INSTALLATION GUIDE XR2400F ADDRESSABLE FIRE ALARM CONTROL PANEL MODEL XR2400F Addressable Fire Alarm Control Panel INSTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed and used properly in strict accordance with the manufacturer’s instructions, may cause interference with radio and television reception. It has been type tested and found to comply with the limits for a Class B computing device in accordance with the speciÞcation in Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the installer is encouraged to try to correct the interference by one or more of the following measures: Reorient the receiving antenna Relocate the computer with respect to the receiver Move the computer away from the receiver Plug the compute into a different outlet so that computer and receiver are on different branch circuits If necessary, the installer should consult the dealer or an experienced radio/television technician for additional suggestions. The installer may Þnd the following booklet, prepared by the Federal Communications Commission, helpful: “How to identify and Resolve Radio-TV Interference Problems.” This booklet is available from the U.S. Government Printing OfÞce, Washington D.C. 20402 Stock No. 004-000-00345-4 Copyright © 2000 - 2003 Digital Monitoring Products, Inc. Information furnished by DMP is believed to be accurate and reliable. This information is subject to change without notice. TABLE OF CONTENTS Revisions to This Document Introduction 1.1 1.2 1.3 1.4 1.5 1.6 Mounting 2.1 2.2 2.3 2.4 2.5 2.6 Overview................................................1 System Components ...............................1 Power SpeciÞcations ...............................1 Before you begin ....................................1 About this Guide .....................................1 How to use this Guide .............................1 Mounting the Enclosure...........................2 Surface Mounting....................................2 Flush Mounting .......................................2 Fire Command Center LCD Keyboard ........2 Metal Backplate ......................................2 Wiring Diagram.......................................3 AC Connection 3.1 3.2 3.3 3.4 Transformers and AC Power Connection ...4 28 VAC Transformer ................................4 16 VAC Transformer ...............................4 Earth Ground from the XR2400F Panel ....4 Secondary Power Supply 4.1 4.2 4.3 Description .............................................5 Battery Connection to XR2400F Command Processor panel ......................5 Battery Connection to the 504-24 Power Supply .........................................5 Two 866 NAC Modules 5.1 5.2 5.3 5.4 Description .............................................6 Connection .............................................6 Bell Silence/Bell Trouble ..........................6 NotiÞcation Appliances ...........................7 462N LX-Bus™ Expansion Card 6.1 6.2 6.3 Description .............................................8 LX-Bus™ Expansion Capability .................8 Installing the 462N Module ......................8 Telephone RJ Connector 7.1 7.2 7.3 7.4 Description .............................................9 FCC registration .....................................9 NotiÞcation.............................................9 Ground start...........................................9 893A Dual Phone Line Module 8.1 8.2 8.3 8.4 8.5 8.6 XR2400F Installation Guide Description ...........................................10 Connection ...........................................10 Jumper Settings....................................10 Digital Dialer/Multiplex ..........................10 Phone Line Monitor ...............................10 Processor Fail Buzzer.............................10 Digital Monitoring Products i TABLE OF CONTENTS 504-24 Power Supply 9.1 9.2 9.3 9.4 9.5 9.6 Description ...........................................11 LED’s ..................................................11 504-24 Condition Chart .........................11 504-24 UL Listings ................................11 24 VDC NAC Standby Battery Calculations11 Connection ...........................................12 Interconnect Wiring Harness 10.1 Interconnect Harness ............................12 Fire Command Center 11.1 11.2 11.3 Description ...........................................13 Connection ...........................................13 Remote Fire Command Center ...............13 XR2400F Command Processor Panel 12.1 12.2 12.3 12.4 Description ...........................................14 Connection ..........................................14 Relays .................................................14 Zone Reference ....................................14 XR2400F Product SpeciÞcations 13.1 13.2 13.3 13.4 13.5 13.6 Power Supply .......................................15 Communication.....................................15 Panel Zones..........................................15 Remote Annunciator .............................15 LX-Bus™ ..............................................15 Outputs................................................15 Expansion 14.1 14.2 Expansion Zones...................................16 Output (Relay) Expansion ......................16 Accessory Devices 15.1 15.2 15.3 15.4 15.5 Wiring Diagram.....................................17 Lightning Protection ..............................17 Accessory Devices.................................18 Mounting Keypads and Zone Expanders..19 Connecting serial devices ......................19 Battery Information 16.1 16.2 16.3 16.4 16.5 16.6 16.7 Battery Only Restart..............................20 Replacement Period ..............................20 Discharge/recharge...............................20 Battery Supervision ...............................20 Battery Cutoff.......................................20 XR2400F Power Requirements ...............20 XR2400F Standby Battery Calculations....21 Bell Output 17.1 Digital Monitoring Products ii Terminals 5 and 6 .................................22 XR2400F Installation Guide TABLE OF CONTENTS Keypad and Zone Expander Bus 18.1 18.2 18.3 18.4 18.5 Description ...........................................22 Terminal 7 - RED ..................................22 Terminal 8 - YELLOW ............................22 Terminal 9 - GREEN ..............................22 Terminal 10 - BLACK .............................22 Smoke Detector Output 19.1 19.2 Terminals 11 and 12..............................22 Current Rating ......................................22 Powered Zones for 2-Wire Smoke Detectors 20.1 Terminals 25-26 and 27-28 ....................22 20.2 Compatible 2-Wire Smoke Detectors ...........23 Protection Zones 21.1 21.2 21.3 21.4 Description ...........................................24 Operational Parameters .........................24 Zone Response Time .............................24 Keyswitch Arming Zone .........................24 Dry Contact Relay Outputs 22.1 22.2 22.3 Description ...........................................25 Contact Rating......................................25 Output Harness Wiring ..........................25 12 VDC Voltage Outputs 3 to 10 23.1 23.2 Description ...........................................25 Output Harness Wiring ..........................25 Reset and Tamper Headers 24.1 24.2 J16 Reset Header .................................26 J4 Tamper Header ................................26 Universal UL Burglary SpeciÞcations 25.1 25.2 25.3 25.4 25.5 25.6 25.7 25.8 Introduction .........................................27 Wiring..................................................27 Control outside of protected area ...........27 Police station phone numbers ................27 Bypass reports......................................27 System maintenance .............................27 Partitions..............................................27 UL Listed Receivers ...............................27 UL 1023 SpeciÞcations 26.1 26.2 26.3 26.4 Bell cutoff.............................................27 Entry delay...........................................27 Exit delay .............................................27 Weekly test ..........................................27 UL 1610 And 1076 SpeciÞcations 27.1 27.2 27.3 27.4 27.5 XR2400F Installation Guide Multiplex network capacity ....................28 Opening/Closing reports ........................28 Closing wait..........................................28 Proprietary dialer ..................................28 AA Network Communication ..................28 Digital Monitoring Products iii TABLE OF CONTENTS UL 1635 SpeciÞcations 28.1 28.2 28.3 28.4 28.5 28.6 System trouble display ..........................29 Digital Dialer telephone number .............29 Entry delay...........................................29 Exit delay .............................................29 Test time..............................................29 Closing wait..........................................29 UL 365 And 609 SpeciÞcations 29.1 29.2 29.3 29.4 29.5 29.6 System trouble display ..........................29 Grade A bell .........................................29 Bell cutoff.............................................29 Automatic bell test ................................29 Line security for Police Connect..............29 High Line Security.................................29 Universal UL And NFPA Fire Alarm SpeciÞcations 30.1 30.2 30.3 30.4 30.5 30.6 30.7 30.8 30.9 30.10 30.11 30.12 30.13 Introduction .........................................30 Wiring..................................................30 Transformer..........................................30 End-of-Line resistor...............................30 System trouble display ..........................30 Fire display...........................................30 Police station phone number..................30 System maintenance .............................30 Audible alarm .......................................30 Fire zone programming .........................30 Style D zones .......................................30 Video Option ........................................30 UL Listed Receivers ...............................30 UL 985 NFPA 72 (Chapter 2) SpeciÞcations 31.1 Bell output deÞnition .............................31 UL 864 NFPA 72 (Chapter 9) SpeciÞcations 32.1 32.2 32.3 32.4 32.5 32.6 32.7 32.8 32.9 32.10 Zone restoral reports.............................31 Power fail delay ....................................31 Sprinkler supervisory.............................31 DACT systems ......................................31 Type 2 and Type 3 Central Station Service.................................................31 Type 1 Central Station Service ...............31 Local Protective Signaling Systems .........31 Proprietary Protective Signaling Systems 32 Remote Station Protective Signaling Systems .................................32 Fire Protective Signaling Systems with an iCOM™.....................................32 California State Fire Marshal SpeciÞcations 33.1 Digital Monitoring Products iv Bell output deÞnition .............................32 XR2400F Installation Guide TABLE OF CONTENTS System Wiring Diagrams 34.1 34.2 34.3 34.4 34.5 34.6 34.7 34.8 34.9 Multiple NotiÞcation Circuit Modules .......33 Multiple NotiÞcation Circuit Modules for Zoned Annunciation .........................34 Dual Style D Zone Module Installation ....35 Remote Station Reversing Relay Connection ..................................36 Supervised Remote Relay ......................37 Cellular Backup Installation for Derived Channel Burglary ......................38 LX-Bus™ Module Connection..................39 Second LX-Bus™ with Auxiliary Power Supply .......................................40 Multiple NotiÞcation Circuits with Strobes and Bells ..................................41 OPERATING INSTRUCTIONS XR2400F Installation Guide Digital Monitoring Products v REVISIONS Revisions to This Document This section explains the changes that were made to this document during this revision. This section lists the date the change was made, the section number and section heading, and a quick summary of the change. Date Section Number and Heading Quick Explanation of Changes 4/04 5.4 NotiÞcation Appliances 10.1 Interconnect Harness Sections 15.1, 15.3, 15.4 16.7 Standby Battery Calculations Removed obsolete products and added Models 850S and 850D. ClariÞed table information. Added keypad models 690F and 790F. Added keypad models 690F and 790F and 734 Wiegand Interface Card. Added/revised current draw information. 5/03 FCC Statement Entire Document 16.7 Standby Battery Calculations 20.1 Terminals 25-26 and 27-28 21.3 Zone Response Time 34.9 Notif. with Strobes and Bells Adjusted to properly reßect Class A. Added SCS-1R references to the appropriate places. Current Draw on some products adjusted. EOL information clariÞed. Changed from 160 milliseconds to 167. Wiring Diagram corrected. 