Homeworx™ HFC Access Platform HISU Uninterruptible Power

ADCP-61-641 • Issue 1 • July 1999
Homeworx™ HFC Access Platform
HISU Uninterruptible Power Supply
(UPS/Battery Backup) Installation Instructions
Content
Page
INTRODUCTION ........................................................................... 1
Revision History...................................................................... 2
Trademark Information ................................................................. 2
Admonishments ...................................................................... 2
FCC Compliance Statement .............................................................. 2
1
DESCRIPTION ....................................................................... 3
2
INSTALLATION ....................................................................... 4
2.1
Inspect Kit Components and Begin .................................................... 4
2.2
Route the Connection Cable ........................................................ 5
2.3
Connect Cable to the HISU ......................................................... 5
2.4
Connect Battery Inside UPS......................................................... 7
2.5
Connect Cable and Power Cord to the UPS .............................................. 8
2.6
Verify that the UPS is Working....................................................... 9
3
OPERATION (UPS BATTERY ALARMS/LED INDICATORS) .......................................... 9
4
CONSTRUCTING THE CABLE ASSEMBLY ..................................................... 10
4.1
5
Overview .................................................................... 10
4.2
Parts and Tools................................................................ 11
4.3
Construction Procedure and Diagram ................................................. 12
CUSTOMER INFORMATION AND ASSISTANCE ................................................. 14
INTRODUCTION
This instruction manual provides procedures and directions for connecting the HISU
Uninterruptible Power Supply (HISU-UPS or UPS) to the Home Integrated Services Unit
(HISU). This system may also be referred to as the HISU Battery Backup System. The
HISU-UPS provides power backup for the HISU in the event of AC power failure. The UPS
requires an AC input voltage of 90 to 264 V rms and input frequency from 47 to 63 Hz.
The UPS works with a twisted-pair powered HISU that has the battery backup alarm feature
(catalog number ISU-H2UST-30-M-GBD). The UPS will NOT work with (1) coaxial powered
HISUs, and (2) HISUs prior to Release 2.0.1.
The HISU-UPS is ordered separately in kit form and then field-installed with the on-site HISU.
A label with the catalog number is applied to the front of the module for identification purposes.
As an option, ADC offers a factory-assembled cable that is pre-terminated for the HISU alarm
and power connections at one end and stub at the other end. This cable assembly (150 foot
connection cable) may be ordered separately (U.S. catalog number ISU-ACC-PAC01), or may
be constructed in the field using specific materials and tools (see Constructing the Cable
Assembly section of this manual).
1034093 Rev A
Page 1
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
Revision History
ISSUE
DATE
REASON FOR CHANGE
Issue 1
07/99
Original
Trademark Information
ADC and ADC Telecommunications are registered trademarks of ADC Telecommunications, Inc.
Homeworx is a trademark of ADC Telecommunications, Inc.
Admonishments
Important safety admonishments are used throughout this manual to warn of possible hazards
to persons or equipment. An admonishment identifies a possible hazard and then explains
what may happen if the hazard is not avoided. The admonishments — in the form of Dangers,
Warnings, and Cautions — must be followed at all times. These warnings are flagged by use
of the triangular alert icon (seen below), and are listed in descending order of severity of
injury or damage and likelihood of occurrence.
Danger: Danger is used to indicate the presence of a hazard that will cause severe personal
injury, death, or substantial property damage if the hazard is not avoided.
Warning: Warning is used to indicate the presence of a hazard that can cause severe personal
injury, death, or substantial property damage if the hazard is not avoided.
Caution: Caution is used to indicate the presence of a hazard that will or can cause minor
personal injury or property damage if the hazard is not avoided.
FCC Compliance Statement
Warning: This equipment generates, uses, and can radiate radio frequency energy and if not
installed and used in accordance with the instruction manual, may cause interference to radio
communications. It has been tested and found to comply with limits for a Class B digital
device pursuant to Subpart B of Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference when operated in a residential environment.
