Automation Products Variable Frequency Drives Soft Starters Panels Industrial Control Products This catalog will be periodically updated with new and updated pages. The current version and update packages can be found on our website www.pamensky.com or can be requested from V.J. Pamensky Canada Inc. 1 877 PAMENSKY. PAMENSKY 101 TERMS AND CONDITIONS OF SALE V.J. PAMENSKY CANADA INC. 1. EXCLUSIVE CONDITIONS OF SALE: This Quotation or Order is subject to terms and conditions contained here-in and supersedes Buyer’s Specification and/or Purchase Order. Seller will recognize no modifications or additions to these conditionsunless specifically agreed to in writing by Seller. Failure of Seller to object to provisions contained in the Purchaser’s Order or any other communication from Buyer shall not be construed as a waiver of these conditions or an acceptance of any such provisions. If Buyer places an Order with Seller based on Seller’s Quotation, whether the Order is placed in writing or orally, then the Quotation (including Seller’s terms and conditions) and the Seller’s acceptance of the Order will constitute the entire contract between Buyer and Seller with respect to the subject matter thereof notwithstanding any terms and conditions inconsistent with these terms and conditions on any of Buyer’s forms or correspondence. All orders, sales contracts and other documentation between Buyer and Seller shall become effective only when approved and accepted by the Seller. 2. PRICES: Prices quoted herein are based upon presently prevailing duties, rates of duties, taxes, special assessments, monetary exchange and freight as applied to materials and/or equipment purchased or imported by Seller. Seller reserves the right to amend the price(s) in this quotation where variations in regulated costs such as rate of duties, taxes, special assessments, monetaryexchange and freight between the date of quotation and date of delivery are deemed significant by the Seller. 3. TERMS OF PAYMENT: The standard terms of payment are Net-30 Days from date of invoice, with a service and interest charge of 1-1/2% per month (18% per annum) on past due invoices applying. If Buyer defaults in any payment when due or refuses to accept delivery or becomes insolvent, the Seller at its option, without prejudice to other lawful remedies, may defer deliveries or cancel the remainder of the order. Equipment held for Buyer shall be at the risk and expense of Buyer and payment shall become due from the date of which Seller is prepared to make shipment. Printed terms on face of our Quotation will take precedence. 4. TITLE: Title to the goods covered by this Quotation and the right to immediate possession thereof shall remain with the Seller until the purchase price is paid in full and Buyer hereby grants to Seller a security interest in the equipment (and all proceeds thereof) to secure the Buyer’s obligation to pay for the equipment. 5. CERTIFICATIONS AND TAXES: Prices do not include sales, use or other similar federal, state or local taxes. Any certification for special duty or tax rate must be supplied at time of order. A service charge will be applied on any credit notes necessitated by the Buyer not providing proper certification at time of order. Exception from taxes extended to the buyer does not prejudice our right to charge the buyer with taxes plus any penalties assessed at any subsequent date should the taxing authorities determinethat the equipment is taxable. 6. PENALTIES AND DELAYS: No penalty clause of any kind, in any specification of order will be effective unless specifically approved in writing by Seller. Seller shall not be liable for any damage, expenses or consequential damages caused by delays beyond Seller’s control including without limiting the generality of the foregoing; fire, strike, act of the Buyer, restriction by civil or military authority, Act of God, transportation failures or inability to obtain labor, materials or manufacturing facilities. In the event of any such delay, the date of delivery shall be extended for a period equal to the time lost by reason of the delay. 