10/02 1.2 System Components 1.3 Power SpeciÞcations 2.6 Wiring Diagram 3.1 Transformers and AC Power 3.3 16.5 VAC Transformer 13.1 Power Supply 15.1 Wiring Diagram 32.9 Remote Station Protective 34.4 Remote Station Reversing 9/02 1.2 System Components 1.3 Power SpeciÞcations 2.6 Wiring Diagram 3.1 Transformers and AC Power 3.3 16.5 VAC Transformer 13.1 Power Supply 13.5 LX-Bus™ 15.1 Wiring Diagram 15.4 Mounting Keypads 16.6 XR2400F Power Requirements 20.1 Terminals 25-26 and 27-28 32.9 Remote Station Protective 34.4 Remote Station Reversing 3/02 15.5 Connecting Serial Devices 16.6 XR2400F Power Requirements Digital Monitoring Products vi Updated to 16 VAC 56 VA transformer. Updated to Transformer Input of 16 VAC 56 VA and Standby battery of 12 VDC 28Ah (four Model 367 batteries) with 56 VA transformer. Changed drawing to show 56 VA transformer. Updated to 16 VAC 56 VA transformer. Updated to 16 VAC 56 VA transformer. Updated to 16 VAC 56 VA transformer and Standby battery of 12 VDC 28Ah (four Model 367 batteries) with 56 VA transformer. Changed drawing to show 56 VA transformer. Added the section back to the manual. Added the system diagram back to the manual. Updated to Model 320 16.5 VAC 40 VA transformer. Updated to Transformer Input or 16.5 VAC 40 VA and Standby battery of 12 VDC 15.4 Ah (two Model 367 batteries) with 40 VA transformer. Changed drawing to show 40 VA transformer. Updated to 16.5 VAC 40 VA transformer. Updated to 16.5 VAC 40 VA transformer. Updated to 16.5 VAC 40 VA transformer and Standby battery of 12 VDC 15.4 Ah (two Model 367 batteries) with 40 VA transformer. Added 462FM. Removed Model 321 and 322 transformers from Figure 13, and changed drawing to show Model 320 transformer. Added 710 and 710F. Removed Model 670 keypad. Added note about sensor reset dropping power to zones 9 and 10. Removed section. Removed system diagram of remote station reversing relay. LX-Bus and Keypad Bus wiring information clariÞed. iCOM™ Internet Alarm Router added to the Standby Battery Calculations Chart XR2400F Installation Guide INTRODUCTION Introduction 1.1 Overview The DMP XR2400F Addressable Fire Alarm Control Panel (FACP) is an expandable 24 VDC Fire Alarm Control with built-in DACT and LCD Fire Command Center keyboard with membrane keyswitch. A complete system can provide a total of 494 programmable inputs and outputs for commercial and industrial Þre alarm service. The 24 VDC 4 Amp notiÞcation appliance power is distributed between two class B style W NAC outputs. Additional NAC outputs can be added with conventional supervision modules or addressable power supply/ boosters. Addressable smoke detectors and input modules round out the XR2400F to deliver a truly ßexible and expansive Þre detection and notiÞcation system. The Fire Alarm Control Panel is shipped pre-wired in a red metal enclosure housing the necessary components to monitor and control Þre alarm notiÞcation appliances. The enclosure’s dimensions are as follows: 32” H x 14.5” W x 4” D. The lid adds about 0.5” to each side. 1.2 System Components The XR2400F FACP consists of the following components: • • • • • 1.3 One Model XR2400F Command Processor panel Two Model 866 Class B Style W NAC modules One Model 504-24 VDC Power Supply One 16 VAC, 56 VA transformer Two Model 305 Relays • One Model 893A Dual Phone Line module • One Model 630F PCB and membrane switch • One 28 VAC transformer, TF-0030 • One Model 462N LX-Bus Expansion Card • One Metal Backplate Power SpeciÞcations Command Processor: Transformer Input of 16 VAC 56 VA Standby battery of 12 VDC 28Ah (56 VA charges up to four 7.7Ah batteries) Auxiliary power of 12 VDC at 1 Amp NAC Output of 12 VDC at 1.5 Amp All circuits are inherent Power Limited except red battery wires. NAC Output: 24 VDC 4 Amps shared between NACs 1 and 2 1.4 Before you begin Before installing the XR2400F, we recommend you read through the entire contents of this guide. Familiarize yourself with the features of the panel and the key points to remember during the installation. Be sure to read and understand all of the caution statements printed in bold italics. 1.5 About this Guide The information in this guide is organized into Þve sections: Table of Contents, Introduction, Installation, Compliance, and System Wiring Diagrams. • The Table of Contents at the front lists the headings and subheadings used throughout each section of the guide. • The Introduction section gives you an overview of the XR2400F and this document. • The Installation section begins with mounting instructions for the enclosure. Wiring diagrams for each component also appear in this section. • The Compliance section lists all UL listings the XR2400F currently follows. • The System Wiring Diagrams provide illustrations of typical XR2400F systems. 1.6 How to use this Guide To locate information about the installation of the XR2400F, go to the Table of Contents at the front of this guide. Find the subject heading that best describes the information you need and turn to the section number shown to the right of the heading. If you cannot Þnd the information you need under that heading, scan through a few of the headings and read the text under those that sound similar. XR2400F Installation Guide Digital Monitoring Products 1 INSTALLATION Mounting 2.1 Mounting the Enclosure The XR2400F must be mounted in a secure, dry location to protect the unit from damage due to tampering and the elements. The enclosure can be either ßush mounted or surface mounted and includes a hinged door with lock. The hole in the enclosure door allows access to the Fire Command Center without opening the door. Figure 1 illustrates the mounting hole locations for the panel’s enclosure. The enclosure’s dimensions are 32” tall, 14.5” wide, by 4” deep. The lid adds about 0.5” to each side. 2.2 Hole for Flush Mounting Holes for Surface Mounting Surface Mounting The center hole of the enclosure should be attached to a stud in the wall. Due to the weight of the enclosure, especially the batteries, it is extremely important to mount the enclosure on the stud. Attach the two holes beside the center hole to sheetrock to secure enclosure. When mounting the enclosure, be sure to leave room for the panel door to swing open. The door’s lock should be easily accessible. 2.3 3/4" X 1/2" Knockouts Holes for 1" screws for Flush Mounting Flush Mounting The enclosure can also be ßush mounted. Use 1” screws to secure the enclosure between two studs using the two sets of holes on the sides of the enclosure. Use the top and bottom holes to secure to horizontal studs, if necessary. 2.4 Fire Command Center LCD Keyboard A Fire Command Center LCD Keyboard has been factory installed on the XR2400F enclosure. Also, a keyswitch has been installed and prewired to the left of the keyboard. The user can turn the keyswitch to enable the four functions keys without opening the enclosure door. 2.5 Metal Backplate The XR2400F components are pre-wired and installed on a metal backplate. The backplate can easily be removed to keep components safe during pre-wire activities. Battery Shelf Additional Holes for Surface Mounting Hole for Flush Mounting Figure 1: Mounting the XR2400F Enclosure To remove the backplate, disconnect the wires to the batteries, transformers, and the Fire Command Center LCD keyboard. Also remove the AC wires from the 504-24 power supply. From the panel, disconnect the AC wires from terminals 1 and 2. Disconnect the battery wires either from the batteries or the panel terminals 3 and 4. Finally, disconnect the keyboard wires from panel terminals 7, 8, 9, and 10. Remove the screws securing the backplate to the enclosure. Then loosen the two top screws that the backplate hangs on. After the screws are removed and loosened, lift the backplate up slightly and pull the backplate toward you. When reinstalling the backplate, be sure all connections are secure. Refer to Figure 2 for an illustration of the backplate and the components. The backplate is shown in light gray. Digital Monitoring Products 2 XR2400F Installation Guide INSTALLATION 2.6 Wiring Diagram The XR2400F system below shows the layout of the components. The wires shown in this guide have been factory installed and connected. The dashed lines represent wires that run underneath a component. Detailed wiring diagrams for each supplied component appear in following sections of this guide. WHITE BLACK GREE N S S S = Supervised Wire 28 VAC Transformer 866 Module #1 WHITE WHITE BLACK GREEN BLACK 866 Module #2 56 VA Transformer charges 4 batteries 16 VAC Transformer S S To Telco S S S S 504-24 Power Supply 893A 1K EOL To Notification Appliances 1K EOL + DC - See LT-0554, 504-24 Power Supply section for complete 504-24 information. P10 AC TRBL BATT TRBL Red + Bat - Red wire to positive battery terminal. Black Black wire to negative battery terminal. XR2400F Command Processor™ Panel See LT-0554, XR2400F Command Processor™ Panel section for complete XR2400F information. Output Header J2 AC +B From XR2400F panel to 12 VDC. + J16 -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 Black AC Red From 504-24 Power Supply to 24 VDC. J10 Z3 GND Z4 Z5 GND Z6 Z7 GND Z8 Z9+ Z9- Z10+ Z10- To Fire Command Center on enclosure door - 12 VDC battery 12 VDC battery 24 VDC Circuit + 504-24 Secondary Power Supply 1.5 Amps maximum charge current. Use only 24 VDC rechargeable batteries or Two DMP Model 367 12 VDC batteries with a Series Connecting Strap. Replace every 3 to 5 years. - + XR2400F Secondary Power Supply 1.5 Amps maximum charge current. Use only 12 VDC rechargeable batteries DMP Model 367. Replace every 3 to 5 years. 12 VDC battery 462N LX-Bus Interface Card AC Two 12 VDC batteries connected in parallel with a Model 318 Dual Battery Harness. See Secondary Power Supply section. - + 12 VDC battery Battery Compartment Two 12 VDC batteries connected in series with the included Series Connecting Strap. See Secondary Power Supply section. Figure 2: XR2400F System XR2400F Installation Guide Digital Monitoring Products 3 INSTALLATION AC Connection 3.1 Transformers and AC Power Connection The AC connection should be completed by a licensed electrician. Never share the Fire Alarm Control Panel circuit with any other equipment. The XR2400F comes supplied with two transformers: the 16 VAC 56 VA transformer and the 28 VAC 175 VA transformer. The 28 VAC and the 16 VAC transformers’ white leads and black leads must be connected together respectively. These wires must be connected to an unswitched 120 VAC 60 Hz power source with at least 1.85 Amps of available current. Black wire - attach the black 120 VAC wire to the black wire of the transformers. White wire - attach the white 120 VAC wire to the white wire of the transformers. Green wire - attach the green wire lead to the green wire attached to the enclosure. Bracket Nut WHITE GREE S BLACK N S Blue To Model 504-24 AC Terminals L-Bracket WHITE 16 VAC 56 VA Transformer Bracket Nut Yellow WHITE BLACK GREEN BLACK 28 VAC Transformer 56 VA Transformer charges 4 batteries. Violet Gray Terminal 1 Terminal 2 To XR2400F Panel Figure 3: Transformers and AC Power Connection Always ground the panel before applying power to any devices! Use 18 AWG or larger for all power connections. The XR2400F must be properly grounded before connecting any devices or applying power to the panel. Proper grounding protects against Electrostatic Discharge (ESD) that can damage system components. 3.2 28 VAC Transformer The 28 VAC Transformer supplies power to the AC terminals of the 504-24 Power Supply which is factory prewired to the two 866 NAC modules. The 28 VAC is located in the upper right hand corner of the enclosure surrounded by a metal divider. See Figure 3 above and the 504-24 Power Supply section. 3.3 16 VAC Transformer The 16 VAC 56 VA transformer supplies power to the XR2400F panel and is factory pre-wired. See Figure 3: Transformers and AC Power Connection. Also refer to Figure 11: XR2400F Panel Wiring Diagram. 3.4 Earth Ground from the XR2400F Panel Terminal 4 of the XR2400F panel must be connected to earth ground using 14 gauge or larger wire to provide proper transient suppression. DMP recommends connecting to a cold water pipe or ground rod only. Do not connect to an electrical ground or conduit, sprinkler or gas pipes, or to a telephone company ground. Digital Monitoring Products 4 XR2400F Installation Guide INSTALLATION Secondary Power Supply 4.1 Description The XR2400F system includes pre-wired cables for connecting a 24 VDC battery to the 504-24 power supply and a 12 VDC battery to the XR2400F panel. For 24 VDC battery operation to the 504-24, connect two 12 VDC sealed lead-acid batteries in series using the included series connecting strap. See Figure 4. Observe polarity when connecting all batteries. Use sealed lead-acid batteries only. Use the DMP Model 367, 12 VDC 7.7Ah sealed lead-acid rechargeable battery. Batteries supplied by DMP or manufactured by Eagle Picher or Yuasa have been tested to ensure proper charging with DMP products. Gel cell batteries cannot be used with the XR2400F panel. 4.2 Battery Connection to XR2400F Command Processor panel For 12 VDC battery operation to the XR2400F, connect the black battery lead to the negative terminal of the battery. The black battery wire is connected to terminal 4 of the XR2400F panel. Connect the red battery lead to the positive terminal of the battery. The red battery wire is connected to terminal 3 of the XR2400F panel. See Figure 11 and Figure 2. You can add a second battery in parallel using the DMP Model 318 Dual Battery Harness. When wiring two batteries with the Model 318 Dual Battery Harness, plug the red male end of the Dual Battery Harness into the red female battery lead from the panel. Plug the black male end of the Dual Battery Harness into the black female battery lead from the panel. Attach both female leads from the Dual Wiring Harness to the two batteries as described above. See Table 3: Battery Calculations. 4.3 Battery Connection to the 504-24 Power Supply The 504-24 is powered by 24 VDC. After connecting two 12 VDC batteries together using the series connecting strap (or after installing one 24 VDC battery) connect the black battery wire to the negative terminal of the 24 VDC battery. The black battery wire is connected to the negative AC terminal of the 50424. Connect the red battery wire to the positive terminal of the 24 VDC battery. The red battery wire is connected to the positive AC terminal of the 504-24. RED Series Connecting Strap BLACK 12 VDC Battery 12 VDC Battery Figure 4: 24 VDC Battery Wiring See Figure 9 and Figure 2. Also see the Battery Information section. XR2400F Installation Guide Digital Monitoring Products 5 INSTALLATION Two 866 NAC Modules 5.1 Description Each 866 provides one style W indicating circuit for supervising UL polarized notiÞcation appliances, such as bells, strobes, and horns. See Table 1: NotiÞcation Appliances for a list of approved notiÞcation appliances. 