conductors are separated from the fitting or raceway by substantial insulating material that is securely fastened in place. Change Description and Impact to Worker Safety Modified to clarify that it is the circuit conductors that determine the need for the substantial fitting, not just ungrounded conductors. As Safe or Safer. 300.5 Underground Installations. 300.5 Underground Installations. (B) Wet Locations. The interior of enclosures or raceways installed underground shall be considered to be a wet location. Insulated conductors and cables installed in these enclosures or raceways in underground installations shall be listed for use in wet locations and shall comply with 310.8(C). Any connections or splices in an underground installation shall be approved for wet locations. 300.5 Underground Installations. (D) Protection from Damage. Directburied conductors and cables shall be protected from damage in accordance (D) Protection from Damage. Directburied conductors and cables shall be protected from damage in accordance Page 100 of 361 Finally, the declaration that the interior of underground conduits are indeed a wet location. It is well known that these areas are wet, but now the declaration helps reinforce the need for everything to be listed for wet locations. As Safe or Safer. Clarified the intent of the original requirement. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety with 300.5(D)(1) through (D)(4). with 300.5(D)(1) through (D)(4). (1) Emerging from Grade. Direct-buried conductors and enclosures emerging from grade shall be protected by enclosures or raceways extending from the minimum cover distance below grade required by 300.5(A) to a point at least 2.5 m (8 ft) above finished grade. In no case shall the protection be required to exceed 450 mm (18 in.) below finished grade. (1) Emerging from Grade. Direct-buried conductors and cables emerging from grade and specified in columns 1 and 4 of Table 300.5 shall be protected by enclosures or raceways extending from the minimum cover distance below grade required by 300.5(A) to a point at least 2.5 m (8 ft) above finished grade. In no case shall the protection be required to exceed 450 mm (18 in.) below finished grade. 300.6 Protection Against Corrosion Changed “non-ferrous” to “aluminum” and Deterioration. to specifically address the attack on aluminum by concrete materials and (B) Aluminum Metal Equipment. other underground chemicals versus Aluminum raceways, cable trays, the less catastrophic on other metals cablebus, auxiliary gutters, cable not containing iron. armor, boxes, cable sheathing, cabinets, elbows, couplings, nipples, As Safe or Safer. fittings, supports, and support hardware embedded or encased in concrete or in direct contact with the earth shall be provided with supplementary corrosion protection. 300.9 Raceways in Wet Locations Finally, the declaration that the interior Above Grade. Where raceways are of conduits in wet locations are indeed installed in wet locations above grade, themselves a wet location. It is well the interior of these raceways shall be known that these areas are wet, but considered to be a wet location. now the declaration in this new section 300.6 Protection Against Corrosion and Deterioration. (B) Non-Ferrous Metal Equipment. Non-ferrous raceways, cable trays, cablebus, auxiliary gutters, cable armor, boxes, cable sheathing, cabinets, elbows, couplings, nipples, fittings, supports, and support hardware embedded or encased in concrete or in direct contact with the earth shall be provided with supplementary corrosion protection. Page 101 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Insulated conductors and cables installed in raceways in wet locations above grade shall comply with 310.8(C). Change Description and Impact to Worker Safety 300.9 helps reinforce the need for everything to be listed for wet locations. As Safe or Safer. 300.11 Securing and Supporting. 300.11 Securing and Supporting. Added “and shall be permitted to be attached to the assembly” to indicate (A) Secured in Place. (A) Secured in Place. that the support means could be attached to the ceiling system, but not (2) Non–Fire-Rated Assemblies. Wiring (2) Non–Fire-Rated Assemblies. Wiring individual conductors. located within the cavity of a non–firelocated within the cavity of a non–firerated floor–ceiling or roof–ceiling rated floor–ceiling or roof–ceiling As Safe or Safer. assembly shall not be secured to, or assembly shall not be secured to, or supported by, the ceiling assembly, supported by, the ceiling assembly, including the ceiling support wires. An including the ceiling support wires. An independent means of secure support independent means of secure support shall be provided. shall be provided and shall be permitted to be attached to the assembly. 300.12 Mechanical Continuity — 300.12 Mechanical Continuity — New Exception No. 2 added to address Raceways and Cables. Metal or Raceways and Cables. Metal or the unnecessary limitations placed on nonmetallic raceways, cable armors, nonmetallic raceways, cable armors, installations including the types of and cable sheaths shall be continuous and cable sheaths shall be continuous equipment that incorporate open areas between cabinets, boxes, fittings, or between cabinets, boxes, fittings, or for cable installation. other enclosures or outlets. other enclosures or outlets. As Safe or Safer. Exception No. 2: Raceways and cables installed into the bottom of open bottom equipment, such as switchboards, motor control centers, and floor or pad-mounted transformers, Page 102 of 361 70 2008 851 Evaluation 2005 NEC 300.16 Raceway or Cable to Open or Concealed Wiring. (A) Box or Fitting. A box or terminal fitting having a separately bushed hole for each conductor shall be used wherever a change is made from conduit, electrical metallic tubing, electrical nonmetallic tubing, nonmetallic-sheathed cable, Type AC cable, Type MC cable, or mineralinsulated, metal-sheathed cable and surface raceway wiring to open wiring or to concealed knob-and-tube wiring. A fitting used for this purpose shall contain no taps or splices and shall not be used at luminaire (fixture) outlets. 300.19 Supporting Conductors in Vertical Raceways. 2008 NEC shall not be required to be mechanically secured to the equipment. 300.16 Raceway or Cable to Open or Concealed Wiring. Change Description and Impact to Worker Safety Adds conduit bodies to the types of protection allowed for conductor transitions and provides specific requirements by reference. (A) Box, Conduit Body, or Fitting. A box, conduit body, or terminal fitting having a separately bushed hole for As Safe or Safer. each conductor shall be used wherever a change is made from conduit, electrical metallic tubing, electrical nonmetallic tubing, nonmetallicsheathed cable, Type AC cable, Type MC cable, or mineral-insulated, metalsheathed cable and surface raceway wiring to open wiring or to concealed knob-and-tube wiring. A fitting used for this purpose shall contain no taps or splices and shall not be used at luminaire outlets. A conduit body used for this purpose shall contain no taps or splices, unless it complies with 314.16(C)(2). 300.19 Supporting Conductors in Inserted new (B) to address the Vertical Raceways. support methods allowed for fire-rated cables and conductors not specifically (B) Fire-Rated Cables and Conductors. addressed previously. Support methods and spacing intervals for fire-rated cables and conductors As Safe or Safer. shall comply with any restrictions Page 103 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC provided in the listing of the electrical circuit protective system used and in no case shall exceed the values in Table 300.19(A). 300.20 Induced Currents in Metal 300.20 Induced Currents in Ferrous Enclosures or Metal Raceways. Metal Enclosures or Ferrous Metal (A) Conductors Grouped Together. Raceways. Where conductors carrying alternating (A) Conductors Grouped Together. current are installed in metal Where conductors carrying alternating enclosures or metal raceways, they current are installed in ferrous metal shall be arranged so as to avoid enclosures or ferrous metal raceways, heating the surrounding metal by they shall be arranged so as to avoid induction. To accomplish this, all phase heating the surrounding ferrous metal conductors and, where used, the by induction. To accomplish this, all grounded conductor and all equipment phase conductors and, where used, grounding conductors shall be grouped the grounded conductor and all together. equipment grounding conductors shall be grouped together. 300.22 Wiring in Ducts, Plenums, and 300.22 Wiring in Ducts, Plenums, and Other Air-Handling Spaces. Other Air-Handling Spaces. (C) Other Space Used for Environmental Air. (C) Other Space Used for Environmental Air. (1) Wiring Methods. The wiring methods for such other space shall be limited to totally enclosed, nonventilated, insulated busway having no provisions for plug-in connections, Type MI cable, Type MC cable without an overall nonmetallic covering, Type (1) Wiring Methods. The wiring methods for such other space shall be limited to totally enclosed, nonventilated, insulated busway having no provisions for plug-in connections, Type MI cable, Type MC cable without an overall nonmetallic covering, Type Page 104 of 361 Change Description and Impact to Worker Safety Added “ferrous” since that is the type of material that is susceptible to inductive heating effects. This change allows non-ferrous metallic raceways to contain some but not all phase conductors of a circuit, but should only be employed where necessary due to physical constraints. As Safe or Safer. Allows for the installation of raceways in the metal wiring methods allowed in air handling spaces. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC AC cable, or other factory assembled multiconductor control or power cable that is specifically listed for the use, or listed prefabricated cable assemblies of metallic manufactured wiring systems without nonmetallic sheath. Other types of cables, conductors, and raceways shall be permitted to be installed in electrical metallic tubing, flexible metallic tubing, intermediate metal conduit, rigid metal conduit without an overall nonmetallic covering, flexible metal conduit, or, where accessible, surface metal raceway or metal wireway with metal covers or solid bottom metal cable tray with solid metal covers. 300.40 Insulation Shielding. Metallic 300.40 Insulation Shielding. Metallic and semiconducting insulation and semiconducting insulation shielding components of shielded shielding components of shielded cables shall be removed for a distance cables shall be removed for a distance dependent on the circuit voltage and dependent on the circuit voltage and insulation. Stress reduction means insulation. Stress reduction means shall be provided at all terminations of shall be provided at all terminations of factory-applied shielding. factory-applied shielding. Metallic shielding components such as Metallic shielding components such as tapes, wires, or braids, or combinations tapes, wires, or braids, or combinations thereof, and their associated thereof, shall be connected to a conducting or semiconducting grounding conductor, grounding components shall be grounded. busbar, or a grounding electrode. 300.50 Underground Installations. 300.50 Underground Installations. Change Description and Impact to Worker Safety AC cable, or other factory assembled multiconductor control or power cable that is specifically listed for the use, or listed prefabricated cable assemblies of metallic manufactured wiring systems without nonmetallic sheath. Other types of cables and conductors shall be installed in electrical metallic tubing, flexible metallic tubing, intermediate metal conduit, rigid metal conduit without an overall nonmetallic covering, flexible metal conduit, or, where accessible, surface metal raceway or metal wireway with metal covers or solid bottom metal cable tray with solid metal covers. Page 105 of 361 Continuing with the emphasis on “connected to a grounding conductor….” versus just “grounded” provides assurance of a connection to ground. Eliminates the ambiguous reference to “associated” components. Actually improves worker safety by assuring a continuous ground path. Changed wording to eliminate 70 2008 851 Evaluation 2005 NEC 2008 NEC (B) Protection from Damage. Conductors emerging from the ground shall be enclosed in listed raceways. Raceways installed on poles shall be of rigid metal conduit, intermediate metal conduit, PVC Schedule 80, or equivalent, extending from the minimum cover depth specified in Table 300.50 to a point 2.5 m (8 ft) above finished grade. Conductors entering a building shall be protected by an approved enclosure or raceway from the minimum cover depth to the point of entrance. Where direct-buried conductors, raceways, or cables are subject to movement by settlement or frost, they shall be installed to prevent damage to the enclosed conductors or to the equipment connected to the raceways. Metallic enclosures shall be grounded. Table 300.50 Minimum Cover Requirements (B) Protection from Damage. Conductors emerging from the ground shall be enclosed in listed raceways. Raceways installed on poles shall be of rigid metal conduit, intermediate metal conduit, Schedule 80 PVC conduit, or equivalent, extending from the minimum cover depth specified in Table 300.50 to a point 2.5 m (8 ft) above finished grade. Conductors entering a building shall be protected by an approved enclosure or raceway from the minimum cover depth to the point of entrance. Where direct-buried conductors, raceways, or cables are subject to movement by settlement or frost, they shall be installed to prevent damage to the enclosed conductors or to the equipment connected to the raceways. Metallic enclosures shall be grounded. Table 300.50 Minimum Cover Requirements General Notes: General Notes: 3. In industrial establishments, where conditions of maintenance and supervision ensure that qualified persons will service the installation, the Page 106 of 361 Change Description and Impact to Worker Safety confusion and to specifically identify “Schedule 80 PVC conduit” versus “PVC Schedule 80” so listed conduit would be used. As Safe or Safer. Added new Note 3 to allow reduction of the backfill requirement by six inches for each 2” of concrete cover. Applicable to 600V and above underground installations other than in rigid metal conduit and intermediate metal conduit in industrial establishments. 70 2008 851 Evaluation 2005 NEC 2008 NEC Table 300.50 Minimum Cover Requirements minimum cover requirements, for other than rigid metal conduit and intermediate metal conduit, shall be permitted to be reduced 150 mm (6 in.) for each 50 mm (2 in.) of concrete or equivalent placed entirely within the trench over the underground installation. Table 300.50 Minimum Cover Requirements Specific Footnotes: Specific Footnotes: Change Description and Impact to Worker Safety As Safe or Safer. Added new footnote d to require a marker tape to be installed over unprotected direct buried cables which will provide some measure of contact avoidance by excavators. d 310.4 Conductors in Parallel. Underground direct-buried cables that are not encased or protected by concrete and are buried 750 mm (30 in.) or more below grade shall have their location identified by a warning ribbon that is placed in the trench at least 300 mm (12 in.) above the cables. Article 310 310.4 Conductors in Parallel. Aluminum, copper-clad aluminum, or copper conductors of size 1/0 AWG and larger, comprising each phase, polarity, neutral, or grounded circuit conductor, shall be permitted to be connected in parallel (electrically joined at both ends). (A) General. Aluminum, copper-clad aluminum, or copper conductors of size 1/0 AWG and larger, comprising each phase, polarity, neutral, or grounded circuit conductor shall be permitted to be connected in parallel (electrically joined at both ends). Page 107 of 361 Improves worker safety. Deleted old Exception 1 and reference to Article 620. Made provision for higher frequency systems by combining old Exceptions 2 and 3 into new Exception 2. Old Exception 4 becomes Exception 2. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC Exception No. 1: As permitted in 620.12(A)(1). Exception No. 2: Conductors in sizes smaller than 1/0 AWG shall be permitted to be run in parallel to supply control power to indicating instruments, contactors, relays, solenoids, and similar control devices, provided all of the following apply: (a) They are contained within the same raceway or cable. (b) The ampacity of each individual conductor is sufficient to carry the entire load current shared by the parallel conductors. (c) The overcurrent protection is such that the ampacity of each individual conductor will not be exceeded if one or more of the parallel conductors become inadvertently disconnected. Exception No. 3: Conductors in sizes smaller than 1/0 AWG shall be permitted to be run in parallel for frequencies of 360 Hz and higher where conditions (a), (b), and (c) of Exception No. 2 are met. 2008 NEC Exception No. 1: Conductors in sizes smaller than 1/0 AWG shall be permitted to be run in parallel to supply control power to indicating instruments, contactors, relays, solenoids, and similar control devices, or for frequencies of 360 Hz and higher, provided all of the following apply: (a) They are contained within the same raceway or cable. (b) The ampacity of each individual conductor is sufficient to carry the entire load current shared by the parallel conductors. (c) The overcurrent protection is such that the ampacity of each individual conductor will not be exceeded if one or more of the parallel conductors become inadvertently disconnected. Exception No. 2: Under engineering supervision, grounded neutral conductors in sizes 2 AWG and larger shall be permitted to be run in parallel for existing installations. Page 108 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC Exception No. 4: Under engineering supervision, grounded neutral conductors in sizes 2 AWG and larger shall be permitted to be run in parallel for existing installations. 310.4 Conductors in Parallel. The paralleled conductors in each phase, polarity, neutral, or grounded circuit conductor shall comply with all of the following: (1) Be the same length (2) Have the same conductor material (3) Be the same size in circular mil area (4) Have the same insulation type (5) Be terminated in the same manner 2008 NEC 310.4 Conductors in Parallel. 310.4 Conductors in Parallel. (B) Conductor Characteristics. The paralleled conductors in each phase, polarity, neutral, grounded circuit conductor, or equipment grounding conductor shall comply with all of the following: (1) Be the same length (2) Have the same conductor material (3) Be the same size in circular mil area (4) Have the same insulation type (5) Be terminated in the same manner 310.4 Conductors in Parallel. Where run in separate raceways or cables, the raceways or cables shall have the same physical characteristics. Where conductors are in separate raceways or cables, the same number of conductors shall be used in each raceway or cable. Conductors of one phase, polarity, neutral, or grounded circuit conductor shall not be required to have the same physical (C) Separate Cables or Raceways. Where run in separate cables or raceways, the cables or raceways with conductors shall have the same number of conductors and shall have the same electrical characteristics. Conductors of one phase, polarity, neutral, grounded circuit conductor, or equipment grounding conductor shall not be required to have the same Page 109 of 361 Change Description and Impact to Worker Safety Reorganized sections to provide headings and consolidate information as well as include equipment grounding conductors in the parallel requirements. As Safe or Safer. Reorganized sections to provide headings and consolidate information as well as include equipment grounding conductors in the parallel requirements. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC characteristics as those of another phase, polarity, neutral, or grounded circuit conductor to achieve balance. 2008 NEC 310.4 Conductors in Parallel. physical characteristics as those of another phase, polarity, neutral, grounded circuit conductor, or equipment grounding conductor to achieve balance. 310.4 Conductors in Parallel. Conductors installed in parallel shall comply with the provisions of 310.15(B)(2)(a). 310.4 Conductors in Parallel. (D) Ampacity Adjustment. Conductors installed in parallel shall comply with the provisions of 310.15(B)(2)(a). 310.4 Conductors in Parallel. Where equipment grounding conductors are used with conductors in parallel, they shall comply with the requirements of this section except that they shall be sized in accordance with 250.122. (E) Equipment Grounding Conductors. Where parallel equipment grounding conductors are used, they shall be sized in accordance with 250.122. Sectioned equipment grounding conductors smaller than 1/0 AWG shall be permitted in multiconductor cables in accordance with 310.13, provided the combined circular mil area in each cable complies with 250.122. 310.6 Shielding. Solid dielectric insulated conductors operated above 2000 volts in permanent installations shall have ozone-resistant insulation and shall be shielded. All metallic insulation shields shall be connected to a grounding electrode conductor, grounding busbar, or a grounding 310.6 Shielding. Solid dielectric insulated conductors operated above 2000 volts in permanent installations shall have ozone-resistant insulation and shall be shielded. All metallic insulation shields shall be grounded through an effective grounding path meeting the requirements of Page 110 of 361 Change Description and Impact to Worker Safety Deleted Fine Print Note. Reorganized sections to provide headings and consolidate information. As Safe or Safer. Reorganized sections to provide headings and consolidate information as well as include equipment grounding conductors in the parallel requirements. As Safe or Safer. Continuing effort to clarify the connection to the grounding electrode system versus the loose term “grounded” for meeting the requirements of the section. Exception 1 redirected the reference to the appropriate table in the 2008 Code and Exception No. 2 was added to provide 70 2008 851 Evaluation 2005 NEC 2008 NEC 250.4(A)(5) or 250.4(B)(4). Shielding shall be for the purpose of confining the voltage stresses to the insulation. electrode. Shielding shall be for the purpose of confining the voltage stresses to the insulation. Exception: Nonshielded insulated conductors listed by a qualified testing laboratory shall be permitted for use up to 2400 volts under the following conditions: (a) Conductors shall have insulation resistant to electric discharge and surface tracking, or the insulated conductor(s) shall be covered with a material resistant to ozone, electric discharge, and surface tracking. (b) Where used in wet locations, the insulated conductor(s) shall have an overall nonmetallic jacket or a continuous metallic sheath. (c) Insulation and jacket thicknesses shall be in accordance with Table 310.63. Exception No. 1: Nonshielded insulated conductors listed by a qualified testing laboratory shall be permitted for use up to 2400 volts under the following conditions: (a) Conductors shall have insulation resistant to electric discharge and surface tracking, or the insulated conductor(s) shall be covered with a material resistant to ozone, electric discharge, and surface tracking. (b) Where used in wet locations, the insulated conductor(s) shall have an overall nonmetallic jacket or a continuous metallic sheath. (c) Insulation and jacket thicknesses shall be in accordance with Table 310.13(D). Change Description and Impact to Worker Safety cross reference to section 310.7 Exception No. 2. As Safe or Safer. Exception No. 2: Where permitted in 310.7, Exception No. 2. 310.7 Direct Burial Conductors. 310.7 Direct-Burial Conductors. Conductors used for direct burial Conductors used for direct-burial applications shall be of a type identified applications shall be of a type identified for such use. for such use. Cables rated above 2000 volts shall be Cables rated above 2000 volts shall be shielded. shielded. Page 111 of 361 Continuing effort to clarify the connection to the grounding electrode system versus the loose term “grounded” for meeting the requirements of the section. Exception 1 modified to reduce the allowable 70 2008 851 Evaluation 2005 NEC 2008 NEC Exception: Nonshielded multiconductor cables rated 2001– 5000 volts shall be permitted if the cable has an overall metallic sheath or armor. Exception No. 1: Nonshielded multiconductor cables rated 2001– 2400 volts shall be permitted if the cable has an overall metallic sheath or armor. Change Description and Impact to Worker Safety voltage for cables without shields and Exception No. 2 was added to allow the special case for airport lighting since it is a particularly different case than other medium voltage systems. As Safe or Safer. The metallic shield, sheath, or armor shall be grounded through an effective grounding path meeting the requirements of 250.4(A)(5) or (B)(4). The metallic shield, sheath, or armor shall be connected to a grounding electrode conductor, grounding busbar, or a grounding electrode. 310.8 Locations. Exception No. 2: Airfield lighting cable used in series circuits that are rated up to 5000 volts and are powered by regulators shall be permitted to be nonshielded. 310.8 Locations. (D) Locations Exposed to Direct Sunlight. Insulated conductors or cables used where exposed to direct rays of the sun shall comply with one of the following: (1) Cables listed, or listed and marked, as being sunlight resistant (2) Conductors listed, or listed and marked, as being sunlight resistant (3) Covered with insulating material, such as tape or sleeving, that is listed, or listed and marked, as being sunlight (D) Locations Exposed to Direct Sunlight. Insulated conductors or cables used where exposed to direct rays of the sun shall comply with (D)(1) or (D)(2): (1) Conductors and cables shall be listed, or listed and marked, as being sunlight resistant (2) Conductors and cables shall be covered with insulating material, such as tape or sleeving, that is listed, or listed and marked, as being sunlight Page 112 of 361 Consolidated subsections and made the language specifically directive to emphasize the intended action. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC resistant 310.13 Conductor Constructions and Applications. Insulated conductors shall comply with the applicable provisions of one or more of the following: Table 310.13, Table 310.61, Table 310.62, Table 310.63, and Table 310.64. These conductors shall be permitted for use in any of the wiring methods recognized in Chapter 3 and as specified in their respective tables or as permitted elsewhere in this Code. Table 310.13, Table 310.61, Table 310.62, Table 310.63, and Table 310.64. 310.15 Ampacities for Conductors Rated 0–2000 Volts. 2008 NEC resistant 310.13 Conductor Constructions and Applications. Insulated conductors shall comply with the applicable provisions of Table 310.13(A) through Table 310.13(E). These conductors shall be permitted for use in any of the wiring methods recognized in Chapter 3 and as specified in their respective tables or as permitted elsewhere in this Code. Equipment grounding conductors shall be permitted to be sectioned within a listed multiconductor cable, provided the combined circular mil area complies with 250.122. Table 310.13(A) through Table 310.13(E). 310.15 Ampacities for Conductors Rated 0–2000 Volts. Page 113 of 361 Change Description and Impact to Worker Safety Table renumbering necessitated the reference changes. New paragraph allows equipment grounding conductor contained within a listed multiconductor cable to be sectioned, provided the equivalent conductor is properly sized. As Safe or Safer. Table 310.13, Table 310.61, Table 310.62, Table 310.63, and Table 310.64 of the 2005 Code were rearranged and modified slightly into Table 310.13(A) through Table 310.13(E) for the 2008 Code mainly to differentiate between voltage levels covered in the tables. As Safe or Safer. Changed wording in (B)(2)(a) to clarify the intent to allow for installations other than just stacked or bundled. Added 70 2008 851 Evaluation 2005 NEC 2008 NEC (B) Tables. Ampacities for conductors rated 0 to 2000 volts shall be as specified in the Allowable Ampacity Table 310.16 through Table 310.19, and Ampacity Table 310.20 and Table 310.21 as modified by (B)(1) through (B)(6). (B) Tables. Ampacities for conductors rated 0 to 2000 volts shall be as specified in the Allowable Ampacity Table 310.16 through Table 310.19, and Ampacity Table 310.20 and Table 310.21 as modified by (B)(1) through (B)(6). (1) General. For explanation of type letters used in tables and for recognized sizes of conductors for the various conductor insulations, see 310.13. For installation requirements, see 310.1 through 310.10 and the various articles of this Code. For flexible cords, see Table 400.4, Table 400.5(A), and Table 400.5(B). (1) General. For explanation of type letters used in tables and for recognized sizes of conductors for the various conductor insulations, see Table 310.13(A) and Table 310.13(B). For installation requirements, see 310.1 through 310.10 and the various articles of this Code. For flexible cords, see Table 400.4, Table 400.5(A), and Table 400.5(B). (2) Adjustment Factors. (2) Adjustment Factors. (a) More Than Three Current(a) More Than Three CurrentCarrying Conductors in a Raceway Carrying Conductors in a Raceway or Cable. Where the number of or Cable. Where the number of current-carrying conductors in a current-carrying conductors in a raceway or cable exceeds three, or raceway or cable exceeds three, or where single conductors or where single conductors or multiconductor cables are stacked multiconductor cables are installed or bundled longer than 600 mm (24 without maintaining spacing for a in.) without maintaining spacing and continuous length longer than 600 are not installed in raceways, the mm (24 in.) and are not installed in allowable ampacity of each raceways, the allowable ampacity of Page 114 of 361 Change Description and Impact to Worker Safety (B)(2)(c) to address the concern of conductors installed outside on rooftops exposed to direct sunlight and the effect that it has on ampacity. Reworded (B)(3) to clarify the intent to have the temperature rating of the covered or bare conductors compared with the insulated conductors in the installation. Inserted “conductor” in (B)(4) to reinforce the proper use of the term and address the fact that it is a conductor, not some other entity that is to be considered. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC conductor shall be reduced as shown in Table 310.15(B)(2)(a). Each current-carrying conductor of a paralleled set of conductors shall be counted as a current carrying conductor. (b) More Than One Conduit, Tube, or Raceway. Spacing between conduits, tubing, or raceways shall be maintained. (3) Bare or Covered Conductors. Where bare or covered conductors are used with insulated conductors, their allowable ampacities shall be limited to those permitted for the adjacent insulated conductors. 2008 NEC each conductor shall be reduced as shown in Table 310.15(B)(2)(a). Each current-carrying conductor of a paralleled set of conductors shall be counted as a current-carrying conductor. (b) More Than One Conduit, Tube, or Raceway. Spacing between conduits, tubing, or raceways shall be maintained. (c) Conduits Exposed to Sunlight on Rooftops. Where conductors or cables are installed in conduits exposed to direct sunlight on or above rooftops, the adjustments shown in Table 310.15(B)(2)(c) shall be added to the outdoor temperature to determine the applicable ambient temperature for application of the correction factors in Table 310.16 and Table 310.18. (3) Bare or Covered Conductors. Where bare or covered conductors are installed with insulated conductors, the temperature rating of the bare or covered conductor shall be equal to the lowest temperature rating of the insulated conductors for the purpose of determining ampacity. Page 115 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety (4) Neutral Conductor. (4) Neutral Conductor. (a) A neutral conductor that carries (a) A neutral conductor that carries only the unbalanced current from only the unbalanced current from other conductors of the same circuit other conductors of the same circuit shall not be required to be counted shall not be required to be counted when applying the provisions of when applying the provisions of 310.15(B)(2)(a). 310.15(B)(2)(a). (b) In a 3-wire circuit consisting of (b) In a 3-wire circuit consisting of two phase wires and the neutral of two phase conductors and the a 4-wire, 3-phase, wye-connected neutral conductor of a 4-wire, 3system, a common conductor phase, wye connected system, a carries approximately the same common conductor carries current as the line-to-neutral load approximately the same current as currents of the other conductors the line-to-neutral load currents of and shall be counted when applying the other conductors and shall be the provisions of 310.15(B)(2)(a). counted when applying the (c) On a 4-wire, 3-phase wye circuit provisions of 310.15(B)(2)(a). where the major portion of the load (c) On a 4-wire, 3-phase wye circuit consists of nonlinear loads, where the major portion of the load harmonic currents are present in consists of nonlinear loads, the neutral conductor; the neutral harmonic currents are present in the shall therefore be considered a neutral conductor; the neutral current-carrying conductor. conductor shall therefore be considered a current-carrying conductor. Article 312 I. Installation I. Installation 312.2 Damp, Wet, or Hazardous (Classified) Locations. Page 116 of 361 Deleted reference to “Hazardous (Classified) Locations” since by definition these requirements are found in Articles 500 through 517, regardless 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety of wet or damp conditions. (A) Damp and Wet Locations. In damp or wet locations, surface-type enclosures within the scope of this article shall be placed or equipped so as to prevent moisture or water from entering and accumulating within the cabinet or cutout box, and shall be mounted so there is at least 6-mm (1⁄4in.) airspace between the enclosure and the wall or other supporting surface. Enclosures installed in wet locations shall be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts shall use fittings listed for wet locations. 312.2 Damp and Wet Locations. In damp or wet locations, surface-type As Safe or Safer. enclosures within the scope of this article shall be placed or equipped so as to prevent moisture or water from entering and accumulating within the cabinet or cutout box, and shall be mounted so there is at least 6-mm (1⁄4in.) airspace between the enclosure and the wall or other supporting surface. Enclosures installed in wet locations shall be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts shall use fittings listed for wet locations. (B) Hazardous (Classified) Locations. Installations in hazardous (classified) locations shall conform to Articles 500 through 517. 312.4 Repairing Plaster and Drywall or Plasterboard. Plaster, drywall, or plasterboard surfaces that are broken or incomplete shall be repaired so there will be no gaps or open spaces greater than 3 mm (1⁄8 in.) at the edge of the cabinet or cutout box employing a flush-type cover. 312.4 Repairing Noncombustible Surfaces. Noncombustible surfaces that are broken or incomplete shall be repaired so there will be no gaps or open spaces greater than 3 mm (1⁄8 in.) at the edge of the cabinet or cutout box employing a flush-type cover. Article 314 Page 117 of 361 Changed surface types to be more inclusive of the many types of surfaces available. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 314.4 Metal Boxes. All metal boxes shall be grounded in accordance with the provisions of Article 250. 314.4 Metal Boxes. Metal boxes shall be grounded and bonded in accordance with Parts I, IV, V, VI, VII, and X of Article 250 as applicable, except as permitted in 250.112(I). II. Installation II. Installation 314.15 Damp, Wet, or Hazardous (Classified) Locations. 314.15 Damp or Wet Locations. In damp or wet locations, boxes, conduit bodies, and fittings shall be placed or (A) Damp or Wet Locations. In damp or equipped so as to prevent moisture wet locations, boxes, conduit bodies, from entering or accumulating within and fittings shall be placed or equipped the box, conduit body, or fitting. Boxes, so as to prevent moisture from entering conduit bodies, and fittings installed in or accumulating within the box, conduit wet locations shall be listed for use in body, or fitting. Boxes, conduit bodies, wet locations. and fittings installed in wet locations shall be listed for use in wet locations. (B) Hazardous (Classified) Locations. Installations in hazardous (classified) locations shall conform to Articles 500 through 517. 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies. Boxes and conduit bodies shall be of sufficient size to provide free space for all enclosed conductors. In no case shall the volume of the box, as calculated in Change Description and Impact to Worker Safety More specific direction provided to eliminate confusion and misapplication of the grounding and bonding requirements. As Safe or Safer. Deleted reference to “Hazardous (Classified) Locations” since by definition these requirements are found in Articles 500 through 517, regardless of wet or damp conditions. As Safe or Safer. 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies. Boxes and conduit bodies shall be of sufficient size to provide free space for all enclosed conductors. In no case shall the volume of the box, as calculated in Page 118 of 361 Generators were added as an exception since the same situation exists for manufacturer supplied generator connections as for manufacturer supplied motor terminals. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety 314.16(A), be less than the fill calculation as calculated in 314.16(B). The minimum volume for conduit bodies shall be as calculated in 314.16(C). The provisions of this section shall not apply to terminal housings supplied with motors. 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies. 314.16(A), be less than the fill calculation as calculated in 314.16(B). The minimum volume for conduit bodies shall be as calculated in 314.16(C). The provisions of this section shall not apply to terminal housings supplied with motors or generators. 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies. (B) Box Fill Calculations. (B) Box Fill Calculations. (1) Conductor Fill. Each conductor that originates outside the box and terminates or is spliced within the box shall be counted once, and each conductor that passes through the box without splice or termination shall be counted once. A looped, unbroken conductor not less than twice the minimum length required for free conductors in 300.14 shall be counted twice. The conductor fill shall be calculated using Table 314.16(B). A conductor, no part of which leaves the box, shall not be counted. 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies. (1) Conductor Fill. Each conductor that originates outside the box and terminates or is spliced within the box shall be counted once, and each conductor that passes through the box without splice or termination shall be counted once. Each loop or coil of unbroken conductor not less than twice the minimum length required for free conductors in 300.14 shall be counted twice. The conductor fill shall be calculated using Table 314.16(B). A conductor, no part of which leaves the box, shall not be counted. 314.16 Number of Conductors in Added double volume allowance Outlet, Device, and Junction Boxes, requirements for devices and and Conduit Bodies. equipment wider than a standard Clarified wording to include “coil” as well as “loop” to eliminate controversy. As Safe or Safer. Page 119 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC (B) Box Fill Calculations. (B) Box Fill Calculations. (4) Device or Equipment Fill. For each yoke or strap containing one or more devices or equipment, a double volume allowance in accordance with Table 314.16(B) shall be made for each yoke or strap based on the largest conductor connected to a device(s) or equipment supported by that yoke or strap. (4) Device or Equipment Fill. For each yoke or strap containing one or more devices or equipment, a double volume allowance in accordance with Table 314.16(B) shall be made for each yoke or strap based on the largest conductor connected to a device(s) or equipment supported by that yoke or strap. A device or utilization equipment wider than a single 50 mm (2 in.) device box as described in Table 314.16(A) shall have double volume allowances provided for each gang required for mounting. 314.24 Minimum Depth of Boxes for Outlets, Devices, and Utilization Equipment. Outlet and device boxes shall have sufficient depth to allow equipment installed within them to be mounted properly and with sufficient clearance to prevent damage to conductors within the box. 314.24 Depth of Outlet Boxes. No box shall have an internal depth of less than 12.7 mm (1⁄2 in.). Boxes intended to enclose flush devices shall have an internal depth of not less than 23.8 mm (15⁄16 in.). (A) Outlet Boxes Without Enclosed Devices or Utilization Equipment. No box shall have an internal depth of less than 12.7 mm (1⁄2 in.). Page 120 of 361 Change Description and Impact to Worker Safety single gang box to include them in the criteria for box fill. As Safe or Safer. Significantly expanded this section to address the problems encountered when insufficient volume allowance and box depth causes pinching of wiring and forced installations of devices or equipment. Improves long term safety aspects of electrical maintenance. 70 2008 851 Evaluation 2005 NEC 2008 NEC (B) Outlet and Device Boxes with Enclosed Devices. Boxes intended to enclose flush devices shall have an internal depth of not less than 23.8 mm (15⁄16 in.). (C) Utilization Equipment. Outlet and device boxes that enclose utilization equipment shall have a minimum internal depth that accommodates the rearward projection of the equipment and the size of the conductors that supply the equipment. The internal depth shall include, where used, that of any extension boxes, plaster rings, or raised covers. The internal depth shall comply with all applicable provisions of (C)(1) through (C)(5). (1) Large Equipment. Boxes that enclose utilization equipment that projects more than 48 mm (17⁄8 in.) rearward from the mounting plane of the box shall have a depth that is not less than the depth of the equipment plus 6 mm (1⁄4 in.). (2) Conductors Larger Than 4 AWG. Boxes that enclose utilization equipment supplied by conductors larger than 4 AWG shall be Page 121 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC identified for their specific function. (3) Conductors 8, 6, or 4 AWG. Boxes that enclose utilization equipment supplied by 8, 6, or 4 AWG conductors shall have an internal depth that is not less than 52.4 mm (21⁄16 in.). (4) Conductors 12 or 10 AWG. Boxes that enclose utilization equipment supplied by 12 or 10 AWG conductors shall have an internal depth that is not less than 30.2 mm (13⁄16 in.). Where the equipment projects rearward from the mounting plane of the box by more than 25 mm (1 in.), the box shall have a depth not less than that of the equipment plus 6 mm (1⁄4 in.). (5) Conductors 14 AWG and Smaller. Boxes that enclose equipment supplied by 14 AWG or smaller conductors shall have a depth that is not less than 23.8 mm (15⁄16 in.). Exception to (C)(1) through (C)(5): Utilization equipment that is listed to be installed with specified boxes shall be Page 122 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC 314.27 Outlet Boxes. permitted. 314.27 Outlet Boxes. (A) Boxes at Luminaire Outlets. Boxes used at luminaire or lampholder outlets in a ceiling shall be designed for the purpose and shall be required to support a luminaire weighing a minimum of 23 kg (50 lb). Boxes used at luminaire or lampholder outlets in a wall shall be designed for the purpose and shall be marked to indicate the maximum weight of the luminaire that is permitted to be supported by the box in the wall, if other than 23 kg (50 lb). At every outlet used exclusively for lighting, the box shall be designed or installed so that a luminaire may be attached. 314.27 Outlet Boxes. (B) Maximum Luminaire (Fixture) Weight. Outlet boxes or fittings installed as required by 314.23 shall be permitted to support luminaires (lighting fixtures) weighing 23 kg (50 lb) or less. A luminaire (lighting fixture) that weighs more than 23 kg (50 lb) shall be supported independently of the outlet box unless the outlet box is listed for the weight to be supported. (B) Maximum Luminaire Weight. Outlet boxes or fittings designed for the support of luminaires and installed as required by 314.23 shall be permitted to support a luminaire weighing 23 kg (50 lb) or less. A luminaire that weighs more than 23 kg (50 lb) shall be supported independently of the outlet box unless the outlet box is listed and marked for the maximum weight to be supported. 314.27 Outlet Boxes. (A) Boxes at Luminaire (Lighting Fixture) Outlets. Boxes used at luminaire (lighting fixture) or lampholder outlets shall be designed for the purpose. At every outlet used exclusively for lighting, the box shall be designed or installed so that a luminaire (lighting fixture) may be attached. Page 123 of 361 Change Description and Impact to Worker Safety Clarified intent that the original section addressed ceiling lighting and the requirements for wall mounted lighting were added. Language changes to incorporate the term “luminaire” referring to the “complete lighting unit consisting of a light source such as a lamp or lamps, together with the parts designed to position the light source and connect it to the power supply.” As Safe or Safer. Modified to address the requirement that the box has to be designed, listed and marked to carry the weight of luminaires. Language changes to incorporate the term “luminaire” referring to the “complete lighting unit consisting of a light source such as a lamp or lamps, together with the parts designed to position the light source and connect it to the power supply.” As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 314.27 Outlet Boxes. 2008 NEC 314.27 Outlet Boxes. (E) Utilization Equipment. Boxes used for the support of utilization equipment other than ceiling-suspended (paddle) fans shall meet the requirements of 314.27(A) and (B) for the support of a luminaire that is the same size and weight. Change Description and Impact to Worker Safety New section added to specifically address utilization equipment supported by outlet boxes and that the same requirements apply as for luminaires. The exception for less than 3 kg allows mounting of lighter equipment without the strict requirements as in 314.27(A) or (B). As Safe or Safer. 314.28 Pull and Junction Boxes and Conduit Bodies. (A) Minimum Size. For raceways containing conductors of 4 AWG or larger, and for cables containing conductors of 4 AWG or larger, the minimum dimensions of pull or junction boxes installed in a raceway or cable run shall comply with (A)(1) through (A)(3). 314.30 Handhole Enclosures. Exception: Utilization equipment weighing not more than 3 kg (6 lb) shall be permitted to be supported on other boxes or plaster rings that are secured to other boxes, provided the equipment or its supporting yoke is secured to the box with no fewer than two No. 6 or larger screws. 314.28 Pull and Junction Boxes and Conduit Bodies. Clarification that the requirement only applies to conductors required to be insulated. (A) Minimum Size. For raceways containing conductors of 4 AWG or As Safe or Safer. larger that are required to be insulated, and for cables containing conductors of 4 AWG or larger, the minimum dimensions of pull or junction boxes installed in a raceway or cable run shall comply with (A)(1) through (A)(3)…. 314.30 Handhole Enclosures. Clarified original intent and added the Page 124 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Handhole enclosures shall be designed and installed to withstand all loads likely to be imposed. Handhole enclosures shall be designed and installed to withstand all loads likely to be imposed on them. They shall be identified for use in underground systems. 314.30 Handhole Enclosures. 314.30 Handhole Enclosures. (C) Handhole Enclosures Without Bottoms. Where handhole enclosures without bottoms are installed, all enclosed conductors and any splices or terminations, if present, shall be listed as suitable for wet locations. 314.30 Handhole Enclosures. (C) Enclosed Wiring. All enclosed conductors and any splices or terminations, if present, shall be listed as suitable for wet locations. (D) Covers. Handhole enclosure covers shall have an identifying mark or logo that prominently identifies the function of the enclosure, such as “electric.” Handhole enclosure covers shall require the use of tools to open, or they shall weigh over 45 kg (100 lb). Metal covers and other exposed conductive surfaces shall be bonded in accordance with 250.96(A). (D) Covers. Handhole enclosure covers shall have an identifying mark or logo that prominently identifies the function of the enclosure, such as “electric.” Handhole enclosure covers shall require the use of tools to open, or they shall weigh over 45 kg (100 lb). Metal covers and other exposed conductive surfaces shall be bonded in accordance with 250.92(A) if the conductors in the handhole are service conductors, or in accordance with 250.96(A) if the conductors in the handhole are feeder or branch-circuit conductors. Article 320 Change Description and Impact to Worker Safety requirement that the enclosures need to be identified for underground use. As Safe or Safer. Modified to eliminate the caveat that the handhole enclosures had to have no bottom for the requirements of the section to apply. It now applies to all enclosed wiring in handholes. As Safe or Safer. 314.30 Handhole Enclosures. Page 125 of 361 Modified to redirect the user to the proper section for services and to differentiate them from feeders and branch circuits. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC II. Installation 320.10 Uses Permitted. Type AC cable shall be permitted as follows: (1) In both exposed and concealed work (2) In cable trays (3) In dry locations (4) Embedded in plaster finish on brick or other masonry, except in damp or wet locations (5) To be run or fished in the air voids of masonry block or tile walls where such walls are not exposed or subject to excessive moisture or dampness II. Installation 320.10 Uses Permitted. Type AC cable shall be permitted as follows: (1) For feeders and branch circuits in both exposed and concealed work (2) In cable trays (3) In dry locations (4) Embedded in plaster finish on brick or other masonry, except in damp or wet locations (5) To be run or fished in the air voids of masonry block or tile walls where such walls are not exposed or subject to excessive moisture or dampness 320.108 Equipment Grounding. Type 320.108 Equipment Grounding AC cable shall provide an adequate Conductor. Type AC cable shall path for equipment grounding as provide an adequate path for fault required by 250.4(A)(5) or 250.4(B)(4). current as required by 250.4(A)(5) or (B)(4) to act as an equipment grounding conductor. Article 328 II. Installation II. Installation 328.10 Uses Permitted. Type MV cable 328.10 Uses Permitted. Type MV cable shall be permitted for use on power shall be permitted for use on power systems rated up to 35,000 volts systems rated up to 35,000 volts nominal as follows: nominal as follows: (1) In wet or dry locations (1) In wet or dry locations (2) In raceways (2) In raceways (3) In cable trays as specified in (3) In cable trays, where identified for Page 126 of 361 Change Description and Impact to Worker Safety Modified to restrict the use to feeders and branch circuits and not services. As Safe or Safer. Emphasis on “conductor” to clarify that it is the conduction of fault current that must be adequate, not just a ground connection. As Safe or Safer. Modified to stress the identification for use of MV cable and to allow it to be used if “identified as MV or MC.” Added exposed runs per 300.37 as another permitted use. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 392.3(B)(2) 2008 NEC Change Description and Impact to Worker Safety the use, in accordance with 392.3, 392.6(F), 392.8, and 392.12. Exception: Type MV cable that has an overall metallic sheath or armor, also complies with the requirements for Type MC cable, and is identified as “MV or MC” shall be permitted to be installed in cable trays in accordance with 392.3(B)(2). (4) Direct buried in accordance with 300.50 (5) In messenger-supported wiring 328.12 Uses Not Permitted. Unless identified for the use, Type MV cable shall not be used as follows: (1) Where exposed to direct sunlight (2) In cable trays, unless specified in 392.3(B)(2) (4) Direct buried in accordance with 300.50 (5) In messenger-supported wiring in accordance with Part II of Article 396 (6) As exposed runs in accordance with 300.37 Exception: Type MV cable that has an overall metallic sheath or armor, also complies with the requirements for Type MC cable, and is identified as “MV or MC” shall be permitted to be installed as exposed runs of metal-clad cable in accordance with 300.37. 328.12 Uses Not Permitted. Type MV cable shall not be used where exposed to direct sunlight, unless identified for the use. Items (2) and (3) changed language and moved to Uses Permitted leaving only direct sunlight exposure as a use not permitted. As Safe or Safer. Page 127 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety (3) Direct buried, unless in accordance with 300.50 Article 330 II. Installation 330.10 Uses Permitted. II. Installation 330.10 Uses Permitted. Added “corrosion-resistant jacket” requirement for the metal sheath Type MC cable in wet locations. (A) General Uses. Type MC cable shall (A) General Uses. Type MC cable shall be permitted as follows: be permitted as follows: As Safe or Safer. (11) In wet locations where any of the following conditions are met: a. The metallic covering is impervious to moisture. b. A lead sheath or moistureimpervious jacket is provided under the metal covering. c. The insulated conductors under the metallic covering are listed for use in wet locations. 330.12 Uses Not Permitted. Type MC cable shall not be used where exposed to the following destructive corrosive conditions, unless the metallic sheath is suitable for the conditions or is protected by material suitable for the conditions: (1) Where subject to physical damage (2) Direct burial in the earth (3) In concrete (11) In wet locations where any of the following conditions are met: a. The metallic covering is impervious to moisture. b. A lead sheath or moistureimpervious jacket is provided under the metal covering. c. The insulated conductors under the metallic covering are listed for use in wet locations and a corrosion-resistant jacket is provided over the metallic sheath. 330.12 Uses Not Permitted. Type MC Separated the “subject to physical cable shall not be used under either of damage” clause from the allowance the following conditions: provided by “unless the metallic sheath or armor is resistant to the conditions (1) Where subject to physical damage or is protected by material resistant to the conditions” to indicate that there is (2) Where exposed to any of the no remedy by the use of a sheath or destructive corrosive conditions in (a) armor. or (b), unless the metallic sheath or armor is resistant to the conditions or is As Safe or Safer. Page 128 of 361 70 2008 851 Evaluation 2005 NEC (4) Where subject to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids III. Construction Specifications 330.104 Conductors. The conductors shall be of copper, aluminum, or copper-clad aluminum, solid or stranded. The minimum conductor size shall be 18 AWG copper and 12 AWG aluminum or copper-clad aluminum. 2008 NEC protected by material resistant to the conditions: a. Direct buried in the earth or embedded in concrete unless identified for direct burial b. Exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids III. Construction Specifications III. Construction Specifications 330.104 Conductors. Conductors shall be of copper, aluminum, copper-clad aluminum, nickel or nickel-coated copper, solid or stranded. The minimum conductor size shall be 18 AWG copper, nickel or nickel-coated copper, and 12 AWG aluminum or copper-clad aluminum. 330.108 Equipment Grounding Conductor. Where Type MC cable is used to provide an equipment grounding conductor, it shall comply with 250.118(10) and 250.122. Article 332 III. Construction Specifications 332.108 Equipment Grounding. Where the outer sheath is made of copper, it shall provide an adequate path for equipment grounding purposes. Where made of steel, an equipment grounding 332.108 Equipment Grounding Conductor. Where the outer sheath is made of copper, it shall provide an adequate path to serve as an equipment grounding conductor. 330.108 Equipment Grounding. Where Type MC cable is used for equipment grounding, it shall comply with 250.118(10) and 250.122. Page 129 of 361 Change Description and Impact to Worker Safety Inserted “nickel, or nickel-coated copper” to allow for newer manufacturing techniques. Table references changed to coordinate with changes in the tables. As Safe or Safer. Emphasis on conductor to make it clear that there is a specific function it performs. As Safe or Safer. Continued emphasis on conductor to make it clear that there is a specific function it performs. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC conductor shall be provided. ARTICLE 334 Nonmetallic-Sheathed Cable: Types NM, NMC, and NMS 2008 NEC Where the outer sheath is made of steel, a separate equipment grounding conductor shall be provided. Article 334 ARTICLE 334 Nonmetallic-Sheathed Cable: Types NM, NMC, and NMS Change Description and Impact to Worker Safety Added exception to allow cables in conduit rated for the location type. As Safe or Safer. 334.12 Uses Not Permitted. (A) Types NM, NMC, and NMS. Types NM, NMC, and NMS cables shall not be permitted as follows: (1) In any dwelling or structure not specifically permitted in 334.10(1), (2), and (3) 334.12 Uses Not Permitted. (B) Types NM and NMS. Types NM and NMS cables shall not be used under the following conditions or in the following locations: (1) Where exposed to corrosive fumes or vapors (2) Where embedded in masonry, concrete, adobe, fill, or plaster (3) In a shallow chase in masonry, concrete, or adobe and covered with 334.12 Uses Not Permitted. (A) Types NM, NMC, and NMS. Types NM, NMC, and NMS cables shall not be permitted as follows: (1) In any dwelling or structure not specifically permitted in 334.10(1), (2), and (3) Exception: Type NM, NMC, and NMS cable shall be permitted in Type I and II construction when installed within raceways permitted to be installed in Type I and II construction. 334.12 Uses Not Permitted. (B) Types NM and NMS. Types NM and NMS cables shall not be used under the following conditions or in the following locations: (1) Where exposed to corrosive fumes or vapors (2) Where embedded in masonry, concrete, adobe, fill, or plaster (3) In a shallow chase in masonry, concrete, or adobe and covered with Page 130 of 361 Points to specific definition for wet or damp locations to reduce the confusion and misinterpretation. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC plaster, adobe, or similar finish (4) Where exposed or subject to excessive moisture or dampness 334.15 Exposed Work. plaster, adobe, or similar finish (4) In wet or damp locations (B) Protection from Physical Damage. Cable shall be protected from physical damage where necessary by rigid metal conduit, intermediate metal conduit, electrical metallic tubing, Schedule 80 PVC rigid nonmetallic conduit, or other approved means. Where passing through a floor, the cable shall be enclosed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, Schedule 80 PVC rigid nonmetallic conduit, or other approved means extending at least 150 mm (6 in.) above the floor. Where Type NMC cable is installed in shallow chases in masonry, concrete, or adobe, the cable shall be protected against nails or screws by a steel plate at least 1.59 mm (1⁄16 in.) thick and covered with plaster, adobe, or similar finish. 334.15 Exposed Work. (B) Protection from Physical Damage. Cable shall be protected from physical damage where necessary by rigid metal conduit, intermediate metal conduit, electrical metallic tubing, Schedule 80 PVC conduit, or other approved means. Where passing through a floor, the cable shall be enclosed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, Schedule 80 PVC conduit, or other approved means extending at least 150 mm (6 in.) above the floor. Type NMC cable installed in shallow chases or grooves in masonry, concrete, or adobe, shall be protected in accordance with the requirements in 300.4(E) and covered with plaster, adobe, or similar finish. (C) In Unfinished Basements. Where cable is run at angles with joists in unfinished basements, it shall be (C) In Unfinished Basements and Crawl Spaces. Where cable is run at angles with joists in unfinished 334.15 Exposed Work. 334.15 Exposed Work. Page 131 of 361 Change Description and Impact to Worker Safety Removed “rigid nonmetallic” from the PVC conduit as it was redundant. Now refers to Article 300 where the details of the installation methods are covered. As Safe or Safer. Added crawl spaces to specifically include those areas in the requirements of this section. Clarified to refer to Article 300 requirements for protective means. Added connection 70 2008 851 Evaluation 2005 NEC 2008 NEC permissible to secure cables not smaller than two 6 AWG or three 8 AWG conductors directly to the lower edges of the joists. Smaller cables shall be run either through bored holes in joists or on running boards. NM cable used on a wall of an unfinished basement shall be permitted to be installed in a listed conduit or tubing. Conduit or tubing shall utilize a nonmetallic bushing or adapter at the point the cable enters the raceway. Metal conduit and tubings and metal outlet boxes shall be grounded. basements and crawl spaces, it shall be permissible to secure cables not smaller than two 6 AWG or three 8 AWG conductors directly to the lower edges of the joists. Smaller cables shall be run either through bored holes in joists or on running boards. NM cable installed on the wall of an unfinished basement shall be permitted to be installed in a listed conduit or tubing or shall be protected in accordance with 300.4. Conduit or tubing shall be provided with a suitable insulating bushing or adapter at the point the cable enters the raceway. The NM cable sheath shall extend through the conduit or tubing and into the outlet or device box not less than 6 mm (1⁄4 in.). The cable shall be secured within 300 mm (12 in.) of the point where the cable enters the conduit or tubing. Metal conduit, tubing, and metal outlet boxes shall be connected to an equipment grounding conductor. 334.80 Ampacity. The ampacity of Types NM, NMC, and NMS cable shall be determined in accordance with 310.15. The ampacity shall be in accordance with the 60°C (140°F) conductor temperature rating. The 334.80 Ampacity. The ampacity of Types NM, NMC, and NMS cable shall be determined in accordance with 310.15. The ampacity shall be in accordance with the 60°C (140°F) conductor temperature rating. The Page 132 of 361 Change Description and Impact to Worker Safety requirements for the sheath to assure a secure protective connection. Continued emphasis on grounding conductor to make it clear that there is a specific function it performs. As Safe or Safer. Altered wording to assure that the cables did not have to be bundled to require the installation to comply with this section. Adds requirements for ampacity adjustment previously not addressed. 70 2008 851 Evaluation 2005 NEC 90°C (194°F) rating shall be permitted to be used for ampacity derating purposes, provided the final derated ampacity does not exceed that for a 60°C (140°F) rated conductor. The ampacity of Types NM, NMC, and NMS cable installed in cable tray shall be determined in accordance with 392.11. Where more than two NM cables containing two or more current-carrying conductors are bundled together and pass through wood framing that is to be fire- or draft-stopped using thermal insulation or sealing foam, the allowable ampacity of each conductor shall be adjusted in accordance with Table 310.15(B)(2)(a). III. Construction Specifications 2008 NEC Change Description and Impact to Worker Safety 90°C (194°F) rating shall be permitted to be used for ampacity derating As Safe or Safer. purposes, provided the final derated ampacity does not exceed that for a 60°C (140°F) rated conductor. The ampacity of Types NM, NMC, and NMS cable installed in cable tray shall be determined in accordance with 392.11. Where more than two NM cables containing two or more current-carrying conductors are installed, without maintaining spacing between the cables, through the same opening in wood framing that is to be fire- or draftstopped using thermal insulation, caulk, or sealing foam, the allowable ampacity of each conductor shall be adjusted in accordance with Table 310.15(B)(2)(a) and the provisions of 310.15(A)(2), Exception, shall not apply. Where more than two NM cables containing two or more current-carrying conductors are installed in contact with thermal insulation without maintaining spacing between cables, the allowable ampacity of each conductor shall be adjusted in accordance with Table 310.15(B)(2)(a). III. Construction Specifications Deleted reference to Article 780 as the Page 133 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC 334.104 Conductors. The 600 volt insulated conductors shall be sizes 14 AWG through 2 AWG copper conductors or sizes 12 AWG through 2 AWG aluminum or copper-clad aluminum conductors. The signaling conductors shall comply with 780.5. The communication conductors shall comply with Part V of Article 800. 334.104 Conductors. The 600-volt insulated conductors shall be sizes 14 AWG through 2 AWG copper conductors or sizes 12 AWG through 2 AWG aluminum or copper-clad aluminum conductors. The communications conductors shall comply with Part V of Article 800. 334.108 Equipment Grounding. In addition to the insulated conductors, the cable shall have an insulated or bare conductor for equipment grounding purposes only. ARTICLE 336 Power and Control Tray Cable: Type TC 334.108 Equipment Grounding Conductor. In addition to the insulated conductors, the cable shall have an insulated, covered, or bare equipment grounding conductor. Article 336 ARTICLE 336 Power and Control Tray Cable: Type TC II. Installation 336.10 Uses Permitted. Type TC cable shall be permitted to be used as follows: II. Installation 336.10 Uses Permitted. Type TC cable shall be permitted to be used as follows: (7) In industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation, and where the cable is continuously (7) In industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation, and where the cable is continuously Page 134 of 361 Change Description and Impact to Worker Safety article was deleted. As Safe or Safer. Continued emphasis on conductor to make it clear that there is a specific function it performs. As Safe or Safer. Added the exception to allow the cables to make the less than six foot transition between trays and equipment without support, but only in areas where they will not be subject to physical damage. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC supported and protected against physical damage using mechanical protection, such as struts, angles, or channels, Type TC tray cable that complies with the crush and impact requirements of Type MC cable and is identified for such use with the marking Type TC–ER shall be permitted between a cable tray and the utilization equipment or device. The cable shall be secured at intervals not exceeding 1.8 m (6 ft). Equipment grounding for the utilization equipment shall be provided by an equipment grounding conductor within the cable. In cables containing conductors sized 6 AWG or smaller, the equipment grounding conductor shall be provided within the cable or, at the time of installation, one or more insulated conductors shall be permanently identified as an equipment grounding conductor in accordance with 250.119(B). supported and protected against physical damage using mechanical protection, such as struts, angles, or channels, Type TC tray cable that complies with the crush and impact requirements of Type MC cable and is identified for such use with the marking Type TC–ER shall be permitted between a cable tray and the utilization equipment or device. The cable shall be secured at intervals not exceeding 1.8 m (6 ft). Equipment grounding for the utilization equipment shall be provided by an equipment grounding conductor within the cable. In cables containing conductors sized 6 AWG or smaller, the equipment grounding conductor shall be provided within the cable or, at the time of installation, one or more insulated conductors shall be permanently identified as an equipment grounding conductor in accordance with 250.119(B). Exception: Where not subject to physical damage, Type TC-ER shall be permitted to transition between cable trays and between cable trays and utilization equipment or devices for a distance not to exceed 1.8 m (6 ft) Page 135 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC III. Construction Specifications 336.104 Conductors. The insulated conductors of Type TC tray cable shall be in sizes 18 AWG through 1000 kcmil copper and sizes 12 AWG through 1000 kcmil aluminum or copper-clad aluminum. Insulated conductors of sizes 14 AWG and larger copper and sizes 12 AWG and larger aluminum or copper-clad aluminum shall be one of the types listed in Table 310.13 or Table 310.62 that is suitable for branch circuit and feeder circuits or one that is identified for such use. 2008 NEC without continuous support. The cable shall be mechanically supported where exiting the cable tray to ensure that the minimum bending radius is not exceeded. III. Construction Specifications II. Installation 336.104 Conductors. The insulated conductors of Type TC cables shall be in sizes 18 AWG to 1000 kcmil copper, nickel, or nickel-coated copper, and sizes 12 AWG through 1000 kcmil aluminum or copper-clad aluminum. Insulated conductors of sizes 14 AWG, and larger copper, nickel, or nickelcoated copper, and sizes 12 AWG through 1000 kcmil aluminum or copper-clad aluminum shall be one of the types listed in Table 310.13(A) or Table 310.13(B) that is suitable for branch circuit and feeder circuits or one that is identified for such use. Article 338 II. Installation 338.10 Uses Permitted. (A) Service-Entrance Conductors. Service-entrance cable shall be permitted to be used as serviceentrance conductors and shall be installed in accordance with 230.6, 338.10 Uses Permitted. (A) Service-Entrance Conductors. Service-entrance cable shall be permitted to be used as serviceentrance conductors and shall be installed in accordance with 230.6, Page 136 of 361 Change Description and Impact to Worker Safety Inserted “nickel, or nickel-coated copper” to allow for newer manufacturing techniques. Table references changed to coordinate with changes in the tables. As Safe or Safer. Deleted the allowance for USE cable to be consistent with the requirements of underground to surface transitions in conduit. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 230.7, and Parts II, III, and IV of Article 230. Type USE used for service laterals shall be permitted to emerge from the ground outside at terminations in meter bases or other enclosures where protected in accordance with 300.5(D). 338.10 Uses Permitted. 230.7, and Parts II, III, and IV of Article 230. (B) Branch Circuits or Feeders. (B) Branch Circuits or Feeders. (1) Grounded Conductor Insulated. Type SE service entrance cables shall be permitted in wiring systems where all of the circuit conductors of the cable are of the rubber covered or thermoplastic type. (1) Grounded Conductor Insulated. Type SE service entrance cables shall be permitted in wiring systems where all of the circuit conductors of the cable are of the thermoset or thermoplastic type. As Safe or Safer. 338.10 Uses Permitted. 338.10 Uses Permitted. (B) Branch Circuits or Feeders. (B) Branch Circuits or Feeders. Modified exception to clearly identify the criteria for use of the referenced articles. (2) Grounded Conductor Not Insulated. Type SE service-entrance cable shall be permitted for use where the insulated conductors are used for circuit wiring and the uninsulated conductor is used only for equipment grounding purposes. (2) Grounded Conductor Not Insulated. Type SE service-entrance cable shall be permitted for use where the insulated conductors are used for circuit wiring and the uninsulated conductor is used only for equipment grounding purposes. Exception: Uninsulated conductors Exception: Uninsulated conductors 338.10 Uses Permitted. Page 137 of 361 Change Description and Impact to Worker Safety Updated to modern manufacturing techniques and applicability of cable types. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC shall be permitted as a grounded conductor in accordance with 250.140, 250.32, and 225.30 through 225.40. 2008 NEC 338.10 Uses Permitted. shall be permitted as a grounded conductor in accordance with 250.32 and 250.140 where the uninsulated grounded conductor of the cable originates in service equipment, and 225.30 through 225.40. 338.10 Uses Permitted. (B) Branch Circuits or Feeders. (B) Branch Circuits or Feeders. (4) Installation Methods for Branch Circuits and Feeders. (4) Installation Methods for Branch Circuits and Feeders. (a) Interior Installations. In addition to the provisions of this article, Type SE service-entrance cable used for interior wiring shall comply with the installation requirements of Parts I and II of Article 334, excluding 334.80. (a) Interior Installations. In addition to the provisions of this article, Type SE service-entrance cable used for interior wiring shall comply with the installation requirements of Part II of Article 334. Change Description and Impact to Worker Safety Deleted “unless used as messengersupported wiring as permitted in Part II of Article 396” and “Where Type USE cable emerges from the ground at terminations, it shall be protected in accordance with 300.5(D). Multiconductor service-entrance cable shall be permitted to be installed as messenger-supported wiring in accordance with 225.10 and Part II of Article 396” and rewrote into 338.12 Uses Not Permitted. As Safe or Safer. (b) Exterior Installations. In addition to the provisions of this article, serviceentrance cable used for feeders or branch circuits, where installed as exterior wiring, shall be installed in accordance with Part I of Article 225. The cable shall be supported in accordance with 334.30, unless used as messenger-supported wiring as permitted in Part II of Article 396. Type USE cable installed as underground (b) Exterior Installations. In addition to the provisions of this article, serviceentrance cable used for feeders or branch circuits, where installed as exterior wiring, shall be installed in accordance with Part I of Article 225. The cable shall be supported in accordance with 334.30. Type USE cable installed as underground feeder and branch circuit cable shall comply with Part II of Article 340. Page 138 of 361 70 2008 851 Evaluation 2005 NEC feeder and branch circuit cable shall comply with Part II of Article 340. Where Type USE cable emerges from the ground at terminations, it shall be protected in accordance with 300.5(D). Multiconductor service-entrance cable shall be permitted to be installed as messenger-supported wiring in accordance with 225.10 and Part II of Article 396. 2008 NEC Change Description and Impact to Worker Safety 338.12 Uses Not Permitted. Extracted words from 338.10 and created new section to specify uses not permitted for service-entrance cable. (A) Service-Entrance Cable. Serviceentrance cable (SE) shall not be used under the following conditions or in the following locations: As Safe or Safer. (1) Where subject to physical damage unless protected in accordance with 230.50(A) (2) Underground with or without a raceway (3) For exterior branch circuits and feeder wiring unless the installation complies with the provisions of Part I of Article 225 and is supported in accordance with 334.30 or is used as messenger-supported wiring as permitted in Part II of Article 396 (B) Underground Service-Entrance Cable. Underground service-entrance Page 139 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety Underground Feeder and BranchCircuit Cable: Type UF cable (USE) shall not be used under the following conditions or in the following locations: (1) For interior wiring (2) For aboveground installations except where USE cable emerges from the ground and is terminated in an enclosure at an outdoor location and the cable is protected in accordance with 300.5(D) (3) As aerial cable unless it is a multiconductor cable identified for use aboveground and installed as messenger supported wiring in accordance with 225.10 and Part II of Article 396 Article 340 Underground Feeder and BranchMade allowance for exceptions Circuit Cable: Type UF granted by other Code sections. 340.12 Uses Not Permitted. Type UF cable shall not be used as follows: 340.12 Uses Not Permitted. Type UF cable shall not be used as follows: (7) In hazardous (classified) locations (7) In any hazardous (classified) location, except as otherwise permitted in this Code 340.108 Equipment Grounding Conductor. In addition to the insulated conductors, the cable shall be permitted to have an insulated or bare equipment grounding conductor. 340.108 Equipment Grounding. In addition to the insulated conductors, the cable shall be permitted to have an insulated or bare conductor for equipment grounding purposes only. Page 140 of 361 As Safe or Safer. Modified to reinforce that an equipment grounding conductor is the specific function of the conductor in the cable. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Intermediate Metal Conduit: Type IMC Article 342 Intermediate Metal Conduit: Type IMC 342.30 Securing and Supporting. IMC shall be installed as a complete system in accordance with 300.18 and shall be securely fastened in place and supported in accordance with 342.30(A) and (B). 342.30 Securing and Supporting. Rigid Metal Conduit: Type RMC 344.2 Definition. Rigid Metal Conduit (RMC). A Change Description and Impact to Worker Safety Provides the installer controlled options for installing unsupported IMC. 342.30 Securing and Supporting. IMC shall be installed as a complete system As Safe or Safer. in accordance with 300.18 and shall be securely fastened in place and supported in accordance with 342.30(A) and (B), or permitted to be unsupported in accordance with 342.30(C). 342.30 Securing and Supporting. New section to specify the allowable methods for installing IMC (C) Unsupported Raceways. Where unsupported. oversized, concentric or eccentric knockouts are not encountered, Type As Safe or Safer. IMC shall be permitted to be unsupported where the raceway is not more than 450 mm (18 in.) and remains in unbroken lengths (without coupling). Such raceways shall terminate in an outlet box, junction box, device box, cabinet, or other termination at each end of the raceway. Article 344 Rigid Metal Conduit: Type RMC Replaced “silicon bronze” with “red brass” to adapt to the current 344.2 Definition. manufacturing processes and to identify the more widely used copper Rigid Metal Conduit (RMC). A alloys. Page 141 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC threadable raceway of circular cross section designed for the physical protection and routing of conductors and cables and for use as an equipment grounding conductor when installed with its integral or associated coupling and appropriate fittings. RMC is generally made of steel (ferrous) with protective coatings or aluminum (nonferrous). Special use types are silicon bronze and stainless steel. II. Installation threadable raceway of circular cross section designed for the physical protection and routing of conductors and cables and for use as an equipment grounding conductor when installed with its integral or associated coupling and appropriate fittings. RMC is generally made of steel (ferrous) with protective coatings or aluminum (nonferrous). Special use types are red brass and stainless steel. II. Installation 344.10 Uses Permitted. 344.10 Uses Permitted. (A) All Atmospheric Conditions and Occupancies. Use of RMC shall be permitted under all atmospheric conditions and occupancies. Ferrous raceways and fittings protected from corrosion solely by enamel shall be permitted only indoors and in occupancies not subject to severe corrosive influences. (A) Atmospheric Conditions and Occupancies. Change Description and Impact to Worker Safety As Safe or Safer. Expanded section to specifically identify the applications for the specific types (galvanized, stainless steel, red brass, aluminum and ferrous) of RMC conduits. As Safe or Safer. (1) Galvanized Steel and Stainless Steel RMC. Galvanized steel and stainless steel RMC shall be permitted under all atmospheric conditions and occupancies. (2) Red Brass RMC. Red brass RMC shall be permitted to be installed for direct burial and swimming pool applications. (3) Aluminum RMC. Aluminum RMC shall be permitted to be installed where Page 142 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety judged suitable for the environment. Rigid aluminum conduit encased in concrete or in direct contact with the earth shall be provided with approved supplementary corrosion protection. 344.10 Uses Permitted. (B) Corrosion Environments. RMC, elbows, couplings, and fittings shall be permitted to be installed in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences where protected by corrosion protection and judged suitable for the condition. (4) Ferrous Raceways and Fittings. Ferrous raceways and fittings protected from corrosion solely by enamel shall be permitted only indoors and in occupancies not subject to severe corrosive influences. 344.10 Uses Permitted. (B) Corrosive Environments. (1) Galvanized Steel, Stainless Steel, and Red Brass RMC, Elbows, Couplings, and Fittings. Galvanized steel, stainless steel, and red brass RMC elbows, couplings, and fittings shall be permitted to be installed in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences where protected by corrosion protection and judged suitable for the condition. (2) Supplementary Protection of Aluminum RMC. Aluminum RMC shall be provided with approved Page 143 of 361 Modified section to specifically address the properties of each type of RMC and their applications and to specifically set requirements for use of aluminum underground or in concrete. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 344.10 Uses Permitted. 2008 NEC supplementary corrosion protection where encased in concrete or in direct contact with the earth. 344.10 Uses Permitted. (C) Cinder Fill. RMC shall be permitted to be installed in or under cinder fill where subject to permanent moisture where protected on all sides by a layer of noncinder concrete not less than 50 mm (2 in.) thick; where the conduit is not less than 450 mm (18 in.) under the fill; or where protected by corrosion protection and judged suitable for the condition. (C) Cinder Fill. Galvanized steel, stainless steel, and red brass RMC shall be permitted to be installed in or under cinder fill where subject to permanent moisture where protected on all sides by a layer of noncinder concrete not less than 50 mm (2 in.) thick; where the conduit is not less than 450 mm (18 in.) under the fill; or where protected by corrosion protection and judged suitable for the condition. 344.30 Securing and Supporting. RMC 344.30 Securing and Supporting. RMC shall be installed as a complete system shall be installed as a complete system in accordance with 300.18 and shall be in accordance with 300.18 and shall be securely fastened in place and securely fastened in place and supported in accordance with supported in accordance with 344.30(A) and (B). 344.30(A) and (B) or permitted to be unsupported in accordance with 344.30(C). 344.30 Securing and Supporting. 344.30 Securing and Supporting. (C) Unsupported Raceways. Where oversized, concentric or eccentric knockouts are not encountered, Type RMC shall be permitted to be Page 144 of 361 Change Description and Impact to Worker Safety Modified to specifically identify which types of RMC may be used in cinder fill locations. As Safe or Safer. Added the new alternative (C) to the allowable support installations. As Safe or Safer. New section to specify the allowable methods for installing RMC unsupported. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC Flexible Metal Conduit: Type FMC 348.12 Uses Not Permitted. FMC shall not be used in the following: (1) In wet locations unless the conductors are approved for the specific conditions and the installation is such that liquid is not likely to enter raceways or enclosures to which the conduit is connected (2) In hoistways, other than as permitted in 620.21(A)(1) (3) In storage battery rooms (4) In any hazardous (classified) location other than as permitted in 501.10(B) and 504.20 (5) Where exposed to materials having a deteriorating effect on the installed conductors, such as oil or gasoline (6) Underground or embedded in poured concrete or aggregate (7) Where subject to physical damage 2008 NEC Change Description and Impact to Worker Safety unsupported where the raceway is not more than 450 mm (18 in.) and remains in unbroken lengths (without coupling). Such raceways shall terminate in an outlet box, junction box, device box, cabinet, or other termination at each end of the raceway. Article 348 Flexible Metal Conduit: Type FMC Removed the qualifier to wet locations to reinforce that FMC is not to be used 348.12 Uses Not Permitted. FMC shall in any wet location and changed the not be used in the following: hazardous location requirement to (1) In wet locations allow for the other sections of the Code that contain permissions. As Safe or Safer. (2) In hoistways, other than as permitted in 620.21(A)(1) (3) In storage battery rooms (4) In any hazardous (classified) location except as permitted by other articles in this Code (5) Where exposed to materials having a deteriorating effect on the installed conductors, such as oil or gasoline (6) Underground or embedded in poured concrete or aggregate (7) Where subject to physical damage Page 145 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC 348.30 Securing and Supporting. FMC shall be securely fastened in place and supported in accordance with 348.30(A) and (B). 348.30 Securing and Supporting. FMC shall be securely fastened in place and supported in accordance with 348.30(A) and (B). (A) Securely Fastened. FMC shall be securely fastened in place by an approved means within 300 mm (12 in.) of each box, cabinet, conduit body, or other conduit termination and shall be supported and secured at intervals not to exceed 1.4 m (41⁄2 ft). (A) Securely Fastened. FMC shall be securely fastened in place by an approved means within 300 mm (12 in.) of each box, cabinet, conduit body, or other conduit termination and shall be supported and secured at intervals not to exceed 1.4 m (41⁄2 ft). Exception No. 1: Where FMC is fished. Exception No. 1: Where FMC is fished between access points through concealed spaces in finished buildings or structures and supporting is impractical. Exception No. 2: At terminals where flexibility is required, lengths shall not exceed the following: (1) 900 mm (3 ft) for metric designators 16 through 35 (trade sizes 1⁄2 through 11⁄4) (2) 1200 mm (4 ft) for metric designators 41 through 53 (trade sizes 11⁄2 through 2) (3) 1500 mm (5 ft) for metric designators 63 (trade size 21⁄2) and larger Exception No. 2: Where flexibility is necessary after installation, lengths shall not exceed the following: (1) 900 mm (3 ft) for metric designators 16 through 35 (trade sizes 1⁄2 through 11⁄4) (2) 1200 mm (4 ft) for metric designators 41 through 53 (trade sizes 11⁄2 through 2) (3) 1500 mm (5 ft) for metric designators 63 (trade size 21⁄2) and larger Page 146 of 361 Change Description and Impact to Worker Safety Modified Exceptions No. 1 and 2 to specifically address the fact that the “fished” FMC is to be for retrofit installations and does not apply to new installations. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety 348.60 Grounding and Bonding. Where 348.60 Grounding and Bonding. Where Inserted “after installation” to indicate used to connect equipment where used to connect equipment where that the requirement is intended for the flexibility is required, an equipment flexibility is required after installation, installed condition, not for installation grounding conductor shall be installed. an equipment grounding conductor purposes. This change limits the use of Where flexibility is not required, FMC shall be installed. FMC for equipment grounding. shall be permitted to be used as an Where flexibility is not required after equipment grounding conductor when installation, FMC shall be permitted to As Safe or Safer. installed in accordance with be used as an equipment grounding 250.118(5). conductor when installed in Where required or installed, equipment accordance with 250.118(5). grounding conductors shall be installed Where required or installed, equipment in accordance with 250.134(B). grounding conductors shall be installed Where required or installed, equipment in accordance with 250.134(B). bonding jumpers shall be installed in Where required or installed, equipment accordance with 250.102. bonding jumpers shall be installed in accordance with 250.102. Article 350 Liquidtight Flexible Metal Conduit: Liquidtight Flexible Metal Conduit: Modified Exceptions No. 1 and 2 to Type LFMC Type LFMC specifically address the fact that the “fished” LFMC is to be for retrofit 350.30 Securing and Supporting. 350.30 Securing and Supporting. installations and does not apply to new LFMC shall be securely fastened in LFMC shall be securely fastened in installations. place and supported in accordance place and supported in accordance with 350.30(A) and (B). with 350.30(A) and (B). As Safe or Safer. (A) Securely Fastened. LFMC shall be (A) Securely Fastened. LFMC shall be securely fastened in place by an securely fastened in place by an approved means within 300 mm (12 approved means within 300 mm (12 in.) of each box, cabinet, conduit body, in.) of each box, cabinet, conduit body, or other conduit termination and shall or other conduit termination and shall be supported and secured at intervals be supported and secured at intervals not to exceed 1.4 m (41⁄2 ft). not to exceed 1.4 m (41⁄2 ft). Page 147 of 361 70 2008 851 Evaluation 2005 NEC Exception No. 1: Where LFMC is fished. 2008 NEC Change Description and Impact to Worker Safety Exception No. 1: Where LFMC is fished between access points through concealed spaces in finished buildings or structures and supporting is impractical. Exception No. 2: Where flexibility is necessary after installation, lengths shall not exceed the following: (1) 900 mm (3 ft) for metric designators 16 through 35 (trade sizes 1⁄2 through 11⁄4) (2) 1200 mm (4 ft) for metric designators 41 through 53 (trade sizes 11⁄2 through 2) (3) 1500 mm (5 ft) for metric designators 63 (trade size 21⁄2) and larger 350.60 Grounding and Bonding. Where 350.60 Grounding and Bonding. Where used to connect equipment where used to connect equipment where flexibility is required, an equipment flexibility is required after installation, grounding conductor shall be installed. an equipment grounding conductor Where flexibility is not required, LFMC shall be installed. shall be permitted to be used as an Where flexibility is not required after equipment grounding conductor when installation, LFMC shall be permitted to installed in accordance with be used as an equipment grounding 250.118(6). conductor when installed in accordance with 250.118(6). Article 352 Page 148 of 361 Inserted “after installation” to indicate that the requirement is intended for the installed condition, not for installation purposes. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Rigid Nonmetallic Conduit: Type RNC Rigid Polyvinyl Chloride Conduit: Type PVC I. General I. General 352.1 Scope. This article covers the use, installation, and construction specifications for rigid nonmetallic conduit (RNC) and associated fittings. 352.1 Scope. This article covers the use, installation, and construction specifications for rigid polyvinyl chloride conduit (PVC) and associated fittings. 352.2 Definition. 352.2 Definition. Rigid Nonmetallic Conduit (RNC). A nonmetallic raceway of circular cross section, with integral or associated couplings, connectors, and fittings for the installation of electrical conductors and cables. Rigid Polyvinyl Chloride Conduit (PVC). A rigid nonmetallic conduit (RNC) of circular cross section, with integral or associated couplings, connectors, and fittings for the installation of electrical conductors and cables. II. Installation II. Installation 352.10 Uses Permitted. The use of RNC shall be permitted in accordance with 352.10(A) through (H). 352.10 Uses Permitted. The use of PVC conduit shall be permitted in accordance with 352.10(A) through Page 149 of 361 Change Description and Impact to Worker Safety This article was changed to specifically address rigid polyvinyl chloride conduit (PVC) as opposed to other types of conduit some believed to fit the requirements rigid nonmetallic conduit (RNC). As Safe or Safer. This article was changed to specifically address rigid polyvinyl chloride conduit (PVC) as opposed to other types of conduit some believed to fit the requirements rigid nonmetallic conduit (RNC). As Safe or Safer. Throughout Article 352, PVC and polyvinyl chloride were inserted in lieu of RNC and rigid nonmetallic and will not be compared individually. The remaining changes in the article are addressed in the subsequent table sections in this document. Clarified intent that conduit may be installed exposed but must be identified for use in areas of physical damage. 70 2008 851 Evaluation 2005 NEC 2008 NEC (H). (F) Exposed. RNC shall be permitted for exposed work where not subject to physical damage if identified for such use. 352.10 Uses Permitted. (G) Underground Installations. For underground installations, see 300.5 and 300.50. 352.12 Uses Not Permitted. RNC shall not be used under the following conditions. (A) Hazardous (Classified) Locations. (1) In hazardous (classified) locations, except as permitted in 503.10(A), 504.20, 514.8 Exception No. 2, and 515.8 (2) In Class I, Division 2 locations, except as permitted in 501.10(B)(3) 352.30 Securing and Supporting. RNC shall be installed as a complete system as provided in 300.18 and shall be fastened so that movement from (F) Exposed. PVC conduit shall be permitted for exposed work. PVC conduit used exposed in areas of physical damage shall be identified for the use. 352.10 Uses Permitted. (G) Underground Installations. For underground installations, homogenous and nonhomogenous PVC shall be permitted for direct burial and underground encased in concrete. See 300.5 and 300.50. 352.12 Uses Not Permitted. PVC conduit shall not be used under the conditions specified in 352.12(A) through (F). (A) Hazardous (Classified) Locations. In any hazardous (classified) location, except as permitted by other articles of this Code. Change Description and Impact to Worker Safety As Safe or Safer. Clarified intent that both homogenous and nonhomogenous PVC can be used underground and in concrete. As Safe or Safer. Changed the hazardous location requirement to allow for the other sections of the Code that contain permissions. As Safe or Safer. 352.30 Securing and Supporting. PVC conduit shall be installed as a complete system as provided in 300.18 and shall be fastened so that movement from Page 150 of 361 Part of the overall effort to address securing and supporting conduits and to include conditions for not supporting by reference to new section. 70 2008 851 Evaluation 2005 NEC thermal expansion or contraction is permitted. RNC shall be securely fastened and supported in accordance with 352.30(A) and (B). 352.30 Securing and Supporting. 2008 NEC thermal expansion or contraction is permitted. PVC conduit shall be securely fastened and supported in accordance with 352.30(A) and (B) or permitted to be unsupported in accordance with 352.30(C). 352.30 Securing and Supporting. Change Description and Impact to Worker Safety As Safe or Safer. New section to specify the allowable methods for installing PVC unsupported. (C) Unsupported Raceways. Where oversized, concentric or eccentric knockouts are not encountered, PVC As Safe or Safer. conduit shall be permitted to be unsupported where the raceway is not more than 450 mm (18 in.) and remains in unbroken lengths (without coupling). Such raceway shall terminate in an outlet box, junction box, device box, cabinet, or other termination at each end of the raceway. III. Construction Specifications III. Construction Specifications This article was changed to specifically address rigid polyvinyl chloride conduit 352.100 Construction. RNC and fittings 352.100 Construction. PVC conduit (PVC) as opposed to other types of shall be composed of suitable shall be made of rigid (nonplasticized) conduit some believed to fit the nonmetallic material that is resistant to polyvinyl chloride (PVC). PVC conduit requirements rigid nonmetallic conduit moisture and chemical atmospheres. and fittings shall be composed of (RNC). For use above ground, it shall also be suitable nonmetallic material that is flame retardant, resistant to impact and resistant to moisture and chemical As Safe or Safer. crushing, resistant to distortion from atmospheres. For use aboveground, it heat under conditions likely to be shall also be flame retardant, resistant encountered in service, and resistant to impact and crushing, resistant to Page 151 of 361 70 2008 851 Evaluation 2005 NEC to low temperature and sunlight effects. For use underground, the material shall be acceptably resistant to moisture and corrosive agents and shall be of sufficient strength to withstand abuse, such as by impact and crushing, in handling and during installation. Where intended for direct burial, without encasement in concrete, the material shall also be capable of withstanding continued loading that is likely to be encountered after installation. 2008 NEC Change Description and Impact to Worker Safety II. Installation distortion from heat under conditions likely to be encountered in service, and resistant to low temperature and sunlight effects. For use underground, the material shall be acceptably resistant to moisture and corrosive agents and shall be of sufficient strength to withstand abuse, such as by impact and crushing, in handling and during installation. Where intended for direct burial, without encasement in concrete, the material shall also be capable of withstanding continued loading that is likely to be encountered after installation. Article 353 High Density Polyethylene Conduit: Added provision (5) to address the Type HDPE Conduit need to allow above ground installations with the exclusions II. Installation addressed in 353.12 enforced. 353.10 Uses Permitted. The use of HDPE conduit shall be permitted under the following conditions: (1) In discrete lengths or in continuous lengths from a reel (2) In locations subject to severe corrosive influences as covered in 300.6 and where subject to chemicals for which the conduit is listed (3) In cinder fill 353.10 Uses Permitted. The use of HDPE conduit shall be permitted under the following conditions: (1) In discrete lengths or in continuous lengths from a reel (2) In locations subject to severe corrosive influences as covered in 300.6 and where subject to chemicals for which the conduit is listed (3) In cinder fill High Density Polyethylene Conduit: Type HDPE Conduit Page 152 of 361 As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC (4) In direct burial installations in earth or concrete (5) Above ground, except as prohibited in 353.12, where encased in not less than 50 mm (2 in.) of concrete. 353.12 Uses Not Permitted. HDPE 353.12 Uses Not Permitted. HDPE conduit shall not be conduit shall not be used under the used under the following conditions: following conditions: (1) Where exposed (1) Where exposed (2) Within a building (2) Within a building (3) In hazardous (classified) locations, (3) In any hazardous (classified) except as permitted in 504.20 location, except as permitted by other articles in this Code (4) Where subject to ambient (4) Where subject to ambient temperatures in excess of 50°C temperatures in excess of 50°C (122°F) unless listed otherwise (122°F) unless listed otherwise (5) For conductors or cables operating (5) For conductors or cables operating at a temperature higher than the HDPE at a temperature higher than the HDPE conduit listed operating temperature conduit listed operating temperature rating rating 353.20 Size. 353.20 Size. Change Description and Impact to Worker Safety (4) In direct burial installations in earth or concrete (B) Maximum. HDPE conduit larger than metric designator 103 (trade size 4) shall not be used. Nonmetallic Underground Conduit with Conductors: Type NUCC (B) Maximum. HDPE conduit larger than metric designator 155 (trade size 6) shall not be used. Article 354 Nonmetallic Underground Conduit with Conductors: Type NUCC II. Installation II. Installation Page 153 of 361 Made allowance for exceptions granted by other Code sections rather than a specific single section. As Safe or Safer. Allows for larger size limit of HDPE conduit to be utilized. As Safe or Safer. Added provision (5) to address the need to allow above ground installations with the exclusions addressed in 354.12 enforced. 70 2008 851 Evaluation 2005 NEC 2008 NEC 354.10 Uses Permitted. The use of NUCC and fittings shall be permitted in the following: (1) For direct burial underground installation (For minimum cover requirements, see Table 300.5 and Table 300.50 under Rigid Nonmetallic Conduit.) (2) Encased or embedded in concrete (3) In cinder fill (4) In underground locations subject to severe corrosive influences as covered in 300.6 and where subject to chemicals for which the assembly is specifically approved 354.10 Uses Permitted. The use of NUCC and fittings shall be permitted in the following: (1) For direct burial underground installation (For minimum cover requirements, see Table 300.5 and Table 300.50 under Rigid Nonmetallic Conduit.) (2) Encased or embedded in concrete (3) In cinder fill (4) In underground locations subject to severe corrosive influences as covered in 300.6 and where subject to chemicals for which the assembly is specifically approved (5) Aboveground, except as prohibited in 354.12, where encased in not less than 50 mm (2 in.) of concrete. 354.12 Uses Not Permitted. NUCC shall not be used in the following: (1) In exposed locations (2) Inside buildings 354.12 Uses Not Permitted. NUCC shall not be used in the following: (1) In exposed locations (2) Inside buildings Change Description and Impact to Worker Safety As Safe or Safer. Made allowance for exceptions granted by other Code sections rather than addressing specific sections. As Safe or Safer. Exception: The conductor or the cable portion of the assembly, where suitable, shall be permitted to extend within the building for termination purposes in accordance with 300.3. Exception: The conductor or the cable portion of the assembly, where suitable, shall be permitted to extend within the building for termination purposes in accordance with 300.3. (3) In hazardous (classified) locations except as permitted by 503.10(A), (3) In any hazardous (classified) location, except as permitted Page 154 of 361 70 2008 851 Evaluation 2005 NEC 504.20, 514.8, and 515.8, and in Class I, Division 2 locations as permitted in 501.10(B)(3) 2008 NEC Change Description and Impact to Worker Safety by other articles of this Code Liquidtight Flexible Nonmetallic Conduit: Type LFNC Article 356 Liquidtight Flexible Nonmetallic Conduit: Type LFNC New section to address use in concrete encased installations. II. Installation II. Installation As Safe or Safer. 356.10 Uses Permitted. LFNC shall be permitted to be used in exposed or concealed locations for the following purposes: 356.10 Uses Permitted. LFNC shall be permitted to be used in exposed or concealed locations for the following purposes: 356.12 Uses Not Permitted. LFNC shall not be used as follows: (7) For encasement in concrete where listed for direct burial and installed in compliance with 356.42. 356.12 Uses Not Permitted. LFNC shall not be used as follows: (5) In any hazardous (classified) location other than as permitted in 501.10(B), 502.10(A) and (B), 503.10(A), and 504.20 356.20 Size. (A) Minimum. LFNC smaller than metric designator 16 (trade size 1⁄2) shall not be used unless permitted in 356.20(A)(1) through (A)(3) for metric designator 12 (trade size 3⁄8). (1) For enclosing the leads of motors (5) In any hazardous (classified) location, except as permitted by other articles in this Code 356.20 Size. (A) Minimum. LFNC smaller than metric designator 16 (trade size 1⁄2) shall not be used unless permitted in 356.20(A)(1) or (A)(2) for metric designator 12 (trade size 3⁄8). (1) For enclosing the leads of motors Page 155 of 361 Made allowance for exceptions granted by other Code sections rather than addressing specific sections. As Safe or Safer. Deleted (3) due to the daisy chain reference provided in Article 600 that stated follow Chapter 3 which is already a requirement. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC as permitted in 430.245(B) (2) In lengths not exceeding 1.8 m (6 ft ) as part of a listed assembly for tap connections to luminaires (lighting fixtures) as required in 410.67(C), or for utilization equipment (3) For electric sign conductors in accordance with 600.32(A) 2008 NEC Change Description and Impact to Worker Safety as permitted in 430.245(B) (2) In lengths not exceeding 1.8 m (6 ft ) as part of a listed assembly for tap connections to luminaires as required in 410.117(C), or for utilization equipment Electrical Metallic Tubing: Type EMT Article 358 Electrical Metallic Tubing: Type EMT 358.12 Uses Not Permitted. EMT shall not be used under the following conditions: 358.12 Uses Not Permitted. EMT shall not be used under the following conditions: (4) In any hazardous (classified) location except as permitted by 502.10, 503.10, and 504.20 358.30 Securing and Supporting. EMT shall be installed as a complete system in accordance with 300.18 and shall be securely fastened in place and supported in accordance with 358.30(A) and (B). (4) In any hazardous (classified) location except as permitted by other articles in this Code. 358.30 Securing and Supporting. EMT shall be installed as a complete system in accordance with 300.18 and shall be securely fastened in place and supported in accordance with 358.30(A) and (B) or permitted to be unsupported in accordance with 358.30(C). (C) Unsupported Raceways. Where oversized, concentric or eccentric knockouts are not encountered, Type EMT shall be permitted to be unsupported where the raceway is not Page 156 of 361 Made allowance for exceptions granted by other Code sections rather than addressing specific sections. As Safe or Safer. Part of the overall effort to address securing and supporting conduits and to include conditions for not supporting by reference to new section. As Safe or Safer. New section to specify the allowable methods for installing EMT unsupported. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Electrical Nonmetallic Tubing: Type ENT more than 450 mm (18 in.) and remains in unbroken lengths (without coupling). Such raceways shall terminate in an outlet box, device box, cabinet, or other termination at each end of the raceway. Article 362 Electrical Nonmetallic Tubing: Type ENT 362.12 Uses Not Permitted. ENT shall not be used in the following: (1) In hazardous (classified) locations, except as permitted by 504.20 and 505.15(A)(1) 362.30 Securing and Supporting. ENT shall be installed as a complete system in accordance with 300.18 and shall be securely fastened in place and supported in accordance with 362.30(A) and (B). 362.12 Uses Not Permitted. ENT shall not be used in the following: (1) In any hazardous (classified) location, except as permitted by other articles in this Code 362.30 Securing and Supporting. ENT shall be installed as a complete system in accordance with 300.18 and shall be securely fastened in place and supported in accordance with 362.30(A) and (B). (A) Securely Fastened. ENT shall be securely fastened at intervals not exceeding 900 mm (3 ft). In addition, ENT shall be securely fastened in place within 900 mm (3 ft) of each outlet box, device box, junction box, cabinet, or fitting where it terminates. (A) Securely Fastened. ENT shall be securely fastened at intervals not exceeding 900 mm (3 ft). In addition, ENT shall be securely fastened in place within 900 mm (3 ft) of each outlet box, device box, junction box, cabinet, or fitting where it terminates. Exception No. 3: For concealed work in Page 157 of 361 Change Description and Impact to Worker Safety Made allowance for exceptions granted by other Code sections rather than addressing specific sections. As Safe or Safer. New exception (3) added to address specific requirements for fished ENT conduits. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Auxiliary Gutters finished buildings or prefinished wall panels where such securing is impracticable, unbroken lengths (without coupling) of ENT shall be permitted to be fished. 362.60 Grounding. Where equipment grounding is required, a separate equipment grounding conductor shall be installed in the raceway in compliance with Article 250, Part VI. Article 366 Auxiliary Gutters 366.2 Definitions. 366.2 Definitions. Metallic Auxiliary Gutters. Sheet metal enclosures with hinged or removable covers for housing and protecting electric wires, cable, and busbars in which conductors are laid in place after the wireway has been installed as a complete system. Metallic Auxiliary Gutter. A sheet metal enclosure used to supplement wiring spaces at meter centers, distribution centers, switchboards, and similar points of wiring systems. The enclosure has hinged or removable covers for housing and protecting electrical wires, cable, and busbars. The enclosure is designed for conductors to be laid or set in place after the enclosures have been installed as a complete system. Nonmetallic Auxiliary Gutters. Flame retardant, nonmetallic enclosures with removable covers for housing and Nonmetallic Auxiliary Gutter. A flame retardant, nonmetallic enclosure used to supplement wiring spaces at meter 362.60 Grounding. Where equipment grounding is required, a separate equipment grounding conductor shall be installed in the raceway. Page 158 of 361 Change Description and Impact to Worker Safety Added the specific requirements for the grounding conductor. Will actually improve worker safety working on these systems. Rewrite of the two definitions to specifically address the function and installation techniques required for auxiliary gutters. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC protecting electric wires, cable, and busbars in which conductors are laid in place after the wireway has been installed as a complete system. centers, distribution centers, switchboards, and similar points of wiring systems. The enclosure has hinged or removable covers for housing and protecting electrical wires, cable, and busbars. The enclosure is designed for conductors to be laid or set in place after the enclosures have been installed as a complete system. II. Installation II. Installation 366.10 Uses Permitted. Auxiliary gutters shall be permitted to supplement wiring spaces at meter centers, distribution centers, switchboards, and similar points of wiring systems and may enclose conductors or busbars. 366.10 Uses Permitted. (A) Sheet Metal Auxiliary Gutters. 366.60 Grounding. Metal auxiliary gutters shall be grounded. Busways (A) Sheet Metal Auxiliary Gutters. 366.60 Grounding. Metal auxiliary gutters shall be connected to an equipment grounding conductor(s), to an equipment bonding jumper, or to the grounded conductor where permitted or required by 250.92(B)(1) or 250.142. Article 368 Busways 368.56 Branches from Busways. 368.56 Branches from Busways. Page 159 of 361 Change Description and Impact to Worker Safety Moved verbiage into the definition section for the two types of gutters. As Safe or Safer. Specifies the grounding requirements for gutters. Will actually improve worker safety working on these systems. Modified (8) for the PVC changes and inserted “Type RTRC reinforced thermosetting resin conduit” as (9). 70 2008 851 Evaluation 2005 NEC 2008 NEC Branches from busways shall be permitted to be made in accordance with 368.56(A), (B), and (C). Branches from busways shall be permitted to be made in accordance with 368.56(A), (B), and (C). (A) General. Branches from busways shall be permitted to use any of the following wiring methods: (A) General. Branches from busways shall be permitted to use any of the following wiring methods: (1) Type AC armored cable (2) Type MC metal-clad cable (3) Type MI mineral-insulated, metalsheathed cable (4) Type IMC intermediate metal conduit (5) Type RMC rigid metal conduit (6) Type FMC flexible metal conduit (7) Type LFMC liquidtight flexible metal conduit (8) Type RNC rigid nonmetallic conduit (9) Type LFNC liquidtight flexible nonmetal conduit (10) Type EMT electrical metallic tubing (11) Type ENT electrical nonmetallic tubing (12) Busways (13) Strut-type channel raceway (14) Surface metal raceways (15) Surface nonmetallic raceways (1) Type AC armored cable (2) Type MC metal-clad cable (3) Type MI mineral-insulated, metalsheathed cable (4) Type IMC intermediate metal conduit (5) Type RMC rigid metal conduit (6) Type FMC flexible metal conduit (7) Type LFMC liquidtight flexible metal conduit (8) Type PVC rigid polyvinyl chloride conduit (9) Type RTRC reinforced thermosetting resin conduit (10) Type LFNC liquidtight flexible nonmetallic conduit (11) Type EMT electrical metallic tubing (12) Type ENT electrical nonmetallic tubing (13) Busways (14) Strut-type channel raceway (15) Surface metal raceway Page 160 of 361 Change Description and Impact to Worker Safety As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 368.60 Grounding. Busway shall be grounded. Metal Wireways 376.22 Number of Conductors. The sum of the cross-sectional areas of all contained conductors at any cross section of a wireway shall not exceed 20 percent of the interior crosssectional area of the wireway. The derating factors in 310.15(B)(2)(a) shall be applied only where the number of current-carrying conductors, including neutral conductors classified as current-carrying under the provisions of 310.15(B)(4), exceeds 30. Conductors for signaling circuits or controller conductors between a motor and its starter and used only for starting duty shall not be considered as currentcarrying conductors. 