7. CANCELLATION: Orders once accepted are not subject to cancellation unless on terms that will indemnify Seller against loss and/or expenses incurred. 8. SHIPMENT: Unless otherwise specified in writing, all shipments are EX-WORKS (Incoterms 2000) Seller’s shop, in which case Seller is not responsible for damage, apparent or concealed, or loss in transit and all claims on “collect” shipments must be made by Buyer direct to the carrier. Seller will assist insofar as practical in securing satisfactory adjustment to reasonable claims. 9. ACCEPTANCE, INSPECTION: By virtue of Buyer issuing an order for equipment in accordance with this Quotation, he also accepts Seller’s Terms and Conditions as part of the order. Buyer shall inspect the goods immediately upon the receipt thereof. All claims by Buyer (including claims for shortages), except only those provided for under the WARRANTY clauses below, must be asserted in writing by Buyer within a 10 day period or they are waived. If this contract involves partial performances, all such claims must be asserted within a 10-day period for each partial performance. 10. WARRANTY: Seller warrants to the Buyer that its products are free from defects in workmanship and materials when operated under normal conditions and in accordance with nameplate characteristic limits. This warranty will be in effect for the following time period and for the following products: Low voltage standard efficiency motors NEMA & IEC frames are warranted for a period of 12 months from date of installation, but not more than 18 months from date of manufacture. EPACT & NEMA Premium Efficiency motors both NEMA & IEC frames are warranted for a period of 24 months from date of installation but for not more than 30 months from date of manufacture. IEEE841 motors are warranted for a period of 60 months from date of installation but for not more than 66 months from date of manufacture. Machines & Generators are warranted for a period of 12 months from date of installation, but not more than 18 months from date of manufacture. These products include but are not limited to; Above NEMA size Motors: low voltage, medium voltage and high voltage, DC motors, Turbo Generators, Hydro Generators, Synchronous Motors, and Wound Rotor Motors. Automation products (variable frequency drives and soft starters) and Electrical components are warranted for a period of 12months from date of installation, but not more than 18 months from date of manufacture. If any defects are claimed by the Buyer during the 101 warranty period, Seller’s sole obligation shall be limited to alteration, repair or replacement at Seller’s expense, EX-WORKS (Incoterms 2000) Seller’s shop, on parts or equipment which upon return to Buyer and upon Buyer’s examination prove to be defective. UNLESS OTHERWISE SPECIFIED IN WRITING HEREIN, THERE ARE NO REPRESENTATION, WARRANTIES OR CONDITIONS, EXPRESSED OR IMPLIED STATUTORY OR OTHERWISE, EXCEPT FOR THE FOREGOING AND WITHOUT LIMITING THE GENERALITY OF THE ABOVE, THERE ARE NO EXPRESS OR IMPLIED REPRESENTATIONS OR WARRANTIES CONCERNING THE QUALITY OF THE EQUIPMENT OR THAT ANY SUCH EQUIPMENT WILL BE FIT FOR ANY PARTICULAR PURPOSE OF THE PURCHASER. THE SELLER SHALL HAVE NO OBLIGATION TO REPAIR OR REPLACE SUCH PRODUCTS OR PARTS UNLESS IT RECEIVES AT ITS OFFICES IN CANADA WRITTEN NOTICE OF SUCH DEFECT WITHIN THE ABOVE-MENTIONED WARRANTY PERIOD. This warranty does not cover the cost of transportation, labor, removal, installation, or re-testing of the new or repaired goods or parts, or any other direct or incidental expenses incurred in shipping the product to or from Seller. Replacement goods or parts are warranted for the remainder of the warranty period applicable to the goods originally supplied by the seller. No warranty shall apply to any equipment upon which repairs or alterations have been made unless authorized by Seller, nor to equipment which hasbeen subjected to misuse, negligence or mishandling. 