The FLEXUS series is suitable for protecting information and telecommunications systems, information networks and critical systems in general, where the risks connected with a power supply of poor quality energy could put the continuity of activities and services at risk, entailing high costs. The FLEXUS series is available in 10-1215-20 kVA three-phase input and output models, with double conversion on-line technology according to the VFI-SS-111 classification, as defined by the IEC EN 62040-3 standard. Flexus has been designed and produced with state-ofthe-art technologies and components, in order to guarantee maximum protection for the users powered, no impact on the supply mains and energy saving. Flexus impact on the power supply source, be it the mains or a generator set: • low distortion of input current – less than 3% • input power factor 0.99 • power walk-in function that guarantees progressive start-up of the rectifier • delayed switching-on function, to restart the rectifier igniters when the mains returns, in case of systems with various UPS The Flexus also acts a filter and phaseshift mechanism in respect of the supply mains ahead of the UPS, since it removes the harmonic components and the reactive power generated by the users powered. • Charge block system to reduce consumption of the electrolyte and further extend the life of VRLA batteries. Compensation of the recharge voltage according to temperature in order to avoid excessive charges and battery overheating. Battery Test in order to detect any falloff in performance or failure of the batteries in good time. Protection against deep discharges: in case of long low load discharges, the end-of-discharge voltage tension will be BATTERY CARE SYSTEM ZERO IMPACT SOURCE Thanks to the technology used, Flexus can solve any problem of connection in installations where the supply mains has a limited installed power, where the UPS is also powered by a generator set or where there are problems of compatibility with loads that generate current harmonics; Flexus has indeed zero Management of the batteries is fundamental to guaranteeing operation of the power supply unit under emergency conditions. The Battery Care System consists of a series of functions and performances that permit management of the storage batteries in such a way as to obtain the best performance and to extend battery life. increased, as prescribed by the battery manufacturers, in order to avoid damage to or a drop in performance of the storage batteries. Ripple Current: the recharge ripple current (residual AC component) is one of the most important causes that reduce battery reliability and life. Flexus, thanks to the high-frequency battery charger, reduces this value to negligible levels, extending battery life and maintaining high performance for a long time. Wide voltage range: the rectifier is made to be operated with a wide range of values of the input voltage (up to 40% with half load), reducing the need to discharge the batteries and, as a result, extending battery life. LOW MANAGEMENT COST The technology used and the choice of high performance components mean that Flexus can obtain exceptional performance and efficiency levels, from a very low footprint and dimensions: • the lowest footprint in this category, only 0.26 sq. m. for 20kVA Flexus, batteries included • high performance up to 94% that permits 35% of the energy dissipated in one year to be saved, compared to similar products present on the market (with average performance 91%). This exceptional performance value makes it possible to recover the initial investment in less than 4 years in operation. • output power with power factor 0.9 that provides up to 15% more active power compared to a normal UPS in commerce, guaranteeing the greatest margin in sizing of the UPS for further load increases FLEXIBILITY Flexus can be used for a wide range of applications, thanks to its characteristics of configuration flexibility, accessories and options available and performance levels: • suitable for powering capacitive loads such as blade servers, without any reduction of the active power, from 0.9 leading to 0.9 lagging • modes of operation: On Line, Eco, Smart Active and Stand By Off Battery recharge: Flexus is suitable for working with hermetically sealed (VRLA), AGM and GEL lead batteries, and openvase and Nickel-Cadmium batteries. According to the type of battery, various recharge methods are available. • One-level recharge, typical for the most commonly used VRLA AGM batteries • Two voltage levels recharge according the IU characteristic Leading Cosϕ (capacitive loads) cosϕ 0,9 Flexus Output Power cosϕ 1 100% kW Lagging Cosϕ (inductive loads) cosϕ 0,9 1,00 0,75 Active Power 0,50 100% kVA UPS @ Cosϕ 0,9 Es. 20kVA - 18kW !!! 0,25 -1 -0,8 -0,6 -0,4 -0,2 0 0,2 0,4 0,6 0,8 1 Reactive Power • 3 slots for the installation of optional communication accessories such as network adapters, zero-potential contacts, etc. • REPO (Remote Emergency Power Off) with which to power down the UPS through a remote emergency pushbutton • Input for connection of the auxiliary contact of an external manual bypass • Input for synchronization from an external source • Graphic mimic panel display for remote connection • frequency converter mode • Power Share sockets that can be configured in order to maintain the back-up time for the most critical loads or to be activated only when the mains goes down • Cold Start to switch on the UPS including when the supply mains is off • battery cabinets of various dimensions and capacity, for longer back-up times • option to connect a temperature sensor for external battery cabinets, for recharge voltage compensation • additional battery chargers to optimize recharge times • optional double input of the supply mains • isolation transformers to modify the neutral arrangements, in case of separate sources or for galvanic isolation between input and output ADVANCED COMMUNICATION Flexus is equipped with a graphic display that provides information, measures, states and alarms regarding the UPS in 5 different languages. • Advanced multiplatform communication, for all operating systems and network environments: Watch&Save 3000 monitoring and shutdown software included with SNMP agent • Compatible with PowerNetGuard for the remote assistance service RS232 or USB serial port LE FOR SUITABY LIGHTING NC EMERGEPLICATIONS AP 50 51 Three-phase input Three-phase output Three-phase input Three-phase output Flexus Flexus Models Power (kVA) Technical data FT 10 10 FT 12 12 FT 15 15 FT 20 20 System Weight with internal batteries (kg) FT 10 180 FT 12 182 Dimensions (hwd) (mm) Input FT 10 Rated voltage FT 12 FT 15 FT 20 FT 15 FT 20 Compliance 380-400-415 Vac three-phase +N FT 20 195 90% non condensing Colour Dark grey (RAL 7024) < 56 dBA at 1 m Protection rating IP20 Efficiency FT 12 3+N Number of phases 190 3 communication interface slots/RS232/USB O°C - 40°C Relative humidity 50/60 Hz 40 ÷ 72 Hz Noise 0.99 Pf THDI ≤ 3% FT 10 180 ± 264V (selectable) Voltage tolerance FT 15 930 x 320 x 840 Communication Operating temperature 380- 400-415 Vac three-phase +N Rated frequency Frequency tolerance Power factor at full load Current distortion By pass Rated voltage 50 or 60 Hz (selectable) Rated frequency Frequency tolerance Output ≥ 94% in On-line mode, ≥ 98% in Economy mode European Directives: L V 73/23/EC and 93/68/EC Low voltage directive EMC 2004/108/EC and 89/336/EC Electromagnetic compatibility directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2 Classification according to IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111 Details ±5 (selectable) FT 10 9 Active power with load PF from 0,9 cap. to 0,9 ind. 10 Rated power (kVA) FT 12 FT 15 12 15 10.8 13.5 3+N Number of phases 0.9 Output power factor 3:1 Crest factor (Ipeak/Irms) ± 3% Dynamic variation ± 1% Static variation 380-400-415 Vac (selectable) Rated voltage Voltage distortion FT 20 Communication interface slot Powershare sockets 20 18 Remote contacts connectors Parallel board Serial interface port USB port ≤ 1% with linear load / ≤ 3% with non-linear load Frequency 50/60 Hz Frequency stability on battery mode 0.01% Overload at Pf 0.8 Batteries 115% infinite, 125% for 10 minutes, 150% for 1 minute, 168% for 5 seconds FT 10 FT 12 Type FT 15 FT 20 VRLA AGM/GEL Recharge time 6h 52 53 Personal computerS iPlug 600-800 VA single-phase ECO LINE The iPlug series is the ideal solution for household, and small home office systems. Its compact size and versatility - push-button operation, LED status panel and user-replaceable batteries - make iPlug easy to install within a domestic environment to protect systems from surges and blackouts. When mains power fails the load is powered by the inverter and built-in battery. PowerShield3 UPS monitoring and control software (available for download from www.riello-ups.com) can be used for an orderly unattended shutdown of IT systems. LOAD CONFIGURATOR Load type Power (VA)* Personal computer 250 LCD Monitor 70 15” Monitor 150 Scanner, printer 200 Modem, TV, DVD reader, PlayStation, Hi-Fi, Phone, Fax 50 Laser printer** 200 *Average estimated value. **Use the iPLUG filtered power output. FEATURES • ECO LINE energy efficient product • Compact, ergonomic design • 5 sockets with battery backup •3 sockets with surge protection only • Cold start capability to power up the UPS without mains power • User replaceable batteries • USB interface for remote monitoring • Power cable included • Protection from short-circuits • Auto restart - when the mains returns after battery exhaustion • GS/Nemko safety marking • Available with French (2P+E), English, Schuko and Italian outlets. ADVANCED COMMUNICATION •PowerShield3 supervision and shut-down software for Windows 7, 2008, Vista, 2003, XP, Linux, Mac OS X and Sun Solaris operating systems • Plug and Play function. 2 YEAR WARRANTY MODELS POWER iPlug 600 iPlug 800 600VA/360W 800VA/480W INPUT Rated voltage 220-240 Vac Voltage range 230 Vac (+20/-25%) Frequency 50/60 Hz with auto sensing OUTPUT Voltage on mains operation 230 Vac (+20/-25%) Voltage on battery operation 230 Vac (+/- 10%) Frequency on battery operation 50 or 60 Hz (+/- 1%) BATTERIES VRLA AGM Maintenance-free lead-acid Type Recharge time 6-8 h ENVIRONMENTAL Net weight (kg) Gross weight (kg) 3.7 4.1 4 4.4 Dimensions (hwd) (mm) 99 x 175 x 313 Packaging dimensions (hwd) (mm) 260 x 380 x 140 Communication Compliance USB EN 62040-1-1 and Directive 2006/95/EC; EN 62040-3 EN 62040-2 and Directive 2004/108 EC CE; GS/NEMKO on Schuko version Marks Operating temperature 0°C / +40°C Colour Altitude and relative humidity Black 6000 meters max. elevation, <95% non condensing Accessories provided 1 input supply cable, user guide iPlug 600 - iPlug 800 Rear detail Sockets with UPS protection (no break in power if mains fails) IEC OUTLETS WITH UPS PROTECTION SAFETY FUSE USB communication port Filtered socketS: overvoltage protection only TECHNICAL DETAILS LED detail AVAILABLE SOCKETS schuko socket French socket ITALIAN socket British socket CEE 7/7P CEE 7/5 CEI 23/16 BS1363A QUALITY POWER SUPPLY SENTRY MPS is an on-line double conversion UPS (VFI SS 111 in accordance with IEC EN 62040-3) with a transformer isolated inverter. With a compact footprint and high power quality output, SENTRY MPS is designed to protect “mission critical” applications including data processing, telecommunications, industrial processes, security and electro-medical systems. SENTRY MPS is available from 100 to 800kVA in two or four versions each with different harmonic distortion and power factor for better matching the market requirements: • • • • MPS (100 to 200kVA only), MPS LH (100 to 200kVA only), MPS Plus, MPS Sinus. Sentry MPS Three-phase output FLEXIBILITY SENTRY MPS technology removes the problems of over sizing downstream power sources, whilst improving load power factors and current harmonics. The UPS features the latest input current absorption techniques including progressive rectifier start-up and the option to reduce battery charging currents. These features make SENTRY MPS one of the most generator compatible and environmentally friendly UPS available. Traditionally, when a mains supply is present the UPS charges its batteries. Battery power is used for the inverter should the input supply