E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) EXTERNAL THERMAL INSULATION COMPOSITE SYSTEMS (ETICS) 180 www.atlas.com.pl E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) ATLAS SYSTEM (ETA)..............................182 - 183 with standard and elasticized polystyrene boards (EPS) ATLAS XPS SYSTEM (ETA) ...............184 - 185 with extruded polystyrene boards (XPS) ATLAS ROKER SYSTEM (ETA) .....186 - 187 with mineral wool panels ATLAS ROKER G SYSTEM .................188 - 191 with mineral wool panels – for ceilings ATLAS RENOTER SYSTEM ...............192 - 193 extra insulation system for walls with existing thermal insulation ATLAS CERAMIK SYSTEM ...............194 - 195 external wall insulation with ceramic cladding MECHANICAL FIXINGS .................................... 196 REINFORCING FIBERGLASS MESHES............ .................................................................................................................. 197 FAÇADE FINISHING PROFILES .......................... ............................................................................................... 198 - 199 Product Data Sheets Catalogue 181 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) EXTERNAL THERMAL INSULATION COMPOSITE Proper thermal insulation of a building is one of the most important issues to be considered before the facade installation. Thermal modernization of a building allows to save over 30% of heating energy costs. It improves the aesthetic appearance of the building and positively influences the environment, as it reduces the CO2 emission and and energy use. The main tasks of the external thermal insulation are: − achieving the required thermal insulation for all construction partitions - in accordance to local requirements − reduction of building operation costs – reduction of costs of heating, which positively influences the environment (reduction of harmful compounds emission) − increasing the durability of the external walls - thanks to the protection against negative weather conditions influence − giving aesthetic appearance of the facade - through the use of various renders, cladding and paints The long - time experience in external thermal insulation systems manufacturing allows ATLAS to provide the Customers with products of the highest quality. They allow to finish the facade in many ways meeting different expectations of the homeowners. The proper choice of the thermal insulation system may depend on: - substrate type (material, a building is made of ) - building age (old, newly constructed) - location and intended use - surface area and height - finishing type as designed ATLAS offers systems based on the polystyrene and mineral wool thermal insulation. They allow to finish the facade with one of a few render types or ceramic tiles. ATLAS holds as well in its offer jointless external wall insulation systems and garage systems. Thanks to proper choice of thermal insulation, not only the thermo - insulation parameters of the wall are improved, but also acoustic insulation, fire resistance and mechanical resistance. The multiplicity of technical solutions, used in ATLAS adhesives and renders, allows the investor to choose almost any thermal insulation material available: − traditional expanded polystyrene − elasticized expanded polystyrene − extruded polystyrene − mineral wool •Thickness of thermal insulation The effectiveness of thermal insulation depends first of all on the thickness of the thermo-insulating material. As a free-of-charge service for investors, ATLAS experts make calculations of the U value, i.e. thermal resistance of the walls and the so-called diffusion resistance of walls, i.e. water vapor permeability. The current requirements for the thermal insulation capacity of walls, published in the “Regulation on technological conditions to be met by buildings and their situation”, state that the maximum value for thermal conductivity coefficient for external walls Uk(max) must not exceed 0.3 W/m2K (for double layer walls). Our systems hold Domestic (AT) and European Technical Approvals describing unambiguously the system composition and its parameters. ATLAS is as well one of few thermal insulation system manufacturers holding the local technical approvals for: Germany (Allgemeine Bauaufsichtliche Zulassung Z-33.84-963 and Z-33.83-964), Ireland (Irish Agrement Board Certificate 10/0347) and the United Kingdom (British Board of Agrement Certificate 13/5018). 182 www.atlas.com.pl E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) SYSTEMS (ETICS) Comparison of the insulation systems Name ATLAS Distinction ATLAS external wall insulation systems ATLAS XPS ATLAS ROKER ATLAS RENOTER ATLAS CERAMIK ATLAS ROKER G External wall insulation systems with thin-coat renders with ceramic cladding traditional Thermo-insulaEPS polystyrene tion material Use Properties renovation XPS - extruded polystyrene --thermal insulation of all types of buildings - recommended in the ground -- EWI system used for differzone of building (plinths ent types of buildings basements, foundations), -- basic, most frequently used the gable walls, attics, EWI system along the corners, at the entrances to the enclosures -- improving the thermal insulation -- simultaneous improvement of both thermal insulation and acoustic insulation of external walls - in case of the use of elasticized polystyrene Ceiling thermal insulation system --improving the thermal insulation --very high resistance to mechanical damages and impact compared to systems with EPS polystyrene --significant resistance to corrosion action of microorganisms, moisture, groundwater and rainwater (in insulation layer) - the ability to use next to each other (at the same elevation) of XPS and EPS polystyrene boards mineral wool - MW --thermal insulation of all types of buildings --required in high buildings, above 25 m --recommended for walls of utility buildings , for which acoustic and fire protection requirements are increased, e.g. hospitals --improving the thermal insulation --strengthens the fire protection of building construction components -- the system is classified as incombustible --high vapour permeability --increased acoustic insulation --ease insulation of convex surfaces EPS polystyrene or XPS extruded polystyrene EPS polystyrene --repair of the existing insulation of all types of buildings when it is: --in poor condition --does not meet current insulation requirements and it is necessary to increase the insulation thickness --additional improvement of thermal insulation --no need to remove old render --improving the aesthetics of the facade mineral wool - MW --insulation of all types of buildings --recommended for facade --susceptible to increased loads --insulation of all types of buildings --recommended for ceiling insulation above the garages, basements, crossing, underground crossing, in parking spaces in the commercial-entertaining centers, shopping malls, office buildings, etc. --improving the thermal insulation --full compatibility of all components elements --reduce of heat loss and costs of heating --increasing the durability of the external walls --protection against direct weathering --increased resistance to biocorrosion --ability to use on one facade both EPS boards and XPS ones --improvement of thermal insulation --strengthens the building fire protection --improving the acoustic insulation --option to finish the insulation layer: --base coat painted - option I --base coat covered with a thin-coat render (painted or unpainted) - option II --sprayable thin-coat render --ATLAS CERMIT G (without the basecoat) option III Product Data Sheets Catalogue 183 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) ATLAS SYSTEM (ETA) - with standard and elasticized polystyrene boards (EPS) 1. Ceramic hollow blocks 1 2 2. Primed substrate (optionally) 3 5 6 3. Adhesive for boards application 6 4. Thermal insulation of EPS boards 5. Additional fixing – mechanical fixings for EPS and XPS 7 4 6. Adhesive for reinforced layer 9 8 10 7. Base coat (reinforced layer) 8. Priming mass 9. Thin-coat render 10. Paint (optionally) Use General system characteristic The system is designed for installation of the external wall insulation of build- ATLAS system is an external thermal insulation composite system (ETICS). ings - it may be used both on the rendered/plastered façades and rough walls made The thermal insulation technology consists in the application of EPS boards of bricks and blocks (ceramic, cement-lime, stone, of aerated concrete and concrete onto the outer side of the wall, next the installation of a base coat with reinforcing fiberglass mesh, and further application of the finishing layer - monolithic or precast). For thermal insulation with the use of standard or elasticized polystyrene (EPS) - made of thin - coat render. the thermal insulation thickness is even up to 250 mm. System elements For installation of the thermal insulation of the buildings up to 25 m high. According to the current regulations the thermal insulation system is It can be fixed to the surfaces of horizontal or inclined building elements - proconsidered in its entirety as one construction product, therefore it must vided that they are not directly exposed to weather conditions. Recommended for thermal insulation works in the traditional constructions, en- be applied with the layers arrangement and with materials which are described in its technical approval. It is unacceptable to use the so-called ergy- saving and passive ones. compilations or to use products from other systems or from other manu Properties facturers, which are not covered by the technical approval. The system meets European technical requirements - designed for thermal insula- The products used in ATLAS system, according to the European Technical tion systems throughout the European Union. Approval, are listed in the table below: A complete set of materials for thermal insulation installation - provides full and checked compatibility of all components, which is particularly important during the subsequent years of system operation. Insulation fixing - basic General - purpose – enables the choice from the widest range of adhesives, renders and paints within one insulation system. ATLAS STOPTER K-10 adhesive mortar ATLAS STOPTER K-20 adhesive mortar Enables achievement of the external wall thermal insulation required by building ATLAS HOTER S adhesive mortar regulations - reduces heat loss and heating costs, provides an effective method of ATLAS HOTER U adhesive mortar thermal bridging avoiding. Improves the acoustic insulation of walls - thanks to the use of elasticized polystyInsulation material Polystyrene boards (EPS) described by a code which constitutes a combination rene the weighted acoustic insulation rate (ΔRw) can be improved by more than three of the following symbols: T2 (thickness); L1 or L2 (length); W2 (width); S1 or S2 decibels (fig. 1 - for system with adhesive, fig. 2 - system with adhesive and additional (rectangularity); DS(N)2; DS(70,-)1 or DS(70,-)2, BS(75), TR80 (elasticized polystyrene) mechanical fixing). or TR100 (standard polystyrene) Low water absorption – below 0.5 kg/m2 , making the system more resistant to thawInsulation fixing – additional freeze cycles. Authorized mechanical fixings, holding the European Technical Approval (ETA) issued in High system impact resistance - provides durability and resistance to damage during accordance with ETAG 014. operation of the system. If the building is lower than 12 m and the polystyrene thickness does not exceed 15 cm Increases durability of external walls - protecting them from direct exposure to the mechanical fixings are not obligatory.. weather conditions. Reinforced layer – ATLAS STOPTER K-20 or ATLAS HOTER U adhesive mortar The system is fire retardant - it relates to the thermal insulation systems with polystywith fiberglass mesh: SSA-1363-SM 05 or AKE 145 rene boards (EPS) of a thickness up to 250 mm. Outer (finishing) layer ATLAS CERMIT thin-coat render (mineral or acrylic) + ATLAS CERPLAST priming mass ATLAS SILKAT thin-coat render + ATLAS SILKAT ASX priming mass ATLAS SILKON thin-coat render + ATLAS SILKON ANX priming mass ATLAS ARKOL E façade paint ATLAS ARKOL S façade paint + ARKOL SX primer ATLAS ARKOL N façade paint + ARKOL NX primer ATLAS FASTEL NOVA façade paint fig.1 ,fig.2 insulation thickness [mm] thermal insulation with elastified EPS thermal insulation with standard EPS 184 www.atlas.com.pl E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) Technical requirements ATLAS System has been granted: - European Technical Approval ETA No. ETA-06/0081. Declaration of Performance No.001/ CPR. EC Certificate of Conformity No. 1488-CPD-0021. - Allgemeine Bauaufsichtliche Zullassung Z-33.84-963 (for Germany). - NSAI Certificate No. 10/0347 (for Ireland). - BBA Certificate No. 13/5018 (for the UK). Requirements for execution of thermal insualtion works Insulation boards sanding The surface of insulating boards applied to the substrate should be even, so when the mortar sets (after ca. 24 h), the boards should be sanded with the use of sanding boards or floats covered with coarse sanding paper. It eliminates any board edges slips. In the case of polystyrene boards installed 3 months earlier or more sanding and removal of any surface tarnish is mandatory. Additional elements installation Work conditions Carry out the work in dry weather, at the substrate and ambient temperature not lower than +5 °C and not higher than +30 °C. The only exception is the ATLAS STOPTER K-20 adhesive, which can also be used at 0 ° C, assuming that after 8 hours from the work completion the temperature does not drop below -5 ° C. The façade should be on time of thermal insulation work protected and secured against precipitation, strong wind and direct sunlight - it is recommended to use fine mesh scaffolding covers. Insulation works should be carried out in dry conditions (no precipitation, relative humidity below 80%). In order to increase the system resistance against mechanical damage, to allow free drainage and execution of expansion joints - the finishing profiles should be installed on the fixed thermal