DZS 907-1 : 2015 ISC Edition1 Draft for Public Comment Zambian Standard ELECTRICITY DISTRIBUTION INFRASTRUCTURE - APPLICATION GUIDE Part 1: Construction (Design, Selection, Installation and Commissioning) This draft standard is for public enquiry only. It must not be used or referred to as a Zambian Standard ZAMBIA BUREAU OF STANDARDS DZS 907-1:2015 DATE OF PUBLICATION This Zambian Standard has been published under the authority of the Standards Council of the Zambia Bureau of Standards on ………………. ZAMBIA BUREAU OF STANDARDS The Zambia Bureau of Standards is the Statutory National Standards Body for Zambia established under an Act of Parliament, the Standards Act, Cap 416 of 1994 of the Laws of Zambia for the preparation and promulgation of Zambian Standards. REVISION OF ZAMBIAN STANDARDS Zambian Standards are revised, when necessary, by the issue of either amendments or of revised editions. It is important that users of Zambian Standards should ascertain that they are in possession of the latest amendments or editions. CONTRACT REQUIREMENTS A Zambian standard does not purport to include all the necessary provisions of a contract. Users of Zambian standards are responsible for their correct application. TECHNICAL COMMITTEE RESPONSIBLE This Zambian Standard was prepared by the Technical Committee TC 5/7 on Electricity Distribution Infrastructure upon which the following organizations were represented: Copperbelt Energy Corporation Plc (CEC) Energy Regulation Board (ERB) Engineering Institution of Zambia (EIZ) Kansanshi Mining Company Plc (KMP) Konkola Copper Mines Plc (KCM) Lunsemfwa Hydro Power Company Plc (LHPC) Department of Energy, Ministry of Mines, Energy and Water Development Rural Electrification Authority (REA) University of Zambia (UNZA) Zambia Bureau of Standards (ZABS) ZESCO Limited Zambia Bureau of Standards Lechwe House Freedom Way South End P.O. Box 50259, Lusaka Email: zabs@zamnet.zm /infozabs@zamnet.zm website: www.zabs.org.zm i DZS 907-1:2015 CONTENTS FOREWORD ...............................................................................................................................................v INTRODUCTION .......................................................................................................................................1 1. SCOPE ...............................................................................................................................................2 2. NORMATIVE REFERENCES .......................................................................................................2 3. DEFINITIONS AND ABBREVIATIONS ......................................................................................3 4. 5. 3.1 Definitions ................................................................................................................................3 3.2 Abbreviations and Acronyms ...................................................................................................5 NETWORK PLANNING AND DESIGN .......................................................................................6 4.1 General......................................................................................................................................6 4.2 Substation Equipment and Component Sizing .........................................................................8 SUBSTATIONS.................................................................................................................................9 5.1 Transformers .............................................................................................................................9 5.2 Switchgear ..............................................................................................................................15 5.3 Busbars ...................................................................................................................................43 5.4 Controlgear .............................................................................................................................46 Equipment .......................................................................................................................................67 5.5 6. 7. Auxiliary Equipment ..............................................................................................................67 CABLES AND CONDUCTORS....................................................................................................68 6.1. General....................................................................................................................................68 6.2. Fault currents and short-circuit ratings of cables ....................................................................68 OVERHEAD DISTRIBUTION LINES ........................................................................................72 7.1 General....................................................................................................................................72 7.2 System Voltages .....................................................................................................................72 7.3 Conductors ..............................................................................................................................72 7.4 Support Structures ..................................................................................................................74 7.5 Insulators.................................................................................................................................77 7.6 Aerial Guard Earth Wire .........................................................................................................80 7.7 Anti-climbs .............................................................................................................................80 ii DZS 907-1:2015 7.8 Cradle Catch nets ....................................................................................................................80 7.9 Red Balls.................................................................................................................................80 7.10 Goal posts ...............................................................................................................................81 7.11 Pole Mounted Equipment .......................................................................................................81 8. 9. 10. UNDERGROUND DISTRIBUTION SYSTEMS.........................................................................85 8.1. Components ............................................................................................................................85 8.2. All joints shall comply with IEEE 404, IEC 60840 and SANS 10198-9 to 11. Trenches: ...85 8.3. Cable Trays/Racks ..................................................................................................................86 8.4. Cable Route Markers ..............................................................................................................86 EARTHING AND LIGHTNING PROTECTION REQUIREMENTS .....................................87 9.1. General....................................................................................................................................87 9.2. Earthing of Equipment ............................................................................................................87 9.3. Lightning protection ...............................................................................................................94 9.4. Insulation Co-ordination .........................................................................................................94 VOLTAGE REGULATORS ..........................................................................................................95 10.1. General....................................................................................................................................95 10.2. Secondary Transformer Voltage Regulation ..........................................................................95 11. CAPACITORS ................................................................................................................................96 11.1. Power Capacitors ....................................................................................................................96 11.2. Shunt Capacitors .....................................................................................................................96 11.3. Capacitor Banks ......................................................................................................................96 12. FEEDER PILLAR ........................................................................................................................102 12.1. General..................................................................................................................................102 12.2. Specification for Feeder Pillars.............................................................................................102 13. SUBSTATION CONCRETE WORKS .......................................................................................104 13.1 General..................................................................................................................................104 13.2 Substation equipment plinths ................................................................................................104 13.3 Oil containment tanks ...........................................................................................................105 14. WAYLEAVE .................................................................................................................................106 14.1. General Requirements...........................................................................................................106 iii DZS 907-1:2015 14.2. Specific requirements ...........................................................................................................106 14.3. Prevention against Animal diseases ......................................................................................108 15. LONG-TERM PRESERVATION OF SUPPORT STRUCTURES FOR DISTRIBUTION INFRASTRUCTURE ...................................................................................................................109 15.1 Painting .................................................................................................................................109 15.2 Concrete Poles ......................................................................................................................109 15.3 Steel Poles.............................................................................................................................109 15.4 Steel Structures for Outdoor Substations ..............................................................................109 APPENDICES .........................................................................................................................................110 APPENDIX 1: ORDER INFORMATION REQUIRED WITH TRANSFORMER ENQUIRY AND 110 iv DZS 907-1:2015 FOREWORD The Zambia Bureau of Standards (ZABS) is the Statutory Organization established by an Act of Parliament. ZABS is responsible for the preparation of national standards through its various technical committees composed of representation from government departments, the industry, academia, regulators, consumer associations and non- governmental organizations. This National standard has been prepared in accordance with the procedures of the ZABS. All users should ensure that they have the latest edition of this publication as standards are revised from time to time. No liability shall attach to ZABS or its Director, employees, servants or agents including individual experts and members of its technical committees for any personal injury, property damage or other damages of any nature whatsoever, whether direct or indirect, or for costs (Including legal fees) and expenses arising out of the publication, use of, or reliance upon this ZABS publication or any other ZABS publication. Compliance with a Zambian standard does not of itself confer immunity from legal obligations. DZS 907: 2015 was prepared by the TC 5/7 on Electricity Supply v ZAMBIAN STANDARD ELECTRICITY DISTRIBUTION INFRASTRUCTURE – Application Guide Part 1: Construction (Design, Selection, Installation and Commissioning) INTRODUCTION This standard provides a set of guidelines for the design, construction and installation and commissioning of electricity distribution infrastructure within Zambia. These guidelines are to be applied to all publicly and privately owned electricity distribution infrastructure, so as to ensure safety and quality electricity distribution within Zambia. Electricity distribution infrastructure needs to be planned, designed, constructed, maintained and operated in accordance with the requirements, standards and guidelines provided in the approved standards document to achieve the set objectives of equipment reliability, safety, providing quality service to the consumer and meeting the environmental protection requirements. The quality and reliability of the installed infrastructure is of paramount importance and compliance to set standards will help achieve the objective of reliability and security of supply, safe operation and safety of the consumer and the general public. Therefore, the focus of this standard will be on quality of electrical components and other accessories and requirements for installations of these components in the distribution system. The standards are intended to ensure that: components are able to be interchanged without any deviation; there is minimum interruption on the service delivery to the consumer and that the utilities‟ expenditure on electrical components replacements is reduced due to increased life of the components. This standard is expected to achieve the following: i). ii). iii). iv). v). vi). vii). viii). ix). Electrical equipment design and construction in accordance with good engineering practices; High operational reliability owing to good quality material and installation; Reduction on maintenance costs; Improvement of the quality of service delivery to consumer; Promote product upgrade and technological innovation in the electricity supply industry in Zambia; Control on the quality of electrical products on the market; Operational safety; Electrical equipment designed for use within certain voltage limits that is safe to use; and, Environmental protection. 1 1. SCOPE This part of DZS 907 covers the planning, design, construction, installation, and commissioning of ac distribution networks ranging from three phase 33,000 volts to 220 volts a.c. single phase. It is a general guide to good technical practice for economical overhead and underground distribution networks in Zambia. This standard excludes power supply to mining underground power distribution and other zoned and categorized areas e.g. explosive environments, solvent extraction plants, military installations and flammable environments. 2. NORMATIVE REFERENCES The following standards contain provisions which, through reference in this text, constitute provisions of this part of DZS 907. All standards are subject to revision and since any reference to a standard is deemed to be a reference to the latest edition of that standard party to agreements based on this part of DZS 907 are encouraged to take steps to ensure the use of the most recent editions of the standards indicated below. Information on currently valid national and international standards can be obtained from Zambia Bureau of Standards. IEV 441-18-09 IEV 441-18-081 IEV 441-18-111 IEV 441-18-131 IEC 60 IEC60812 IEC 60865 IEC 60909 IEC 60050-195, 195-06-05 IEC 61024 IEC 62262 – IK Code IEC 62305 IP Code - IEC 60529 IEC 61643 IEC 60071, IEC60085, IEC 60283, IEC 60296, IEC 60815, IEC 61211, IEC61467 IEC 60801- EMI & RFI, EMC-IEC 61000 IEC 60947, IEC 61363 IEC 61892 IEC 61439 2 IEC 62271 IEC 62357, IEC 61850 ZS387 IEEE C57.12.00 - Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers ZS791- Wiring of Premises ZS 746-1 ZS 746-2 3. DEFINITIONS AND ABBREVIATIONS 3.1 Definitions 3.1.1 Bund wall: A wall/barrier of sufficient height constructed around fluid filled equipment to contain spillage of liquids.) 3.1.2 Busbar: a low-impedance conductor to which several electric circuits can be separately connected. 3.1.3 Controlgear: general term covering switching devices and their combination with measuring, protective and regulating equipment, also assemblies of associated control, such devices and equipment with associated interconnections, accessories, enclosures and supporting structures, intended in principle for the control of electric energy consuming equipment 3.1.4 Cross-arm: a pole that is used in a horizontal or near- horizontal position in a structure for the support of power distribution lines, but that is not intended to be used in contact with the ground 3.1.5 Cut-out base: The fixed part of a cut-out provided with the contacts and terminals. 3.1.6 Degree of protection: The extent of protection provided by an enclosure against access to hazardous parts, against. ingress of solid foreign objects and/or against ingress of water and verified by standardized test methods 3.1.7 Direct contact: Contact of persons or livestock with live parts. NOTE: This IEV definition is given for information. In this standard "direct contact" is replaced by "access to hazardous parts ". 3.1.8 Drop-out fuse-link assembly [cut-out]: An assembly that comprises all components that form a complete device intended to protect equipment or parts of a reticulation system (or both), in which the fuse-carrier automatically drops into a position that provides an isolating distance after the fuse has operated. NOTE: In this specification the term “cut-out” is often used in place of “drop-out fuse-link” assembly. 3.1.9 Enclosure: A part providing protection of equipment against certain external influences and, in any direction, protection against direct contact. 3 NOTE: This definition taken from the existing International Electro-technical Vocabulary (IEV) needs the following explanations under the scope of this standard: 1) Enclosures provide protection of persons or livestock against access to hazardous parts. 2) Barriers, shapes of openings or any other means - whether attached to the enclosure or formed by the enclosed equipment - suitable to prevent or limit the penetration of the specified test probes are considered as a part of the enclosure, except when they can be removed without the use of a key or tool. 3.1.10 Expulsion fuse: A fuse in which operation is accomplished by the expulsion of gases produced by the arc. [IEV 441-18-111] 3.1.11 Fuse element: That part of the fuse-link which is designed to melt under the action of a current that exceeds some definite value for a definite period of time. [IEV 441-18081] 3.1.12 Fuse-carrier: The movable part of a fuse-link assembly designed to carry a fuse-link. [IEV 441-18-131] 3.1.13 Fuse-link: The part of a fuse including the fuse element(s) intended to be replaced after the fuse has operated. [IEV 441-18-09] 3.1.14 Hazardous live part: A live part which, under certain conditions of external influences, can give an electric shock (see IEC 60050-195, 195-06-05). 3.1.15 Hazardous mechanical part :A moving part, other than a smooth rotating shaft, that is hazardous to touch 3.1.16 Hazardous part: A part that is hazardous to approach or touch 3.1.17 Insulator: That component of a cut-out base, which is intended to insulate the loadside and the source-side from each other and from earth and which is fitted with an insulator-fixing stem. 3.1.18 Insulator-fixing stem: A component for attaching the insulator to the mounting Lbracket. 3.1.19 IP Code: A coding system to indicate the degrees of protection provided by an enclosure against access to hazardous parts, ingress of solid foreign objects, ingress of water and to give additional information in connection with such protection 3.1.20 Lower contact: The load-side contact of a cut-out base, which also allows a removable fuse-carrier or solid-link to pivot. 3.1.21 Mounting L-bracket: A device used to facilitate the mounting of a cut-out on either a wooden cross-arm or a steel cross-arm. 3.1.22 Outdoor distribution cut-out: A drop-out vented expulsion fuse-link assembly or solid-link assembly, together with the associated components. 3.1.23 Rated fibre stress: stress in the wood from the applied load just before breaking 4 3.1.24 Solid-link assembly: An assembly that comprises all components that form a complete device intended to isolate equipment or parts of a reticulation system, or both, from the source of supply. 3.1.25 Solid-link: A component for use in place of a fuse-carrier, to effect a manual disconnection. 3.1.26 Spacer block: a piece of timber that is used as a spacer between poles and cross-arms in five- pole structures but that is not intended to be used in contact with the ground 3.1.27 Substation- An enclosed assemblage of equipment, e.g., switches, circuit breakers, buses, and transformers, under the control of qualified persons, through which electric energy is passed for the purpose of switching or modifying its characteristics to increase or decrease voltage or control frequency or other characteristics. 3.1.28 Switchgear: the combination of electrical disconnects switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. It is used both to deenergize equipment to allow work to be done and to clear faults downstream. 3.1.29 Treated/treatment: impregnated/impregnation with an acceptable preservative 3.1.30 Upper contact: The source-side spring-loaded contact of a cut-out base. 3.2 Abbreviations and Acronyms 3.2.1 ACSR: Aluminium Conductor Steel Reinforced 3.2.2 ONAN: Oil Natural Air Natural 3.2.3 ONAF: Oil Natural Air Forced 3.2.4 OFAF: Oil Forced Air Forced 3.2.5 OFWF: Oil Forced Water Forced 5 4. NETWORK PLANNING AND DESIGN 4.1 General The primary purpose of an electricity distribution network system is to meet the customer‟s demands for energy. Depending on the geographical location, the distribution network can be in the form of overhead lines or underground cables. The objective of planning for the distribution network is to ensure that the required power demand by the customers is met. However, to achieve this objective the designer of the network should take into account the technical performance of the network being designed and its associated costs so that the electricity distribution network is technically sound and cost effective. The factors influencing network design that need to be considered fall into the following three categories; a). Fixed parameters within which the electrical designer might have to work, include: i). Statutory requirements: ii). Existing services: iii). Environmental Impact Assessment with ZEMA, Environmental Protection and Pollution Act Land Acquisition Act Local Government Act Town and Country Planning Act Occupational Health and Safety Act 36 of 2010 Factories Act Cap 441 Electricity Act Energy Regulation Act Petroleum Act Mines and Minerals Act Water Resource Management Authority Act Zambezi River Authority Act Forestry Act Civil Aviation Act Zambia Wildlife Act Electricity Utilities Water Utilities and sewerage Information and Communication Technology service providers Road Development agency Local Authorities Oil pipeline Rail line Existing area layout: 6 iv). Nature of the terrain: v). Topographic Soil conductivity for earthing Soil bearing capacity for civil works Geographic location: vi). Local Authority Geological Survey Planning and Buildings Department ZAWA Proximity to sensitive infrastructures i.e. fuel storage tanks, storage magazines or other explosive materials Seismic Zones Lightening prone areas Existing infrastructures i.e. tall buildings, airport area Factors over which the designer has limited or no control, including: Consumer loads; Diversity; vii). Factors over which the designer should exercise control, including: b). Initial capital costs and life cycle costs; New area layout; Number and positioning of metering points; Cable and conductor sizes and types of cable and conductor; and, Number, sizes, locations and types of substation; The designer shall obtain supply characteristics at the supply points from the service provider i.e. Voltage drop and unbalance, within limits of design load, and all other parameters as prescribed in the Zambian Power Quality Standard ZS 387 NOTE: No design should be considered in isolation. The planner should take into account the relationship between the area to be supplied and adjacent supply areas, proposed future developments and environmental considerations. When applying the guidelines to individual schemes, it is necessary to take into account all local conditions and total life cycle cost (for example, capital outlay and the upgrading of operational and maintenance requirements). c). Climatic Conditions Some examples of the effects of climatic conditions on overhead lines are: i). ii). iii). iv). Ambient temperature and wind affect the sag of overhead conductors and their current-carrying capacity; Wind affects pole supports, stays and clearances; Lightning causes surge voltages to be induced into the network; and In cases where overhead lines are situated close to the coast, the combined effects 7 of pollution and high relative humidity on insulators have an adverse effect on the system. Salt fog can be corrosive on conductors with steel reinforcing if not adequately greased. 4.2 Substation Equipment and Component Sizing A substation is a part of an electrical generation, transmission and distribution system. Its primary purpose is to transform voltages from high to low, or the reverse, or perform any of several other important functions. All substation equipment and associated components shall be designed, constructed, installed and commissioned to meet the requirements as set out in this standard. The expected thermal, chemical, mechanical and environmental conditions shall be considered in the design of the equipment. Further, all equipment shall be designed to withstand the effects of normal, emergency and fault conditions expected during operation. The substation equipment specified in this standard include; transformers, switchgear (circuit breakers, busbars, fuses), control gear and substation auxiliary equipment (substation lighting, fire suppression systems and telemetry). The following safety considerations shall be taken into account in the planning, designing, construction, installation and commissioning of substations in accordance with the provisions of ZS 418 Parts 1 and 2: i). ii). iii). iv). v). Safety clearance Signage Fencing Personal Protective Equipment ( PPE) Substation Perimeter For other safety considerations refer to IEC 61558 on Safety of installations and IEC 61557 8 5. SUBSTATIONS 5.1 Transformers 5.1.1 General All distribution transformers shall comply with IEC 60076- Power Transformers – All Parts. In this standard, a transformer is an electrical device that transfers energy between two or more circuits through electromagnetic induction. The standard applies to three-phase and single- phase power transformers (including autotransformers) with the exception of certain categories of small and special transformers such as; a). b). c). d). e). f). g). single-phase transformers with rated power less than 1 kVA and three-phase transformers less than 5 kVA; instrument transformers; transformers for static convertors; traction transformers mounted on rolling stock; starting transformers; testing transformers; and welding transformers. It‟s recommended that an agreement shall be reached concerning alternative or additional technical solutions or procedures. Such agreement is to be made between the manufacturer and the purchaser, the matters should preferably be raised at an early stage and the agreements included in the contract specification. 5.1.2 General Design and Construction This part of the standard prescribes the specific technical requirements applicable to transformers. NOTE 1: For the exact limit and acceptable tolerance of a particular parameter, this specification is to be used in conjunction with the descriptions and the specifications of IEC 60076 Part 1, 2 and 3. 5.1.2.1 Service Conditions The service conditions for transformer shall be as specified in Table 5-1 below: Table 5-1: Service Conditions for Transformers S/N Service Condition 1. 2. 3. 4. 5. 6. 7. 8. 9. Altitude above mean sea level Maximum ambient temperature for design purpose Average ambient temperature for design purposes Minimum ambient temperature for design purposes Relative humidity maximum at 35oC Maximum wind speed Mean annual rain fall Maximum solar radiation Isokeraunic Level average 9 Specification 1400m 40oC 30oC -1oC 95% 40m/s 1065mm 1200 W/m2 130 days/year 5.1.2.2 Installation Power transformers shall be so installed that all energized parts are enclosed or guarded so as to limit the likelihood of inadvertent contact, or the energized parts shall be physically isolated. The case shall be effectively grounded or guarded. Oil-immersed transformers are to be hermetically sealed with integral filling. Oil in transformers is used as insulation and also serves as a cooling medium. The installation of liquid-filled transformers shall utilise one or more of methods highlighted below to minimise fire hazards. The method to be applied shall be according to the degree of the fire hazard. Recognised methods are the use of less flammable liquids, space separation, fire resistant barriers, automatic extinguishing systems, absorption beds, and enclosures. The amount and characteristics of liquid contained should be considered in the selection of space separation, fire-resistant barriers, automatic extinguishing systems, absorption beds, and enclosures that confine the liquid of a ruptured transformer tank, all of which are recognized as safeguards. i). Transformers and regulators 75 kVA and above containing an appreciable amount of flammable liquid and located indoors shall be installed in ventilated rooms or vaults separated from the balance of the building by fire walls. Doorways to the interior of the building shall be equipped with fire doors and shall have means of containing the liquid. ii). Transformers or regulators of the dry type or containing a nonflammable liquid or gas may be installed in a building without a fireproof enclosure. When installed in a building used for other than station purposes, the case or the enclosure shall be so designed that all energised parts are enclosed in the case that is effectively grounded. As an alternate, the entire unit may be enclosed so as to limit the likelihood of inadvertent contact by persons with any part of the case or wiring. When installed, the pressure-relief vent of a unit containing a non-biodegradable liquid shall be furnished with a means for absorbing toxic gases. iii). Transformers containing less flammable liquid may be installed in a supply station building in such a way as to minimize fire hazards. The amount of liquid contained, the type of electrical protection, and tank venting shall be considered in the selection of space separation from combustible materials or structures, liquid confinement, fireresistant barriers or enclosures, or extinguishing systems. 5.1.2.3 External Clearances External clearances shall be such that there will be no visible corona up to 1.1 pu system voltage. In addition, the minimum external clearances between live parts and live parts to ground shall not be less than that specified in ZS 418. 5.1.2.4 Identification The transformer must contain a nameplate reverted on the tank and clearly visible. The nameplate shall indicate: 10 The year of Manufacture The standard to which the unit is made Name of manufacturer Serial number Cooling type Vector Symbol Vector group diagram Winding configuration diagram Tap changer type (Onload/Offload) Number of Taps and nominal Tap Specific tap voltages Inscribed Tested Voltage percent impedance KVA rating Frequency Primary and Secondary Voltage at Nominal Maximum Secondary and primary currents at Nominal Weight of the oil Weight of core and tank Gross weight 5.1.2.5 Manufacturers’ Drawings The following drawings approved by the purchaser shall be availed by the manufacturer: Wiring and schematic drawing of the tap changer and transformer Complete assembly drawing of the transformer and accessories Foundation Drawings Outline drawing Instruction Manuals An instruction manual shall be availed by the manufacturer composed of the following sections: Introduction General Transformer features Parking, Transportation and Handling Assembling and Installation Pre-commissioning checks Commissioning Maintenance Troubleshooting End of life disposal Drawings and catalogue Loss evaluation and Payment 11 Both No Load and Full Load losses shall be specified to the potential supplier of the Transformer. The calculated and actual losses shall be compared during factory acceptance test and payment may be calculated. In the event of actual loss being higher than agreed, parties may agree on a price discount or rejection of the unit. 5.1.3 Rating Characteristics 5.1.3.1 Transformer Rating The transformer shall have an assigned rated power for each winding which shall be marked on the rating plate. The rated power refers to continuous loading. This is a reference value for guarantees and tests concerning load losses and temperature rises. If different values of apparent power are assigned under different circumstances, for example, with different methods of cooling, the highest of these values is the rated power. A two-winding transformer has only one value of rated power, identical for both windings. When the transformer has rated voltage applied to a primary winding, and rated current flows through the terminals of a secondary winding, the transformer receives the relevant rated power for that pair of windings. The transformer shall be capable of carrying, in continuous service, the rated power [for a multiwinding transformer: the specified combination(s) of winding rated powers] under conditions listed in Clause 5.1.2.1 and without exceeding the temperature-rise limitations specified in IEC 60076-2. 