fail. Efficient battery management and care is therefore essential to the overall performance of the UPS in an emergency. The SENTRY MPS Battery Care System consists of a range of features designed to provide optimum performance and enhanced operating life: • Dual level charging regime to optimise recharge currents and lower recharge times; • Temperature compensation and deep discharge protection to reduce overall battery aging; • Charge blocking system to reduce electrolyte consumption and lengthen the life of VRLA batteries; • Predictive battery testing to spot potential battery deterioration and failure. SENTRY MPS is also compatible with different battery technologies: openvase lead acid and AGM and Gel VRLA, NiCd. MINIMUM INPACT ON SUPPLIES EASY SOURCE BATTERY CARE SYSTEM: MAXIMUM LIFETIME POTENTIAL SENTRY MPS is suitable for a wide range of applications including IT and the most demanding industrial environments suitable for power capacitive loads such as blade servers, without any reduction of the active power, from 0,8 lagging to 0,9 leading. With a broad of accessories and options, complex configurations and system architectures can be achieved to guarantee maximum power availability and the option to add new UPS without interruption to existing users. Using the AROS UPS Group Synchroniser (USG) and Parallel Systems Joiner (PSJ) sophisticated inter group parallel and redundant systems can be achieved to provide the highest possible levels of resilience and availability. EASY INSTALLATION SENTRY MPS has a small footprint (only 0,64 sqm for 200kVA and 1,63 sqm for 400kVA). Front access to internal assemblies and top panel ventilation make space allocation within confined data processing or plant rooms easy. SENTRY MPS can be placed against a wall as there is no requirement for rear or side panel access for maintenance or ventilation. Leading Cosϕ (capacitive loads) cosϕ 0,9 cosϕ 0,8 MPS Output Power 100% kW cosϕ 1 cosϕ 0,9 Lagging Cosϕ (inductive loads) cosϕ 0,8 cosϕ 0,7 1,00 0,75 cosϕ 0,6 Active Power 100% kVA 0,50 0,25 -1 -0,8 -0,6 -0,4 -0,2 0 0,2 0,4 0,6 0,8 1 1,2 Reactive Power APPLICATIONS ADVANCED COMMUNICATION • Servers • Local Area Network (LAN) • Data centers • Telecommunications • Industrial equipment • Electro-medical equipment • Compatible with PowerNetGuard for remote maintenance • Advanced, multi-platform communication, for all operating systems and network environments: Watch&Save 3000 supervision and shut-down software included, with SNMP agent, for Windows 95, 98, NT 4.0, Me, 2000, 2003, XP, Mac OS 9.x, X, Linux, Novell operating systems. The UPS is supplied with a cable for direct connection to the PC (Plug and Play) • RS232 double serial port • Slot for installation of the mains adapter; EPO contact (Emergency Switching Device) for switching off the UPS with a remote emergency switch • Remote mimic panel (LED or LCD) • Graphic Remote Panel OPTIONS Input Isolation transformer UPS Group Syncroniser (UGS) Parallel System Joiner (PSJ) Interface for generator LED remote status panel LCD based remote control panel Graphic Display Remote panel Empty battery cabinets for prolonged runtime 66 67 DUAL BUS SYSTEM The Dual Bus System powers the priority loads from two independent sources. This configuration increases the redundancy and availability level of a multi-module configuration. Each bus may consist of a single module or up to 8 modules in parallel, kept in synchro by the UGS (UPS Group Synchroniser). Fig 1- Bock diagram UPS in parallel up to 8 units Fig. 2 - Dual bus System EXPANDABILITY The units can be connected in parallel up to 8 units to increase power availability or redundancy. The single module or the system can be expanded any time to suit power requirements without influencing the initial investment. Thanks to the peculiarity of the “Hot System Expansion” feature, the additional unit can be connected in parallel while the other units are on-line and supplying regular power to the load. The new UPS is on-line and will be set up automatically. 200kVA DYNAMIC DUAL BUS SYSTEM Two independent systems set in Dual Bus Configuration can be merged together at any time for system expansion or maintenance thanks to the PSJ (Parallel System Joiner) option. This provides a lot of flexibility in your installation in case of maintenance or when it is necessary to change the redundancy level of both systems. Fig. 3 - Dynamic Dual Bus System 68 69 Three-phase input Three-phase output Three-phase input Three-phase output Sentry MPS Sentry MPS Models Power (kVA) Input Technical data MPS 100 100 MPS 100 MPS 120 120 MPS 120 MPS 160 160 MPS 160 400 V ± 20% Voltage tolerance 380 - 400 - 415 Vac three-phase Nominal voltage Frequency MPS 200 200 MPS 200 MPS 120 MPS 160 MPS 120 Models Power (kVA) Technical data MPS 250 250 MPS 250 160 MPS 200 200 160 Output Rated power (kVA) Active power with load PF from 0,9 cap. to 0,8 ind. (kW) MPS 160 810 System Weight (kg) MPS 300 300 MPS 300 MPS 400 400 MPS 400 Lead, open vase acid and VRLA, AGM / GEL; NiCd 250 MPS 300 MPS 400 300 400 240 320 3+N ≤1% 50 or 60 Hz configurable 3:1 Overload MPS 200 110% for 60’; 125% for 10’; 150% for 1’ MPS 250 MPS 300 MPS 400 Voltage-free contacts (configurable) EPO and bypass Double RS232 + remote contacts + 2 communication interface slots Up to 94% Dimensions (wdh) (mm) 770 63 ÷ 68 dBA a 1 m 850x1630x1900 2200 1000x1630x1900 2200 Noise level 2600 70 dBA a 1 m Operating temperature 0 °C / +40 °C Relative humidity <95% non condensing IP20 Colour Compliance MPS 400 >0.95 in the Sinus version 0 ÷ 100% in 30’’ configurable ± 2% (selectable from ± 1% to ± 5% from the front panel) Back Feed protection; separable bypass line MPS 250 Zero -0,5 Vx °C MPS 250 200 Number of phases 380 - 400 - 415 Vac three-phase + N ± 1% ± 5% in 10 msec. ≤3% Frequency Sinusoidal Crest factor (Ipeak/Ipms) MPS 120 System Remote signalling Communication Efficiency 650 0 °C / +40 °C <95% non condensing Relative humidity Protection degree Light grey (RAL 7035) Directives EEC 73/23 - 93/68 - 89/336 Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3 (Voltage Frequency Independent) VFI - SS - 111 MPS 300 400 V ± 20% 45 ÷ 65 Hz Power factor Battery Type AC ripple current Temperature compensation MPS 160 120 128 3+N Nominal voltage Static stability Dynamic stability Voltage distortion with linear load ≤1% MPS 100 <3% in the Sinus version Soft start Permitted frequency tolerance Standard features MPS 200 Lead, open vase acid and VRLA, AGM / GEL; NiCd 100 96 380 - 400 - 415Vac three-phase + N ± 1% ± 5% in 10 msec. Voltage distortion with linear load 50 or 60 Hz configurable Frequency Waveform 3:1 110% for 60’; 125% for 10’; 150% for 1’ Voltage-free contacts (configurable) Remote signalling Remote commands Double RS232 + remote contacts + 2 communication interface slots Up to 94% 800x800x1900 (base version) 640 380 - 400 - 415 Vac three-phase Frequency >0.95 in the Sinus version Power factor Current harmonic distortion 0 ÷ 100% in 30’’ configurable ± 2% (selectable from ± 1% to ± 5% from the front panel) Back Feed protection; separable bypass line MPS 100 Zero -0,5 Vx °C MPS 100 Rated power (kVA) Input Nominal voltage Voltage tolerance 45 ÷ 65 Hz <3% in the Sinus version Current harmonic distortion Soft start Permitted frequency tolerance Standard features Battery Type AC ripple current Temperature compensation Output 80 Active power with load PF from 0,9 cap. to 0,8 ind. (kW) Number of phases Nominal voltage Static stability Dynamic stability Voltage distortion with non linear load ≤3% Voltage distortion with non linear load Sinusoidal Waveform Crest factor (Ipeak/Ipms) Overload EPO and bypass Remote commands Communication Efficiency Dimensions (wdh) (mm) Weight (kg) Noise level Operating temperature IP20 Protection degree Colour Compliance Classification as per IEC 62040-3 Light grey (RAL 7035) Directives EEC 73/23 - 93/68 - 89/336 Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3 Classification as per IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111 70 71 Sentry MPS Technical data Three-phase input Three-phase output Models Power (kVA) Input MPS 500 500 MPS 500 MPS 600 600 MPS 600 400 V ± 20% Voltage tolerance 380 - 400 - 415 Vac three-phase Nominal voltage Frequency MPS 800 800 MPS 800 45 ÷ 65 Hz <3% in the Sinus version Current harmonic distortion >0.93 in the Sinus version Power factor Soft start 0 ± 100% in 30" configurable Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from the front panel) Standard features Battery Back Feed protection; separable bypass line MPS 500 Type MPS 600 MPS 800 Lead, open vase acid and VRLA, AGM / GEL; NiCd AC ripple current < 1% Temperature compensation Output -0,5 Vx °C MPS 500 MPS 600 3+N Number of phases 480 400 Active power with load PF from 0,9 cap. to 0,8 ind. (kW) 500 Rated power (kVA) MPS 800 600 Nominal voltage 800 640 380 - 400 - 415 Vac three-phase + N Static stability ± 1% Dynamic stability ± 5% in 10 msec. ≤3% Voltage distortion with non linear load ≤1% Voltage distortion with linear load Sinusoidal Waveform 50 or 60 Hz configurable Frequency Crest factor (Ipeak/Ipms) 3:1 Overload System 110% for 60’; 125% for 10’; 150% for 1’ MPS 500 MPS 600 EPO and bypass Remote commands Voltage-free contacts (configurable) Remote signalling Communication MPS 800 Double RS232 + remote contacts + 2 communication interface slots Efficiency Up to 94% Dimensions (wdh) (mm) 3200x980x1900 3600 4400x1000x1900 0 °C / +40 °C Operating temperature 78 dBA a 1 m Noise level 4000 Weight (kg) IP20 Protection degree <95% non condensing Relative humidity Colour Compliance 5300 Light grey (RAL 7035) Directives EEC 73/23 - 93/68 - 89/336 Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3 Classification as per IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111 72 Sentry MPS Single-phase output Sentry MPS Technical data Three-phase input Single-phase output Models Power (kVA) Input MPM 30 30 MPM 30 MPM 40 40 MPM 40 MPS 1Ph is an on-line double conversion UPS (VFI SS 111 in accordance with IEC EN 62040-3) with transformers isolated inverter and rectifier. MPS 1Ph has a compact foot print and high quality output to provide the ultimate power protection for industrial applications: industrial processes, petrochemical, power plant, energy etc. MINIMUM IMPACT ON SUPPLIES EASY SOURCE PROTECTION FOR INDUSTRIAL APPLICATION BATTERY CARE SYSTEM: MAXIMUM LIFETIME POTENTIAL Traditionally, when a mains supply is present the UPS charges its batteries. Battery power is used for the inverter should the input supply fail. Efficient battery management and care is therefore essential to the overall performance of the UPS in an emergency. The MPS 1Ph Battery Care System consists of a range of features designed to provide optimum performance and enhanced operating life: • Dual level charging regime to optimise recharge currents and lower recharge times • Temperature compensation and deep discharge protection to reduce overall battery aging • Charge blocking system to reduce electrolyte consumption and lengthen the life of VRLA batteries • Predictive battery testing to spot potential battery deterioration and failure MPS 1Ph is also compatible with different battery technologies: openvase lead acid and AGM and Gel VRLA, NiCd. MPM 60 60 MPM 60 400 V ± 20% Voltage tolerance 380 - 400 - 415 Vac three-phase Nominal voltage Frequency ≥0.93 Power factor Battery MPM 80 80 MPM 80 45 ÷ 65 Hz <5% C Current harmonic distortion Soft start 0 ÷ 100% in 120’’ configurable Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from the front panel) Standard features MPS 1Ph technology removes the problems of over sizing upstream power sources, whilst improving load power factors and current harmonics. The UPS features the latest input current absorption techniques including progressive rectifier start-up and the option to reduce battery charging currents. These features make MPS 1Ph one of the most generator compatible and environmentally friendly UPS available. INDUSTRIAL ENVIRONMENT MPS 1Ph is suitable for severe installation environments such as petrochemical manufacturing sites, where the operating conditions (levels of vibration, mechanical stress, ambient temperatures and dust ingress) require a more robust and industrialized UPS design to those installed within, for example, data centres. HIGH Icc A high short-circuit current (Icc = 3 In) making the UPS suitable for loads with high current peaks; during switch-on or a load step-change. 