HVAC Guide Specifications Multi Indoor Unit, Variable Refrigerant Flow Section 15700 – Mechanical HVAC Size Range: 6 TO 24 TONS NOMINAL HEAT PUMP Model Numbers Ton 6 8 12 14 16 18 20 22 24 Capacity (Btu/ h) 72,000 96,000 144,000 168,000 192,000 216,000 240,000 264,000 288,000 Model name AOUA72RLBV AOUA96RLBV AOUA144RLBVG AOUA168RLBVG AOUA192RLBVG AOUA216RLBVG AOUA240RLBVG AOUA264RLBVG AOUA288RLBVG 1.01 SYSTEM DESCRIPTION The variable capacity heat pump air conditioning system shall be a Fujitsu Airstage VII. The Heat Pump system shall consist of AOUA outdoor units, multiple indoor units, and Fujitsu DDC (Direct Digital Controls). Each indoor unit or group of indoor units shall be independently controlled. The sum of connected capacity of all indoor air handlers shall range from 50% to 130% of outdoor rated capacity. 1.02 QUALITY ASSURANCE A. The units shall be listed by Electrical Laboratories (ETL) and bear the ETL label. B. All wiring shall be in accordance with the National Electrical Code (N.E.C.). C. The units shall be manufactured in a facility registered to ISO 9001 and ISO14001 which is a set of standards applying to environmental protection set by the International Standard Organization (ISO). D. A full charge of R-410A for the condensing unit only shall be provided in the condensing unit. 1.03 DELIVERY, STORAGE AND HANDLING A. Unit shall be stored and handled according to the manufacturer’s recommendation. Part 2 – Warranty 2.01 The units shall be covered by the manufacturer’s limited warranty for a period of one (1) year on parts and 2 years on the compressor from date of installation. The units shall be covered by an extended manufacturer’s limited warranty for a period of five (5) on parts and 7 years on the compressor from date of installation, provided If the systems are: 1) designed by a certified AIRSTAGE VII Designer, 2) installed by a certified AIRSTAGE VII Dealer, AND 3) verified with a completed commissioning report submitted to Fujitsu Service Department. If, during this period, any part should fail to function properly due to defects in workmanship or material, it shall be replaced or repaired at the discretion of the manufacturer. This warranty shall not include labor. 2.02 Manufacturer shall have a minimum of twelve years of HVAC experience in the U.S. market 2.03 The AIRSTAGE VII system shall be installed by a Fujitsu authorized AIRSTAGE VII Dealer with extensive AIRSTAGE VII installation and service training. The mandatory contractor service and installation training should be performed by the manufacturer. Part 3 – Outdoor Units 3.01 Heat Pump Outdoor Unit A. General: The Fujitsu Airstage VII Heat Pump AOUA outdoor unit shall be specifically used with AIRSTAGE VII components. The AOUA outdoor units shall be equipped with multiple circuit boards that interface to the Fujitsu DDC controls system and shall perform all functions necessary for operation. Each outdoor unit module shall be completely factory assembled, piped, wired and run tested at the factory. 1. The model nomenclature and unit requirements are shown below. All units requiring a factory supplied Outdoor Branch Kit shall be piped together in the field, without the need for equalizing line(s). If an alternate manufacturer is selected, any additional material, cost, and labor to install additional lines shall be incurred by the contractor. 208/230 Volt Model Number AOUA72RLBV AOUA96RLBV AOUA144RLBVG AOUA168RLBVG AOUA192RLBVG AOUA216RLBVG AOUA240RLBVG AOUA264RLBVG AOUA288RLBVG Units 1 1 2 2 2 3 3 3 3 Outdoor Branch Kit None None UTR-CP567X UTR-CP567X UTR-CP567X UTR-CP567X UTR-CP567X UTR-CP567X UTR-CP567X 2. Outdoor unit shall have a sound rating no higher than 61 dB(A) individually or 65 dB(A) twinned. Units shall have a sound rating no higher than 50 dB(A) individually or 55 dB(A) twinned while in Low Noise Mode operation. If an alternate manufacturer is selected, any additional material, cost, and labor to meet published sound levels shall be incurred by the contractor. 3. Outdoor unit shall be able to connect to up to 45 indoor units depending upon model. 4. Both refrigerant lines from the outdoor unit to indoor units shall be insulated. 5. The outdoor unit shall have an accumulator with refrigerant level sensors and controls. 6. The outdoor unit shall have a high pressure safety switch, over-current protection and DC bus protection. 7. The outdoor unit shall have the ability to operate with a maximum height difference of 164 feet and have a total refrigerant tubing length of 3,280 feet. The greatest length is not to exceed 492 feet between the outdoor unit and the indoor units without the need for line size changes or traps. 