Operation of this equipment in a residential area is not likely to cause interference to TV and
radio reception in which case the user, at their own expense, will be required to take whatever
measures may be required to correct the interference.
This equipment does not exceed Class B limits for radio emission for digital apparatus, set out
in the radio interference regulation of the authorization methods of Industry Canada.
Operation in a residential area may cause unacceptable interference to TV and radio
reception requiring the owner or operator to take whatever steps are necessary to correct the
interference.
Page 2
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
1
DESCRIPTION
The HISU Battery Backup System (HISU-Uninterruptible Power Supply) provides a dual function:
(1) converts an AC main input voltage to a usable power source for the HISU, and (2) provides the
HISU a battery back-up in the event of an AC line voltage failure. The UPS requires an AC input
voltage of 90 to 264 V rms and input frequency from 47 to 63 Hz.
The UPS works with a twisted-pair powered HISU that has the battery backup alarm
connector feature. These HISUs have a catalog number with a “T” (for “twisted”) immediately
before the second dash (-) and a “B” somewhere after the last dash (-), for example: ISU-H2UST30-M-GBD.
The UPS will NOT work with: (1) coaxial powered HISUs (with an “R” immediately before the
second dash in its catalog number, for example, ISU-H2ESR-21-M-GD, or (2) any HISU released
prior to Release 2.0.1.
The UPS can provide up to approximately 50 Watt-hours of backup power, for example: 6
hours operating at 5 Watts output load plus 2 hours when operating at 10 Watts output load
(6x5+2x10=50), or a hours-load combination that totals less than or equal to approximately 50
Watt-hours.
The UPS unit must be mounted indoors and may be located up to 150 feet from the HISU and is
plugged into a power outlet.
The HISU-UPS battery is capable of recharging once normal power is restored. It should be 80%
recharged within 14 hours after the resumption of normal power. The battery is a sealed lead acid
type battery with a useful life of 5 years under normal usage conditions.
LED #1
LED #2
NORMAL
CHARGE
BACK UP
LOW BATT
LED #3
INDICATOR
PANEL
(FRONT)
SERVICE BATT
CONNECTION
PANEL
(BACK)
12709-A
BATTERY
COMPARTMENT
(BOTTOM)
Figure 1. HISU Battery Backup System Unit
Page 3
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
2
INSTALLATION
Installation consists of the following tasks:
• unpack and inspect the UPS kit
• obtain tools, open HISU covers
• install/route the connection cable (not included in kit)
• connect connection cable to the HISU (to PTBM and connector socket)
• connect the 12 VDC battery inside the UPS
• connect “cut-end” of connection cable to UPS, and 110 VAC power cord to the UPS
• verify proper functioning of the UPS
Danger: To avoid electric shock and possible serious injury or death, exercise care when
working with or near RF distribution cables and taps. They contain hazardous voltages.
Caution: HISUs can be damaged by static electrical discharge. Before HISUs, wear an ESD
anti-static discharge wrist strap to prevent damage to electronic components. Place channel
units in anti-static packing material when transporting or storing.
Caution: To prevent electrical shock, never install telephone equipment in a wet location or
during a lightning storm.
2.1 Inspect Kit Components and Begin
The HISU-UPS kit consists of the following:
• UPS unit (Uninterruptible Power Supply)
• UPS backup battery (packaged and shipped inside the UPS)
• UPS power cord
The installation also requires two items which are not included in the kit: (1) a connection
cable (see Introduction section), and (2) a PTBM (Power Terminal Block Module), or a TTBM
(Twisted-pair Terminal Block Module).
Leave all the Battery Backup System kit components packed in the original packing materials
until you are ready to begin the installation.
When ready to begin,
1. Determine an acceptable location for the UPS as explained in step 1 of the next section.
2. Obtain the necessary tools, including a flat screwdriver, utility knife, drill and bit (if needed).
3. Unpack and inspect kit components to ensure that they are all present and appear OK.
4. Mount unit per local code/practices, using a 5.6 inch (approx. 55/8 inches or 14.2 cm)
displacement between mounting holes. (Note: Some units may not lend to vertical mounting
as may be suggested in the mounting instruction sheet.)
