ExplosionProtection An International Comparison Guide for the Oil & Gas Industry USA & CANADA EUROPE (National Electrical Code / Canadian Electrical Code) (Atmosphere Explosive) Explosion Protection 1.0 Hazardous-Area Classification Hazardous locations are defined as areas where fire or explosion hazards may exist due to the presence of flammable gases or vapours, liquids or dusts. • • 1.2 European Classification (CENELEC) 1.3 Australian Classification (IEC) 1.4 IEC Classification (NEC 505, CEC Section 18) • • Within Europe, the ATEX directives are imposed as a minimum requirement for Ex legislation. • Australia has also implemented the IEC’s International Zoning System. • The IEC’s International Zoning System has become increasingly accepted worldwide. • ATEX 1999/92/EC enforces hazardous area classification of work places into zones depending on the frequency and time that an explosive atmosphere is present. • For further information on the Australian IEC hazardous classification system, see: AS/NZS60079.10 (NB. This standard has replaced the formally, AS2430.1) • Although the IEC’s system aims to create a standardised approach to Explosion Protection, users and manufactures should be aware that many nations such as the US have incorporated a number of countryspecific deviations in order to comply to current wiring methods under the NEC. North American Ex standards in both the US and Canada follow two different approaches; the traditional ‘Class, Division’ method under NEC 500 (US) / CEC Annex J (Canada) and the new, ‘International Zoning System’ under NEC 505 (US) / CEC Section 18 (Canada). Flammable Atmosphere Present Continuously ZONE 1 *DIVISION 1 ZONE 2 *DIVISION 2 CEC Section 18 CEC Annex J ZONE 0 *DIVISION 1 ZONE 1 *DIVISION 1 ZONE 2 *DIVISION 2 Groups further define the type of hazard in a Class I location: Group Type Group A Group B Group C Group D Group A hazards represent gases with extremely high explosion pressures while Group D represent gases with lower explosion pressures. Temperature classes are assigned to indicate the safe working limit of the gases and vapours that could be present in a hazardous area. Throughout the world, differing country-specific standards impose different equipment marking methods, so it is important to understand how they compare. • For more information, visit www.pyroban.com/information-faq.html • • Atmospheres containing... Acetylene & similar gases Hydrogen & similar gases Ethylene, & similar gases Propane & similar gases Maximum Surface Temp. 450˚ C (842˚F) 300˚ C (572˚F) 280˚ C (536˚F) 260˚ C (500˚F) 230˚ C (446˚F) 215˚ C (419˚F) 200˚ C (392˚F) T Class T1 T2 T2A T2B T2C T2D T3 Maximum Surface Temp. 180˚ C (365˚F) 165˚ C (329˚F) 160˚ C (320˚F) 135˚ C (275˚F) 120˚ C (248˚F) 100˚ C (212˚F) 85˚ C (185˚F) ZONE 1 ZONE 2 IEC For more information, visit www.pyroban.com/aus Flammable Atmosphere is likely to occur in normal operation Flammable Atmosphere is not likely to occur in normal operation ZONE 0 ZONE 1 ZONE 2 • IEC 60079-10 - Electrical Apparatus for Explosive Atmospheres, Classification of Hazardous Areas. • Australia has adopted the IEC methods of classifying explosion groups. • • Hazardous areas with gas or vapours present designated Group II locations and the gases which make up atmosphere are sub-categorised under the IEC’s three groups, A, B and C. Group Type Group A Group B Group C ATEX has adopted the IEC’s methods of temperature classification, appointing a more generalised classification to a range of temperatures rather than the North