SECTION 15676 AIR COOLED CHILLER PART 1 - GENERAL 1.01 GENERAL A. 1.02 SCOPE A. 1.03 1.04 The Bidding and Contract requirements, Division 1 - General Requirements, section 15010 - General Provisions, and Section 15050 - Basic Materials and Methods, shall apply to this section. A complete factory assembled package air-cooled water chiller shall be installed. QUALITY ASSURANCE A. Unit shall be run tested at the factory and start-up and check out shall be done by a factory certified technician. Pressurized components shall comply with the ASME code for unfired pressure vessels. Rating and construction shall be in accordance with ARI Standard 59086, ANSI B9.1 safety code and the National Electrical Code. B. Manufacturer shall provide a certification that the equipment has been performance tested at the factory. Certification shall record the unit capacity in BTU/hour and kilowatts. C. Factory start-up- The manufacturer shall supply complete factory start-up by a factory approved start-up agent. D. Equipment installer shall attend a controls coordination meeting with the section15900 contractor as described in 15900, 1.03. SUBMITTALS A. Provide shop drawings on this equipment as described in section 15010, 1.04. The controls coordination meeting described in 15900, 1.03 shall be held before the shop drawings are submitted. PART 2 - PRODUCTS 2.01 AIR COOLED CHILLER The air-cooled chiller shall be of the type and capacity shown in the equipment schedule on the drawings. The unit shall be manufactured by TRANE. A unit fully equal to that specified and manufactured by CARRIER or McQUAY is acceptable. 15676-1 11/13 AIR COOLED CHILLER SECTION 15676 A. Unit Description - The Air Cooled chiller shall be a factory assembled, piped, wired and tested unit consisting of a corrosion protected steel casing, an evaporator, condensers, multiple scroll or screw compressors, control panel, refrigerant piping and dual refrigeration system all assembled on one base with accessories as required in this specification or as shown on the drawings. Motor starters shall be unit mounted. The refrigerant used shall have an ozone depletion potential of less than .05 and a global warming potential of less than 0.37, (R-134A, R-410A). B. Unit Casing - Unit shall be enclosed in a galvanized steel casing, zinc phosphatized, with an electrostatically applied baked enamel finish, capable of withstanding Federal Test Method Standard No. 141, Method 6061, 500 hour salt spray test. C. Evaporator/Cooler - Shall be shell and tube type with removable heads and shall have two independent direct-expansion refrigerant circuits. Cooler shall be tested and stamped in accordance with ASME code for refrigerant side working pressure of 235 psig and a minimum waterside working pressure of 150 psig. Copper tubes shall be rolled into the tube sheets. Shell shall be covered with 3/4" layer of closedcell foam plastic, vapor insulated. D. Condenser 1. Air cooled condenser coils shall have aluminum fins mechanically bonded to seamless copper tubes, cleaned, dehydrated, sealed, leak tested at 150 psig and pressure tested at 450 psig. 2. Condenser fans shall be propeller type with PVC coated steel wire safety guards, balanced statically and dynamically, and shall discharge vertically. 3. Condenser fan motors shall have inherent overcurrent protection. 4. Provide metal hail guards to protect the condenser coil from damage. E. Compressors - Shall be scroll hermetic type with a maximum speed of 3500 rpm, or rotary screw, serviceable and shall have an automatically reversible oil pump and operating oil charge. Compressors shall be equipped with suction and discharge shutoff valves and shall be mounted on individual spring vibration isolators. Each compressor motor shall be cooled by suction gas passing around the motor windings and shall be thermally protected with manual restart after thermal or pressure overload stoppage. Each compressor shall be equipped with an insert type crankcase heater to control oil dilution during shutdown. Cycles per hour per compressor shall not exceed six. F. Refrigeration Circuit - Each refrigeration circuit shall include: hot gas muffler, combination moisture indicator and sight glass, replaceable core refrigerant filter drier, liquid line solenoid valve, expansion valve, suction and discharge pressure gauges with manual shutoff valves, high side pressure relief device, and charging valve. 15676-2 11/13 AIR COOLED CHILLER G. SECTION 15676 Controls 1. Unit controls, including microprocessor, shall be factory mounted and wired in a weatherproof enclosure with hinged access doors for easy access. The controls shall include automatic lead-lag except where noted, pumpdown at beginning and end of every circuit cycle, loss-of-charge protection, inherent low water flow protection, low chilled water temperature safety, low- and high-suction superheat protection, low oil pressure protection for each circuit, ground current protection for each compressor, low control voltage to unit, current limit, field power and control circuit terminal blocks, compressor and fan motor circuit breakers, ON/OFF switch, replaceable relay board, individual solid-state compressor protection board, leaving chilled water set point board, diagnostic digital display module, a microprocessor board and a temperature reset board. The chiller shall be capable of sending a chill water pump run request to the building automation system. 2. Unit control capacity is based upon leaving water temperature and will be compensated by return water temperature. 3. Minimum number of capacity control steps shall be as shown in the equipment schedule. 4. Provide a definite purpose magnetic contactor for each compressor. 5. Calibrated circuit breakers shall be factory installed for each compressor, shall be manual reset and ambient insensitive, and shall open all three phases should an overload occur on any phase. 6. Unit primary electrical power supply shall be connected to a single point with lugs sized for specified conductors. 7. Control voltage shall be provided by a factory installed integral control transformer. 8. Heat tracing for exterior piping shall be provided by a separate 120 volt, single phase power supply. 9. Provide a barrel freeze alarm output for connection to the BAS. H. Chiller shall be capable of operating at ambient air temperatures down to 0 deg F without the use of glycol or any other type of antifreeze. Chillers that do not meet this requirement are not acceptable. I. Flow switches- switches for flow conformation shall be provided. Switches shall be paddle type with stainless steel bellows and paddle. Switches shall be suitable for outdoor installation. 15676-3 11/13 AIR COOLED CHILLER SECTION 15676 PART 3 - EXECUTION 3.01 INSTALLATION A. Factory Start-up- The manufacturer shall supply complete factory start-up by a factory approved start-up agent. B. Installation - The chiller shall be installed in accordance with the manufacturer's recommendations. C. Install isolation valves on evaporator water inlet and outlet at chiller. D. Install thermometers on evaporator water inlet and outlet at chiller. E. Isolation - Provide spring isolators as recommended by chiller manufacturer. F. Pipe Connections - The machine shall have water boxes or the contractor shall provide flanged pipe connections in the piping adjacent to the machine to allow removal of headers for inspection, cleaning or removal of tubes. G. Provide an engraved nameplate permanently affixed to the front of the control cabinet (inside of cabinet for outdoor locations) with the following information. INSTALLING CONTRACTOR: _______________________________ CONTRACTOR PHONE # : _______________________________ WARRANTY DATE FROM: __________ TO: ___________________ END OF SECTION 15676-4 11/13