5.1.3.2 Transformer Loading The maximum loading of the transformer shall be specified at all cooling levels i.e. ONAN, ONAF, OFAF and OFWF. The transformer will be loaded to not more than 1.5 times maximum nameplate rating. All transformer parts shall be sized to allow full use of the winding's loading capability for the following loading types (These loading capabilities shall apply to all transformers for the following conditions): i). Preload of 90 % of nameplate MVA rating;, ii). The hottest spot temperature not to exceed 140º C, a top oil temperature not to exceed 110ºC; and, iii). Loss of life not to exceed 1.0% per incident. Short Time Minimum Acceptable Loading Capability p.u. of nameplate MVA rating. The loadings are depicted in the Table 5-2 below: Table 5-2: Transformer Loading Ambient Temperature (oC) Load In Per Unit of Nameplate Rating 12 10 40 5.1.3.3 Short Circuit Capability (Load Duration in Hours) 0.5 1.0 2.0 1.50 1.45 1.39 1.26 1.23 119 4.0 1.34 1.15 8.0 1.31 1.13 The transformer and its current-carrying parts including tap changers and bushings shall have short circuit capability in accordance with IEC 60076-5. Tertiary Windings, when specified, shall be self-protecting. System fault power may be supplied from either one or both unfaulted terminals. The maximum short circuit current at the tertiary bushings shall not exceed either, 25 times the rated tertiary winding capacity or 32 kA whichever is lower. 5.1.3.4 Earthquake Strength The completely assembled transformer shall meet the High Seismic Qualification Level with 2% which is the highest seismic reading in Zambia. 5.1.3.5 Wind Loading Strength The transformer shall be designed to withstand winds up 40m/sec in its service configuration (i.e., with bushings, arresters, radiator/coolers, conservator, etc. installed). The earthquake and wind forces need not be considered as occurring simultaneously. Documentation in the form of test data or calculations shall be provided to confirm the transformer‟s wind and mechanical shock withstand capabilities. 5.1.3.6 Sound Level The sound level shall not exceed 75db at full load 5.1.3.7 Vibration The transformer accessories shall be protected from damage by vibration during operation, transportation or short circuits 5.1.4 Transformer Auxiliary Equipment The size, type and location of the transformer dictate the amount of auxiliary equipment associated with it. All auxiliary equipment should be checked for proper operation to assure they are not defective. The following accessories shall be included on all oil filled substation transformers: i). ii). iii). iv). v). vi). vii). Pad lockable tap changer for de-energized operation ( for transformers greater than 1000 kVA rating) Upper filling plug and filter press connection Drain valve with a sampler (two-inch drain valve for transformers above 2500 kVA rating) Dial type thermometer Pressure/vacuum gauge [with] [without] bleeder connection Magnetic liquid level gauge Pressure Relief Valve/Device, 13 viii). ix). x). Alarm contacts on [all gauges] [dial thermometer] [liquid level gauge] [pressure vacuum gauge] Pressure relief diaphragm Buchholz relay( for transformers greater than and including 1200 kVA rating) 14 5.2 Switchgear Switchgear shall comply with IEC 62271-SER ed1.0 (2015-02) High-voltage switchgear and control gear - ALL PARTS. 5.2.1. Normal Service Conditions 5.2.1.1 Indoor switchgear and controlgear a). The ambient air temperature does not exceed 40 °C and its average value, measured over a period of 24 h, does not exceed 35 °C. The preferred values of minimum ambient air temperature are –5 °C, –15 °C and –25 °C. b). c). d). e). The influence of solar radiation may be neglected. The altitude does not exceed 1 000 m. The ambient air is not significantly polluted by dust, smoke, corrosive and/or flammable gases, vapours or salt. The manufacturer will assume that, in the absence of specific requirements from the user, there are none. The conditions of humidity are as follows: the average value of the relative humidity, measured over a period of 24 h, does not exceed 95 %; the average value of the water vapour pressure, over a period of 24 h, does not exceed 2.2 kPa; the average value of the relative humidity, over a period of one month, does not exceed 90 %; the average value of the water vapour pressure, over a period of one month, does not exceed 1.8 kPa. For these conditions, condensation may occasionally occur. f). NOTE 1: Condensation can be expected where sudden temperature changes occur in periods of high humidity. NOTE 2: To withstand the effects of high humidity and condensation, such as breakdown of insulation or corrosion of metallic parts, switchgear designed for such conditions should be used. NOTE 3: Condensation may be prevented by special design of the building or housing, by suitable ventilation and heating of the station or by the use of dehumidifying equipment. Vibrations due to causes external to the switchgear and controlgear or earth tremors are insignificant relative to the normal operating duties of the equipment. The manufacturer will assume that, in absence of specific requirements from the user, there are none. NOTE 4: The interpretation of the term “insignificant” is the responsibility of the user or specifier of the equipment. Either the user is not concerned with seismic events, or his analysis shows that the risk is “insignificant”. Outdoor switchgear and controlgear a). The ambient air temperature does not exceed 40 °C and its average value, measured over a period of 24 h, does not exceed 35 °C. The preferred values of minimum ambient air temperature are -10 °C, -25 °C, -30 °C and 40 °C. 15 Rapid temperature changes should be taken into account. b). Solar radiation up to a level of 1 000 W/m2 (on a clear day at noon) should be considered. NOTE 1: NOTE 2: Under certain levels of solar radiation, appropriate measures, for example roofing, forced ventilation, test simulating solar gain, etc., may be necessary, or derating may be used, in order not to exceed the specified temperature rises and design pressure limits. Details of global solar radiation are given in IEC 60721-2-4. c). The altitude does not exceed 1 000 m. d). The ambient air may be polluted by dust, smoke, corrosive gas, vapours or salt. e). The ice coating shall be considered in the range from 1 mm up to, but not exceeding, 20 mm. f). The wind speed does not exceed 34 m/s (corresponding to 700 Pa on cylindrical surfaces). NOTE 3: g). Consideration should be given to condensation or precipitations that may occur. NOTE 4: h). Characteristics of wind are described in IEC 60721-2-2. Characteristics of precipitation are defined in IEC 60721-2-2. Vibrations due to causes external to the switchgear and controlgear or earth tremors are insignificant relative to the normal operating duties of the equipment. The manufacturer will assume that, in the absence of specific requirements from the user, there are none. NOTE 5: The interpretation of the term “insignificant” is the responsibility of the user or specifier of the equipment. Either the user is not concerned with seismic events, or his analysis shows that the risk is “insignificant”. 5.2.2. General Design and Construction Switchgear can be of indoor and outdoor types. Metal-enclosed switchgear and control gear shall be designed so that normal service, inspection and maintenance operations, determination of the energized or de-energized state of the main circuit, including the usual checking of phase sequence, earthing of connected cables, locating of cable faults, voltage connected cables or other apparatus and the elimination of dangerous electrostatic charges, can be carried out safely. An earthing conductor shall be provided extending the whole length of the metal-enclosed switchgear and control gear. The current density in the earthing conductor, if of copper, shall under the specified earth fault conditions not exceed 200 A/mm2 for a rated duration of short circuit of 1 s and 125 A/mm2 for a rated duration of short-circuit of 3 s. However, its cross section shall be not less than 30mm2. It shall be terminated by an adequate terminal intended for connection to the earth system of the installation. The metallic parts of a withdrawable part which are normally earthed shall also remain earthconnected in the test and disconnected positions under the prescribed conditions for the isolating distance and also in any intermediate position. The metallic parts of a removable part which are normally earthed shall remain earth-connected until the removable part is separated from the switchgear. 16 5.2.1.1. Shutters Means shall be provided to ensure the reliable operation of the shutters, e.g. by a mechanical drive, where the movement of the shutters is positively driven by the Movement of the removable part. If, for maintenance or test purposes, there is a requirement that one set of fixed contacts shall be accessible through opened shutters, all the shutters shall be provided with means of locking them independently in the closed position or it shall be possible to insert a screen to prevent the live set of fixed contacts being exposed. When, for maintenance or test purposes, the automatic closing of shutters is made inoperative in order to retain them in the open position, it shall not be possible to return the switching device to the service position until the automatic operation of the shutters is restored. This restoration may be achieved by the action of returning the switching device to the service position. The shutters of the three types of metal-enclosed switchgear and control gear may be either metallic or non-metallic. If shutters are of insulating material, they shall not become part of the enclosure, If they are metallic, they shall be earthed, and if they become part of the enclosure, they shall provide the degree of protection specified for the enclosure. 5.2.1.2. Interlocks It shall not be possible to close the circuit-breaker, switch or contactor in the service position unless any auxiliary circuits associated with the automatic opening of these Devices are connected. Conversely, it shall not be possible to disconnect the auxiliary Circuits with the circuit-breaker closed in the service position. Interlocks shall be provided to prevent operation of disconnections under conditions other than those they are intended for. The operation of a disconnector shall not be possible unless the associated circuit-breaker, switch or contactor is in the open position. If earthing of a circuit is provided by a circuitbreaker in series with an earthing switch, the earthing switch shall be interlocked with the circuit-breaker and the circuit-breaker shall be secured against unintentional opening. 5.2.1.3. Earthing of Switchgear and Controlgear 5.2.1.3.1. Earthing of the main circuit To ensure safety during maintenance work, all parts of the main circuit to which access is required or provided shall be capable of being earthed prior to becoming accessible. This does not apply to withdrawable and removable parts which become accessible after being separated from the switchgear. 5.2.1.3.2. Earthing of the enclosure Switchgear and controlgear shall be provided with a reliable earthing terminal having a clamping screw or bolt for connection of an earthing conductor suitable for specified fault conditions. The connecting point shall be marked with the "protective earth" symbol, as indicated by symbol 5019 of IEC 60417. Parts of metallic enclosures connected to the earthing system may be considered as an earthing conductor. 17 All metallic components and enclosures that may be touched during normal operating conditions and are intended to be earthed shall be connected to an earthing terminal. An earthing conductor shall be provided extending the whole length of the metal-enclosed switchgear and control gear. The current density in the earthing conductor, if of copper, shall not exceed 200 A/mm2 under the specified earth fault conditions; however, its crosssection area shall be not less than 30 mm2. It shall be terminated by an adequate terminal intended for connection to the earth system of the installation. NOTE - If the earthing conductor is not made of copper, equivalent thermal and mechanical requirements should be met. In general, the continuity of the earth system shall be ensured taking into account the thermal and mechanical stresses caused by the current it may have to carry. The maximum value of earth fault currents depends upon the type of system neutral earthing employed and shall be indicated by the user. Where earthing connections have to carry the full three-phase short-circuit current (as in the case of the shortcircuiting connections used for earthing devices) these connections shall be dimensioned accordingly. 5.2.1.4. Requirements for liquids in switchgear and control gear The manufacturer shall specify the type and the required quantity and quality of the liquid to be used in switchgear and controlgear and provide the user with necessary instructions for renewing the liquid and maintaining its required quantity and except for sealed pressure systems. NOTE: Attention is drawn to the need to comply with local regulation relevant to pressure vessels. 5.2.1.4.1. Liquid level A device for checking the liquid level, preferably during service, with indication of minimum and maximum limits permissible for correct operation, shall be provided. NOTE: This is not applicable to dash-pots. 5.2.1.4.2. Liquid quality Liquids for use in switchgear and controlgear shall comply with the instructions of the manufacturer. For oil-filled switchgear and controlgear, new insulating oil shall comply with IEC 60296. NOTE: For sealed pressure systems, instructions for maintaining the liquid quality are not applicable. 5.2.1.5. Requirements for gases in switchgear and control gear The manufacturer shall specify the type and the required quantity, quality and density of the gas to be used in switchgear and controlgear and provide the user with necessary instructions for renewing the gas and maintaining its required quantity and quality except for sealed pressure systems. For sulphur hexafluoride (SF6) filled switchgear and controlgear, SF6 in accordance with either IEC 60376 or IEC 60480 can be used. In order to prevent condensation, the maximum allowable moisture content within gas-filled switchgear and controlgear filled with gas at the rated filling density for insulation ρre shall be such that the dew-point is not higher than −5 °C for a measurement at 20 °C. Adequate correction shall be made for measurement made at other 18 temperatures. For the measurement and determination of the dew-point, refer to IEC 60376 and IEC 60480. Parts of high-voltage switchgear and controlgear housing compressed gas shall comply with the requirements laid down in the relevant IEC standards. NOTE - For checking of sulphur hexafluoride in service, refer to IEC 60480. 5.2.1.6. Auxiliary and control equipment Auxiliary and control equipment is considered to be of conventional or non-conventional (electronic) design components. For non-conventional design components refer to IEC 62063. For electronic devices, electro-magnetic (EM) susceptibility shall be considered. 5.2.1.6.1 Enclosures 5.2.1.6.1.1 General The enclosures for low-voltage control and auxiliary circuits shall be constructed of materials capable of withstanding the mechanical, electrical and thermal stresses, as well as the effects of humidity which are likely to be encountered in normal service. 5.2.1.6.1.2 Protection against corrosion Protection against corrosion shall be ensured by the use of suitable materials or by the application of suitable protective coatings to the exposed surfaces, taking into account the intended conditions of use in accordance with the service conditions stated in Clause 5.2.1. 5.2.1.6.1.3 Degrees of protection The degree of protection provided by an enclosure for low-voltage auxiliary and control circuits shall be in accordance with 5.13. Openings in cable entries, cover plates, etc. shall be so designed that, when the cables are properly installed, the stated degree of protection of an enclosure for low-voltage auxiliary and control circuits, as defined in 5.13, shall be obtained. A means of entry, suitable for the application stated by the manufacturer, should be selected. Any ventilation openings shall be shielded or arranged so that the same degree of protection as that specified for the enclosure is obtained. 5.2.1.6.1.4 Protection against electric shock 5.2.1.6.1.4.1 Protection by segregation of auxiliary and control circuits from the main circuit Auxiliary and control equipment which is installed on the frame of switching devices shall be suitably protected against disruptive discharge from the main circuit. 19 The wiring of auxiliary and control circuits, with the exception of short lengths of wire at terminals of instrument transformers, tripping coils, auxiliary contacts, etc. shall be either segregated from the main circuit by earthed metallic partitions (for example, tubes) or separated by partitions (for example, tubes) made of insulating material. 5.2.1.6.1.4.2 Accessibility Auxiliary and control equipment to which access is required during service shall be accessible without the need to compromise clearances to hazardous parts. Where clearances may be compromised by environmental related changes in the service access level (for example accumulation of snow, sand, etc.) the use of increased clearances should be considered. 5.2.1.6.1.5 Fire hazard 5.2.1.6.1.5.1 General As the risk of fire is present in auxiliary and control circuits, the likelihood of fire shall be reduced under conditions of normal use and even in the event of malfunction or failure. The first objective is to prevent ignition due to an electrically energized part of auxiliary and control circuits. The second objective is to limit the fire impact, if fire or ignition occurs inside the enclosure. 5.2.1.6.1.5.2 Components and circuit design In normal operation, heat dissipation of components is generally small. However, a component may, when faulty or in an overload condition resulting from an external fault, generate excess heat such that fire may be initiated. The manufacturer should design or choose components taking into account normal conditions and self-ignition characteristics due to the effects of the maximum fault power. Special attention should be given to resistors. Consideration should be given to the assembly of components and the relative arrangement of those that may dissipate excessive heat by providing around them sufficient space and/or ventilation. 5.2.1.6.1.5.3 Managing fire impact Provisions should be taken in order to manage fire impact. Enclosures should be constructed, insulated, made watertight, etc. with materials sufficiently resistant to probable ignition and heat sources situated within. The manufacturer should consider that, if it ignites, a component may emit melted flaming material and/or glowing particles. 5.2.1.6.1.6 Components installed in enclosures 5.2.1.6.1.6.1 Selection of components 20 Components installed in enclosures shall comply with the requirements of the relevant IEC standards where applicable. Where an IEC standard does not exist the component should be qualified with reference to another standard (issued by a country or another organization). All components used in the auxiliary and control circuits shall be designed or selected to be operational with their rated characteristics over the whole actual service conditions inside auxiliary and control circuits enclosures. These internal conditions can differ from the external service conditions specified in Clause 5.2.1. Suitable precautions (insulation, heating, ventilation, etc) should be taken to ensure that those service conditions essential for proper functioning are maintained, for example, heaters to maintain the required minimum temperature for the correct operation of relays, contactors, lowvoltage switches, meters, operation counters, push-buttons, etc. according to the relevant specifications. The loss of those precaution means should not cause failures of the components nor untimely operation of switchgear and controlgear. The operation of switchgear and controlgear shall be possible during 2 h after the loss of those means. After this period, nonoperation of the switchgear and controlgear with its associated auxiliary and control circuit is acceptable provided that the functionality resets to its original characteristics when environmental conditions inside the enclosure for auxiliary and control circuits are back to the specified service conditions. Where heating is essential for correct functioning of the equipment, monitoring of the heating circuit shall be provided. In the case of switchgear and controlgear designed for outdoor installation, suitable arrangements (ventilation and/or internal heating, etc.) shall be made to prevent harmful condensation in low-voltage control and auxiliary circuits enclosures. Polarity reversal at the interfacing point shall not damage auxiliary and control circuits. 5.2.1.6.1.6.2 Installation of components Components shall be installed in accordance with the instructions of their manufacturer. 5.2.1.6.1.6.3 Accessibility Closing and opening actuators and emergency shut-down system actuators should be located between 0.4 m and 2 m above servicing level. Other actuators should be located at such a height that they can be easily operated, and indicating devices should be located at such a height that they can be easily readable. Structure-mounted or floor-mounted enclosures for low-voltage auxiliary and control circuits should be installed at such a height, with respect to the servicing level, that the above requirements for accessibility, operating and reading heights are met. 21 Components in enclosures should be so arranged as to be accessible for mounting, wiring, maintenance and replacement. W here a component may need adjustment during its service life; easy access should be considered without danger of electrical shock. 5.2.1.6.1.6.4 Identification Identification of components installed in enclosures is the responsibility of the manufacturer and it shall be in agreement with the indication on the wiring diagrams and drawings. If a component is of the plug-in type, an identifying mark should be placed on the component and on the fixed part where the component plugs in. W here mixing of components or voltages could cause confusion, consideration should be given to more explicit marking. 5.2.1.6.1.6.5 Requirements for auxiliary and control circuit components The auxiliary and control circuit components shall comply with applicable IEC standards if one exists. Annex D is provided as a quick reference to many of the component standards. 5.2.1.6.1.6.5.1 Cables and wiring The specification of cables to connect auxiliary and control circuits of the switchgear and controlgear is the responsibility of the manufacturer. The choice is governed by the current that must be carried, by the voltage drop and the current transformer burden, by the mechanical stresses to which the cable is subjected and by the type of insulation. The choice of conductors in enclosures is also the responsibility of the manufacturer. Where a facility for external wiring is required, an appropriate connecting device shall be provided for example terminal blocks, plug-in terminations, etc. Cables between two terminal blocks shall have no intermediate splices or soldered joints. Connections shall be made at fixed terminals. Insulated conductors shall be adequately supported and shall not rest against sharp edges. W ire routing should take into account the proximity of heating elements. The available wiring space shall permit spreading of the cores of multi-core cables and the proper termination of the conductors. The conductors shall not be subjected to stresses that reduce their normal life. Conductors connected to apparatus and indicating devices in covers or doors shall be so installed that no mechanical damage can occur to the conductors as a result of movement of these covers or doors. The number of connections made to a terminal shall not exceed its designed maximum. The method and extent of identification of conductors, for example by numbers, colours or symbols, is the responsibility of the manufacturer. Identification of conductors shall be in agreement with the wiring diagrams and drawings, and the specification of the user, if 22 applicable. This identification may be limited to the ends of the conductors. W here appropriate, identification of wiring according to IEC 60445 may be applied. 5.2.1.6.1.6.5.2 Terminals Terminals shall maintain the necessary contact pressure, corresponding to the current rating and the short-circuit current of circuits. Terminal blocks for wiring components inside the enclosure shall be chosen according to the cross-section of the conductors used. If facilities are provided for connecting incoming and outgoing neutral, protective and PEN conductors, they shall be situated in the vicinity of the associated phase conductor terminal. 5.2.1.6.1.6.5.3 Auxiliary switches Auxiliary switches shall be suitable for the number of electrical and mechanical operating cycles specified for the switching device. Auxiliary switches, which are operated in conjunction with the main contacts, shall be positively driven in both directions. However, a set of two one-way positively driven auxiliary contacts (one for each direction) can be used. 5.2.1.6.1.6.5.4 Auxiliary and control contacts Auxiliary and control contacts shall be suitable for their intended duty in terms of environmental conditions (refer to 5.4.3.1), making and breaking capacity and timing of the operation of the auxiliary and control contacts in relation to the operation of the main equipment. Auxiliary and control contacts shall be suitable for the number of electrical and mechanical operating cycles specified for the switching device. Where an auxiliary contact is made available to the user, the technical documents provided by the manufacturer should contain information regarding the class of this contact. The operational characteristics of the auxiliary contacts should comply with one of the classes shown in Table 5-3. 23 Table 5-3: Auxiliary contact classes D.c. Class Rated continuous current Rated shorttime withstand current 1 10 A 100 A/30 ms 2 2A 100 A/30 ms 3 200 mA 1 A/30 ms Breaking capacity 110 V ≤ U a ≤ 250 V ≤48 440 W 22 W 50 mA NOTE 1 This table refers to auxiliary contacts [IEV 441-15-10] which are included in an auxiliary circuit and mechanically operated by the switching device. Control contacts [IEV 441-15-09] which are included in a control circuit of a mechanical switching device may be covered by this table. NOTE 2 If insufficient current is flowing through the contact, oxidation may increase the resistance. Therefore, a minimum value of current may be required for class 1 contact. NOTE 3 In the case of the application of static contacts, the rated short-time withstand current may be reduced if current-limiting equipment, other than fuses, is employed. NOTE 4 For all classes, breaking capacity is based on a circuit time constant of not less than 20 ms with a relative tolerance of ±20%. 0 NOTE 5 An auxiliary contact which complies with class 1, 2 or 3 for d.c is normally able to handle corresponding a.c. current and voltage. NOTE 6 Class 3 contacts are not intended to be subjected to full substation auxiliary-supply short-circuit current. Class 1 and 2 contacts are intended to be subjected to full substation auxiliary-supply short- circuit current. NOTE 7 Breaking current at a defined voltage value between 110 V and 250 V may be deduced from the indicated power value for class 1 and class 2 contacts (for example, 2 A at 220 V d.c. for a class 1 contact). 5.2.1.6.1.6.5.5 Contacts other than auxiliary and control contacts A contact other than an auxiliary or control contact is a contact driven by a component (relay, contactor, low-voltage switch, etc.) used in the auxiliary and control circuits. Where a contact other than an auxiliary or control contact is made available to the user, the technical documents provided by the manufacturer should include the rated continuous current and making and breaking capacity of this contact. The user is responsible for ensuring that the contact performance is adequate for the task. The number of contacts provided shall be specified to the manufacturer in accordance with Clause 9 or the relevant equipment standard. 5.2.1.6.1.6.5.6 Relays Where a relay is chosen and used at a voltage different from the rated voltage of auxiliary and control circuits, an appropriate device shall be provided to allow it to operate correctly under the conditions specified in 4.8 (for example, provision of a series resistor). 5.2.1.6.1.6.5.7 Shunt releases 24 Shunt releases are designed for specific purposes. As no IEC standard exists for shunt releases, they should satisfy the requirements of the relevant equipment standard. The electrical power of the shunt releases shall be stated by the manufacturer. 5.2.1.6.1.6.5.8 Heating elements All heating elements shall be of the non-exposed type. Heaters shall be situated so that they do not cause any deterioration in the wiring or in the operation of the components. W here contact with a heater or shield can occur accidentally, the surface temperature shall not exceed the temperature-rise limits for accessible parts which need not be touched in normal operation, as specified in Table 3. 5.2.1.6.1.6.5.9 Operation counters Operation counters shall be suitable for their intended duty in terms of environmental conditions and for the number of electrical and mechanical operating cycles specified for the switching devices. 5.2.1.6.1.6.5.10 Illumination In some enclosures, for example enclosures containing manual operating means (handles, pushbuttons, etc.), lighting should be considered. W here lighting is installed, consideration should be given to the heat and electromagnetic disturbance produced by the lighting on the auxiliary and control-circuit components. 5.2.1.6.1.6.5.11 5.4.4.5.11 Coils Coils not covered by a component standard shall be suitable for their intended duty (for example, with respect to temperature rise, dielectric withstand, etc.). 5.2.1.7. Dependent power closing A switching device arranged for dependent power operation with external energy supply shall be capable of making and/or breaking its rated short-circuit current (if any) when the voltage or the pressure of the power supply of the operating device is at the lower of the limits specified under clauses 5.2.2.7 and 5.2.2.10 (the term "operating device" here embraces intermediate control relays and contactors where provided). If maximum closing and opening times are stated by the manufacturer, these shall not be exceeded. Except for slow operation during maintenance, the main contacts shall only move under the action of the drive mechanism and in the designed manner. The closed or open position of the main contacts shall not change as a result of loss of the energy supply or the re-application of the energy supply after a loss of energy, to the closing and/or opening device. 25 5.2.1.8. Stored energy closing A switching device arranged for stored energy operation shall be capable of making and breaking all currents up to its rated values when the energy storage device is suitably charged. If maximum closing and opening times are stated by the manufacturer, these shall not be exceeded. Except for slow operation during maintenance, the main contacts shall only move under the action of the drive mechanism and in the designed manner, and not in the case of reapplication of the energy supply after a loss of energy. A device indicating when the energy storage device is charged shall be mounted on the switching device except in the case of an independent unlatched operation. It shall not be possible for the moving contacts to move from one position to the other, unless the stored energy is sufficient for satisfactory completion of the opening or closing operation. Stored energy devices shall be able to be discharged to a safe level prior to access. 5.2.1.8.1 Energy storage in gas receivers or hydraulic accumulators When the energy storage device is a gas receiver or hydraulic accumulator, the requirements of 5.2.1.8 apply at operating pressures between the limits specified in items a) and b). a). External pneumatic or hydraulic supply Unless otherwise specified by the manufacturer, the limits of the operating pressure are 85 % and 110 % of the rated pressure. These limits do not apply where receivers also store compressed gas for interruption. b). Compressor or pump integral with the switching device or the operating device The limits of operating pressure shall be stated by the manufacturer. 5.2.1.8.2 Energy storage in springs (or weights) When the energy storage device is a spring (or weight), the requirements of 5.2.1.8 apply when the spring is charged (or the weight lifted). 