INSTALLATION GUIDE
XR2400F ADDRESSABLE
FIRE ALARM CONTROL PANEL
MODEL XR2400F
Addressable Fire Alarm Control Panel
INSTALLATION GUIDE
FCC NOTICE
This equipment generates and uses radio frequency energy and, if not installed and used properly in strict accordance
with the manufacturer’s instructions, may cause interference with radio and television reception. It has been type
tested and found to comply with the limits for a Class B computing device in accordance with the speciÞcation in
Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in
a residential installation. If this equipment does cause interference to radio or television reception, which can be
determined by turning the equipment off and on, the installer is encouraged to try to correct the interference by one
or more of the following measures:
Reorient the receiving antenna
Relocate the computer with respect to the receiver
Move the computer away from the receiver
Plug the compute into a different outlet so that computer and receiver are on different branch circuits
If necessary, the installer should consult the dealer or an experienced radio/television technician for additional
suggestions. The installer may Þnd the following booklet, prepared by the Federal Communications Commission,
helpful:
“How to identify and Resolve Radio-TV Interference Problems.”
This booklet is available from the U.S. Government Printing OfÞce, Washington D.C. 20402
Stock No. 004-000-00345-4
Copyright © 2000 - 2003 Digital Monitoring Products, Inc.
Information furnished by DMP is believed to be accurate and reliable.
This information is subject to change without notice.
TABLE OF CONTENTS
Revisions to This Document
Introduction
1.1
1.2
1.3
1.4
1.5
1.6
Mounting
2.1
2.2
2.3
2.4
2.5
2.6
Overview................................................1
System Components ...............................1
Power SpeciÞcations ...............................1
Before you begin ....................................1
About this Guide .....................................1
How to use this Guide .............................1
Mounting the Enclosure...........................2
Surface Mounting....................................2
Flush Mounting .......................................2
Fire Command Center LCD Keyboard ........2
Metal Backplate ......................................2
Wiring Diagram.......................................3
AC Connection
3.1
3.2
3.3
3.4
Transformers and AC Power Connection ...4
28 VAC Transformer ................................4
16 VAC Transformer ...............................4
Earth Ground from the XR2400F Panel ....4
Secondary Power Supply
4.1
4.2
4.3
Description .............................................5
Battery Connection to XR2400F
Command Processor panel ......................5
Battery Connection to the 504-24
Power Supply .........................................5
Two 866 NAC Modules
5.1
5.2
5.3
5.4
Description .............................................6
Connection .............................................6
Bell Silence/Bell Trouble ..........................6
NotiÞcation Appliances ...........................7
462N LX-Bus™ Expansion Card
6.1
6.2
6.3
Description .............................................8
LX-Bus™ Expansion Capability .................8
Installing the 462N Module ......................8
Telephone RJ Connector
7.1
7.2
7.3
7.4
Description .............................................9
FCC registration .....................................9
NotiÞcation.............................................9
Ground start...........................................9
893A Dual Phone Line Module
8.1
8.2
8.3
8.4
8.5
8.6
XR2400F Installation Guide
Description ...........................................10
Connection ...........................................10
Jumper Settings....................................10
Digital Dialer/Multiplex ..........................10
Phone Line Monitor ...............................10
Processor Fail Buzzer.............................10
Digital Monitoring Products
i
TABLE OF CONTENTS
504-24 Power Supply
9.1
9.2
9.3
9.4
9.5
9.6
Description ...........................................11
LED’s ..................................................11
504-24 Condition Chart .........................11
504-24 UL Listings ................................11
24 VDC NAC Standby Battery Calculations11
Connection ...........................................12
Interconnect Wiring Harness
10.1
Interconnect Harness ............................12
Fire Command Center
11.1
11.2
11.3
Description ...........................................13
Connection ...........................................13
Remote Fire Command Center ...............13
XR2400F Command Processor Panel
12.1
12.2
12.3
12.4
Description ...........................................14
Connection ..........................................14
Relays .................................................14
Zone Reference ....................................14
XR2400F Product SpeciÞcations
13.1
13.2
13.3
13.4
13.5
13.6
Power Supply .......................................15
Communication.....................................15
Panel Zones..........................................15
Remote Annunciator .............................15
LX-Bus™ ..............................................15
Outputs................................................15
Expansion
14.1
14.2
Expansion Zones...................................16
Output (Relay) Expansion ......................16
Accessory Devices
15.1
15.2
15.3
15.4
15.5
Wiring Diagram.....................................17
Lightning Protection ..............................17
Accessory Devices.................................18
Mounting Keypads and Zone Expanders..19
Connecting serial devices ......................19
Battery Information
16.1
16.2
16.3
16.4
16.5
16.6
16.7
Battery Only Restart..............................20
Replacement Period ..............................20
Discharge/recharge...............................20
Battery Supervision ...............................20
Battery Cutoff.......................................20
XR2400F Power Requirements ...............20
XR2400F Standby Battery Calculations....21
Bell Output
17.1
Digital Monitoring Products
ii
Terminals 5 and 6 .................................22
XR2400F Installation Guide
TABLE OF CONTENTS
Keypad and Zone Expander Bus
18.1
18.2
18.3
18.4
18.5
Description ...........................................22
Terminal 7 - RED ..................................22
Terminal 8 - YELLOW ............................22
Terminal 9 - GREEN ..............................22
Terminal 10 - BLACK .............................22
Smoke Detector Output
19.1
19.2
Terminals 11 and 12..............................22
Current Rating ......................................22
Powered Zones for 2-Wire Smoke Detectors
20.1
Terminals 25-26 and 27-28 ....................22
20.2 Compatible 2-Wire Smoke Detectors ...........23
Protection Zones
21.1
21.2
21.3
21.4
Description ...........................................24
Operational Parameters .........................24
Zone Response Time .............................24
Keyswitch Arming Zone .........................24
Dry Contact Relay Outputs
22.1
22.2
22.3
Description ...........................................25
Contact Rating......................................25
Output Harness Wiring ..........................25
12 VDC Voltage Outputs 3 to 10
23.1
23.2
Description ...........................................25
Output Harness Wiring ..........................25
Reset and Tamper Headers
24.1
24.2
J16 Reset Header .................................26
J4 Tamper Header ................................26
Universal UL Burglary SpeciÞcations
25.1
25.2
25.3
25.4
25.5
25.6
25.7
25.8
Introduction .........................................27
Wiring..................................................27
Control outside of protected area ...........27
Police station phone numbers ................27
Bypass reports......................................27
System maintenance .............................27
Partitions..............................................27
UL Listed Receivers ...............................27
UL 1023 SpeciÞcations
26.1
26.2
26.3
26.4
Bell cutoff.............................................27
Entry delay...........................................27
Exit delay .............................................27
Weekly test ..........................................27
UL 1610 And 1076 SpeciÞcations
27.1
27.2
27.3
27.4
27.5
XR2400F Installation Guide
Multiplex network capacity ....................28
Opening/Closing reports ........................28
Closing wait..........................................28
Proprietary dialer ..................................28
AA Network Communication ..................28
Digital Monitoring Products
iii
TABLE OF CONTENTS
UL 1635 SpeciÞcations
28.1
28.2
28.3
28.4
28.5
28.6
System trouble display ..........................29
Digital Dialer telephone number .............29
Entry delay...........................................29
Exit delay .............................................29
Test time..............................................29
Closing wait..........................................29
UL 365 And 609 SpeciÞcations
29.1
29.2
29.3
29.4
29.5
29.6
System trouble display ..........................29
Grade A bell .........................................29
Bell cutoff.............................................29
Automatic bell test ................................29
Line security for Police Connect..............29
High Line Security.................................29
Universal UL And NFPA Fire Alarm SpeciÞcations
30.1
30.2
30.3
30.4
30.5
30.6
30.7
30.8
30.9
30.10
30.11
30.12
30.13
Introduction .........................................30
Wiring..................................................30
Transformer..........................................30
End-of-Line resistor...............................30
System trouble display ..........................30
Fire display...........................................30
Police station phone number..................30
System maintenance .............................30
Audible alarm .......................................30
Fire zone programming .........................30
Style D zones .......................................30
Video Option ........................................30
UL Listed Receivers ...............................30
UL 985 NFPA 72 (Chapter 2) SpeciÞcations
31.1
Bell output deÞnition .............................31
UL 864 NFPA 72 (Chapter 9) SpeciÞcations
32.1
32.2
32.3
32.4
32.5
32.6
32.7
32.8
32.9
32.10
Zone restoral reports.............................31
Power fail delay ....................................31
Sprinkler supervisory.............................31
DACT systems ......................................31
Type 2 and Type 3 Central Station
Service.................................................31
Type 1 Central Station Service ...............31
Local Protective Signaling Systems .........31
Proprietary Protective Signaling Systems 32
Remote Station Protective
Signaling Systems .................................32
Fire Protective Signaling Systems
with an iCOM™.....................................32
California State Fire Marshal SpeciÞcations
33.1
Digital Monitoring Products
iv
Bell output deÞnition .............................32
XR2400F Installation Guide
TABLE OF CONTENTS
System Wiring Diagrams
34.1
34.2
34.3
34.4
34.5
34.6
34.7
34.8
34.9
Multiple NotiÞcation Circuit Modules .......33
Multiple NotiÞcation Circuit Modules
for Zoned Annunciation .........................34
Dual Style D Zone Module Installation ....35
Remote Station Reversing
Relay Connection ..................................36
Supervised Remote Relay ......................37
Cellular Backup Installation for
Derived Channel Burglary ......................38
LX-Bus™ Module Connection..................39
Second LX-Bus™ with Auxiliary
Power Supply .......................................40
Multiple NotiÞcation Circuits with
Strobes and Bells ..................................41
OPERATING INSTRUCTIONS
XR2400F Installation Guide
Digital Monitoring Products
v
REVISIONS
Revisions to This Document
This section explains the changes that were made to this document during this revision. This section lists the date
the change was made, the section number and section heading, and a quick summary of the change.
Date
Section Number and Heading
Quick Explanation of Changes
4/04
5.4 NotiÞcation Appliances
10.1 Interconnect Harness
Sections 15.1, 15.3, 15.4
16.7 Standby Battery Calculations
Removed obsolete products and added Models 850S and 850D.
ClariÞed table information.
Added keypad models 690F and 790F.
Added keypad models 690F and 790F and 734 Wiegand Interface Card.
Added/revised current draw information.
5/03
FCC Statement
Entire Document
16.7 Standby Battery Calculations
20.1 Terminals 25-26 and 27-28
21.3 Zone Response Time
34.9 Notif. with Strobes and Bells
Adjusted to properly reßect Class A.
Added SCS-1R references to the appropriate places.
Current Draw on some products adjusted.
EOL information clariÞed.
Changed from 160 milliseconds to 167.
Wiring Diagram corrected.
10/02 1.2 System Components
1.3 Power SpeciÞcations
2.6 Wiring Diagram
3.1 Transformers and AC Power
3.3 16.5 VAC Transformer
13.1 Power Supply
15.1 Wiring Diagram
32.9 Remote Station Protective
34.4 Remote Station Reversing
9/02
1.2 System Components
1.3 Power SpeciÞcations
2.6 Wiring Diagram
3.1 Transformers and AC Power
3.3 16.5 VAC Transformer
13.1 Power Supply
13.5 LX-Bus™
15.1 Wiring Diagram
15.4 Mounting Keypads
16.6 XR2400F Power Requirements
20.1 Terminals 25-26 and 27-28
32.9 Remote Station Protective
34.4 Remote Station Reversing
3/02
15.5 Connecting Serial Devices
16.6 XR2400F Power Requirements
Digital Monitoring Products
vi
Updated to 16 VAC 56 VA transformer.
Updated to Transformer Input of 16 VAC 56 VA and Standby battery of
12 VDC 28Ah (four Model 367 batteries) with 56 VA transformer.
Changed drawing to show 56 VA transformer.
Updated to 16 VAC 56 VA transformer.
Updated to 16 VAC 56 VA transformer.
Updated to 16 VAC 56 VA transformer and Standby battery of 12 VDC
28Ah (four Model 367 batteries) with 56 VA transformer.
Changed drawing to show 56 VA transformer.
Added the section back to the manual.
Added the system diagram back to the manual.
Updated to Model 320 16.5 VAC 40 VA transformer.
Updated to Transformer Input or 16.5 VAC 40 VA and Standby battery of
12 VDC 15.4 Ah (two Model 367 batteries) with 40 VA transformer.
Changed drawing to show 40 VA transformer.
Updated to 16.5 VAC 40 VA transformer.
Updated to 16.5 VAC 40 VA transformer.
Updated to 16.5 VAC 40 VA transformer and Standby battery of 12 VDC
15.4 Ah (two Model 367 batteries) with 40 VA transformer.
Added 462FM.
Removed Model 321 and 322 transformers from Figure 13, and changed
drawing to show Model 320 transformer.
Added 710 and 710F.
Removed Model 670 keypad.
Added note about sensor reset dropping power to zones 9 and 10.
Removed section.
Removed system diagram of remote station reversing relay.
LX-Bus and Keypad Bus wiring information clariÞed.
iCOM™ Internet Alarm Router added to the Standby Battery Calculations
Chart
XR2400F Installation Guide
INTRODUCTION
Introduction
1.1
Overview
The DMP XR2400F Addressable Fire Alarm Control Panel (FACP) is an expandable 24 VDC Fire Alarm Control
with built-in DACT and LCD Fire Command Center keyboard with membrane keyswitch. A complete system
can provide a total of 494 programmable inputs and outputs for commercial and industrial Þre alarm service.
The 24 VDC 4 Amp notiÞcation appliance power is distributed between two class B style W NAC outputs.
Additional NAC outputs can be added with conventional supervision modules or addressable power supply/
boosters. Addressable smoke detectors and input modules round out the XR2400F to deliver a truly ßexible
and expansive Þre detection and notiÞcation system. The Fire Alarm Control Panel is shipped pre-wired
in a red metal enclosure housing the necessary components to monitor and control Þre alarm notiÞcation
appliances. The enclosure’s dimensions are as follows: 32” H x 14.5” W x 4” D. The lid adds about 0.5” to
each side.
1.2
System Components
The XR2400F FACP consists of the following components:
•
•
•
•
•
1.3
One Model XR2400F Command Processor panel
Two Model 866 Class B Style W NAC modules
One Model 504-24 VDC Power Supply
One 16 VAC, 56 VA transformer
Two Model 305 Relays
• One Model 893A Dual Phone Line module
• One Model 630F PCB and membrane switch
• One 28 VAC transformer, TF-0030
• One Model 462N LX-Bus Expansion Card
• One Metal Backplate
Power SpeciÞcations
Command Processor:
Transformer Input of 16 VAC 56 VA
Standby battery of 12 VDC 28Ah (56 VA charges up to four 7.7Ah batteries)
Auxiliary power of 12 VDC at 1 Amp
NAC Output of 12 VDC at 1.5 Amp
All circuits are inherent Power Limited except red battery wires.
