Cooling Unit – Cooler installation and Maintenance instructions

advertisement
GB.COOLER.INST.060501
Cooling Unit – Cooler
Installation and Maintenance Instructions
Sizes 14-60
Sizes 14-18
Sizes 24-60
GB.COOLER.INST.060501
Contents
1.Overview
1.1.
General
1.2
Operating Principle
1.2.1 Cooler 14 and 18 1.2.2 Cooler 24, 34, 48 and 60
2
Safety Precautions
2.1
Safety switch/main switch
2.2
Hazards
2.3
Electrical equipment
2.4
User qualification
2.5
Decals
3
3
4
4
5
6
6
6
6
6
6
3Installation
3.1
Unloading/site transport
3.1.1 Transport using a forklift truck
3.1.2 Lifting using a crane
3.2
Mounting
3.2.1 Fitting handles on Unit
3.3
Installation Principle
3.3.1 Installation – Cooler, size 14 3.3.2 Installation – Cooler, size 18
3.3.3 Installation – Cooler, size 24-60
7
7
7
7
7
7
8
9
9
9
4Electrical Wiring
4.1
Wiring to mains power
4.1.1 Cooler – size 14
4.1.2 Cooler – size 18
4.1.3 Cooler – size 24 - 34
4.1.4 Cooler – size 48 - 60
4.2
Other electrical connections 4.2.1 GOLD, Verson B 4.2.2 Other types of air handling unit
10
10
10
10
10
10
10
10
11
5
Ferrit Block, 019 210
12
6
Communication Cable, 019 007
13
6
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.8.1
6.8.2
Cooling Connections
Location
Draining the cooling coil
Liquid connections
Venting nipples
Insulating the cooling agent circuits
Connection to the cooling unit
Safety drain Filling with water/glycol mixture
Filling
Venting the system
13
13
13
13
13
13
13
13
13
14
14
7
7.1
7.1.1
7.1.2
7.1.3
Commissioning
Preparations
Before starting for first time
Starting up
To correct the phase sequence
15
15
15
15
15
www.swegon.se
8
8.1
8.1.2
8.2
8.3
Programming and Managing the Menus
Hand-held micro terminal
Display and buttons
Menu button captions and symbols
Menu groups and levels
16
16
16
16
16
9
9.1
9.2
9.3
9.4
9.5
Menus
Main menu
Information menus
Settings menus
Test menus
Alarm menus
17
17
17
18
19
20
10
10.1
10.2
10.3
10.4
10.5
Alarms
General
Resetting the alarms
Settings
Alarm conditions
Alarm priorities
20
20
20
21
21
22
11
11.1
11.2
11.3
11.4
11.5
11.6
Maintenance
Cleaning
Changing the water/glycol mixture
Handling the refrigerant
Charging with refrigerant Annual inspection
Service
23
23
23
23
23
24
24
12
12.1
12.1.1
12.1.2
12.2
12.2.1
Cooling Coil and Cooling Agent Cooler
Instructions for BASIC
BCKO Cooling agent cooler, 006-014
BCKA Cooling coil, 004-014
Instructions for the GOLD, sizes 11-32
Installing the TBKA, TBKC cooling coil
24
24
24
25
26
26
13
13.1
Connection to Ducting
Type of end connection
29
29
14Electrical Data
14.1
Cooling unit
14.2 Power supply
29
29
29
15General Technical Data 30
16
Mechanical Design
16.1
Design 16.1.1 Dimensions and weights
31
31
31
17Other Particulars
32
18Enviromental Compatibility Declaration
18.1
Scrapping
32
32
19
33
Compliance Declaration
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
1.
Overview
1.1.
General
Cooling Unit Cooler
The Cooler is a complete one-piece cooling unit for comfort
cooling in air handling systems. All the refrigeration and
electrical components are interconnected and housed in one
common casing. The units are test run prior to delivery.
The coils are designed for installation in the ducting. The
arrangement of piping between the cooling unit and the
coils and the electrical wiring of the cooling unit is carried
out at the building site.
The Cooler can be used together with an air handling unit.
The capacities of the six sizes are however matched to the
size 08-60 GOLD air handling system and the size 004-014
Basic air handling units.
Complete indirect system (sizes 24, 34, 48 and 60)
The size 24-60 Coolers have a complete indirect system.
Heat/cooling energy is transferred across a heat exchanger from the refrigerant to the circulating water mixed with
glycol. Both the brine circuit and the cooling agent circuit
must be filled with a mixture of water and 30% ethylene
glycol after the unit has been installed.
Compressors
Sizes 14, 18, 24 and 34 each have two-piston compressors. Sizes 48 and 60 each have two compressors as well,
but they are of Scroll-type.
Partially indirect system (sizes 14 and 18)
The size 14 and 18 Coolers have a partially indirect system.
On the warm side, a coil (condenser) is used for directevaporating refrigerant, while on the cold side, there is a
heat exchanger, where energy is transferred to the water
mixed with glycol (brine) circulated to the cooling coil in
the supply air duct. The circuits must be filled with a mixture of water and 30% ethylene glycol after the unit has
been installed.
The condenser coil is integrated into the cooling unit fitted
in the exhaust air duct.
Fig. 2
Refrigerant
Cooler has double refrigerant circuits which are separate from one another. The refrigerants used are of type
R407C and R134A in each circuit respectively, each with
its own compressor. On delivery, the refrigerant circuits
are charged. These refrigerants do not have any known
impact on the ozone layer and there are no known restrictions for their use at this present time.
Refrigerant volume
See section 14. General Technical Data.
Reporting obligation
The user is required to submit periodic reports to the local
inspectorate only if the total charge volume exceeds 10
kg.
Annual inspections
Annual inspections by an accredited inspectorate are
required if the volume of refrigerant in the one-piece unit
exceeds 3 kg. This is applicable to the size 24, 34, 48 and
60 Coolers only.
Fig. 1
Specifications are subject to alteration without notice.
Quality Management System to ISO 9001 and
Environmental Management System to ISO 14001
Swegon maintains documented and certificated Quality
Management and Environmental Management Systems
that meet the provisions of ISO 9001 and ISO 14001
respectively.
www.swegon.se
GB.COOLER.INST.060501
1.2
Operating Principle
1.2.1
Size 14 and 18 Coolers
HT
E1
BT2 RP2:2
M2
SS
RP2:1
VVX2
EV2
Cooling coil
G1
BT4
SV EK
BT3
Condenser
coil
EV1
VVX1
M1
BT1 RP1:2
RP1:1
Fig. 3
BT1
Hot gas thermostat R134A
BT2
Hot gas thermostat R407C
BT3
Brine temperature sensor
BT4
Extract air temperature sensor
RP1:2
High pressure switch R134A
RP2:2
High pressure switch R407C
RP1:1
Low pressure switch R134A
RP2:1
Low pressure switch R407C
G1
Brine pump
M1
Compressor R134A
M2
Compressor R407C
VVX1
Evaporator
VVX2
Evaporator
SV
Safety valve
EK
Expansion vessel
E1
Electrical cubicle with safety switch, power section, control card
SS
Start and control signals
EV1
Expansion valve 1
EV2
Expansion valve 2
HT
Hand terminal
www.swegon.se
Operation
There are two refrigerant circuits in the cooling unit The
circuits are separate from one another and each contains a
different type of refrigerant.
Each circuit is equipped with its own heat exchanger on
the cold side. On the warm side, both circuits are arranged
through a condenser coil.
The brine (water/ethylene glycol) passes the heat exchanger of both refrigerant circuits.
The refrigerant in gas form is compressed by each compressor and then passes to the condenser coil, where it is
chilled by the air flowing through the coil, and condenses
to liquid form.
A reduction in pressure occurs in expansion valve EV. From
the expansion valve the refrigerant advances to evaporator VVX where the refrigerant vaporises and absorbs heat
from the adjacent medium, i.e. the brine. This chills the
brine. Gas leaves the evaporator and flows back to the
compressor.
Water pump G1 pumps the brine (water/ethylene glycol)
in a circuit from evaporators VVX1 and VVX2, where it is
chilled by the refrigerant and advances to the cooling coil,
which in turn cools the supply air flowing to the air handling unit. The refrigerants are never in physical contact
with the brine. Heat and cooling energy are transferred
across the heat exchangers in the evaporator and condenser.
Control
In a response to an ON/OFF control signal, the controller
switches in pump G1 and compressor M1. The cooling
capacity is controlled by switching in one or two compressors. On increasing cooling load, the controller switches in
compressor M2 and at the same time switches out compressor M1. If even more cooling is required, compressor
M1 is switched in to operate together with compressor
M2.
If the temperature of the outgoing brine becomes too
low, one of the compressors is switched out. When this
condition subsides, it is restarted automatically. Should the
pressure become too low, the low pressure switch will trip.
The equivalent will occur on the warm side. If the temperature of the exhaust air becomes too high, one of the
compressors is switched out. If the pressure still rises, the
high pressure switch will trip.