insulation layer. These profiles are installed at every specific locations of the façade (i.e. corners, reveals, sills, etc.). They can also be simultaneously installed during the base coat mesh embedding. Substrate preparation General instructions In all corners of window and door reveals, additional reinforcing mesh strips (rectangles with dimensions of 20 x 35 cm) embedded in the adhesive mortar ATLAS STOPTER K-20 or ATLAS HOTER U should be installed. The strips should be applied diagonally, at a 45° angle in relation to the line set by the edges of the reveals. Before the work commencement, evaluate the substrate technical condition and on that basis decide on the scope and the method of surface preparation. For the time of works remove any elements hindering tight adhesion of the thermal insulation boards and the finishing coat application. An additional layer of insulation will increase the thickness of the walls, and therefore it will cause the need to increase the reach of flashings, downspouts anchors, etc. For the time of works the windows and doors should be protected against the dirt by a plastic film. Requirements for the substrate The substrate should be aged, sound, stable, even, clean and dry. The absorbent substrates should be primed with ATLAS UNI-GRUNT, smooth and non-absorbent (concrete) with ATLAS CERPLAST. The substrate should be even to the extent enabling easy execution of a plane formed by the bonded insulation boards on the walls. Clean the surface from any layers which may weaken mortar adhesion, dirt, loose and dusty elements. Note! Particular attention should be paid to the proper assessment and preparation of substrate with problematic bearing capacity, e.g. finished with glass-mosaics, glazed brick, covered with paint coats, etc. If in doubt, conduct a pull - off test of adhesion (the ultimate tensile strength should be above 0.08 MPa) or apply 8÷10 cubes of EPS 10x10 cm each, in various places of the façade and tear them off after 3 days. The use of thermal insulation system for buildings with reinforced concrete sandwich walls, should always be preceded by a thorough assessment of their technical condition. This applies to the technical condition of the metal fittings (hooks, pins, rods) as well as to how they are connected and interact with the elements of the wall. Starter tracks installation The insulation should be commenced with the installation of the starter tracks. They support the first row of thermal insulation boards, facilitate to maintain the uniform level of successive layers, strengthen the bottom edge of the system, and the bottom edge drip prevents water bleeding. The boards should be installed horizontally on the plinth of the building, not lower than 30 cm above the ground level, which provides protection from the effects of rising damp and protects against dirt - mud particles brought by raindrops reflected from the ground. Instead of skirting boards, it is permitted to use strips of armour mesh or two layers of fiberglass mesh. Thermal insulation application Polystyrene boards application In the case of even substrates, the mortar can be applied with the use of a notched trowel (with notch size 12 mm)– the adhesive is applied then directly onto the board and not onto the substrate. In the case of less smooth surfaces the adhesive should be spread on the board surface using the “strip - point” method. It consists in the application of continuous circumferential bead (at least 3 cm wide) at the edge of the board and 6÷8 patches of 8÷12 cm in diameter evenly distributed on the whole surface. Peripheral bead is placed at a distance from the edge, so that when pressed to the wall the mortar is not squeezed out of the contour and side edges. The adhesive mortar applied on board should cover at least 40% of its surface (after pressing down to the substrate at least 60%).Thermal insulation application should commence from the building corners. The first row of the boards is fixed on the starter tracks, the subsequent rows positioned so that the vertical board joints are staggered and overlapped at the building corners. It is unacceptable to fit the edges of the insulation boards with the edges of the reveals on the façade. As the adhesive is applied, the board should be placed onto the substrate, moved tightly to the already fixed boards and pressed – be sure to control the plane with a level. If the adhesive is squeezed out the board contour, it should be removed. If there are gaps between adjoining boards, we recommend filling them with cut stripes of polystyrene or low expansion polyurethane foam. Reveals corners strengthening Mechanical fixing The additional fixing with the use of mechanical fasteners with plastic pins can commence after ca. 24 hours from the boards application. Detailed information about the number of fixings, their distribution, length and depth of anchorage should be specified in the thermal insulation technical design and meet the requirements of the fixings manufacturers. Base coat (reinforced layer) application The base coat can be installed once the adhesive mortar used for board application has sufficiently set and any necessary additional mechanical fixings have been installed (after three days on average). Apply the adhesive mortar onto the surface of the installed insulation boards and spread it using a notched trowel (notch size 10 - 12 mm). The adhesive should be spread in vertical strips of width slightly greater than the fiberglass mesh width. Then, starting from the top, subsequent strips of mesh are applied and in a few points along the entire length embedded in the prepared adhesive layer. The adjoining strips of mesh should overlap horizontally and vertically by a minimum coverage of 10 cm (15 cm in quoins). Mesh overlaps should not coincide with the joints between the insulation boards. When applied, the mesh should be carefully embed in the adhesive. In order to embed the mesh evenly, the adhesive is squeezed with the slightly inclined trowel led from the top, in the direction from the center to the mesh strip side. The correctly embedded mesh should be completely not visible under adhesive coat and should not be in direct contact with the polystyrene boards surface. Façade finishing The outer layer of the system may be a thin-coat render solely or a thincoat render coated with a façade paint. The execution of the finishing layer can start after ca. 3 days from the reinforced layer installation. You can use thin - coat render: ATLAS CERMIT (mineral or acrylic), ATLAS SILKAT (silicate) or ATLAS SILKON (silicone). The renders surface can be painted optionally with ATLAS ARKOL E, ATLAS ARKOL S, ATLAS ARKOL N or ATLAS FASTEL NOVA façade paints. All works must be performed in accordance with the technology described in the technical data sheets of the individual products. The above information constitutes basic guidelines for the application of the product and does not release the user from the obligation of carrying out works according to engineering principles and OHS regulations. At the time of publication of this product data sheet all previous ones become void. Date of update: 2013-07-01 Product Data Sheets Catalogue 185 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) ATLAS XPS SYSTEM (ETA) – with extruded polystyrene boards (XPS) 2 1. Ceramic hollow blocks 1 2. Primed substrate (optionally) 4 3. Adhesive for boards application 4. Thermal insulation of XPS boards 3 5. Additional fixing – mechanical fixings for EPS and XPS 5 8 6 7 6 10 9 6. Adhesives for reinforced layer 7. Base coat (reinforced layer) 8. Priming mass 9. Thin-coat render 10. Paint (optionally) Use The system is designed for installation of the external wall insulation of buildings - it may be used both on the rendered/plastered façades and rough walls made of bricks and blocks (ceramic, cement-lime, stone, of aerated concrete and concrete monolithic or precast). For thermal insulation with the use of extruded polystyrene (XPS) - the thermal insulation thickness is from 20 up to 200 mm. Recommended on plinths, foundation and cellar walls - due to the nature and type of insulation material, the system can be also used on gable walls, attics, at the building entrances. It can be fixed to the surfaces of horizontal or inclined building elements - provided that they are not directly exposed to weather conditions. Recommended for thermal insulation works in the traditional constructions, energy- saving and passive ones. Properties The products used in ATLAS XPS system, according to the European Technical Approval, are listed in the table below: Insulation fixing - basic ATLAS STOPTER K-10 adhesive mortar ATLAS STOPTER K-20 adhesive mortar ATLAS HOTER S adhesive mortar ATLAS HOTER U adhesive mortar Insulation material XPS panels with the codes: - T2-CS(10/Y)200-DS(TH)-TR100-WL(T)1,5 - T1-CS(10/Y)250-DS(TH)-TR100-WL(T)1,5 Insulation fixing – additional*) WKRĘT-MET: ŁIT, ŁIM, ŁFM8, ŁFN8, ŁFM10, ŁFN10 EJOT: ejotherm ST U, STR U, SDM-T plus U, NT U Fischer: TERMOZ 8N, 8U KOELNER: KI8M Hilti: SD-FV, SX-FV The system meets European technical requirements - designed for thermal insulation systems throughout the European Union. Reinforced layer A complete set of materials for thermal insulation installation - provides full and ATLAS STOPTER K-20 or ATLAS HOTER U adhesive mortar with fiberglass mesh: checked compatibility of all components, which is particularly important during the SSA-1363-SM 05 or AKE 145 subsequent years of system operation. Outer (finishing) layer Compatible with ATLAS thermal insulation EPS - based system - for the thermal ATLAS CERMIT thin-coat render (mineral or acrylic) + ATLAS CERPLAST insulation of the places most vulnerable to moisture and mechanical damage we the priming mass XPS is used, for other wall areas - EPS boards. ATLAS SILKAT thin-coat render + ATLAS SILKAT ASX priming mass High system durability - due to low water absorbability of the finishing coat (not ATLAS SILKON thin-coat render + ATLAS SILKON ANX priming mass more than 0.5 kg/m2 after 24 hours), combined with high resistance to water of XPS boards. ATLAS ARKOL E façade paint Impact resistance - the system has been classified as Category III. ATLAS ARKOL S façade paint + ARKOL SX primer ARKOL N façade paint + ARKOL NX primer Enables achievement of the external wall thermal insulation required by building ATLAS FASTEL NOVA façade paint + ARKOL NX primer regulations - reduces heat loss and heating costs, provides an effective method of thermal bridging avoiding. Increases durability of external walls - protecting them from direct exposure to *) other authorized mechanical fixings, holding the European Techniweather conditions. cal Approval (ETA) issued in accordance with ETAG 014 can be used. The system is fire retardant - it relates to the thermal insulation systems with ex Technical requirements truded polystyrene boards (XPS) of a thickness up to 200 mm. ATLAS XPS System has been granted: - European Technical Approval ETA No. ETA-07/0316. Declaration of Per General system characteristic formance No.003/CPR. EC Certificate of Conformity No. 1488-CPD-0075. ATLAS XPS system is an external thermal insulation composite system (ETICS). The thermal - NSAI Certificate No. 10/0347 (for Ireland). insulation technology consists in the application of XPS boards onto the outer side of the wall, next the installation of a base coat with reinforcing fiberglass mesh, and further Requirements for execution of thermal insualtion works application of the finishing layer made of thin - coat render. Work conditions Carry out the work in dry weather, at the substrate and ambient temper System elements ature not lower than +5 °C and not higher than +30 °C. The only excepAccording to the current regulations the thermal insulation system is considered in its tion is the ATLAS STOPTER K-20 adhesive, which can also be used at 0 ° C, entirety as one construction product, therefore it must be applied with the layers arrange- assuming that after 8 hours from the work completion the temperature ment and with materials which are described in its technical approval. It is unacceptable does not drop below -5 ° C. The façade should be on time of thermal into use the so-called compilations or to use products from other systems or from other sulation work protected and secured against precipitation, strong wind manufacturers, which are not covered by the technical approval. 