8. The outdoor unit shall be capable of operating in heating mode down to -4F ambient temperature or cooling mode down to 5F ambient temperature for single outdoor unit installations and 23F for multiple outdoor unit installations, without additional low ambient controls. If an alternate manufacturer is selected, any additional material, cost, and labor to meet low ambient operating condition and performance shall be incurred by the contractor. 9. The outdoor unit shall have a high efficiency oil separator plus additional logic controls to ensure adequate oil volume in the compressor is maintained. B. 1. Unit Cabinet: The casing(s) shall be fabricated of painted galvanized steel. C. Fan: 1. Each outdoor unit module shall be furnished with one direct drive, variable speed propeller type fan. 2. The fan shall have a high performance DC motor. 3. The fan motor shall have inherent protection, have permanently lubricated bearings, and be completely variable speed. 4. The fan shall be factory set for operation under 0 in. WG external static pressure, but capable of normal operation under a maximum of 0.32 in. Outdoor unit external static pressure set via Outdoor Unit Function Setting or with a dip switch in the outdoor unit. 5. The fan motor shall be mounted for quiet operation. 6. The fan shall be provided with a raised guard to prevent contact with moving parts. 7. The outdoor unit shall have vertical discharge airflow. D. 1. Refrigerant R410A refrigerant shall be required for AOUA outdoor unit systems. E. Coil: 1. The outdoor coil shall be of nonferrous construction with corrugated plate fins on copper tubing. 2. The coil fins shall have a factory applied corrosion resistant blue-fin finish. 3. The coil shall be protected with an integral metal guard. 4. Copper tubing used for heat exchanger shall have internal spiral grooves for improved heat transfer. F. Compressor: 1. Each outdoor unit module shall be equipped with one inverter driven twin rotary hermetic compressor. Non inverter-driven compressors shall not be allowed. 2. A crankcase heater shall be factory mounted on the compressor. 3. The outdoor unit compressor shall have an inverter to modulate capacity. The capacity shall be completely variable with a turndown of 30%-100% of rated capacity, depending upon unit size. 4. The compressor shall be equipped with an internal thermal overload. 5. The compressor shall be mounted to avoid the transmission of vibration. G. Electrical: 1. The outdoor unit electrical power shall be 208/230 volt, 3-phase, 60 hertz. 2. The unit shall be capable of satisfactory operation within voltage limitations of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). H. Control 1. The outdoor unit shall be controlled by integral microprocessors. 2. The control circuit between the indoor units and the outdoor unit shall be completed using a 22 AWG, 2-conductor, Solid Core, non-polar twisted pair shielded LON Compatible cable to provide total integration of the system. 3. The control circuit between outdoor units on the same refrigerant circuit shall be completed using a 22 AWG, 2-conductor, Solid Core, non-polar twisted pair shielded LON Compatible cable. 4. The control circuit between master outdoor units on different refrigerant circuits shall be completed using a 22 AWG, 2-conductor, Solid Core, non-polar twisted pair shielded LON Compatible cable. Part 4 – Indoor Units 4.01 Compact Wall Mounted and Wall Mounted Indoor Units (ASUA) A. General: 1. The ASUA shall be a wall-mounted indoor unit section and shall have a modulating Electronic Expansion Valve (EEV). The ASUA shall be used with the AOUA Heat Pump Outdoor Unit. The ASUA shall support individual control using Fujitsu DDC controllers. 2. The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating Electronic Expansion Valve (EEV), control circuit board and fan motor. 3. The unit shall have an auto restart function. C. Unit Cabinet: 1. The casing shall have a white finish. 2. Multi directional drain and refrigerant piping offering four (4) directions for refrigerant piping and four (4) directions for draining shall be standard. 3. There shall be a separate back plate which secures the unit firmly to the wall. D. Fan: 1. The indoor fan shall be an assembly with one or two line-flow fan(s) direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. A manual adjustable guide vane shall be provided with the ability to change the airflow from side to side (left to right) in 18 MBH and 24 MBH units. 