Page 4
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
2.2 Route the Connection Cable
Note: Cable Assembly. The UPS system also requires a power and alarm cable assembly,
which is not included in the HISU-UPS kit. This assembly, a 150 foot cable (45.7 m)
properly terminated at one end with telemetry connector and spade lugs, may be ordered
separately (U.S. catalog number ISU-ACC-PAC01), or may be constructed in the field
using specific materials and tools (see section Constructing the Cable Assembly).
Note: “Cut end” and “Lug-connector end” of cable. One end of the connection cable
has 2 spade lugs and a 5-position female telemetry connector. This end of the cable will
be referred to as the “connector end” of the cable and is connected to the HISU. The
other end of the cable is cut cable (not terminated) and is referred to as the “cut end” of
the cable. The “cut end” will be connected to the UPS after it is routed from the HISU
location to the UPS location, through holes if necessary.
1. Determine an acceptable location for the UPS. This location requires (a) an AC outlet
within reach of the power cord from the UPS, and (b) a cabling distance to the installed
HISU no greater than 150 feet (45.7 m).
Note: Do not connect the cut end of the connection cable to the UPS at this time.
2. If it is necessary to make the cable connection between HISU and UPS by drilling holes,
drill sufficient-sized hole(s) to permit the “cut end” to pass through the hole.
Note: The cable should be run from the HISU to the UPS, not vice versa!
3. Pull the “cut end” of the connection cable from the HISU location to the UPS location.
2.3 Connect Cable to the HISU
See Figures 2 and 3 for this section of the installation. Either a PTBM R2.1 (Power
Terminal Block Module) or TTBM 3.1 (Twisted-pair Terminal Block Module) may be
inserted, depending on the HISU. Specifically, a TTBM R3.1 can be installed on any
Release 3.1 (or higher) HISU, and a PTBM R2.1 can be used for a Release 2.1 HISU which is
factory configured.
MALE
CONNECTOR
LOCATION
12727-A
Figure A. Location of Male Connector on HISU
Page 5
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
1. Open HISU customer and craft covers.
2. Using utility knife, properly slit weather plug (see Figure 2) and pass female connector and
all wires (including 2 twisted wires for PTBM or TTBM) in the correct direction through
the weather plug before connecting the wires to the HISU or the PTBM or TTBM. Reinsert weather plug into HISU housing.
3. Connect the cable’s 5-position female connector into the 5-position male connector on
the lower right of the HISU (Figure A). The connector is keyed to ensure proper
insertion inside the HISU.)
4. If a PTBM or TTBM has already been inserted into the HISU, go to step 4. Otherwise,
insert a PTBM or TTBM as follows:
Position the tab at the bottom of the PTBM (or TTBM) into the slot at the bottom of the
module recess (labeled “POWER”), then rotate the top of the PTBM (or TTBM) down
into the recess until the latch at the top of the module snaps closed.
5. Open the PTBM (or TTBM) cover by pushing upward on the snap on the module. (When
open, two screws can be seen.)
6. Connect the White wire (spade lug) to the “RTN” (right) screw on the PTBM (or TTBM).
7. Connect the Black wire (spade lug) to the “HOT” (left) screw on the PTBM (or TTBM).
POWER
LINE 1 LIN
E2
LINE 3
LINE 4
(B) INSERT PTBM (or TTBM)
(A) PLUG CONNECTOR
IN HERE
2 SPADE LUGS
(OPTIONAL)
5-POSITION
FEMALE CONNECTOR
(NOT TO SCALE)
PTBM
(or TTBM)
(C) CONNECT WIRES
AFTER PTBM (or TTBM)
IS INSERTED
BLACK & WHITE
WIRES (TWISTED)
WEATHER
PLUG
Figure 2. Inserting the PTBM (or TTBM) into the HISU
Page 6
© 1999, ADC Telecommunications, Inc.