186 www.atlas.com.pl E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) and direct sunlight - it is recommended to use fine mesh scaffolding covers. Insulation works should be carried out in dry conditions (no precipitation, relative humidity below 80%). Substrate preparation General instructions with dimensions of 20 x 35 cm) embedded in the adhesive mortar ATLAS STOPTER K-20 or ATLAS HOTER U should be installed. The strips should be applied diagonally, at a 45° angle in relation to the line set by the edges of the reveals. Mechanical fixing Before the work commencement, evaluate the substrate technical condition and on that basis decide on the scope and the method of surface preparation. For the time of works remove any elements hindering tight adhesion of the thermal insulation boards and the finishing coat application. An additional layer of insulation will increase the thickness of the walls, and therefore it will cause the need to increase the reach of flashings, downspouts anchors, etc. For the time of works the windows and doors should be protected against the dirt by a plastic film. The additional fixing with the use of mechanical fasteners with plastic pins can commence after ca. 24 hours from the boards application. Detailed information about the number of fixings, their distribution, length and depth of anchorage should be specified in the thermal insulation technical design and meet the requirements of the fixings manufacturers. Requirements for the substrate The base coat can be installed once the adhesive mortar used for board application has sufficiently set and any necessary additional mechanical fixings have been installed (after three days on average). Apply the adhesive mortar onto the surface of the installed insulation boards and spread it using a notched trowel (notch size 10 - 12 mm). The adhesive should be spread in vertical strips of width slightly greater than the fiberglass mesh width. Then, starting from the top, subsequent strips of mesh are applied and in a few points along the entire length embedded in the prepared adhesive layer. The adjoining strips of mesh should overlap horizontally and vertically by a minimum coverage of 10 cm (15 cm in quoins). Mesh overlaps should not coincide with the joints between the insulation boards. When applied, the mesh should be carefully embed in the adhesive. In order to embed the mesh evenly, the adhesive is squeezed with the slightly inclined trowel led from the top, in the direction from the center to the mesh strip side. The correctly embedded mesh should be completely not visible under adhesive coat and should not be in direct contact with the polystyrene boards surface. The substrate should be aged, sound, stable, even, clean and dry. The absorbent substrates should be primed with ATLAS UNI-GRUNT, smooth and non-absorbent (concrete) with ATLAS CERPLAST. The substrate should be even to the extent enabling easy execution of a plane formed by the bonded insulation boards on the walls. Clean the surface from any layers which may weaken mortar adhesion, dirt, loose and dusty elements. Note! Particular attention should be paid to the proper assessment and preparation of substrate with problematic bearing capacity, e.g. finished with glass-mosaics, glazed brick, covered with paint coats, etc. If in doubt, conduct a pull - off test of adhesion (the ultimate tensile strength should be above 0.08 MPa) or apply 8÷10 cubes of polystyrene 10x10 cm each, in various places of the façade and tear them off after 3 days. The use of thermal insulation system for buildings with reinforced concrete sandwich walls, should always be preceded by a thorough assessment of their technical condition. This applies to the technical condition of the metal fittings (hooks, pins, rods) as well as to how they are connected and interact with the elements of the wall. Starter tracks installation The insulation should be commenced with the installation of the starter tracks. They support the first row of thermal insulation boards, facilitate to maintain the uniform level of successive layers, strengthen the bottom edge of the system, and the bottom edge drip prevents water bleeding. The boards should be installed horizontally on the plinth of the building, not lower than 30 cm above the ground level, which provides protection from the effects of rising damp and protects against dirt - mud particles brought by raindrops reflected from the ground. Instead of skirting boards, it is permitted to use strips of armour mesh or two layers of fiberglass mesh. Thermal insulation application XPS boards application In the case of even substrates, the mortar can be applied with the use of a notched trowel (with notch size 12 mm)– the adhesive is applied then directly onto the board and not onto the substrate. In the case of less smooth surfaces the adhesive should be spread on the board surface using the “strip - point” method. It consists in the application of continuous circumferential bead (at least 3 cm wide) at the edge of the board and 6÷8 patches of 8÷12 cm in diameter evenly distributed on the whole surface. Peripheral bead is placed at a distance from the edge, so that when pressed to the wall the mortar is not squeezed out of the contour and side edges. The adhesive mortar applied on board should cover at least 40% of its surface (after pressing down to the substrate at least 60%).Thermal insulation application should commence from the building corners. The first row of the boards is fixed on the starter tracks, the subsequent rows positioned so that the vertical board joints are staggered and overlapped at the building corners. It is unacceptable to fit the edges of the insulation boards with the edges of the reveals on the façade. As the adhesive is applied, the board should be placed onto the substrate, moved tightly to the already fixed boards and pressed – be sure to control the plane with a level. If the adhesive is squeezed out the board contour, it should be removed. If there are gaps between adjoining boards, we recommend filling them with cut stripes of polystyrene or low expansion polyurethane foam. Base coat (reinforced layer) application Façade finishing The outer layer of the system may be a thin-coat render solely or a thincoat render coated with a façade paint. The execution of the finishing layer can start after ca. 3 days from the reinforced layer installation. You can use thin - coat render: ATLAS CERMIT (mineral or acrylic), ATLAS SILKAT (silicate) or ATLAS SILKON (silicone). The renders surface can be painted optionally with ATLAS ARKOL E, ATLAS ARKOL S, ATLAS ARKOL N or ATLAS FASTEL NOVA façade paints. All works must be performed in accordance with the technology described in the technical data sheets of the individual products. The above information constitutes basic guidelines for the application of the product and does not release the user from the obligation of carrying out works according to engineering principles and OHS regulations. At the time of publication of this product data sheet all previous ones become void. Date of update: 2013-07-01 Insulation boards sanding The surface of insulating boards applied to the substrate should be even, so when the mortar sets (after ca. 24 h), the boards should be sanded with the use of sanding boards or floats covered with coarse sanding paper. It eliminates any board edges slips. Installation of additional elements In order to increase the system resistance against mechanical damage, to allow free drainage and execution of expansion joints - the finishing profiles should be installed on the fixed thermal insulation layer. These profiles are installed at every specific locations of the façade (i.e. corners, reveals, sills, etc.). They can also be simultaneously installed during the base coat mesh embedding. Reveals corners strengthening In all corners of window and door reveals, additional reinforcing mesh strips (rectangles Product Data Sheets Catalogue 187 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) ATLAS ROKER SYSTEM (ETA) -with mineral wool panels 1. 2. 3. 4. Ceramic hollow blocks Primed substrate (optionally) Adhesive for panels application Thermal insulation of mineral wool (MW) - lamella or façade panels 5. Additional fixing – mechanical fixings for mineral wool 6. Adhesive for reinforced layer 7. Base coat (reinforced layer) 8. Priming mass 9. Thin-coat mineral render 10. Paint (optionally) Use Insulation fixing - basic The system is designed for installation of the external wall insulation of buildings - it may be used both on the rendered/plastered façades and rough walls made of bricks and blocks (ceramic, cement-lime, stone, of aerated concrete and concrete - monolithic or precast). For thermal insulation with the use of mineral wool - both the façade panels (of thickness 50 - 250 mm) and the lamella panels (of thickness 20 - 250 mm). For thermal insulation of buildings irrespectively of their height - especially for high buildings and skyscrapers (above 25 m). Recommended for thermal insulation works in the traditional constructions, energy- saving and passive ones - due to non - flammability the system is recommended for thermal insulation of public access buildings, schools, hospitals, etc. Properties The system meets European technical requirements - designed for thermal insulation systems throughout the European Union. Increases fire protection of buildings - increases the safety of their users protecting the construction elements against fire. The system is non-flammable (with mineral renders) and fire retardant. Very high vapour permeability - does not restrict the water vapour flow through the insulated partition, allowing free drying of the wall technological moisture (diffusion resistance coefficient 0.12 m for the system with mineral render finishing coat). Provides legally required external wall insulation - ensures heat loss and heating costs reduction. Impact resistance - the system has been classified as Category I or Category II, depending on the finishing coat type. Safety of use - the system has been tested in wind load resistance, which is especially important in case of high buildings or located in the mountains or by the sea. Allows to install the thermal insulation on surfaces of irregular shapes - with the use of lamella panels. A complete set of materials for thermal insulation installation - provides full and checked compatibility of all components, which is particularly important during the subsequent years of system operation. Increases durability of external walls - protecting them from direct exposure to weather conditions. General system characteristic ATLAS ROKER system is an external thermal insulation composite system (ETICS). The thermal insulation technology consists in the application of mineral wool panels (MW) onto the outer side of the wall, next the installation of a base coat with reinforcing fiberglass mesh, and further application of the finishing layer made of thin - coat render. System elements According to the current regulations the thermal insulation system is considered in its entirety as one construction product, therefore it must be applied with the layers arrangement and with materials which are described in its technical approval. It is unacceptable to use the so-called compilations or to use products from other systems or from other manufacturers, which are not covered by the technical approval. The products used in ATLAS ROKER system, according to the European Technical Approval, are listed in the table below: 188 www.atlas.com.pl ATLAS ROKER W-20 - adhesive for mineral wool Insulation material Mineral wool panels (MW) with the codes: Standard wool: T4 or T5 (thickness); DS(TH); WS, WL(P), TR10 or TR15, CS(10)40 or CS(10,Y)50 Lamella wool: T5 (thickness); DS(TH); WS, WL(P), TR80 or TR100, CS(10)30 or CS(10)40 Insulation fixing – additional WKRĘT-MET: ŁMX 8, ŁTX 8, ŁMX 10, ŁTX 10 EJOT: ejotherm STR U, SDK-U, NT U, NK U, SDM-T plus U Fischer: TERMOZ 8N, 8NZ, PN8 KOELNER: TFIX-8M, KI-10N MKaM-Łi3A 10, MKaM-Łi3A 10 Mt BRAVOLL PTH-S 60/8-La, BRAVOLL PTH-SL 60/8-La Hilti SD-FV Reinforced layer ATLAS ROKER W-20 adhesive mortar with fiberglass mesh: SSA-1363-SM 05 or AKE 145 Outer (finishing) layer ATLAS CERMIT (mineral) thin-coat render + ATLAS CERPLAST priming mass ATLAS SILKAT thin-coat render + ATLAS SILKAT ASX priming mass ATLAS SILKON thin-coat render + ATLAS SILKON ANX priming mass ATLAS ARKOL S façade paint + ARKOL SX primer ARKOL N façade paint + ARKOL NX primer ATLAS FASTEL NOVA façade paint + ARKOL NX primer Technical requirements ATLAS ROKER System has been granted: - European Technical Approval ETA No. ETA-06/0173. Declaration of Performance No.E002/CPR. EC Certificate of Conformity No. 1488-CPD-0036. - Allgemeine Bauaufsichtliche Zullassung Z-33.84-964 (for Germany). - NSAI Certificate No. 10/0347 (for Ireland). - BBA Certificate No. 13/5018 (for the UK). Requirements for execution of thermal insualtion works Work conditions Carry out the work in dry weather, at the substrate and ambient temperature not lower than +5 °C and not higher than +30 °C. The façade should be on time of thermal insulation work protected and secured against precipitation, strong wind and direct sunlight - it is recommended to use fine mesh scaffolding covers. Insulation works should be carried out in dry conditions (no precipitation, relative humidity below 80%). Substrate preparation General instructions Before the work commencement, evaluate the substrate technical condition and on that basis decide on the scope and the method of surface preparation. For the time of works remove any elements hindering tight adhesion of the thermal insulation panels and the finishing coat application. An additional layer of insulation will increase the thickness of the walls, and therefore it will cause the need to increase the reach of flashings, downspouts anchors, etc. For the time of works the windows and doors should be protected against the dirt by a plastic film. E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) Requirements for the substrate The substrate should be aged, sound, stable, even, clean and dry. The absorbent substrates should be primed with ATLAS UNI-GRUNT, smooth and non-absorbent (concrete) with ATLAS CERPLAST. The substrate should be even to the extent enabling easy execution of a plane formed by the bonded insulation panels on the walls. Clean the surface from any layers which may weaken mortar adhesion, dirt, loose and dusty elements. Note! Particular attention should be paid to the proper assessment and preparation of substrate with problematic bearing capacity, e.g. finished with glass-mosaics, glazed brick, covered with paint coats, etc. If in doubt, conduct a pull - off test of adhesion (the ultimate tensile strength should be above 0.08 MPa) or apply 8÷10 cubes of mineral wool 10x10 cm each, in various places of the façade and tear them off after 3 days. The use of thermal insulation system for buildings with reinforced concrete sandwich walls, should always be preceded by a thorough assessment of their technical condition. This applies to the technical condition of the metal fittings (hooks, pins, rods) as well as to how they are connected and interact with the elements of the wall. Starter tracks installation The insulation should be commenced with the installation of the starter tracks. They support the first row of thermal insulation boards, facilitate to maintain the uniform level of successive layers, strengthen the bottom edge of the system, and the bottom edge drip prevents water bleeding. The boards should be installed horizontally on the plinth of the building, not lower than 30 cm above the ground level, which provides protection from the effects of rising damp and protects against dirt - mud particles brought by raindrops reflected from the ground. Instead of skirting boards, it is permitted to use strips of armour mesh or two layers