4. A motorized air sweep louver shall provide an automatic change in airflow by directing the air up and down to provide uniform air distribution. E. 1. Filter: Return air shall be filtered by means of an easily removable, washable filter. F. Coil: 1. The indoor coil shall be of nonferrous construction with louvered fins on copper tubing. 2. The tubing shall have inner v grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. 6. A condensate pan and drain shall be provided under the coil. Both refrigerant lines to the ASUA indoor units shall be insulated. G. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase and 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187228 volts (208V/60Hz) or 207-253 volts (230V/60Hz) H. Controls: 1. This unit shall use controls provided by Fujitsu to perform functions necessary to operate the system. 4.02 Compact Cassette Indoor Unit (AUUA) A. General: 1. The AUUA shall be a four-way cassette style indoor unit that recesses into the ceiling with a ceiling grille. The AUUA shall be used with the AOUA Heat Pump Outdoor Unit. The ASUA shall support individual control using Fujitsu DDC controllers. 2. The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating Electronic Expansion Valve (EEV), control circuit board and fan motor. 3. The unit shall have an auto restart function. B. Unit Cabinet: 1. The cabinet shall be a compact 22-7/16” wide x 22-7/16” deep so it will fit within a standard 24” square suspended ceiling grid. 2. The unit shall have provisions for a field installed filtered outside air intake. 3. Four-way grille shall be fixed to bottom of cabinet allowing two, three or four-way blow. C. Fan: 1. The indoor fan shall be an assembly with a turbo fan direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor fan shall consist of three (3) speeds, Low, Mid, and High. 4. The fan shall have a selectable Auto fan setting that will adjust the fan speed based on the difference between controller set-point and space temperature. 5. The indoor unit vanes shall have 4 fixed positions and a swing feature that shall be capable of automatically swinging the vanes up and down for uniform air distribution. 6. The indoor unit shall have an adjustable air outlet system offering 4-way airflow, 3-way airflow, or 2-way airflow. D. 1. Filter: Return air shall be filtered by means of a long-life washable filter. E. Coil: 1. The indoor coil shall be of nonferrous construction with louvered fins on copper tubing. 2. The tubing shall have inner v grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. The unit shall be provided with an integral condensate lift mechanism that will be able to raise drain water 27 1/2” inches above the bottom of the unit. 7. Both refrigerant lines to the AUUA indoor units shall be insulated. F. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). G. Controls: 1. This unit shall use controls provided by Fujitsu to perform functions necessary to operate the system. 4.03 Ceiling Cassette Indoor Unit (AUUB) A. General: 1. The AUUB shall be a four-way cassette style indoor unit that recesses into the ceiling with a ceiling grille. The indoor unit shall be factory assembled, wired and run tested. The AUUB shall be used with the AOUA Heat Pump Outdoor Unit. The ASUA shall support individual control using Fujitsu DDC controllers. 2. Contained within the unit shall be all factory wiring, piping, electronic modulating Electronic Expansion Valve (EEV), control circuit board and fan motor. 3. The unit shall have an auto restart function. 4. Indoor unit and refrigerant pipes shall be charged with dehydrated air before shipment from the factory. B. Unit Cabinet: 1. The cabinet shall be space-saving ceiling-recessed cassette. 2. The cabinet panel shall have provisions for a field installed filtered outside air intake. 3. Branch ducting shall be allowed from cabinet. 4. Four-way grille shall be fixed to bottom of cabinet allowing two, three or four-way blow. 5. The grille vane angles shall be individually adjustable from the Wired Remote Controller to customize the airflow pattern for the conditioned space. C. Fan: 1. The indoor fan shall be an assembly with a turbo fan direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor fan shall consist of three (3) speed settings, Low, Mid and High. 4. The fan shall have a selectable Auto fan setting that will adjust the fan speed based on the difference between controller set-point and space temperature. 5. The indoor unit shall have an adjustable air outlet system offering 4-way airflow, 3-way airflow, or 2-way airflow. 6. The indoor unit shall have switches that can be set to provide optimum airflow based on ceiling height and number of outlets used. 7. The indoor unit vanes shall have 4 fixed positions and a swing feature that shall be capable of automatically swinging the vanes up and down for uniform air distribution. 