Saskatchewan Amendments - Saskatchewan Publications Centre

advertisement
1
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
The
Canadian Electrical
Code (Saskatchewan
Amendments)
Regulations, 1995
Repealed
by Chapter E-6.3 Reg 6 (effective March 18, 1999).
Formerly
Chapter E-6.3 Reg 3 (effective September 7, 1995) as
amended by Saskatchewan Regulations 1/96.
NOTE:
This consolidation is not official. Amendments have been
incorporated for convenience of reference and the original statutes
and regulations should be consulted for all purposes of interpretation
and application of the law. In order to preserve the integrity of the
original statutes and regulations, errors that may have appeared are
reproduced in this consolidation.
2
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
CHAPTER E-6.3 REG 3
The Electrical Inspection Act, 1993
Title
1 These regulations may be cited as The Canadian Electrical Code (Saskatchewan
Amendments) Regulations, 1995.
Canadian Electrical Code amended
2 Part I of the latest prescribed edition of the Canadian Electrical Code, being
Canadian Standards Association standard C22.1-1994, is amended in the manner
set forth in the Appendix.
22 Sep 95 cE-6.3 Reg 3 s2.
Repeal
3(1) The Canadian Electrical Code (Saskatchewan Amendments) Regulations,
1991, being chapter E-6.2 Reg 2 of The Revised Regulations of Saskatchewan, are
repealed.
(2) The Canadian Electrical Code (Saskatchewan Amendments) Regulations,
being chapter E-7.1 Reg 3 of The Revised Regulations of Saskatchewan, are
repealed.
22 Sep 95 cE-6.3 Reg 3 s3.
APPENDIX
PREFACE AND SCOPE
The Canadian Electrical code, Seventeenth Edition, as supplemented and amended
by these requirements, issued under Section 5 of The Electrical Inspection Act, 1993,
shall govern the workmanship and all other matters whatever pertaining to electrical
equipment and the installation of electrical equipment in or upon any land, buildings,
structures and premises. It contains supplementary and amendatory requirements
which by their inclusion herein are adopted as requirements under Section 5 of The
Electrical Inspection Act, 1993.
Section 0:
Definitions
Section 0 is supplemented by the following:
Grade Level means the level of earth surrounding a building, and in cases where
the electrical installation is performed before the building is back-filled, shall be
considered as that level 50 mm below the basement windows, other than those in
window wells, or 150 mm below siding, or stucco line on basementless homes.
Kiosk means an enclosure of steel or a combination of masonry and steel and
which may be partly buried and within which may be installed a standard oil-filled
transformer and protective equipment.
3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Pad-mounted transformer means a transformer consisting of compartmented
steel enclosure with space for standard oil-filled transformer, high-voltage protective
and switching equipment and low-voltage feeder connections or distribution
transformers of special design to which compartmented enclosures can be attached, all
of such equipment designed to be mounted on a concrete or fibreglass pad of suitable
dimensions on grade.
Rural Area means an area outside of the limits of any hamlet, village, town or
city.
Service Factor means a multiplier which, when applied to the rated horsepower
of an AC motor, the rated armature current of a DC motor, or to the rated output of a
generator, indicates a permissible loading which may be carried continuously at rated
voltage and frequency.
Service Stack means that portion of service conductors including raceway,
armour or sheathing, between the point of attachment to the service supply and the
consumers service box or equivalent service equipment.
Shallow Box means an outlet box with a depth less than 1 1/2 inches and a
minimum depth of 1/2 inch.
Tamperproof as applied to pad-mounted transformers and kiosks, means that
live parts cannot be contacted by inserting through any openings, wire and other
foreign objects, nor can access to the unit be gained by the use of common tools. Such
units will not have any covers or doors which can be opened by the removal of
externally accessible bolts or hinge pins and such access doors as are provided have
adequate provision for padlocking. In addition, such equipment has no external means
for operation of switching equipment nor will it have any glass-viewing windows.
Temporary Wiring means a wiring installation to be utilized for a period not
exceeding 90 days, unless otherwise stipulated.
Section 2:
General Rules
2-010 Posting of Permit
Rule 2-010 is deleted.
2-014 Plans for High-Voltage Installations
Rule 2-014 is deleted and the following substituted.
Plans for high-voltage installations shall be submitted for examination and
review and shall contain the following data:
(1)
Schematic (One-Line Diagram)
This is a diagram which indicates by means of single lines and simplified symbols
the sequence of component devices or parts of an electric circuit or system of
circuits and should indicate:
(a) All voltages of the proposed installation.
(b) Transformer-bank capacity, rating, impedance, type of cooling, etc.
(c) Primary and secondary protective and switching devices and their shortcircuit capacity and rating.
4
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
(d) Where additions or alterations are being made, clearly distinguished
from existing or unchanged portions of the installation.
(2) Site Plan
This should indicate the location of the station, relative to buildings, structures,
roads, property lines and equipment not associated with the station and the route
of supply, if possible.
(3) Electrical Arrangement
This portion of the plan must provide the following data:
(a) Plan, elevation and profile views of the electrical and physical
arrangement of the equipment.
(b) Dimensions to clearly indicate the electrical physical and work clearances
and relative locations of the equipment.
(c) Fencing arrangement where required on outdoor substations.
(d) Details of vault construction where required in indoor installations.
(e)
Grounding details.
(f) Interlocking arrangements and an explanation of the sequence of
operation.
(g) A Bill of Material properly referenced to the drawings.
(h) Provisions made for metering equipment where required.
(i) Manufacturers drawings of tower structures, power transformer and of
metalclad switchgear, showing the internal arrangement of equipment,
means of access and provisions for personnel safety. Except in special cases,
manufacturers drawings of other equipment will not be required.
(j)
Copy of Electrical Specifications
(4) One copy of all plans and specifications shall be submitted for examination
prior to construction, and the submitter will receive a report on the proposed
installation.
(5) All plans must be submitted before service connection is authorized.
2-015 Plans for Low Voltage Installations (See Appendix B)
Rule 2-015 is added.
Plans and specifications for installations as required by Section 19 of the Act
shall be submitted where ampacities exceed 200 Amps or voltages exceed 300 V, and in
hazardous locations, other than service stations or oil wells, and shall contain the
following:
(1) calculated loads;
(2) main and feeder sizes; and
(3) maximum short circuit current available at each point of application of
protective devices in installations exceeding 600 amperes.
5
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
(4) a schematic (one-line diagram) indicating all voltages of the proposed
installation.
(5) One copy of all plans and specifications shall be submitted for examination
prior to construction, and the submitter will receive a report on the proposed
installation.
2-021 Removal of Substandard Equipment
Rule 2-021 is added.
All dead or disused conductors and equipment which do not conform to present
requirements shall either be removed from the building, where exposed, or otherwise
rendered useless for electrical purposes, to the satisfaction of the Inspector.
2-028 Availability of Work for Inspection
Rule 2-028 is amended as follows:
An inspector may post a notice requiring that an electrical installation not be
rendered inaccessible by sheathing of walls or backfilling of trenches, and concealment
of such wiring shall only be done after it has been approved.