of fiberglass mesh. Thermal insulation application Mineral wool panels application The adhesive can be applied onto the panels with two methods: partly with the “strip point” method or fully (lamella panels or façade wool panels, but only on respectively even substrates). In both cases, the surface of the panel should be floated with thin layer of adhesive mortar, pressed into the structure of wool by stripping using the edge of a steel trowel. This activity is designed to pre-moisten the wool fibers and improve adhesion. Then, in the case of partial application, apply the proper layer of adhesive in the form of continuous circumferential bead (3÷5 cm wide) at the edge of the panel and 6÷8 patches of 8÷12 cm in diameter evenly distributed on the whole surface. The adhesive mortar applied on panel should cover at least 40% of its surface. In the case of full adhesive application, the adhesive is applied onto the entire surface of the panel with the use of smooth float and then profiled with notched trowel (notch height of 8 - 12 mm). As the adhesive is applied on the underside of the panels, both façade or lamella, the panels should be applied onto the substrate, lightly moved and pressed. The subsequent panels rows should be positioned so that the vertical panel joints are staggered and overlapped. It is unacceptable to leave gaps between adjacent panels or adhesive residues in the joints. Control the plane with a level continuously. Pressing and correcting of panels position is allowed only with the use of wooden float with round edges. Base coat (reinforced layer) application The base coat can be installed once the adhesive mortar used for panel application has sufficiently set and any necessary additional mechanical fixings have been installed (after three days on average). Apply the adhesive mortar onto the surface of the installed insulation panels and spread it using a notched trowel (notch size 10 - 12 mm). The adhesive should be spread in vertical strips of width slightly greater than the fiberglass mesh width. Then, starting from the top, subsequent strips of mesh are applied and in a few points along the entire length embedded in the prepared adhesive layer. The adjoining strips of mesh should overlap horizontally and vertically by a minimum coverage of 10 cm (15 cm in quoins). Mesh overlaps should not coincide with the joints between the insulation panels. When applied, the mesh should be carefully embed in the adhesive. In order to embed the mesh evenly, the adhesive is squeezed with the slightly inclined trowel led from the top, in the direction from the center to the mesh strip side. The correctly embedded mesh should be completely not visible under adhesive coat and should not be in direct contact with the mineral wool panels surface. Façade finishing The outer layer of the system may be a thin-coat render solely or a thincoat render coated with a façade paint. The execution of the finishing layer can start after ca. 3 days from the reinforced layer installation. You can use thin - coat render: ATLAS CERMIT (mineral), ATLAS SILKAT (silicate) or ATLAS SILKON (silicone). The renders surface can be painted optionally with ATLAS ARKOL S, ATLAS ARKOL N or ATLAS FASTEL NOVA façade paints. All works must be performed in accordance with the technology described in the technical data sheets of the individual products. The above information constitutes basic guidelines for the application of the product and does not release the user from the obligation of carrying out works according to engineering principles and OHS regulations. At the time of publication of this product data sheet all previous ones become void. Date of update: 2013-07-01 Installation of additional elements In order to increase the system resistance against mechanical damage, to allow free drainage and execution of expansion joints - the finishing profiles should be installed on the fixed insulation layer. These profiles are installed at every specific locations of the façade (i.e. corners, reveals, sills, etc.). They can also be simultaneously installed during the base coat mesh embedding. Reveals corners strengthening In all corners of window and door reveals, additional reinforcing mesh strips (rectangles with dimensions of 20 x 35 cm) embedded in the adhesive mortar ATLAS ROKER W-20 should be installed. The strips should be applied diagonally, at a 45° angle in relation to the line set by the edges of the reveals. Mechanical fixing The additional fixing with the use of plastic mechanical fasteners with steel pins can commence after ca. 24 hours from the panels application. Detailed information about the number of fixings, their distribution, length and depth of anchorage should be specified in the thermal insulation technical design and meet the requirements of the fixings and mineral wool manufacturers. It is recommended to use 4 to 6 fixings per 1 m2 (buildings up to 20 m high) and 6 to 10 (in buildings exceeding 20 m). The amount of fixings should be bigger in the wall corners and edge zones of width of about 1.5 m. Product Data Sheets Catalogue 189 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) ATLAS ROKER G SYSTEM – with mineral wool panels – for ceilings ATLAS ROKER G THERMAL INSULATION SYSTEM Option I Option III Use System elements The system is designed for insulation of ceilings and walls - if not directly exposed to weathering or mechanical damage, in residential, commercial, public access and industrial premises, both in existing and newly constructed buildings. Indoor use - options I, II and III - on ceilings and walls in unheated rooms (e.g. garages, basements, multi-level parking spaces), open and closed, over or in the vicinity of heated rooms. Outdoor use - options II and III - the outer surfaces of ceilings, e.g. over driveways, walkways, parking spaces, over which heated rooms are located. According to the current regulations the thermal insulation system is considered in its entirety as one construction product, therefore it must be applied with the layers arrangement and with materials which are described in its technical approval. It is unacceptable to use the so-called compilations or to use products from other systems or from other manufacturers, which are not covered by the technical approval. The products used in ATLAS ROKER G system, according to the ITB Technical Approval No. AT-15-7314/2011, are listed in the tables below. Properties A complete set of materials for thermal insulation installation - provides full and checked compatibility of all components, which is particularly important during the subsequent years of system operation. Available in three material and technological options - allows execution of thermal insulation in one of three options (marked with Roman symbols I, II or III), depending on the needs and objectives of the project. Option I and II - allows to use insulation method similar to the standard external wall thermal insulation method, installation of the reinforced layer ensures greater resistance to mechanical damages and factors related to the operation and the use of the premises. Option III - allows for less intensive works, faster progress of thermal insulation and reduction of labor costs due to lack of the base coat installation need and spray application of the finishing coat directly onto the outer layer of thermal insulation panels. Allows to reach the required ceiling thermal insulation - reduces heat loss and cost of heating. System components are non-flammable - ATLAS ROKER G system increases protection of structural elements of the building against fire and high temperature. Classified as fire retardant - in accordance with applicable regulations (applies to all three types of material- technological system options). Characterized by high reaction to fire class - insulation systems in the option II (with mineral and silicate render) and in the option III are classified as fully non-flammable (reaction to fire class A2 s2 , d0 ). General system characteristic Technology of ATLAS ROKER G system consists in application of the mineral wool insulation panels onto the surfaces of inner walls or ceilings and then the execution of the finishing coat according to one of three material/ technological options. In the option I the base coat with fiberglass mesh is applied manually on the mineral wool surface and then the resulting surface is coated with façade paint. In the option II the base coat with fiberglass mesh is applied manually on the mineral wool surface and then the resulting surface is coated with thin - coat render, with optional painting. In the option III, an outer layer of thin-coat render is spray - applied on the mineral wool panels (one side impregnated). Option III allows to reduce the cost of both material and labor, and shorten the system installation time while maintaining its full technical and use functionality. . 190 Option II www.atlas.com.pl Technical requirements ATLAS ROKER G System has been granted the Technical Approval ITB No. AT-15-7314/2011. Domestic Declaration of Conformity No. 115 of 16.07.2012. FPC Certificate No. ITB-0222/Z. Requirements for execution of thermal insualtion works Work conditions Carry out the works at ambient and substrate temperature not lower than +5 °C and not higher than +30 °C. Substrate preparation General recommendation The insulation works should be conducted in accordance with the technical design prepared individually for an object. The design should include (at least): substrate preparation method, the thickness of the insulation material, the insulation application method, the type of the outer layer and the technology of its application, the number and distribution of mechanical fixings (if required), finishing of special zones. The design should also include a range of thermal insulation works i.e., whether in addition the ceiling plane insulation, other elements (columns, joists or wall fragments) are to be insulated as well. For the time of works remove any elements hindering tight adhesion of the thermal insulation panels and the finishing coat application. Elements of the permanent equipment of the building (installations, ducts, etc.) must be protected from contamination and/or damage. In the case of spray application of renders the floor should also be protected. Requirements for the substrate The substrate should be aged, sound, stable, even, clean and dry. The absorbent substrates should be primed with ATLAS UNI-GRUNT, smooth and non-absorbent (concrete) with ATLAS CERPLAST. The substrate should be even to the extent enabling easy execution of a plane formed by the bonded insulation panels. Clean the surface from any layers which may weaken mortar adhesion, dirt, loose and dusty elements. . If in doubt, conduct a pull - off test of adhesion (the ultimate tensile strength should be above 0.08 MPa) or apply 8÷10 cubes of mineral wool 10x10 cm each, in various places of the façade and tear them off after 3 days. dimensions of 10 x 10 cm and breaking them after 3 days. E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) Thermal insulation application Standard (façade) wool panels application It is recommended to use adhesive mortar and, obligatorily, mechanical fixings (4-6 pieces/1m2). The adhesive can be applied onto the panels with two methods: partly with the “strip - point” method or fully (lamella panels or façade wool panels, but only on respectively even substrates). In both cases, the surface of the panel should be floated with thin layer of adhesive mortar, pressed into the structure of wool by stripping using the edge of a steel trowel. This activity is designed to pre-moisten the wool fibers and improve adhesion. Then, in the case of partial application, apply the proper layer of adhesive in the form of continuous circumferential bead (3÷5 cm wide) at the edge of the panel and 6÷8 patches of 8÷12 cm in diameter evenly distributed on the whole surface. The adhesive mortar applied onto panel should cover at least 40% of its surface. In the case of full adhesive application, the adhesive is applied onto the entire surface of the panel with the use of smooth float and then profiled with notched trowel (notch height of 8 - 12 mm). Lamella wool panels application In the case of lamella wool, to the panels may be applied onto the substrate with the use of adhesive mortar solely (without mechanical fixings) in the following cases: when the substrate is rough (not rendered), its ultimate tensile strength is higher than 0.08 MPa and when the thermal insulation is executed on the height not exceeding 20 m. In that situations the adhesive mortar layer should be spread on the whole mineral wool panel surface. In other conditions the lamella panels should be fixed with the use of adhesive mortar and mechanical fixings. As the adhesive is applied on the underside of the panels, they should be applied to the substrate, lightly moved and pressed. The subsequent panels rows should be positioned so that the vertical panel joints are staggered and overlapped. It is unacceptable to leave gaps between adjacent panels or adhesive residues in the joints. Control the plane with a level continuously. Pressing and correcting the panels position is allowed only with the use of wooden float with round edges. Installation of the mechanical fixings can commence after about 24 hours from the panels application. Detailed information about the number of fixings, their distribution, length and depth of anchorage should be specified in the thermal insulation technical design and meet the requirements of the fixings and mineral wool manufacturers. Finishing coat Option II In the system option II, the fixed thermal insulation is covered with the reinforced layer (base coat) installed with the same method as in option I. Then, the thin - coat render is applied and optionally painted. After about 3 days from application of the base coat, its surface may be primed with a priming mass appropriate for the type of render and after the mass drying - coated with the thin - coat render. The use of priming mass improves the adhesion of the render to the substrate and prevents contamination of the rendering coat by