8. The vanes shall have an Auto-Wave selectable option in the heating mode that shall randomly cycle the vanes up and down to evenly heat the space. D. 1. Filter: Return air shall be filtered by means of a long-life washable filter E. Coil: 1. The indoor coil shall be of nonferrous construction with louvered fins on copper tubing. 2. The tubing shall have inner v grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. The unit shall be provided with an integral condensate lift mechanism that will be able to raise drain water 33 inches above the bottom of the unit. 7. Both refrigerant lines to the AUUB indoor units shall be insulated. F. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). G. Controls: 1. This unit shall use controls provided by Fujitsu to perform functions necessary to operate the system. 4.04 Slim Compact Duct Indoor Unit (ARUL) A. General: 1. The ARUL Slim Compact Duct Unit shall be a ceiling-concealed ducted indoor fan coil that mounts above the ceiling with a rear return and a fixed horizontal discharge supply and shall have a modulating Electronic Expansion Valve (EEV). The ARUL shall be used with AOUA Heat Pump outdoor unit. The ARUL shall support individual control using Fujitsu DDC controllers. 2. ARUL Slim Compact Duct models shall have an extremely compact profile (77/8”) which requires minimal ceiling space. ARUL models shall feature external static pressure settings up to 0.35 in. WG. 3. The ARUL unit shall also have the ability to operate both horizontally and vertically. 4. The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating Electronic Expansion Valve (EEV), control circuit board and fan motor. 5. The unit shall have an auto restart function. B. 1. Unit Cabinet: The cabinet shall be space saving, low profile, ceiling-concealed ducted. C. Fan: 1. The indoor unit fan shall be an assembly with one Sirocco fan direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor fan shall consist of three (3) speeds, High, Mid, and Low. 4. The indoor unit shall have a ducted air outlet system and ducted return air system. D. Filter: 1. Return air shall be filtered by means of a standard factory installed return air filter. E. Coil: 1. The indoor coil shall be of nonferrous construction with louvered fins on copper tubing. 2. The tubing shall have inner v grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. The unit shall be provided with an integral condensate lift mechanism able to raise drain water 21 inches above the condensate pan. 7. The unit shall have a curved condensate pan that enables the unit to be installed in a vertical configuration. 8. Both refrigerant lines to the ARUL indoor units shall be insulated. E. Electrical: 1. The unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). F. Controls: 1. This unit shall use controls provided by Fujitsu to perform functions necessary to operate the system. 4.05 Duct Indoor Unit (ARUM) A. General: 1. The ARUM Low Static Pressure Duct/Duct unit shall be a ceiling concealed ducted indoor fan coil that mounts above the ceiling with a fixed rear return and a horizontal discharge supply, and shall have a modulating Electronic Expansion Valve (EEV). 2. The ARUM shall be used with the AOUA Heat Pump outdoor unit. 3. The ARUM shall support individual control using Fujitsu DDC controllers. 4. ARUM Low Static Pressure Duct/Duct models shall feature external static pressure settings up 0.60 in. WG. 5. The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating Electronic Expansion Valve (EEV), control circuit board and fan motor. 6. The unit shall have an auto restart function. B. Unit Cabinet: 1. The cabinet shall be ceiling-concealed, ducted. 2. The cabinet panel shall have provisions for a field installed filtered outside air intake. C. Fan: 1. The indoor unit fan shall be an assembly with one or two Sirocco fan(s) direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor unit shall have a ducted air outlet system and ducted return air system. D. 1. Filter: Return air shall be filtered by a field-supplied filter. E. Coil: 1. The indoor coil shall be of nonferrous construction with louvered fins on copper tubing. 2. The tubing shall have inner v grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. 7. The condensate shall be gravity drained from the fan coil. Both refrigerant lines to the ARUM indoor units shall be insulated. F. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). H. Controls: 1. This unit shall use controls provided by Fujitsu to perform functions necessary to operate the system. 