addendum number 1 - Lochridge Priest

advertisement
Baylor BRIC Olafsen/Blair Laboratory Buildout
Addendum No. 1
Perkins+Will
185162.000
February 05, 2016
February 05, 2016
BRIC Olafsen/Blair Laboratory Buildout out
– Addendum 1
Perkins+Will Project No.: 185162.000
________________________________________________________________
ADDENDUM NUMBER 1
________________________________________________________________
Bidders are hereby notified of the following changes/clarifications in the Project Manual and Drawings,
and are requested to acknowledge receipt of the Addendum in the space provided on the Bid Form.
DRAWINGS
Revised Drawings: The following revised Drawings are reissued herewith:




E00-10 ELECTRICAL ONE LINE DIAGRAM
E01-02 DEMOLITION ELECTRICAL PLAN LEVEL 02
E02-02 RENOVATION POWER PLAN LEVEL 02
E03-02 RENOVATION LIGHTING PLAN LEVEL 02
Submitted by:
Ed Cordes, AIA
Principal
Enclosures
Copies to Baylor University for distribution to all recipients of Bidding Documents
ADDENDUM NO. 1
A1-1
5
4
3
2
1
GENERAL NOTES - DEMO E0102
TO EXISTING SOURCE
D
2HDPC (EXISTING)
EXISTING
1SHDPC PARTIAL
800A, 480Y/277V, 3PH, 4W+GND, 65 KAIC
225A, 480Y/277V, 3PH, 4W+GND, 65 KAIC
A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO WORK.
B. BRANCH CIRCUIT CONDUCTORS AND CONDUIT NOT TO BE
RE-UTILIZED SHALL BE REMOVED BACK TO THE
RESPECTIVE PANELBOARD.
C. ALL LIGHTING FIXTURES TO BE DEMOLISHED MAY NOT BE
SHOWN ON THIS DRAWING. THE ELECTRICAL
CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL
EQUIPMENT, LIGHT FIXTURES, DEVICES, CONDUIT, AND
BRANCH CIRCUIT CONDUCTORS TO BE REMOVED AND
INCLUDE IN BID.
D. EXISTING WIRING DEVICES AND OUTLET BOXES IN
DEMOLISHED WALLS AND/OR NOT BEING REUTILIZED IN
THE DEMOLITION AREAS SHALL BE REMOVED AND
PATCHED. COORDINATE ALL REQUIREMENTS WITH THE
ARCHITECT.
800A
3P
LSIG
500A
3P
LSIG
40A
3P
40A
3P
15A
3P
15A
3P
125A
2P
1001 McKinney
Suite 1300
Houston, TX 77002
t 713.366.4000
f 713.528.3339
www.perkinswill.com
CONSULTANTS
MEP
SHAH SMITH & ASSOCIATES
1946 SOUTH I-35 SUITE 305, AUSTIN, TX 78704
OWNER
D
BAYLOR UNIVERSITY
101 BAGBY AVENUE, WACO, TEXAS 76706
100A
3P
3-100A/3P
EQUIPPED
SPACES
NEUTRAL
GROUND
#2 GND,
3/4"C
2TC1
225KVA
480V-208Y/120V
3PH, 4W
K-13 RATED
3#12
#12G
3/4"C
3#8
#10G
3/4"C
60A
3P
40AF
2TC10
2HC1
3-3"C EA.W/
3-350
2-350 NEUTRAL
1#2 GND
3#12
#12G
3/4"C
1.5
EUH2-5
EXISTING
EUH2-6
EXISTING
FCU-2-1
EXISTING
37.5KVA
480240/120V
#6 GND,
3/4"C
1
3#8
#10G
3/4"C
3#8
#10G
3/4"C
4-#2
1-#8G
1 1/4"C
2#2,
#6G,
1 1/4"C
60A
3P
40AF
1
EXISTING
3#12
#12G
3/4"C
MECHANICAL
PENTHOUSE
3#3/0,
#6G,
2"C
3#12
#12G
3/4"C
3SHC1
1
200A
3P
200AF
1.5
FCU-2-2
EXISTING
2
3#3/0,
#6G,
2"C
NO SCALE
Tx. Registration # F-2113
C
200A
NEW
AT
E O F TEX
A
S
ST
C
1SHDPC FIRST FLOOR STANDBY ONE
LINE DIAGRAM AREA C BLAIR
DOUGLAS B. BELISLE
PR
80083
LIC
D
ENSE
ES
GI
S IO
NA L E N
OF
2LDPC (EXISTING)
