02/20/2015 Advanced Topics in Stray Voltage ‐ Why is that voltage there? Paul Ortmann, P.E. Senior Electrical Engineer Idaho Power Company portmann@idahopower.com Imagine… You are “the stray voltage person” at work. Your phone rings … 1 02/20/2015 Five phone calls… 1. Blown transformer fuse, voltage normal. 2. Customer shocked from aluminum siding, where is the fault? 3. Worker shocked on grounded pivot sprinkler. 4. Gas company tech finds about 60V AC between gas pipeline and earth. 5. High frequency NEV and contact voltage. Phone call 1: Blown transformer fuse Routine neutral-to-earth voltage check: neutralto-earth voltage “seems a little high” Three-phase transformer bank has one fuse blown. 120/240V three-phase service has normal voltage; dairy is running. 2 02/20/2015 We find this: Are these really any different? A B C N Open Fuse a b n c Grounded-Wye Delta (with blown fuse on one power transformer) Open-Wye – Open-Delta 3 02/20/2015 Grounded‐Wye – Delta • Contributes to primary system ground fau s – hence blown fuse. • Used temporarily on ungrounded wye-delta banks. • Sometimes installed accidentally. • Contributes primary neutral current. lt Ungrounded‐Wye ‐ Delta • Primary neutral point is deliberately floated. • No primary neutral current due to transformer. 4 02/20/2015 Open‐Wye – Open‐Delta • Three-phase service from two p mary phases • Less prone to ferroresonance than some other connections • Significant primary neutral current contribution ri Primary Neutral Current Comparison Open W ye Open Delta Grounded W ye-Delta Ungrounded Wye-Delta 0 2 4 6 8 10 12 Load: 60kVA 3-phase (balanced) 5 02/20/2015 Primary Neutral Current Comparison Open W ye Open Delta Grounded W ye-Delta Ungrounded Wye-Delta 0 2 4 6 8 10 12 Load: 60kVA 3-phase 25kVA 240V single-phase Ungrounding a grounded‐wye‐delta transformer 72-hour NEV at Transformer Pole 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 0 Grounded W ye-Delta Ungrounded Wye-Delta 6 02/20/2015 Closing an Open‐Delta transformer Primary Profile NEV 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 1 2 3 4 5 6 Open Delta NEV 7 8 9 10 11 12 13 Closed Delta NEV An NEV model Two important laws: Kirchhoff’s Current Law: Current In = Current Out Ohm’s Law: Voltage = Current x Impedance 7 02/20/2015 Open, Grounded, and Ungrounded‐Wye‐Delta Primary System NEV 9 8 7 6 5 4 3 2 1 0 1 11 21 31 41 Ungrounded W ye-Delta Grounded W ye-Delta 51 61 71 81 91 Open W ye-Delta Lessons Learned Check Delta transformer connections carefully. Close open wye-open delta banks if possible. Adding balanced 3-phase load to an ungrounded wye-delta transformer bank should not change NEV. If it does, investigate further. 8 02/20/2015 Intelligent troubleshooting: Compare conditions to expectations: Example expectations: “If this transformer is connected properly and we add load, NEV should…” “If there is a good neutral-to-ground bond, then voltage between these two points should be…” “If the neutral connections between these two panels are in good condition then I should measure…” In short, if you don’t know what “normal” is, you won’t recognize “abnormal”. Phone call 2: Shock from aluminum siding • Customer touched aluminum siding on garage and got shocked • No breakers have tripped • Customer’s equipment appears to operate normally 9 02/20/2015 Ground faults and effective current paths: From the 2014 NEC: (paraphrased) • Ground Fault. An unintentional connection between an ungrounded conductor and the normally non–current-carrying conductors, metallic enclosures, metallic raceways, metallic equipment, or earth. • Effective Ground-Fault Current Path. An intentional, low-impedance path to carry current under ground-fault conditions and facilitates the operation of the overcurrent protective device or ground-fault detectors. Earth faults: The earth shall not be considered an effective ground-fault current path. (2014 NEC-250.4) But what if the earth is the only path for ground‐ fault current? We’ll call this an “Earth fault" 10 02/20/2015 Observations: • Separate garage has a short 3-wire 120/240V overhead service from a breaker in the house panel. • Garage has a subpanel with a main breaker and several branch circuit breakers. • No GFCI circuit breakers or receptacles are installed in garage. Faults – What is supposed to happen? Low-impedance fault current path ensures that plenty of current flows to quickly trip the circuit breaker 11 02/20/2015 A few cycles after the fault starts… Circuit breaker quickly trips. But the breaker did not trip… Earth faults rarely produce enough current to trip