2008 NEC (16) Surface nonmetallic raceway 368.60 Grounding. Busway shall be connected to an equipment grounding conductor(s), to an equipment bonding jumper, or to the grounded conductor where permitted or required by 250.92(B)(1) or 250.142. Article 376 Metal Wireways 376.22 Number of Conductors and Ampacity. The number of conductors and their ampacity shall comply with 376.22(A) and (B). Change Description and Impact to Worker Safety Specifies the grounding requirements for busways. Will actually improve worker safety working on these systems. Expanded version of 376.22 points to the same basic requirements, but more appropriately addresses the basis for the limitation of the number of conductors allowed. As Safe or Safer. (A) Cross-Sectional Areas of Wireway. The sum of the cross-sectional areas of all contained conductors at any cross section of a wireway shall not exceed 20 percent of the interior crosssectional area of the wireway. (B) Adjustment Factors. The adjustment factors in 310.15(B)(2)(a) shall be applied only where the number of current-carrying conductors, including neutral conductors classified as current-carrying under the provisions of 310.15(B)(4), exceeds 30. Conductors for signaling circuits or controller conductors between a motor Page 161 of 361 70 2008 851 Evaluation 2005 NEC 376.56 Splices, Taps, and Power Distribution Blocks. (B) Power Distribution Blocks. (4) Live Parts. Power distribution blocks shall not have exposed live parts in the wireway after installation. III. Construction Specifications 2008 NEC Change Description and Impact to Worker Safety and its starter and used only for starting duty shall not be considered as current-carrying conductors. 376.56 Splices, Taps, and Power Modified to clarify the confusion Distribution Blocks. surrounding what qualified as “exposed” since, with the cover on, the (B) Power Distribution Blocks. live parts were not exposed outside of the wireway. (4) Live Parts. Power distribution blocks shall not have uninsulated live May actually provide a safer work parts exposed within a wireway, environment for the electrical worker. whether or not the wireway cover is installed. III. Construction Specifications New section addressing the specific requirements for wireway construction. 376.100 Construction. May actually provide a safer work (A) Electrical and Mechanical environment for the electrical worker. Continuity. Wireways shall be constructed and installed so that adequate electrical and mechanical continuity of the complete system is secured. (B) Substantial Construction. Wireways shall be of substantial construction and shall provide a complete enclosure for the contained conductors. All surfaces, both interior and exterior, shall be suitably protected from corrosion. Corner joints shall be made tight, and Page 162 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety where the assembly is held together by rivets, bolts, or screws, such fasteners shall be spaced not more than 300 mm (12 in.) apart. (C) Smooth Rounded Edges. Suitable bushings, shields, or fittings having smooth, rounded edges shall be provided where conductors pass between wireways, through partitions, around bends, between wireways and cabinets or junction boxes, and at other locations where necessary to prevent abrasion of the insulation of the conductors. Nonmetallic Extensions (D) Covers. Covers shall be securely fastened to the wireway. Article 382 Nonmetallic Extensions 382.2 Definition. 382.2 Definitions. Nonmetallic Extension. An assembly of two insulated conductors within a nonmetallic jacket or an extruded thermoplastic covering. The classification includes surface extensions intended for mounting directly on the surface of walls or ceilings. Concealable Nonmetallic Extension. A listed assembly of two, three, or four insulated circuit conductors within a nonmetallic jacket, an extruded As Safe or Safer. thermoplastic covering, or a sealed nonmetallic covering. The classification includes surface extensions intended for mounting directly on the surface of Page 163 of 361 Expands the original definition to include “listed assembly”, the fact that the unit may be concealed by dry wall finishing or similar materials and that a sealed non-metallic covering is acceptable. 70 2008 851 Evaluation 2005 NEC 382.10 Uses Permitted. Nonmetallic extensions shall be permitted only in accordance with 382.10(A), (B), and (C). (A) From an Existing Outlet. The extension shall be from an existing outlet on a 15- or 20-ampere branch circuit. 2008 NEC walls or ceilings, and concealed with paint, texture, joint compound, plaster, wallpaper, tile, wall paneling, or other similar materials. 382.6 Listing Requirements. Concealable nonmetallic extensions and associated fittings and devices shall be listed. The starting/source tap device for the extension shall contain and provide the following protection for all load-side extensions and devices. (1) Supplementary overcurrent protection (2) Level of protection equivalent to a Class A GFCI (3) Level of protection equivalent to a portable GFCI (4) Line and load-side miswire protection (5) Provide protection from the effects of arc faults 382.10 Uses Permitted. Nonmetallic extensions shall be permitted only in accordance with 382.10(A), (B), and (C). Change Description and Impact to Worker Safety New section to clearly state the listing requirements. As Safe or Safer. Provides specific guidance for determining the grounding requirements for these units. May actually provide a safer work (A) From an Existing Outlet. The environment for the electrical worker. extension shall be from an existing outlet on a 15- or 20-ampere branch circuit. Where a concealable nonmetallic extension originates from a Page 164 of 361 70 2008 851 Evaluation 2005 NEC 382.10 Uses Permitted. (B) Exposed and in a Dry Location. The extension shall be run exposed and in a dry location. 382.10 Uses Permitted. 2008 NEC non–grounding-type receptacle, the installation shall comply with 250.130(C), 406.3(D)(3)(b), or 406.3(D)(3)(c). 382.10 Uses Permitted. (B) Exposed and in a Dry Location. The extension shall be run exposed, or concealed as permitted in 382.15, and in a dry location. 382.10 Uses Permitted. (C) Residential or Offices. For nonmetallic surface extensions mounted directly on the surface of walls or ceilings, the building shall be occupied for residential or office purposes and shall not exceed three floors above grade. (C) Residential or Offices. For nonmetallic surface extensions mounted directly on the surface of walls or ceilings, the building shall be occupied for residential or office purposes and shall not exceed three floors above grade. Where identified for the use, concealable nonmetallic extensions shall be permitted more than three floors above grade. 382.15 Exposed. One or more extensions shall be permitted to be run in any direction from an existing outlet, but not on the floor or within 50 mm (2 in.) from the floor. 382.15 Exposed. (A) Nonmetallic Extensions. One or more extensions shall be permitted to be run in any direction from an existing outlet, but not on the floor or within 50 mm (2 in.) from the floor. Page 165 of 361 Change Description and Impact to Worker Safety Allows for the new concealed installation provisions. As Safe or Safer. Allows for the new concealed installation provisions. As Safe or Safer. Allows for the new concealed installation provisions. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC (B) Concealable Nonmetallic Extensions. Where identified for the use, nonmetallic extensions may be concealed with paint, texture, concealing compound, plaster, wallpaper, tile, wall paneling, or other similar materials and installed per 382.15(A). 382.26 Bends. A bend that reduces the 382.26 Bends. normal spacing between the conductors shall be covered with a cap (A) Nonmetallic Extensions. A bend to protect the assembly from physical that reduces the normal spacing damage. between the conductors shall be covered with a cap to protect the assembly from physical damage. 382.30 Securing and Supporting. Nonmetallic surface extensions shall be secured in place by approved means at intervals not exceeding 200 mm (8 in.), with an allowance for 300 mm (12 in.) to the first fastening where the connection to the supplying outlet is by means of an attachment plug. There shall be at least one fastening between each two adjacent outlets (B) Concealable Nonmetallic Extensions. Concealable extensions shall be permitted to be folded back over themselves and flattened as required for installation. 382.30 Securing and Supporting. (A) Nonmetallic Extensions. Nonmetallic surface extensions shall be secured in place by approved means at intervals not exceeding 200 mm (8 in.), with an allowance for 300 mm (12 in.) to the first fastening where the connection to the supplying outlet is by means of an attachment plug. Page 166 of 361 Change Description and Impact to Worker Safety Allows for the new concealed installation provisions. As Safe or Safer. Allows for the new concealed installation provisions. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC supplied. An extension shall be attached to only woodwork or plaster finish and shall not be in contact with any metal work or other conductive material other than with metal plates on receptacles. 2008 NEC Change Description and Impact to Worker Safety There shall be at least one fastening between each two adjacent outlets supplied. An extension shall be attached to only woodwork or plaster finish and shall not be in contact with any metal work or other conductive material other than with metal plates on receptacles. (B) Concealable Nonmetallic Extensions. All surface mounted concealable nonmetallic extension components shall be firmly anchored to the wall or ceiling using an adhesive or mechanical anchoring system identified for this use. 382.40 Boxes and Fittings. Each run 382.40 Boxes and Fittings. Each run Allows for termination of the run in a shall terminate in a fitting that covers shall terminate in a fitting, connector, connector or box in addition to a fitting. the end of the assembly. All fittings and or box that covers the end of the devices shall be of a type identified for assembly. All fittings, connectors, and As Safe or Safer. the use. devices shall be of a type identified for the use. 382.42 Devices. (A) Receptacles. All receptacles, receptacle housings, and selfcontained devices used with concealable nonmetallic extensions shall be identified for this use. Page 167 of 361 New section to cover the devices used with non-metallic extensions. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety (B) Receptacles and Housings. Receptacle housings and selfcontained devices designed either for surface or for recessed mounting shall be permitted for use with concealable nonmetallic extensions. Receptacle housings and self contained devices shall incorporate means for facilitating entry and termination of concealable nonmetallic extensions and for electrically connecting the housing or device. Receptacle and self-contained devices shall comply with 406.3. Power and communications outlets installed together in common housing shall be permitted in accordance with 800.133(A)(1)(c), Exception No. 2. III. Construction Specifications New section to address the new (Concealable Nonmetallic Extensions Concealable Nonmetallic Extensions only) provisions. 382.100 Construction. Concealable nonmetallic extensions shall be a multilayer flat conductor design consisting of a center ungrounded conductor enclosed by a sectioned grounded conductor, and an overall sectioned grounding conductor. 382.104 Flat Conductors. Concealable nonmetallic extensions shall be Page 168 of 361 As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC constructed, using flat copper conductors equivalent to 14 AWG or 12 AWG conductor sizes, and constructed per 382.104(A), (B), and (C). (A) Ungrounded Conductor (Center Layer). The ungrounded conductor shall consist of one or more ungrounded flat conductor(s) enclosed per 382.104(B) and (C) and identified in accordance with 310.12(C). (B) Grounded Conductor (Inner Sectioned Layers). The grounded conductor shall consist of two sectioned inner flat conductors that enclose the center ungrounded conductor(s). The sectioned grounded conductor shall be enclosed by the sectioned grounding conductor and identified in accordance with 200.6. (C) Grounding Conductor (Outer Sectioned Layers). The grounding conductor shall consist of two overall sectioned conductors that enclose the grounded conductor and ungrounded conductor(s) and shall comply with 250.4(A)(5). The grounding conductor layers shall be identified by any one of Page 169 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC the following methods: (1) As permitted in 250.119 (2) A clear covering (3) One or more continuous green stripes or hash marks (4) The term ″Equipment Ground″ printed at regular intervals throughout the cable 382.112 Insulation. The ungrounded and grounded flat conductor layers shall be individually insulated and comply with 310.10. The grounding conductor shall be covered or insulated. 382.120 Marking. (A) Cable. Concealable nonmetallic extensions shall be clearly and durably marked on both sides at intervals of not more than 610 mm (24 in.) with the information required by 310.11(A) and with the following additional information: (1) Material of conductors (2) Maximum temperature rating (3) Ampacity (B) Conductor Identification. Page 170 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC Conductors shall be clearly and durably identified on both sides throughout their length as specified in 382.104. Article 388 Surface Nonmetallic Raceways 388.30 Securing and Supporting. Surface nonmetallic raceways shall be supported at intervals in accordance with the manufacturer’s installation instructions. 388.56 Splices and Taps. Splices and 388.56 Splices and Taps. Splices and taps shall be permitted in surface taps shall be permitted in surface nonmetallic raceways having a nonmetallic raceways having a cover removable cover that is accessible capable of being opened in place that after installation. The conductors, is accessible after installation. The including splices and taps, shall not fill conductors, including splices and taps, the raceway to more than 75 percent of shall not fill the raceway to more than its area at that point. Splices and taps 75 percent of its area at that point. in surface nonmetallic raceways Splices and taps in surface nonmetallic without removable covers shall be raceways without covers capable of made only in boxes. All splices and being opened in place shall be made taps shall be made by approved only in boxes. All splices and taps shall methods. be made by approved methods. Article 392 Cable Trays Cable Trays Change Description and Impact to Worker Safety New section to address securing and supporting requirements of these raceways. As Safe or Safer. Inserted “capable of being opened in place” to differentiate from covers that actually separate from the raceway. As Safe or Safer. 392.7 Grounding. 392.7 Grounding. Modified to reinforce the grounding conductor requirements for tray installations. (A) Metallic Cable Trays. Metallic cable (A) Metallic Cable Trays. Metallic cable May actually provide a safer work Page 171 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC trays that support electrical conductors shall be grounded as required for conductor enclosures in accordance with 250.96. trays that support electrical conductors shall be grounded as required for conductor enclosures in accordance with 250.96 and Part IV of Article 250. (B) Steel or Aluminum Cable Tray Systems. Steel or aluminum cable tray systems shall be permitted to be used as equipment grounding conductors, provided that all the following requirements are met: (B) Steel or Aluminum Cable Tray Systems. Steel or aluminum cable tray systems shall be permitted to be used as equipment grounding conductors, provided all the following requirements are met: (1) The cable tray sections and fittings shall be identified for grounding purposes. 392.8 Cable Installation. (1) The cable tray sections and fittings are identified as an equipment grounding conductor. 392.8 Cable Installation. (A) Cable Splices. Cable splices made and insulated by approved methods shall be permitted to be located within a cable tray, provided they are accessible and do not project above the side rails. 392.9 Number of Multiconductor Cables, Rated 2000 Volts or Less, in Cable Trays. (A) Cable Splices. Cable splices made and insulated by approved methods shall be permitted to be located within a cable tray, provided they are accessible. Splices shall be permitted to project above the side rails where not subject to physical damage. 392.9 Number of Multiconductor Cables, Rated 2000 Volts or Less, in Cable Trays. (A) Any Mixture of Cables. (A) Any Mixture of Cables. (1) Where all of the cables are 4/0 (1) Where all of the cables are 4/0 Change Description and Impact to Worker Safety environment for the electrical worker. Makes an allowance for splices where they are not subject to physical damage. As Safe or Safer. Provides for the tray width requirements not previously referenced when ampacity may impact the physical relationships. As Safe or Safer. Page 172 of 361 70 2008 851 Evaluation 2005 NEC AWG or larger, the sum of the diameters of all cables shall not exceed the cable tray width, and the cables shall be installed in a single layer. 392.11 Ampacity of Cables, Rated 2000 Volts or Less, in Cable Trays. 2008 NEC AWG or larger, the sum of the diameters of all cables shall not exceed the cable tray width, and the cables shall be installed in a single layer. Where the cable ampacity is determined according to 392.11(A)(3), the cable tray width shall not be less than the sum of the diameters of the cables and the sum of the required spacing widths between the cables. 392.11 Ampacity of Cables, Rated 2000 Volts or Less, in Cable Trays. Change Description and Impact to Worker Safety New section to specifically address requirements for the situation where multiconductor and single conductor (C) Combinations of Multiconductor cables must be installed in the same and Single-Conductor Cables. Where a tray. cable tray contains a combination of multiconductor and single-conductor As Safe or Safer. cables, the allowable ampacities shall be as given in 392.11(A) for multiconductor cables and 392.11(B) for single-conductor cables, provided that the following conditions apply: (1) The sum of the multiconductor cable fill area as a percentage of the allowable fill area for the tray calculated per 392.9, and the singleconductor cable fill area as a percentage of the allowable fill area for the tray calculated per 392.10, totals not more than 100 percent. Page 173 of 361 70 2008 851 Evaluation 2005 NEC Messenger-Supported Wiring 396.30 Messenger Support. The messenger shall be supported at dead ends and at intermediate locations so as to eliminate tension on the conductors. The conductors shall not be permitted to come into contact with the messenger supports or any structural members, walls, or pipes. 2008 NEC (2) Multiconductor cables are installed according to 392.9 and singleconductor cables are installed according to 392.10 and 392.8(D) and (E). Article 396 Messenger-Supported Wiring 396.30 Messenger. (A) Support. The messenger shall be supported at dead ends and at intermediate locations so as to eliminate tension on the conductors. The conductors shall not be permitted to come into contact with the messenger supports or any structural members, walls, or pipes. (B) Neutral Conductor. Where the messenger is used as a neutral conductor, it shall comply with the requirements of 225.4, 250.184(A), 250.184(B)(7), and 250.186(B). (C) Equipment Grounding Conductor. Where the messenger is used as an equipment grounding conductor, it shall comply with the requirements of 250.32(B), 250.118, 250.184(B)(8), Page 174 of 361 Change Description and Impact to Worker Safety New sections to provide the requirements for the situations where the messenger is used for either a neutral conductor or an equipment grounding conductor. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 400.5 Ampacities for Flexible Cords and Cables. and 250.186(D). Article 400 400.5 Ampacities for Flexible Cords and Cables. (B) Ultimate Insulation Temperature. In no case shall conductors be associated together in such a way with respect to the kind of circuit, the wiring method used, or the number of conductors such that the limiting temperature of the conductors is exceeded. A neutral conductor that carries only the unbalanced current from other conductors of the same circuit shall not be required to meet the requirements of a current-carrying conductor. In a 3-wire circuit consisting of two phase wires and the neutral of a 4wire, 3-phase, wye-connected system, a common conductor carries approximately the same current as the line-to-neutral currents of the other conductors and shall be considered to be a current-carrying conductor. On a 4-wire, 3-phase, wye circuit where the major portion of the load consists of nonlinear loads, there are harmonic currents present in the neutral conductor and the neutral shall (B) Ultimate Insulation Temperature. In no case shall conductors be associated together in such a way with respect to the kind of circuit, the wiring method used, or the number of conductors such that the limiting temperature of the conductors is exceeded. A neutral conductor that carries only the unbalanced current from other conductors of the same circuit shall not be required to meet the requirements of a current-carrying conductor. In a 3-wire circuit consisting of two phase conductors and the neutral conductor of a 4-wire, 3-phase, wye connected system, a common conductor carries approximately the same current as the line-to-neutral currents of the other conductors and shall be considered to be a currentcarrying conductor. On a 4-wire, 3-phase, wye circuit where more than 50 percent of the load consists of nonlinear loads, there are harmonic currents present in the Page 175 of 361 Change Description and Impact to Worker Safety Continued emphasis on conductors and the functional requirements of them and, in addition, provides specific criteria for determination of neutral conductor as a current carrying conductor. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC be considered to be a current-carrying conductor. An equipment grounding conductor shall not be considered a currentcarrying conductor. Where a single conductor is used for both equipment grounding and to carry unbalanced current from other conductors, as provided for in 250.140 for electric ranges and electric clothes dryers, it shall not be considered as a current-carrying conductor. 400.23 Equipment Grounding Conductor Identification. A conductor intended to be used as an equipment grounding conductor shall have a continuous identifying marker readily distinguishing it from the other conductor or conductors. Conductors having a continuous green color or a continuous green color with one or more yellow stripes shall not be used for other than equipment grounding purposes. The identifying marker shall consist of one of the methods in 400.23(A) or 400.23(B). III. Portable Cables Over 600 Volts, Nominal neutral conductor and the neutral conductor shall be considered to be a current carrying conductor. An equipment grounding conductor shall not be considered a currentcarrying conductor. Where a single conductor is used for both equipment grounding and to carry unbalanced current from other conductors, as provided for in 250.140 for electric ranges and electric clothes dryers, it shall not be considered as a current-carrying conductor. 400.23 Equipment Grounding Conductor Identification. A conductor intended to be used as an equipment grounding conductor shall have a continuous identifying marker readily distinguishing it from the other conductor or conductors. Conductors having a continuous green color or a continuous green color with one or more yellow stripes shall not be used for other than equipment grounding conductors. The identifying marker shall consist of one of the methods in 400.23(A) or (B). III. Portable Cables Over 600 Volts, Nominal 400.30 Scope. This part applies to 400.30 Scope. Part III applies to Page 176 of 361 Change Description and Impact to Worker Safety Continued emphasis on equipment grounding conductors and the functional requirements of them. As Safe or Safer. Reduced minimum size of conductors due to improved manufacturing processes and eliminated the exception since it no longer applies. 70 2008 851 Evaluation 2005 NEC 2008 NEC multiconductor portable cables used to connect mobile equipment and machinery. multiconductor portable cables used to connect mobile equipment and machinery. 400.31 Construction. (A) Conductors. The conductors shall be 8 AWG copper or larger and shall employ flexible stranding. 400.31 Construction. (A) Conductors. The conductors shall be 12 AWG copper or larger and shall employ flexible stranding. Exception: The size of the insulated ground-check conductor of Type G-GC cables shall be not smaller than 10 AWG. 400.32 Shielding. All shields shall be grounded. 400.33 Grounding. Grounding conductors shall be connected in accordance with Part V of Article 250. 400.32 Shielding. All shields shall be connected to an equipment grounding conductor. 400.33 Equipment Grounding Conductors. Equipment grounding conductors shall be connected in accordance with Parts VI and VII of Article 250. Change Description and Impact to Worker Safety As Safe or Safer. Continuing with the emphasis on “connected to an equipment grounding conductor….” versus just “grounded” provides assurance of a connection to ground. May actually improve worker safety. Continuing with the emphasis on “equipment grounding conductor” and specific reference sections provide assurance of a good connection to ground. May actually improve worker safety. Article 404 Switches Switches 404.4 Wet Locations. A switch or 404.4 Damp or Wet Locations. A Page 177 of 361 Expanded the section to include damp locations and to distinguish between surface-mounted and flush-mounted 70 2008 851 Evaluation 2005 NEC circuit breaker in a wet location or outside of a building shall be enclosed in a weatherproof enclosure or cabinet that shall comply with 312.2(A). Switches shall not be installed within wet locations in tub or shower spaces unless installed as part of a listed tub or shower assembly. 404.8 Accessibility and Grouping. 2008 NEC Change Description and Impact to Worker Safety requirements. surface-mounted switch or circuit breaker in a damp or wet location shall be enclosed in a weatherproof As Safe or Safer. enclosure or cabinet that shall comply with 312.2. A flush-mounted switch or circuit breaker in a damp or wet location shall be equipped with a weatherproof cover. Switches shall not be installed within wet locations in tub or shower spaces unless installed as part of a listed tub or shower assembly. 404.8 Accessibility and Grouping. Continuing the expansion of this section from last cycle, section (C) was (C) Multipole Snap Switches. A added to address multipole, generalmultipole, general-use snap switch use snap switches. shall not be permitted to be fed from more than a single circuit unless it is As Safe or Safer. listed and marked as a two-circuit or three-circuit switch, or unless its voltage rating is not less than the nominal line-to-line voltage of the system supplying the circuits. 404.9 Provisions for General-Use Snap 404.9 Provisions for General-Use Snap Inserted “connected to an equipment Switches. Switches. grounding conductor” in lieu of “effectively grounded” and similar (B) Grounding. Snap switches, (B) Grounding. Snap switches, changes to specifically provide including dimmer and similar control including dimmer and similar control requirements for a connection to an switches, shall be effectively grounded switches, shall be connected to an equipment grounding conductor. and shall provide a means to ground equipment grounding conductor and metal faceplates, whether or not a shall provide a means to connect metal May actually improve worker safety. Page 178 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC metal faceplate is installed. Snap switches shall be considered effectively grounded if either of the following conditions is met: faceplates to the equipment grounding conductor, whether or not a metal faceplate is installed. Snap switches shall be considered to be part of an effective ground-fault current path if either of the following conditions is met: (1) The switch is mounted with metal screws to a metal box or to a nonmetallic box with integral means for grounding devices. (1) The switch is mounted with metal screws to a metal box or metal cover that is connected to an equipment grounding conductor or to a nonmetallic box with integral means for connecting to an equipment grounding conductor. (2) An equipment grounding conductor or equipment bonding jumper is connected to an equipment grounding termination of the snap switch. (2) An equipment grounding conductor or equipment bonding jumper is connected to an equipment grounding termination of the snap switch. Exception to (B): Where no grounding means exists within the snap-switch enclosure or where the wiring method does not include or provide an equipment ground, a snap switch without a grounding connection shall be permitted for replacement purposes only. A snap switch wired under the provisions of this exception and located within reach of earth, grade, Exception to (B): Where no means exists within the snapswitch enclosure for connecting to the equipment grounding conductor or where the wiring method does not include or provide an equipment grounding conductor, a snap switch without a connection to an equipment grounding conductor shall be permitted for replacement purposes only. A snap Page 179 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC switch wired under the provisions of this exception and located within reach of earth, grade, conducting floors, or other conducting surfaces shall be provided with a faceplate of nonconducting, noncombustible material or shall be protected by a ground-fault circuit interrupter. 404.12 Grounding of Enclosures. Metal 404.12 Grounding of Enclosures. Metal enclosures for switches or circuit enclosures for switches or circuit breakers shall be grounded as breakers shall be connected to an specified in Article 250. Where equipment grounding conductor as nonmetallic enclosures are used with specified in Part IV of Article 250. metal raceways or metal-armored Metal enclosures for switches or circuit cables, provision shall be made for breakers used as service equipment grounding continuity. shall comply with the provisions of Part V of Article 250. Where nonmetallic enclosures are used with metal raceways or metal-armored cables, provision shall be made for connecting the equipment grounding conductor(s). Except as covered in 404.9(B), Except as covered in 404.9(B), Exception, nonmetallic boxes for Exception, nonmetallic boxes for switches shall be installed with a wiring switches shall be installed with a wiring method that provides or includes an method that provides or includes an equipment ground. equipment grounding conductor. Article 406 Receptacles, Cord Connectors, Receptacles, Cord Connectors, and Attachment Plugs (Caps) and Attachment Plugs (Caps) Change Description and Impact to Worker Safety conducting floors, or other conducting surfaces shall be provided with a faceplate of nonconducting, noncombustible material or shall be protected by a groundfault circuit interrupter. 406.2 Receptacle Rating and Type. 406.2 Receptacle Rating and Type. Page 180 of 361 Inserted “connected to an equipment grounding conductor” in lieu of “grounded” and similar changes to specifically provide requirements for a connection to an equipment grounding conductor. May actually improve worker safety. Continued emphasis on equipment grounding conductor connection versus just grounding. 70 2008 851 Evaluation 2005 NEC 2008 NEC (D) Isolated Ground Receptacles. Receptacles incorporating an isolated grounding connection intended for the reduction of electrical noise (electromagnetic interference) as permitted in 250.146(D) shall be identified by an orange triangle located on the face of the receptacle. (D) Isolated Ground Receptacles. Receptacles incorporating an isolated grounding conductor connection intended for the reduction of electrical noise (electromagnetic interference) as permitted in 250.146(D) shall be identified by an orange triangle located on the face of the receptacle. (1) Isolated Equipment Grounding Conductor Required. Receptacles so identified shall be used only with grounding conductors that are isolated in accordance with 250.146(D). 406.3 General Installation Requirements. (1) Isolated Equipment Grounding Conductor Required. Receptacles so identified shall be used only with equipment grounding conductors that are isolated in accordance with 250.146(D). 406.3 General Installation Requirements. (B) To Be Grounded. Receptacles and cord connectors that have equipment grounding conductor contacts shall have those contacts connected to an equipment grounding conductor. 406.3 General Installation Requirements. (C) Methods of Grounding. The grounding contacts of receptacles and cord connectors shall be grounded by connection to the equipment grounding conductor of the circuit supplying the (C) Methods of Grounding. The equipment grounding conductor contacts of receptacles and cord connectors shall be grounded by connection to the equipment grounding 406.3 General Installation Requirements. (B) To Be Grounded. Receptacles and cord connectors that have grounding contacts shall have those contacts effectively grounded. Page 181 of 361 Change Description and Impact to Worker Safety May actually improve worker safety. Continued emphasis on equipment grounding conductor connection versus just “effectively grounded.” May actually improve worker safety. Continued emphasis on equipment grounding conductor connection versus just grounding. May actually improve worker safety. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety receptacle or cord connector. conductor of the circuit supplying the receptacle or cord connector. The branch-circuit wiring method shall include or provide an equipmentgrounding conductor to which the grounding contacts of the receptacle or cord connector are connected. 406.3 General Installation Requirements. The branch-circuit wiring method shall include or provide an equipment grounding conductor to which the equipment grounding conductor contacts of the receptacle or cord connector are connected. 406.3 General Installation Requirements. (D) Replacements. Replacement of receptacles shall comply with 406.3(D)(1), (D)(2), and (D)(3) as applicable. (D) Replacements. Replacement of receptacles shall comply with 406.3(D)(1), (D)(2), and (D)(3) as applicable. (1) Grounding-Type Receptacles. Where a grounding means exists in the receptacle enclosure or a grounding conductor is installed in accordance with 250.130(C), grounding-type receptacles shall be used and shall be connected to the grounding conductor in accordance with 406.3(C) or 250.130(C). (1) Grounding-Type Receptacles. Where a grounding means exists in the receptacle enclosure or an equipment grounding conductor is installed in accordance with 250.130(C), grounding-type receptacles shall be used and shall be connected to the equipment grounding conductor in accordance with 406.3(C) or 250.130(C). 406.3 General Installation Continued emphasis on equipment Requirements. grounding conductor connection versus just grounding. (D) Replacements. 406.3 General Installation Requirements. (D) Replacements. Page 182 of 361 Continued emphasis on equipment grounding conductor connection versus just grounding. May actually improve worker safety. 70 2008 851 Evaluation 2005 NEC 2008 NEC (3) Non–grounding-Type Receptacles. Where grounding means does not exist in the receptacle enclosure, the installation shall comply with (D)(3)(a), (D)(3)(b), or (D)(3)(c). 406.4 Receptacle Mounting. (3) Non–Grounding-Type Receptacles. Where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, the installation shall comply with (D)(3)(a), (D)(3)(b), or (D)(3)(c). 406.4 Receptacle Mounting. (D) Position of Receptacle Faces. After installation, receptacle faces shall be flush with or project from faceplates of insulating material and shall project a minimum of 0.4 mm (0.015 in.) from metal faceplates. (D) Position of Receptacle Faces. After installation, receptacle faces shall be flush with or project from faceplates of insulating material and shall project a minimum of 0.4 mm (0.015 in.) from metal faceplates. Exception No. 1: Listed kits or assemblies encompassing receptacles and nonmetallic faceplates that cover the receptacle face, where the plate cannot be installed on any other receptacle, shall be permitted. Exception: Listed kits or assemblies encompassing receptacles and nonmetallic faceplates that cover the receptacle face, where the plate cannot be installed on any other receptacle, shall be permitted. Exception No. 2: Listed nonmetallic faceplates that cover the receptacle face to a maximum thickness of 1 mm (0.040 in.) shall be permitted. 406.4 Receptacle Mounting. 406.4 Receptacle Mounting. (G) Voltage Between Adjacent Devices. A receptacle shall not be Page 183 of 361 Change Description and Impact to Worker Safety May actually improve worker safety. Deleted Exception No. 2 to eliminate the misuse of the nonmetallic faceplates. As Safe or Safer. New section (G) to address grouping of receptacles and the allowable voltage potential difference between them. 70 2008 851 Evaluation 2005 NEC 406.6 Attachment Plugs, Cord Connectors, and Flanged Surface Devices. (B) Connection of Attachment Plugs. Attachment plugs shall be installed so that their prongs, blades, or pins are not energized unless inserted into an energized receptacle. No receptacle shall be installed so as to require the insertion of an energized attachment plug as its source of supply. 2008 NEC grouped or ganged in enclosures with other receptacles, snap switches, or similar devices, unless they are arranged so that the voltage between adjacent devices does not exceed 300 volts, or unless they are installed in enclosures equipped with identified, securely installed barriers between adjacent devices. 406.6 Attachment Plugs, Cord Connectors, and Flanged Surface Devices. 406.8 Receptacles in Damp or Wet Locations. (B) Connection of Attachment Plugs. Attachment plugs shall be installed so that their prongs, blades, or pins are not energized unless inserted into an energized receptacle or cord connectors. No receptacle shall be installed so as to require the insertion of an energized attachment plug as its source of supply. 406.8 Receptacles in Damp or Wet Locations. (A) Damp Locations. A receptacle installed outdoors in a location protected from the weather or in other damp locations shall have an enclosure for the receptacle that is weatherproof when the receptacle is (A) Damp Locations. A receptacle installed outdoors in a location protected from the weather or in other damp locations shall have an enclosure for the receptacle that is weatherproof when the receptacle is Page 184 of 361 Change Description and Impact to Worker Safety May actually improve worker safety. Added cord connectors to allow for extension cord use for cord and plug connected devices. As Safe or Safer. Added listing requirements for the common devices addressed by this section. May actually improve worker safety. 70 2008 851 Evaluation 2005 NEC covered (attachment plug cap not inserted and receptacle covers closed). An installation suitable for wet locations shall also be considered suitable for damp locations. A receptacle shall be considered to be in a location protected from the weather where located under roofed open porches, canopies, marquees, and the like, and will not be subjected to a beating rain or water runoff. 406.8 Receptacles in Damp or Wet Locations. (B) Wet Locations. (1) 15- and 20-Ampere Receptacles in a Wet Location. 15- and 20-ampere, 125- and 250-volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. 2008 NEC Change Description and Impact to Worker Safety covered (attachment plug cap not inserted and receptacle covers closed). An installation suitable for wet locations shall also be considered suitable for damp locations. A receptacle shall be considered to be in a location protected from the weather where located under roofed open porches, canopies, marquees, and the like, and will not be subjected to a beating rain or water runoff. All 15and 20-ampere, 125- and 250-volt nonlocking receptacles shall be a listed weather-resistant type. 406.8 Receptacles in Damp or Wet Added listing requirements for the Locations. common devices addressed by this section and made allowances for wash (B) Wet Locations. down areas. (1) 15- and 20-Ampere Receptacles in a Wet Location. 15- and 20-ampere, As Safe or Safer. 125- and 250-volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. All 15- and 20-ampere, 125and 250-volt nonlocking receptacles shall be listed weather-resistant type. Exception: 15- and 20-ampere, 125through 250-volt receptacles installed in a wet location and subject to routine Page 185 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC 406.9 Grounding-Type Receptacles, Adapters, Cord Connectors, and Attachment Plugs. high-pressure spray washing shall be permitted to have an enclosure that is weatherproof when the attachment plug is removed. 406.9 Grounding-Type Receptacles, Adapters, Cord Connectors, and Attachment Plugs. (B) Grounding-Pole Identification. Grounding-type receptacles, adapters, cord connections, and attachment plugs shall have a means for connection of a grounding conductor to the grounding pole. 406.9 Grounding-Type Receptacles, Adapters, Cord Connectors, and Attachment Plugs. (B) Grounding-Pole Identification. Grounding-type receptacles, adapters, cord connections, and attachment plugs shall have a means for connection of an equipment grounding conductor to the grounding pole. 406.9 Grounding-Type Receptacles, Adapters, Cord Connectors, and Attachment Plugs. (D) Grounding-Pole Requirements. Grounding-type attachment plugs and mating cord connectors and receptacles shall be designed such that the equipment grounding connection is made before the currentcarrying connections. Grounding-type devices shall be so designed that grounding poles of attachment plugs cannot be brought into contact with current-carrying parts of receptacles or cord connectors. 406.11 Tamper-Resistant Receptacles Page 186 of 361 Change Description and Impact to Worker Safety Inserted “an equipment” here and in (3) and (4) to address the specific requirement that the grounding pole must be connected to the equipment grounding conductor. As Safe or Safer. Inserted “equipment” here to address the specific requirement that the grounding pole must be connected to the equipment grounding conductor. As Safe or Safer. New section added to address the 70 2008 851 Evaluation 2005 NEC 2008 NEC Switchboards and Panelboards in Dwelling Units. In all areas specified in 210.52, all 125-volt, 15- and 20ampere receptacles shall be listed tamper-resistant receptacles. Article 408 Switchboards and Panelboards 408.3 Support and Arrangement of Busbars and Conductors. 408.3 Support and Arrangement of Busbars and Conductors. (D) Terminals. In switchboards and panelboards, load terminals for field wiring, including grounded circuit conductor load terminals and connections to the ground bus for load equipment grounding conductors, shall be so located that it is not necessary to reach across or beyond an uninsulated ungrounded line bus in order to make connections. (D) Terminals. In switchboards and panelboards, load terminals for field wiring, including grounded circuit conductor load terminals and connections to the equipment grounding conductor bus for load equipment grounding conductors, shall be so located that it is not necessary to reach across or beyond an uninsulated ungrounded line bus in order to make connections. 408.3 Support and Arrangement of 408.3 Support and Arrangement of Busbars and Conductors. Busbars and Conductors. (F) Minimum Wire-Bending Space. The (F) High-Leg Identification. A minimum wire-bending space at switchboard or panelboard containing terminals and minimum gutter space a 4-wire, delta-connected system provided in panelboards and where the midpoint of one phase switchboards shall be as required in winding is grounded shall be legibly 312.6. and permanently field marked as follows: “Caution _____ Phase Has _____ Page 187 of 361 Change Description and Impact to Worker Safety requirement for tamper resistant receptacle installations. As Safe or Safer. Inserted “equipment grounding conductor” here to continue with the emphasis on connections to the equipment grounding conductor, not just a ground. As Safe or Safer. Inserted new section (F) to specifically address the requirements for High-Leg identification. May actually improve worker safety. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety Volts to Ground” (G) Minimum Wire-Bending Space. The minimum wire-bending space at terminals and minimum gutter space provided in panelboards and switchboards shall be as required in 312.6. 408.4 Circuit Directory or Circuit 408.4 Circuit Directory or Circuit Identification. Every circuit and circuit Identification. Every circuit and circuit modification shall be legibly identified modification shall be legibly identified as to its clear, evident, and specific as to its clear, evident, and specific purpose or use. The identification shall purpose or use. The identification shall include sufficient detail to allow each include sufficient detail to allow each circuit to be distinguished from all circuit to be distinguished from all others. The identification shall be others. Spare positions that contain included in a circuit directory that is unused overcurrent devices or located on the face or inside of the switches shall be described panel door in the case of a panelboard, accordingly. The identification shall be and located at each switch on a included in a circuit directory that is switchboard. located on the face or inside of the panel door in the case of a panelboard, and located at each switch on a switchboard. No circuit shall be described in a manner that depends on transient conditions of occupancy. III. Panelboards III. Panelboards 408.30 General. All panelboards shall have a rating not less than the minimum feeder capacity required for 408.30 General. All panelboards shall have a rating not less than the minimum feeder capacity required for Page 188 of 361 Reinforced requirements for panel directories to include specific direction for spare circuits and to assure the identification is understandable regardless of who occupies the premises. May actually improve worker safety. Part III of Article 408 has been reworked such that portions of 408.30, 408.34, 408.35 and 408.36 have been transformed into the new 408.30, 408.36, 408.54 and 408.58. Section 70 2008 851 Evaluation 2005 NEC 2008 NEC the load calculated in accordance with Article 220. the load calculated in accordance with Parts II, III, IV, or V of Article 220 as applicable. Panelboards shall be durably marked by the manufacturer with the voltage and the current rating and the number of phases for which they are designed and with the manufacturer’s name or trademark in such a manner so as to be visible after installation, without disturbing the interior parts or wiring. 408.34 Classification of Panelboards. Panelboards shall be classified for the purposes of this article as either lighting and appliance branch-circuit panelboards or power panelboards, based on their content. A lighting and appliance branch circuit is a branch circuit that has a connection to the neutral of the panelboard and that has overcurrent protection of 30 amperes or less in one or more conductors. Change Description and Impact to Worker Safety 408.30 was shortened by moving the second phrase into new section 408.58 and adding specific references to address the applicable sections of Article 220. As Safe or Safer. Part III of Article 408 has been reworked such that portions of 408.30, 408.34, 408.35 and 408.36 have been transformed into the new 408.30, 408.36, 408.54 and 408.58. Section 408.34 was removed since panelboards are panelboards and not classified as lighting or power. As Safe or Safer. (A) Lighting and Appliance BranchCircuit Panelboard. A lighting and appliance branch-circuit panelboard is one having more than 10 percent of its overcurrent devices protecting lighting and appliance branch circuits. (B) Power Panelboard. A power Page 189 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC panelboard is one having 10 percent or fewer of its overcurrent devices protecting lighting and appliance branch circuits. 408.35 Number of Overcurrent Devices on One Panelboard. Not more than 42 overcurrent devices (other than those provided for in the mains) of a lighting and appliance branch-circuit panelboard shall be installed in any one cabinet or cutout box. A lighting and appliance branch-circuit panelboard shall be provided with physical means to prevent the installation of more overcurrent devices than that number for which the panelboard was designed, rated, and approved. For the purposes of this article, a 2pole circuit breaker shall be considered two overcurrent devices; a 3-pole circuit breaker shall be considered three overcurrent devices. 408.36 Overcurrent Protection. 408.36 Overcurrent Protection. In addition to the requirement of 408.30, (A) Lighting and Appliance Brancha panelboard shall be protected by an Circuit Panelboard Individually overcurrent protective device having a Protected. Each lighting and appliance rating not greater than that of the branch-circuit panelboard shall be panelboard. This overcurrent protective individually protected on the supply device shall be located within or at any side by not more than two main circuit point on the supply side of the Page 190 of 361 Change Description and Impact to Worker Safety Part III of Article 408 has been reworked such that portions of 408.30, 408.34, 408.35 and 408.36 have been transformed into the new 408.30, 408.36, 408.54 and 408.58. Section 408.35 was transformed into 408.54 and modified to remove the specific 42 breaker limit and rely on the maximum number of devices for which the panelboard was designed, rated, and listed. As Safe or Safer. Part III of Article 408 has been reworked such that portions of 408.30, 408.34, 408.35 and 408.36 have been transformed into the new 408.30, 408.36 and 408.58. Total rework of this section provides some of the old wording, but 70 2008 851 Evaluation 2005 NEC breakers or two sets of fuses having a combined rating not greater than that of the panelboard. Exception No. 1: Individual protection for a lighting and appliance panelboard shall not be required if the panelboard feeder has overcurrent protection not greater than the rating of the panelboard. Exception No. 2: For existing installations, individual protection for lighting and appliance branch-circuit panelboards shall not be required where such panelboards are used as service equipment in supplying an individual residential occupancy. 2008 NEC panelboard. Exception No. 1: Individual protection shall not be required for a panelboard used as service equipment with multiple disconnecting means in accordance with 230.71. In panelboards protected by three or more main circuit breakers or sets of fuses, the circuit breakers or sets of fuses shall not supply a second bus structure within the same panelboard assembly. Exception No. 2: Individual protection shall not be required for a panelboard protected on its supply side by two main circuit breakers or two sets of fuses having a combined rating not greater than that of the panelboard. A panelboard constructed or wired under this exception shall not contain more than 42 overcurrent devices. For the purposes of determining the maximum of 42 overcurrent devices, a 2-pole or a 3-pole circuit breaker shall be considered as two or three overcurrent devices, respectively. (B) Power Panelboard Protection. In addition to the requirements of 408.30, a power panelboard with supply conductors that include a neutral, and having more than 10 percent of its overcurrent devices protecting branch circuits rated 30 amperes or less, shall be protected by an overcurrent protective device having a rating not greater than that of the panelboard. This overcurrent protective device shall Exception No. 3: For existing be located within or at any point on the panelboards, individual protection shall Page 191 of 361 Change Description and Impact to Worker Safety reformatted to adhere to the new “nonclassified” panelboard requirements. Sections (A) and (B) were merged into the general introductory section and (C), (D), (E) and (F) became new (A), (B), (C) and (D). As Safe or Safer. 70 2008 851 Evaluation 2005 NEC supply side of the panelboard. Exception: This individual protection shall not be required for a power panelboard used as service equipment with multiple disconnecting means in accordance with 230.71. 408.40 Grounding of Panelboards. Panelboard cabinets and panelboard frames, if of metal, shall be in physical contact with each other and shall be grounded. Where the panelboard is used with nonmetallic raceway or cable or where separate grounding conductors are provided, a terminal bar for the grounding conductors shall be secured inside the cabinet. The terminal bar shall be bonded to the cabinet and panelboard frame, if of metal; otherwise it shall be connected to the grounding conductor that is run with the conductors feeding the panelboard. Exception: Where an isolated equipment grounding conductor is provided as permitted by 250.146(D), the insulated equipment grounding conductor that is run with the circuit 2008 NEC Change Description and Impact to Worker Safety not be required for a panelboard used as service equipment for an individual residential occupancy. 408.40 Grounding of Panelboards. Panelboard cabinets and panelboard frames, if of metal, shall be in physical contact with each other and shall be connected to an equipment grounding conductor. Where the panelboard is used with nonmetallic raceway or cable or where separate equipment grounding conductors are provided, a terminal bar for the equipment grounding conductors shall be secured inside the cabinet. The terminal bar shall be bonded to the cabinet and panelboard frame, if of metal; otherwise it shall be connected to the equipment grounding conductor that is run with the conductors feeding the panelboard. Exception: Where an isolated equipment grounding conductor is provided as permitted by 250.146(D), the insulated equipment grounding conductor that is run with the circuit Page 192 of 361 Inserted “connected to an equipment grounding conductor” in lieu of just “grounded” to continue the emphasis on equipment grounding conductor function and connections. May actually improve worker safety. 70 2008 851 Evaluation 2005 NEC 2008 NEC conductors shall be permitted to pass through the panelboard without being connected to the panelboard’s equipment grounding terminal bar. conductors shall be permitted to pass through the panelboard without being connected to the panelboard’s equipment grounding terminal bar. Grounding conductors shall not be connected to a terminal bar provided for grounded conductors (may be a neutral) unless the bar is identified for the purpose and is located where interconnection between equipment grounding conductors and grounded circuit conductors is permitted or required by Article 250. Equipment grounding conductors shall not be connected to a terminal bar provided for grounded conductors or neutral conductors unless the bar is identified for the purpose and is located where interconnection between equipment grounding conductors and grounded circuit conductors is permitted or required by Article 250. 408.54 Maximum Number of Overcurrent Devices. A panelboard shall be provided with physical means to prevent the installation of more overcurrent devices than that number for which the panelboard was designed, rated, and listed. For the purposes of this section, a 2pole circuit breaker or fusible switch shall be considered two overcurrent devices; a 3-pole circuit breaker or fusible switch shall be considered three overcurrent devices. 408.55 Wire-Bending Space in Panelboards. The enclosure for a panelboard shall have the top and bottom wire-bending space sized in 408.55 Wire-Bending Space in Panelboards. The enclosure for a panelboard shall have the top and bottom wire-bending space sized in Page 193 of 361 Change Description and Impact to Worker Safety Section 408.35 was transformed into the new 408.54 and modified to remove the specific 42 breaker limit and rely on the maximum number of devices for which the panelboard was designed, rated, and listed. As Safe or Safer. Reintroduced the 42 device limit, but only for the purposes of using an alternative table to determine wire bending space. 70 2008 851 Evaluation 2005 NEC 2008 NEC accordance with Table 312.6(B) for the largest conductor entering or leaving the enclosure. Side wire-bending space shall be in accordance with Table 312.6(A) for the largest conductor to be terminated in that space. accordance with Table 312.6(B) for the largest conductor entering or leaving the enclosure. Side wire-bending space shall be in accordance with Table 312.6(A) for the largest conductor to be terminated in that space. Exception No. 1: Either the top or bottom wire-bending space shall be permitted to be sized in accordance with Table 312.6(A) for a lighting and appliance branch-circuit panelboard rated 225 amperes or less. Exception No. 1: Either the top or bottom wire-bending space shall be permitted to be sized in accordance with Table 312.6(A) for a panelboard rated 225 amperes or less and designed to contain not over 42 overcurrent devices. For the purposes of this exception, a 2-pole or a 3-pole circuit breaker shall be considered as two or three overcurrent devices, respectively. 408.58 Panelboard Marking. Panelboards shall be durably marked by the manufacturer with the voltage and the current rating and the number of phases for which they are designed and with the manufacturer’s name or trademark in such a manner so as to be visible after installation, without disturbing the interior parts or wiring. Article 409 Industrial Control Panels Industrial Control Panels Page 194 of 361 Change Description and Impact to Worker Safety As Safe or Safer. New section created from the original 408.30 second phrase. As Safe or Safer. Introduced new definition of control circuit and reworded the definition of 70 2008 851 Evaluation 2005 NEC 409.2 Definitions. 2008 NEC 409.2 Definitions. Control Circuit. The circuit of a control apparatus or system that carries the electric signals directing the performance of the controller but does not carry the main power current. Industrial Control Panel. An assembly of a systematic and standard arrangement of two or more components such as motor controllers, overload relays, fused disconnect switches, and circuit breakers and related control devices such as pushbutton stations, selector switches, timers, switches, control relays, and the like with associated wiring, terminal blocks, pilot lights, and similar components. The industrial control panel does not include the controlled equipment. 409.21 Overcurrent Protection. Change Description and Impact to Worker Safety industrial control panel. As Safe or Safer. Industrial Control Panel. An assembly of two or more components consisting of one of the following: (1) Power circuit components only, such as motor controllers, overload relays, fused disconnect switches, and circuit breakers (2) Control circuit components only, such as pushbuttons, pilot lights, selector switches, timers, switches, control relays (3) A combination of power and control circuit components These components, with associated wiring and terminals, are mounted on or contained within an enclosure or mounted on a subpanel. The industrial control panel does not include the controlled equipment. 409.21 Overcurrent Protection. Page 195 of 361 Inserted “for each incoming supply circuit” to reinforce the intent that each 70 2008 851 Evaluation 2005 NEC 2008 NEC (B) Location. This protection shall be provided by either of the following: (B) Location. This protection shall be provided for each incoming supply circuit by either of the following: 409.60 Grounding. Multisection 409.60 Grounding. Multisection industrial control panels shall be industrial control panels shall be bonded together with an equipment bonded together with an equipment grounding conductor or an equivalent grounding conductor or an equivalent grounding bus sized in accordance equipment grounding bus sized in with Table 250.122. Equipment accordance with Table 250.122. grounding conductors shall terminate Equipment grounding conductors shall on this grounding bus or to a grounding be connected to this equipment termination point provided in a singlegrounding bus or to an equipment section industrial control panel. grounding termination point provided in a single-section industrial control panel. 409.104 Wiring Space in Industrial 409.104 Wiring Space in Industrial Control Panels. Control Panels. (B) Wire Bending Space. Wire bending space for the main supply terminals shall be in accordance with the requirements in 312.6. Wire bending space for other terminals shall be in accordance with the requirements in 430.10(B). The gutter space shall comply with 312.8. (B) Wire Bending Space. Wire bending space within industrial control panels for field wiring terminals shall be in accordance with the requirements in 430.10(B). 409.106 Spacings. Spacings between live bare metal parts in feeder circuits shall not be less than specified in Table 430.97. Page 196 of 361 Change Description and Impact to Worker Safety circuit requires protection. As Safe or Safer. Continued emphasis on equipment grounding conductor connection versus just grounding. May actually improve worker safety. Deleted references to Article 312 and maintained the Article 430 reference as that is where the specific information for wire bending space in controller enclosures resides. As Safe or Safer. New section to address the spacing between live bare metal parts in control panels referencing the controller section in Article 430. 70 2008 851 Evaluation 2005 NEC 2008 NEC Exception: Spacings shall be permitted to be less than those specified in Table 430.97 at circuit breakers and switches and in listed components installed in industrial control panels. 409.108 Service-Entrance Equipment. 409.108 Service Equipment. Where Where used as service equipment, used as service equipment, each each industrial control panel shall be of industrial control panel shall be of the the type that is suitable for use as type that is suitable for use as service service equipment. equipment. Where a grounded conductor is Where a grounded conductor is provided, the industrial control panel provided, the industrial control panel shall be provided with a main bonding shall be provided with a main bonding jumper, sized in accordance with jumper, sized in accordance with 250.28(D), for connecting the 250.28(D), for connecting the grounded conductor, on its supply side, grounded conductor, on its supply side, to the industrial control panel to the industrial control panel equipment ground bus or terminal. equipment ground bus or equipment ground terminal. 409.110 Marking. An industrial control 409.110 Marking. An industrial control panel shall be marked with the panel shall be marked with the following information that is plainly following information that is plainly visible after installation: visible after installation: (1) Manufacturer’s name, trademark, or (1) Manufacturer’s name, trademark, or other descriptive marking by which the other descriptive marking by which the organization responsible for the organization responsible for the product can be identified. product can be identified. (2) Supply voltage, phase, frequency, and full-load current. (2) Supply voltage, number of phases, frequency, and full-load current for each incoming supply circuit. Page 197 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Continued emphasis on equipment grounding conductor connection versus just grounding. May actually improve worker safety. Modified to clarify intent that each supply circuit is required to be included in the requirements for marking and to also identify number of phases. The exception to short circuit current markings was added to address the confusion when no load power circuits are controlled by the control panel. Clarified the drawing reference to reinforce the need for an available wiring diagram. 70 2008 851 Evaluation 2005 NEC (3) Short-circuit current rating of the industrial control panel based on one of the following: a. Short-circuit current rating of a listed and labeled assembly b. Short-circuit current rating established utilizing an approved method 2008 NEC Change Description and Impact to Worker Safety As Safe or Safer. (3) Short-circuit current rating of the industrial control panel based on one of the following: a. Short-circuit current rating of a listed and labeled assembly b. Short-circuit current rating established utilizing an approved method Exception to (3): Short-circuit current rating markings are not required for industrial control panels containing only control circuit components. (4) If the industrial control panel is intended as service equipment, it shall be marked to identify it as being suitable for use as service equipment. (4) If the industrial control panel is intended as service equipment, it shall be marked to identify it as being suitable for use as service equipment. (5) Electrical wiring diagram or the number of the index to the electrical drawings showing the electrical wiring diagram. (5) Electrical wiring diagram or the identification number of a separate electrical wiring diagram or a designation referenced in a separate wiring diagram. (6) An enclosure type number shall be marked on the industrial control panel enclosure. (6) An enclosure type number shall be marked on the industrial control panel enclosure. Article 410 Luminaires, Lampholders, and Lamps Page 198 of 361 Definition of storage space moved 70 2008 851 Evaluation 2005 NEC 410.2 Application of Other Articles. Equipment for use in hazardous (classified) locations shall conform to Articles 500 through 517. Lighting systems operating at 30 volts or less shall conform to Article 411. Arc lamps used in theaters shall comply with 520.61, and arc lamps used in projection machines shall comply with 540.20. Arc lamps used on constantcurrent systems shall comply with the general requirements of Article 490. 2008 NEC 410.2 Definitions. Closet Storage Space. The volume bounded by the sides and back closet walls and planes extending from the closet floor vertically to a height of 1.8 m (6 ft) or to the highest clotheshanging rod and parallel to the walls at a horizontal distance of 600 mm (24 in.) from the sides and back of the closet walls, respectively, and continuing vertically to the closet ceiling parallel to the walls at a horizontal distance of 300 mm (12 in.) or the width of the shelf, whichever is greater; for a closet that permits access to both sides of a hanging rod, this space includes the volume below the highest rod extending 300 mm (12 in.) on either side of the rod on a plane horizontal to the floor extending the entire length of the rod. See Figure 410.2. Lighting Track. A manufactured assembly designed to support and energize luminaires that are capable of being readily repositioned on the track. Its length can be altered by the addition or subtraction of sections of Page 199 of 361 Change Description and Impact to Worker Safety from original 410.8 to new 410.2 and renamed Closet Storage Space to make the article consistent with the standard format of x.2 being designated Definitions in each article. Figure 410.8 likewise became Figure 410.2. Definition of Lighting Track relocated from original 410.100. Original 410.2 Application of Other Articles was deleted. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety track. 410.6 Listing Required. All luminaires and lampholders shall be listed. New 410.6 to require listing for all devices covered in the article. As Safe or Safer. Moved Inspection requirements from original 410.16(B) to new 410.8. II. Luminaire (Fixture) Locations 410.8 Inspection. Luminaires shall be installed such that the connections between the luminaire conductors and the circuit conductors can be inspected without requiring the disconnection of any part of the wiring unless the luminaires are connected by attachment plugs and receptacles. II. Luminaire Locations 410.4 Luminaires (Fixtures) in Specific Locations. 410.10 Luminaires in Specific Locations. (D) Bathtub and Shower Areas. No parts of cord-connected luminaires (fixtures), chain-, cable-, or cordsuspended-luminaires (fixtures), lighting track, pendants, or ceilingsuspended (paddle) fans shall be located within a zone measured 900 mm (3 ft) horizontally and 2.5 m (8 ft) vertically from the top of the bathtub rim or shower stall threshold. This zone is all encompassing and includes the (D) Bathtub and Shower Areas. No parts of cord-connected luminaires, As Safe or Safer. chain-, cable-, or cord-suspended luminaires, lighting track, pendants, or ceiling-suspended (paddle) fans shall be located within a zone measured 900 mm (3 ft) horizontally and 2.5 m (8 ft) vertically from the top of the bathtub rim or shower stall threshold. This zone is all encompassing and includes the space directly over the tub or shower Page 200 of 361 As Safe or Safer. Original 410.4 became 410.10 and additional requirements added to address marking of the devices used within the defined shower and bathtub space. 70 2008 851 Evaluation 2005 NEC zone directly over the tub or shower stall. Luminaires (lighting fixtures) located in this zone shall be listed for damp locations, or listed for wet locations where subject to shower spray. 2008 NEC Change Description and Impact to Worker Safety stall. Luminaires located within the actual outside dimension of the bathtub or shower to a height of 2.5 m (8 ft) vertically from the top of the bathtub rim or shower threshold shall be marked for damp locations, or marked for wet locations where subject to shower spray. IV. Luminaire (Fixture) Supports IV. Luminaire Supports 410.15 Supports. 410.30 Supports. (B) Metal or Nonmetallic Poles Supporting Luminaires (Lighting Fixtures). Metal or nonmetallic poles shall be permitted to be used to support luminaires (lighting fixtures) and as a raceway to enclose supply conductors, provided the following conditions are met: (1) A pole shall have a handhole not less than 50 mm × 100 mm (2 in. × 4 in.) with a rain-tight cover to provide access to the supply terminations within the pole or pole base. IV. Luminaire (Fixture) Supports (B) Metal or Nonmetallic Poles Supporting Luminaires. Metal or nonmetallic poles shall be permitted to be used to support luminaires and as a raceway to enclose supply conductors, provided the following conditions are met: (1) A pole shall have a handhole not less than 50 mm × 100 mm (2 in. × 4 in.) with a cover suitable for use in wet locations to provide access to the supply terminations within the pole or pole base. 410.30 Supports. Page 201 of 361 Will not address changes associated with “410.16 Luminaires in Clothes Closets.” As that is determined to be residential in nature. Inserted “suitable for use in wet locations” into original 410.15(B)(1) in lieu of “rain-tight” to align with listing language and renumbered 410.30(B)(1). As Safe or Safer. Continued emphasis on equipment grounding conductor connection 70 2008 851 Evaluation 2005 NEC 410.15 Supports. 2008 NEC (B) Metal or Nonmetallic Poles Supporting Luminaires. (B) Metal or Nonmetallic Poles Supporting Luminaires (Lighting Fixtures). (3) A metal pole shall be provided with a grounding terminal as follows: a. A pole with a handhole shall have the grounding terminal accessible from the handhole. b. A pole with a hinged base shall have the grounding terminal accessible within the base. 410.18 Exposed Luminaire (Fixture) Parts. (A) Exposed Conductive Parts. Exposed metal parts shall be grounded or insulated from ground and other conducting surfaces or be inaccessible to unqualified personnel. Lamp tie wires, mounting screws, clips, and decorative bands on glass spaced at least 38 mm (11⁄2 in.) from lamp terminals shall not be required to be grounded. 410.18 Exposed Luminaire (Fixture) Parts. (B) Made of Insulating Material. Change Description and Impact to Worker Safety versus just grounding. May actually improve worker safety. (3) A metal pole shall be provided with an equipment grounding terminal as follows: a. A pole with a handhole shall have the equipment grounding terminal accessible from the handhole. b. A pole with a hinged base shall have the equipment grounding terminal accessible within the base. 410.42 Exposed Luminaire. Continued emphasis on equipment grounding conductor connection versus just grounding. (A) Exposed Conductive Parts. Exposed metal parts shall be connected to an equipment grounding May actually improve worker safety. conductor or insulated from the equipment grounding conductor and other conducting surfaces or be inaccessible to unqualified personnel. Lamp tie wires, mounting screws, clips, and decorative bands on glass spaced at least 38 mm (11⁄2 in.) from lamp terminals shall not be required to be grounded. 410.42 Exposed Luminaire. Continued emphasis on equipment grounding conductor connection (B) Made of Insulating Material. versus just grounding. Page 202 of 361 70 2008 851 Evaluation 2005 NEC Luminaires (fixtures) directly wired or attached to outlets supplied by a wiring method that does not provide a ready means for grounding shall be made of insulating material and shall have no exposed conductive parts. 410.30 Cord-Connected Lampholders and Luminaires (Fixtures). (C) Electric-Discharge Luminaires (Fixtures). (1) Cord Connected Installation. A listed luminaire (fixture) or a listed assembly shall be permitted to be cord connected if the following conditions apply: (1) The luminaire (fixture) is located directly below the outlet or busway. (2) The flexible cord meets all the following: a. Is visible for its entire length outside the luminaire (fixture) b. Is not subject to strain or physical damage c. Is terminated in a groundingtype attachment plug cap or busway plug, or is a part of a listed assembly incorporating a manufactured wiring system 2008 NEC Change Description and Impact to Worker Safety Luminaires directly wired or attached to outlets supplied by a wiring method May actually improve worker safety. that does not provide a ready means for grounding attachment to an equipment grounding conductor shall be made of insulating material and shall have no exposed conductive parts. 410.62 Cord-Connected Lampholders Added “having a maximum 152 mm (6 and Luminaires. in.) long section of raceway for attachment to an outlet box above a (C) Electric-Discharge Luminaires. suspended ceiling” to limit the long raceway sections typically used to (1) Cord-Connected Installation. A connect to a power source. The power luminaire or a listed assembly shall be source should be near the luminaire permitted to be cord connected if the location. following conditions apply: (1) The luminaire is located directly As Safe or Safer. below the outlet or busway. (2) The flexible cord meets all the following: a. Is visible for its entire length outside the luminaire b. Is not subject to strain or physical damage c. Is terminated in a groundingtype attachment plug cap or busway plug, or is a part of a listed assembly incorporating a manufactured wiring system connector in accordance with Page 203 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC connector in accordance with 604.6(C), or has a luminaire (fixture) assembly with a strain relief and canopy 604.6(C), or has a luminaire assembly with a strain relief and canopy having a maximum 152 mm (6 in.) long section of raceway for attachment to an outlet box above a suspended ceiling 410.68 Feeder and Branch-Circuit Conductors and Ballasts. Feeder and branch-circuit conductors within 75 mm (3 in.) of a ballast shall have an insulation temperature rating not lower than 90°C (194°F) unless supplying a luminaire marked as suitable for a different insulation temperature. 410.74 Luminaire Rating. (A) Marking. All luminaires shall be marked with the maximum lamp wattage or electrical rating, manufacturer’s name, trademark, or other suitable means of identification. A luminaire requiring supply wire rated higher than 60°C (140°F) shall be marked with the minimum supply wire temperature rating on the luminaire and shipping carton or equivalent. 410.33 Branch Circuit Conductors and Ballasts. Branch circuit conductors within 75 mm (3 in.) of a ballast shall have an insulation temperature rating not lower than 90°C (194°F) unless supplying a luminaire (fixture) listed and marked as suitable for a different insulation temperature. 410.35 Luminaire (Fixture) Rating. (A) Marking. All luminaires (fixtures) shall be marked with the maximum lamp wattage or electrical rating, manufacturer’s name, trademark, or other suitable means of identification. A luminaire (fixture) requiring supply wire rated higher than 60°C (140°F) shall be marked in letters not smaller than 6 mm (1⁄4 in.) high, prominently displayed on the luminaire (fixture) and shipping carton or equivalent. 410.45 Tests. All wiring shall be free from short circuits and grounds and shall be tested for these defects prior to being connected to the circuit. 410.85 Tests. All wiring shall be free from short circuits and ground faults as defined in 250.2 and shall be tested for these defects prior to being connected Page 204 of 361 Change Description and Impact to Worker Safety Added “feeder” to assure that feeder conductors are also protected from excessive heat if installed near luminaires. As Safe or Safer. Replaced the phrase “in letters not smaller than 6 mm (1⁄4 in.) high, prominently displayed on the luminaire (fixture) and shipping carton or equivalent” with the phrase “with the minimum supply wire temperature rating on the luminaire and shipping carton or equivalent” to assure that the required wire temperature rating actually made it to the luminaire markings. As Safe or Safer. Modified to specifically point to the defined term “ground faults” versus the ambiguous term “grounds.” 70 2008 851 Evaluation 2005 NEC 2008 NEC XIII. Special Provisions for ElectricDischarge Lighting Systems of 1000 Volts or Less to the circuit. XIII. Special Provisions for ElectricDischarge Lighting Systems of 1000 Volts or Less 410.73 General. 410.130 General. Change Description and Impact to Worker Safety As Safe or Safer. Added new sections to provide the specific requirements for the location of the disconnecting means and for multiwire branch circuit operation. May actually improve worker safety. (G) Disconnecting Means. (G) Disconnecting Means. (2) Multiwire Branch Circuits. When connected to multiwire branch circuits, the disconnecting means shall simultaneously break all the supply conductors to the ballast, including the grounded conductor. 410.81 Control (3) Location. The disconnecting means shall be located so as to be accessible to qualified persons before servicing or maintaining the ballast. Where the disconnecting means is external to the luminaire, it shall be a single device, and shall be attached to the luminaire or the luminaire shall be located within sight of the disconnecting means. 410.141 Control. (B) Within Sight or Locked Type. The switch or circuit breaker shall be located within sight from the luminaires (fixtures) or lamps, or it shall be (B) Within Sight or Locked Type. The switch or circuit breaker shall be located within sight from the luminaires or lamps, or it shall be permitted Page 205 of 361 This change aligns with many other articles throughout the Code, where provision for locking the disconnecting means is specified to be a permanent part of the disconnecting means. 70 2008 851 Evaluation 2005 NEC permitted elsewhere if it is provided with a means for locking in the open position. XV. Lighting Track 410.101 Installation. (D) Support. Fittings identified for use on lighting track shall be designed specifically for the track on which they are to be installed. They shall be securely fastened to the track, shall maintain polarization and grounding, and shall be designed to be suspended directly from the track. Lighting Systems Operating at 30 Volts or Less 411.2 Definition. Lighting Systems Operating at 30 Volts or Less. A lighting system consisting of an isolating power supply operating at 30 volts (42.4 volts peak) or less under 2008 NEC Change Description and Impact to Worker Safety elsewhere if it is provided with a means As Safe or Safer. for locking in the open position. The provisions for locking or adding a lock to the disconnecting means must remain in place at the switch or circuit breaker whether the lock is installed or not. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. XV. Lighting Track Continued emphasis on connection to the equipment grounding conductor 410.151 Installation. versus just grounding. (D) Support. Fittings identified for use May actually improve worker safety. on lighting track shall be designed specifically for the track on which they are to be installed. They shall be securely fastened to the track, shall maintain polarization and connections to the equipment grounding conductor, and shall be designed to be suspended directly from the track. Article 411 Lighting Systems Operating at 30 Volts Modified to emphasize the rating of the or Less output circuits and the entire system under all load conditions. 411.2 Definition. Lighting Systems Operating at 30 Volts As Safe or Safer. or Less. A lighting system consisting of an isolating power supply, the low voltage luminaires, and associated Page 206 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC any load condition, with one or more secondary circuits, each limited to 25 amperes maximum, supplying luminaires (lighting fixtures) and associated equipment identified for the use. 411.3 Listing Required. Lighting systems operating at 30 volts or less shall be listed. equipment that are all identified for the use. The output circuits of the power supply are rated for not more than 25 amperes and operate at 30 volts (42.4 volts peak) or less under all load conditions. 411.3 Listing Required. Lighting systems operating at 30 volts or less shall comply with 411.3(A) or 411.3(B). (A) Listed System. Lighting systems operating at 30 volts or less shall be listed as a complete system. The luminaires, power supply, and luminaire fittings (including the exposed bare conductors) of an exposed bare conductor lighting system shall be listed for the use as part of the same identified lighting system. (B) Assembly of Listed Parts. A lighting system assembled from the following listed parts shall be permitted: (1) Low-voltage luminaires (2) Low-voltage luminaire power supply (3) Class 2 power supply (4) Low-voltage luminaire fittings (5) Cord (secondary circuit) for which the luminaires and power supply are listed for use Page 207 of 361 Change Description and Impact to Worker Safety Modified to add the specific listing requirements and allowances to assure proper installations. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 411.4 Locations Not Permitted. Lighting systems operating at 30 volts or less shall not be installed in the locations described in 411.4(A) and 411.4(B). (A) Where concealed or extended through a building wall unless permitted in (1) or (2): (1) Installed using any of the wiring methods specified in Chapter 3 (2) Installed using wiring supplied by a listed Class 2 power source and installed in accordance with 725.52 (B) Where installed within 3.0 m (10 ft) of pools, spas, fountains, or similar locations, unless permitted by Article 680. 411.5 Secondary Circuits. 2008 NEC (6) Cable, conductors in conduit, or other fixed wiring method for the secondary circuit The luminaires, power supply, and luminaire fittings (including the exposed bare conductors) of an exposed bare conductor lighting system shall be listed for use as part of the same identified lighting system. 411.4 Specific Location Requirements. (A) Walls, Floors, and Ceilings. Conductors concealed or extended through a wall, floor, or ceiling shall be in accordance with (1) or (2): (1) Installed using any of the wiring methods specified in Chapter 3 Change Description and Impact to Worker Safety Modified to convert to positive Code language and detail the requirements rather than indicate “not permitted” for the lighting systems and allow exceptions. As Safe or Safer. (2) Installed using wiring supplied by a listed Class 2 power source and installed in accordance with 725.130 (B) Pools, Spas, Fountains, and Similar Locations. Lighting systems shall be installed not less than 3 m (10 ft) horizontally from the nearest edge of the water, unless permitted by Article 680. 411.5 Secondary Circuits. Page 208 of 361 New section to address the complete 70 2008 851 Evaluation 2005 NEC 2008 NEC (D) Insulated Conductors. Exposed insulated secondary circuit conductors shall be of the type, and installed as, described in (1), (2), or (3): Change Description and Impact to Worker Safety system – grounding, isolation, bare conductors AND insulated conductors. As Safe or Safer. (1) Class 2 cable supplied by a Class 2 power source and installed in accordance with Parts I and III of Article 725. Appliances (2) Conductors, cord, or cable of the listed system and installed not less than 2.1 m (7 ft) above the finished floor unless the system is specifically listed for a lower installation height. (3) Wiring methods described in Chapter 3 Article 422 Appliances 422.51 Cord-and-Plug-Connected Vending Machines. Cord-and-plugconnected vending machines manufactured or re-manufactured on or after January 1, 2005, shall include a ground-fault circuit-interrupter as an integral part of the attachment plug or located in the power supply cord within 300 mm (12 in.) of the attachment plug. Cord-and-plug connected 422.51 Cord-and-Plug-Connected Vending Machines. Cord-and-plugconnected vending machines manufactured or re-manufactured on or after January 1, 2005, shall include a ground-fault circuit interrupter as an integral part of the attachment plug or be located within 300 mm (12 in.) of the attachment plug. Older vending machines manufactured or Page 209 of 361 Clarified the original intent of the section introduced during the 2005 cycle with respect to the location and integral plug requirement and to provide a definition of vending machine. May actually increase worker safety. 70 2008 851 Evaluation 2005 NEC vending machines not incorporating integral GFCI protection shall be connected to a GFCI protected outlet. 2008 NEC remanufactured prior to January 1, 2005, shall be connected to a GFCIprotected outlet. For the purpose of this section, the term vending machine means any self-service device that dispenses products or merchandise without the necessity of replenishing the device between each vending operation and is designed to require insertion of a coin, paper currency, token, card, key, or receipt of payment by other means. 422.52 Electric Drinking Fountains. Electric drinking fountains shall be protected with ground-fault circuit interrupter protection. Change Description and Impact to Worker Safety New section added to address concerns of electrocution via water fountains. May actually increase worker safety. Fixed Electric Space-Heating Equipment Article 424 Fixed Electric Space-Heating Equipment III. Control and Protection of Fixed Electric Space-Heating Equipment III. Control and Protection of Fixed Electric Space-Heating Equipment 424.19 Disconnecting Means. Means shall be provided to disconnect the heater, motor controller(s), and supplementary overcurrent protective device(s) of all fixed electric spaceheating equipment from all ungrounded conductors. Where heating equipment 424.19 Disconnecting Means. Means shall be provided to simultaneously disconnect the heater, motor controller(s), and supplementary overcurrent protective device(s) of all fixed electric space-heating equipment from all ungrounded conductors. Page 210 of 361 Added disconnecting means rating requirements as well as locking means requirements. May actually improve worker safety. 70 2008 851 Evaluation 2005 NEC is supplied by more than one source, the disconnecting means shall be grouped and marked. 2008 NEC VI. Control and Protection Where heating equipment is supplied by more than one source, the disconnecting means shall be grouped and marked. The disconnecting means specified in 424.19(A) and (B) shall have an ampere rating not less than 125 percent of the total load of the motors and the heaters. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Article 426 Fixed Outdoor Electric Deicing and Snow-Melting Equipment 426.44 Grounding. The ferromagnetic envelope shall be connected to an equipment grounding conductor at both ends; and, in addition, it shall be permitted to be connected to an equipment grounding conductor at intermediate points as required by its design. The provisions of 250.30 shall not apply to the installation of skin-effect heating systems. VI. Control and Protection 426.50 Disconnecting Means. 426.50 Disconnecting Means. Fixed Outdoor Electric Deicing and Snow-Melting Equipment 426.44 Grounding. The ferromagnetic envelope shall be grounded at both ends; and, in addition, it shall be permitted to be grounded at intermediate points as required by its design. The provisions of 250.30 shall not apply to the installation of skin-effect heating systems. Page 211 of 361 Change Description and Impact to Worker Safety Continued emphasis on connected to an equipment grounding conductor versus grounded. May actually improve worker safety. Inserted “simultaneous” to eliminate bad habit of singly disconnecting each conductor. 70 2008 851 Evaluation 2005 NEC (A) Disconnection. All fixed outdoor deicing and snow-melting equipment shall be provided with a means for disconnection from all ungrounded conductors. Where readily accessible to the user of the equipment, the branch-circuit switch or circuit breaker shall be permitted to serve as the disconnecting means. The disconnecting means shall be of the indicating type and be provided with a positive lockout in the “off” position. 426.52 Overcurrent Protection. Fixed outdoor electric deicing and snowmelting equipment shall be permitted to be protected against overcurrent where supplied by a branch circuit as specified in 426.4. Fixed Electric Heating Equipment for Pipelines and Vessels 427.13 Identification. The presence of electrically heated pipelines, vessels, or both, shall be evident by the posting of appropriate caution signs or markings at frequent intervals along the pipeline or vessel. 2008 NEC Change Description and Impact to Worker Safety (A) Disconnection. All fixed outdoor deicing and snow-melting equipment May actually improve worker safety. shall be provided with a means for simultaneous disconnection from all ungrounded conductors. Where readily accessible to the user of the equipment, the branch-circuit switch or circuit breaker shall be permitted to serve as the disconnecting means. The disconnecting means shall be of the indicating type and be provided with a positive lockout in the “off” position. Deleted 426.52 due to incorporation into Article 240 requirements. As Safe or Safer. Article 427 Fixed Electric Heating Equipment for Pipelines and Vessels 427.13 Identification. The presence of electrically heated pipelines, vessels, or both, shall be evident by the posting of appropriate caution signs or markings at intervals not exceeding 6 m (20 ft) along the pipeline or vessel and on or adjacent to equipment in the piping system that requires periodic servicing. Page 212 of 361 Places specific requirements in the Code to assure that “frequent intervals” are implemented consistently. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety Again, simultaneously was interjected to assure the intent of the section regarding disconnecting means. VII. Control and Protection VII. Control and Protection 427.55 Disconnecting Means. 427.55 Disconnecting Means. (A) Switch or Circuit Breaker. Means shall be provided to disconnect all fixed electric pipeline or vessel heating equipment from all ungrounded conductors. The branch-circuit switch or circuit breaker, where readily accessible to the user of the equipment, shall be permitted to serve as the disconnecting means. The disconnecting means shall be of the indicating type and shall be provided with a positive lockout in the “off” position. 427.56 Controls. (A) Switch or Circuit Breaker. Means shall be provided to simultaneously disconnect all fixed electric pipeline or vessel heating equipment from all ungrounded conductors. The branchcircuit switch or circuit breaker, where readily accessible to the user of the equipment, shall be permitted to serve as the disconnecting means. The disconnecting means shall be of the indicating type and shall be provided with a positive lockout in the “off” position. 427.56 Controls. (A) Temperature Control with “Off” Position. Temperature-controlled switching devices that indicate an “off” position and that interrupt line current shall open all ungrounded conductors when the control device is in this “off” position. These devices shall not be permitted to serve as the disconnecting means unless provided with a positive lockout in the “off” position. 427.56 Controls. (A) Temperature Control with “Off” Position. Temperature-controlled switching devices that indicate an “off” position and that interrupt line current shall open all ungrounded conductors when the control device is in this “off” position. These devices shall not be As Safe or Safer. permitted to serve as the disconnecting means unless capable of being locked in the open position. 427.56 Controls. Modified to read “capable of being locked in the open position” instead of Page 213 of 361 As Safe or Safer. Modified to read “capable of being locked in the open position” instead of “provided with a positive lockout in the “off” position” to assure the disconnect itself, was actually capable of being locked in the open position versus “being provided” another means. 70 2008 851 Evaluation 2005 NEC 2008 NEC (D) Combined Switching Devices. Switching devices consisting of combined temperature-actuated devices and manually controlled switches that serve both as the controllers and the disconnecting means shall comply with all the following conditions: (1) Open all ungrounded conductors when manually placed in the “off” position (2) Be designed so that the circuit cannot be energized automatically if the device has been manually placed in the “off” position (3) Be provided with a positive lockout in the “off” position (D) Combined Switching Devices. Switching devices consisting of combined temperature-actuated devices and manually controlled switches that serve both as the controllers and the disconnecting means shall comply with all the following conditions: (1) Open all ungrounded conductors when manually placed in the “off” position (2) Be designed so that the circuit cannot be energized automatically if the device has been manually placed in the “off” position (3) Be capable of being locked in the open position Motors, Motor Circuits, and Controllers Article 430 Motors, Motor Circuits, and Controllers 430.2 Definitions. 430.2 Definitions. III. Motor and Branch-Circuit Overload Valve Actuator Motor (VAM) Assemblies. A manufactured assembly, used to operate a valve, consisting of an actuator motor and other components such as controllers, torque switches, limit switches, and overload protection. III. Motor and Branch-Circuit Overload Page 214 of 361 Change Description and Impact to Worker Safety “provided with a positive lockout in the “off” position” to assure the disconnect itself, was actually capable of being locked in the open position versus “being provided” another means. As Safe or Safer. Added definition for Valve Actuator Motors as they have become more and more widely used in industry. As Safe or Safer. The definition of Overload was moved 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety to Article 100 to be consistent with NFPA Manual of Style for the NEC to make definitions that affect more than one Article available for the entire document. Protection Protection 430.31 General. Part III specifies overload devices intended to protect motors, motor-control apparatus, and motor branch-circuit conductors against excessive heating due to motor overloads and failure to start. Overload in electrical apparatus is an operating overcurrent that, when it persists for a sufficient length of time, would cause damage or dangerous overheating of the apparatus. It does not include short circuits or ground faults. These provisions shall not be interpreted as requiring overload protection where it might introduce additional or increased hazards, as in the case of fire pumps. 430.32 Continuous-Duty Motors. 430.31 General. Part III specifies overload devices intended to protect motors, motor-control apparatus, and motor branch-circuit conductors against excessive heating due to motor As Safe or Safer. overloads and failure to start. (C) Selection of Overload Relay. Where the sensing element or setting of the overload relay selected in accordance with 430.32(A)(1) and 430.32(B)(1) is not sufficient to start the motor or to carry the load, higher size sensing elements or incremental settings shall be permitted to be used, provided the trip current of the (C) Selection of Overload Device. Where the sensing element or setting or sizing of the overload device selected in accordance with 430.32(A)(1) and 430.32(B)(1) is not sufficient to start the motor or to carry the load, higher size sensing elements or incremental settings or sizing shall be permitted to be used, provided the These provisions shall not be interpreted as requiring overload protection where it might introduce additional or increased hazards, as in the case of fire pumps. 430.32 Continuous-Duty Motors. Page 215 of 361 Use of the term “relay” limited the types of overload devices that could be used for overload selection and was replaced with the generic term “device” and words inserted to assure that all listed types of overload devices could be applied. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC trip current of the overload device does not exceed the following percentage of motor nameplate full-load current rating: 430.73 Mechanical Protection of 430.73 Protection of Conductor from Conductor. Where damage to a motor Physical Damage. Where damage to a control circuit would constitute a motor control circuit would constitute a hazard, all conductors of such a hazard, all conductors of such a remote motor control circuit that are remote motor control circuit that are outside the control device itself shall be outside the control device itself shall be installed in a raceway or be otherwise installed in a raceway or be otherwise suitably protected from physical suitably protected from physical damage. damage. Where one side of the motor control circuit is grounded, the motor control 430.74 Electrical Arrangement of circuit shall be arranged so that an Control Circuits. Where one side of the accidental ground in the control circuit motor control circuit is grounded, the remote from the motor controller will motor control circuit shall be arranged (1) not start the motor and (2) not so that an accidental ground in the bypass manually operated shutdown control circuit remote from the motor devices or automatic safety shutdown controller will (1) not start the motor devices. and (2) not bypass manually operated shutdown devices or automatic safety shutdown devices. VII. Motor Controllers VII. Motor Controllers Change Description and Impact to Worker Safety overload relay does not exceed the following percentage of motor nameplate full-load current rating: 430.81 General. Part VII is intended to require suitable controllers for all motors. (A) Stationary Motor of 1⁄8 Horsepower or Less. For a stationary motor rated at 430.81 General. Part VII is intended to require suitable controllers for all motors. (A) Stationary Motor of 1⁄8 Horsepower or Less. For a stationary motor rated at Page 216 of 361 Old section 430.73 was split into 430.73 and 430.74 and old 430.74 was renumbered 430.75. The change was made to accentuate the new headings of “Protection of Conductor from Physical Damage” and “Electrical Arrangement of Control Circuits” which may have hidden by the old heading “Mechanical Protection of Conductor.” As Safe or Safer. The term “disconnecting means” replaced “protective device” to emphasize that it must actually be a disconnecting means, not just a protective device, since some protective devices do not qualify as a disconnecting means. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety 1⁄8 hp or less that is normally left running and is constructed so that it cannot be damaged by overload or failure to start, such as clock motors and the like, the branch-circuit protective device shall be permitted to serve as the controller. 430.87 Number of Motors Served by Each Controller. Each motor shall be provided with an individual controller. 1⁄8 hp or less that is normally left running and is constructed so that it cannot be damaged by overload or failure to start, such as clock motors and the like, the branch-circuit disconnecting means shall be permitted to serve as the controller. 430.87 Number of Motors Served by Each Controller. Each motor shall be provided with an individual controller. Exception: For motors rated 600 volts or less, a single controller rated at not less than the equivalent horsepower, as determined in accordance with 430.110(C)(1), of all the motors in the group shall be permitted to serve the group under any of the following conditions: (a) Where a number of motors drive several parts of a single machine or piece of apparatus, such as metal and woodworking machines, cranes, hoists, and similar apparatus (b) Where a group of motors is under the protection of one overcurrent device as permitted in 430.53(A) (c) Where a group of motors is located in a single room within sight from the controller location Exception No. 1: For motors rated 600 volts or less, a single controller rated at As Safe or Safer. not less than the equivalent horsepower, as determined in accordance with 430.110(C)(1), of all the motors in the group shall be permitted to serve the group under any of the following conditions: (a) Where a number of motors drive several parts of a single machine or piece of apparatus, such as metal and woodworking machines, cranes, hoists, and similar apparatus (b) Where a group of motors is under the protection of one overcurrent device as permitted in 430.53(A) (c) Where a group of motors is located in a single room within sight from the controller location Page 217 of 361 As Safe or Safer. Added Exception No. 2 to address the change made in 430.81(A) regarding the branch-circuit disconnecting means used as the controller. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety Exception No. 2: A branch-circuit disconnecting means serving as the controller as allowed in 430.81(A) shall be permitted to serve more than one motor. 430.91 Motor Controller Enclosure Types. Table 430.91 provides the basis for selecting enclosures for use in specific locations other than hazardous (classified) locations. The enclosures are not intended to protect against conditions such as condensation, icing, corrosion, or contamination that may occur within the enclosure or enter via the conduit or unsealed openings. These internal conditions shall require special consideration by the installer and user. 430.96 Grounding. Multisection motor control centers shall be bonded together with an equipment grounding conductor or an equivalent grounding bus sized in accordance with Table 250.122. Equipment grounding conductors shall terminate on this grounding bus or to a grounding termination point provided in a singlesection motor control center. 430.102 Location. This information was moved to new Section 110.20 as an effort to have enclosure types apply to more than motor controllers. As Safe or Safer. 430.96 Grounding. Multisection motor control centers shall be connected together with an equipment grounding conductor or an equivalent equipment grounding bus sized in accordance with Table 250.122. Equipment grounding conductors shall be connected to this equipment grounding bus or to a grounding termination point provided in a single-section motor control center. 430.102 Location. Page 218 of 361 Continued emphasis on “connected” to an equipment grounding conductor. As Safe or Safer. Added new exception to cover 70 2008 851 Evaluation 2005 NEC (A) Controller. 2008 NEC (A) Controller. Exception No. 3: The disconnecting means shall not be required to be in sight from valve actuator motor (VAM) assemblies containing the controller where such a location introduces additional or increased hazards to persons or property and conditions (a) and (b) are met. (a) The valve actuator motor assembly is marked with a warning label giving the location of the disconnecting means. (b) The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. 430.102 Location. 430.102 Location. (B) Motor. A disconnecting means shall (B) Motor. A disconnecting means shall be located in sight from the motor be provided for a motor in accordance location and the driven machinery with (B)(1) or (B)(2). location. (1) Separate Motor Disconnect. A disconnecting means for the motor shall be located in sight from the motor location and the driven machinery location. (2) Controller Disconnect. The Page 219 of 361 Change Description and Impact to Worker Safety disconnecting means for valve actuator motor (VAM) assemblies. As Safe or Safer. Clarified that a second disconnecting means is not required where the controller disconnecting means is located within sight of the motor and driven machinery. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC controller disconnecting means required in accordance with 430.102(A) shall be permitted to serve as the disconnecting means for the motor if it is in sight from the motor location and the driven machinery location. 430.103 Operation. The disconnecting 430.103 Operation. The disconnecting means shall open all ungrounded means shall open all ungrounded supply conductors and shall be supply conductors and shall be designed so that no pole can be designed so that no pole can be operated independently. The operated independently. The disconnecting means shall be disconnecting means shall be permitted in the same enclosure with permitted in the same enclosure with the controller. the controller. The disconnecting means shall be designed so that it cannot be closed automatically. 430.108 Every Disconnecting Means. 430.108 Every Disconnecting Means. Every disconnecting means in the Every disconnecting means in the motor circuit between the point of motor circuit between the point of attachment to the feeder and the point attachment to the feeder or branch of connection to the motor shall comply circuit and the point of connection to with the requirements of 430.109 and the motor shall comply with the 430.110. requirements of 430.109 and 430.110. 430.110 Ampere Rating and 430.110 Ampere Rating and Interrupting Capacity. Interrupting Capacity. (C) For Combination Loads. Change Description and Impact to Worker Safety Added provision prohibiting automatic closure of a motor disconnecting means. As Safe or Safer. Revised to recognize there may be more than one disconnecting means in a motor branch circuit. As Safe or Safer. Added a requirement to use the largest value when comparing the full-load current and locked-rotor current tables. (C) For Combination Loads. As Safe or Safer. (1) Horsepower Rating. (1) Horsepower Rating. Page 220 of 361 70 2008 851 Evaluation 2005 NEC 430.126 Motor Overtemperature Protection. (A) General. Adjustable speed drive systems shall protect against motor overtemperature conditions. Overtemperature protection is in addition to the conductor protection required in 430.32. Protection shall be provided by one of the following means. 2008 NEC ….In cases where different current ratings are obtained when applying these tables, the largest value obtained shall be used. 430.126 Motor Overtemperature Protection. (A) General. Adjustable speed drive systems shall protect against motor overtemperature conditions where the motor is not rated to operate at the nameplate rated current over the speed range required by the application. This protection shall be provided in addition to the conductor protection required in 430.32. Protection shall be provided by one of the following means. (1) Motor thermal protector in accordance with 430.32 (1) Motor thermal protector in accordance with 430.32 (2) Adjustable speed drive controller with load and speed sensitive overload protection and thermal memory retention upon shutdown or power loss (2) Adjustable speed drive system with load and speed sensitive overload protection and thermal memory retention upon shutdown or power loss (3) Overtemperature protection relay Exception to (2): Thermal memory retention upon shutdown or power loss is not required for continuous duty loads. (3) Overtemperature protection relay Page 221 of 361 Change Description and Impact to Worker Safety Clarified the conditions where motor overtemperature protection is required. Added exception under which thermal memory retention is not required. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC utilizing thermal sensors embedded in the motor and meeting the requirements of 430.32(A)(2) or (B)(2) utilizing thermal sensors embedded in the motor and meeting the requirements of 430.32(A)(2) or (B)(2) (4) Thermal sensor embedded in the motor that is received and acted upon by an adjustable speed drive (4) Thermal sensor embedded in the motor whose communications are received and acted upon by an adjustable speed drive system 430.126 Motor Overtemperature Protection. 430.126 Motor Overtemperature Protection. (B) Motors with Cooling Systems. Motors that utilize external forced air or liquid cooling systems shall be provided with protection that shall be continuously enabled or enabled automatically if the cooling system fails. (C) Multiple Motor Applications. For multiple motor applications, individual motor overtemperature protection shall be provided. 430.227 Disconnecting Means. The controller disconnecting means shall be capable of being locked in the open position. (B) Multiple Motor Applications. For multiple motor applications, individual motor overtemperature protection shall be provided as required in 430.126(A). 430.227 Disconnecting Means. The controller disconnecting means shall be capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain Change Description and Impact to Worker Safety Deleted reference to motors with cooling systems and provided specific direction for multiple motor applications. As Safe or Safer. Page 222 of 361 This change aligns with many other articles throughout the Code, where provision for locking the disconnecting means is specified to be a permanent part of the disconnecting means. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC in place with or without the lock installed. 430.243 Portable Motors. The frames 430.243 Portable Motors. The frames of portable motors that operate at over of portable motors that operate over 150 volts to ground shall be guarded or 150 volts to ground shall be guarded or grounded. grounded. Change Description and Impact to Worker Safety The two exceptions have been added to align the section with the requirements for portable motors in Article 250. Exception No. 1: Listed motor-operated As Safe or Safer. tools, listed motor-operated appliances, and listed motor-operated equipment shall not be required to be grounded where protected by a system of double insulation or its equivalent. Double-insulated equipment shall be distinctively marked. 430.244 Controllers. Controller enclosures shall be grounded regardless of voltage. Controller enclosures shall have means for attachment of an equipment grounding conductor termination in accordance with 250.8. Exception No. 2: Listed motor-operated tools, listed motor-operated appliances, and listed motor-operated equipment connected by a cord and attachment plug, other than those required to be grounded in accordance with 250.114. 430.244 Controllers. Controller Continued emphasis on “connected” to enclosures shall be connected to the an equipment grounding conductor. equipment grounding conductor regardless of voltage. Controller As Safe or Safer. enclosures shall have means for attachment of an equipment grounding conductor termination in accordance with 250.8. Page 223 of 361 70 2008 851 Evaluation 2005 NEC 430.245 Method of Grounding. Where required, grounding shall be done in the manner specified in Part VI of Article 250. Air-Conditioning and Refrigerating Equipment 440.14 Location. Disconnecting means shall be located within sight from and readily accessible from the airconditioning or refrigerating equipment. The disconnecting means shall be permitted to be installed on or within the air-conditioning or refrigerating equipment. The disconnecting means shall not be located on panels that are designed to allow access to the air-conditioning or refrigeration equipment. 440.14 Location. Exception No. 1…..The provision for locking or adding a lock to the disconnecting means shall be permanently installed on or at the switch or circuit breaker used as the disconnecting means. 440.53 Overload Relays. Overload relays and other devices for motor 2008 NEC 430.245 Method of Grounding. Connection to the equipment grounding conductor shall be done in the manner specified in Part VI of Article 250. Article 440 Air-Conditioning and Refrigerating Equipment 440.14 Location. Disconnecting means shall be located within sight from and readily accessible from the airconditioning or refrigerating equipment. The disconnecting means shall be permitted to be installed on or within the air-conditioning or refrigerating equipment. The disconnecting means shall not be located on panels that are designed to allow access to the air-conditioning or refrigeration equipment or to obscure the equipment nameplate(s). 440.14 Location. Exception No. 1…..The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker and shall remain in place with or without the lock installed. 440.53 Overload Relays. Overload relays and other devices for motor Page 224 of 361 Change Description and Impact to Worker Safety Continued emphasis on “connected” to an equipment grounding conductor. As Safe or Safer. Revised to prohibit disconnecting means from obscuring equipment nameplate. As Safe or Safer. Clarified the type of locking provision that has to be provided as part of the installed equipment. As Safe or Safer. Revised to require that overload relays or other devices be identified for group 70 2008 851 Evaluation 2005 NEC 2008 NEC overload protection that are not capable of opening short circuits shall be protected by fuses or inverse time circuit breakers with ratings or settings in accordance with Part III unless approved for group installation or for part-winding motors and marked to indicate the maximum size of fuse or inverse time circuit breaker by which they shall be protected. 