5.2 Connection Each 866 module is pre-installed on the removable backplate using the standard three-hole conÞguration. The modules are factory pre-wired to each other, the 504-24, and the XR2400F panel. Refer to the Þgure below and to Figure 2: XR2400F System for wiring connections. You can connect 24 VDC NotiÞcation Appliances to terminals 5 and 6 of each module. Each module provides a zone of notiÞcation and can be activated separately. Normal/Silence Switch 10K EOL DMP Model 308 866 Module #1 1 2 3 4 5 6 7 8 AUX PWR GND Alarm In Bell PWR In Bell Out + Bell Out Bell Trouble Bell Trouble To XR2400F Output #1 (J2 pin #2) 24 VDC To XR2400F terminal 13 (Zone 1) UL Listed, Polarized Notification Appliances See Table 1: Notification Appliances Pre-installed 1K EOL Normal/Silence Switch 10K EOL DMP Model 308 866 Module #1 1 2 3 4 5 6 7 8 AUX PWR GND Alarm In Bell PWR In Bell Out + Bell Out Bell Trouble Bell Trouble To To To To XR2400F terminal 7 504-24 DC XR2400F Output #2 (J2 pin #5) 504-24 DC + Pre-installed 1K EOL To XR2400F terminal 15 (Zone 2) To 504-24 BATT TRBL C (Common) 24 VDC UL Listed, Polarized Notification Appliances See Table 1: Notification Appliances Figure 5: 866 Modules Wiring 5.3 Bell Silence/Bell Trouble A bell silence switch on the 866 module is provided to prevent sounding of the indicating devices when testing the system. When the Silence position is selected, a 15-second delay occurs before the 866 bell trouble contacts (terminals 7 and 8) open. Select the Normal position after testing to return the 866 module to normal operation. Digital Monitoring Products 6 XR2400F Installation Guide INSTALLATION 5.4 NotiÞcation Appliances The following table indicates the approved notiÞcation appliances that can be used with the XR2400F system. DMP Model Description 802 12/24 VDC Multi-Tone Horn 802WP-75W 24 VDC Weatherproof Multi-Tone Horn 803 12/24 VDC Standard Horn 850S Single Action Dry Contact Pull Station 850D Dual Action Dry Contact Pull Station 806-6 12 VDC 6-Inch Bell 806-10 12 VDC 10-Inch Bell 821 12 VDC Strobe 822 12 VDC Strobe with RetroÞt Plate 823 12 VDC Horn Strobe 831 12/24 VDC Single Circuit Sync Module 832 12/24 VDC Dual Circuit Sync Module 901 24 VDC Mini Horn 904 24 VDC Horn 904WP 24 VDC Weatherproof Horn 906-6 24 VDC 6-Inch Bell 906-10 24 VDC 10-Inch Bell 921-MCW 24 VDC Multi-Candela Strobe 922-MCW 24 VDC Multi-Candela Strobe with RetroÞt Plate 923-MCW 24 VDC Multi-Candela Horn Strobe 924-MCW 24 VDC Multi-Candela Audible Strobe 924WP-75W 24 VDC Weatherproof Audible Strobe Table 1: NotiÞcation Appliances XR2400F Installation Guide Digital Monitoring Products 7 INSTALLATION 462N LX-Bus™ Expansion Card 6.1 Description The 462N LX-Bus™ Expansion Card provides an additional 100 zones to the XR2400F. 6.2 LX-Bus™ Expansion Capability The 462N card provides a 4-wire LX-Bus™ that allows you to connect up to 100 Model 521LX or 521LXT Addressable Smoke Detectors. Also the LX-Bus™ could connect up to 25 Model 714, 715, and 725 Zone Expanders or 716 Output Expanders, up to six Model 714-16 or 715-6 Zone Expanders, and up to 100 Model 711 and 711E Zone Expanders. Power for the devices is provided through the Black and Red wires of the expansion harness. 6.3 Installing the 462N Module 1. Remove AC and battery power from the XR2400F panel before installing the 462N card. 2. Align the 50 pin connector of the 462N with the J6 connector on the XR2400F panel. 3. Press the 462N onto the J6 connector while applying even pressure to both sides. XR2400F Panel J6 Expansion Connector 462N Network Interface Card Configuration Jumpers LX-Bus Connector B To LX-Bus Modules Black - Aux. Common Black Green - Serial Data Out Green Yellow - Serial Data In Yellow Red - Aux. Positive Red Figure 6: 462N Wiring Digital Monitoring Products 8 XR2400F Installation Guide INSTALLATION Telephone RJ Connector 7.1 Description Connect the XR2400F system to two lines of the public telephone network by installing two DMP 356 RJ Cables between the RJ31X or RJ38X phone jacks, and the 893’s J4 connector (for main line) and J5 (for backup line). Set the 3-pin headers on the XR2400F labeled J11 and J12 to DD for digital dialer, Contact ID, or Modem IIe operation. See 893A Dual Phone Line Module. To Telephone Line Ring Tip 5 4 6 3 7 2 1 8 Ring 1 To Premise Phone RJ31X or RJ38X Phone Block Tip 1 Figure 7: Phone Jack Wiring 7.2 FCC registration The Model XR200/XR2400F complies with FCC part 68 and is registered with the FCC. Registration number: CCKUSA-18660-AL-R / Ringer Equivalence: 1.1B 7.3 NotiÞcation Registered terminal equipment must not be repaired by the user. In case of trouble, the device must be immediately unplugged from the telephone jack. The factory warranty provides for repairs. Registered terminal equipment may not be used on party lines or in connection with coin telephones. NotiÞcation must be given to the telephone company of: a. The particular line(s) the service is connected to (the speciÞc phone line) b. The FCC registration number (CCKUSA-18660-AL-R) c. The ringer equivalence (1.1B) d. The make, model, and serial number (see the serial # sticker on the panel) of the device 7.4 Ground start Ground start phone service cannot be used on commercial or residential Þre applications. XR2400F Installation Guide Digital Monitoring Products 9 INSTALLATION 893A Dual Phone Line Module 8.1 Description The 893A is a dual telephone line supervision module that allows the panel to indicate a phone line failure to the premises and the central monitoring station. After the 893A senses a failure on the main line, it switches to the backup, or secondary, phone line. The 893A is installed on the removable backplate above the XR2400F circuit board. 8.2 Connection The 893A connects the panel to the public telephone network by installing a DMP 356 RJ Cable between the XR2400F panel’s J3 connector and the 893’s J3 connector labeled PANEL. The two communication jumpers must be set to either DD or MPX. Factory pre-wired to XR2400F panel Phone Jack Connector, J3 J3 PANEL 893A Dual Telephone Line Module Communication Jumpers: Both Jumpers must be set DD MPX P10 Factory pre-wired to XR2400F panel J10 Connector J1 J2 To Primary telephone line J4 MAIN DD MPX J5 BACKUP Processor Stopped Buzzer To Secondary telephone line Figure 8: 893A Dual Phone Line Module Wiring 8.3 Jumper Settings There are two sets of jumpers on the 893A module. When setting the module for either DD (digital dialer) or MPX (multiplex), both jumpers must be set. 8.4 Digital Dialer/Multiplex You can conÞgure the 893A to provide two lines of digital dialer or one line of multiplex with digital dialer backup. For multiplex operation both jumpers (J1 and J2) must be set to MPX. Also, jumpers J11 and J12 on the panel must be set to MPX. See XR2400F Command Processor Panel Connection. The XR2400F is preset at the factory for Digital Dialer. The Main modular jack (J4) is used for the primary dialer or multiplex line. The Backup modular jack (J5) is used for the secondary digital dialer line. 8.5 Phone Line Monitor The 893A uses a phone line monitor for the main and backup phone lines. When sending a report, the 893A veriÞes the main phone line is working before sending. If the line is bad, the module tests the backup phone line. The 893A sends the report on the Þrst working phone line. The phone line monitor has a 2-minute trouble delay and a 1-minute restore delay. Phone line trouble is displayed in the Fire Command Center LCD Status List as a System Trouble. The Fire Command Center LCD is factory programmed to display system troubles in the Status List. 8.6 Processor Fail Buzzer The 893A module also monitors the panel’s CPU and sounds a trouble buzzer whenever either the panel’s processor is reset using J16 or the processor stops functioning. Digital Monitoring Products 10 XR2400F Installation Guide INSTALLATION 504-24 Power Supply 9.1 Description The 504-24 is a power limited, switching power supply that meets UL, CSFM, NFPA, and FCC compliance standards. Model 504-24 is rated for 24 VDC @ 4 Amps maximum and supplies power to the 866 Modules. 9.2 LED’s The 504-24 has two status LED’s that show the current state of power. The green LED indicates low AC input. The red LED indicates low standby battery power after AC has failed. 9.3 504-24 Condition Chart Condition Voltage Levels LED Status Condition AC Trouble Approx. 102 VAC AC LED (Green) On AC Good Battery Trouble Below 23.6 VDC AC LED (Green) Off AC Bad Battery Restoral Above 25.0 VDC DC LED (Red) On Battery Good Battery Cutoff Below 20.4 VDC DC LED (Red) Off Battery Bad Table 2: 504-24 Condition and LED Indicators 9.4 504-24 UL Listings For UL 603 Power Supplies for Burglary Alarm Systems and UL 294 Power Supplies for Access Control System applications: Voltage Range of 22.9 to 25.5 VDC. For UL 1481 Power Supplies for Fire Protective Signaling the following maximum battery standby Ampere hours apply for 24 hours of battery backup: Battery Standby Maximum: 49.2Ah Output Voltage: 24 VDC Output Current: 1.5A standby, 4 Amp alarm 9.5 24 VDC NAC Standby Battery Calculations The following calculation deÞnes the total number of standby battery Amp-hours required to support operation of the NACs and any other devices attached to the 504-24 power supply. From this calculation, assemble the appropriate number of batteries that will just exceed the calculated total Amp-hour requirement. The 866 NACs receive power for internal operation from the XR2400F panel and do not enter in this calculation themselves. 1. Add all standby current values including the power supply operating current. 2. Multiply the total standby current by the number of standby hours needed. 3. Add all alarm current values from the notiÞcation appliances attached to the 866 NACs and multiply by 0.25. 4. Add the total alarm mA-hour with the total standby mA-hour and then multiply this number by 0.001. Power Supply Operating Current Other Standby Current 1. 200 mA + ______ mA Total Standby Current + ______ mA Number of Standby Hours Required X ______ hr 2. Total Standby (mA-hr) Required = ______ mA-hr 3. Total Alarm Current = ______ mA Total Alarm Current X 0.25 = ______ mA-hr Total Standby (Required) + ______ mA-hr Total = ______ mA-hr X 0.001 = ______ (0.25 = 5 minutes in alarm) 4. Total Required Amp-hours Table 3: Battery Calculations XR2400F Installation Guide Digital Monitoring Products 11 INSTALLATION 9.6 Connection The 24 VDC power supply is completely pre-wired. Refer to the following 504-24 wiring diagram for speciÞc wire connections. + DC - 504-24 Power Supply Yellow Both wires to 28 VAC Transformer Black To XR2400F Panel terminal 10 (BLK) Black To 866 Module #2 terminal 2 (GND) White/Red To 866 Module #2 terminal 4 (Bell PWR In) Blue AC Green LED DC Red LED AC TRBL BATT TRBL NC C NO NC C NO + Bat - Green AC Red wire to positive Red battery terminal. Black wire to negative Black battery terminal. Green Black To 866 Module #2 terminal 8 (BELL TRBL) To XR2400F Panel To XR2400F Panel terminal 18 (Zone 4) terminal 16 (Zone 3) Figure 9: 504-24 Wiring Interconnect Wiring Harness 10.1 Interconnect Harness This chart explains the colors of the wires on the Interconnect Wiring Harnesses. It also explains what each wire connects. Wire Color Connection From Connection To Red Panel Terminal 7 (DC Power) 866 Module #2 Terminal 1 (Auxiliary Power) Black Panel Terminal 10 (Common) 504-24 DC - Negative DC Terminal (Ground) Brown Panel Terminal 13 (Zone 1) 866 Module #1 Terminal 7 (Bell Trouble) Violet Panel Terminal 15 (Zone 2) 866 Module #2 Terminal 7 (Bell Trouble) Green Panel Terminal 16 (Zone 3) 504-24 Battery Trouble Terminal N/O White Panel Terminal 18 (Zone 4) 504-24 AC Trouble Terminal N/C Blue Panel J2 Pin 2 (Common) 866 Module #1 Terminal 3 (Alarm In) Orange Panel J2 Pin 3 (Output 1 N/O) Panel Terminal 5 (Bell Output) Yellow Panel J2 Pin 5 (Common) 866 Module #2 Terminal 3 (Alarm In) Orange Panel J2 Pin 6 (Output 2 N/O) Panel Terminal 5 (Bell Output) White/Red 504-24 DC + (Positive DC Terminal) 866 Module #2 Terminal 4 (Bell Power In) Black 504-24 DC - (Negative DC Terminal) 866 Module #2 Terminal 2 (Ground) Red 866 Module #2 Terminal 1 (Auxiliary Power) 866 Module #1 Terminal 1 (Auxiliary Power) Black 866 Module #2 Terminal 2 (Ground) 866 Module #1 Terminal 2 (Ground) Black 866 Module #2 Terminal 2 (Ground) 866 Module #1 Terminal 8 (Bell Trouble) White/Red 866 Module #2 Terminal 4 (Bell Power In) 866 Module #1 Terminal 4 (Bell Power In) Black 866 Module #2 Terminal 8 (Bell Trouble) 504-24 Battery Trouble Common Terminal Black 866 Module #2 Terminal 8 (Bell Trouble) 866 Module #1 Terminal 8 (Bell Trouble) Table 4: Interconnect Wiring Harness Digital Monitoring Products 12 XR2400F Installation Guide INSTALLATION Fire Command Center 11.1 Description The XR2400F provides an LCD display and 20-key keyboard for programming and user operation of the system. The Fire Command Center is installed on the enclosure door of the XR2400F. To the left of the keyboard, a keyswitch has been installed and pre-wired. The user must turn the keyswitch to enable the four function keys. See the illustration below. Figure 10: Fire Command Center LCD and Keyboard 11.2 Connection The display and keyboard are factory pre-wired to terminals 7, 8, 9, and 10 of the XR2400F panel. For standby battery calculations, the display draws 100mA of current in normal standby or alarm condition. See Panel Standby Battery Calculations. The keyswitch has been pre-wired to the membrane keyboard. 11.3 Remote Fire Command Center Up to seven Model 630F Remote Fire Command Centers may be remotely attached to the XR2400F system. See the 630F Installation Guide, LT-0562, for complete information. XR2400F Installation Guide Digital Monitoring Products 13 INSTALLATION XR2400F Command Processor Panel 12.1 Description The DMP XR2400F Command Processor is a versatile Þre communicator panel with battery backup. The XR2400F provides eight on-board grounded zones for connection of Model 869 class A zones and two on-board 12 VDC class B style A powered zones. The powered zones have a reset capability to provide for 2-wire smoke detectors, relays, or other latching devices. The XR2400F can communicate to one or two DMP SCS-1 Receivers using multiplex or digital dialer, to one or two DMP SCS-1R Receivers using digital dialer, or to nonDMP receivers using the Contact ID and Modem IIe formats. 