12710-B
ADCP-61-641 • Issue 1 • July 1999
HOT
RTN
HOT
BLACK
WIRE
12711-A
WHITE
WIRE
Figure 3. Connecting to the PTBM (or TTBM)
2.4 Connect Battery Inside UPS
The backup system battery is packed UNCONNECTED in the battery compartment of the
UPS. This section ensures that the battery is properly connected to the UPS unit.
BUTTONS
(SNAPS)
SLIDE
12712-A
Figure 4. Bottom of UPS – Battery Compartment
Note: Some UPS battery compartment covers may have screws instead of release buttons
(snaps).
1. Turn the UPS unit upside down as shown (Figure 4).
2. Press (at the same time) the two release buttons (snaps), then slide the cover out. (OR:
Unscrew the screws.)
3. Lift the battery out of the UPS battery compartment.
4. Connect the red wire lead to the positive(+) red post on the battery, and connect the
black wire lead to the negative(–) black post on the battery.
Page 7
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
5. Carefully place the connected battery and wires into the battery compartment so that
there is no obstruction when the cover is closed.
6. Rest the battery compartment cover on the opening and slide it until the two release
buttons snap the cover into place. (OR: screw-in the screws.)
BLACK
POST
(–)
RED
POST
(+)
BACK UP
BATTERY
RED
WIRE
BLACK
WIRE
12713-A
Figure 5. Connecting Wires to UPS Battery
2.5 Connect Cable and Power Cord to the UPS
Refer to Figure 6 for this procedure.
INLET
EXT.
BATT.
ALARM 2
RTN
48 VDC
48 VDC
RTN
ALARM 1
ALARM 2
ALARM 1
RTN
12714-A
Figure 6. Back of UPS – Screw Labels
1. Strip the cable covering so that about 3 inches of each colored wire is free.
Note: The 150 foot cable length is to ensure that the cable will be long enough to reach the
UPS mounting location in most applications. Excess cable may be removed from the “cut
end” or it may be bundled together. Bundling will provide flexibility if the UPS needs to be
relocated at a later time.
Page 8
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
2. Strip the insulation off each colored wire and loosen all screws.
3. Attach proper colored wire to corresponding screw as indicated below:
WIRE
COLOR:
Screw
Label:
DRAIN
BLACK
WHITE
48DCV
48VDC
RTN
GREEN
RED
ALARM 1 ALARM 1
RTN
UNINSULATED GND
BLUE
BROWN
DATA GND
ALARM 2
ALARM 2
RTN
(no connection
on UPS)
4. Repeat step 3 until all wires have been attached to proper screws.
5. Cut the drain lead (uninsulated GND lead) off flush at end of cable insulation jacket.
6. Connect the UPS power cord to the UPS unit.
7. Plug in the power cord to an AC outlet.
2.6 Verify that the UPS is Working
Upon initial application of AC voltage to the UPS, the LOW BATTery LED indicator (Figure 7,
center) may flash on momentarily, then turn off. The NORMAL/CHARGE LED indicator
(Figure 7, left) will start to flash and remain flashing until the battery has become 80% charged
in 14 hours. (See section on Operation.)
Note: Once the 80% charge threshold has been reached, the NORMAL/CHARGE
indicator will turn on and remain on.
3
OPERATION (UPS BATTERY ALARMS/LED INDICATORS)
Figure 7 shows the UPS front panel containing its three (3) LED indicators.
NORMAL
BACK UP
CHARGE
LOW BATT
SERVICE BATT
12715-A
LED
#1
LED
#2
LED
#3
Figure 7. UPS front panel: LED Indicators
Page 9
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
The following table explains the LED indications for several status conditions:
LED# (LOCATION
ON PANEL)
INDICATOR
DESCRIPTION
LED
INDICATION
1
(left)
NORMAL/
CHARGE
FLASHING
Indicates that the battery is being charged (recharged)
and that normal operation from AC power is being
delivered. This LED will remain flashing until the
battery has become 80% charged in 14 hours.
ON (but not
flashing)
Indicates normal AC operation with remaining 20%
of charge to battery being done.