11. DAMAGES: Subject to the balance of the provisions of this clause, Seller shall only be liable for the cost of replacement of any defective Equipment provided hereunder. Seller shall not be liable to the Buyer in any circumstances for any incidental, special, consequential or indirect damages, including but not limited to loss of profits or revenue, loss of use of equipment and facilities, and claims by or payments to customers, suppliers or other parties who have a relationship with the Buyer. This disclaimer applies to consequential damages based upon any cause of action whatever asserted against Seller including causes of action arising out ofany breach of warranty, express or implied, guarantee, product liability, negligence, tort, or any other cause pertaining to the performance or non-performance of this Quotation or contract by Seller and the Buyer hereby waives any right to claim punitive,aggravated or exemplary damages with respect to a breach of this Quotation or the performance or non-performance of the Equipment, and whether such claim is founded in contract, tort or otherwise. Seller shall not be responsible for losses or damages arising out of the negligence of the Buyer, its’ employees, agents or third party contractors. In no event will Sellers maximumliability to the Purchaser in connection with the Equipment, including without limitation resulting from breach of contract or any other performance or non-performance of this Quotation or contract, exceed the amount of the purchase price paid to Seller hereunder. 12. RETURNING EQUIPMENT: No equipment is to be returned without first obtaining from Seller shipping instructions and a return material identification number and agreement in writing as to terms. Returned equipment, which Seller elects to accept for credit is subject to reasonable handling and restocking charge commensurate with the policy of the manufacturer plus all charges incurred by Seller. Seller is not responsible for equipment that is returned without complying with the foregoing. Equipment isreturned at the expense and risk of the Buyer. Returned equipment must be in the original packaging and unused. 13. PRIVILEGE AND LIEN RIGHTS: Seller retains all lien rights with regard to the equipment in accordance with any Builder’s Lien Act, Mechanic’s Lien Act, Builder and Works Act or other legislation passed pursuant to or in replacement thereof. 14. BACK CHARGES: Seller will accept no back charges for any reason without Seller’s written permission to incur such back charges. 15. TECHNICAL ADVICE: Any technical advice furnished or recommendation made by Seller or any representative of Seller concerning any use or application of any of the goods is believed to be reliable, but SELLER MAKES NO WARRANTY, EXPRESSED OR IMPLIED, ON RESULTS TO BE OBTAINED. BUYER ASSUMES ALL RESPONSIBILITY FOR LOSS OR DAMAGE RESULTING FROM THE HANDLING OR USE OF ANY OF THE GOODS. 16. INVALIDITY: If any provision of this contract shall be found to be invalid or illegal by reason of any determination made by a court of competent jurisdiction or any governmental authority having jurisdiction in the circumstances, such provisions shall be severed from this contract to the extent of such invalidity or illegality and the validity, legality or enforceability of the remaining provisions of this contract shall not in way be affected or impaired thereby. Waiver of any default shall not be a waiver of any other or subsequent default. 