ADDENDUM #01 02.05.2016
2LC10
800A, 208Y/120V, 3PH, 4W+GND, 22 KAIC
800A
3P
LSIG
100A
3P
100A
3P
100A
3P
100A
3P
100A
3P
100A
3P
100A
3P
100A
3P
100A
3P
100A
3P
SPD
2-100A/3P
EQUIPPED
SPACES
ER
4#1/0
#6G
2"C
3#8
#10G
3/4"C
NE
2-2"C EA.W/
3-#4/0
1#2GND
2/5/2016
PROJECT
BRIC OLAFSEN/BLAIR
LABORATORY
BUILDOUT
100 RESEARCH PKWY.
WACO, TX 76704
NEUTRAL
GROUND
4#3
#8G
1 1/4"C
Baylor University
B
1311 S 5TH STREET
WACO, TX 76798
B
EXISTING
2LC1
EXISTING
EXISTING
2LC2
2LC3
EXISTING
2LC4
EXISTING
EXISTING
2LC5
2LC6
EXISTING
2LC7
EXISTING
2LC8
4#3
#8G
1 1/4"C
EXISTING
KEYPLAN
2LC8
NEW
C:\Users\mhernandez\Documents\1111-053-01_Elec_R15_mhernandez.rvt
1
2LC11
2HDPC SECOND FLOOR ONE LINE DIAGRAM AREA B2 BLAIR &
OLASFEN LABS
ISSUE CHART
NO SCALE
ADDENDUM #1
ISSUE
Job Number
A
A
Drawn
Checked
Approved
2/5/16
Date 5
DATE
185143.000
Author
BDM
Approver
TITLE
ELECTRICAL ONE LINE
DIAGRAM
SHEET NUMBER
ELECTRICAL LEGEND
2/5/2016 3:30:19 PM
1
MARK
EXSTING WORK SHOWN LIGHT
NEW WORK SHOWN BOLD
5
4
3
2
1
E00-10
5
4
3
2
1
GENERAL NOTES - DEMO E0102
34
35
36
37
37.1
37.2
37.3
D
38
1
39
2
1
40
A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO WORK.
B. BRANCH CIRCUIT CONDUCTORS AND CONDUIT NOT TO BE
RE-UTILIZED SHALL BE REMOVED BACK TO THE
RESPECTIVE PANELBOARD.
C. ALL LIGHTING FIXTURES TO BE DEMOLISHED MAY NOT BE
SHOWN ON THIS DRAWING. THE ELECTRICAL
CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL
EQUIPMENT, LIGHT FIXTURES, DEVICES, CONDUIT, AND
BRANCH CIRCUIT CONDUCTORS TO BE REMOVED AND
INCLUDE IN BID.
40.1
F
1
S
S
S
2
2
2
CONSULTANTS
MEP
SHAH SMITH & ASSOCIATES
1946 SOUTH I-35 SUITE 305, AUSTIN, TX 78704
D. EXISTING WIRING DEVICES AND OUTLET BOXES IN
DEMOLISHED WALLS AND/OR NOT BEING REUTILIZED IN
THE DEMOLITION AREAS SHALL BE REMOVED AND
PATCHED. COORDINATE ALL REQUIREMENTS WITH THE
ARCHITECT.