2-031 Deviation or Postponement
Rule 2-031 is added.
Request for special permission shall be made in writing, in duplicate, giving all
details pertaining to the requests; if acceptable, permission applying to the particular
installation will be confirmed in writing.
2-033 Lightning Protection
Rule 2-033 is added.
Installation of systems for the protection of buildings and other structures from
lightning damage shall comply with CAN/CSA B72-M 87 Installation Code for
Lightning Protection Systems.
2-203 Cables Awaiting Utilization Equipment
Rule 2-203 is added.
Where utilization equipment is not available for connection, the circuits
shall be terminated in a junction box complete with cover.
2-322 Electrical Equipment Near Gas Meters
Rule 2-322 is deleted and the following substituted:
Electric meters, receptacles, and other arc producing electrical equipment
shall not be installed within a 900 mm of a meter or pressure regulator used to
measure or regulate natural gas, manufactured gas, or liquefied petroleum gases
which are distributed in a gaseous state.
2-400(4) Weatherproof Enclosure Terminations
2-400(4) added as follows:
Raceways or cables shall not enter a weatherproof enclosure, unless the enclosure
is provided with an approved weatherproof fitting for termination.
6
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Section 4:
Conductors
4-005 Conductors Exposed to High Temperatures
Rule 4-005 is added.
(1) Conductors in raceways located on roofs directly exposed to the sun shall be
deemed to have an ambient temperature of 50 degrees C.
(2) Conductors in cables placed above thermal insulation in unventilated attic
spaces shall be considered as being exposed to not less than 50 degrees C.
(3) Subrule (2) pertains to high ambient conditions in unventilated attic spaces.
It is to be noted that natural ventilation is not mentioned. A ventilated attic space
means a mechanical ventilation and thermostaticly controlled system is in place to
maintain an inexcessive ambient temperature in an attic space.
4-022 Size of Neutral Conductor
Rule 4-022 is supplemented as follows:
(5) For residential services without electric heat loads, the size of
neutral conductor shall be not less than two trade sizes smaller than the
ungrounded conductors and not less than #8 Cu. or #6 Al.
4-036 Colour of Conductors
Rule 4-036 is supplemented as follows:
(6) No 240 volt single-phase load from a 4 wire Delta connected system
shall be connected to:
(a)
the red colored phase-A, or
(b)
from a three phase panel.
Section 6: Low-potential Services
6-111 Renewal of Services
Rule 6-111 is added.
(1) Where a building is relocated, or where additional loading exceeds the
capacity of the service in an existing structure, adequate alterations shall be made to
the existing substandard service, or a new service entrance of adequate capacity shall
be installed to replace the substandard service.
(2) Where a permit is required for connection or re-connection of an
electric service, the electrical service shall be made to comply with the
requirements of the current Canadian Electrical Code.
6-115 Service Splitter
Rule 6-115 is added.
Where an outdoor splitter is required for connection of utility conductors to
consumer service conductors the following shall apply:
7
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
(1) Splitter boxes shall be constructed of code gauge steel and shall be CSA
approved for outdoor use (TYPE 3R) with covers secured by bolts or non-slotted
screws.
(2) If locking provisions are furnished, such provisions must be for padlocking
only, with keyed handles strictly prohibited.
(3) The boxes shall contain the required number of terminal blocks or connectors
to accommodate termination of the utility service cables.
(4) Terminals and duct openings into the splitter box shall be arranged to allow
for a bending radius of not less than 180 mm for the utility cables.
(5) The bottom of the box shall be mounted a minimum height of 0.6 m from grade
level, and the top shall not extend beyond a maximum height of 1.8 m from grade level.
(6) The dimensions of the enclosures shall be in accordance with those for
instrument transformer enclosures as specified by the supply authority.
6-200 Service Equipment
Rule 6-200 is supplemented as follows:
(4) Where a panelboard can employ more than two single-pole breakers,
one two-pole breaker, or one three-pole breaker they shall be installed in an
approved assembly on the load side of a main fused switch or breaker.
(5) A single phase meter socket rated at 400 Amps or less with dual wire
connectors on the load side shall be permitted to have two subdivisions made
in the meter socket provided such subdivisions are not contained in the same
building.
6-206 Consumers Service Equipment Location
Rule 6-206(1) is supplemented as follows:
(f) within 6 conduit meters of the point where the service conductors enter
the building provided such conductors are in rigid conduit, EMT, metal
armour, or metal sheathing.
(g) Service boxes or combination service and panelboards shall not be
recessed in walls containing thermal insulation.
6-300 Underground Consumers Services
Subrule (1) is deleted and the following substituted therefor:
(1) Consumer service conductors run underground from an underground supply
system or from a pole shall be:
(a) installed in rigid conduit and be of a type acceptable for use in wet
locations as indicated in Table 19; or
(b) single and multi-conductor armoured cables, metallic sheathed cables or
concentric neutral cables in accordance with Table 19 for service entrance use
below ground providing that:
(i)
the installation is in accordance with rule 12-012, and
(ii) a rigid conduit is used for mechanical protection where portions of
the cable are exposed to injury, and
8
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
(iii) there is no splice or joint in the cable from the point of connection
at the supply service to the point of connection at the service equipment
in the building, and
(iv) all cables are protected with a corrosion resistant outer covering in
accordance with rule 2-112.
(v) when USEB 90 cable is used as a subservice, a subservice switch
and a ground electrode shall be required. USEB 90 cable is not to be
used as a sub-service feeder within the same building.
(vi) an additional conductor installed together with and alongside of
a 3 conductor cable shall not be accepted for a 3 phase 4 wire installation
and only a 4 conductor cable shall be permitted.
6-302 Consumers Service Conductors
Subrule 1(k) is added as follows:
(k) Liquid-tight flexible conduit in short lengths, where flexibility is
required, or protection from liquids, vapours or solids is necessary.
6-308 Bare Neutral Service Conductors
Rule 6-308 is extended as follows:
(2) The bare neutral conductor must be terminated in the main service
disconnect.
(3) The neutral conductor in an underground service to any type of premises shall
not be bare or unjacketed when directly buried in the earth.
6-312 Condensation in Service Conduit
Subrule (1) is deleted and the following substituted therefor:
(1) Service conduit or the equivalent shall be effectively drained outdoors and
sealed with an electrically approved duct sealant.
Section 8: Demand Factors
8-106 Use of Demand Factors
Subrule (4) is deleted and the following substituted therefor:
(4) Where it is known the electric space heating, car plug heating loads and air
conditioning loads will not be used simultaneously, whichever is the greater load shall
be used in calculating the demand.
8-202 Apartments
Rule 8-202 is supplemented as follows:
(5) Notwithstanding subrule (1), an existing residential unit with only one or
two rooms, that is equipped with a range, may have service feeder conductors rated at
not less than 40 amperes.
9
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Section 10: Grounding
10-204
Grounding Connections for Alternating-Current Systems
Paragraph (b) of subrule 10-204(1) is supplemented as follows:
NOTE: The term “another device specifically intended for the purpose located in
the grounding circuit” refers to tingle voltage filter or similar devices.
