FUJI Earth Leakage Circuit Breakers FUJI Earth Leakage Circuit

advertisement
GLOBAL-TWIN
Conforming to IEC & local Standards
The G-TWIN series is a global breaker series that satisfies all major standards.
IEC
UL/CSA
IEC 60947-2
EN
North
America
Europe
Europe
EN 60947-2
North America
UL489
CAN/CSA C22.2 NO.5
NEMA AB1
GB
China
China
GB 14048.2
JIS
S
Japan
JIS C 8201-2-1 MCCB
JIS C 8201-2-2 ELCB
CE model
CCC model
EN 60947-2
JIS C 8201-2-1
JIS C 8201-2-2
CE marking (TÜV)
JIS model
GB 14048.2 (China)
CCC approved
UL 489
CAN/CSA C22.2 NO.5
NEMA AB1
IEC 60947-2
JIS C 8201-2-1
JIS C 8201-2-2
UL mark (cUL)
CE marking (TÜV)
CCC
model
-TWIN
-TWIN
-TWIN
JIS
model
-TWIN
UL mark (cUL) + CE marking (TÜV) + CCC approved + JIS
CE marking (TÜV) + CCC approved + JIS
G-TWIN Standard series
G-TWIN Global series
IEC 60947-2
EN 60947-2 (CE marking)
GB 14048.2 (CCC)
JIS C 8201-2-1
JIS C 8201-2-2
IEC 60947-2
EN 60947-2 (CE marking)
GB 14048.2 (CCC)
JIS C 8201-2-1
JIS C 8201-2-2
Ampere frame size (AF)
32
50
63
FUJI Earth Leakage
Circuit Breakers
UL489 model
CE
model
JIS C 8201-2-1
JIS C 8201-2-2
UL 489
CAN/CSA C22.2 NO.5
NEMA AB1
Ampere frame size (AF)
100 125 160 250 400 630 800
50
100 125 250 400 630
ETH132
Usefulness Leading the way in user-friendliness
Compact & High performance
Compact size meeting UL489 480V requirements
& same dimensions as MCCB
Unifying and reducing the types of internal accessories
32 to 100AF
ELCB
MCCB
Rated voltage 480V
(W105×H181×D68mm)
Rated voltage 480V
(W105×H181×D68mm)
Same
dimentions
sInternal and external accessories
A wider range of customer-mountable accessories
ELCB
Technical innovation
Arc and gas flow control technology
Effect of “ablation breaking technology”
125 to 250AF
G-TWIN
sSharing internal accessories of 125/160/250AF breakers.
Shunt trip device
Short-circuit current
Auxiliary switch
Decrease
by
Narrow slit resin
s Increased arc voltage due to narrow
slit effect
s Increased arc voltage and highspeed moving contact opening by
ablation effect
s Suppression of internal pressure rise
by adjusting the narrow slit width
Magnetic yoke arrangement
s An increase in the repulsion
force of the moving contact at
initiation of contact opening
Alarm switch
Ecology
Number of types of internal accessories
AF
-TWIN
G-TWIN
125
8
8
160/250
8
400 to 800AF
Advanced environmental technology
Conforming to the RoHS Directive
The G-TWIN Series is designed to lower
environmental impact.
Moving
contact
Recycling
s For easier recycling, all major parts are marked with the
names of the materials used.
Stationary
Conforming to the RoHS Directive
contact
s Lead-free (Pb-free) solder is used.
6+
s Free of hexavalent chromium (Cr -free)
(125 to 800AF)
Lower environmental impact
Advanced green
engineering and
energy-saving support
Conforming to the RoHS
Directive
G-TWIN
Standard series
ELCB
Compact &
High
performance
ELCB
sThe number of types of internal accessories of
400/630/800AF has been significantly reduced.
GLOBAL TWIN
Ecology
Conforming to certifications
and standards in major
world markets Expanded
frame sizes in G-TWIN
Global Series
Undervoltage trip
device
Auxiliary switch
FUJI MCCB and ELCB
Conforming
to IEC & local
Standards
30%!
Current model
Arc energy
Moving contact cover
s Arcing prevention at the bottom of moving
contact
Undervoltage trip device
Shunt trip device
The Twin Breakers have advanced to
an entirely new stage.
Alarm switch
Earth Alarm switch
Number of types of internal accessories
AF
-TWIN
G-TWIN
400
630
26
6
800
G-TWIN
Global series
ELCB
Compact models with unified
dimensions meeting
UL489 480V and IEC 440V
requirements
G-TWIN
Global series
ELCB
GLOBAL TWIN History
Usefulness
ELCB
Cadmium-free contact material
Shunt trip device
Undervoltage trip
device
Auxiliary switch
Alarm switch
1990 TWIN Breaker 1992 Super TWIN
1995 Super 60
2001 -TWIN
2006 G-TWIN
Leading the way in
user-friendliness
G-TWIN
Standard series
ELCB
Fuji Electric launched the Twin Breaker Series to world markets
in 1990, in which molded case circuit breaker (MCCB) and
earth leakage circuit breaker (ELCB) types were unified in
external dimensions for the first time in the world. The Twin
Breaker Series was highly evaluated and gained strong support,
and the concept of Twin Breakers was established as Japan's
de facto standards for MCCBs and ELCBs.
