KEYED NOTES: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. CAP GENERAL NOTES: GAS FIRED ROOFTOP UNIT LOCATE A MINIMUM OF 10'-0" FROM EDGE OF ROOF CANVAS FLEXIBLE CONNECTION 1" ACOUSTIC INSULATED DUCTS 4x4 ANGLE FASTENED TO ROOF DECK AND STRUCTURAL SYSTEM. PROVIDE SUPPORTS AS REQUIRED FACTORY FABRICATED, INSULATED ROOF CURB (BY SAME MFG'R AS UNIT) FASTEN CURB TO DECK RADIUSED ELBOW UNION BY PLUMBING CONTRACTOR (PC) GAS SHUT-OFF VALVE BY PC GAS LINE (BLACK STEEL) BY PC SECURE TO CURB WOOD NAILER ROOFING MEMBRANE, FLASH UP TO BELOW WOOD NAILOR CANT STRIP ROOF DECK - CUT OPENINGS FOR DUCT PENETRATIONS ONLY CONDENSATE TRAP - SEE CONDENSATE DRAIN TRAP DETAIL HIGH WATER ALARM IN CONDENSATE DRAIN PAN. WIRE TO BREAK 24 VOLT CONTROL POWER IN THE CASE OF A HIGH WATER EVENT. A. B. CONTRACTOR SHALL PROVIDE CURB TO MAINTAIN 14" MINIMUM ABOVE FINISHED ROOFING SYSTEM. PROVIDE ADDITIONAL BLOCKING AS REQUIRED TO ACCOMMODATE ROOF INSULATION THICKNESS FINAL LOCATION AND STRUCTURAL VERIFICATION BY OTHERS. K = MINIMUM OF 1/2" M = 1/2" PLUS MAXIMUM TOTAL PRESSURE CAP GENERAL NOTES: GENERAL NOTES: STATIC A. PIPE FULL SIZE OF AIR UNIT DRAIN CONNECTION B. C. K D. FLOW SEE NOTE 2 LOCATE TRAPS SO AS TO BE ACCESSIBLE FOR CLEANING CONDENSATE PIPING SHALL GRADUALLY SLOPE DOWN FROM DRAIN TRAP CONFIRM TRAP REQUIREMENTS WITH EQUIPMENT MANUFACTURER REFER TO SPECIFICATIONS FOR MATERIAL AND INSULATION REQUIREMENTS 1. 2. RETURN TUBE VERIFY WITH AHJ M 3. AIR DUCT 4. 5. CAP POSITIVE PRESSURE H = (1" FOR EACH 1" OF MAXIMUM NEGATIVE STATIC PRESSURE) + 1" J = HALF OF H L = H + J + PIPE DIAMETER + INSULATION SMOKE DETECTOR KEYED NOTES: PROVIDE SPLITTER DAMPER (SD) AT ALL MAIN BRANCH TAKEOFFS PROVIDE MANUAL VOLUME DAMPERS AT ALL BRANCH TAKEOFFS PROVIDE MINIMUM 3 TIMES STRAIGHT INLET DIAMETER TO ALL VAV TERMINAL DEVICES DAMPER NOT REQUIRED AT TERMINAL DEVICE TAKEOFF ALL MANUAL DAMPERS SHALL BE LOCATED IN AN ACCESSIBLE CEILING. PROVIDE ACCESS PANEL AS REQUIRED 1. AIR FLOW 2. 3. 4. AIR FLOW AIR FLOW 7. PIPE FULL SIZE OF AIR UNIT DRAIN CONNECTION AIR FLOW CAP L H AIR FLOW SAMPLING TUBE FLOW SEE NOTE 2 J NEGATIVE PRESSURE NOTE: OUTDOOR UNITS AND UNITS LOCATED IN UNCONDITIONED SPACES WHICH PROVIDE COOLING IN THE WINTER MUST HAVE HEAT TRACE ON CONDENSATE PIPING. ROOF CURB AND MOUNTING 232113.23-05 SCALE: NONE AIR FLOW COND. DRAIN TRAP POSITIVE & NEGATIVE SCALE: NONE Note: Refer to manufacturer recommendation for smoke detector mounting location. Provide straight run up and downstream of sampling tube per manufacturer's requirements. 230500.00-02 AIR FLOW AIR FLOW DUCT MOUNTED SMOKE DETECTOR 233300.00-01 SCALE: NONE SCALE: NONE GENERAL NOTES: A. 3 INSTALLATION TO CONFORM TO NFPA 90A AND MANUFACTURERS INSTRUCTIONS 10 4 12" MIN. INSULATION MAIN BRANCH MANUAL DAMPER DETAIL 2 5 7 6 ITEM. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. DESCRIPTION ADJUSTABLE CONNECTING ROD FLEX CONDUIT DAMPER FRAME ACTUATOR OVER CENTER LOCK DAMPER SLEEVE PFMA OR CONVENTIONAL MOUNTING ANGLES SLEEVE TO DUCT CONNECTION ACCESS DOOR IN DUCT PROVIDE ARCHITECTURAL ACCESS PANEL IN NON-ACCESSIBLE WALLS OR CEILINGS MAIN SUPPLY DUCT KEYED NOTES: 9 8 1. 