440.54 Motor-Compressors and Equipment on 15- or 20- Ampere Branch Circuits — Not Cord-andAttachment- Plug-Connected. (A) Overload Protection. The motorcompressor shall be provided with overload protection selected as specified in 440.52(A). Both the controller and motor overload protective device shall be approved for installation with the short-circuit and ground-fault protective device for the branch circuit to which the equipment is connected. overload protection that are not capable of opening short circuits shall be protected by fuses or inverse time circuit breakers with ratings or settings in accordance with Part III unless identified for group installation or for part-winding motors and marked to indicate the maximum size of fuse or inverse time circuit breaker by which they shall be protected. 440.54 Motor-Compressors and Equipment on 15- or 20-Ampere Branch Circuits — Not Cord-andAttachment-Plug-Connected. 440.55 Cord-and-Attachment-PlugConnected Motor-Compressors and Equipment on 15- or 20-Ampere Branch Circuits. (A) Overload Protection. The motorcompressor shall be provided with overload protection selected as specified in 440.52(A). Both the controller and motor overload protective device shall be identified for installation with the short-circuit and ground-fault protective device for the branch circuit to which the equipment is connected. 440.55 Cord-and-Attachment-PlugConnected Motor-Compressors and Equipment on 15- or 20-Ampere Branch Circuits. (A) Overload Protection. The motor- (A) Overload Protection. The motor- Page 225 of 361 Change Description and Impact to Worker Safety installations. As Safe or Safer. Revised to require the controller and the overload protective device to be identified for installation with the branch-circuit short-circuit and groundfault protective device. As Safe or Safer. Revised to require the controller and the overload protective device to be identified for installation with the branch-circuit short-circuit and groundfault protective device. 70 2008 851 Evaluation 2005 NEC 2008 NEC compressor shall be provided with overload protection as specified in 440.52(A). Both the controller and the motor overload protective device shall be approved for installation with the short-circuit and ground-fault protective device for the branch circuit to which the equipment is connected. 440.61 Grounding. Room air conditioners shall be grounded in accordance with 250.110, 250.112, and 250.114. Generators compressor shall be provided with overload protection as specified in 440.52(A). Both the controller and the motor overload protective device shall be identified for installation with the short-circuit and ground-fault protective device for the branch circuit to which the equipment is connected. 440.61 Grounding. The enclosures of room air conditioners shall be connected to the equipment grounding conductor in accordance with 250.110, 250.112, and 250.114. Article 445 Generators 445.13 Ampacity of Conductors. …Conductors that must carry groundfault currents shall not be smaller than required by 250.24(C). ……….. 445.13 Ampacity of Conductors. …Conductors that must carry groundfault currents shall not be smaller than required by 250.30(A). …………. 445.18 Disconnecting Means Required for Generators. Generators shall be equipped with disconnect(s) by means of which the generator and all protective devices and control apparatus are able to be disconnected entirely from the circuits supplied by the generator except where both of the following conditions apply: (1) The driving means for the generator 445.18 Disconnecting Means Required for Generators. Generators shall be equipped with disconnect(s), lockable in the open position, by means of which the generator and all protective devices and control apparatus are able to be disconnected entirely from the circuits supplied by the generator except where both of the following conditions apply: Page 226 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Continued emphasis on “connected” to an equipment grounding conductor. As Safe or Safer. Revised to require sizing generator conductors that carry ground-fault current by 250.30(A) instead of 250.24(C). As Safe or Safer. Revised to require the disconnecting means be lockable in the open position. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC can be readily shut down. (2) The generator is not arranged to operate in parallel with another generator or other source of voltage. 2008 NEC Transformers and Transformer Vaults (Including Secondary Ties) (1) The driving means for the generator can be readily shut down. (2) The generator is not arranged to operate in parallel with another generator or other source of voltage. 445.19 Generators Supplying Multiple Loads. A single generator supplying more than one load, or multiple generators operating in parallel, shall be permitted to supply either of the following: (1) A vertical switchboard with separate sections (2) Individual enclosures with overcurrent protection tapped from a single feeder for load separation and distribution. Article 450 Transformers and Transformer Vaults (Including Secondary Ties) 450.5 Grounding Autotransformers 450.5 Grounding Autotransformers (B) Ground Reference for Fault Protection Devices. A grounding autotransformer used to make available a specified magnitude of ground-fault current for operation of a ground-responsive protective device on a 3-phase, 3-wire ungrounded system shall conform to 450.5(B)(1) (B) Ground Reference for Fault Protection Devices. A grounding autotransformer used to make available a specified magnitude of ground-fault current for operation of a ground-responsive protective device on a 3-phase, 3-wire ungrounded system shall conform to 450.5(B)(1) Page 227 of 361 Change Description and Impact to Worker Safety Added section covering the type of distribution equipment that can be used with a generator(s) that supplies multiple loads. As Safe or Safer. Revised to include provisions on overcurrent protection of grounding autotransformers used in highimpedance grounded neutral systems. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC and (B)(2). and (B)(2). (2) Overcurrent Protection. An overcurrent protective device of adequate short-circuit rating that will open simultaneously all ungrounded conductors when it operates shall be applied in the grounding autotransformer branch circuit and shall be rated or set at a current not exceeding 125 percent of the autotransformer continuous per-phase current rating or 42 percent of the continuous-current rating of any series connected devices in the autotransformer neutral connection. Delayed tripping for temporary overcurrents to permit the proper operation of ground-responsive tripping devices on the main system shall be permitted but shall not exceed values that would be more than the short-time current rating of the grounding autotransformer or any series connected devices in the neutral connection thereto. (2) Overcurrent Protection. Overcurrent protection shall comply with (a) and (b). (a) Operation and Interrupting Rating. An overcurrent protective device having an interrupting rating in compliance with 110.9 and that will open simultaneously all ungrounded conductors when it operates shall be applied in the grounding autotransformer branch circuit. (b) Ampere Rating. The overcurrent protection shall be rated or set at a current not exceeding 125 percent of the autotransformer continuous perphase current rating or 42 percent of the continuous-current rating of any series-connected devices in the autotransformer neutral connection. Delayed tripping for temporary overcurrents to permit the proper operation of ground-responsive tripping devices on the main system shall be permitted but shall not exceed values that would be more than the short-time current rating of the grounding autotransformer or any series connected devices in the neutral connection thereto. Page 228 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 450.10 Grounding. Exposed non– current-carrying metal parts of transformer installations, including fences, guards, and so forth, shall be grounded where required under the conditions and in the manner specified for electric equipment and other exposed metal parts in Article 250. Phase Converters 455.3 Other Articles. All applicable requirements of this Code shall apply to phase converters except as amended by this article. 2008 NEC Exception: For high-impedance grounded systems covered in 250.36, where the maximum ground-fault current is designed to be not more than 10 amperes, and where the grounding autotransformer and the grounding impedance are rated for continuous duty, an overcurrent device rated not more than 20 amperes that will simultaneously open all ungrounded conductors shall be permitted to be installed on the line side of the grounding autotransformer. 450.10 Grounding. Where grounded, exposed non–current-carrying metal parts of transformer installations, including fences, guards, and so forth, shall be grounded and bonded under the conditions and in the manner specified for electrical equipment and other exposed metal parts in Parts V, VI, and VII of Article 250. Article 455 Phase Converters 455.3 Other Articles. Phase converters shall comply with this article and with the applicable provisions of other articles of this Code. Article 460 Page 229 of 361 Change Description and Impact to Worker Safety Modified to provide specific reference for the requirements for grounding and bonding of exposed non-current carrying metal parts. As Safe or Safer. Converted to positive Code text to indicate that this article governs phase converters and that other articles of the Code may apply as well. No negative imapct. 70 2008 851 Evaluation 2005 NEC 2008 NEC Capacitors Capacitors 460.10 Grounding. Capacitor cases shall be grounded in accordance with Article 250. 460.27 Grounding. Capacitor neutrals and cases, if grounded, shall be grounded in accordance with Article 250. 460.10 Grounding. Capacitor cases shall be connected to the equipment grounding conductor. 460.27 Grounding. Capacitor cases shall be connected to the equipment grounding conductor. If the capacitor neutral point is connected to a grounding electrode conductor, the connection shall be made in accordance with Part III of Article 250. Exception: Where the capacitor units are supported on a structure that is designed to operate at other than ground potential. Resistors and Reactors Exception: Capacitor cases shall not be connected to the equipment grounding conductor where the capacitor units are supported on a structure designed to operate at other than ground potential. Article 470 Resistors and Reactors 470.19 Grounding. Resistor and reactor cases or enclosures shall be grounded in accordance with Article 250. 470.19 Grounding. Resistor and reactor cases or enclosures shall be connected to the equipment grounding conductor. Exception: Resistor or reactor cases or enclosures supported on a structure designed to operate at other than ground potential shall not be grounded. Exception: Resistor or reactor cases or enclosures supported on a structure designed to operate at other than ground potential shall not be Page 230 of 361 Change Description and Impact to Worker Safety Continued emphasis on “connected” to an equipment grounding conductor. As Safe or Safer. Revised to describe more specifically the grounding component and function. As Safe or Safer. Continued emphasis on “connected” to an equipment grounding conductor. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC Storage Batteries 480.3 Wiring and Equipment Supplied from Batteries. Wiring and equipment supplied from storage batteries shall be subject to the requirements of this Code applying to wiring and equipment operating at the same voltage, unless otherwise permitted by 480.4. Equipment, Over 600 Volts, Nominal 490.36 Grounding. Frames of switchgear and control assemblies shall be grounded. 490.37 Grounding of Devices. Devices with metal cases or frames, or both, such as instruments, relays, meters, 2008 NEC connected to the equipment grounding conductor. Article 480 Storage Batteries 480.3 Wiring and Equipment Supplied from Batteries. Wiring and equipment supplied from storage batteries shall be subject to the applicable provisions of this Code applying to wiring and equipment operating at the same voltage, unless otherwise permitted by 480.4. 480.5 Disconnecting Means. A disconnecting means shall be provided for all ungrounded conductors derived from a stationary battery system over 30 volts. A disconnecting means shall be readily accessible and located within sight of the battery system. Article 490 Equipment, Over 600 Volts, Nominal 490.36 Grounding. Frames of switchgear and control assemblies shall be connected to an equipment grounding conductor or, where permitted, the grounded conductor. 490.37 Grounding of Devices. The metal cases or frames, or both, such as instruments, relays, meters, and Page 231 of 361 Change Description and Impact to Worker Safety Refines the requirements to applicable provisions of the Code pertaining to batteries. As Safe or Safer. New section providing the requirements for a disconnecting means for battery systems over 30 volts. As Safe or Safer. Continued emphasis on “connected” to an equipment grounding conductor. As Safe or Safer. Continued emphasis on “connected” to an equipment grounding conductor. 70 2008 851 Evaluation 2005 NEC and instrument and control transformers, located in or on switchgear or control, shall have the frame or case grounded. 490.44 Fused Interrupter Switches. (C) Switching Mechanism. The switching mechanism shall be arranged to be operated from a location outside the enclosure where the operator is not exposed to energized parts and shall be arranged to open all ungrounded conductors of the circuit simultaneously with one operation. Switches shall be capable of being locked in the open position. 490.55 Power Cable Connections to Mobile Machines. A metallic enclosure 2008 NEC instrument and control transformers, located in or on switchgear or control, shall be connected to an equipment grounding conductor or, where permitted, the grounded conductor. 490.44 Fused Interrupter Switches. (C) Switching Mechanism. The switching mechanism shall be arranged to be operated from a location outside the enclosure where the operator is not exposed to energized parts and shall be arranged to open all ungrounded conductors of the circuit simultaneously with one operation. Switches shall be capable of being locked in the open position. The provisions for locking shall remain in place with or without the lock installed. 490.46 Circuit Breaker Locking. Circuit breakers shall be capable of being locked in the open position or, if they are installed in a drawout mechanism, that mechanism shall be capable of being locked in such a position that the mechanism cannot be moved into the connected position. In either case, the provision for locking shall remain in place with or without the lock. 490.55 Power Cable Connections to Mobile Machines. A metallic enclosure Page 232 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Added requirement for the type of locking provision that has to be provided as part of the installed equipment. As Safe or Safer. 490.46: Added requirement for locking circuit breakers, including the drawout type, in the open position and provisions covering the type of locking provision that has to be provided as part of the installed equipment. Continued emphasis on “connected” to an equipment grounding conductor. 70 2008 851 Evaluation 2005 NEC shall be provided on the mobile machine for enclosing the terminals of the power cable. The enclosure shall include provisions for a solid connection for the ground wire(s) terminal to effectively ground the machine frame. Ungrounded conductors shall be attached to insulators or be terminated in approved high-voltage cable couplers (which include ground wire connectors) of proper voltage and ampere rating. 490.72 Branch-Circuit Requirements. (D) Ground Current Detection. Means shall be provided for detection of the sum of the neutral and ground currents and shall trip the circuit-interrupting device if the sum of those currents exceeds the greater of 5 amperes or 71⁄2 percent of the boiler full-load current for 10 seconds or exceeds an instantaneous value of 25 percent of the boiler full-load current. Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 500.1 Scope — Articles 500 Through 504. Articles 500 through 504 cover 2008 NEC Change Description and Impact to Worker Safety shall be provided on the mobile machine for enclosing the terminals of As Safe or Safer. the power cable. The enclosure shall include terminal connections to the machine frame for the equipment grounding conductor. Ungrounded conductors shall be attached to insulators or be terminated in approved high-voltage cable couplers (which include equipment grounding conductor connectors) of proper voltage and ampere rating. 490.72 Branch-Circuit Requirements. Continued emphasis on an equipment grounding conductor versus just (D) Ground Current Detection. Means ground. shall be provided for detection of the sum of the neutral conductor and As Safe or Safer. equipment grounding conductor currents and shall trip the circuitinterrupting device if the sum of those currents exceeds the greater of 5 amperes or 71⁄2 percent of the boiler full-load current for 10 seconds or exceeds an instantaneous value of 25 percent of the boiler full-load current. Article 500 Hazardous (Classified) Locations, Revised scope and other sections to Classes I, II, and III, Divisions 1 and 2 include ‘‘combustible liquid–produced vapors’’ as affecting area classification, 500.1 Scope — Articles 500 Through and replaced ‘‘ignitible fibers or flyings’’ 504. Articles 500 through 504 cover with ‘‘ignitible fibers/flyings’’ in the Page 233 of 361 70 2008 851 Evaluation 2005 NEC the requirements for electrical and electronic equipment and wiring for all voltages in Class I, Divisions 1 and 2; Class II, Divisions 1 and 2; and Class III, Divisions 1 and 2 locations where fire or explosion hazards may exist due to flammable gases or vapors, flammable liquids, combustible dust, or ignitible fibers or flyings. 500.5 Classifications of Locations. 2008 NEC Change Description and Impact to Worker Safety scope and other sections. the requirements for electrical and electronic equipment and wiring for all voltages in Class I, Divisions 1 and 2; As Safe or Safer. Class II, Divisions 1 and 2; and Class III, Divisions 1 and 2 locations where fire or explosion hazards may exist due to flammable gases, flammable liquid– produced vapors, combustible liquid– produced vapors, combustible dusts, or ignitible fibers/flyings. 500.5 Classifications of Locations. Revised several sections to include ‘‘combustible liquid–produced vapors’’ as affecting area classification, and replaced ‘‘ignitible fibers or flyings’’ with ‘‘ignitible fibers/flyings’’. (K) Combustible Gas Detection System. (1) Inadequate Ventilation. (2) Interior of a Building. (3) Interior of a Control Panel. As Safe or Safer. Added listing requirements in (K)(1) through (K)(3) for specific applications of combustible gas detection equipment with a statement similar to: “Combustible gas detection equipment shall be listed for Class I, Division 1 or Class I, Division 2, for the appropriate material group, and for the detection of the specific gas or vapor to be encountered.” 500.8 Equipment. As Safe or Safer. New section extracted from original (A)(1) was inserted to emphasize the 500.7 Protection Techniques. Page 234 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC 500.8 Equipment. (A) Suitability. Suitability of identified equipment shall be determined by one of the following: (1) Equipment listing or labeling (2) Evidence of equipment evaluation from a qualified testing laboratory or inspection agency concerned with product evaluation (3) Evidence acceptable to the authority having jurisdiction such as a manufacturer’s self-evaluation or an owner’s engineering judgment. 500.8 Equipment. (A) Approval for Class and Properties. (1) Equipment shall be identified not only for the class of location but also for the explosive, combustible, or ignitible properties of the specific gas, vapor, dust, fiber, or flyings that will be present. In addition, Class I equipment shall not have any exposed surface that operates at a temperature in excess of the ignition temperature of the specific gas or vapor. Class II equipment shall not have an external temperature higher than that specified in 500.8(C)(2). Class III equipment shall not exceed the maximum surface temperatures specified in 503.5. 500.8 Equipment. (B) Approval for Class and Properties. (1) Equipment shall be identified not only for the class of location but also for the explosive, combustible, or ignitible properties of the specific gas, vapor, dust, or fibers/flyings that will be present. In addition, Class I equipment shall not have any exposed surface that operates at a temperature in excess of the ignition temperature of the specific gas or vapor. Class II equipment shall not have an external temperature higher than that specified in 500.8(D)(2). Class III equipment shall not exceed the maximum surface temperatures specified in 503.5. 500.8 Equipment. Page 235 of 361 Change Description and Impact to Worker Safety requirements for determining suitability of equipment. As Safe or Safer. Revised to replace ‘‘ignitible fibers or flyings’’ with ‘‘ignitible fibers/flyings’’. As Safe or Safer. Clarified that the required temperature 70 2008 851 Evaluation 2005 NEC 2008 NEC (B) Marking. (C) Marking. (5) Ambient Temperature Range. For equipment rated for a temperature range other than –25°C to +40°C, the marking shall specify the special range of ambient temperatures. The marking shall include either the symbol “Ta” or “Tamb.” Class I Locations (5) Ambient Temperature Range. For equipment rated for a temperature range other than –25°C to +40°C, the marking shall specify the special range of ambient temperatures in degrees Celsius. The marking shall include either the symbol “Ta” or “Tamb.” Article 501 Class I Locations 501.10 Wiring Methods. 501.10 Wiring Methods. (A) Class I, Division 1. (A) Class I, Division 1. (1) General. (1) General. Exception: Rigid nonmetallic conduit complying with Article 352 shall be permitted where encased in a concrete envelope…… 501.10 Wiring Methods. Exception: Type PVC conduit and Type RTRC conduit shall be permitted where encased in a concrete envelope….. 501.10 Wiring Methods. (B) Class I, Division 2. (B) Class I, Division 2. (1) General. (1) General. Change Description and Impact to Worker Safety range marking is to be in degrees Celsius. As Safe or Safer. Revised to permit PVC and RTRC types of nonmetallic conduit. As Safe or Safer. Deleted requirement for all single conductor MV cables to be shielded or metallic armored where not required by Chapter 3. As Safe or Safer. (6) Type MI, MC, MV, or TC cable with termination fittings, or in cable tray (6) Type MI, MC, MV, or TC cable with termination fittings, or in cable tray Page 236 of 361 70 2008 851 Evaluation 2005 NEC systems and installed in a manner to avoid tensile stress at the termination fittings. Single conductor Type MV cables shall be shielded or metallic armored. 2008 NEC Change Description and Impact to Worker Safety systems and installed in a manner to avoid tensile stress at the termination fittings. 501.10 Wiring Methods. (B) Class I, Division 2. Added new section for provisions on the use of Schedule 80 PVC and RTRC types of nonmetallic conduit in Class I, Division 2 locations. (1) General. As Safe or Safer. (7) In industrial establishments with restricted public access where the conditions of maintenance and supervision ensure that only qualified persons service the installation and where metallic conduit does not provide sufficient corrosion resistance, reinforced thermosetting resin conduit (RTRC), factory elbows, and associated fittings, all marked with the suffix -XW, and Schedule 80 PVC conduit, factory elbows, and associated fittings shall be permitted. Where seals are required for boundary conditions as defined in 501.15(A)(4), the Division 1 wiring method shall extend into the Division 2 area to the seal, which shall be located on the Division 2 side of the Division 1– Division 2 boundary. Page 237 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC 501.30 Grounding and Bonding, Class I, Divisions 1 and 2. 501.30 Grounding and Bonding, Class I, Divisions 1 and 2. (B) Types of Equipment Grounding Conductors. Where flexible metal conduit or liquidtight flexible metal conduit is used as permitted in 501.10(B) and is to be relied on to complete a sole equipment grounding path, it shall be installed with internal or external bonding jumpers in parallel with each conduit and complying with 250.102. 501.35 Surge Protection. (B) Types of Equipment Grounding Conductors. Flexible metal conduit and liquidtight flexible metal conduit shall not be used as the sole ground-fault current path. Where equipment bonding jumpers are installed, they shall comply with 250.102. (A) Class I, Division 1. Surge arresters, transient voltage surge suppressors (TVSS), and capacitors shall be installed in enclosures identified for Class I, Division 1 locations. Surgeprotective capacitors shall be of a type designed for specific duty. (A) Class I, Division 1. Surge arresters, surge-protective devices, and capacitors shall be installed in enclosures identified for Class I, Division 1 locations. Surge-protective capacitors shall be of a type designed for specific duty. 501.35 Surge Protection. 501.35 Surge Protection. (B) Class I, Division 2. Surge arresters and TVSS shall be nonarcing, such as metal-oxide varistor (MOV) sealed type, and surge-protective capacitors shall be of a type designed for specific duty. Enclosures shall be permitted to (B) Class I, Division 2. Surge arresters and surge-protective devices shall be nonarcing, such as metal-oxide varistor (MOV) sealed type, and surgeprotective capacitors shall be of a type designed for specific duty. Enclosures 501.35 Surge Protection. Page 238 of 361 Change Description and Impact to Worker Safety Clarified that flexible metal conduit and liquidtight flexible metal conduit cannot be used as the sole ground-fault current path and that an internal or external bonding jumper is required. As Safe or Safer. Revised to correlate with changes made in Articles 280 and 285 and UL 1449. As Safe or Safer. Revised to correlate with changes made in Articles 280 and 285 and UL 1449. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC be of the general-purpose type. Surge protection of types other than described in this paragraph shall be installed in enclosures identified for Class I, Division 1 locations. III. Equipment shall be permitted to be of the generalpurpose type. Surge protection of types other than described in this paragraph shall be installed in enclosures identified for Class I, Division 1 locations. III. Equipment 501.100 Transformers and Capacitors. 501.100 Transformers and Capacitors. Revised to permit transformers identified for Class I locations to be installed without a vault. (A) Class I, Division 1. (A) Class I, Division 1. As Safe or Safer. (2) Not Containing Liquid That Will Burn. Transformers and capacitors that do not contain a liquid that will burn shall be installed in vaults complying with 501.100(A)(1) or be approved for Class I locations. (2) Not Containing Liquid That Will Burn. Transformers and capacitors that do not contain a liquid that will burn shall be installed in vaults complying with 501.100(A)(1) or be identified for Class I locations. Article 502 Class II Locations Deleted performance requirement on surface temperatures of equipment 502.5 Explosionproof Equipment. because it is covered by 500.8(D)(2). Class II Locations 502.5 General. The general rules of this Code shall apply to the electric wiring and equipment in locations classified as Class II locations in 500.5(C). Change Description and Impact to Worker Safety As Safe or Safer. Equipment installed in Class II locations shall be able to function at full rating without developing surface temperatures high enough to cause Page 239 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety excessive dehydration or gradual carbonization of any organic dust deposits that may occur. Explosionproof equipment and wiring shall not be required and shall not be acceptable in Class II locations unless identified for such locations. II. Wiring Explosionproof equipment and wiring shall not be required and shall not be acceptable in Class II locations unless identified for such locations. II. Wiring 502.10 Wiring Methods. 502.10 Wiring Methods. (A) Class II, Division 1. (A) Class II, Division 1. (1) General. (1) General. (3) In industrial establishments with limited public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation, Type MC cable, listed for use in Class II, Division 1 locations, with a gas/vaportight continuous corrugated metallic sheath, an overall jacket of suitable polymeric material, separate grounding conductors in accordance with 250.122, and provided with termination fittings listed for the application, shall be permitted. 502.30 Grounding and Bonding, Class (3) In industrial establishments with limited public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation, Type MC-HL cable, listed for use in Class II, Division 1 locations, with a gas/vaportight continuous corrugated metallic sheath, an overall jacket of suitable polymeric material, a separate equipment grounding conductor(s) in accordance with 250.122, and provided with termination fittings listed for the application, shall be permitted. 502.30 Grounding and Bonding, Class Clarified that listed MC cable must be marked MC-HL. As Safe or Safer. Page 240 of 361 Clarified that flexible metal conduit and 70 2008 851 Evaluation 2005 NEC 2008 NEC II, Divisions 1 and 2. II, Divisions 1 and 2. (B) Types of Equipment Grounding Conductors. Where flexible conduit is used as permitted in 502.10, it shall be installed with internal or external bonding jumpers in parallel with each conduit and complying with 250.102. (B) Types of Equipment Grounding Conductors. Liquidtight flexible metal conduit shall not be used as the sole ground-fault current path. Where equipment bonding jumpers are installed, they shall comply with 250.102. 502.35 Surge Protection — Class II, Divisions 1 and 2. Surge arresters and surge-protective devices installed in a Class II, Division 1 location shall be in suitable enclosures. Surge-protective capacitors shall be of a type designed for specific duty. 502.35 Surge Protection — Class II, Divisions 1 and 2. Surge arresters and transient voltage surge suppressors (TVSS) installed in a Class II, Division 1 location shall be in suitable enclosures. Surge-protective capacitors shall be of a type designed for specific duty. 502.115 Switches, Circuit Breakers, Motor Controllers, and Fuses. 502.115 Switches, Circuit Breakers, Motor Controllers, and Fuses. Change Description and Impact to Worker Safety liquidtight flexible metal conduit cannot be used as the sole ground-fault current path and that an internal or external bonding jumper is required. As Safe or Safer. Revised to correlate with changes made in Articles 280 and 285 and UL 1449. As Safe or Safer. (A) Class II, Division 1. (A) Class II, Division 1. Deleted provisions permitting isolating and disconnecting switches to be installed in other than dustignitionproof enclosures. (2) Isolating Switches. Disconnecting and isolating switches containing no fuses and not intended to interrupt current and not installed where dusts may be of an electrically conductive nature shall be provided with tight metal enclosures that shall be designed to minimize the entrance of dust and that shall (1) be equipped As Safe or Safer. Page 241 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC with telescoping or close-fitting covers or with other effective means to prevent the escape of sparks or burning material and (2) have no openings (such as holes for attachment screws) through which, after installation, sparks or burning material might escape or through which exterior accumulations of dust or adjacent combustible material might be ignited. 502.120 Control Transformers and 502.120 Control Transformers and Resistors. Resistors. (B) Class II, Division 2. Change Description and Impact to Worker Safety Revised to include dusttight enclosures and set effective date after which all enclosures are required to be dusttight. (B) Class II, Division 2. As Safe or Safer. (2) Coils and Windings. Where not located in the same enclosure with switching mechanisms, control transformers, solenoids, and impedance coils shall be provided with tight metal housings without ventilating openings. 502.130 Luminaires. (2) Coils and Windings. Where not located in the same enclosure with switching mechanisms, control transformers, solenoids, and impedance coils shall be provided with tight metal housings without ventilating openings or shall be installed in dusttight enclosures. Effective January 1, 2011, only dusttight enclosures shall be permitted. 502.130 Luminaires. (B) Class II, Division 2. (B) Class II, Division 2. (2) Fixed Lighting. Luminaires (lighting (2) Fixed Lighting. Luminaires for fixed Page 242 of 361 Revised to require luminaires for fixed lighting be identified for Class II locations or be provided with dusttight enclosures. 70 2008 851 Evaluation 2005 NEC 2008 NEC fixtures) for fixed lighting, where not of a type identified for Class II locations, shall provide enclosures for lamps and lampholders that shall be designed to minimize the deposit of dust on lamps and to prevent the escape of sparks, burning material, or hot metal. Each fixture shall be clearly marked to indicate the maximum wattage of the lamp that shall be permitted without exceeding an exposed surface temperature in accordance with 500.8(C)(2) under normal conditions of use. 502.150 Signaling, Alarm, RemoteControl, and Communications Systems; and Meters, Instruments, and Relays. lighting, where not of a type identified for Class II locations, shall be provided with dusttight enclosures. Each fixture shall be clearly marked to indicate the maximum wattage of the lamp that shall be permitted without exceeding an exposed surface temperature in accordance with 500.8(D)(2) under normal conditions of use. (B) Class II, Division 2. (1) Contacts. Enclosures shall comply with 502.150(A)(2), or contacts shall have tight metal enclosures designed to minimize the entrance of dust and shall have telescoping or tight-fitting covers and no openings through which, after installation, sparks or burning material might escape. Change Description and Impact to Worker Safety As Safe or Safer. 502.150 Signaling, Alarm, RemoteRevised to include dusttight enclosures Control, and Communications and set effective date after which all Systems; and Meters, Instruments, and enclosures are required to be dusttight. Relays. As Safe or Safer. (B) Class II, Division 2. (1) Contacts. Contacts shall comply with 502.150(A)(1), or contacts shall have tight metal enclosures designed to minimize the entrance of dust and shall have telescoping or tight-fitting covers and no openings through which, after installation, sparks or burning material might escape or shall be installed in dusttight enclosures. Effective January 1, 2011, only Page 243 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety dusttight enclosures shall be permitted. 502.150 Signaling, Alarm, Remote502.150 Signaling, Alarm, RemoteAdded reference to 502.120(B)(2) for Control, and Communications Control, and Communications the type of enclosure, which includes Systems; and Meters, Instruments, and Systems; and Meters, Instruments, and dusttight enclosures. Relays. Relays. As Safe or Safer. (B) Class II, Division 2. (B) Class II, Division 2. (2) Transformers and Similar Equipment. The windings and terminal connections of transformers, choke coils, and similar equipment shall be provided with tight metal enclosures without ventilating openings. 502.150 Signaling, Alarm, RemoteControl, and Communications Systems; and Meters, Instruments, and Relays. (2) Transformers and Similar Equipment. The windings and terminal connections of transformers, choke coils, and similar equipment shall comply with 502.120(B)(2). 502.150 Signaling, Alarm, RemoteControl, and Communications Systems; and Meters, Instruments, and Relays. Added reference to 502.120(B)(3) for the type of enclosure. Deleted exception for (3) in lieu of the modified compliance statement. (B) Class II, Division 2. (B) Class II, Division 2. As Safe or Safer. (3) Resistors and Similar Equipment. Resistors, resistance devices, thermionic tubes, rectifiers, and similar equipment shall comply with 502.130(A)(3). (3) Resistors and Similar Equipment. Resistors, resistance devices, thermionic tubes, rectifiers, and similar equipment shall comply with 502.120(B)(3). Exception: Enclosures for thermionic tubes, nonadjustable resistors, or rectifiers for which maximum operating temperature will not exceed 120°C Page 244 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety (248°F) shall be permitted to be of the general-purpose type. 502.150 Signaling, Alarm, RemoteControl, and Communications Systems; and Meters, Instruments, and Relays. 502.150 Signaling, Alarm, RemoteDeleted (5) as it was redundant. Control, and Communications Systems; and Meters, Instruments, and As Safe or Safer. Relays. (B) Class II, Division 2. (B) Class II, Division 2. (5) Wiring Methods. The wiring method shall comply with 502.10(B). Class III Locations Article 503 Class III Locations I. General 503.1 Scope. Article 503 covers the requirements for electrical and electronic equipment and wiring for all voltages in Class III, Division 1 and 2 locations where fire or explosion hazards may exist due to ignitible fibers or flyings. 503.30 Grounding and Bonding — Class III, Divisions 1 and 2. I. General 503.1 Scope. Article 503 covers the requirements for electrical and electronic equipment and wiring for all voltages in Class III, Division 1 and 2 locations where fire or explosion hazards may exist due to ignitible fibers/flyings. 503.30 Grounding and Bonding — Class III, Divisions 1 and 2. (B) Types of Equipment Grounding Conductors. Where flexible conduit is used as permitted in 503.10, it shall be installed with internal or external bonding jumpers in parallel with each (B) Types of Equipment Grounding Conductors. Liquidtight flexible metal conduit shall not be used as the sole ground-fault current path. Where equipment bonding jumpers are Page 245 of 361 Replaced ‘‘ignitible fibers or flyings’’ with ‘‘ignitible fibers/flyings’’ in the scope and other sections. As Safe or Safer. Clarified that flexible metal conduit and liquidtight flexible metal conduit cannot be used as the sole ground-fault current path and that an internal or external bonding jumper is required. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC conduit and complying with 250.102. Intrinsically Safe Systems 2008 NEC installed, they shall comply with 250.102. Article 504 Intrinsically Safe Systems Change Description and Impact to Worker Safety Clarified permitted wiring methods. 504.20 Wiring Methods. Intrinsically safe apparatus and wiring shall be permitted to be installed using any of the wiring methods suitable for unclassified locations, including Chapter 7 and Chapter 8. Sealing shall be as provided in 504.70, and separation shall be as provided in 504.30. 504.30 Separation of Intrinsically Safe Conductors. 504.20 Wiring Methods. Any of the As Safe or Safer. wiring methods suitable for unclassified locations, including those covered by Chapter 7 and Chapter 8, shall be permitted for installing intrinsically safe apparatus. Sealing shall be as provided in 504.70, and separation shall be as provided in 504.30. (A) From Nonintrinsically Safe Circuit Conductors. (A) From Nonintrinsically Safe Circuit Conductors. (1) In Raceways, Cable Trays, and Cables. Conductors of intrinsically safe circuits shall not be placed in any raceway, cable tray, or cable with conductors of any nonintrinsically safe circuit. (1) In Raceways, Cable Trays, and Cables. Conductors of intrinsically safe circuits shall not be placed in any raceway, cable tray, or cable with conductors of any nonintrinsically safe circuit. 504.30 Separation of Intrinsically Safe Conductors. Exception No. 3: Intrinsically safe circuits in a Division 2 or Zone 2 location shall be permitted to be installed in a raceway, cable tray, or Page 246 of 361 Added two exceptions on intrinsically safe and nonincendive field wiring circuits sharing a common raceway, cable, or cable tray in Division or Zone 2 locations and on intrinsically safe circuits passing through a Division or Zone 2 location in route to a Division 1, Zone 0, or Zone 1 sharing a common raceway, cable, or cable tray with nonincendive field wiring circuits. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety cable along with nonincendive field wiring circuits when installed in accordance with 504.30(B). 504.30 Separation of Intrinsically Safe Conductors. Exception No. 4: Intrinsically safe circuits passing through a Division 2 or Zone 2 location to supply apparatus that is located in a Division 1, Zone 0 or Zone 1 location shall be permitted to be installed in a raceway, cable tray, or cable along with nonincendive field wiring circuits when installed in accordance with 504.30(B). 504.30 Separation of Intrinsically Safe Conductors. (A) From Nonintrinsically Safe Circuit Conductors. (A) From Nonintrinsically Safe Circuit Conductors. (2) Within Enclosures. (2) Within Enclosures. Conductors of intrinsically safe circuits shall be separated from conductors of nonintrinsically safe circuits by one of the following means: Added three methods to separate intrinsically safe circuits from nonintrinsically safe circuits in enclosures. As Safe or Safer. (1) Conductors of intrinsically safe circuits shall be separated at least 50 mm (2 in.) from conductors of any nonintrinsically safe circuits, or as specified in 504.30(A)(2). (2) All conductors shall be secured so that any conductor that might come loose from a terminal cannot come in contact with another terminal. (1) Separation by at least 50 mm (2 in.) from conductors of any nonintrinsically safe circuits. (2) Separation from conductors of nonintrinsically safe circuits by use of a Page 247 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety grounded metal partition 0.91 mm (0.0359 in.) or thicker. (3) Separation from conductors of nonintrinsically safe circuits by use of an approved insulating partition. 504.50 Grounding. (4) Where either (1) all of the intrinsically safe circuit conductors or (2) all of the nonintrinsically safe circuit conductors are in grounded metalsheathed or metalclad cables where the sheathing or cladding is capable of carrying fault current to ground. 504.50 Grounding. (A) Intrinsically Safe Apparatus, Associated Apparatus, and Raceways. Intrinsically safe apparatus, associated apparatus, cable shields, enclosures, and raceways, if of metal, shall be grounded. 504.50 Grounding. (A) Intrinsically Safe Apparatus, Enclosures, and Raceways. Intrinsically safe apparatus, enclosures, and raceways, if of metal, shall be connected to the equipment grounding conductor. 504.50 Grounding. (B) Associated Apparatus and Cable Shields. Associated apparatus and cable shields shall be grounded in accordance with the required control drawing. See 504.10(A). (B) Connection to Grounding (C) Connection to Grounding Page 248 of 361 Continued emphasis on connected to an equipment grounding conductor versus just grounded. As Safe or Safer. Added requirement for associated apparatus and cable shields to be grounded in accordance with the control diagram. Old section (C) incorporated into new Section (B). As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Electrodes. Where connection to a grounding electrode is required, the grounding electrode shall be as specified in 250.52(A)(1), (A)(2), (A)(3), and (A)(4) and shall comply with 250.30(A)(7). Section 250.52(A)(5), (A)(6), and (A)(7) shall not be used if electrodes specified in 250.52(A)(1), (A)(2), (A)(3), or (A)(4) are available. Electrodes. Where connection to a grounding electrode is required, the grounding electrode shall be as specified in 250.52(A)(1), (A)(2), (A)(3), and (A)(4) and shall comply with 250.30(A)(7). Sections 250.52(A)(5), (A)(7), and (A)(8) shall not be used if any of the electrodes specified in 250.52(A)(1), (A)(2), (A)(3), or (A)(4) are present. (C) Shields. Where shielded conductors or cables are used, shields shall be grounded. Exception: Where a shield is part of an intrinsically safe circuit. 504.70 Sealing. Conduits and cables that are required to be sealed by 501.15, 502.15, and 505.16 shall be sealed to minimize the passage of gases, vapors, or dusts. Such seals shall not be required to be explosionproof or flameproof. Change Description and Impact to Worker Safety Class I, Zone 0, 1, and 2 Locations 504.70 Sealing. Conduits and cables that are required to be sealed by 501.15, 502.15, 505.16, and 506.16 shall be sealed to minimize the passage of gases, vapors, or dusts. Such seals shall not be required to be explosionproof or flameproof but shall be identified for the purpose of minimizing passage of gases, vapors, or dusts under normal operating conditions and shall be accessible. Article 505 Class I, Zone 0, 1, and 2 Locations 505.7 Special Precaution. Article 505 505.7 Special Precaution. Article 505 Page 249 of 361 Revised to require that seals be identified for the purpose of minimizing passage of gases, vapors, or dust under normal operating conditions and for seals to be accessible. As Safe or Safer. Revised to require that all functions associated with using the zone classification system for electrical 70 2008 851 Evaluation 2005 NEC 2008 NEC requires equipment construction and installation that ensures safe performance under conditions of proper use and maintenance. requires equipment construction and installation that ensures safe performance under conditions of proper use and maintenance. (A) Supervision of Work. Classification of areas and selection of equipment and wiring methods shall be under the supervision of a qualified Registered Professional Engineer. 505.8 Protection Techniques. (A) Implementation of Zone Classification System. Classification of areas, engineering and design, selection of equipment and wiring methods, installation, and inspection shall be performed by qualified persons. 505.8 Protection Techniques. 505.8 Protection Techniques. (I) Encapsulation “mb”. This protection technique shall be permitted for equipment in Class I, Zone 1 or Zone 2 locations. 505.8 Protection Techniques. Change Description and Impact to Worker Safety installations involve qualified persons. As Safe or Safer. Added to specify application of ‘‘ma’’ and ‘‘mb’’ encapsulation protection (H) Encapsulation “ma”. This protection techniques. technique shall be permitted for equipment in Class I, Zone 0, Zone 1, As Safe or Safer. or Zone 2 locations. (I) Combustible Gas Detection System. (K) Combustible Gas Detection System. (1) Inadequate Ventilation. In a Class I, Zone 1 location that is so classified due to inadequate ventilation, electrical (1) Inadequate Ventilation. In a Class I, Zone 1 location that is so classified due to inadequate ventilation, electrical Added listing requirements for specific applications of combustible gas detection equipment. As Safe or Safer. Page 250 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC equipment suitable for Class I, Zone 2 locations shall be permitted. equipment suitable for Class I, Zone 2 locations shall be permitted. Combustible gas detection equipment shall be listed for Class I, Zone 1, for the appropriate material group, and for the detection of the specific gas or vapor to be encountered. 505.8 Protection Techniques. 505.8 Protection Techniques. (I) Combustible Gas Detection System. (2) Interior of a Building. In a building located in, or with an opening into, a Class I, Zone 2 location where the interior does not contain a source of flammable gas or vapor, electrical equipment for unclassified locations shall be permitted. 505.8 Protection Techniques. (I) Combustible Gas Detection System. (3) Interior of a Control Panel. In the interior of a control panel containing instrumentation utilizing or measuring (K) Combustible Gas Detection System. Change Description and Impact to Worker Safety Added listing requirements for specific applications of combustible gas detection equipment. As Safe or Safer. (2) Interior of a Building. In a building located in, or with an opening into, a Class I, Zone 2 location where the interior does not contain a source of flammable gas or vapor, electrical equipment for unclassified locations shall be permitted. Combustible gas detection equipment shall be listed for Class I, Zone 1 or Class I, Zone 2, for the appropriate material group, and for the detection of the specific gas or vapor to be encountered. 505.8 Protection Techniques. (K) Combustible Gas Detection System. Added listing requirements for specific applications of combustible gas detection equipment. As Safe or Safer. (3) Interior of a Control Panel. In the interior of a control panel containing Page 251 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC flammable liquids, gases, or vapors, electrical equipment suitable for Class I, Zone 2 locations shall be permitted. 505.9 Equipment. instrumentation utilizing or measuring flammable liquids, gases, or vapors, electrical equipment suitable for Class I, Zone 2 locations shall be permitted. Combustible gas detection equipment shall be listed for Class I, Zone 1, for the appropriate material group, and for the detection of the specific gas or vapor to be encountered. 505.9 Equipment. (C) Marking. (C) Marking. (2) Zone Equipment. ………..Electrical equipment of types of protection “e,” “m,” “p,” or “q” shall be marked Group II. (2) Zone Equipment. ………..Electrical equipment of types of protection “e,” “m,” “ma,” “mb,” “px,” “py,” “pz,” or “q” shall be marked Group II……. Change Description and Impact to Worker Safety Included encapsulation types ‘‘ma’’ and ‘‘mb,’’ replaced pressurization type ‘‘p’’ with ‘‘px, ‘‘py,’’ and ‘‘pz,’’ and added a note to identify the conditions under which associated apparatus can be installed in hazardous locations. As Safe or Safer. Table 505.9(C)(2)(4) Types of Protection Designation 505.9 Equipment. **Associated apparatus is permitted to be installed in a hazardous (classified) location if suitably protected using another type of protection. 505.9 Equipment. (D) Class I Temperature. (D) Class I Temperature. (1) Temperature Classifications. (1) Temperature Classifications. Clarified that the required temperature range marking is to be in degrees Celsius. Moved commentary to a new Fine Print Note. As Safe or Safer. Page 252 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC ………….Electrical equipment that is designed for use in a range of ambient temperatures other than −20°C and +40°C is considered to be special; and the ambient temperature range shall then be marked on the equipment, including either the symbol “Ta” or “Tamb” together with the special range of ambient temperatures. As an example, such a marking might be “−30°C ≤ Ta ≤ + 40°C.” 505.9 Equipment. …………..Electrical equipment that is designed for use in a range of ambient temperatures other than −20°C to +40°C is considered to be special; and the ambient temperature range shall then be marked on the equipment, including either the symbol “Ta” or “Tamb” together with the special range of ambient temperatures, in degrees Celsius. 505.9 Equipment. 505.15 Wiring Methods. (F) Fiber Optic Cable Assembly. Where a fiber optic cable assembly contains conductors that are capable of carrying current, the fiber optic cable assembly shall be installed in accordance with 505.15 and 505.16, as applicable. 505.15 Wiring Methods. (C) Class I, Zone 2. (C) Class I, Zone 2. (1) General. (1) General. (g) In industrial establishments with restricted public access where the conditions of maintenance and supervision ensure that only qualified persons service the installation and Page 253 of 361 Change Description and Impact to Worker Safety Added requirement on the installation of fiber optic cable assemblies. As Safe or Safer. Added provisions on the use of Schedule 80 PVC and RTRC types of nonmetallic conduit in Class I, Zone 2 locations by inserting new section (g) ahead of the existing section (g) and renumbering it (h). As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 505.17 Flexible Cords, Class I, Zones 1 and 2. where metallic conduit does not provide sufficient corrosion resistance, reinforced thermosetting resin conduit (RTRC), factory elbows, and associated fittings, all marked with the suffix -XW, and Schedule 80 PVC conduit, factory elbows, and associated fittings shall be permitted. Where seals are required for boundary conditions as defined in 505.16(C)(1)(b), the Zone 1 wiring method shall extend into the Zone 2 area to the seal, which shall be located on the Zone 2 side of the Zone 1–Zone 2 boundary. 505.17 Flexible Cords, Class I, Zones 1 and 2. 505.25 Grounding and Bonding. (6) Cord entering an increased safety “e” enclosure shall be terminated with a listed increased safety “e” cord connector. 505.25 Grounding and Bonding. (B) Types of Equipment Grounding Conductors. Where flexible metal conduit or liquidtight flexible metal conduit is used as permitted in 505.15(C) and is to be relied on to complete a sole equipment grounding path, it shall be installed with internal (B) Types of Equipment Grounding Conductors. Flexible metal conduit and liquidtight flexible metal conduit shall not be used as the sole ground-fault current path. Where equipment bonding jumpers are installed, they shall comply with 250.102. Page 254 of 361 Change Description and Impact to Worker Safety Added requirement for cord connectors entering safety ‘‘e’’ enclosures. As Safe or Safer. Clarified that flexible metal conduit and liquidtight flexible metal conduit cannot be used as the sole ground-fault current path and that an internal or external bonding jumper is required. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety or external bonding jumpers in parallel with each conduit and complying with 250.102. Article 506 Zone 20, 21, and 22 Locations for Zone 20, 21, and 22 Locations for Combustible Dusts, Fibers, and Flyings Combustible Dusts or Ignitible Fibers/Flyings 506.2 Definitions. 506.2 Definitions. Protection by Encapsulation “mD.” Type of protection where electrical parts that could cause ignition of a mixture of combustible dust or fibers/flyings in air are protected by enclosing them in a compound in such a way that the explosive atmosphere cannot be ignited. Protection by Enclosure “tD.” Type of protection for explosive dust atmospheres where electrical apparatus is provided with an enclosure providing dust ingress protection and a means to limit surface temperatures. Protection by Intrinsic Safety “iD.” Type of protection where any spark or thermal effect is incapable of causing Page 255 of 361 Replaced ‘‘ignitible fibers or flyings’’ with ‘‘ignitible fibers/flyings’’ in the scope and other sections. As Safe or Safer. Added definitions for protection by encapsulation ’’mD,’’ enclosure ‘‘tD,’’ intrinsic safety ‘‘iD,’’ and pressurization ‘‘pD.’’ As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety ignition of a mixture of combustible dust, fibers, or flyings in air under prescribed test conditions. 506.8 Protection Techniques. Protection by Pressurization “pD.” Type of protection that guards against the ingress of a mixture of combustible dust or fibers/flyings in air into an enclosure containing electrical equipment by providing and maintaining a protective gas atmosphere inside the enclosure at a pressure above that of the external atmosphere. 506.8 Protection Techniques. (E) Encapsulation “maD”. This protection technique shall be permitted for equipment in Zone 20, Zone 21, and Zone 22 locations for which it is identified. (F) Encapsulation “mbD”. This protection technique shall be permitted for equipment in Zone 21 and Zone 22 locations for which it is identified. (E) Nonincendive Circuit. This protection technique shall be permitted for equipment in Zone 22 locations for which it is identified. (G) Nonincendive Circuit. This protection technique shall be permitted for equipment in Zone 22 locations for which it is identified. Page 256 of 361 • 506.8: Added section to specify application of protection techniques: encapsulation ‘‘maD,’’ encapsulation ‘‘mbD,’’ enclosure ‘‘tD,’’ pressurization ‘‘pD,’’ and intrinsic safety ‘‘iD.’’ As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC (F) Nonincendive Equipment. This protection technique shall be permitted for equipment in Zone 22 locations for which it is identified. (H) Nonincendive Equipment. This protection technique shall be permitted for equipment in Zone 22 locations for which it is identified. Change Description and Impact to Worker Safety (I) Protection by Enclosure “tD”. This protection technique shall be permitted for equipment in Zone 21 and Zone 22 locations for which it is identified. (J) Protection by Pressurization “pD”. This protection technique shall be permitted for equipment in Zone 21 and Zone 22 locations for which it is identified. 506.9 Equipment Requirements. (C) Marking. Equipment identified for Class II, Division 1 or Class II, Division 2 shall, in addition to being marked in accordance with 500.8(B), be permitted to be marked with both of the following: (1) Zone 20, 21, or 22 (as applicable) (K) Protection by Intrinsic Safety “iD”. This protection technique shall be permitted for equipment in Zone 20, Zone 21, and Zone 22 locations for which it is listed. 