American approach, using a number of further T-Classes. Maximum Surface Temp. ˚C ˚F 450˚ C 842˚ F 300˚ C 572˚ F 200˚ C 392˚ F 135˚ C 275˚ F 100˚ C 212˚ F 85˚ C 185˚ F T Class T3A T3B T3C T4 T4A T5 T6 ZONE 0 Flammable Atmosphere Present Continuously 2.4 IEC Explosion Groups (NEC 505, CEC Sec. 18) Group Type Atmospheres containing... Group A Acetone, Methane & similar gases Acetaldehyde, Ethylene & similar gases Group B Group C Acetylene, Hydrogen, & similar gases • The traditional North American ‘Class, Division’ system uses a unique temperature classification system to that adopted under the IEC. Flammable Atmosphere is not likely to occur in normal operation 2.3 Australian Explosion Groups These groups are defined under EN60079 Group IIA gases represent gases most difficult to ignite while Group IIC represents gases easiest to ignite Flammable Atmosphere is likely to occur in normal operation For further information on IEC hazardous classifications, see: • In comparison to the traditional North American standards, ATEX classifies atmospheres containing flammable gases / vapours as Group II hazardous areas. • for more information, visit www.pyroban.com • • • Special precautions need to be taken in hazardous areas to prevent equipment becoming a source of ignition. Flammable Atmosphere Present Continuously Australia ZONE 2 • 3.2 European Temperature Classification (CENELEC) Different country-specific Ex standards have appointed different temperature classification systems so it important to ensure your Ex equipment is modified to the correct level of protection. Explosion Proof equipment should be supplied with certified documentation and be clearly marked, displaying the measures the equipment has undergone to operate in classified hazardous areas. ZONE 1 3.1 North American Temperature Classification (NEC 500 / CEC Annex J) Equipment and apparatus working in a hazardous area must be designed / modified to the assigned TClass to ensure surface temperatures do not exceed the ignition temperature of hazardous gases and vapours. 4.0 Equipment Marking / Certification ZONE 0 Flammable Atmosphere is not likely to occur in normal operation 2.2 European Explosion Groups (CENELEC) The NEC & CEC Division systems use Classes and Groups to identify a hazard. The systems refer to Class I environments, where gases & vapours represent an explosive atmosphere, most commonly present in the oil and gas industry. Worldwide, there are a number of different systems in place. The traditional North American ‘Class, Division’ system uses a different system to that used under ATEX in Europe and by the IEC, altering the way in which equipment manufactures build and mark certified Ex equipment. 3.0 Temperature Classifications • ATEX 1999/92/EC 2.1 North American Explosion Groups (NEC 500 / CEC Annex J) • • Flammable Atmosphere is likely to occur in normal operation Flammable Atmosphere Present Continuously * The Division classifications stated above are in accordance to Class 1 areas. for more information, visit www.pyroban.com • Flammable Atmosphere is not likely to occur in normal operation ZONE 0 *DIVISION 1 for more information, visit www.pyroban.com • Flammable Atmosphere is likely to occur in normal operation NEC 505 NEC® 500 ® Hazardous area classification should be carried out as an integral part of the risk assessment to identify areas where control over ignition sources is needed. Explosion groups are designated to classified hazardous areas to identify the ignition related properties of an explosive atmosphere. IECEx (International Electrotechnical Commission) 1.1 North American Classification Worldwide, differing Ex standards use Hazardous area classifications to classify environments dependant on the frequency and persistence of a potentially explosive atmosphere occurring. 