17. GST NUMBER: V.J. Pamensky Canada Inc. GST Number is 105553648 18. APPLICABLE LAWS AND FORUM: This contract shall be interpreted in accordance with and shall be governed by the laws of the Province of Ontario, and the parties agree that any disputes hereunder or with respect to this quotation or the resulting contract between the parties shall be determined exclusively by the Courts in the Province of Ontario, and the parties hereby expressly attorn to the exclusive jurisdiction of the Courts in the Province of Ontario. 19. LANGUAGE: The parties acknowledge that they have required that this contract and all related documents be prepared in English. Les parties reconnaissent avoir exige que la présente convention et tous les documents connexes solent rédigés en anglais. If the Buyer requests, a French version of this agreement will be used. 20. LIABILITY: Notwithstanding anything to the contrary herein contained, the Liability of the Seller under any circumstances whatsoever and without exception shall be limited to the Purchase Price of the particular item forming part of the goods. 102 www.pamensky.com Table of Contents Variable Frequency Drives CFW 08 Plus - Low Voltage VFD CFW 08 Wash - Low Voltage NEMA 4X VFD CFW 09 - Low Voltage VFD CFW 09 Shark - Low Voltage NEMA 4X VFD CFW 10 - Low Voltage VFD CFW 11 - Low Voltage VFD CFW 11M - - Low Voltage Modular VFD CFW 700 - Low Voltage VFD CFW 701 - Low Voltage HVAC VFD MVW 01 - Medium Voltage VFD MVW 01 - Compact Medium Voltage VFD 1.1 1.4 1.8 1.12 1.18 1.21 1.30 1.38 1.43 1.50 1.53 Soft Starters SSW 05 Plus - Low Voltage Soft Starter SSW 06 - Low Voltage Soft Starter SSW 07 - Low Voltage Soft Starter 2.1 2.5 2.13 Panels EDP - Enclosed Drive Panels GPH - Combination Soft Starter 3.1 3.4 Industrial Control Products PESW - Enclosed Motor Starters CWC - Miniature Contactors CWM - Standard Contactors RW - Thermal Overload Relays MPW - Manual Motor Protector Pushbuttons and Pilot Lights 4.1 4.8 4.13 4.25 4.30 4.37 Reference Variable Frequency Drive Sizing Guide Direct On-Line Starters Sizing Guide Soft Starters Sizing Guide 5.1 5.8 5.10 Version: CAN.AUT.09.2013 101 www.pamensky.com CFW 08 Plus - VFD - Features The WEG CFW-08 line of VFD‘s offers Single and Three Phase Input Power Supply options for motors up to 20HP. Outstanding features and options in a NEMA 1 enclosure allow the CFW08 Plus to be successfully used in a large variety of applications. Standard Features • • • • • • • • • • • • • • V/Hz or Sensorless Vector Control NEMA 1 Enclosure Single and Three-phase input voltage 200-240V, 380-480V or 500-600V input voltage, 50 - 60 Hz 150% current overload capacity 16 bit DSP controlled PWM output 2.5 / 5 / 10 / 15 kHz adjustable swiching frequency Four isolated programmable digital inputs Two programmable relay outputs Two isolated programmable analog inputs (with special function) One analog output Protective features: Over current, motor overload, drive over temperature, output phase-to-phase and phase-to-ground short circuit, DC bus over and under voltage and external fault Control features: Linear and “S” ramp acceleration and deceleration, local/remote control, DC braking, torque boost, motor slip compensation, electronic pot, preset speeds, adjustable V/Hz profile, maximum and minimum adjustable frequency limits, two skip frequencies, adjustable output current limit, JOG, ride-thru, flying start and PID regulator. Display readings: Motor speed, frequency, voltage, current, last fault, heatsink temperature and drive status • Ambient: 32ºF (0ºC) to 104ºF (40ºC), 3300ft (1000m) altitude, 90% humidity, non-condensing Optional Features • • • • • Dynamic Braking capabilities available Remote Keypad with Copy Function RS-232 or RS-485 Serial Interface Modbus Communication* DIN rail mounting through 2HP *Requires optional RS-232 or RS-485 Interface Applications • • • • • • • Pumps Fans Blowers Conveyors Rollout tables Agitators Mixers Variable Frequency