4.06 High Static Pressure Duct Indoor Unit (ARUH) A. General: 1. The ARUH (High Static Pressure Duct) unit shall be a ceiling concealed ducted indoor fan coil that mounts above the ceiling with a fixed rear return and a horizontal discharge supply, and shall have a modulating Electronic Expansion Valve (EEV). 2. The ARUH shall be used with the AOUA Heat Pump outdoor unit. The ARUH shall support individual control using Fujitsu DDC controllers. 3. ARUH (HIGH STATIC Pressure Duct) models shall feature external static pressure settings up 1.20 in. WG. 4. The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating Electronic Expansion Valve (EEV), control circuit board and fan motor. 5. The unit shall have an auto restart function. B. Unit Cabinet: 1. The cabinet shall be ceiling-concealed, ducted. 2. The cabinet panel shall have provisions for a field installed filtered outside air intake. C. Fan: 1. The indoor unit fan shall be an assembly with one or two Sirocco fan(s) direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor unit shall have a ducted air outlet system and ducted return air system. D. 1. Filter: Return air shall be filtered by a field-supplied filter. E. Coil: 1. The indoor coil shall be of nonferrous construction with louvered fins on copper tubing. 2. The tubing shall have inner v grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. 7. The condensate shall be gravity drained from the fan coil. Both refrigerant lines to the ARUH indoor units shall be insulated. F. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase and 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). G. Controls: 1. This unit shall use controls provided by Fujitsu to perform functions necessary to operate the system. 4.07 Universal Floor/Ceiling and Ceiling Indoor Unit (ABUA) A. General: 1. The ABUA shall consist of a Universal Floor/Ceiling mount or Ceiling mount indoor section that can be suspended from the ceiling, placed low on the wall or rested on the floor. 2. The ABUA shall be used with theAOUA Heat Pump outdoor unit. The ABUA shall support individual control using Fujitsu DDC controllers. 3. The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating Electronic Expansion Valve (EEV), control circuit board and fan motor. 4. The unit shall have an auto restart function. B. 1. Unit Cabinet, The casing shall have a white finish. C. Fan: 1. The indoor unit fan shall be an assembly with one or two Sirocco fan(s) direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor fan shall consist of three (3) speeds Low, Med and High. D. 1. Filter: Return air shall be filtered by means of an easily removable washable filter. E. Coil: 1. The indoor coil shall be of nonferrous construction with louvered fins on copper tubing. 2. The tubing shall have inner v grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. Both refrigerant lines to the ABUA indoor units shall be insulated. F. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase and 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). G. Controls: 1. This unit shall use controls provided by Fujitsu to perform functions necessary to operate the system. Part 5 – Controls 5.01 Overview A. General: 1. The AIRSTAGE VII Controls shall be capable of supporting remote controllers, system controllers, centralized controllers, an integrated web based interface, graphical user workstation, and system integration to Building Management Systems via BACnet® and LonWorks®. 5.02 Electrical Characteristics A. Wiring: 1. Controller power and communications shall be via a common non-polar communications bus. 2. Control wiring shall be installed in a system daisy chain configuration from indoor unit to indoor unit and to the outdoor unit. 3. Control wiring to remote controllers shall be run from the indoor unit terminal block to the controller associated with that unit. 4. The remaining associated indoor units for a remote controller are to be connected in a daisy chain configuration. 5. Control wiring for System Controllers, Touch Screen Controllers and Centralized Controllers shall be installed in a daisy chain configuration at any point on the Transmission line from the indoor units to the outdoor units. 6. Control wiring the remote controller to the first associated indoor unit then to the remaining associated indoor units in a daisy chain configuration. B. Wiring type: 1. Wiring shall be 22AWG LEVEL 4 (NEMA) non-polar 2core, twisted pair solid core diameter 0.65mm Lon Compatible Cable, as defined by the Design Simulator AutoCAD output. 