APPLIC ATION NOTE APPLIC ATION NOTE AE 500TX (Formerly known as PVP500kW) Integrated DC circuit breaker based subcombiner option A P P L I C AT I O N N O T E Introduction CONTENTS •Introduction Page 1 •Advantages of Circuit Breaker Based Subarray Combiners Page 1 •Available Circuit Breaker Based Subarray Combiner Options Page 2 •DC Breaker Applications Information Page 3 •Circuit Breaker Terminal Data Page 3 •DC Circuit Breaker Subcombiner Components Page 3 •Conclusion Page 3 AE Solar Energy • 20720 Brinson Blvd • Bend, OR 97701 U.S.A. www.advanced-energy.com/solarenergy 877.312.3832 • sales.support@aei.com • invertersupport@aei.com Please see www.advanced-energy.com for worldwide contact information. Advanced Energy’s new AE 500TX inver ter features an integrated DC circuit breaker based subcombiner option which features DC breakers in place of the fused subcombiner options available on other inver ters in AE’s TX product line. The intent of this application note is to discuss the advantages of using DC circuit breakers with respect to the National Electrical Code (NEC) requirements, provide an overview of the DC circuit breaker configurations available from AE and review the basic proper ties of the DC circuit breakers. Advantages of Circuit Breaker Based Subarray Combiners Every revision of the National Electrical Code (NEC) brings changes intended to create safer electrical installations. The rules per taining to photovoltaic installations have been changing rapidly as the technology evolves and sees more widespread adoption. Advanced Energy developed a circuit breaker based subcombiner solution to specifically address 2011 NEC section 690.16(B), which reads as follows: 690.16(B) Fuse Servicing. Disconnecting means shall be installed on PV output circuits where overcurrent devices (fuses) must be serviced that cannot be isolated from energized circuits. The disconnecting means shall be within sight of, and accessible to, the location of the fuse or integral with fuse holder and shall comply with 690.17. Where the disconnecting means are located more than 1.8m (6 ft) from the over current device, a directory showing the location of each disconnect shall be installed at the overcurrent device location. Previous editions of the NEC required disconnects for fuse maintenance as well. These were contained in 690.16 in the 2008 NEC, which became 690.16(A) in the 2011 NEC. However, the 2008 NEC does not specify a location for the required disconnects. Under the 2008 NEC, it would be permissible to have a DC Fused fused subarray combiner Disconnect AC Subarray located at the inver ter Disconnect Combiner Combiner Combiner Box Box at ground level and the disconnecting means in the roof mounted combiner boxes. This is shown in Figure 1. Combiner Box Combiner Box © Advanced Energy Industries, Inc. 2012 All rights reserved. Printed in U.S.A. Figure 1 - Installation compliant with 2008 NEC ENG-AE500TXBreakers-270-01 12/12 Advanced Energy is a registered U.S. trademark of Advanced Energy Industries, Inc. AE Solar Energy is a US based company. APPLIC ATION NOTE APPLIC ATION NOTE Combiner Box Combiner Box On DC Disconnect On DC Disconnect Off Off Fused Subarray Combiner DC Disconnect AC Disconnect It is impor tant to note that since the circuit breakers serve as the load break rated disconnecting means, a single main DC disconnect is not provided. If the circuit breaker based subarray combiner is not installed, an external DC disconnect will be required. On DC Disconnect Off Combiner Box On DC Disconnect Combiner Box Additional Disconnects required per 2011 NEC 690.16(B) Available Circuit Breaker Based Subarray Combiner Options If the roof were not easily accessible, maintenance personnel might choose to work on live fuses rather than locating and shutting off the disconnects. This scenario is especially likely if roof access requires a ladder, a lift, or advanced notice to the proper ty owner. Section 690.16(B) was added to the 2011 National Electrical Code to eliminate this potential safety problem. If a designer wants to use subcombiner fuses, then 690.16(B) requires the addition of disconnects within sight of a fused subarray combiner as shown in Figure 2. The definition of within sight gives a maximum distance of 50’. Also, the final sentence of 690.16(B) requires a directory be installed if the disconnects are more than 6’ from the fuses they isolate. This does not remove the requirement to install these disconnects within sight of the fusing if a directory is installed. Combiner Box Combiner Box Circuit Breaker Based Subcombiner AC Disconnect Combiner Box Combiner Box Figure 3 - Circuit breaker based subarray combiner In response to this change in the National Electrical Code, Advanced Energy is offering circuit breaker based inver ter integrated subarray combiners on its AE 500TX inver ter. Moving from the fuse based inver ter integrated