220V DC VOLTAGE An input transformer and isolated inverter to protect the 220Vdc bus bar (from 108 to 114 blocks), the recognised industrial standard. REDUNDANT VENTILATION 100% redundant ventilation with 50% fan loading at nominal load and each fan monitored for breakdown or failure. Back Feed protection; separable bypass line MPM 30 MPM 40 Numeber of cells MPM 60 MPM 80 108 ÷ 114 Max Vdc 274 V Temperature compensation -0,5 Vx °C FLEXIBILITY With a broad range of accessories and options, complex configurations and system architectures can be achieved to guarantee maximum power availability and the option to add new UPS without interruption to existing users. Using the Aros UPS Group Synchroniser (USG) and Parallel Systems Joiner (PSJ) sophisticated inter group parallel and redundant systems can be achieved to provide the highest possible levels of resilience and availability. Output MPM 30 24 Active power (kW) 30 Rated power (kVA) MPM 40 MPM 60 40 60 32 Nominal voltage 48 MPM 80 80 64 230Vac single-phase <1% Voltage distortion with linear load ± 5% Dynamic stability ± 1% Static stability Voltage distortion with non linear load <3% Frequency 50 or 60 Hz configurable Crest factor (Ipeak/Ipms) 3:1 Overload 110% for 60’; 125% for 10’; 150% for 1’ Short circuit current 3 I nom. ADVANCED COMMUNICATION • Compatible with PowerNetGuard for remote maintenance • Advanced, multi-platform communication, for all operating systems and network environments: Watch&Save 3000 supervision and shut-down software included, with SNMP agent, for Windows 95, 98, NT 4.0, Me, 2000, 2003, XP, Mac OS 9.x, X, Linux, Novell operating systems. The UPS is supplied with a cable for direct connection to the PC (Plug and Play) • RS232 double serial port • Slot for installation of the mains adapter; EPO contact (Emergency Switching Device) for switching off the UPS with a remote emergency switch • Remote mimic panel (LED or LCD) System MPM 30 MPM 40 MPM 60 EPO and bypass Remote commands Voltage-free contacts Remote signalling Communication MPM 80 Double RS232 + remote contacts + 2 communication interface slots Efficiency Up to 94% Dimensions (wdh) (mm) Weight (kg) 800x800x1900 850 1600x800x1900 900 1400 0 °C / +40 °C Operating temperature Redundant fans Ventilation 63 ÷ 68 dBA a 1 m Noise level IP20 Protection degree <95% non condensing Relative humidity Colour Compliance 1500 Light grey (RAL 7035) Directives EC 73/23 - 93/68 - 2004/108 Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3 Classification as per IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111 74 75 LE FOR SUITABY LIGHTING NC EMERGEPLICATIONS AP Sentry Multistandard SENTRY MULTISTANDARD provides maximum protection for critical data processing networks and security applications, thanks to its advanced design, selectable operating modes and communications capabilities. Operating modes include: On-line, Economy, Smart-Active, Standby/Off and Voltage Stabilisation. Standard communications features include a front panel LCD with 128 potential messages, RS232 interfaces, EPO input, communications interface slot and Watch&Save 3000 management software. The SENTRY MULTISTANDARD series includes 10-15-20kVA single/singlephase, three/single-phase and 10-1520-30-40-60-80 kVA three-phase models, and uses on-line double conversion technology (VFI). The load is powered continuously by the inverter with a filtered, stabilised and regulated sinewave supply. The input and output filters considerably increase the immunity of the load to mains disturbances and surges, even on bypass. 10/30 kVA LOW POWER CONSUMPTION • On-line Mode: up to 92% efficiency can be achieved due to the use of IGBT technology, increasing to 98% in one of the other operating modes • Economy Mode: uses Line Interactive (VI) technology to power less critical loads from the mains supply for certain periods • Smart Active: if the mains supply is out of range, the UPS will power the load from the inverter as an On-line UPS. When the mains supply returns to within range again, the UPS will monitor this for a certain period before selecting Line Interactive operation. Fig. 1 – Block diagram UPS in parallel up to 8 units 10/30 kVA • Automatic battery test • Recharge compensated for temperature • Automatic or manual rapid charge (boost) – duration progammable • Option to connect the UPS to singlephase or three phase mains supplies (SM series) • Panel adjustment to offset voltage drop down long cable runs HIGH LEVEL BATTERY RELIABILITY SIMPLE TO INSTALL For the 40 to 80 kVA models, open the door and remove the protective panel (standards requirement) and the power components - mounted on a sliding tray - can be pulled out to provide easy access to all the electrical and electronic components for maintenance and repair work. This particular feature means that the MTTR (Mean Time To Repair) is much lower than traditional UPS designs with less easily reached assemblies, • Connect up to 8 units in parallel for power capacity or redundancy MAINTENANCE SIMPLICITY = LOW MTTR MAXIMUM RELIABILITY AND AVAILABILITY Battery cabinet which has longer times due to the compact size of the products and difficult access to the parts. A large amount of maintenance information is available from the front mimic panel and LCD. In addition system operating parameters are software configurable via a local PC to allow new functions to be added or adjustments made to operating specifications. 55 54 SENSITIVE SUPPLY COMPATIBLE For power supply sources that are particularly sensitive to harmonics (generator sets or transformers of low power with respect to that of the UPS) it is often a good idea to take action to limit the harmonics injected back into the supply by the UPS. SENTRY MULTISTANDARD series is also available with built-in active filter using high frequency Isolated Gate Bipolar (IGBT) Technology with Digital Signal Processor (DSP) control. The Active Filter helps to reduce harmonics generated by the UPS into the supply which could disrupt the operation of downstream generators and transformers whose rating is closely matched to that of UPS. • advanced technology The active filter reduces harmonic distortion of the phase and neutral currents. The Digital Signal Processor (DSP) and the “current mode” instantly control and monitor the input current to maintain a perfect sinewave with less than 4% harmonic distortion • maximum efficiency Thanks to the active filter Sentry Multistandard systems have low input distortion even at low loads and their overall efficiency is not affected by generator frequency variations or line impedance • reduction of neutral current The active filter reduces the input neutrals current by up to 3.5 times their nominal rating to help avoid oversizing input protections and conductors • maximum reliability Sentry Multistandard systems are extremely reliable. Overall UPS performance is unaffected should the harmonic filter fail • excellent capabilities Input distortion: (THDi) less than 4% Input power factor: >0.99 Efficiency: up to 93% Leading Cosϕ (capacitive loads) cosϕ 0,8 Multistandard Output Power cosϕ 0,9 100% kW cosϕ 1 cosϕ 0,9 Lagging Cosϕ (inductive loads) cosϕ 0,8 Operating status, alarms, applied load, battery charging. 1,00 Sentry Multistandard can also be supplied without the Active Filter for installations less sensitive to current harmonics. OTHER CHARACTERISTICS • • • • • • • Sentry Multistandard is able to supply loads with power factor from 0,8 capacitive to 0,8 inductive without derating the active power (KW) High level diagnostics: event log with 128 messages, states, measurements and alarms - available from the built-in LCD in several languages Reduced noise levels: high frequency inverter bridge Back feed protection standard: to avoid energy feeding back into the mains supply (in compliance with CEI 11-20; DK5600) Power factor correction (input power factor, close to 1) By pass may be deactivated to allow operation as a frequency converter (at 50 or 60 Hz) Emergency operation: the UPS can be set to operate only when the mains fails (for emergency lighting) 0,75 0,50 Active Power 100% kVA Controls and settings menu. 0,25 -1 -0,8 -0,6 -0,4 -0,2 0 0,2 0,4 0,6 0,8 1 Reactive Power ADVANCED COMMUNICATION Language selection menu. APPLICATIONS • Compatible with PowerNetGuard for remote maintenance • Advanced, multi-platform communication, for all operating systems and network environments: Watch&Save 3000 supervision and shut-down software included, with SNMP agent, for Windows 95, 98, NT 4.0, Me, 2000, 2003, XP, Mac OS 9.x, X, Linux, Novell operating systems. The UPS is supplied with a cable for direct connection to the PC (Plug and Play) • Double RS232 serial ports • Network adapter slot for SNMP agent • Emergency Power Off (EPO) shutdown input contact • Remote control mimic panel • Local Area Networks (LAN) • Data Centers • Servers • Industrial PLCs • Cash registers • Electromedical devices • Emergency devices (lights/alarms) • Telecommunication devices • e-Business (Servers, Farms, ISP/ASP/POP) Battery voltages, internal operating temperatures. OPTIONS Input isolation transformer Active filter LED remote status panel LCD based remote control panel Graphic Display remote control panel Empty battery cabinet for prolonged runtime Additional battery charger Dual input mains UPS input current with optional Active Filter Sentry Multistandard with Active Filter (internal view) 40/80kVA 40/80kVA 56 57 Three-phase input Three-phase output Three- / Single-phase input Single-phase output Sentry Multistandard Sentry Multistandard Input Technical data SM10 SM15 ± 20% Voltage range 230 Vac single-phase or 400 Vac three-phase + N Rated voltage Frequency range SM20 SM10 SM15 ST10 Technical data ST15 ST20 By pass Rated power (kVA) ST40 ST15 ST20 ST30 ST40 ST60 ST15 ST20 ST30 ST40 ST60 ST80 ST80 Lead, open vase acid and VRLA, AGM / GEL; NiCd 10 ST15 4-8 h ST20 15 20 12 16 ST30 30 24 346 ÷ 422 Vac Voltage regulation range ST40 40 32 50 / 60 Hz selectable Frequency ST10 ST15 ST20 ST30 From 110 to 258 From 115 to 335 From 130 to 350 From 144 to 370 ST40 160 450x750x1200 ST60 60 48 ST60 180 ST80 80 64 ST80 192 500x740x1400 EPO and bypass Remote controls Volt free contacts Remote signaling O °C / +40 °C <95% non condensing Relative humidity <56 dBA at 1 m Protection degree Efficiency ST80 400 Vac 3+N 50/60 Hz ± 2% (selectable from ± 1% to ± 5%) ST10 6h ST10 8 3+N 380 - 400 - 415 Vac selectable 3:1 Crest factor (Ipeak/Irms) ± 1% ± 5% in 10 ms 110%125% 150% of the rated current for 5h/10’/1’ Overload System Weight (kg) ST60 > 0.99 Sinewave absorbtion THDi <4% (3Ph input) (1) ST10 Rated voltage SM20 20 16/12 (2) Active power with load PF from 0,8 cap. to 0,8 ind. (kW) Number of phases Rated voltage 2% Distortion with linear load Static stability Dynamic stability SM20 From 125 to 345 Dimensions (wdh) (mm) Volt free contacts Remote signaling Double RS232/C + remote contacts + communication interface slot Communication Operating temperature Dark grey (RAL 7024) Colour Noise IP20 > 92% in On-Line Mode, > 98% in Economy Mode/Smart Active Mode/Standby-Off Mode/AVS Mode EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3 ST30 400 Vac three-phase + N 45 ÷ 65 Hz Power factor Current harmonic distortion SM20 Batteries Type Recharge time 6h SM15 15 200 ÷ 243 Vac Voltage regulation range SM15 From 110 to 330 ± 15% (selectable from ± 5% to ± 25%) Rated frequency Permitted frequency range SM20 Lead, open vase acid and VRLA, AGM / GEL; NiCd SM10 10 Rated power (kVA) 12/10,5 (2) 1 230 Vac 3:1 Crest factor (Ipeak/Irms) ± 1% ± 5% in 10 ms 50 / 60 Hz selectable Frequency SM10 System 450x750x1200 EPO and bypass Remote controls O °C / +40 °C < 95% non condensing Dark grey (RAL 7024) Colour ± 20% Frequency range > 0.99 Sinewave absorbtion THDi <4% (3Ph input) (1) SM15 By pass Number of phases 1 Permitted voltage range ± 15% (selectable from ± 5% to ± 25%) 50/60 Hz ± 2% (selectable from ± 1% to ± 5%) SM10 Input Rated voltage Voltage range 45 ÷ 65 Hz Power factor Current harmonic distortion 230 Vac Rated voltage Number of phases Permitted voltage range Rated frequency Permitted frequency range