In 1992, Fuji Electric released the Super Twin Breaker Series,
which enabled user installation of internal accessories for the
first time in Japan.
In 1995, Fuji Electric released the Super 60 Series and
advanced modularization via uniform external dimensions.
In 2001, Fuji Electric launched the -Twin Series to further
advance the miniaturization and modularization of economic
types with 100A frame or less as Japan's first multi-standard
circuit breakers satisfying domestic and inter national
standards. Since then, Fuji Electric has been making further
product improvements by predicting market trends.
In recent years, market globalization has increasingly
accelerated.
At the end of 2004, the Japanese Industrial Standards (JIS)
were aligned with the IEC standards, and the globalization in
this field has been further accelerated.
Based on the Twin Breaker Series, Fuji Electric has expanded
the range of its products conforming to and approved by
international standards for global markets, always advanced
the innovative development of fundamental technologies in
response to the market demand, and developed the G-TWIN
Series of MCCBs and ELCBs.
5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo 103-0011, Japan
URL http://www.fujielectric.co.jp/fcs/eng/
Information in this catalog is subject to change without notice.
2010-8 PDF FOLS ETH132
Your Best Choice is FUJI.
FUJI Earth Leakage Circuit Breakers
G-TWIN series
32AF
50AF
63AF
100AF
125AF
250AF
CNS5422(IEC/EN60947-2, GB14048.2, JISC8201-2-2)
Type
EW32AAG
Pole
2
3
EW32EAG
EW32SAG
EW50AAG
3
3
2
In [A] 5, 10, 15, 20, 30, (32)*2
Rated current
Rated impulse withstand voltage
Uimp [kV] 2.5
Isolation compliant
4
4
Rated sensitive current [mA] 15, 30, 100
Tripping time
4
2.5
EW50RAG
EW63EAG
EW63SAG
EW63RAG
EW100AAG
EW100EAG
EW125JAG
3
3
3
3
3
2
3
10, 15, 20, 30, (32)*2, 60, (63)*2
40, 50
60, (63)*2, 75, 100
50, 60, (63)*2, 75,
100
15, 20, 30, 40, 50, 60, 75, 100, 125
125, 150, 160, 175, 200, 225, 250*1
4
6
6
4
4
6
6
Approved
Approved
Approved
Approved
100-230-440
100-230
100-230
30, 100/200
30, 100/200/500
6
6
100-230-440
100-230-440
100-230
100-230-440
100-230-440
100-230-440
15, 30, 100
30, 100/200/500
15, 30, 100
15, 30, 100/200
30, 100/200/500
30, 100/200/500
[s] 0.1
0.1
Instanteneous/time delay trip type Rated sensitive current [mA] –
15, 30, 100/200
30, 100/200/500
30, 100/200/500
0.1
3
6
4*2
EW125RAG
EW250EAG
EW250JAG
3
3
3
4
100-230- 100-230-440
440
0.1
4*2
30
0.1
–
–
–
–
–
–
–
–
–
100/200/500/1000 changeover
100/200/500/1000 changeover
[s] –
–
–
–
–
–
–
–
–
–
–
–
0.1/0.4/1/2 changeover
0.1/0.4/1/2 changeover
Inertia non-tripping time [s] –
–
–
–
–
–
–
–
–
–
–
–
0/0.2/0.5/1
0/0.2/0.5/1
[Hz] 50-60
AC
440V
50-60
50-60
50-60
3
4
30
0.1
–
Rated frequency
EW250RAG
100-230-440
–
Tripping time
Rated breaking CNS5422
capacity
IEC60947-2
Icu/Ics
[kA] EN60947-2
JIS8201-2-2
EW50SAG
3
Approved
Ue [V AC] 100-230
Instantaneous trip type
EW50EAG
3
3, 5, 10, 15, 20, 30, 5, 10, 15, 20, 30, (32)*2, 40, 50
(32)*2
Approved
Rated voltage
3
50-60
50-60
–
1.5/1
2.5/2
–
2.5/2
7.5/4
10/5
2.5/2
7.5/4
10/5
–
–
10/5
30/15
50/25
18/9
30/15
50/25
240V
–
–
–
–
–
–
–
–
–
–
–
–
–
50/25
100/50
36/18
50/25
100/50
230V
2.5/2
2.5/2
5/3
2.5/2
5/3
10/5
25/13
5/3
10/5
25/13
5/3
10/5
25/13
50/25
415V
400V
380V
GB14048.2
Dimensions
a
AC
100V
2.5/2
400V
–
1.5/1
2.5/2
–
2.5/2
7.5/4
10/5
2.5/2
7.5/4
10/5
–
–
10/5
30/15
50/25
18/9
30/15
230V
2.5/2
2.5/2
5/3
2.5/2
5/3
10/5
25/13
5/3
10/5
25/13
5/3
10/5
25/13
50/25
100/50
36/18
50/25
75
75
50
75
75
75
75
75
75
75
75
90
105
105
100
100
100
100
100
100
100
100
100
100
100
155
165
165
[mm] a
d
c
50
b
b
5/3
5/3
75
100
2.5/2
5/3
75
90
120
155
100/50
140
105
c
60
60
60
60
60
60
60
60
60
60
60
60
68
68
68
68
68
84
84
84
84
84
84
84
84
84
84
84
84
95
95
95
95
95
0.5
0.6
0.4
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
1.3
1.8
1.8
[kg] 0.4
Tripping device
0.5
0.6
Hydraulic-magnetic
1.7
1.3
1.7
140
165
d
Mass
*1 4-pole, 250A Breakers cannot be made.