Drives 1.1 www.pamensky.com 101 CFW-08 - Part Number Specification CFW08 0016 T 3848 P O -- SI DB A1 DN H1 S3 1 2 3 4 5 6 7 8 9 10 11 12 13 1. CFW-08 Variable Frequency Drive 2. Output Rated Current 3. Power Supply: S = single-phase T = three-phase B = single-phase or three-phase 4. Power Supply Voltage: 2024 = 200-240 V 3848 = 380-480 V 5060 = 500-600 V 5. Language: P = Portuguese E = English G = German S = Spanish 6. Product Version: S = Standard O = With options 7. Enclosure: blank = Standard (see technical specifications table) N1 = NEMA 1 N4 = NEMA 4X 8. HMI - Human Machine Interface: blank = standard SI = without HMI 9. Control Board: blank = standard (CFW-08 Standard) A1 = control 1 (CFW-08 PLUS) A2 = control 2 (CFW-08 Plus with bipolar analog inputs) A3 = CANopen (1) A4 = DeviceNet (1) A5 = Pumps 10. EMI Filter: blank = without filter FA = Internal Class A filter 11. Special Hardware: Blank = not provided Hx = X version special hardware 12. Special Software: Blank = not provided Sx = X version special software Example: CFW080040B2024EOA1 Note: (1) 1.2 220-240V 380-480V 500-600V 0016 = 1.6 A 0026 = 2.6 A 0040 = 4.0 A 0070 = 7.0 A 0073 = 7.3 A 0100 = 10 A 0160 = 16 A 0220 = 22 A 0280 = 28 A 0330 = 33 A 0010 = 1.0 A 0016 = 1.6 A 0026 = 2.6 A 0027 = 2.7 A 0040 = 4.0 A 0043 = 4.3 A 0065 = 6.5 A 0100 = 10 A 0130 = 13 A 0160 = 16 A 0240 = 24 A 0300 = 30 A 0017 = 1.7 A 0030 = 3.0 A 0043 = 4.3 A 0070 = 7.0 A 0100 = 10 A 0120 = 12 A * Selection Table for 2 Not avaliable for 500-600V Variable Frequency Drives 101 www.pamensky.com CFW 08 Plus - Table of Products 200-240V - Single Phase Electrical Data Mechanical Data Current (A) Braking Transistor Motor (HP) 1.6 2.6 4.0 7.3 10 N N N Y Y 0.25 0.5 1 2 3 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price 1 1 1 2 2 2.2 2.2 2.2 4.4 4.4 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 5.95 x 2.95 x 5.16 5.95 x 2.95 x 5.16 5.95 x 2.95 x 5.16 7.87 X 4.53 X 5.91 7.87 X 4.53 X 5.91 CFW080016S2024EON1A1 CFW080026S2024EON1A1 CFW080040S2024EON1A1 CFW080073B2024EON1A1 CFW080100B2024EON1A1 $460 465 491 788 866 Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 5.95 x 2.95 x 5.16 5.95 x 2.95 x 5.16 5.95 x 2.95 x 5.16 5.95 x 2.95 x 5.16 7.87 X 4.53 X 5.91 7.87 X 4.53 X 5.91 7.87 X 4.53 X 5.91 7.99 x 5.63 x 6.50 11.41 x 7.16 x 7.71 11.41 x 7.16 x 7.71 CFW080016B2024EON1A1 CFW080026B2024EON1A1 CFW080040B2024EON1A1 CFW080070T2024EON1A1 CFW080073B2024EON1A1 CFW080100B2024EON1A1 CFW080160T2024EON1A1 CFW080220T2024EON1A1 CFW080280T2024EON1A1 CFW080330T2024EON1A1 $535 543 568 669 788 866 1,044 1,643 2,114 2,711 200-240V - Three Phase Electrical Data Mechanical Data Purchasing Data Current (A) Braking Transistor Motor (HP) Frame Weight (lb) 1.6 2.6 4.0 7.0 7.3 10 16 22 28 33 N N N N Y Y Y Y Y Y 0.25 0.5 1 2 2 3 5 7.5 10 12.5 1 1 1 1 2 2 2 3 4 4 2.2 2.2 2.2 2.2 4.4 4.4 4.4 5.5 13.2 13.2 Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 5.95 x 2.95 x 5.16 5.95 x 2.95 x 5.16 5.95 x 2.95 x 5.16 7.87 X 4.53 X 5.91 5.95 x 2.95 x 5.16 7.87 X 4.53 X 5.91 7.87 X 4.53 X 5.91 7.87 X 4.53 X 5.91 7.99 x 5.63 x 6.50 7.99 x 5.63 x 6.50 11.41 x 7.16 x 7.71 11.41 x 7.16 x 7.71 CFW080010T3848EON1A1 CFW080016T3848EON1A1 CFW080026T3848EON1A1 CFW080027T3848EON1A1 CFW080040T3848EON1A1 CFW080043T3848EON1A1 CFW080065T3848EON1A1 CFW080100T3848EON1A1 CFW080130T3848EON1A1 CFW080160T3848EON1A1 CFW080240T3848EON1A1 CFW080300T3848EON1A1 $662 685 705 767 793 979 1,168 1,357 1,574 1,775 2,556 3,078 380-480V - Three Phase Electrical Data Mechanical Data Purchasing Data Current (A) Braking Transistor Motor (HP) Frame Weight (lb) 1.0 1.6 2.6 2.7 4 4.3 6.5 10 13 16 24 30 N N N Y N Y Y Y Y Y Y Y 0.33 0.75 1 1 2 2 3 5 7.5 10 15 20 1 1 1 2 1 2 2 2 3 3 4 4 2.2 2.2 2.2 4.4 2.2 4.4 4.4 4.4 5.5 5.5 13.2 13.2 Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 7.99 x 5.63 x 6.50 7.99 x 5.63 x 6.50 7.99 x 5.63 x 6.50 7.99 