NAC Output:
24 VDC 4 Amps shared between NACs 1 and 2
1.4
Before you begin
Before installing the XR2400F, we recommend you read through the entire contents of this guide.
Familiarize yourself with the features of the panel and the key points to remember during the installation.
Be sure to read and understand all of the caution statements printed in bold italics.
1.5
About this Guide
The information in this guide is organized into Þve sections: Table of Contents, Introduction, Installation,
Compliance, and System Wiring Diagrams.
• The Table of Contents at the front lists the headings and subheadings used throughout each section of
the guide.
• The Introduction section gives you an overview of the XR2400F and this document.
• The Installation section begins with mounting instructions for the enclosure. Wiring diagrams for each
component also appear in this section.
• The Compliance section lists all UL listings the XR2400F currently follows.
• The System Wiring Diagrams provide illustrations of typical XR2400F systems.
1.6
How to use this Guide
To locate information about the installation of the XR2400F, go to the Table of Contents at the front of
this guide. Find the subject heading that best describes the information you need and turn to the section
number shown to the right of the heading. If you cannot Þnd the information you need under that heading,
scan through a few of the headings and read the text under those that sound similar.
XR2400F Installation Guide
Digital Monitoring Products
1
INSTALLATION
Mounting
2.1
Mounting the Enclosure
The XR2400F must be mounted in a secure, dry
location to protect the unit from damage due
to tampering and the elements. The enclosure
can be either ßush mounted or surface mounted
and includes a hinged door with lock. The hole
in the enclosure door allows access to the Fire
Command Center without opening the door.
Figure 1 illustrates the mounting hole locations
for the panel’s enclosure.
The enclosure’s dimensions are 32” tall, 14.5”
wide, by 4” deep. The lid adds about 0.5” to
each side.
2.2
Hole for Flush
Mounting
Holes for Surface Mounting
Surface Mounting
The center hole of the enclosure should
be attached to a stud in the wall. Due to
the weight of the enclosure, especially the
batteries, it is extremely important to mount
the enclosure on the stud. Attach the two holes
beside the center hole to sheetrock to secure
enclosure. When mounting the enclosure,
be sure to leave room for the panel door to
swing open. The door’s lock should be easily
accessible.
2.3
3/4" X 1/2" Knockouts
Holes for 1" screws for
Flush Mounting
Flush Mounting
The enclosure can also be ßush mounted. Use
1” screws to secure the enclosure between two
studs using the two sets of holes on the sides of
the enclosure. Use the top and bottom holes to
secure to horizontal studs, if necessary.
2.4
Fire Command Center LCD Keyboard
A Fire Command Center LCD Keyboard has been
factory installed on the XR2400F enclosure.
Also, a keyswitch has been installed and prewired to the left of the keyboard. The user can
turn the keyswitch to enable the four functions
keys without opening the enclosure door.
2.5
Metal Backplate
The XR2400F components are pre-wired and
installed on a metal backplate. The backplate
can easily be removed to keep components safe
during pre-wire activities.
Battery Shelf
Additional Holes for Surface Mounting
Hole for Flush Mounting
Figure 1: Mounting the XR2400F Enclosure
To remove the backplate, disconnect the wires to the batteries, transformers, and the Fire Command Center
LCD keyboard. Also remove the AC wires from the 504-24 power supply. From the panel, disconnect the AC
wires from terminals 1 and 2. Disconnect the battery wires either from the batteries or the panel terminals
3 and 4. Finally, disconnect the keyboard wires from panel terminals 7, 8, 9, and 10.
Remove the screws securing the backplate to the enclosure. Then loosen the two top screws that the
backplate hangs on. After the screws are removed and loosened, lift the backplate up slightly and pull the
backplate toward you. When reinstalling the backplate, be sure all connections are secure.
Refer to Figure 2 for an illustration of the backplate and the components. The backplate is shown in light
gray.
Digital Monitoring Products
2
XR2400F Installation Guide
INSTALLATION
2.6
Wiring Diagram
The XR2400F system below shows the layout of the components. The wires shown in this guide have been
factory installed and connected. The dashed lines represent wires that run underneath a component.
Detailed wiring diagrams for each supplied component appear in following sections of this guide.
WHITE
BLACK
GREE
N
S
S
S
= Supervised Wire
28 VAC
Transformer
866
Module
#1
WHITE
WHITE
BLACK
GREEN
BLACK
866
Module
#2
56 VA Transformer
charges 4 batteries
16 VAC
Transformer
S
S
To Telco
S
S
S
S
504-24
Power Supply
893A
1K EOL
To Notification
Appliances
1K EOL
+ DC -
See LT-0554, 504-24 Power
Supply section for complete
504-24 information.
P10
AC TRBL BATT TRBL
Red
+ Bat -
Red wire to positive
battery terminal.
Black
Black wire to negative
battery terminal.
XR2400F Command Processor™
Panel
See LT-0554, XR2400F Command Processor™
Panel section for complete XR2400F information.
Output Header J2
AC
+B
From XR2400F
panel to 12 VDC.
+
J16
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
Black
AC
Red
From 504-24 Power Supply to 24 VDC.
J10
Z3 GND Z4
Z5 GND Z6
Z7 GND Z8
Z9+ Z9- Z10+ Z10-
To Fire Command Center on enclosure door
-
12 VDC
battery
12 VDC battery
24 VDC
Circuit
+
504-24 Secondary Power Supply
1.5 Amps maximum charge current.
Use only 24 VDC rechargeable batteries
or Two DMP Model 367 12 VDC batteries
with a Series Connecting Strap.
Replace every 3 to 5 years.
-
+
XR2400F Secondary Power Supply
1.5 Amps maximum charge current.
Use only 12 VDC rechargeable batteries
DMP Model 367.
Replace every 3 to 5 years.
12 VDC battery
462N LX-Bus Interface Card
AC
Two 12 VDC batteries
connected in parallel with a
Model 318 Dual Battery
Harness. See Secondary
Power Supply section.
-
+
12 VDC
battery
Battery
Compartment
Two 12 VDC batteries
connected in series with the
included Series Connecting
Strap. See Secondary
Power Supply section.
Figure 2: XR2400F System
XR2400F Installation Guide
Digital Monitoring Products
3
INSTALLATION
AC Connection
3.1
Transformers and AC Power Connection
The AC connection should be completed by a licensed electrician.
Never share the Fire Alarm Control Panel circuit with any other equipment.
The XR2400F comes supplied with two transformers: the 16 VAC 56 VA transformer and the 28 VAC 175 VA
transformer. The 28 VAC and the 16 VAC transformers’ white leads and black leads must be connected
together respectively. These wires must be connected to an unswitched 120 VAC 60 Hz power source with at
least 1.85 Amps of available current.
Black wire - attach the black 120 VAC wire to the black wire of the transformers.
White wire - attach the white 120 VAC wire to the white wire of the transformers.
Green wire - attach the green wire lead to the green wire attached to the enclosure.
Bracket
Nut
WHITE
GREE
S
BLACK
N
S
Blue
To Model 504-24
AC Terminals
L-Bracket
WHITE
16 VAC
56 VA
Transformer
Bracket
Nut
Yellow
WHITE
BLACK
GREEN
BLACK
28 VAC
Transformer
56 VA Transformer
charges 4 batteries.
Violet
Gray
Terminal 1 Terminal 2
To XR2400F Panel
Figure 3: Transformers and AC Power Connection
Always ground the panel before applying power to any devices! Use 18 AWG or larger for all power
connections. The XR2400F must be properly grounded before connecting any devices or applying power
to the panel. Proper grounding protects against Electrostatic Discharge (ESD) that can damage system
components.
3.2
28 VAC Transformer
The 28 VAC Transformer supplies power to the AC terminals of the 504-24 Power Supply which is factory prewired to the two 866 NAC modules. The 28 VAC is located in the upper right hand corner of the enclosure
surrounded by a metal divider. See Figure 3 above and the 504-24 Power Supply section.
3.3
16 VAC Transformer
The 16 VAC 56 VA transformer supplies power to the XR2400F panel and is factory pre-wired. See Figure 3:
Transformers and AC Power Connection. Also refer to Figure 11: XR2400F Panel Wiring Diagram.
3.4
Earth Ground from the XR2400F Panel
Terminal 4 of the XR2400F panel must be connected to earth ground using 14 gauge or larger wire to provide
proper transient suppression. DMP recommends connecting to a cold water pipe or ground rod only. Do not
connect to an electrical ground or conduit, sprinkler or gas pipes, or to a telephone company ground.
Digital Monitoring Products
4
XR2400F Installation Guide
INSTALLATION
Secondary Power Supply
4.1
Description
The XR2400F system includes pre-wired cables for connecting a 24 VDC battery to the 504-24 power supply
and a 12 VDC battery to the XR2400F panel. For 24 VDC battery operation to the 504-24, connect two 12
VDC sealed lead-acid batteries in series using the included series connecting strap. See Figure 4. Observe
polarity when connecting all batteries.
Use sealed lead-acid batteries only. Use the DMP Model 367, 12 VDC 7.7Ah sealed lead-acid rechargeable
battery. Batteries supplied by DMP or manufactured by Eagle Picher or Yuasa have been tested to ensure
proper charging with DMP products.
Gel cell batteries cannot be used with the XR2400F panel.
4.2
Battery Connection to XR2400F Command Processor panel
For 12 VDC battery operation to the XR2400F, connect the black battery lead to the negative terminal of the
battery. The black battery wire is connected to terminal 4 of the XR2400F panel.
Connect the red battery lead to the positive terminal of the battery. The red battery wire is connected to
terminal 3 of the XR2400F panel. See Figure 11 and Figure 2.
You can add a second battery in parallel using the DMP Model 318 Dual Battery Harness. When wiring two
batteries with the Model 318 Dual Battery Harness, plug the red male end of the Dual Battery Harness into
the red female battery lead from the panel. Plug the black male end of the Dual Battery Harness into the
black female battery lead from the panel. Attach both female leads from the Dual Wiring Harness to the
two batteries as described above. See Table 3: Battery Calculations.
4.3
Battery Connection to the 504-24 Power Supply
The 504-24 is powered by 24 VDC. After connecting two 12 VDC batteries together using the series
connecting strap (or after installing one 24 VDC battery) connect the black battery wire to the negative
terminal of the 24 VDC battery. The black battery wire is connected to the negative AC terminal of the 50424.
Connect the red battery wire to the positive terminal of the 24 VDC battery. The red battery wire is
connected to the positive AC terminal of the 504-24.
RED
Series
Connecting
Strap
BLACK
12 VDC
Battery
12 VDC
Battery
Figure 4: 24 VDC Battery Wiring
See Figure 9 and Figure 2. Also see the Battery Information section.
XR2400F Installation Guide
Digital Monitoring Products
5
INSTALLATION
Two 866 NAC Modules
5.1
Description
Each 866 provides one style W indicating circuit for supervising UL polarized notiÞcation appliances, such as
bells, strobes, and horns. See Table 1: NotiÞcation Appliances for a list of approved notiÞcation appliances.
5.2
Connection
Each 866 module is pre-installed on the removable backplate using the standard three-hole conÞguration.
The modules are factory pre-wired to each other, the 504-24, and the XR2400F panel. Refer to the Þgure
below and to Figure 2: XR2400F System for wiring connections.
You can connect 24 VDC NotiÞcation Appliances to terminals 5 and 6 of each module. Each module provides
a zone of notiÞcation and can be activated separately.
Normal/Silence Switch
10K EOL
DMP Model 308
866
Module #1
1
2
3
4
5
6
7
8
AUX PWR
GND
Alarm In
Bell PWR In
Bell Out +
Bell Out Bell Trouble
Bell Trouble
To XR2400F Output #1 (J2 pin #2)
24 VDC
To XR2400F terminal 13 (Zone 1)
UL Listed,
Polarized
Notification
Appliances
See Table 1:
Notification
Appliances
Pre-installed 1K EOL
Normal/Silence Switch
10K EOL
DMP Model 308
866
Module #1
1
2
3
4
5
6
7
8
AUX PWR
GND
Alarm In
Bell PWR In
Bell Out +
Bell Out Bell Trouble
Bell Trouble
To
To
To
To
XR2400F terminal 7
504-24 DC XR2400F Output #2 (J2 pin #5)
504-24 DC +
Pre-installed 1K EOL
To XR2400F terminal 15 (Zone 2)
To 504-24 BATT TRBL C (Common)
24 VDC
UL Listed,
Polarized
Notification
Appliances
See Table 1:
Notification
Appliances
Figure 5: 866 Modules Wiring
5.3
Bell Silence/Bell Trouble
A bell silence switch on the 866 module is provided to prevent sounding of the indicating devices when
testing the system. When the Silence position is selected, a 15-second delay occurs before the 866 bell
trouble contacts (terminals 7 and 8) open. Select the Normal position after testing to return the 866
module to normal operation.
Digital Monitoring Products
6
XR2400F Installation Guide
INSTALLATION
5.4
NotiÞcation Appliances
The following table indicates the approved notiÞcation appliances that can be used with the XR2400F
system.
DMP Model
Description
802
12/24 VDC Multi-Tone Horn
802WP-75W
24 VDC Weatherproof Multi-Tone Horn
803
12/24 VDC Standard Horn
850S
Single Action Dry Contact Pull Station
850D
Dual Action Dry Contact Pull Station
806-6
12 VDC 6-Inch Bell
806-10
12 VDC 10-Inch Bell
821
12 VDC Strobe
822
12 VDC Strobe with RetroÞt Plate
823
12 VDC Horn Strobe
831
12/24 VDC Single Circuit Sync Module
832
12/24 VDC Dual Circuit Sync Module
901
24 VDC Mini Horn
904
24 VDC Horn
904WP
24 VDC Weatherproof Horn
906-6
24 VDC 6-Inch Bell
906-10
24 VDC 10-Inch Bell
921-MCW
24 VDC Multi-Candela Strobe
922-MCW
24 VDC Multi-Candela Strobe with RetroÞt Plate
923-MCW
24 VDC Multi-Candela Horn Strobe
924-MCW
24 VDC Multi-Candela Audible Strobe
924WP-75W
24 VDC Weatherproof Audible Strobe
Table 1: NotiÞcation Appliances
XR2400F Installation Guide
Digital Monitoring Products
7
INSTALLATION
462N LX-Bus™ Expansion Card
6.1
Description
The 462N LX-Bus™ Expansion Card provides an additional 100 zones to the XR2400F.