5.2.1.8.3 Manual charging If a spring (or weight) is charged by hand, the direction of motion of the handle shall be marked. The manual charging facility shall be designed such that the handle is not driven by the operation of the switching device. The maximum actuating force required for manually charging a spring (or weight) shall not exceed 250 N. 26 5.2.1.8.4 Motor charging Motors, and their electrically operated auxiliary equipment for charging a spring (or weight) or for driving a compressor or pump, shall operate satisfactorily between 85 % and 110 % of the rated supply voltage (refer to 5.2.2.7), the frequency, in the case of a.c., being the rated supply frequency (refer to 5.2.2.8). NOTE For electric motors, the limits do not imply the use of non-standard motors but only the selection of a motor which at these values provides the necessary effort, and the rated voltage of the motor need not coincide with the rated supply voltage of the closing device. 5.2.1.8.5 Energy storage in capacitors When the energy store is a charged capacitor, the requirements of 5.2.1.8 apply when the capacitor is charged. 5.2.1.9. Operating of releases The operation limits of releases shall be as follows: 5.2.1.9.1 Shunt closing release A shunt closing release shall operate correctly between 85 % and 110 % of the rated supply voltage of the closing device (see 5.2.2.7), the frequency, in the case of a.c., being the rated supply frequency of the closing device (see 5.2.2.8). 5.2.1.9.2 Shunt opening release A shunt opening release shall operate correctly under all operating conditions of the switching device up to its rated short-circuit breaking current, and between 70 % in the case of d.c. – or 85 % in the case of a.c. – and 110 % of the rated supply voltage of the opening device (refer to 5.2.2.7), the frequency in the case of a.c being the rated supply frequency of the opening device (see 5.2.2.8). 5.2.1.9.3 Capacitor operation of shunt releases When, for stored energy operation of a shunt release, a rectifier-capacitor combination is provided as an integral part of the switching device, the charge of the capacitors to be derived from the voltage of the main circuit or the auxiliary supply, the capacitors shall retain a charge sufficient for satisfactory operation of the release 5 s after the voltage supply has been disconnected from the terminals of the combination and replaced by a short-circuiting link. The voltages of the main circuit before disconnection shall be taken as the lowest voltage of the system associated with the rated voltage of the switching device (refer to IEC 60038 for the relation between "highest voltage for equipment" and system voltages). 5.2.1.9.4 Under-voltage release An under-voltage release shall operate to open the switching device when the voltage at the terminals of the release falls below 35 % of its rated voltage, even if the fall is slow and gradual. 27 On the other hand, it shall not operate the switching device when the voltage at its terminals exceeds 70 % of its rated supply voltage. The closing of the switching device shall be possible when the values of the voltage at the terminals of the release are equal to or higher than 85 % of its rated voltage. Its closing shall be impossible when the voltage at the terminals is lower than 35 % of its rated supply voltage. 5.2.1.10. Low and high pressure interlocking devices All vacuum or gas filled switchgear shall be fitted with a pressure gauge. The operating pressure shall be indicated in both Bars and MPa and clearly Visible. The pressure gauge shall have contacts for Low pressure alarm, Lockout and spare contacts. The switchgear shall be fitted with both visible and audible low pressure alarms. In case of a breaker, the breaker shall be wired in such a way that gas pressure below the low pressure set point shall render the breaker inoperational or into lockout mode. In such a state, the breaker will maintain the initial position until the anomaly is corrected. The lockout alarm shall also be both visible and audible. The breaker shall also be fitted with both audible and visible alarms for pressure above manufacturer‟s maximum recommended limits. In case of loss of vacuum the breaker shall be rendered inoperational or into lockout mode. Values for pressure points shall be as specified by the manufacturer of the switchgear corrected to 20ºCelsius and the switchgear shall be filled with gas not exceeding the manufacturer‟s recommendation. All parts in direct contact with the gas such as pipes, flanges, seals and others shall be of material that is non-reactive to the gas. 5.2.1.11. Nameplates Switchgear and controlgear and their operating devices shall be provided with nameplates which contain the necessary information such as the name or mark of the manufacturer, the year of manufacture, the manufacturer's type designation, the serial number or equivalent, the rated characteristics etc. as specified in the relevant IEC standards. If applicable, the type and mass of insulating fluid shall be noted on the nameplate. NOTE It should be stated whether pressures (or densities) are absolute or relative values. For outdoor switchgear and controlgear, the nameplates and their methods of attachment shall be weather-proof and corrosion-proof. If the switchgear and controlgear consist of several poles with independent operating mechanisms, each pole shall be provided with a nameplate. For an operating device combined with a switching device, it may be sufficient to use only one combined nameplate. Technical characteristics on nameplates and/or in documents which are common to several kinds of high-voltage switchgear and controlgear shall be represented by the same symbols. 28 Such characteristics and their symbols are: rated voltage Ur rated lightning impulse withstand voltage Up rated switching impulse withstand voltage Us rated power-frequency withstand voltage Ud rated normal current Ir rated short-time withstand current Ik rated peak withstand current Ip rated frequency Fr rated duration of short circuit Tk rated auxiliary voltage Ua rated filling pressure (density) for insulation p re (ρ re) p rm (ρ rm ) rated filling pressure (density) for operation p ae (ρ ae) p am (ρ am ) alarm pressure (density) for insulation alarm pressure (density) for operation minimum functional pressure (density) for insulation minimum functional pressure (density) for operation p me (ρ me) p mm (ρ mm ) Metal-enclosed switchgear and control gear, all their components and operating devices shall be provided with durable and clearly legible nameplates which shall contain the following information: a). Manufacturer‟s name or trade mark; b). Type designation or serial number; c). Applicable rated values; d). Number of the relevant standard. The nameplates of each functional unit shall be legible during normal service. The removable parts, if any, shall have a separate nameplate with the data relating to the functional units they belong to, but this nameplate need only be legible when the removable part is in the removed position. 5.2.1.12. Protection of persons against approach to live parts The degree of protection shall be specified separately for the enclosure and for partitions. For cubicle switchgear and control gear, it is only necessary to specify the degree of protection for the enclosure. For main circuits of gas-filed compartments, no degree of protection needs to be specified. The degree of protection against contact of persons with live parts of auxiliary circuits and with any moving parts (other than smooth rotating shafts and moving linkages) shall be indicated by means of the designation specified in Table 5-4. 29 The characteristic numeral indicates the degree of protection provided by the enclosure with respect to persons, also to the equipment inside the enclosure. Table 5-4 gives details of objects which will be “excluded” from the enclosure for each of the degrees of protection. The term “excluded” implies that a part of the body or an object held by a person, either will not enter the enclosure or, if it enters, that adequate clearance will be maintained and no moving part will be touched. Degree of Protection against approach to live parts and contact with moving parts protection Table 5-4: Degrees of protection against solid foreign objects indicated by the first characteristic Numeral Degree of Protection IP2X Protection against approach to live parts and contact with moving parts By fingers or similar objects of diameter greater than 12mm IP3X By tools, wires, etc., of diameter or thickness greater than 2.5mm IP4X By wires of diameter or strips of thickness greater than 1.0mm NOTE – the designation of the degree of protection corresponds to IEC 60529 5.2.1.13. Internal fault Failure within the enclosure of metal-enclosed switchgear and control gear due either to a defect or an exceptional service condition or mal-operation may initiate an internal arc. There is little probability of such an event occurring in constructions which satisfy the requirements of this standard, but it cannot be completely disregarded. Such an event may lead to the risk of injury, if persons are present, but with an even lower probability. It is desirable that the highest possible degree of protection to persons should be provided. The principal objective should be to avoid such error or to limit their duration and consequences. Experience has shown that faults are more likely to occur in some locations inside an enclosure than in others, so special attention should be paid to these. 5.2.1.14. Enclosure Enclosures shall be metallic. When the metal-enclosed switchgear and control gear is installed, the enclosure shall provide at least the degree of protection specified in table 1. It shall also assure protection in accordance with the following conditions: The floor surface, even if not metallic, may be considered as part of the enclosure. The measures to be taken in order to obtain the degree of protection provided by floor surfaces shall be subject to an agreement between manufacturer and user. The walls of a room shall not be considered as parts of the enclosure. Gas-filled compartments shall be capable of withstanding the normal and transient pressures to which they are subjected in service. While these compartments are permanently pressurized in service they are subjected to particular conditions of service which distinguish them from compressed air receivers and similar storage vessels. These conditions are: - gas-filled compartments enclose the main circuit not only to prevent hazardous approach to 30 live or moving parts but are so shaped that, when at or above the minimum functional pressure they ensure that the rated insulation level for the equipment is achieved (electrical rather than mechanical considerations predominate in determining the shape and materials employed); gas-filled compartments shall be filled with a non-corrosive gas, thoroughly dried, stable and inert. 5.2.1.15. Inspection windows Inspection windows shall provide at least the degree of protection specified for the enclosure. They shall be covered by a transparent sheet of mechanical-strength comparable to that of the enclosure. Precautions shall be taken to prevent the formation of dangerous electrostatic charges, either by clearance or by electrostatic shielding (for example a suitable earthed Wiremesh on the inside of the window). The insulation between live parts of the main circuit and the inspection windows shall withstand the test voltages specified in Sub-clause 4.2.1 of IEC 62271-1 for voltage tests to earth and between poles. 5.2.1.16. Ventilating openings, vent outlets Ventilating openings and vent outlets shall be so arranged or shielded that the same degree of protection as that specified for the enclosure is obtained. Such openings may make use of wire mesh or the like provided that it is of suitable mechanical strength. Ventilating openings and vent outlets shall be arranged in such a way that gas or vapour escaping under pressure does not endanger the operator. 5.2.1.17. Partitions and shutters Partitions and shutters shall provide at least the degree of protection specified in Partitions and shutters made of insulating material shall meet the following requirements a). b). c). The insulation between live parts of the main circuit and the accessible surface of insulating partitions and shutters shall withstand the test voltages specified in Subclause 4.2.1 of IEC 62271-1 for voltage tests to earth and between poles; Apart from mechanical strength, the insulating material shall withstand likewise the test voltages specified in Item a), The appropriate test-methods given in IEC 60243-1 should be applied; The insulation between live parts of the main circuit and the inner surface of insulating partitions and shutters facing these shall withstand at least 150 % of the rated voltage of the equipment; 5.2.1.18. Partitions Partitions of metal-clad switchgear and control gear shall be metallic and earthed. Partitions of compartmented and cubicle switchgear and control gear may be non-metallic. If partitions become part of the enclosure with the removable part in any of these positions, they shall be metallic, earthed and provide the degree of protection specified for the enclosure. Partitions between two gas-filled compartments or between a gas-filled compartment and another compartment may be of insulating material provided they do not become part of the enclosure but are not intended by themselves to provide electrical safety of personnel, for which other 31 means such as earthing of the equipment may be necessary; they shall, however, provide mechanical safety against the normal gas pressure still present in the adjacent compartment. 5.2.1.19. Pressure relief of gas-filled compartments Where pressure relief devices are provided, they shall be arranged so as to minimize the danger to an operator during the time that he is performing his normal operating duties if gases or vapours are escaping under pressure. In certain designs pressure relief may be achieved by allowing the arc to burn through the enclosure at designated points. Where such means are employed, the resultant hole is deemed to be a pressure relief device. 5.2.1.20. Disconnections and earthing switches The devices for ensuring the isolating distance between the high-voltage conductors are considered to be disconnections which shall comply with IEC 60129, except for mechanical operation tests The requirement that it shall be possible to know the operating position of the disconnector or earthing switch is met if one of the following conditions is fulfilled: i). ii). The isolating distance is visible; The position of the withdrawable part in relation to the fixed part is clearly visible and the positions corresponding to full connection and full isolation are clearly identified; the position of the disconnector or earthing switch is indicated by a reliable indicating device. Any removable part shall be so attached to the 'fixed part that its contacts will not open inadvertently due to forces which may occur in service, in particular those due to a short circuit. 5.2.1.21. Interlocks Interlocks between different components of the equipment are provided for reasons of safety and for convenience of operation. Visible indication shall be provided to show whether the mechanism is locked or free. The following provisions are mandatory for main circuits: 5.2.1.21.1. Metal-enclosed switchgear and control gear -with removable parts The withdrawal or engagement of a circuit-breaker, switch or contactor shall be impossible unless it is in the open position. The operation of a circuit-breaker, switch or‟ contactor shall be impossible unless it is in the service, disconnected, removed, test or earthing position. It shall be impossible to close the circuit-breaker, switch or contactor in the service position unless it is connected to the auxiliary circuit, unless it is designed to open automatically without the use of an auxiliary circuit. 32 5.2.1.21.2. Metal-enclosed switchgear and control gear without removable parts and provided with disconnector Interlocks shall be provided to prevent operation of disconnector under conditions other than those they are intended for. The operation of a disconnector shall be impossible unless the associated circuit-breaker, switch or contactor is in the open position. NOTE - This rule may be disregarded if it is possible to have a busbar transfer in a double busbar system without current interruption. The operation of the circuit-breaker, switch or contactor shall be impossible unless the associated disconnector is in the closed, open or earthing position (if provided). The provision of additional or alternative interlocks shall be subject to agreement between manufacturer and user. The manufacturer shall give all necessary information on the character and function of interlocks. It is recommended that earthing switches having a short-circuit making capacity less than the rated peak withstand current of the circuit should be interlocked with the associated disconnector 5.2.3. Rating Characteristics The ratings of metal-enclosed switchgear and control gear shall cover the following: a). b). c). d). e). f). g). h). i). Rated voltage and number of phases; Rated insulation level; Rated frequency; Rated normal current (for main circuits); Rated short-time withstands current (for main and earthing circuits); Rated peak withstand current, if applicable (for main and earthing circuits); Rated duration of short circuit;‟ Rated values of the components forming part of the metal-enclosed switchgear and Rated filling pressure (of gas-filled compartments). NOTE: For the co-ordination of rated voltages, rated short-time withstand currents, rated peak withstand currents and rated normal currents of metal enclosed switchgear and control gear. 5.2.2.1. Rated voltage The rated voltage is equal to the maximum system voltage for which the equipment is designed. It indicates the maximum value of the "highest system voltage" of networks for which the equipment may be used. Standard values of rated voltages are given below: a). Range I for rated voltages 245 kV and below: 3.6 kV, 7.2 kV, 12 kV, 17.5 kV, 24 kV, 36 kV, 52 kV, 72.5 kV, 100 kV, 123 kV, 145 kV, 170 kV, 245 kV b). Range II for rated voltages above 245 kV: 300 kV, 362 kV, 420 kV, 550 kV, 800 kV NOTE - Components forming part of metal-enclosed switchgear and control gear may have individual values of rated voltage in accordance with their relevant standards. 5.2.2.2. Rated insulation level The rated insulation level of switchgear and controlgear shall be selected from the values given in Tables 6-1. In these tables, the withstand voltage applies at the standardised reference atmosphere (temperature (20 °C), pressure (101.3 kPa) and humidity (11 g/m3)) specified in 33 IEC 60071-1. These withstand voltages include the altitude correction to a maximum altitude of 1 000 m specified for the normal operating conditions. The rated withstand voltage values for lightning impulse voltage (Up), switching impulse voltage (Us) (when applicable), and power-frequency voltage (Ud) shall be selected without crossing the horizontal marked lines. The rated insulation level is specified by the rated lightning impulse withstand voltage phase to earth. For most of the rated voltages, several rated insulation levels exist to allow for application of different performance criteria or overvoltage patterns. The choice should be made considering the degree of exposure to fast-front and slow-front overvoltages, the type of neutral earthing of the system and the type of overvoltage limiting devices. The "common values" used in Tables 1a and 1b apply to phase-to-earth, between phases and across the open switching device, if not otherwise specified in this standard. The withstand voltage values "across the isolating distance" are valid only for the switching devices where the clearance between open contacts is designed to meet the functional requirements specified for disconnectors. Table 5-5: Rated Insulation levels for rated voltages of Range I Rated voltage Ur kV (r.m.s. value) Rated short-duration powerfrequency withstand voltage Ud kV (r.m.s value) Common value (1) (2) Across the isolating distance (3) 3.6 10 12 7.2 20 23 12 28 32 17.5 38 45 24 50 60 36 70 80 52 72.5 100 95 140 150 185 185 230 110 160 175 210 210 265 123 34 Rated lightning impulse withstand voltage Up kV (peak value) Common value (4) Across the isolating distance (5) 20 40 40 60 60 75 75 95 95 125 145 170 250 325 380 450 450 550 23 46 46 70 70 85 85 110 110 145 165 195 290 375 440 520 520 630 145 170 245 230 275 275 325 360 395 460 265 315 315 375 415 460 530 550 650 650 750 850 950 1 050 630 750 750 860 950 1 050 1 200 5.2.2.3. Rated frequency (fr) The standard values of the rated frequency are 16 2/3 Hz, 25 Hz, 50 Hz and 60 Hz. 5.2.2.4. Rated normal current and temperature rise 5.2.2.4.1. Rated normal current (Ir) The rated normal current of switchgear and controlgear is the r.m.s value of the current which switchgear and controlgear shall be able to carry continuously under specified conditions of use and behavior. Some main circuits of metal-enclosed switchgear and control gear (e.g. busbars, feeder circuits, etc.) may not have the same value of rated normal current. 5.2.2.4.2. Temperature rise The temperature rise of components contained in metal-enclosed switchgear and control gear which are subject to individual specifications not covered by the scope of IEC 62271-1 shall not exceed the temperature-rise limits permitted in the relevant IEC standard for that component. The maximum permissible temperatures and temperature rises to be taken into account for busbars are those specified for contacts, connections and' metal parts in contact with insulation, as the case may be. 5.2.2.5. Rated peak withstand current The peak current associated with the first major loop of the rated short-time withstand current which switchgear and controlgear can carry in the closed position under prescribed conditions of use and behaviour. The rated peak withstand current shall be defined according to the d.c time constant which is a system characteristic. A d.c time constant of 45 ms covers the majority of cases and corresponds to a rated peak withstand current equal to 2.5 times the rated short-time withstand current for a rated frequency of 50 Hz and below it, and for a rated frequency of 60 Hz it is equal to 2.6 times the rated short-time withstand current. For some applications, system characteristics are such that the d.c. time constant is higher than 45 ms. Other values generally suitable for special systems are 60 ms, 75 ms and 120 ms depending on the rated voltage. For those cases, the preferred value is 2.7 times the rated shorttime withstand current. 35 NOTE - In principle, the rated short-time withstand current and the rated peak withstand current of a main circuit cannot exceed the corresponding rated values of the weakest of its series connected components. However, for each circuit or compartment, advantage may be taken of apparatus limiting the short-circuit current, such as current-limiting fuses, reactors, etc. 5.2.2.6. Rated duration of short circuit The intervals of time for which switchgear and controlgear can carry, in the closed position, a current equal to its rated short-time withstand current. The standard value of rated duration of short circuit is 1 s. If it is necessary, a value lower or higher than 1 s may be chosen. The recommended values are 0.5 s, 2 s and 3 s. 5.2.2.7. Rated supply voltage of closing and opening devices and auxiliary circuits 5.2.2.7.1. General The supply voltage of closing and opening devices and auxiliary and control circuits shall be understood to mean the voltage measured at the circuit terminals of the apparatus itself during its operation, including, if necessary, the auxiliary resistors or accessories supplied or required by the manufacturer to be installed in series with it, but not including the conductors for the connection to the electricity supply. NOTE The supply system should preferably be referenced to earth (i.e. not completely floating) in order to avoid the accumulation of dangerous static voltages. The location of the earthing point should be defined according to good practice. 5.2.2.7.2. Rated supply voltage (Ua) The rated supply voltage should be selected from the standard values given in Tables 5-6 and 5-7. The values marked with an asterisk are preferred values for electronic auxiliary equipment. Table 5-6: Direct current voltage Ua [V] 24 48* 60 110* or 125 Table 5-7: Alternating current voltage Three-phase, three-wire or Single-phase, three-wire 36 Single-phase, two-wire four- wire systems [V] – 120/208 (220/380) 230/400* (240/415) 277/480 347/600 systems [V] 120/240 – – – – – – systems [V] 120 120 (220) 230* (240) 277 347 NOTE 1 The lower values in the first column of this table are voltages to neutral and the higher values are voltages between phases. The lower value in the second column is the voltage to neutral and the higher value is the voltage between lines. NOTE 2 The value 230/400 V indicated in this table should be, in the future, the only IEC standard voltage and its adoption is recommended in new systems. The voltage variations of existing systems at 220/380 V and 240/415 V should be brought within the range 230/400 V ± 10 %. The reduction of this range will be considered at a later stage of standardization. 5.2.2.7.3. Tolerances The relative tolerance of a.c. and d.c. power supply in normal duty measured at the input of the auxiliary equipment (electronic controls, supervision, monitoring and communication) is 85 % to 110 %. For supply voltages less than the minimum stated for power supply, precautions shall be taken to prevent any damage to electronic equipment and/or unsafe operation due to its unpredictable behaviour. For operation of shunt-opening releases, the relative tolerance shall comply with the requirements of 5.2.1.9 5.2.2.7.4. Ripple voltage In the case of d.c supply, the ripple voltage, that is the peak-to-peak value of the a.c. component of the supply voltage at the rated load, shall be limited to a value not greater than 5 % of the d.c. component. The voltage is measured at the supply terminals of the auxiliary equipment. 5.2.2.7.5. Voltage drop and supply interruption IEC 61000-4-29 (d.c supply voltage) and IEC 61000-4-11 (a.c supply voltage) should apply to electrical and electronic components. As far as supply interruptions are concerned, the system is considered to perform correctly if: There are no false operations; There are no false alarms or false remote signaling; Any pending action is correctly completed, even with a short delay. 5.2.2.8. Rated supply frequency of operating devices and auxiliary circuits The standard values of rated supply frequency are d.c or 50 Hz. 37 5.2.2.9. Rated filling pressure (of gas-filled compartments) This shall be the pressure in bars (gauge) assigned by the manufacturer referred to atmospheric air conditions of 20°C at which the gas-filled compartment is filled before being put into service. 5.2.2.10. Rated pressure of compressed gas supply for controlled pressure systems The preferred values of rated pressure (relative pressure) are: 0.5 MPa – 1 MPa – 1.6 MPa – 2 MPa – 3 MPa – 4 MPa. 5.2.4. Circuit breakers 5.2.3.1. General Circuit-breakers for voltages above 600V shall be either SF6 or vacuum type, whereas moulded case circuit breakers shall be used for voltages up to 600 V. Note: Oil circuit breakers are not recommended. 5.2.3.2. Connection The supply end connections to equipment will be at the top end and load end connections at the bottom. 5.2.3.3. Operating Mechanisms The circuit-breaker mechanism shall normally be motor wound spring with hand wound spring as standby. The circuit-breaker shall be capable of closing fully and latching against its rated making current. In the case of designs utilising portable jacking devices, three devices per switchboard are required subject to a minimum of one for each rating of equipment in the switchboard. Spring operated mechanisms shall have the following additional measures:a). If the circuit-breaker is opened and the springs charged the circuit-breaker can be closed and then tripped without further rewind. b). If the circuit-breaker is closed and the springs charged there shall be sufficient energy to trip, close and then trip the circuit-breaker without further rewind.. c). Mechanical indication shall be provided to indicate the state of the charging spring and main contacts. d). Motor charged mechanisms shall be provided with means for charging the springs by hand and also a shrouded push button for releasing the springs. An electrical release coil shall also be provided. 38 e). Under normal operation, motor recharging of the operating spring shall commence immediately and automatically upon completion of each circuit-breaker closing operation. The time required for spring recharging shall not exceed 3 minutes. f). It shall not be possible to close a circuit-breaker, whilst the spring is being charged. It shall be necessary for the spring to be fully charged and the associated charging mechanism fully prepared for closing before it can be released to close the circuitbreaker. g). For SF6 circuit breakers there shall be a lock-out facility incorporated when the gas pressure is low. All circuit-breaker operating mechanisms shall be fitted with an electrical shunt trip release coil and in addition a mechanical hand tripping devices. The electrical tripping and closing devices shall be suitable for operation from a power supply as stated in this Specification and shall operate satisfactorily over the ambient temperature range when the voltage at their terminals is any value within the voltage range stipulated in 5.2.2.1 All operating coils for use on the d.c supply shall be connected so that failure of insulation to earth does not cause the coil to become energised. Tripping and closing circuits shall be provided with a fuse in each pole on each unit and shall be independent of each other and all other circuits. Approved positively driven mechanically operated indicating devices shall be provided to indicate whether a circuit-breaker is in the open or closed service, isolated or earthed position. Locking facilities with padlocks shall be provided so that the circuit-breaker can be prevented from being closed when it is open and from being manually tripped when it is closed. These facilities shall not require the fitting of any loose components prior to the insertion of the single padlock required. It shall not be possible, without the aid of tools, to gain access to the tripping toggle or any part of the mechanism which would permit defeat of the locking of the manual trip. It shall not be possible to lock mechanically the trip mechanism so as to render inoperative the electrical tripping. 5.2.3.4. SF6 Circuit-Breakers Circuit-breakers employing SF6 gas as an interrupting medium shall operate on the principle of self-generated gas pressure for arc extinction. The rate of gas leakage per annum shall be guaranteed and shall not be greater than 1% for any compartment. Means of confirming the existence of adequate gas density in the circuit-breakers shall be available without removing the unit from service. The system of gas monitoring shall be temperature compensated and shall be to the approval of the Engineer. Suitable facilities shall be included for replenishing the volume of SF6 gas should this be necessary due to leakage. Absorption of moisture and the decomposition products of the gas shall be achieved by integral filters. 39 5.2.3.5. Vacuum Circuit-Breakers Circuit-breakers employing the vacuum interruption principle shall incorporate vacuum bottles of declared and established manufacture. Each interrupter shall be capable of individual adjustment for correct operation and easily removed for maintenance or replacement. Full instructions for monitoring the state of vacuum and contact life shall be provided to the approval of the Engineer. Vacuum bottles shall not require the addition of insulation or stress shielding to achieve the necessary dielectric strength externally and shall not be mechanically braced by components which may reduce the integrity of the insulation across the open gap. Further reference is available in IEC 62271 series 5.2.3.6. Moulded case circuit breakers This section covers single- or multi-pole moulded case circuit breakers for use in power distribution systems, suitable for panel mounting, for rating up to 1000A, 600V, 50Hz; a). The circuit-breakers shall comply with IEC 60947; b). The continuous current rating, trip rating and rupturing capacity shall be as specified; c). The contacts shall be silver alloy and shall close with a high pressure wiping action; d). Where specified, the circuit breaker shall be capable of accommodating factory fitted shunt trip or auxiliary contact units or similar equipment; e). The operating handle shall provide clear indication of “ON‟”, “OFF” and “TRIP” positions; f). The mechanism shall be of the TRIP-FREE type preventing the unit from being held in the ON position under overload conditions; g). All moulded-case circuit breakers in particular installation as far as practical are to be supplied by a single manufacturer; h). The incoming terminals of single-pole miniature circuit breakers shall be suitable for connection to a common busbar; i). The circuit breaker shall have a rating plate indicating the current rating, voltage rating and breaking capacity. For further reference on moulded circuit breakers see IEC 60947 series. 