10-302
See Diagram 27 for assistance in conductor enclosure bonding.
10-406
Non Electrical Equipment
Subrule (4) is deleted and the following substituted therefor:
(4) All metallic gas piping shall be made electrically continuous and shall be
bonded in accordance with the requirements of subrule (2).
10-606
See Diagram 27 for assistance in bonding of service conductors.
10-702
Artificial Electrodes
Subrule (3) of Rule 10-702 is supplemented as follows:
(f) be galvanized or provided with other corrosion resisting cladding.
Rule 10-702 is extended as follows:
(7) A driven electrode, which must protrude 150 mm above grade for accessibility
of the connection, shall be bent towards the building or pole to which it is adjacent.
(8) Additional electrodes, as required by rule 10-702 may be buried completely
below grade.
10-808
Equipment Bonding Conductors
Rule 10-808 is supplemented as follows:
(8) Aluminum shall not be used for an equipment bonding conductor where
corrosion may occur, as at buried electrodes or at water pipes.
Section 12: Wiring Methods
12-012
Conductors Buried in Earth
Subrule (4) is deleted and the following substituted therefor:
(4) Direct buried conductors or cables shall be installed so that they run
adjacent to each other and do not cross over each other and covered with a
layer of earth free of particles larger than 6 mm, to a depth of 75 mm below
and above the conductors.
Subrule (13) of Rule 12-012 is supplemented as follows:
(13) Underground cable, or conductors installed under a building shall be in a
raceway that extends beyond the outside walls of the building.
12-013
Burial of Conductors in Proximity to Gas Lines
(1) No electrical wiring shall be installed within 600 mm of a utility natural gas
service.
10
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
(2) Electrical wiring may be installed in the same trench as customer-owned
propane or natural gas lines provided the conductors are placed at a greater depth and
a separation of at least 300 mm of earth or 150 mm if a treated plank is installed
between the piping and conductor.
12-021
Nylon Cable Ties
Rule 12-021 is added:
The use of nylon cable ties will be allowed only when they properly
support cables in an approved manner.
12-200
Open Wiring Rules
Rule 12-200 is extended as follows:
In all new indoor installations no open wiring shall be installed except by special
permission.
12-318
Use of Neutral-Supported Cables (See Appendix D-15 for Sag Table)
Clause (e) is deleted and the following substituted therefor:
(e)
Where dead-ended, the messenger of the neutral-supported cable shall:
(i) be anchored, by means of an approved anchoring device, to a
bolted hook, bolted insulator, or bolted bracket with eye; and
(ii) be provided with a tail for the connection thereto of the neutral
conductor.
12-1118
Rule 12-1118 is amended as follows;
A minimum of one expansion joint shall be installed for every 12 lineal
meters of conduit in a run.
12-3026 See Diagram 27 for assistance in terminating to avoid heating when
single conductor cables enter a metal box.
Section 14:
14-501
Protection & Control
Mounting Height of Switches and Circuit Breakers
Rule 14-501 is added.
Except as provided by rule 26-442(2) Switches and circuit breakers shall
be so installed that the centre of the grip of the operating handle when in its
highest position will not be more than 2 m above the floor or working
platform.
Section 18: Hazardous Locations
NOTE:
See Diagram 26 for assistance with sealing in hazardous areas.
18-403 Line Grain Elevators, Farm Elevators, Seed Cleaning Plants and
Feed Mills
11
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Rule 18-403 is added as follows:
Line grain elevators, farm elevators, seed cleaning plants and feed mills shall be
classified hazardous locations as shown in Diagram 11, 12 & 13.
18-405
Ammonia Compressor Rooms (see Appendix B)
Rule 18-405 is added as follows:
When ammonia is used in a refrigerant system the room shall be
considered Class 1, Div 2 hazardous location unless the room is constructed
to Class T machinery room as specified in CSA Standard B52-95 Mechanical
Refrigeration Code.
Section 20: Flammable Liquid Dispensing and Service Stations, Garages,
Bulk Storage Plants, Finishing Processes, and Aircraft Hangars
20-004 Rule 20-004 is supplemented as follows: (Refer to diagram 14 &15 for
area classification)
(11) Where above ground dispensing tanks (Envirotanks) are installed
an area of 1.5 m around the storage tank and an area of 450 mm above grade
extending 6 m in all directions from the tank shall be classified as Class 1
Division 2.
20-035
Rule 20-035 is added as follows:
Domestic heating propane tanks shall meet the requirements of Table 63
Part J.
20-102 Diagram 16 is included to assist in determining hazardous area
classification in commercial garages and repair shops.
Bulk Storage Plants
20-301
Anhydrous Ammonia Plants
Rule 20-301 is added.
Anhydrous ammonia distribution or bulk storage plants shall be wired in
accordance with Rules 20-302 to 20-312 and the Boiler and Pressure Vessel Act and
current Regulations 361-77 and 1983 amendments.
20-302 Diagrams 17 & 18 are included to assist in determining hazardous
area classification for flammable liquids bulk plants.
Finishing Processes
20-402 Diagram 19 is included to assist in determining hazardous area
classification for finishing processes.
20-403
Fibreglass Finishing and Storage
12
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Rule 20-403 is added.
Fibreglass manufacturing, finishing, or raw material storage areas shall be wired
in accordance with Rules 20-400.
20-502 Diagram 20 is included to assist in determining hazardous area
classifications for aircraft hangars.
Section 22: Wet & Corrosive Locations
22-700
Bulk Fertilizer Storage
Rule 22-700 is added.
(1) All equipment in ammonium nitrate bulk storage structures shall be considered
as subject to corrosion from a combination of the fertilizer dust and moisture.
(2) Raceways shall be PVC or aluminum, with fittings and enclosure entries of
such design as to not constitute dissimilar metals in contact with each other, and to
exclude dust.
(3) Teck 90 cable shall be permitted to be installed in bulk fertilizer storage
structures.
22-800
Sewage Lift & Treatment Plants
(1) Classification of such areas shall be as follows:
(a) Unless provided with adequate heating and ventilation, all below
ground location suitably cut off from locations in which sewage gases are
present, shall be deemed Category 1 locations.
(b) All locations in which sewage gases are present shall be deemed
Category 2 locations.
(c) All locations suitably cut off from Category 2 locations and not classed as
Category 1 may be considered ordinary locations.
(d) Locations not suitable cut off from a Category 2 location may be
considered ordinary locations if provided with:
(i) ventilation such as will maintain a positive pressure therein, with
clean air;
(ii) effective safeguards against ventilation failure.
(2) For purposes of this rule suitable cut off means an area cut off from another,
with no communication such as by doors, windows, grills or similar openings.
Section 26: Installation of Electrical Equipment
26-701
Receptacle Terminal Screws
Rule 26-701 is added.
(1) Unused terminal screws shall be done up tight.
13
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
(2)
26-702
E-6.3 REG 3
A maximum of 4 wires and a ground may be connected to a receptacle.