6.2
LX-Bus™ Expansion Capability
The 462N card provides a 4-wire LX-Bus™ that allows you to connect up to 100 Model 521LX or 521LXT
Addressable Smoke Detectors. Also the LX-Bus™ could connect up to 25 Model 714, 715, and 725 Zone
Expanders or 716 Output Expanders, up to six Model 714-16 or 715-6 Zone Expanders, and up to 100 Model
711 and 711E Zone Expanders. Power for the devices is provided through the Black and Red wires of the
expansion harness.
6.3
Installing the 462N Module
1. Remove AC and battery power from the XR2400F panel before installing the 462N card.
2. Align the 50 pin connector of the 462N with the J6 connector on the XR2400F panel.
3. Press the 462N onto the J6 connector while applying even pressure to both sides.
XR2400F Panel
J6 Expansion
Connector
462N Network
Interface Card
Configuration
Jumpers
LX-Bus
Connector
B
To LX-Bus Modules
Black - Aux. Common
Black
Green - Serial Data Out
Green
Yellow - Serial Data In
Yellow
Red - Aux. Positive
Red
Figure 6: 462N Wiring
Digital Monitoring Products
8
XR2400F Installation Guide
INSTALLATION
Telephone RJ Connector
7.1
Description
Connect the XR2400F system to two lines of the public telephone network by installing two DMP 356 RJ
Cables between the RJ31X or RJ38X phone jacks, and the 893’s J4 connector (for main line) and J5 (for
backup line). Set the 3-pin headers on the XR2400F labeled J11 and J12 to DD for digital dialer, Contact ID,
or Modem IIe operation. See 893A Dual Phone Line Module.
To Telephone
Line
Ring
Tip
5
4
6
3
7
2
1
8
Ring 1
To Premise
Phone
RJ31X or RJ38X
Phone Block
Tip 1
Figure 7: Phone Jack Wiring
7.2
FCC registration
The Model XR200/XR2400F complies with FCC part 68 and is registered with the FCC. Registration number:
CCKUSA-18660-AL-R / Ringer Equivalence: 1.1B
7.3
NotiÞcation
Registered terminal equipment must not be repaired by the user. In case of trouble, the device must be
immediately unplugged from the telephone jack. The factory warranty provides for repairs. Registered
terminal equipment may not be used on party lines or in connection with coin telephones. NotiÞcation must
be given to the telephone company of:
a. The particular line(s) the service is connected to (the speciÞc phone line)
b. The FCC registration number (CCKUSA-18660-AL-R)
c. The ringer equivalence (1.1B)
d. The make, model, and serial number (see the serial # sticker on the panel) of the device
7.4
Ground start
Ground start phone service cannot be used on commercial or residential Þre applications.
XR2400F Installation Guide
Digital Monitoring Products
9
INSTALLATION
893A Dual Phone Line Module
8.1
Description
The 893A is a dual telephone line supervision module that allows the panel to indicate a phone line failure
to the premises and the central monitoring station. After the 893A senses a failure on the main line, it
switches to the backup, or secondary, phone line. The 893A is installed on the removable backplate above
the XR2400F circuit board.
8.2
Connection
The 893A connects the panel to the public telephone network by installing a DMP 356 RJ Cable between the
XR2400F panel’s J3 connector and the 893’s J3 connector labeled PANEL. The two communication jumpers
must be set to either DD or MPX.
Factory pre-wired
to XR2400F panel
Phone Jack
Connector, J3
J3
PANEL
893A Dual Telephone Line Module
Communication Jumpers: Both
Jumpers must be set
DD
MPX
P10
Factory pre-wired
to XR2400F panel
J10 Connector
J1
J2
To Primary
telephone line
J4
MAIN
DD
MPX
J5
BACKUP
Processor
Stopped Buzzer
To Secondary telephone line
Figure 8: 893A Dual Phone Line Module Wiring
8.3
Jumper Settings
There are two sets of jumpers on the 893A module. When setting the module for either DD (digital dialer) or
MPX (multiplex), both jumpers must be set.
8.4
Digital Dialer/Multiplex
You can conÞgure the 893A to provide two lines of digital dialer or one line of multiplex with digital dialer
backup. For multiplex operation both jumpers (J1 and J2) must be set to MPX. Also, jumpers J11 and J12 on
the panel must be set to MPX. See XR2400F Command Processor Panel Connection. The XR2400F is preset
at the factory for Digital Dialer. The Main modular jack (J4) is used for the primary dialer or multiplex line.
The Backup modular jack (J5) is used for the secondary digital dialer line.
8.5
Phone Line Monitor
The 893A uses a phone line monitor for the main and backup phone lines. When sending a report, the 893A
veriÞes the main phone line is working before sending. If the line is bad, the module tests the backup phone
line. The 893A sends the report on the Þrst working phone line.
The phone line monitor has a 2-minute trouble delay and a 1-minute restore delay. Phone line trouble is
displayed in the Fire Command Center LCD Status List as a System Trouble. The Fire Command Center LCD is
factory programmed to display system troubles in the Status List.
8.6
Processor Fail Buzzer
The 893A module also monitors the panel’s CPU and sounds a trouble buzzer whenever either the panel’s
processor is reset using J16 or the processor stops functioning.
Digital Monitoring Products
10
XR2400F Installation Guide
INSTALLATION
504-24 Power Supply
9.1
Description
The 504-24 is a power limited, switching power supply that meets UL, CSFM, NFPA, and FCC compliance
standards. Model 504-24 is rated for 24 VDC @ 4 Amps maximum and supplies power to the 866 Modules.
9.2
LED’s
The 504-24 has two status LED’s that show the current state of power. The green LED indicates low AC
input. The red LED indicates low standby battery power after AC has failed.
9.3
504-24 Condition Chart
Condition
Voltage Levels
LED
Status
Condition
AC Trouble
Approx. 102 VAC
AC LED (Green)
On
AC Good
Battery Trouble
Below 23.6 VDC
AC LED (Green)
Off
AC Bad
Battery Restoral
Above 25.0 VDC
DC LED (Red)
On
Battery Good
Battery Cutoff
Below 20.4 VDC
DC LED (Red)
Off
Battery Bad
Table 2: 504-24 Condition and LED Indicators
9.4
504-24 UL Listings
For UL 603 Power Supplies for Burglary Alarm Systems and UL 294 Power Supplies for Access Control System
applications: Voltage Range of 22.9 to 25.5 VDC.
For UL 1481 Power Supplies for Fire Protective Signaling the following maximum battery standby Ampere
hours apply for 24 hours of battery backup:
Battery Standby Maximum: 49.2Ah
Output Voltage: 24 VDC
Output Current: 1.5A standby, 4 Amp alarm
9.5
24 VDC NAC Standby Battery Calculations
The following calculation deÞnes the total number of standby battery Amp-hours required to support
operation of the NACs and any other devices attached to the 504-24 power supply. From this calculation,
assemble the appropriate number of batteries that will just exceed the calculated total Amp-hour
requirement. The 866 NACs receive power for internal operation from the XR2400F panel and do not enter
in this calculation themselves.
1. Add all standby current values including the power supply operating current.
2. Multiply the total standby current by the number of standby hours needed.
3. Add all alarm current values from the notiÞcation appliances attached to the 866 NACs and multiply by
0.25.
4. Add the total alarm mA-hour with the total standby mA-hour and then multiply this number by 0.001.
Power Supply Operating Current
Other Standby Current
1.
200 mA
+
______ mA
Total Standby Current
+
______ mA
Number of Standby Hours Required
X
______ hr
2.
Total Standby (mA-hr) Required
=
______ mA-hr
3.
Total Alarm Current
=
______ mA
Total Alarm Current X 0.25
=
______ mA-hr
Total Standby (Required)
+
______ mA-hr
Total
=
______ mA-hr
X
0.001
=
______
(0.25 = 5 minutes in alarm)
4.
Total Required Amp-hours
Table 3: Battery Calculations
XR2400F Installation Guide
Digital Monitoring Products
11
INSTALLATION
9.6
Connection
The 24 VDC power supply is completely pre-wired. Refer to the following 504-24 wiring diagram for speciÞc
wire connections.
+ DC -
504-24 Power Supply
Yellow
Both wires to
28 VAC
Transformer
Black
To XR2400F Panel
terminal 10 (BLK)
Black
To 866 Module #2
terminal 2 (GND)
White/Red
To 866 Module #2
terminal 4 (Bell PWR In)
Blue
AC
Green
LED
DC
Red
LED
AC TRBL BATT TRBL
NC C NO NC C NO
+ Bat -
Green
AC
Red wire to positive Red
battery terminal.
Black wire to negative Black
battery terminal.
Green
Black To 866 Module #2
terminal 8 (BELL TRBL)
To XR2400F Panel
To XR2400F Panel
terminal 18 (Zone 4) terminal 16 (Zone 3)
Figure 9: 504-24 Wiring
Interconnect Wiring Harness
10.1 Interconnect Harness
This chart explains the colors of the wires on the Interconnect Wiring Harnesses. It also explains what each
wire connects.
Wire Color
Connection From
Connection To
Red
Panel Terminal 7 (DC Power)
866 Module #2 Terminal 1 (Auxiliary Power)
Black
Panel Terminal 10 (Common)
504-24 DC - Negative DC Terminal (Ground)
Brown
Panel Terminal 13 (Zone 1)
866 Module #1 Terminal 7 (Bell Trouble)
Violet
Panel Terminal 15 (Zone 2)
866 Module #2 Terminal 7 (Bell Trouble)
Green
Panel Terminal 16 (Zone 3)
504-24 Battery Trouble Terminal N/O
White
Panel Terminal 18 (Zone 4)
504-24 AC Trouble Terminal N/C
Blue
Panel J2 Pin 2 (Common)
866 Module #1 Terminal 3 (Alarm In)
Orange
Panel J2 Pin 3 (Output 1 N/O)
Panel Terminal 5 (Bell Output)
Yellow
Panel J2 Pin 5 (Common)
866 Module #2 Terminal 3 (Alarm In)
Orange
Panel J2 Pin 6 (Output 2 N/O)
Panel Terminal 5 (Bell Output)
White/Red
504-24 DC + (Positive DC Terminal)
866 Module #2 Terminal 4 (Bell Power In)
Black
504-24 DC - (Negative DC Terminal)
866 Module #2 Terminal 2 (Ground)
Red
866 Module #2 Terminal 1 (Auxiliary Power)
866 Module #1 Terminal 1 (Auxiliary Power)
Black
866 Module #2 Terminal 2 (Ground)
866 Module #1 Terminal 2 (Ground)
Black
866 Module #2 Terminal 2 (Ground)
866 Module #1 Terminal 8 (Bell Trouble)
White/Red
866 Module #2 Terminal 4 (Bell Power In)
866 Module #1 Terminal 4 (Bell Power In)
Black
866 Module #2 Terminal 8 (Bell Trouble)
504-24 Battery Trouble Common Terminal
Black
866 Module #2 Terminal 8 (Bell Trouble)
866 Module #1 Terminal 8 (Bell Trouble)
Table 4: Interconnect Wiring Harness
Digital Monitoring Products
12
XR2400F Installation Guide
INSTALLATION
Fire Command Center
11.1 Description
The XR2400F provides an LCD display and 20-key keyboard for programming and user operation of the
system. The Fire Command Center is installed on the enclosure door of the XR2400F. To the left of the
keyboard, a keyswitch has been installed and pre-wired. The user must turn the keyswitch to enable the
four function keys. See the illustration below.
Figure 10: Fire Command Center LCD and Keyboard
11.2 Connection
The display and keyboard are factory pre-wired to terminals 7, 8, 9, and 10 of the XR2400F panel. For
standby battery calculations, the display draws 100mA of current in normal standby or alarm condition. See
Panel Standby Battery Calculations. The keyswitch has been pre-wired to the membrane keyboard.
11.3 Remote Fire Command Center
Up to seven Model 630F Remote Fire Command Centers may be remotely attached to the XR2400F system.
See the 630F Installation Guide, LT-0562, for complete information.
XR2400F Installation Guide
Digital Monitoring Products
13
INSTALLATION
XR2400F Command Processor Panel
12.1 Description
The DMP XR2400F Command Processor is a versatile Þre communicator panel with battery backup. The
XR2400F provides eight on-board grounded zones for connection of Model 869 class A zones and two on-board
12 VDC class B style A powered zones. The powered zones have a reset capability to provide for 2-wire
smoke detectors, relays, or other latching devices. The XR2400F can communicate to one or two DMP SCS-1
Receivers using multiplex or digital dialer, to one or two DMP SCS-1R Receivers using digital dialer, or to nonDMP receivers using the Contact ID and Modem IIe formats.
12.2 Connection
The XR2400F Command Processor panel is factory pre-wired and controls the other components in the
system. Refer to the wiring diagram below for wiring. See the following sections for descriptions of
additional applications of the XR2400F.
J12
J11
462N Network Interface Card
To 893 J3 PANEL Connector
XR2400F Command Processor™ Panel
J3
J2 Output Color Code for
Model 430 Output Harness
J4
Tamper
Header
DD, MPX
Selection
Headers
To 866 Module
#1 terminal 3
(Alarm In)
Form C Relays
Output 1 N/C Violet
Output 1 Com Gray
Output 1 N/O Orange
Output 2 N/C Violet
Output 2 Com Gray
Output 2 N/O Orange
Voltage Outputs
Output 3 White/Orange
Output 4 White/Yellow
Output 5 White/Green
Output 6 White/Blue
Output 7 White/Violet
Output 8 White/Gray
Output 9 White
Output 10 White/Black
Ground
Black
To 866 Module
#2 terminal 3
(Alarm In)
J2 Output Header
To 893 P10
Connector
J10
J6
To LX-Bus
Modules
J16
Panel
Reset
AC
AC
+B
1
2
3
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
4
5
6
7
8
9
10
11
12
To 16 VAC
Transformer
To Fire
Command
Center
Red wire to
positive terminal
of 12 VDC Battery
To 866 Module To 504-24
#2 terminal 1
DC (AUX PWR)
Black wire to
negative terminal
of 12 VDC Battery
13
14
15
Z3 GND Z4
Z5 GND Z6
16
19
17
18
20
21
Z7 GND Z8
22
23
24
Z9+ Z9- Z10+ Z10-
25
26
27
28
To 504-24
BATT TRBL
NC
To 866 Module
#2 terminal 7
(BELL TRBL)
To 866
Module #1
terminal 7
(BELL TRBL)
To 504-24
AC TRBL
NC
Figure 11: XR2400F Panel Wiring
12.3 Relays
The XR2400F is shipped with two Model 305 Relays pre-installed to allow zone alarm control for the 866 NAC
Modules. When a Þre alarm occurs the bell output is factory programmed to turn on and provide power to
the contacts of the relays. SpeciÞc zone programming determines whether one or both relays turn on signal
voltage to the 866 NACs. This allows control of the NACs by zone.