5.03 AIRSTAGE VII Controls Network 1. The AIRSTAGE VII Controls Network consists of remote controllers, system controllers, centralized controllers, and/or integrated web based interface communicating over a high-speed communication bus. 2. The AIRSTAGE VII Controls Network shall support operation monitoring, scheduling, error email distribution, electricity charge apportionment, online maintenance support, and integration with Building Management Systems (BMS) using either LonWorks® or BACnet® interfaces. 5.04 Remote Controllers A. Wired Remote Controller (UTY-RNKU) 1. The Wired Remote Controller (UTY-RNKU) shall be capable of controlling up to 16 indoor units (defined as 1 group). 2. The Wired Remote Controller shall be approximately 5” x 5” in size and white in color with a light-green LCD display. 3. The Wired Remote Controller shall support a selection from multiple languages (English, Chinese, French, German, Polish, Spanish & Russian) for display information. 4. The Wired supports temperature display selection of Fahrenheit or Celsius. The Wired Remote Controller shall control the following grouped operations: On/Off, Operation Mode (cool, heat, auto, and dry), temperature set point, fan speed setting, and airflow direction setting. 5. The Wired Remote Controller shall support timer settings of on/off/temperature up to 2 times in a day. The Wired Remote Controller shall support an Auto Off timer. 6. The Wired Remote Controller shall be able to limit the set temperature range. 7. The room temperature shall be sensed at either the Wired Remote Controller or the Indoor Unit dependent on the indoor unit. 8. The Wired Remote Controller shall display a four-digit error code in the event of system abnormality/error. 9. The Wired Remote Controller shall only be used in the same group with other Wired Remote Controllers and Simple Wired Remotes, with up to two remote controllers per group. 10. The Wired Remote Controller shall require no addressing. 11. The Wired Remote Controller shall connect using three-wire, stranded, non-polar control wire. B. Simple Wired Remote Controller w/ Operation Mode Button (UTY-RSKU) 1. The Simple Wired Remote Controller (UTY-RSKU) shall be capable of controlling up to 16 indoor units (defined as 1 group). 2. The Simple Wired Remote Controller shall be compact in size, approximately 3” x 5” and have limited user functionality. 3. The Simple Wired supports temperature display selection of Fahrenheit or Celsius. 4. The Simple Wired Remote Controller shall allow the user to change on/off, mode (cool, heat, auto, dry, and fan), temperature setting, and fan speed setting. 5. The Simple Wired Remote Controller shall be able to limit the set temperature range from the Simple Wired Remote Control. 6. The Simple Wired Remote Controller shall display a four-digit error code in the event of system abnormality/error. 7. The Simple Wired Remote Controller shall only be used in same group with WIRED REMOTE CONTROLLER (Wired Remote Controllers), or with other UTY-RSKU (Simple Wired Remote Controllers), with up to two remote controllers per group. 8. The Simple Wired Remote Controller shall require no addressing. 9. The Simple Wired Remote Controller shall connect using three-wire, stranded, non-polar control wire. 10. The UTY-RSKU shall require cross-over wiring for grouping across indoor units. C. Simple Wired Remote Controller w/o Operation Mode Button (UTY-RHKU) 1. The Simple Wired Remote Controller (UTY-RHKU) shall be capable of controlling up to 16 indoor units (defined as 1 group). 2. The Simple Wired Remote Controller shall be compact in size, approximately 3” x 5” and have limited user functionality. 3. The Simple Wired supports temperature display selection of Fahrenheit or Celsius. The Simple Wired Remote Controller shall allow the user to change on/off, temperature setting, and fan speed setting. 4. The Simple Wired Remote Controller shall be able to limit the set temperature range from the Simple Wired Remote Control. 5. The Simple Wired Remote Controller shall display a four-digit error code in the event of system abnormality/error. 6. The Simple Wired Remote Controller shall only be used in same group with WIRED REMOTE CONTROLLER (Wired Remote Controllers), or with other UTY-RHKU (Simple Wired Remote Controllers), with up to two remote controllers per group. 7. The Simple Wired Remote Controller shall require no addressing. 8. The Simple Wired Remote Controller shall connect using three-wire, stranded, non-polar control wire. 9. The UTY-RHKU shall require cross-over wiring for grouping across indoor units. D. Wireless Remote Controller (UTY-LNHU) 1. The Wireless Remote Controller (UTY-LNHU) shall be capable of controlling up to 16 indoor units (defined as 1 group). 