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
1.2.2
Size 24, 34, 48 and 60 Coolers
HT
E1
BT2 RP2:2
M2
VVX2
Cooling agent
cooler
SV EK
VVX3
EV2
BT4
SS
RP2:1
Cooling coil
G1
BT3
G2
SV EK
EV1
VVX1
BT1 RP1:2
VVX4
M1
RP1:1
Fig. 4
BT1
Hot gas thermostat R134A
BT2
Hot gas thermostat R407C
BT3
Brine temperature
BT4
Cooling agent temperature
RP1:2
High pressure switch R134A
RP2:2
High pressure switch R407C
RP1:1
Low pressure switch R134A
RP2:1
Low pressure switch R407C
G1
Brine pump
G2
Heating medium pump
M1
Compressor R134A
M2
Compressor R407C
VVX1
Condenser
VVX2
Condenser
VVX3
Evaporator
VVX4
Evaporator
EK
Expansion vessel
SV
Safety valve
E1
Ellectrical cubicle with safety switch, power section, control card
SS
Start and control signal
EV1
Expansion valve 1
EV2
Expansion valve 2
HT
Hand-held micro terminal
Specifications are subject to alteration without notice.
Operation
There are two refrigerant circuits in the cooling unit. The
circuits are separate from one another and each contains a
different type of refrigerant.
Each circuit is equipped with its own set of heat exchangers on the warm and cold side respectively. The cooling
agent and the brine (water/ethylene glycol) both pass
through the heat exchanger of both refrigerant circuits.
The refrigerant in gas form is compressed by each compressor and then advances to condenser VVX1 or VVX2,
where it is chilled by the cooling agent (water/ethylene
glycol) and condenses to liquid form.
A reduction in pressure occurs in expansion valve EV and
the pressure drops. From the expansion valve the refrigerant advances to evaporator VVX3 or VVX4 where the
refrigerant vaporises, boils, and absorbs heat from the
adjacent medium, i.e. the brine (water/ethylene glycol).
Gas leaves the evaporator and flows back to the cooling
compressor.
Water pump G1 pumps the brine (water/ethylene glycol)
in one circuit from condensers VVX3 and VVX4 where the
brine is chilled by the refrigerant and then proceeds to
the cooling coil, where it in turn cools the supply air discharged from the air handling unit.
Water pump G pumps brine (water and ethylene glycol)
in the circuit from condensers VVX1 and VVX2, where the
brine cools the refrigerant and further to the brine cooler
(the coil in the exhaust air duct). The brine is cooled there
where it transfers heat to the exhaust air leaving the air
handling unit. After that the brine returns to the condenser.
If the cooling agent isn’t chilled adequately, the COOLER
will temporarily lower its capacity to avoid a shutdown
(shuts off one refrigerant circuit and compressor). The
cooling unit will however revert to operating at full capacity again as soon as the operating conditions so permit.
Control
In response to an ON/OFF control signal, the controller
switches in pumps G1 and G2 and compressor M1. The
cooling capacity is controlled by switching in one or both
compressors. On increasing cooling load the controller
switches in compressor M2 and at the same time
switches out compressor M1. If still more cooling is required compressor M1 is switched in to operate together
with M2.
If the temperature of the outgoing brine becomes too
low, one of the compressors is switched out. When the
condition subsides, it is restarted automatically. Should the
pressure become too low, the low pressure switch will trip.
The equivalent will occur on the warm side. If the temperature of the exhaust air becomes too high, one of the
compressors is switched out. If the pressure still rises, the
high pressure switch will trip.
www.swegon.se
GB.COOLER.INST.060501
2
Safety Precautions
2.3
2.1
Safety switch/main power switch
The electrical equipment of the unit is located behind the
inspection door in a separate electrical cubicle.
The safety switch is located inside the inspection door
(right-hand door on the size 24 - 60 units).
The safety switch must not be used for starting or stopping the cooling unit. Make sure that the Cooler is
switched off by shutting down the air handling unit or by
temporarily switching out the cooling unit in the display.
Enter SET in the main menu, select SET again, then select
PROG and then SHUT OFF. After doing this, the safety
switch can be used to isolate the power.
Important!
Always switch off the safety switch when servicing unless otherwise specified in the relevant instruction.
2.2
Hazards
2.4
Electrical equipment
User Authorisation
Only a qualified electrician or trained service personnel is
permitted to carry out electrical wiring in the unit.
Only staff of an accredited refrigeration service company
is permitted to modify or repair the refrigerant circuit.
Modification or work on the cooling unit may only be carried out by service personnel trained by Swegon.
Should the need arise to do any repair work, get in touch
with your nearest Swegon service representative, see the
last page of these instructions.
2.5
Decals
The model number label with type designation, serial
number, refrigerant volume, etc. is affixed to the inspection door of the unit.
Caution!
Make sure that the power has been switched off before
carrying out any work inside the unit.
Caution!
Unauthorized personnel are not under any circumstances permitted to open the refrigerant circuit. The circuit
contains gas under high pressure.
Hazardous areas where there is refrigerant
The entire cooling unit is in principle a hazardous area due
to the presence of refrigerant. For particulars of how to
deal with leakage, see Section 10.3.
The circuits contain type R 407C and R134A refrigerant.
Caution!
Since the Cooler is located on the pressue side downstream of the air handling unit, the inspection lid must
not be opened while the fan is in operation. The door
may fly open and cause injury to personnel. (Applicable
to the size 14 and 18 units).
www.swegon.se
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
3
Installation
3.1
Unloading/transport within the
building site
Important!
3.1.2Lifting using a crane
Place two sling spreaders on the upper side of the unit
and two on the underside of the pallet or under the unit.
Then lift in the pallet (or the unit if the pallet is not to be
attached).
See fig. 6.
The unit should always be horizontal while it is being
transported.
3.1.1Transport using a forklift truck
Fig. 6
3.2
Fig. 5
Caution!
Low centre of gravity! Lift the unit carefully.
Mounting
The Cooler cooling unit should be located at a suitable
spot in the fan room.
The unit can be located with its backside against the
wall. Adequate open space must be provided outside the
inspection door to allow access to the safety isolating
switch/main circuit breaker located behind the inspection
door in compliance with local electrical safety regulations.
3.2.1
Fitting handles to the unit
Fit the handles on the inspection doors.
Specifications are subject to alteration without notice.
www.swegon.se
GB.COOLER.INST.060501
3.3
Installation principle
The dimensions and capacity of the cooling coil and the
cooling agent cooler are specially suited for connection to
the size 08-60 GOLD and size 004-014 Basic air handling
units. For a survey of the sizes of cooling unit and their capacities that correspond to each size of air handling unit,
see Section 14, General Technical Data.
Cooler, sizes 14-18
Venting nipple
Power supply
Start and control signal
Brine
Venting nipple
Exhaust air
Extract air
Outdoor air
Support legs
Supply air
Condensate drain
Cooling coil
Fig. 7
Cooler 24-60
Venting nipples
Cooling agent
Start and control signal
Brine
Exhaust air
Extract air
Outdoor air
Cooling agent cooler
Power supply
Supply air
Condensate drain
Cooling coil
Fig. 8
www.swegon.se
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
General
The unique Wing fans in the GOLD and Basic air handling
units make it possible to connect coils directly against the
duct connection of the air handling unit without any pressure losses or nonuniform air distribution.
Provision for inspecting and cleaning the GOLD unit must
be provided when the unit is installed, such as by fitting inspection covers to the ducting or making the coils
withdrawable. The cooling coil can be incorporated into a
block or can be located separately at an appropriate spot
next to a Basic casing on the supply air side of the unit.
3.3.1Installing size 14 Coolers
For GOLD: The cooling coil and the refrigerating machine
of the size 14 Cooler have an approved rubber seal for
circular connection to the supply air duct and exhaust air
duct respectively of the GOLD 08. A 400/500 mm conical
transition piece is required on the supply air side of the air
handling unit. The cooling unit has a rectangular outlet
connection to decrease pressure losses. The connections
of the GOLD 14-20 are rectangular and their dimensions
are matched to fit this unit. Slip-clamps are used for connection.
For the Basic: The cooling unit is connected without any
end panel to the exhaust air side downstream of the fan in
the Basic. A cover plate must be fitted to the air handling
unit since the refrigerating machine is somewhat smaller,
see Fig. 9. The cooling coil can be incorporated into a
block or can be arranged separately at an optional spot in
a Basic casing on the supply air side of the unit .
See Section 5 for particulars of the cooling connection.
3.3.2Installing size 18 Coolers
For the GOLD: The cooling coil and the size 18 cooling
unit have rectangular connections.Slip-clamps are used for
connection to the ducting.
For the Basic: The cooling unit is connected without any
end panel to the exhaust air side downstream of the fan
in the Basic. The cooling coil can be incorporated into a
block or located separately at an appropriate spot in a
Basic casing on the supply air side of the unit.
See Section 5 for particulars of the cooling connections.
3.3.3Installing size 24-60 Coolers
For the GOLD: Cooling coil and cooling agent cooler for
the size 24, 34, 48 and 60 cooling units have rectangular
connections. Slip-clamps are used for connection.
For the Basic: The cooling coil and cooling agent cooler
can be incorporated into a block or can be installed separately in the Basic casing at an appropriate spot on the
supply air or exhaust air side of the unit.
See Section 5 for particulars of the cooling connections.
Fig. 9
Specifications are subject to alteration without notice.
www.swegon.se
GB.COOLER.INST.060501
4
Electrical Wiring
Important!
The installation work shall be carried out by an authorized
electrician.
4.1
Wiring to the mains power
The power cable must be arranged through the front
panel of the unit. A permanent cable gland has been factory-fitted to the side of the inspection door.
The location of the gland varies slightly depending on the
size of cooling unit.