40 5.2.5. Disconnector/Isolator 5.2.4.1. Guide to the selection of disconnector and earthing switches 5.2.4.1.1 Selection Criteria For the selection of disconnectors and earthing switches the following conditions and requirements at site should be considered: a). b). c). d). e). f). g). h). Normal current load and overload conditions; Existing fault conditions; Static and dynamic terminal loads resulting from the substation design; Use of rigid or flexible conductors to be connected to the disconnector or earthing switch or to which the separated contact is mounted; Environmental conditions (climate, pollution, etc.); Altitude of the substation site; Required operational performance (mechanical endurance); Switching requirements (bus transfer current switching by disconnectors, induced current switching by earthing switches; short-circuit making capacity of earthing switches). 5.2.4.2. Requirements in respect of the isolating distance of disconnector For reasons of safety, disconnectors shall be designed in such a way that no dangerous leakage currents can pass from the terminals of one side to any of the terminals of the other side of the disconnector. This safety requirement is met when any leakage current is led away to earth by a reliable earth connection or when the insulation involved is effectively protected against pollution in service. NOTE: It is usual that the isolating gap of a disconnector is longer than the phase-to-ground insulating distance since IEC 62271-1 specifies higher withstand test levels across the isolating distance than for the phase-to-ground insulation. Where a long creepage distance is required, the phase-to-ground insulation distance should become longer than the isolating gap. For such cases, to maintain low probability of disruptive discharge across the isolating gap, the use of protective devices such as surge arresters or rod gaps may be necessary. 5.2.4.3. Operation of disconnectors and earthing switches - Position of the movable contact system and its indicating and signalling devices 5.2.4.2.1. Securing of position Disconnectors and earthing switches, including their operating mechanisms, shall be designed in such a way that they cannot come out of their open or closed position by gravity, wind pressure, vibrations, reasonable shocks or accidental touching of the connecting rods of their operating system. 41 Disconnectors and earthing switches shall permit temporary mechanical locking in both the open and closed position for safety purposes (for example maintenance). NOTE: This last requirement need not be met in the case of disconnectors or earthing switches that are operated by means of a hook-stick. 5.2.4.2.2. Additional requirements for power-operated mechanisms Power operated mechanisms shall also provide a manual operating facility. Connecting a handoperating device (for instance a hand crank) to the power-operated mechanism shall ensure safe interruption of the control energy to the power-operated mechanism. 5.2.4.2.3. Indication and signalling of position Indication and signaling of the closed and open position shall not take place unless the movable contacts have reached their closed or open position, respectively: and the first paragraph of clause 5.2.4.2.1 (securing of position) is fulfilled. 5.2.4.2.3.1. Indication of position It shall be possible to know the operating position of the disconnector or earthing switch. For the open position this requirement is met if one of the following conditions is fulfilled: the isolating distance or gap is visible; the position of each movable contact ensuring the isolating distance or gap is indicated by a reliable visual position indicating device. 5.2.4.4. Electrical position signalling by auxiliary contacts A common signal for all poles of a disconnector or earthing switch shall be given only if all poles of the disconnector or earthing switch have a position in accordance with 5.2.4.2.3. Where all poles of a disconnector or earthing switch are mechanically coupled so as to be operable as a single unit, it is permissible to use a common position-indicating device. 5.2.4.5. Maximum force required for manual operation The values given below also apply to maintenance and operation of normally motor-operated disconnector and earthing switches. NOTE: These values include ice-breaking, if applicable. The operating height above servicing level should be agreed between manufacturer and user. 5.2.4.6. Operation requiring up to one revolution The force needed to operate a disconnector or earthing switch requiring up to one revolution (swing lever for example) should not exceed 250. A peak value of 450 N is accepted during a rotation of 15° maximum. 42 5.2.4.7. Dimensional tolerances For the mounting dimensions and the dimensions of high-voltage connections as well as the earthing connections of disconnector and earthing switches, the tolerances given in ISO 2768-1 shall apply for linear and angular dimensions. 5.2.4.8. Mechanical operating tests Operating tests are made to ensure that the disconnector or earthing switches show the specified operating behaviour within the specified voltage and supply pressure limits of their operating mechanisms. During these tests, which are performed without voltage on, or current flowing through the main circuit, it shall be verified that the disconnector or earthing switches open and close correctly when their operating mechanisms are energized. The tests shall be performed according to IEC 62771-102. The mentioned test programme shall be performed only once. During these tests no adjustment shall be made and the operation shall be faultless. The closed and open position shall be reached with the specified indication and signaling during each operating cycle. After these tests, no parts of the disconnector or earthing switch shall be damaged. For disconnector and earthing switches with a rated voltage of 52 kV and above, the mechanical operating routine tests may be performed on sub-assemblies. Where mechanical routine tests are performed on separate components, they shall be repeated at site on a complete assembled disconnector during the commissioning tests. The same total number of operations as specified in IEC 62771-102 shall be performed. NOTE: The mechanical operating test will not be representative for the operating conditions in the substation when complicated linkages are used between the point of operation and the switchgear and when the bearings are mounted to weak supports. 5.2.6. Fuses Fuses for use in distribution systems shall be as per ZS 746 -1 and ZS 746-2. 5.3 Busbars 5.3.1. General A busbar is a low-impedance conductor to which several electric circuits can be separately connected. NOTE: The term busbar does not presuppose the geometrical shape, size or dimensions of the conductor. A main busbar is a busbar to which one or several distribution busbars and/or incoming and outgoing units can be connected. A distribution busbar is a busbar within one section which is connected to a main busbar and from which outgoing units are supplied (see IEC 60439-1) Three phase busbars and one neutral busbar shall be provided in accordance with SANS 43 10198. At the lower end of the compartment an earth bar shall be provided to which all metal parts of the substation are to be bonded. The neutral of the substation shall be connected to the earth bar at one point only by means of a removable link. Provision shall be made to connect the substation earth to the earth bar. 5.3.2. Busbars Indoor Type 5.3.2.1. Current rating a) The maximum allowable temperature of busbars (including joints) carrying full load current in an ambient temperature as specified shall not exceed 80°C taking into consideration a maximum ambient temperature of 40°C in Zambia. ; 5.3.2.2. Mounting The rating and fixing of busbars shall be designed to withstand mechanical and temperature stresses during fault conditions. 5.3.2.3. Neutral busbar The current density in the neutral busbar shall under the specified earth fault conditions not exceed 200A/mm2 for a rated duration of short circuit of 1s and 125A/mm2 for a rated duration of short circuit of 3s. The neutral shall be terminated by an adequate terminal intended for the connection to the earth system of the installation, refer to IEC 60298. 5.3.2.4. Street lighting busbars The street lighting busbar shall have a cross-sectional area equal to that of a phase busbar. The busbar shall be of standard mounting and insulated. 5.3.2.5. Busbar connections Conductor ends will be terminated in accordance with SANS 1213. 5.3.2.6. Screws, bolts and nuts a) All bolts and screws shall be cadmium plated yellow passivated stainless steel grade 304 to BSS standards; b) All nuts and washers shall be electro-plated; c) Coach screws shall be electro-plated galvanized; d) All bolts, nuts, screws shall have ISO threads; e) The largest possible size bolt that will fit into holes in lugs and fixing holes of equipment shall be used; f) Bolts shall be of sufficient length so that at least two but not more than five threads 44 protrude beyond the nut. For voltages less than 1000 V, the guidelines in the following table must be used. 5.3.3. Busbars Outdoor Type The busbars shall consist of either stranded conductors or tubes. Stranded conductors having hollow cores shall not be used. Material used for busbars, busbar connections and their supports, whether insulated or otherwise, shall not be stressed beyond two fifths of its elastic limit or its 0.1% proof stress whichever is applicable. Satisfactory provision shall be made for expansion and contraction of busbars connections with variation in temperature. The maximum permissible temperature of unprotected bare busbars or busbar connections when carrying rated current shall be 85 oC. All busbar connections shall be kept as short and as straight as possible. The design of connections to busbars and other equipment shall be such as to permit easy dismantling for maintenance purposes. The busbars shall be so arranged that they may be extended in length without difficulty. All clamps and fittings necessary for attaching the busbars and busbar connections to either insulated supports, together with all connectors, terminals and accessories required for attaching the connections to the busbars, switchgear, transmission lines and power transformer bushings shall be provided. Where dissimilar metals are connected approved bi-metal clamps shall be provided to prevent electrochemical action or corrosion. Stranded copper connections shall be tinned at clamping points. The open ends of all tubes shall be fitted with end caps. Busbar supports shall be designed and constructed so that resonant vibrations are eliminated or reduced to negligible proportions. Overhead conductors carried by substation structures shall be erected with such sags and tensions that the maximum loading of structures is not exceeded when the conductors, at minimum temperature, are subjected to maximum transverse wind pressure and of fault currents on the whole projected area. Copies of the conductor sag charts and calculations relating to the design of tubular busbar systems shall be submitted to the Engineer for approval. Where bolted connections are used for current carrying joints torque spanners shall be used for tightening bolts and nuts. Also where necessary washers shall be provided under bolt heads and nuts to spread the load and reduce the effect of compressive creep under pressure. Torque value must be quoted on drawings. Where current carrying surfaces of alloy connections are bolted together such surfaces shall have the oxide film removed and shall be cleaned and de-greased. A coating of approved jointing compound shall be applied to contact surfaces and voids before bolting. Copperconnectors shall be tinned 45 5.4 Controlgear 5.4.1 Equipment Cubicles and Ancillary Apparatus 5.4.1.1 General All cubicles shall be manufactured from enameled sheet and protection classification at least IP3X. Each item of equipment mounted on each cubicle shall be positioned to allow full and easy access to the item and to all equipment adjacent of it. All equipment shall be mounted not more than 2 metres and not less than 500 mm from the floor. Subject to the approval of the Engineer one cubicle may accommodate equipment associated with two primary circuits. In this case a vertical barrier must be provided inside the cubicle to segregate the wiring and equipment associated with each primary circuit. If 400V connections are taken through a cubicle they shall be adequately screened or insulated and a “400 Volts DANGER” notice shall be fixed on the outside of the cubicle. Cubicle doors shall be hinged to lie back flat to avoid restricting access. Hinges shall be of the lift-off type. Doors shall be secured by means of handles and locking facilities shall be provided to the approval of the Engineer. Each cubicle shall have an interior light fitted to illuminate all apparatus inside the cubicle without dazzle. The interior lights in each suite of cubicles shall be controlled by a switch complete with indicating lamp which shall be mounted prominently at one end of the suite. All cubicles shall be complete with all necessary labels fitted to the front & back to describe the function of the equipment which shall be approved by the Engineer. 5.4.1.2 Control switches Control switches for electrically operated circuit-breakers shall be of the pistol grip or discrepancy type and shall be arranged to operate clockwise when closing the circuit-breakers and anti-clockwise when opening them. The control switches shall be so designed as to prevent them from being operated inadvertently and where switches of the discrepancy type are used they shall require two independent movements to effect operation. The control switch shall be so designed that when released by the operator it shall return automatically to the “neutral” position after having been turned to the “closed” position and shall at the same time interrupt the supply of current to the operating mechanism of the circuit-breaker. Switches for other apparatus shall be operated by shrouded push buttons or have handles of the spade type, the pistol-grip type shall be reserved for circuit-breaker operation only. Control, reversing, selector and test switches shall be so mounted, constructed and wired as to facilitate the maintenance of contacts without the necessity for disconnecting wiring. 46 5.4.1.3 Instruments All instruments shall be of the flush mounting type, dust and moisture proof, 96mm DIN square cases complying with IEC 60051, and shall be fitted with non-reflecting glass. All instruments and apparatus shall be capable of carrying their full load currents without undue heating. They shall not be damaged by the passage of fault currents within the rating of the associated switchgear through the primaries of their corresponding instrument transformers. All instruments and apparatus shall be back connected and all cases shall be earthed. Means shall be provided for zero adjustment of instruments without dismantling.. All voltage circuits to instruments shall be protected by a fuse in each unearthed phase of the circuit placed as close as practicable to the instrument transformer terminals or, where instruments are direct-connected, as close as practicable to the main connection. All power factor indicators shall have the star point of their current coils brought out to a separate terminal which shall be connected to the star point of the instrument current transformer secondary windings. Electrical energy meters where specified shall be of static type, class 0.5s, complying with ZS 644 (ZS IEC 62053-22). They shall be 3-phase instruments with two measuring elements and equipped with operation monitoring indicators. Where maximum demand indicator has been specified the measuring period shall be capable being selected either 30min or 60min. All indicating instrument scales shall be long, clearly divided and indelibly marked and the pointers shall be of clean outline. The marking on the dials shall be restricted to the scale marking. In general, instrument dials should be white with black markings. Scales shall be of such material that no peeling or discolouration will take place with age under humid tropical conditions. Instrument scales shall be submitted for the approval of the Engineer. Kilowatt-hour integrating meters shall comply with the requirements of ZS 643 (ZS IEC 6205321) unless otherwise approved by the Engineers. Cyclometer type registers including a minimum of five drums reading whole kWh shall be provided. 5.4.1.4 Indications and Alarms Indicators shall operate reliably at voltages down to 80 per cent of nominal. A trip circuit supervision scheme shall be provided for each circuit and shall be arranged to monitor the continuity of the circuit-breaker or fault throwing switch trip coil and as much of the associated tripping wires as possible. The scheme shall be to approval. Annunciated alarms and indications shall be by lamps illuminating a legend and shall operate from the battery specified. The annunciation shall be grouped, each group containing the alarms and indications associated with the particular switchgear concerned. There shall be two push buttons for each group of annunciation, one for “Accept” and the other for “Reset”. When an 47 alarm is originated the lamp shall flash, an audible alarm shall sound and a flashing amber beacon mounted on the substation roof shall be activated. On operation of the “Accept” key the lamp shall cease to flash and shall give a steady illumination and the audible and visible alarms shall cease unless already cancelled by the common cut off key. A distinction shall be made between functions by the use of the following colours: Red .... Amber .... White .... Trip Alarm Indication The lettering should show white on a dark background or black on an illuminated background. In the former case the amber or red shall show as a bar of approximately 3 mm below the inscription. Where it is desired to include fire alarms in an annunciator group, the facias surround should be coloured red. The duration of the flash shall be such that the legend may be easily read and the speed of flashing shall not exceed three times per second. An alarm whose initiating device does not reset until the abnormality is remedied shall remain illuminated until the initiating device is reset, when it shall be extinguished without the use of the reset key. Annunciations which arise from signals of short duration (fleeting alarms) shall not restore when the initiating contact restores. It shall be necessary to operate the reset key to clear these. The reset key shall not be effective until after the alarm has been accepted. If a fleeting alarm is re-operated after acceptance but before resetting, the annunciation shall return to the flashing condition. The annunciation circuit shall be readily adaptable for use with a fleeting or persistent initiating signal. Facilities shall be provided for lamp test. The lamp test shall include a test for all spare windows, which shall be identifiable as such under test conditions. At each 33/11 kV substation, facilities shall also be provided to extend a common substation alarm into a remote supervisory system. As a minimum requirement the following signals shall initiate the audible and visible alarms at the 33/11 kV substations. a). b). c). d). e). f). g). Circuit-breaker tripped Trip circuit failed Battery charger failed Low battery volts Transformer gas relay operated Transformer high winding temperature Transformer overpressure 48 h). i). Tap-changer relay operated Transformer automatic voltage control panel VT supply failed. 5.4.1.5 Indicating lamps Indicators shall be of the LED or type and all colours shall be to approval by the Engineer. Filament types may be considered but not encouraged. LED indicators shall operate at not less than 20mA and red LED indicators shall be of the high brightness type. The rated lamp voltage should be ten percent in excess of the auxiliary supply voltage, whether AC or DC. The lamp glasses shall be in standard colours (IEC 60073): red, green, blue, white and amber. The colour is to be in the glass and not applied coating and the different coloured glasses are not be interchangeable. Transparent synthetic materials may be used instead of glass, provided such materials have fast colours and are completely suitable for use in tropical climates. Normally energized indicating lamps, if employed, shall in general be energized from the station LV AC supply. In addition, facilities shall be provided for manual changeover from the AC supply to the station DC supply via an automatically resetting switch arranged to reset after a time interval of approximately five minutes. Lamps and relays incorporated in alarm facia equipment may be arranged for normal operation from the station battery, subject to the approval of the Engineer. Lamp test facilities shall be provided so that all lamps on one panel can be tested simultaneously by operation of a common key. Where alarm facias are specified, all alarm and monitoring indications, apart from CB and disconnector position indications, shall be incorporated in the facia. All indicating lamps and lamp holder assemblies shall be suitable for continuous operation at the maximum site ambient temperature. Indicating lamps and lamp holders shall be arranged so that replacement of lamps and the cleaning of glasses and reflectors can be readily effected. To reduce heating and fouling of the panels, lamps which are continuously alight shall have the minimum consumption consistent with the good visibility of indications in a brightly-lit room. Indicating lamp glasses on control and relay panels shall conform to the following standard colour code:Red .... Circuit-breaker closed Green .... Circuit-breaker open White .... Indications normally alight 49 Amber .... Alarm indications (on which an action is necessary) 5.4.1.6 Relays, fuses, links and ancillary apparatus All relays for front of panel mounting shall be flush pattern. Where practicable the clearances between relay stems or connecting studs shall not be less than 30 mm and in no case less than 25 mm. Relays associated with the three phases shall be marked with the appropriate phase identification and the fuses and links shall also be suitably labelled. Isolating links and fuses shall be provided on each panel to facilitate the isolation of all sources of electrical potential, to allow testing or other work to be carried out on the panel without danger to personnel or interference with similar circuits on other panels. All fuses and links shall be accommodated within the cubicle. Fuses and links shall be grouped and spaced according to their function in order to facilitate identification. As an alternative to fuses and links miniature circuit-breakers will be accepted. Links in current transformer circuits shall be of the bolted type. All incoming circuits in which the voltage exceeds 125 volts shall be fed through insulated fuses and/or links, the supply being connected to the lower terminal. The contacts of the fixed portion of the fuse or link shall be shrouded so that accidental contact with live metal cannot be made when the moving portion is withdrawn. Resistance boxes shall be so mounted inside the cubicle that their adjustment screws are on a vertical and accessible face. Resistances shall be provided with stud terminals. Set screws shall not be used. 5.4.1.7 Earthing arrangements All control and relay panels shall have a continuous earth bar of a sectional area of not less than 75 mm2 run along the bottom of the panels, each end being connected to the main earthing system. All metal cases of equipment on the panels shall be connected to this bar by conductors having a sectional area not less than 2.5 mm2. Current transformer and voltage transformer secondary circuits shall be complete in themselves and shall be earthed at one point only through links situated in an accessible position. Each separate link shall be suitably labelled. The links shall be of the bolted type with provision for attaching test leads. 5.4.1.8 Auxiliary Switches Where appropriate, each item of plant is to be equipped with all necessary auxiliary switches, contactors and mechanisms for indication, protection, metering, control, interlocking, supervisory and other services. All auxiliary switches are to be wired up to a terminal board on the fixed portion of the plant, whether they are in use or not in the first instance. 50 The number of switches to be provided shall be determined to cater initial installation and allow for all anticipated future extensions. 5.4.1.9 Cable terminations 5.4.1.9.1 General All junction boxes, terminal boxes and marshalling kiosks shall be constructed of steel. All main equipment shall be arranged so that it is accessible from the front of the box or kiosk. 5.4.1.9.2 Outdoor Boxes and Kiosks Outdoor boxes and kiosks shall have domed or sloping roofs and the enclosure shall be of IP54 protection classification with adequate ventilation and draining facilities. They shall be so designed that condensation does not affect the insulation of the apparatus, the terminal boards or the cables. Where necessary, heaters shall be provided. Where these exceed 40 watts, they shall be controlled by means of a switch mounted on the outside of the box or kiosk. Any divisions between compartments inside the boxes or kiosks shall be perforated to assist the natural air circulation. If the width of the box necessitates the provision of two hinged front covers they shall close on to a centre post which shall be removable to facilitate cable termination. The depth of the outer case shall be not less than 200 mm unless otherwise approved. The outer cases shall be treated before painting to prevent corrosion and shall be finished in glossy enamel to colour approved by the Engineer. Access shall be provided at both the front and back of kiosks and junction boxes except for small terminal boxes of the type normally employed for wall mounting. Doors and access covers shall be easily opened and shall not be secured by nuts and bolts. Doors and covers under 14 kg in weight may be of the slide-on pattern; above this weight they shall preferably be hinged. Kiosk doors shall be fastened with integral handles. Nuts, bolts or carriage keys shall not be used. Provision shall be made for padlocking each door. 5.4.1.10 Terminal boards All terminals boards shall be mounted in accessible position and, when in enclosed cubicles, are preferably to be inclined towards the door. Spacing of adjacent terminal boards shall be not less than 100 mm and the bottom of each board shall be not less than 200 mm above the incoming cable gland plate. Separate terminations shall be provided on terminal boards for the cores of incoming and outgoing cables including all spare cores. Not more than two cores may be connected to any one terminal. Where bridging connections are necessary, these shall be incorporated in the terminal boards. 51 For terminations modular terminals, Weidmueller type (or approved equivalent) SAK 2.5/35 or SAK 4/35 (the latter for CT circuits) shall be provided. Current transformers shall be connected in two parallel terminations in the way that test instrument can be connected in the CT circuit without a need to short circuit that particular CT. 10 percent spare terminals shall be provided 400/230 V circuit terminals shall be segregated from other terminals and shall be fitted with non-flammable plastic covers to prevent contact with any live parts. They shall have warning labels, with red lettering, mounted thereon in a conspicuous position. 5.4.1.11 Cable Entry All cables shall enter boxes and kiosks at the base via removable gland plates. Conduits shall not be run at or below ground level but shall wherever practicable enter boxes or kiosks near the base. Plates for supporting cable glands shall be at least 450 mm above ground level. Means shall be provided to drain water off the surface of the gland plate. The back, sides and front of the box or kiosk shall project at least 50 mm below the gland plate to prevent moisture draining on to the plate and cable glands. 5.4.1.12 Small Wiring All control and relay panel wiring, secondary control wiring in CBs, motor starters, controlgear and the like shall be carried out in a neat and systematic manner with cable supported clear of the panels and other surfaces at all points to obtain free circulation of air. In all cases, the sequence of the wiring terminals shall be such that the junction between multicore cables and the terminals is accomplished without crossover. For wiring inside cabinets PVC-insulated single core non-sheathed cable with single-wire copper conductor, cross section 1.5 or 2.5 mm2, type H07V-U (GENELEC standard HD 21.S2 and IEC 227-3) shall be used. Multi-stranded flexible conductor cable shall be employed where connections are subject to movement or vibration during shipment, operation or maintenance. All wires shall be fitted with numbered ferules of approved type at each termination. At points of inter-connection between wiring, where a change of numbering cannot be avoided, double markers shall be provided. Such points shall be clearly indicated on the wiring diagram. The markers on all wiring directly connected to circuit breaker trip coils, tripping switches, etc., shall be of a colour, preferably red, different from that of the remainder and marked "trip". No wires may be teed or jointed between terminal points. Bus wiring between control panels, etc., shall be fully insulated and completely segregated from the main panel wiring. 52 All metallic cases of instruments, control switches, relays, etc., mounted on control panels or in cubicles shall be connected by means of copper conductors of not less than 2.5 mm2 section to the nearest earth bar. These conductors shall have yellow/green coloured insulation. 5.4.2 Protective Relays and Associated Apparatus 5.4.2.1. General Protective equipment shall be designed to disconnect faulty circuit with speed and certainty without interference with healthy circuits. They shall also be so designed that when properly applied incorrect operation of the circuit-breakers does not occur as a result of transient phenomena not arising from a faulty condition of the section of line or plant associated with each set of relays but which may occur during fault periods due to disturbances on the system. The equipment owner shall be responsible for ensuring the correct operation of the protective equipment and shall submit for approval recommended relay settings supported by design calculations for all protective equipment being supplied. 5.4.2.2. Protective Relays 5.4.2.2.1. General All d.c relays used for tripping shall operate when the supply voltage is reduced to not less than 60% or raised up to 120% of rated voltage. All relays shall be capable of withstanding voltages up to 120% of rated voltage. In order to minimise the effect of electrolytic corrosion, indicator coils and d.c. relay operating coils shall be so placed in the circuit that they are not connected to the positive pole of the battery except through contacts which are normally open. 5.4.2.2.2. Protection Settings Unless otherwise specified the equipment owner shall calculate maximum and minimum short circuit currents in faults at all substation buses. Based on the results of these calculations the Equipment owner shall prepare a table of all settings for relays in those substations which belong to the scope of the particular Contract. This table of settings shall be submitted to the Engineer and Employer for approval prior to commissioning of any plant. The Equipment owners shall co-operate closely in determining relay settings. 5.4.2.2.3. Form of Relays All relays shall be contained in dustproof cases. Relays shall be of solid state type and shall be drawout pattern, modular construction for flush mounting in standard racks. All metal bases and frames of relays shall be earthed except where the latter must be insulated for special requirements. This specification applies particularly to stand alone relays, but relays forming part of a comprehensive measurement/protection/ interlocking system may be proposed where overall advantages can be offered. . 53 The relays shall be so arranged that replacements can be effected quickly and with the minimum amount of labour. Relay equipment incorporating electronic devices shall be arranged to plug in and shall have positive means for retaining them in the service position. Equipment incorporating telephone type relays shall have similar facilities. All relays shall be arranged so that provided reasonable care is taken any dust which may have collected in or upon the case shall not fall on the relay mechanism when opening the case. Where relays are required to operate with a time delay the delaying apparatus shall not be of the dashpot type. 5.4.2.2.4. Performance Requirements Relays shall provide the electrical characteristics, repeatability, immunity to harmonics, transients and interference, and environmental protection needed to ensure that system performance can be achieved. The system performance requirements will be defined in procurement schedules, and the relays and other components shall be designed to provide the degree of discrimination, back-up and supply integrity required. 5.4.2.2.5. Reliability The Tenderers shall quote the reliability for each device offered, in terms of designed mean time to failures. This figure shall be used in evaluating the reliability of the overall system, the requirement for which shall be defined in specifications covering system design. 