x 5.63 x 6.50 7.99 x 5.63 x 6.50 7.99 x 5.63 x 6.50 CFW080017T5060EON1A1 CFW080030T5060EON1A1 CFW080043T5060EON1A1 CFW080070T5060EON1A1 CFW080100T5060EON1A1 CFW080120T5060EON1A1 $1,057 1,111 1,256 1,406 1,625 1,824 500-600V - Three Phase Electrical Data Mechanical Data Current (A) Braking Transistor Motor (HP) Frame Weight (lb) 1.7 3 4.3 7 10 12 Y Y Y Y Y Y 1 2 3 5 7.5 10 3 3 3 3 3 3 5.5 5.5 5.5 5.5 5.5 5.5 Notes: Purchasing Data The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 1.3 www.pamensky.com 101 CFW 08 Wash - NEMA 4X (IP56) VFD The frequency inverter CFW-08 Wash is an inverter dedicated to applications that require a higher protection degree. The Nema 4X protection degree assures protection against dust, dirt and directed water jets. Standard Features - CFW 08 • • • • • • • • • • • • • • 1.4 • V/Hz or Sensorless Vector Control NEMA 4X Enclosure Single and Three-phase input voltage 200-240V, 380-480V or 500-600V input voltage, 50 - 60 Hz 150% current overload capacity 16 bit DSP controlled PWM output 2.5 / 5 / 10 / 15 kHz adjustable swiching frequency Four isolated programmable digital inputs Two programmable relay outputs Two isolated programmable analog inputs (with special function) One analog output Protective features: Over current, motor overload, drive over temperature, output phase-to-phase and phase-to-ground short circuit, DC bus over and under voltage and external fault Control features: Linear and “S” ramp acceleration and deceleration, local/remote control, DC braking, torque boost, motor slip compensation, electronic pot, preset speeds, adjustable V/Hz profile, maximum and minimum adjustable frequency limits, two skip frequencies, adjustable output current limit, JOG, ride-thru, flying start and PID regulator. Display readings: Motor speed, frequency, voltage, current, last fault, heatsink temperature and drive status Ambient: 32ºF (0ºC) to 104ºF (40ºC), 3300ft (1000m) altitude, 90% humidity, non-condensing Recommended Environments • • • NEMA 4X indoor environments NEMA 12 indoor environments IP56 environments Optional Features • Dynamic Braking capabilities available • RS-232 or RS-485 Serial Interface • Modbus Communication* *Requires optional RS-232 or RS-485 Interface Applications • • • • • • • Pumps Fans Blowers Conveyors Rollout tables Agitators Mixers Variable Frequency Drives 101 www.pamensky.com CFW 08 Wash - Table of Products 200-240V - Single Phase Electrical Data Mechanical Data Current (A) Braking Transistor Motor (HP) 7.3 10 Y Y 2 3 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price A A 11.2 11.2 NEMA 4X NEMA 4X 10.43 x 6.50 x 8.50 10.43 x 6.50 x 8.50 CFW080073B2024EON4A1 CFW080100B2024EON4A1 $1,326 1,456 Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X 10.43 x 6.50 x 8.50 10.43 x 6.50 x 8.50 10.43 x 6.50 x 8.50 13.40 x 8.47 x 8.50 13.40 x 8.47 x 8.50 13.40 x 8.47 x 8.50 CFW080073B2024EON4A1 CFW080100B2024EON4A1 CFW080160T2024EON4A1 CFW080220T2024EON4A1 CFW080280T2024EON4A1 CFW080330T2024EON4A1 $1,326 1,456 1,558 2,090 2,688 3,296 200-240V - Three Phase Electrical Data Mechanical Data Purchasing Data Current (A) Braking Transistor Motor (HP) Frame Weight (lb) 7.3 10 16 22 28 33 Y Y Y Y Y Y 2 3 5 7.5 10 12.5 A A A B B B 11.2 11.2 11.0 15.4 15.9 15.9 Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X 10.43 x 6.50 x 8.50 10.43 x 6.50 x 8.50 10.43 x 6.50 x 8.50 10.43 x 6.50 x 8.50 13.40 x 8.47 x 8.50 13.40 x 8.47 x 8.50 13.40 x 8.47 x 8.50 13.40 x 8.47 x 8.50 CFW080027T3848EON4A1 CFW080043T3848EON4A1 CFW080065T3848EON4A1 CFW080100T3848EON4A1 CFW080130T3848EON4A1 CFW080160T3848EON4A1 CFW080240T3848EON4A1 CFW080300T3848EON4A1 $1,120 1,428 1,680 1,800 2,088 2,354 3,248 4,250 380-480V - Three Phase Electrical Data Mechanical Data Purchasing Data Current (A) Braking Transistor Motor (HP) Frame Weight (lb) 2.7 4.3 6.5 10 13 16 24 30 Y Y Y Y Y Y Y Y 1 2 3 5 7.5 10 15 20 A A