GE Consumer & Industrial Electrical Distribution ™ Record Plus FB 100 Current Limiting Molded Case Circuit Breakers Catalog/Selection Guide imagination at work FB 100 Amp Frame Overview u u Breaker Frame Rating v Product Description w Standards & Markings x Interrupting Ratings y Lug Data & Torque Info z Catalog Number { Push to Trip v w x y z FB Breaker Markings UL file E-11592 { HACR HID NAVAL Cu/Al 60/75°C Current Limiting 15 to 100A 15 to 50A 15 to 100A 15 to 100A 15 to 100A 1, 2, 3 Pole 1, 2, 3 Pole 1, 2, 3 Pole 1, 2, 3 Pole 1, 2, 3 Pole FB breakers are NOT marked LINE/LOAD and can be reverse fed. Interrupting Ratings Ampere Maximum Rating Voltage Type Poles 240 35 65 65 65 150 150 100 200 200 100 200 200 1 2 3 1 2 3 1 2 3 1 2 3 FBV FBN 600Y/347 15-100 Vac FBH FBL UL Listed Interrupting Rating rms Symmetrical Amperes (Thousands) AC Voltage 277 347 480 600/347 35 22 35 22 35 22 65 25 65 25 65 25 100 35 100 35 100 35 100 42 150 42 150 42 Dimensions "D" "D" "G1" "A" "E" "B" "F" "C" Dimensions (inches) A B C D E F G1 G2 H "G2" "G2" "G2" "H" "E" "D" "F" "E" "G1" "G1" "H" "H" 1 3.88 3.28 1.06 1.36 NA NA 5.11 5.01 6.45 Poles 2 3.88 3.28 1.06 2.74 0.69 1.38 5.11 5.01 6.45 3 3.88 3.28 1.06 4.11 1.38 1.38 5.11 5.01 6.45 Catalog Number Structure F Frame Rating (Amperes) Family F = Record B = 100 Plus Interruption Capacity V = 35kA N = 65kA H = 100 kA L = 150kA B N 3 6 TE 050 R Voltage Rated Rating Type Current (A)1 Connection 6 = 600/347 TE = Fixed Thermal 015 – 100 R = Standard, No Lugs Magnetic R2 = Load Lugs Only RV = A-Series AD Plus Lighting Panel (Includes load lugs 1Available ampere ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100. and panel connections) Poles 1 = 1 pole 2 = 2 poles 3 = 3 poles Internal Accessories Refer to Next Page for Mounting Locations & Limitations Shunt Trip & Undervoltage Release Shunt Trip Vac 24 48 110 - 130 120 220 - 240 277 400 - 480 Vdc 12 24 48 110 - 125 250 - Undervoltage Release Catalog Numbers FASHTBW n/a FASHTDW FAUVRDW FASHTFW FAUVRFW FASHTJW FAUVRJW FASHTKW FAUVRKW FASHTNW FAUVRNW FASHT7W FAUVR7W FASHTUW FAUVRUW UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads (#18 AWG). Shunt trip wire leads are black and UVR wire leads are blue. Bell Alarm & Auxiliary Switches Bell Alarm Switches FABAM10W FABAM01W FABAM11W FABAM11GW Auxiliary Switches Catalog Numbers FAS10LW FAS01LW FAS11LW FAS11LGW FAS10RW FAS01RW FAS11RW FAS11RGW Contact Configuration Contacts 1 NO (Form A) 1 NC (Form B) 1 NO + 1 NC (Form C) 1 NO + 1 NC (Form C) Standard Standard Standard Gold plated Contact Rating Wire Leads 5A @ 277Vac 0.3A @ 125Vdc #16 AWG 1A @ 30Vac/dc #18 AWG UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads. Reference instruction sheet DEH-40324 for wire lead colors. External Accessories Padlock Devices Suitable for use on 1, 2 and 3 pole FB breakers Description Catalog Number Padlock, Fixed Toggle FB1PF Padlock, EUSERC Toggle FB1PE Lugs Description Lug (15 to 20A) Lug (25 to 60A) Lug (70 to 100A) Catalog Number Catalog Number Wire Range (60/75° C (Individual Lugs) (3-Lug Kits) Insulated Conductor) FCAL12 FCAL13 FCAL14 FCALK12 FCALK13 FCALK14 14-10 AWG Cu/Al 10-4 AWG Cu/Al 4-1/0 AWG Cu/Al Torque 25-32 lb-in Slot 25-32 lb-in 5/32” Hex 25-32 lb-in 5/32” Hex Panelboard Mounting Kits Panelboard Description Catalog Number Notes A-Series AD Plus Breaker Mounting Kit A-Series AD Plus Panelboard ASPFB12P Kit includes screws and washers for mounting up to 12 poles. Order FB breaker with “RV” suffix for A-Series AD Plus Panelboards. Bolt-On FB Strap and Cover Kit 2 Pole Bolt-On FB Strap Kit 2 Pole Bolt-On FB Strap and Cover Kit 3 Pole Bolt-On FB Strap Kit 3 Pole Mounting Hardware Only (No Brackets or Straps) FB Module 2 Pole with Covers FB Module 2 Pole FB Module 3 Pole with Covers FB Module 3 Pole Mounting Hardware – Single Breaker FB Module 2 Pole with Covers ADS FB Module 2 Pole ADS FB Module 3 Pole with Covers ADS FB Module 3 Pole ADS AMCB4FBFP AMCB4FB AMCB6FBFP AMCB6FB AHKBFB1 AMC4FBFP AMC4FB AMC6FBFP AMC6FB AHKFB1 AMC4FBSFP AMC4FBS AMC6FBSFP AMC6FBS These kits can also be used to mount single pole breakers. Order FB breaker with “R2” suffix for Spectra Series™ Power Panelboards. Spectra™ Bolt-on Spectra™ Plug-in Spectra™ ADS Tool Internal Accessory Mounting Locations & Limitations Accessory Mounting Pocket Location Shunt Trip or Under Voltage Release Aux. Switch - Left Mount Aux. Switch - Right Mount Accessory Installation 1 Pole 2 Pole 3 Pole 0 1 1 0 0 1 0 0 1 Bell Alarm 0 0 1 Maximum Number of Internal Accessories That Can Be Installed 0 1 4 Shunt Trip or Undervoltage Release Bell Alarm Switch Auxiliary Switches 2 pole 3 pole Publications & References Available for download from www.geindustrial.com/publibrary FB Breaker Installation Instructions Fact Sheet DEH-41073 DET-406 FB Breaker Accessories Bell Alarm & Aux. Switch Shunt Trip & UVR Padlock Device Lug Kits DEH-40324 DEH-40363 DEH-40521 DEH-40532 Panelboards A-Series AD Plus Catalog/Selection Guide A-Series AD Plus Fact Sheet Spectra Power Panel - Plug-in Kits Spectra Power Panel - Bolt-on Kits Spectra Power Panel - Filler Plates DEP-134 DET-397 DEH-41123 DEH-41124 DEH-41125 Series Ratings DET-008 Outline Drawings FB 1 Pole FB 2 Pole FB 3 Pole 10091632SH1 10091636SH1 10091641SH1 Time Current Curves 15A FB & FC 20A FB & FC 25A FB & FC 30A FB & FC 35A FB & FC 40A FB & FC 45A FB & FC 50A FB & FC 60A FB & FC 70A FB & FC 80A FB & FC 90A FB & FC 100A FB & FC DES-013 DES-014 DES-015 DES-016 DES-017 DES-018 DES-019 DES-020 DES-021 DES-022 DES-023 DES-024 DES-025 Peak Let-Through Current/Energy Curves FB & FC Peak Let-Through Current DES-030 FB & FC Let-Through Energy DES-031 Data are subject to change without notice. Should further information be desired, or should particular problems arise that are not sufficiently covered here for the purchaser’s purposes, the matter should be referred to the General Electric Company. GE Consumer & Industrial 41 Woodford Avenue, Plainville, CT 06062 www.geindustrial.com © 2006 General Electric Company imagination at work DEP-131A (05/06)