Batteries Type Recharge time Output Output 8 Active power with load PF from 0,8 cap. to 0,8 ind. (kW) Number of phases Rated voltage 2% Distortion with linear load Static stability Dynamic stability 110% 125% 150% of the rated current for 5 h/10’/1’ Overload From 105 to 243 Weight (kg) Dimensions (wdh) (mm) Double RS232/C + remote contacts + communication interface slot Communication Operating temperature Relative humidity <56 dBA at 1 m Noise Protection degree Efficiency Compliance <60 dBA at 1 m IP20 > 92% in On-Line Mode, > 98% in Economy Mode/Smart Active Mode/Standby-Off Mode/AVS Mode Compliance EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3 (1) Version with Active Filter (2) Version with single-phase input 59 58 Sentinel 7 Sentinel 7 Technical data Models S7-700 Power S7-1000 700VA/560W Input S7-700 S7-1000 POWER 1000VA/800W S7-1000 S7-1500 S7-1000 POWER Nominal voltage S7-1500 S7-3000 S7-2200 S7-3000 POWER 3000VA/2400W S7-2200 POWER S7-3000 S7-3000 POWER 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD Maximum permitted voltage 300 Vac Nominal frequency 50/60 Hz ± 5% Power factor > 0.99 Current distortion δ7% By pass S7-700 S7-1000 S7-1000 POWER Voltage tolerance S7-1500 S7-2200 S7-2200 POWER S7-3000 S7-3000 POWER S7-3000 S7-3000 POWER 180 - 264 Vac Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable) Output S7-700 MAIN FEATURES ADVANCED COMMUNICATION Voltage distortion with linear load/with distorting load • Filtered, stabilised, reliable output voltage: on-line double-conversion technology (VFI in accordance with IEC 62040-3) with built-in EMI filters • High overload capability up to 150% • Programmable auto-restart when mains power returns • Programmable cold-start from battery • Power factor correction (UPS input power factor close to 1) • Wide input voltage tolerance (from 120280Vac) without battery usage • Possibility to extend autonomy for several hours • Fully configurable using UPS Tools configuration software • High level of battery reliability (automatic and manually-activated battery tests) • High level of UPS reliability (total microprocessor control) • Low impact on the mains (sinusoidal absorption) • Input protection with fuse which can be reset. • Advanced communication, multiplatform, for all operating systems and network environments, Watch&Save 3000 supervision and shut-down software included for Windows 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris and VMware ESX operating systems and other Unix operating systems • UPS Tools configuration and personalisation software supplied as standard • RS232 serial port and opto-isolated contacts • USB port • Slot for communication cards. Frequency S7-1000 S7-1000 POWER S7-1500 S7-2200 S7-2200 POWER < 2% / < 4% Can be selected: 50 Hz or 60 Hz or self-learning Static variation / Dynamic variation ± 1% / 5% in 20 msec. Waveform Sinewave Current crest factor 3:1 On Line / ECO Mode and Smart Active efficiency 98% Overload 2 min. (100%<Load<110%), 5 sec. (100%<Load<150%), 1 sec. (8>Load>150%) Batteries S7-700 S7-1000 S7-1000 POWER Type S7-1500 S7-2200 S7-2200 POWER S7-3000 S7-3000 POWER N.A. 2-4 hours N.A. S7-3000 POWER VRLA AGM lead, maintenance-free Charging time 2-4 hours System N.A. 2-4 hours S7-700 S7-1000 S7-1000 POWER S7-1500 S7-2200 S7-2200 POWER S7-3000 Net weight (kg) 10,9 13,3 7 14,8 25,6 10,6 28 14 Gross weight (kg) 12,5 14,9 8,6 16,4 28,8 13,8 31,2 17,2 Dimensions (wdh) (mm) 422x235x158 Packaging dimensions (wdh) (mm) 500x340x245 Protection against overvoltages 446x333x190 585x470x325 300 joules Protection devices Overcurrent - short circuit - overvoltage - undervoltage - circuit breaker - excessively low battery Communication USB / DB9 with RS232 and contacts / Slot for communication interface Standards Safety: EN 62040-1 and Directive 2006/95/EC; EMC: EN 620040-2 category C2 and Directive 2004/108/EC Ambient temperature / Relative humidity 0°C / +40°C / < 95% not condensed Colour Black Noise level < 40 dBA @ 1 m Standard equipment Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM Details S7 2200-2200 POWER power-off push-button feature to reduce energy consumption to zero, when no load is connected or switched off. Sentinel 7 models include 700VA, 1000VA, 1500VA, 2200VA and 3000VA. S7-2200 POWER 2200VA/1760W 220-230-240 Vac Voltage range for no battery intervention Sentinel 7 is the latest evolution of the successful Aros Sentinel 6 online UPS. This latest development has been designed with the environment in mind. Sentinel 7 is an on-line double- conversion UPS offering the highest levels of reliability and protection for critical servers, voice and data processing IT systems. For long runtime applications, Sentinel 7 (POWER models) can be fitted with matching battery extension packs which also include additional battery boost chargers. In terms of communications, each Sentinel 7 has a built-in mimic panel with an LCD to show input and output voltages, and battery charge status. The inverter is a totally new design, fully microprocessor controlled and constructed to achieve the highest levels of operating efficiency and configuration options. Sentinel 7 UPS also have USB communication ports as standard, with a built-in expansion slot for additional adapters, protocol converters and relate contact cards. The UPS is highly efficient. Sentinel 7 is designed to save energy and has a S7-2200 1500VA/1200W S7 3000-3000 POWER Usb port S7 700-1500 S7 1000-1000 POWER Serial Interface Communication slot Battery Expansion connector Thermal output Protection Output Sockets Input therm al protection Input socket Sentinel 7 RT REDUCED MANAGEMENT COSTS Sentinel 7 RT is the high density version of the Sentinel 7 range of doubleconversion on-line UPS. Sentinel 7 RT is designed to power critical loads such as servers, storage systems, telephone equipment, medical systems and industrial applications. The UPS is ideal for Blade servers with an input power factor close to Unity (1). The UPS has can be used as tower UPS or within a rackmount cabinet, and takes up only 2U in height. Sentinel 7 RT has a modern design, choice of functional formats, and represents the state-of-the-art technology from the Aros research & development team. The UPS can achieve an on-line operating efficiency of 92%. For critical business continuity applications requiring long runtimes, Sentinel 7 RT can be installed with battery extension packs (POWER models) with their own internal battery chargers to maintain sensible recharge times. The UPS also incorporates the Aros “power-off” function found in other UPS. Sentinel 7 RT is designed to save energy when no loads are connected. SIMPLIFIED INSTALLATION • Tower or Rackmount UPS: Sentinel 7 RT can be installed as tower or 19” rackmount UPS, with a front mimic panel that can be turned through 90º to suit the installation. • Noise Free Operation (<40dBA): the UPS can be installed in any environment thanks to its PWM digitally-controlled high frequency inverter. • High Temperature Operation: UPS components are sized for high temperature operation up to 40ºC and are not therefore stressed during normal operational environments. • EnergyShare: Sentinel 7 RT output sockets can be programmed to disconnect less critical loads when the mains power fails. Sentinel 7 RT can be programmed remotely via software or set manually from the front mimic panel to operate in a range of energy saving operating modes: • On Line: maximum power protection and output voltage waveform quality • ECO: to increase operating efficiency to 98% and provide line interactive protection • Smart Active: with the UPS selecting automatically its operating mode - ECO or On-Line dependent upon the reliability and quality of the local mains power supply. • Backup: for emergencies only with the UPS only operating when mains power fails • Frequency converter: from 50 to 60Hz or 60 to 50Hz. ADVANCED COMMUNICATION • Sentinel 7 RT offers maximum flexibility for integrations with any communication system. • Multiplatform communication for all operating systems and network environments, Watch&Save 3000 supervision and shut-down software included for Windows 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris and VMware ESX operating systems and other Unix operating systems. • UPS Tools configuration and personalisation software supplied as standard. • RS232 serial port and opto-isolated contacts. • USB port • Slot for communication cards such as Modbus/Jbus, TCP/IP, SNMP and relay contacts. HIGH OUTPUT VOLTAGE QUALITY • Even with distorting loads (IT loads with a crest factor of up to 3:1). • High short circuit current on bypass. • High overload capacity: 150% from inverter (even with no mains power). • Filtered, stabilised, reliable (On Line double conversion technology (VFI in accordance with EN62040-2 class C1) standard with filters to suppress atmospheric disturbances. • Load power factor correction: incoming UPS power factor close to 1 and sinusoidal current absorption. HIGH LEVELS OF BATTERY RELIABILITY • Automatic and manual battery tests • Batteries are ‘hot-swappable’ and user replaceable. • Unlimited battery runtime extension using battery extension packs. OTHER FEATURES • Output voltage can be selected using software (220-230-240V). • Auto-restart when mains power returns (programmed via software). • Stand-by on Bypass: when the machine is switched off, it automatically goes into bypass operation with batteries charging. • Power-Off with zero load connected to save energy. • Low battery warning • Power-on delay • Full microprocessor control. • Automatic bypass without interruption • Status, measurements and alarms available on the front panel mimic panel and LCD • UPS firmware upgrade via PC platform • Input protection including a user reset thermal switch (up to 1500VA) • Back-feed protection • Manual option to switch to bypass. Sentinel 7 RT Models Power Sentinel 7 RT Technical data S7 RT-1000 S7 RT-1500 S7 RT-2200 S7 RT-2200 POWER S7 RT-3000 S7 RT-3000 POWER 1000VA/900W 1500VA/1350W 2200VA/1980W 2200VA/1760W 3000VA/2700W 3000VA/2400W System Net weight (kg) S7 RT-1000 S7 RT-1500 S7 RT-2200 17.5 18 30.5 15 31 15 21 21.5 35 19.5 35.5 19.5 Gross weight (kg) Input S7 RT-1000 S7 RT-1500 Nominal voltage S7 RT-2200 S7 RT-2200 POWER S7 RT-3000 S7 RT-3000 POWER 760x245x600 300 joules USB / DB9 with RS232 and contacts / Slot for communication interface Standards 50 Hz ± 5% / 60 Hz ± 5% Power factor > 0.98 Ambient temperature Current distortion δ7% Relative humidity Safety: EN 62040-1 and Directive 2006/95/EC; EMC: EN 620040-2 category C2 and Directive 2004/108/EC O°C / +40°C < 95% not condensed Colour By pass S7 RT-1000 S7 RT-1500 Voltage tolerance S7 RT-2200 S7 RT-2200 POWER S7 RT-3000 S7 RT-3000 POWER Frequency tolerance Black Noise level < 40 dBA @ 1 m Standard equipment 200 - 253 Vac Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM Frequency selected (from ±0.Hz to ±5Hz configurable) Details Output S7 RT-1000 S7 RT-1500 Voltage distortion with linear load/with distorting load S7 RT-2200 S7 RT-2200 POWER S7 RT1000 Can be selected: 50 Hz or 60 Hz or self-learning Static variation ±1% S7 RT1500 δ5% in 20 msec Dynamic variation Waveform Input Sockets Sinewave Current crest factor 3:1 On Line / ECO Mode and Smart Active efficiency 98% S7 RT-1000 S7 RT-1500 Type S7 RT-2200 S7 RT-2200 POWER S7 RT-3000 S7 RT-3000 POWER S7 RT-3000 S7 RT-3000 POWER Input thermal protection Emergency switch device (esd) S7 RT2200/2200 POWER Output sockets Battery expansion outlet VRLA AGM lead, maintenance-free Charging time Overload times S7 RT-3000 POWER < 2% / < 4% Frequency Batteries S7 RT-3000 2-4 hours S7 RT-1000 S7 RT-1500 S7 RT-2200 S7 RT-2200 POWER 100% < Load < 110% 1 minute 110% < Load < 150% 4 seconds Load > 150% 0,5 seconds S7 RT-3000 POWER Overcurrent - short circuit - overvoltage - undervoltage - circuit breaker - excessively low battery Communication 50/60 Hz ±5Hz Frequency range 600x245x550 Protection devices 300 V Nominal frequency 625x450x87 (625x19"x2U) Protection against overvoltages 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% load Maximum permitted voltage S7 RT-3000 425x450x87 (425x19"x2U) Packaging dimensions (wdh) (mm) 220-230-240 Vac Voltage range for no battery intervention Dimensions (wdh) (mm) S7 RT-2200 POWER S7 RT3000/3000 POWER Rs232 