A A B B B B 10.1 11.5 11.7 11.7 15.9 15.9 17.2 17.4 Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X 13.40 x 8.47 x 8.50 13.40 x 8.47 x 8.50 13.40 x 8.47 x 8.50 13.40 x 8.47 x 8.50 13.40 x 8.47 x 8.50 13.40 x 8.47 x 8.50 CFW080017T5060EON4A1 CFW080030T5060EON4A1 CFW080043T5060EON4A1 CFW080070T5060EON4A1 CFW080100T5060EON4A1 CFW080120T5060EON4A1 $1,578 1,818 1,876 2,098 2,338 2,624 500-600V - Three Phase Electrical Data Mechanical Data Current (A) Braking Transistor Motor (HP) Frame Weight (lb) 1.7 3 4.3 7 10 12 Y Y Y Y Y Y 1 2 3 5 7.5 10 B B B B B B 13.9 15.4 15.6 15.6 15.6 15.6 Notes: Purchasing Data The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 1.5 www.pamensky.com 101 CFW 08 Plus - Accessories Keypads Description NEMA4 Remote Keypad (requires CFW08-MIS-RS & cable) Remote Keypad Interface Keypad Cover Part Number List Price HMI-CFW08-RS MIP-CFW08-RS TCL-CFW08 $148 70 14 Part Number List Price CAB-RS-1 CAB-RS-2 CAB-RS-3 CAB-RS-5 CAB-RS-7.5 CAB-RS-10 $23 31 42 52 62 73 Part Number List Price KCS-CFW08 KSD-CFW08 KRS-485-CFW08 $112 144 214 Keypad Cables Description 1m (3.3 ft.) Remote Keypad Cable 2m (6.6 ft.) Remote Keypad Cable 3m (10 ft.) Remote Keypad Cable 5m (15 ft.) Remote Keypad Cable 7.5m (25 ft.) Remote Keypad Cable 10m (33 ft.) Remote Keypad Cable Communication and Gland Kits Description RS-232 Serial Comm. Module (mounted in place of keypad) PC Communication Kit (SUPERDRIVE) Interface for RS-485 Communication 1.6 Variable Frequency Drives 101 www.pamensky.com CFW 08 Plus - Technical Data Single-Phase Voltage Power Supply Enclosure Three-Phase Performance Control Inputs Outputs Communication 380-480V: 380/400/415/440/460/480 V (+10% - 15%) 500-600V: 525/575/600 (+10 - 15%) Frequency 50 / 60 Hz +/- 2 Hz ( 48...62 Hz) Cos * (Displacement Power Factor) > 0.98 Drive Standard NEMA 1 in sizes 3 and 4and IP 20 in sizes 1 and 2 HMI Optional NEMA 12 Parallel, remote HMI (IP54) (HMI-CFW08-RS) NEMA 12 Serial, remote HMI (IP54) (HMI-CFW08-RS) Power Supply Type Switching power supply Control Method DSP (Digital Signal Processor), 16 bits, sinusoidal PWM (Space Vector Modulation) Control Type Control 200-240V: 200/220/230/240 V (+10% - 15%) 200-240V: 200/220/230/240 V (+10% - 15%) Imposed voltage - linear V/Hz or quadratic Sensorless vector control (WC: Voltage Vector Control) Switching Frequency IGBT Transistors - Frequencies: 2.5 / 5.0 / 10 / 15 kHz Frequency Range 0...300Hz Fequency Resolution Analog Ref.: 0.1% of Fmax. And digital ref.: 0.01 Hz (f<100Hz); 0.1 Hz (f>100 Hz) Accuracy (25º C = 10ºC) Analog Ref.: 0.5% and digital Ref.: 0.01% Overload capacity 150% during 60 sec. Every 10 min (1.5 x Rated Current.) Efficiency >95% at full load Speed control Regulation: 1% of the rated speed with slip compensation (in Sensorless Vector) Analog 2 isolated inputs 0..10, 0/4...20mA or - 10...+10V (Al1 e Al2)1 Digital Relay (2) 4 Programmable isolated inputs - with NPN or PNP logic (Dl1...Dl4) 2 Isolated PTC inputs via AL1 and AL2 2 Programmable outpluts, 1NO & 1NC Analog (1) 1 Isolated analog output 0...10V, 0/4...20mA ( 8 bits ) Serial Interface RS-232 or RS-485 (optional) “Field Bus” Networks Unit for ProfiBus DP Communication, DeviceNet (optional) and ModBus RTU (optional) DC link overvoltage / undervoltage Overtemperature Output overcurrent Safety Protections Motor overload ( i x t ) Hardware fault, external fault and serial communication error Output phase to phase and phase to ground short circuit Programming fault and self-tuning error On/Off , Parameter Setting ( Programming of special functions ) Commands Frequency Increment / Decrement ( Speed ) JOG, Reversal of Direction of Rotation and Local /Remote Selection Motor Output Frequency ( Hz ) DC Link Voltage ( V ) Human-Machine Interface (HMI) Value proportional to the frequency ( Ex.:RPM ) Monitoring (Reading) Heat Sink Temperature Motor Output Current ( A ) Motor Output Voltage ( V ) Error / Fault Messages Load Torque Environment Finishing Conformities Certifications Temperature 0 ... 