a non‐GFCI circuit breaker or blow a fuse. If someone reports being shocked when they touch something grounded, you may have an earth fault to find. 12 02/20/2015 M easurements: •Voltage measured between a screwdriver in the earth and the garage s aluminum siding is approximately 110-volts, even ’ with meter on “Lo-Z” setting. •Net current on overhead service to garage is about 3-Amps. •Neutral current on overhead service to garage is negligible. Tests: •Open main breaker in garage • Contact voltage disappeared • Fault current is going through main breaker •Close main breaker and open individual breakers one at a time • Opening one branch circuit breaker eliminates the contact voltage • Fault is on that circuit 13 02/20/2015 Investigate: • Open electrical boxes on that circuit • Found line-to-ground fault in metal receptacle box • Why didn t the breaker trip?! ’ One missing screw… No bond Earth fault current is too low; breaker won’t trip. Earth is only fault current path 14 02/20/2015 Lessons Learned: If a “ground fault” doesn’t cause a circuit breaker to trip or a fuse to blow, it may actually be an “Earth fault.” Earth faults are a combination of two problems: Problem 1: The ground fault Problem 2: A poor fault current path Both problems must be found! Normal neutral and ground current 15 02/20/2015 Primary NEV with an earth fault at a service Primary System NEV 6 5 4 3 2 1 0 1 11 21 31 41 Normal 51 61 71 81 91 Earth Fault Primary and service current with an earth fault 16 02/20/2015 Voltage gradients – where current enters or leaves the earth Altitude gradient Voltage gradient Touch and step voltages during an earth fault • Touch and step voltage downstream of the break in the grounding path can be very high – even lethal. For a single isolated vertical ground rod: ~88% of the voltage drop to remote earth is within one rod-length For a 10’ rod, the voltage from 1’ to 3.5’ away will be about 20% of the faulted line voltage 17 02/20/2015 Finding both parts of the earth fault •The ground fault: 1 . M onitor the fault safely while opening circuit breakers, fuses, or disconnects. • M ultimeter or voltage detector can be used. • Can measure contact voltage, gradient, or NEV. 2. Do not assume that first upstream device will interrupt fault current. 3 . W hen opening a disconnect de-energizes the fault, the ground fault is downstream of that disconnect and upstream of other disconnects further downstream. Finding the break in the fault current path 1 . M easure voltage across connections; should be nearly zero 2. For underground or overhead, measure NEV; Downstream of break, NEV will be high, and may approach normal line-toground voltage 3. Upstream of break, NEV will be elevated but not normally to more than 10-20V. 18 02/20/2015 An Example: NEV at panels 2 and 3 is close to line voltage NEV at panel 1 is 14 Volts Opening disconnect 1 or 2 eliminates high NEV readings Opening disconnect 3 does not eliminate high NEV readings W here is the ground fault? W here is the break in the effective ground fault current path? Phone call 3: The shocking pivot 19 02/20/2015 Report and Observations: • Worker receives painful shocks when working from a ladder on the pivot to replace sprinklers • Pivot is parked parallel and next to a 345kV transmission line for service M easurements: • Voltage from earth to pivot is 2V or less along the pivot’s entire length • Not a pivot grounding problem • Voltage between a person standing on the ground in dry shoes and the wheeled pivot towers is also less than 2V. • Person-to-pivot voltage increases to over 600V across a 10MΩ digital voltmeter as the person climbs an insulated ladder in the middle of a pivot span. • A person-grounding problem! 20 02/20/2015 Electric Field Calculations: • Open-circuit person-to-pivot AC voltage with person on insulated ladder: Over 10kV! • No wonder it hurts… • The pivot is not shocking the worker. The worker is shocking the pivot! The effect is very similar to a fencer pulse. • Steady-state short circuit current for person at working height is less than 0.1mA • Not a steady-state problem if person can be kept grounded. The situation: Person touching pivot is shorting the capacitance between them and the earth/pivot. That capacitance is small, but may be charged to over 10kV at the time of contact. 