RMKPANEL2X4 - RECESSED DRYWALL KIT
INSTALLATION INSTRUCTIONS
D
Thank you for buying RAB lighting fixtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.
Call the Marketing Department at 888-RAB-1000 or email: marketing@rabweb.com
.250
IMPORTANT
1.125
[28,56]
[6,35]
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding
1.500
is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE
INSTALLATION CODE BY A
1.125 WITH THE APPLICABLE
[38,1]
[28,58]
PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
C
Make certain power is OFF before installing or maintaining fixture.
SAFETY INSTRUCTIONS
WARNING: Risk of fire or electric shock. Suitable for Damp
locations.
WARNING: Install Drywall Kit & Panel per local codes.
Suitable for installation in Sheet Rock/ Plasterboard in
both Insulated Ceilings and Non-Insulated Ceilings. Not for
continuous row mounting.
WARNING: Do not handle energized fixture when hands are
wet, when standing on wet or damp surfaces, or in water.
WARNING: Vapor barrier must be suitable for 90 ͦ C.
WARNING: Drywall kit to be independently supported to
building structure.
Drywall Kit 2X4
Order CAT# RMKPANEL2X4
B
RAB
L I G H T I N G
TITLE
Drywall Kit 2X4
170 LUDLOW AVE., NORTHVALE, NJ 07647
SHEET ROCK FLANGE KITS
PANEL 2X4 Housing 1X4, 2X4, 2X2
(Available
uponPART
request)
MATERIAL:
No.:
DRAWING NAME:
DRYWALL MOUNTING
THIS DRAWING AND THE INFORMATION IT DISCLOSES IS THE EXCLUSIVE
The fixture is suitable
only for INDOOR RECESSED CEILING
PROPERTY OF RAB LIGHTING, INCORPORATED
ANY REPRODUCTION
OR USE
OF THIS DRAWING
WITHOUT
THE WRITTEN is
CONSENT OF
application. Nominal
Sheet
Rock
cut-out
opening
RAB LIGHTING, INC. IS STRICTLY PROHIBITED. RAB CONFIDENTIAL PATENT PENDING
24 5/8” x 48 5/8”.
3
2
DATE:
REV DATE:
A
REV
8-5-2013
DRAWN BY: CDS
SCALE
2 OF 2
SHEET:
1
To mount in an insulated or non-insulated - sheet rock ceiling
follow the steps below.
1. Assemble the four pieces of the Drywall Kit 2X4 with the
screws provided.
Clip
2. Support the Drywall Kit 2x4 to the building structure by
Hanger Wires (by others), alternatively screw to Wood
Blocking (by others) or black iron (by others).
Hanger Wires (by others)
3. Bend the pre-installed Clips (4) flat to the PANEL 2X4
Housing.
4. Follow wiring directions on fixture installation instruction
sheet to complete electrical splices.
5. Rotate and slide the PANEL 2X4 Housing as required
to fit through the drywall opening as indicated by the
directional arrow in figure and place it on the Drywall Kit.
Wood Blocking (by others)
5”
5”
Drywall Kit 2X4
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation
or maintenance.
Easy Installation & Product Help
©2013 RAB LIGHTING Inc.
Northvale, New Jersey 07647 USA
RMKPANEL2X4 IN-1013
Tech Help Line
Call our experts 888 RAB-1000
rabweb.com
Visit our website for product info
email
Answered promptly sales@rabweb.com
1
4
4
3
2
RMKPANEL1X4 - RECESSED DRYWALL KIT
INSTALLATION INSTRUCTIONS
D
Thank you for buying RAB lighting fixtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.
Call the Marketing Department at 888-RAB-1000 or email: marketing@rabweb.com
.250
1.125
[28,56]
[6,35]
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding
1.500
1.125 WITH THE APPLICABLE
is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE
INSTALLATION CODE BY A
[38,1]
[28,58]
PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
C
Make certain power is OFF before installing or maintaining fixture.
SAFETY INSTRUCTIONS
WARNING: Risk of fire or electric shock. Suitable for Damp
locations.
WARNING: Install Drywall Kit & Panel per local codes.
Suitable for installation in Sheet Rock/ Plasterboard in
both Insulated Ceilings and Non-Insulated Ceilings. Not for
continuous row mounting.
WARNING: Do not handle energized fixture when hands are
wet, when standing on wet or damp surfaces, or in water.
WARNING: Vapor barrier must be suitable for 90 ͦ C.
WARNING: Drywall kit to be independently supported to
building structure.
Drywall Kit 1X4
Order CAT# RMKPANEL1X4
B
RAB
L I G H T I N G
TITLE
DRYWALL MOUNTING
THIS DRAWING AND THE INFORMATION IT DISCLOSES IS THE EXCLUSIVE
The fixture is suitable
onlyOF
forRAB
INDOOR
RECESSED
CEILING
PROPERTY
LIGHTING,
INCORPORATED
ANY REPRODUCTION OR USE OF THIS DRAWING WITHOUT THE WRITTEN CONSENT OF
application. Nominal
Sheet
Rock
cut-out
opening
is PENDING
RAB LIGHTING, INC. IS STRICTLY PROHIBITED. RAB CONFIDENTIAL PATENT
3
2
12 5/8” x 48 5/8”.