12.2 Connection The XR2400F Command Processor panel is factory pre-wired and controls the other components in the system. Refer to the wiring diagram below for wiring. See the following sections for descriptions of additional applications of the XR2400F. J12 J11 462N Network Interface Card To 893 J3 PANEL Connector XR2400F Command Processor™ Panel J3 J2 Output Color Code for Model 430 Output Harness J4 Tamper Header DD, MPX Selection Headers To 866 Module #1 terminal 3 (Alarm In) Form C Relays Output 1 N/C Violet Output 1 Com Gray Output 1 N/O Orange Output 2 N/C Violet Output 2 Com Gray Output 2 N/O Orange Voltage Outputs Output 3 White/Orange Output 4 White/Yellow Output 5 White/Green Output 6 White/Blue Output 7 White/Violet Output 8 White/Gray Output 9 White Output 10 White/Black Ground Black To 866 Module #2 terminal 3 (Alarm In) J2 Output Header To 893 P10 Connector J10 J6 To LX-Bus Modules J16 Panel Reset AC AC +B 1 2 3 -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 4 5 6 7 8 9 10 11 12 To 16 VAC Transformer To Fire Command Center Red wire to positive terminal of 12 VDC Battery To 866 Module To 504-24 #2 terminal 1 DC (AUX PWR) Black wire to negative terminal of 12 VDC Battery 13 14 15 Z3 GND Z4 Z5 GND Z6 16 19 17 18 20 21 Z7 GND Z8 22 23 24 Z9+ Z9- Z10+ Z10- 25 26 27 28 To 504-24 BATT TRBL NC To 866 Module #2 terminal 7 (BELL TRBL) To 866 Module #1 terminal 7 (BELL TRBL) To 504-24 AC TRBL NC Figure 11: XR2400F Panel Wiring 12.3 Relays The XR2400F is shipped with two Model 305 Relays pre-installed to allow zone alarm control for the 866 NAC Modules. When a Þre alarm occurs the bell output is factory programmed to turn on and provide power to the contacts of the relays. SpeciÞc zone programming determines whether one or both relays turn on signal voltage to the 866 NACs. This allows control of the NACs by zone. 12.4 Zone Reference The XR2400F has been pre-wired in the factory. The Þrst 866 NAC module connects to Zone 1. The second 866 NAC module connects to Zone 2. Zone 3 connects to the 504-24 power supply. Digital Monitoring Products 14 XR2400F Installation Guide INSTALLATION XR2400F Product SpeciÞcations 13.1 Power Supply Transformer Input: 16 VAC 56 VA Standby Battery: 12 VDC 28Ah (56 VA charges up to four batteries) Auxiliary: 12 VDC output at 1 Amp Bell Output: 12 VDC at 1.5 Amp All circuits are inherent Power Limited except the red battery wire. 13.2 Communication Built-in dialer communication to DMP Model SCS-1 and SCS-1R Receivers Built-in multiplex communication to DMP Model SCS-1 Receivers Built-in Contact ID communication to non-DMP receivers Built-in Modem IIe communication to non-DMP receivers 893A Dual Phone Line Modules with phone line supervision Can operate as a local panel 13.3 Panel Zones Eight 1k Ohm EOL grounded zones (zones 1 to 8). Connect to 869 class A module for burglary applications. Two 3.3k Ohm EOL Class B (Style A) powered zone with reset (zones 9 and 10) 13.4 Remote Annunciator You can connect up to seven of the following supervised keypads or expanders to the XR2400F keypad data bus: • Alphanumeric Fire Command Centers or keypads • Four and single point zone expanders • Single point detectors 13.5 LX-Bus™ You can connect the following devices to the LX-Bus provided by the DMP 462N (supplied), 462P, 462FM, 472, and/or 481 Interface Cards up to the maximum number of LX-Bus addresses. See Accessory Devices. • • • • • Model 521LX or 521LXT Smoke Detectors with CleanMe Sixteen, eight, four, and single point zone expanders Relay output expanders Graphic annunciator modules Single point detectors 13.6 Outputs Two SPDT relay outputs (requires two Model 305 relays that are provided on the panel, each rated 1 Amp at 30 VDC resistive). Connect only power limited sources to the relay. XR2400F Installation Guide Digital Monitoring Products 15 INSTALLATION Expansion 14.1 Expansion Zones Up to 232 additional Þre and burglary zones are available on the XR2400F using the remote zone capability of keypads and zone expander modules. The panel’s keypad data bus supports up to eight supervised device addresses with each address supporting up to four programmable expansion zones. Up to 200 zones are available using the Model 460 Interface Adaptor, 462N, 462P, 462FM, 472, or 481 Interface Cards, and any combination of sixteen, eight, four, and single point zone expander modules and single point LX-Bus™ detectors. Combined current requirements of additional modules may require an additional 504-24 or 502-12 power supply. See section Standby Battery Calculations when calculating power requirements. 14.2 Output (Relay) Expansion In addition to the two SPDT relays and eight voltage outputs on board the XR2400F, you can also connect up to 25 Model 716 Output Expanders to each card’s LX-Bus™. These modules can provide an additional 200 programmable SPDT relays. The XR2400F provides 50 Output Schedules you can use for programming the 716 to perform a variety of annunciation and control functions. You can also assign the 716 outputs to any of the panel’s Output Options such as Fire Alarm, Communication Fail, or Phone Trouble Outputs. The LX-Bus also supports the Model 717 Graphic Annunciator Module. Each 717 module supplies 20 switched ground outputs that follow the state of their assigned zones. Note: Do not use shielded wire for LX-Bus and keypad bus circuits. XR2400F Command Processor System 462N, 462P, 462FM, 472, or 481 Expansion Interface Card 460 Interface Adaptor 1 AC 2 AC 3 B+ 4 B- 5 BELL 6 GND 7 8 YEL 9 GRN 10 BLK 11 SMK 12 L5+ 13 L5- 14 L1 15 GND 16 L2 17 L3 18 GND 19 Model 711 Zone Expander L4 Model 714 Zone Expander Partition 1 Partition 2 Model 715 Zone Expander DISARM DISARM DISARM ARM ARM ARM Up to eight areas DISARM DISARM ARM ARM Up to four areas Model 716 Output Expander Partition 3 Partition 4 DISARM DISARM DISARM ARM ARM ARM Up to four areas Model 717 Annunciator Module Up to four areas Up to 200 zones and outputs when using two LX-Bus" cards Figure 12: Typical XR2400F System Digital Monitoring Products 16 XR2400F Installation Guide INSTALLATION Accessory Devices 15.1 Wiring Diagram The XR2400F system below shows some of the accessory modules you can connect for use in various applications. A brief description of each module appears in section 15.3 Accessory Devices. S S DMP Transformers: J12 Model 320 16.5 VAC, 40 VA Class 2 Wire-in. J11 J2 Output Color Code for Model 430 Output Harness DD, MPX Selection Headers Model 321 16.5 VAC, 40 VA Class 2 Plug-in. Form C Relays Output 1 N/C Violet Output 1 Com Gray Output 1 N/O Orange Output 2 N/C Violet Output 2 Com Gray Output 2 N/O Orange Voltage Outputs Output 3 White/Orange Output 4 White/Yellow Output 5 White/Green Output 6 White/Blue Output 7 White/Violet Output 8 White/Gray Output 9 White Output 10 White/Black Ground Black J4 Tamper Header Model 322 16 VAC, 56 VA Class 2 Wire-in. Secondary Power Supply 1.2 Amps max. charging current. Use only 12 VDC rechargeable batteries. DMP Model 367. Replace every 3 to 5 years. J2 Output Header J10 +B 2 3 S 4 5 6 8 7 11 12 13 15 14 Z3 GND Z4 Z5 GND Z6 16 19 17 Cold Water Pipe Earth Ground Keyswitch Arming S 18 20 Z7 GND Z8 22 21 23 S S 24 S S S S S 1K 1K 1K Ohm Ohm Ohm 1K Ohm S S S 1K 1K Ohm Ohm Auxliliary Power Total current 1.0 Amps combined from terminals 7, 11, 26, and 28. S ZONE 8 S ZONE 6 ZONE 5 ZONE 4 S ZONE 7 S 1K Ohm S S Bell S ZONE 3 16 to 18 gauge wire ZONE 2 S Maximum AC wire distance With 16 gauge wire: 70 feet With 18 gauge wire: 40 feet Red Black Can be connected to any zone. See section 21.4. 10 9 ZONE 1 S Models 790/790F 75mA at 8 to 14.5 VDC. Tamper protection when required for Model 350A Attack Resistant Enclosure. J6 Heat detectors, pull stations, or any other contact device listed for Fire Protective Signaling can be connected to zones 9 and 10. Z9+ Z9- Z10+ Z10- 26 25 27 28 Zones 9 and 10 and Model 715 compatibility identifier: A. Maximum operating range: 8.8 to 14.2 VDC. Class B, Style A. S 22 Gauge minimum BLACK Model 690/690F 72mA at 8 to 14.5 VDC. -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 22 Gauge minimum GREEN 1 Keypads Model 793 108mA at 8 to 14.5 VDC. Model 630F 60mA at 8 to 14.5 VDC. AC 22 Gauge minimum YELLOW AC 16 VAC Transformer 22 Gauge minimum RED 12 VDC nominal. Total current 1.5 Amps max. Minimum cutoff time is 5 minutes. Rear Tamper J16 Panel Reset Connect to nonswitched 120 VAC. Bell Front Tamper XR2400F Command Processor™ Panel J3 ZONE 9 ZONE 10 S S S S 1K S Ohm 3.3K Ohm 3.3K Ohm EOL EOL DMP DMP Model 309 Model 309 S = Supervised Circuit Red S Model 715 Zone Expansion Module 7mA @ 12 VDC Models 715-8, 715-16 20mA @12 VDC Red Yellow Green Black 4-Wire Smoke Detectors POWER Refer to LT-0164 for a list of approved 4-wire smoke detectors and power supervision releays. ARMED S S Power Supervision Relay S Smoke Detector Ð + Model 714 Zone Expansion Module 7mA @ 12 VDC Models 714-8, 714-16 20mA @12 VDC Model 711 Zone Expansion Module 7mA @ 12 VDC S S Disarm S S S S 1K Ohm S 1K Ohm S S S 1K Ohm Arm 1K Ohm 1K Ohm S S S 3.3K Ohm S S S S S 1K Ohm 1K Ohm 1K Ohm 1K Ohm S S 3.3K Ohm S S 3.3K Ohm S 3.3K Ohm Figure 13: Typical XR2400F Wiring Diagram 15.2 Lightning Protection Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on input and output circuits of the XR2400F. Additional surge protection is available by installing the DMP 370 or 370RJ Lightning Suppressors. XR2400F Installation Guide Digital Monitoring Products 17 INSTALLATION 15.3 Accessory Devices Interface Adaptor and Interface Cards 460 Interface Adaptor Card Allows you to connect two or more expansion interface cards to the XR2400F panel. The 461 is an expansion mother board that plugs into the J6 Interface Connector of the panel and is required when using two or more Interface Cards. Use combinations of Interface Cards for expanding zones, network interfacing, local printing, and connecting wireless devices. Requires Model 349, 350, or 350A Enclosure. 462N Network Interface Card Allows you to connect the XR2400F to any compatible data network and use its communication capability in place of standard dial out telephone lines. The 462N also provides an LX-Bus™ for connecting zone and output expansion modules to the panel. The 462N is listed for Grade AA Burglary communication and supplementary signaling. 462P Printer Interface Card Allows you to connect the XR2400F to any compatible serial printer providing real-time event recording to the user. The 462P also provides an LX-Bus™ for connecting zone and output expansion modules. 472 Inovonics 900 MHz Interface Card Provides an interface between the Inovonics FA400-DMP Wireless Receiver and the XR2400F panel. You can use any of the wireless equipment compatible with the FA400-DMP to construct a strictly wireless or combined wireless/hardwire system. Wireless functionality is listed for Household Fire and Burglary. The 472 also provides one LX-Bus™ for connecting zone and output expansion modules. 481 Expansion Interface Card Provides one LX-Bus for connecting up to 100 zone and output expansion modules. Zone and Output Expansion Modules 710/710F Bus Splitter/Repeater Allows you to increase keypad or LX-Bus™ wiring distance to 2500 feet. Model 710F is for 24 VDC applications. 711/711E Single Point Zone Expanders Provides one Class B zone for connecting burglary and non-powered Þre devices. 714, 714-8, 714-16 Zone Expanders Provides Class B zones for connecting burglary and non-powered Þre devices. 715, 715-8, 715-16 Zone Expanders Provides 12 VDC Class B powered zones for connecting smoke detectors, glassbreak detectors, and other 2- or 4-wire devices. 725 Zone Expanders Provides 24 VDC Class B powered zones for connecting smoke detectors, glassbreak detectors, and other 2- or 4-wire devices. 716 Output Expander Provides four Form C relays (SPDT) and four switched grounds (open collector) for use in a variety of remote annunciation and control applications. 717 Graphic Annunciator Module Provides 20 zone following annunciator outputs (open collector) for use in a variety of remote annunciation and control applications. Indicating and Initiating Devices 865 Supervised Style Y or Z NotiÞcation Circuit Module Provides up to 1.5 Amps of supervised alarm current when using the bell output of the XR2400F panel and up to 5 Amps at 12 or 24 VDC when using a listed auxiliary power supply. The 865 can supervise 2-wire Style Y or W circuits or X circuits for ground faults, opens, shorts, and shorts with individual LED annunciation. 866 NotiÞcation Circuit Module Provides up to 1.5 Amps of supervised alarm current using the bell output of the XR2400F panel and up to 5 Amps at 12 or 24 VDC when using a listed auxiliary power supply. The 866 can supervise Style W circuits for opens and shorts. 867 Style W LX-Bus NotiÞcation Circuit Module Provides up to 1.5 Amps of supervised alarm current using the bell output of the XR2400F panel and up to 5 Amps at 12 or 24 VDC when using a listed auxiliary power supply. The 867 connects to the LXBus™ of the XR2400F panel and provides one 2-wire Style W notiÞcation circuit for ground fault, open, and short conditions. Individual Bell Relay addresses Bell Ring styles. 869 Dual Style D Initiating Module Provides two Style D, 4-wire initiating zones for connecting waterßow switches and other non-powered Þre and burglary devices. Accessory Modules and Keypads 893A Dual Phone Line Module Allows you to supervise two standard phone lines connected to an XR2400F panel. The 893A module monitors the main and backup phone lines for a sustained drop in voltage and alerts users when voltage drops below 3 VDC. ePAD Virtual Keypads Allows users to control the security system from any computer in the world using the Internet. iCOM Internet Alarm Router Allows the panel to send signals through the Internet/Ethernet. iCOM-E High-Security Internet Alarm Router Allows the panel to send encrypted signals through the Internet/Ethernet. 