Receptacles in Residential Occupancies
Subrule (19) is deleted and the following substituted therefor:
(19) All receptacles installed outdoors of single-family dwellings and located
within 2.5 m of ground or grade level or raised platforms with access to ground,
shall be protected by a ground fault interrupter of Class A Type.
Subrule (25) is added as follows:
(25) Where receptacles are required for outdoor wheel chair lifts they
must be a single locking receptacle connected to a separate circuit and must
not be ground fault protected.
26-703
Automobile Heater Receptacles
Receptacles shall be installed with mechanical protection against damage by
vehicles by one of the following or other equivalent means:
(a) Approved manufactured pedestals provided with mechanical protection.
(b) Where mechanical protection is not utilized, the receptacles and conduit
shall be installed on structures of adequate strength, such as fences or walls,
and the receptacles and conduit shall be installed not less than 750 mm above
finished grade.
(c) A reinforced concrete post with a dimension of not less than 300 mm may
be used, and shall be installed to a height of not less than 750 mm and a depth
of not less than 750 mm. The receptacles and conduit shall be installed on the
face of the post not exposed to vehicular damage. The receptacles may, if
desired, be installed on the face of the post exposed to vehicles provided the
conduit and outlet boxes are installed within the post. Mounting height of the
receptacles shall not be less than 750 mm above finished grade.
(d) Conductors for wiring of these receptacles shall have an insulation or
covering suitable for installation and use at temperatures down to minus 40
degrees C except conductors approved for and used underground.
26-954
Deep Well Submersible Pumps Installed in Wells
Paragraph (e) is added.
(e)
Metal well casing shall be bonded to the equipment grounding means.
Section 30: Lighting
30-302
Supports
Rule 30-302 is supplemented as follows:
(5) Lighting fixtures installed in or on suspended ceilings shall be provided with
supplementary means of support unless written confirmation is submitted to the effect
that the suspended ceiling has been designed to support the additional weight of the
fixtures.
14
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Section 32: Fire Alarm Systems and Fire Pumps
32-110
Installation of Smoke Alarm Devices in Dwelling Units
Rule 32-110 is supplemented as follows:
(e) New construction of residential units shall be pre-wired at the
time of construction to accommodate smoke alarms as required by
the NBC plus one location in the basement, to be terminated in a
junction box c/w cover plate and labelled.
32-204
Consumer’s Service for Fire Pumps
Subrule (1) is deleted and the following substituted:
(1) When fire pump equipment is installed, a consumer service
independent of the building consumer service is required.
Section 36: High-potential Installations
36-007
High-Voltage Substation Connections
Rule 36-007 is added.
High voltage substations shall not be connected to the Utility supply lines
before a final inspection is made or approval for the connection is granted by
the Inspections Dept.
Section 45: Stand-by Power Systems
45-000
Scope
Rule 45-000 is added.
(1) This section applies to stand-by systems installed to provide an
alternative source of electrical energy to serve loads, such as heating and
refrigeration systems, power outage, which could cause discomfort, serious
interruption of the process, or damage to the product or process or the like.
(2) This section does not apply to the installation, operation, and
maintenance of circuits, systems and equipment intended to supply on-site
generated power to “selected loads”, automatically or manually, in the event
of failure of the normal source of electrical service.
(3) The systems covered by this section shall include those with provisions for
plug-in of portable or transportable power source and prime mover combinations.
45-002
Other Requirements
Rule 45-002 is added.
All applicable requirements of this Code shall apply to the stand-by systems,
except as amended by this section.
45-004
Controls and Transfer Equipment
Rule 45-004 is added.
15
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
(1) Equipment shall be suitable for intended use and be so designed and installed
as to prevent the inadvertent interconnection of normal and standby sources of supply
in any operation of the transfer equipment.
(2) A manual transfer means shall comprise a double-throw switch with required
number of poles, or individual switches so interlocked as to prevent the interconnection
of the two power sources.
(3)
45-006
Mechanically interlocked fused switches shall not be used.
Systems Protection
Rule 45-006 is added.
Transfer equipment and wiring associated with the stand-by system shall be
provided with suitably rated thermal protection.
45-008
Wiring
Rule 45-008 is added.
Stand-by system wiring is not subject to the provisions of Section 46, and wiring of
such a system may occupy the same raceways, boxes, cabinets and panelboards with
other wiring as permitted by Section 12, except that the wiring shall not occupy the
same raceways, boxes or cabinets as wiring for emergency systems.
Section 52: Diagnostic Imaging Installations
52-013
Industrial and Laboratory Equipment
Rule 52-013 is added.
(1) All radiographic and fluoroscopic-type equipment shall be effectively enclosed
or shall have interlocks that de-energize the equipment automatically to prevent ready
access to live current-carrying parts.
(2) Diffraction and irradiation-type equipment shall be provided with a positive
means to indicate when it is energized; the indicator shall be a pilot light, readable
meter deflection, or equivalent means
(3) Equipment or installations in (2) above, which are effectively enclosed or
provided with interlocks to prevent access to live current-carrying parts during
operation, need not be provided with an indicating means.
Section 62: Fixed Electric Space and Surface Heating Systems
62-114
Overcurrent Protection and Grouping (see Appendix B)
62-214
Installation of Heating Panel and Heating Panel Sets
Rule 62-214 is supplemented as follows:
(13) Until such time as the appropriate standards have been revised, the
following requirements will apply to flexible (thin sheet) radiant ceiling
heating panel installations:
(i) Heating panels shall be certified and marked with a rating of
18 watts/ft2 or less, and
16
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
(ii) The upper surface of the plasterboard in contact with the
heating panels must not exceed 60 degrees C, and
(iii) Heating panels must pass the abnormality test of CSA
Standard C22.2 No. 217-M89 and the results must not exceed a
temperature of 90 degrees C, and
(iv) Full compliance with the manufacturers’ installation
practices, including the installation of building materials, must
be verified in writing by a manufacturer’s representative to the
Electrical Inspection Department, and
(v) Manufacturers of heating panels must have a letter on file
in the office of the Chief Electrical Inspector of SaskPower
confirming their product complies with these requirements. and
(vi) Installation will only be permitted by licensed electrical
contractors.
Section 68: Swimming Pools, Therapeutic Pools
and Hydromassage Bathtubs
68-300
Protection
Rule 68-300 is deleted and the following substituted therefor:
All permanently wired therapeutic pools or hydromassage bathtubs and their
associated electrical components shall be protected by a ground fault circuit interrupter
of the Class A Type, fed by a dedicated circuit serving no other equipment.
68-401
Protection
Rule 68-401 is added:
68-401 Refer to 68-068 for protection of spas and hot tubs.
Section 90: Oil-Gas Field Installations
Section 90 is added
90-000 Scope
(1) This section applies to electrical equipment used in the search for or
transmission or production of oil, natural gas and related hydrocarbons.
(2) This section does not apply to electrical equipment used in
(a)
petroleum refineries, or
(b) gas pipeline systems operated at a pressure of 700 kpa or less,
unless the gas pipeline system is part of a wellhead or gathering
facility or scheme.
(3) These requirements shall be considered to be additional to or
amendatory of the requirements in the Canadian electrical Code.
