DG2 FORM ADDITIONAL INFORMATION FOR OVER 10 kW SOLAR, OR OTHER DISTRIBUTED GENERATION TYPE NETWORK APPROVAL APPLICATION FORM Counties Power Limited | 14 Glasgow Road, Pukekohe, Auckland 2120 Private Bag 4, Pukekohe 2340, New Zealand | www.countiespower.com Data required for each distributed generation system Data required for range of power output 10-100 kVA 100-750 kVA > 750 kVA Type of generation unit – synchronous, asynchronous, etc. P P P Type of prime mover P P P Rated terminal voltage (kV) P P P Rated generation capacity (kVA) P P P P P P P P P Rated minimum power factors (both over and under excited) at rated kVA Maximum continuous active power generated (kW) P Maximum short term active power generated (kW) For asynchronous generations, reactive power requirements (kVAr) P P NA Anticipated operating regime e.g. continuous, intermittent, peak lopping P P P Method of voltage control P P P Generation transformer details, if applicable P Interface arrangements Data required for range of power output 10-100 kVA 100-750 kVA > 750 kVA The means of connection and disconnection P P P The means of synchronisation between the distribution network and the distributed generation P P P Generation neutral earthing arrangements Single line diagram for installation detailing circuit breakers, base loads and generation capabilities P P P P 10-100 kVA 100-750 kVA > 750 kVA Interface arrangements Data required for range of power output Lowest frequency at which the distributed generation can run P Actual low frequency trip setting and time delay P P P Actual over frequency trip setting and time delay P P P Minimum operating power P Generation kW/kVAr capability charts (at lower voltage terminals at nominal and ±10% of nominal voltage) at: (a) maximum short term power (b) maximum continuous power P P P (c) 75% output P (d) 50% output P (e) minimum power P Auxiliary power requirements at: Website Version August 2015 | Page 1 DG2 FORM ADDITIONAL INFORMATION FOR OVER 10 kW SOLAR, OR OTHER DISTRIBUTED GENERATION TYPE NETWORK APPROVAL APPLICATION FORM Counties Power Limited | 14 Glasgow Road, Pukekohe, Auckland 2120 Private Bag 4, Pukekohe 2340, New Zealand | www.countiespower.com Interface arrangements Data required for range of power output 10-100 kVA 100-750 kVA > 750 kVA (a) rated power output P (b) minimum power output P (c) start up P Start up times to minimum operating power: (a) from cold P (b) from warm P (c) from hot P Normal ramp rate P Time for cold start to full rated output P P Inertia constant (seconds) (whole machine) Stator resistance P Direct axis synchronous reactance P Quadrature axis synchronous reactance P Direct axis transient reactance P Quadrature axis transient reactance P Direct axis sub transient reactance P Quadrature axis sub transient reactance P Leakage (positive sequence) reactance P Negative sequence reactance P Zero sequence reactance P Earthing resistance/reactance P Time constants: (a) direct axis transient open circuit P (b) quadrature axis transient open circuit P (c) direct axis sub transient open circuit P (d) quadrature axis sub transient open circuit P Generation transformer details (impedance, tap changer, vector group, earthing, maximum overvoltage capability at rated frequency etc.) P Type of excitation system (block diagram/specifications, forward/feedback gains/time constants and limits) P P Speed governor and prime mover data (detailed functional description of governing system with all subsystems including system control and turbine time) P P Website Version August 2015 | Page 2 DG2 FORM ADDITIONAL INFORMATION FOR OVER 10 kW SOLAR, OR OTHER DISTRIBUTED GENERATION TYPE NETWORK APPROVAL APPLICATION FORM Counties Power Limited | 14 Glasgow Road, Pukekohe, Auckland 2120 Private Bag 4, Pukekohe 2340, New Zealand | www.countiespower.com Protection Requirements Protection Requirements 10-100 kVA 100-750 kVA > 750 kVA Generation circuit breaker P P P Dedicated transformer P Disconnect/isolate switch P P P Over-voltage protection P P P Under-voltage protection P P P Over-frequency protection P P P Under-frequency protection P P P P P Earth-fault protection Over-current voltage restraint protection P Neutral voltage displacement protection P P P Synchronisation P P P Loss of network supply P P P P P Power factor or voltage regulation equipment Website Version August 2015 | Page 3