630F Remote Fire Command Center Allows you control the panel from various remote locations. You may connect up to eight 630F Remote Fire Command Centers to the keypad bus on terminals 7, 8, 9, and 10. Security Command LCD keypads Allows you to control the panel from various remote locations. Connect up to eight supervised Model 690/790, 690F/790F, 791 or 793 Security Command® keypads to the keypad bus (terminals 7, 8, 9, and 10). Table 5: Accessory Devices Digital Monitoring Products 18 XR2400F Installation Guide INSTALLATION 15.4 Mounting Keypads and Zone Expanders Security Command keypads have removable covers that allow you to easily mount the keypad to a wall or other ßat surface using the screw holes provided on each corner of the base. Before mounting the base, connect the keypad wire harness leads to the keypad cable from the panel and to any device wiring run to that location. Then attach the harness to the pin connector on the PC board, mount the base, and install the keypad cover making sure all of the keys extend through their respective holes. For the 690/690F keypads, you can use the Model 695 1-1/2” deep or the Model 696 1/2” deep backboxes. For mounting keypads on solid walls, or for applications where conduit is required, use the Model 695 1-1/2” deep or the Model 696 1/2” deep backboxes. For the 790/790F, 793 keypads, you can use the Model 695 1-1/2” deep or the Model 696 1/2” deep backboxes. The DMP 710, 710F, 711, 711E, 714, 715, 716, 717, and 725 modules are each contained in molded plastic housings with removable covers. The housing cover contains the module while the base provides you with two mounting holes for installing the unit to a wall, switch plate, or other surface. 15.5 Connecting serial devices Several factors determine the performance characteristics of the DMP LX-Bus™ and keypad bus: the length of wire used, the number of devices connected, and the voltage at each device. When planning an LX-Bus™ and keypad bus installation, keep in mind the following information: 1. DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do not use twisted pair or shielded wire for LX-Bus and keypad bus data circuits. 2. On keypad bus circuits, to maintain auxiliary power integrity when using 22-gauge wire do not exceed 500 feet. When using 18-gauge wire do not exceed 1,000 feet. To increase the wire length or to add devices, install an additional power supply that is UL listed for Fire Protective Signaling, power limited, and regulated (12 VDC nominal) with battery backup. Note: Each panel allows a speciÞc number of supervised keypads. Add additional keypads in the unsupervised mode. Refer to the panel installation guide for the speciÞc number of supervised keypads allowed. 3. Maximum distance for any one bus circuit (length of wire) is 2,500 feet regardless of the wire gauge. This distance can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500 feet. As wire distance from the panel increases, DC voltage on the wire decreases. Maximum number of LX-Bus devices per 2,500 feet circuit is 40. 4. Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 VDC. If the voltage at any device is less than the required level, an auxiliary power supply should be added at the end of the circuit. For additional information refer to the 710 Installation Sheet (LT-0310) and or the LX-Bus/Keypad Bus Wiring Application Note (LT-2031). Expansion Interface Cards (Models 462N, 462P, 462FM, 472, 481, and 482) The LX-Bus provided on these cards requires only a 4-wire cable between the card and any devices connected to the bus. You can connect devices (zone or output expanders) together on the same cable or provide separate runs back to the cards. Up to 100 zones or relays are available on each LX-Bus. Note: Do not use shielded wire when running an LX-Bus or keypad bus. XR2400F Installation Guide Digital Monitoring Products 19 INSTALLATION Battery Information 16.1 Battery Only Restart When powering up the XR2400F panel without AC power, it is necessary to short across the CR7 leads to pull in the battery cutoff relay. The leads need a momentary short only. Once the relay has pulled in, the battery voltage holds it in that condition. If the XR2400F panel is powered up with an AC transformer, the battery cutoff relay is pulled in automatically. 16.2 Replacement Period DMP recommends the battery be replaced every 3 to 5 years under normal use. 16.3 Discharge/recharge The XR2400F battery charging circuit ßoat charges at 13.9 VDC at a maximum current of 1.2 Amps using a 40 VA transformer. The total current available is reduced by the combined auxiliary current draw from terminals 5, 6, and 24. The various battery voltage level conditions are listed below: Battery Trouble: Below 11.9 VDC Battery Cutoff: Below 10.2 VDC Battery Restored: Above 12.6 VDC 16.4 Battery Supervision The XR2400F tests the battery when AC power is present. The test is done every 3 minutes and lasts for Þve seconds. During the test, the panel places a load on the battery and if its voltage falls below 11.9 VDC a low battery is detected. If AC power is not present, a low battery is detected any time the battery voltage falls below 11.9 VDC. If a low battery is detected with AC power present, the test is repeated every two minutes until the battery charges above 12.6 VDC; the battery restored voltage. If a weak battery is replaced with a fully charged battery, the restored battery will not be detected until the next two minute test is done. 16.5 Battery Cutoff The panel disconnects the battery any time the voltage of the battery drops below 10.2 VDC. This prevents deep discharge damage to the battery. 16.6 XR2400F Power Requirements During AC power failure, the XR2400F panel and all auxiliary devices connected to the XR2400F draw their power from the battery. All devices must be taken into consideration when calculating the battery standby capacity. On the following page is a list of the power requirements of the XR2400F panel. First add the current draw of the devices included in the XR2400F FACP: • XR2400F Command Processor™ Panel • The Fire Command Center • 893A Dual Phone Line Module • Two 866 NAC modules • 462N Network Interface Then add the additional current draw of Remote Fire Command Centers, zone expanders, smoke detector output, and any other auxiliary devices used in the system for the total current required. The total is then multiplied by the number of standby hours required to arrive at the total ampere-hours required. See the Panel Standby Battery Power Calculations chart on the following page. Digital Monitoring Products 20 XR2400F Installation Guide INSTALLATION 16.7 XR2400F Standby Battery Calculations Standby Battery Power Calculations XR2400F Command Processor™ Panel Relay Outputs 1-2 (ON) Voltage Outputs 3-10 (ON) Active Zones 1-8 Active Zones 9-10 2-Wire Smoke Detectors Panel Bell Output 893/893A Dual Phone Line Module 460 Interface Adaptor Card 462N Network Interface Card 462P Printer Interface Card 472 Inovonics 900MHz Interface Card 481 Expansion Interface Card 485 Enhanced Access Control Expansion Card 865 Style y or Z NotiÞcation Module 866 Style W NotiÞcation Module 867 LX-Bus Style W NotiÞcation Module 630F Remote Fire Command Center 690/690F Security Command Keypad Annunciator (ON) 790/790F Security Command Keypad Active Zones (EOL Installed) Annunciator (ON) 791 Easy Entry Keypad Active Zones (EOL Installed) Annunciator (ON) 793 Easy Entry Keypad Active Zones (EOL Installed) Annunciator (ON) 770, 771 Security Command Keypads Active Zones (EOL Installed) Annunciator (ON) 733 Wiegand Interface Module Active Zones (EOL Installed) Annunciator (ON) 734 Wiegand Interface Module Active Zones (EOL Installed) Annunciator (ON) 736P POPIT Interface Module Radionics Popex, POPITs, OctoPOPITs 738A Ademco Wireless Interface Module 710 Bus Splitter/Repeater Module 710F Fire Bus Splitter/Repeater Module 711, 771E, 714 Zone Expansion Modules Active Zones (EOL Installed) 714-8, 714-16 Zone Expansion Module Active Zones (EOL Installed) 715 Zone Expansion Module Active Zones (EOL Installed) 2-Wire Smokes 715-8, 715-16 Zone Expansion Modules Active Zones (EOL Installed) 2-Wire Smokes 716 Output Expansion Module Active Form C Relays 717 Graphic Annunciator Module Annunciator Outputs 521LX, 521LXT, SLRLX Smoke Detectors iCOM, iCOM-E Internet Alarm Routers Aux. Powered Devices on Terminals 7 and 11 Other than Keypads and LX-Bus Modules Qty Qty Qty Qty Qty Qty Standby Current ______x 80mA ______mA ______x 30mA ______ ______x 5mA ______ ______x 1.6mA ______ ______x 4mA ______ ______x 0.1mA ______ Qty ______x Qty Qty Qty Qty ______x ______x ______x ______x Qty Qty Qty Qty Qty ______x ______x ______x ______x ______x 30mA 7mA 50mA 50mA 85mA 15mA 45mA 26mA 45mA 30mA 60mA 77mA ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty ______x 77mA ______ 1.6mA ______ Qty Qty Qty ______x 100mA ______ 1.6mA ______ Qty Qty Qty ______x 92mA ______ 1.6mA ______ Qty Qty Qty ______x Qty ______x 100mA ______ 1.6mA ______ Qty Qty Qty ______x Qty ______x 30mA ______ 1.6mA ______ Qty ______x Qty ______x 30mA ______ 1.6mA ______ Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty 25mA ___mA 75mA 30mA 40mA 7mA 1.6mA 20mA 1.6mA 7mA 4mA .1mA 20mA 4mA .1mA 7mA Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty Qty ______x ______x ______x ______x ______x ______x ______x ______x ______x ______x ______x ______x ______x Qty ______x ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ Qty ______x 10mA ______ Qty ______x 8.8mA ______ ______mA Qty Qty Qty Qty Qty Alarm Current 80mA ______mA ______x 30mA ______ ______x 5mA ______ ______x *2mA ______ ______x 30mA ______ ______x 0.1mA ______ 1500mA ______mA ______x 50mA ______ 7mA ______ ______x 50mA ______ ______x 50mA ______ ______x 85mA ______ ______x 15mA ______ 45mA ______ ______x 85mA ______ ______x 75mA ______ ______x 85mA ______ ______x 92mA ______ ______x 84mA ______ 20mA ______ ______x 84mA ______ ______x *2mA ______ 20mA ______ ______x 100mA ______ ______x *2mA ______ 20mA ______ ______x 120mA ______ ______x *2mA ______ 20mA ______ ______x 100mA ______ ______x *2mA ______ 20mA ______ ______x 30mA ______ ______x *2mA ______ ______x 20mA ______ ______x 30mA ______ ______x *2mA ______ ______x 20mA ______ ______x 25mA ______ ______x ___mA ______ ______x 75mA ______ ______x 30mA ______ ______x 40mA ______ ______x 7mA ______ ______x *2mA ______ ______x 20mA ______ ______x *2mA ______ ______x 7mA ______ ______x *30mA ______ ______x .1mA ______ ______x 20mA ______ *30mA ______ .1mA ______ ______x 7mA ______ ______x 28mA ______ ______x 10mA ______ ______x 1mA ______ ______x *28mA ______ 78.1mA ______ ______mA *Based on 10% of active zones in alarm Total Standby ______mA Total Alarm ______mA Total Standby______mA x number of Standby Hours needed ______ = ________mA-hours Total Alarm ______mA + ________mA-hours Cannot exceed 7.7Ah with one Model 367 Battery Total ________mA-hours Cannot exceed 15.4Ah with two Model 367 Batteries X .0001 Cannot Exceed 23.1Ah with three Model 367 Batteries Cannot exceed 30.8Ah with four Model 367 Batteries = ________Amp-hrs Required XR2400F Installation Guide Digital Monitoring Products 21 INSTALLATION Bell Output 17.1 Terminals 5 and 6 Terminal 5 supplies positive 12 VDC to power alarm bells or horns. The output is rated for a maximum output of 1.5 Amps. This output can be steady or pulsed or temporal code 3 depending upon the Bell Action speciÞed in Output Options. Terminal 6 is the ground reference for the bell circuit. Keypad and Zone Expander Bus 18.1 Description Terminals 7, 8, 9, and 10 of the XR2400F panel are for the keypad data bus. In addition to Fire Command Centers and Remote Fire Command Centers, you can also connect any combination of up to eight zone expanders, 5845LX Glassbreak detectors, and 6155LX PIRs to the data bus. Note: Do not use shielded wire for LX-Bus or keypad bus circuits. 18.2 Terminal 7 - RED This terminal supplies positive 12 VDC to power Fire Command Centers and zone expanders. This is also where power for any auxiliary device is supplied. The ground reference for terminal 7 is terminal 10 with the maximum output rated at 1 Amp. The output current is shared with the smoke detector output on terminal 11 and Zones 9 and 10. All devices totalled together must not exceed the panel’s maximum current rating of 1 Amp. 18.3 Terminal 8 - YELLOW Data receive from keypads and zone expanders. It cannot be used for any other purpose. 18.4 Terminal 9 - GREEN Data transmit to keypads and zone expanders. It cannot be used for any other purpose. 18.5 Terminal 10 - BLACK Terminal 10 is the ground reference for Fire Command Centers, zone expanders, and any auxiliary devices being powered by terminal 7. Smoke Detector Output 19.1 Terminals 11 and 12 Terminal 11 supplies positive 12 VDC to power 4-wire smoke detectors and other powered devices. This output can be turned off by the user for 5 seconds using the Sensor Reset User Menu option to allow latched devices to reset. Terminal 12 is the ground reference for terminal 11. 19.2 Current Rating The Output current from terminal 11 is shared with terminals 7, 26, and 28. The total current draw of all devices powered from the panel must be included with terminal 11 calculations and must not exceed the maximum output rating of 1 Amp. Powered Zones for 2-Wire Smoke Detectors 20.1 Terminals 25-26 and 27-28 Two resettable Class B (Style A) 2-wire powered zones are provided on terminals 25 through 28 on the panel. For programming purposes the zone numbers are 9 and 10. When using 725 Zone Expansion modules, use UL Listed 6.8k Ohm EOL resistors. The UL compatibility identiÞer for the zones using 725 Zone Expansion Modules is B. When using 715 Zone Expansion modules, use UL Listed 3.3k Ohm EOL resistors (Model 309). When using all other zone expansion modules, use UL Listed 1.0k Ohm EOL resistors (Model 310). The UL compatibility identiÞer for the zones is A. Digital Monitoring Products 22 XR2400F Installation Guide INSTALLATION Do not mix detectors from different manufacturers on the same zone. Caution: Performing a Sensor Reset will momentarily drop power to the devices on Zones 9 and 10. The panel will view these zones 10 as “Open” while the power is dropped. 