serial Usb Port Input plug SENTINEL XR is the best solution for protecting medium sized networking applications which require the highest possible levels of reliability. The UPS is designed to support a wide applications from IT to security. SENTINEL XR is unique in that the UPS can be placed directly onto the floor or mounted in 19” rack mount cabinets. The range is available in 3300-4000-5000-60008000-10000VA models. The UPS is primarily an on-line double-conversion (VFI) technology system with further selectable operating modes that can configure the UPS to protect applications including emergency lighting, security and medical systems. Each UPS features advanced communications and diagnostics including a digital front panel display that can turned to suit the installation format, RS232 and USB interfaces, and an internal adaptor slot for SNMP and other interface card options. Watch&Save 3000 software is supplied as standard. Sentinel XR GUARANTEED OUTPUT QUALITY • On line • Economy Mode: selects Line Interactive VI technology to power noncritical loads from mains and achieve up to 98% operating efficiency • Smart Active Mode: the UPS selects automatically whether to operate in On-line VFI technology - full system protection or Line Interactive VI mode depending on the stability of the mains supply • Emergency: the UPS can be programmed to work only when the mains fails - suitable for emergency lighting • Frequency conversion 50 or 60Hz • The UPS can be installed as a floor standing tower or 19” rack mount UPS. The front panel digital display can be pulled out (using the keys provided) and rotated to suite the installation format • Low noise level (<40dBA) thanks to the digitally PWM controlled ventilation system which is load and temperature dependent, and the use of an inverter with a high switching frequency (>20kHZ, above the audible range) • Optional bolt-on maintenance bypass (SENTINEL XR 5-6-8-10 kVA models) to allow service without disruption to the loads • Performance guaranteed in temperatures up to 40°C • Two IEC output plugs with thermal protection (SENTINEL XR 5-6-8-10 kVA) • PowerShare output socket (2x10A IEC) functionality on SENTINEL XR 56-8-10 kVA models SELECTABLE OPERATING MODES SIMPLIFIED INSTALLATION • Even with typical distorting IT loads with crest factors of 3:1 • Increased short circuit current on the bypass • Increased overload capacity: 150% on inverter even when mains supply has failed • Reliable, filtered, stabilised and regulated sinewave output (double conversion technology VFI in conformity with IEC 62040-3 specifications) with filters for atmospheric disturbance suppression • Rephasing of load as the UPS has an input power factor close to 1, with a sinusoidal input current HIGHLY RELIABLE BATTERY PERFORMANCE • Automatic and manual battery tests • Unique Low Ripple Current Discharge (LRCD) to help prolong battery life • Hot-swap user replaceable batteries • Unlimited extendable back-up time using modular design Battery Extension Packs • Increased ride through (without batteries) on mains breaks up to 40ms and for fluctuations ranging from 84 to 276Vac OTHER CHARACTERISTICS • Output voltage selection: 220-230240Vac • Auto restart when mains power returns programmed using the UPS Tools software supplied • Bypass on: when the UPS is switched off, it automatically goes into bypass mode to charge the batteries • Automatic power down due to minimum load • End of battery discharge pre-alarm • Delayed start up • Completely digitally controlled • Automatic bypass with no break in power supply • Use of IMS (Insulated Metallic Substrates) modules • Status, measurements, and alarms available on the standard backlit display • UPS can be updated digitally (flash upgradeable) • Input protected by resettable thermally activated switch • Back-feed protection: to avoid current being fed back into the mains should a fault occur • Manual switch over to bypass • Microsoft Certified Product ADVANCED COMMUNICATION • Advanced, multi-platform communication for all operating systems and network environments: Watch&Save 3000 supervision and shut-down software included, with SNMP agent, for Windows 95, 98, NT4.0, Me, 2000, 2003, XP, Mac OS 9.x, X, Linux, Novell operating systems. The UPS is supplied with a communications cable for ’Plug and Play’ PC connection • Plug & Play feature • USB port • RS232 serial port • Interface card slot • Microsoft certification APPLICATIONS • Local Area Networks (LAN) • Data Centers • Servers • Industrial PLCs • Cash registers • Electromedical devices • Emergency devices (lights/alarms) 2-YEAR WARRANTY LE FOR SUITABY LIGHTING NC EMERGEPLICATIONS AP OPTIONS Extended runtime solutions with/without battery charger External maintenance bypass (except 3300VA and 4000VA) Interface cards Telescopic rails for rack cabinet Display LCD custom 40 41 Sentinel XR Technical data Sentinel XR Single-phase input Single-phase output Models Power Input SXR-3300 3300VA/2300W SXR-3300 SXR-4000 SXR-5000 4000VA/2400W 5000VA/3500W SXR-4000 Rated voltage SXR-5000 SXR-6000 6000VA/4200W SXR-6000 SXR-8000 SXR-10000 8000VA/6400W 10000VA/8000W SXR-8000 SXR-10000 220 - 230 - 240 Vac 50/60 Hz ± 5 Hz Rated frequency 164 Vac @ load 100% 84 Vac @ load 50% Minimum voltage ≤ 7% Current distortion > 0.98 Power factor By pass SXR-3300 Voltage range SXR-4000 SXR-5000 System Weight (kg) SXR-8000 SXR-10000 SXR-4000 SXR-5000 SXR-6000 SXR-8000 SXR-3300 SXR-4000 SXR-6000 SXR-8000 38 SXR-4000 40 175x520x455 Dimensions (wdh) (mm) tower SXR-5000 62 SXR-10000 SXR-6000 64 SXR-8000 80 175x660x455 92% SXR-10000 85 2x175x660x455 483x660x175(4U) On Line Efficiency 2x483x660x175(4U) O °C / +40 °C Overload - short-circuit - overvoltage - undervoltage - temperature - low battery Protection USB / RS232 + communication interface slot Dark grey (RAL 7035) Noise SXR-10000 4-6h SXR-5000 Output < 95% non condensing EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3 Compliance Communication Colour Selected frequency ±5 % (user configurable) SXR-3300 220 - 230 - 240 Vac selectable Rated voltage SXR-3300 483x520x175(4U) Dimensions (wdh) (mm) rack 98% Line-interactive/Smart Active Efficiency Operating temperature Relative humidity SXR-6000 180 - 264 Vac (selectable in Economy Mode and SMART ACTIVE Mode) Frequency range Accessories provided Batteries Recharge time 1,5 % Static variation <40 dBA at 1 m <45 dBA at 1 m 2x10A cables; 1xIEC-16A plug; software; serial cable; plastic keys to release display; handles kit 2 cable guides; terminal board connection; software; serial cable; plastic keys to release display; handles kit Details USB port Serial port ≤ 5% in 20 ms Dynamic variation Waveform Interface card slot SNMP or additional RS232 ports Sinewave < 6% Voltage distortion with non-linear load < 3% Voltage distortion with linear load Input thermal protection re-set 3:1 Crest factor 50/60 Hz selectable Frequency Overload capacity SXR-3300 SXR-4000 SXR-5000 Input hardwired gland Output hardwired glands SXR-6000 4” 125% ≤ Load < 150% 4” 110% < Load < 125% 1’ 100% < Load < 110% Load > 150% SXR-8000 Battery extension pack connector SXR-10000 Input cable access Output cable access SXR 3300-4000 0.5” SXR 5000-6000 SXR 8000-10000 42 43 Sentinel XR Technical data Sentinel XR Three-phase input Single-phase output Models Power Input SXR-6500 6000VA/5200W SXR-6500 Rated voltage SXR-8000 8000VA/6400W SXR-8000 SXR-10000 10000VA/8000W SXR-10000 400 Vac tree-phase + N 50/60 Hz ± 5 Hz Rated frequency 164 Vac @ load 100% - 84 Vac @ load 50% Minimum voltage Power factor By pass Voltage range SXR-8000 System Weight (kg) SXR-6500 64 SXR-6500 80 2x175x660x455 Dimensions (wdh) (mm) tower 92% On Line Efficiency SXR-10000 85 O °C / +40 °C Relative humidity SXR-10000 180 - 264 Vac (selectable in Economy Mode and SMART ACTIVE Mode) Selected frequency ±5 % (user configurable) SXR-8000 Batteries SXR-8000 2x483x660x175(4U) Dimensions (wdh) (mm) rack 98% Line-interactive/Smart Active Efficiency Operating temperature > 0.95 SXR-6500 Frequency range < 95% non condensing EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-2004/108EC EN 62040-3 Compliance Overload - short-circuit - overvoltage - undervoltage - temperature - low battery Protection Communication USB / RS232 + communication interface slot <45 dBA at 1 m Noise Dark grey (RAL 7035) Colour Accessories provided 4-6h Recharge time 2 cable guides; terminal board connection; software; serial cable; plastic keys to release display; handles kit SXR-10000 Details Output SXR-6500 SXR-8000 1,5 % Static variation 220 - 230 - 240 Vac selectable Rated voltage SXR-10000 Battery connection ≤ 5% in 20 ms Dynamic variation Waveform Sinewave < 6% Voltage distortion with non-linear load < 3% Voltage distortion with linear load 3:1 Crest factor 50/60 Hz selectable Frequency Interface card slot SNMP or additional RS232 ports Serial port USB port Overload capacity SXR-6500 SXR-8000 4” 110% ≤ Load < 150% 1’ 100% < Load < 110% Load > 150% SXR-10000 Input cable access 0.5” Output cable access SXR 6500-8000-10000 44 45 Sentinel XR Plus Sentinel XR Plus is the ideal solution for powering vital mission critical, sensitive loads such as electro-medical security applications in order to guarantee maximum reliability and availability. The series includes 5kVA-6kVA single/single phase and 6.5kVA-8kVA10kVA single/single phase and three/single phase models and uses double conversion on-line technology (VFI). The load is powered constantly by the inverter which supplies filtered, stabilised and regulated sinewave voltage. Moreover, the input and output filters increase the immunity of the load against mains power disturbances and lightning strikes. Sentinel XR Plus is without doubt one of the best UPS systems on the market today thanks to the technology used, the features (selectable Economy Mode and Smart Active Mode) and the diagnostics offered (custom LCD display, RS232 and USB interfaces complete with Watch&Save 3000 software, EPO contact and slots for optional interface boards). HIGH RELIABILITY • Full microprocessor control. • No break static and maintenance bypass. • Features guaranteed up to 40 °C (the components are designed to operate at high temperatures and thus are subject to less stress at ordinary temperatures). SELECTABLE OPERATING MODES The operating mode can be programmed using the software or selected manually on the digital front panel display. • On line Mode (VFI). • Economy Mode: increases efficiency (up to 98%), and uses Line Interactive (VI) technology to power low priority loads from the mains supply. • Smart Active Mode: the UPS automatically decides which operating mode to use (VI or VFI) depending on the quality of the mains supply. • Emergency Mode: the UPS can be set to operate only when mains power fails (emergency only mode). • Frequency converter Mode (50 or 60 Hz). HIGH QUALITY OUTPUT VOLTAGE • Even with distorting loads (IT loads with crest factor of up to 3:1). • High short circuit current on bypass. • High overload capacity: 150% on inverter, even when mains power fails. • Filtered, stabilised and reliable voltage (double conversion on-line technology, VFI compliant with EN62040-3 specifications, with filters to suppress atmospheric interference). • Rephasing of the load: UPS input power factor close to 1 with sinusoidal current absorption. 