12.4 Zone Reference
The XR2400F has been pre-wired in the factory. The Þrst 866 NAC module connects to Zone 1. The second
866 NAC module connects to Zone 2. Zone 3 connects to the 504-24 power supply.
Digital Monitoring Products
14
XR2400F Installation Guide
INSTALLATION
XR2400F Product SpeciÞcations
13.1 Power Supply
Transformer Input: 16 VAC 56 VA
Standby Battery: 12 VDC 28Ah (56 VA charges up to four batteries)
Auxiliary: 12 VDC output at 1 Amp
Bell Output: 12 VDC at 1.5 Amp
All circuits are inherent Power Limited except the red battery wire.
13.2 Communication
Built-in dialer communication to DMP Model SCS-1 and SCS-1R Receivers
Built-in multiplex communication to DMP Model SCS-1 Receivers
Built-in Contact ID communication to non-DMP receivers
Built-in Modem IIe communication to non-DMP receivers
893A Dual Phone Line Modules with phone line supervision
Can operate as a local panel
13.3 Panel Zones
Eight 1k Ohm EOL grounded zones (zones 1 to 8). Connect to 869 class A module for burglary applications.
Two 3.3k Ohm EOL Class B (Style A) powered zone with reset (zones 9 and 10)
13.4 Remote Annunciator
You can connect up to seven of the following supervised keypads or expanders to the XR2400F keypad data
bus:
• Alphanumeric Fire Command Centers or keypads
• Four and single point zone expanders
• Single point detectors
13.5 LX-Bus™
You can connect the following devices to the LX-Bus provided by the DMP 462N (supplied), 462P, 462FM, 472,
and/or 481 Interface Cards up to the maximum number of LX-Bus addresses. See Accessory Devices.
•
•
•
•
•
Model 521LX or 521LXT Smoke Detectors with CleanMe
Sixteen, eight, four, and single point zone expanders
Relay output expanders
Graphic annunciator modules
Single point detectors
13.6 Outputs
Two SPDT relay outputs (requires two Model 305 relays that are provided on the panel, each rated 1 Amp at
30 VDC resistive). Connect only power limited sources to the relay.
XR2400F Installation Guide
Digital Monitoring Products
15
INSTALLATION
Expansion
14.1 Expansion Zones
Up to 232 additional Þre and burglary zones are available on the XR2400F using the remote zone capability
of keypads and zone expander modules. The panel’s keypad data bus supports up to eight supervised device
addresses with each address supporting up to four programmable expansion zones.
Up to 200 zones are available using the Model 460 Interface Adaptor, 462N, 462P, 462FM, 472, or 481
Interface Cards, and any combination of sixteen, eight, four, and single point zone expander modules and
single point LX-Bus™ detectors.
Combined current requirements of additional modules may require an additional 504-24 or 502-12 power
supply. See section Standby Battery Calculations when calculating power requirements.
14.2 Output (Relay) Expansion
In addition to the two SPDT relays and eight voltage outputs on board the XR2400F, you can also connect
up to 25 Model 716 Output Expanders to each card’s LX-Bus™. These modules can provide an additional 200
programmable SPDT relays. The XR2400F provides 50 Output Schedules you can use for programming the 716
to perform a variety of annunciation and control functions. You can also assign the 716 outputs to any of the
panel’s Output Options such as Fire Alarm, Communication Fail, or Phone Trouble Outputs.
The LX-Bus also supports the Model 717 Graphic Annunciator Module. Each 717 module supplies 20 switched
ground outputs that follow the state of their assigned zones.
Note: Do not use shielded wire for LX-Bus and keypad bus circuits.
XR2400F Command Processor System
462N, 462P, 462FM, 472, or
481 Expansion Interface Card
460
Interface
Adaptor
1
AC
2
AC
3
B+
4
B-
5
BELL
6
GND
7
8
YEL
9
GRN
10
BLK
11
SMK
12
L5+
13
L5-
14
L1
15
GND
16
L2
17
L3
18
GND
19
Model 711
Zone
Expander
L4
Model 714
Zone
Expander
Partition 1
Partition 2
Model 715
Zone
Expander
DISARM
DISARM
DISARM
ARM
ARM
ARM
Up to eight areas
DISARM
DISARM
ARM
ARM
Up to four areas
Model 716
Output
Expander
Partition 3
Partition 4
DISARM
DISARM
DISARM
ARM
ARM
ARM
Up to four areas
Model 717
Annunciator
Module
Up to four areas
Up to 200 zones and outputs when
using two LX-Bus" cards
Figure 12: Typical XR2400F System
Digital Monitoring Products
16
XR2400F Installation Guide
INSTALLATION
Accessory Devices
15.1 Wiring Diagram
The XR2400F system below shows some of the accessory modules you can connect for use in various
applications. A brief description of each module appears in section 15.3 Accessory Devices.
S
S
DMP Transformers:
J12
Model 320 16.5 VAC,
40 VA Class 2 Wire-in.
J11
J2 Output Color Code for Model
430 Output Harness
DD, MPX
Selection
Headers
Model 321 16.5 VAC,
40 VA Class 2 Plug-in.
Form C Relays
Output 1 N/C Violet
Output 1 Com Gray
Output 1 N/O Orange
Output 2 N/C Violet
Output 2 Com Gray
Output 2 N/O Orange
Voltage Outputs
Output 3 White/Orange
Output 4 White/Yellow
Output 5 White/Green
Output 6 White/Blue
Output 7 White/Violet
Output 8 White/Gray
Output 9 White
Output 10 White/Black
Ground
Black
J4
Tamper
Header
Model 322 16 VAC,
56 VA Class 2 Wire-in.
Secondary Power
Supply
1.2 Amps max. charging
current. Use only 12
VDC rechargeable
batteries. DMP Model
367. Replace every 3 to
5 years.
J2 Output Header
J10
+B
2
3
S
4
5
6
8
7
11
12
13
15
14
Z3 GND Z4
Z5 GND Z6
16
19
17
Cold Water Pipe
Earth Ground
Keyswitch Arming
S
18
20
Z7 GND Z8
22
21
23
S
S
24
S
S
S
S
S
1K
1K
1K
Ohm Ohm Ohm
1K
Ohm
S
S
S
1K
1K
Ohm Ohm
Auxliliary Power
Total current 1.0 Amps
combined from terminals 7,
11, 26, and 28.
S
ZONE 8
S
ZONE 6
ZONE 5
ZONE 4
S
ZONE 7
S
1K
Ohm
S
S
Bell
S
ZONE 3
16 to 18 gauge wire
ZONE 2
S
Maximum AC wire distance
With 16 gauge wire: 70 feet
With 18 gauge wire: 40 feet
Red
Black
Can be connected to
any zone. See section
21.4.
10
9
ZONE 1
S
Models 790/790F
75mA at 8 to 14.5 VDC.
Tamper protection
when required for
Model 350A Attack
Resistant Enclosure.
J6
Heat detectors, pull
stations, or any
other contact
device listed for
Fire Protective
Signaling can be
connected to zones
9 and 10.
Z9+ Z9- Z10+ Z10-
26
25
27
28
Zones 9 and 10 and
Model 715
compatibility
identifier: A.
Maximum operating
range:
8.8 to 14.2 VDC.
Class B, Style A.
S
22 Gauge minimum BLACK
Model 690/690F
72mA at 8 to 14.5 VDC.
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
22 Gauge minimum GREEN
1
Keypads
Model 793
108mA at 8 to 14.5
VDC.
Model 630F
60mA at 8 to 14.5 VDC.
AC
22 Gauge minimum YELLOW
AC
16 VAC
Transformer
22 Gauge minimum RED
12 VDC nominal. Total
current 1.5 Amps max.
Minimum cutoff time is 5
minutes.
Rear
Tamper
J16
Panel
Reset
Connect to nonswitched 120 VAC.
Bell
Front
Tamper
XR2400F Command Processor™ Panel
J3
ZONE
9
ZONE
10
S
S
S
S
1K S
Ohm
3.3K Ohm 3.3K Ohm
EOL
EOL
DMP
DMP
Model 309 Model 309
S = Supervised Circuit
Red
S
Model 715 Zone
Expansion Module
7mA @ 12 VDC
Models 715-8, 715-16
20mA @12 VDC
Red
Yellow
Green
Black
4-Wire Smoke
Detectors
POWER
Refer to LT-0164 for a
list of approved 4-wire
smoke detectors and
power supervision
releays.
ARMED
S
S
Power
Supervision
Relay
S
Smoke
Detector
Ð +
Model 714 Zone
Expansion Module
7mA @ 12 VDC
Models 714-8, 714-16
20mA @12 VDC
Model 711 Zone
Expansion
Module
7mA @ 12 VDC
S
S
Disarm
S
S
S
S
1K
Ohm
S
1K
Ohm
S
S
S
1K
Ohm
Arm
1K
Ohm
1K
Ohm
S
S S
3.3K
Ohm
S
S
S
S
S
1K
Ohm
1K
Ohm
1K
Ohm
1K
Ohm
S S
3.3K
Ohm
S S
3.3K
Ohm
S
3.3K
Ohm
Figure 13: Typical XR2400F Wiring Diagram
15.2 Lightning Protection
Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on input and
output circuits of the XR2400F. Additional surge protection is available by installing the DMP 370 or 370RJ
Lightning Suppressors.
XR2400F Installation Guide
Digital Monitoring Products
17
INSTALLATION
15.3 Accessory Devices
Interface Adaptor and Interface Cards
460 Interface Adaptor Card
Allows you to connect two or more expansion interface cards to the XR2400F panel. The 461 is an
expansion mother board that plugs into the J6 Interface Connector of the panel and is required when
using two or more Interface Cards. Use combinations of Interface Cards for expanding zones, network
interfacing, local printing, and connecting wireless devices. Requires Model 349, 350, or 350A Enclosure.
462N Network Interface Card
Allows you to connect the XR2400F to any compatible data network and use its communication capability
in place of standard dial out telephone lines. The 462N also provides an LX-Bus™ for connecting zone
and output expansion modules to the panel. The 462N is listed for Grade AA Burglary communication
and supplementary signaling.
462P Printer Interface Card
Allows you to connect the XR2400F to any compatible serial printer providing real-time event recording
to the user. The 462P also provides an LX-Bus™ for connecting zone and output expansion modules.
472 Inovonics 900 MHz Interface Card
Provides an interface between the Inovonics FA400-DMP Wireless Receiver and the XR2400F panel. You
can use any of the wireless equipment compatible with the FA400-DMP to construct a strictly wireless
or combined wireless/hardwire system. Wireless functionality is listed for Household Fire and Burglary.
The 472 also provides one LX-Bus™ for connecting zone and output expansion modules.
481 Expansion Interface Card
Provides one LX-Bus for connecting up to 100 zone and output expansion modules.
Zone and Output Expansion Modules
710/710F Bus Splitter/Repeater
Allows you to increase keypad or LX-Bus™ wiring distance to 2500 feet. Model 710F is for 24 VDC
applications.
711/711E Single Point Zone Expanders
Provides one Class B zone for connecting burglary and non-powered Þre devices.
714, 714-8, 714-16 Zone Expanders
Provides Class B zones for connecting burglary and non-powered Þre devices.
715, 715-8, 715-16 Zone Expanders
Provides 12 VDC Class B powered zones for connecting smoke detectors, glassbreak detectors, and
other 2- or 4-wire devices.
725 Zone Expanders
Provides 24 VDC Class B powered zones for connecting smoke detectors, glassbreak detectors, and
other 2- or 4-wire devices.
716 Output Expander
Provides four Form C relays (SPDT) and four switched grounds (open collector) for use in a variety of
remote annunciation and control applications.
717 Graphic Annunciator Module
Provides 20 zone following annunciator outputs (open collector) for use in a variety of remote
annunciation and control applications.
Indicating and Initiating Devices
865 Supervised Style Y or Z NotiÞcation
Circuit Module
Provides up to 1.5 Amps of supervised alarm current when using the bell output of the XR2400F panel
and up to 5 Amps at 12 or 24 VDC when using a listed auxiliary power supply. The 865 can supervise
2-wire Style Y or W circuits or X circuits for ground faults, opens, shorts, and shorts with individual LED
annunciation.
866 NotiÞcation Circuit Module
Provides up to 1.5 Amps of supervised alarm current using the bell output of the XR2400F panel and up
to 5 Amps at 12 or 24 VDC when using a listed auxiliary power supply. The 866 can supervise Style W
circuits for opens and shorts.
867 Style W LX-Bus NotiÞcation Circuit
Module
Provides up to 1.5 Amps of supervised alarm current using the bell output of the XR2400F panel and
up to 5 Amps at 12 or 24 VDC when using a listed auxiliary power supply. The 867 connects to the LXBus™ of the XR2400F panel and provides one 2-wire Style W notiÞcation circuit for ground fault, open,
and short conditions. Individual Bell Relay addresses Bell Ring styles.
869 Dual Style D Initiating Module
Provides two Style D, 4-wire initiating zones for connecting waterßow switches and other non-powered
Þre and burglary devices.
Accessory Modules and Keypads
893A Dual Phone Line Module
Allows you to supervise two standard phone lines connected to an XR2400F panel. The 893A module
monitors the main and backup phone lines for a sustained drop in voltage and alerts users when voltage
drops below 3 VDC.
ePAD Virtual Keypads
Allows users to control the security system from any computer in the world using the Internet.
iCOM Internet Alarm Router
Allows the panel to send signals through the Internet/Ethernet.
iCOM-E High-Security Internet Alarm
Router
Allows the panel to send encrypted signals through the Internet/Ethernet.
630F Remote Fire Command Center
Allows you control the panel from various remote locations. You may connect up to eight 630F Remote
Fire Command Centers to the keypad bus on terminals 7, 8, 9, and 10.
Security Command LCD keypads
Allows you to control the panel from various remote locations. Connect up to eight supervised Model
690/790, 690F/790F, 791 or 793 Security Command® keypads to the keypad bus (terminals 7, 8, 9, and
10).
Table 5: Accessory Devices
Digital Monitoring Products
18
XR2400F Installation Guide
INSTALLATION
15.4 Mounting Keypads and Zone Expanders
Security Command keypads have removable covers that allow you to easily mount the keypad to a wall or
other ßat surface using the screw holes provided on each corner of the base. Before mounting the base,
connect the keypad wire harness leads to the keypad cable from the panel and to any device wiring run to
that location. Then attach the harness to the pin connector on the PC board, mount the base, and install the
keypad cover making sure all of the keys extend through their respective holes.
For the 690/690F keypads, you can use the Model 695 1-1/2” deep or the Model 696 1/2” deep backboxes.
For mounting keypads on solid walls, or for applications where conduit is required, use the Model 695 1-1/2”
deep or the Model 696 1/2” deep backboxes.
