Performance Specification & Installation Guide 120/277Vac Single-Pole Power Pack Part No. Features Specification PPK1-PLS 1-Pole 120-277Vac • Works with CENTO 24Vac (low voltage) Occupancy and Vacancy Sensors Load Voltage • 120/277Vac • 60Hz • Converts line voltage to low voltage and switches the load Switching Load Connections • 120/277Vac • See Table for contact rating • #14AWG Wire • Mounts to a standard ½” knockout • Fits into a standard 4” octagon box if required to meet local electrical codes Operation The PPK1-PLS power pack is intended for use with CENTO 24Vac, low-voltage occupancy sensors. The power pack provides 24Vac control power to one or more sensors, and the sensor (or gang of sensors) provides a diode-pulse control signal for use by the power pack’s internal relay. Contact Rating Voltage General Tungsten Standard Ballast Electronic Ballast 120V 20A 20A 20A 16A 277V 20A 20A 20A 16A Secondary Power Source Loading Voltage Max # of Linked Sensors 24Vac 10 Power pack is designed for use only with CENTO 24Vac, low-voltage occupancy sensors. Control Inputs • Diode Pulse : For use with CENTO 24Vac occupancy sensors • #22AWG Wires Use #18AWG for connections Secondary Power Source • 24Vac, 150mA • #22AWG Wires Use #18AWG for connections Approvals • Certified to CAN/CSA Std. C22.2 No. 14 • Conforms to UL 508 Standard • Title 24 • FCC • Class 2 Power Supply • Plenum Rated UL2043 Environment • Indoors, stationary, non-vibrating, non-corrosive atmosphere and non-condensing humidity • Ambient Operating Temperature: 14°F to 140°F (-10°C to 60°C) • Storage Temperature: -14°F to 140°F (-25°C to 60°C) * Application and Performance Specification Information Subject to Change without Notification 51 Century Blvd., Suite 230 • Nashville, TN 37214 • 615-316-5100 • (TES) 1-800-BALLAST • www.unvlt.com 1 of 2 Performance Specification & Installation Guide 120/277Vac Single-Pole Power Pack Installation Use the 1/2in electrical hub and a listed junction box to provide a suitable enclosure for the line-side electrical connections. Wiring Instructions Complete the line-side electrical connections as shown in the diagram below. Separately cap and insulate any unused connections. Provide insulation for at least 600Vac. Electrical Connections 24Vac Supply 24Vac Return Diode Pulse Input PPK1-PLS Black LINE White White Blue NEUTRAL Blue Blue Red Class 2 LOAD Class 1 Refer to sensor cut sheets for low voltage wiring diagrams. All line and neutral connections must be derived from the same circuit. Dimensions & Mounting – inches (mm) 1/2” KO 1.93 (49) 0.59 (15) 3.50 (89) 1.85 (47) * Application and Performance Specification Information Subject to Change without Notification 51 Century Blvd., Suite 230 • Nashville, TN 37214 • 615-316-5100 • (TES) 1-800-BALLAST • www.unvlt.com 1 of 2