17
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
90-002
E-6.3 REG 3
Definition
(1) Totally-enclosed, gasketted means so enclosed that transient vapour does
not enter the enclosure. This includes material with threaded hubs or approved tech
connectors with sealing rings. This wiring method shall be used in all areas classified
as transient vapour locations.
(2) Transient Vapours means combustible gases or vapours that are
capable of migrating from hazardous locations through air movement.
90-004
Horizontal Clearance of Overhead Power Lines
Where an overhead powerline is adjacent to an oil or gas well, the
horizontal clearance from the pole will conform to the SaskPower utility
standard.
Gas and Oil Drilling and Servicing Rigs
90-100
Area Classifications (Diagram 21)
(1) Areas within 2 m horizontally and 3 m vertically of the centre of the well hole
or any area where accumulation of ignitable vapours may occur, such as mud tanks or
confined space under the drilling floor, shall be classified as Class I Division 2
hazardous areas.
(2) Areas outside of the Class I Division 2 location surrounding the well hole shall
be considered subject to possible transient combustible vapours, if:
(a) within 22.5 m horizontally and vertically of a well;
(b) enclosed within the derrick structure; or
(c) in a building, any part of which is within 22.5 m of a well.
Oil Well Pump Installations
90-200
Area Classification (Diagram 22)
(1) Areas within 2 m horizontally and 3 m vertically of the centre of a well hole
shall be classified as a Class I Division 2 hazardous location.
(2) Areas outside of the Class I Division 2 location but within 6 m of the well
horizontally and vertically shall be considered exposed to transient vapours.
90-202
(1)
Equipment
Electrical equipment in areas as outlined in Rule 90-200(2):
(a) Where plug receptacles are installed, they shall be a weatherproof type
and so constructed that accidental disconnection of the cord is prevented.
(b) Equipment, including pressure switches, which is frequently moved for
well-servicing operations shall be connected with a type SO, SOW, STW, or
equivalent flexible cord, as short as possible, with approved fittings and shall
have an approved means for readily connecting and disconnecting the flexible
cords.
18
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
(c) The disconnecting means for the flexible cord shall be rigidly
mounted 450 mm above ground level or pump base.
(2) A warning sign must be posted on pumps which are automatically controlled
with wording similar to the following:
WARNING: This equipment is automatically controlled, and the main switch
must be disconnected before work is done on the equipment.
Battery Installations and their Associated Equipment, Pumps, Automatic
Custody Transfer Assemblies, Manifolds, Treaters, Separators, and other
Sources of Ignitable Vapours.
90-300
Area Classification (Diagram 24)
(1) Areas within building or housing treaters, separators, manifolds, or other
equipment which may result in hazardous concentrations of flammable gases or
vapours continuously, intermittently, or periodically, under normal operating conditions
shall be considered as Class I Division 1 hazardous locations.
(2) The following areas shall be classified as Class I Division 2 hazardous
locations:
(a) Outdoor areas within 3 m of the outer confines of building or housings in
which the conditions outlined in subrule (1) exist, plus an additional
horizontal distance of 4.5 m to a height of 450 mm above ground level.
(b) Areas within 3 m of oil storage or surge tanks and extending horizontally
to the perimeter and the height of dykes or fire walls enclosing the tanks.
(c) Outdoor or unhoused areas within 3 m horizontally and 2 m vertically of
pumps, manifolds, treaters, separators, and associated automatic custody
transfer units which incorporate valves, checks, meters or any potential
source of leakage.
Water Flood, Disposal Systems, and Injection Wells
90-400
Area Classification (Diagram 23)
(1) The area above the produced water in a vessel or tank used as a
storage facility shall be Class 1, Division 1, and an area within 1.5 m in any
direction of a ventilation opening into a Class 1, Division 1 hazardous
location will be classified Class 1, Division 1. The area between 1.5 m and 3.0
m from a ventilations opening will be classified Class 1, Division 2.
(2) Areas within buildings or housing at water flood and disposal systems that
enclose wells which extend into oil and gas-producing zones shall be classified as
Class I Division 2 hazardous areas, unless provisions, acceptable to the inspection
authority, are made.
(3) Areas within buildings in which water produced in conjunction with crude oil,
or fresh water, containing gas, is stored, processed, or subjected to pumping operations
shall be classified as Class I Division 2 hazardous location, except that such areas may
be regarded as non-hazardous if:
19
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
(a) the produced or gas-entrained fresh water has been sufficiently processed
to remove any hazardous vapours; and
(b) the disposal well is not located in the building, or
(c) Buildings housing injection wells will be regarded non-hazardous if:
(i) Provision of a concrete floor which will establish are essentially gastight seal over the ground surface and around the surface casing, and
(ii) Provision of an acceptable underfloor vent, extending outside the
building structure, which will vent surface or marsh gases that may
accumulate under floor, adjacent to the surface casing, and
(iii) Venting of the annular space between surface and production
casings to outside atmospheres shall be provided. Valves which are used
in conjunction with this vent must be tagged with a warning to the effect
that they shall be maintained in the open position, and
(d) Adequate cross ventilation of the building shall be established by the
provision of louvres, or openings, or forced ventilations.
Gas-pressuring and Storage Systems, Gas Compressor Stations
90-500
Area Classification (Diagram 24)
(1) Areas within buildings or housings, which enclose gas compressors and their
associated equipment, shall be regarded as Class I Division 1 hazardous locations,
except that such areas may be regarded as Division 2 locations, where:
(a) The building or housing is of the shed type and is open on three sides
from grade to roof levels, and the roof ventilators are provided if lighter than
air gases are involved; or
(b) The gas compressors and their associated piping and equipment are
so designed and installed that they satisfy the conditions set out in
Rule 18-004(b)(i) of the Code; or
(c) Suitable safety features are provided in the form of:
(i) combustible gas-detection equipment which will automatically deenergize the electrical system in the case of unattended locations, or set
off an alarm in attended locations, before the concentration of gas
reaches 40 percent of the lower explosive limit; or
(ii) actuation of a visible or audible alarm upon failure or forced
ventilation, as outlined in Rule 18-004(b(ii), in attended stations and deenergization of the electric system in the case of unmanned stations.
(2) All areas below grade level in buildings or housings shall be regarded as
Class I Division 1 locations.
(3) Outdoor areas within 3 m of the outer confines of buildings or housings in
which the Class I Division 1 conditions outlined in subrule (1) exist, plus an additional
horizontal distance of 4.5 m to a height of 450 mm above ground level shall be classed
as Class I Division 2 hazardous locations.
20
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Section 92: Electrical Installations on Farms
Section 92 is added
92-000 Scope
This section applies to electrical installations on farms, farm irrigation units, feed
lots and other qualified farm-related operation.
General
92-001
Definition of Farm
Farm shall mean a rural land holding, located outside the corporate limits of a city,
town, village or within the boundaries of an area legally zoned for agricultural use,
where the use and development of the land holding is exclusively for purposes of
agricultural production.