5.4.2.2.6. Maintainability Relays shall be designed to facilitate first line on-site maintenance, by provision of diagnostic features and the facility to replace modular elements. As far as practicable any relay fault shall be indicated by an alarm, which shall give a local indication and facility to transmit a signal on the SCADA system. Maintenance should be possible without disturbing any wiring connections or requiring other items of plant to be disconnected. Equipment owners shall provide details of any special test equipment required for site or workshop maintenance and give recommended maintenance procedures. 5.4.2.2.7. Setting The relays shall be capable of being set to cover a range of main circuit parameters, and should generally be selected such that setting ranges give scope for adjustment either side of the design setting. Settings shall be effected at the relay and by a remote link if provided. Any such link shall include a facility to give remote readings of settings. Settings shall be effected by switches or by input of digital data; conventional potentiometers shall not be used for settings. The settings shall be clearly indicated at the relay, either by the position of switches or by a digital display. It shall be possible to alter settings with the relay in service. Loss of electrical supplies to the relay shall not result in loss of settings for a period of 30 days. 5.4.2.2.8. Relay Contacts The contacts of all relays shall be capable of making the maximum current which can occur in the circuit which they have to control. They shall also be capable of breaking such currents 54 unless provision is made for breaking the current on contacts elsewhere in the circuits. Relays shall not be affected by mechanical shock or vibration or by external magnetic fields consistent with the place or method of mounting. The contacts shall be capable of repeated operation without deterioration. Unless otherwise agreed all protective relays which initiate tripping shall have not less than two independent pairs of contacts of which one shall operate the tripping relay or circuit-breaker trip coil without the interposition of auxiliary contactors and without the use of reinforcing contactors. 5.4.2.2.9. Tripping and Lock-out Relay operations shall cause trips or lock-out of main circuits, as required by the equipment schedules. Once initiated the trip signal shall persist until the trip circuit is interrupted by opening of a normally open auxiliary contact on the circuit-breaker or device being tripped. 5.4.2.2.10. Indication of Operation All relays which are connected to complete either the tripping circuit of circuit-breaker or the coil circuit of an auxiliary tripping relay shall be provided with operation indicators. Indication of operation of each element shall be given at the relay, and via the SCADA system. The local indication shall be maintained for a period of 30 days if the electrical supplies to the relay are lost. The remote indication shall be maintained for at least 500 ms, to ensure detection by the SCADA system, and shall reset after no longer than 5 seconds. Indicators shall also be provided on such additional relay elements as will enable the type or phase of the fault condition to be identified. Each indicator shall be capable of being reset by hand without opening the relay case and it shall not be possible to operate the relay when resetting the operation indicator. Each indicator shall be designed so that it will not move before the relay has completed its operation. Indicators shall be clearly visible from the front when operated and concealed at all other times. 5.4.2.2.11. Indication of Protective Relay Failure Internal relay faults shall be diagnosed and shall be indicated by a non-volatile device on the relay. Failure shall also operate a pair of normally open contacts, which may be used either for remote indication or for tripping, as required by the equipment schedules. Failure of any auxiliary supply to the relay shall also be indicated on the relay and shall cause the normally open contacts to operate. Such contacts shall be commoned to provide a single remote alarm of protection equipment failure for each switchboard. 5.4.2.2.12. Facility for Resetting Alarm and trip contacts shall reset automatically on removal of the signal causing the operation. Lock-outs shall have facility for manual resetting at the relay, and for resetting via the SCADA system when called for in the equipment schedules. Local indications of operation shall be reset at the relay. Remote indications of operation shall reset as required in 4.7 above. 55 All relays which are of the hand reset type shall be capable of being reset without the necessity of opening the case. It shall not be possible to operate any relay by hand without opening the case. 5.4.2.2.13. Location of Relays Where practicable relays shall be mounted on the door of a control compartment above the circuit to which they apply. Where this is not practicable, relays may be fitted to separate cubicles. The arrangement of such cubicles will be specified according to site arrangements; they may be free standing, in which case relays should be fitted to fixed front panels with maintenance access via rear doors, or they may be wall mounted, in which case relays shall be fitted on hinged door panels. 5.4.2.2.14. Relay Cases Relay cases shall be of standard height of 177 mm, complying with IEC 297, size 4U, and for mounting on standard 483 mm racks. Covers shall be fitted and shall have provision for sealing to prevent unauthorised access. Manual resetting and inspection of indications and settings shall be possible with the covers in place, but any adjustment shall require removal of covers. With covers in place the degree of enclosure of the relay shall be IP52 to BS 5490. 5.4.2.2.15. Terminals Relay terminals shall accept ring type terminals with an M4 or larger screw fixing. Barriers shall be provided between terminals, and voltage withstand and current rating shall be in accordance with the circuit ratings and test values. 5.4.2.2.16. Test Blocks Test blocks associated with each circuit breaker relay panel shall be provided to permit testing of all functions, and shall be accessible from the front of the equipment. Test blocks shall accept a multi-outlet test plug, which shall accept 4 mm plugs for interconnection and external connection. 5.4.2.2.17. Tripping Arrangements Trip circuits shall be of series seal-in type, and shall be operated from the substation batteries, at voltages as defined in equipment schedules. 5.4.2.2.18. CT Circuits Relay cases shall be fitted with devices to short out CT windings automatically on withdrawal of relays, so that at no time is the CT secondary winding left open circuited. 5.4.2.2.19. Labelling and marking All relays shall either be suitably marked or shall have a label nearby with the following information: a). b). Function of relay Phase identification of the current supply 56 c). d). e). Characteristic curve where appropriate Rated current and voltage of the relay coils Rated making capacity of tripping contacts. Items (a) and (b) above shall be visible from the front without removing the cover. 5.4.2.2.20. Overcurrent & Earth Fault relays Where specified inverse definite minimum time (IDMT) overcurrent relays shall be provided for overcurrent and earth fault protection. They shall be of static type. Overcurrent relays shall be of the three pole type and shall be of the inverse definite minimum time limit (IDMTL) pattern with separate adjustable time and current settings. The time/current characteristic of all IDMTL relays shall be to BS 142 normal inverse curve. The directional overcurrent relays shall have the appropriate technical capability to ensure correct operation during a close three-phase fault. Relay directional elements which are designed to be energised normally by voltage and current when carrying any current between zero and 15 times rated current shall take up such a position that the contacts are open when the voltage coil is not energised. Relays should have adjustable settings for both operating current and time. The range of current settings for phase faults shall be 50-200 per cent of rated current and the time setting adjustment shall be 0.3 to 3 s at ten times the setting current. Inverse time earth fault relays, where specified, shall have a range of settings from 10 to 40 % of rated current. 5.4.2.2.21. Balanced Earth fault relays Balanced earth-fault relays shall be instantaneous in action unless otherwise specified. The arrangement however shall be such that the relay is stable under „transient‟ conditions. 5.4.2.2.22. Automatic Reclosing of 11& 33 kV Lines Where specified the relay protection for 11&33kV overhead lines shall be equipped with autoreclose relay which shall perform high speed and delayed auto-reclose. The dead time for high speed stage shall be adjustable from 0.1 s to 5.0 s and that for delayed stages from 5 s to 180 s. Reclaim time shall be at least 5 s. Reclosure shall be initiated only by the earth fault relay. 5.4.2.2.23. Feeder protection with pilots Pilot wire supervision equipment to the Engineer‟s approval shall be included at all substations where pilot wire feeder protection is installed. The equipment shall include a supply fail relay, an approved test feature for the pilot monitoring relay and adequate spare contacts for remote indication. 5.4.2.2.24. Feeder protection without pilots Feeder protective equipment without pilots shall be of a discriminative type. 57 5.4.2.3. Transformer protection 5.4.2.3.1. General Current transformers which are used for transformer earth fault protection shall not be used for any other purpose unless agreed by the Engineer. 5.4.2.3.2. Earth Fault Protection Where earth fault protection having three line and one neutral current transformers is employed on the winding of a power transformers it shall be so arranged that it does not operate with any type of fault external to the transformer winding. To ensure compliance with this requirement the equipment shall be so designed that the current flowing in the relay operating coil with any type of fault having a magnitude up to the maximum figure specified shall preferably be not more than a quarter and in no case more than one-half of the current required to operate the relay when adjusted to the prescribed setting. The setting of the relay shall be such that it will operate reliably with current of the following magnitudes in the primary winding of the neutral current transformer alone:a). b). Power transformer neutral directly earthed - system voltage 72.5 kV and below - not more than 20% of the rated current. Power transformer neutral earthed through resistor or reactor - all voltages - not more than 25% of the rated current of the resistor or reactor where this rating does not differ greatly from the primary current rating of the current transformers. Where the prescribed settings cannot be obtained special approval of the performance shall be obtained. Where earth fault protection is employed for the winding of a transformer which is earthed either directly or through an earthing device the Equipment owner shall provide and fix current transformers in the neutral earthing connection of the winding of the power transformer. One such current transformer in the neutral connection shall be used for the balanced earth fault protection and wherever the neutral point of the transformer winding is not directly connected to earth standby earth fault protection shall be obtained from a second current transformer having a primary current rating of the standard value nearest to the rated current of the winding of the power transformer with which the standby earth fault current transformer is associated. 5.4.2.3.3. Differential protection Where specified Differential protection shall be of the instantaneous three winding biased differential type capable of detecting phase and earth faults. Separate facilities shall be provided to enable bias settings to be adjusted. The minimum operating setting shall not be greater than 20 % of the rated full load current of the transformer. The blocking based on the ratio of the fifth and the second harmonics shall be included in the transformer differential relay to prevent unwanted operations. No interposing transformers shall be needed. Numerical vector group matching shall be included. 58 The protection shall be designed to ensure stability on any transformer tap position under maximum through fault conditions with maximum DC offset. An infinite source is to be assumed and through fault current calculated using the transformer impedance only. The trip coils of the circuit-breakers on the primary and secondary sides of the transformer shall be so connected to the relays that the circuit-breakers shall operate together when the protective gear functions. Facilities shall be retained for independent tripping by hand of either circuitbreaker. 5.4.2.3.4. Restricted Earth Fault Protection Where specified transformer windings and connections shall be protected by REF relay of high impedance type with necessary protection against overvoltages. Relays shall be stable for faults outside the protected zone and on magnetising inrush surges. Sensitivity for solidly earthed windings shall not be greater than 60% of the winding rating, for resistance earthed windings not greater than 20% of the resistor rating. The rated stability limit shall not be less than the maximum current available for an external fault. This shall be taken as 12 times the rated current of the protected winding of the power transformer. 5.4.2.3.5. Standby earth fault Where specified standby earth fault (SBEF) shall be provided for all earthing resistors fed from a current transformer in the resistor earth connection. The operating current of SBEF-relay shall be adjustable between 20 and 100 per cent of the resistor rated current. The time delay shall be adjustable between 1 and 10 s. 5.4.2.4. Distribution Line Protection 5.4.2.4.1. Overcurrent and Earth fault protection Where specified inverse definite minimum time (IDMT) overcurrent relays shall be provided for overcurrent and earth fault protection. Overcurrent relays shall be of the three pole type and shall be of the inverse definite minimum time limit (IDMTL) pattern with separate adjustable time and current settings. The time/current characteristic of all IDMTL relays shall be to BS 142 normal inverse curve. The directional overcurrent relays shall have the appropriate technical capability to ensure correct operation during a three-phase fault. Relay directional elements which are designed to be energised normally by voltage and current when carrying any current between zero and 15 times rated current shall take up such a position that the contacts are open when the voltage coil is not energised. Relays should have adjustable settings for both operating current and time. The range of current settings for phase faults shall be 50-200 per cent of rated current and the time setting adjustment shall be 0.3 to 3 s at ten times the setting current. 59 Inverse time earth fault relays, where specified, shall have a range of settings from 10 to 40 % of rated current. 5.4.2.5. Fault event recorders When specified fault event recorder or module to an existing protection (without a printer) shall be provided. This shall store all pertinent data for the analysis of the fault by a separate computer and printer. The module shall be equipped with a low speed data interface for the remote data communication to be installed later. Where a fault locator specified shall be provided which uses the inputs available from the distance relay. The locator shall operate on the impedance to fault measuring principle. Preference will be given to schemes with following features: • Digital processing of fault and pre-fault data to calculate distance to fault. • Printed display identifying faulted line, fault type and distance to fault. 5.4.2.6. Integrated Microprocessor Based Schemes 5.4.2.6.1. Measurement-Protection-Control Microprocessor based protection relays may be offered as part of overall schemes to provide protection, control functions and monitoring. The following items are a guide to the capabilities required:• • • • • • • All protective functions for safety tripping and discrimination, Logic for interlocking and sequence operation of substation equipment and, where applicable, for reconfiguring of circuits after protective tripping, Facility for interfacing to SCADA system for remote indication of circuit loading, voltage etc., Facility for remote setting and for remote indication of setting values, Ability to retain historical data on circuit conditions and to transmit information, Facility to record exact timing of events, including all protective and alarm operations, Ability to use historical data to amend tripping levels. No failure of the remote link shall affect protective functions. The particular requirements and the details of interfaces to the SCADA system will be subject to agreement with Utility. 5.4.2.7. Tripping and Control Power Supplies 5.4.2.7.1. Supply Voltage Tripping and protective circuits shall be supplied from substation batteries and shall be at a nominal or 110 V d.c. 5.4.2.7.2. Supply Arrangements Two incoming supplies for tripping and protective equipment will normally be provided from the substation battery, and provision shall be made for connection of one supply at each of the end circuits on the switchboard, via links in each pole of the supply. A tripping supply buswire 60 shall be provided, and isolating links shall be inserted in the buswire at each bus-section switch position on the switchboard. The protective equipment on each circuit shall be connected to the supply via fuse links in each pole. The trip coil circuits and each protective relay shall be separately fused. No other circuits (i.e. auxiliary closing) shall be supplied from the tripping and protective equipment buswire. 5.4.2.7.3. Trip Circuit Supervision Trip circuit supervision shall be provided for all the 11 and 33kV circuits Depending on the extent of integrity required the schedules may call for any of the following types as specified in the Bill of Quantities:• Trip circuit monitoring for the 11 and 33kV indoor type breakers • Full trip circuit supervision for outdoor 33kV breakers. The indications to the SCADA system shall be from changeover contacts, to maintain a positive indication at all times. 5.4.3 Batteries & Battery Chargers 5.4.3.1. General DC auxiliary power supply voltage shall be 110 V for protection tripping and closing supplies. DC battery system shall comprise one 100% duty battery composed of independent cells. The supply for the battery charger may be either three phase 400 V a.c or single phase 230 V a.c. 5.4.3.2. General Design Principals 5.4.3.2.1. Performance Criteria Battery and battery charger systems must be designed for the purpose intended and to meet the requirements of all applicable National standards. The primary role of the substation battery system is to provide a source of energy that is independent of the primary ac supply, so that in the event of the loss of the primary supply the substation control systems that require energy to operate can still do so safely. The battery is required to supply the DC electrical requirements of the substation, including SCADA, control, protection indication, communications and circuit breaker switching operations when there is no output from the battery charger. This may be due to a loss of AC supply to the substation or a fault in the battery charger. Under these conditions the battery shall supply the DC loads for a minimum period of 5 hours after which time the battery should then be able to supply trip-close-trip operations of an HV circuit breaker which would typically restore supply to the battery charger. The 5 hour capacity allows for ageing and a given minimum cell voltage under load at the end of discharge. There will be nominally no remaining capacity on the battery at the end of the 5 hour period if subjected to the given duty cycle at the end of its service life. The absolute minimum requirement is that the battery has sufficient energy to allow the substation to be made safe on loss of ac supply. A secondary requirement is to provide high capacity support to the battery charger for operating high current transient loads that are beyond 61 the charger‟s capability. A substation shall comprise two battery chargers each capable of providing 100% duty. 5.4.3.2.2. Design Criteria The number of batteries provided, and the physical & electrical separation of these, shall be in accordance with Section 17.2.5 (Number of Batteries). Where a 50 V DC supply is required for substation communications systems, this shall be supplied from the 110V DC battery via a 50V DC-DC converter or an independent 50V battery. 5.4.3.2.3. Battery Configuration The battery cells shall be suitable for mounting on their bases. The battery cells shall not sit directly on the ground instead shall be mounted on the none corrosive earth bonded rack. The configuration and nominal capacity of the batteries shall be derived as follows: from a fully charged state the batteries must be capable of meeting both Duty A and Duty B as shown in the table below: Battery Type Solenoid Operated Circuit Breakers Duty A *200 Ah 20 A 5 hr Spring Operated Circuit Breakers Duty A *200 Ah 25 A 5 hr Discharge Current Discharge Time End terminal voltage not less than: Battery ageing factor 50V supply via: 150 A 10 sec 100 V 35 A 10 sec 100 V 20% dc-dc converter/independent charger unit Temperature operating range -1OC to 40 OC 20% dc-dc converter/independent charger unit -1OC to 40 OC Accommodation Cabinet / Rack in separate room Cabinet / Rack in separate room Chemistry VRLA\Lead Acid\Nickel Cadmium\ Lithium 54 124.9 V (2.23 V / cell typical) 135.0 V (2.41 V / cell typical) VRLA\Lead Acid\Nickel Cadmium\ Lithium 54 124.9 V (2.23 V / cell typical) 135.0 V (2.41 V / cell typical) Load Duty Nominal capacity Discharge Current Discharge Time Followed immediately by: Cells in series Float voltage (manufacturer specific) Boost voltage (max) (manufacture specific) 62 * These are nominal capacities only - actual battery capacities are dependent on discharge rates, final battery voltages and the type of loads to be supplied. 5.4.3.2.4. Number of Batteries Substations with duplicated protection systems shall have dual (2) battery systems – one for each protection system. Substations that do not have remote back-up protection systems shall also have dual battery systems. Substations without duplicated protection systems, and which have remote back-up protection, shall have a single (1) battery system. Where dual battery systems are provided the batteries and associated chargers, including all associated wiring, shall be kept physically and electrically isolated to ensure that potential problems with one system do not affect the other. Each battery shall have a separate dedicated charger. „A‟ and „B‟ protection systems shall be supplied by different batteries and the overall substation DC load shall be distributed as evenly as possible between the two batteries, for example „A‟ protection and SCADA supplied by battery 1, „B‟ protection, local control, protection, indication and communications, etc supplied by battery 2. 5.4.3.2.5. Cell Casing Cell casings shall be clear or translucent material fitted with safety (anti-explosion) vents. 5.4.3.2.6. Connections All bolts, nuts, fasteners and electrical connections shall be of material that is resistant to corrosion. 5.4.3.2.7. Cell Numbering Battery cells shall be numbered starting from the positive terminal i.e. cell “1” for the first cell. 5.4.3.2.8. Battery Charging Battery charging is to be strictly to the manufacturer‟s specification with no unapproved changes to the regime. 5.4.3.2.9. Accommodation 5.4.3.2.9.1. a). b). c). d). Battery Cabinets Batteries are to be accommodated in a separate ventilated room fitted with extractor fans and fire protection systems; Cabinet to be designed to facilitate front access to the batteries, with sufficient space in front of the cabinet for lifting and carrying gear for handling individual cells; Cabinet to be treated against electrolyte spill (electrolyte is gel and limited quantity, so spread under cell rupture is limited); Where multiple battery groups are provided, the batteries shall be located with sufficient separation to enable maintenance or similar activities on one battery to not adversely affect operation of the other; 63 5.4.3.2.9.2. a). b). c). d). e). f). g). h). i). j). Safety Battery rooms shall provide easy access for batteries and battery stands. In addition, battery rooms shall be dry, well lit, well ventilated and protected against the ingress of dust and foreign matter. Battery room shall have eye wash facilities. Battery rooms shall provide for possible future expansion / refurbishment, therefore it shall be located at the end of the building. Battery rooms shall be situated as near to the associated loads and rectifier equipment as possible. Every endeavor shall be made to ensure that the battery room is situated on the coolest side of the building. Separate battery rooms shall be provided for batteries with different types of electrolyte, i.e. nickel cadmium and lead-acid batteries shall not be installed in the same room. Two or more batteries with the same type of electrolyte may be installed in the same room but on separate battery stands. An access passage at least one metre wide to all battery rows and a minimum of one metre between rows of battery stands shall be provided. Only single row or stepped double row single tier battery stands may be positioned against a wall. The step shall be such that the top of the cell plates of the back row is exposed. The minimum distance between any battery terminal and the nearest water supply point shall be two metres. Rows of battery stands shall be positioned such that they do not jeopardize or obstruct the doorway. Wherever possible the stands shall be positioned perpendicular to the entrance wall. The battery arrangements shall comply with the layout drawing, showing the positioning of the different batteries. 5.4.3.3. Battery Chargers 5.4.3.3.1. Type Battery chargers shall be low ripple, UPS style switch mode charger with temperature compensation facility. Battery chargers shall be suitable for providing supply to a load with or without a battery connected in parallel and are to be a suitable for wall and floor mounting. Battery chargers are to be single-phase connected to facilitate connection of portable generator sets in situations of loss of ac supply (such as under “black start” conditions or other loss of ac supply). 5.4.3.3.2. Location Battery charger units shall be located within the Substation Control Room, as close as practicable to the relevant battery. 64 5.4.3.3.3. AC Supply For substations where two battery systems are provided, AC supply to each battery charger shall be taken from a different auxiliary AC distribution switchboard. 5.4.3.3.4. Features Battery chargers are to have an AC input circuit breaker, battery monitor relay, DC output fuses or circuit breakers and output voltage indicator. The charger is to be operated in accordance with the battery manufacturer‟s recommendations. 5.4.3.3.5. DC Supply Circuits The positive and negative shall be in separate conduits and fused as shown in the figure. Figure 5-1: Schematic representation of a battery charger 5.4.3.4. Battery Disposal Disposal of all batteries shall be in accordance with the Environmental Management Act No.12 of 2011 65 5.4.4 Metering 5.4.4.1. General The metering shall be for the purpose of measuring kVA/kVAr-hours/kWh for tariff purposes. The metering equipment shall be static and comply with the following Zambia Standards: a). ZS IEC 62053 61: Electricity metering equipment (a.c.) Particular requirements - Part 61: Power consumption and voltage requirements b). ZS IEC62053 31: Electricity metering equipment (a.c.) Particular requirements - Part 31: Pulse output devices for electromechanical and electronic meters (two wires only) c). ZS IEC 62053 23: Electricity metering equipment (a.c.) Particular requirements - Part 23: Static meters for reactive energy (classes 2 and 3) d). ZS IEC 62053 22:2003 Electricity metering equipment (a.c.) Particular requirements Part 22: Static meters for active energy (classes 0.2 S and 0.5 S) e). ZS IEC 62053 21: Electricity metering equipment (a.c.) Particular requirements Part 21: Static meters for active energy (classes 1 and 2) f). ZS IEC 62053 11: Electricity metering equipment (a. c.) – Particular requirements - Part 11: Electromechanical meters for active energy (classes 0.5, 1 and 2) 5.4.4.2. Design All integrating meters shall be static and shall be suitable for operating in the following manner:a). Single Element Meters (2-wire). These may be of either whole current or current transformer operated type. In either case the voltage coil shall be suitable for a nominal voltage of 230 volt connected phase to neutral. Such meters will be used to measure a single phase input or three single phase meters will be combined to measure a three phase input where the load may be balanced or otherwise. b). Three Element Meters (4-wire). These shall be of either the whole current or current transformer operated type and shall be used for balanced and unbalanced three phase loads at a nominal voltage of 400/230 volt. c). Two and Half Element Meters (4 wire) These shall be designed to operate from current transformers in each of the three phases and potential transformers connected between two of the phases and neutral d). Three Element Meters (3-wire) These shall be of either the whole current or current transformer operated type and shall 66 be used for balanced and unbalanced three phase loads at a nominal voltage of 400/231 volt 5.4.4.3. Meter Accuracy The accuracy class or equivalent, is based on the MVA capacity of the connection and for new installations shall as a minimum be as follows, subject to operating within the combined limits of error set out in Table 5-8 below: Table 5-8: Meter accuracy Equipment Equipment Accuracy Class For connections Equipment Type Meters > 100 MVA >20-100 MVA 1 – 20 MVA < 1MVA 0.2S 0.5S 1.0 2 5.4.4.4. Meter Enclosure Meter enclosure shall be IP 51 in accordance with IEC 60529 5.4.4.5. Labels All meters shall be clearly and permanently labelled. 5.5 Auxiliary Equipment Substation lighting Recommended minimum levels of substation lighting shall be maintained at all times for the safety and security of personnel and the facility. The substation lighting requirements can be referred to ZS 418. 5.5.1. Fire suppression systems The design and operation of a new or existing substation shall take recognition of the fire hazards associated with the installations, the risks involved and the responsible person shall provide appropriate fire-protection mitigation measures. The requirements can be referred to ZS IEEE 979. 67 6. CABLES AND CONDUCTORS 6.1. General When cables and conductors are being selected, some of the main points to be considered are: a). b). c). d). e). f). g). h). i). j). Maximum operating current; Cyclic pattern of the current; Voltage drop; Short-circuit requirement; Exposure to mechanical damage; Lifetime costs, including the cost of losses; Earthing requirement; Current ratings, including de-rating factors; Possibility of theft of cable and energy, and Ability to withstand ultraviolet radiation. For the preferred type of cable or conductor available within the ranges covered by the relevant Zambian cable standards. The permissible short-circuit current for a cable or conductor is determined by the maximum permissible conductor temperature and the duration of the shortcircuit current, in other words, the time from the start of the short-circuit until it is broken by protective devices. The relevant formulas or tables and charts that list the maximum permissible short-circuit currents for different time intervals can be obtained from the cable manufacturers. 