the adhesive mortar. You can use the following renders: ATLAS CERMIT (mineral), ATLAS SILKAT (silicate) or ATLAS SILKON (silicone). The render surface may be painted optionally with ATLAS ARKOL S, ATLAS ARKOL N, ATLAS ARKOL E or ATLAS FASTEL NOVA paints. All works must be performed in accordance with the technology described in the technical data sheets of the individual products. Option III For option III the reinforced layer is not installed and the thin-coat render is spray - applied directly onto the lamella wool panels surface. In the case of mineral wool boards factory - impregnated the use of additional priming masses is not required. If the mineral wool surface is not pre - impregnated, use ATLAS CERPLAST priming mass, which is spray - applied onto the applied panels surface. It is possible to use a mineral render, stirred with water before use, or acrylic render provided to the site in the form of ready-to-use mass. All works must be performed in accordance with the technology described in the technical data sheets of the individual products. The above information constitutes basic guidelines for the application of the product and does not release the user from the obligation of carrying out works according to engineering principles and OHS regulations. At the time of publication of this product data sheet all previous ones become void. Date of update: 2013-07-01 The technology of the finishing coat application depends on the ATLAS ROKER G system option used, i.e. I, II or III. Option I In the system option I, the fixed thermal insulation is covered with the reinforced layer (base coat) which may be painted with one of the façade paints. The base coat can be installed after min. 3 days from the panels application. Apply the ATLAS ROKER W-20 adhesive mortar onto the surface of the installed insulation panels evenly and embed subsequent mesh strips. The correctly embedded mesh should be completely not visible under adhesive coat and should not be in direct contact with the mineral wool panels surface. The adjoining strips of mesh should overlap by a minimum coverage of 10 cm. Mesh overlaps should not coincide with the joints between the insulation panels. The last step is smoothing the base coat with a steel float. After about 3 days from application of the base coat, its surface may be primed with a primer appropriate for the type of paint and then coated with façade paint. The following paints can be used for the base coat painting: ATLAS ARKOL S, ATLAS ARKOL N, ATLAS ARKOL E or ATLAS FASTEL NOVA. All works must be performed in accordance with the technology described in the technical data sheets of the individual products. Note! In case of thermal insulation application in open garages, over the crossings, etc., where there is a possibility of insulation moistening by jamming rain or snow, it is obligatory to apply the thin - coat render both on walls and ceilings, and in the edge zones of the insulation. The edge zones should be understood as insulation at a distance of not less than 3 m from the edge exposed to the rain, with the exception of entries where this distance should be 10 m. Product Data Sheets Catalogue 191 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) OPTION I OPTION III Insulation fixing - basic ATLAS ROKER W-20 - adhesive for mineral wool Insulation material *) Standard wool FASROCK (MW-EN13162-T5-DS(T+)-DS(TH)-CS(10)40-TR15-WS-WL(P)-MU1) FASROCK MAX (MW-EN13162-T4-DS(TH)-CS(10)10-TR7,5-WS- MU1) PAROC FAS 3 (MW-EN13162-T5-DS(TH)-CS(10)30-TR10-WS-WL(P)-MU1) PAROC FAS 4 (MW-EN13162-T5-DS(TH)-CS(10)40-TR15-WS-WL(P)-MU1) PAROC FAS B (MW-EN13162-T5-DS(TH)-CS(10/20)-TR10-WS-WL(P)-MU1) FRONTROCK MAX E (MW-EN13162-T5-DS(T+)-DS(TH)-CS(10)20-TR10-PL(5)250-WS-WL(P)-MU1) FASOTERM PF (MW-EN13162-T5-DS(TH)-CS(10/40)-TR15-MU1-AFr5) Lamella wool FASROCK L (MW-EN13162-T5-DS(T+)-DS(TH)-CS(10\Y)40-TR100-WS-WL(P)-MU1) PAROC FAL 1 (MW-EN13162-T5-DS(TH)-CS(Y)50-TR80-WS-WL(P)-MU1) FASOTERM NF (MW-EN13162-T5-CS(10/30)-TR80-MU1-AFr5 Insulation fixing - basic - ATLAS ROKER W-10 adhesive mortar - ATLAS ROKER W-20 adhesive mortar Insulation material *) Lamella wool PAROC CGL20 CY (MW-EN13162-T5-DS(TH)-CS(Y)20-TR20-WS-WL(P)-MU1) FASROCK L (MW-EN 13162-T5-DS(TH+)-DS(TH)-CS(10\Y)40-TR100-WSWL(P)-MU1) ISOVER NF333 (MW-EN 13162-T5-DS(TH)-CS(10)40-TR15-WS-WL(P)-MU1) ISOROC ISOFAS LM (MW-EN 13162-T5-DS(TH)-CS(10)50-TR90-WS-WL(P)-MU1) Thermal insulation fixing – additional Fasteners are not required in the following cases: - the substrate is rough (not rendered) - substrate tensile strength > 0.08 MPa - thermal insulation is executed up to 20 m Outer (finishing) layer ATLAS CERMIT MN thin-coat render Insulation fixing – additional Standard wool Mechanical fasteners with steel pin Lamella wool Fasteners are not required in the following cases: - the substrate is rough (not rendered) - substrate tensile strength > 0.08 MPa - thermal insulation is executed up to 20 m Reinforced layer – ATLAS ROKER W-20 adhesive with fiber-glass mesh embedded: SSA-1363 SM(100) / SSA-1363-SM 0.5 or VERTEX 145 /AKE 145 Outer (finishing) layer ATLAS ARKOL E façade paint ATLAS ARKOL S façade paint + ARKOL SX primer ATLAS ARKOL N façade paint + ARKOL NX primer ATLAS FASTEL NOVA façade paint OPTION II Insulation fixing - basic ATLAS ROKER W-20 - adhesive for mineral wool Insulation material *) Standard wool FASROCK (MW-EN13162-T5-DS(T+)-DS(TH)-CS(10)40-TR15-WS-WL(P)-MU1) FASROCK MAX (MW-EN13162-T4-DS(TH)-CS(10)10-TR7,5-WS- MU1) PAROC FAS 3 (MW-EN13162-T5-DS(TH)-CS(10)30-TR10-WS-WL(P)-MU1) PAROC FAS 4 (MW-EN13162-T5-DS(TH)-CS(10)40-TR15-WS-WL(P)-MU1) PAROC FAS B (MW-EN13162-T5-DS(TH)-CS(10/20)-TR10-WS-WL(P)-MU1) FRONTROCK MAX E (MW-EN13162-T5-DS(T+)-DS(TH)-CS(10)20-TR10-PL(5)250-WS-WL(P)-MU1) FASOTERM PF (MW-EN13162-T5-DS(TH)-CS(10/40)-TR15-MU1-AFr5) Lamella wool FASROCK L (MW-EN13162-T5-DS(T+)-DS(TH)-CS(10\Y)40-TR100-WS-WL(P)-MU1) PAROC FAL 1 (MW-EN13162-T5-DS(TH)-CS(Y)50-TR80-WS-WL(P)-MU1) FASOTERM NF (MW-EN13162-T5-CS(10/30)-TR80-MU1-AFr5 Thermal insulation fixing – additional Standard wool Mechanical fasteners with steel pin Lamella wool Fasteners are not required in the following cases: - the substrate is rough (not rendered) - substrate tensile strength > 0.08 MPa - thermal insulation is executed up to 20 m Reinforced layer – ATLAS ROKER W-20 adhesive with fiber-glass mesh embedded: SSA-1363 SM(100) / SSA-1363-SM 0.5 or VERTEX 145 /AKE 145 VARIETY II Outer (finishing) layer ATLAS CERMIT (mineral) thin-coat render + ATLAS CERPLAST priming mass ATLAS SILKAT thin-coat render + ATLAS SILKAT ASX priming mass ATLAS SILKON thin-coat render + ATLAS SILKON ANX priming mass ATLAS ARKOL E façade paint ATLAS ARKOL S façade paint + ARKOL SX primer ATLAS ARKOL N façade paint + ARKOL NX primer ATLAS FASTEL NOVA façade paint 192 www.atlas.com.pl *) It is acceptable to use other mineral wool panels, provided that the results of thermal insulation systems using these panels meet the requirements of the technical approval (this note applies to all options) E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) ATLAS ROKER G THERMAL INSULATION SYSTEM Option I 1. Concrete ceiling 1 2 3 4 5 7 2. Optional priming 3. Adhesive for panel fixing 4. Mineral wool 5. Mechanical fasteners with steel pin 6. Adhesive for reinforced layer 7. Reinforcing mesh 6 8. Paint coat 8 ATLAS ROKER G THERMAL INSULATION SYSTEM Option II 1. Concrete ceiling 2. Optional priming 1 3. Adhesive for panel fixing 2 3 4. Lamella mineral wool 4 5 6 7 8 9 5. Mechanical fasteners with steel pin 6. Adhesive for reinforced layer 7. Reinforcing mesh 8. Priming mass 9. Thin-coat render 10 10. Optional paint coat ATLAS ROKER G THERMAL INSULATION SYSTEM Option III 1. Concrete ceiling 1 3 2. Optional priming 3. Adhesive for panel fixing 2 4. Lamella mineral wool 4 5. ATLAS CERMIT MN render for spray application 5 6. Optional paint coat 6 Product Data Sheets Catalogue 193 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) ATLAS RENOTER – extra insulation system for walls with existing thermal insulation 1 1a 1 1b 2 4 3 5 6 6 7 8 9 • improves the thermal insulation properties of insulated walls • 30 cm maximum total insulation thickness • for all types of buildings • does not require removing old render • two application techniques System elements 1. a) Wall — substrate for mechanical fixings, b) Old thin - coat render — substrate for adhesive application 2. ATLAS adhesive for EPS boards application 3. New EPS thermal insulation board 4. Main mechanical fixing — anchor for EPS installation 5. Blanking plug 6. ATLAS adhesive for base coat application 7. ATLAS reinforcing mesh 8. ATLAS priming mass for thin-coat render 9. ATLAS thin-coat render Use The system is designed for installation of the external wall insulation of buildings - in case when the existing external wall insulation is in bad condition and/or does not meet the current requirements for thermal insulation. For thermal insulation with the use of polystyrene - enables insulation refurbishment by applying extra layer of thermal insulation material (in case of existing polystyrene thermal insulation systems). Recommended for thermal insulation works in the traditional constructions, energy- saving and passive ones. Properties 194 According to the current regulations the thermal insulation system is considered in its entirety as one construction product, therefore it must be applied with the layers arrangement and with materials which are described in its technical approval. It is unacceptable to use the so-called compilations or to use products from other systems or from other manufacturers, which are not covered by the technical approval. Insulation fixing - basic ATLAS STOPTER K-10 adhesive mortar ATLAS STOPTER K-20 adhesive mortar ATLAS STOPTER K-50 adhesive mortar ATLAS HOTER S adhesive mortar ATLAS HOTER U adhesive mortar Insulation material Polystyrene boards (EPS) of the minimum properties meeting the code: EPS–EN 13163–T1–L2–W2–S5–P5–BS75–DS(N)2–DS(70,-)2–TR100 Caution. Boards of tensile strength TR80 may be used if are covered by the ITB Technical and Quality Recommendation or volitional Certificate issued by an approved assessment unit. Insulation fixing – additional Mechanical fixings authorized for use in construction works, obligatorily with a steel pin protected against corrosion or made of stainless steel. Reinforced layer ATLAS STOPTER K-20, ATLAS STOPTER K-50 or ATLAS HOTER U adhesive mortar with fiberglass mesh: SSA-1363-SM 05 or AKE 145. Outer (finishing) layer ATLAS CERMIT thin-coat render(mineral or acrylic) + ATLAS CERPLAST priming mass ATLAS SILKAT thin-coat render + ATLAS SILKAT ASX priming mass ATLAS SILKON thin-coat render + ATLAS SILKON ANX priming mass A complete set of materials for thermal insulation installation - to be used in repairs of the main building insulation, provides full and checked compatibility of all components, which is particularly important during the subsequent years of system operation. Enables achievement of the external wall thermal insulation required by building regulations - reduces heat loss and heating costs. Enables effective repairs of the thermal insulation systems - damaged due to design and installation errors, or as a result of the natural ageing and weathering processes. Enables to install the thermal insulation of thickness up to 30 cm - this applies to the total thickness of the old and the new thermal insulation. Classified as fire retardant - in accordance with applicable regulations. ATLAS RENOTER System has been granted the Technical Approval ITB No. AT-15-8477/2010. Domestic Declaration of Conformity No. 113 of 01.01.2011. FPC Certificate No. ITB-0456/Z. General system characteristic Requirements for execution of thermal insulation works The thermal insulation technology is based on installation of an extra outer thermal insulation layer onto the existing external wall insulation. This system consists of polystyrene as thermal insulation material, reinforced layer made of adhesive and reinforcing mesh, a layer of render and decorative paint coat (optionally). Polystyrene boards are attached with the use of adhesive mortar and mechanical fixings. The use of mechanical fixings is obligatory regardless of the height of the building. ATLAS RENOTER is a system that is fastened mechanically, i.e. loads are completely transmitted by mechanical connections, and the adhesive provides a flat adherence of the system to the substrate (acts as an assembly). The construction material layer of the outer wall of the building should always be treated as the substrate, not the existing layer of thermal insulation. Fixings should therefore go through all the layers of the existing insulation. This fact should be taken into account during designing and selection of mechanical fixings. Work conditions Carry out the work in dry weather, at the substrate and ambient temperature not lower than +5°C and not higher than +30°C. The only exception is the ATLAS STOPTER K-20 adhesive, which can also be used at 0°C, assuming that after 8 hours from the work completion the temperature does not drop below -5°C. www.atlas.com.pl ATLAS ARKOL E façade paint ATLAS ARKOL S façade paint + ARKOL SX primer ATLAS ARKOL N façade paint + ARKOL NX primer ATLAS FASTEL NOVA façade paint + ARKOL NX primer Technical requirements E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) Substrate preparation Reveals corners strengthening General instructions In all corners of window and door reveals, additional reinforcing mesh strips (rectangles with dimensions of 20 x 35 cm) embedded in the adhesive mortar ATLAS STOPTER K-20, ATLAS STOPTER K-50 or ATLAS HOTER U should be installed. The strips should be applied diagonally, at a 45° angle in relation to the line set by the edges of the reveals. Before the work commencement is necessary to carry out an inspection at the site of the system installation, cataloguing and providing full evaluation of the technical condition of the existing insulation. The cataloguing should consist in completing the available documentation (design, construction log, etc.), determining the type of wall partition and construction material used, the type and thickness of the