20.2 Compatible 2-Wire Smoke Detectors Manufacturer Model Detector ID Base Base DC # of ID Voltage Detectors Range (12V/24V) Zone Expansion Modules Detection Systems DS230, DS230F B/A MB2W, MB2WL A 8.5-33 10 725 Detection Systems DS250, DS250TH B MB2W, MB2WL A 8.5-33 10/12 715, 715-8, 715-16, 725 Detection Systems DS250HD B MB2W, MB2WL A 8.5-33 10 715, 715-8, 715-16 Detection Systems DS260 B/A MB2W, MB2WL A 8.5-33 17 725 Detection Systems DS282, DS282TH B 8.5-33 10/12 715, 715-8, 715-16, 725 DMP/Hochiki SLK-835 HD-5 HSB-200, HSB200N HB55 8-35 7 715, 715-8, 715-16 DMP/Hochiki SLR-835 HD-3 NS6-100 HB55 8-35 7/14 715, 715-8, 715-16, 725 DMP/Hochiki SLR-835B HD-6 8-35 7/14 715, 715-8, 715-16, 725 Hochiki SLR-835B-2 HD-6 8-35 14 725 Hochiki SLR-24, SLR-24H HD-3 NS4-220 HB-3 15-33 15 725 Hochiki SIJ-24, DCD-190, DCD135 HD-3 NS4-220 HB-3 15-33 15 725 Hochiki SLR-24, SLR-24H HD-3 NS6-220 HB-3 15-33 15 725 Hochiki SIJ-24 HD-3 NS6-220 HB-3 15-33 20 725 NS6-220 HB-3 Hochiki DCD-190, DCD-135 HD-3 15-33 16 725 Sentrol/ESL 429AT, 521B, 521BXT S09A 6.5-20 12 715, 715-8, 715-16 Sentrol/ESL 429C, 429CT, 521B/BXT S10A 8.5-33 12 725 Sentrol/ESL 429CRT, 429CST, 429CSST, 521CRXT S11A 8.5-33 12 725 Sentrol/ESL 711U, 712U, 713-5U, 713-6U, 721U, 721UT S10A 701E, 70-1U, 702E, 702U S00 8.5-33 12 725 Sentrol/ESL 731U, 723U S11A 701E, 701U, 702E, 702U, 702RE, 702RU S00 8.5-33 12 725 System Sensor 1100, 1400 STD 8.5-33 10 715 System Sensor 1151, 2151 STD B110PL, B401 8.5-33 10/10 715, 725 System Sensor 1451, 2451TH STD B401, B401B 8.5-33 10 715 System Sensor 1451DH STD DH400 8.5-33 10 715 System Sensor 2100, 2100T STD 8.5-33 10 715 System Sensor 2100S, 2100TS A 8.5-35 12 725 System Sensor 2400, 2400AT, 2400AIT, 2400TH STD 8.5-33 10 715 System Sensor 2451 STD 8.5-35 10 715 System Sensor DH100P A 8.5-35 10 725 B401, B401B, DH400 Table 6: Compatible 2-Wire Smoke Detectors XR2400F Installation Guide Digital Monitoring Products 23 INSTALLATION Protection Zones 21.1 Description Zones 1 to 8 on the XR2400F panel (terminals 13 to 24) are all grounded burglary zones. For programming purposes, the zone numbers are 1 through 8. Terminals 13 to 24 provide connection as listed below. Terminal Function Terminal Function 13 14 15 16 17 18 Zone 1 voltage sensing Ground for Zones 1 & 2 Zone 2 voltage sensing Zone 3 voltage sensing Ground for Zones 3 & 4 Zone 4 voltage sensing 19 20 21 22 23 24 Zone 5 voltage sensing Ground for Zones 5 & 6 Zone 6 voltage sensing Zone 7 voltage sensing Ground for Zones 7 & 8 Zone 8 voltage sensing Note: Zones 1 through 4 have been pre-wired to the two 866 NAC modules and the 504-24 power supply. All other zones are available. The voltage sensing terminal measures the voltage through a 1k Ohm End-of-Line resistor to ground. Dry contact sensing devices can be used in series (normally-closed) or in parallel (normally-open) with any of the burglary protection zones. 1K Ohm Normally Closed 1K Ohm Normally Open 1K Ohm Combination Normally Open and Normally Closed Figure 14: Protection Zone Wiring 21.2 Operational Parameters Each protection zone detects three conditions: open, normal, and short. The voltage and resistance parameters for each condition are listed below: Condition Open Normal Short Resistance on zone over 1300 ohms 600 to 1300 ohms under 600 ohms Voltage on positive terminal over 2.0 VDC 1.2 to 2.0 VDC under 1.2 VDC 21.3 Zone Response Time A condition must be present on a zone for 500 milliseconds before it’s detected by the XR2400F panel. Ensure detection devices used on the protection zones are rated for use with this delay. The zones can also be programmed for a fast response delay of 167 milliseconds. 21.4 Keyswitch Arming Zone Using a keyswitch on an Arming type zone allows you to arm and disarm selected areas without having to enter a user code. Digital Monitoring Products 24 XR2400F Installation Guide INSTALLATION Dry Contact Relay Outputs 22.1 Description The XR2400F panel provides two auxiliary SPDT relays when equipped with two DMP Model 305 relays in sockets K6 (Output 1) and K7 (Output 2) and a Model 430 Output Harness. Each relay provides one single pole, double throw (SPDT) set of contacts that can be operated by any of the functions listed below: 1) Activation by zone condition Steady Pulsing Momentary Follow 2) Activation by 24 hour 7 day schedule One on and one off time per day for each relay 3) Manually from the Fire Command Center menu 4) Communication failure 5) Armed area annunciation 6) Fire Alarm or Fire Trouble 7) Other system conditions. See the Programming Guide (LT-0196). 22.2 Contact Rating The Model 305 relay contacts are rated for 1 Amp at 30 VDC resistive. You can connect auxiliary power to the common terminal of Relay Output 1 by installing the gray harness wire to terminal 7. 22.3 Output Harness Wiring The relay contacts are accessible by installing the DMP 430 Output Harness on the 15-pin header labeled J2. The contact locations on the wire harness are shown below: Output Output Output Output Output Output Contact 1 normally 1 common 1 normally 2 normally 2 common 2 normally closed open closed open Color Violet Gray Orange Violet Gray Orange The relay contacts must be connected to devices located within the same room as the XR2400F panel. 12 VDC Voltage Outputs 3 to 10 23.1 Description The XR2400F also provides eight 12 VDC, 50mA resistive voltage outputs on J2 to power external relays or other devices. The voltage outputs are operated from the same functions as Outputs 1 and 2. When connecting any devices to outputs 3 to 10, subtract the current draw of the device from the panel’s available auxiliary power. 23.2 Output Harness Wiring The voltage outputs are accessible by installing the DMP 430 Harness on the 15-pin header labeled J2. The output locations are shown below: Output Color Output Color Output Color 3 White/Orange 6 White/Blue 9 White 4 White/Yellow 7 White/Violet 10 White/Black 5 White/Green 8 White/Gray Ground Black Devices connected to the outputs must be located within the same room as the XR2400F panel. XR2400F Installation Guide Digital Monitoring Products 25 INSTALLATION Reset and Tamper Headers 24.1 J16 Reset Header The reset header is located just above the terminal strip on the right side of the circuit board and is used to reset the microprocessor of the XR2400F. To reset the panel when Þrst installing the system, install the reset jumper before applying power to the panel. After connecting the AC and battery, remove the reset jumper. To reset the panel while the system is operational, such as prior to reprogramming, install the reset jumper without powering down the system. Remove the reset jumper after one or two seconds. After resetting the panel, you must begin programming within 30 minutes. If you wait longer than 30 minutes, you will have to reset the panel again. J4 Tamper Momentarily place the Reset jumper over the J16 header to reset the panel. J16 Panel Reset AC AC +B 1 2 3 -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 4 5 6 7 8 9 10 11 12 13 14 15 Z3 GND Z4 Z5 GND Z6 16 19 17 18 20 21 Z7 GND Z8 22 23 24 Z9+ Z9- Z10+ Z10- 25 26 27 28 Figure 15: XR2400F Panel Showing Reset 24.2 J4 Tamper Header The J4 header is for use with the optional DMP 306 Tamper Harness. The harness connects to one or more tamper switches mounted inside the panel enclosure to supervise against unauthorized opening or removal of the enclosure. Refer to the wiring diagram on the enclosure door for correct tamper switch wiring. How the tamper works If the enclosure is opened or removed while one or more of the system’s areas are armed, a panel tamper alarm is indicated. If all areas are disarmed, a panel tamper trouble is indicated. Digital Monitoring Products 26 XR2400F Installation Guide COMPLIANCE Universal UL Burglary SpeciÞcations 25.1 Introduction The programming and installation speciÞcations contained in this section must be completed when installing the XR2400F panel in accordance with any of the UL burglary standards. Additional speciÞcations may be required by a particular standard. 25.2 Wiring All wiring must be in accordance with NEC, ANSI/NFPA 70, UL 681, and UL 611 for all burglary installations. 25.3 Control outside of protected area A Potter EVD or Sentrol 5402 should be used in place of a lined cabinet when the panel is installed outside of the protected area. 25.4 Police station phone numbers The digital dialer telephone number programmed for communication must not be a police station phone number, unless that phone number is speciÞcally provided for that purpose. 25.5 Bypass reports The Bypass Reports option must be programmed as YES for all UL burglary applications. See section 6.4 of the XR200 and XR2400F Programming Guide (LT-0196). 25.6 System maintenance Proper installation and regular maintenance by the installing alarm company and frequent testing by the end user is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance program and acquainting the user with the correct procedure for use and testing of the system is also the responsibility of the installing alarm company. 25.7 Partitions The partition option may only be used for UL burglary applications when all partitions are used for one subscriber. See section 4.2 and 11.2 of the XR200 and XR2400F Programming Guide (LT-0196). The panel must be tamper protected and Sentrol Model 5402 or Potter EVD listed vibration detectors should be used. 25.8 UL Listed Receivers UL has veriÞed operation with the DMP SCS-1 and SCS-1R, Sur-Gard SG-HLR2-DG, FBII CP220PB, OsborneHoffman Quick-Alert, and Radionics D6500 receivers. UL 1023 SpeciÞcations Household Burglar-Alarm System Units 26.1 Bell cutoff The Bell Cutoff time cannot be less than Þve minutes. See section 8.2 of the XR200 and XR2400F Programming Guide (LT-0196). 26.2 Entry delay The maximum entry delay used must not be more than 45 seconds. See section 7.3 of the XR200 and XR2400F Programming Guide (LT-0196). 26.3 Exit delay The maximum exit delay used must not be more than 60 seconds. See section 13.4 of the XR200 and XR2400F Programming Guide (LT-0196). 26.4 Weekly test The product should be tested weekly. XR2400F Installation Guide Digital Monitoring Products 27 COMPLIANCE UL 1610 And 1076 SpeciÞcations Central-Station and Proprietary Burglar-Alarm Units 27.1 Multiplex network capacity The total number of panels assigned to a standard MPX receiving line of the SCS-1 Receiver System must not exceed 90. This may be increased to 180 by setting the SNRM option to NO in the SCS-1 Receiver system. This is to allow any signal from a XR2400F panel to be transmitted to the receiver within 90 seconds. This allows Grade AA Multiplex service. 27.2 Opening/Closing reports The Opening/Closing Reports option must be programmed as YES. See section 13.6 of the XR200 and XR2400F Programming Guide (LT-0196). 27.3 Closing wait The Closing Wait option must be programmed YES. See section 7.2 of the Programming Guide (LT-0196). 27.4 Proprietary dialer The Model XR2400F provides Grade A proprietary service when conÞgured as a digital dialer. 27.5 AA Network Communication When HST network communication is used, a dialer line must also be used along with the Model 893 Dual Phone Line Module to supervise the dialer line. The HST network Check-in time must be set from 01 to 06 minutes or AA. This provides AA Central Station Service. See sections 3.2, 3.2.4, and 3.3 of the XR200 Programming Guide (LT-0196). The Model XR2400F Protected Premises Control Unit is suitable for Grade AA service when conÞgured for multiplex DNET or HST communication with SCS-1/SCS-1R receiving system. This conÞguration is approved for: AMCX - Central Station Alarm Units APAW - Police Station Alarm Units APOU - Proprietary Alarm Units This approval is for communication over public data networks, provided that the protected premise (XR2400F) and receiving units (SCS-1/SCS-1R) are listed. Additionally, the network device connected to the 462N Network Interface Card must be listed for UL Fire and Shock hazards. For combined burglary and Þre alarm systems, UL has an established set of requirements that specify certain hardware redundancies and communication protocols to ensure that indications of a Þre or burglary are properly transmitted at the time of their occurrence. Typically in a combined system, two dialer phone lines are dedicated to the alarm. This limits the interruption of normal business phone trafÞc caused by supervisory communication requirements of the alarm system. With the DMP system communicating over a data network however, this interruption of business phones is avoided by the panel’s ability to send its trafÞc at any time directly over the network. The business phone lines are then used only to send a nightly Recall Test report or the report of an actual alarm to the central monitoring station. This eliminates the monthly expense of two phone lines dedicated to the alarm. The DMP products meeting the UL requirements include the listed Model 893 Dual Phone Line Module used in supervising two separate analog phone lines and the Model 462N Network Interface Card listed as a supplementary signaling device for commercial Þre systems. If the requirement for the two dedicated phone lines is made by the local AHJ for the purpose of avoiding situations where the burglary/Þre alarm system is incapable of communicating, the DMP panels have a builtin ability to seize the phone line and interrupt any call in progress as required by NFPA and UL. Instructions to the system installer for correctly wiring of the telephone jacks is also included in all DMP installation guides as an added measure of ensuring the system’s communicating ability. Digital Monitoring Products 28 XR2400F Installation Guide COMPLIANCE UL 1635 SpeciÞcations Digital Burglar Alarm Communicator System Units 28.1 System trouble display The Status List Display must include at least one keypad that displays system monitor troubles. See section 10.1 of the XR200 and XR2400F Programming Guide (LT-0196). 