The incoming cable for 400 V power (5-wire system) must be
connected directly to the safety switch, which has four normally-closed contact functions. The safety switch is installed
in the built-in electrical cubicle. The terminal block for incoming earth is situated adjacent to the safety switch.
If a 4-wire system is used, a jumper should be fitted between the earth and zero terminal blocks in the Cooler.
For access to the connections of the safety switch, the
safety guard above the electrical cubicle components has
to be dismantled.
4.1.1 Size 14 Coolers
The cable gland is located to the right at the top of the
front panel.
The fuse for the cable shall be rated for 20 A(T).
When sizing the cable, take into account the ambient temperature and how the cable will be arranged.
See Fig. 10.
4.1.2 Size 18 Coolers
The cable gland is located at the bottom edge of the front
panel.
Fuse for the cable should be rated for 25 A(T). When sizing
the cable, take into account the ambient temperature and
how the cable will be arranged.
See Fig. 10.
4.1.3
Size 24 and 34 Coolers
The cable gland is located uppermost and to the right on
the front panel.
The fuse for the cable shall be rated for 32/35 A (T) for the
size 24 Coolers and 35 A(T) for the size 34 Coolers. When
sizing the cable, take into account the ambient temperature
and how the cable will be arranged.
See Fig. 10.
4.1.4 Cooler sizes 48 - 60
The cable gland is located uppermost and to the right on
the front panel.
The fuse for the cable shall be rated for 63 A(T). When sizing the cable, take into account the ambient temperature
and how the cable will be arranged.
10
www.swegon.se
Fig. 10
4.2
Other electrical connections
4.2.1GOLD, Version B
General
The Cooler is supplied with two alternative accessories for
controlling the cooling load.
Extra interference protection is required for the Cooler
variants operating where the cooling load is controlled by
an external 0 –10 V DC signal.
To meet the provisions stipulated in the EMC Directive,
concerning insensitivity to interference, the analogue
inputs must be protected by a Ferrit block, 019 210.
Communication cable 019 007 is the accessory, that must
be used when the Cooler operates together with the
Version B GOLD ventilation unit. See the individual instructions.
Design
The ferrit block, 019 210, is designed for snapping
around wires.
The block consists of two ferrit-halves, enclosed in a
plastic casing that can be opened.
The plastic casing has ”hinges” and a simple lock that make
it easy to open and close around relevant wires.
Dimensions: H = 15 mm, W = 15 mm, L = 29 mm and
diameter of the openings = 6.6 mm.
Communication cable 019 007 is a 5 m long flat cable,
with a type RJ 1 modular connection fitted at both ends.
The cable transfers normal communication signals between the control unit and the GOLD unit (Version B), but
not 4 V DC. Both types of control have their own 4 V DC
supply.
Important: Do not use an ordinary bus cable! If the 4 V DC
connections are interconnected, this will cause malfunctions.
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
Connection of the control and regulation cable to
the air handling unit.
Only one communication cable is required for transmitting
information between the Cooler and the GOLD control
systems. All the operating conditions and alarms are
transmitted across this cable.
Communication: Communication between the Cooler
and the GOLD unit takes place by means of a special
communication cable (PM part number 019 007).
Installation in the GOLD:
Connect communication cable 019 007 to any of the
ABC Bus outlets on the control unit. For the Gold (Version B) see Fig.11!
Use one of the holes in the oval rubber-covered cable
glands on the backside of the electrical cubicle’s junction
hood, for running the cable in to the control unit. See
Fig. 12! Move a part of the cable gland to the side to
insert the Modular connection through it. Connect the
cable to a bus connection on the control unit. Adjust
the cable length inside the electrical cubicle and adjust
the cable in the cable gland. Refit the cable gland in its
correct position.
Lay the communication cable in a safe manner from the
plastic hood on the top panel of the GOLD unit (Version
B) to the Cooler unit.
Installation in the Cooler: Connect communication cable 019 007 to any of the ABC Bus outlets on the control
unit. For the Cooler, see Fig. 11b!
Remove the safety guard over the electric cubicle of the
Cooler. Loosen the oval cable gland on the front side of
the electrical cubicle just so much to enable you to push
the quick connector on the communication cable through the opening. See Fig. 12!
Fasten the connector in any of the connections for ABC
Bus/communication on the control circuit card
ABC Bus
ABC-Bus
Fig. 11
Specifications are subject to alteration without notice.
Dip switch
SW1
ABC Bus
Fig 11b.
Hand-held Micro Terminal Connect the quick connector
of the hand-held micro terminal to one of the connections
on the control circuit card, i.e. to the centre outlet up to
the left or any of the 6 right-hand modular connections at
the lower edge of the control circuit card. Lead the cable
through the cable gland in the same manner as the communication cable, described above.
hand-held micro terminal of the Cooler can also be connected to any vacant ABC Bus connection on the circuit
card or hand-held terminal of the GOLD unit.
Commissioning
At the lower edge of the control unit in the Cooler there
is a red block with four DIP switches that have to be set to
appropriate settings. For communication with the GOLD
unit, set all 4 switches to the ON position (up).
Use the hand-held terminal to set the cooling unit function to the auto operation mode. Do this under SETTINGS.
See the Operation and Maintenance Instructions for the
GOLD.
4.2.2Other types of air handling unit
Instructions for the Cooler with 0-10 V controller
Connection of the control and regulation cable to air
handling units other than the GOLD version B.
DIP-switch settings: At the bottom of the control unit in
the Cooler there is a red block with 4 DIP switches, which
have to be set. If 0-10V control is used, set the switch no.
1 to the OFF position (down) and switch nos. 2 – 4 to the
ON position (up). See Fig. 11b!
Hand-held micro terminal: The hand-held micro terminal is connected to one of the ABC-Bus-connections on
the control circuit card,The centre outlet up to the left (Fig.
13) or one of the 6 right-hand modular connections at the
lower edge of the control circuit card (Fig. 11).
www.swegon.se
11
GB.COOLER.INST.060501
Mounting: Dismantle the safety guard over the electri-
In-operation Indications
cal cubicle of the Cooler. Loosen the oblong cable gasket
on the front of the electrical cubicle, just so much that the
quick connector of the communication cable can be inserted
through the opening. See Fig. 12.
A common cable can be used for both the signals. The existing cable glands can be used if the diameter of the cable
does not exceed 6.5 mm. If a thicker cable is used, wire it through any of the lead-throughs to the side of the cable gland.
There is no external operation input in the GOLD unit.
Ferrite block
019 210
1 2 3 4
5 6 7 8
9
10
11
12
13
14
15
16
17 18 19 20
21
22
23
23
24
P N L
- + - +
- + - +
- +
- + - +
25 27
29 31
33 35
37 39
41 43
45 47
49 51
26 28
30 32
34 36
38 40
42 44
46 48
50 52
Fig. 12
Fig. 13
Start signal free normally-open contacts for cooling,
on/off
Connect to terminal blocks 45 and 46.
0-10 V control signal for regulating the cooling capacity
The control signal must not exceed 10 V +10 %.
Connect to terminal blocks 47 (−) and 48 (+).
5 FERRITE BLOCK 019 210
Important!
Both signal inputs must be connected.
Type A and B Group alarms
Priority A group alarms are indicated on a closure of the potentialfree relay contacts between terminals 9 and 10.
Priority A group alarms are indicated on a closure of the potentialfree relay contacts between terminals 11 and 12.
In-operation indication
Indication that the pumps are in operation can be
obtained by an alternating potential free relay contact. Terminal
block 15(NC), 16(Com) and 17(NO).
A common cable may be used for all signals. The existing cable
gasket may be used if the cable diameter does not exceed 6.5
mm. If a thicker cable is used, it will have to be run through one
of the cable glands to the side of the cable gasket.
Installation in the GOLD, Version C.
Run the cable(es) into the electrical cubicle via the cable gland, or
via lead-throughs on the backside of the top panel hood.
Start signal
Connect to terminal numbers 7 and 8.
0-10 V control signal
Connect to terminal numbers 42 (-) and 43 (+).
Group alarm A and possibly group alarm B
Connect alarms from the Cooler to the External Alarm 1 or the
External Alarm 2 terminals. The alarm in the Cooler is factorypreset with priority A, which means that only group alarm A
normally needs to be connected. Connect the conductors from
terminals 9 and 10 in the Cooler controller to terminal numbers
50 and 51, or 52 and 53, in the GOLD control unit.
Instructions for the Cooler with 0-10 V Controller
General
The Cooler is supplied with two optional accessories for
controlling the cooling load. Extra interference protection
is required for the Cooler variants for which the cooling
load is controlled by an external 0 –10 V DC signal.
To comply with the provisions of the EMC Directive that
deals with insensitivity to interference, analogue inputs
must be protected by a Ferrite block, 019 10.
Communication cable 019 007 is the accessory that must
be used if the Cooler operates together with the GOLD
ventilation unit, Version B. See individual instructions on
this topic.
Design
Ferrite block, 019 10 is designed to snap on around cables. The block consists of two ferrite halves that rest in a
plastic casing that can be opened. The plastic casing has
”hinges” and a simple lock that simplifies opening and
closing it around relevant conductors.
Dimensions: H= 15 mm, W= 15 mm, L= 9 mm and diameter of openings = 6.6 mm
Installation
After installing the relevant cables for operating and controlling the Cooler, fit the ferrite block.