6.2. Fault currents and short-circuit ratings of cables 6.2.1. Fault current on the MV network If the fault level in megavolt amperes is known, the fault current on the MV network is given by: If Pf Vs 3 (7.1) Where If is the fault current, in kilo amperes; Pf is the MV fault level, in megavolt amperes; Vs is the MV system voltage, in kilovolts. The size of the cable can then be checked against the manufacturer‟s tables of short-circuit ratings for the expected fault clearance time. Example: For an MV fault level of 250 MVA, and an 11 kV three-phase system, the fault current is: 68 250 13.12 kA 3 11 If (7.2) 6.2.2. Fault level at the LV terminals of the transformer The MV fault level should be taken into account in the calculation of the LV fault current at the transformer bushings. To allow for MV growth, use the maximum planned fault level at the step- down MV substation or the rating of that substation‟s switchgear. The formula for the fault level at the LV terminals is: If 1000 1 Z p 10 Vs 3 P T r f (7.3) A simplified formula which does not take the MV fault level into account (i.e. assumes an infinite MV bus) can be used. It gives an LV fault level around 5 % higher than when equation 7.3 is used. The simplified formula is: If 100 Tr Z p Vs 3 (7.4) Where; If is the fault current, in kiloamperes; Pf is the MV fault level, in megavolt amperes; Zp is the transformer impedance, as a percentage; Tr is the transformer rating, in kilovolt amperes; Vs is the LV system voltage, in volts. Example: For an MV fault level of 250 MVA, an LV system voltage of 400 V and a transformer of 500 kVA and 5 % impedance, the fault current is: If 1000 13.88 kA 5 10 1 400 3 250 500 (7.5) Using the simplified formula, the calculated fault current would be 14.43 kA. 69 6.2.3. Maximum fault current at service distribution points (SDPs). The three-phase fault level should be calculated at each node on the distributor where the cable size changes to allow checking whether the fault current rating of the cable from the SDP will be exceeded. The impedance at the transformer LV terminals is mainly reactive, whereas the LV feeder impedances have both resistive and reactive components. For reasonable accuracy, the cable resistance and reactance both have to be taken into account. The impedance at any point is the vector sum of the impedance up to the transformer LV terminals plus the sum of all LV feeder impedances. The feeder impedances should be taken at the same temperatures used for voltage drop calculations, i.e. 30 °C for underground cables and 40 °C for overhead lines and ABC. The reactance up to the LV terminals, in ohms, referred to the LV side, is given by: Vs 3 I s 1000 Xs (7.6) Where; Xs is the reactance up to the LV terminals, in ohms; Is is the three-phase fault current at the LV terminals, in kilo Amperes; Vs is the LV system voltage, in volts. If the sum of the LV feeder impedances is Rf + jXf, then the total impedance, in ohms, is: Z t R X f X s 2 f 2 Vs R X f 3 I 1000 s 2 2 f (7.7) Where: Rf: is the sum of the feeder resistances Xf: is the sum of the feeder reactances The three-phase fault current, in kilo amperes, is then given by: If Vs 1000 Z t Vs Vs 1000 R X f 3 I s 1000 2 2 f (7.8) For a fault level at the transformer LV terminals of 13.88 kA (see previous example) and a total LV feeder impedance of (0.01299 + j 0.0061) Ω, the fault current in kilo amperes would be: 70 If 400 400 3 1000 0.01299 2 0.0061 3 13.88 1000 2 8.82 (7.9) 6.2.4. Minimum fault level at ends of feeders To ensure that fault protection devices operate successfully, the single-phase fault current at the end of each branch and at the consumer‟s point of supply should be calculated. This is particularly significant in long, lightly loaded LV feeders. Since these feeders are longer than usual, their impedance Z rather than resistance only, should be used. The fault current should be larger than 1.6 times the full load current. 6.2.5. Standardized procedure for short-circuit calculations Methods for the calculation of short-circuit currents are given in IEC 60909-0 and other standard texts. These methods can be applied to evaluate the maximum and the minimum shortcircuit currents, in order to correctly select and adjust protection device. 71 7. 7.1 OVERHEAD DISTRIBUTION LINES General Overhead power lines will be selected based on the suitability for current carrying capacity, topology of terrain, interaction with users of the area (crossing points, human proximity, mobile machinery, agricultural machinery, wildlife and livestock), and the economic requirements. The overhead line basically consists of the overhead lines (conductors), support structures i.e. poles/tower, stay wires, insulators, aerial guard earth wire(s), cross arms, lightning arrestors, arc horns, anti-climbs, red ball aviation warnings systems, catch nets, goal posts. 7.2 System Voltages Distribution systems in Zambia use system voltages of 33kV, 11kV, 3.3kV, 0.55kV and 0.4kV. The suitability of the system voltage is basically dependent on the choice of supply of the distributor with respect to the length of the line, operational machinery, segregation of voltage ranges etc. Overhead lines may consist of similar components, however special consideration must be taken into account with respect to the system voltage of the overhead line in line height clearance, line to line spacing, aerial earth guard wire to line clearance, choice of insulators, fuse links, arc horns, and lightning surge arrestors. 7.3 Conductors 7.3.1 Insulated Conductors 7.3.1.1 Aerial Bundled Cables (ABC) Voltages up to 600V Aerial Bundled Cables are used as a preferred economic means to supply power to areas where the property of insulation is of prominent importance such as national parks, sub-urban areas with a large density in population and heavily built-up places with no provision for underground cabling. As a guide for determining the specifications for cores consisting of stranded that are insulated with cross-linked polyethylene (XLPE) and that are intended for use in aerial bundled conductor (ABC) systems for overhead single-phase and three-phase electricity distribution operating up to 600/1 000 V, please make use of SANS 1418-1 and refer to IEC 60502. As a guide for determining the requirements for assembled insulated conductor bundles, please make use of the SANS 1418-2. As for further standards for aerial bundled conductors, please make reference to SANS 1713 and for testing guidance and fittings, fasteners, line taps, brackets the following standards can be used: 1. SANS 10198-14: Handling and installation of electrical aerial bundled conductor (ABC) cables power cables of rating not exceeding 33 000V. 2. SANS 6282-1: Conductor resistance testing of electrical aerial bundled bare and insulated conductors. 3. SANS 6282-3: Mechanical testing of electrical aerial bundled bare and insulated conductors. 4. SANS 6101: Testing to dielectric adherence to conductor of supporting cores of aerial bundled conductors. 72 5. SANS 6100: performance testing of mechanical and thermal stresses of supporting cores. 7.3.1.2 Aerial Bundled Cables (ABC) voltages above 600V to 33kV Considering the nature of the aerial bundled conductors for use up to voltages of 33kV, there supporting structure and components are mainly the same. However, for guidance make reference: 1. SANS 10198-14: Selection, handling and installation of electrical aerial bundled conductor (ABC) cables power cables of rating not exceeding 33,000V. 2. SANS 6282-1: Conductor resistance testing of electrical aerial bundled bare and insulated conductors. 3. SANS 6282-3: Mechanical testing of electrical aerial bundled bare and insulated conductors. 4. SANS 6101: Testing to dielectric adherence to conductor of supporting cores of aerial bundled conductors. 5. SANS 6100: Performance testing of mechanical and thermal stresses of supporting cores. 7.3.2 Bare Conductor 7.3.2.1 Aluminum Conductor, Steel Reinforced (ACSR) Aluminium conductors with steel reinforcement shall be selected based on the standard size suitability of current loading and mechanical withstand strength of the support structures and the requirements of IEC 60889. 7.3.2.1.1 Maximum Limits - Reduced limits to avoid fatigue failure due to vibrations for Aluminium Conductor, Steel Reinforced (ASCR): If vibration dampers are not used and the lines have relatively short spans, typically under 200 m, the initial tension at -5 °C should not exceed 25 % of the ultimate tensile strength of the conductor. When vibration dampers are used, the following limitations are recommended: a) The initial tension at -5 °C should not exceed 33.3 % of the ultimate tensile strength of the conductor; b) The initial tension at 15 °C should not exceed 2 5 % of the ultimate tensile strength of the conductor; and c) The final tension at 15 °C should not exceed 20 % of the ultimate tensile strength of the conductor. Additional dampers are not required for bundled conductors if the tension is below a certain value 7, proportional to the conductor weight: T = 1 800 Mc Where; T is the limiting tension, in newton‟s; and Mc is the conductor weight per metre, in newton‟s per metre. In the case of single conductors, it is not economical to use this value to limit initial 73 tensions, and current practice is to limit the final tensions. Initial tensions are limited by the support structure capacity on short spans. All Aluminium Alloy Conductors (AAAC) Aluminium conductors shall be selected based on the standard size suitability of current loading and mechanical withstand strength of the support structures and the requirements IEC 61089. Maximum Limits - Reduced limits to avoid fatigue failure due to vibrations for All Aluminum Alloy Conductor (AAAC) (Refer to Item on ASCR) 7.3.2.2 Copper Conductor Copper conductors shall be selected based on the standard size suitability of current loading and mechanical withstand strength of the support structures and the requirements of BS 7884. The tension at 15 °C should not exceed 26 % of the ultimate tensile strength of the conductor. 7.3.3 Conductor Joints All joints shall be such that their current-carrying capacity exceeds that of the conductors that are being joined. Tension joints shall have a breaking strength of at least 95 % of that of the conductor. In areas that are conducive to corrosion, it is good practice to coat the joined ends and fill the fittings with chemically inert corrosion-inhibiting paste. There shall be no joints made in either the conductors or the earth wires on a road or rail crossing span. 7.4 Support Structures 7.4.1 Wooden Poles The wooden poles shall comply with the specifications in the Zambian standard on wood poles ZS 746 – 6. 7.4.2 Concrete Poles 7.4.2.1 General Concrete poles shall be one of the following types, as specified by the purchaser and in accordance with SANS 470: a). b). c). Reinforced concrete pole, Partially pre-stressed concrete pole, or Pre-stressed concrete pole Poles shall be manufactured in accordance with NRS 038 7.4.2.2 Design Length, tip and butt dimension: The overall length of the pole shall be as specified, and shall be one of the following standard lengths: 4m, 7m, 9m, 10m, 11m, 12m, 15m, 18m, 21m and 24m. The tip and butt dimensions of the 4m up to 11m poles shall be as per the detailed figures in NRS 038. 74 7.4.2.3 Cover of reinforcement The minimum thickness of the overall reinforcement in the case of centrifugally spun poles shall be not less than 15mm over the entire length of the pole. In the case where poles are manufactured by any other process the cover shall not be less than 20mm. When poles are required for use in aggressive soils the special additional requirements may include one or more of the following: Protective coatings; Additional concrete cover to reinforcement; Replacement of cement with slagment; higher factor of safety (to limit crack widths) 7.4.2.4 Finish The finished product will have a smooth external surface free from honeycombing. All corners shall be clean, straight and rounded to a radius of at least 5mm. 7.4.2.5 Holes Holes shall be provided in the poles during the manufacturing of the poles. These holes shall be used for the attachment of strain or suspension and other equipment. The holes shall be positioned as specified in the relevant figures detailed in NRS 038. Drawings indicating the specified poles with pole holes shall be furnished for approval prior to ordering thereof. On all transformer poles, the integral earthing facility EW 2900 and EW 8700 shall be replaced with a PVC conduit embedded in the concrete to protect the earth conductor in order to allow for separate earthing of the MV and LV earth in accordance with SANS 10292 and SANS 10200 respectively. This separate earthing is necessary when the earth resistivity value of the transformer structure is above 1 ohm. On all other MV poles the earthing ferrules (EW 2200 and EW 8000) shall be provided for earthing of the poles. 7.4.2.6 Pole Strength Pole strengths shall comply with Table 7-1, Table 7-1: Standard pole lengths, minimum ultimate loads and torsional capacities 75 7.4.3 Steel Poles/Towers 11.4.3.1 Design All steel structures shall be manufactured in accordance with industry standards and ISO certifications in accordance with SANS 121. Steel structures shall be galvanized in order to protect the structure from corrosion. 11.4.3.2 Paint and Finishing Painting and finishing shall be in accordance with BS 2569 and SANS 1091. Where the galvanized coating has been damaged during erection and after all assemblies have been attached to the structure, zinc metal paint in accordance with BS 2569 shall be applied to the areas for protection against corrosion. 7.4.4 Stay wires The stay should be installed in accordance with figure below and carefully backfilled: Figure 7-1: Stay anchor assembly installation detail When the stay is installed, the stay wire should be made off in accordance with figure above. Stayed poles should be so erected that they lean away from the stay position by at least half a pole diameter at the top. This will ensure correct alignment when the stay is made off correctly. 76 When the stay wire is tensioned using the correct tensioning equipment such as a pull-lift and come-along clamps, the stay is tensioned until the pole leans towards the stay by at least half a pole diameter at the top. No off-cuts of stay wire should be left on site, since these are dangerous to livestock. 7.4.5 Failure Limits of Support Structures: Type Supports Material of elements All elements, except guys Loading mode Ultimate (breaking) tensile stress Yield (elastic) stress Shear Compression (buckling) 90% (elastic) shear stress Non elastic deformation from //500 to //100 Tension Lowest value of: yield stress(70% to 75 % UTS) deformation corresponding to 5% reduction in tower strength need to readjust tension Ultimate tensile stress Moments 1% of non-elastic deformation at the top, or elastic deformation that impairs clearances. Local buckling in compression or ultimate tensile stress in tension. Compression (buckling) Non elastic deformation from //500 to //100 Shear (breaking) stress Moments 3% of non-elastic deformation at the top, or elastic deformation that impairs clearances. Local buckling in compression or ultimate tensile stress in tension. Steel Poles Wood Compression (buckling) Concrete Failure limit Tension Lattice towers, selfsupporting or guyed Steel guys Damage limit Permanent or nonpermanent loads Non elastic deformation from //500 to //100 Crack opening after release of loads, or 0.5% non-elastic deformation. Shear (breaking) stress Collapse by instability Collapse by instability Collapse of the pole NOTE 1 The deformation of compression elements is the maximum deflection from the line joining end points. For elements subjected to moments, it is the displacement of the free end from the vertical NOTE 2 / is the free length of the element NOTE 3 The width of crack for concrete poles to be agreed upon. 7.5 Insulators 7.5.1 General Long rod, Class A insulators shall be used at all cross arms for medium voltage strain, terminal and pole mounted transformer structures. The cycloaliphatic long rod, polymer type (silicone rubber) and porcelain insulator shall be puncture proof and of the type as specified in design Detail Specifications as approved by the user/utility. The end fitted attachment shall be of the aluminium alloy clevis and tongue twisted type or made of hot-dip galvanized forged steel or ductile cast iron, are directly attached to the glassfiber-reinforced plastic (FRP) core rod as in the case of silicone rubber insulators. The insulator 77 shed material shall have a high resistance to tracking by surface leakage currents and operate normally under adverse weather conditions. Line post type insulators shall be installed on straight line structures and the insulating material shall be a cycloaliphatic resin, silicone rubber or porcelain complete with 20mm spindle including nuts and washers. Line post insulators shall furthermore be of the capless, solid-core type, be puncture proof, radio interference free and shall display superior performance in polluted environments. They shall have a basic insulation level of either 135kV or 150kV as specified in the Detail Specification in accordance with referenced standards. All standards referenced at the end of this section shall be adhered to. Glass type insulators shall where possible not be used due to vandalism. However glass insulators can be used if the service feels it necessary and is in accordance with the relevant international standards. Glass insulators are permitted in coastal regions up to 40 km in land from the coastal region, due to corrosion and heavy pollution (of which silicone rubber insulators off a great resistance to pollution effects). 7.5.2 Electrical design Insulators together with their fittings shall comply with SANS 60305, SANS 60383, BS EN 60305, BS 3288 and IEC 61109 and shall offer a high resistance to damage, caused by malicious vandalism. Insulator material shall be cycloalipohatic resin or polymer type such as silicon rubber based. As an alternative high grade porcelain insulators shall be used. The flashover and puncture voltages shall not be less than the values stated in the table below. Insulator flashover voltage, wet and dry, shall be less than the puncture voltage. Shackle insulators shall be used on all low voltage overhead conductors. The shackle insulators suitable for mounting to the pole with a D-bracket shall be of the type specified in the Standard Specification in accordance with the requirement. 7.5.3 Mechanical design The strength of the insulator shall be such that at the maximum working load of 4kN for line post insulators and 40kN for strain insulators shall be afforded. 7.5.4 Clamps and conductor fittings Tension conductor clamps shall be of approved type and shall be as light as possible, and shall be designed to avoid any possibility of deforming the stranded conductor and separating the individual strands. All fittings shall comply with the stranded coupling dimensions specified in the reference standards. Intermediate pole conductor binding shall be carried out by means of wrap lock ties complete with neoprene cover. Tension fittings shall be the preformed wire type, specially designed for the ACSR conductor used together with suitable fittings for securing the tension insulators. Tension insulator sets and fittings shall be of approved standards to give the minimum required clearances between the jumper conductor and the rim of the live end insulator units. Adequate bearing area between fittings shall be provided and “point” or “line” contacts shall be avoided. All split pins for securing the attachment of fittings of insulator sets shall be of stainless steel type material and shall be backed by washers. D-shackles between insulator and eye shall be installed at all strain positions in accordance with SANS 10280. 78 7.5.5 Strain insulators Strain insulators of the twisted clevis tongue type are required for strain and terminal poles. The insulators shall be cycloaliphatic resin or high grade porcelain material as specified in the detailed project specification and the approved national standards. Strain insulators shall be complete with galvanized clevis pin (to SANS 121) c/w washer and stainless steel split pin (304 s/steel), for preformed dead end. Strain insulators shall be installed and connected to cross-arms and A-frames, with D- shackles, clevis thimble and preformed dead end for conductor as per design specifications. Table 7-2: Mechanical strengths Nominal voltage: Impulse withstand (Minimum) Mechanical strength (Minimum) 11kV 22kV 33kV 120kV 150kV 180kV 70kN 70kN 70kN 7.5.6 Porcelain disc insulator High grade porcelain, 70kN mechanical strength. Nominal voltage – 11kV, 22kV or 33kV as specified in this standard. 7.5.7 Long rod insulator: Cycloaliphatic long rod, min. failing load 70kN, with clevis tongue twisted arrangement with corrosion resistant end caps, complete with galvanized clevis pin (to SANS 121) c/w washer and stainless steel split pin (304 s/steel), preformed dead end type for conductor size as specified – nominal voltage of 11kV, 22kV or 33 kV as specified. Silicone long rod insulators are designed to meet the highest requirements in distribution power systems up to 72 kV. They have high lightning impulse and power frequency withstand voltages and a long creepage class (> 31 mm/kV). Silicone long rod insulators are available with mechanical ratings up to Specified Mechanical Load (SML) = 70 kN. 7.5.8 Intermediate insulators Line post insulators are required for the intermediate poles on A-frames and for staggered vertical delta configurations. Complete installed and connected to A-frame, with spindles or on poles c/w spindles, curved washer (50 x 50), spring washer and nuts. A-frame mounting: Short spindle – Type M2 threaded to 44mm complete with washer, nut and locknut, for mounting bracket, complete with line tie for specified the specified conductor. Pole-mounting: long spindle – Type M2 with 178mm shank threaded to 100mm, 250mm for mounting through pole, c/w curved washer (50 x 50), spring washer and nut. Complete with line tie for specified conductor. 7.5.9 Porcelain line post insulator High grade porcelain for 11kV, 22kV or 33kV, 4kN lateral mechanical strength. Complete installed with line ties for specified conductor. 79 7.5.10 Cycloaliphatic line post insulator For A-frame mounting cycloaliphatic line post insulator – cantilever failing load 4kN, for M20 spindle – for 11kV and 22kV as specified 7.6 Aerial Guard Earth Wire For high voltage lines, two longitudinal 18 to 27 mm2 galvanized steel earth wires are to be provided with 6mm diameter galvanized steel cross lacings. The longitudinal earth wires are to be located at a horizontal distance outside the conductors of not less than two-thirds of the vertical distance between the lowest adjacent high voltage conductor and the aerial earth wire, or 200mm, whichever is the greater. The aerial earth guard wire shall be so placed that all conductors fall within the shielding angle. 7.6.1 Mechanical Strength of the aerial earth guard wire: In the case of galvanized steel earth wires of minimum breaking strength in the range 700 MPa to 1100 MPa, the maximum tension at 15 °C should be such that the stress in the earth wire does not exceed 180 MPa. This criterion permits the use of tensions (at 15 °C) of the following percentages of minimum breaking strength: a). b). 700 MPa wires: 25 %; and 1 100 MPa wires: 15 %. Earth wires are often strung to match, approximately, the sag of the conductors, and, when the conductors are strung to the tension limits recommended for vibration, the earth wire tension limits stated above are usually not exceeded. If the limits are exceeded, satisfactory performance can usually be obtained by the addition of a damping device to the earth wires. Because the conductors generally have a higher thermal expansion coefficient than the earth wire, in cold weather the clearance between the two will reduce if the line is not operational. This could lead to flashovers when the line is energized. As an additional safety margin and also to improve the shield angle at mid-span, earth wires should sag to 85 % of the sag of the conductors. 7.7 Anti-climbs An anti-climb shall serve as a deterrent to unauthorized persons from climbing support structures. All support structures for overhead lines or pole mounted transformers shall be fitted with anti-climbs. These shall be of the nature of steel spikes, barbered wire or razor wire and come at a height of significant safety. The recommended minimum height shall be not less than 3m above ground, but within standard height clearance from the overhead conductor. 7.8 Cradle Catch nets At points of crossing overhead lines of system voltage of 11kV and 33kV at major commercial roads, rail lines and other voltage power lines, a catch net shall be provided under the overhead lines with the highest system voltage at not less than 1.2m without bleaching clearances of the other voltages. 7.9 Red Balls 80 Where there is extreme aviation proximity with power overhead lines, visible red balls will be placed on over the conductors in that vicinity as per guidance of relevant standards. 7.10 Goal posts For 11kV and 33kV overhead lines heavy machinery crossings, goal posts will be erected at the designated crossing point for that machinery under the overhead lines. 7.11 Pole Mounted Equipment 7.11.1. Switches 7.11.1.1. Line Isolation Switch Isolators shall comply with the requirements of IEC 60129 and IEC 60265-1. The switch shall be of the triple pole, gang operated, rocking type, spring assisted manually operated preferably having hinged blades and front connections and shall be capable of breaking full load current at a power factor 0.7 leading. The isolators shall be capable of making the system fault current specified in the Technical Schedules, without damage to the equipment or danger to the operator. 7.11.1.2. Isolator with Earth Switch The equipment shall comprise a line isolator integral with an earth switch and shall be suitable for pole mounted operation. The line isolation switches shall be fitted with approved type three phase earthing switches to be located on either the top or the bottom contact terminals of the switch. The earth switch shall be of three pole construction, spring assisted manually operated and fully rated for the system fault rating. The earth switch shall form an integral part of the main switch. Two independent earthing pads with connectors suitable for the specified size of the earth conductor shall be provided, one at each end of the switch. The main switch and the earth switch shall be mechanically interlocked such that it will not be possible to close the earth switch when the main switch is closed. The rated peak short circuit current and the rated short time current of the earthing switch. 7.11.1.3. Switch Fuses Switch fuses shall comply with the requirements of IEC 60129 and IEC 60265 and shall meet the interrupting current requirements of IEC 282-2. The design and mounting shall be such as to permit easy operation from ground level using an operating rod i.e. an operating eye shall be provided on the fuse tube designed for use with a hook stick. The fuse holder of a switch fuse shall be dimensionally compatible with a universal fuse link of corresponding rating. The main assembly may be mounted on a two insulator base arrangement, the top and bottom contact sub-assemblies and mounting fitting shall be fitted into the porcelain insulators, the 81 upper fixed contacts shall positively latch. Insulators shall be of the solid glazed porcelain type and be bird proof, they shall meet the electrical and mechanical characteristics of IEC 383 and provide a minimum creepage distance as specified in SP-GGE-001 and in the Technical Schedules. The assembly shall be designed such that the tube can be closed without using undue care even when the closing force is applied at an angle. The angle of the fuse tube or link relative to the vertical shall be a minimum of 20o. The fuse tube shall be capable of accepting IEC/BS EN fuse links. The toggle mechanism shall provide locking action to protect the fuse link from shock. A spring assisted flipper shall assist arc interruption by withdrawal of the fuse tail. The fuse tube cap shall preferably be of the non-expendable type and an arc shortening rod, if provided, shall be attached to the fuse tube cap. 7.11.1.4. Isolator with Switch Fuse and Earth Switch The equipment shall comprise a combined 33kV line isolator with switch fuse and earth switch suitable for pole mounted outdoor operation. The fuse switch arrangement shall be mounted on the same phase below the line isolator and shall comprise three single pole type expulsion fuses or drop-out fuses as specified. 7.11.1.5. 11 and 33 kV Fuse Links 11 and 33 kV fuse links shall be general purpose, powder filled, fault limiting fuses and shall comply with their requirements of IEC 60282 Part 1 and 2 and shall be suitable for use with fuse isolators to be provided and shall be so rated and shall have such fusing characteristics as to be suitable for selective operations with the fuse links presently in use on the system. All current carrying parts of the fuse links shall be on non-ferrous materials, the main requirements being resistance to atmospheric corrosion. Each fuse link shall be permanently marked with the following information:Vendor or identifying mark, current rating, type designation (e.g. K or T). The switch fuse mechanical arrangement shall allow for any rating or dimension of the fuse, within the standard design of the isolator including modifications required, if any. 7.11.1.6. Drop Out Fuses and Line Links These shall be single phase pole mounted link stick operated. They shall be provided on pole mounted transformer supplies and on overhead line Tee-Offs at 11kV and 33kV.. The mounting arrangement shall be as detailed in the attached detail drawing. Fusible links shall be designed to carry 150% of their rated current without deterioration of the fusible element or damage to the cut-out unit in which they are installed. Melting of the element shall cause the cut-out link to be expelled from the line contacts. All metallic hardware and components of fuses and links shall be hot-dip galvanised. . 82 7.11.1.7. Operating Mechanisms The switches along with their interlocked earth switches shall be complete with gang/manually operated switch opening and spring assisted push button triggered closing operating mechanisms. The mechanism drive and linkage of the isolator shall allow the operating handle to be mounted about 1.25 metres above the ground and shall be designed to minimize wear and permit some degree of misalignment of the structure. It shall be as simple as possible comprising a minimum of bearing and wearing parts. Shaft and pin bearings shall be of selflubricating or dry type and shall be such as to permit easy manual operation by one person even following long periods of non-operation. The operating rod shall have an insulator insert of wood (e.g. Permalli) or approved equivalent, the insulating medium used to be stated by the Contractor. The mechanism shall provide simultaneous isolation of all three phases and arranged for up‟ON‟ operation. The closing mechanism shall be a spring assisted manual device designed so that the speed of operation is independent of the operator. The mechanism shall be of robust construction and shall be carefully fitted to ensure a quick, smooth simple and effective operation. The time of operation shall be as fast as possible. The operating mechanism shall be of substantial construction utilising such materials as may be necessary to prevent sticking due to rust or corrosion. The ganged switching mechanism shall be provided with sufficient adjustment to allow for final alignment of the switch blades for simultaneous operation. Adjustable stops shall be provided to prevent over travel in either direction. It shall not be possible after final adjustment has been made, for any part of the mechanism to be displaced at any point in the travel sufficiently to allow improper functioning of the switch when the switch is opened or closed at any speed. The overall design of the mechanism shall be such as to reduce mechanical shock to a minimum and shall prevent its inadvertent operation due to fault current stresses, vibrations or other causes. The mechanisms shall be self-locking in both the open and closed position and shall be of a type that shall operate all three phases simultaneously. The operating mechanism shall be suitable for manual off operation by means of the operating handle positioned as specified above on the overhead line structure and push button triggered “ON‟ operation after the spring is charged using the operating handle. The operating mechanism and operating handle shall be complete with all supporting accessories, all brackets, angles, guides or guide bearings or other members as may be required for attaching the operating mechanism and operating handles to the wood pole structures. All bearings as required shall be weather protected by means of covers. The lubrication requirements shall be as specified. The connecting assembly between the mechanism of the switches and their operating down rods shall be robust and strong with a positive mechanical connection between linkages to provide adequate gripping force in order to prevent slipping between the mechanisms during the operating of the switches. 83 7.11.1.8. Accessories 7.11.1.8.1. Counter Balance Springs These shall be provided as may be necessary for counter balancing the switches to prevent impact at the end of travel both on opening and closing of the switch/earth switch. The springs shall be of non-rusting alloy. 7.11.1.8.2. Earthing Pads Each pole of the switch shall be provided with two earthing pads of non-corroding material at opposite ends, brazed to the supporting base. Flexible copper earth connectors shall be provided for connecting operating handles of switches/earth switches to the earthing system. 7.11.1.8.3. Position Indicator A mechanical position indicating device shall be provided for each switch/earth switch. 7.11.1.8.4. Padlocks The operating mechanism of each switch and the earth switch shall be provided with facilities for locking the switch in the “OPEN” or “CLOSED” position. The facilities include those for the spring charging handle and the closing push button. 7.11.1.8.5. Name Plate A weather proof and corrosion proof name plate shall be provided on the switches, and the operating devices. The name plates shall conform to IEC standards. 7.11.1.8.6. Live Line/Earthing Clamp Support In order to carry out live line maintenance, clamp supports to receive a live line clamp and an earthing clamp shall be provided adjacent to bottom terminal of line isolation switches and, when equipped, at the bottom terminals of the fuses. Necessary extension of the terminals shall be provided in order to enable proper support of the clamps as described above. The extension shall be at least 150 mm long and shall have a 16 mm diameter hole to suit the dimension the cable lug to which connection shall be made. 7.11.2. Fencing off All substations and pole mounted units shall be fenced off and locked out to avoid unauthorized access to the structures. 84 8. UNDERGROUND DISTRIBUTION SYSTEMS 8.1. Components 8.1.1. Cables Cables shall be selected based on their suitability for the terrain and current carrying capacity and shall be compliant to ZS 688. 8.1.1.1. Cable accessories such as glands, bolts and fasteners: 8.1.1.1.1. Cable Glands: A gland is a cable terminating fastener used on armoured cable which may or may not include a metallic inner sheath or screen, but shall be so constructed that provision is made to ensure electrical earthing continuity between the armour of the cable and the metallic structure of the enclosure to which the gland may be attached. For further reference please make reference to SANS1213 and IEC 60079. 8.1.1.1.2. Bolts and nuts: All metal parts shall be secured by means of bolts and nuts whose minimum diameter shall be 12mm. All bolts, nuts and screw threads shall comply with SABS 135 (there is no SANS equivalent) and galvanized in accordance with SANS 121 unless otherwise approved. Bolts and nuts shall be of steel with hexagonal heads. The nuts of all bolts for attaching to the tower plats, brackets or angles supporting insulator sets or droppers to earth conductor clamps shall be locked by approved means. No screwed threads shall form part of the shearing plane between members. Unless otherwise approved, all bolts and screwed rods shall be galvanized including the threaded portions; all nuts shall be galvanized with the exception of the threads, which shall be greased. When in position all bolts or screwed rods shall project through corresponding nuts, but such projection shall not exceed the diameter of the actual bolt. Where different grades of steel are used, bolts of any given diameter and length shall conform to the same grade of steel. 8.1.1.1.3. Junctions/Joints: 8.2. All joints shall comply with IEEE 404, IEC 60840 and SANS 10198-9 to 11. Trenches: Cables of voltages above 600V shall be buried at a minimum depth of 1000mm below ground level and cables for voltages below and including 600volts shall be buried at a minimum depth of 800mm.. Trenches shall not be less than 300mm wide for single and multiple LV service connection cables, and the trench width shall be increased where more than two LV feeder or service connection cables are laid together so that the cables may be placed at least 150mm apart throughout the run. Cables installed in earth trenches shall be laid on a bedding of sand or soil free of stones, and covered with the same material to a depth of at least 100 mm. Special constructions of cables can be chosen, if necessary, to protect against chemical effects. Cable routes shall be identified with cable route markers – SANS10142-2; 85 Streetlight cables buried in trenches under un-tarred roads shall be buried in a trench with minimum depth of 600mm and 300mm wide. Trenches under tarred roads shall be buried a minimum of 500mm deep, and normally in HDPE corrugated sleeving of applicable size, quantity and required spare quantities. Where the nature of the ground does not permit the excavation of the cable trenches to the specified depth, the engineer may authorize trenches not less than 500mm deep. Such authority shall be given in writing. The Contractor must take all the necessary precautions to prevent trenching work being in any way a hazard to the public, and to safeguard all structures, roads, railways, sewer works or other property from any risk of subsidence and damage. Soil type shall be graded. For further guidance on trenches make reference to IEC 60502, IEC60840, and BS6622. 8.3. Cable Trays/Racks This is an assembly of cable supports consisting of cable tray lengths or cable rack lengths and other system components such as cable tray/rack fittings, support devices, mounting/anchorage devices and various accessories required to demarcate or segregate the cables, offer cable retention on the tray/rack and covering devices. For further guidance on installation, testing and use, please refer to IEC 61537: CABLE TRAY SYSTEMS AND CABLE LADDER SYSTEMS FOR CABLE MANAGEMENT 8.4. Cable Route Markers Cable route markers of approved manufacture shall be provided at each end of an underground cable route and at all points where such routes deviate from a straight line. Joints in the cable shall be marked and the maximum distance between route markers shall not exceed 100m. For underground cabling, above ground route markers shall also be provided at every change of direction in the routing and at both sides of road or pipeline crossings, except when cable routing is already indicated by colored concrete pavement. The cable markers shall be tapered blocks cast from concrete in accordance with approved detail drawings Each cable marker shall be buried with its upper face 100mm above the natural ground level. Marking of cable markers shall also be in accordance with approved detail drawings. For underground cable marking purposes non‐ corroding strips shall be used, each having ample length to be wrapped twice around the cable and in which the cable number has been imprinted by means of letter/cipher punches. For above ground cabling, plastic markers resistant to the site conditions shall be strapped round the cables. Tempering with the position of this installed cable markers shall be strictly prohibited and supported with an inspection and maintenance regime in place for every installation. 86 9. EARTHING AND LIGHTNING PROTECTION REQUIREMENTS 9.1. General Every substation shall be provided with an earthing installation designed so that in both normal and abnormal conditions there is no danger to persons in any place to which they have legitimate access. The installation must be able to pass the maximum current from any fault point back to the system neutral without establishing dangerous potential gradients in the ground or dangerous potential drops between parts of the substation with which a person may be in a simultaneous contact. The design shall be such that the passage of fault current through the earthing system does not result in any thermal or mechanical damage or damage to insulation of connected apparatus and that protective gear, including surge protection is able to operate correctly. Measures shall be taken to minimize high “substation potential rise” and “transferred potentials” as necessary. Such measures are usually necessitated by large earth fault currents, particularly if these occur in a substation in an area of higher than 250 ohm metres specific soil resistivity. Substation earthing design shall be based on IEC Recommendations 634-5-54 and IEC 1219 93 The earthing installation shall be designed with earth electrodes as necessary to reduce step, touch and mesh potentials within the substation to the permissible safe limits. Such potentials at the substation boundaries and transferred potentials shall also be similarly reduced to safe levels by approved means. 9.2. Earthing of Equipment 9.2.1. General All earth conductors attached to structures shall be fixed by an approved means at approximately 1 m centres. Bare copper conductors shall not be in direct contact with galvanised surfaces except at approved electrical joints. Steps shall be taken to ensure compliance with this requirement which shall be to the approval of the Engineer. Each item of electrical apparatus shall be connected to the main earth conductor by means of a separate subsidiary connection. Minor items of plant e.g. small fuse protected motors and field mounted control equipment etc., may be connected to earth through their associated cable armour provided that the armouring is connected at each end by copper tape and that the cable gland is not relied upon for continuity. Any metalwork or chain link fencing around the substation site shall be adequately earthed in an approved manner. 9.2.2. Earthing system The earthing system will comprise a network of continuous main copper earthing conductor installed in and around the substation buildings together with subsidiary and branch copper conductors to the various items of electrical equipment in the substation. Where the earthing system is installed outside the substations, it shall be to approval but shall be at a depth not less than 500 mm. The main earth conductor shall consist of copper wire or strip of minimum section 95 mm2. Branch earth conductors shall be 70 mm2 Cu minimum section wire or strip. 87 Cable sheaths may be earthed in groups by a separate branch connection to each item of equipment in the group with the branch connections being connected by a single subsidiary connection to the main earth conductor. 9.2.3. Earthing electrodes Earth electrodes shall consist of round steel-cored copper rods not less than 16 mm diameter. An earth electrode inspection pit shall be provided at each electrode (or set of electrodes) to facilitate testing of individual items. 9.2.4. Terminations The contact faces of earth terminals shall be cleaned before connections are made to the earthing system. Earth conductors shall be tinned before being clamped at each earth stud. When earthing switchgear, connection points shall be positioned not less than 300 mm above finished floor or ground level and preferably on a vertical plane. Foundation bolts shall not be used for connections to the earthing system 9.2.5. Guards against mechanical damage Where earthing conductors are exposed to mechanical damage galvanised sheet steel guards shall be provided for protection. 9.2.6. Neutral Earthing Resistor Earthing resistors shall be dry type installed into floor -mounting IP 31 classified hot dip galvanised steel housing suitable for outdoor service. The resistors shall be complete with lifting and jacking lugs, access panels, holding down bolts or clamps, high voltage, earth terminals, connectors and connections as well as with bottom mounting U-bars for erection on the concrete pad. Provisions shall also be made for temporary bypassing the resistors with a maintenance earthing device.. Each resistor shall be equipped with removable link at the earth side for checking the resistance during bypass. For connecting the resistors to the neutral, single core XLPE cables (specification see previous clause) with outdoor terminations shall be used. 9.2.7. Earthing conductor All grounding (earthing) and bonding conductors shall be insulated stranded copper conductors unless otherwise specified. The insulation shall be green, green with a yellow stripe or properly marked with a distinctive green coloring, green tape or stripe or green adhesive label. 9.2.8. Apparatus, Steel Structures and Overhead Shield wires The frames of all electric apparatus and the bases of all structural steelwork shall be connected by branches to the earth grid. All disconnector bases, earth terminals, and earthing switches, 88 neutral current transformers, lightning arrester bases as well as tower and gantries on which overhead shield wires are terminated shall be connected to earth grid. Lightning arresters installed for the protection of transformers shall be connected by direct low reactance paths both to the transformer tank and to the earth grid. Capacitor voltage transformers used in connection with the line traps shall be connected by direct low reactance paths to a single earth rod in addition to the earth grid. Galvanised steel structures with sufficient area and current carrying capacity may be used as part of the earth connection to post and strain insulators and to overhead shield wires which shall be terminated directly on to the steelwork. 9.2.9. Operating Mechanisms and Control Kiosks Disconnector and earthing switch operating mechanisms and circuit-breaker control kiosks not integral with the circuit-breakers shall be connected to the earth system by a riser entirely separate from that employed for earthing the apparatus structures. Such riser shall be connected to equipotential earth mat which shall be provided beneath the position where an operator will stand. This mat shall be joined to the earth grid. 9.2.10. Earthing of distribution transformers The neutral terminals of the transformers shall be connected to earth grid with a bar isolated from the transformer tank. This busbar shall be tied to the earthing grid via two separate risers. The transformer tank shall be connected to the earth grid via two separate risers. The following specifications shall be complimented by the following international and regional standards, IEEE 80:2000, SANS 10200 and SANS 10292; The transformer MV surge diverter earth shall be connected to the transformer tank earthing stud. The transformer tank earthing stud shall be connected to the MV three point star earth electrode arrangement with insulated copper earth lead (size dependent on short circuit rating -70mm2 minimum) The transformer LV neutral shall be bonded to the transformer tank earthing stud (MV earth) via a metal oxide valve (MOV) surge diverter to protect the transformer The transformer LV phase surge diverter earths shall be connected to transformer neutral bushing. The transformer neutral bushing shall be connected to the LV three point star earth electrode arrangement with 70mm2 insulated copper earth lead. This may be directly from the transformer, or via the distribution kiosk/board earthing bar. Bare portions of transformer MV and LV earth electrodes arrangements shall be separated by at least 5000mm, so that the LV earth is outside the resistance area of the MV earth. The transformer MV earth electrodes arrangement and bare parts of consumer‟s ECC shall be separated by at least 5000mm so that the ECC is outside the resistance area of the MV earth. 89 Where split earthing and combined earthing issues are raised, the following standards shall be consulted and applied: SANS 10200:Neutral Earthing in Medium Voltage Industrial Power Systems; SANS 10292: Earthing of Low Voltage Distribution Systems. 9.2.11. 33/11/0.4 kV substations The object of an earthing system in a substation is to provide under and around the substation a surface which shall be at a uniform potential and near zero or absolute earth potential as possible. The provision of such a surface of uniform potential under and around the substation ensures that no human being in the substation is subject to shock or injury on the occurrence of a short circuit or development of other abnormal conditions in the equipment installed in the yard. a). Mesh earthing Mesh earthing comprises an earthing mat buried horizontally at a depth of about half-a meter below the surface of ground and ground rods at suitable points. All non-current carrying parts contribute little towards lowering the ground resistance. The earth mat is connected to following in a substation: i). ii). iii). iv). The natural point of each system through its own independent earth. Equipment framework and other non-current carrying parts. The earth point of lightning arresters, capacitive voltage transformers, voltage transformers, coupling capacitors and the lightning down conductors in the substation through their permanent independent earth electrode. Substation fence. b). Solidly grounded systems Solid grounding refers to the connection of the neutral of the power transformer or grounding transformer directly to the substation grounding or to the earth. The solidly-grounded system is the most common system arrangement, and one of the most versatile. The most commonly-used configuration is the solidly-grounded wye, because it will support single-phase, phase-toneutral loads. Because of the reactance of the grounded transformer in series with the neutral circuit, a solid connection does not provide a zero impedance neutral circuit. If the reactance of the system zero sequence circuit is too great with respect to the positive sequence reactance, the objectives sought in grounding, principally freedom from transient overvoltages, may not be achieved. First, the system voltage with respect to ground is fixed by the phase-to-neutral winding voltage. Because parts of the power system, such as equipment frames, are grounded, and the rest of the environment essentially is at ground potential also, this has big implications for the system. It means that the line-to-ground insulation level of equipment need only be as large as the phaseto-neutral voltage, which is 57.7% of the phase-to-phase voltage. It also means that the system is less susceptible to phase-to-ground voltage transients. 90 Second, the system is suitable for supplying line-to-neutral loads. The operation of a singlephase load connected between one phase and neutral will be the same on any phase since the phase voltage magnitudes are equal. This system arrangement is very common, both at the utilization level as 480 Y/277 V and 208 Y/120 V, and also on most utility distribution systems. While the solidly-grounded wye system is by far the most common solidly-grounded system, the wye arrangement is not the only arrangement that can be configured as a solidly grounded system. The delta system can also be grounded this has a number of disadvantages. The phaseto-ground voltages are not equal, and therefore the system is not suitable for single-phase loads. And, without proper identification of the phases there is the risk of shock since one conductor. A common characteristic of all solidly-grounded systems in general, is that a short-circuit to ground will cause a large amount of short-circuit current to flow. This condition is known as a ground fault and the voltage on the faulted phase is depressed and large current flows in the faulted phase since the phase and fault impedance are small. The voltage and current on the other two phases are not affected. The fact that a solidly-grounded system will support a large ground fault current is an important characteristic of this type of system grounding and does affect the system design. c). Resistive grounding One ground arrangement that has gained in popularity in recent years is the high-resistance grounding arrangement. For low voltage systems, this arrangement typically consists of a wye winding arrangement with the neutral connected to ground through a resistor. The resistor is sized to allow 1-10 A to flow continuously if a ground fault occurs. The resistor is sized to be less than or equal to the magnitude of the system charging capacitance to ground. If the resistor is thus sized, the high-resistance grounded system is usually not susceptible to the large transient overvoltages that an ungrounded system can experience. The ground resistor is usually provided with taps to allow field adjustment of the resistance during commissioning. If no ground fault current is present, the phasor diagram for the system is the same as for a solidly-grounded wye system However; if a ground fault occurs on one phase the system response is that the ground fault current is limited by the grounding resistor. The faulted phase voltage to ground in that case would be zero and the unfaulted phase voltages to ground would be 173% of their values without a ground fault present. This is the same phenomenon exhibited by the ungrounded system arrangement, except that the ground fault current is larger and approximately in-phase with the phase-to-neutral voltage on the faulted phase. The limitation of the ground fault current to such a low level, along with the absence of a solidly-grounded system neutral, has the effect of making this system ground arrangement unsuitable for singlephase line-to- neutral loads. The ground fault current is not large enough to force its removal by taking the system off-line. Therefore, the high-resistance grounded system has the same operational advantage in this respect as the ungrounded system. However, in addition to the improved voltage transient 91 response as discussed above, the high-resistance grounded system has the advantage of allowing the location of a ground fault to be tracked. d). Impedance grounding In industrial and commercial facilities, reactance grounding is commonly used in the neutrals of generators. In most generators, solid grounding may permit the level of ground-fault current available from the generator to exceed the three-phase value for which its windings are braced. For these cases, grounding of the generator neutral through an air-core reactance is the standard solution for lowering the ground fault level. This reactance ideally limits the ground-fault current to the three-phase available fault current and will allow the system to operate with phase-to-neutral loads. 9.2.11.1. Ground Mounted Substations (33/0.4kV and 11/0.4kV) A distribution transformer is normally connected in delta-star with the star winding supplying the load. The neutral point of the star winding is then earthed either directly or through low impedance. Where a distribution transformer is so connected that no neutral is available (normally a transformer connected in star-delta with the delta winding supplying the load), an artificial neutral point is created. For a transformer which supplies only high voltage motors, neutral is frequently earthed via low value impedance usually a resistor. This limits the earth fault currents and the voltage rise above earth at the fault position. Intermediate switchboards and motor control centres are earthed via the sheath/armoured wires of supply cables or via a separate earth continuity conductor or both. It is good practice to provide an additional connection to structural steel work at each high voltage motor by means of either a copper strip or an insulated lead. 9.2.11.2. Pole mounted substations (33/0.4kV and 11/0.4kV) Where surge arresters are installed: The main earth conductor between the surge arrester and the electrode system shall be as short and straight as possible with no sharp bends. Except at locations where it is necessary for an operator to carry out switching operations, the electrode shall be installed at the base of the pole. At locations where it is necessary for an operator to carry out switching operations the earth electrode shall be installed 5m away from the pole to avoid unacceptable step potentials close to the operator. Any earth conductor within 5m of the operating position shall be insulated. The insulated conductor shall be installed inside a PVC duct to provide additional mechanical protection and insulation. It also serves to maintain the conductor in a slow bend which improves lightning performance. The main earth conductor shall be insulated to a depth of 1m below ground level. The earth electrode resistance value shall not exceed 10Ω. Aerial Earth Guard Wire Arc horns Pole leaded Earth wire 92 An earth down lead conductor (stranded galvanized steel wire, size ¾.00mm) shall be stapled to each MV pole in a straight line from 500mm below the lowest conductive part at the top of the pole to the bottom. The conductor shall not be wrapped around the pole at any point since this will increase the reactance of the down lead. The interval between staples shall not exceed 500mm 9.2.12. Distribution lines The permitted earth electrodes are given below. Note: The use of rod electrodes is preferred but due to practical difficulties, particularly in urban areas where damage can be caused to other services, cable electrodes are acceptable. Function Network Fault level Electrode Earth EPN Up to 4kA 35mm2 bare Hard drawn stranded copper cable SPN Up to 8kA 70mm2 bare Hard drawn stranded copper cable EPN/SPN All 1m or 1.2m copper clad earth Rods Electrode Rod Electrode o o o The earth rods shall comply with the requirements of SANS 62305-3 with the additions given below Earth rods shall comply with the requirements of SANS 1063, and earth electrodes shall be installed in accordance with the requirements of SANS 10199. Specific attention is drawn to the requirements for explosive manufacturing and storage areas (see 12.2). Earth mat /and pit Refer to IEEE 80 and ECS 06-0023 o A preformed earth mat (preferred and shown) or an earth mat constructed of bare conductor shall be: o Approximately 1m x 1m in size. o Installed directly below where the operator will stand when operating the switchgear. o Installed at a depth of 300mm below ground. o Connected to the switch handle or control unit. o Segregated from all other earthing conductors where possible. o Protected above ground by a cable guard. o Embedded below ground in earthing compound (two bags below and above) to protect against theft (preformed mat only). Lightning arrestors (line Arrestors) shall refer to IEC 60099 and ECS 06-0023 Pole mounted lightning spikes shall refer to standard IEC60099-4, SABS171 NOTE: Earthing for premises shall be covered under the Wiring standard 93 9.2.13. Fence Metallic fences shall be connected to earth grid at all supporting posts with 35sq.mm copper conductor. The gate shall be connected to an equipotential earth mat 9.2.14. Jointing and bonding Joints shall have a resistance not exceeding that of an equivalent length of conductor and the Engineer may require any joint to be tested to prove compliance with this requirement. All underground connections shall be made by the thermoweld procedure or equivalent. No bolted clamps shall be used for them. No drilling of the earth conductor shall be allowed except for jointing or terminating Joints and connections to the earthing system shall not reduce the current carrying capacity of the earth conductor and shall be to approval. Special precautions shall be taken to ensure that the available contact area is fully utilised in all connections to plant and apparatus. Connections to plant and equipment shall be carried out by using the earthing terminals specified. Stranded earthing conductors shall be terminated with sweated or crimped cable lugs. 9.3. Lightning protection Protection against lightning shall be in accordance with IEC 62305 A substation has to be shielded against direct lightning strikes by provision of overhead earth wires or spikes. This equipment is essential irrespective of the isokeraunic level of the area due to serious consequences and damage to costly equipment in case substation is hit by a direct stroke. The choice between these two methods depends upon several factors economy being the most important consideration. Both the methods have been used sometimes even in the same station. Substations shall be provided with overhead earthed screens or spikes in accordance with the requirements of IEC 62305 to protect against direct lightning stroke to the substation. Down conductors shall be free of joints and they shall be protected by non-metallic sleeves for a height of 1.5 m from the ground. Separate down conductors shall be used only when galvanised steel structure has not sufficient area and current carrying capacity. Generally an angle of shield of about 45° for the area between ground wires and, 30° for other areas is considered adequate for the design of lightning protection system. 9.4. Insulation Co-ordination Insulation Co-ordination shall be in accordance with IEC 60071-2 94 10. VOLTAGE REGULATORS 10.1. General Voltage regulation at the customer metering point shall not exceed: • • +10% for voltages less than 11kV. (Refer to ZS 387-1: 2011) +5% for voltages greater than or equal to 11kV Designers of 11 and 33 kV networks shall ensure that under normal feeding arrangements the 11kV design voltage drop shall be less than 5%. In cases of commercial and industrial customers the overall power factor for loads shall be 0.92 lagging or better, no leading power factor shall be permitted. 10.2. Secondary Transformer Voltage Regulation 10.2.1. Methods of Voltage regulation 10.2.1.1. Line Drop Compensation Line drop compensation is applied in cases of poor regulation. To some Primary and Grid Substations, use of this is dependent on the geographical location of the particular substation and the nature of the circuits it feeds. During the design of line drop compensations voltage control schemes, system volt drop calculations for the feeders have to be conducted and the line drop compensation settings applied accordingly. Distribution substations supplied from the Primary or Grid Substation shall then have their taps set according to their distance (circuit length) from the source. NOTE: The presence of embedded generation will affect the operation of Line Drop Compensation rendering it inappropriate for some 11kV and 33kV networks. 10.2.1.2. Static Balancers Interconnected Star Balancing Transformers, commonly known as Static Balancers improve voltage regulation by redistributing some of the neutral current across the phases. They have proved to be particularly useful on long LV feeders serving small numbers of customers by improving the load balance. 10.2.1.3. Voltage Regulators Where Line Drop Compensation is not appropriate, voltage regulators shall be used. 95 11. CAPACITORS 11.1. Power Capacitors The capacitor units or bank are the fundamental part in each power factor correction installation and/or filter. A thorough study should therefore be performed in order to obtain optimal capacitor design. The capacitor current consists of fundamental and harmonic frequency components. As the magnitude of harmonic components may be very high, especially in a tuned filter, it is necessary to take them into account when defining rated values of the capacitors. For filters the voltage increase on the capacitor caused by the series connection of the reactor should be considered. Refer to IEC61642 (1997). The capacitor bank is the fundamental part in each filter equipment. A thorough study should therefore be performed in order to obtain optimum capacitor design. The filter current consists of fundamental and harmonic frequency components. As the magnitude of harmonic components may be very high, it is necessary to take them into account when defining rated data of the capacitors. The following definitions and designing criteria are specific to filter capacitors: i). Rated capacitor voltage, rated capacitor current and tolerances: see the relevant capacitor standard; ii). The ratings of a capacitor should make allowances for element failure or fuse operation and should co-ordinate with filter protection. During service, if the capacitance change exceeds the acceptable range for the filter, the filter should be disconnected from the system. For further reference, refer to IEC61642 (1997). 11.2. Shunt Capacitors This type of power factor correction installation can be used when it is not necessary to take measures to avoid resonance problems or to reduce harmonics. This is generally the case when the resonant frequency given by the network inductance and the capacitance of the power factor correction installation is relatively high and the harmonic content of the network (i.e. bus voltage and harmonic currents generated by the loads) is very low. It should however be understood that the total resulting capacitance of all power factor correction installations connected to the low voltage side of one distribution transformer determines the possibility of a harmonic resonance problem. Avoiding such problems when the power factor correction installation is already in service can be more difficult and costly than at the original installation time as it is often not possible to re-use existing capacitors, frames, etc. 11.3. Capacitor Banks 96 11.3.1 General This part of the specification covers the design, manufacture, delivery, transportation, and commissioning of capacitor banks. The capacitors shall be installed indoors or outdoors as specified along with the related inrush current reactors, switching facilities and protections. All necessary equipment for the control, protection and supervision of the capacitor banks is also deemed to be included. The capacitor bank shall be factory mounted to a maximum possible extent to reduce the work required at site. The capacitor banks shall be designed as compactly as possible in order to reduce space requirements. The capacitor banks shall be designed for temperature class D (max. 55° C) for outdoor installation and class B (max. 45° C) for indoor installation. 11.3.2 Capacitor Units The capacitor banks shall comprise a series of single phase capacitor units suitably designed for the required total amount of reactive power for the specified frequency and voltage. The capacitor containers shall be of steel with an adequate corrosion protection. The final coat shall comply with « light grey ». The guaranteed minimum values of losses of the capacitor units shall include losses due to discharge resistors which shall be mounted inside each unit to discharge each unit from peak voltage to maximum 75 V in less than 10 minutes. Internal fuses shall be provided in order to limit possible failure to a single capacitor element only. The capacitors shall be able to carry continuously 1.3 times the rated current 1.1 times the maximum system voltage and shall provide continuously 1.35 times the rated output. All the above requirements shall be fulfilled under maximum ambient temperature. The dielectric material shall consist of an all film material being suitable to operate the capacitors on continuous load under the specified ambient conditions. The impregnate shall be of a hydrocarbon type fluid characterised by high electrical strength and adequate physical and chemical properties and shall be non-PCB. Oil to conform to IEC 60296-03. Low toxicity is required and the impregnate shall be a class III B combustible fluid as per IEC 60296-3. Each capacitor shall have one or two bushings dependent on the mounting arrangement. For outdoor installation a creepage distance of 50 mm/kV for open rack material or 25 mm/kV for complete enclosed material and for indoor installation of 25 mm/kV shall be considered. The arrangement of the fixing and the bushings shall be identical in order to easily exchange and replace any capacitor element of the total capacitor bank. The terminals for bushings and fixing elements shall be ISO standard (metric). 