28.2 Digital Dialer telephone number Both programmed telephone numbers must begin with a D or P. See sections 3.17 and 3.18 of the XR200 and XR2400F Programming Guide (LT-0196). 28.3 Entry delay The maximum entry delay used must not be more than 60 seconds. See section 7.3 of the XR200 and XR2400F Programming Guide (LT-0196). 28.4 Exit delay The maximum exit delay used must not be more than 60 seconds. See section 13.4 of the XR200 and XR2400F Programming Guide (LT-0196). 28.5 Test time The Test Time option must be programmed so that the XR2400F sends a report once every 24 hours. See sections 3.8 to 3.10 of the Programming Guide (LT-0196). 28.6 Closing wait The Closing Wait option must be programmed YES. See section 7.2 of the Programming Guide (LT-0196). UL 365 And 609 SpeciÞcations Police Station Connected and Local Burglar Alarm Units and Systems 29.1 System trouble display The Status List Display must include at least one keypad that displays system monitor troubles. See section 10.3 of the Programming Guide (LT-0196). 29.2 Grade A bell A Grade A local audible signal appliance must be used. 29.3 Bell cutoff The Bell Cutoff time cannot be less than 15 minutes. See section 8.2 of the Programming Guide (LT-0196). 29.4 Automatic bell test The Automatic Bell Test option must be programmed as YES. See section 8.3 of the Programming Guide. 29.5 Line security for Police Connect Basic line security is provided when the Model XR2400F is conÞgured as a dialer system. 29.6 High Line Security High Line Security is provided when conÞgured as a MPX, DNET, or HST system. When HST communication is used, a dialer line must also be used along with the Model 893 Dual Phone Line Module to supervise the dialer line. The HST Check-in time must be set from 01 to 06 minutes or AA. See section AA Network Communication (27.5). Also see sections 3.2, 3.2.4, and 3.3 of the XR200 and XR2400F Programming Guide (LT-0196). XR2400F Installation Guide Digital Monitoring Products 29 COMPLIANCE Universal UL And NFPA Fire Alarm SpeciÞcations 30.1 Introduction The programming and installation speciÞcations contained in this section must be completed when installing the Model XR2400F in accordance with any of the UL or NFPA Þre standards. Additional speciÞcations may be required by a particular standard. 30.2 Wiring All wiring must be in accordance with NEC, ANSI/NFPA 70. 30.3 Transformer A wire-in transformer should be used. Use the 16 VAC 40 VA DMP Model 320. The transformer must be mounted within 20 feet of the panel connected by conduit. 30.4 End-of-Line resistor The DMP Model 310 1k Ohm EOL resistor should be used on all 1k Ohm EOL Þre zones. 30.5 System trouble display The Status List Display must include at least one keypad that displays system monitor troubles. See section 10.3 of the Programming Guide (LT-0196). 30.6 Fire display The Status List Display must include at least one keypad that displays troubles and alarms on Þre type zones. See section 10.4 of the Programming Guide (LT-0196). 30.7 Police station phone number The digital dialer telephone number programmed for communication must not be a police station phone number, unless that phone number is speciÞcally provided for that purpose. 30.8 System maintenance Proper installation and regular maintenance by the installing alarm company and frequent testing by the end user is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance program and acquainting the user with the correct procedure for use and testing of the system is also the responsibility of the installing alarm company. 30.9 Audible alarm Fire Type zones should be programmed to activate an audible alarm. The Bell Action for Fire Type zones should not be programmed as “N”. See section 8.4.1 in the Programming Guide (LT-0196). 30.10 Fire zone programming If a retard delay is used on a waterßow zone, it cannot exceed 90 seconds and any retard delay in the waterßow initiating devices must be subtracted from the 90 seconds allowed. See sections 14.4 and 14.17 in the Programming Guide (LT-0196). The retard delay should not be used on a zone with smoke detectors. 30.11 Style D zones If required, the DMP 869 Dual Style D Initiating Module provides for connection of two Style D zones to the Model XR2400F. See section Dual Style D Zone Module Installation in System Wiring Diagrams and the 869 Installation Guide (LT-0186) for wiring information. 30.12 Video Option The Video option must be selected as NO when any Þre protection is connected to the XR2400F. See section 7.9 in the Programming Guide (LT-0196). 30.13 UL Listed Receivers UL has veriÞed operation with the DMP SCS-1/SCS-1R (SDLC), Sur-Gard SG-HLR2-DG (CID, M2E), FBII CP220PB (CID), Osborne-Hoffman Quick-Alert (CID, M2E), and Radionics D6500 (M2E) receivers. Digital Monitoring Products 30 XR2400F Installation Guide COMPLIANCE UL 985 NFPA 72 (Chapter 2) SpeciÞcations Household Fire Warning System Units 31.1 Bell output deÞnition The Bell Output of the Model XR2400F must be programmed to operate steady on burglary alarms and pulsed or temporal on Þre alarms. See section 8 of the Programming Guide (LT-0196). UL 864 NFPA 72 (Chapter 9) SpeciÞcations Control Units for Fire-Protective Signaling Systems 32.1 Zone restoral reports The Restoral Reports option must be selected as YES or DISARM. See section 6.3 in the Programming Guide (LT-0196). 32.2 Power fail delay The Power Fail Delay option must be selected as 6 hours. See section 7.6 of the Programming Guide (LT0196). 32.3 Sprinkler supervisory Any zone used for sprinkler supervisory must be programmed with “SPRINKLR XXX” as the zone name. The last three characters in the zone name may be assigned a number to identify the zone. The Model 893 or 893A Dual Phone Line Module must be used on all sprinkler supervisory systems. 32.4 DACT systems Two phone lines must be used. The two phone lines cannot be ground start or party lines. The 893 or 893A Dual Phone Line Module is used to provide connection of two phone lines to the system. The 2ND Phone Line communication option must be selected as YES. See section 3.3 of the Programming Guide (LT-0196). Two different phone numbers must be programmed for digital communication. See sections 3.17 and 3.18 of the Programming Guide (LT-0196). The Test Time option must be programmed so that the XR2400F sends a report every 24 hours. See sections 3.8 to 3.10 of the Programming Guide (LT-0196). Additionally, you can use the 462N Network Interface Card and the HST (Host) Communication type for supplementary communication over digital data networks. 32.5 Type 2 and Type 3 Central Station Service Type 2 and Type 3 Central Station Service can be provided by using MPX communication to the DMP SCS-1/ SCS-1R Receiver system. See section 3.2 of the Programming Guide (LT-0196). 32.6 Type 1 Central Station Service Type 1 Central Station Service can be provided by using MPX as the main communication and digital dialer as backup. The 893 Dual Phone Line Module is used to provide connection of the MPX and dialer lines. See section 3.2 of the Programming Guide (LT-0196). If Type 1 Central Station service is provided, the Test Time option must be programmed to send a report every 24 hours. See sections 3.8 to 3.10 of the Programming Guide (LT-0196). With both Type 1 and Type 2 Central Station service, the total number of panels assigned to a standard MPX receiving line of the SCS-1/SCS-1R Receiver System must not exceed 90. This may be increased to 180 by setting the SNRM option to NO in the SCS-1/SCS-1R Receiver system. This is to allow any signal from a XR2400F to be transmitted to the receiver within 90 seconds. 32.7 Local Protective Signaling Systems The DMP Model 865, 866, or 867 NotiÞcation Circuit Module must be used on the bell circuit for detection of shorts and grounds. See sections 25.1 to 25.3 for wiring diagrams. Model 770 series keypads that are used to display troubles for local Þre alarm systems must be installed within a DMP Model 777 Keypad Protector. Model 790 series keypads that are used to display troubles for local Þre alarm systems must be installed within a DMP Model 777 with 777S 1.0” spacer. Any burglary or other off premises communication must be done with the Model 893 or 893A Dual Phone Line Module. XR2400F Installation Guide Digital Monitoring Products 31 COMPLIANCE 32.8 Proprietary Protective Signaling Systems The total number of panels assigned to one MPX or DNET receiving line of the DMP SCS-1 Receiver system must not exceed 90. This may be increased to 180 by setting the SNRM option to NO in the SCS-1 Receiver system. This allows any report from a XR2400F to be sent to the receiver within 90 seconds. 32.9 Remote Station Protective Signaling Systems You must provide 60 hours of standby battery. Up to four 12 VDC, 6.5Ah batteries may be used. See section Standby Battery Power Calculations. Two Radionics Model D127 Reversing Relay Modules provide two reversing polarity telephone connections. See section Remote Station Reversing Relay Connection and the D127 Installation Instruction sheet for wiring details. A DMP Model 893 or 893A is used to provide two line dialer communication or Type 1 Multiplex communication. 32.10 Fire Protective Signaling Systems with an iCOM™ The XR2400F Panel must be programmed as described below for Fire Protective Signaling Systems using an iCOM™ Internet Alarm Router for communication. • UL AA must be programmed as NO • SUB CODE must be programmed as YES • CHECKIN must be programmed as 1 • RETRY TIME must be programmed as 1 • FAIL TIME must be programmed as 1 • NET TRBL must be programmed as YES Refer to the iCOM™ Internet Alarm Router Installation Sheet (LT-0587) for more information. California State Fire Marshal SpeciÞcations 33.1 Bell output deÞnition The Bell Output of the XR2400F panel must be programmed to operate steady on burglary alarms and pulsed, temporal, or California School Code on Þre alarms. See sections 8.4.1 and 8.4.2 of the Programming Guide (LT-0196). Digital Monitoring Products 32 XR2400F Installation Guide XR2400F Installation Guide Notification Circuit Module DMP Model 865 25mA @12 VDC 1 AUX PWR 2 GND 3 Alarm In 4 Bell PWR In + 5 Bell PWR In 6 Bell Out A + 7 Bell Out A 8 Bell Out B + 9 Bell Out B 10 Bell Trouble 11 Bell Trouble 865 Module Normal/Silence Switch Power Supply Trouble Contacts N/C + Auxiliary Power Supply AUX PWR GND Alarm In Bell PWR In Bell Out + Bell Out Bell Trouble Bell Trouble 24 VDC 5 Amp Maximum 1 2 3 4 5 6 7 8 866 Module Normal/Silence Switch S S S S 1K EOL S S S S UL Listed, Polarized Notification Appliances 24 VDC 5 Amp Maximum + Auxiliary Power Supply S S S S S S Power Supply Trouble Contacts N/C Each 866 Notification Appliance Circuit Module in alarm draws up to 30mA through its Terminal 3 Alarm Input and 45mA from its Terminal 1 Aux Power Input. Style W 10K EOL DMP Model 308 - + 1 AC 2 AC 3 +B J11 J10 J4 Tamper Header 4 5 6 S 8 9 S 10 11 12 13 14 15 16 Each 865 Notification Appliance Circuit Module in alarm draws up to 59mA through its Terminal 3 Alarm Input and 26mA from its Terminal 1 Aux Power Input. 7 S 17 Note: If an auxiliary power supply is not used, terminals 3 and 4 can be jumpered together to supply Bell Power from the XR200 panel. A maximum of 1.5 Amps as 12 VDC is available from terminal 5 of the XR200 panel. S 18 Z3 GND Z4 21 22 23 24 25 26 27 28 Z9+ Z9- Z10+ Z10- S = Supervised Circuit 20 Z7 GND Z8 J16 Panel Reset 462N Network Interface Card The Auxiliary Power Supply and Notification Circuit Module trouble contact zone must be programmed as a Supervisory Type zone and must be selected for display in the keypad status list (See section 10.6 in the Programming Guide (LT-0196)). 19 Z5 GND Z6 J2 Output Header XR2400F Command Processor™ Panel -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 DD, MPX Selection Headers J12 UL Listed, Polarized Notification Appliances J3 Auxiliary Power Supply must be regulated, UL Listed for Fire Protective Signaling Service. Power Supplies must have battery backup. - + Style Z To additional 866 Notification Circuit Modules. Up to a maximum of twenty-five 866 Modules on the XR2400F panel. All modules must be installed in a 340FC, 349, or 350 Notification Circuit Module Enclosure connected by no more than 20 feet of conduit. DMP Model 866 45mA @12 VDC WIRING DIAGRAMS System Wiring Diagrams 34.1 Multiple NotiÞcation Circuit Modules Digital Monitoring Products 33 WIRING DIAGRAMS J12 J11 XR2400F Command Processor™ Panel J3 J4 Tamper Header DD, MPX Selection Headers Answering Machine Bypass Relay Use Model 305 462N Network Interface Card 34.2 Multiple NotiÞcation Circuit Modules for Zoned Annunciation J2 Output Header All outputs must be located Ground Start Relay within the same room as K2 K4 Use Model 305 the control panel. To additional Zone 1 Notification Circuit Modules. Install up to a maximum of twenty-five 866 Modules by using the relay outputs available on the XR2400F panel. J10 Relay Output 1 Use Model 305 All modules must be installed in a 340FC, 349, or 350 Enclosure connected by no more than 20 feet of conduit. AC AC +B 1 2 3 4 5 6 8 7 S 10 9 14 15 16 19 17 S S Common Notification Circuit Module DMP Model 866 45mA @ 12 VDC 10K EOL DMP Model 308 S S S Style W S UL Listed, Polarized Notification Appliances S 1K EOL S + 504-24 Power Supply Each 866 Notification Appliance Circuit Module in alarm draws up to 30mA through its Terminal 3 Alarm Input and 45mA from its Terminal 1 Aux Power Input. 504-24 Power Supply + - 24 VDC 5 Amp Maximum + 504-24 Power Supply 20 21 22 23 24 Z9+ Z9- Z10+ Z10- 25 26 Outputs 3 through 10 can switch up to 50mA each at 12 VDC. This is sufficient for one 866 Module per indicating zone 3 through 10. 