Fit the ferrite block around the conductors connected to
terminals 47 – 48 (0-10 V control signal) and the conductors on terminals 43 – 44 (steady 10V output signal), if
used.
Position the ferrite block as near as possible to terminals
47 – 48.
Ferritblock
019 210
P N L
- +
- +
43 45
47
44 46
48
Fig.26
12
www.swegon.se
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
6 Communication Cable 019 007
6
Instructions for the Cooler
Connection of the cooling coil and the cooling agent
cooler to cooling unit
General
6.1
The Cooler is supplied with two optional accessories for controlling the cooling load.
Communication cable 019 007 is the accessory that must be
used if the Cooler operates together with the GOLD ventilation
unit, Version B. See individual instructions on this topic.
Extra interference protection is required for the Cooler variants
for which the cooling load is controlled by an external 0 –10 V
DC signal. In these cases, the ”Ferrite block” accessory should be
used. See individual instructions.
The cooling coil shall be located in the supply air ductwork.
Sizes 14 and 18: Install the refrigerating machine in the
exhaust air ductwork down-stream of the fan. Sizes 24,
34, 48 and 60: install the cooling agent cooler in the
exhaust air ductwork. The cooling unit is designed to
stand alone in the fan room.
Design
Communication cable 019 007 is a 5 m long flat cable, with a
type RJ 1 modular connection fitted at both ends.
The cable transfers normal communication signals between the
control unit and the GOLD unit (Version B), but not 4 V DC. Both
types of control have their own 4 V DC supply.
If an ordinary bus cable is used, the 4 V DC connections will be
interconnected and this will cause malfunctions.
Installation
Connect communication cable 019 007 to any of the ABC Bus
outlets on the control unit.
Use one of the holes in the oval rubber-covered cable glands on
the backside of the electrical cubicle’s junction hood, for running
the cable in to the control unit.
Move a part of the cable gland to the side to insert the Modular
connection through it. Connect the cable to a bus connection
on the control unit. Adjust the cable length inside the electrical
cubicle and adjust the cable in the cable gland. Refit the cable
gland in its correct position.
Lay the communication cable in a safe manner from the plastic
hood on the top panel of the GOLD unit.
Insert and connect the cable correspondingly in the Gold control
unit.
Commissioning
Set the Dip switches on the control unit in the Cooler for communication with the GOLD.
Set Dip switches SW1, 1– 4 = On (up). The Cooler controller will
then operate as a ”slave”.
On delivery, Dip switch SW1, 1 = Off and 2 – 4 = On. The Cooler
controller is then a “master”.
Use the hand-held terminal to set the cooling unit function to
the auto operation mode.
Do this under SETTINGS. See the Operation and Maintenance
Instructions for the GOLD.
Dip switch
SW1
ABC Bus
Fig. 14
‘
Specifications are subject to alteration without notice.
6.2
Cooling Connections
Location
Condensate from cooling coil
The cooling coil is equipped with a drip tray with drain
connection (to collect condensate from the coil). A drain
pipe should be arranged from the condensate drain connection to a floor gulley. Size 14 units with the size 08
Gold unit: use the connection on the outlet air side and
plug the connection by the inlet air.
6.3
Liquid connections
Liquid is conveyed by means of pipework. The coils have
female-threaded connections and the Cooler has smooth
connections for brazing or compression ring fittings. The
liquid circuits should be connected in a counter-flow mode
to enable maximal cooling capacity. Shut-off valves should
be installed in the pipework leading to and from the cooling coil to avoid having to drain the whole system of fluid
if work is necessary (such as having to replace a circulation
pump).
6.4
Venting nipples
Fit venting nipples at the highest point of the connecting pipework at both the outlet and inlet of the cooling
coil and the cooling agent cooler respectively. Locate the
nipples where the water is on its way downstream.
See illustrations in Section 3.3.
6.5
Insulating the brine circuit
Insulate the brine circuit of the cooling coil in compliance
with local standards.
6.6
Connection to cooling unit
Connect the cooling coil and the cooling agent cooler to
cooling unit as illustrated in Section 3.3.
6.7
Safety drain
Safety valves for relieving the water circuits are fitted to
the expansion vessels. The safety valves open if the pressure in the system is too high, i.e. they open if the pressure
reaches 1.5 bar.
The drain pipe from the safety valve should be extended to
a receptacle; not directly to a floor gulley since the liquid
circuit contains glycol.
One (sizes 14-18) or two hoses (sizes 4-60),13 mm i.d., is/
are run from the safety valves and out through the casing
to be fitted with an extension to a collecting tank, see Fig.
7 and 8.
www.swegon.se
13
GB.COOLER.INST.060501
6.8
Filling with water/glycol mixture
Caution!
The ethylene glycol used is toxic and must never be
consumed!
Accessories used
• Mixing vessel.
• Filling pump for pipes and coils.
5.8.1 Filling
For particulars of the volume to be filled, see information
for the relevant size in the charts in Section 11.
• Blend water/glycol (with 30% admixture of glycol)
into an appropriate mixing vessel and stir.
• Connect the filling hose to the tap in the unit.
Important!
The system must be vented, see Section 6.8.2.
It is essential to evacuate all the air out of the system. It is
advisable to run the pumps with connection to an open
vessel and to alternately vent the unit and hoses, and fill
up. See fig. 15.2.
6.8.2 Venting the system
Vent the system as follows:
• Set the safety switch of the cooling unit in the ON
position.
• Start the pumps.
Important!
If you are starting the unit for the first time, first follow
the directions in Section 6, Commissioning.
Strainer
Strainer
Pump
Pump
Return from coil
Fig. 15.1
•
•
•
•
14
Open the tap.
Use an appropriate filling pump with hose.
Fill up the water/glycol mixture until the plastic vessel
is filled halfway (cold side). On the hot side the expansion vessel can be filled until the safety valve opens.
See Fig. 15.1.
Shut-off the tap.
www.swegon.se
Return from coil
Fig. 15.2
•
•
•
•
Press button 3 TEST in the main menu for 5 seconds.
Press the arrow button to advance down to Brine pump
press button 4 PROG, press button + so that the value
will be 1, do the same for the cooling agent pump.
Open venting plugs by cooling coil and cooling agent
cooler. Cooling coil only on sizes 14 - 18.
Open the venting nipples on the water connections
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
•
•
•
•
•
The venting holes shouldn’t be completely open, but
only slightly to allow the air to be forced out.
To remove all the air from the cooling unit, start the
pumps to transport any air remaining in the circuit to
the venting nipple. Always check that there is
positive pressure in the system (check the
manometer), otherwise the air cannot be forced out.
If the pressure isn’t positive, fill up with more of the
water/glycol mixture.
The system should maintain a positive pressure of
about 0.5 bar while you are venting it.
If there is still air in the system, repeat the venting
procedure as many times as necessary until there is
no air left in the system.
When the system reaches the correct pressure,
close the tap and take away the filling pump.
7
Commissioning
7.1
Preparations
7.1.1 Before starting up for the first time
• The water circuits shall be filled and vented.
• The power supply must be connected.
• The external control signal or communication cable of
the GOLD unit must be connected.
• Check the Dip-switch settings on the control
card. For communication via bus with the GOLD
unit, all switches (1 - 4) should be in the ON position.
For control via external 0 - 10 V DC signals, switch 1
should be OFF and switches 2 - 4 should be ON.
• The hand-held micro terminal must be connected.
• Check that all fuses and motor protection circuit
breakers are switched in.
The control system of the unit has a preprogrammed factory setting, which makes the unit ready to use when basic
settings have been entered.
7.1.2 Starting up
• Set the Cooler safety isolating switch to the ON position.
• Take the hand-held terminal and enter the TEST mode
by pressing the TEST pressure button and holding it
pressed in for about 5 seconds.
• Start the pump/pumps to run for a few minutes to
check that the liquid control systems are free from air.
Start the pumps by pressing the PROG button to
advance to the control position. Use the ”arrow
right” and ”arrow left” buttons to move the marker
and press the ”+” button to highlight ”1” (operation)
or the ”--” button to highlight ”0” (stop).
•
•
•
•
•
•
•
•
Repeat the same procedure to start the compressors
in the next menu image.
(The pumps must be in operation).
Size 48 and 60 Coolers: the direction of rotation of
the compressors is important.
Start one compressor at a time and advance 2 menus,
to the temperature reading image. Check that BRINE
TEMP drops and that COOLING AGENT TEMP rises
after just a few minutes of operation. If this does not
occur, the direction of rotation may be wrong. If this
is the case, change the sequence of the power supply
phase wires, see Section 7.1.3.
Repeat this check to make sure that the direction of
rotation is correct.
Set the compressors and pumps to 0 (stop).
Press the RET button to return to the main menu.
From there, press the SET button to advance to the
settings mode. Press button 2 for Auto operation and
confirm by pressing the SET button.
The Cooler is now ready for operation and will operate whenever the connected control signal calls for
cooling.
Remove any impurities that may have collected in the
strainer(s)!
7.1.3
Correcting the phase sequence
Caution!
To be carried out by an authorized electrician or trained
service personnel only.
•
•
Stop the Cooler by selecting SWITCHED OFF under
the settings mode.
Then switch off the safety isolating switch on the
Cooler.
Important!
Isolate the power supply to the unit.
•
•
•
•
Transpose the two phase power supply conductors to
obtain the correct direction of rotation.
Switch on the power supply to the unit.