A
1
1001 McKinney
Suite 1300
Houston, TX 77002
t 713.366.4000
f 713.528.3339
www.perkinswill.com
OWNER
D
BAYLOR UNIVERSITY
101 BAGBY AVENUE, WACO, TEXAS 76706
SCOPE OF WORK
KEYED NOTES - E0102
S
F
S
30
1
F
1/6
30
1
1
2
1
1
1
3
B
F
J
2
4
5
F
110
F
S
2
2
1
30
J
S
J
1
DEMOLISH LIGHT FIXTURE AND ASSOCIATED,
CONDUCTORS AND CONDUIT. BACK TO CLOSEST
JUNCTION BOX. CLEAN FIXTURE AND RETURN TO THE
OWNER.
DEMOLISH FIRE ALARM DEVICES BACK TO SOURCE. CLEAN
AND RETURN DEVICES BACK TO OWNER.
EXISTING WALL TO BE RELOCATED. RECEPTACLES TO BE
RELOCATED MOVED TO NEW WALL SEE ARCH PLANS FOR
LOCATION. CONTRACTOR TO RE-USED EXISTING CIRCUIT.
DASHED LINE REPRESENTS SCOPE OF WORK.
EXISTING FCU-6 TO BE RELOCATED. CONTRACTOR SHALL
DISCONNECT AND RECONNECT CONDUCTORS TO NEW
LOCATIONS. PROVIDE NECESSARY CONDUIT AND
ACCESSORIES AS REQUIRED FOR FCU.
1
J
C
1
1
S
2
F
S
1
Tx. Registration # F-2113
C
1
AT
E O F TEX
A
S
2
ST
C
2
S
F
15
S
F
S
15
15
V
15
1
15
S
D
1
V
S
FCU-6
SCOPE OF WORK
S
S
1.5
1.5
3
S
4
5
F?
F?
S
S
NE
4
ADDENDUM #01 02.05.2016
S
80083
LIC
D
ENSE
ES
GI
S IO
NA L E N
OF
F
F
F
PR
S
15
ER
DOUGLAS B. BELISLE
2/5/2016
PROJECT
BRIC OLAFSEN/BLAIR
LABORATORY
BUILDOUT
100 RESEARCH PKWY.
WACO, TX 76704
Baylor University
B
1
1311 S 5TH STREET
WACO, TX 76798
B
LEVEL 02 DEMO ELECTRICAL PLAN BLAIR & OLAFSEN LABS
KEYPLAN
1/8" = 1'-0"
2/5/2016 3:27:28 PM
C:\Users\mhernandez\Documents\1111-053-01_Elec_R15_mhernandez.rvt
ISSUE CHART
1
ADDENDUM #1
MARK
ISSUE
Job Number
A
A
Date 5
2/5/16
DATE
185143.000
Author
Drawn
BDM
Checked
Approved
Approver
TITLE
DEMOLITION
ELECTRICAL PLAN
LEVEL 02
ELECTRICAL LEGEND
EXSTING WORK SHOWN LIGHT
SHEET NUMBER
NEW WORK SHOWN BOLD
0'
1/8" = 1'-0"
5
4
3
2
1
8'
16'
E01-02
5
4
3
2
1
GENERAL NOTES - POWER
KEYED NOTES - E0202
1
2
2LC10-11
J
J
2LC10-9
5
2LC10-19,21
2LC10-7
L630R FOR LASER
FUMEHOOD
J
J
S
CB-E2-07-B
LE-2-07
PC
4
M
4
2LC10-2
2LC10-3
5
J
2LC10-23
2LC10-16,18
PURGE GAS GEN
2LC10-15
1
J
CB-E2-08-B
CB-E2-07-A
OLAFSEN LAB
227.07
2LC10-4,6
MEP
SHAH SMITH & ASSOCIATES
1946 SOUTH I-35 SUITE 305, AUSTIN, TX 78704
OWNER
D
BAYLOR UNIVERSITY
101 BAGBY AVENUE, WACO, TEXAS 76706
2
J
2LC11-11
+84"
2LC10-8,10
2
2LC10-1
3
2LC11-7
M 4
LS-2-07
CB-E2-28-C
+84"
CB-E2-08-D
T e
cto
i g
n
yri h
p
o
C
7
0
t2
VV-E2-28
CB-E2-07-C
2LC10
4
LS-2-08
M
S
S
J
M
CB-E2-08-C
2LC10-13
J
4
J
+84"
2LC11-3
2LC11-17
4
2LC11-1
2LC11
2SLC1-3
2LC10-17
CB-E2-28-D
S
J
S
J
CONSULTANTS
2LC11-5
CB-E2-08-A
GE-2-07
1
BLAIR LAB
227.09
2LC11-9
1
CB-E2-07-D
CB-E2-28-B
6
J
2LC10-12,14
CB-E2-28-A
M
D
3
2LC10-5
1001 McKinney
Suite 1300
Houston, TX 77002
t 713.366.4000
f 713.528.3339
www.perkinswill.com
A. SEE SHEET 1-E00-01 FOR ELECTRICAL LEGEND AND
ABBREVIATIONS.