Yard Wiring and Services
92-100
Aerial Conductors on Utility Poles
(1) Overhead conductors forming parts of the farm wiring system shall not be
supported on, or fastened to, any utility pole, except the yard transformer pole.
(2) Where additional guying of the yard pole is made necessary, such guying shall
be at the cost of the owner upon consultation with the utility.
92-102
be:
Customer-Owned Poles
(1) Where additional poles are required for support of overhead conductors, shall
(a) 7.5 m or more in length with a minimum top diameter of 125 mm;
(b) set into the ground at least 1.5 m;
(c) treated for prevention of rot; and
(d) guyed at corners and deadends
(2) Installation or addition of overhead conductors shall be made only if the pole
is capable of withstanding the resultant directional stresses.
92-104
Yard Light on Transformer Pole
(1) The yard light may be mounted on the transformer pole provided:
(a) it is located below the secondary rack where there is one;
(b) with a separation of at least 500 mm between the bottom of the
transformer and the fixture base where there is no secondary rack;
(c) on the quadrant of the pole which would not interfere with pole climbing
and transformer removal.
21
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Services
92-200
Subdivision of Service
(1) Where the main service switch or breaker is located outdoors, subservice
drops may be run from a splitter located on the load side thereof or from a service rack.
(2) Where three phase 4-wire systems are installed, four wires must be
present in the service.
92-202
Classification of Services to Buildings
(1) On all farms a service box shall be installed at the residence, buildings
housing livestock and buildings requiring 3-wire 120/240 volt supply when such
buildings are to be supplied with energy directly from the transformer-pole secondary
rack, or a splitter box
(2) On any farm building, other than the residence, the service stack may
be installed on a wooden mast of at least 100 X 100 mm securely fastened to
the building with two through bolts.
92-204
Splitter Box on Yard Pole
(1) Where one or more underground services are being connected to a yard pole
supply and the utility service is not provided with a splitter compartment, an approved
weatherproof splitter box shall be installed.
92-206
Service Drops
(1) Where a farm building is extended, a second service drop may be run to the
extension, other than the residence.
(2) Services including the grounding electrode shall be installed a
minimum of 9 m from any watering bowl.
Grounding
92-300
Grounding Service Equipment
Service equipment shall be grounded in the following manner:
(1) The service to the residence, pump house, buildings housing livestock and any
other building shall be grounded by means of at least one electrode and when there is
only one service on a farmstead, at least two electrodes shall be provided.
Wiring Methods
92-400
Wet Locations
(1) Non-metallic boxes shall be installed at outlets in buildings housing livestock
or poultry and other buildings subject to condensation or moisture.
(2) Ceiling-mounted lighting outlets in moist or wet locations may be wired with
NMW or NMWU.
22
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Installation of Equipment
92-500
Portable Motors
Portable motors shall meet the requirements of Section 28 of the C.E.C.
92-502
Heat Lamp Installations (Brooder Fixtures)
(1) Circuits supplying infra-red heat lamps must be permanently installed.
(2) heat lamps shall only be used in approved brooder fixture assemblies, and the
assemblies shall be suitable for use in damp locations.
(3) Brooder fixtures shall be the 3-wire grounded type.
(4) Brooder fixtures shall be independently supported by a chain, wire or bracket,
and shall not be suspended by the cord.
(5) Brooder fixtures shall be so suspended as to be more than 450 mm from litter
or from combustible material.
(6) Brooder fixtures shall be protected by barriers to prevent animals from
contacting and damaging the brooder units.
92-504
Electric Heaters in Buildings Housing Livestock
Electric heaters for use in buildings housing livestock shall be approved for the
purpose and marked Suitable for Use in Buildings Housing Livestock or a similar
wording.
Electrically Driven Pivot Irrigation Machines
92-600
General
Rule 92-602 to 610 apply to pivot type multi-motor irrigation machines which
revolve around a central pivot and employ alignment switches or similar devices to
control individual motors.
92-602
Several Motors on One Branch Circuit
(1) Several motors, each not exceeding 2 H.P. rating, may be used on an irrigation
machine circuit protected at not more than 30 amperes at 600 volts or less, provided all
of the following conditions are met:
(a) The full-load rating of any motor in the circuit shall not exceed 6
amperes.
(b) Each motor in the circuit shall have individual running overload
protection in accordance with Section 28.
(c) Taps to individual motors shall not be smaller than 14 AWG copper and
not more than 7.5 m in length.
(2) Individual branch-circuit short-circuit protection for motors and motor
controllers shall not be required where the requirements of subrule (1) are met.
23
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
92-604
E-6.3 REG 3
Disconnecting Means
(1) The main disconnecting means for machine shall be located at the point of
connection of electrical power to the machine, be readily accessible and capable of
being locked in the open position, and have the same horsepower and current ratings
as required for the main controller.
92-606
Interconnecting Wiring
(1) Wiring to interconnect the unit collector rings, control panels and motors may
be multi-conductor, jacketed cables suitable for outdoor use, suitable for hard usage
according to Table 11, and have a grounding conductor.
(2)
Cables may be supported along water pipe sections between towers.
(3) Supporting of cables shall be at intervals not exceeding 1.2 m and within 300
mm of terminal fittings by means of straps, hangers or similar fittings.
(4) Where routing of cables is such that additional strain might be imposed on
terminal fittings, supplemental strain relief shall be provided.
(5) Protection by location, or by supplemental means shall be provided for cables
subject to mechanical damage such as at tower drive motors.
92-608
Lightning Protection
If an irrigation machine has a stationary point, a driven ground rod shall be
connected, with minimum #6 AWG copper conductor to the machinery at the
stationary point for lightning protection.
92-610
Ground Fault Protection
Connection and re-connection of new and existing irrigation equipment
must meet the requirements of the current CEC Part 2 standards with respect
to ground fault protection.
Table 66 is added.
TABLES
Table 66
Limits of Approach to Normally Live Parts
Nominal
Voltage
Phase-toPhase
230 kV
138 kV
72 kV
25 kV
15 kV
4.16 kV
Voltage
to
Ground
133 kV
79.8 kV
41.6 kV
14.4 kV
8.6 kV
2.4 kV
Minimum
Recommended
Working
Clearance
for Personnel
*Absolute
Limit of
Approach
for Personnel
and Tools
1.83 m
1.22 m
0.80 m
0.60 m
0.60 m
0.60 m
1.40 m
1.00 m
0.60 m
0.30 m
0.30 m
0.15 m
* Absolute limit of approach is the least permissible distance between live electrical apparatus and the
position that an experienced qualified tradesman’s body (or tools and material he may be handling) could be
in, through an accidental or unplanned movement.
26 Jan 96 SR 1/96 s2.
24
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 11
25
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 12
E-6.3 REG 3
26
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 13
27
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 14
E-6.3 REG 3
28
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 15
29
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 16
E-6.3 REG 3
30
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 17
31
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 18
E-6.3 REG 3
32
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 19
33
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 20
E-6.3 REG 3
34
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 21
35
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 22
E-6.3 REG 3
36
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 23
37
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 24
Diagram 25
E-6.3 REG 3
38
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 26
39
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
Diagram 27
E-6.3 REG 3
40
E-6.3 REG 3
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
APPENDICES
Appendix B
2-015
Appendix note 2-015 is added pertaining to Rule 2-015.