97 11.3.3 Capacitor bank A number of capacitor units shall be combined to capacitor banks in double star arrangement. The modules shall be arranged as an assembly on suitably designed enclosure and constructional members of aluminium to avoid any corrosion problem. The capacitor banks shall include all necessary internal connections and busbars, insulators and other fittings. The capacitor enclosure structure shall be designed to carry all required unit capacitors and facilities, and the conductors comprising the incoming and outgoing circuits under the loadings and factors of safety specified and to give the minimum phase and earth clearances. The safe removal and safe replacement of capacitor units shall minimise the dismantling of any structural member, support, including insulators or main connections. Where necessary, approved means shall be provided upon the capacitor equipment for the fixing and bonding of external connections to secure efficient earthing. Steelwork and all items of the capacitor equipment shall be bonded as necessary with copper straps of adequate cross-section. In case of outdoor open rack installation tinned copper shall be used. Approved facilities shall be provided to temporarily earth the connections and apparatus during maintenance. 11.3.4 Switching Device 11.3.4.1 Source circuit breaker The …KV Source circuit breaker is excluded from the scope of supply of the multi-stages capacitor bank equipment. The contractor shall verify with the purchaser that the nominated source circuit breaker is suitable for capacitor switching duties. Tenderers shall state in their tender the circuit breaker requirements for the capacitor bank being offered 11.3.4.2 Capacitor switches Each stage shall be controlled by a suitable SF6 circuit breaker for switching in and out the respective capacitor stage, according to the capacitive demand required by the system operating conditions The tenderer shall provide details of the proposed circuit breaker in his tender, together with evidence that they are suitable for switching duties and that the circuit breaker and associated power equipment will not be subject to damaging over-voltages when switching. 11.3.5 Safety Interlocking and Earthing Interlocking shall be provided to ensure that the access to the capacitor bank enclosure is not possible until the associated main incoming circuit breaker has been racked and the faulty stage has been locked out and circuit earth applied. One earthing switch shall be provided in each capacitor stage and will be placed after the automatic circuit breaker. For safety raison this earthing switch will be also interlocked with the main outgoing feeder. 98 11.3.6 Reactor and discharge device 11.3.6.1 Current limiting reactor The transient current that flows on energising shall not exceed the rated making current of the circuit breaker controlling the capacitor bank stage. If necessary, current limiting reactor shall be connected in series with each capacitor stage to limit the current to an acceptable value. The current calculation which flows upon energising shall be declared and shall take into account the contribution from parallel connected capacitor stages Current limiting reactors shall be designed for the full system lightning impulse withstand level The reactor shall be dry air cored, mounted on suitably rated support insulator. 11.3.6.2 Discharge devices Discharge resistors, suitable to discharge the capacitors from peak rated voltage to less than 75 volt within 10 minutes shall be fitted within the capacitor container. Tenderer shall also propose suitable fast-discharge devices for consideration that will achieve de-energization in less than 30 seconds 11.3.7 Capacitor Protection The capacitor banks/units shall be provided completely with its internal and external protection which is considered as part of the capacitor equipment.. Protection relays shall be of the numerical type. 11.3.7.1 Fuses Fuses shall be provided internally for protection of individual capacitor units. The fuses shall not deteriorate when the capacitor is subjected to discharge testing nor the currents associated with service operations of the capacitor equipment. Fuses shall only rupture in case the related unit is subject to failure and shall be capable of breaking the current following a failure of the capacitor unit without hazard from the fuse or the capacitor. The ruptured fuse of each element shall withstand indefinitely the voltage imposed across it under all operating conditions. The remaining capacitor units shall be able to operate within the capacitor bank without undue disturbance for a present number of unit capacitor failures. 11.3.7.2 Unbalance Protection Sensitive loss of capacitance and fuse failure detection and alarm facilities shall be provided. The protection shall comprise two independently adjustable steps with separate alarm and tripping contacts at each stage. The first stage is set to operate an alarm when a significant number of capacitor units have failed and the second stage shall initiate tripping after a reset time delay via a trip relay (block-close function) before the loss of capacitance has resulted in an unacceptable over-loading of any capacitor. The Tenderer shall submit a table showing the number of units that can be lost per phase and per series group for a period of 1 month without derating of the capacitor bank and without reduction in the designed life of the capacitor. The minimum number of unit capacitors to satisfy these requirements shall not be less than one. The protection shall be insensitive against inrush and harmonic currents. 99 11.3.7.3 Overload and Over-current Protection For each phase of each capacitor bank an overload and overcurrent protection system shall be provided to protect the capacitors from excess current (rms), including harmonic currents. 11.3.7.3.1 Overload protection A first alarm shall be given at a current of approx. 110 to 120 percent of the rated current if applied for more than approx. 30 min. A second alarm (selectable by links for tripping as well) shall be initiated at currents of 120 to 140 percent of the rated current suitably time delayed to avoid spurious alarms (trippings) being situated during short time disturbances. Each stage of the overload protection shall be independently adjustable. 11.3.7.3.2 Over-current protection For currents above 140 percent of the rated current a time delayed relay shall be provided to initiate tripping. An instantaneous element for initiating tripping at currents above 200 percent of rated current, however properly secured against tripping due to inrush currents shall be added per phase with separate alarm and trip contacts. Reference is made to the MV over-current relays specified in Article of these specifications. 11.3.7.4 Over-voltage protection Suitable over-voltage protection devices shall be provided to control transferred internal and external over-voltages on the capacitor banks. 11.3.7.5 Loss of Capacitance Facilities shall be provided to allow for safe, simple and quick identification of defective capacitor units. Portable test equipment or other means shall be supplied being able to detect defective units. 11.3.7.5.1 Protection Scheme The protection scheme shall be designed to isolate the faulted capacitor stage without disruption to the other stages. Schemes which require tripping the main incoming feeder circuit breaker are not acceptable. Over-voltage over-load and unbalance protections may be combined within proprietary relay designed specifically for protection of capacitor banks. 11.3.8 Capacitor Bank Control Automatic and manual switching control shall be provided for the different stages. Automatic control shall be preferably provided by a numerical type of reactive power regulator including harmonic current supervision and the operating mode of each capacitor bank shall be selectable via an Auto/ Manual / Off switch. There shall be On / Off push buttons for manual Close/trip. Manual closing shall only be possible with the selector switch in Manual position. Time delay facilities shall be provided in the manual control circuit to inhibit any re-closing within a set delay time. Delay time shall be adjustable over the range of 0-5 minutes. The automatic control unit will initiate switching f the appropriate number of stages in or out of 100 service. The control unit shall select the capacitor stage to be switched in and means shall be provided to vary the duty cycle to ensure a reasonable distribution of switching operations between different capacitor stages. The control system shall provide facility for manual / remote switching out, both locally and remotely from the control centre. Suitable indications of the status of the capacitor bank shall be provided locally and made available for signalling to the control centre. 11.3.8.1 Control Panel A modular panel housing the individual and master controllers is required to be supplied and will be installed in the control room of the substation. The enclosures shall provide at least IP42 protection to the control equipment. The capacitor bank will be controlled by a logic control scheme as specified in section below: 11.3.8.2 Controller The controller shall automatically switch off the Capacitor Banks in the event of loss of the system supply where applicable. The scheme must be capable of re-starting automatically following restoration of supplies. The automatic sequence of switching IN/OUT of the capacitor units in stages shall be controlled by a programmable logic controller of the power factor controller (PFC). The switching sequence shall be coordinated with the logic control of the sub-station device and Voltage Control (VC) device, and these shall be selectable from manual selection facilities. The switching steps shall be programmable to achieve switching of capacitor sub-banks through stage controlled circuit breaker. 11.3.9 Power Factor Control Where applicable, The PFC relay/equipment shall have a range suitable for proper selection of switching In/Out of the Sub-banks to maintain the Target Power Factor via the PLC. The relay PF setting range shall be: The relay shall have as a minimum a digital display of PF, Target PF, Operation Time Delay, voltage and current. 11.3.10 Testing Each capacitor unit shall be routine tested to IEC 60871-1&2. Type test certification according to IE C60871-1&2. Type test evidence in lieu of tests shall only be accepted on units of identical construction and similar rating to those proposed for this application. Other equipment associated with that capacitor banks shall be subject to routine tests to the relevant IEC standard. 101 12. FEEDER PILLAR 12.1. General 12.2. Specification for Feeder Pillars 12.2.1 General 12.2.1.1 Weatherproof Housing The weatherproof housing shall be manufactured from sheet steel or other approved material and designed for ground mounting on a flat base or pier at or slightly above ground level. Fixing holes shall be provided complete with M16 foundation bolts. It shall be of a totally enclosed design with cables entering from the bottom. The housing shall be arranged for front access only by means of side hinged doors which shall be fitted with an internal document holder and a locking bar to secure them top and bottom. The locking bar shall be operated by a central handle which shall be lockable by means of a padlock. The housing shall be dust and vermin proof but adequate ventilation shall be maintained to permit natural circulation of filtered air. Provision shall be made for the installation of an electrical heating device to prevent condensation within the housing. Such heaters shall be of the metalclad convection type and shall be continuously rated complete with fuses and control switch. 12.2.1.2 Incoming Cables, Links, Busbars and Conductors Links, busbars and conductors shall be manufactured from hard drawn high conductivity copper and arranged for access from the front only. The busbars must be fully shrouded. Phase cables shall be connected to the distribution board busbars by pole operated hinged slow break links. The neutral connection shall be made by means of a bolted copper link. Links shall be of the same current rating as the associated busbar. Busbar support insulators shall be capable of withstanding rated short circuit conditions without undue stress and be resistant to mechanical shock and vibration however caused. 12.2.1.3 Distribution Circuits Each distributor board shall be equipped for the number of 3 phase, 4 wire distributor circuits as specified by the purchaser. Each phase circuit shall be controlled by high rupturing capacity cartridge type fuse links which conform to IEC 60282 part 1&2;1994. Insulated dividing barriers shall be provided between phase contact assemblies and phase and neutral contact assemblies which shall make it impossible to insert a fuse link between contacts of different phases. 12.2.1.4 Instrument Panel The accessories to be provided on each distribution board are specified by the purchaser. 102 12.2.1.5 Future Requirement The feeder circuits shall be so designed that additional current transformers can be easily incorporated so that separate kilowatt hour meters can be installed to record the consumption in each feeder. 12.2.1.6 Cable Glands Each item of equipment shall be supplied with a complete set of screw type compression cable glands suitable for outdoor use with those cables specified in the schedules. Each gland shall be capable of carrying the short circuit current rating of its associated cable and be provided with such fittings necessary for fixing in an untapped entry hole. 12.2.1.7 Cable Termination Lugs Each item of equipment shall be supplied with a complete set of termination lugs and fixing bolts for the types of cables specified by the purchaser. 12.2.1.8 Fuses and Fuse Carriers 12.2.1.8.1 Fuses for Distributor Circuits The fuse links shall be in accordance with the requirements 0f IEC 60269 having single tag contacts for insertion into spring loaded contacts. Each distribution pillar shall be provided with an insulated fuse removal device. The nominal rating of the fuses shall be one of the standard values within the range 125 A to 400 A. Within this range the fuses shall be of the same physical dimensions irrespective of the rating. 12.2.1.8.2 Fuse links All fuses shall be of appropriate duty, category and conform to IEC 60269. They shall be fully interchangeable with those of any other make which conform to the dimensions described in IEC 60269. The fuse links shall be fitted with striker-pins to actuate the common trip-bar of the fuse switch. 12.2.1.8.3 Fuses for Auxiliary Supply Fuse carriers for auxiliary circuits shall be of the withdrawable handle insulator type with a rating of 60 A and shall accommodate cartridge type fuse links of 15 A, 30 A and 60 A ratings. The fuse links shall conform to IEC 60269. 12.2.1.9 Enclosures To conform to IEC 60529 (Degrees of Protection for Enclosures) 103 13. SUBSTATION CONCRETE WORKS 13.1 General This section covers the construction of cast in-situ reinforced concrete slabs and plinths onto which mechanical/electrical equipment is to be fixed, concrete slabs used for the protection of cables as well as grouting and screeding. 13.2 Substation equipment plinths 13.2.1 Concreting All concrete units will be solidly formed using concrete and steel reinforcing as indicated on drawings which will be submitted to the engineer for approval within 30 days of the contract having been awarded. Drawings will be submitted in threefold. Each unit will have rectangular sides. In general the edges of pockets for holding-down bolts or the centre-lines of holes drilled for expansion bolts will not be closer than 100 mm to any concrete edge. The concrete unit will furthermore be designed to be adequate to carry and distribute all live and imposed loads. For concrete units to be constructed in situ, the excavation will be made 600 mm wider than the outside dimensions of the unit and to a minimum depth of 200 mm below the lowest point of the finished ground level (measured along the perimeter of the concrete unit). The bottom of the excavation will be levelled and compacted to 93% of modified AASHTO density. A 50 mm thick level concrete blinding layer will be cast covering the entire bottom of the excavation and will be allowed to set for at least one day, after which the construction of the concrete unit (fixing of reinforcement, erection of formwork, casting of concrete, etc) will take place. The top of the concrete unit will protrude for a minimum of 200 mm above the highest point of the finished ground level (measured along the perimeter of the unit). No concrete will be cast without the engineer having had the opportunity to inspect and approve the formwork and reinforcing. The formwork will not be removed before 7 days, and installation of mechanical/electrical equipment will not commence until 28 days after the concrete have been cast. For concrete units constructed on floors which have been constructed by others, adequate dowelling and bonding of the surfaces of the concrete unit and the existing floor will be included. 13.2.1.1 Concrete mix The following concrete mix will be used: Cement (dry) Clean dry river sand Crushed stone (10 mm) 1 part per volume 3 parts per volume 6 parts per volume The concrete will have 28-day minimum cube strength of 10 MPa. 13.2.2 Reinforcing Standard brick force as used in 230 mm brick walls will be used as reinforcing and will be indicated on the drawings. 104 All reinforcing will be inspected by the engineer prior to the concrete being cast. 13.2.3 Grouting Grout under base plates and machine bases which are subjected only to gravity loading shall consist of 1:1 sand, cement semi-dry mortar well caulked into the grouting space, unless otherwise specified by the supplier of the equipment. The relevant concrete surfaces shall be prepared by scrabbing and cleaning them. The mortar grout shall consist of an approved mixture of cement, sand, water, and admixture, and shall be so rammed under each base or bedplate (as applicable) that all voids and pockets are completely filled around the bolt or between the top of the concrete and the underside of the metalwork, and, in the case of a base or a bedplate, that the grout projects beyond the base or bedplate. After the void has been completely filled, the edges of the mortar grout shall be trimmed at an angle of 45 outward from the bottom edges of each base or bedplate and the trimmed edge wood-floated to a neat finish. Grout used in bolted fastenings which are subjected to tensile, shear and/or vibration loads shall be an approved epoxy mortar well caulked into the grouting space, bolt hole pocket or sleeve, unless otherwise specified by the supplier of the equipment. 13.2.4 Dimensions The dimensions shall be as indicated on the drawings provided. 13.2.5 Finishing At all corners that are exposed after backfilling, the concrete will be chamfered 25 mm x 25 mm. The concrete will be well vibrated to eliminate cavities or honeycombing. Unformed horizontal surfaces (top of concrete) will be floated with a wooden trowel to render a uniform, skid resistant, horizontal surface. 13.2.6 Testing of Concrete A sample from each batch of concrete will be taken by the Engineer or his representative for testing purposes. 13.3 Oil containment tanks (Definition - Refers to a vessel made from concrete or masonry that is usually wholly or partially buried, that provides containment of lost oil and can also be an oil/water separator.) 13.3.1 Bund Walls Bunds shall be designed to contain spillages and leaks of liquids used, stored or processed above ground and to facilitate clean-up operations. As well as being used to prevent pollution of the receiving environment, bunds are also used for fire protection, product recovery and process isolation 105 14. WAYLEAVE The requirements for the acquisition, management and operation of wayleaves shall be in accordance with the Zambian Wayleave Code of Practice. Notwithstanding the provisions of the Wayleave Code of Practice the following requirements shall also apply: 14.1. General Requirements General requirements relating to access to land and premises by a Distribution System Operator are as follows: 14.1.1 Occupational staff and contractors acting for an electricity utility company will be briefed on their responsibilities before entering private lands (or premises) or dealing with owners. 14.1.2 The electricity utility company will take reasonable steps to contact the owner of the land (or premises) before entering private lands (or premises). The company staff or contractors will carry identification cards and produce this to the owner of the land (or premises) when introducing themselves. 14.1.3 The owners of land (or premises) will be dealt with honestly and fairly. 14.1.4 Queries from the owner of the land (or premises) will be dealt with promptly and courteously. 14.1.5 Company staff or contractors will only enter lands or premises for legitimate purposes related to its licensed activities including surveying, maintenance, construction and meter reading. 14.1.6 Company staff and contractors will take due care and attention to minimize land damage by crews and equipment. 14.1.7 Due care and attention will be taken to minimize the risk of spreading any disease to or from farmland. 14.1.8 Company staff and contractors will take reasonable steps to ensure that land (or premises) is left in as good (or better) state than when Company staff or contractors arrived. 14.1.9 Company staff and contractors will endeavor to ensure that restrictions on the use of the land (or premises) during construction are minimized. 14.1.10 In the event of queries from the owner of the land (or premises) for further information, a contact telephone number for the company will be advised to allow for such queries to be dealt with. 14.2. 14.2.1 Specific requirements Staff shall take great care to close all gates behind them and not to damage excessively fences or hedges. Any non-self-restoring damage done to fences or hedges shall be made good by company staff within one month of agreement and any damage which requires urgent attention shall be made good or rectified within one week of notification. 106 14.2.2 Trial holes in advance of the main construction programmes, where necessary, shall be opened only after consultation with the landowner. The method of carrying out this work, shall be such as to cause the least disturbance. The trial holes shall either be opened and filled in on the same day or made safe with fencing. The topsoil shall be stacked to one side separately for reinstatement when refilling the hole. The subsoil shall be properly compacted and the topsoil spread over it neatly. Rock and other debris thrown up by the excavation shall be removed off the site by company staff. Stones thrown up by the excavation shall be removed from the surface. a). Before any construction work commences, a representative from the electricity company will discuss the entry routes for construction and as far as possible give the landowner the proposed programme of work and the date of commencement of work. b). Company representatives shall leave with the owner of land or premises, the name and address of the person to be contacted in the event of any queries arising out of the company‟s activities on the land or premises. c). Where construction work is to take place and the entry routes have been agreed, if the landowner requires, the agreed route shall be outlined by posts placed at suitable intervals. These marking posts shall not be required in the case of single entry, such as for wood d). pole erection but must be provided, in the case of multiple entries such as concreting operations. 14.2.3 The electricity company will cut up any trees that may be felled into transportable lengths and bring them to the farmyard or other adjacent storage place. The company shall dispose of rubbish and all debris from hedge and tree cutting caused by its activities during line construction and maintenance operations. The landowner or his representative shall be notified in advance of entry by the company for purposes of hedge trimming and tree cutting in connection with line construction and maintenance. a). Fences shall be provided by the company as necessary for the protection of persons, animals or crops and to prevent trespass. It must conform to the reasonable requirements of the landowner. The type of fencing should depend on its location, purpose and its expected stay in a particular location. b). If a fenced off area crosses existing farm pathways or roadways, or other access routes required by the landowner, the company shall provide a means of crossing them to the reasonable requirements of the landowner, for passage of persons, machinery and livestock. c). All permanent pathways and roadways affected by the construction shall be restored to their original condition before construction started or alternative arrangements agreed. d). Before construction work or trial boring operations commence, the landowner shall notify the company insofar as he knows of the position, type and size of all underground services, pipelines, drains and wells. e). All watercourses and water supplies must be protected against pollution arising 107 f). g). h). i). j). 14.3. from the work. All proper steps shall be taken to avoid any interference with water supplies. Where construction work interferes with drainage or septic tanks, these facilities shall be maintained by the electricity company with the minimum of interruption during the course of the work and the landowner shall provide all necessary access facilities to enable the company to do so. They shall be subsequently restored to the satisfaction of the landowner or an alternative equivalent service provided. All ditches, open drains or watercourses interfered with by the works shall be maintained in effective condition during construction and finally restored to as good a condition as before the commencement of works. In excavation where rock has been removed from the foundations, priority shall be given to the removal off site of broken rock where it is surplus to back filing requirements, if required by the landowner. On completion of works, the company shall remove all temporary buildings, roadways, surplus soil, stone or gravel and any debris such as trees, brush woods and any material that does not naturally belong on the site and was brought there through the operations of the company. The utility company, after consultation with the landowner, shall take all necessary precautions to prevent the straying of livestock. Prevention against Animal diseases 14.3.1 The utility company shall comply with any regulation which may be necessary in connection with any Disease Eradication Scheme. The company shall ensure that the local District Veterinary Officer is informed of the entry of company vehicles on farms with a disease problem and that the Epidemiology Unit of the Department of Agriculture is made aware of the company activities in a TB affected area. 14.3.2 Where possible the company shall not drive machinery through farmyards or other places where there is an accumulation of animal manure. If this is necessary, the company shall take adequate precautions to disinfect vehicles before and after entering the land, especially on farms with a disease problem (or with neighbouring farms having a disease problem), or where the company vehicles have recently been in a farm with a disease problem. 108 15. LONG-TERM PRESERVATION OF SUPPORT STRUCTURES FOR DISTRIBUTION INFRASTRUCTURE 15.1 Painting The following paint and treatment shall apply to the listed types of poles; Type of Poles Paint and treatment Exceptions (aviation purposes) Wooden Poles Creosote (preservative) Signal red and white Concrete poles Gray Signal red and white Steel poles Admiral gray Signal red and white 15.2 Concrete Poles Concrete poles shall maintain the natural colour. Install reflective barrier for concrete poles in close proximity to roads. Concrete shall be manufactured in line with SANS 470 15.3 Steel Poles The Steel poles shall be hot dip galvanized in accordance to relevant Standards Install reflective barrier for steel poles in close proximity to roads 15.4 Steel Structures for Outdoor Substations Steel structures shall be hot dip galvanized in accordance to a relevant standards e.g. ZS COMESA 293 AND IEC 61400. 109 APPENDICES APPENDIX 1: INFORMATION REQUIRED WITH TRANSFORMER ENQUIRY AND ORDER A.1 Rating and general data A.1.1 Normal information The following information shall be given in all cases: a). b). c). d). e). f). g). h). i). j). k). l). m). n). o). p). q). r). s). t). Particulars of the specifications to which the transformer shall comply; Kind of transformer, for example, separate winding transformer, auto-transformer or booster transformer; Single or three-phase unit; Number of phases in system; Frequency; Dry-type or oil-immersed type. If oil-immersed type, whether mineral oil or synthetic insulating liquid. If dry-type, degree of protection (see IEC 60529). Indoor or outdoor type. Type of cooling. Rated power for each winding and, for tapping range exceeding ± 5%, the specified maximum current tapping, if applicable. If the transformer is specified with alternative methods of cooling, the respective lower power values are to be stated together with the rated power (which refers to the most efficient cooling). Rated voltage for each winding For a transformer with tappings: – which winding is tapped, the number of tappings, and the tapping range or tapping step; – whether 'off-circuit' or 'on-load' tap-changing is required; – if the tapping range is more than ±5 %, the type of voltage variation, and the location of the maximum current tapping, if applicable. Highest voltage for equipment (Um) for each winding (with respect to insulation, see IEC 60076-3). Method of system earthing (for each winding). Insulation level (see IEC 60076-3), for each winding. Connection symbol and neutral terminals, if required for any winding. Any peculiarities of installation, assembly, transport and handling. Restrictions on dimensions and mass. Details of auxiliary supply voltage (for fans and pumps, tap-changer, alarms, etc.). Fittings required and an indication of the side from which meters, rating plates, oil-level indicators, etc., shall be legible. Type of oil preservation system. For multi-winding transformers, required power-loading combinations, stating, when necessary, the active and reactive outputs separately, especially in the case of multiwinding auto-transformers. 110 A.1.2 Special information The following additional information may need to be given: a). b). c). d). e). f). g). h). i). j). k). l). m). n). o). p). q). r). s). If a lightning impulse voltage test is required, whether or not the test is to include chopped waves (see IEC 60076-3). Whether a stabilizing winding is required and, if so, the method of earthing. Short-circuit impedance, or impedance range (see annex C). For multiwinding transformers, any impedances that are specified for particular pairs of windings (together with relevant reference ratings if percentage values are given). Tolerances on voltage ratios and short-circuit impedances as left to agreement in table 1, or deviating from values given in the table. Whether a generator transformer is to be connected to the generator directly or through switchgear, and whether it will be subjected to load rejection conditions. Whether a transformer is to be connected directly or by a short length of overhead line to gas-insulated switchgear (GIS). Altitude above sea-level, if in excess of 1 000 m (3 300 ft). Special ambient temperature conditions or restrictions to circulation of cooling air. Expected seismic activity at the installation site which requires special consideration. Special installation space restrictions which may influence the insulation clearances and terminal locations on the transformer. Whether load current wave shape will be heavily distorted. Whether unbalanced threephase loading is anticipated. In both cases, details to be given. Whether transformers will be subjected to frequent overcurrents, for example, furnace transformers and traction feeding transformers. Details of intended regular cyclic overloading other than covered by 4.2 (to enable the rating of the transformer auxiliary equipment to be established). Any other exceptional service conditions. If a transformer has alternative winding connections, how they should be changed, and which connection is required ex works. Short-circuit characteristics of the connected systems (expressed as short-circuit power or current, or system impedance data) and possible limitations affecting the transformer design (see IEC 60076-5). Whether sound-level measurement is to be carried out (see IEC 60551). Vacuum withstand of the transformer tank and, possibly, the conservator, if a specific value is required. Any special tests not referred to above which may be required. A.2 Parallel operation If parallel operation with existing transformers is required, this shall be stated and the following information on the existing transformers given: a) Rated power. b) Rated voltage ratio. c) Voltage ratios corresponding to tappings other than the principal tapping. d) Load loss at rated current on the principal tapping, corrected to the appropriate reference temperature. e) Short-circuit impedance on the principal tapping and at least on the extreme tappings, if the tapping range of the tapped winding exceeds ±5 %. f) Diagram of connections, or connection symbol, or both. NOTE On multi-winding transformers, supplementary information will generally be required.