Turn the safety isolating switch to the ON position.
Start the Cooler as described under Starting up, see
Section 7.1.2.
Commissioning Report
www.swegon.com
Specifications are subject to alteration without notice.
www.swegon.se
15
GB.COOLER.INST.060501
8
8.1
Programming and ManaGIng the Menus
The hand-held micro terminal
The GOLD Cooler has a hand-held micro terminal with
menus viewing settings, readings and possible alarms.
The hand-held terminal consists of a sealed control box
with a bus cable connection. The bus cable supplied is 3
m long and its one end is designed for connection to the
control circuit card in the electrical cubicle of the Cooler.
If a communication cable is used for connecting the Cooler to a GOLD unit, the hand-held terminal of the Cooler
can also be connected to a free bus connection on the
control circuit card or hand terminal of the GOLD.
The hand-held terminal has a four line display screen and
4 push-buttons The right-hand button contains an alarm
LED.
8.1.2 Display and Buttons
All settings can be read in clear text in the display.
All information is presented in various menus.
The main menu normally appears in the display, if no other
menu has been selected.
If no return to the main menu is manually keyed, the
display will automatically return to the main menu after
about 30 minutes.
The functions of the four buttons change depending
on which menu is shown. The function of the buttons is
explained by the caption or symbol shown in the display
right above each button. For explanation, see Section 8.2.
16
www.swegon.se
8.2
Menu button captions and symbols
The most common button functions are described below.
In some of the separate menus, the buttons have other
functions. These different functions are explained in the
relevant menu section.
↓
Advance 1 step to the next menu in the group.
↑
Go back 1 step to the previous menu in the group.
RET
Return to preceding menu level (main or start
menu).
PROG Changes to the submenu of the menu shown
(alter settings level).
+
Increases the value of the highlighted figures.
−
Decreases the value of the highlighted figures.
→
Advance to highlight new figures/line.
After the last figure/line, the image changes back
to the readings level in the menu.
←
Go back to highlight previous figures/line.
After the last figure/line, the image changes back
to the readings level in the menu.
1-4
Used to select a function if numbered options
appear in the image displayed.
SET
Confirms your choice and changes the image
back to the readings level in the menu.
8.3
Menu groups and levels
The menus of the hand-held micro terminal are broken
down into various menu groups. The four menu groups
can be selected in the main menu by pressing the buttons
identified by their captions: INFO, SET, TEST and ALARM.
Menus and functions are explained under each group as
specified in Section 9.
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
9
Menus
9.1
Main Menu
OPER LEVEL indicates the present cooling load, as in the
main menu.
BRINE PUMP shows the pump status.
1 = On and 0 = Off.
COOLING AGENT PUMP shows the status of the pump.
1 = On and 0 = Off. (Size 14 and 18 Coolers: this line is
empty).
COMPRESSOR.1
COMPRESSOR.2
:
::
1
1
RET
:
▼
*COOLER* TUES 12:49
. . : 100%
AUTO OPER
INFO : INST : : TEST : LARM
COMPRESSOR.1 shows the status of compressor 1.
1 = On and 0 = Off.
COMPRESSOR.2 shows status of the compressor 2.
1 = On and 0 = Off.
▼
Fig. 16
The COOLER image indicates type of unit, the present day
of the week and the time.
The second and third lines indicate the in-operation status
of the cooling unit.
SWITCHED OFF is shown when the control circuit card has
not received an operation command. STOP is shown when
operation command has been given, but the cooling load
signal is 0. A percentage figure that may vary between
0–100% together with the text AUTO OPER indicates the
cooling capacity at which the unit is operating.
The text DELAYED START and the percentage figure are
alternately displayed when any of the cooling compressors
are unable to start, because the restart delay time has not
run out.
9.2
Information Menus
*COOLER* TUES 12:49
. . : 100%
AUTO OPER
INFO : INST : : TEST : LARM
▼
BRINE temp
COOLING AGENT temp
PROGRAM VERSION
:
: : RET
-7,9˚c
34,6˚C
: 1.14
:
▼
BRINE TEMP shows the present temperature of the brine
medium.
COOLING AGENT TEMP shows the present temperature of
the heat carrying medium. (Size 14 and 18 Coolers: CONDENSER TEMP is displayed).
PROGRAM VERSION shows the current program version of
the control equipment.
*oper time Day and night*
cOMPRESSOR 1
2999
cOMPRESSOR 2
1998
:
::
RET
:
OPER TIME DAY AND NIGHT shows current operation time
for each compressor. The time is measured in minutes
but specified in day and night, due to limited space in the
display.
Main menu.
OPER LEVEL
BRINE PUMP
COOLING AGENT PUMP
:
::
RET
100%
1
1
:
▼
Specifications are subject to alteration without notice.
www.swegon.se
17
GB.COOLER.INST.060501
9.3
Settings Menus
* COOLER * TUES 12:49
STOP
AUTO OPER
INFO : INST : : TEST : LARM
▼
* ACTTUAL TIME *
WED TIME 07:30
DATE 17/03 - 2003
:
:
:RET
* språk/LANGUAGE *
ENGLISH
: PROG
:
▼
The preset operating mode is shown on the second line.
Pressing PROG changes the image to the settings menu.
1 = SWITCHED OFF and 2 = AUTO OPER.
Select appropriate number and confirm by pressing SET.
* REGULATION SPEED*
STAGE TIME 600S
:
:RET
: PROG
▼
:
:RET
Preset value for the STAGE TIME, delayed switching in
from compressor stage 1 to stage 2 and vice-versa. Same
delay also applies to switching between stage 2 and stage
3.
Pressing PROG changes the image to the settings menu.
The step time can be set between 0 and 600 s.
*** COOLER ***
SIZE 24
:
:RET
: PROG
▼
: PROG
▼
Shows preset LANGUAGE. The second line shows current
language selected.
Pressing PROG changes the image to the settings menu.
Press the arrow up or down to advance to the desired language from the current list and confirm by pressing SET.
If the Cooler is connected to the GOLD unit by means of
a communication cable, same language appears in both
displays.
FACTORY SETTING
:
: PROG
▼
** OPER MODE **
AUTO OPER
:
:RET
Shows preset ACTUAL TIME. The second line shows the
current day of the week and time. The third line shows
current date. (dd/mm – year)
Pressing PROG changes the image to the settings menu.
Main menu.
:
:
:
:
0
:RET
: PROG
Activating the FACTORY SETTING. The factory setting
function resets all the parameters back to their original
settings. This function should only be used when problems
with settings have arisen.
Pressing PROG changes the image to the settings menu.
Set the value to 1, confirm by pressing SET. The parameters will be reset when the display image returns to the
Main Menu.
The preset COOLER SIZE is shown on the second line. The
preset size must agree with current unit size and should
only be changed if the control circuit card is replaced.
Pressing PROG changes the image to the settings menu.
The sizes 14, 18, 24 , 34, 48 and 60 can be set.
18
www.swegon.se
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
9.4
Test menus
Whenever any of the menus under TEST is selected, the
control system will leave the normal in-operation status
and go over to manual test run status.
Warning!
The various ouputs are now controlled by the operator
in fully manual mode. The safety functions are switched
off and the operator assumes all responsibility.
The only provision is that the pumps must be in operation
before any compressor can be started.
*COOLER* TUES 12:49
SHUT OFF
INFO : INST : : TEST : LARM
▼
:
:
:RET
:
00%
1
1
: PROG
▼
OPER LEVEL indicates the current percentage, the same as
in the main menu.
BRINE PUMP and COOLING AGENT PUMP shows the status for each pump in the manual mode.
Pressing PROG alters the image to the settings menu.
(Cooler 14 and 18: Line 3 is empty.
Specifications are subject to alteration without notice.
1
1
:
:RET
: PROG
▼
COMPRESSOR 1 and COMPRESSOR 2 show the status of
each compressor in the manual mode.
Pressing PROG alters the image to the settings menu.
Important!
The pumps must be in operation before the compressors
can be started.
GROUP ALARM
A
OPER INDICATION
OPER INDICATION
:
Main menu
The TEST button must be held in for 5 s. before the
image will change.
OPER LEVEL
BRINE PUMP
COOLING AGENT PUMP
COMPRESSOR.1
COMPRESSOR.2
:
1
:RET
B
0
1
10V
: PROG
▼
GROUP ALARM A, B and OPER INDICATION show the
status of each relay output in the manual mode.
Pressing PROG alters the image to the settings menu.
BRINE temp -2,6˚c
COOLING AGENT temp 34,6˚C
:
::
RET
:
BRINE TEMP and COOLING AGENT TEMP show present
temperatures. (For the size 14 and 18 Coolers: BRINE
TEMP and CONDENSER TEMP is shown).
www.swegon.se
19
GB.COOLER.INST.060501
9.5
Alarm menus
* COOLER * TUES 12:49
SWITCHED OFF
INFO : INST : : TEST : LARM
▼
10
Alarms
10.1
General
The alarm number and cause is displayed in clear text on
the screen. A red lamp incorporated into button number
four also flashes on the hand-held micro terminal.
Typical alarm text in the display.
Main menu
L1
l2
* ALARM HISTORY *
NR 55 17/02 12:15
nr 54 14/02 12:11
:
::
RET
:
▼
L3
l4
* ALARM HISTORY *
NR 52 12/01 22:47
nr 52 11/02 02:30
:
::
RET
:
* * * ALARM 50 * * *
HIGH PRESSURE SWITCH
COMPRESSOR. 1 TRIPPED
▼
ALARM HISTORY shows the 4 most recent alarms initiated
in the system. L1 shows the most recent one.
The alarms are shown with the number of the alarm and
the date and time when it was initiated.
* PRESET Alarm * NR 50
PRIORITY
ALARM IND 1 STOP
:
:
:RET
:
: PROG
:
RES
Fig. 17
10.2
1
1
: :
To reset alarms
Manual reset means, unless otherwise indicated, that the
RES button on the hand-held terminal is pressed.
Automatic reset means that the control unit resets the
alarm after the fault has been remedied.
PRESET ALARM is the reading and settings menu for the
12 different alarms that have been present in the system.
By pressing PROG the image changes to the menu for setting the alarm numbers. From here you can advance to the
desired alarm number.
By pressing SET the image changes over to the level for
setting of the current priority and condition of the alarm.
PRIORITY can be selected for 1 or 2.
ALARM INDICATION can be selected to 0 (no indication on
the hand terminal) or 1.
STOP can be selected by marking 0 (when alarm the unit
continues) or 1 (when alarm the unit is switched off).
20
www.swegon.se
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
10.3
Settings
Priority, Indication and Stop
All alarms have factory preset options for priority, indication on/off and stop. Some of these settings can be altered. None of the alarms can be completely blocked.
Priority option
1 = The alarm has priority A and initiates group alarm A
2 = The alarm has priority B and initiates group alarm B
Alarm indication, on/off
0 = The alarm indication on the hand terminal is shut off.
1 = The alarm indication on the hand terminal is active.
Alternative for Stop
0 = The cooling unit will not stop when the alarm is initiated.
1 = The cooling unit will stop when the alarm is initiated
Delay
Delay implies that the alarm will not trip immediately when
a fault is registered, but firstly after the fault has lasted a certain period or repeated itself a certain number of times.
Action
The cause of the alarm is given, and possible sources as
well as a few simple spots to check for fault tracing.
Other Particulars
The alarms are not activated in the programming menus.
10.4
Alarm conditions
Alarm 50
HIGH PRESSURE SWITCH
COMPRESSOR.1 TRIPPED
The alarm is initiated if input 25-26 is interrupted and if
BT4 >45°C.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 1 s.
The alarm can only be reset locally i.e. via hand terminal,
not via communication system or similar remote control,
due to regulations in the cooling standards.
Alarm 52
CONTACTOR REPLY
COMPRESSOR. 1 TRIPPED
The alarm is initiated when input 35-36 is interrupted
while compressor 1 is operating or when the input is
closed while compressor 1 is switched out.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 3 s.
The alarm can only be reset locally i.e. via hand terminal
not via communication system or similar remote control
due to regulations in cooling standards.
Alarm 53.
LOW PRESSURE SWITCH
COMPRESSOR. 1 TRIPPED
The alarm is initiated if input 25-26 is interrupted and if
BT4 <45°C.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 1 s.
The alarm can only be reset locally i.e. via hand terminal
not via communication system or similar remote control
due to regulations in cooling standards and that low pressure - high pressure switches are connected in series.
Alarm 54
LOW PRESSURE SWITCH
COMPRESSOR. 2 TRIPPED
The alarm is initiated if input 29-30 is interrupted and if
BT4 <45°C.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 1 s.
The alarm can only be reset locally i.e. via hand terminal
not via communication system or similar remote control
due to regulations in cooling standards and that low pressure - high pressure switches are connected in series.
Alarm 51
HIGH PRESSURE SWITCH
COMPRESSOR.2 TRIPPED
The alarm is initiated if input 29-30 is interrupted and if
BT4 >45°C.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 1 s.
The alarm can only be reset locally i.e. via hand terminal,
not via communication system or similar remote control
due to regulations in the cooling standards.
Specifications are subject to alteration without notice.
www.swegon.se
21
GB.COOLER.INST.060501
Alarm 55
CONTACTOR REPLY
COMPRESSOR. 2 TRIPPED
The alarm is initiated when input 37-38 is interrupted
while compressor 2 is operating or when the input is
closed while compressor 2 is switched out.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 3 s.
The alarm can only be reset locally i.e. via hand terminal
not via communication system or similar remote control
due to regulations in cooling standards.
Alarm 56
EXCESS TEMP
COMPRESSOR. 1 TRIPPED
The alarm is initiated if input 27-28 is interrupted while
Compressor.1 is operating.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 5 s.
Alarm 57
EXCESS TEMP
COMPRESSOR. 2 TRIPPED
The alarm is initiated if input 31-32 is interrupted while
Compressor.2 is operating.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 5 s.
Alarm 58
PUMP FUSE F1
TRIPPED
The alarm is initiated when input 50 does not receive
a signal stronger than 5 V DC.
When the alarm has been initiated, neither the pumps nor
the compressors can start.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 3 s.
The alarm can only be reset locally i.e. via hand terminal
not via the communication system or similar remote control due to regulations in cooling standards.
Alarm 60
COOLING AGENT SENSOR
(CONDENSER SENSOR, SIZE 14-18)
DEFECT
The alarm is initiated if communication is not obtained
with the (BT4) cooling agent sensor.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 5 s.
The alarm resets itself automatically.
Alarm 61
BRINE SENSOR
DEFECT
The alarm is initiated if communication is not obtained
with the (BT3) brine sensor.
The alarm has factory settings: Priority A, Indication 1,
Stop 1. Time delay: 5 s.
The alarm resets itself automatically.
10.5
Alarm Priorities
Setting of Priority, Indication and Stop:
All alarms have factory preset options for priority, indication and stop. Some of these settings can be changed.
None of the alarms can be entirely blocked.
Possible Settings:
Priority:
For all alarms priority 1 (A) or 2 (B) can be
selected.
Indication: For all alarms, option on the hand terminal:
0 (alarm LED doesn’t light at all) or
1 (LED flashes in the event of an alarm).
Stop:
No alarm can be selected for continued operation.
The cooling compressors will stop if any
alarms are initiated. If alarm 59 is initiated,
the pumps will continue to operate.
Alarm 59
BRINE TEMP
EXCEEDS ALARM LIMIT
The alarm is initiated if (BT3) the brine temperature >15°C
for more than one hour while one or more
compressors are operating.
The pumps continue operating after alarm has been initiated.
The alarm has factory settings: Priority 1, Indication 1,
Stop 1. Time delay: 1 hour.
The alarm resets itself automatically.
22
www.swegon.se
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
11
Maintenance
Clean the inside of the unit whenever necessary.
Carry out a visual inspection at least twice a year.
11.1
•
•
•
•
Cleaning
Stop the Cooler by shutting down the air handling unit or
by setting the cooling unit to ”0” in the cooling menu
image in the air handling unit terminal (i.e. alternate
the ON/OFF signal).
Then shut off the safety isolating switch of the GOLD
Cooler.
Open the inspection door.
Vacuum clean the space and wipe with a damp cloth.
11.2
To change the water/glycol mixture
The need for filling or changing the liquid arises only if
leakage is detected, or if you fear that the water doesn’t
contain enough glycol.
To fill the circuit, follow the directions in Section 5.8.
The correct mixture is 30% ethylene glycol, 70% water.
Do not forget to vent the system!
11.3
Handling refrigerant
Type R 407C and R134A refrigerant is used in the Cooler.
The refrigerant circuit has been charged at the factory.
Caution!
11.4
Charging with refrigerant
Type R 407C and R134A refrigerant is used
If a low pressure alarm is initiated, this have been caused
by too low a volume of refrigerant.
Caution!
Always wear protective goggles and protective gloves
when working with refrigerant. Contact with skin and
eyes may cause frostbite.
Caution!
If the refrigerant is exposed to fire or is intensely heated
in some other way, toxic gases will form.
Important!
Charging with refrigerant must be carried out according
to the refrigerant manufacturer’s recommendations.
Whenever possible, employ working methods that prevent refrigerant contact directly with skin.
Arrange adequate ventilation/local extraction.
Wear tight-fitting protective goggles, protective gloves
and an overall.
Under no circumstances shall unauthorized personnel
be permitted to open the refrigerant circuit. The circuit
contains gas under high pressure. The refrigerant circuit
may only be modified or repaired by qualified personnel
from an accredited refrigeration company.
If refrigerant comes in contact with eyes
Use an eye douche to flush the eyes (alternatively with
lukewarm water) for 20 minutes. Seek a doctor.
Important!
If refrigerant causes frostbite
Seek a doctor.
If you detect any refrigerant leakage, get in touch with
your nearest Swegon Service representative.
Specifications are subject to alteration without notice.
If refrigerant comes in contact with skin
Carefully wash with soap and lukewarm water.
www.swegon.se
23
GB.COOLER.INST.060501
11.5
Annual inspection
Annual inspection by an accredited inspectorate is required if refrigerant volume in a one-piece unit exceeds 3
kg per circuit.
This is thus not required the for size 14 and 18 units, but
on the other hand it is for the size 24, 34, 48 and 60 units.
Obligation to file reports
Obligation to report to a local supervisory authority is only
required if the total volume of refrigerant in the company
exceeds 10 kg.
11.6
Service
Only service personnel trained by Swegon shall be permitted to do any work on the cooling unit.
If any repair work is needed, get in touch with your nearest Swegon service representative, see the backside of
these user instructions.