Rule 2-015 requires that plans and specifications shall, in addition to other
details, contain the maximum short circuit current available at each point of
application of protective devices in installations exceeding 600 A. Because of
the lower impedance’s in the energy-efficient transformers currently being
used by utilities and available for customer-owner installations, the resultant
higher short circuit availability makes the requirement in this rule even
more important. For example, a 500 KVA 120/208 V transformer with 2%
impedance has a short circuit current of 69400 amp available at its
terminals (based on infinite primary) whereas one with 5% impedance
would have only 27760 amp available.
On the basis that code fuses and many circuit breakers have an interrupting
capacity rating of 10000 amps, it will be apparent from the tabulation below,
that a substantial number of systems will require careful fault current
analysis to ensure compliance with rule 14-012 and related note in
Appendix B of the Code. Whereas the short circuit current available for the
overcurrent device to interrupt is dependent upon several factors, such as
distance, type and size of circuit conductors careful attention must be given
to arrangements with a short bus between a transformer and a distribution
centre.
Review of plans not having the required short circuit current information
will be withheld until it is made available and the selected overcurrent
devices are determined to have satisfactory IC rating. If values are not
available from utilities (on rare occasions) the inspection office should be
consulted for concurrence with an estimated value.
18-405
Appendix note 18-405 is added regarding Rule 18-405
As per CSA Standard B52-M a Class T machine room requires the
following:
A Class T machinery room shall have no ignition source apparatus
permanently installed and operated and also shall conform to the
following:
a) Emergency remote controls to stop the refrigerant compressor
shall be provided and located immediately outside the machinery room;
b) An independent mechanical ventilation system conforming to
Clause 7.10.4 shall be provided for all machinery rooms. In basements and
sub/basements the ventilation system shall be operated continuously. In all
other locations the machinery rooms shall have continuous ventilation or be
equipped with a gas-monitoring system that will automatically start up the
ventilation system and actuate a remote alarm at the lowest practical
instrument-detection level not exceeding 25% of the lower explosive limit;
41
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
c) Emergency remote controls for the mechanical means of
ventilation shall be provided and located outside the machinery room.
62-114
Appendix note 62-114 is added pertaining to subrules 62-114 (6) and (7).
With continuing increase in use of electric furnaces and the need for proper
sizing of disconnect, overcurrent protection and supply conductors, the table
thereunder has been prepared for ease of reference.
ELECTRIC FURNACES AND OTHER HEATING EQUIPMENT
Ref. C.E.C. 62-114 (6) and (7)
Nameplate
Furnace
Rating
(KW)
5 KW
10 KW
15 KW
20 KW
25 KW
30 KW
Conductor Size
Copper
Aluminum
No.10 AWG R90
No. 8 AWG R90
No. 8 AWG R90
No. 6 AWG R90
No. 4 AWG R90
No. 3 AWG R90
No. 3 AWG R90
No. 1 AWG R90
No. 2 AWG R90
No. 0 AWG R90
No. 1 AWG R90
No. 00 AWG R90
Fuse or
C.B. Rating
30 Ampere
60 Ampere
100 Ampere
125 Ampere
150 Ampere
175 Ampere
A sample selection for a 20 KW furnace follows: The ampacity of the conductors
supplying the electric furnace and the size of the overcurrent devices are determined
by applying Rule 62-114.
The overcurrent device for the furnace must be sized so that the total connected
load of the heating equipment does not exceed 80% of the rating of the overcurrent
device in accordance with subrule (6). In this case, the load is 83.3 amps, the minimum
size of overcurrent devices is 83.3 / 0.8 = 104 amperes. The next available fuse is 125
amperes.
Since this fuse is supplying a heating load, Rule 14-610 requires that the fuses be a
time delay type or HRC Form I.
The conductor size is determined by applying subrule (7) of 62-114. The conductor
must be of an ampacity sufficient to carry the load, must have an ampacity rating at
least 80% of the rating or setting of the branch circuit overcurrent device. A conductor
rated at 100 amperes, i.e. #3 AWG R90 (Column 3 of Table 2) would satisfy these
requirements.
Based on the conduit fill requirements of Rule 12-1014 and Tables 6 and 10, it can
be determined that the 2 #3 AWG R90 conductors require a 1 1/4" conduit.
The size of the conduit used for bonding equipment must be considered. Rule 10814 and Table 16 require a 1 1/2 EMT conduit where the overcurrent protection
exceeds 100 amperes.
Therefore in this installation the 1 1/4 EMT conduit would have to be increased
to 1 1/2 EMT.
42
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Table D-13 is added.
Table D-13
Table D-13 suggested maximum capacitor rating when motor and capacitor are
switched as a unit (For 3-phase, 60 Hz NEMA Class B motors to raise full-load power
factor to 95%).
NOMINAL MOTOR SPEED IN RPM
3600
1800
1200
900
720
600
MOTOR
RATING
HP
CAPS
KVARS
AMPRE
REDUCE
%
CAPS
KVARS
AMPRE
REDUCE
%
CAPS
KVARS
AMPRE
REDUCE
%
CAPS
KVARS
AMPRE
REDUCE
%
CAPS
KVARS
AMPRE
REDUCE
%
CAPS
KVARS
AMPRE
REDUCE
%
3
1.5
14
1.5
15
1.5
20
2
27
2.5
35
3.5
41
5
2
12
2
13
2
17
3
25
4
32
4.5
37
7.5
2.5
11
2.5
12
3
15
4
22
5.5
30
6
34
10
3
10
3
11
3.5
14
5
21
6.5
27
7.5
31
15
4
9
4
10
5
13
6.5
18
8
23
9.5
27
20
5
9
5
10
6.5
12
7.5
16
9
21
12
25
25
6
9
6
10
7.5
11
9
15
11
20
14
23
30
7
8
7
9
9
11
10
14
12
18
16
22
40
9
8
9
9
11
10
12
13
15
16
20
20
50
12
8
11
9
13
10
15
12
19
15
24
19
60
14
8
14
8
15
10
18
11
22
15
27
19
75
17
8
16
8
18
10
21
10
26
14
32.5
18
100
22
8
21
8
25
9
27
10
32.5
13
40
17
125
27
8
26
8
30
9
32.5
10
40
13
47.5
16
150
32.5
8
30
8
35
9
37.5
10
47.5
12
52.5
15
200
40
8
37.5
8
42.5
9
47.5
10
60
12
65
14
250
50
8
45
7
52.5
8
57.5
9
70
11
77.5
13
300
57.5
8
52.5
7
60
8
65
9
80
11
87.5
12
350
65
8
60
7
67.5
8
75
9
87.5
10
95
11
400
70
8
65
6
75
8
85
9
95
10
105
11
450
75
8
67.5
6
80
8
92.5
9
100
9
110
11
500
77.5
8
72.5
6
82.5
8
97.5
9
107.5
9
115
10
43
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Table D-14 is added.