For the 790/790F, 793 keypads, you can use the Model 695 1-1/2” deep or the Model 696 1/2” deep
backboxes.
The DMP 710, 710F, 711, 711E, 714, 715, 716, 717, and 725 modules are each contained in molded plastic
housings with removable covers. The housing cover contains the module while the base provides you with
two mounting holes for installing the unit to a wall, switch plate, or other surface.
15.5 Connecting serial devices
Several factors determine the performance characteristics of the DMP LX-Bus™ and keypad bus: the length
of wire used, the number of devices connected, and the voltage at each device. When planning an LX-Bus™
and keypad bus installation, keep in mind the following information:
1. DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do not use
twisted pair or shielded wire for LX-Bus and keypad bus data circuits.
2. On keypad bus circuits, to maintain auxiliary power integrity when using 22-gauge wire do not exceed
500 feet. When using 18-gauge wire do not exceed 1,000 feet. To increase the wire length or to add
devices, install an additional power supply that is UL listed for Fire Protective Signaling, power limited,
and regulated (12 VDC nominal) with battery backup.
Note: Each panel allows a speciÞc number of supervised keypads. Add additional keypads in the
unsupervised mode. Refer to the panel installation guide for the speciÞc number of supervised keypads
allowed.
3. Maximum distance for any one bus circuit (length of wire) is 2,500 feet regardless of the wire gauge.
This distance can be in the form of one long wire run or multiple branches with all wiring totaling no
more than 2,500 feet. As wire distance from the panel increases, DC voltage on the wire decreases.
Maximum number of LX-Bus devices per 2,500 feet circuit is 40.
4. Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 VDC. If the
voltage at any device is less than the required level, an auxiliary power supply should be added at the
end of the circuit.
For additional information refer to the 710 Installation Sheet (LT-0310) and or the LX-Bus/Keypad Bus Wiring
Application Note (LT-2031).
Expansion Interface Cards (Models 462N, 462P, 462FM, 472, 481, and 482)
The LX-Bus provided on these cards requires only a 4-wire cable between the card and any devices
connected to the bus. You can connect devices (zone or output expanders) together on the same cable or
provide separate runs back to the cards. Up to 100 zones or relays are available on each LX-Bus.
Note: Do not use shielded wire when running an LX-Bus or keypad bus.
XR2400F Installation Guide
Digital Monitoring Products
19
INSTALLATION
Battery Information
16.1 Battery Only Restart
When powering up the XR2400F panel without AC power, it is necessary to short across the CR7 leads to pull
in the battery cutoff relay. The leads need a momentary short only. Once the relay has pulled in, the battery
voltage holds it in that condition. If the XR2400F panel is powered up with an AC transformer, the battery
cutoff relay is pulled in automatically.
16.2 Replacement Period
DMP recommends the battery be replaced every 3 to 5 years under normal use.
16.3 Discharge/recharge
The XR2400F battery charging circuit ßoat charges at 13.9 VDC at a maximum current of 1.2 Amps using a 40
VA transformer. The total current available is reduced by the combined auxiliary current draw from terminals
5, 6, and 24. The various battery voltage level conditions are listed below:
Battery Trouble:
Below 11.9 VDC
Battery Cutoff:
Below 10.2 VDC
Battery Restored:
Above 12.6 VDC
16.4 Battery Supervision
The XR2400F tests the battery when AC power is present. The test is done every 3 minutes and lasts for Þve
seconds. During the test, the panel places a load on the battery and if its voltage falls below 11.9 VDC a low
battery is detected. If AC power is not present, a low battery is detected any time the battery voltage falls
below 11.9 VDC.
If a low battery is detected with AC power present, the test is repeated every two minutes until the battery
charges above 12.6 VDC; the battery restored voltage. If a weak battery is replaced with a fully charged
battery, the restored battery will not be detected until the next two minute test is done.
16.5 Battery Cutoff
The panel disconnects the battery any time the voltage of the battery drops below 10.2 VDC. This prevents
deep discharge damage to the battery.
16.6 XR2400F Power Requirements
During AC power failure, the XR2400F panel and all auxiliary devices connected to the XR2400F draw their
power from the battery. All devices must be taken into consideration when calculating the battery standby
capacity. On the following page is a list of the power requirements of the XR2400F panel. First add the
current draw of the devices included in the XR2400F FACP:
• XR2400F Command Processor™ Panel
• The Fire Command Center
• 893A Dual Phone Line Module
• Two 866 NAC modules
• 462N Network Interface
Then add the additional current draw of Remote Fire Command Centers, zone expanders, smoke detector
output, and any other auxiliary devices used in the system for the total current required. The total is then
multiplied by the number of standby hours required to arrive at the total ampere-hours required.
See the Panel Standby Battery Power Calculations chart on the following page.
Digital Monitoring Products
20
XR2400F Installation Guide
INSTALLATION
16.7 XR2400F Standby Battery Calculations
Standby Battery Power Calculations
XR2400F Command Processor™ Panel
Relay Outputs 1-2 (ON)
Voltage Outputs 3-10 (ON)
Active Zones 1-8
Active Zones 9-10
2-Wire Smoke Detectors
Panel Bell Output
893/893A Dual Phone Line Module
460 Interface Adaptor Card
462N Network Interface Card
462P Printer Interface Card
472 Inovonics 900MHz Interface Card
481 Expansion Interface Card
485 Enhanced Access Control Expansion Card
865 Style y or Z NotiÞcation Module
866 Style W NotiÞcation Module
867 LX-Bus Style W NotiÞcation Module
630F Remote Fire Command Center
690/690F Security Command Keypad
Annunciator (ON)
790/790F Security Command Keypad
Active Zones (EOL Installed)
Annunciator (ON)
791 Easy Entry Keypad
Active Zones (EOL Installed)
Annunciator (ON)
793 Easy Entry Keypad
Active Zones (EOL Installed)
Annunciator (ON)
770, 771 Security Command Keypads
Active Zones (EOL Installed)
Annunciator (ON)
733 Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
734 Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
736P POPIT Interface Module
Radionics Popex, POPITs, OctoPOPITs
738A Ademco Wireless Interface Module
710 Bus Splitter/Repeater Module
710F Fire Bus Splitter/Repeater Module
711, 771E, 714 Zone Expansion Modules
Active Zones (EOL Installed)
714-8, 714-16 Zone Expansion Module
Active Zones (EOL Installed)
715 Zone Expansion Module
Active Zones (EOL Installed)
2-Wire Smokes
715-8, 715-16 Zone Expansion Modules
Active Zones (EOL Installed)
2-Wire Smokes
716 Output Expansion Module
Active Form C Relays
717 Graphic Annunciator Module
Annunciator Outputs
521LX, 521LXT, SLRLX Smoke Detectors
iCOM, iCOM-E Internet Alarm Routers
Aux. Powered Devices on Terminals 7 and 11
Other than Keypads and LX-Bus Modules
Qty
Qty
Qty
Qty
Qty
Qty
Standby Current
______x
80mA ______mA
______x
30mA ______
______x
5mA ______
______x
1.6mA ______
______x
4mA ______
______x
0.1mA ______
Qty ______x
Qty
Qty
Qty
Qty
______x
______x
______x
______x
Qty
Qty
Qty
Qty
Qty
______x
______x
______x
______x
______x
30mA
7mA
50mA
50mA
85mA
15mA
45mA
26mA
45mA
30mA
60mA
77mA
______
______
______
______
______
______
______
______
______
______
______
______
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty ______x
77mA ______
1.6mA ______
Qty
Qty
Qty ______x
100mA ______
1.6mA ______
Qty
Qty
Qty ______x
92mA ______
1.6mA ______
Qty
Qty
Qty ______x
Qty ______x
100mA ______
1.6mA ______
Qty
Qty
Qty ______x
Qty ______x
30mA ______
1.6mA ______
Qty ______x
Qty ______x
30mA ______
1.6mA ______
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
25mA
___mA
75mA
30mA
40mA
7mA
1.6mA
20mA
1.6mA
7mA
4mA
.1mA
20mA
4mA
.1mA
7mA
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
______x
______x
______x
______x
______x
______x
______x
______x
______x
______x
______x
______x
______x
Qty ______x
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
Qty ______x
10mA ______
Qty ______x
8.8mA ______
______mA
Qty
Qty
Qty
Qty
Qty
Alarm Current
80mA ______mA
______x
30mA ______
______x
5mA ______
______x
*2mA ______
______x
30mA ______
______x
0.1mA ______
1500mA ______mA
______x
50mA ______
7mA ______
______x
50mA ______
______x
50mA ______
______x
85mA ______
______x
15mA ______
45mA ______
______x
85mA ______
______x
75mA ______
______x
85mA ______
______x
92mA ______
______x
84mA ______
20mA ______
______x
84mA ______
______x
*2mA ______
20mA ______
______x
100mA ______
______x
*2mA ______
20mA ______
______x
120mA ______
______x
*2mA ______
20mA ______
______x
100mA ______
______x
*2mA ______
20mA ______
______x
30mA ______
______x
*2mA ______
______x
20mA ______
______x
30mA ______
______x
*2mA ______
______x
20mA ______
______x
25mA ______
______x
___mA ______
______x
75mA ______
______x
30mA ______
______x
40mA ______
______x
7mA ______
______x
*2mA ______
______x
20mA ______
______x
*2mA ______
______x
7mA ______
______x
*30mA ______
______x
.1mA ______
______x
20mA ______
*30mA ______
.1mA ______
______x
7mA ______
______x
28mA ______
______x
10mA ______
______x
1mA ______
______x
*28mA ______
78.1mA ______
______mA
*Based on 10% of active zones in alarm
Total Standby ______mA
Total Alarm ______mA
Total Standby______mA x number of Standby Hours needed ______ =
________mA-hours
Total Alarm ______mA + ________mA-hours
Cannot exceed 7.7Ah with one Model 367 Battery
Total ________mA-hours
Cannot exceed 15.4Ah with two Model 367 Batteries
X .0001
Cannot Exceed 23.1Ah with three Model 367 Batteries
Cannot exceed 30.8Ah with four Model 367 Batteries
= ________Amp-hrs
Required
XR2400F Installation Guide
Digital Monitoring Products
21
INSTALLATION
Bell Output
17.1 Terminals 5 and 6
Terminal 5 supplies positive 12 VDC to power alarm bells or horns. The output is rated for a maximum
output of 1.5 Amps. This output can be steady or pulsed or temporal code 3 depending upon the Bell Action
speciÞed in Output Options. Terminal 6 is the ground reference for the bell circuit.
Keypad and Zone Expander Bus
18.1 Description
Terminals 7, 8, 9, and 10 of the XR2400F panel are for the keypad data bus. In addition to Fire Command
Centers and Remote Fire Command Centers, you can also connect any combination of up to eight zone
expanders, 5845LX Glassbreak detectors, and 6155LX PIRs to the data bus.
Note: Do not use shielded wire for LX-Bus or keypad bus circuits.
18.2 Terminal 7 - RED
This terminal supplies positive 12 VDC to power Fire Command Centers and zone expanders. This is also
where power for any auxiliary device is supplied. The ground reference for terminal 7 is terminal 10 with the
maximum output rated at 1 Amp.
The output current is shared with the smoke detector output on terminal 11 and Zones 9 and 10. All devices
totalled together must not exceed the panel’s maximum current rating of 1 Amp.
18.3 Terminal 8 - YELLOW
Data receive from keypads and zone expanders. It cannot be used for any other purpose.
18.4 Terminal 9 - GREEN
Data transmit to keypads and zone expanders. It cannot be used for any other purpose.
18.5 Terminal 10 - BLACK
Terminal 10 is the ground reference for Fire Command Centers, zone expanders, and any auxiliary devices
being powered by terminal 7.
Smoke Detector Output
19.1 Terminals 11 and 12
Terminal 11 supplies positive 12 VDC to power 4-wire smoke detectors and other powered devices. This
output can be turned off by the user for 5 seconds using the Sensor Reset User Menu option to allow latched
devices to reset. Terminal 12 is the ground reference for terminal 11.
19.2 Current Rating
The Output current from terminal 11 is shared with terminals 7, 26, and 28. The total current draw of all
devices powered from the panel must be included with terminal 11 calculations and must not exceed the
maximum output rating of 1 Amp.
Powered Zones for 2-Wire Smoke Detectors
20.1 Terminals 25-26 and 27-28
Two resettable Class B (Style A) 2-wire powered zones are provided on terminals 25 through 28 on the panel.
For programming purposes the zone numbers are 9 and 10. When using 725 Zone Expansion modules, use
UL Listed 6.8k Ohm EOL resistors. The UL compatibility identiÞer for the zones using 725 Zone Expansion
Modules is B. When using 715 Zone Expansion modules, use UL Listed 3.3k Ohm EOL resistors (Model 309).
When using all other zone expansion modules, use UL Listed 1.0k Ohm EOL resistors (Model 310). The UL
compatibility identiÞer for the zones is A.
Digital Monitoring Products
22
XR2400F Installation Guide
INSTALLATION
Do not mix detectors from different manufacturers on the same zone.
Caution: Performing a Sensor Reset will momentarily drop power to the devices on Zones 9 and 10. The
panel will view these zones 10 as “Open” while the power is dropped.