120
2.3
1.8
2.3
Thermal-magnetic
*2 Contact FUJI.
G-TWIN series
400AF
630AF
HG series
800AF
CNS5422(IEC/EN60947-2, GB14048.2, JISC8201-2-2)
CNS5422(JISC8201-2-2
50AF
100AF
225AF
Ann 2)
DV series
JISC8221
30AF
Ann 2)
Type
EW400EAG
EW400SAG
EW400RAG
EW400HAG
EW630EAG
EW630RAG
EW630HAG
EW800EAG
EW800RAG
EW800HAG
Type
HG53B
HG103B
HG203B
Type
DV32
DV33
Pole
3
3
3
3
3
3
3
3
3
3
Pole
3
3
3
Pole
2
3
Rated current
4
4
In [A] 250, 300, 350, 400
Rated impulse withstand voltage
700, 800
6
6
Approved
Approved
100-230-440
100-230-440
[mA] 30
–
–
[s] 0.1
–
–
100/200/500/1000 changeover
100/200/500/1000 changeover
Uimp [kV] 6
Isolation compliant
Approved
Rated voltage
Ue [V AC] 100-230-440
Rated sensitive current
Instantaneous trip type
Tripping time
Instanteneous/time delay trip type Rated sensitive current
[mA] 100/200/500/1000 changeover
0.1/0.4/1/2 changeover
0.1/0.4/1/2 changeover
[s] 0/0.2/0.5/1
0/0.2/0.5/1
0/0.2/0.5/1
AC
440V
30/15
50-60
36/18
50/25
70/35
36/18
50-60
50/25
70/35
36/18
50/25
70/35
Rated
breaking
capacity
Icu/Ics [kA]
[Hz] 50-60
CNS5422
AC
IEC60947-2
EN60947-2
JIS8201-2-2
400V
380V
50/25
85/43
100/50
125/63
50/25
100/50
125/63
50/25
100/50
Dimensions
a
d
c
100V
AC
400V
230V
Dimensions
a
d
c
b
Mass
Tripping device
65
65
Dimensions
a
b
400V
30/15
36/18
50/25
50/25
85/43
100/50
[mm] a
140
140
140
b
257
257
257
c
103
103
d
146
146
[kg] 5.8
5.8
5.8
Thermal-magnetic
70/35
36/18
125/63
50/25
70/35
36/18
50/25
50/25
100/50
125/63
50/25
100/50
125/63
210
210
210
210
210
257
275
275
275
275
275
275
103
103
103
103
103
103
103
103
146
146
146
146
146
146
146
146
9.1
9.1
9.1
9.6
9.6
9.6
7.8
140
5.8
185
7.8
b
70/35
210
185
240V
–
–
–
230V
100
100
100
100V
125/63
230V
GB14048.2
65
415V
380V
415V
240V
440V
Ue [V AC] 100-200
Mass
Tripping device
[mm] a
b
90
90
105
155
155
165
c
82
82
99
d
104
104
127
[kg] 2.3
2.3
3.3
Thermal-magnetic
[mA] 15, 30
[s] 0.1
[Hz] 50-60
Rated short-time
withstand current
Icw
[s] 0.1
Rated frequency
Rated voltage
Rated frequency
Rated sensitive current [mA] 30, 100/200/500 changeover
Tripping time
In [A] 30
Tripping time
Ue [V AC] 100-230-440
Instantaneous trip type
Rated current
Rated sensitive current
–
Rated voltage
[s] 0.1/0.4/1/2 changeover
15, 20, 30, 40, 50, 1 2 5 , 1 5 0 , 1 7 5 ,
60, 75, 100
200, 225
Uimp [kV] –
Isolation compliant
Inertia non-tripping time
[Hz] 50-60
In [A] 15, 20, 30, 40, 50
Rated impulse withstand voltage
Tripping time
Rated frequency
Rated breaking CNS5422
capacity
IEC60947-2
Icu/Ics
[kA] EN60947-2
JIS8201-2-2
Rated current
500, 600, 630
Mass
Tripping device
d
c
AC200V 1.5
1.5
[kA] AC100V
[mm] a
68
90
b
70
80
c
40
40
d
63
[kg] 0.17
63
0.24
Ground fault protection only
Related documents
Download