subarray combiners to circuit breaker based subarray combiners eliminates the need for additional, external disconnecting means. Because there are no fuses, there is no need for fuse servicing disconnects. This is shown schematically in Figure 3. This change maintains the advantage of having an inver ter integrated subarray combiner while complying with the latest code revision. In addition, Page 2 DC Breaker Applications Information Circuit Breaker Thermal Derating Advanced Energy offers a number of options for inver ter integrated circuit breaker based subcombiners on the AE 500TX. There are two frame sizes available, 225 A and 400 A. Different factory installed trip units give a selection of trip settings within each frame size. The mix of trip settings can be specified based on the array design. The available options are listed in the table below. Option Monitoring Available Trip Units 8 x 400 A Available 400 A, 350 A, 300 A, 250 A, 200 A, 150 A, 100 A 16 x 225 A Available 225 A, 200 A, 175 A, 150 A, 125 A, 100 A, 80 A Not Available 225 A, 200 A, 175 A, 150 A, 125 A, 100 A, 80 A 20 x 225 A Note: The sum of all overcurrent protection must be 3500 A or less. When a mix of breaker trip settings is used, the breakers will be installed with the highest ampacity setting at the top of the subarray combiner and the lowest value at the bottom. If fewer than the standard number of breakers are specified, the bottom position(s) will be left vacant. There will be empty spaces at the bottom of the enclosure. Breaker positions and settings are not field configurable. The circuit breaker based subcombiner is optional for the AE 500TX. It is not necessary to order the inver ter with an integrated subcombiner. However, the breakers serve as both overcurrent protection and disconnecting means. If a subcombiner is not included with the inver ter, external DC disconnects must be installed. DC Circuit Breaker Subcombiner Components The DC circuit breakers used in Advanced Energy’s integrated subcombiner are not rated for continuous operation at 100% duty. Therefore, when selecting the appropriate circuit breaker, the 125% safety factor given in NEC 690.8(B)(1) must be used. This is in addition to the 125% safety factor given for high irradiance required by NEC 690.8(A)(1). Off Figure 2 - Disconnects added per 2011 NEC the DC circuit breakers serve as load break rated disconnect switches. They can be used to disconnect DC power from the inver ter for routine maintenance or for an emergency response. After installation, the terminals are covered by a dead front cover, leaving only the operating handles accessible. Circuit Breaker Thermal Derating ASHRAE 2% Temperature Breaker Derating 39 °C or less 1.00 40 °C to 44 °C 0.96 45 °C to 49 °C 0.92 50 °C or greater 0.88 In addition, consideration must be given to the inver ter’s thermal environment. At elevated temperature circuit breakers will trip at a lower current level. To prevent nuisance tripping, circuit breakers should be derated based on the expected ambient temperature. For inver ters installed outdoors, the use of American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2% dry bulb temperature data for the hottest month is recommended. The breakers should then be derated based on the table on the values in the table above. The thermal derating is multiplied by the nominal trip setting to give the effective breaker ampacity. For example, a 200 A circuit breaker installed in Barstow, CA with a July ASHRAE 2% temperature of 43 °C, would have an effective ampacity of 200 A x 0.96 = 192 A. Circuit Breaker Terminal Data Breakers Breakers DC + bus bus bar DC+ bar 400 A (frame) circuit breaker Dead front removed for access Bus bar for conductor landing Deadfront front Dead Subcombiner monitoring I/O unit Figure 4 - Subcombiner components - 8 x 400 A option Conclusion The AE 500TX continues Advanced Energy’s tradition of innovative products and solutions for PV applications. By introducing a DC circuit breaker based subarray combiner option, AE provides a path for simple, low cost compliance with the 2011 National Electrical Code. The allowable wire range and terminal temperature rating vary depending on the selected subcombiner option. The table below shows the terminal characteristics for all options. Option Allowable Wire Size Conductor Material Terminal Temp Rating 8 x 400 A Direct to Bus bar Cu/Al 90 °C 20 x 225 A 4-4/0 AWG Cu/Al 75 °C Direct to Bus bar Cu/Al 90 °C None The 8 x 400 A and 16 x 225 A breaker options simply present the installer with a shor t piece of bus bar containing a 3/8” hole for landing conductors. The installer provides an appropriate crimp on a mechanical lug based on the desired wire size. This allows the installer to use any reasonable conductor size. If parallel conductors are required, it is possible to mount one on each side (front/back) of the bus bar. Page 3