48 SIMPLIFIED INSTALLATION OTHER FEATURES ADVANCED COMMUNICATION • The UPS can be connected to both single phase and three phase mains supplies. • Output terminal board + 2 IEC plugs to power local equipment (computers, modems, etc.). • Easy to move thanks to built-in wheels. • Advanced diagnostics: status, measurements and alarms available on the custom LCD display. • Very low noise level (<40dBA): for installation in any environment thanks to the PWM digitally controlled ventilation that is load dependent, and the use of an inverter with high switching frequency (>20kHz, value above the audible range). • Autorestart when mains power returns, can be programmed using software or the digital front panel display. • Emergency mode: the UPS can be programmed to work only when mains power fails (suitable for emergency lighting). • Standard back feed protection: to avoid current being fed back into the mains system. • Digital updating of the UPS (flash upgradable). • Compatible with the AROS TeleNetGuard remote assistance system. • Advanced, multiplatform communication for all operating systems and network environments: Watch&Save 3000 monitoring and shutdown software included, for Windows 2008, Vista, 2003, XP, Mac OS X, Sun Solaris, Linux, Novell and other Unix operating systems. • RS232 serial port. • Plug and Play connection. • Slots for communication interface boards. HIGH BATTERY RELIABILITY • Automatic and manual battery tests. • Low Ripple Current Discharge system “LRCD” to prolong battery life. • Unlimited extendable runtime thanks to dedicated modular design Battery Boxes. • Increased ride-through for mains failures up to 40ms (high hold up time) and for fluctuations in the input voltage ranging from 84V to 276V). LOW IMPACT ON MAINS POWER • Sinusoidal input current on single phase/single phase series. APPLICATIONS • Local Area Networks (LAN) • Data Centers • Servers • Industrial PLCs • Cash registers • Electromedical devices • Emergency devices (lights/alarms) • Telecomunication devices 49 Sentinel XR Plus Technical data Models XRMP 5000 XRMP 6000 XRTP 6500 XRTP 8000 XRTP 10000 Power 5000VA/4000W 6000VA/4800W 6500VA/5200W 8000VA/6400W 10000VA/8000W Input XRMP 5000 XRMP 6000 XRTP 6500 XRTP 8000 XRTP 10000 Rated voltage 220-230-240 Vac single-phase Minimum voltage without battery intervention 220-230-240 Vac single-phase or 380-400-415 Vac three-phase with neutral 170 Vac @ load 100% / 140 Vac @ load 50% Rated frequency By pass 50/60 Hz ± 5Hz XRMP 5000 Voltage range XRMP 6000 Frequency range Batteries XRTP 8000 XRMP 5000 XRMP 6000 XRTP 6500 XRTP 8000 XRTP 10000 XRTP 8000 XRTP 10000 6-8h XRMP 5000 Rated voltage XRMP 6000 XRTP 6500 220 - 230 - 240 Vac selectable Static variation ± 1,5 % ≤ 5% in 20 ms Dynamic variation Waveform Sinewave Voltage distortion with linear load < 3% Voltage distortion with non-linear load < 6% Frequency 50/60 Hz selectable or auto sensing Crest factor ≥3:1 Overload capacity 100% < Load < 125% 125% ≤ Load < 150% Load ≥ 150% XRTP 10000 Selected frequency ±5Hz Recharge time Output XRTP 6500 180 - 264 Vac (selectable in Economy Mode and SMART Mode) XRMP 5000 XRMP 6000 SXRP 6500 SXRP 8000 SXRP 10000 1’ 4” 0.5” 50 Sentinel XR Plus System XRMP 5000 XRMP 6000 XRTP 6500 XRTP 8000 XRTP 10000 Weight (kg) 89 90 91 94 95 Dimensions (wdh) (mm) 282x785x615 Efficiency Smart Mode up to 98% Operating temperature O °C ÷ +40 °C Humidity < 95% non condensing Protection Overload - short-circuit - overvoltage - undervoltage - temperature - low battery Compliance EN 62040-1 EMC EN 62040-2 Directives 2006/95/EC - 2004/108 EC EN 62040-3 Communication RS232 + USB + remote contacts + communication interface slot Colour Dark grey (RAL 7016) Noise <45 dBA at 1 m Details ON/OFF switch Communication interface slot Emergency power off (EPO) Serial interface port IEC sockets Input switch (SWIN) Battery fuse holders (SWBT) USB port Maintenance bypass (SWMB) Output switch (SWOUT) 51 SENTRY HPS HM/HT provides maximum protection for vital ‘missioncritical’ networks, security applications (electro-medical) and industrial applications thanks to its outstanding mechanical and electrical design. The load is powered continuously by the inverter with a filtered, stabilised and regulated sinewave supply. The input and output EMI filters considerably increase the immunity of the load to mains disturbances and surges. The SENTRY HPS HM/HT series uses on-line double conversion technology (VFI) with an isolation transformer on the inverter output. SENTRY HPS HM/HT is supplied with Watch&Save 3000 software as standard and can be remotely monitored using the PowerNetGuard system from anywhere in the world. Additional battery extension packs allow the standard battery runtime to be extended up to several hours. Sentry HPS The Sentry HPS range features a wide range of modules and configurations that can be manufactured into one complete system to solve your power problems. Each system is therefore unique and we ask that you consult our engineers for your specific application. • Sentry HPS can achieve efficiencies >98% thanks to a selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity should the mains fail. • 0.8 power factor makes Sentry HPS suitable for powering ICT and industrial loads • High level diagnostics: event log with 128 messages, states, measurements and alarms - available from the built-in LCD in several languages • BACK FEED protection: to avoid energy feeding back into the mains supply should a fault occur NO-BREAK POWER ARCHITECTURES LOW CONSUMPTION LEVELS OTHER CHARACTERISTICS OPTIONS MINIMUM IMPACT ON SUPPLIES EASY SOURSE Input current distortion <4% for the Sentry HPS with filter with sinusoidal absorption to remove the risk of resonance with other input supply users or phase shift capacitor sets. The absorbed current distortion is independent of input supply parameters such as impedance. This enables Sentry HPS to deliver maximum performance levels regardless of the installation environment. With these input features Sentry HPS can achieve significant savings in terms of sizing and power supply sources - isolation transformers and generators over less sophisticated power systems. MAXIMUM BATTERY CARE SIMPLE TO INSTALL • Capability to install the UPS into any distribution system (neutral not required on rectifier input) • Capability to separate the rectifier/bypass power networks and to power these from two separate sources, without Galvanic isolation (necessary on UPS without an output transformer) HIGH RELIABILITY • Extremely high short-circuit current to ensure compatibility with the most difficult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output • Full microprocessor control with no-break static and manual bypasses • IGBT technology • Battery deep discharge protection • Temperature compensating charger • Built-in automatic and manual battery test feature • Isolation transformers • Various lead acid battery types including 5 year, 10 year and 20 year design life, VRLA, NiCad options and runtimes up to several hours • Communications software • Solutions for low input current distortion • Closed loop parallel kit option (to be ordered with the unit) SPECIFIC SOLUTIONS The UPS can be adapted to your requirements. Please contact AROS S.r.l. to discuss specific applications and options. MAXIMUM RELIABILITY AND AVAILABILITY • Connect up to 8 units in parallel or N+1 redundancy, even of different power ratings. The UPS continue to work in parallel even if one of the interconnecting communication cables is disconnected (CLOSED LOOP). ADVANCED COMMUNICATION • Compatible with PowerNetGuard for remote maintenance • Advanced, multi-platform communication, for all operating systems and network environments: Watch&Save 3000 supervision and shut-down software included, with SNMP agent, for Windows 95, 98, NT 4.0, Me, 2000, 2003, XP, Mac OS 9.x, X, Linux, Novell operating systems. The UPS is supplied with a cable for direct connection to the PC (Plug and Play) • RS232 serial port • Volt-free signal contacts • EPO (Emergency Power Off) shutdown input contact • Input for switching to bypass by remote signal • LCD or LED-based remote control panel • Graphic Display Remote Panel • Generator interface: enables desynchronisation of the UPS output from a generator supply which may be subject to phase and frequency variations. The interface also enables more economic use of the battery charger. APPLICATIONS • Servers • Local Area Network (LAN) • Data centers • Telecommunications • Industrial equipment • Electro-medical equipment 60 61 Sentry HPS Fig 1- Bock diagram UPS in parallel up to 8 units EXPANDABILITY The units can be connected in parallel up to 8 units to increase power availability or redundancy. The single module or the system can be expanded any time to suit power requirements without influencing the initial investment. Thanks to the peculiarity of the “Hot System Expansion” feature, the additional unit can be connected in parallel while the other units are on-line and supplying regular power to the load. The new UPS is on-line and will be set up automatically. 80 kVA 62 Three-phase input Three-phase output Three-phase input Single-phase output Sentry HPS Sentry HPS 8 Power (kVA) HM8 Models Input HM8 Technical data HM10 10 HM10 HM15 15 HM15 Rated voltage Voltage range Frequency range Power factor Current harmonic distortion Soft start By pass HM20 20 HM20 HM30 30 HM30 HM40 40 HM40 HM60 60 HM60 HM80 80 HM80 HM100 100 HM100 400 Vac three-phase ± 20% 45 ÷ 65 Hz > 0.92 with harmonic filter < 5% with harmonic filter 0-100% in 10” HM8 HM10 Rated voltage Permitted voltage range Rated frequency Permitted frequency range Standard features Batteries HM15 HM20 HM30 HM40 HM10 HM15 HM20 HM30 HM40 HM60 HM80 HM100 HM8 System HM10 10 8 HM10 HM15 HM20 HM30 HM40 HM100 HM20 HM30 290 HM40 340 Models Power (kVA) Batteries HT10 10 HT10 HT15 15 HT15 HT20 20 HT20 HM60 440 HM80 80 64 HM80 520 HM100 100 80 HM100 650 1070x 740x1400 65 dBA at 1 m >92% Safety EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3 Yes Yes Yes No No No No Inverter output Rated power (kVA) Active power (kW) Number of phases Rated voltage Regulation of the output voltage Crest factor (Ipeak/Irms) Static stability Dynamic stability Frequency Overload Frequency stability System Weight (kg) HT15 HT15 HT20 HT20 HT30 30 HT30 HT30 HT40 40 HT40 HT40 HT40 HT60 60 HT60 HT60 HT60 HT80 80 HT80 HT80 HT80 Maintenance-free lead-acid VRLA AGM/GEL; NiCd 0,2xC10 <1% HT10 10 8 HT10 From 210 to 480 Dimensions (wdh) (mm) Remote signaling Remote controls Communication Operating temperature Relative humidity Colour Noise Protection degree Efficiency Compliance Internal batteries HT30 400 Vac three-phase ± 20% 45 ÷ 65 Hz > 0.9 with harmonic filter < 5% with harmonic filter 0-100% in 10” HT10 400 Vac three-phase ± 15% (selectable from ± 10% to ± 25% from front panel) 50/60 Hz ± 2% (selectable from ± 1% to ± 5% from front panel) BackFeed protection; split bypass line HT10 Type Maximum recharge current (A) AC ripple voltage HM60 15 20 30 40 60 12 16 24 32 48 1 230 Vac single-phase 220 ÷ 244 Vac phase/neutral (from control panel) 3:1 ± 1% ± 5% 50/60 Hz configurable 110% 125% 150% of the rated current for 5h/10’/1’ ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5%) with mains supply present HM15 800x740x1400 60 dBA at 1 m By pass Rated voltage Permitted voltage range Rated frequency Permitted frequency range Standard features HM80 Maintenance-free lead-acid VRLA AGM / GEL; NiCd 0,2xC10 <1% HM8 8 6.4 Weight (kg) From 200 to 470 From 220 From 230 to 490 to 500 555x720x1200 Volt free contacts EPO and Bypass RS232 + remote contacts O °C / +40 °C < 95% non condensing Light grey (RAL 7035) 54 dBA at 1 m IP20 >91% Yes Input Rated voltage Voltage range Frequency range Power factor Current harmonic distortion Soft start HM60 230 Vac single-phase ± 15% (selectable from ± 10% to ± 25% from front panel) 50/60 Hz ± 2% (selectable from ± 1% to ± 5% from front panel) BackFeed protection; split bypass line HM8 Type Maximum recharge current (A) AC ripple voltage Inverter output Rated power (kVA) Active power (kW) Number of phases Rated voltage (V) Regulation of the output voltage Crest factor (Ipeak/Irms) Static stability Dynamic stability Frequency Overload Frequency stability From 190 to 460 Dimensions (wdh) (mm) Remote signaling Remote controls Communication Operating temperature Relative humidity Colour Noise Protection degree Efficiency Compliance Internal batteries HT15 HT20 HT30 HT40 HT60 15 20 30 40 60 12 16 24 32 48 3+N 400 Vac 348 ÷ 424 Vac phase/neutral (from control panel) 3:1 ± 1% ± 5% 50/60 Hz configurable 110% 125% 150% of the rated current for 5h/10’/1’ ± 0,05% on mains failure; ± 2% (selectable from ± 1% to ± 5%) with mains supply present HT15 From 220 to 490 54 dBA at 1 m HT20 HT30 From 230 From 282 to 500 to 552 555x720x1200 Volt free contacts EPO and Bypass RS232 + remote contacts O °C / +40 °C < 95% non condensing Light grey (RAL 7035) 60 dBA at 1 m IP20 > 90% HT40 330 HT60 450 HT80 80 64 HT80 555 800x740x1400 62 dBA at 1 m > 91% > 92% Safety EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3 Yes Yes Yes No No Yes No No 64 65 The SPRING series includes models from 500VA to 3000VA and uses sinewave digital technology. The SPRING range, with its advanced communications