insulation used, verification of the mechanical fixings use and checking the type of the surface layer and whether it was painted. It is recommended to carry out excavations, the number depending the size of the building, preferably on each wall of the building. Assessment of technical condition of the old thermal insulation should determine the current condition of the individual layers of the system, their adhesion to the substrate and interlayer one and should allow to establish and identify the type and extent of damage. Basing on the information gathered, appropriate for the situation, technology of thermal insulation work and the method of preparation of the existing thermal insulation should be chosen. Caution! For buildings with three-layered reinforced concrete walls, making an additional layer of insulation should be preceded by a service inspection in accordance with the recommendations in this regard, including ITB Instruction No. 360/99, 371/02, 374/02 and 447/2009. For the time of works remove any elements hindering tight adhesion of the thermal insulation boards and the finishing coat application. An additional layer of insulation will increase the thickness of the walls, and therefore it will cause the need to increase the reach of flashings, downspouts anchors, etc. For the time of works the windows and doors should be protected against the dirt by a plastic film. Thermal insulation application Polystyrene boards application In the case of even substrates, the mortar can be applied with the use of a notched trowel (with notch size 12 mm)– the adhesive is applied then directly onto the board and not onto the substrate. In the case of less smooth surfaces the adhesive should be spread on the board surface using the “strip - point” method. It consists in the application of continuous circumferential bead (at least 3 cm wide) at the edge of the board and 6÷8 patches of 8÷12 cm in diameter evenly distributed on the whole surface. Peripheral bead is placed at a distance from the edge, so that when pressed to the wall the mortar is not squeezed out of the contour and side edges. The adhesive mortar applied on board should cover at least 40% of its surface (after pressing down to the substrate at least 60%).Thermal insulation application should commence from the building corners. The first row of the boards is fixed on the starter tracks, the subsequent rows positioned so that the vertical board joints are staggered and overlapped at the building corners. It is unacceptable to fit the edges of the insulation boards with the edges of the reveals on the façade. As the adhesive is applied, the board should be placed onto the substrate, moved tightly to the already fixed boards and pressed – be sure to control the plane with a level. If the adhesive is squeezed out the board contour, it should be removed. If there are gaps between adjoining boards, we recommend filling them with cut stripes of polystyrene or low expansion polyurethane foam. Insulation boards sanding The surface of insulating boards applied to the substrate should be even, so when the mortar sets (after ca. 24 h), the boards should be sanded with the use of sanding boards or floats covered with coarse sanding paper. It eliminates any board edges slips. In the case of polystyrene boards installed 3 months earlier or more sanding and removal of any surface tarnish is mandatory. Base coat (reinforced layer) application The base coat can be installed once the adhesive mortar used for board application has sufficiently set and any necessary additional mechanical fixings have been installed (after three days on average). Apply the adhesive mortar onto the surface of the installed insulation boards and spread it using a notched trowel (notch size 10 - 12 mm). The adhesive should be spread in vertical strips of width slightly greater than the fiberglass mesh width. Then, starting from the top, subsequent strips of mesh are applied and in a few points along the entire length embedded in the prepared adhesive layer. The adjoining strips of mesh should overlap horizontally and vertically by a minimum coverage of 10 cm (15 cm in quoins). Mesh overlaps should not coincide with the joints between the insulation boards. When applied, the mesh should be carefully embed in the adhesive. In order to embed the mesh evenly, the adhesive is squeezed with the slightly inclined trowel led from the top, in the direction from the center to the mesh strip side. The correctly embedded mesh should be completely not visible under adhesive coat and should not be in direct contact with the polystyrene boards surface. Façade finishing The outer layer of the system may be a thin-coat render solely or a thin-coat render coated with a façade paint. The choice of the render should be carried out including the insulated walls heat - and - moisture calculation as well as the conditions of thermal insulation system usage. The execution of the finishing layer can start after ca. 3 days from the reinforced layer installation. The base coat surface should be primed with a priming mass adequate for the render type - for mineral and acrylic renders – ATLAS CERPLAST, for silicate renders – ATLAS SILKAT ASX, for silicone renders – ATLAS SILKON ANX. If the reinforced layer was installed with the use of ATLAS STOPTER K-50 adhesive mortar, no priming mass is needed. You can use thin - coat render: ATLAS CERMIT (mineral or acrylic), ATLAS SILKAT (silicate) or ATLAS SILKON (silicone). The renders surface can be painted optionally with ATLAS ARKOL E, ATLAS ARKOL S, ATLAS ARKOL N or ATLAS FASTEL NOVA façade paints. All works must be performed in accordance with the technology described in the technical data sheets of the individual products. The above information constitutes basic guidelines for the application of the product and does not release the user from the obligation of carrying out works according to engineering principles and OHS regulations. At the time of publication of this product data sheet all previous ones become void. Date of update: 2013-11-12 Mechanical fixing Fixing with mechanical anchors (with pins of steel protected against corrosion or of stainless steel)can commence after ca. 24 hours from the boards application. We recommend using screwed - in fixings, in the amount of minimum 4 - 6 pieces per m2 of the façade. Fixings length should be the sum of the total thickness of the old thermal insulation and new insulation material designed, whereas the anchoring depth in the mineral substrate should be clearly defined in the technical design of thermal insulation. Note! As the bearing substrate the layer of construction material of the outer wall of the building should be considered. Detailed information about the number of fixings, their distribution, length and depth of anchorage should be specified in the thermal insulation technical design and should meet the requirements of the fixings manufacturers. Installation of additional elements In order to increase the system resistance against mechanical damage, to allow free drainage and execution of expansion joints - the finishing profiles should be installed on the fixed insulation layer. These profiles are installed at every specific locations of the façade (i.e. corners, reveals, sills, etc.). They can also be simultaneously installed during the base coat mesh embedding. For profiles embedding, use adhesive mortars ATLAS STOPTER K-20, ATLAS STOPTER K-50 or ATLAS HOTER U. The layout of the existing thermal insulation expansion joints should also be preserved by applying appropriate expansion joint profiles with mesh. Product Data Sheets Catalogue 195 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) ATLAS CERAMIK SYSTEM -external wall insulation with ceramic cladding 1. 2. 3. 4. Use For installation of the external wall insulation of buildings - it may be used on the newly constructed or under thermal modernization, both on rendered/ plastered façades and rough walls made of bricks and blocks (ceramic, cement-lime, stone, of aerated concrete and concrete - monolithic or precast). Recommended for façades exposed to increased operational load and dirt for example on plinths, foundations and for insulation of public access, commercial buildings, etc. Properties A complete set of materials for thermal insulation installation - provides full and checked compatibility of all components, which is particularly important during the subsequent years of system operation. Enables achievement of the external wall thermal insulation required by building regulations - reduces heat loss and heating costs. Increases durability of external walls – protects them against direct weathering. Very durable material solution – the wear of ceramic cladding is slower than in case of insulation with rendering coat, it also provides high system resistance to damages. Resistance to biological corrosion – the cladding is easy to keep clean and is less exposed to possible development of fungi, algae and lichens. General - purpose – enables the use on a single façade both expanded polystyrene (EPS) and extruded polystyrene (XPS) boards. The system is fire retardant - it relates to the thermal insulation systems with EPS and XPS boards of thickness up to 250 mm. General system characteristic ATLAS CERAMIK system is an external thermal insulation composite system (ETICS). The thermal insulation technology consists in the application of EPS or XPS boards onto the outer side of the wall, next the installation of a base coat with reinforcing fiberglass mesh, and further application of the finishing layer made of ceramic tiles fixed to base coat with the use of an adhesive and finished with a grout. Due to the type of the finishing layer, the insulation boards must be mechanically fixed through the first layer of mesh. System elements According to the current regulations the thermal insulation system is considered in its entirety as one construction product, therefore it must be applied with the layers arrangement and with materials which are described in its technical approval. It is unacceptable to use the so-called compilations or to use products from other systems or from other manufacturers, which are not covered by the technical approval. The products used in ATLAS CERAMIK system, according to the ITB Technical Approval No. AT-15-8592/2011, are listed in the table below. Adhesives for fixing thermal insulation: ATLAS STOPTER K-20, ATLAS HOTER U adhesives Materials for thermal insulation Polystyrene boards (EPS) of the minimum properties meeting the code: EPS–EN 13163–T1–L2–W2–S5–P5–BS75–DS(N)2–DS(70,-)2–TR100 Caution. Boards of tensile strength TR80 may be used if are covered by the ITB Technical and Quality Recommendation or volitional Certificate issued by an approved assessment unit. extruded polystyrene (XPS) boards of codes: XPS-EN 13164-XPS-EN13164-T1-DS(TH)-TR100 196 www.atlas.com.pl Ceramic hollow blocks Primed substrate (optionally) Adhesive for EPS boards application EPS thermal insulation boards - standard or graphite - enhanced 5. Adhesive for base coat application 6. Reinforcing mesh - 1st layer 7. Mechanical fixing – fixings for EPS and XPS 8. Reinforcing mesh - 2nd layer 9. Adhesive for base coat application 10. Adhesive for tiles 11. Façade tiles 12. Grout Mechanical fixings: Mechanical fixings authorized for use in construction works. Reinforced layer ATLAS STOPTER K-20 or ATLAS HOTER U adhesive mortar with fiberglass mesh: SSA-1363-SM 05 or AKE 145. Finishing layer ATLAS CERPLAST acrylic priming mass for renders Adhesive for fixing ceramic cladding ATLAS PLUS adhesive ATLAS PLUS WHITE adhesive ATLAS PLUS EXPRESS adhesive Ceramic cladding Façade ceramic tiles, frost-resistant, pressed or extruded , belonging to groups Bla, BIb or AI acc. to PN-EN 14411:2009 standard, with maximum thickness 15 mm and of surface mass max. 40 kg/m² Grouting of ceramic cladding ATLAS ARTIS GROUT Complementary elements Drip profile, corner profile, window profile, expansion joint profile (straight, angle), sill profile Technical requirements ATLAS CERAMIK System has been granted the Technical Approval ITB No. AT-15-8592/2011. Domestic Declaration of Conformity No. 114 of 25.03.2011. FPC Certificate No. ITB-0472/Z. Requirements for execution of thermal insulation works Work conditions Carry out the work in dry weather, at the substrate and ambient temperature not lower than +5°C and not higher than +30°C. The only exception is the ATLAS STOPTER K-20 adhesive, which can also be used at 0°C, assuming that after 8 hours from the work completion the temperature does not drop below -5°C. The façade should be on time of thermal insulation work protected and secured against precipitation, strong wind and direct sunlight - it is recommended to use fine mesh scaffolding covers. Insulation works should be carried out in dry conditions (no precipitation, relative humidity below 80%). Substrate preparation General provisions Before the work commencement, evaluate the substrate technical condition and on that basis decide on the scope and the method of surface preparation. For the time of works remove any elements hindering tight adhesion of the thermal insulation panels and the finishing coat application. An additional layer of insulation will increase the thickness of the walls, and therefore it will cause the need to increase the reach of flashings, downspouts anchors, etc. For the time of works the windows and doors should be protected against the dirt by a plastic film. E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) Requirements for the substrate The substrate should be aged, sound, stable, even, clean and dry. The absorbent substrates should be primed with ATLAS UNI-GRUNT, smooth and non-absorbent (concrete) with ATLAS CERPLAST. The substrate should be even to the extent enabling easy execution of a plane formed by the bonded insulation boards on the walls. Clean the surface from any layers which may weaken mortar adhesion, dirt, loose and dusty elements. Note! Particular attention should be paid to the proper assessment and preparation of substrate with problematic bearing capacity, e.g. finished with glass-mosaics, glazed brick, covered with