CCWF-Nurse Call System Replacement 08-091 State of California Department of Corrections and Rehabilitation SECTION 16902 ELECTRONIC CONTROLS AND RELAYS PART 1 1.1 GENERAL SUMMARY A. Section Includes: 1. Pushbutton and selector switches. 2. Control stations. 3. Relays. 4. Time delay relays. 5. Control power transformers. 6. Control panels. 7. Time switches. 8. Indicator lights. B. Products Furnished but Not Installed Under This Section: 1. Section 15970 - Controls: Installation of pressure, temperature, and flow switches in piping, ductwork, and mechanical equipment. C. Related Sections: 1. Section 16010 - Basic Electrical Requirements. 2. Section 16160 - Cabinets: Cabinets and terminal blocks. 3. Section 16161 – Cabinets and Enclosures for Electrified Fence System. 4. Section 16485 - Contactors. 1.2 REFERENCES A. CEC - 2007 California Electrical Code. B. NEMA ICS 1 - General Standards for Industrial Control Systems. C. NEMA ICS 2 - Standards for Industrial Control Devices, Controllers and Assemblies. D. NEMA ICS 6 - Enclosures for Industrial Controls and Systems. E. NEMA ST 1 - Standard for Specialty Transformers (Except General Purpose Type). ELECTRONICS CONTROLS AND RELAY 16902 - 1 CCWF-Nurse Call System Replacement 08-091 1.3 State of California Department of Corrections and Rehabilitation SUBMITTALS A. Submit under provisions of Division 1. B. Submit shop drawings to NEMA ICS 1 indicating control panel layouts, wiring connections and diagrams, dimensions, support points. C. Submit product data for each component specified. D. Special Requirements for Control Equipment Related to the Electrified Fence: 1. Phase 1 as defined in Section 16900: Product data for each component specified. 2. Phase 2 as defined in Section 16900: Submit shop drawings per NEMA ICS 1 indicating control panel layouts, wiring connections and diagrams, dimensions support points. 1.4 A. 1.5 AS-BUILT DOCUMENTS Accurately record actual locations of control equipment. Revise diagrams included in Drawings to reflect actual control device connections. OPERATION AND MAINTENANCE DATA A. Submit operation data under provisions of Division 1. B. Include instructions for adjusting and resetting time delay relays, timers, and counters. C. Submit maintenance data under provisions of Division 1. D. Include recommended preventive maintenance procedures and materials. 1.6 EXTRA MATERIALS A. Submit under provisions of Division 1. B. Lamps: Furnish 10 percent of quantity provided. C. For electrified fence equipment, submit extra materials as specified in Section 01431. ELECTRONICS CONTROLS AND RELAY 16902 - 2 CCWF-Nurse Call System Replacement 08-091 PART 2 2.1 State of California Department of Corrections and Rehabilitation PRODUCTS MANUFACTURERS A. Allen-Bradley Co. B. General Electric Co. C. Westinghouse. D. Substitutions: Under provisions of Division 1. E. Allen-Bradley bulletin numbers are used to indicate the level of quality required and for reference. 2.2 CONTROL SWITCHES AND STATIONS A. Contacts: NEMA ICS 2. B. Contact Ratings: NEMA ICS 2; A300. C. Terminations: Quick connect terminals. D. Selector Switches Operators: NEMA ICS 2; two- or three-position rotary selector switch; Model 800MR. E. Pushbutton Operator: NEMA ICS 2; recessed type; Model 800MR. F. Control Stations: NEMA ICS 2; Standard duty oiltight type pushbutton station; with Model 800MR switches. G. Limit Switches: NEMA type 13 Model 8027. H. Pressure Switches: Model 836. I. Temperature Switches: Model 837. J. Proximity Switches: Model 871. K. Other control devices as required for the function indicated shall be of the same quality with similar features. ELECTRONICS CONTROLS AND RELAY 16902 - 3 CCWF-Nurse Call System Replacement 08-091 2.3 State of California Department of Corrections and Rehabilitation ENCLOSURES A. Control Station Enclosure: NEMA ICS 6; Type 1 unless otherwise indicated. B. Relay Enclosure: NEMA ICS 6; Type 1 unless otherwise indicated. 2.4 A. FABRICATION Control Panels: Shop fabricate control panels to NEMA ICS 1, using cabinets and terminal blocks furnished under the provisions of Sections 16160 and 16161. PART 3 3.1 EXECUTION INSTALLATION A. Install devices and equipment in accordance with manufacturer's instructions. B. Install individual relays and time delay relays in enclosures. C. Install cabinets under the provisions of Sections 16160 and 16161. D. Make electrical wiring interconnections as shown on Drawings. END OF SECTION ELECTRONICS CONTROLS AND RELAY 16902 - 4