2.0 Explosion Groups AS/NZS ATEX NEC / CEC Essential Requirements WORLDWIDE AUSTRALIA Atmospheres containing... Acetone, Methane & similar gases Acetaldehyde, Ethylene & similar gases Acetylene, Hydrogen, & similar gases are the • The IEC’s apparatus grouping system has been adopted by the ATEX directives in Europe and throughout the world, including the US (NEC 505) Canada (CEC Sec. 18) and Australia. The groups below, assigned to gases and vapours are categorised as Group II locations, as used in Europe. Group Type Group A Group B Group C For more information on the Australian IEC’s gas grouping system, see: AS/NZS2430.3.4 Atmospheres containing... Acetone, Methane & similar gases Acetaldehyde, Ethylene & similar gases Acetylene, Hydrogen, & similar gases 3.3 Australian Temperature Classifications 3.4 IEC Temperature Classification • • Australia has also adopted the IEC methods of temperature classification. • Maximum Surface Temp. ˚C ˚F 450˚ C 842˚ F 300˚ C 572˚ F 200˚ C 392˚ F 135˚ C 275˚ F 100˚ C 212˚ F 85˚ C 185˚ F T Class T1 T2 T3 T4 T5 T6 Group IIA gases are similar to the NEC Group D gases. Group IIB are similar to NEC Group C while IEC Group IIC gases are similar to NEC group A & B. The IEC’s new international approach has been adopted by many nations and Ex standards. For more information on IEC temperature classification, see: IEC 60079-20 Maximum Surface Temp. ˚C ˚F 450˚ C 842˚ F 300˚ C 572˚ F 200˚ C 392˚ F 135˚ C 275˚ F 100˚ C 212˚ F 85˚ C 185˚ F T Class T1 T2 T3 T4 T5 T6 T Class T1 T2 T3 T4 T5 T6 4.1 North American Equipment Marking (NEC 500 / CEC Annex J) 4.2 European Equipment Marking (CENELEC) 4.3 Australian Equipment Marking 4.4 IEC Equipment Marking (IEC, NEC 505, CEC Sec. 18) • • • Electrical equipment used in a hazardous area must be certified to the IEC or Australian standards via an acceptable certification scheme. Acceptable schemes include IECEx, ANZEx and AUSEx. • • Other equipment (e.g. ATEX, FM, UL) can usually be used if the legal owner justifies and accepts their use and an assessment is made as to the equivalence in safety of the equipment compared to IECEx / ANZEx or AUSEx equipment NEC 500 / CEC Annex J Equipment Marking: ATEX Equipment Marking: Ex Standard Typical Example of Equipment Marking Ex Standard NEC 500 / CEC Annex J CLASS 1, DIVISION 1, GROUPS A, B, C, D, T5 ATEX 94/9/EC Typical Example of Equipment Marking , II, 2G, Ex, de, IIC, T5 ATEX 94/9/EC NEC 500 / CEC Annex J (Class 1 = Hazard Class, Division 1 = Area Classification, Groups A, B, C, D = Permitted gas groups, T5 = Equipment Temperature Class) ( = CE Conformity Marking, = EU Explosion-Protection Marking, II = Equipment Groups [I = for mines, II = for other than mines], [2 = Equipment Category, G = Type of Ex Atmosphere; G (Gas), D (Dust)], Ex = Explosion Protected according to CENELEC standards, de = Protection Method, [II = Apparatus Group, C = Gas Group], T5 = Temperature Class for more information, visit www.pyroban.com Ex Standard Typical Example of Equipment Marking AS/NZS2381 Ex, de, IIC, T5 IEC Equipment Marking: Ex Standard Typical Example of Equipment Marking IEC & CEC Sec. 18 Ex, d, [ia], IIC, T5 NEC 505 Class I, Zone 1, AEx, d, [ia], IIC, T5 IEC & CEC Sec. 18: AS/NZS2381: Ex = Explosion-Protected, de = Protection