paint coats, etc. If in doubt, conduct a pull - off test of adhesion (the ultimate tensile strength should be above 0.08 MPa) or apply 8÷10 cubes of EPS 10x10 cm each, in various places of the façade and tear them off after 3 days. The use of thermal insulation system for buildings with reinforced concrete sandwich walls, should always be preceded by a thorough assessment of their technical condition. This applies to the technical condition of the metal fittings (hooks, pins, rods) as well as to how they are connected and interact with the elements of the wall. Starter tracks installation The insulation should be commenced with the installation of the starter tracks. They support the first row of thermal insulation boards, facilitate to maintain the uniform level of successive layers, strengthen the bottom edge of the system, and the bottom edge drip prevents water bleeding. The boards should be installed horizontally on the plinth of the building, not lower than 30 cm above the ground level, which provides protection from the effects of rising damp and protects against dirt - mud particles brought by raindrops reflected from the ground. Instead of skirting boards, it is permitted to use strips of armour mesh or two layers of fiberglass mesh. Thermal insulation application Polystyrene boards application In the case of even substrates, the mortar can be applied with the use of a notched trowel (with notch size 12 mm)– the adhesive is applied then directly onto the board and not onto the substrate. In the case of less smooth surfaces the adhesive should be spread on the board surface using the “strip - point” method. It consists in the application of continuous circumferential bead (at least 3 cm wide) at the edge of the board and 6÷8 patches of 8÷12 cm in diameter evenly distributed on the whole surface. Peripheral bead is placed at a distance from the edge, so that when pressed to the wall the mortar is not squeezed out of the contour and side edges. The adhesive mortar applied on board should cover at least 40% of its surface (after pressing down to the substrate at least 60%).Thermal insulation application should commence from the building corners. The first row of the boards is fixed on the starter tracks, the subsequent rows positioned so that the vertical board joints are staggered and overlapped at the building corners. It is unacceptable to fit the edges of the insulation boards with the edges of the reveals on the façade. As the adhesive is applied, the board should be placed onto the substrate, moved tightly to the already fixed boards and pressed – be sure to control the plane with a level. If the adhesive is squeezed out the board contour, it should be removed. If there are gaps between adjoining boards, we recommend filling them with cut stripes of polystyrene or low expansion polyurethane foam. Insulation boards sanding The surface of insulating boards applied to the substrate should be even, so when the mortar sets (after ca. 24 h), the boards should be sanded with the use of sanding boards or floats covered with coarse sanding paper. It eliminates any board edges slips. In the case of polystyrene boards installed 3 months earlier or more sanding and removal of any surface tarnish is mandatory. Installation of additional elements In order to increase the system resistance against mechanical damage, to allow free drainage and execution of expansion joints - the finishing profiles should be installed on the fixed thermal insulation layer. These profiles are installed at every specific locations of the façade (i.e. corners, reveals, sills, etc.). They can also be simultaneously installed during the base coat mesh embedding. For profiles embedding, use adhesive mortars ATLAS STOPTER K-20 or ATLAS HOTER U. Reveals corners strengthening In all corners of window and door reveals, additional reinforcing mesh strips (rectangles with dimensions of 20 x 30 cm) embedded in the adhesive mortar ATLAS STOPTER K-20 or ATLAS HOTER U should be installed. The strips should be applied diagonally, at a 45° angle in relation to the line set by the edges of the reveals. Base coat (reinforced layer) application Because the finishing coat of ATLAS CERAMIK consists of ceramic tile cladding, it is required to apply the base coat (reinforced layer) and to install mechanical fixings in the same work phase. For application of the reinforced layer two layers of mesh embedded in ATLAS STOPTER K-20 or ATLAS HOTER U adhesives are used. Mechanical fixings are installed through the first mesh layer. The base coat can be installed after min. 3 days from the boards application. Apply the adhesive mortar onto the surface of the installed insulation boards and spread it using a notched trowel (notch size 10 - 12 mm). The adhesive should be spread in vertical strips of width slightly greater than the fiberglass mesh width. Then, starting from the top, subsequent strips of mesh are applied and in a few points along the entire length embedded in the prepared adhesive layer. The adjoining strips of mesh should overlap horizontally and vertically by a minimum coverage of 10 cm (15 cm in quoins). Mesh overlaps should not coincide with the joints between the insulation boards. When applied, the mesh should be carefully embed in the adhesive. In order to embed the mesh evenly, the adhesive is squeezed with the slightly inclined trowel led from the top, in the direction from the center to the mesh strip side. The correctly embedded mesh should be completely not visible under adhesive coat and should not be in direct contact with the polystyrene boards surface. The next step is the installation of mechanical fixings through the first layer of mesh. The fixings should be with galvanized steel pin, in an amount of min. 8 pcs per 1 m2. Detailed information about the number of fixings, their distribution, length and depth of anchorage should be specified in the thermal insulation technical design. When fixings are properly installed, their plates should be lightly pressed into the adhesive layer. Then the entire surface should be covered with the next fiberglass mesh embedded thoroughly in the mortar and smoothed with a float. Cladding application Contact layer application After ca. 3 days from reinforced layer application, the contact layer made of ATLAS CERPLAST priming mass might be made, however it is not obligatory. Ceramic cladding application The deformable cement - based adhesives of C2TE S1 type according to the PN-EN 12004:2008 standard are recommended, i.e. ATLAS PLUS, ATLAS PLUS WHITE or ATLAS PLUS EXPRESS. When applying the tiles, one should pay special attention to ensure proper adhesion of an adhesive in order to eliminate the possible cavities under the cladding, e.g. notched trowel marks. Taking these factors into account, it is recommended to use the ‘double spreading’ method, consisting in the distribution of an adhesive both onto the substrate - with a notched trowel, and on the bottom side of the tile - with the smooth side of a trowel. Only then after the tile is pressed to the substrate and slightly moved. Follow the adhesive coat thickness advised in the technical data sheets. Do not cover too large area with an adhesive at the same time, as the spread adhesive retains its binding properties for 10 - 30 minutes (depending on the substrate and ambient characteristics). The position of a tile can be adjusted delicately within 10 minutes after it is pressed. Remove the excess of the adhesive appearing in the joints after pressing the tile immediately. Grouting The grouting of the ceramic cladding should be commenced after the complete setting of adhesive, i.e. after ca 24 h from the tiles application. It is recommended to use ATLAS ARTIS GROUT. Due to cladding operation conditions the width of the joints should be within the range from 6 mm to 20 mm (the width should be adequate to the size of the tiles used) and the percentage of the joints on the entire surface should not be less than 6%. In order to avoid various colour shades, it is recommended to use grout of the same manufacturing date and the same batch number (shown on the packaging). Conduct the grouting of the same plane with no breaks and on adjoining scaffolding levels, using the compound of the same manufacturing date and batch number. Keep equal water/dry mix proportions. The cladding should be protected against precipitation (mesh covers on scaffoldings) within min. 3 days from its application; it refers to the temperature of +20 °C and relative humidity of 60%; in less positive conditions the slower setting of the used materials should be considered. Expansion joints of the ceramic cladding The construction and plane expansion joints of the insulation as well as the angle ones should be repeated on the surface of the ceramic cladding. The surface should be divided into smaller sections of max. 9 m2. In case of installation of the ATLAS CERAMIK thermal insulation system on large and high façades it is recommended to apply additional horizontal consoles or stabilizing brackets. The above information constitutes basic guidelines for the application of the product and does not release the user from the obligation of carrying out works according to engineering principles and OHS regulations. At the time of publication of this product data sheet all previous ones become void. Date of update: 2013-11-12 Product Data Sheets Catalogue 197 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) MECHANICAL FIXINGS Use Mechanical fixings installation Additional fixing for the thermal insulation – protecting the thermal insulation system against forces connected with wind loads (suction). Installation of mechanical fixings can start not earlier than after ca. 24 hours from the insulation material application. First drill a hole of the depth recommended by the manufacturer for the given fixing length. Then, remove the dust from the hole and insert the fixing. Next, hammer in (in case of hammered in fixings) or screw in (screwed in fixings) the pin. Damaging the structure of the thermal insulation material with the fixing is not acceptable. The head of the fixing should be level with the surface of the thermal insulation material. Properties Fixings with plastic pin – recommended for fixing polystyrene boards. Fixings with metal pin – recommended for fixing both polystyrene boards and mineral wool panels. They don’t cause the occurrence of thermal bridging in the place of passage of the fixing through the thermal insulation. Technical requirements Important technical information For TERMO fixing: AT-15-7920/2009 Domestic Declaration of Conformity 02.007/2009 of 28.10.2009. For TFIX-8M fixing: ETA-07/0336, Declaration of Conformity EC No. EC/02.004/2008. For KI-10N fixing: ETA-07/0221, Declaration of Conformity EC No. EC/02.002/2007. • The application of fixings is not required for wall up to 12 m high with appropriately reliable and strong substrate (concerns systems with polystyrene). • In case of doubt concerning the bearing capacity of the substrate, it is recommended to carry out the pull - off test. • It is recommended that the number of fixings be not less than 4 pieces for each 1 m2. Increased number of fixings is recommended in the corner zones of the buildings. • Detailed data concerning the number, the type and the length of pins and their arrangement should be included in the technical design of the thermal insulation. • The depth of the fixing anchoring in the structural layer of the wall depends on the substrate material and should be in concordance with the requirements of the fixings manufacturer. Types of substrates: type A – concrete, type B – clay brick, sand - lime clay brick, type C – sand - lime and clay hollow brick, type D – lightweight concrete blocks, lightweight concrete aggregate bricks, type E - aerated concrete. Symbol TERMO fixing for EPS and XPS, with plastic pin, hammered in, diameter 10 mm TFIX-8M fixing for polystyrene and mineral wool, with metal pin, hammered in, diameter 8 mm, for A, B and C type substrates 198 Anchoring depth in A and B type substrates [mm] A - TERMO-090 90 25 A - TERMO-120 120 A - TERMO-140 140 A - TERMO-160 Insulation thickness on A and B type substrates [mm] Anchoring depth in C, D and E type substrates [mm] Insulation thickness on C, D and E type substrates [mm] Number of pieces in one packaging 50 50 30 250 25 80 50 60 250 25 100 50 80 250 160 25 120 50 100 250 A - TERMO-180 180 25 140 50 120 250 A - TERMO-200 200 25 160 50 140 250 Symbol KI-10N fixing for polystyrene and mineral wool, with metal pin, long expansion zone, hammered in, diameter 10 mm, for B, C, D and E type substrates Available fixing length [mm] The above information constitutes basic guidelines for the application of the product and does not release the user from the obligation of carrying out works according to engineering principles and OHS regulations. At the time of publication of this product data sheet all previous ones become void. Date of update: 2009-09-14 Available fixing length [mm] Anchoring depth [mm] Min. insulation thickness [mm] Number of pieces in one packaging A - KI-120-N 120 60 50 250 A - KI-140-N 140 60 70 250 A - KI-160-N 160 60 90 250 A - KI-180-N 180 60 110 250 A - KI-200-N 200 60 130 250 A - KI-220-N 220 60 150 250 A - KI-260-N 260 60 190 200 A - KI-300-N 300 60 210 200 A - TFIX-8M-095 95 25 40 200 A - TFIX-8M-115 115 25 80 200 A - TFIX-8M-135 135 25 100 200 A - TFIX-8M-155 155 25 120 200 A - TFIX-8M-175 175 25 140 200 A - TFIX-8M-195 195 25 160 200 A - TFIX-8M-215 215 25 180 100 A - TFIX-8M-235 235 25 200 100 A - TFIX-8M-255 255 25 220 100 A - TFIX-8M-275 275 25 240 100 A - TFIX-8M-295 295 25 260 100 www.atlas.com.pl Additional accessories Symbol Number of pieces in one packaging KWL140 Pressing collar for fixing lamella mineral wool panels. Collar diameter 140 mm. For application with KI-10N fixing. 