20.2 Compatible 2-Wire Smoke Detectors
Manufacturer
Model
Detector
ID
Base
Base
DC
# of
ID
Voltage Detectors
Range (12V/24V)
Zone
Expansion
Modules
Detection Systems
DS230, DS230F
B/A
MB2W, MB2WL
A
8.5-33
10
725
Detection Systems
DS250, DS250TH
B
MB2W, MB2WL
A
8.5-33
10/12
715, 715-8,
715-16, 725
Detection Systems
DS250HD
B
MB2W, MB2WL
A
8.5-33
10
715, 715-8,
715-16
Detection Systems
DS260
B/A
MB2W, MB2WL
A
8.5-33
17
725
Detection Systems
DS282, DS282TH
B
8.5-33
10/12
715, 715-8,
715-16, 725
DMP/Hochiki
SLK-835
HD-5
HSB-200, HSB200N
HB55
8-35
7
715, 715-8,
715-16
DMP/Hochiki
SLR-835
HD-3
NS6-100
HB55
8-35
7/14
715, 715-8,
715-16, 725
DMP/Hochiki
SLR-835B
HD-6
8-35
7/14
715, 715-8,
715-16, 725
Hochiki
SLR-835B-2
HD-6
8-35
14
725
Hochiki
SLR-24, SLR-24H
HD-3
NS4-220
HB-3
15-33
15
725
Hochiki
SIJ-24, DCD-190, DCD135
HD-3
NS4-220
HB-3
15-33
15
725
Hochiki
SLR-24, SLR-24H
HD-3
NS6-220
HB-3
15-33
15
725
Hochiki
SIJ-24
HD-3
NS6-220
HB-3
15-33
20
725
NS6-220
HB-3
Hochiki
DCD-190, DCD-135
HD-3
15-33
16
725
Sentrol/ESL
429AT, 521B, 521BXT
S09A
6.5-20
12
715, 715-8,
715-16
Sentrol/ESL
429C, 429CT, 521B/BXT
S10A
8.5-33
12
725
Sentrol/ESL
429CRT, 429CST,
429CSST, 521CRXT
S11A
8.5-33
12
725
Sentrol/ESL
711U, 712U, 713-5U,
713-6U, 721U, 721UT
S10A
701E, 70-1U,
702E, 702U
S00
8.5-33
12
725
Sentrol/ESL
731U, 723U
S11A
701E, 701U,
702E, 702U,
702RE, 702RU
S00
8.5-33
12
725
System Sensor
1100, 1400
STD
8.5-33
10
715
System Sensor
1151, 2151
STD
B110PL, B401
8.5-33
10/10
715, 725
System Sensor
1451, 2451TH
STD
B401, B401B
8.5-33
10
715
System Sensor
1451DH
STD
DH400
8.5-33
10
715
System Sensor
2100, 2100T
STD
8.5-33
10
715
System Sensor
2100S, 2100TS
A
8.5-35
12
725
System Sensor
2400, 2400AT, 2400AIT,
2400TH
STD
8.5-33
10
715
System Sensor
2451
STD
8.5-35
10
715
System Sensor
DH100P
A
8.5-35
10
725
B401, B401B,
DH400
Table 6: Compatible 2-Wire Smoke Detectors
XR2400F Installation Guide
Digital Monitoring Products
23
INSTALLATION
Protection Zones
21.1 Description
Zones 1 to 8 on the XR2400F panel (terminals 13 to 24) are all grounded burglary zones. For programming
purposes, the zone numbers are 1 through 8. Terminals 13 to 24 provide connection as listed below.
Terminal
Function
Terminal
Function
13
14
15
16
17
18
Zone 1 voltage sensing
Ground for Zones 1 & 2
Zone 2 voltage sensing
Zone 3 voltage sensing
Ground for Zones 3 & 4
Zone 4 voltage sensing
19
20
21
22
23
24
Zone 5 voltage sensing
Ground for Zones 5 & 6
Zone 6 voltage sensing
Zone 7 voltage sensing
Ground for Zones 7 & 8
Zone 8 voltage sensing
Note: Zones 1 through 4 have been pre-wired to the two 866 NAC modules and the 504-24 power supply. All
other zones are available.
The voltage sensing terminal measures the voltage through a 1k Ohm End-of-Line resistor to ground. Dry
contact sensing devices can be used in series (normally-closed) or in parallel (normally-open) with any of the
burglary protection zones.
1K Ohm
Normally
Closed
1K Ohm
Normally Open
1K Ohm
Combination Normally Open
and Normally Closed
Figure 14: Protection Zone Wiring
21.2 Operational Parameters
Each protection zone detects three conditions: open, normal, and short. The voltage and resistance
parameters for each condition are listed below:
Condition
Open
Normal
Short
Resistance on zone
over 1300 ohms
600 to 1300 ohms
under 600 ohms
Voltage on positive terminal
over 2.0 VDC
1.2 to 2.0 VDC
under 1.2 VDC
21.3 Zone Response Time
A condition must be present on a zone for 500 milliseconds before it’s detected by the XR2400F panel.
Ensure detection devices used on the protection zones are rated for use with this delay. The zones can also
be programmed for a fast response delay of 167 milliseconds.
21.4 Keyswitch Arming Zone
Using a keyswitch on an Arming type zone allows you to arm and disarm selected areas without having to
enter a user code.
Digital Monitoring Products
24
XR2400F Installation Guide
INSTALLATION
Dry Contact Relay Outputs
22.1 Description
The XR2400F panel provides two auxiliary SPDT relays when equipped with two DMP Model 305 relays in
sockets K6 (Output 1) and K7 (Output 2) and a Model 430 Output Harness. Each relay provides one single
pole, double throw (SPDT) set of contacts that can be operated by any of the functions listed below:
1) Activation by zone condition
Steady
Pulsing
Momentary
Follow
2) Activation by 24 hour 7 day schedule
One on and one off time per day for each relay
3) Manually from the Fire Command Center menu
4) Communication failure
5) Armed area annunciation
6) Fire Alarm or Fire Trouble
7) Other system conditions. See the Programming Guide (LT-0196).
22.2 Contact Rating
The Model 305 relay contacts are rated for 1 Amp at 30 VDC resistive. You can connect auxiliary power to the
common terminal of Relay Output 1 by installing the gray harness wire to terminal 7.
22.3 Output Harness Wiring
The relay contacts are accessible by installing the DMP 430 Output Harness on the 15-pin header labeled J2.
The contact locations on the wire harness are shown below:
Output
Output
Output
Output
Output
Output
Contact
1 normally
1 common
1 normally
2 normally
2 common
2 normally
closed
open
closed
open
Color
Violet
Gray
Orange
Violet
Gray
Orange
The relay contacts must be connected to devices located within the same room as the XR2400F panel.
12 VDC Voltage Outputs 3 to 10
23.1 Description
The XR2400F also provides eight 12 VDC, 50mA resistive voltage outputs on J2 to power external relays or
other devices. The voltage outputs are operated from the same functions as Outputs 1 and 2.
When connecting any devices to outputs 3 to 10, subtract the current draw of the device from the panel’s
available auxiliary power.
23.2 Output Harness Wiring
The voltage outputs are accessible by installing the DMP 430 Harness on the 15-pin header labeled J2. The
output locations are shown below:
Output
Color
Output
Color
Output
Color
3
White/Orange
6
White/Blue
9
White
4
White/Yellow
7
White/Violet
10
White/Black
5
White/Green
8
White/Gray
Ground
Black
Devices connected to the outputs must be located within the same room as the XR2400F panel.
XR2400F Installation Guide
Digital Monitoring Products
25
INSTALLATION
Reset and Tamper Headers
24.1 J16 Reset Header
The reset header is located just above the terminal strip on the right side of the circuit board and is used to
reset the microprocessor of the XR2400F. To reset the panel when Þrst installing the system, install the reset
jumper before applying power to the panel. After connecting the AC and battery, remove the reset jumper.
To reset the panel while the system is operational, such as prior to reprogramming, install the reset jumper
without powering down the system. Remove the reset jumper after one or two seconds.
After resetting the panel, you must begin programming within 30 minutes. If you wait longer than 30
minutes, you will have to reset the panel again.
J4
Tamper
Momentarily place the
Reset jumper over the J16
header to reset the panel.
J16
Panel Reset
AC
AC
+B
1
2
3
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
4
5
6
7
8
9
10
11
12
13
14
15
Z3 GND Z4
Z5 GND Z6
16
19
17
18
20
21
Z7 GND Z8
22
23
24
Z9+ Z9- Z10+ Z10-
25
26
27
28
Figure 15: XR2400F Panel Showing Reset
24.2 J4 Tamper Header
The J4 header is for use with the optional DMP 306 Tamper Harness. The harness connects to one or more
tamper switches mounted inside the panel enclosure to supervise against unauthorized opening or removal
of the enclosure. Refer to the wiring diagram on the enclosure door for correct tamper switch wiring.
How the tamper works
If the enclosure is opened or removed while one or more of the system’s areas are armed, a panel tamper
alarm is indicated. If all areas are disarmed, a panel tamper trouble is indicated.
Digital Monitoring Products
26
XR2400F Installation Guide
COMPLIANCE
Universal UL Burglary SpeciÞcations
25.1 Introduction
The programming and installation speciÞcations contained in this section must be completed when installing
the XR2400F panel in accordance with any of the UL burglary standards. Additional speciÞcations may be
required by a particular standard.
25.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70, UL 681, and UL 611 for all burglary installations.
25.3 Control outside of protected area
A Potter EVD or Sentrol 5402 should be used in place of a lined cabinet when the panel is installed outside
of the protected area.
25.4 Police station phone numbers
The digital dialer telephone number programmed for communication must not be a police station phone
number, unless that phone number is speciÞcally provided for that purpose.
25.5 Bypass reports
The Bypass Reports option must be programmed as YES for all UL burglary applications. See section 6.4 of
the XR200 and XR2400F Programming Guide (LT-0196).
25.6 System maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end
user is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance
program and acquainting the user with the correct procedure for use and testing of the system is also the
responsibility of the installing alarm company.
25.7 Partitions
The partition option may only be used for UL burglary applications when all partitions are used for one
subscriber. See section 4.2 and 11.2 of the XR200 and XR2400F Programming Guide (LT-0196). The panel must
be tamper protected and Sentrol Model 5402 or Potter EVD listed vibration detectors should be used.
25.8 UL Listed Receivers
UL has veriÞed operation with the DMP SCS-1 and SCS-1R, Sur-Gard SG-HLR2-DG, FBII CP220PB, OsborneHoffman Quick-Alert, and Radionics D6500 receivers.
UL 1023 SpeciÞcations
Household Burglar-Alarm System Units
26.1 Bell cutoff
The Bell Cutoff time cannot be less than Þve minutes. See section 8.2 of the XR200 and XR2400F
Programming Guide (LT-0196).
26.2 Entry delay
The maximum entry delay used must not be more than 45 seconds. See section 7.3 of the XR200 and
XR2400F Programming Guide (LT-0196).
26.3 Exit delay
The maximum exit delay used must not be more than 60 seconds. See section 13.4 of the XR200 and XR2400F
Programming Guide (LT-0196).
26.4 Weekly test
The product should be tested weekly.
XR2400F Installation Guide
Digital Monitoring Products
27
COMPLIANCE
UL 1610 And 1076 SpeciÞcations
Central-Station and Proprietary Burglar-Alarm Units
27.1 Multiplex network capacity
The total number of panels assigned to a standard MPX receiving line of the SCS-1 Receiver System must not
exceed 90. This may be increased to 180 by setting the SNRM option to NO in the SCS-1 Receiver system. This
is to allow any signal from a XR2400F panel to be transmitted to the receiver within 90 seconds. This allows
Grade AA Multiplex service.
27.2 Opening/Closing reports
The Opening/Closing Reports option must be programmed as YES. See section 13.6 of the XR200 and
XR2400F Programming Guide (LT-0196).
27.3 Closing wait
The Closing Wait option must be programmed YES. See section 7.2 of the Programming Guide (LT-0196).
27.4 Proprietary dialer
The Model XR2400F provides Grade A proprietary service when conÞgured as a digital dialer.
27.5 AA Network Communication
When HST network communication is used, a dialer line must also be used along with the Model 893 Dual
Phone Line Module to supervise the dialer line. The HST network Check-in time must be set from 01 to
06 minutes or AA. This provides AA Central Station Service. See sections 3.2, 3.2.4, and 3.3 of the XR200
Programming Guide (LT-0196).
The Model XR2400F Protected Premises Control Unit is suitable for Grade AA service when conÞgured for
multiplex DNET or HST communication with SCS-1/SCS-1R receiving system. This conÞguration is approved
for:
AMCX - Central Station Alarm Units
APAW - Police Station Alarm Units
APOU - Proprietary Alarm Units
This approval is for communication over public data networks, provided that the protected premise
(XR2400F) and receiving units (SCS-1/SCS-1R) are listed. Additionally, the network device connected to the
462N Network Interface Card must be listed for UL Fire and Shock hazards.
For combined burglary and Þre alarm systems, UL has an established set of requirements that specify certain
hardware redundancies and communication protocols to ensure that indications of a Þre or burglary are
properly transmitted at the time of their occurrence.
Typically in a combined system, two dialer phone lines are dedicated to the alarm. This limits the
interruption of normal business phone trafÞc caused by supervisory communication requirements of the
alarm system. With the DMP system communicating over a data network however, this interruption of
business phones is avoided by the panel’s ability to send its trafÞc at any time directly over the network.
The business phone lines are then used only to send a nightly Recall Test report or the report of an actual
alarm to the central monitoring station. This eliminates the monthly expense of two phone lines dedicated
to the alarm.
The DMP products meeting the UL requirements include the listed Model 893 Dual Phone Line Module used
in supervising two separate analog phone lines and the Model 462N Network Interface Card listed as a
supplementary signaling device for commercial Þre systems.
If the requirement for the two dedicated phone lines is made by the local AHJ for the purpose of avoiding
situations where the burglary/Þre alarm system is incapable of communicating, the DMP panels have a builtin ability to seize the phone line and interrupt any call in progress as required by NFPA and UL. Instructions
to the system installer for correctly wiring of the telephone jacks is also included in all DMP installation
guides as an added measure of ensuring the system’s communicating ability.
Digital Monitoring Products
28
XR2400F Installation Guide
COMPLIANCE
UL 1635 SpeciÞcations
Digital Burglar Alarm Communicator System Units
28.1 System trouble display
The Status List Display must include at least one keypad that displays system monitor troubles. See section
10.1 of the XR200 and XR2400F Programming Guide (LT-0196).
28.2 Digital Dialer telephone number
Both programmed telephone numbers must begin with a D or P. See sections 3.17 and 3.18 of the XR200 and
XR2400F Programming Guide (LT-0196).
28.3 Entry delay
The maximum entry delay used must not be more than 60 seconds. See section 7.3 of the XR200 and
XR2400F Programming Guide (LT-0196).
28.4 Exit delay
The maximum exit delay used must not be more than 60 seconds. See section 13.4 of the XR200 and XR2400F
Programming Guide (LT-0196).
28.5 Test time
The Test Time option must be programmed so that the XR2400F sends a report once every 24 hours. See
sections 3.8 to 3.10 of the Programming Guide (LT-0196).
28.6 Closing wait
The Closing Wait option must be programmed YES. See section 7.2 of the Programming Guide (LT-0196).
UL 365 And 609 SpeciÞcations
Police Station Connected and Local Burglar Alarm Units and Systems
29.1 System trouble display
The Status List Display must include at least one keypad that displays system monitor troubles. See section
10.3 of the Programming Guide (LT-0196).
29.2 Grade A bell
A Grade A local audible signal appliance must be used.
29.3 Bell cutoff
The Bell Cutoff time cannot be less than 15 minutes. See section 8.2 of the Programming Guide (LT-0196).
29.4 Automatic bell test
The Automatic Bell Test option must be programmed as YES. See section 8.3 of the Programming Guide.
29.5 Line security for Police Connect
Basic line security is provided when the Model XR2400F is conÞgured as a dialer system.