and connectivity options, is the ideal solution for the most demanding of customers looking for superior protection and versatility. SPRING is the best protection for network devices, rack mounted servers, conventional rack-mounted or tower servers, network storage systems. VERY HIGH PROTECTION The Automatic Voltage Regulation provides stabilisation from brownouts, sag and surge voltages without making use of the batteries. Less frequent usage of the batteries means that they will be fully charged when really needed and last longer. EMI filters then provide further protection from spikes and transients. When the mains power supply fails, the load is powered by the inverter and receives a true SINEWAVE supply for maximum power continuity and reliability. The UPS also incorporates a protection for PC and network, telephone line/modem connections (RJ45-RJ11). Spring Spring Models S 500T Technical data S 800T 235x110x383 Dimensions (hwd) (mm) 800VA/540W Power Weight (kg) 500VA/350W 7,2 4 (10A) IEC output sockets 1 (10A) IEC mains input plug S 1100T 1100VA/740W S 1500T S 2000T 11 1 (10A) 4 (10A) S 2200RT S 3000RT 1500VA/1050W 2000VA/1350W 2200VA/1540W 3000VA/2100W 235x160x425 10,6 1 (10A) 4 (10A) 18 1 (10A) 4 (10A) 18,4 1 (10A) 4 (10A) 88x582x438 31 32 1 (16A) 1 (16A) 8 (10A) - 1 (16A) Input 160 V - 294 V Voltage range 230 Vac Rated voltage Frequency 50/60 Hz auto sensing Frequency range • Advanced, multi-platform communication for all operating systems and network environments: Watch&Save 3000 monitoring and shut-down software included, with SNMP agent, for Windows 95, 98, NT 4.0, Me, 2000, 2003, XP, Mac OS 9.x, X, Linux, Novell and many other popular operating systems • USB or RS232 serial port (selectable) • Slot-in SNMP network adapter card • LCD display provides information concerning alarms, status and measure of the major electrical parameters of input, output and battery. Powershare output socket provides the load-shedding of the least critical load to maximise the back up time of the most critical servers. Hot Swappable battery from the front of the UPS allows easy and no-risks maintenance of the UPS. Additional Battery Box and extended charging current are available in 2200RT and 3000RT for very long back up time applications. Predictive battery testing to spot potential battery deterioration and failure. Deep discharge protection to reduce overall battery aging. ADVANCED COMMUNICATION HIGH AVAILABILITY VERSATILITY Spring (2200RT and 3000RT) can be placed directly onto the floor or mounted in 19’’ rack mount cabinets. The front panel digital display can be easily pulled out and rotated to suit the installation format. Tower and Rack versions includes Emergency Power Off switch, which allows to shutdown the output power in case of emergency situations. Cold start function enables Spring to start up when power network is not available. ± 5% Output Rated voltage 230 Vac (-5%, -10%) True sinewave Waveform 50 or 60 Hz auto sensing Frequency Batteries Type VRLA AGM Maintenance-free lead-acid Recharge time 4-6 h System Protection Overload - short-circuit - overvoltage - undervoltage - temperature - low battery Communication USB / RS232 / slot for interface communication Safety compliance IEC / EN62040-1-1 and Directive EEC 73/23 EMC conformance IEC / EN62040-2 and Directive EEC 89/336 Performance IEC / EN62040-3 Relative humidity • Personal computers • Small computers network • Local Area Networks (LAN) • Workstations • Servers • EPOS (Electronic Point Of Sales) system -15 °C - 45 °C Storage temperature APPLICATIONS 0 °C / + 40 °C Operating temperature < 95% non condensing Noise < 55 dBA Details USB port 2-YEAR WARRANTY Serial interface port RS232 Slot for SNMP network adapter card Output sockets IEC Telephone/ it network protection OPTIONS Battery box (only 2200RT/3000RT) Powershare socket Mains input IEC S 500T-800T-1100T S 1500T-2000T 33 32 The SPRING series includes models from 500VA to 3000VA and uses sinewave digital technology.The SPRING range, with its advanced communications and connectivity options, is the ideal solution for the most demanding of customers looking for superior protection and versatility. SPRING is the best protection for network devices, rack mounted servers, conventional rack-mounted or tower servers, network storage systems. VERY HIGH PROTECTION The Automatic Voltage Regulation provides stabilisation from brownouts, sag and surge voltages without making use of the batteries. Less frequent usage of the batteries means that they will be fully charged when really needed and last longer. EMI filters then provide further protection from spikes and transients. When the mains power supply fails, the load is powered by the inverter and receives a true SINEWAVE supply for maximum power continuity and reliability. The UPS also incorporates a protection for PC and network, telephone line/modem connections (RJ45-RJ11). Spring Rack Spring Rack Models Power Dimensions (hwd) (mm) Weight (kg) S 500R Technical data S 800R 500VA/350W 1U x 19” x 460 12 S 500R Input 4 (10A) IEC output sockets 1 (10A) IEC mains input plug 800VA/540W 1U x 19” x 460 13,5 1 (10A) 4 (10A) S 800R S 1100R 1100VA/740W 2U x 19” x 582 15,6 1 (10A) 4 (10A) S 1100R ADVANCED COMMUNICATION HIGH AVAILABILITY APPLICATIONS • Personal computers • Small computers network • Local Area Networks (LAN) • Workstations • Servers • EPOS (Electronic Point Of Sales) system S 1500RT 230 Vac Rated voltage Output 2U x 19” x 582 31 1 (16A) S 3000RT 3000VA/2100W 2U x 19” x 582 32,8 1 (16A) 8 (10A) - 1 (16A) S 2200RT S 3000RT 50/60 Hz auto sensing ± 5% S 500R S 800R Rated voltage S 1100R S 1500RT S 2200RT S 3000RT 230 Vac (-5%, -10%) True sinewave Waveform 50 or 60 Hz auto sensing Frequency Batteries S 500R S 800R Type S 1100R S 1500RT S 2200RT S 3000RT VRLA AGM Maintenance-free lead-acid Recharge time System S 2200RT 1500VA/1050W 2200VA/1540W 2U x 19” x 582 28,7 1 (10A) 8 (10A) S 1500RT 160 V - 294 V Voltage range Frequency Frequency range • Advanced, multi-platform communication for all operating systems and network environments: Watch&Save 3000 monitoring and shut-down software included, with SNMP agent, for Windows 95, 98, NT 4.0, Me, 2000, 2003, XP, Mac OS 9.x, X, Linux, Novell and many other popular operating systems • USB or RS232 serial port (selectable) • Slot-in SNMP network adapter card • LCD display provides information concerning alarms, status and measure of the major electrical parameters of input, output and battery. Powershare output socket provides the load-shedding of the least critical load to maximise the back up time of the most critical servers. Hot Swappable battery from the front of the UPS allows easy and no-risks maintenance of the UPS. Additional Battery Box and extended charging current are available in tower 2200 and 3000 for very long back up time applications. Predictive battery testing to spot potential battery deterioration and failure. Deep discharge protection to reduce overall battery aging. VERSATILITY Spring RT (tower 1500, 2200 and 3000) can be placed directly onto the floor or mounted in 19’’ tower mount cabinets. The front panel digital display can be easily pulled out and rotated to suit the installation format. Tower and rack versions includes Emergency Power Off switch, which allows to shutdown the output power in case of emergency situations. Cold start function enables Spring to start up when power network is not available. 4-6 h S 500R S 800R Protection S 1100R S 1500RT S 2200RT S 3000RT Overload - short-circuit - overvoltage - undervoltage - temperature - low battery Communication USB / RS232 / slot for interface communication IEC / EN62040-2 and Directive EEC 89/336 EMC conformance IEC / EN62040-1-1 and Directive EEC 73/23 Safety compliance Performance IEC / EN62040-3 -15 °C - 45 °C Storage temperature 0 °C / + 40 °C Operating temperature Relative humidity < 95% non condensing Noise < 55 dBA Details Output sockets IEC S 500R-800R-1100R Powershare socket S 1500R Output sockets IEC Mains input IEC Powershare socket USB Serial port interface port RS232 OPTIONS Battery box (only 2200RT/3000RT) EPO Thermal fuses Output sockets IEC Telephone/it network protection S 2200R-3000R Battery expansion connector Output sockets IEC 16A 35 34 Stabilisers The operating principle of an electronic stabiliser is based on the regulation of the voltage through self-transformer sockets selected and connected to the output via static switches. Regulation is determined by a specific electronic control circuit. Advantages of using an electronic stabiliser are: • No harmonic distortion • Insensitive to the type of load or power factor • Low weight/power ratio • High reliability • High voltage regulation speed. Proper operation of most electric and electronic equipment depends to a large extent on the power supply voltage that must be kept as steady and as near to the nominal value as possible. In many installations, the mains power supply tends to fluctuate for a number of reasons. So devices that overcome and correct this problem are often used and the ideal solution is a stabiliser. AROS produces a full range of electromechanical and electronic stabilisers as well as electronic line conditioners. ELECTRONIC STABILISERS WHY USE STABILISERS? ELECTROMECHANICAL STABILISERS This type of stabiliser controls the voltage output by adding or removing (by moving a brush converter) voltage so as to restore output to the nominal value. Advantages of using an electromechanical stabiliser are: • High quality voltage • Insensitive to the type of load or power factor • Low weight/power ratio • High stabilizing accuracy • High reliability • Wide range of power ratings for single-phase or three-phase voltages. ELECTRONIC LINE CONDITIONERS An electronic line conditioner combines an electronic stabiliser, an isolating transformer and high attenuation EMI/RFI filters in a single unit. It provides maximum protection for installations susceptible to voltage fluctuations, high frequency line noise and power surges. Advantages of the line conditioners are: • Isolation between the line and the load • No harmonic distortion • Insensitive to the type of load or power factor • High voltage regulation speed • Protection against power surges • Protection against line noise. 77 Voltronic 4 single-phase Voltronic 4 single-phase Technical data V4-500 V4-1000 Nominal output voltage V4-2000 A LED panel provides information on: • Mains input voltage exceeding regulation limits • Mains frequency exceeding limit • Load level • Overload • Alarm for input overvoltage and/or overheating (the visual alarm is accompanied by an acoustic alarm). V4-4000 V4-5000 V4-10000 220-230-240 Vac single-phase Input voltage range -18% +14% depending on the selected output voltage Frequency 48 -62 Hz 2,4 Maximum output current at 230V (A) 0,5 Power (kVA) 1 2 4,5 4 9 18 ±3% Accuracy 98% Efficiency 0 to 100% Accepted load variation 2 Regulation speed (ms/V) Load power factor 5 22 10 44 Any Overload The VOLTRONIC 4 single-phase electronic voltage stabiliser is able to adjust the output voltage within ±3% of the rated voltage. The main features of the VOLTRONIC 4 electronic voltage stabilisers are: • Microprocessor full control • Compact size • High regulation speed • High efficiency • Insensitivity to load variations and power factor. 1,5 IN x 5 sec Harmonic distortion <0,5% Cooling Natural Forced ventilation Operating ambient temperature 0°C ÷ 40°C Mains OK, load level, overload, alarms Display indications IP 20 Protection degree Acoustic alarm Active for overload, over-voltage, over-temperature Schuko socket Output connection Cable with Schuko plug Input connection Fuse Output protection Fuse Input protection V4-500 Dimensions (wdh) mm Weight (kg) Automatic switch Fuse Internal terminal board Internal terminal board V4-1000 V4-2000 V4-4000 180x215x194 9 V4-5000 230x350x275 10 21 V4-10000 340x540x310 25 27 51 78 79 Voltronic 4 three-phase Voltronic 4 three-phase Technical data V4 3F-6000 Nominal output voltage V4 3F-10000 A LED panel provides information on: • Mains input voltage exceeding regulation limits • Mains frequency exceeding limit • Load level • Overload • Alarm for input overvoltage and/or overheating (the visual alarm is accompanied by an acoustic alarm). V4 3F-12000 V4 3F-15000 380/400/415 Vac + N selectable Input voltage range -18% +14% depending on the selected output voltage Frequency 48 - 62 Hz 9 Maximum output current at 230V (A) 6 Power (kVA) 10 12 15 18 Independent on each phase Regulation ±3% Accuracy 98% Efficiency Regulation speed (ms/V) 15 22 2 Overload 1,5 IN x 5 sec Accepted load variation The VOLTRONIC 4 three-phase electronic voltage stabiliser is able to adjust the output voltage within ±3% of the rated voltage. Voltage stabilisation is performed independently on each phase. The main features of the VOLTRONIC 4 three-phase electronic voltage stabilisers are: • Microprocessor full control • Compact size • High regulation speed • High efficiency • Insensitivity to load variations and power factor. 