200 KFS (cutter) Tool for cutting holes in thermal insulation 1 KES (plug) Plug to close the holes in thermal insulation 250 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) REINFORCING FIBERGLASS MESHES • resistant to alkali • durable • flexible Use Base coat installation For the reinforced layer (base coat) installation – to be embedded in the adhesive layer during installation of thermal insulation systems both with polystyrene and mineral wool. Element of external wall insulation systems - covered with Domestic Approvals (AT) and European Technical Approvals (ETA). The base coat (reinforced layer) installation can commence after the adhesive used for fixing the thermal insulation boards has properly set and additional mechanical fixings have been installed (usually after three days). Apply the adhesive evenly over the whole surface of thermal insulation and embed consecutive strips of mesh into it. Put the mesh strips vertically – from top to bottom. It is most convenient to press the mesh into the adhesive in a few spots only and then embed the whole strip using a notched trowel. Properly set mesh should be embedded in the adhesive layer not deeper than a half of the layer thickness and therefore be completely invisible under the surface of the adhesive and should not contact the surface of the boards. The base coat should be ca. 3 mm thick and be a continuous layer, i.e. consecutive strips should be applied with at least 10 cm overlap both vertically and horizontally and 15 cm overlap at the corners. The overlaps of the mesh cannot correspond with the joints between polystyrene boards. After embedding the mesh, carefully float the adhesive layer with a smooth steel float. Properties Durable – consists of interlacing weft and warp yarns creating strong gauze weave, providing the mesh with high mechanical resistance and preventing the yarns from slipping out of position. Flexible – ensures compensation of thermal and mechanical deformations the thermal insulation system is subject to during operation, prevents formation of cracks in the façade layers and enables obtaining of stable substrate for the rendering coat. Resistant to alkali – the yarns are protected against aggressive alkali present in adhesive mortars, by immersion in acrylic bath. Technical data The mesh is manufactured of fiber glass, protected against aggressive alkali present in adhesive mortars, by immersion in acrylic bath. Important technical information • The properties of the mesh are fully utilized when it is applied together with the other elements of the system in accordance to its execution technology. • The mesh has to be stored in vertical position, in dry, airy rooms, away from heating devices. Note: The mesh must not be exposed to direct sunshine and atmospheric factors. Colour Density [g/m ] 2 Weave type Width [m] Mesh size [mm] Packaging Technical requirements The above information constitutes basic guidelines for the application of the product and does not release the user from the obligation of carrying out works according to engineering principles and OHS regulations. At the time of publication of this product data sheet all previous ones become void. Date of update: 2014-05-21 AKE 145 SSA-1363 SM 0.5 yellow with print ATLAS yellow 145 (-0/+10%) 155 ± 5% gauze gauze 1.0 1.0 4.0x4.5 3.5x3.5 roll of 50 rm roll of 50 rm AT-15-7373/2013 AT-15-8489/2010 The meshes are the elements of external thermal wall insulation systems according to European requirements: System name Approval No. EC Conformity Certificate ATLAS ETA 06/0081 1488-CPD-0021 ATLAS XPS ETA 07/0316 1488-CPD-0075 ATLAS ROKER ETA 06/0173 1488-CPD-0036 The meshes are the elements of external thermal wall insulation systems according to European requirements: System name Approval No. FPC Certifificate No. ATLAS ETICS AT-15-9090/2014 FPC No. ITB-0562/Z ATLAS ROKER G AT-15-7314/2011 FPC No. ITB-0222/Z ATLAS ROKER AT-15-2930/2012 FPC No. ITB-0436/Z ATLAS CERAMIK AT-15-8592/2011 FPC No. ITB-0472/Z ATLAS RENOTER AT-15-8477/2010 FPC No. ITB-0456/Z Product Data Sheets Catalogue 199 E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) FAÇADE FINISHING PROFILES • for protection of the corners of the building • for expansion joints for the thermal insulation system • resistant to weather conditions • resistant to mechanical damage • easy and fast assembly Use Technical data Protect and provide expansion joints for specific areas of the insulated façade – they are used in all ATLAS thermal insulation systems. They reinforce the corners of the insulated façades and all kinds of edges of concrete and ferroconcrete elements, e.g. repaired with ATLAS BETONER system. Provide effective runoff of precipitation water – from the surface of the façade and other construction elements. Constitute expansion joints – they separate elements of façade differing in the load bearing or properties, e.g. thermal expansion. Enable transferring the construction expansion joints of the building onto the thermal insulation system layers. Even the edges and give them aesthetic appearance. The finishing profiles are made of high quality PVC granulate (without cadmium). Properties Long time durability – they are resistant to weather conditions, aggressive effects of polluted environment and other construction materials, ageing and UV rays. Resistant to mechanical damage during transport, storage and operation – owing to the application of hard and highly flexible PVC profile. Thermal expansion of the profiles and thermal insulation materials is similar – eliminates the risk of damage to the render. Easy and fast assembly – allow to save about 15% of time at reveals treatment. Equipped with reinforcement mesh – 10 cm wide, made of fiber glass, additionally reinforcing the area along the edges; owing to acrylic bathing, it is protected against the influence of alkaline environment. Joints of the profile and the mesh are executed in high frequency welding technology – which makes them much more durable and resistant than methods used so far, e.g. gluing. The finishing profile are manufactured in white (RAL 9010) colour and the elements of the profile made in co-extrusion technology are grey. The profiles can be painted with acrylic or silicone façade paints – e.g. ATLAS ARKOL E or ATLAS ARKOL N. 200 www.atlas.com.pl Technical requirements The finishing profiles constitute supplementing elements of the following thermal insulation systems: System name Technical Approval No. Certificate No. ATLAS ETA 06/0081 EC No. 1488-CPD-0021 ATLAS XPS ETA 07/0316 EC No. 1488-CPD-0075 ATLAS ROKER ETA 06/017 EC No. 1488-CPD-0036 ATLAS ROKER AT-15-2930/2012 FPC-ITB-0436/Z ATLAS ETICS AT-15-9090/2014 FPC-ITB-0562/Z ATLAS ROKER G AT-15-7314/2011 FPC-ITB-0222/Z ATLAS RENOTER AT-15-8477/2010 FPC-ITB-0456/Z ATLAS CERAMIK AT-15-8592/2011 FPC-ITB-0472/Z E X T E R N A L T H E R MA L I N S U L AT I O N CO M P O S I T E S YS T E M S ( E T I C S ) General principles of finishing profiles application The finishing profiles are applied after the thermal insulation layer has been fixed, before or during the installation of the reinforced layer of the system. Apply adhesive used for mesh embedding, e.g. ATLAS STOPTER K-20, ATLAS STOPTER K-50, ATLAS HOTER U or ATLAS ROKER W-20 along the edge on which the profile is to be installed. Put the profile against the edge, embedding its reinforcement mesh into the freshly applied mortar so that the mesh is not visible. When the adhesive dries, the execution of the reinforced layer of the system on the whole façade surface can start. The reinforcement mesh of the system should completely cover the finishing profile mesh. Cut the finishing profiles to the desired size with shears for PVC strips. Join perpendicular sections by cutting the ends at the angle less than 45° and filling in the space with a silicone filler. PROTECTIVE PROFILES Drip profile Drip profiles are installed on horizontal edges of window and door reveals and other façade recesses. They are also applied on bottom edges of balcony slabs; the mesh is embedded in the finishing layer e.g. ATLAS ENDER in ATLAS BETONER repair system. They are also fixed on the bottom edge of the thermal insulation if the skirting board cannot be used, e.g. thermal insulation panels are thicker than the largest available board size. First of all, they provide correct runoff of water flowing down the vertical façade surfaces, eliminating this way the risk of stains and render damage. The profiles also protect the edge from mechanical damage. Corner profile Corner profiles are fixed on various edges exposed to mechanical damage during usage of the façade, like door and window reveals, corners, etc. The flexibility of the materials prevents mechanical impact from causing permanent damage to the corner. EXPANISON JOINT PROFILES Window profile Window profiles are fixed between window or door frame woodwork and finishing layers of the thermal insulation system. They are available in two widths: 6 and 9 mm. The window profile has a polyurethane tape that eliminates render cracks and damages resulting from differences in thermal expansion of the reveals and renders. Moreover, it facilitates the application and control of render thickness and protects woodwork from dirt during works – quick and easy fixing of the protective foil to the profile “flap” and then quick removal by breaking off the flap with the used foil after completion of the works. The window profile protects the space between the casing and render against humidity, dirt, microorganisms and insects and improves thermal, sound and damp insulation there. It can be used for all types of joinery (wood, PVC, aluminum). Select the type of profile (6 or 9 mm) appropriately to the assumed thickness of the reinforced layer and render. Mark the planned contact line with the render coat on the casing and then remove the white protective strip from the polyurethane tape and adhere the profile to the casing so that its edge corresponds with the line marked on the casing. The profile is always fixed with the “flap” towards the inside of the reveal. Remove the yellow protective strip and attach appropriately cut foil in its place to protect the joinery. Fill the inside of the profile completely with the reinforced layer and thin-coat render. Break off the flap with the foil after work completion. Expansion joint profile The expansion joint profile is fixed between thermal insulation panels in places where construction expansion joints run or if the thermal insulation layer itself needs to be divided. It is available in two versions: straight – expansion joint in the façade plane and angle - expansion joint in the internal corner. The profile can be used in the expansion gap of 10 to 30 mm width. The profile consists of two parts: hard (PVC-U) – contacting thermal insulation panels and soft (PVC-P) – filling the space between them. The soft part is made in the co-extrusion process and therefore, its joint with the hard part ensures very high durability and resistance. The application of the expansion joint profile ensures permanent tightness (in regard to humidity, dirt, microorganisms and insects) and proper correct cooperation of adjacent parts of the building and thermal layer arrangement. The precondition to the tightness of the whole expansion joint is the correct vertical arrangement of two adjacent profiles: the upper one and the lower one. They are joined by means of a special assembly section attached to each profile. It is made of soft PVC-P and has adhesive layers (protected with a protective tape). Attach the assembly section to the lower end of the upper profile (on the bottom side of its soft part) and to the upper end of the lower profile (on the top side of the soft part). It is also possible join profiles with overlaps – the upper profile needs to overlap the lower one. To do that, cut off 10 mm sections from the hard part of the profile so that the overlap is made only of the soft parts. To obtain perfectly straight run of combined profiles, apply the attached plugs pressing them from the bottom into the sticking out parts, “tips”, of the upper profile and then the lower profile during assembly. Note. Before the application of the expansion joint profile, fill the joint with thermo-insulating material, e.g. polyethylene or polyurethane backer. After the application of the profile, protect the joint against soiling during the execution of the reinforced layer or the render. For that purpose, put foamed polystyrene strips into the joint and remove them after the rendering is completed. Sill profile The profile is fixed under the sill, ensuring appropriate expansion joints between the sill and thermal insulation system layers. The application of the sill profile ensures permanent tightness (to humidity, dirt, microorganisms and insects) and stiffens the sill (owing to the appropriately shaped upper surface of the profile). The sill profile has a polyethylene tape that eliminates render cracks and damages resulting from different thermal expansion of materials. Moreover, it facilitates the application and control of render thickness. When fixing the profile, pay special attention to cutting of thermal insulation boards exactly to reveal clearance and that the profile is fixed horizontally. Directly before profile fixing, remove the protective tape from the polyethylene foam strip. Important additional information • It is not recommended to use agents containing chlorine for cleaning the profiles. • Fix profiles in temperature above 5°C. At temperatures from 5°C to 15°C, expect lower flexibility of the profile. • During storage and transport, protect the profiles against deformation – horizontal position, dry, heated room (temperature above 5°C). Shelf life in conditions as specified is 18 months from the production date shown on the packaging. Packaging Profile length [m] Quantity in one packaging [rm / pcs] drip profile 2.5 62.5 / 25 corner profile 2.5 125.0 / 50 window profile 6 mm 2.4 48.0 / 20 window profile 9 mm 2.4 48.0 / 20 straight expansion joint profile 2.0 50.0 / 25 corner expansion joint profile 2.0 50.0 / 25 sill profile 2.0 50.0 / 25 The above information constitutes basic guidelines for the application of the product and does not release the user from the obligation of carrying out works according to engineering principles and OHS regulations. At the time of publication of this product data sheet all previous ones become void. Date of update: 2014-05-21 Product Data Sheets Catalogue 201