29.6 High Line Security
High Line Security is provided when conÞgured as a MPX, DNET, or HST system. When HST communication
is used, a dialer line must also be used along with the Model 893 Dual Phone Line Module to supervise
the dialer line. The HST Check-in time must be set from 01 to 06 minutes or AA. See section AA Network
Communication (27.5). Also see sections 3.2, 3.2.4, and 3.3 of the XR200 and XR2400F Programming Guide
(LT-0196).
XR2400F Installation Guide
Digital Monitoring Products
29
COMPLIANCE
Universal UL And NFPA Fire Alarm SpeciÞcations
30.1 Introduction
The programming and installation speciÞcations contained in this section must be completed when installing
the Model XR2400F in accordance with any of the UL or NFPA Þre standards. Additional speciÞcations may be
required by a particular standard.
30.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.
30.3 Transformer
A wire-in transformer should be used. Use the 16 VAC 40 VA DMP Model 320. The transformer must be
mounted within 20 feet of the panel connected by conduit.
30.4 End-of-Line resistor
The DMP Model 310 1k Ohm EOL resistor should be used on all 1k Ohm EOL Þre zones.
30.5 System trouble display
The Status List Display must include at least one keypad that displays system monitor troubles. See section
10.3 of the Programming Guide (LT-0196).
30.6 Fire display
The Status List Display must include at least one keypad that displays troubles and alarms on Þre type zones.
See section 10.4 of the Programming Guide (LT-0196).
30.7 Police station phone number
The digital dialer telephone number programmed for communication must not be a police station phone
number, unless that phone number is speciÞcally provided for that purpose.
30.8 System maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end
user is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance
program and acquainting the user with the correct procedure for use and testing of the system is also the
responsibility of the installing alarm company.
30.9 Audible alarm
Fire Type zones should be programmed to activate an audible alarm. The Bell Action for Fire Type zones
should not be programmed as “N”. See section 8.4.1 in the Programming Guide (LT-0196).
30.10 Fire zone programming
If a retard delay is used on a waterßow zone, it cannot exceed 90 seconds and any retard delay in the
waterßow initiating devices must be subtracted from the 90 seconds allowed. See sections 14.4 and 14.17 in
the Programming Guide (LT-0196). The retard delay should not be used on a zone with smoke detectors.
30.11 Style D zones
If required, the DMP 869 Dual Style D Initiating Module provides for connection of two Style D zones to the
Model XR2400F. See section Dual Style D Zone Module Installation in System Wiring Diagrams and the 869
Installation Guide (LT-0186) for wiring information.
30.12 Video Option
The Video option must be selected as NO when any Þre protection is connected to the XR2400F. See section
7.9 in the Programming Guide (LT-0196).
30.13 UL Listed Receivers
UL has veriÞed operation with the DMP SCS-1/SCS-1R (SDLC), Sur-Gard SG-HLR2-DG (CID, M2E), FBII CP220PB
(CID), Osborne-Hoffman Quick-Alert (CID, M2E), and Radionics D6500 (M2E) receivers.
Digital Monitoring Products
30
XR2400F Installation Guide
COMPLIANCE
UL 985 NFPA 72 (Chapter 2) SpeciÞcations
Household Fire Warning System Units
31.1 Bell output deÞnition
The Bell Output of the Model XR2400F must be programmed to operate steady on burglary alarms and
pulsed or temporal on Þre alarms. See section 8 of the Programming Guide (LT-0196).
UL 864 NFPA 72 (Chapter 9) SpeciÞcations
Control Units for Fire-Protective Signaling Systems
32.1 Zone restoral reports
The Restoral Reports option must be selected as YES or DISARM. See section 6.3 in the Programming Guide
(LT-0196).
32.2 Power fail delay
The Power Fail Delay option must be selected as 6 hours. See section 7.6 of the Programming Guide (LT0196).
32.3 Sprinkler supervisory
Any zone used for sprinkler supervisory must be programmed with “SPRINKLR XXX” as the zone name. The
last three characters in the zone name may be assigned a number to identify the zone. The Model 893 or
893A Dual Phone Line Module must be used on all sprinkler supervisory systems.
32.4 DACT systems
Two phone lines must be used. The two phone lines cannot be ground start or party lines. The 893 or 893A
Dual Phone Line Module is used to provide connection of two phone lines to the system. The 2ND Phone Line
communication option must be selected as YES. See section 3.3 of the Programming Guide (LT-0196).
Two different phone numbers must be programmed for digital communication. See sections 3.17 and 3.18
of the Programming Guide (LT-0196). The Test Time option must be programmed so that the XR2400F sends a
report every 24 hours. See sections 3.8 to 3.10 of the Programming Guide (LT-0196).
Additionally, you can use the 462N Network Interface Card and the HST (Host) Communication type for
supplementary communication over digital data networks.
32.5 Type 2 and Type 3 Central Station Service
Type 2 and Type 3 Central Station Service can be provided by using MPX communication to the DMP SCS-1/
SCS-1R Receiver system. See section 3.2 of the Programming Guide (LT-0196).
32.6 Type 1 Central Station Service
Type 1 Central Station Service can be provided by using MPX as the main communication and digital dialer
as backup. The 893 Dual Phone Line Module is used to provide connection of the MPX and dialer lines. See
section 3.2 of the Programming Guide (LT-0196). If Type 1 Central Station service is provided, the Test Time
option must be programmed to send a report every 24 hours. See sections 3.8 to 3.10 of the Programming
Guide (LT-0196).
With both Type 1 and Type 2 Central Station service, the total number of panels assigned to a standard
MPX receiving line of the SCS-1/SCS-1R Receiver System must not exceed 90. This may be increased to 180
by setting the SNRM option to NO in the SCS-1/SCS-1R Receiver system. This is to allow any signal from a
XR2400F to be transmitted to the receiver within 90 seconds.
32.7 Local Protective Signaling Systems
The DMP Model 865, 866, or 867 NotiÞcation Circuit Module must be used on the bell circuit for detection
of shorts and grounds. See sections 25.1 to 25.3 for wiring diagrams. Model 770 series keypads that are used
to display troubles for local Þre alarm systems must be installed within a DMP Model 777 Keypad Protector.
Model 790 series keypads that are used to display troubles for local Þre alarm systems must be installed
within a DMP Model 777 with 777S 1.0” spacer. Any burglary or other off premises communication must be
done with the Model 893 or 893A Dual Phone Line Module.
XR2400F Installation Guide
Digital Monitoring Products
31
COMPLIANCE
32.8 Proprietary Protective Signaling Systems
The total number of panels assigned to one MPX or DNET receiving line of the DMP SCS-1 Receiver system
must not exceed 90. This may be increased to 180 by setting the SNRM option to NO in the SCS-1 Receiver
system. This allows any report from a XR2400F to be sent to the receiver within 90 seconds.
32.9 Remote Station Protective Signaling Systems
You must provide 60 hours of standby battery. Up to four 12 VDC, 6.5Ah batteries may be used. See section
Standby Battery Power Calculations. Two Radionics Model D127 Reversing Relay Modules provide two
reversing polarity telephone connections. See section Remote Station Reversing Relay Connection and the
D127 Installation Instruction sheet for wiring details. A DMP Model 893 or 893A is used to provide two line
dialer communication or Type 1 Multiplex communication.
32.10 Fire Protective Signaling Systems with an iCOM™
The XR2400F Panel must be programmed as described below for Fire Protective Signaling Systems using an
iCOM™ Internet Alarm Router for communication.
• UL AA must be programmed as NO
• SUB CODE must be programmed as YES
• CHECKIN must be programmed as 1
• RETRY TIME must be programmed as 1
• FAIL TIME must be programmed as 1
• NET TRBL must be programmed as YES
Refer to the iCOM™ Internet Alarm Router Installation Sheet (LT-0587) for more information.
California State Fire Marshal SpeciÞcations
33.1 Bell output deÞnition
The Bell Output of the XR2400F panel must be programmed to operate steady on burglary alarms and pulsed,
temporal, or California School Code on Þre alarms. See sections 8.4.1 and 8.4.2 of the Programming Guide
(LT-0196).
Digital Monitoring Products
32
XR2400F Installation Guide
XR2400F Installation Guide
Notification Circuit Module
DMP Model 865
25mA @12 VDC
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In +
5 Bell PWR In 6 Bell Out A +
7 Bell Out A 8 Bell Out B +
9 Bell Out B 10 Bell Trouble
11 Bell Trouble
865
Module
Normal/Silence Switch
Power Supply Trouble
Contacts N/C
+ Auxiliary
Power
Supply
AUX PWR
GND
Alarm In
Bell PWR In
Bell Out +
Bell Out Bell Trouble
Bell Trouble
24 VDC 5
Amp
Maximum
1
2
3
4
5
6
7
8
866
Module
Normal/Silence Switch
S
S
S
S
1K EOL
S
S
S
S
UL Listed,
Polarized
Notification
Appliances
24 VDC 5
Amp
Maximum
+ Auxiliary
Power
Supply
S
S
S
S
S
S
Power Supply
Trouble
Contacts N/C
Each 866 Notification Appliance
Circuit Module in alarm draws up to
30mA through its Terminal 3 Alarm
Input and 45mA from its Terminal 1
Aux Power Input.
Style W
10K EOL
DMP Model 308
-
+
1
AC
2
AC
3
+B
J11
J10
J4
Tamper
Header
4
5
6
S
8
9
S
10
11
12
13
14
15
16
Each 865 Notification Appliance
Circuit Module in alarm draws up to
59mA through its Terminal 3 Alarm
Input and 26mA from its Terminal 1
Aux Power Input.
7
S
17
Note: If an auxiliary power supply is not used, terminals 3 and 4 can be
jumpered together to supply Bell Power from the XR200 panel. A
maximum of 1.5 Amps as 12 VDC is available from terminal 5 of the
XR200 panel.
S
18
Z3 GND Z4
21
22
23
24
25
26
27
28
Z9+ Z9- Z10+ Z10-
S = Supervised Circuit
20
Z7 GND Z8
J16
Panel
Reset
462N Network Interface Card
The Auxiliary Power Supply and
Notification Circuit Module trouble
contact zone must be programmed as
a Supervisory Type zone and must be
selected for display in the keypad
status list (See section 10.6 in the
Programming Guide (LT-0196)).
19
Z5 GND Z6
J2 Output Header
XR2400F Command Processor™ Panel
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
DD, MPX
Selection
Headers
J12
UL Listed,
Polarized
Notification
Appliances
J3
Auxiliary Power Supply must be regulated, UL Listed for Fire Protective
Signaling Service. Power Supplies must have battery backup.
-
+
Style Z
To additional 866 Notification Circuit Modules. Up to a
maximum of twenty-five 866 Modules on the XR2400F panel.
All modules must be installed in a 340FC, 349, or 350
Notification Circuit Module Enclosure connected by no more than 20 feet of conduit.
DMP Model 866
45mA @12 VDC
WIRING DIAGRAMS
System Wiring Diagrams
34.1 Multiple NotiÞcation Circuit Modules
Digital Monitoring Products
33
WIRING DIAGRAMS
J12
J11
XR2400F Command Processor™ Panel
J3
J4
Tamper
Header
DD, MPX
Selection
Headers
Answering Machine
Bypass Relay
Use Model 305
462N Network Interface Card
34.2 Multiple NotiÞcation Circuit Modules for Zoned Annunciation
J2 Output Header
All outputs must be located
Ground Start Relay within the same room as
K2 K4 Use Model 305
the control panel.
To additional Zone 1 Notification Circuit
Modules.
Install up to a maximum of twenty-five
866 Modules by using the relay outputs
available on the XR2400F panel.
J10
Relay Output 1
Use Model 305
All modules must be installed in a
340FC, 349, or 350 Enclosure connected
by no more than 20 feet of conduit.
AC
AC
+B
1
2
3
4
5
6
8
7
S
10
9
14
15
16
19
17
S
S
Common Notification
Circuit Module
DMP Model 866
45mA @ 12 VDC
10K EOL
DMP Model 308
S
S
S
Style W
S
UL Listed,
Polarized
Notification
Appliances
S
1K EOL
S
+ 504-24
Power
Supply
Each 866 Notification Appliance
Circuit Module in alarm draws up to
30mA through its Terminal 3 Alarm
Input and 45mA from its Terminal 1
Aux Power Input.
504-24
Power
Supply
+ -
24 VDC 5
Amp
Maximum
+ 504-24
Power
Supply
20
21
22
23
24
Z9+ Z9- Z10+ Z10-
25
26
Outputs 3 through 10
can switch up to
50mA each at 12
VDC. This is
sufficient for one 866
Module per indicating
zone 3 through 10.
27
28
Zone 1 Output
Relay 1
N/O
Orange
Zone 2 Output
Relay 1
N/O
Orange
10K EOL
DMP Model 308
866 Module
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out 7 Bell Trouble
8 Bell Trouble
S
18
Z7 GND Z8
Relay 1 and 2
Common
Gray
Normal/Silence Switch
S
Power Supply Trouble
Contacts N/C
24 VDC
5 Amp
Maximum
13
Z5 GND Z6
S = Supervised Circuit
Normal/Silence Switch
24 VDC
5 Amp
Maximum
12
Z3 GND Z4
S S
S
866 Module
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out 7 Bell Trouble
8 Bell Trouble
11
J16
Panel
Reset
Relay Output 2
Use Model 305
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
S
Zone 1 Notification
Circuit Module
DMP Model 866
45mA @ 12 VDC
K6 K7
Style W
UL Listed,
Polarized
Notification
Appliances
1K EOL
Auxiliary Power Supply must be
regulated, UL Listed for Fire Protective
Signaling Service. Power Supplies must
have battery backup.
Power Supply Trouble
Contacts N/C
Normal/Silence Switch
+
865 Module
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In +
5 Bell PWR In 6 Bell Out A +
7 Bell Out A 8 Bell Out B +
9 Bell Out B 10 Bell Trouble
11 Bell Trouble
Zone 2 Notification
Circuit Module
DMP Model 865
26mA @ 12 VDC
Style y
+
UL Listed,
Polarized
Notification
Appliances
S
S
S
S
S
S
To additional notification
circuit modules.
Digital Monitoring Products
34
Each 865 Notification Appliance
Circuit Module in alarm draws up to
59mA through its Terminal 3 Alarm
Input and 26mA from its Terminal 1
Aux Power Input.
The Auxiliary Power Supply and
Notification Circuit Module trouble
contact zone must be programmed as
a Supervisory Type zone and must be
selected for display in the keypad
status list (See section 10.6 in the
Programming Guide (LT-0196)).
Note: If an auxiliary power supply is
not used, terminals 3 and 4 can be
jumpered together to supply Bell
Power from the XR2400F panel.
A maximum of 1.5 Amps as 12 VDC is
available from terminal 5 of the
XR2400F panel.
XR2400F Installation Guide
XR2400F Installation Guide
GND
Fault A
Zone A
GND
Fault B
A1
A1
A2
A2
Zone A
GND
Aux Power
Zone B
B1
B1
Zone B
B2
B2
Model 869
Dual Style D Initiating Module
DMP Model 869
25mA Standby, 75mA Alarm
@ 12 VDC
1
AC
2
AC
S
S
S
S
S
S
S
S
J3
3
+B
J11
J10
J4
Tamper
Header
S
4
5
6
8
9
10
11
12
S
13
14
S
15
16
18
19
20
21
22
23
24
Z7 GND Z8
S = Supervised Circuit
17
Z5 GND Z6
Heat Detectors, manual pull stations, or any other UL
Listed shorting device. Unlimited number of units.
S
7
Z3 GND Z4
J2 Output Header
J16
Panel
Reset
25
26
27
28
Z9+ Z9- Z10+ Z10-
XR2400F Command Processor™ Panel
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
DD, MPX
Selection
Headers
J12
WIRING DIAGRAMS
34.3 Dual Style D Zone Module Installation
Digital Monitoring Products
35
462N Network Interface Card
WIRING DIAGRAMS
J12
J11
XR2400F Command Processor™ Panel
J3
J4
Tamper
Header
DD, MPX
Selection
Headers
Answering Machine
Bypass Relay
Use Model 305
K2 K4
462N Network Interface Card
34.4 Remote Station Reversing Relay Connection
Note: Output 3 must be programmed as a Fire Alarm
Output and Output 4 must be programmed as a Fire
Trouble Output. See Output Options section of the
XR200/XR2400F Programming Guide (LT-0196).
J2 Output Header
All outputs must be located
within the same room as
the control panel.
Ground Start Relay
Use Model 305
Outputs 3 through 6 supply
up to 50mA at 12 VDC.
J2 Output Header
Model 430
Output Harness
J10
Relay Output 1
Use Model 305
AC
AC
1
2
+B
3
K6 K7
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
4
5
6
7
S
8
9
10
11
12
13
14
J16
Panel
Reset
Relay Output 2
Use Model 305
15
Z3 GND Z4
Z5 GND Z6
16
19
17
18
20
21
Z7 GND Z8
22
23
24
Z9+ Z9- Z10+ Z10-
25
26
27
28
S
S
S
S = Supervised Circuit
Black
Red
S
+
-
+
-
+
Black
Red
Up to 60 hours of battery standby time can be supplied
using three or four 7.0Ah, sealed, Lead-Acid batteries.
Four 7.0Ah batteries may be required based on total current
draw of all devices connected to the panel. See section
titled 24 VDC NAC Standby Battery Calculations.
To connect four batteries to the XR2400F Command
Processor™ Panel, use three Model 318 Battery Harnesses.
-
+
-
All modules must be installed in a
UL Listed enclosure connected by
no more than 20 feet of conduit.
Reversing Relay Module
Radionics Model D127
5mA Standby, 55mA Alarm
@12 VDC
Alternate Alarm
Combo Alarm
Auxiliary Power In
+ Signal Voltage In
+ To Remote Receiver
- To Remote Receiver
- Signal Voltage In
EARTH GROUND
GROUND
GROUND
Fire Alarm Output 3 White/Orange
To Telephone Line
Intended for connection to a
polarity reversal circuit of a
remote station receiving unit
having compatible ratings.
Alternate Alarm
Combo Alarm
Auxiliary Power In
+ Signal Voltage In
+ To Remote Receiver
- To Remote Receiver
- Signal Voltage In
EARTH GROUND
GROUND
GROUND
Fire Trouble Output 4 White/Yellow
To Telephone Line
Reversing Relay Module
Radionics Model D127
5mA Standby, 55mA Alarm
@12 VDC
Digital Monitoring Products
36
XR2400F Installation Guide
WIRING DIAGRAMS
J12
J11
XR2400F Command Processor™ Panel
J3
J4
Tamper
Header
DD, MPX
Selection
Headers
Answering Machine
Bypass Relay
Use Model 305
K2 K4
462N Network Interface Card
34.5 Supervised Remote Relay
J2 Output Header
All outputs must be located
within the same room as
the control panel.
Ground Start Relay
Use Model 305
Model 430
Output Harness
J2 Output Header
J10
Relay Output 1
Use Model 305
AC
AC
+B
1
2
3
K6 K7
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
4
5
6
7
8
9
10
S
11
12
13
14
J16
Panel
Reset
Relay Output 2
Use Model 305
15
Z3 GND Z4
Z5 GND Z6
16
19
17
18
20
21
Z7 GND Z8
22
24
25
26
27
28
S
S = Supervised Circuit
S
23
Z9+ Z9- Z10+ Z10-
S
DPDT Relay
Use Model ASRB-1 from Advanced
Signaling. 30mA coil operating
current at 12 VDC.
Normally Open
contacts will
close on alarm.
Normally Closed
contacts will
Open on alarm.
Remote DPDT
Relay
DMP Part #DI-001 Rectifier (1N4001
diode) in series with input from Model
866 Module terminal 6.
The zone connected to
the Bell Trouble contacts
on the 866 Notification
Circuit Module must be
programmed as a
Supervisory Type zone
and selecetd for display
in the Status List. See
the XR200/XR2400F
Programming Guide
(LT-0196).
10K EOL Resistor
DMP Model 308
Wiring between the 866 Module
and the DPDT Relay is supervised
against open, shorts, and grounds.
Any of these trouble conditions will
cause the 866 Module's Bell
Trouble contacts to open.
Notification Circuit Module
DMP Model 866
45mA @12 VDC
The 866 Module must be
installed in the panel enclosure
or in a 340FC, 349, or 350
Enclosure connected by no more
than 20 feet of conduit.
Normal/Silence Switch
866
Module
1
2
3
4
5
6
7
8
XR2400F Installation Guide
AUX PWR
GND
Alarm In
Bell PWR In
Bell Out +
Bell Out Bell Trouble
Bell Trouble
1K EOL
Digital Monitoring Products
37
WIRING DIAGRAMS
34.6 Cellular Backup Installation for Derived Channel Burglary
Auxiliary
Power
Supply
The Secure-Com Cellular
System must be connected
to a separate power supply.
Use only for supplementary
(backup communication).
893A
Cellular
Transceiver
Cellular Data
Interface
J3
XR2400F Command Processor
Phone Jack
Connector
DCX Systems
STU-2Z
J6
Telco Jack
Output Header J2 All outputs must be
connected to devices located within the
same room as the panel.
1 2 3 4 5 6
J10
K6
N/O
Common
N/O
K7
Use EOL Termination
Assembly P/N 21024-0003
(590 Ohm 1/2 W Resistor)
Common
Command Processor Reset J16
AC
Auxiliary Power Supply must be
regulated, UL Listed for Fire
Protective Signaling Service.
Power Supplies must have battery backup.
1
AC
+B
-B
BELL
GND
RED
YEL
GRN
BLK
2
3
4
5
6
7
8
9
10
S
SM K G ND
11
12
Z1
GND
Z2
Z3
GND
Z4
Z5
GND
Z6
Z7
GND
Z8
Z9 +
Z9 -
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Z10 + Z10 27
28
S
S
Panel Auxiliary Power - Terminal 7
S = Supervised Circuit
Panel Common - Terminal 10
Supervisory Zone Input - Terminal 13
Note 1
Note 1
S
S
S
S
Note 1: Use EOL Termination Assembly P/N
21024-0001 (2.2k Ohm 1/2 W Resistor).
Digital Monitoring Products
38
XR2400F Installation Guide
WIRING DIAGRAMS
34.7 LX-Bus™ Module Connection
LX-Bus Expansion
Interface Card
DMP Models 462N, 462P,
472, or 481
Model 867
Notification Module
Normal/Silence Switch
Ground Fault LED
Bell Trouble LED
12 or 24 VDC
Bell Power
Supply
10K EOL Resistor
DMP Model 308
+ -
1 Bell In +
12 or 24 VDC
2 Bell In 3 Bell Out +
UL Listed,
Polarized
Notification
Devices
4 Bell Out 5 Bell Trouble
6 Bell Trouble
Each LX-Bus Module must
have its own independent
address ranging from 00 to
99. A Supervisory zone must
be programmed into the
XR2400F to properly
supervise each module.
S
S
S
S
7 PWR Mon.
8 Mon. RTN
Bell Relay
Address
Supervisory
Address
ONES
Bell Ring Style
TENS
ONES
Power Supply Monitor LED
Data LED
Red
Yellow
To additional LX-Bus Modules
Green
Black
S
S
S
S
S
Connect to panel
Supervisory zone
TENS
LX-Bus™ Wiring
= Supervised Circuit
Optional LED wiring 50mA at
50 VDC resistive
Relay 3
S
Relay 1
S
S
Relay 2
Open Collector
Annunciator Outputs
S
Relay 4
Form C Contacts
Typical
Normally Closed
Common
Normally Open
Model 716 Output
Expander Module
7m at 12 VDC
Optional LED wiring 50mA at
50 VDC resistive
Model 717 Graphic
Annunciator
Module
10m at 12 VDC
XR2400F Installation Guide
Digital Monitoring Products
39
WIRING DIAGRAMS
34.8 Second LX-Bus™ with Auxiliary Power Supply
LX-Bus Expansion Cards:
DMP Models 481, 462N, 462P, and 472
Interface Cards
J11
J4
Tamper
Header
DD, MPX
Selection
Headers
1
XR2400F
Command
Processor™
Panel
2
3
4
5
462N Network Interface Card
J12
J3
481
462N
Answering Machine
Bypass Relay
Use Model 305
K2 K4
Ground Start Relay
Use Model 305
460 Interface Adaptor Card
B
J2 Output Header
J10
Relay Output 1
Use Model 305
AC
AC
+B
1
2
3
K6 K7
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
4
5
6
7
8
9
10
11
12
13
14
J16
Panel
Reset
Relay Output 2
Use Model 305
15
Z3 GND Z4
Z5 GND Z6
16
19
17
18
20
Connect the red wire to Smoke
Output (terminal 11).
S
21
Z7 GND Z8
22
23
24
Do not connect
the red wire
between the
Interface Card
and the first
device.
Z9+ Z9- Z10+ Z10-
25
26
27
28
LX-Bus 1
= 521LX Addressable Smoke Detector
LX-Bus 2
100 zones on LX-Bus 1, Numbered 100 to 199.
S
S
S
S
S
Black
Green
Yellow
Red
S
Black
Green
Yellow
Red
S
100 zones on LX-Bus 2, Numbered 200 to 299.
S
S
S
S
710
S
Refer to LT-0310 for more
information about the 710 Bus
Splitter/Repeater Module.
Black
Green
Yellow
Red
N/O C N/C
S
Digital Monitoring Products
40
S
Black
Green
Yellow
Red
S
Black
Green
Yellow
Red
716
Program the 716 Output
Expander Module as
Sensor Reset Output.
DMP
505-12
XR2400F Installation Guide
XR2400F Installation Guide
AUX PWR
GND
Alarm In
Bell PWR In
Bell Out +
Bell Out Bell Trouble
Bell Trouble
1
2
3
4
5
6
7
8
AUX PWR
GND
Alarm In
Bell PWR In
Bell Out +
Bell Out Bell Trouble
Bell Trouble
866
Module
Normal/Silence Switch
Notification Circuit Module
DMP Model 866
45mA @12 VDC
1
2
3
4
5
6
7
8
866
Module
Normal/Silence Switch
Notification Circuit Module
DMP Model 866
45mA @12 VDC
1K EOL
S
1K EOL
S
Style W
10K EOL
DMP Model 308
Style W
-
+
-
+
10K EOL
DMP Model 308
3
2
1
J11
J10
4
5
6
S
8
9
S
10
11
12
13
S
S
S
14
AC
Green
LED
AC AC
DC
Red
LED
+ Bat -
24 VDC 4 Amp
S
15
504-24 Power Supply
7
S
S
17
S
18
19
21
22
23
24
Z7 GND Z8
25
26
27
28
Z9+ Z9- Z10+ Z10-
J16
Panel
Reset
462N Network Interface Card
Power Supply
Trouble
Contacts N/C
NC C NO NC C NO
+ DC -
The Power Supply and Notification
Circuit Module trouble contact
zone must be programmed as a
Supervisory Type zone and must
be selected for display in the
keypad status list (See section
10.6 in the Programming Guide
(LT-0196)).
20
Z5 GND Z6
AC TRBL BATT TRBL
S
16
Z3 GND Z4
J2 Output Header
This diagram illustrates an example
configuration that would allow strobes to
operate after the horns or bells are silenced
at the keypad. To stop the strobes in this
configuration, perform a Sensor Reset from
the User Menu.
XR2400F Command Processor™ Panel
-B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2
J12
Horns or
Bells
+B
AC
AC
J3
Auxiliary Power Supply must be regulated, UL
Listed for Fire Protective Signaling Service.
Power Supply must have battery backup.
Strobes
S = Supervised Circuit
WIRING DIAGRAMS
34.9 Multiple NotiÞcation Circuits with Strobes and Bells
Digital Monitoring Products
41
OPERATING INSTRUCTIONS
XR2400F Addressable Fire Alarm Control Panel
NORMAL STANDBY CONDITION
When the system is in the normal standby condition, the display shows either the time
of day or a blank display.
ALARM CONDITION
When the system is in an alarm condition, the display shows the alarmed zone name(s)
followed by an alarm display.
Keyswitch operation
In order to use the four function keys, the keyswitch must be turned to the enable
position.
ALARM SILENCE
To silence the alarm while the bell or siren is sounding, press the key labeled “Silence”
or enter your code number and press the COMMAND key. This silences the alarm but
does not cancel any alarm reports to the central station.
RESETTING DETECTORS
To reset a smoke or other detector, press the key labeled “Reset” or enter the User
Menu by pressing the COMMAND key until MENU? NO YES appears in the display. Press
the top row key under YES. The display shows ENTER CODE: - . Enter your code number
and press COMMAND. The display now shows ALARM SILENCE?. Press the COMMAND key
until SENSOR RESET? appears in the display. Press any top row key.
TROUBLE CONDITION
When a device is in a trouble condition, the keyboard tones and displays the zone or
device name followed by TRBL. Press any top row key to silence.
SYSTEM TESTING
You should test the security system periodically to ensure proper operation. You can do
this by pressing the key labeled “Test” or through a function in the User Menu. After
entering the User Menu, press the COMMAND key until SYSTEM TEST? displays. Press
any top row key. The system bell, battery, and communication to the central station
system is then tested.
ALARM SERVICE
If service is required for this system, please contact:
Company ________________________________________________________
Address _________________________________________________________
Telephone _______________________________________________________
The operating instructions above should be attached to the
front, or framed and located adjacent to, the Fire Alarm
Control Panel or a Remote Fire Command Center.