170 LUDLOW AVE., NORTHVALE, NJ 07647
SHEET ROCK FLANGE KITS
1X4, 2X4, 2X2
PANEL
1X4 Housing
MATERIAL:
PART No.:
(Available upon request)
DATE:
DRAWING NAME:
REV DATE:
A
Drywall Kit 1X4
REV
8-5-2013
DRAWN BY: CDS
SCALE
2 OF 2
SHEET:
1
To mount in an insulated or non-insulated - sheet rock ceiling
follow the steps below.
1. Assemble the four pieces of the Drywall Kit 1X4 with the
screws provided.
Clip
2. Support the Drywall Kit 1x4 to the building structure by
Hanger Wires (by others), alternatively screw to Wood
Blocking (by others) or black iron (by others).
Hanger Wires (by others)
3. Bend the pre-installed Clips (4) flat to the PANEL 1X4
Housing.
4. Follow wiring directions on fixture installation instruction
sheet to complete electrical splices.
5. Rotate and slide the PANEL 1X4 Housing as required
to fit through the drywall opening as indicated by the
directional arrow in figure and place it on the Drywall Kit.
Wood Blocking (by others)
5”
5”
Drywall Kit 1X4
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation
or maintenance.
Easy Installation & Product Help
©2013 RAB LIGHTING Inc.
Northvale, New Jersey 07647 USA
RMKPANEL1X4 IN-1013
Tech Help Line
Call our experts 888 RAB-1000
rabweb.com
Visit our website for product info
email
Answered promptly sales@rabweb.com
1
4
4
3
2
RMKPANEL2X2 - RECESSED DRYWALL KIT
INSTALLATION INSTRUCTIONS
D
Thank you for buying RAB lighting fixtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.
Call the Marketing Department at 888-RAB-1000 or email: marketing@rabweb.com
.250
IMPORTANT
1.125
[28,56]
[6,35]
4
3
2
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding
1.500
is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE
INSTALLATION CODE BY A
1.125 WITH THE APPLICABLE
[38,1]
[28,58]
PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
C
Make certain power is OFF before installing or maintaining fixture.
D
SAFETY INSTRUCTIONS
Drywall Kit 2X2
Order CAT# RMKPANEL2X2
C
WARNING: Risk of fire or electric shock. Suitable for Damp
locations.
WARNING: Install Drywall Kit & Panel per local codes.
Suitable for installation in Sheet Rock/ Plasterboard in
both Insulated Ceilings and Non-Insulated Ceilings. Not for
continuous row mounting.
WARNING: Do not handle energized fixture when hands are
wet, when standing on wet or damp surfaces, or in water.
WARNING: Vapor barrier must be suitable for 90 ͦ C.
WARNING: Drywall kit to be independently supported to
building structure.
B
B
RAB
L I G H T I N G
TITLE
A
170 LUDLOW AVE., NORTHVALE, NJ 07647
THIS DRAWING AND THE INFORMATION IT DISCLOSES IS THE EXCLUSIVE
SHEET ROCK FLANGE KITS
1X4, 2X4, 2X2
PROPERTY OF RAB LIGHTING, INCORPORATED
ANY REPRODUCTION OR USE OF THIS DRAWING WITHOUT THE WRITTEN CONSENT OF
RAB LIGHTING, INC. IS STRICTLY PROHIBITED. RAB CONFIDENTIAL PATENT PENDING
4
DRYWALL MOUNTING
MATERIAL:
THIS DRAWING AND THE INFORMATION IT DISCLOSES IS THE EXCLUSIVE
The fixture is suitable
only for INDOOR RECESSED CEILING
PROPERTY OF RAB LIGHTING, INCORPORATED
ANY REPRODUCTION
OR USE
OF THIS DRAWING
WITHOUT
THE WRITTEN is
CONSENT OF
application. Nominal
Sheet
Rock
cut-out
opening
RAB LIGHTING, INC. IS STRICTLY PROHIBITED. RAB CONFIDENTIAL PATENT PENDING
24 5/8” x 24 5/8”.
3
2
.250
[6,35]
PART No.:
DRAWING NAME:
DATE:
REV DATE:
PANEL 2X2 Housing8-5-2013
(Available
uponSCALE
request)
DRAWN BY: CDS
3
2
A
Drywall Kit 2X2
REV
2 OF 2
SHEET:
1
To mount in an insulated or non-insulated - sheet rock ceiling
follow the steps below.
1. Assemble the four pieces of the Drywall Kit 2X2 with the
screws provided.
Clip
2. Support the Drywall Kit 2x2 to the building structure by
Hanger Wires (by others), alternatively screw to Wood
Blocking (by others) or black iron (by others).
Hanger Wires (by others)
3. Bend the pre-installed Clips (4) flat to the PANEL 2X2
Housing.
4. Follow wiring directions on fixture installation instruction
sheet to complete electrical splices.
5. Rotate and slide the PANEL 2X2 Housing as required
to fit through the drywall opening as indicated by the
directional arrow in figure and place it on the Drywall Kit.
Wood Blocking (by others)
5”
5”
Drywall Kit 2X2
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation