General Guide to Low Voltage Motor Protection This guide is a general recommendation and does not include the many variables that can exist for specific situations such as special local codes, unusual temperature or other operating conditions, NEC demand factors, conductor derating, etc. Code Requirements The NEC or CEC requires that motor branch circuits be protected against overloads and short circuits. Overload protection may be provided by fuses, overload relays or motor thermal protectors. Short circuit protection may be provided by fuses or circuit breakers. Overload Protection The NEC or CEC allows fuses to be used as the sole means of overload protection for motor branch circuits. This approach is often practical for single phase motors. If the fuses is the sole means of protection, the fuse ampere rating must not exceed the values shown in Table 1. Short Circuit Protection The motor branch circuit fuses may be sized as large as shown in Table 2 when an overload relay or motor thermal protector is included in the branch circuit. Time delay fuse ratings may be increased to 225% and non-time delay fuse ratings to 400% (300% if over 600 amperes) if the ratings shown in Table 2 will not carry motor starting current. Some manufacturers’ motor starters may not be adequately protected by the maximum fuse sizing shown in Table 2. If this is the case, the starter manufacturer is required by UL 508 to label the starter with the maximum permissible fuse size. If so labeled, the maximum value is not to be exceeded. Where the percentages shown in Table 2 do not correspond to standard fuse ratings, the next larger fuse rating may be used. Standard fuse ratings in amperes: 15 45 100 225 500 1600 6000 20 50 110 250 600 2000 25 60 125 300 700 2500 30 70 150 350 800 3000 35 80 175 400 1000 4000 40 90 200 450 1200 5000 Time Delay vs. Non-Time Delay Time delay fuses are the most useful fuses for motor branch circuit application. A time-delay fuse can be sized closer to motor full load current, providing a degree of overload protection, better short circuit protection, and possible use of a smaller disconnect switch. What Ampere Rating? The selection of fuse ampere rating is a matter of experience and personal preference. Some prefer to size time delay fuses at 125% of motor full load amps. This sizing will provide a degree of protection for motors with a service factor of 1.15. Sizing fuses at 125% of motor nameplate amps in some applications may result in nuisance fuse openings. Time delay fuses sized at 125% may open at motor locked rotor current before some NEMA Class 20 overload relays operate. Nuisance fuse openings may result if Class RK1 or Class 115V Single Phase Motors Table 1 - Maximum Fuse Rating for Overload Protection Motor Service Factor or Marked Temperature Rise Service Factor of 1.15 or greater Fuse Rating as % * of Motor Full Load 125 Marked Temperature Rise not exceeding 40°C 125 All Others 115 *These percentages are not to be exceeded. Table 2 - Maximum Fuse Rating for Short Circuit Protection Fuse Rating as % * of Motor Full Load FUSE TYPE Type of Motor Non-Time Time Delay Delay All Single Phase AC Motors 300 175 AC Polyphase Motors other than Would Rotor Squirrel Cage Other than Design E 300 175 Design E 300 175 300 175 Wound Rotor Synchronous 150 150 Direct-Current (Constant Voltage) 150 150 *The non-time delay ratings apply to all class CC fuses. J fuses are sized at 125% of motor full load current. These fuses are more limiting than the RK5 and have less short time current carrying capability. Sizing time delay fuses between 125% and 150% of motor full load current provides advantages. The fuse will coordinate with NEMA Class 20 overload relays. Nuisance fuse opening will virtually be eliminated and effective short circuit protection will be maintained. 