27 28 Zone 1 Output Relay 1 N/O Orange Zone 2 Output Relay 1 N/O Orange 10K EOL DMP Model 308 866 Module 1 AUX PWR 2 GND 3 Alarm In 4 Bell PWR In 5 Bell Out + 6 Bell Out 7 Bell Trouble 8 Bell Trouble S 18 Z7 GND Z8 Relay 1 and 2 Common Gray Normal/Silence Switch S Power Supply Trouble Contacts N/C 24 VDC 5 Amp Maximum 13 Z5 GND Z6 S = Supervised Circuit Normal/Silence Switch 24 VDC 5 Amp Maximum 12 Z3 GND Z4 S S S 866 Module 1 AUX PWR 2 GND 3 Alarm In 4 Bell PWR In 5 Bell Out + 6 Bell Out 7 Bell Trouble 8 Bell Trouble 11 J16 Panel Reset Relay Output 2 Use Model 305 -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 S Zone 1 Notification Circuit Module DMP Model 866 45mA @ 12 VDC K6 K7 Style W UL Listed, Polarized Notification Appliances 1K EOL Auxiliary Power Supply must be regulated, UL Listed for Fire Protective Signaling Service. Power Supplies must have battery backup. Power Supply Trouble Contacts N/C Normal/Silence Switch + 865 Module 1 AUX PWR 2 GND 3 Alarm In 4 Bell PWR In + 5 Bell PWR In 6 Bell Out A + 7 Bell Out A 8 Bell Out B + 9 Bell Out B 10 Bell Trouble 11 Bell Trouble Zone 2 Notification Circuit Module DMP Model 865 26mA @ 12 VDC Style y + UL Listed, Polarized Notification Appliances S S S S S S To additional notification circuit modules. Digital Monitoring Products 34 Each 865 Notification Appliance Circuit Module in alarm draws up to 59mA through its Terminal 3 Alarm Input and 26mA from its Terminal 1 Aux Power Input. The Auxiliary Power Supply and Notification Circuit Module trouble contact zone must be programmed as a Supervisory Type zone and must be selected for display in the keypad status list (See section 10.6 in the Programming Guide (LT-0196)). Note: If an auxiliary power supply is not used, terminals 3 and 4 can be jumpered together to supply Bell Power from the XR2400F panel. A maximum of 1.5 Amps as 12 VDC is available from terminal 5 of the XR2400F panel. XR2400F Installation Guide XR2400F Installation Guide GND Fault A Zone A GND Fault B A1 A1 A2 A2 Zone A GND Aux Power Zone B B1 B1 Zone B B2 B2 Model 869 Dual Style D Initiating Module DMP Model 869 25mA Standby, 75mA Alarm @ 12 VDC 1 AC 2 AC S S S S S S S S J3 3 +B J11 J10 J4 Tamper Header S 4 5 6 8 9 10 11 12 S 13 14 S 15 16 18 19 20 21 22 23 24 Z7 GND Z8 S = Supervised Circuit 17 Z5 GND Z6 Heat Detectors, manual pull stations, or any other UL Listed shorting device. Unlimited number of units. S 7 Z3 GND Z4 J2 Output Header J16 Panel Reset 25 26 27 28 Z9+ Z9- Z10+ Z10- XR2400F Command Processor™ Panel -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 DD, MPX Selection Headers J12 WIRING DIAGRAMS 34.3 Dual Style D Zone Module Installation Digital Monitoring Products 35 462N Network Interface Card WIRING DIAGRAMS J12 J11 XR2400F Command Processor™ Panel J3 J4 Tamper Header DD, MPX Selection Headers Answering Machine Bypass Relay Use Model 305 K2 K4 462N Network Interface Card 34.4 Remote Station Reversing Relay Connection Note: Output 3 must be programmed as a Fire Alarm Output and Output 4 must be programmed as a Fire Trouble Output. See Output Options section of the XR200/XR2400F Programming Guide (LT-0196). J2 Output Header All outputs must be located within the same room as the control panel. Ground Start Relay Use Model 305 Outputs 3 through 6 supply up to 50mA at 12 VDC. J2 Output Header Model 430 Output Harness J10 Relay Output 1 Use Model 305 AC AC 1 2 +B 3 K6 K7 -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 4 5 6 7 S 8 9 10 11 12 13 14 J16 Panel Reset Relay Output 2 Use Model 305 15 Z3 GND Z4 Z5 GND Z6 16 19 17 18 20 21 Z7 GND Z8 22 23 24 Z9+ Z9- Z10+ Z10- 25 26 27 28 S S S S = Supervised Circuit Black Red S + - + - + Black Red Up to 60 hours of battery standby time can be supplied using three or four 7.0Ah, sealed, Lead-Acid batteries. Four 7.0Ah batteries may be required based on total current draw of all devices connected to the panel. See section titled 24 VDC NAC Standby Battery Calculations. To connect four batteries to the XR2400F Command Processor™ Panel, use three Model 318 Battery Harnesses. - + - All modules must be installed in a UL Listed enclosure connected by no more than 20 feet of conduit. Reversing Relay Module Radionics Model D127 5mA Standby, 55mA Alarm @12 VDC Alternate Alarm Combo Alarm Auxiliary Power In + Signal Voltage In + To Remote Receiver - To Remote Receiver - Signal Voltage In EARTH GROUND GROUND GROUND Fire Alarm Output 3 White/Orange To Telephone Line Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings. Alternate Alarm Combo Alarm Auxiliary Power In + Signal Voltage In + To Remote Receiver - To Remote Receiver - Signal Voltage In EARTH GROUND GROUND GROUND Fire Trouble Output 4 White/Yellow To Telephone Line Reversing Relay Module Radionics Model D127 5mA Standby, 55mA Alarm @12 VDC Digital Monitoring Products 36 XR2400F Installation Guide WIRING DIAGRAMS J12 J11 XR2400F Command Processor™ Panel J3 J4 Tamper Header DD, MPX Selection Headers Answering Machine Bypass Relay Use Model 305 K2 K4 462N Network Interface Card 34.5 Supervised Remote Relay J2 Output Header All outputs must be located within the same room as the control panel. Ground Start Relay Use Model 305 Model 430 Output Harness J2 Output Header J10 Relay Output 1 Use Model 305 AC AC +B 1 2 3 K6 K7 -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 4 5 6 7 8 9 10 S 11 12 13 14 J16 Panel Reset Relay Output 2 Use Model 305 15 Z3 GND Z4 Z5 GND Z6 16 19 17 18 20 21 Z7 GND Z8 22 24 25 26 27 28 S S = Supervised Circuit S 23 Z9+ Z9- Z10+ Z10- S DPDT Relay Use Model ASRB-1 from Advanced Signaling. 30mA coil operating current at 12 VDC. Normally Open contacts will close on alarm. Normally Closed contacts will Open on alarm. Remote DPDT Relay DMP Part #DI-001 Rectifier (1N4001 diode) in series with input from Model 866 Module terminal 6. The zone connected to the Bell Trouble contacts on the 866 Notification Circuit Module must be programmed as a Supervisory Type zone and selecetd for display in the Status List. See the XR200/XR2400F Programming Guide (LT-0196). 10K EOL Resistor DMP Model 308 Wiring between the 866 Module and the DPDT Relay is supervised against open, shorts, and grounds. Any of these trouble conditions will cause the 866 Module's Bell Trouble contacts to open. Notification Circuit Module DMP Model 866 45mA @12 VDC The 866 Module must be installed in the panel enclosure or in a 340FC, 349, or 350 Enclosure connected by no more than 20 feet of conduit. Normal/Silence Switch 866 Module 1 2 3 4 5 6 7 8 XR2400F Installation Guide AUX PWR GND Alarm In Bell PWR In Bell Out + Bell Out Bell Trouble Bell Trouble 1K EOL Digital Monitoring Products 37 WIRING DIAGRAMS 34.6 Cellular Backup Installation for Derived Channel Burglary Auxiliary Power Supply The Secure-Com Cellular System must be connected to a separate power supply. Use only for supplementary (backup communication). 893A Cellular Transceiver Cellular Data Interface J3 XR2400F Command Processor Phone Jack Connector DCX Systems STU-2Z J6 Telco Jack Output Header J2 All outputs must be connected to devices located within the same room as the panel. 1 2 3 4 5 6 J10 K6 N/O Common N/O K7 Use EOL Termination Assembly P/N 21024-0003 (590 Ohm 1/2 W Resistor) Common Command Processor Reset J16 AC Auxiliary Power Supply must be regulated, UL Listed for Fire Protective Signaling Service. Power Supplies must have battery backup. 1 AC +B -B BELL GND RED YEL GRN BLK 2 3 4 5 6 7 8 9 10 S SM K G ND 11 12 Z1 GND Z2 Z3 GND Z4 Z5 GND Z6 Z7 GND Z8 Z9 + Z9 - 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Z10 + Z10 27 28 S S Panel Auxiliary Power - Terminal 7 S = Supervised Circuit Panel Common - Terminal 10 Supervisory Zone Input - Terminal 13 Note 1 Note 1 S S S S Note 1: Use EOL Termination Assembly P/N 21024-0001 (2.2k Ohm 1/2 W Resistor). Digital Monitoring Products 38 XR2400F Installation Guide WIRING DIAGRAMS 34.7 LX-Bus™ Module Connection LX-Bus Expansion Interface Card DMP Models 462N, 462P, 472, or 481 Model 867 Notification Module Normal/Silence Switch Ground Fault LED Bell Trouble LED 12 or 24 VDC Bell Power Supply 10K EOL Resistor DMP Model 308 + - 1 Bell In + 12 or 24 VDC 2 Bell In 3 Bell Out + UL Listed, Polarized Notification Devices 4 Bell Out 5 Bell Trouble 6 Bell Trouble Each LX-Bus Module must have its own independent address ranging from 00 to 99. A Supervisory zone must be programmed into the XR2400F to properly supervise each module. S S S S 7 PWR Mon. 8 Mon. RTN Bell Relay Address Supervisory Address ONES Bell Ring Style TENS ONES Power Supply Monitor LED Data LED Red Yellow To additional LX-Bus Modules Green Black S S S S S Connect to panel Supervisory zone TENS LX-Bus™ Wiring = Supervised Circuit Optional LED wiring 50mA at 50 VDC resistive Relay 3 S Relay 1 S S Relay 2 Open Collector Annunciator Outputs S Relay 4 Form C Contacts Typical Normally Closed Common Normally Open Model 716 Output Expander Module 7m at 12 VDC Optional LED wiring 50mA at 50 VDC resistive Model 717 Graphic Annunciator Module 10m at 12 VDC XR2400F Installation Guide Digital Monitoring Products 39 WIRING DIAGRAMS 34.8 Second LX-Bus™ with Auxiliary Power Supply LX-Bus Expansion Cards: DMP Models 481, 462N, 462P, and 472 Interface Cards J11 J4 Tamper Header DD, MPX Selection Headers 1 XR2400F Command Processor™ Panel 2 3 4 5 462N Network Interface Card J12 J3 481 462N Answering Machine Bypass Relay Use Model 305 K2 K4 Ground Start Relay Use Model 305 460 Interface Adaptor Card B J2 Output Header J10 Relay Output 1 Use Model 305 AC AC +B 1 2 3 K6 K7 -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 4 5 6 7 8 9 10 11 12 13 14 J16 Panel Reset Relay Output 2 Use Model 305 15 Z3 GND Z4 Z5 GND Z6 16 19 17 18 20 Connect the red wire to Smoke Output (terminal 11). S 21 Z7 GND Z8 22 23 24 Do not connect the red wire between the Interface Card and the first device. Z9+ Z9- Z10+ Z10- 25 26 27 28 LX-Bus 1 = 521LX Addressable Smoke Detector LX-Bus 2 100 zones on LX-Bus 1, Numbered 100 to 199. S S S S S Black Green Yellow Red S Black Green Yellow Red S 100 zones on LX-Bus 2, Numbered 200 to 299. S S S S 710 S Refer to LT-0310 for more information about the 710 Bus Splitter/Repeater Module. Black Green Yellow Red N/O C N/C S Digital Monitoring Products 40 S Black Green Yellow Red S Black Green Yellow Red 716 Program the 716 Output Expander Module as Sensor Reset Output. DMP 505-12 XR2400F Installation Guide XR2400F Installation Guide AUX PWR GND Alarm In Bell PWR In Bell Out + Bell Out Bell Trouble Bell Trouble 1 2 3 4 5 6 7 8 AUX PWR GND Alarm In Bell PWR In Bell Out + Bell Out Bell Trouble Bell Trouble 866 Module Normal/Silence Switch Notification Circuit Module DMP Model 866 45mA @12 VDC 1 2 3 4 5 6 7 8 866 Module Normal/Silence Switch Notification Circuit Module DMP Model 866 45mA @12 VDC 1K EOL S 1K EOL S Style W 10K EOL DMP Model 308 Style W - + - + 10K EOL DMP Model 308 3 2 1 J11 J10 4 5 6 S 8 9 S 10 11 12 13 S S S 14 AC Green LED AC AC DC Red LED + Bat - 24 VDC 4 Amp S 15 504-24 Power Supply 7 S S 17 S 18 19 21 22 23 24 Z7 GND Z8 25 26 27 28 Z9+ Z9- Z10+ Z10- J16 Panel Reset 462N Network Interface Card Power Supply Trouble Contacts N/C NC C NO NC C NO + DC - The Power Supply and Notification Circuit Module trouble contact zone must be programmed as a Supervisory Type zone and must be selected for display in the keypad status list (See section 10.6 in the Programming Guide (LT-0196)). 20 Z5 GND Z6 AC TRBL BATT TRBL S 16 Z3 GND Z4 J2 Output Header This diagram illustrates an example configuration that would allow strobes to operate after the horns or bells are silenced at the keypad. To stop the strobes in this configuration, perform a Sensor Reset from the User Menu. XR2400F Command Processor™ Panel -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 J12 Horns or Bells +B AC AC J3 Auxiliary Power Supply must be regulated, UL Listed for Fire Protective Signaling Service. Power Supply must have battery backup. Strobes S = Supervised Circuit WIRING DIAGRAMS 34.9 Multiple NotiÞcation Circuits with Strobes and Bells Digital Monitoring Products 41 OPERATING INSTRUCTIONS XR2400F Addressable Fire Alarm Control Panel NORMAL STANDBY CONDITION When the system is in the normal standby condition, the display shows either the time of day or a blank display. ALARM CONDITION When the system is in an alarm condition, the display shows the alarmed zone name(s) followed by an alarm display. Keyswitch operation In order to use the four function keys, the keyswitch must be turned to the enable position. ALARM SILENCE To silence the alarm while the bell or siren is sounding, press the key labeled “Silence” or enter your code number and press the COMMAND key. This silences the alarm but does not cancel any alarm reports to the central station. RESETTING DETECTORS To reset a smoke or other detector, press the key labeled “Reset” or enter the User Menu by pressing the COMMAND key until MENU? NO YES appears in the display. Press the top row key under YES. The display shows ENTER CODE: - . Enter your code number and press COMMAND. The display now shows ALARM SILENCE?. Press the COMMAND key until SENSOR RESET? appears in the display. Press any top row key. TROUBLE CONDITION When a device is in a trouble condition, the keyboard tones and displays the zone or device name followed by TRBL. Press any top row key to silence. SYSTEM TESTING You should test the security system periodically to ensure proper operation. You can do this by pressing the key labeled “Test” or through a function in the User Menu. After entering the User Menu, press the COMMAND key until SYSTEM TEST? displays. Press any top row key. The system bell, battery, and communication to the central station system is then tested. ALARM SERVICE If service is required for this system, please contact: Company ________________________________________________________ Address _________________________________________________________ Telephone _______________________________________________________ The operating instructions above should be attached to the front, or framed and located adjacent to, the Fire Alarm Control Panel or a Remote Fire Command Center. LT-0554 (4/04) © 2004 Digital Monitoring Products, Inc. 800-641-4282 INTRUSION • FIRE • ACCESS • NETWORKS www.dmp.com 2500 North Partnership Boulevard Made in the USA Springfield, Missouri 65803-8877