506.9 Equipment Requirements. Added new section for marking requirements for zone equipment. (C) Marking. As Safe or Safer. (1) Division Equipment. Equipment identified for Class II, Division 1 or Class II, Division 2 shall, in addition to being marked in accordance with 500.8(C), be permitted to be marked Page 257 of 361 70 2008 851 Evaluation 2005 NEC (2) Temperature classification in accordance with 506.9(D) 2008 NEC Change Description and Impact to Worker Safety with both of the following: (1) Zone 20, 21, or 22 (as applicable) (2) Temperature classification in accordance with 506.9(D) (2) Zone Equipment. Equipment meeting one or more of the protection techniques described in 506.8 shall be marked with the following in the order shown: (1) Symbol “AEx” (2) Protection technique(s) in accordance with Table 506.9(C)(2)(2) (3) Zone (4) Temperature classification, marked as a temperature value, in degrees C, preceded by T (5) Ambient temperature marking in accordance with 506.9(D) Table 506.9(C)(2)(2) Types of Protection Designation Added Table 506.9(C)(2)(2) providing information on permitted zone applications for protection techniques. Designation – Technique – Zone 506.9 Equipment Requirements. 506.9 Equipment Requirements. (F) Fiber Optic Cable Assembly. Where a fiber optic cable assembly contains conductors that are capable Page 258 of 361 As Safe or Safer. Added new section for requirements on the installation of fiber optic cable assemblies. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 506.15 Wiring Methods. of carrying current, the fiber optic cable assembly shall be installed in accordance with 506.15 and 506.16, as applicable. 506.15 Wiring Methods. (A) Zone 20. (A) Zone 20. (3) In industrial establishments with limited public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation, Type MC cable, listed for continuous use in Zone 20 locations, with a gas/vaportight continuous corrugated metallic sheath, and overall jacket of suitable polymeric material, separate grounding conductors in accordance with 250.122, and provided with termination fittings listed for the application, shall be permitted. (3) In industrial establishments with limited public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation, Type MC-HL cable, listed for use in Zone 20 locations, with a gas/vaportight continuous corrugated metallic sheath and overall jacket of suitable polymeric material, a separate equipment grounding conductor(s) in accordance with 250.122, and provided with termination fittings listed for the application, shall be permitted. Exception: MC cable and fittings listed for Class II, Division 1 locations are permitted to be used. 506.25 Grounding and Bonding. Exception: Type MC-HL cable and fittings listed for Class II, Division 1 locations are permitted to be used. 506.25 Grounding and Bonding. (B) Types of Equipment Grounding Conductors. Where flexible conduit is used as permitted in 506.15, it shall be (B) Types of Equipment Grounding Conductors. Liquidtight flexible metal conduit shall not be used as the sole Change Description and Impact to Worker Safety Clarified that listed MC cable must be marked MC-HL. As Safe or Safer. Page 259 of 361 Clarified that flexible metal conduit and liquidtight flexible metal conduit cannot be used as the sole ground-fault current path and that an internal or external bonding jumper is required. 70 2008 851 Evaluation 2005 NEC installed with internal or external bonding jumpers in parallel with each conduit and complying with 250.102. 2008 NEC ground-fault current path. Where equipment bonding jumpers are installed, they shall comply with 250.102. Article 511 Commercial Garages, Repair and Storage 511.2 Definitions. Major Repair Garage. A building or portions of a building where major repairs, such as engine overhauls, painting, body and fender work, and repairs that require draining of the motor vehicle fuel tank are performed on motor vehicles, including associated floor space used for offices, parking, or showrooms. [30A:3.3.12.1] Minor Repair Garage. A building or portions of a building used for lubrication, inspection, and minor automotive maintenance work, such as engine tune-ups, replacement of parts, fluid changes (e.g., oil, antifreeze, transmission fluid, brake fluid, airconditioning refrigerants), brake system repairs, tire rotation, and similar routine maintenance work, including associated floor space used for offices, parking, or showrooms. Page 260 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Added definitions for major and minor repair garages. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 511.3 Classifications of Locations. (A) Unclassified Locations. (1) Parking and Repair Garages. Parking garages used for parking or storage shall be permitted to be unclassified. Repair garages shall be permitted to be unclassified when designed in accordance with 511.3(A)(2) through 511.3(A)(7). (2) Alcohol-Based Windshield Washer Fluid. The storage, handling, or dispensing into motor vehicles of alcohol based windshield washer fluid in areas used for the service and repair operations of the vehicles shall not cause such areas to be classified as hazardous (classified) locations. 2008 NEC [30A:3.3.12.2] 511.3 Area Classification, General. Where Class I liquids or gaseous fuels are stored, handled, or transferred, electrical wiring and electrical utilization equipment shall be designed in accordance with the requirements for Class I, Division 1 or 2 hazardous (classified) locations as classified in accordance with 500.5 and 500.6, and this article. A Class I location shall not extend beyond an unpierced wall, roof, or other solid partition that has no openings. [30A:8.3.5, 8.3.2] (A) Parking Garages. Parking garages used for parking or storage shall be permitted to be unclassified. (B) Repair Garages, With Dispensing. Major and minor repair garages that (3) Specific Areas Adjacent to dispense motor fuels into the fuel tanks Classified Locations. Areas adjacent to of vehicles, including flammable liquids classified locations in which flammable having a flash point below 38°C vapors are not likely to be released, (100°F) such as gasoline, or gaseous such as stock rooms, switchboard fuels such as natural gas, hydrogen, or rooms, and other similar locations, LPG, shall have the dispensing shall not be classified where functions and components classified in mechanically ventilated at a rate of four accordance with Table 514.3(B)(1) in or more air changes per hour, or addition to any classification required designed with positive air pressure, or by this section. Where Class I liquids, Page 261 of 361 Change Description and Impact to Worker Safety Clarified area classification requirements based on categories of commercial repair and storage garages. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC where effectively cut off by walls or partitions. (4) Pits in Lubrication or Service Room Where Class I Liquids Are Not Transferred. Any pit, belowgrade work area, or subfloor work area that is provided with exhaust ventilation at a rate of not less than 0.3 m3/min/m2 (1 cfm/ft2) of floor area at all times that the building is occupied or when vehicles are parked in or over this area and where exhaust air is taken from a point within 300 mm (12 in.) of the floor of the pit, belowgrade work area, or subfloor work area is unclassified. [NFPA 30A:7.4.5.4 and Table 8.3.1] (5) Up to a Level of 450 mm (18 in.) Above the Floor in Lubrication or Service Rooms Where Class I Liquids Are Transferred. For each floor, the entire area up to a level of 450 mm (18 in.) above the floor shall be considered unclassified where there is mechanical ventilation providing a minimum of four air changes per hour or one cubic foot per minute of exchanged air for each square foot of floor area. Ventilation shall provide for air exchange across the entire floor area, and exhaust air 2008 NEC other than fuels, are dispensed, the area within 900 mm (3 ft) of any fill or dispensing point, extending in all directions, shall be a Class I, Division 2 location. (C) Major Repair Garages. Where flammable liquids having a flash point below 38°C (100°F) such as gasoline, or gaseous fuels such as natural gas, hydrogen, or LPG, will not be dispensed, but repair activities that involve the transfer of such fluids or gases are performed, the classification rules in (1), (2), and (3) shall apply. (1) Floor Areas. (a) Ventilation Provided. The floor area shall be unclassified where there is mechanical ventilation providing a minimum of four air changes per hour or one cubic foot per minute of exchanged air for each square foot of floor area. Ventilation shall provide for air exchange across the entire floor area, and exhaust air shall be taken at a point within 0.3 m (12 in.) of the floor. (b) Ventilation Not Provided. The entire floor area up to a level of 450 mm (18 in.) above the floor shall be Page 262 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC shall be taken at a point within 0.3 m (12 in.) of the floor. (6) Flammable Liquids Having Flash Points Below 38°C (100°F). Where flammable liquids having a flash point below 38°C (100°F) (such as gasoline) or gaseous fuels (such as natural gas, hydrogen, or LPG) will not be transferred, such location shall be considered to be unclassified. Unless the location is required to be classified in accordance with 511.3(B)(2) or (B)(4). (7) Within 450 mm (18 in.) of the Ceiling. In major repair garages, where lighter-than-air gaseous fuels (such as natural gas or hydrogen) vehicles are repaired or stored, the area within 450 mm (18 in.) of the ceiling shall be considered unclassified where ventilation of at least 1 cfm/sq ft of ceiling area taken from a point within 450 mm (18 in.) of the highest point in the ceiling is provided. (B) Classified Locations. (1) Flammable Fuel Dispensing Areas. Areas in which flammable fuel is dispensed into vehicle fuel tanks shall 2008 NEC classified as Class I, Division 2 if the ventilation does not comply with 511.3(C)(1)(a). (2) Ceiling Areas. Where lighterthan-air gaseous fueled vehicles, such as vehicles fueled by natural gas or hydrogen, are repaired or stored, the area within 450 mm (18 in.) of the ceiling shall be considered for classification in accordance with (a) and (b). (a) Ventilation Provided. The ceiling area shall be unclassified where ventilation is provided, from a point not less than 450 mm (18 in.) from the highest point in the ceiling, to exhaust the ceiling area at a rate of not less than 0.3 m3/min/m2 (1 cfm/ft2) of ceiling area at all times that the building is occupied or when vehicles using lighter-than-air gaseous fuels are parked below this area. (b) Ventilation Not Provided. Ceiling areas that are not ventilated in accordance with 511.3(C)(2)(a) shall be classified as Class I, Division 2. (3) Pit Areas in Lubrication or Service Room. Any pit, belowgrade work area, or subfloor work area shall be classified as provided in (a) Page 263 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC conform to Article 514. (2) Lubrication or Service Room Where Class I Liquids or Gaseous Fuels (Such as Natural Gas, Hydrogen, or LPG) Are Not Transferred. The following spaces that are not designed in accordance with 511.3(A)(4) shall be classified as Class I, Division 2: (1) Entire area within any unventilated pit, belowgrade work area, or subfloor area. (2) Area up to 450 mm (18 in.) above any such unventilated pit, belowgrade work area, or subfloor work area and extending a distance of 900 mm (3 ft) horizontally from the edge of any such pit belowgrade work area, or subfloor work area. (3) Lubrication or Service Room Where Class I Liquids or Gaseous Fuels (Such as Natural Gas, Hydrogen, or LPG) Are Transferred. The following spaces that are not designed in accordance with 511.3(A)(5) shall be classified as follows: (1) Up to a Level of 450 mm (18 in.) Above the Floor. For each floor, the entire area up to a level of 450 mm (18 in.) above the floor shall be a Class I, Division 2 location. or (b). (a) Ventilation Provided. The pit area shall be a Class I, Division 2 location where there is mechanical ventilation providing a minimum of six air changes per hour. (b) Ventilation Not Provided. Where ventilation is not provided in accordance with 511.3(C)(3)(a), any pit or depression below floor level shall be a Class I, Division 1 location that extends up to the floor level. (D) Minor Repair Garages. Where flammable liquids having a flash point below 38°C (100°F) such as gasoline, or gaseous fuels such as natural gas or hydrogen, will not be dispensed or transferred, the classification rules in (D)(1), (D)(2), and (D)(3) shall apply to the lubrication and service rooms. (1) Floor Areas. Floor areas in minor repair garages without pits, belowgrade work areas, or subfloor work areas shall be unclassified. Where floor areas include pits, belowgrade work areas, or subfloor work areas in lubrication or service rooms, the classification rules in (a) or (b) shall apply. (a) Ventilation Provided. The entire Page 264 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC (2) Any Unventilated Pit or Depression Below Floor Level. Any unventilated pit or depression below floor level shall be a Class I, Division 1 location and shall extend up to said floor level. (3) Any Ventilated Pit or Depression Below Floor Level. Any ventilated pit or depression in which six air changes per hour are exhausted from a point within 300 mm (12 in.) of the floor level of the pit shall be a Class I, Division 2 location. (4) Space Above an Unventilated Pit or Depression Below Floor Level. Above a pit, or depression below floor level, the space up to 450 mm (18 in.) above the floor or grade level and 900 mm (3 ft) horizontally from a lubrication pit shall be a Class I, Division location. (5) Dispenser for Class I Liquids, Other Than Fuels. Within 900 mm (3 ft) of any fill or dispensing point, extending in all directions shall be a Class I, Division 2 location. See also 511.3(B)(1). (4) Within 450 mm (18 in.) of the Ceiling. In major repair garages where lighter-than-air gaseous fuel (such as natural gas or hydrogen) vehicles are 2008 NEC floor area shall be unclassified where there is mechanical ventilation providing a minimum of four air changes per hour or one cubic foot per minute of exchanged air for each square foot of floor area. Ventilation shall provide for air exchange across the entire floor area, and exhaust air shall be taken at a point within 0.3 m (12 in.) of the floor. (b) Ventilation Not Provided. The floor area up to a level of 450 mm (18 in.) above any unventilated pit, belowgrade work area, or subfloor work area and extending a distance of 900 mm (3 ft) horizontally from the edge of any such pit, belowgrade work area, or subfloor work area, shall be classified as Class I, Division 2. (2) Ceiling Areas. Where lighterthan-air gaseous fuels (such as natural gas or hydrogen) will not be transferred, such locations shall be unclassified. (3) Pit Areas in Lubrication or Service Room. Any pit, belowgrade work area, or subfloor work area shall be classified as provided in (a) or (b). Page 265 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC repaired or stored, ceiling spaces that are not designed in accordance with 511.3(A)(7) shall be classified as Class I, Division 2. (a) Ventilation Provided. Where ventilation is provided to exhaust the pit area at a rate of not less than 0.3 m3/min/m2 (1 cfm/ft2) of floor area at all times that the building is occupied, or when vehicles are parked in or over this area and where exhaust air is taken from a point within 300 mm (12 in.) of the floor of the pit, belowgrade work area, or subfloor work area, the pit shall be unclassified. [30A:7.4.5.4. Table 8.3.1] (b) Ventilation Not Provided. Where ventilation is not provided in accordance with 511.3(D)(3)(a), any pit or depression below floor level shall be a Class I, Division 2 location that extends up to the floor level. (E) Modifications to Classification. (1) Specific Areas Adjacent to Classified Locations. Areas adjacent to classified locations in which flammable vapors are not likely to be released, such as stock rooms, switchboard rooms, and other similar locations, shall be unclassified where mechanically ventilated at a rate of four or more air changes per hour, or designed Page 266 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety with positive air pressure, or where effectively cut off by walls or partitions. (2) Alcohol-Based Windshield Washer Fluid. The area used for storage, handling, or dispensing into motor vehicles of alcohol-based windshield washer fluid in repair garages shall be unclassified unless otherwise classified by a provision of 511.3. [30A:8.3.5, Exception] Article 513 Aircraft Hangars 513.2 Definitions. For the purpose of this article, the following definitions shall apply. Aircraft Painting Hangar. An aircraft hangar constructed for the express purpose of spray/coating/dipping applications and provided with dedicated ventilation supply and exhaust. (C) Vicinity of Aircraft. (1) Aircraft Maintenance and Storage Hangars. The area within 1.5 m (5 ft) horizontally from aircraft power plants or aircraft fuel tanks shall be classified Page 267 of 361 Added definition for an aircraft painting hangar. As Safe or Safer. Added requirements on area classification for aircraft painting hangars. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety as a Class I, Division 2 or Zone 2 location that shall extend upward from the floor to a level 1.5 m (5 ft) above the upper surface of wings and of engine enclosures. (2) Aircraft Painting Hangars. The area within 3 m (10 ft) horizontally from aircraft surfaces from the floor to 3 m (10 ft) above the aircraft shall be classified as Class I, Division 1 or Class I, Zone 1. The area horizontally from aircraft surfaces between 3.0 m (10 ft) and 9.0 m (30 ft) from the floor to 9.0 m (30 ft) above the aircraft surface shall be classified as Class I, Division 2 or Class I, Zone 2. Bulk Storage Plants Article 515 Bulk Storage Plants 515.7 Wiring and Equipment Above Class I Locations. 515.7 Wiring and Equipment Above Class I Locations. Revised to permit Schedule 80 PVC and RTRC types of nonmetallic conduit. As Safe or Safer. (A) Fixed Wiring. All fixed wiring above Class I locations shall be in metal raceways or PVC Schedule 80 rigid nonmetallic conduit, or equivalent, or be Type MI, TC, or MC cable. (A) Fixed Wiring. All fixed wiring above Class I locations shall be in metal raceways, Schedule 80 PVC conduit, Type RTRC marked with the suffix XW, or Type MI, TC, or MC cable. Article 516 Page 268 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Spray Application, Dipping, and Coating Processes Spray Application, Dipping, and Coating Processes 516.10 Special Equipment. 516.10 Special Equipment. Change Description and Impact to Worker Safety Emphasis on connected to an equipment grounding conductor versus grounded. As Safe or Safer. (C) Powder Coating. (C) Powder Coating. (1) Electric Equipment and Sources of Ignition. Electric equipment and other sources of ignition shall comply with the requirements of Article 502. Portable electric lamps and other utilization equipment shall not be used within a Class II location during operation of the finishing processes. Where such lamps or utilization equipment are used during cleaning or repairing operations, they shall be of a type identified for Class II, Division 1 locations, and all exposed metal parts shall be effectively grounded. (1) Electrical Equipment and Sources of Ignition. Electrical equipment and other sources of ignition shall comply with the requirements of Article 502. Portable electric luminaires and other utilization equipment shall not be used within a Class II location during operation of the finishing processes. Where such luminaires or utilization equipment are used during cleaning or repairing operations, they shall be of a type identified for Class II, Division 1 locations, and all exposed metal parts shall be connected to an equipment grounding conductor. Article 517 Health Care Facilities Ambulatory Health Care Facility. A building or part thereof used to provide services or treatment to four or more Ambulatory Health Care Occupancy. A building or portion thereof used to provide services or treatment Page 269 of 361 Replaced the term patient vicinity with patient care vicinity and wet location with wet procedure location, for correlation with changes to definitions in 517.2. Revised definitions of ambulatory health care occupancy, limited care facility, nursing home, and patient care 70 2008 851 Evaluation 2005 NEC patients at the same time and meeting either (1) or (2). (1) Those facilities that provide, on an outpatient basis, treatment for patients that would render them incapable of taking action for self-preservation under emergency conditions without assistance from others, such as hemodialysis units or freestanding emergency medical units. (2) Those facilities that provide, on an outpatient basis, surgical treatment requiring general anesthesia. Limited Care Facility. A building or part thereof used on a 24-hour basis for the housing of four or more persons who are incapable of self-preservation because of age, physical limitation due to accident or illness, or mental limitations, such as mental retardation/developmental disability, mental illness, or chemical dependency. Nursing Home. A building or part thereof used for the lodging, boarding, and nursing care, on a 24-hour basis, of four or more persons who, because of mental or physical incapacity, may be unable to provide for their own 2008 NEC Change Description and Impact to Worker Safety vicinity for correlation with source document, NFPA 99. simultaneously to four or more patients that provides, on an outpatient basis, one or more of the following: (1) Treatment for patients that renders As Safe or Safer. the patients incapable of taking action for self-preservation under emergency conditions without assistance of others. (2) Anesthesia that renders the patients incapable of taking action for self-preservation under emergency conditions without the assistance of others. (3) Emergency or urgent care for patients who, due to the nature of their injury or illness, are incapable of taking action for self-preservation under emergency conditions without the assistance of others. [101:3.3.168.1] Limited Care Facility. A building or portion thereof used on a 24-hour basis for the housing of four or more persons who are incapable of selfpreservation because of age; physical limitation due to accident or illness; or limitations such as mental retardation/developmental disability, mental illness, or chemical dependency. [99:3.3.97] Nursing Home. A building or portion of Page 270 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC needs and safety without the assistance of another person. Nursing home, wherever used in this Code, shall include nursing and convalescent homes, skilled nursing facilities, intermediate care facilities, and infirmaries of homes for the aged. a building used on a 24-hour basis for the housing and nursing care of four or more persons who, because of mental or physical incapacity, might be unable to provide for their own needs and safety without the assistance of another person. [99:3.3.129] Patient Vicinity. In an area in which patients are normally cared for, the patient vicinity is the space with surfaces likely to be contacted by the patient or an attendant who can touch the patient. Typically in a patient room, this encloses a space within the room not less than 1.8 m (6 ft) beyond the perimeter of the bed in its nominal location, and extending vertically not less than 2.3 m (71⁄2 ft) above the floor. 517.13 Grounding of Receptacles and Fixed Electric Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Patient Care Vicinity. In an area in which patients are normally cared for, the patient care vicinity is the space with surfaces likely to be contacted by the patient or an attendant who can touch the patient. Typically in a patient room, this encloses a space within the room not less than 1.8 m (6 ft) beyond the perimeter of the bed in its nominal location, and extending vertically not less than 2.3 m (71⁄2 ft) above the floor. [99:3.3.140] 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring Methods. All branch circuits serving patient care areas shall be provided with a ground path for fault current by installation in a metal raceway system, or a cable having a (A) Wiring Methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a Page 271 of 361 Change Description and Impact to Worker Safety Continued emphasis on connected to the equipment grounding conductor. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding return path in accordance with 250.118. metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. The grounding terminals of all receptacles and all non currentcarrying conductive surfaces of fixed electric equipment likely to become energized that are subject to personal contact, operating at over 100 volts, shall be grounded by an insulated copper conductor. The equipment grounding conductor shall be sized in accordance with Table 250.122 and installed in metal raceways or as a part of listed cables having a metallic armor or sheath assembly with the branchcircuit conductors supplying these receptacles or fixed equipment. (B) Insulated Equipment Grounding Conductor. The grounding terminals of all receptacles and all non currentcarrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts, shall be connected to an insulated copper equipment grounding conductor. The equipment grounding conductor shall be sized in accordance with Table 250.122 and installed in metal raceways or as a part of listed cables having a metallic armor or sheath assembly with the branchcircuit conductors supplying these receptacles or fixed equipment. Exception No. 1: Metal faceplates shall be permitted to be grounded by means of a metal mounting screw(s) securing the faceplate to a grounded outlet box or grounded wiring device. Exception No. 2: Luminaires (light Exception No. 1: Metal faceplates shall be permitted to be connected to the equipment grounding conductor by means of a metal mounting screw(s) securing the faceplate to a grounded outlet box or grounded wiring device. Page 272 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC fixtures) more than 2.3 m (71⁄2 ft) above the floor and switches located outside of the patient vicinity shall not be required to be grounded by an insulated equipment grounding conductor. 2008 NEC 517.20 Wet Locations. Exception No. 2: Luminaires more than 2.3 m (71⁄2 ft) above the floor and switches located outside of the patient care vicinity shall be permitted to be connected to an equipment grounding return path complying with 517.13(A). 517.20 Wet Procedure Locations. (A) Receptacles and Fixed Equipment. All receptacles and fixed equipment within the area of the wet location shall have ground-fault circuitinterrupter protection for personnel if interruption of power under fault conditions can be tolerated, or be served by an isolated power system if such interruption cannot be tolerated. (A) Receptacles and Fixed Equipment. All receptacles and fixed equipment within the area of the wet procedure location shall have ground-fault circuitinterrupter protection for personnel if interruption of power under fault conditions can be tolerated, or be served by an isolated power system if such interruption cannot be tolerated. Exception: Branch circuits supplying only listed, fixed, therapeutic and diagnostic equipment shall be permitted to be supplied from a normal grounded service, single- or 3-phase system, provided that (a) Wiring for grounded and isolated circuits does not occupy the same raceway, and (b) All conductive surfaces of the equipment are grounded. Exception: Branch circuits supplying only listed, fixed, therapeutic and diagnostic equipment shall be permitted to be supplied from a grounded service, single- or 3-phase system, provided that (a) Wiring for grounded and isolated circuits does not occupy the same raceway, and (b) All conductive surfaces of the equipment are connected to an equipment grounding conductor. Page 273 of 361 Change Description and Impact to Worker Safety Deleted the word ‘‘normal’’ in the exception to clarify that the exception applies to branch-circuit supplies from any grounded supply system and continued the emphasis on connected to an equipment grounding conductor. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 517.32 Life Safety Branch. 517.32 Life Safety Branch. (C) Alarm and Alerting Systems. Alarm and alerting systems including the following: (C) Alarm and Alerting Systems. Alarm and alerting systems including the following: (1) Fire alarms (1) Fire alarms (2) Alarms required for systems used for the piping of nonflammable medical gases (2) Alarms required for systems used for the piping of nonflammable medical gases 517.32 Life Safety Branch. (3) Mechanical, control, and other accessories required for effective life safety systems operation shall be permitted to be connected to the life safety branch. 517.32 Life Safety Branch. Change Description and Impact to Worker Safety Revised to permit equipment and circuits required for life safety system operation to be supplied by life safety branch. As Safe or Safer. (E) Generator Set Location. Task illumination battery charger for emergency battery-powered lighting unit(s) and selected receptacles at the generator set location. 517.34 Equipment System Connection to Alternate Power Source. (E) Generator Set and Transfer Switch Locations. Task illumination battery charger for battery-powered lighting unit(s) and selected receptacles at the generator set and essential transfer switch locations. [99:4.4.2.2.2.2(5)] (F) Generator Set Accessories. Generator set accessories as required for generator performance. 517.34 Equipment System Connection to Alternate Power Source. Page 274 of 361 Added section to permit generator set accessories to be connected to the life safety branch. As Safe or Safer. • 517.34(A)(7): Added section to permit supply, return, and exhaust ventilating 70 2008 851 Evaluation 2005 NEC 2008 NEC (A) Equipment for Delayed Automatic Connection. (A) Equipment for Delayed Automatic Connection. 517.40 Essential Electrical Systems for Nursing Homes and Limited Care Facilities. (7) Supply, return, and exhaust ventilating systems for operating and delivery rooms. 517.40 Essential Electrical Systems for Nursing Homes and Limited Care Facilities. (B) Inpatient Hospital Care Facilities. Nursing homes and limited care facilities that provide inpatient hospital care shall comply with the requirements of Part III, 517.30 through 517.35. 517.44 Sources of Power. (B) Alternate Source of Power. Exception No. 2: Nursing homes or limited care facilities meeting the requirements of 517.40(A), Exception, shall be permitted to use a battery system or self-contained battery integral with the equipment. [NFPA Change Description and Impact to Worker Safety systems in operating and delivery rooms to be arranged for delayed automatic connection to the alternate power source. As Safe or Safer. Revised description of ‘‘inpatient hospital care facilities’’ for correlation with NFPA 99. (B) Inpatient Hospital Care Facilities. As Safe or Safer. For those nursing homes and limited care facilities that admit patients who need to be sustained by electrical life support equipment, the essential electrical system from the source to the portion of the facility where such patients are treated shall comply with the requirements of Part III, 517.30 through 517.35. 517.44 Sources of Power. Revised to permit health care facilities other than nursing homes and limited (B) Alternate Source of Power. care facilities to use battery power for the essential electrical system. Exception No. 2: Nursing homes or As Safe or Safer. limited care facilities meeting the requirement of 517.40(A) and other health care facilities meeting the requirement of 517.45 shall be permitted to use a battery system or Page 275 of 361 70 2008 851 Evaluation 2005 NEC 99:17.3.4.1.3, 18.3.4.1.1] 2008 NEC Change Description and Impact to Worker Safety 517.61 Wiring and Equipment. self-contained battery integral with the equipment. 517.61 Wiring and Equipment. (C) Other-Than-Hazardous (Classified) Anesthetizing Locations. (C) Other-Than-Hazardous (Classified) Anesthetizing Locations. (2) Receptacles and Attachment Plugs. Receptacles and attachment plugs installed and used in other-thanhazardous (classified) locations shall be listed for hospital use for services of prescribed voltage, frequency, rating, and number of conductors with provision for connection of the grounding conductor. This requirement shall apply to 2-pole, 3-wire grounding type for single phase, 120-, 208-, or 240-volt, nominal, ac service. 517.71 Connection to Supply Circuit. (2) Receptacles and Attachment Plugs. Receptacles and attachment plugs installed and used in other-thanhazardous (classified) locations shall be listed “hospital grade” for services of prescribed voltage, frequency, rating, and number of conductors with provision for connection of the grounding conductor. This requirement shall apply to 2-pole, 3-wire grounding type for single-phase, 120-, 208-, or 240-volt, nominal, ac service. 517.71 Connection to Supply Circuit. Revised to specifically reference Chapters 1 through 4 of the Code. (A) Fixed and Stationary Equipment. Fixed and stationary X-ray equipment As Safe or Safer. shall be connected to the power supply by means of a wiring method complying with applicable requirements of Chapters 1 through 4 of this Code, as modified by this article. VI. Communications, Signaling Added provision that secondary Systems, Data Systems, Fire Alarm circuits of transformer-powered limited Systems, and Systems Less Than 120 energy communications and signaling (A) Fixed and Stationary Equipment. Fixed and stationary X-ray equipment shall be connected to the power supply by means of a wiring method that meets the general requirements of this Code. VI. Communications, Signaling Systems, Data Systems, Fire Alarm Systems, and Systems Less Than 120 Page 276 of 361 Clarified that the receptacles are required to be listed as hospital grade. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Volts, Nominal Volts, Nominal 517.80 Patient Care Areas. Equivalent insulation and isolation to that required for the electrical distribution systems in patient care areas shall be provided for communications, signaling systems, data system circuits, fire alarm systems, and systems less than 120 volts, nominal. VII. Isolated Power Systems 517.80 Patient Care Areas. Equivalent insulation and isolation to that required for the electrical distribution systems in patient care areas shall be provided for communications, signaling systems, data system circuits, fire alarm systems, and systems less than 120 volts, nominal. Secondary circuits of transformerpowered communications or signaling systems shall not be required to be enclosed in raceways unless otherwise specified by Chapter 7 or 8. [99:4.4.2.2.4.6] VII. Isolated Power Systems 517.160 Isolated Power Systems. (A) Installations. 517.160 Isolated Power Systems. (A) Installations. (1) Isolated Power Circuits. Each isolated power circuit shall be controlled by a switch that has a disconnecting pole in each isolated circuit conductor to simultaneously disconnect all power. Such isolation shall be accomplished by means of one or more transformers having no electrical connection between primary and secondary windings, by means of (1) Isolated Power Circuits. Each isolated power circuit shall be controlled by a switch that has a disconnecting pole in each isolated circuit conductor to simultaneously disconnect all power. Such isolation shall be accomplished by means of one or more isolation transformers, by means of generator sets, or by means of electrically isolated batteries. Page 277 of 361 Change Description and Impact to Worker Safety systems need not be installed in a raceway unless otherwise required by the Code. As Safe or Safer. Clarified that the transformers are required to be the isolation type and batteries are required to be electrically isolated. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC motor generator sets, or by means of suitably isolated batteries. 517.160 Isolated Power Systems. 517.160 Isolated Power Systems. (A) Installations. (A) Installations. (5) Conductor Identification. The isolated circuit conductors shall be identified as follows: (5) Conductor Identification. The isolated circuit conductors shall be identified as follows: (1) Isolated Conductor No. 1 — Orange (2) Isolated Conductor No. 2 — Brown For 3-phase systems, the third conductor shall be identified as yellow. Where isolated circuit conductors supply 125-volt, single-phase, 15- and 20-ampere receptacles, the orange conductor(s) shall be connected to the terminal(s) on the receptacles that are identified in accordance with 200.10(B) for connection to the grounded circuit conductor. (1) Isolated Conductor No. 1 — Orange with a distinctive colored stripe other than white, green, or gray (2) Isolated Conductor No. 2 — Brown with a distinctive colored stripe other than white, green, or gray For 3-phase systems, the third conductor shall be identified as yellow with a distinctive colored stripe other than white, green, or gray. Where isolated circuit conductors supply 125volt, single-phase, 15- and 20-ampere receptacles, the striped orange conductor(s) shall be connected to the terminal(s) on the receptacles that are identified in accordance with 200.10(B) for connection to the grounded circuit conductor. Page 278 of 361 Change Description and Impact to Worker Safety Added requirement that conductors have a distinctive colored stripe to distinguish them from other systems using similar colored conductors. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Assembly Occupancies Article 518 Assembly Occupancies 518.4 Wiring Methods. 518.4 Wiring Methods. (A) General. The fixed wiring methods shall be metal raceways, flexible metal raceways, nonmetallic raceways encased in not less than 50 mm (2 in.) of concrete, Type MI, MC, or AC cable containing an insulated equipment grounding conductor sized in accordance with Table 250.122. (A) General. The fixed wiring methods shall be metal raceways, flexible metal raceways, nonmetallic raceways encased in not less than 50 mm (2 in.) of concrete, Type MI, MC, or AC cable. The wiring method shall itself qualify as an equipment grounding conductor according to 250.118 or shall contain an insulated equipment grounding conductor sized in accordance with Table 250.122. 518.5 Supply. Portable switchboards 518.5 Supply. Portable switchboards and portable power distribution and portable power distribution equipment shall be supplied only from equipment shall be supplied only from listed power outlets of sufficient voltage listed power outlets of sufficient voltage and ampere rating. Such power outlets and ampere rating. Such power outlets shall be protected by overcurrent shall be protected by overcurrent devices. Such overcurrent devices and devices. Such overcurrent devices and power outlets shall not be accessible to power outlets shall not be accessible to the general public. Provisions for the general public. Provisions for connection of an equipment grounding connection of an equipment grounding conductor shall be provided. The conductor shall be provided. The neutral of feeders supplying solid-state, neutral conductor of feeders supplying 3-phase, 4-wire dimmer systems shall solid-state phase control, 3-phase, 4be considered a current-carrying wire dimmer systems shall be conductor. considered a current-carrying Page 279 of 361 Change Description and Impact to Worker Safety Revised to specify that the wiring method must be an equipment grounding conductor per 250.118. As Safe or Safer. Revised to specify that neutral conductors of solid-state sine-wave, 3phase 4-wire, dimming systems are not considered to be current-carrying conductors for the purpose of ampacity adjustment. Added exception to specify that neutral conductors of feeders supplying both phase-control and sine-wave dimmers are current-carrying for ampacity adjustment purposes. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety conductor for purposes of derating. The neutral conductor of feeders supplying solid-state sine wave, 3phase, 4-wire dimming systems shall not be considered a current-carrying conductor for purposes of derating. Exception: The neutral conductor of feeders supplying systems that use or may use both phase-control and sinewave dimmers shall be considered as current-carrying for purposes of derating. NOTE: Articles 520 through 555 are determined to have minimal application at the Idaho site and will not be addressed. Article 590 Temporary Installations Temporary Installations Revised to reference applicable parts of Article 230 that apply to temporary 590.4 General. 590.4 General. installations. (A) Services. Services shall be (A) Services. Services shall be installed in conformance with Article installed in conformance with Parts I As Safe or Safer. 230. through VIII of Article 230, as applicable. 590.4 General. 590.4 General. Clarified that a metal raceway or cable (D) Receptacles. All receptacles shall (D) Receptacles. All receptacles shall that is not continuous or does not be of the grounding type. Unless be of the grounding type. Unless qualify as an equipment grounding installed in a continuous grounded installed in a continuous metal raceway conductor in accordance with 250.118 metal raceway or metal-covered cable, that qualifies as an equipment must contain a separate wire-type all branch circuits shall contain a grounding conductor in accordance equipment grounding conductor. separate equipment grounding with 250.118 or a continuous metalconductor, and all receptacles shall be covered cable that qualifies as an Actually may improve electrical safety Page 280 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC electrically connected to the equipment grounding conductors. Receptacles on construction sites shall not be installed on branch circuits that supply temporary lighting. Receptacles shall not be connected to the same ungrounded conductor of multiwire circuits that supply temporary lighting. equipment grounding conductor in accordance with 250.118, all branch circuits shall include a separate equipment grounding conductor, and all receptacles shall be electrically connected to the equipment grounding conductor(s). Receptacles on construction sites shall not be installed on branch circuits that supply temporary lighting. Receptacles shall not be connected to the same ungrounded conductor of multiwire circuits that supply temporary lighting. 590.4 General. (E) Disconnecting Means. Suitable disconnecting switches or plug connectors shall be installed to permit the disconnection of all ungrounded conductors of each temporary circuit. Multiwire branch circuits shall be provided with a means to disconnect simultaneously all ungrounded conductors at the power outlet or panelboard where the branch circuit originated. Identified handle ties shall be permitted. 590.6 Ground-Fault Protection for Personnel. Ground-fault protection for personnel for all temporary wiring installations shall be provided to comply with 590.6(A) and (B). This 590.4 General. (E) Disconnecting Means. Suitable disconnecting switches or plug connectors shall be installed to permit the disconnection of all ungrounded conductors of each temporary circuit. Multiwire branch circuits shall be provided with a means to disconnect simultaneously all ungrounded conductors at the power outlet or panelboard where the branch circuit originated. Approved handle ties shall be permitted. 590.6 Ground-Fault Protection for Personnel. Ground-fault protection for personnel for all temporary wiring installations shall be provided to comply with 590.6(A) and 590.6(B). Page 281 of 361 Change Description and Impact to Worker Safety for the worker. Revised to specify that only identified handle ties are permitted. As Safe or Safer. Revised to specify that ground-fault protection for personnel (GFCI) requirements apply to temporary installations supplied by electric utility or on-site generated power. 70 2008 851 Evaluation 2005 NEC 2008 NEC This section shall apply only to temporary wiring installations used to supply temporary power to equipment used by personnel during construction, remodeling, maintenance, repair, or demolition of buildings, structures, equipment, or similar activities. Change Description and Impact to Worker Safety section shall apply only to temporary wiring installations used to supply temporary power to equipment used by personnel during construction, remodeling, maintenance, repair, or demolition of buildings, structures, equipment, or similar activities. This section shall apply to power derived from an electric utility company or from an on-site-generated power source. NOTE: Article 600 is determined to have minimal application at the Idaho site and will not be addressed. Article 604 Manufactured Wiring Systems Manufactured Wiring Systems Revised definition to describe types of equipment connected to manufactured 604.2 Definition. 604.2 Definition. wiring systems. Manufactured Wiring System. A Manufactured Wiring System. A system containing component parts system containing component parts As Safe or Safer. that are assembled in the process of that are assembled in the process of manufacture and cannot be inspected manufacture and cannot be inspected at the building site without damage or at the building site without damage or destruction to the assembly. destruction to the assembly and used for the connection of luminaires, utilization equipment, continuous plugin type busways, and other devices. 604.6 Construction. 604.6 Construction. Added Type MC cable with a combined bore grounding conductor (A) Cable or Conduit Types. (A) Cable or Conduit Types. and metal armor as the equipment grounding conductor to the list of (1) Cables. Cable shall be listed Type (1) Cables. Cable shall be one of the acceptable cable wiring methods. AC cable or listed Type MC cable following: containing nominal 600-volt, 8 to 12 (1) Listed Type AC cable containing As Safe or Safer. Page 282 of 361 70 2008 851 Evaluation 2005 NEC AWG insulated copper conductors with a bare or insulated copper equipment grounding conductor equivalent in size to the ungrounded conductor. 2008 NEC Change Description and Impact to Worker Safety nominal 600-volt, 8 to 12 AWG insulated copper conductors with a bare or insulated copper equipment grounding conductor equivalent in size to the ungrounded conductor. (2) Listed Type MC cable containing nominal 600-volt, 8 to 12 AWG insulated copper conductors with a bare or insulated copper equipment grounding conductor equivalent in size to the ungrounded conductor. 604.6 Construction. (3) Listed Type MC cable containing nominal 600-volt, 8 to 12 AWG insulated copper conductors with a grounding conductor and armor assembly listed and identified for grounding in accordance with 250.118(10). The combined metallic sheath and grounding conductor shall have a current-carrying capacity equivalent to that of the ungrounded copper conductor. 604.6 Construction. (A) Cable or Conduit Types. (A) Cable or Conduit Types. (3) Flexible Cord. (3) Flexible Cord. Added exception permitting listed electric discharge luminaires with conductors smaller than 12 AWG for use in accordance with 410.62(C) As Safe or Safer. Exception: Listed electric-discharge Page 283 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC 604.6 Construction. luminaires that comply with 410.62(C) shall be permitted with conductors smaller than 12 AWG. 604.6 Construction. (A) Cable or Conduit Types. (A) Cable or Conduit Types. Change Description and Impact to Worker Safety Added new section to address busways. As Safe or Safer. 604.6 Construction. (C) Receptacles and Connectors. Receptacles and connectors shall be of the locking type, uniquely polarized and identified for the purpose, and shall be part of a listed assembly for the appropriate system. (4) Busways. Busways shall be listed continuous plug-in type containing factory mounted, bare or insulated conductors, which shall be copper or aluminum bars, rods, or tubes. The busway shall be grounded and provided with an equipment ground busbar equivalent in size to the ungrounded busbar. The busway shall be rated nominal 600 volts, 20, 30, or 40 amperes. Busways shall be installed in accordance with 368.12, 368.17(D) and 368.30. 604.6 Construction. (C) Receptacles and Connectors. Receptacles and connectors shall be of the locking type, uniquely polarized and identified for the purpose, and shall be part of a listed assembly for the appropriate system. All connector openings shall be designed to prevent inadvertent contact with live parts or capped to effectively close the Page 284 of 361 Revised to require all connector openings to be designed to prevent inadvertent contact with live parts or to be capped so as to effectively close the connector opening. 70 2008 851 Evaluation 2005 NEC 604.6 Construction. (E) Securing and Supporting. Manufactured wiring systems shall be secured and supported in accordance with the applicable cable or conduit article for the cable or conduit type employed. 2008 NEC connector openings. 604.7 Installation. Manufactured wiring systems shall be secured and supported in accordance with the applicable cable or conduit article for the cable or conduit type employed. Change Description and Impact to Worker Safety Renumbered and renamed 604.6(E) and deleted 604.6(F) and original 604.7. As Safe or Safer. (F) Luminaires (Fixtures). Installation of listed electric discharge luminaires (fixtures) complying with 410.30(C) shall be permitted. 604.7 Unused Outlets. All unused outlets shall be capped to effectively close the connector openings. Cranes and Hoists III. Contact Conductors Article 605 had no substantial changes. Article 610 Cranes and Hoists Continued emphasis on connection to an equipment grounding conductor III. Contact Conductors versus just grounding. 610.21 Installation of Contact Conductors. 610.21 Installation of Contact Conductors. (F) Track as Circuit Conductor. (F) Track as Circuit Conductor. (4) The rail serving as a conductor is (4) The rail serving as a conductor Page 285 of 361 As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC effectively grounded at the transformer and also shall be permitted to be grounded by the fittings used for the suspension or attachment of the rail to a building or structure. IV. Disconnecting Means shall be bonded to the equipment grounding conductor at the transformer and also shall be permitted to be grounded by the fittings used for the suspension or attachment of the rail to a building or structure. IV. Disconnecting Means 610.31 Runway Conductor Disconnecting Means. 610.31 Runway Conductor Disconnecting Means. Change Description and Impact to Worker Safety Added requirement on the type of locking provision to be provided as part of the installed equipment. As Safe or Safer. (2) Capable of being locked in the open position 610.32 Disconnecting Means for Cranes and Monorail Hoists. A motorcircuit switch, molded-case switch, or circuit breaker shall be provided in the leads from the runway contact conductors or other power supply on all cranes and monorail hoists. The disconnecting means shall be capable (2) Capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted as the means required to be installed at and remain with the equipment. 610.32 Disconnecting Means for Cranes and Monorail Hoists. A motorcircuit switch, molded-case switch, or circuit breaker shall be provided in the leads from the runway contact conductors or other power supply on all cranes and monorail hoists. The disconnecting means shall be capable Page 286 of 361 Added requirement on the type of locking provision to be provided as part of the installed equipment. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC of being locked in the open position. VII. Grounding 610.61 Grounding. All exposed non– current-carrying metal parts of cranes, monorail hoists, hoists, and accessories, including pendant controls, shall be metallically joined together into a continuous electrical conductor so that the entire crane or hoist will be grounded in accordance with Article 250. 620.2 Definitions. 2008 NEC of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. VII. Grounding 610.61 Grounding. All exposed non– current-carrying metal parts of cranes, monorail hoists, hoists, and accessories, including pendant controls, shall be bonded either by mechanical connections or bonding jumpers, where applicable, so that the entire crane or hoist is a ground-fault current path as required or permitted by Article 250, Parts V and VII. Article 620 Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts 620.2 Definitions. Page 287 of 361 Change Description and Impact to Worker Safety Modified to provide specific grounding and bonding requirements. As Safe or Safer. Replaced wheel chair lift with platform lift throughout the article for correlation with ASME A18.1, Safety Standard on Platform Lifts and Wheelchair Lifts. As Safe or Safer. Added definitions for remote machine room and control room and remote 70 2008 851 Evaluation 2005 NEC 2008 NEC Remote Machine Room and Control Room (for Elevator, Dumbwaiter). A machine room or control room that is not attached to the outside perimeter or surface of the walls, ceiling, or floor of the hoistway. 620.3 Voltage Limitations. Remote Machinery Space and Control Space (for Elevator, Dumbwaiter). A machinery space or control space that is not within the hoistway, machine room, or control room and that is not attached to the outside perimeter or surface of the walls, ceiling, or floor of the hoistway. 620.3 Voltage Limitations. (A) Power Circuits. Branch circuits to door operator controllers and door motors and branch circuits and feeders to motor controllers, driving machine motors, machine brakes, and motorgenerator sets shall not have a circuit voltage in excess of 600 volts. Internal voltages of power conversion and functionally associated equipment, including the interconnecting wiring, shall be permitted to have higher voltages, provided that all such equipment and wiring shall be listed for the higher voltages. Where the voltage (A) Power Circuits. Branch circuits to door operator controllers and door motors and branch circuits and feeders to motor controllers, driving machine motors, machine brakes, and motorgenerator sets shall not have a circuit voltage in excess of 600 volts. Internal voltages of power conversion equipment and functionally associated equipment, and the operating voltages of wiring interconnecting the equipment, shall be permitted to be higher, provided that all such equipment and wiring shall be listed for Page 288 of 361 Change Description and Impact to Worker Safety machinery space and control space. As Safe or Safer. Clarified that both the internal voltages of power conversion equipment and the operating voltages of wiring interconnecting the equipment are permitted to exceed 600 volts. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC exceeds 600 volts, warning labels or signs that read “DANGER — HIGH VOLTAGE” shall be attached to the equipment and shall be plainly visible. 2008 NEC Change Description and Impact to Worker Safety III. Wiring the higher voltages. Where the voltage exceeds 600 volts, warning labels or signs that read “DANGER — HIGH VOLTAGE” shall be attached to the equipment and shall be plainly visible. III. Wiring 620.21 Wiring Methods. 620.21 Wiring Methods. Added section to permit cordconnected sump and oil recovery pumps in elevator pits. (A) Elevators. (A) Elevators. As Safe or Safer. (1) Hoistways. (1) Hoistways. (d) The following wiring methods shall be permitted in the hoistway in lengths not to exceed 1.8 m (6 ft): (1) Flexible metal conduit (2) Liquidtight flexible metal conduit (3) Liquidtight flexible nonmetallic conduit (4) Flexible cords and cables, or conductors grouped together and taped or corded, shall be permitted to be installed without a raceway. They shall be located to be protected from physical damage and shall be of a flame-retardant type and shall be part of the following: a. Listed equipment b. A driving machine, or c. A driving machine brake (d) Flexible metal conduit, liquidtight flexible metal conduit, liquidtight flexible nonmetallic conduit or flexible cords and cables, or conductors grouped together and taped or corded that are part of listed equipment, a driving machine, or a driving machine brake shall be permitted in the hoistway, in lengths not to exceed 1.8 m (6 ft), without being installed in a raceway and where located to be protected from physical damage and are of a flame-retardant type. Page 289 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC 620.21 Wiring Methods. (e) A sump pump or oil recovery pump located in the pit shall be permitted to be cord connected. The cord shall be a hard usage oil-resistant type, of a length not to exceed 1.8 m (6 ft), and shall be located to be protected from physical damage. 620.21 Wiring Methods. (C) Platform Lifts and Stairway Chairlift Raceways. (C) Platform Lifts and Stairway Chairlift Raceways. 620.23 Branch Circuits for Machine Room or Control Room/Machinery Space or Control Space Lighting and Receptacle(s). (3) Flexible Cords and Cables. Flexible cords and cables that are components of listed equipment and used in circuits operating at 30 volts rms or less or 42 volts dc or less shall be permitted in lengths not to exceed 1.8 m (6 ft), provided the cords and cables are supported and protected from physical damage and are of a jacketed and flame retardant type. 620.23 Branch Circuits for Machine Room or Control Room/Machinery Space or Control Space Lighting and Receptacle(s). (C) Duplex Receptacle. At least one 125-volt, single-phase, duplex receptacle shall be provided in each (C) Duplex Receptacle. At least one 125-volt, single-phase, 15- or 20ampere duplex receptacle shall be Page 290 of 361 Change Description and Impact to Worker Safety Added section to permit the use of limited lengths of flame-retardant flexible cord and cable for limitedenergy circuits associated with platform lifts and stairway chairlifts. As Safe or Safer. Specified that the required receptacle must be rated 15 or 20 amperes. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC machine room or control room and machinery space or control space. 620.24 Branch Circuit for Hoistway Pit Lighting and Receptacle(s). (C) Duplex Receptacle. At least one 125-volt, single-phase, duplex receptacle shall be provided in the hoistway pit. 620.44 Installation of Traveling Cables. Traveling cable shall be permitted to be run without the use of a raceway for a distance not exceeding 1.8 m (6 ft) in length as measured from the first point of support on the elevator car or hoistway wall, or counterweight where applicable, provided the conductors are grouped together and taped or corded, or in the original sheath. Traveling cables shall be permitted to be continued as fixed wiring to elevator controller enclosures and to elevator car and machine room, control room, machinery space, and control space connections, provided they are suitably supported and protected from physical damage. 2008 NEC provided in each machine room or control room and machinery space or control space. 620.24 Branch Circuit for Hoistway Pit Lighting and Receptacle(s). (C) Duplex Receptacle. At least one 125-volt, single-phase, 15- or 20ampere duplex receptacle shall be provided in the hoistway pit. 620.44 Installation of Traveling Cables. Traveling cables that are suitably supported and protected from physical damage shall be permitted to be run without the use of a raceway in either or both of the following: (a) When used inside the hoistway, on the elevator car, hoistway wall, counterweight, or controllers and machinery that are located inside the hoistway, provided the cables are in the original sheath. (b) From inside the hoistway, to elevator controller enclosures and to elevator car and machine room, control room, machinery space, and control space connections that are located outside the hoistway for a distance not exceeding 1.8 m (6 ft) in length as Page 291 of 361 Change Description and Impact to Worker Safety Specified that the required receptacle must be rated 15 or 20 amperes. As Safe or Safer. Revised to permit lengths of traveling cable exceeding 6 ft inside the hoistway without having to be installed in a raceway. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety measured from the first point of support on the elevator car or hoistway wall, or counterweight where applicable, provided the conductors are grouped together and taped or corded, or in the original sheath. These traveling cables shall be permitted to be continued to this equipment. VI. Disconnecting Means and Control VI. Disconnecting Means and Control • Article 620, Part VI Disconnecting Means and Control: Revised several 620.51 Disconnecting Means. 620.51 Disconnecting Means. requirements on the type of locking provision to be provided as part of the (A) Type. The disconnecting means (A) Type. The disconnecting means installed equipment. shall be an enclosed externally shall be an enclosed externally operable fused motor circuit switch or operable fused motor circuit switch or (Sections 620.53, 620.54 and 620.55 circuit breaker capable of being locked circuit breaker capable of being locked have similar wording insertions.) in the open position. The disconnecting in the open position. The provision for means shall be a listed device. locking or adding a lock to the As Safe or Safer. disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted as the means required to be installed at and remain with the equipment. 620.51 Disconnecting Means. The disconnecting means shall be a listed device. 620.51 Disconnecting Means. Page 292 of 361 Revised to cover motor controllers 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety installed in hoistways by requiring the (C) Location. The disconnecting means (C) Location. The disconnecting means main power disconnecting means to be shall be located where it is readily shall be located where it is readily located outside the hoistway (in a accessible to qualified persons. accessible to qualified persons. machine room or space or control room or space) and an additional non(1) On Elevators Without Generator (1) On Elevators Without Generator fused disconnecting means to be Field Control. On elevators without Field Control. On elevators without installed within sight of the motor generator field control, the generator field control, the controller in the elevator hoistway. disconnecting means shall be located disconnecting means shall be located within sight of the motor controller. within sight of the motor controller. As Safe or Safer. Driving machines or motion and Where the motor controller is located in operation controllers not within sight of the elevator hoistway, the the disconnecting means shall be disconnecting means required by provided with a manually operated 620.51(A) shall be located in a switch installed in the control circuit to machinery space, machine room, prevent starting. The manually control space or control room outside operated switch(es) shall be installed the hoistway; and an additional, nonadjacent to this equipment. fused enclosed externally operable motor circuit switch capable of being Where the driving machine of an locked in the open position to electric elevator or the hydraulic disconnect all ungrounded main machine of a hydraulic elevator is power-supply conductors shall be located in a remote machine room or located within sight of the motor remote machinery space, a single controller. The additional switch shall means for disconnecting all be a listed device and shall comply ungrounded main power supply with 620.91(C). conductors shall be provided and be capable of being locked in the open The provision for locking or adding a position. lock to the disconnecting means, required by this section, shall be installed on or at the switch or circuit Page 293 of 361 70 2008 851 Evaluation 2005 NEC IX. Grounding 2008 NEC breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. IX. Grounding 620.81 Metal Raceways Attached to Cars. Metal raceways, Type MC cable, Type MI cable, or Type AC cable attached to elevator cars shall be bonded to grounded metal parts of the car that they contact. 620.81 Metal Raceways Attached to Cars. Metal raceways, Type MC cable, Type MI cable, or Type AC cable attached to elevator cars shall be bonded to metal parts of the car that are bonded to the equipment grounding conductor. 620.82 Electric Elevators. For electric elevators, the frames of all motors, elevator machines, controllers, and the metal enclosures for all electrical equipment in or on the car or in the hoistway shall be grounded in accordance with Article 250. 620.82 Electric Elevators. For electric elevators, the frames of all motors, elevator machines, controllers, and the metal enclosures for all electrical equipment in or on the car or in the hoistway shall be bonded in accordance with Article 250, Parts V and VII. 620.83 Nonelectric Elevators. For elevators other than electric having any electric conductors attached to the car, the metal frame of the car, where normally accessible to persons, shall be grounded in accordance with Article 620.83 Nonelectric Elevators. For elevators other than electric having any electrical conductors attached to the car, the metal frame of the car, where normally accessible to persons, shall be bonded in accordance with Article Page 294 of 361 Change Description and Impact to Worker Safety Revised several sections to address specific bonding requirements and the connection to the equipment grounding conductor. May actually improve safety. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety 250. 250, Parts V and VII. NOTE: Articles 625, 626 and 630 did not have substantial revisions. Article 640 Audio Signal Processing, Amplification, Audio Signal Processing, Amplification, Changed to specifically state that and Reproduction Equipment and Reproduction Equipment Section 300.21 applies to Article 640 to eliminate the confusion and 640.3 Locations and Other Articles. 640.3 Locations and Other Articles. controversy surrounding applicability of Circuits and equipment shall comply Circuits and equipment shall comply the wiring method section. with 640.3(A) through 640.3(L), as with 640.3(A) through (L), as applicable. applicable. As Safe or Safer. (A) Spread of Fire or Products of Combustion. The accessible portion of abandoned audio distribution cables shall be removed. See 300.21. 640.6 Mechanical Execution of Work. (A) Spread of Fire or Products of Combustion. Section 300.21 shall apply. Equipment and cables shall be installed in a neat workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported in such a manner that the cables will not be damaged by normal building use. Such cables shall be supported by straps, staples, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall conform to 300.4(D) and 300.11. (A) Neat and Workmanlike Manner. Audio signal processing, amplification, and reproduction equipment, cables, and circuits shall be installed in a neat workmanlike manner. 640.6 Mechanical Execution of Work. (B) Installation of Audio Distribution Cables. Cables installed exposed on the surface of ceilings and sidewalls shall be supported in such a manner that the audio distribution cables will not be damaged by normal building use. Such cables shall be secured by straps, staples, cable ties, hangers, or Page 295 of 361 Revised to require installations to comply with all requirements in 300.4 and 300.11(A), to require securing of audio cables, and to permit cable ties as a securing means. Relocated requirement on removing accessible portions of abandoned cables. Added identification requirements for cables installed for future use. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety similar fittings designed and installed so as not to damage the cable. The installation shall conform to 300.4 and 300.11(A). (C) Abandoned Audio Distribution Cables. The accessible portion of abandoned audio distribution cables shall be removed. (D) Installed Audio Distribution Cable Identified for Future Use. 640.7 Grounding. (A) General. Wireways and auxiliary gutters shall be grounded and bonded in accordance with the requirements of (1) Cables identified for future use shall be marked with a tag of sufficient durability to withstand the environment involved. (2) Cable tags shall have the following information: (1) Date cable was identified for future use (2) Date of intended use (3) Information related to the intended future use of cable 640.7 Grounding. Provides specific requirements for grounding and bonding which (A) General. Wireways and auxiliary addresses connection to an equipment gutters shall be connected to an grounding conductor. equipment grounding conductor(s), to Page 296 of 361 70 2008 851 Evaluation 2005 NEC Article 250. Where the wireway or auxiliary gutter does not contain power-supply wires, the equipment grounding conductor shall not be required to be larger than 14 AWG copper or its equivalent. Where the wireway or auxiliary gutter contains power-supply wires, the equipment grounding conductor shall not be smaller than specified in 250.122. Information Technology Equipment 2008 NEC an equipment bonding jumper, or to the grounded conductor where permitted or required by 250.92(B)(1) or 250.142. Where the wireway or auxiliary gutter does not contain power-supply wires, the equipment grounding conductor shall not be required to be larger than 14 AWG copper or its equivalent. Where the wireway or auxiliary gutter contains power-supply wires, the equipment grounding conductor shall not be smaller than specified in 250.122. Article 645 Information Technology Equipment Change Description and Impact to Worker Safety May actually improve safety. 645.2 Definition. Added definition of abandoned cables. As Safe or Safer. 645.5 Supply Circuits and Interconnecting Cables. Abandoned Supply Circuits and Interconnecting Cables. Installed supply circuits and interconnecting cables that are not terminated at equipment and not identified for future use with a tag. 645.5 Supply Circuits and Interconnecting Cables. (D) Under Raised Floors. Power cables, communications cables, connecting cables, interconnecting cables, and receptacles associated (D) Under Raised Floors. Power cables, communications cables, connecting cables, interconnecting cables, cord-and-plug connections, Page 297 of 361 Revised to specifically permit flexible cords in the space below a raised floor to make a cord-and-plug connection to a supply receptacle. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC with the information technology equipment shall be permitted under a raised floor, provided the following conditions are met: 645.5 Supply Circuits and Interconnecting Cables. 2008 NEC Change Description and Impact to Worker Safety and receptacles associated with the information technology equipment shall be permitted under a raised floor, provided the following conditions are met: (3) Supply cords of listed information technology equipment in accordance with 645.5(B). 645.5 Supply Circuits and Interconnecting Cables. (D)(5) c. Cable type designations Type TC (Article 336); Types CL2, CL3, and PLTC (Article 725); Type ITC (Article 727); Types NPLF and FPL (Article 760); Types OFC and OFN (Article 770); Type CM (Article 800); and Type CATV (Article 820). These designations shall be permitted to have an additional letter P or R or G. Green, or green with one or more yellow stripes, insulated single conductor cables, 4 AWG and larger, marked “for use in cable trays” or “for CT use” shall be permitted for equipment grounding. (D)(6) c. Cable type designations shown in Table 645.5 shall be permitted. Green, or green with one or more yellow stripes, insulated singleconductor cables, 4 AWG and larger, marked “for use in cable trays” or “for CT use” shall be permitted for equipment grounding. (6) Abandoned cables shall be removed unless contained in metal raceways. 645.5 Supply Circuits and 645.5 Supply Circuits and Page 298 of 361 Moved text to new Table 645.5 to clarify cable types permitted beneath a raised floor and relocated reference to abandoned cables to new Section (F). As Safe or Safer. Relocated requirement for removal of 70 2008 851 Evaluation 2005 NEC Interconnecting Cables. 2008 NEC Interconnecting Cables. (F) Abandoned Supply Circuits and Interconnecting Cables. The accessible portion of abandoned supply circuits and interconnecting cables shall be removed unless contained in a metal raceway. 645.5 Supply Circuits and Interconnecting Cables. 645.5 Supply Circuits and Interconnecting Cables. (G) Installed Supply Circuits and Interconnecting Cables Identified for Future Use. (1) Supply circuits and interconnecting cables identified for future use shall be marked with a tag of sufficient durability to withstand the environment involved. (2) Supply circuit tags and interconnecting cable tags shall have the following information: a. Date identified for future use b. Date of intended use c. Information relating to the intended future use 645.10 Disconnecting Means. A means 645.10 Disconnecting Means. An shall be provided to disconnect power approved means shall be provided to to all electronic equipment in the disconnect power to all electronic information technology equipment equipment in the information Page 299 of 361 Change Description and Impact to Worker Safety accessible portions of abandoned cables. As Safe or Safer. Added identification requirements for cables installed for future use. As Safe or Safer. Revised to require approval of the disconnecting means and allow for shutdown of designated zones within IT rooms. 70 2008 851 Evaluation 2005 NEC 2008 NEC room. There shall also be a similar means to disconnect the power to all dedicated HVAC systems serving the room and cause all required fire/smoke dampers to close. The control for these disconnecting means shall be grouped and identified and shall be readily accessible at the principal exit doors. A single means to control both the electronic equipment and HVAC systems shall be permitted. Where a pushbutton is used as a means to disconnect power, pushing the button in shall disconnect the power. technology equipment room or in designated zones within the room. There shall also be a similar approved means to disconnect the power to all dedicated HVAC systems serving the room or designated zones and shall cause all required fire/smoke dampers to close. The control for these disconnecting means shall be grouped and identified and shall be readily accessible at the principal exit doors. A single means to control both the electronic equipment and HVAC systems in the room or in a zone shall be permitted. Where a pushbutton is used as a means to disconnect power, pushing the button in shall disconnect the power. Where multiple zones are created, each zone shall have an approved means to confine fire or products of combustion to within the zone. Article 647 Sensitive Electronic Equipment (C) Color Coding. All feeders and branch-circuit conductors installed under this section shall be identified as to system at all splices and terminations by color, marking, tagging, or equally effective means. (C) Conductor Identification. All feeders and branch-circuit conductors installed under this section shall be identified as to system at all splices and terminations by color, marking, tagging, or equally effective means. Page 300 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Revised title to correlate with text of the section permitting other than color coding as a means of conductor identification. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC The means of identification shall be posted at each branch-circuit panelboard and at the disconnecting means for the building. 647.8 Lighting Equipment. The means of identification shall be posted at each branch-circuit panelboard and at the disconnecting means for the building. 647.8 Lighting Equipment. (A) Disconnecting Means. All luminaires (lighting fixtures) connected to separately derived systems operating at 60 volts to ground, and associated control equipment if provided, shall have a disconnecting means that simultaneously opens all ungrounded conductors. The disconnecting means shall be located within sight of the luminaire (lighting fixture) or be capable of being locked in the open position. (A) Disconnecting Means. All luminaires connected to separately derived systems operating at 60 volts to ground, and associated control equipment if provided, shall have a disconnecting means that simultaneously opens all ungrounded conductors. The disconnecting means shall be located within sight of the luminaire or be capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. Article 665 Induction and Dielectric Heating Equipment The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or Page 301 of 361 Change Description and Impact to Worker Safety Added requirement on the type of locking equipment to be provided as part of the installed equipment. As Safe or Safer. 665.12, 665.22: Added requirement on the type of locking provision to be provided as part of the installed 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety equipment. circuit breaker used as the disconnecting means and shall remain in place with or without the lock As Safe or Safer. installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. 665.26 Grounding and Bonding. 665.26 Grounding and Bonding. Continuing the emphasis on Grounding or inter-unit bonding, or Bonding to the equipment grounding connection to the equipment grounding both, shall be used wherever required conductor or inter-unit bonding, or conductor versus grounding. for circuit operation, for limiting to a both, shall be used wherever required safe value radio frequency voltages for circuit operation, and for limiting to As Safe or Safer. between all exposed non–currenta safe value radio frequency voltages carrying parts of the equipment and between all exposed non–currentearth ground, between all equipment carrying parts of the equipment parts and surrounding objects, and and earth ground, between all between such objects and earth equipment parts and surrounding ground. Such grounding and bonding objects, and between such objects and shall be installed in accordance with earth ground. Such connection to the Article 250, Parts II and V. equipment grounding conductor and bonding shall be installed in accordance with Article 250, Parts II and V. NOTE: Articles 667 through 692 are determined to have minimal applicability at the Idaho site and are not included. Article 695 Fire Pumps 695.4 Continuity of Power. 695.4 Continuity of Power. Added requirement that conductors supplied by an on-site standby (A) Direct Connection. The supply (A) Direct Connection. The supply generator(s) connect to a separate conductors shall directly connect the conductors shall directly connect the disconnecting means dedicated to the power source to either a listed fire power source to either a listed fire fire pump. Page 302 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC pump controller or listed combination fire pump controller and power transfer switch. pump controller or listed combination fire pump controller and power transfer switch. Where the power source is supplied by on-site generator(s), the supply conductors shall connect to a generator disconnecting means dedicated for the purposes of serving the fire pump. The disconnecting means shall be located in a separate enclosure from the other generator disconnecting means. (1) Overcurrent Device Selection. The overcurrent protective device(s) shall be selected or set to carry indefinitely the sum of the locked-rotor current of the fire pump motor(s) and the pressure maintenance pump motor(s) and the full-load current of the associated fire pump accessory equipment when connected to this power supply. The next standard overcurrent device shall be used in accordance with 240.6. The requirement to carry the locked-rotor currents indefinitely shall not apply to conductors or devices other than overcurrent devices in the fire pump motor circuit(s). Article 700 Emergency Systems Emergency Systems Page 303 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Added provision to limit size of overcurrent protective device to the next standard size or rating specified in 240.6. As Safe or Safer. Revised to require that automatic transfer switches rated 600 volts and 70 2008 851 Evaluation 2005 NEC 2008 NEC 700.6 Transfer Equipment. 700.6 Transfer Equipment. (C) Automatic Transfer Switches. Automatic transfer switches shall be electrically operated and mechanically held. II. Circuit Wiring (C) Automatic Transfer Switches. Automatic transfer switches shall be electrically operated and mechanically held. Automatic transfer switches, rated 600 VAC and below, shall be listed for emergency system use. II. Circuit Wiring 700.9 Wiring, Emergency System. 700.9 Wiring, Emergency System. (B) Wiring. (B) Wiring. Change Description and Impact to Worker Safety below be listed for use with emergency systems. As Safe or Safer. Added wiring separation provisions for emergency sources supplying combinations of emergency, legally required, or optional loads. As Safe or Safer. (5) Wiring from an emergency source to supply any combination of emergency, legally required, or optional loads in accordance with (a), (b), and (c): a. From separate vertical switchboard sections, with or without a common bus, or from individual disconnects mounted in separate enclosures. b. The common bus or separate sections of the switchboard or the individual enclosures shall be permitted to be supplied by single or multiple feeders without overcurrent Page 304 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety protection at the source. Exception to (5)(b): Overcurrent protection shall be permitted at the source or for the equipment, provided the overcurrent protection is selectively coordinated with the downstream overcurrent protection. II. Circuit Wiring c. Legally required and optional standby circuits shall not originate from the same vertical switchboard section, panelboard enclosure, or individual disconnect enclosure as emergency circuits. II. Circuit Wiring 700.9 Wiring, Emergency System. 700.9 Wiring, Emergency System. (D) Fire Protection. (1) Feeder-Circuit Wiring. (4) Be protected by a fire-rated assembly listed to achieve a minimum fire rating of 1 hour 700.9 Wiring, Emergency System. (D) Fire Protection. (1) Feeder-Circuit Wiring. (4) Be protected by a listed firerated assembly that has a minimum fire rating of 1-hour and contains only emergency wiring circuits. 700.9 Wiring, Emergency System. (D) Fire Protection. (D) Fire Protection. (3) Generator Control Wiring. Control conductors installed between the Page 305 of 361 Revised to require that fire-rated assemblies protecting emergency circuits contain only emergency wiring. As Safe or Safer. Added requirement for the separation and protection of generator control wiring. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety III. Sources of Power transfer equipment and the emergency generator shall be kept entirely independent of all other wiring and shall meet the conditions of 700.9(D)(1). III. Sources of Power 700.12 General Requirements. (B) Generator Set. 700.12 General Requirements. (B) Generator Set. As Safe or Safer. (6) Outdoor Generator Sets. Where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. (6) Outdoor Generator Sets. Where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. The disconnecting means shall meet the requirements of 225.36. V. Control — Emergency Lighting Circuits Added requirements for dimmer systems listed for emergency use. V. Control — Emergency Lighting Circuits 700.23 Dimmer Systems. A dimmer system containing more than one dimmer and listed for use in emergency systems shall be permitted to be used as a control device for energizing emergency lighting circuits. Upon failure of normal power, the Page 306 of 361 Clarified that the disconnecting means must comply with 225.36. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 700.27 Coordination. Emergency system(s) overcurrent devices shall be selectively coordinated with all supply side overcurrent protective devices. dimmer system shall be permitted to selectively energize only those branch circuits required to provide minimum emergency illumination. All branch circuits supplied by the dimmer system cabinet shall comply with the wiring methods of Article 700. 700.27 Coordination. Emergency system(s) overcurrent devices shall be selectively coordinated with all supply side overcurrent protective devices. Change Description and Impact to Worker Safety Added exception with two conditions where selective coordination is not required. As Safe or Safer. Exception: Selective coordination shall not be required in (1) or (2): (1) Between transformer primary and secondary overcurrent protective devices, where only one overcurrent protective device or set of overcurrent protective devices exists on the transformer secondary, (2) Between overcurrent protective devices of the same size (ampere rating) in series. Article 701 Legally Required Standby Systems 701.7 Transfer Equipment. (C) Automatic Transfer Switches. Page 307 of 361 Revised to require that automatic transfer switches rated 600 volts and below be listed for use with legally 70 2008 851 Evaluation 2005 NEC 2008 NEC III. Sources of Power Automatic transfer switches shall be electrically operated and mechanically held. Automatic transfer switches, rated 600 VAC and below, shall be listed for legally required standby system use. III. Sources of Power 701.11 Legally Required Standby Systems. 701.11 Legally Required Standby Systems. (B) Generator Set. (B) Generator Set. (5) Outdoor Generator Sets. Where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. (5) Outdoor Generator Sets. Where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. The disconnecting means shall meet the requirements of 225.36. 701.18 Coordination. Legally required standby system(s) overcurrent devices shall be selectively coordinated with all supply side overcurrent protective devices. 701.18 Coordination. Legally required standby system(s) overcurrent devices shall be selectively coordinated with all supply side overcurrent protective devices. Exception: Selective coordination shall Page 308 of 361 Change Description and Impact to Worker Safety required standby systems. As Safe or Safer. Clarified that the disconnecting means must comply with 225.36. As Safe or Safer. Added exception with two conditions where selective coordination is not required. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety not be required in (1) or (2): (1) Between transformer primary and secondary overcurrent protective devices, where only one overcurrent protective device or set of overcurrent protective devices exists on the transformer secondary, (2) Between overcurrent protective devices of the same size (ampere rating) in series. Article 702 Optional Standby Systems 702.5 Capacity and Rating. An optional 702.5 Capacity and Rating. standby system shall have adequate capacity and rating for the supply of all (A) Available Short-Circuit Current. equipment intended to be operated at Optional standby system equipment one time. Optional standby system shall be suitable for the maximum equipment shall be suitable for the available short-circuit current at its maximum available fault current at its terminals. terminals. The user of the optional (B) System Capacity. The calculations standby system shall be permitted to of load on the standby source shall be select the load connected to the made in accordance with Article system. 220 or by another approved method. (1) Manual Transfer Equipment. Where manual transfer equipment is used, an optional standby system shall have adequate capacity and rating for the supply of all equipment Page 309 of 361 Revised requirement on the standby source capacity based on whether manual or automatic transfer is employed and on how standby loads are to be calculated. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety intended to be operated at one time. The user of the optional standby system shall be permitted to select the load connected to the system. (2) Automatic Transfer Equipment. Where automatic transfer equipment is used, an optional standby system shall comply with (2)(a) or (2)(b). (a) Full Load. The standby source shall be capable of supplying the full load that is transferred by the automatic transfer equipment. IV. Sources of Power (b) Load Management. Where a system is employed that will automatically manage the connected load, the standby source shall have a capacity sufficient to supply the maximum load that will be connected by the load management system. IV. Sources of Power 702.11 Outdoor Generator Sets. Where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied, an additional 702.11 Outdoor Generator Sets. Where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied, an additional Page 310 of 361 Clarified that the disconnecting means must comply with 225.36, which requires that the disconnecting means be suitable for service equipment. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. 2008 NEC disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. The disconnecting means shall meet the requirements of 225.36. Article 705 and 708 Article 705 Interconnected Electric Power Production Sources Article 708 Critical Operations Power Systems (COPS) Change Description and Impact to Worker Safety Extensively revised/rewritten and added two new parts covering “UtilityInteractive Inverters” and “Generators.” As Safe or Safer. New article to provide requirements for the installation, operation, control, and maintenance of the portions of premise wiring systems intended to supply, distribute, and control electricity to designated critical operations areas of a building or facility that requires an electrical supply and distribution system with a high degree of reliability and resiliency to natural disasters and other threats. As Safe or Safer. Circuits and Equipment Operating at Less Than 50 Volts Article 720 Circuits and Equipment Operating at Less Than 50 Volts 720.2 Other Articles. Installations operating at less than 50 volts, direct 720.2 Other Articles. Direct current or alternating-current installations Page 311 of 361 Clarified by providing the specific parts or sections of other articles that are not subject to the requirements of Article 720. 70 2008 851 Evaluation 2005 NEC 2008 NEC current or alternating current, as covered in Articles 411, 517, 550, 551, 552, 650, 669, 690, 725, and 760 shall not be required to comply with this article. operating at less than 50 volts, as covered in 411.1 through 411.7; Part VI of Article 517; Part II of Article 551; Parts II and III and 552.60(B) of Article 552; 650.1 through 650.8; 669.1 through 669.9; Parts I and VIII of Article 690; Parts I and III of Article 725; or Parts I and III of Article 760 shall not be required to comply with this article. 720.3 Hazardous (Classified) Locations. Installations within the scope of this article and installed in hazardous (classified) locations shall also comply with the appropriate provisions for hazardous (classified) locations in other applicable articles of this Code. Article 725 Class 1, Class 2, and Class 3 RemoteControl, Signaling, and Power-Limited Circuits 725.24 Mechanical Execution of Work. Class 1, Class 2, and Class 3 circuits shall be installed in a neat and workmanlike manner. Cables and conductors installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. 720.3 Hazardous (Classified) Locations. Installations coming within the scope of this article and installed in hazardous (classified) locations shall also comply with the appropriate provisions of Articles 500 through 517. 725.8 Mechanical Execution of Work. Class 1, Class 2, and Class 3 circuits shall be installed in a neat and workmanlike manner. Cables and conductors installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Page 312 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Removed limitation referencing just Articles 500 – 517 to include any applicable articles. As Safe or Safer. Revised to add cable ties as a supporting means. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC Such cables shall be supported by straps, staples, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform with 300.4(D). 725.3 Other Articles. (B) Spread of Fire or Products of Combustion. Section 300.21. The accessible portion of abandoned Class 2, Class 3, and PLTC cables shall be removed. 2008 NEC Such cables shall be supported by straps, staples, hangers, cable ties, or similar fittings designed and installed so as not to damage the cable. The installation shall also comply with 300.4(D). 725.25 Abandoned Cables. The accessible portion of abandoned Class 2, Class 3, and PLTC cables shall be removed. Where cables are identified for future use with a tag, the tag shall be of sufficient durability to withstand the environment involved. 725.26 Conductors of Different Circuits in the Same Cable, Cable Tray, Enclosure, or Raceway. 725.48 Conductors of Different Circuits in the Same Cable, Cable Tray, Enclosure, or Raceway. (B) Class 1 Circuits with Power Supply Circuits. (B) Class 1 Circuits with Power-Supply Circuits. (4) In Cable Trays. In cable trays, where the Class 1 circuit conductors and power-supply conductors not functionally associated with them are separated by a solid fixed barrier of a material compatible with the cable tray, or where the power-supply or Class 1 circuit conductors are in a metalenclosed cable. (4) In Cable Trays. Installations in cable trays shall comply with 725.48(B)(4)(1) or (B)(4)(2). Change Description and Impact to Worker Safety Relocated requirement on removing accessible portions of abandoned cables from 725.3, and added requirement on the durability of tags used to identify cable(s) intended for future use. As Safe or Safer. Added new provision permitting separation of Class 1 circuit conductors from power supply conductors in cable trays using Types AC, MC, MI, or TC cables. As Safe or Safer. (1) Class 1 circuit conductors and power-supply conductors not functionally associated with the Class 1 circuit conductors shall be separated by a solid fixed barrier of a material compatible with the cable Page 313 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety tray. 725.52 Wiring Methods and Materials on Load Side of the Class 2 or Class 3 Power Source. (2) Class 1 circuit conductors and power-supply conductors not functionally associated with the Class 1 circuit conductors shall be permitted to be installed in a cable tray without barriers where all of the conductors are installed with separate multiconductor Type AC, Type MC, Type MI, or Type TC cables and all the conductors in the cables are insulated at 600 volts. 725.130 Wiring Methods and Materials on Load Side of the Class 2 or Class 3 Power Source. (B) Class 2 and Class 3 Wiring Methods. (B) Class 2 and Class 3 Wiring Methods. 725.56 Installation of Conductors of Different Circuits in the Same Cable, Enclosure, or Raceway. Exception No. 3: Bare Class 2 conductors shall be permitted as part of a listed intrusion protection system where installed in accordance with the listing instructions for the system. 725.139 Installation of Conductors of Different Circuits in the Same Cable, Enclosure, or Raceway. (E) Class 2 or Class 3 Cables with Other Circuit Cables. Jacketed cables (E) Class 2 or Class 3 Cables with Other Circuit Cables. Jacketed cables Page 314 of 361 Added exception to permit bare Class 2 conductors as part of a listed intrusion protection system. The Code Panel 3 had much discussion around this issue since it involved energized bare conductors most prevalent on window intrusion detection systems. It was determined to be a safe installation technique. As Safe or Safer. Revised to include cable trays. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC of Class 2 or Class 3 circuits shall be permitted in the same enclosure or raceway with jacketed cables of any of the following: 725.61 Applications of Listed Class 2, Class 3, and PLTC Cables. of Class 2 or Class 3 circuits shall be permitted in the same enclosure, cable tray, or raceway with jacketed cables of any of the following: 725.154 Applications of Listed Class 2, Class 3, and PLTC Cables. (B) Riser. Cables installed in risers shall be as described in any of (B)(1), (B)(2), or (B)(3): (B) Riser. Cables installed in risers shall be as described in any of (B)(1), (B)(2), or (B)(3): (1) Cables installed in vertical runs and penetrating more than one floor, or cables installed in vertical runs in a shaft, shall be Type CL2R or CL3R. Floor penetrations requiring Type CL2R or CL3R shall contain only cables suitable for riser or plenum use. Listed riser signaling raceways shall be permitted to be installed in vertical riser runs in a shaft from floor to floor. Only Type CL2R, CL3R, CL2P, or CL3P cables shall be permitted to be installed in these raceways. 725.61 Applications of Listed Class 2, Class 3, and PLTC Cables. (1) Cables installed in vertical runs and penetrating more than one floor, or cables installed in vertical runs in a shaft, shall be Type CL2R or CL3R. Floor penetrations requiring Type CL2R or CL3R shall contain only cables suitable for riser or plenum use. Listed riser signaling raceways and listed plenum signaling raceways shall be permitted to be installed in vertical riser runs in a shaft from floor to floor. Only Type CL2R, CL3R, CL2P, or CL3P cables shall be permitted to be installed in these raceways. 725.154 Applications of Listed Class 2, Class 3, and PLTC Cables. (C) Cable Trays. Cables installed in cable trays outdoors shall be Type PLTC. Cables installed in cable trays (C) Cable Trays. Cables installed in cable trays outdoors shall be Type PLTC. Cables installed in cable trays Page 315 of 361 Change Description and Impact to Worker Safety Revised to include listed plenum signaling raceways. As Safe or Safer. Revised to specify that listed generalpurpose, listed riser, and listed plenum signaling raceways are permitted to be installed in cable trays. 70 2008 851 Evaluation 2005 NEC indoors shall be Types PLTC, CL3P, CL3R, CL3, CL2P, CL2R, and CL2. Listed signaling raceways shall be permitted for use with cable trays. 2008 NEC 725.61 Applications of Listed Class 2, Class 3, and PLTC Cables. indoors shall be Types PLTC, CL3P, CL3R, CL3, CL2P, CL2R, and CL2. Listed general-purpose signaling raceways, listed riser signaling raceways, and listed plenum signaling raceways shall be permitted for use with cable trays. 725.154 Applications of Listed Class 2, Class 3, and PLTC Cables. (D) Hazardous (Classified) Locations. Cables installed in hazardous locations shall be as described in 725.61(D)(1) through (D)(4). (D) Hazardous (Classified) Locations. Cables installed in hazardous locations shall be as described in 725.154(D)(1) through (D)(4). (4) In Industrial Establishments. In industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation, and where the cable is not subject to physical damage, Type PLTC cable that complies with the crush and impact requirements of Type MC cable and is identified for such use shall be permitted to be exposed between the cable tray and utilization equipment or device. The cable shall be continuously supported and protected against physical damage using mechanical protection such as dedicated struts, (4) In Industrial Establishments. In industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation, Type PLTC cable shall be permitted in accordance with either (1) or (2): (1) Type PLTC cable, with a metallic sheath or armor in accordance with 725.179(E), shall be permitted to be installed exposed. The cable shall be continuously supported and protected against physical damage using mechanical protection such as dedicated struts, angles, or channels. Page 316 of 361 Change Description and Impact to Worker Safety • 725.154(D)(4): Added provisions for PLTC-ER cable to be installed exposed in industrial occupancies. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC angles, or channels. The cable shall be The cable shall be secured at intervals secured at intervals not exceeding 1.8 not exceeding 1.8 m (6 ft). m (6 ft). (2) Type PLTC cable, without a metallic sheath or armor, that complies with the crush and impact requirements of Type MC cable and identified for such use with the marking PLTC-ER, shall be permitted to be installed exposed. The cable shall be continuously supported and protected against physical damage using mechanical protection such as dedicated struts, angles, or channels. The cable shall be secured at intervals not exceeding 1.8 m (6 ft). IV. Listing Requirements IV. Listing Requirements 725.82 Listing and Marking of Class 2, Class 3, and Type PLTC Cables. 725.179 Listing and Marking of Class 2, Class 3, and Type PLTC Cables. 727.4 Uses Permitted. (E)…………….Type PLTC cable used in a wet location shall be listed for use in wet locations or have a moisture impervious metal sheath. Article 727 Instrumentation Tray Cable: Type ITC 727.4 Uses Permitted. (5) Without a metallic sheath or armor between cable tray and equipment in (5) Cable, without a metallic sheath or armor, that complies with the crush Page 317 of 361 Change Description and Impact to Worker Safety • 725.179(E): Revised to require that Type PLTC cables used in wet locations be listed for use in wet locations or have a moistureimpervious metal sheath. As Safe or Safer. Revised to permit exposed, continuously supported installations of Type ITC-ER without length limitation. 70 2008 851 Evaluation 2005 NEC lengths not to exceed 15 m (50 ft), where the cable is supported and protected against physical damage using mechanical protection, such as struts, angles, or channels. The cable shall be supported and secured at intervals not exceeding 1.8 m (6 ft). 2008 NEC and impact requirements of Type MC cable and is identified for such use with the marking ITC-ER shall be permitted to be installed exposed. The cable shall be continuously supported and protected against physical damage using mechanical protection such as dedicated struts, angles, or channels. The cable shall be secured at intervals not exceeding 1.8 m (6 ft). (6) Between cable tray and equipment in lengths not to exceed 15 m (50 ft), where the cable complies with the crush and impact requirements of Type MC cable and is identified for such use. The cable shall be supported and secured at intervals not exceeding 1.8 m (6 ft). 727.5 Uses Not Permitted. 727.5 Uses Not Permitted. Type ITC cable shall not be installed with power, lighting, Class 1, or non– power-limited circuits. 760.3 Other Articles. …………………Type ITC cable shall not be installed with power, lighting, Class 1 circuits that are not power limited, or non–power-limited circuits. Article 760 Fire Alarm Systems 760.3 Other Articles. (G) Installation of Conductors with Other Systems. Installations shall comply with 300.8. Page 318 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Revised to clarify that Type ITC can be installed with Class 1 power-limited circuits. As Safe or Safer. Added requirement for fire alarm system conductors to comply with 300.8. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC 760.8 Mechanical Execution of Work. Fire alarm circuits shall be installed in a neat workmanlike manner. Cables and conductors installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be supported by straps, staples, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform with 300.4(D). 760.24 Mechanical Execution of Work. Fire alarm circuits shall be installed in a neat workmanlike manner. Cables and conductors installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be supported by straps, staples, cable ties, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also comply with 300.4(D). 760.25 Abandoned Cables. The accessible portion of abandoned fire alarm cables shall be removed. Where cables are identified for future use with a tag, the tag shall be of sufficient durability to withstand the environment involved. 760.30 Fire Alarm Circuit Identification. Fire alarm circuits shall be identified at terminal and junction locations in a manner that helps to prevent unintentional signals on fire alarm system circuit(s) during testing and servicing of other systems. 760.41 NPLFA Circuit Power Source Requirements. 760.10 Fire Alarm Circuit Identification. Fire alarm circuits shall be identified at terminal and junction locations in a manner that will prevent unintentional interference with the signaling circuit during testing and servicing. 760.21 NPLFA Circuit Power Source Requirements. Page 319 of 361 Change Description and Impact to Worker Safety Added cable ties as a supporting means. As Safe or Safer. Relocated requirement on removing accessible portions of abandoned cables, and added requirement on the durability of tags used to identify cable(s) intended for future use. As Safe or Safer. Revised to specify the intended objective of identifying fire alarm circuits at terminal and junction locations. As Safe or Safer. Added requirement for NPLFA power sources to be supplied by an individual branch circuit. 70 2008 851 Evaluation 2005 NEC 2008 NEC The power source of non–powerlimited fire alarm circuits shall comply with Chapters 1 through 4, and the output voltage shall not be more than 600 volts, nominal. These circuits shall not be supplied through ground-fault circuit interrupters or arc-fault circuit interrupters. (A) Power Source. The power source of non–power-limited fire alarm circuits shall comply with Chapters 1 through 4, and the output voltage shall be not more than 600 volts, nominal. 760.41 Power Sources for PLFA Circuits. The power source for a power-limited fire alarm circuit shall be as specified in 760.41(A), (B), or (C). These circuits shall not be supplied through ground-fault circuit interrupters or arc-fault circuit interrupters. (B) Branch Circuit. An individual branch circuit shall be required for the supply of the power source. This branch circuit shall not be supplied through ground-fault circuit interrupters or arc-fault circuit interrupters. 760.121 Power Sources for PLFA Circuits. (A) Power Source. The power source for a power-limited fire alarm circuit shall be as specified in 760.121(A)(1), (A)(2), or (A)(3). (1) A listed PLFA or Class 3 transformer. (2) A listed PLFA or Class 3 power supply. (3) Listed equipment marked to identify the PLFA power source. (B) Branch Circuit. An individual branch circuit shall be required for the supply of the power source. This branch circuit shall not be supplied through ground-fault circuit interrupters Page 320 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Added requirement for PLFA power sources to be supplied by an individual branch circuit. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 760.52 Wiring Methods and Materials on Load Side of the PLFA Power Source. (B) PLFA Wiring Methods and Materials. Power-limited fire alarm conductors and cables described in 760.82 shall be installed as detailed in 760.52(B)(1), (B)(2), or (B)(3) of this section. Devices shall be installed in accordance with 110.3(B), 300.11(A), and 300.15. 760.56 Installation of Conductors of Different PLFA Circuits, Class 2, Class 3, and Communications Circuits in the Same Cable, Enclosure, or Raceway. IV. Listing Requirements 760.81 Listing and Marking of NPLFA Cables. Non–power-limited fire alarm cables installed as wiring within buildings shall be listed in accordance with 760.81(A) and 760.81(B) and as being resistant to the spread of fire in accordance with 760.81(C) through 760.81(F), and shall be marked in accordance with 760.81(G). 2008 NEC or arc-fault circuit interrupters. 760.130 Wiring Methods and Materials on Load Side of the PLFA Power Source. (B) PLFA Wiring Methods and Materials. Power-limited fire alarm conductors and cables described in 760.179 shall be installed as detailed in 760.130(B)(1), (B)(2), or (B)(3) of this section and 300.7. Devices shall be installed in accordance with 110.3(B), 300.11(A), and 300.15. 760.139 Installation of Conductors of Different PLFA Circuits, Class 2, Class 3, and Communications Circuits in the Same Cable, Enclosure, Cable Tray, or Raceway. IV. Listing Requirements Change Description and Impact to Worker Safety Added 300.7 to compliance requirements for installation of PLFA cables and conductors. As Safe or Safer. Revised to include cable trays in (A), (B), (C) and (D). As Safe or Safer. Added requirement that NPLFA cables used in wet locations be listed for use in wet locations or have a moistureimpervious metal sheath. 760.176 Listing and Marking of NPLFA Cables. Non–power-limited fire alarm cables installed as wiring within buildings shall be listed in accordance As Safe or Safer. with 760.176(A) and (B) and as being resistant to the spread of fire in accordance with 760.176(C) through (F), and shall be marked in accordance with 760.176(G). Cable used in a wet location shall be listed for use in wet locations or have a moisture- Page 321 of 361 70 2008 851 Evaluation 2005 NEC 760.82 Listing and Marking of PLFA Cables and Insulated Continuous LineType Fire Detectors. Type FPL cables installed as wiring within buildings shall be listed as being resistant to the spread of fire and other criteria in accordance with 760.82(A) through 760.82(H) and shall be marked in accordance with 760.82(I). Insulated continuous line-type fire detectors shall be listed in accordance with 760.82(J). 770.2 Definitions. 2008 NEC impervious metal sheath. 760.179 Listing and Marking of PLFA Cables and Insulated Continuous LineType Fire Detectors. Type FPL cables installed as wiring within buildings shall be listed as being resistant to the spread of fire and other criteria in accordance with 760.179(A) through (H) and shall be marked in accordance with 760.179(I). Insulated continuous line-type fire detectors shall be listed in accordance with 760.179(J). Cable used in a wet location shall be listed for use in wet locations or have a moisture-impervious metal sheath. Article 770 Optical Fiber Cables and Raceways 770.2 Definitions. See Article 100. For purposes of this article, the following additional definitions apply. Change Description and Impact to Worker Safety Added requirement for PLFA cables used in wet locations be listed for use in wet locations or have a moistureimpervious metal sheath. As Safe or Safer. Added a reference to Article 100. As Safe or Safer. 770.2 Definitions. 770.2 Definitions. 770.2 Definitions. Exposed (to Accidental Contact). A conductive optical fiber cable in such a As Safe or Safer. position that, in case of failure of supports or insulation, contact between the cable’s non–current-carrying conductive members and an electrical circuit may result. 770.2 Definitions. Added to define a term used Page 322 of 361 Clarified the meaning of the term as applied in Article 770. 70 2008 851 Evaluation 2005 NEC 770.3 Other Articles. Circuits and equipment shall comply with 770.3(A) and 770.3(B). Only those sections of Article 300 referenced in this article shall apply to optical fiber cables and raceways. (A) Spread of Fire or Products of Combustion. The requirements of 300.21 for electrical installations shall also apply to installations of optical fiber cables and raceways. The accessible portion of abandoned optical fiber cables shall be removed. 770.24 Mechanical Execution of Work. Optical fiber cables shall be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be secured by straps, staples, hangers, or similar fittings designed and installed so as not to damage the cable. The 2008 NEC Optical Fiber Cable. A factory assembly of one or more optical fibers having an overall covering. 770.3 Other Articles. Circuits and equipment shall comply with 770.3(A) and (B). Only those sections of Chapter 2 and Article 300 referenced in this article shall apply to optical fiber cables and raceways. (A) Composite Cables. Composite optical fiber cables shall be classified as electrical cables in accordance with the type of electrical conductors. They shall be constructed, listed, and marked in accordance with the appropriate article for each type of electrical cable. 770.24 Mechanical Execution of Work. Optical fiber cables shall be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be secured by hardware including straps, staples, cable ties, hangers, or similar fittings designed and installed so as not to Page 323 of 361 Change Description and Impact to Worker Safety throughout Article 770. As Safe or Safer. Specified that Chapter 2 requirements apply only if referenced. Added new (A) after relocating abandoned cable text to 770.25. As Safe or Safer. Added cable ties as a securing means. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC installation shall also conform with 300.4(D) and 300.11. 770.3 Other Articles. (A) Spread of Fire or Products of Combustion. The requirements of 300.21 for electrical installations shall also apply to installations of optical fiber cables and raceways. The accessible portion of abandoned optical fiber cables shall be removed. 770.3 Other Articles. (A) Spread of Fire or Products of Combustion. The requirements of 300.21 for electrical installations shall also apply to installations of optical fiber cables and raceways. The accessible portion of abandoned optical fiber cables shall be removed. 2008 NEC damage the cable. The installation shall also conform with 300.4(D) and 300.11. 770.25 Abandoned Cables. The accessible portion of abandoned optical fiber cables shall be removed. Where cables are identified for future use with a tag, the tag shall be of sufficient durability to withstand the environment involved. 770.26 Spread of Fire or Products of Combustion. Installations of optical fiber cables and raceways in hollow spaces, vertical shafts, and ventilation or air-handling ducts shall be made so that the possible spread of fire or products of combustion will not be substantially increased. Openings around penetrations of optical fiber cables and raceways through fireresistant–rated walls, partitions, floors, or ceilings shall be fire-stopped using approved methods to maintain the fire resistance rating. II. Cables Outside and Entering Buildings. 770.48 Unlisted Cables and Raceways Entering Buildings. Page 324 of 361 Change Description and Impact to Worker Safety Relocated requirement on removing accessible portions of abandoned cables, and added requirement on the durability of tags used to identify cable(s) intended for future use. As Safe or Safer. Relocated requirement on the spread of fire or products of combustion with new text that is parallel with the provisions of 300.21. As Safe or Safer. Added section to provide specific installation requirements for unlisted conductive and nonconductive optical fiber cable. 70 2008 851 Evaluation 2005 NEC 2008 NEC (A) Conductive and Nonconductive Cables. Unlisted conductive and nonconductive outside plant optical fiber cables shall be permitted to be installed in locations as described in 770.154(C), where the length of the cable within the building, measured from its point of entrance, does not exceed 15 m (50 ft) and the cable enters the building from the outside and is terminated in an enclosure. 770.48 Unlisted Cables and Raceways Entering Buildings. II. Protection (B) Nonconductive Cables. Unlisted nonconductive optical fiber outside plant optical fiber cables shall be permitted to enter the building from the outside and run in raceway systems installed in compliance with any of the following articles in Chapter 3: Article 342, Intermediate Metal Conduit: Type IMC; Article 344, Rigid Metal Conduit: Type RMC; Article 352, Rigid Polyvinyl Chloride Conduit: Type PVC; and Article 358, Electrical Metallic Tubing: Type EMT. III. Protection 770.93 Grounding of Entrance Cables. 