B. FIELD VERIFY EXISTING CONDITIONS PRIOR TO WORK.
C. ALL RECEPTACLES ARE MOUNTED 18", UON. VERIFY
HEIGHT AND ALIGNMENT OF DEVICES WITH ARCH
DRAWINGS. COORDINATE OUTLET/RECEPTACLE
LOCATIONS WITH MILLWORK, CASEWORK, ETC.
D. LOCATE ALL LOCAL DISCONNECT SWITCHES FOR
MECHANICAL EQUIOPMENT ADJACENT TO, BUT SEPARATE
FROM, EQUIPMENT SERVED, PROVIDE
SECURELY-ANCHORED METAL FRAMING PER SECTION 26
05 25.
E. UPDATE PANELBOARD SCHEDULES AT COMPLETION OF
PROJECT TO REFLECT FINAL CIRCUIT NUMBERS AND
DESCRIPTIONS.
F. REFERENCE ARCHITECTURAL PLANS FOR ROUGH-IN
LOCATIONS OF DATA OUTLETS.
JUNCTION BOX FOR POWER CONNECTION TO MODULAR
FURNITURE VIA POWER POLE. COORDINATE POWER POLE
LOCATION WITH FURNITURE SUPPLIER PRIOR TO
ROUGH-IN.
JUNCTION BOX FOR POWER CONNECTION TO OPTICS
RACK. COORDINATE POWER LOCATION WITH EQUIPMENT
SUPPLIER PRIOR TO ROUGH-IN.
PROVIDE A POKE-THROUGH FLOOR BOX LEGRAND
#8ATCBK. COORDINATE FINISH WITH ARCHITECT.
COORDINATE A/V AND TELECOM REQUIREMENTS WITH
OWNER PIOR TO ORDERING.
PROVIDE A MOTOR RATED SNAP SWITCH. COORDINATE
WITH DIV 23.
PROVIDE NEMA L6-30R COORDINATE EXACT
CONFIGURATION WITH OWNER PRIOR TO ROUGH-IN.
SUSPEND FROM STRUCTURE ABOVE.