2. The Simple Wired Remote Controller shall be compact in size, approximately 3” x 5” and have limited user functionality. 3. The Wireless Remote Controller supports temperature display selection of Fahrenheit or Celsius. The Simple Wired Remote Controller shall allow the user to change on/off, temperature setting, and fan speed setting. 4. The Wireless Remote Controller shall display a four-digit error code in the event of system abnormality/error. 5. The Wireless Remote Controller shall only be used in same group with Wired Remote Controllers or Simple Wired Remote Controllers, with up to two remote controllers per group. 6. The Wireless Remote Controller shall require no addressing. 5.05 Centralized Controllers A. Touch Panel Controller (UTY-DTGY) 1. The Touch Panel Controller shall be capable of controlling a maximum of 400 indoor units across multiple AIRSTAGE VII outdoor units (Max 100). 2. The Touch Panel Centralized Controller shall be approximately 9-1/2”x10”. 3. The Touch Panel Controller shall support operation superseding that of the remote controllers, system configuration, daily/weekly scheduling, monitoring of operation status, and malfunction monitoring. 4. The Touch Panel Controller shall have five basic operation controls which can be applied to an individual indoor unit, a group of indoor units (up to 400 indoor units), or all indoor units (collective batch operation). 5. This basic control set of operation controls for the Touch Panel Controller shall include on/off, operation mode selection (cool, heat, auto, dry, and fan), temperature setting, fan speed setting, and airflow direction setting. 6. Since the Touch Panel Controller provides centralized control it shall be able to enable or disable operation of local remote controllers. 7. The Touch PanelController shall allow the user to define daily, weekly and annual schedules with operations consisting of ON/OFF, mode selection, temperature setting, vane direction, fan speed, and permit/prohibit of remote controllers. 8. All Touch Panel Controllers shall be equipped with USB port to support data import and export. 9. The Touch Panel Controller shall be capable of performing initial settings via the 7 1/2” high-resolution, backlit and color touch panel on the controller or imported in CSV format via the USB connection. B. Central Remote Controller (UTY-DCGY) 1. The Central Remote Controller shall be capable of controlling a maximum of 400 indoor units across multiple AIRSTAGE VII outdoor units (Max 100). 2. The Central Remote Controller shall support operation superseding that of the remote controllers, system configuration, daily/weekly scheduling, monitoring of operation status, and malfunction monitoring. 3. The Central Remote Controller shall have five basic operation controls which can be applied to an individual indoor unit, a group of indoor units (up to 100 indoor units), or all indoor units (collective batch operation). 4. This basic control set of operation controls for the Central Remote Controller shall include on/off, operation mode selection (cool, heat, auto, dry, and fan), temperature setting, fan speed setting, and airflow direction setting. 5. Since the Central Remote Controller provides centralized control it shall be able to enable or disable operation of local remote controllers. 6. The Central Remote Controller has external input / output contacts. 7. Available in 7 different languages: English, Chinese, French, German, Spanish, Russian, and Polish. C. System Controller (UTY-APGX) 1. The Graphical User Workstation Software (SYSTEM CONTROLLER) shall require a field supplied PC. 2. The System Controller is advanced monitoring and control for Fujitsu Airstage VII VRF systems. 3. A maximum of 4 network systems comprised of 1,600 indoor units and up to 400 outdoor units can be controlled. 4. The various functions of the System Controller are central remote control, electricity charge calculation, schedule management, and energy saving function. 5. The System Controller provides a graphical view of site, building and floor layout just as they are located in the actual sites. Unit status can be monitored at a glance. 6. Control can also be performed from various views as individual unit or as a whole site, building or a whole floor. 7. User defined groups are neatly arranged so as to be easy to find, monitor and operate. 8. Tenant electricity use billing is apportioned according to the accumulated operation time and indoor unit operating conditions. 9. This systems allows accounting for special rates (e.g., for night or weekend use). Calculations can be printed as final bills. 