TD503075EN-Linear Dimming Control Module Spec Sheet

Technical Data
INS #
Linear Dimming Control Module
Catalog#
Prepared by
Project
Date
Comments
Type
Overview
Linear Dimming Control Module Plenum Rated (LDCM-PL) takes a
0-10V dimming dignal and a fixed line voltage input and converts it to
an ELV dimmed output for up to 1000W with a 277V load and 450W
on a 120V load. One LDCM can be used per run up to the maximum
wattage. The LDCM-PL is rated to directly mount to a junction box
in a plenum space for easier installations and to meet building
requirements.
Features
Dims ELV only fixtures with 0-10V
Simple Installation
Direct J-Box Mount
120V and 277V compatible
Auto-Sensing Voltage Switch
450W @120V, 1000W @277V
Plenum Rated
One LDCM per fixture run
Technical Data


July 2016

Specifications
ELECTRICAL
Power Rating
Max Fixture Run Length
Operating Voltage
Operating Hertz
Startup Temperature
Operating Temperature
Storage Temperature
Dimming
CONTROL
Requirements
PHYSICAL
RATING &
CERTIFICATIONS
Dimensions
Housing / Lens
Connectors
Weight
Environment
Mounting Options
ETL / cETL Damp
Locations
450W Max @ 110-120V
1000W Max @ 277V
Calculate Maximum Run per LDCM unit based on the Power Consumption of the fixture used.
110VAC-120VAC, 277VAC - Auto-Sensing Voltage Switch
60 Hz
-4°F to 104°F (-20°C to 40°C)
-4°F to 104°F (-20°C to 40°C)
-40°F to 176°F (-40°C to 80°C)
110-120VAC; ELV (forward/reverse) - RP; converted from 0-10V Controller
277VAC; ELV (forward/reverse) - RP; converted from 0-10V Controller
W 3.4” x H 2”” x L 7”; (87mm x 50mm x 178mm)
Injection Molded Polycarbonate
Lead Wire 6” From Conduit
0.99 lbs (0.45 kg)
ETL Damp Location
Conduit Mounting For Both Sides
RoHS
COMPLIANT
This product is provided by Eaton Lighting Solutions in cooperation
with EcoSense Lighting Inc.
Ordering
Choose the option that best suits your needs and write
its corresponding code on the appropriate line to form the
product code.
LDCM-PL
MODEL
120-277
VOLTAGE
010V
CONTROL
LDCM-PL
120-277
010V-0-10V
110VAC-120VAC,277V
Auto-Sensing Voltage Switch
GR
COLOR
GR - Grey
EXAMPLE: LDCM-PL - 120-277 - 010V -GR
Dimensions
7.0in 178mm
5.4in 138mm
0-10V DATA IN
3.4in 87mm
110VAC-120VAC,
277VAC POWER IN
110VAC-120VAC, 277VAC
+ ELV DATA TO FIXTURE RUN
152mm
WIRE
6in
152mm
WIRE
2.0in 50mm
6in
1/2-14 NPS Thread
2
www.eaton.com/lightingsystems
Technical Data


July 2016

Connections
LDCM NOTE:
The EcoSense LDCM module
takes a 0-10V dimming signal and
fixed line voltage input and converts
it to a ELV dimmed output for up to
1000W @ 277V or 450W @120V.
The LDCM is rated to mount
directly to a junction box in the
plenum space for easy installation.
RED
GREY
HOT
NEUTRAL
LDCM
BLACK
YELLOW
120V receptacle
circuit
WHITE
Sensors
Sensors
Slider
Station
Wallstations
+
+
A/V
Mode
+
Demand
Response
+
Alert
Mode
Time
Clock
Adjustable Skylights
6
5
Blue
Red
4
Integration Controls
QuickConnect Cables
Adjustable Skylights
Switchpack
Receptacle
BMS/Out
Black
Brown
Dual Technology
Wall Corner
Occupancy/Vacancy Sensor
(OAWC-DT-120W)
OCC-RJ45
(Occupancy Coupler)
3
2
1
3
4
Reset
Not Used
Occupancy
Occ
Vac (default)
Energy
Options
2
Status
Low End
1
High End
Energy Options DIP Switch
Demand Response
Default 10%
20%
30%
40%
0-10V Gain
Adjustment
BLUE - Emergency Power In
(120/277VAC)
Green
Integration Controls
Red - Load 2 Out
Purple - Load 3 Out
Blue - Load In
Yellow - Load 1 Out
Black - Line In
White/Black - 120V N
White/Orange - 277V N
YELLOW
Emergency Power OUT
Black
Daylight sensor
(DSRC-FMOIR)
Model: OCC-RJ45
Occupancy Sensor Coupler
BLUE - Relay In
(120/277VAC)
White
Red
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
WHT/ORG or WHT/BLK
Neutral
BLACK - Hot
(120/277VAC)
SPRC-R-20-120
20A Receptacle
Control
Blue - EM Line In
Blue - EM Loads Out
ELV
LIGHTING LOAD (1)
0-10V Dimming Outputs
+ + + Dimmer 3
Dimmer 2
Dimmer 1
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
+
-
0-10V Dimming
Button 1: Load (1),(2),(3) ON, Dimmer 1: 100%,
Dimmer 2: 80%, Dimmer 3: 100%
Button 2: Load (1),(2),(3) ON, Dimmer 1: 80%,
Dimmer 2: 20%, Dimmer 3: 100%
Button 3: Load (1),(2),(3) ON, Dimmer 1: 50%,
Dimmer 2: 100%, Dimmer 3: 25%
Button 4: Press and Hold Raises all dimmers
Button 5: Press and Hold Lowers all dimmers
Button 6: All Loads OFF
Violet - Dimmer 1
Gray - Dimmer 1
Scene 1
Zone 1 UP
Scene 2
Zone 1 DN
Scene 3
Zone 2 UP
Raise
Zone 2 DN
Lower
Zone 3 UP
All Off
Zone 3 DN
Button 1: Press and hold increase Zone 1 lighting 5%
Button 2: Press and hold decrease Zone 1 lighting 5%
Button 3: Press and hold increase Zone 2 lighting 5%
Button 4: Press and hold decrease Zone 2 lighting 5%
Button 5: Press and hold increase Zone 3 lighting 5%
Button 6: Press and hold decrease Zone 3 lighting 5%
RC-6TSB-P4-* RC-6TSB-ZAD-*
Scene Station
Office Station
Scenes are programmable within the
Room Controller using the Personal
Remote (HHPR-RC) and new
programming is accessed through
the Scene Wallstations.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton
Lighting Systems – Controls Products
1121 Highway 74 South
Peachtree City, GA 30269
eaton.com/lightingsystems
© 2016 Eaton
All Rights Reserved
Printed in USA
Publication No. TD503075EN
July 19, 2016
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.