12
Cooling Coil and Cooling Agent Cooler
Cooling coil and cooling agent cooler are sized to match
the size 08-60 Gold and the size 004-014 Basic units.
The coils consist of copper tubes and profiled aluminium
fins. The casing is made of hot galvanized sheet steel. The
headers are made of steel.
12.1
Instructions for the BASIC unit
Installation
The coil must be vented before the system is commissioned, thus a venting valve should be fitted to the venting
nipple.
The BCKO Cooling agent cooler should be connected for
cross-flow mode as indicated by the arrows on the connection branches. If a shunt unit is fitted, make sure that it
is installed so as not to block inspection of the other functional sections.
Care
Check whether cleaning is required at least twice a year.
The unit should be cleaned in the following way only:
Blow with compressed air towards the ordinary direction
of airflow and then vacuum clean the side facing the ordinary direction of airflow using a soft nozzle.
Wet cleaning can be carried out by flushing with water.
If a solvent is used, it must be of a quality that doesn’t
corrode aluminium or copper. Cover adjacent functional
sections to protect them before you begin cleaning. After
you’ve finished cleaning, blow the surfaces with compressed air to remove all traces of detergent. Swegon
detergent, sold by Swegon Service is recommended.
While cleaning, check for trapped air in circuits, the glycol
content and density, if necessary.
BCKO Dimensions
L
P
12.1.1 BCKO, 006-014 Cooling agent cooler
The BCKO cooling agent cooler is finned tube coil. Water
is used as the heat carrier, usually mixed with glycol.
The BCKO is made of copper tubes with aluminium fins.
The headers and connections are made of steel.
Specification
The design, size, etc. of the cooler are specified in the
delivery documents.
BCKO
24
BASIC
COOLER
004
14
006
18
006
24
25
20.1
009
24
32
23
009
34
32
23
014
34
32
30
014
48
32
37
www.swegon.se
R dia.
VOLUME/L
K
Fig. 18
BCKO 004-014
B
H
L
004
1039
546
453
006
1259
656
453
009
1459
756
453
014
1759
906
453
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
12.1.2 BCKA 004-014 COOLING COIL
Specification
Design, size etc. is specified in the documents supplied.
BCKA
BASIC
COOLER
RØ
VOLUME/L
004
14
25
5
006
18
32
8,5
006
24
40
11
009
24
40
12
009
34
50
22
014
34
65
32
014
48
65
39
Installation
The coil must be purged of air before it is commissioned,
because a venting valve must be fitted on the venting
nipple.
The BCKA is designed for horizontal airflow, the cooling
section should be mounted with the circuit pipes horizontal to access for venting and draining.
Brine connection (Water)
The BCKA should be installed in accordance with the
airflow direction arrows on the inspection side. The piping should be connected for counter-flow circulation as
indicated by the arrows on the connection pipes. Parallel
circulation is wrong and will lead to a substantial reduction
in capacity.
Keep in mind that the connection pipes must not be in the
way and hamper inspection in other unit sections.
Height A (the distance between the runoff level in the
unit section and the run-off level in the water trap) must
be at least just as large in mm as the negative pressure in
the unit is in mm gauge.
Height B (the distance between the runoff level in the
water trap and the uppermost point in the bend of the Upipe) must be at least just as large in mm as half the negative pressure is in mm gauge.
A set of connection parts that fit the condensate connection are also included when a water trap is ordered from
Swegon.
BCKA dimensions
S
P
X
K
Fig. 19
BCKA
B
H
X
L
004
1039
546
215
453
006
1259
656
215
453
009
1459
756
215
453
014
1759
906
215
453
Pipe connections
Make sure that the deadweight and/or expansion forces of
the piping system will not be applied to the connections.
Use appropriate sealant for sealing the thread of the coil
connections.
Installing the water trap
The water trap must be filled with water before the unit is
started up. The drain pipe should discharge in such a way
that the adjacent unit sections and the building structure
won’t sustain damage. The drain pipe must be insulated
against the cold if it is run through a cold space. A heating
cable may be required.
If the coil is fitted on the suction side of the fan, it is especially important to fit a water trap.
Specifications are subject to alteration without notice.
www.swegon.se
25
GB.COOLER.INST.060501
12.2
Instructions for size 08-60 GOLD units
Coils with rectangular connections
The coil can be fitted to the ductwork or directly to the
unit. The coil should be jointed by means of slip clamps for
so-called PG connection and a sealing strip designed for
this purpose.
11.2.1Installation of TBKA, TBKC cooling coils
A. The coils shall be connected to the ducting as follows:
Coils with round connection spigots:
The coil is designed for direct connection to spiro ducts.
The coil should be secured to the duct by means of pop
rivets.
G
30
Ø 500
630
H
500
30
A
E
C
B
Fig. 21
500
105
688
105
50
Fig. 20
If a duct bend or some other unit section is situated upstream of the cooling coil, the distance to the coil should
be adequately long for avoiding a non-uniform air distribution across the coil. The design of the duct bend fitted
upstream of the coil must also be aerodynamically correct.
Cooling coil
For Cooler
size
Type
A
14
TBKA-2-100-040-3
400
18
TBKA-2-100-040-4
400
24
TBKA-2-100-040-5
24
B
C
E
G
H
RØ
Wgt. in kg,
excl. liquid
Filling
volume, L
1295 1000
148
113
625
25
89
9
1295 1000
148
113
625
32
95
12
400
1295 1000
148
113
625
32
101
14
TBKA-2-120-050-3
500
1595 1200
198
133
765
32
130
18
24
TBKA-2-140-060-3
600
1885 1400
243
170
940
32
172
25
34
TBKA-2-120-050-4
500
1595 1200
198
168
835
40
156
28
34
TBKA-2-140-060-4
600
1885 1400
243
170
940
32
184
31
48
TBKA-2-120-050-5
500
1595 1200
198
168
835
32
165
32
48
TBKA-2-140-060-5
600
1885 1400
243
170
940
40
197
37
60
TBKA-2-140-060-6
600
1885 1400
243
170
940
40
220
48
E
G
H
RØ
Wgt. in kg,
excl. liquid
Filling
volume, L
Cooling agent cooler
For Cooler
size
Type
A
24
TBCO-1-100-040-1
400
1191 1000
82
70
540
25
98
20
24
TBCO-1-120-050-1
500
1330 1200
30
20
540
25
58
20
24
TBCO-1-140-060-1
600
1530 1400
30
20
640
25
65
22
34
TBCO-1-120-050-2
500
1575 1200
188
158
815
32
153
32
34
TBCO-1-140-060-2
600
1875 1400
238
175
950
32
186
38
48
TBCO-1-120-050-3
500
1575 1200
188
158
815
32
162
36
48
TBCO-1-140-060-3
600
1875 1400
238
158
915
32
195
43
60
TBCO-1-140-060-4
600
1875 1400
238
158
915
32
208
47
26
www.swegon.se
B
C
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
Fig. 22
Cooling coil
For Cooler
size
Type
48
TBKA-2-160-080-3-0-1
60
TBKA-2-160-080-4-0-1
B
H
L
Wgt. in kg,
excl. liquid
Filling
volume, L
2311 1141
510
215
39
2311 1141
510
230
46
Cooling agent cooler
For Cooler
size
Type
48
TBCO-1-160-080-1-x
60
TBCO-1-160-080-2-x
B
L
RØ
Wgt. in kg,
excl. liquid
Filling
volume, L
2311 1141
510
32
225
46
2311 1141
510
32
250
53
Specifications are subject to alteration without notice.
H
www.swegon.se
27
GB.COOLER.INST.060501
B. The coil should be located as follows:
The coil is desiged for horizontal airflow. Double drain
connections enable an optional direction of airflow. The
tubes of the liquid circuit shall be horizontal to enable
venting and drainage.
The coils with round connection spigots are fitted with
double drain connections which enable optional directin
of airflow.
C. For the TBKA – coil for cold water – the capacity of the
coil is conditional on the direction of airflow through the
coil and the connection mode. For best capacity, the coil
shall be connected for counter-flow water circulation.
See Fig. 21a-b.
The lower connection shall be used for filling with water.
Vent the coil before commissioning.
G. The temperature sensor for the supply air should be
fitted as far downstream of the coil as practically posible
(at least 1.5 meter) to avoid incorrect readings, caused by
layering in the air downstream of the coil. However, the
bulb of the temperature sensor should be located opposite
the connections. See Fig. 22a and 22b.
Round connection
Temperature sensor
Zone within which the temperature
sensor should be vertically positioned
Fig.24a
Fig. 23a
Rectangular connection
Temperature sensor
Fig. 23b
D. The coil section shall be installed where it is accessible
for replacement and inspection. On coils with round duct
connection spigots, the inspection side can be dismantled.
E. The cooling coil shall be insulated in accordance with
local regulations for ventilation ducts and connected pipework in accordance with local trade standards.
F. On coils with round duct connection spigots, the drain
pipe shall be connected to the connection branch on the
outgoing air side of the coil. The connection on the ingoing air side shall be plugged.
28
www.swegon.se
Zone within which the temperature
sensor should be vertically positioned
Fig. 24b
H. To prevent frost damage on the TBKA water coil, antifreeze must be added to the water.
If for some reason anti-freeze cannot be used, other measures to protect the coil from freezing must be taken.