770.93 Grounding or Interruption of Page 325 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Added section to provide specific installation requirements for unlisted conductive and nonconductive optical fiber cable. As Safe or Safer. Relocated and expanded the detailed requirements for fiber optic cables entering buildings. 70 2008 851 Evaluation 2005 NEC Where exposed to contact with electric light or power conductors, the non– current-carrying metallic members of optical fiber cables entering buildings shall be grounded as close to the point of entrance as practicable or shall be interrupted as close to the point of entrance as practicable by an insulating joint or equivalent device. 2008 NEC Non–Current-Carrying Metallic Members of Optical Fiber Cables. Optical fiber cables entering the building or terminating on the outside of the building shall comply with 770.93(A) or (B). (A) Entering Buildings. In installations where an optical fiber cable is exposed to contact with electric light or power conductors and the cable enters the building, the non-current-carrying metallic members shall be either grounded as specified in 770.100, or interrupted by an insulating joint or equivalent device. The grounding or interruption shall be as close as practicable to the point of entrance. (B) Terminating On the Outside of Buildings. In installations where an optical fiber cable is exposed to contact with electric light or power conductors and the cable is terminated on the outside of the building, the non– current-carrying metallic members shall be either grounded as specified in 770.100, or interrupted by an insulating joint or equivalent device. The grounding or interruption shall be as close as practicable to the point of Page 326 of 361 Change Description and Impact to Worker Safety As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC termination of the cable. IV. Grounding Methods 770.100 Entrance Cable Grounding. Where grounded, the non–currentcarrying metallic members of optical fiber cables entering buildings shall be grounded as specified in 770.100(A) through (D). (A) Grounding Conductor. (1) Insulation. The grounding conductor shall be insulated and shall be listed. (2) Material. The grounding conductor shall be copper or other corrosionresistant conductive material, stranded or solid. (3) Size. The grounding conductor shall not be smaller than 14 AWG. It shall have a current-carrying capacity approximately equal to or greater than that of the metallic member(s). The grounding conductor shall not be required to exceed 6 AWG. (4) Run in Straight Line. The grounding conductor shall be run to the grounding electrode in as straight a line as practicable. (5) Physical Damage. Where necessary, the grounding conductor Page 327 of 361 Change Description and Impact to Worker Safety Inserted specific Part for grounding and consolidated the requirements from other sections. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC shall be guarded from physical damage. Where the grounding conductor is run in a metal raceway, both ends of the raceway shall be bonded to the grounding conductor or the same terminal or electrode to which the grounding conductor is connected. (B) Electrode. The grounding conductor shall be connected in accordance with 770.100(B)(1), (B)(2), or (B)(3). (1) In Buildings or Structures with an Intersystem Bonding Termination. If the building or structure served has an intersystem bonding termination, the grounding conductor shall be connected to the intersystem bonding termination. (2) In Buildings or Structures with Grounding Means. If the building or structure served has no intersystem bonding termination, the grounding conductor shall be connected to the nearest accessible location on the following: (1) The building or structure grounding electrode system as covered in 250.50 Page 328 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC (2) The grounded interior metal water piping system, within 1.5 m (5 ft) from its point of entrance to the building, as covered in 250.52 (3) The power service accessible means external to enclosures as covered in 250.94 (4) The metallic power service raceway (5) The service equipment enclosure (6) The grounding electrode conductor or the grounding electrode conductor metal enclosure (7) The grounding conductor or the grounding electrode of a building or structure disconnecting means that is grounded to an electrode as covered in 250.32 (3) In Buildings or Structures Without Intersystem Bonding Termination or Grounding Means. If the building or structure served has no intersystem bonding termination or grounding means, as described in 770.100(B)(2), the grounding conductor shall be connected to either of the following: (1) To any one of the individual electrodes described in 250.52(A)(1), (A)(2), (A)(3), or Page 329 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC (A)(4). (2) If the building or structure served has no grounding means, as described in 770.100(B)(2) or (B)(3)(1), to an effectively grounded metal structure or to a ground rod or pipe not less than 1.5 m (5 ft) in length and 12.7 mm ( in.) in diameter, driven, where practicable, into permanently damp earth and separated from lightning conductors as covered in 800.53 and at least 1.8 m (6 ft) from electrodes of other systems. Steam or hot water pipes or air terminal conductors (lightningrod conductors) shall not be employed as electrodes for protectors. (C) Electrode Connection. Connections to grounding electrodes shall comply with 250.70. (D) Bonding of Electrodes. A bonding jumper not smaller than 6 AWG copper or equivalent shall be connected between the grounding electrode and power grounding electrode system at the building or structure served where separate electrodes are used. Page 330 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC Exception: At mobile homes as covered in 770.106. V. Installation Methods Within Buildings 770.113 Installation and Marking of Listed Optical Fiber Cables. Listed optical fiber cables shall be installed as wiring within buildings. Optical fiber 770.110 Raceways for Optical Fiber Cables. Where optical fiber cables are installed in a raceway, the raceway shall be either of a type permitted in Chapter 3 and installed in accordance with Chapter 3 or listed plenum optical fiber raceway, listed riser optical fiber raceway, or listed general-purpose optical fiber raceway selected in accordance with the provisions of 770.154, and installed in accordance with 362.24 through 362.56, where the requirements applicable to electrical nonmetallic tubing apply. Where optical fiber cables are installed in raceway without current-carrying conductors, the raceway fill tables of Chapter 3 and Chapter 9 shall not apply. Where nonconductive optical fiber cables are installed with electric conductors in a raceway, the raceway fill tables of Chapter 3 and Chapter 9 shall apply. 770.113 Installation of Optical Fiber Cables. Optical fiber cables installed in buildings shall be listed. Page 331 of 361 Change Description and Impact to Worker Safety Clarified that raceway fill provisions apply to Chapter 3 raceways and to listed plenum, riser, and generalpurpose optical fiber raceways. As Safe or Safer. Relocated information and revised entire part to consolidate and clarify requirements. 70 2008 851 Evaluation 2005 NEC cables shall be marked in accordance with Table 770.113. 2008 NEC 770.133 Installation of Optical Fibers and Electrical Conductors. Exception: Optical fiber cables that comply with 770.48 shall not be required to be listed. 770.133 Installation of Optical Fibers and Electrical Conductors. (A) With Conductors for Electric Light, Power, Class 1, Non–Power-Limited Fire Alarm, or Medium Power NetworkPowered Broadband Communications Circuits. (A) With Conductors for Electric Light, Power, Class 1, Non–Power-Limited Fire Alarm, or Medium Power NetworkPowered Broadband Communications Circuits. 770.133 Installation of Optical Fibers and Electrical Conductors. (C) Grounding. Non–current-carrying conductive members of optical fiber cables shall be grounded in accordance with Article 250. Change Description and Impact to Worker Safety As Safe or Safer. Added exception to permit optical fiber cables in the same raceway, outlet box, or other enclosure where separated by a permanent barrier or a listed divider. As Safe or Safer. Exception No. 5: Where all of the conductors of electric light, power, Class 1, non-power-limited fire alarm, and medium-power network-powered broadband communications circuits are separated from all of the optical fiber cables by a permanent barrier or listed divider. 770.133 Installation of Optical Fibers Added requirement prohibiting optical and Electrical Conductors. fiber cables from being supported by attachment to the exterior of raceways (C) Support of Cables. Raceways shall other than raceway-type masts. be used for their intended purpose. Optical fiber cables shall not be As Safe or Safer. strapped, taped, or attached by any means to the exterior of any conduit or raceway as a means of support. Page 332 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Exception: Overhead (aerial) spans of optical fiber cables shall be permitted to be attached to the exterior of a raceway-type mast intended for the attachment and support of such cables. 770.154 Applications of Listed Optical Fiber Cables and Raceways. (B) Riser. Cables installed in risers shall be as described in any of (B)(1), (B)(2), or (B)(3). (1) Cables in Vertical Runs. Cables installed in vertical runs and penetrating more than one floor, or cables installed in vertical runs in a shaft, shall be Type OFNR or OFCR. Floor penetrations requiring Type OFNR or OFCR shall contain only cables suitable for riser or plenum use. Listed riser optical fiber raceways and listed plenum optical fiber raceways shall also be permitted to be installed in vertical riser runs in a shaft from floor to floor. Only Type OFNP, OFCP, OFNR, and OFCR cables shall be permitted to be installed in these raceways. Article 800 Communications Circuits Page 333 of 361 Change Description and Impact to Worker Safety Added listed plenum optical fiber raceways as acceptable for use in a riser. As Safe or Safer. Revised to ensure applicability to 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety modern telecommunications systems used in new and existing buildings and structures. As Safe or Safer. Added definition to describe the type of circuit covered by the requirements of Article 800. 800.2 Definitions. 800.2 Definitions. Communications Equipment. The electronic equipment that performs the telecommunications operations for the transmission of audio, video, and data, and including power equipment (e.g., dc converters, inverters and batteries) and technical support equipment (e.g., computers). Communications Circuit. The circuit that extends voice, audio, video, data, interactive services, telegraph (except As Safe or Safer. radio), outside wiring for fire alarm and burglar alarm from the communications utility to the customer’s communications equipment up to and including terminal equipment such as a telephone, fax machine, or answering machine. 800.2 Definitions. Clarified meaning of the term as used in Article 800 requirements. Exposed (to Accidental Contact). A circuit that is in such a position that, in As Safe or Safer. case of failure of supports or insulation, contact with another circuit may result. 800.3 Other Articles. Added requirement for networkpowered broadband communications (C) Network-Powered Broadband systems to comply with Article 830. Communications Systems. Article 830 shall apply to network-powered As Safe or Safer. broadband communications systems. 800.2 Definitions. Exposed. A circuit that is in such a position that, in case of failure of supports and insulation, contact with another circuit may result. 800.3 Other Articles. (C) Spread of Fire or Products of Combustion. Section 300.21 shall apply. The accessible portion of abandoned communications cables shall not be permitted to remain. 800.24 Mechanical Execution of Work. 800.24 Mechanical Execution of Work. Page 334 of 361 Added cable ties as a securing means. 70 2008 851 Evaluation 2005 NEC Communications circuits and equipment shall be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be secured by straps, staples, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform with 300.4(D) and 300.11. 800.3 Other Articles. (C) Spread of Fire or Products of Combustion. Section 300.21 shall apply. The accessible portion of abandoned communications cables shall not be permitted to remain. 800.3 Other Articles. (C) Spread of Fire or Products of Combustion. Section 300.21 shall apply. The accessible portion of abandoned communications cables shall not be permitted to remain. 2008 NEC Communications circuits and equipment shall be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be secured by hardware, including straps, staples, cable ties, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform to 300.4(D) and 300.11. 800.25 Abandoned Cables. The accessible portion of abandoned communications cables shall be removed. Where cables are identified for future use with a tag, the tag shall be of sufficient durability to withstand the environment involved. 800.26 Spread of Fire or Products of Combustion. Installations of communications cables and communications raceways in hollow spaces, vertical shafts, and ventilation or air-handling ducts shall be made so that the possible spread of fire or products of combustion will not be substantially increased. Openings Page 335 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Relocated requirement on removing accessible portions of abandoned cables, and added requirement on the durability of tags used to identify cable(s) intended for future use. As Safe or Safer. Relocated requirement on the spread of fire or products of combustion with new text that is parallel with the provisions of 300.21. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety III. Protection around penetrations of communications cables and communications raceways through fireresistant-rated walls, partitions, floors, or ceilings shall be fire-stopped using approved methods to maintain the fire resistance rating. 800.48 Unlisted Cables Entering Buildings. Unlisted outside plant communications cables shall be permitted to be installed in locations as described in 800.154(C) where the length of the cable within the building, measured from its point of entrance, does not exceed 15 m (50 ft) and the cable enters the building from the outside and is terminated in an enclosure or on a listed primary protector. III. Protection 800.90 Protective Devices. 800.90 Protective Devices. (A) Application. (A) Application. Clarified that for the purposes of this section, exposure is subject to accidental contact with electric light or power conductors operating at over 300 volts to ground. (1) Fuseless Primary Protectors. (1) Fuseless Primary Protectors. As Safe or Safer. (b) Where insulated conductors in accordance with 800.50(A) are used to extend circuits to a building from a cable with an effectively grounded (b) Where insulated conductors in accordance with 800.50(A) are used to extend circuits to a building from a cable with an effectively grounded Page 336 of 361 Provided requirements for unlisted outside plant communications cables entering buildings. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC metallic sheath member(s) and where the conductors in the cable or cable stub, or the connections between the insulated conductors and the exposed plant, safely fuse on all currents greater than the current-carrying capacity of the primary protector, or the associated insulated conductors and of the primary protector grounding conductor metallic sheath member(s) and where the conductors in the cable or cable stub, or the connections between the insulated conductors and the plant exposed to accidental contact with electric light or power conductors operating at greater than 300 volts to ground, safely fuse on all currents greater than the current-carrying capacity of the primary protector, or the associated insulated conductors and of the primary protector grounding conductor (c) Where insulated conductors in accordance with 800.50(A) or 800.50(B) are used to extend circuits to a building from other than a cable with metallic sheath member(s), where (1) the primary protector is listed as being suitable for this purpose for application with circuits extending from other than a cable with metallic sheath members, and (2) the connections of the insulated conductors to the exposed plant or the conductors of the exposed plant safely fuse on all currents greater than the currentcarrying capacity of the primary protector, or associated insulated conductors and of the primary (c) Where insulated conductors in accordance with 800.50(A) or (B) are used to extend circuits to a building from other than a cable with metallic sheath member(s), where (1) the primary protector is listed as being suitable for this purpose for application with circuits extending from other than a cable with metallic sheath members, and (2) the connections of the insulated conductors to the plant exposed to accidental contact with electric light or power conductors operating at greater than 300 volts to ground or the conductors of the plant exposed to accidental contact with electric light or power conductors Page 337 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC protector grounding conductor. 2008 NEC Change Description and Impact to Worker Safety operating at greater than 300 volts to ground safely fuse on all currents greater than the current-carrying capacity of the primary protector, or associated insulated conductors and of the primary protector grounding conductor (d) Where insulated conductors in accordance with 800.50(A) are used to extend circuits aerially to a building from an unexposed buried or underground circuit (d) Where insulated conductors in accordance with 800.50(A) are used to extend circuits aerially to a building from a buried or underground circuit that is unexposed to accidental contact with electric light or power conductors operating at greater than 300 volts to ground 800.93 Cable Grounding. The metallic 800.93 Grounding or Interruption of sheath of communications cables Metallic Sheath Members of entering buildings shall be grounded as Communications Cables. close as practicable to the point of Communications cables entering the entrance or shall be interrupted as building or terminating on the outside close to the point of entrance as of the building shall comply with practicable by an insulating joint or 800.93(A) or (B). equivalent device. (A) Entering Buildings. In installations where the communications cable enters a building, the metallic sheath members of the cable shall be either grounded as specified in 800.100 or interrupted by an insulating joint or equivalent device. The grounding or Page 338 of 361 Clarified location of cable grounding connections for cable terminations inside and outside of buildings. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety interruption shall be as close as practicable to the point of entrance. IV. Grounding Methods (B) Terminating on the Outside of Buildings. In installations where the communications cable is terminated on the outside of the building, the metallic sheath members of the cable shall be either grounded as specified in 800.100 or interrupted by an insulating joint or equivalent device. The grounding or interruption shall be as close as practicable to the point of termination of the cable. IV. Grounding Methods 800.100 Cable and Primary Protector Grounding. 800.100 Cable and Primary Protector Grounding. (B) Electrode. The grounding conductor shall be connected in accordance with 800.100(B)(1) and (B)(2). (B) Electrode. The grounding conductor shall be connected in accordance with 800.100(B)(1), (B)(2), or (B)(3). (1) In Buildings or Structures with Grounding Means. To the nearest accessible location on the following: (1) The building or structure grounding electrode system as covered in 250.50 (2) The grounded interior metal water piping system, within 1.5 m (5 ft) from (1) In Buildings or Structures with an Intersystem Bonding Termination. If the building or structure served has an intersystem bonding termination, the grounding conductor shall be connected to the intersystem bonding termination. Page 339 of 361 Provided requirements for connecting the grounding conductor at buildings with an intersystem bonding termination, at buildings with only a grounding means, and at buildings without either item. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC its point of entrance to the building, as covered in 250.52 (3) The power service accessible means external to enclosures as covered in 250.94 (4) The metallic power service raceway (5) The service equipment enclosure (6) The grounding electrode conductor or the grounding electrode conductor metal enclosure (7) The grounding conductor or the grounding electrode of a building or structure disconnecting means that is grounded to an electrode as covered in 250.32 For purposes of this section, the mobile home service equipment or the mobile home disconnecting means, as described in 800.90(B), shall be considered accessible. (2) In Buildings or Structures Without Grounding Means. If the building or structure served has no grounding means, as described in 800.100(B)(1), the grounding conductor shall be connected to either of the following: (1) To any one of the individual electrodes described in 250.52(A)(1), (A)(2), (A)(3), or 2008 NEC (2) In Buildings or Structures with Grounding Means. If the building or structure served has no intersystem bonding termination, the grounding conductor shall be connected to the nearest accessible location on the following: (1) The building or structure grounding electrode system as covered in 250.50 (2) The grounded interior metal water piping system, within 1.5 m (5 ft) from its point of entrance to the building, as covered in 250.52 (3) The power service accessible means external to enclosures as covered in 250.94 (4) The metallic power service raceway (5) The service equipment enclosure (6) The grounding electrode conductor or the grounding electrode conductor metal enclosure (7) The grounding conductor or the grounding electrode of a building or structure disconnecting means that is grounded to an electrode as covered in 250.32 Page 340 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety (A)(4) (2) If the building or structure served has no grounding means, as described in 800.100(B)(1) or (B)(2)(1), to an effectively grounded metal structure or to a ground rod or pipe not less than 1.5 m (5 ft) in length and 12.7 mm (1⁄2 in.) in diameter, driven, where practicable, into permanently damp earth and separated from lightning conductors as covered in 800.53 and at least 1.8 m (6 ft) from electrodes of other systems. Steam or hot water pipes or air terminal conductors (lightning-rod conductors) shall not be employed as electrodes for protectors. 800.133 Installation of Communications Wires, Cables, and Equipment. A bonding device intended to provide a termination point for the grounding conductor (intersystem bonding) shall not interfere with the opening of an equipment enclosure. A bonding device shall be mounted on nonremovable parts. A bonding device shall not be mounted on a door or cover even if the door or cover is nonremovable. For purposes of this section, the mobile home service equipment or the mobile home disconnecting means, as described in 800.90(B), shall be considered accessible. 800.133 Installation of Communications Wires, Cables, and Equipment. Revised to include installations in cable trays. As Safe or Safer. (A) Separation from Other Conductors. (1) In Raceways, Boxes, and Cables. (a) Other Power-Limited Circuits. Communications cables shall be permitted in the same raceway or enclosure with cables of any of the following: (A) Separation from Other Conductors. (1) In Raceways, Cable Trays, Boxes, and Cables. (a) Other Power-Limited Circuits. Communications cables shall be permitted in the same raceway, cable tray, or enclosure with cables of any of the following: Page 341 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC 800.154 Applications of Listed Communications Wires and Cables and Communications Raceways. 800.154 Applications of Listed Communications Wires and Cables and Communications Raceways. (B) Riser. Cables installed in risers shall comply with 800.154(B)(1), (B)(2), or (B)(3). (1) Cables in Vertical Runs. Cables installed in vertical runs and penetrating more than one floor, or cables installed in vertical runs in a shaft, shall be Type CMR. Floor penetrations requiring Type CMR shall contain only cables suitable for riser or plenum use. Abandoned cables shall not be permitted to remain. Listed riser communications raceways shall be permitted to be installed in vertical riser runs in a shaft from floor to floor. Only Type CMR and CMP cables shall be permitted to be installed in these raceways. 800.154 Applications of Listed Communications Wires and Cables and Communications Raceways. (B) Riser. Cables installed in risers shall comply with 800.154(B)(1), (B)(2), or (B)(3). (1) Cables in Vertical Runs. Cables installed in vertical runs and penetrating more than one floor, or cables installed in vertical runs in a shaft, shall be Type CMR. Floor penetrations requiring Type CMR shall contain only cables suitable for riser or plenum use. Listed riser communications raceways and listed plenum communications raceways shall be permitted to be installed in vertical riser runs in a shaft from floor to floor. Only Type CMR and CMP cables shall be permitted to be installed in these raceways. 800.154 Applications of Listed Communications Wires and Cables and Communications Raceways. (E) Other Wiring Within Buildings. Cables installed in building locations other than the locations covered in 800.154(A) through 800.154(D) shall be in accordance with 800.154(E)(1) (C) Other Wiring Within Buildings. Cables installed in building locations other than the locations covered in 800.154(A), (B), (D), and (G) shall be in accordance with 800.154(C)(1) Page 342 of 361 Change Description and Impact to Worker Safety Added listed plenum communication raceways as acceptable for use in a riser. As Safe or Safer. Added listed riser communications raceways and listed plenum communications raceways as being acceptable for use in other areas within buildings in addition to plenums and risers. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC through (E)(6). through (C)(6). (1) General. Cables shall be Type CMG or Type CM. Listed communications general-purpose raceways shall be permitted. Only Types CMG, CM, CMR, or CMP cables shall be permitted to be installed in general-purpose communications raceways. (1) General. Cables shall be Type CMG or Type CM. Listed communications general-purpose raceways, listed riser communications raceways, and listed plenum communications raceways shall be permitted. Only Types CMG, CM, CMR, or CMP cables shall be permitted to be installed in these communications raceways. 800.154 Applications of Listed Communications Wires and Cables and Communications Raceways. 800.154 Applications of Listed Communications Wires and Cables and Communications Raceways. Change Description and Impact to Worker Safety Revised to permit communications raceways in cable trays. As Safe or Safer. (D) Cable Trays. Types CMP, CMR, CMG, and CM communications cables shall be permitted to be installed in cable trays. (D) Cable Trays. Types CMP, CMR, CMG, and CM communications cables shall be permitted to be installed in cable trays. Communications raceways, as described in 800.182, shall be permitted to be installed in cable trays. 800.179 Communications Wires and 800.179 Communications Wires and Cables. Communications wires and Cables. Communications wires and cables shall have a voltage rating of cables shall be listed in accordance not less than 300 volts and shall be with 800.179(A) through (I) and listed in accordance with 800.179(A) marked in accordance with Table through 800.179(J). Conductors in 800.179. Conductors in communications cables, other than in a communications cables, other than in a coaxial cable, shall be copper. coaxial cable, shall be copper. Page 343 of 361 Revised to include relocated communications cable marking requirements and to specify insulation rating of not less than 300 volts for individual conductors. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC Table 800.113 Cable Markings 2008 NEC Change Description and Impact to Worker Safety Communications wires and cables shall have a voltage rating of not less than 300 volts. The insulation for the individual conductors, other than the outer conductor of a coaxial cable, shall be rated for 300 volts minimum. The cable voltage rating shall not be marked on the cable or on the undercarpet communications wire. Communications wires and cables shall have a temperature rating of not less than 60°C. Exception: Voltage markings shall be permitted where the cable has multiple listings and voltage marking is required for one or more of the listings. Table 800.179 Cable Markings Article 810 Radio and Television Equipment 810.21 Grounding Conductors — 810.21 Grounding Conductors — Receiving Stations. Grounding Receiving Stations. Grounding conductors shall comply with 810.21(A) conductors shall comply with 810.21(A) through 810.21(K). through (K). (F) Electrode. The grounding conductor shall be connected as follows: (F) Electrode. The grounding conductor shall be connected as required in (F)(1) through (F)(3). Page 344 of 361 Provided requirements for connecting the grounding conductor at buildings with an intersystem bonding termination, at buildings with only a grounding means, and at buildings without either item. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC (1) To the nearest accessible location on the following: a. The building or structure grounding electrode system as covered in 250.50 b. The grounded interior metal water piping systems, within 1.52 m (5 ft) from its point of entrance to the building, as covered in 250.52 c. The power service accessible means external to the building, as covered in 250.94 d. The metallic power service raceway e. The service equipment enclosure, or f. The grounding electrode conductor or the grounding electrode conductor metal enclosures; or (2) If the building or structure served has no grounding means, as described in 810.21(F)(1), to any one of the individual electrodes described in 250.52; or (3) If the building or structure served has no grounding means, as described 2008 NEC (1) In Buildings or Structures with an Intersystem Bonding Termination. If the building or structure served has an intersystem bonding termination, the grounding conductor shall be connected to the intersystem bonding termination. (2) In Buildings or Structures with Grounding Means. If the building or structure served has no intersystem bonding termination, the grounding conductor shall be connected to the nearest accessible location on the following: (1) The building or structure grounding electrode system as covered in 250.50 (2) The grounded interior metal water piping systems, within 1.52 m (5 ft) from its point of entrance to the building, as covered in 250.52 (3) The power service accessible means external to the building, as covered in 250.94 (4) The metallic power service raceway (5) The service equipment Page 345 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC in 810.21(F)(1) or (F)(2), to an effectively grounded metal structure or to any of the individual electrodes described in 250.52 2008 NEC enclosure, or (6) The grounding electrode conductor or the grounding electrode conductor metal enclosures A bonding device intended to provide a termination point for the grounding conductor (intersystem bonding) shall not interfere with the opening of an equipment enclosure. A bonding device shall be mounted on nonremovable parts. A bonding device shall not be mounted on a door or cover even if the door or cover is nonremovable. (3) In Buildings or Structures Without Intersystem Bonding Termination or Grounding Means. If the building or structure served has no intersystem bonding termination or grounding means, as described in 810.21(F)(1). (1) To any one of the individual electrodes described in 250.52; or (2) If the building or structure served has no grounding means, as described in 810.21(F)(1) or (F)(2), to an effectively grounded metal structure. Page 346 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC 810.71 General. Transmitters shall comply with 810.71(A) through (C). 810.71 General. Transmitters shall comply with 810.71(A) through (C). (B) Grounding of Controls. All external metal handles and controls accessible to the operating personnel shall be effectively grounded. (B) Grounding of Controls. All external metal handles and controls accessible to the operating personnel shall be effectively connected to an equipment grounding conductor if the transmitter is powered by the premises wiring system or grounded with a conductor in accordance with 810.21. Article 820 Community Antenna Television and Radio Distribution Systems Exposed (to Accidental Contact). A circuit in such a position that, in case of failure of supports and or insulation, contact with another circuit may result. Exposed. An exposed cable is one that is in such a position that, in case of failure of supports and insulation, contact with another circuit could result. 820.15 Energy Limitations. Coaxial cable shall be permitted to deliver lowenergy power to equipment that is directly associated with the radio frequency distribution system if the voltage is not over 60 volts and if the current supply is from a transformer or other device that has energy-limiting characteristics. 820.15 Power Limitations. Coaxial cable shall be permitted to deliver power to equipment that is directly associated with the radio frequency distribution system if the voltage is not over 60 volts and if the current is supplied by a transformer or other device that has power-limiting characteristics. Power shall be blocked from premises devices on the network that are not intended to be powered via the coaxial Page 347 of 361 Change Description and Impact to Worker Safety Provided specific means for grounding external metal handles and controls of transmitters. As Safe or Safer. Clarified meaning of the term as used in Article 820 requirements. As Safe or Safer. Added requirement for blocking power delivered through coaxial cable to premises devices not intended for network supply. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 820.24 Mechanical Execution of Work. Community antenna television and radio distribution systems shall be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceiling and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be secured by straps, staples, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform with 300.4(D) and 300.11. 820.3 Other Articles. Circuits and equipment shall comply with 820.3(A) through 820.3(G). (A) Spread of Fire or Products of Combustion. Section 300.21 shall apply. The accessible portion of abandoned coaxial cables shall be removed. 820.3 Other Articles. Circuits and equipment shall comply with 820.3(A) through 820.3(G). (A) Spread of Fire or Products of 2008 NEC cable. 820.24 Mechanical Execution of Work. Community television and radio distribution systems shall be installed in a neat and workmanlike manner. Coaxial cables installed exposed on the surface of ceiling and sidewalls shall be supported by the building structure in such a manner that the cables will not be damaged by normal building use. Such cables shall be secured by hardware including straps, staples, cable ties, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform to 300.4(D) and 300.11. 820.25 Abandoned Cables. The accessible portion of abandoned coaxial cables shall be removed. Where cables are identified for future use with a tag, the tag shall be of sufficient durability to withstand the environment involved. 820.26 Spread of Fire or Products of Combustion. Installations of coaxial cables and CATV raceways in hollow spaces, vertical shafts, and ventilation or air-handling ducts shall be made so Page 348 of 361 Change Description and Impact to Worker Safety Added cable ties as a securing means. As Safe or Safer. Relocated requirements on removing accessible portions of abandoned cables, and added requirement on the durability of tags used to identify cable(s) intended for future use. As Safe or Safer. Relocated requirement on the spread of fire or products of combustion with new text that is parallel with the provisions of 300.21. 70 2008 851 Evaluation 2005 NEC Combustion. Section 300.21 shall apply. The accessible portion of abandoned coaxial cables shall be removed. III. Protection 820.93 Grounding of Outer Conductive Shield of a Coaxial Cable. The outer conductive shield of the coaxial cable shall be grounded at the building premises as close to the point of cable entrance or attachment as practicable. For purposes of this section, grounding located at mobile home service equipment located in sight from, and not more than 9.0 m (30 ft) from, the exterior wall of the mobile home it 2008 NEC that the possible spread of fire or products of combustion will not be substantially increased. Openings around penetrations of coaxial cables and CATV raceways through fireresistant-rated walls, partitions, floors, or ceilings shall be firestopped using approved methods to maintain the fire resistance rating. 820.48 Unlisted Cables Entering Buildings. Unlisted outside plant coaxial cables shall be permitted to be installed in locations as described in 820.154(D), where the length of the cable within the building, measured from its point of entrance, does not exceed 15 m (50 ft) and the cable enters the building from the outside and is terminated at a grounding block. III. Protection 820.93 Grounding of the Outer Conductive Shield of Coaxial Cables. Coaxial cables entering buildings or attached to buildings shall comply with 820.93(A) or (B). Where the outer conductive shield of a coaxial cable is grounded, no other protective devices shall be required. For purposes of this section, grounding located at mobile home service equipment located within 9.0 m (30 ft) of the exterior wall of the Page 349 of 361 Change Description and Impact to Worker Safety As Safe or Safer. Provided requirements for unlisted outside plant coaxial cables entering buildings. As Safe or Safer. Clarified location of cable shield grounding for cable terminations inside and outside of buildings and to specify the location of primary protectors. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 2008 NEC serves, or at a mobile home disconnecting means grounded in accordance with 250.32 and located in sight from and not more than 9.0 m (30 ft) from the exterior wall of the mobile home it serves, shall be considered to meet the requirements of this section. mobile home it serves, or at a mobile home disconnecting means grounded in accordance with 250.32 and located within 9.0 m (30 ft) of the exterior wall of the mobile home it serves, shall be considered to meet the requirements of this section. (A) Shield Grounding. Where the outer conductive shield of a coaxial cable is grounded, no other protective devices shall be required. (A) Entering Buildings. In installations where the coaxial cable enters the building, the outer conductive shield shall be grounded in accordance with 820.100. The grounding shall be as close as practicable to the point of entrance. (B) Shield Protection Devices. Grounding of a coaxial drop cable shield by means of a protective device that does not interrupt the grounding system within the premises shall be permitted. (B) Terminating Outside of the Building. In installations where the coaxial cable is terminated outside of the building, the outer conductive shield shall be grounded in accordance with 820.100. The grounding shall be as close as practicable to the point of attachment or termination. (C) Location. Where installed, a listed primary protector shall be applied on each community antenna and radio distribution (CATV) cable external to the premises. The listed primary protector shall be located as close as Page 350 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety practicable to the entrance point of the cable on either side or integral to the ground block. (D) Hazardous (Classified) Locations. Where a primary protector or equipment providing the primary protection function is used, it shall not be located in any hazardous (classified) location as defined in 500.5 or in the vicinity of easily ignitible material. IV. Grounding Methods 820.100 Cable Grounding. Exception: As permitted in 501.150, 502.150, and 503.150. IV. Grounding Methods 820.100 Cable Grounding. (B) Electrode. The grounding conductor shall be connected in accordance with 820.100(B)(1) and (B)(2). (B) Electrode. The grounding conductor shall be connected in accordance with 820.100(B)(1), (B)(2), or (B)(3). Provided requirements for connecting the grounding conductor at buildings with an intersystem bonding termination, at buildings with only a grounding means, and at buildings without either item. As Safe or Safer. (1) In Buildings or Structures with Grounding Means. To the nearest accessible location on the following: (1) The building or structure grounding electrode system as covered in 250.50 (2) The grounded interior metal (1) In Buildings or Structures with an Intersystem Bonding Termination. If the building or structure served has an intersystem bonding termination, the grounding conductor shall be connected to the intersystem bonding termination. Page 351 of 361 70 2008 851 Evaluation 2005 NEC water piping system, within 1.52 m (5 ft) from its point of entrance to the building, as covered in 250.52 (3) The power service accessible means external to enclosures as covered in 250.94 (4) The metallic power service raceway (5) The service equipment enclosure (6) The grounding electrode conductor or the grounding electrode conductor metal enclosure, or (7) The grounding conductor or the grounding electrode of a building or structure disconnecting means that is grounded to an electrode as covered in 250.32 (2) In Buildings or Structures Without Grounding Means. If the building or structure served has no grounding means, as described in 820.100(B)(1): (1) To any one of the individual electrodes described in 250.52(A)(1), (A)(2), (A)(3), (A)(4); or, (2) If the building or structure served has no grounding means, as 2008 NEC (2) In Buildings or Structures with Grounding Means. If the building or structure served has no intersystem bonding termination, the grounding conductor shall be connected to the nearest accessible location on the following: (1) The building or structure grounding electrode system as covered in 250.50 (2) The grounded interior metal water piping system, within 1.52 m (5 ft) from its point of entrance to the building, as covered in 250.52 (3) The power service accessible means external to enclosures as covered in 250.94 (4) The metallic power service raceway (5) The service equipment enclosure (6) The grounding electrode conductor or the grounding electrode conductor metal enclosure, or (7) The grounding conductor or the grounding electrode of a building or structure disconnecting means that is connected to an electrode as covered in 250.32 Page 352 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC described in 820.100(B)(1) or (B)(2)(1), to an effectively grounded metal structure or to any one of the individual electrodes described in 250.52(A)(5), (A)(6), and (A)(7). 2008 NEC A bonding device intended to provide a termination point for the grounding conductor (intersystem bonding) shall not interfere with the opening of an equipment enclosure. A bonding device shall be mounted on nonremovable parts. A bonding device shall not be mounted on a door or cover even if the door or cover is nonremovable. For purposes of this section, the mobile home service equipment or the mobile home disconnecting means, as described in 820.93, shall be considered accessible. (3) In Buildings or Structures Without Intersystem Bonding Termination or Grounding Means. If the building or structure served has no intersystem bonding termination or grounding means, as described in 820.100(B)(2), the grounding conductor shall be connected to either of the following: (1) To any one of the individual electrodes described in 250.52(A)(1), (A)(2), (A)(3), (A)(4); or, Page 353 of 361 Change Description and Impact to Worker Safety 70 2008 851 Evaluation 2005 NEC 820.100 Cable Grounding. 820.133 Installation of Cables and Equipment. Beyond the point of grounding, as defined in 820.93, the cable installation shall comply with 820.133(A) through 820.133(C). (A) Separation from Other Conductors. (1) In Raceways and Boxes. (1) Other Circuits. Coaxial cables shall be permitted in the same raceway or enclosure with jacketed cables of any of the following: 820.154 Applications of Listed CATV Cables and CATV Raceways. 2008 NEC (2) If the building or structure served has no intersystem bonding termination or grounding means, as described in 820.100(B)(2) or (B)(3)(1), to any one of the individual electrodes described in 250.52(A)(5), (A)(7), and (A)(8). 820.100 Cable Grounding. (E) Shield Protection Devices. Grounding of a coaxial drop cable shield by means of a protective device that does not interrupt the grounding system within the premises shall be permitted. 820.133 Installation of Coaxial Cables and Equipment. Beyond the point of grounding, as defined in 820.93, the coaxial cable installation shall comply with 820.133(A) and (B). (A) Separation from Other Conductors. (1) In Raceways, Cable Trays, and Boxes. (a) Other Circuits. Coaxial cables shall be permitted in the same raceway, cable tray, or enclosure with jacketed cables of any of the following: 820.154 Applications of Listed CATV Cables and CATV Raceways. Page 354 of 361 Change Description and Impact to Worker Safety Added provision to permit use of a shield protection device for grounding shield of a coaxial cable. As Safe or Safer. Revised to include installations in cable trays. As Safe or Safer. Added listed riser CATV raceways and listed plenum CATV raceways as 70 2008 851 Evaluation 2005 NEC (D) Other Wiring Within Buildings. Cables installed in building locations other than the locations covered in 820.154(A) and 820.154(B) shall be with any of the requirements in 820.154(D)(1) through (D)(5). Abandoned cables in hollow spaces shall not be permitted to remain. (1) General. Type CATV shall be permitted. Listed CATV generalpurpose raceways shall be permitted. Only Types CATV, CATVX, CATVR, or CATVP cables shall be permitted to be installed in general-purpose communications raceways. VI. Listing Requirements 820.179 Coaxial Cables. Cables shall be listed in accordance with 820.179(A) through 820.179(D). 2008 NEC (C) Other Wiring Within Buildings. Cables installed in building locations other than the locations covered in 820.154(A) and (B) shall be in accordance with any of the requirements in 820.154(C)(1) through (C)(5). (1) General. Type CATV shall be permitted. Listed CATV generalpurpose raceways, listed riser CATV raceways, and listed plenum CATV raceways shall be permitted. Only Types CATV, CATVX, CATVR, or CATVP cables shall be permitted to be installed in these CATV raceways. VI. Listing Requirements 820.179 Coaxial Cables. Cables shall be listed in accordance with 820.179(A) through (D) and marked in accordance with Table 820.179. The cable voltage rating shall not be marked on the cable. Exception: Voltage markings shall be permitted where the cable has multiple listings and voltage marking is required for one or more of the listings. Article 830 Page 355 of 361 Change Description and Impact to Worker Safety acceptable for use in other areas within buildings in addition to plenums and risers. As Safe or Safer. Revised to include relocated marking requirement for coaxial cables. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC 830.15 Power Limitations. Networkpowered broadband communications systems shall be classified as having low or medium power sources as defined in Table 830.15. 830.24 Mechanical Execution of Work. Network-powered broadband communications circuits and equipment shall be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be secured by straps, staples, hangers, or similar fittings designed and installed so as 2008 NEC Network-Powered Broadband Communications Systems 830.15 Power Limitations. Networkpowered broadband communications systems shall be classified as having low or medium-power sources as specified in 830.15(1) or (2). (1) Sources shall be classified as defined in Table 830.15. (2) Direct-current power sources exceeding 150 volts to ground, but no more than 200 volts to ground, with the current to ground limited to 10 mA dc, that meet the current and power limitation for medium-power sources in Table 830.15 shall be classified as medium-power sources. 830.24 Mechanical Execution of Work. Network-powered broadband communications circuits and equipment shall be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be secured by hardware including straps, staples, cable ties, hangers, or similar fittings Page 356 of 361 Change Description and Impact to Worker Safety Provided alternative for equipment that meets the requirements of the table but are DC voltages. As Safe or Safer. Added cable ties as a securing means. As Safe or Safer. 70 2008 851 Evaluation 2005 NEC not to damage the cable. The installation shall also conform with 300.4(D) and 300.11. 830.3 Other Articles. Circuits and equipment shall comply with 830.3(A) through 830.3(E). (A) Spread of Fire or Products of Combustion. Section 300.21 shall apply. The accessible portion of abandoned network-powered broadband communications cables shall be removed. 830.3 Other Articles. Circuits and equipment shall comply with 830.3(A) through 830.3(E). (A) Spread of Fire or Products of Combustion. Section 300.21 shall apply. The accessible portion of abandoned network-powered broadband communications cables shall be removed. 830.93 Grounding or Interruption of Metallic Members of Network-Powered Broadband Communications Cables. 2008 NEC designed and installed so as not to damage the cable. The installation shall also conform to 300.4(D) and 300.11. 830.25 Abandoned Cables. The accessible portion of abandoned network-powered broadband cables shall be removed. Where cables are identified for future use with a tag, the tag shall be of sufficient durability to withstand the environment involved. 830.26 Spread of Fire or Products of Combustion. Installations of networkpowered broadband cables in hollow spaces, vertical shafts, and ventilation or air-handling ducts shall be made so that the possible spread of fire or products of combustion will not be substantially increased. Openings around penetrations of networkpowered broadband cables through fire-resistant-rated walls, partitions, floors, or ceilings shall be firestopped using approved methods to maintain the fire resistance rating. 830.93 Grounding or Interruption of Metallic Members of Network-Powered Broadband Communications Cables. Page 357 of 361 Change Description and Impact to Worker Safety Relocated requirement on removing accessible portions of abandoned cables, and added requirement on the durability of tags used to identify cable(s) intended for future use. As Safe or Safer. Relocated requirement on the spread of fire or products of combustion with new text that is parallel with the provisions of 300.21. As Safe or Safer. Clarified location of cable shield grounding for cable terminations inside and outside of buildings. 70 2008 851 Evaluation 2005 NEC The shields of network-powered broadband communications cables used for communications or powering shall be grounded at the building as close as practicable to the point of entrance or attachment of the NIU. Metallic cable members not used for communications or powering shall be grounded or interrupted by an insulating joint or equivalent device as close as practicable to the point of entrance or attachment of the NIU. For purposes of this section, grounding or interruption of network-powered broadband communications cable metallic members installed at mobile home service equipment located in sight from and no more than 9.0 m (30 ft) from the exterior wall of the mobile home it serves, or at a mobile home disconnecting means grounded in accordance with 250.32 and located in sight from and not more than 9.0 m (30 ft) from the exterior wall of the mobile home it serves, shall be considered to meet the requirements of this section. 2008 NEC Change Description and Impact to Worker Safety Network-powered communications cables entering buildings or attaching As Safe or Safer. to buildings shall comply with 830.93(A) or (B). For purposes of this section, grounding located at mobile home service equipment located within 9.0 m (30 ft) of the exterior wall of the mobile home it serves, or at a mobile home disconnecting means grounded in accordance with 250.32 and located within 9.0 m (30 ft) of the exterior wall of the mobile home it serves, shall be considered to meet the requirements of this section. (A) Entering Buildings. In installations where the network-powered communications cable enters the building, the shield shall be grounded in accordance with 830.100 and metallic members of the cable not used for communications or powering shall be grounded in accordance with 830.100, or interrupted by an insulating joint or equivalent device. The grounding or interruption shall be as close as practicable to the point of entrance. (B) Terminating Outside of the Building. In installations where the Page 358 of 361 70 2008 851 Evaluation 2005 NEC IV. Grounding Methods 830.100 Cable, Network Interface Unit, and Primary Protector Grounding. (B) Electrode. The grounding conductor shall be connected as follows. (1) In Buildings or Structures with Grounding Means. To the nearest accessible location on the following: (2) In Buildings or Structures Without Grounding Means. If the building or structure served has no grounding means, as described in (B)(1), the grounding conductor shall be connected to either of the following: 2008 NEC Change Description and Impact to Worker Safety network-powered communications cable is terminated outside of the building, the shield shall be grounded in accordance with 830.100, and metallic members of the cable not used for communications or powering shall be grounded in accordance with 830.100 or interrupted by an insulating joint or equivalent device. The grounding or interruption shall be as close as practicable to the point of attachment of the NIU. IV. Grounding Methods Provided requirements for connecting the grounding conductor at buildings 830.100 Cable, Network Interface Unit, with an intersystem bonding and Primary Protector Grounding. termination, at buildings with only a grounding means, and at buildings (B) Electrode. The grounding without either item. conductor shall be connected in accordance with 830.100(B)(1), (B)(2), As Safe or Safer. or (B)(3). (1) In Buildings or Structures with an Intersystem Bonding Termination. If the building or structure served has an intersystem bonding termination, the grounding conductor shall be connected to the intersystem bonding termination. (2) In Buildings or Structures with Grounding Means. If the building or Page 359 of 361 70 2008 851 Evaluation 2005 NEC 2008 NEC Change Description and Impact to Worker Safety structure served has no intersystem bonding termination, the grounding conductor shall be connected to the nearest accessible location on the following: V. Wiring Methods Within Buildings 830.133 Installation of Network- (3) In Buildings or Structures Without Intersystem Bonding Termination or Grounding Means. If the building or structure served has no intersystem bonding termination or grounding means, as described in 830.100(B)(2), the grounding conductor shall be connected to either of the following: V. Installation Methods Within Buildings 830.110 Raceways for Low- and Medium-Power Network-Powered Broadband Communications Cables. Where low- and medium-power network-powered broadband communications cables are installed in a raceway, the raceway shall be of a type permitted in Chapter 3 and installed in accordance with Chapter 3. Exception: Conduit fill restrictions shall not apply to low-power networkpowered broadband communications cables. 830.133 Installation of Network- Page 360 of 361 Added to provide reference to Chapter 3 requirements for raceway installations with exception on conduit fill for low-power broadband systems. As Safe or Safer. Revised to include installations in 70 2008 851 Evaluation 2005 NEC 2008 NEC Powered Broadband Communications Cables and Equipment. Cable and equipment installations within buildings shall comply with 830.133(A) through 830.133(D), as applicable. Powered Broadband Communications Cables and Equipment. Cable and equipment installations within buildings shall comply with 830.133(A) through (C), as applicable. (A) Separation of Conductors. (1) In Raceways and Enclosures. 830.133 Installation of NetworkPowered Broadband Communications Cables and Equipment. (A) Separation of Conductors. (1) In Raceways, Cable Trays, and Enclosures. 830.154 Applications of Low-Power Network-Powered Broadband Communications System Cables. (C) Cable Substitutions. The substitutions for network-powered broadband cables listed in Table 830.133 shall be permitted. All cables in Table 830.133, other than networkpowered broadband cables, shall be coaxial cables. (D) Cable Substitutions. The substitutions for network-powered broadband cables listed in Table 830.154 shall be permitted. All cables in Table 830.154, other than networkpowered broadband cables, shall be coaxial cables. Change Description and Impact to Worker Safety cable trays. As Safe or Safer. Relocated provisions for cable substitutions. As Safe or Safer. Page 361 of 361