0 to 100% Load power factor Any Harmonic distortion <0,5% Cooling Natural Forced ventilation Operating ambient temperature 0°C ÷ 40°C Mains OK, load level, overload, alarms Display indications IP 20 Protection degree Internal terminal board Output connection Internal terminal board Input connection Fuse on each phase Output protection Automatic switch Input protection Active for overload, over temperature, irrecoverable failure Acoustic alarm V4 3F-6000 V4 3F-10000 Dimensions (wdh) (mm) Weight (kg) V4 3F-12000 V4 3F-15000 340x540x310 44 48 52 60 80 81 ELC Line Conditioners ELC Line Conditioners Technical data ELC 1500 guarantee and effective protection as they combine an electronic stabilizer, EMI/RFI filters and an isolating transformer in a single unit. The equipment is controlled by a microprocessor logic that also sounds alarms in the event of overloads, overvoltage or overheating. ELC 3000 220/230/240 Vac selectable, single-phase Nominal output voltage 220/230/240 Vac single-phase Nominal input voltage Input voltage range ELC 5000 -18% +14% depending on the selected output voltage Input frequency Power (kVA) Max. output current at 230V (A) 48 - 62 Hz 1,5 3 7 5 14 ±3% Accuracy 95% Efficiency Regulation speed (ms/Volt) 22 2 Overload 1,5 IN x 5 sec Accepted load variation The electronic line conditioners of the ELC range have been specially designed to protect electronic control equipment such as PC’s, PLC’s, internet devices, laboratory instrumentation, data transmission and audio-video apparatus, against anomalies or interference in the power supply circuit. In particular, ELC protect against line noise and power surges ensuring effective voltage regulation. The electronic line conditioners 0 to 100% Load power factor Any Harmonic distortion <0,5% 70 dB Common mode rejection ratio Up to 4KV - 130 Joule Input peak voltage protection Primary and secondary insulation voltage 2500V input/output Cooling Natural Operating ambient temperature Forced ventilation 0°C ÷ 40°C Line OK, load level, overload, alarms Display indications IP 20 Protection degree Acoustic alarm Active for overload, overvoltage, overtemperature Internal terminal board Output connection Internal terminal board Input connection Fuses Output protection Automatic switch Input protection ELC 1500 Dimensions (wdh) (mm) Weight (kg) ELC 3000 230x350x275 ELC 5000 340x540x310 26 44 56 82 83 RQ RQ Power (kVA) Input voltage range mains nor by the value and load power factor; the output power distortion is very low (<0,2%) and the total efficiency is very high. The installation of the RQ stabilizers is very flexible: their special shape makes it easy to install them near the equipment to power or inside it. They can be mounted on the wall or in a cabinet. Technical data 2,5 / 2 1 RQ 2500 RQ 1000 ±25% 18 Regulation speed (ms/Volt) 4 Maximum output current (A) Efficiency 94% ±15/20% 11 18 96% ±15/20% Input voltage range 15 / 10 10 / 7,5 Power (kVA) RQ K15 RQ K10 18 Regulation speed (ms/Volt) 44 Maximum output current (A) Efficiency The RQ stabilizers belong to the electromechanical series with electronic control. They provide a perfect constant single-phase output voltage completely independent from any variation of the input voltage within the accepted voltage range. The stabilisation of the output voltage is not affected neither by eventual harmonic distortion present in the 96% ±15/20% 65 18 98% RQ 5000 5/4 ±15/20% 22 18 97% RQ K25 25 / 18 ±15/20% 109 20 98% RQ 7000 7 / 5,5 ±15/20% 31 18 98% RQ K35 35 / 26 ±15/20% 152 20 98% Common characteristics Nominal input/output voltage 230 Vac Accuracy ±1% 0 to 100% Load variation 50/60 Hz Nominal frequency Load power factor Any Harmonic distortion <0,2% Cooling Natural Operating ambient temperature -5°C ÷ 40°C Protection degree Dimensions (wdh) (mm) Weight (kg) Dimensions (wdh) (mm) Weight (kg) IP 21 275x425x260 275x425x260 RQ 2500 RQ 1000 19 RQ 5000 275x425x260 22 28 300x565x280 300x565x280 RQ K15 RQ K10 50 RQ K25 405x670x1150 55 125 RQ 7000 300x565x280 42 RQ K35 405x670x1150 130 85 84 Tristab-T Tristab-T provided on the average value of threephases and then these stabilizers are suitable for maximum 50% unbalanced load. There is the possibility of choosing between two input voltage ranges according to the nominal power required (see table). The operator panel includes a digital voltmeter which inform on the status of the line downstream on the voltage of each phase and the linked voltages. All models (up to 60kVA) are provided with wheels for an easier positioning and handling. Technical data 4 Power (kVA) with input ±20% 10 5 Power (kVA) with input ±15% T10 T5 Input voltage range 7,5 60 Power (kVA) with input ±20% 105 75 Power (kVA) with input ±15% T105 T75 96% 95% Efficiency 18/13 18/13 Regulation speed (ms/Volt) 14 7 Maximum output current (A) ±15/20% ±15/20% Input voltage range TRISTAB-T series includes several voltage stabilizers of electromechanical type with electronic control. They provide a perfect three-phase output voltage completely independent from any variation of the input voltage within the accepted voltage range. The stabilisation of the output voltage is not affected neither by eventual harmonic distortion present in the mains nor by the value and the load power factor; the distortion of the output voltage is very low (<0,2%); the total efficiency is very high. The voltage regulation is 18/13 18/13 Regulation speed (ms/Volt) 150 107 Maximum output current (A) ±15/20% ±15/20% T15 15 12 ±15/20% 21 18/13 97% T135 135 80 98% 98% Efficiency 105 ±15/20% 193 18/13 98% T20 20 15 ±15/20% 28 18/13 98% T175 175 135 ±15/20 253 18/13 98% T30 30 24 ±15/20% 43 18/13 98% T230 230 175 ±15/20% 332 20/18 98% T50 50 36 ±15/20% 71 18/13 98% T60 60 45 ±15/20% 87 18/13 98% T300 300 230 ±15/20% 433 20/18 98% Common characteristics Nominal input/output voltage 400 Vac Accuracy ±1% Nominal frequency 50/60 Hz Load variation 0 to 100% Load power factor Any Harmonic distortion <0,2% Cooling Forced ventilation Operating ambient temperature -5°C ÷ 40°C Protection degree IP 21 T5 Dimensions (wdh) (mm) Weight (kg) T10 T15 T20 360x520x1000 50 T75 Dimensions (wdh) (mm) Weight (kg) T30 T50 405x670x1150 60 T105 605x800x1400 320 110 T135 605x800x1600 480 120 T175 160 T230 T60 605x800x1400 200 250 T300 605x850x1650 1210x800x1600 1210x850x1700 500 700 800 1200 86 87 Tristab-Y Tristab-Y useful with unbalanced three-phase loads or single-phase loads. For proper operation, the presence of the neutral wire is necessary. There is the possibility of choosing between two input voltage ranges according to the nominal power required (see table). The operator panel includes a digital voltmeter which provides information on the voltage of each phase and the linked voltages. All models (up to 60kVA) are provided with wheels for an easier positioning and handling. Technical data 4 Power (kVA) with input ±20% 10 5 Power (kVA) with input ±15% Y10 Y5 Input voltage range 7,5 105 75 Y105 Y75 96% 95% Efficiency 18/13 18/13 Regulation speed (ms/Volt) 14 7 Maximum output current (A) ±15/20% ±15/20% 60 Power (kVA) with input ±20% Power (kVA) with input ±15% Input voltage range TRISTAB-Y series includes several voltage stabilizers of electromechanical type with electronic control from 5 to 300kVA. They provide a perfect threephase output voltage completely independent from any input voltage variation within the accepted voltage range. The stabilisation of the output voltage is not affected neither by eventual harmonic distortion present in the mains nor by the value and load power factor; the output voltage distortion is very low (<0,2%); the total efficiency is very high. In the "Y" version the stabilising effect is obtained independently on each phase. This solution is therefore particularly 18/13 18/13 Regulation speed (ms/Volt) 151 107 Maximum output current (A) ±15/20% ±15/20% Y15 15 12 ±15/20% 21 18/13 97% Y135 135 80 98% 98% Efficiency 105 ±15/20% 193 18/13 98% Y20 20 15 ±15/20% 28 18/13 98% Y175 175 135 ±15/20% 253 18/13 98% Y30 30 24 ±15/20% 43 18/13 98% Y230 230 175 ±15/20% 332 20/18 98% Y50 50 36 ±15/20% 71 18/13 98% Y60 60 45 ±15/20% 87 18/13 98% Y300 300 230 ±15/20% 433 20/18 98% Common characteristics Nominal input/output voltage 400 Vac Accuracy ±1% Nominal frequency 50/60 Hz Load variation 0 to 100% Load power factor Any Harmonic distortion <0,2% Cooling Forced ventilation Operating ambient temperature -5°C ÷ 40°C Protection degree IP 21 Y5 Y10 Dimensions (wdh) (mm) Weight (kg) Dimensions (wdh) (mm) Weight (kg) Y15 Y20 360x520x1000 70 Y30 Y50 405x670x1150 75 110 605x800x1600 605x800x1400 Y135 Y75 Y105 350 540 580 145 Y175 170 Y230 Y60 605x800x1400 190 260 Y300 1210x800x1600 1210x850x1700 610 900 1200 88 89 The SYNCRO series includes the 8002000VA models and uses digital technology. The load is powered from the mains through an AVR to stabilise brownout, sag and surge voltages, and EMI filters to suppress spikes and transients. When the mains fails, the load is powered by the inverter with a pseudo sinewave to provide sufficient runtime for computer system shutdown using the Watch&Save 3000 software supplied as standard. The UPS also incorporates a filtered socket for PC network and telephone line cable protection. Syncro Syncro Models Power Input Technical data Syncro 800 800VA/480W Syncro 800 Syncro 1000 1000VA/600W Syncro 1000 ADVANCED COMMUNICATION CHARACTERISTICS Syncro 1500 1500VA/900W 220-230-240 Vac Rated voltage Syncro 1000 Syncro 1500 230 Vac (-8%, +10%) Syncro 2000 2000VA/1200W Syncro 2000 Pseudo sinewave Syncro 800 Syncro 1000 Syncro 1500 Syncro 2000 Maintenance-free lead-acid VRLA, AGM 6-8 h Syncro 800 14 Syncro 1000 Syncro 1500 14.5 15 140x375x180 Dimensions (wdh) (mm) Safety compliance APPLICATIONS Syncro 2000 50/60 Hz auto sensing Syncro 800 Voltage on mains operation 50 or 60 Hz (± 0.5%) 2 ms Waveform on battery operation Batteries Type Recharge time System Weight (kg) Battery low - overcurrent - short-circuit Protection Tel/Modem protection Syncro 2000 20 140x410x214 RJ45 connectors Communication EMC conformance • Personal computers • Small computers network 2-YEAR WARRANTY Syncro 1500 230 Vac (±25%) Voltage range Frequency Output 230 Vac (± 5%) Voltage on battery operation Frequency on battery operation Transfer time • High level multi-platform communication for all operating systems and network environments: Watch&Save 3000 monitoring and shut-down software included, with standard integrated SNMP agent, for Windows 95, 98, NT 4.0, Me, 2000, 2003, XP, Mac OS 9.x, X, Linux, Novell operating systems • The UPS is supplied with a communications cable for ‘Plug and Play’ PC connection • Mains power supply stabilisation and filtering (technology with AVR and filters for atmospheric disturbance suppression) • Cold start capability: the UPS can power up without a mains supply present • Auto restart at power-up • Integrated protection for PC networks and telephone line/modem connections RJ11 • High reliability with built-in automatic battery test feature For advanced communication and top flight performance, SYNCRO is the ideal solution for small network users requiring total control of their power system. RS232 port EN 62040-1-1 and Directive 73/23, 93/68 EEC, EN 62040-3 EN 62040-2 and Directive 89/336, 192/31 EEC, 93/68 EEC Surge capability IEC 801-5 Noise < 40 dBA at 1 m Colour Dark grey Operating temperature 0 °C / +40 °C Storage temperature -15 °C / +45 °C Relative humidity < 95% non condensing Details Serial interface port Telephone line/ modem protection Output sockets Mains input Syncro 800-1000-1500 Syncro 2000 31 30