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
13
Connection to Ducting
The cooling coils for size 14 Coolers have - if they are to
be connected to a GOLD 08 unit - circular duct connections fitted with a rubber gasket. The coils designed for
connection to GOLD 14-60 units have rectangular duct
connections with rigidly mounted slip clamps.
The cooling coils for size 18 Coolers have - if they are to
be connected to a GOLD 14-60 - rectangular duct connections with rigidly mounted slip clamps.
The cooling coils and cooling agent coolers for size 24-60
Coolers have - if they are to be connected to a GOLD rectangular duct connections with rigidly mounted slip
clamps.
If the cooling coils are to be connected to the Basic air
handling unit, they are incorporated with other components as standard cooling coils for the Basic.
13.1 for COOLER 14 and 18. All items are supplied in kit form.
Included in the supply
COOLER
size
For end connection wall
facing the air handling unit
For end connection wall
facing the exhaust air duct
For end connection wall
facing the exhaust air duct
14
GOLD 08
Inlet end connection wall
with 400 mm dia.
connection
Connection frame with
slip-clamp joint,
800x400 mm1
—
14, 18
GOLD 14-60
Connection frame with
slip-clamp joint,
1000x400 mm
Connection frame with
slip-clamp joint,
1000x400 mm
—
14
BCEA/BASIC 004
Supplied without end
connection wall
Sealing plate for BCEA/BASIC2
Supplied without end
connection wall
Connection frame with
slip-clamp joint, 850x350
mm (TBXZ-108503523)
For air handling
unit
Accessory
18
BCEA/BASIC 006
Supplied without end
Supplied without end
connection wall
connection wall
1) This end connection wall does not have a circular connection; this
minimises the pressure drop. If connection is made to a circular
exhaust air duct, use a conical adapter as a transition piece.
Connection frame with
slip-clamp joint, 1100x500
mm (TBXZ-111005022)
2) A sealing plate is required for connection to the BCEA/BASIC 004
because the COOLER has smaller dimensions.
14Electrical Data
14.1 Cooling unit
The Cooler unit has pre-wired internal electrical connections and is test run prior to delivery.
All electrical equipment is housed in the electrical cubicle
behind the inspection panel.
Incorporated components:
• Safety isolating switch.
• Control circuit fuse.
• Contactors and motor protection/fuses for
compressors and pumps.
• Terminal blocks for internal/external connections.
• Circuit card for necessary functions and
communication with hand-held micro terminal.
Specifications are subject to alteration without notice.
www.swegon.se
29
GB.COOLER.INST.060501
15General Technical Data
COOLER size
14
18
24
14
7,6
18 24
9,6
11,8
34
48
60
Capacity
Cooling capacity, kW1
Power demand, kW2
34
48
60
16 20 22
Brine
Type of evaporator
Plate
heat
exchanger
Plate
heat
exchanger
Plate
heat
exchanger
Plate
heat
exchanger
Plate
heat
exchanger
Plate
heat
exchanger
Number 2 2 2 2 2 2
Brine flow (l/s)
0,7
1,0
1,1
1,4
1,35
1,63
Max. available
external pressure, kPa
50
70
40
50
60
70
Compressor
Type of compressor
Piston
Piston
Piston
Piston
Scroll
Scroll
Number 2 2 2 2 22
Capacity control, stages
3
3
3
3
3
3
Condenser/
Cooling agent cooler
Type
Direct
Direct
expansion
expansion
Number
Cooling agent flow (l/s)
Max. available
external pressure, kPa
Plate
heat
exchanger
Plate
heat
exchanger
Plate
heat
exchanger
Plate
heat
exchanger
–
–
–2 2 2 2
–
0,62
0,83
0,95
1,17
–
–
10
12
3025
Cooling agent
Type
R134a/
R134a/
R134a/
R134a/
R134a/
R407c
R407c
R407c
R407c
R407c
Number of circuits2 2 2 2 2
Volume, R134a, Kg 2,3 2,9 2,3
4,5
5,4
Volume, R407c, Kg 2,1
3,0
4,0
4,9
8,0
R134a/
R407c
2
8,2
8,0
Electrical connections
Power supply, Volt
400
400
Frequency, Hz
50
50
Fuse, A (delayed/delta-characteristic)20 25
400
50
32/35
400
50
35
400
50
63
400
50
63
Suitable for airhandling unit
GOLD
08, 14/20
14/20
BCEA/BASIC
004
006
1) The cooling capacities tabulated above are applicable to the following
data: Supply air upstream of the cooling coil 28 °C, 50% RH. Exhaust air
upstream of the COOLER (14 and 18) or cooling agent cooler (24-60) 32
°C. These data presuppose cooling energy recovery by means of a rotary
heat exchanger which then provides an outdoor temperature of 32 °C,
40% RH and an extract air temperature of 26 °C.
2) Applicable to operation under conditions described in footnote 1)
above.
30
www.swegon.se
14/20, 25/30, 25/30, 35/4025/30, 35/40,
35/40 50/60
006, 009
009, 014
014
35/40, 50/60
–
Sizing
Many factors influence which size of cooling unit and
which coils are required.
The new cooling unit is designed for meeting a variety of
conditions.
For sizing, it is recommendable to utilize the unit selection
program called PMWIN.
Specifications are subject to alteration without notice.
GB.COOLER.INST.060501
16
Mechanical Design
16.1.1 Dimensions and weights
See Fig. 23 - 25 and the table below.
16.1 Design
The refrigerating machine is incorporated into a casing
consisting of a framework of torsion resistant profiled
sections made of form rolled 1 mm thick aluminiumzinc plated sheet steel, Env. Class C4. The wall, top and
bottom panels are made of aluminium-zinc plated sheet
steel, Env. Class C4. They are constructed according to
the sandwich principle: 0.7 mm thick sheet steel + 50 mm
thick insulation + 0.7 mm thick sheet steel.
The size 14 and 18 Coolers are to be connected to the
exhaust air connection of the air handling unit by means
of slip clamps. The larger units stand alone and alongside
the air handling unit.
Wgt., kg
R1
Ø
R2
Ø
546 1666
-
28
18
1595 656 945
-
24
975 1075 1759 35
34
975 1075 1759 35
35
48
975 1200 1759 35
35
625
592
60
975 1200 1759 35
42
675
638
Size
B
14
985
H
Cooler 14
B
L
At site
Excl. packaging
incl. water
and water
306
300
28
325
318
35
445
415
555
523
Electrical connections
L
H
R2
End facing the air handling
unit
End facing the exhaust air
duct
Hose from safety
valve
Fig. 25
Cooler 18
B
L
H
End facing the air handling
unit
R2
R2
Electrical connections
End facing the exhaust air
duct
Hose from safety
valve
Fig. 26
Cooling Agent Cooler
Cooling Coil
Electrical connections
Cooler 24, 34, 48, 60.
B
L
R1
R1
R2
R2
H
Fig. 27
Specifications are subject to alteration without notice.
Hose from safety valve
www.swegon.se
31
GB.COOLER.INST.060501
17Other Particulars
Serial number
Every cooling unit has a specific serial number which together with its type designation forms a unique identification number for each unit. The serial number is stamped
on the identification plate affixed on the inspection cover
of the unit.
Standards
The electrical equipment meets the provisions of Electrical
Safety Standard ELSÄK-FS 1999:5 and is CE-labelled in accordance with PED and the Low Voltage Directive 73/23/
EEC with Harmonization Standard EN 60204-1.
Interference level
The Cooler is designed for installation in electical
environments where the Low Voltage Directive specifies
interference levels in accordance with the standards for
electromagnetic radiation in dwellings, offices, shops and
similar environment as well as in industrial environments.
18Environmental Documentation
18.1 Scrapping
The design of the unit makes it easy to dismantle and
sort according to the various types of material used in its
manufacture. When the unit has outlived its useful service
life, an accredited re-cycling firm should be engaged.
95% of the GOLD Cooler is re-cyclable.
Swegon AB is affiliated with REPA,
Reg. no. 5560778465.
Get in touch with Swegon AB, phone: +46 (0)512-32200 if
you have any questions on dismantling and scrapping the
GOLD Cooler or the unit’s environmental impact.
32
www.swegon.se
Specifications are subject to alteration without notice.
ANNEX IIA
(Storbritannien, Irland)
GB.COOLER.INST.060501
Compliance Declaration
We at:
DECLARATION OF CONFORMITY
We,
Swegon AB
Box 300
S-535 23 KVÄNUM
assure on our own responsibility that the air handling unit of the following type:
BC (fitted with control system)
CACA
CoolDX
GA (fitted with control system)
GOLD
GOLD Cooler
LBTA
LLVC
LLVD
LMTA
LPMA-1
LTCE
LTCW (fitted with control system)
TA (fitted with control system)
VVVA
VVRV
covered by this declaration, comforms to the following Standards:
EN 292-1, 2; EN 294; EN 60204-1; EN 61000-6-2; and EN 61000-6-3
according to the provisions in Directives: 98/37/EG , 89/336/EEC and 73/23/EEC.
This assurance is applicable only if the air handling unit has been installed according to the
instructions and if the air handling unit has not been altered in any way.
Kvänum, February 20, 2006
Thord Gustafsson,
Quality and Environmental Policy Manager
Specifications are subject to alteration without notice.
www.swegon.se
33
GB.COOLER.INST.060501
www.swegon.com
Swegon AB, Box 300, SE-535 23 Kvänum +46 512 32200 www.swegon.com
Download