OFF
Indicates that the HISU is running from the normal
AC power source of the UPS.
FLASHING
Indicates there is approximately 25% of battery
capacity left without recharge during battery power
operation.
ON (but not
flashing)
Indicates that back-up power is being delivered, that is,
the HISU is running from the battery source of the UPS.
2
(center)
BACKUP/
LOWBATT
ery
3
(right)
SERVICE
BATTERY
STATUS
CONDITION
OFF
Indicates that the HISU is not running from the
battery source of the UPS.
ON (but not
flashing)
Indicates that the battery can no longer provide
enough capacity to meet the power backup
requirement. The battery must be replaced.
OFF
Indicates that the battery still has enough capacity to
meet the power backup requirement.
The UPS system delivers these alarm conditions, which are explained in the table:
• On Battery Alarm (LED#2 FLASHING) – indicates that back-up power is being
delivered, that is, the HISU is running from the battery source of the UPS.
• Low Battery Alarm (LED#2 ON but not flashing) – indicates there is approximately
25% of battery capacity left without recharge during battery power operation.
• Service Battery Alarm (LED#3 ON) – indicates that the battery can no longer provide
enough capacity to meet the power backup requirement. The battery must be replaced.
Caution: Battery Replacement. The UPS battery should be replaced (1) when the HISU is
operating from AC power, or (2) when the SERVICE BATTERY indicator is ON. The UPS
battery should not be replaced when the HISU is operating from battery power (when LED#2,
the BACKUP/LOWBATTery indicator, is ON or FLASHING), but the SERVICE BATTERY
indicator is OFF (not ON). This ensures that there will be no interruption to HISU service
unless service has already been interrupted and drained the battery to the point where backup
service cannot be maintained.
4
CONSTRUCTING THE CABLE ASSEMBLY
4.1 Overview
This section provides instructions for constructing the cable assembly in the field if the cable
assembly (ADC catalog number ISU-ACC-PAC01) is not ordered. The cable used must be
22AWG, 6 conductor, shielded, with drain. Spade lugs are optional (may or may not be used)
for terminating the Black and White wires (for the PTBM or TTBM).
Page 10
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
The 5-position Female Telemetry Connector may be constructed using either AMP part number
103958-4 or Molex part number 16-02-8052. Both parts require a special tool that is specific to
that manufacturer. This tool must be purchased separately and is not interchangeable for use on
other manufacturer’s parts.
4.2 Parts and Tools
Table 1. Required Parts and/or Tools for Cable Assembly
REQUIRED PART (IF AVAILABLE)
COMPONENT PARTS & TOOLS NEEDED TO MAKE REQUIRED PART
DESCRIPTION
QTY.
MFGR. PART NO.
COMMENTS / TOOLS NEEDED
1)
1 ea
AMP/103958-4
Strip Form,
Polarized/
Latching, Single
Row .100”
(2.54mm)
Centers
Receptacle assemblies are furnished
with strip contacts partially inserted into
housing, with contacts latched into
“pre-load” windows. Contacts are fully
inserted into housings when terminated
with the proper manufacturer’s hand
tool:
When using AMP parts:
AMP Manual Pistol Grip Tool –
Handle Assembly
AMP Part No. 58074-1
Modular Head Part No.
AMP 58336-1.
or
When using Molex parts:
Molex Hand Tool Handle,
Molex Part No. 11-21-5194,
required for all modules.
Module for 2.54mm (.100”)
Molex Part No. 11-31-7597
When using AMP parts:
AMP Pro-Crimper II Hand Tool:
tool only, die set only, and tool with die set.