2LC11-13
2LC10-20,22
2LC11-15
5
2LC1-14
CB-E2-26-A
CB-E2-26-B
CB-E2-26-C
Tx. Registration # F-2113
C
ST
ADDENDUM #01 02.05.2016
VV-E2-27
36
36
GRAD STUDENT
227
S
M
CB-E2-27-A
35
35
4
J
2SLC1-5
CB-E2-27-B
CB-E2-27-C
1
D
2SLC1
6
WORK ROOM
227.08
T
2LC1-16
2LC2
2/5/2016
ER
PROJECT
BRIC OLAFSEN/BLAIR
LABORATORY
BUILDOUT
100 RESEARCH PKWY.
WACO, TX 76704
2TC10
2LC1-1
2LC1-6
D
TO PANEL
2LC10 LAB
ROOM
2LC1
2LC1-4
80083
LIC
D
ENSE
ES
GI
S IO
NA L E N
OF
J
1
E O F TEX
A
NE
4
VV-E2-26
2LC1-12
AT
DOUGLAS B. BELISLE
PR
J
S
M
S
J
4
S
GE-E2-08
M
C
2LC2-1
2LC2-2
2LC1-8
2LC3
2ELC1
2LC2-8
2LC2-3
CB-E2-29-A
B
OFFICE
227.06
CB-E2-29-B
2EHC1
Baylor University
2LC2-6
2HC1
2TC1
CB-E2-29-C
1311 S 5TH STREET
WACO, TX 76798
B
T
OFFICE
227.04
EXISTING
OFFICE
A333
2LDPC
CB-E2-27-D
4 M
S
J
VV-E2-29
2HDPC
2SLC1-2,4 2SLC1-1
KEYPLAN
+42"
E
C:\Users\mhernandez\Documents\1111-053-01_Elec_R15_mhernandez.rvt
1
E
LEVEL 02 RENO POWER PLAN AREA B2 BLAIR & OLASFEN LABS
1/4" = 1'-0"
2
ENLARGED LEVEL 02 EXISTING ELEC RM B2
BLAIR & OLASFEN LABS
1/4" = 1'-0"
1
ADDENDUM #1
MARK
ISSUE
Job Number
A
A
Drawn
Checked
Approved
2/5/16
Date 5
DATE
185143.000
Author
BDM
Approver
TITLE
RENOVATION POWER
PLAN LEVEL 02
ELECTRICAL LEGEND
EXSTING WORK SHOWN LIGHT
NEW WORK SHOWN BOLD
SHEET NUMBER
0'
1/4" = 1'-0"
2/5/2016 3:27:31 PM
ISSUE CHART
5
4
3
2
1
4'
8'
E02-02
5
4
3
2
1
GENERAL NOTES - LIGHTING
EX
D
B
B d
a
B a
b
B
1
OS
c
B
2EHC1-7
OS
B
d
aOLAFSEN
BLAB b
a
B
227.07
1
1
OS
d c b a
S S S S
XL
EX
b
BLAIR LAB
227.09 1
OS
B
a
B
b
B
2LC10
OS
1001 McKinney
Suite 1300
Houston, TX 77002
t 713.366.4000
f 713.528.3339
www.perkinswill.com
CONSULTANTS
MEP
SHAH SMITH & ASSOCIATES
1946 SOUTH I-35 SUITE 305, AUSTIN, TX 78704
OWNER
D
OS
2HC1-23 B
1
B
a
B
101 BAGBY AVENUE, WACO, TEXAS 76706
KEYED NOTES - 1-E03-02
1
a
ba
SS
2LC11
BAYLOR UNIVERSITY
SCPOE OF WORK
T cC
ie g
tn
p
o
riy
7
0
t2
h
B c
A. SEE SHEET 1-E00-01 FOR ELECTRICAL LEGEND AND
ABBREVIATIONS.
B. FIELD VERIFY EXISTING CONDITIONS PRIOR TO WORK.
C. REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL
INFORMATION PERTAINING TO DEMOLITION AND EXISTING
CONDITIONS. USE EXISTING LIGHT FIXTURES WHERE
OWNER'S STOCK PERMITS, COORDINATE AVAILABLE
QUANTITIES WITH FACILITY SERVICES.
D. BRANCH CIRCUIT CONDUCTORS AND CONDUIT NOT TO BE
UTILIZED SHALL BE REMOVED BACK TO THE RESPECTIVE
PANELBOARD.
2
1
SWITCH EMERGENCY LIGHTING WITH NORMAL POWERED
LIGHTS AS INDICIATED, PROVIDE UL 924 RELAY
CONNECTED TO NORMAL AND EMERGENCY CIRCUITS.
REFER TO DETAIL E06-01 FOR ADDITIONAL INFORMATION.
CONNECT NEW LIGHT TO EXISTING LIGHT CIRCUIT IN
TELECOM ROOM.