10. Annual schedules can be set for each remote controller group / user defined group. 11. Start / stop, operation mode, remote controller prohibition, and temperature settings can be recorded up to 143 times per day at 10 minute intervals for up to 101 configurations for each remote controller group. 12. The system allows programming of special settings for holidays for a complete year. 13. Error notification is available through popup messages, audible sounds and email when error occurs. Errors for the past 1 year are logged and can be reviewed later. 14. System Controller also displays the history of operation status and errors. 15. Optional Energy Manager Software provides energy saving operation considering comfort by economy setting, temperature set point limitation, etc. 16. System controller may be used on site or remotely over various networks for remote central control. System controller requires server and client programs working together. Server program runs in the background and communicate with VRF System. Client program provides user interface and communication with the server. Server and client program may run in a single PC or in different PCs separated by network. Both server and client programs run when using System Controller on site. System Controller can be managed remotely over the internet using client program. Server programs run in VRF sites, and client programs run in remote sites with users. 5.06 Web Monitoring Tool (UTY-AMGX) 1. The Web Monitoring Tool is a Service & Maintenance tool for Fujitsu VRF products. 2. This tool is used for checking the refrigerant cycle and operation status of VRF systems. 3. The Web monitoring tool can be used at the location where the VRF system is installed or remotely via the web. 4. The Web Monitoring Tool can be used to carry out the commissioning of the VRF system. 5. The Web Monitoring Tool can immediately send information on VRF system failures locally or by E-mail. 6. Troubleshooting can be performed by monitoring each unit remotely. 7. Monitoring site computer is not required to install special software, requires only Internet Explorer. 8. Operation status can be checked and analyzed at the monitoring site. 9. Operation status and various sensor information can be monitored and checked real time in the form of a list, refrigerant circuit diagram, and graphically as well. Data can be remotely downloaded, and this data can be displayed in off-line mode of the service tool. 10. Error notification can be automatically transmitted to several locations using the internet. 11. A USB adaptor (max. 4 adaptors per PC) can permit control and monitoring of up to 1600 units. Wed Monitoring is suitable for large-scale buildings or hotels. 12. The Web Monitoring Tool Software shall require a field supplied PC. 5.07 Fujitsu Airstage VII LonWorks® Integration The Fujitsu Airstage VII Controls Network shall be capable of supporting integration with Building Management Systems (BMS) via our LonWorks® interface. A. Network Converter for LonWorks® ( UTY-VLGX) 1. The UTY-VLGX permits central monitoring and control of a VRF network system through a LonWorks open network connection. 2. This interface is for small and medium sized BMS and VRF Networks. 3. Up to 128 Indoor units can be connected to one Network Convertor for LonWorks®. 5.08 Fujitsu Airstage VII I BACnet® ntegration The Fujitsu Airstage VII Controls Network shall be capable of supporting integration with Building Management Systems (BMS) via our BACnet® interface. A. BACnet® Gateway (UTY-ABGX) 1. The Fujitsu Airstage VII VRF network system can be incorporated into a Building Management System. 2. The Gateway enables central control of up to 1,600 indoor units through BACnet, a global standard for open networks. 3. The unit conforms to ANSI / ASHRAE Standards 135-2004 for Application Specific Controller (B-ASC) BACnet / IP over Ethernet. 4. The BACnet Gateway connects up to 4 VRF network systems (1,600 indoor units / 400 outdoor units) per gateway. 5. The BACnet® Gateway is Certified by BTL. 6. The BACnet® Gateway Software shall require a field supplied PC. 7. VRF network system can be connected to BACnet Gateway PC via U10 USB interface adaptor, which is field supplied. 5.09 Network Converter for HFI and Halcyon Integration (UTY-VGGXZ1) 1. The Fujitsu Airstage Controls Network shall have the capability of controlling and monitoring the HFI and Halcyon units through the use of a Network Converter. 2. The Netwirk Converter shall have the capability of controlling and monitoring HFI and Halcyon units through the Centralized Controller, Touch Screen Controller, System Controller, LonWorks Network Converter and BacNET Interface.