AMP / 354940-1
Tool frame:
AMP / 58423-1
Die Set:
Tool with die set: AMP / 58433-3
or
When using Molex parts:
Molex Hand Tool:
Molex / RHT-1990
Telemetry Connector
Receptacle (MTE, 5 Position
22-26 AWG*, Female, Positive
Latch, Polarized)
*AWG = American Wire Gauge
or
Molex /
14-56-8052
2.54mm (.100”)
Pitch C-Grid SL
Insulation
Displacement
Connector
2)
Spade Lugs (optional)
(Flanged, Insulated,
22-26 AWG*, # 6 Post
2 ea
AMP / 51874
Flanged spade
tongue terminal,
insulated PIDG
or
3)
Heatshrink
(.25" Black)
3)
Cable
22AWG* 6 Conductor, Shielded,
with Drain (uninsulated wire)
1.5
inches
see
comment
MOLEX /
AA-215-06X
Spade tongue
terminal,
INSULKRIMP
RAYCHEM /
RNF100-1.4-0,
BLK
or equivalent
BELDEN /
5504FE
The Heatshrink must overlap the Cable
by at least 1/4 inch. See Figure 8.
The actual amount of cable needed is
determined at the time of installation.
*AWG = American Wire Gauge
Page 11
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
4.3 Construction Procedure and Diagram
Figure 8 and the following procedure define the construction of the Cable Assembly.
5-POSITION
TELEMETRY
CONNECTOR
ARROW > NOTCH
INDICATING
PIN 1
END OF CABLE
INSULATION
0.25 IN.
(0.64 CM)
HEATSHRINK
PIN 1 – GREEN
HEATSHRINK
OVERWRAP AT
LEAST 0.25 IN.
(0.64 CM)
PIN 2 – RED
PIN 3 – DRAIN
PIN 4 – BLUE
PIN 5 – BROWN
22 AWG,
6-CONDUCTOR,
SHIELDED CABLE,
WITH DRAIN
BLACK
1.5 IN.
(3.8 CM)
SPADE LUGS
(OPTIONAL)
12724-A
WHITE
9 IN. (22.9 CM) AFTER TWISTING
AT LEAST 3 TWISTS PER INCH
(1 TWIST PER CM)
1.25 IN.
(3.18 CM)
Figure 8. Construction of Cable Assembly
Note: (a) The Heakshrink width (diameter) and the size of the Telemetry Connector
shown in the figure are exaggerated to show all the cable wires. Once the Heatshrink has
been shrunk, the shrinkage will actually be much narrower than that shown in Figure 8.
Note: (b) If the optional spade lugs are not used, the length of the Black and White
wires must be 9.5 inches (not 9 inches) after twisting.
1. Obtain the necessary parts and tools.
2. If the Telemetry Connector is already built, go to step 4.
3. To build the Telemetry Connector: Use the manufacturer’s special tool to connect the 5
Female Terminals to the Telemetry Connector Housing.
4. Place the 1.5 inch (3.81 cm) long Heatshrink over the Telemetry Connector end of cable,
then slide it back over the cable (at least 11.5 inches (29.21 cm) from the end) so that it
will not interfere with what needs to be done in the remaining steps of this procedure.
5. Strip 11.5* inches (29.21 cm) of insulation from cable, exposing all wires. *If spade
lugs will not be used, strip 12.5 inches (31.75 cm) of insulation.
6. Starting from the insulation of the cable, twist the Black and White wires so that the
twisting yields the required length of at least 10.25 in (26.04 cm) of twisted wire. DO
NOT OVERTWIST OR UNDERTWIST. A twisting of at least 3 turns per inch (about 1
turn per cm) should yield the required length.
Page 12
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
Note: The required length of at least 10.25 inches is the sum of the 1.25 inch of twisted
wire that will be under the Heatshrink (1.5” – 0.25”) plus at least 9 inches of twisted wire
beyond the Heatshrink.
7. Strip enough insulation from the ends of the Black and White wires only (NOT the other
wires) to allow for proper termination to the spade lugs, or directly to the PTBM (or
TTBM) if spade lugs are not used (see Note (b) above).
8. If spade lugs are to be used, connect the lugs to the Black and White wires using the
proper crimping tool (see Table 1).