230V Single Phase Motors HP FLA* Wire Circuit Breaker Size RK5 Fuse Heavy Load HP FLA* Wire Circuit Breaker Size RK5 Fuse Heavy Load 0.25 5.8 14 15 12 1 2.9 14 15 5-6/10 0.33 7.2 14 15 15 1.5 3.6 14 15 7 0.5 9.8 14 20 17-1/2 2 4.9 14 15 9 0.75 13.8 14 25 25 3 6.9 14 15 15 1 16 14 30 30 5 8 14 15 15 1.5 20 12 40 35 7.5 10 14 20 17-1/2 2 24 10 50 40 10 12 14 25 25 3 34 8 70 60 15 17 12 35 30 5 56 4 90 100 20 28 10 60 50 7.5 80 3 110 150 25 40 8 80 70 10 100 — — 175 30 50 6 90 90 *FLA shown per HP rating is an average and does not reflect a particular motor brand. *FLA shown per HP rating is an average and does not reflect a particular motor brand. Data supplied herein is intended as a general reference tool, is based on information available at time of publication, and is subject to change. Elektrim Motors is not responsible for the accuracy or completeness of information contained herein. Users should evaluate and independently verify correctness and suitability of data herein for each individual intended application. Failure to do so could result in damage to the product, system in which it is installed and/or other property damage or personal injury. 11/14 1.0 208V Three Phase Motors 230V Three Phase Motors HP FLA* Wire Circuit Breaker Size RK5 Fuse Heavy Load HP FLA* Wire Circuit Breaker Size RK5 Fuse Heavy Load 1 4.8 14 15 9 1 4.2 14 15 8 1.5 6.9 14 15 12 1.5 6 14 15 12 2 7.8 14 15 15 2 6.8 14 15 12 3 11 14 20 20 3 9.6 14 20 17-1/2 5 17.5 12 35 30 5 15.2 14 30 30 7.5 25.3 10 50 45 7.5 22 10 45 40 10 32.2 8 60 60 10 28 10 60 50 15 48.3 6 90 90 15 42 6 80 80 20 62.1 4 100 110 20 54 4 90 100 25 78.2 3 110 150 25 68 4 100 125 30 92 2 125 175 30 80 3 110 150 40 120 1/0 175 200 40 104 1 150 200 50 150 3/0 200 300 50 130 2/0 200 250 60 177 4/0 250 300 60 154 3/0 225 300 75 221 300 300 400 75 192 250 250 350 100 285 500 400 500 100 248 350 350 450 125 359 2-4/0 600 600 125 312 2-3/0 450 600 150 414 2-300 600 — 150 360 2-4/0 600 600 200 552 2-500 800 — 200 480 2-350 800 — *FLA shown per HP rating is an average and does not reflect a particular motor brand. *FLA shown per HP rating is an average and does not reflect a particular motor brand. 460V Three Phase Motors 575V Three Phase Motors HP FLA* Wire Circuit Breaker Size RK5 Fuse Heavy Load HP FLA* Wire Circuit Breaker Size RK5 Fuse Heavy Load 1 2.1 14 15 4 1 1.7 14 15 3 1.5 3 14 15 5-6/10 1.5 2.4 14 15 4-1/2 2 3.4 14 15 6 2 2.7 14 15 5 3 4.8 14 15 9 3 3.9 14 15 7 5 7.6 14 15 15 5 6.1 14 15 12 7.5 11 14 20 20 7.5 9 14 15 17-1/2 10 14 14 25 25 10 11 14 20 20 15 21 10 40 40 15 17 12 35 30 20 27 10 60 50 20 22 10 45 40 25 34 8 70 60 25 27 10 60 50 30 40 8 80 70 30 32 8 60 60 40 52 6 90 100 40 41 6 80 75 50 65 4 100 125 50 52 6 90 100 60 77 3 110 150 60 62 4 100 110 75 96 1 125 175 75 77 3 110 150 100 124 2/0 200 225 100 99 1 150 175 125 156 3/0 225 300 125 125 2/0 200 225 150 150 4/0 250 350 150 144 3/0 200 300 200 240 350 350 450 200 192 250 350 *FLA shown per HP rating is an average and does not reflect a particular motor brand. *FLA shown per HP rating is an average and does not reflect a particular motor brand. Data supplied herein is intended as a general reference tool, is based on information available at time of publication, and is subject to change. Elektrim Motors is not responsible for the accuracy or completeness of information contained herein. Users should evaluate and independently verify correctness and suitability of data herein for each individual intended application. Failure to do so could result in damage to the product, system in which it is installed and/or other property damage or personal injury. 11/14 1.0