Installation / monitoring technique Insulation monitor IR 5879/107 varimeter 0222131 • For rooms that are used for medical purposes, in accordance with VDE 0107 • According to IEC 60 364-7-710, IEC 61 557-5, IEC 61 557-8 • For exclusively three-phase and alternating current voltage supply systems, IT system • Choice of fault actuation via slide switch for R AN = 75 or 50 kΩ • Additional monitoring of 2 independent 24 V alternating current supply systems possible via terminals X3, X4, RAN = 100 kΩ, e.g. for operating theatre lights • LED indicators to indicate readiness for operation, insulation status and contact position • Output: 2 changeover contacts • Closed circuit principle • Test pushbutton to determine whether the unit is working properly • Connection of max. 4 UP 5862 test and reporting combinations • External cancel pushbutton can be connected to terminals LT1, LT2 • Width 105 mm Function diagram Approvals and marking U UH A1/A2 t RE Earthfault R AN Application t ISO- ISO- fault fault Reset button For monitoring the insulation resistance of ungrounded three-phase and alternating current voltage supply systems in rooms used for medical purposes in accordance with VDE 0107. Indication 11-14 11-12 yellow LED M6915_a green LED: on, when operating voltage is supplied 1 yellow LED display each for: - RE ≤ 100 kΩ for advance warning - RE ≤ 75 kΩ - RE ≤ 50 kΩ - contact position - insulation fault in 24 V supply system, RE ≤ 100 kΩ Technical data Circuit diagram Auxiliary circuit Auxiliary voltage A 1/A2: Voltage range: Frequency range: A1 A2 11 12 Measuring circuit 21 14 22 24 12 11 14 22 21 24 LT1 LT2 A1 A2 PT1 PT2 X1 X2 X5 X3 X4 L PE M7575_a • LT1 • LT2 Stored • LT1 • LT2 Not stored AC 230 V 0,8 ... 1,2 U H 40 ... 400 Hz All technical data in this list relate to the state at the moment of edition. We reserve the right for technical improvements and changes at any time. Nominal voltage L/PE: Voltage range: Frequency range: Setting value R AN : Setting R AN : Internal test resistance: Alternating current internal resistance: Direct current internal resistance: Measuring voltage: Max. measuring current (RE = 0): Max. permissible external direct current voltage: Operate delay at R = 50 kΩ, CE = 1 µF AN RE from ∞ to 0,9 RAN: RE from ∞ to 0 kΩ: Hysteresis At R AN = 50 kΩ: 1 AC 0 ... 450 V 0 ... 1,15 U N 40 ... 60 Hz 50 kΩ / 75 kΩ (switchable) fixed setting 42 kΩ > 500 kΩ > approx. 130 kΩ < DC 9 V < 70 µA DC 250 V < 500 ms < 200 ms About 10 % IR 5879/107 / 29.10.02 bzd Technical data Measuring fault at RAN = 50 kΩ: Nominal consumption: Mains failure bridging: Accessories < 10 % Ambient temperature - 5 ... 50°C, within the permissible voltage range about 4 VA > 30 ms Output Contacts: IR 5879.12: Max. switching voltage: Thermal current Ith: Switching capacity to AC 15 NO contact: NC contact: Electrical life: AC 15 at 3 A, AC 230 V: Short circuit strength max. fuse rating: 2 changeover contacts AC 250 V 3A EN 60 947-5-1 EN 60 947-5-1 EN 60 947-5-1 2,5 x 105 switching cycles Test and reporting combination UP 5862 For insulation monitors to be used in medically used rooms according to VDE 0107 • For installation in flush-mounted boxes (diameter 60 mm, depth 35 mm) • Test button to check the function of the device • with green LED to indicate operation • Reset button for buzzer • with yelllow LED to indicate earth fault 3 A / AC 230 V 1 A / AC 230 V Dimensions (width x height): 80 x 80 mm Connection example 4 A gL EN 60 947-5-1 Operating mode: Permissible ambient/ storage temperature: Clearance and creepage distances overvoltage category/ contamination level: EMC Electrostatic discharge: HF irradiation: Fast transient: Interference suppression: Degree of protection: Housing: Vibration resistance: Climate resistance: Terminal designation: Wire connection: Wire fixing: Mounting: Weight: M6914_a L1 L2 L3 PE General data Continuous operation - 20 ... + 60°C / - 25 ... + 70°C AC 24V AC 24V 4 kV / 2 IEC 60 664-1 A1 8 kV (air) EN 61 000-4-2 10 V / m EN 61 000-4-3 2 kV EN 61 000-4-4 Limit value class B EN 55 011 Housing: IP 40 EN 60 529 Terminals: IP 20 EN 60 529 Thermoplastic with V0 behaviour according to UL subject 94 Amplitude 0,35 mm frequency 10 ... 55 Hz EN 60 068-2-6 20 / 060 / 04 EN 60 068-1 EN 50 005 2 x 2,5 mm 2 solid DIN 46 288 or 2 x 1,5 mm2 stranded ferruled DIN 46 228-1/-2/-3 Flat terminals with self-lifting clamping piece EN 60 999 DIN rail EN 50 022 (Can also be supplied for screw attachment) 500 g 230V A2 X3 LT X4 LT1 LT2 L PE IR5879.12/107 PT1 PT2 X1 X2 X5 PT1 PT2 X1 X2 X5 11 14 12 21 24 22 UP5862 Test + reporting unit Dimensions Width x height x depth: 105 x 90 x 62 mm Standard type IR 5879.12/107 AC 230 V 50 / 75 kΩ Article number: 0044120 • Output: 2 changeover contacts • Auxiliary voltage UN: AC 230 V • Setting value RAN : 50 / 75 kΩ • Width: 105 mm stock item E. DOLD & SÖHNE KG • D-78114 Furtwangen e-mail dold-relays@t-online.de • internet http://www.dold.com • Postf. 1251 • Tel. +49 7723 654 0 • Telefax +49 7723 654 356 2