3-1/2" MIN. GENERAL NOTES: 1. KEYED NOTES: KEYED NOTES: 1. 2. 3. 1. REGISTER WITH 0 DEGREE DEFLECTION BLADE DAMPER (TO BE SIZED AS SCHEDULED) SUPPLY DUCT SEAL JOINTS BETWEEN COLLAR AND MAIN DUCT 2. 3. 4. 5. 233713.00-01 HORIZONTAL REGISTER INSTALLATION 0 DEGREES SCALE: NONE 24" MIN y x 6" MIN KEYED NOTES: GENERAL NOTES A. B. OPENING SIZE: 12x12 RG = 12x12 DUCT 24x24 RG = 24x18 DUCT x + y DIMENSIONS SHALL BE DETERMINED FROM FLOOR PLANS 233713.00-13 GALVANIZED OPERATOR PAD BRANCH MAIN DUCT DOUBLE THICKNESS TURNING VANES (TYPICAL) 3" RADIUS MINIMUM DUCT TEE AIR UNIT CASING AIR UNIT CASING 237433.00-04 5. 6. 20 GAUGE DOUBLE SHEET METAL AIR FOIL FULL DEPTH OF MAIN DUCT UP TO 12" WIDE BRANCHES 18 GAUGE ON WIDER BRANCHES MAIN DUCT GALVANIZED 3/16" ROD VENTLOCK NO. 600-3 DAMPER BLADE, BRACKET & LOCKING 1. 2. 3. 1/2" ACOUSTIC LINING 12x12 RG OR 24x24 RG (UNLESS OTHER WISE NOTED) OPENING SAME SIZE AS RG NECK PLENUM RETURN AIR GRILLE SCALE: NONE MAXIMUM LENGTH OF INSUL. FLEX DUCT EQUALS 5 FEET. FLEX NOT PERMITTED IN INACCESSIBLE CEILINGS INSULATED DUCT, COLLAR AND DIFFUSER BY HVAC CONTRACTOR SCOOP SPIN IN FITTING WITH MANUAL VOLUME DAMPER INTERNAL BUTTERFLY DAMPER FOR DRYWALL APPLICATIONS ONLY. (PROVIDE KEY FOR ADJUSTMENT) 6. 7. 8. 9. 233713.00-04 SECURE TO CEILING PER MANUFACTURER'S RECOMMENDATIONS AND PER CEILING FINISH. PROVIDE GRID CLIPS PER MFG'R REQUIREMENTS. PROVIDE FRAMING FOR DRYWALL INSTALLATION. HANGER, SECURE TO STRUCTURE AND DUCTWORK PEEL BACK INSULATION AND PROVIDE STRAPPING AND SHEET METAL SCREWS AT FLEX CONNECTION TO DUCT. THEN PROVIDE STRAPPING AROUND INSULATION. SUPPORT FLEX TO PREVENT COLLAPSING DIFFUSER INSTALLATION (TYPICAL) SCALE: NONE WHERE LINEAR DIFFUSER IS ADJACENT TO WINDOWS, ADJUST PATTERN CONTROLLER TO DIRECT AIRFLOW HORIZONTALLY TOWARDS WINDOWS. KEYED NOTES: 1. 2. 3. 4. 5. LOW PRESSURE SUPPLY DUCT 1" WIDE BAND AND CLAMP. SHEET METAL SCREW INSULATED FLEX. DUCT MAX LENGTH 5'-0" ABOVE ACCESSIBLE CEILINGS ONLY. PEEL BACK INSULATION AND PROVIDE STRAPPING AND SHEET METAL SCREWS AT FLEX CONNECTION TO DUCT. THEN PROVIDE 233713.00-14 6. 7. 8. 9. 10. 11. 12. 13. STRAPPING AROUND INSULATION. SHEET METAL PLENUM 1/2" ACOUSTICAL LINING PATTERN CONTROLLER SCREWS, MIN 6" ON CENTER & SEAL AIRTIGHT, TYP, BOTH SIDES VOLUME ADJUSTER BAND CLAMP MAXIMUM SAG 1/2" PER FOOT BETWEEN SUPPORT BRACING TAKE-OFF SPIN-IN FITTING WITH ADJUSTABLE MANUAL DAMPER. LOCATE ABOVE ACCESSIBLE CEILING OR PROVIDE ACCESS PANEL BELOW DAMPER. SHEET METAL BRANCH DUCT MANUAL VOLUME DAMPER PLENUM/LINEAR DIFFUSER SCALE: NONE 11 CEILING BLUE YELLOW BLUE YELLOW FS PRIMARY HEAT SENSOR MANUAL RESET S1 2. 3. 4. 5. 6. S2 GALVANIZED ALL THREAD ROD SUSPEND FROM BUILDING STRUCTURE AND FROM FAN MOUNTING FLANGES. USE CHANNELS UNDER FAN AS AN ALTERNATIVE SUPPORT CEILING FAN OUTLET FLANGE BACKDRAFT OR MOTOR OPERATED DAMPER (SEE SCHEDULE SPEC'S) METAL HANGER, SECURE TO STRUCTURE AND TO DUCTWORK FLEXIBLE CONNECTION BROWN ORANGE BLACK BROWN HL HIGH LIMIT TEMP. SENSOR MANUAL RESET 233313.00-16 SMOKE DAMPER SCALE: NONE 233423.00-02 CABINET EXHAUST FAN SCALE: NONE