21 02/20/2015 Typical electric field shape (horizontal conductors) V/m 0 - 100 - 50 0 50 100 You can use a voltage detector to find the peak of the field near a transmission line The issue: Series capacitance •Electric field redistributes charge •Large voltage can appear across capacitances •Shorting the capacitance results in a capacitive discharge – like a fencer pulse 22 02/20/2015 Solution: • Anti-Static wrist strap with large alligator clip. • Clipped to pivot while worker is on the ground. • 1MΩ wrist strap prevents voltage from building up in capacitance between worker and pivot/earth. • keeps discharge currents low while allowing capacitance between person and pivot to discharge. Phone call 4: Pipeline voltage • Pipeline technician measured ~ 60V AC between earth and piping at cathodic protection test point. These are all Inductors 23 02/20/2015 A pipeline parallel to transmission or distribution conductors Current Earth Pipe Voltage profile But is it induction? • Induced voltage will be highest at the ends of insulated, parallel sections and lowest in the middle of a section. • Resistively coupled voltage, will be relatively uniform along the entire pipeline section. • Software can help you predict voltages 24 02/20/2015 Software simulation: Low-FI (Low Frequency Induction) software from: Sigmapower.com.au M itigating induced voltages: AC, but not DC grounding Before (55.0V M ax) After (8.4V M ax) AC grounding near the ends of sections or where the model predicts excessive voltage Decouplers usually required 25 02/20/2015 Phone call 5: High frequency issues • Call starts as a “routine” stray voltage call • Spot-measured NEV at service is surprisingly high (>5V). • SVM-10 stray voltage recorder doesn’t record NEV that high. When instruments don’t agree: • Check the frequency – push the “Hz” button • Is a high (>1kHz) frequency displayed? • Different bandwidths may explain different readings Homework: The Fluke 87V and some other DMMs have a built‐ in low pass filter. Find out how to use it and try it out! 26 02/20/2015 The SVM ‐10’s frequency response measurements Freq. 60.4Hz 601Hz 1.995kHz 3.019 kHz 6kHz 10.01kHz SVM-10 Ch1 V 1.010 1.003 1.000 1.000 1.005 1.009 1.006 0.994 0.897 0.715 0.120 0.013 Ch2 Ch3 Ch4 1.008 0.996 0.911 0.728 0.117 0.013 1.010 0.997 0.917 0.734 0.120 0.012 1.009 0.996 0.916 0.740 0.140 0.022 The Fluke 87V low-pass filter cuts off at 1kHz. If the measured frequency was several kHz, then using the low-pass setting should get the D M M and the SVM-10 recorder to agree reasonably well. Voltage (Zero to Peak) 500 Ohm Cow Contact Cow frequency response Behavioral response for 5% most sensitive cows, sine waves muzzle to hooves exposure 10000 1 cycle Biphasic 1 cycle Monophasic 1000 Multi Cycle 100 10 1 0.1 1 10 100 1000 10000 Phase Duration (microseconds) = time between zero crossings 27 02/20/2015 Using this information in an investigation Behavioral response for 5% most sensitive cows, sine waves muzzle to hooves exposure 10000 1 cycle Biphasic 1 cycle Monophasic Multi Cycle Recorded transient Voltage (Zero to Peak) 500 Ohm Cow Contact 1000 100 10 1 0.1 Transient plotted on sensitivity graph 0.01 1 10 100 1000 10000 Phase Duration (microseconds) = time between zero crossings Where is the high frequency coming from? High frequency “noise” on the grounding system is nearly always associated with nearby variable frequency drives. Voltage pulses from the VFD cause “ringing” current which travels across the internal stray capacitance of the motor to the case and into the grounding system. M otor grounding current with a VFD Plot from: “Modeling of M otor Bearing Currents in P WM Inverter Drives”, S. Chen, T. Lipo, and D. Fitzgerald; IEEE Transactions on Industry Applications Vol. 32, No. 6 Nov/Dec 1996. 28 02/20/2015 Specialized cabling for VFDs is designed to minimize noise coupling to other conductors VFD-to-motor cable: • Symmetrical grounds • Overall shield • Shield bonded to enclosures at both ends Finding signal sources: Timing For transients, use oscilloscope or recorder to measure time between transients, from seconds to minutes Find devices that operate at the same interval Useful for fencers, refrigerators, float switches, etc. 58 29 02/20/2015 Finding signal sources The time‐of‐arrival method Capture the signals at two A separate locations on the same neutral-grounding system simultaneously Travel direction can be determined from “time of arrival” B A B Oscilloscope In this case, the transient originated closer to location A than to location B. 59 In conclusion: People are often surprised by “normal” voltage measurements. The more you learn about how electrical systems behave, the better you will be at recognizing and resolving truly abnormal conditions. Paul Ortmann, P.E. Senior Electrical Engineer Idaho Power Company portmann@idahopower.com 30