Table D-14
CAPACITOR SWITCHING DEVICES
RECOMMENDED SWITCHING DEVICES (for separate mounting)
CAP
RATING
CAP
RATING
AMPERES
Cap
Fuse
Amps Amps
MC
Brkr
PC
Brkr
Volts
kVar
15
15
15
480
2
2.41
20
20
20
5
6.01
18
30
30
30
7.5
24.1
40
40
40
10
36.1
60
70
50
15
72.2
125
125
100
Volts
kVar
240
2.5
6.01
5
12
7.5
10
15
30
CAP
RATING
AMPERES
Cap
Fuse
Amps Amps
AMPERES
MC
Brkr
PC
Brkr
Volts
MC
Brkr
PC
Brkr
15
15
15
600
5
4.81
15
15
15
10
9.62
15
15
15
20
15
15
9
15
15
15
15
12
20
20
20
20
14.4
25
30
20
19.2
35
30
30
18
30
30
30
25
24.1
40
40
40
20
24
40
40
25
30
50
50
40
30
28.9
50
50
40
50
40
38.5
70
70
70
30
36.1
60
70
50
50
48.1
80
100
70
kVar
Cap
Fuse
Amps Amps
45
108
200
175
150
60
144
250
225
200
75
180
300
275
250
40
48.1
80
100
70
60
57.8
100
100
90
90
217
400
350
300
50
60.1
100
100
90
75
72.2
125
125
100
120
289
500
500
400
60
72.2
125
125
100
80
77
150
125
125
135
325
600
500
500
75
90.2
150
150
125
100
96.2
175
150
150
80
96.2
175
150
150
120
115
200
175
175
150
361
600
600
500
90
108
200
175
150
125
120
200
200
175
180
433
800
700
600
100
120
200
200
175
150
144
250
225
200
225
541
900
900
800
120
144
250
225
200
240
578
1000
900
800
160
154
300
250
225
270
650
1200
1000
1000
125
150
250
225
200
180
173
300
300
250
360
866
1600
---
1200
150
180
300
300
250
200
192
350
300
300
160
192
350
300
300
225
217
400
350
300
180
216
400
350
300
240
231
400
350
350
200
241
400
400
350
250
241
400
400
350
225
271
500
500
400
300
289
500
500
400
240
289
600
500
400
250
301
500
500
400
320
306
600
500
500
360
347
600
600
500
300
361
600
600
500
375
361
600
600
500
320
385
700
600
600
400
385
700
600
600
360
433
800
700
600
450
433
800
700
600
375
451
800
700
600
400
481
800
800
800
450
541
900
900
800
Rule 26-214
MC = Moulded Case Breaker or equivalent. PC = Power Circuit Breaker or equivalent.
44
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Table D-15 is added.
Rule 12-318 Sask. Supp.
Table D-15
RECOMMENDED SAGS FOR NEUTRAL-SUPPORTED CABLE
2-No. 1/0 A1
1-No. 1/0 Bare ACSR
Span in Meters
Temp.
15
Deg. C
-29
-18
0
16
32
23
30
2-No. 2 Al
1-No. 2 Bare ACSR
Span in Meters
38
15
Sag in Centimetres
25
28
28
28
30
58
58
61
64
66
102
104
109
114
117
23
30
38
2-No. 4 Al
1-No. 4 Bare ACSR
Span in Meters
15
Sag in Centimetres
157
163
17
178
183
20
20
23
23
25
Table D-16 is added.
43
46
48
53
56
76
81
86
94
99
23
30
38
Sag in Centimetres
119
127
135
147
155
18
20
20
20
23
43
46
46
48
51
76
79
81
84
89
119
124
130
132
137
Table D-16
THREE PHASE TRANSFORMER FULL LOAD LINE CURRENT IN AMPERES
KVA
208v.
240v.
480v.
600v.
2400v.
4160v.
13800v.
14400v.
3
6
9
15
30
45
50
75
112.5
150
200
225
300
450
500
750
1000
1500
2000
8.3
16.6
25.0
41.7
83.4
125
139
208
313
417
556
625
834
1249
1390
2082
2776
4164
5552
7.2
14.4
21.7
36.1
72.3
108
120
181
271
361
482
542
723
1083
1204
1804
2406
3608
4811
3.6
7.2
10.8
18.2
36.1
54.2
60.2
90.3
135
181
241
271
361
541
602
902
1203
1804
2406
2.9
5.8
8.7
14.5
28.9
43.4
48.2
72.3
108
145
193
217
289
433
482
722
962
1443
1925
0.72
1.46
2.17
3.61
7.23
10.8
12.0
18.1
27.1
36.1
48.2
54.2
72.3
108
120
180
241
361
481
0.42
0.82
1.25
2.09
4.17
6.26
6.96
10.4
15.7
20.9
27.8
31.3
41.7
62.5
69.6
104
139
208
278
0.126
0.251
0.377
0.628
1.26
1.88
2.09
3.14
4.71
6.28
8.37
9.41
12.55
18.83
20.92
31.38
41.84
62.76
83.67
0.120
0.241
0.361
0.601
1.202
1.805
2.00
3.005
4.51
6.01
8.02
9.025
12.02
18.04
20.07
30.07
40.09
60.14
80.19
KVA = 1.73 x VOLTAGE X CURRENT / 1000
45
CANADIAN ELECTRICAL CODE
(SASKATCHEWAN AMENDMENTS), 1995
E-6.3 REG 3
Table D-17 is added.
Table D-17
SINGLE PHASE TRANSFORMER FULL LOAD LINE CURRENT IN AMPERES
KVA
120v.
240v.
480v.
600v.
2400v.
4160v.
14400v.
2
3
5
7.5
10
15
20
25
30
37.5
50
75
100
167
200
250
333
500
750
1000
16.7
25.0
41.7
62.5
83.3
125
167
208
250
313
417
625
833
1391
1667
2083
2115
4167
6250
8333
8.3
12.5
20.8
31.3
41.7
62.5
83.3
104
125
156
208
313
417
695
833
1041
1387
2083
3125
4167
4.2
6.3
10.4
15.6
20.8
31.3
41.7
52.1
62.5
78.0
104
156
208
347
417
520
693
1042
1563
2083
3.3
5.0
8.3
12.5
16.7
25.0
33.3
41.7
50.0
62.5
83.3
125
167
278
333
416
555
833
1250
1667
0.83
1.25
2.08
3.13
4.17
6.25
8.33
10.4
12.5
15.6
20.8
31.3
41.7
69.6
83.3
104
138
208
313
417
0.48
0.73
1.2
1.8
2.4
3.6
4.8
6.0
7.2
9.0
12
18
24.0
40.1
48.1
60.1
80
120
180
240
0.139
0.208
0.347
0.521
0.694
1.04
1.39
1.74
2.08
2.61
3.47
5.21
6.94
11.6
13.9
17.4
23.1
34.7
52.1
69.4
KVA = VOLTAGE (CURRENT) / 1000
REGINA, SASKATCHEWAN
Printed by the authority of
THE QUEEN’S PRINTER
Copyright©1996