technique, II = Apparatus Group, C = Gas Group, T5 = Temperature Class 5.0 Protection Concepts, Methods & Standards (Ex = Explosion-Protected, d = Type of Protection, [ia] = I.S Output, II = Group, C = Gas Group, T5 = Temperature Class NEC 505: (Class I = Permitted Class, Zone 1 = Permitted Zone, AEx = American National Standard, d = Type of Protection, [ia] = I.S Output, II = Group, C = Gas Group, T5 = Temperature Class 5.1 Equipment Certified for Use Protection Method Id. Letter IEC CENELEC CSA (IEC) CSA (Annex J) NEC 505 NEC 500 AS/NZS Type of Protection Mode of Function NEC 500 / CEC Annex J Permitted Division IEC / CENELEC Permitted Zone Flameproof d IEC 60079-1 EN 60079-1 CSA E60079-1 CSA C22.2 No. 30 ISA 60079-1 FM 3618 AS/NZS60079-1 / AS2380.2 Explosion is Contained Enclosure contains internal explosion Division 2 Zone 1 or 2 Intrinsic Safety ia IEC 60079-11 EN 60079-11 CSA E60079-11 CSA C22.2 No. 157 ISA 60079-11 FM3610 AS/NZS60079-11 / AS2380.7 Sparks are not ignition capable (Safe 2 faults) I.S. circuits are unable to cause ignition Division 1 or 2 Zone 0, 1 or 2 Intrinsic Safety ib IEC 60079-11 EN 60079-11 CSA E60079-11 CSA C22.2 No. 157 ISA 60079-11 FM3610 AS/NZS60079-11 / AS2380.7 Sparks are not ignition capable (Safe 1 faults) I.S. circuits are unable to cause ignition Division 2 Zone 1 or 2 Pressurisation p IEC 60079-2 EN 60079-2 CSA E60079-2 CSA TIL. E13 A ISA 60079-2 FM 3620 AS/NZS60079-2 / AS2380.4 Flammable atmosphere is eliminated Protection by over pressured enclosure Division 1 or 2 Zone 1 or 2 Increased Safety e IEC 60079-7 EN 60079-7 CSA E60079-7 -------- ISA 60079-7 FM 3619 AS/NZS60079-7 / AS2380.6 Source of ignition eliminated Division 2 Zone 1 or 2 Oil Immersion o IEC 60079-6 EN 60079-6 CSA E60079-6 -------- ISA 60079-6 FM 3621 AS/NZS60079-6 Flammable atmosphere is eliminated Electric sparks & high temp. possibilities eliminated Protection by Immersion Division 1 or 2 Zone 1 or 2 Encapsulation m IEC 60079-18 EN 60079-18 CSA E60079-18 -------- ISA 60079-18 FM 3614 AS/NZS60079-18 Flammable atmosphere is eliminated Encapsulated apparatus Division 2 Type ‘n’ Protection n IEC 60079-15 EN 60079-15 CSA E60079-15 CSA C22.2 No. 213 ISA 60079-15 ------- AS/NZS60079-15 Non-Sparking apparatus * Ventilation v -------- -------- -------- -------- -------- -------- AS 1482 n Protection includes several methods of ignition protection Flammable atmosphere eliminated Protection by Ventilation Equipment Certified for Use Equipment Certified for use in: Use Appropriately NEC 500 Class 1, Div. 1 NEC 500 Class 1, Div 2 NEC 505 Class 1, Zone 1 NEC 505 Class 1, Zone 2 OK for use in NEC 505 Class 1, Zone 1 & 2 OK for use in NEC 505 Class 1, Zone 2 NOT OK for use in NEC 500 Class 1, Div. 1 OK for use in NEC 500 Class 1, Div. 2 NEC AEx NEC AEx NEC AEx OK for use in NEC Zone 0, 1 2 as marked Not suitable for NEC 500 Class 1, Div. 1 Not suitable for NEC 500 Class 1, Div. 2 Zone 1 or 2 IEC Zone 1 IEC Zone 2 Not suitable for any NEC 500 areas Not suitable for any NEC 500 areas Division 2 Zone 2 IEC Ex Not suitable for any NEC / CEC areas -------- ----- * Only recognised in Australia Pyroban Ltd UK Endeavour Works Dolphin Road, Shoreham-by-Sea West Sussex, BN43 6QG, UK Tel: +44 (0) 1273 466200 Fax: +44 (0) 1273 465313 e.mail: info@pyroban.com Web: www.pyroban.com protecting people, their investment and our environment NB: The information in this wall chart is for guidance only. For detailed information see the relevant Directives, Regulations and Standards or contact us at info@pyroban.com