LASER IN USE
EX
B
1
EX
XA
B
OS
OS
B
GRAD STUDENT
227
B
EX
1
OS
OS
B
B
1
S
S
A
OS
A
B
A
OFFICE OS
227.04
EXISTING
OFFICE
A333
EX
A
C
OFFICE
OS 227.06
OS
A
1
WORK ROOM
227.08
Tx. Registration # F-2113
C
A
XA
S
1
S
AT
E O F TEX
A
S
ST
S
1
OS
2/5/2016
ADDENDUM #01 02.05.2016
F4
OS
F4
FCU-6
SERVER ROOM
EXPANSION
PROJECT
BRIC OLAFSEN/BLAIR
LABORATORY
BUILDOUT
100 RESEARCH PKWY.
WACO, TX 76704
1
1
80083
LIC
D
ENSE
ES
GI
S IO
NA L E N
OF
OS
2
N8
N8
NE
N8
PR
N8
ER
DOUGLAS B. BELISLE
LEVEL 02 RENO LIGHTING PLAN AREA B2
BLAIR & OLASFEN LABS
1/8" = 1'-0"
Baylor University
B
1311 S 5TH STREET
WACO, TX 76798
B
KEYPLAN
LUMINAIRE SCHEDULE
TYPE
A
MANUFACTURER
AND CATALOG NUMBER
DESCRIPTION
CORELITE #R3-WN-2T8-1C/PRS-UNV-24-ST
2X4 FLUORESCENT, LOW PROFILE
HOUSING, 20 GAUGE COLD ROLLED
STEEL, MICRO PRISMATIC ACRYLIC LENS.
277
8' LONG PENDANT MOUNTED
DIRECT/INDIRECT FIXTURE WITH
PARABOLIC BAFFLE.
277
PMC
VOLTAGE
LAMPS
MOUNTING
(2) 32W T8
4100K
85 CRI
RECESSED
2-32WT8
4100K
85CRI
PER 4'
SECTION
2-F032WT8
4100K
85CRI
PENDANT
MAX
WATTS
62
PINNACLE
CORELITE #AP-WB-2T8-1C/PRS-UNV-AC48-ST-8'
B
PINNACLE
1
C:\Users\mhernandez\Documents\1111-053-01_Elec_R15_mhernandez.rvt
F4
2/5/2016 3:59:44 PM
LITE CONTROL
LITHONIA #AF232MVOLTWGAFPVWZHC36GEB10RS 4' HEAVTY DUTY INDUSTRIAL TURRET
LUMINAIRE 20% UPLIGHT, BAKED WHITE
COOPER
ENAMEL FINISH, CHAIN HANGERS, WIRE
GUARD
PHILIPS
LITHOINA #LQMPW1R120/277SW010
XL
EVENLITE
WALL MOUNTED SIGE DISPLAYING
LASER IN USE
277
120/277
124
CHAIN
HUNG
9'-0"AFF
62
LED
PROGRAM START
ELECTRONIC BALLAST,
<10% THD
COORDINATE MOUNTING
HEIGHT W/ ARCHITECT
ISSUE CHART
PROGRAM START
ELECTRONIC BALLAST,
<10% THD
COORDINATE MOUNTING
HEIGHT W/ ARCHITECT
ONE 2-LAMP
PROGRAMMED START
ELECTRONIC BALLAST
SWITCHED AS INDICATED
ON DRAWINGS
WALL
8'-0''
AFF
ISOLITE
REMARKS
1
DELRAY #SW64254-2-SDC-8
N8
A
8' LONG, SUSPENDED DIRECT/INDIRECT
FLUORESCENT FIXTURE WITH T5HO
LAMPS.
277
(4) 54W
T5HO
4100K
85 CRI
PENDANT
229
PROGRAMMED START
ELECTRONIC BALLAST,
<10% THD
1
ADDENDUM #1
MARK
ISSUE
Job Number
A
Drawn
Checked
Approved
Date 5
2/5/16
DATE
185143.000
Author
BDM
Approver
TITLE
ELECTRICAL LEGEND
EXSTING WORK SHOWN LIGHT
NEW WORK SHOWN BOLD
0'
1/8" = 1'-0"
5
4
3
2
1
8'
16'
RENOVATION
LIGHTING PLAN LEVEL
02
SHEET NUMBER
E03-02
Download