9. Cut the remaining 5 wires so that exactly 1-13/16” (1.8125 inches, 5.08 cm) of each
wire is exposed from the cable’s insulation. (This length is the sum of 11/16” of wire
that will be in the connector pin, plus 1/4” between the Connector and the Heatshrink,
plus the 11/4” that will be under the Heatshrink (1.5” – 0.25”)).
Note: The pin-connectors are insulation displacement type. DO NOT STRIP THE
WIRES! (Stripping the wires may not allow proper contact to the connector. Stripping
the wires is NOT recommended.)
10. Without stripping the wires, connect each of the 5 remaining wires to the proper pin of
the Connector as shown in Figure 8 and listed in Table 2. Pin 1 is labeled with an
arrow ( >) notch.
Table 2. Telemetry Connector Wire-to-Pin Connections
WIRE COLOR
CONNECT TO
CONNECTOR PIN
GREEN wire
connect to
Pin 1 (>)
RED wire
connect to
Pin 2
DRAIN (uninsulated)
connect to
Pin 3
BLUE wire
connect to
Pin 4
BROWN wire
connect to
Pin 5
11. Pull the Heatshrink into place around all the wires as shown in Figure 8, making sure that
(a) the Heakshrink overlaps the end of the cable’s insulation by at least 1/4 inch (0.64 cm)
and that (b) the Heakshrink is about 1/4 inch (0.64 cm) from the Telemetry Connector,
leaving about 1/4 inch (0.64 cm) of the 5 wires exposed for flexibility.
12. Apply proper heat, then ensure that the Heatshrink has shrunk properly, leaving a smooth
and tight fit terminating the cable with the Telemetry Connector.
13. Check to see that all wires are properly connected and that the proper lengths exist. If there
has been a mistake in wiring or the lengths are not as specified, repeat this entire procedure
until the assembly is as specified. If the constructed Cable Assembly is as specified, follow
the Connect Cable to HISU section of this manual when ready to connect.
Page 13
© 1999, ADC Telecommunications, Inc.
ADCP-61-641 • Issue 1 • July 1999
5
CUSTOMER INFORMATION AND ASSISTANCE
For customers wanting information on ADC products or help in using them, ADC offers the
services listed below. To obtain any of these services by telephone, first dial the central ADC
telephone number, then dial the extension provided below.
The central number for calls originating in the U.S.A. or Canada is 1-800-366-3891. For calls
originating outside the U.S.A. or Canada, dial country code “1” then dial 612-946-3000.
Sales Assistance
Extension 2300
• Quotation Proposals
• Ordering and Delivery
• General Product Information
Systems Integration
Extension 3000
•
•
•
•
•
•
Complete Solutions (from Concept to Installation)
Broadband Design
Project Engineering and Administration
Detail Engineering
Drafting Services
End-to-End Installation
BND Technical Assistance Center
Extension 2300
E-Mail:
aps_tech_center@adc.com
•
•
•
•
•
•
•
Technical Information
System/Network Configuration
Product Specification and Application
Training (Product-Specific)
Installation and Operation Assistance
System Turn-Up and Test
Troubleshooting and Repair
Product Return Department
Extension 3748
E-Mail: repair&return@adc.com
• ADC Return Authorization number and instructions must
be obtained before returning products.
Product information may also be obtained using the ADC web site at www.adc.com or by
writing ADC Telecommunications, Inc., P.O. Box 1101, Minneapolis, MN 55440-1101, U.S.A.
Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice. In
no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further
disclaims any and all liability for indirect, incidental, special, consequential or other similar damages. This disclaimer of
liability applies to all products, publications and services during and after the warranty period.
This publication may be verified at any time by contacting ADC’s Technical Assistance Center at 1-800-366-3891, extension
2300 (in U.S.A. or Canada) or 612-946-2300 (outside U.S.A. and Canada), or by writing to ADC Telecommunications, Inc.,
Attn: Technical Assistance Center, Mail Station #71, P.O. Box 1101, Minneapolis, MN 55440-1101, U.S.A.
© 1999, ADC Telecommunications, Inc.
All Rights Reserved
Printed in U.S.A.
Page 14