40 °C (up to 50 °C with output current derating 2% / °C) Humidity 5 ... 90% non condensing Altitude 0 ... 1000 m (up tp 4000 m with output current derating 10% / 1000 m) Color Politherm 20 mt gray and Politherm 20 mt blue Electromagnetic Compatibility EMC Directive 89/336/EEC - Industrial Environment; EN 61800-3 (EMC - Emission and Immunity) - Special Request Low Voltage LVD 73/23/EEC - Low Voltage Directive / UL 508C IEC 146 Semiconductors convertors UL 508 C Power conversion equipment EN 50178 Electronic equipment for use in power installations EN 61010 Safety requirements for electrical equipment for measurement, control and laboratory use UL (USA) and cUL (CANADA) Underwriters Laboratories Inc. / USA CE (EUROPE) SGS / England IRAM (ARGENTINA) Instituto Argentino de Normalización C-Tick (AUSTRALIA) Australian Communications Authority Variable Frequency Drives 1.7 www.pamensky.com 101 CFW 09 - Variable Frequency Drive The CFW 09‘s Vectrue Technology combines V/F, Sensorless Vector and Closed Loop Vector (with encoder) control techniques in one product. Optimal Braking saves the need for the dynamic braking resistor in some applications allowing a more compact and economical solution. Standard Features Standard Features - cont. • • • • • • • • • • • • • • • • • 1.8 V/Hz or Sensorless Vector Control Self Tuning to motor parameters NEMA 1 Enclosure up to 200HP IP20 Enclosure from 250 to 500HP 200-240V, 380-480V or 500-600/690V input voltage Single or Three-phase input voltage up to 3HP/230V *Call 1 877 PAMENSKY for higher than 3HP 150% current overload capacity DC bus connections accessible Detachable Smart Keypad with dual display and Copy Function 32 bit RISC microprocessor controlled PWM output 1.25 / 2.5 / 5 / 10 kHz adjustable switching frequency Six isolated programmable digital inputs Three programmable relay outputs (250Vac / 1A) Two isolated programmable analog inputs Two programmable analog outputs (0 - 10 Vdc) Protective features: Over current, motor overload, drive over temperature, output phase-to-phase and phase-to-ground short circuit, DC bus over and under voltage, power supply under voltage and phase loss and external fault • • Control features: Linear and “S” ramp acceleration and deceleration, local/remote control, DC braking, torque boost, motor slip compensation, electronic pot, preset speeds, adjustable V/Hz profile, maximum and minimum adjustable motor speed limits, three skip frequencies, adjustable output current limit, JOG, ride-thru, flying start and PID regulator Display readings: Motor speed, frequency, voltage, current and torque, output power (kW), last ten faults, drive status, digital and analog I/O status, hours powered and hours running Ambient: 32ºF (0ºC) to 104ºF (40ºC), 3300 ft (1000m) altitude, 90% humidity, noncondensing Optional Features • • • • • • • • • Closed loop vector control Remote keypad with cable and mounting frame RS-232 or RS-485 Serial Interface On/Off line PC programming with SUPERDRIVE Fieldbus Comm: Profibus DP, DeviceNet or Modbus RTU, Ethernet TCP/IP Encoder buffered output Additional digital and analog I/O Dynamic Braking capabilities for most models PLC Cards Variable Frequency Drives 101 www.pamensky.com CFW-09 - Part Number Specification CFW09 0016 T 3848 P O -- SI DB A1 DN H1 S3 Z 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1. CFW-09 VSD 2. Output Rated Current for Constant Torque (CT) Sizing 3. Power Supply: T = Three-phase 4. Power Supply Voltage: 2223 = 220 ... 230 VAC 3848 = 380 ... 480 VAC 5060 = 500 ... 600 VAC 5069 = 500 ... 690 VAC 5. Language: P = Portuguese E = English 6. Product Version: S = Standard O = With options 7. Enclosure: blank = Standard (see technical specifications table) N4 = NEMA 4 / IP 56 (models up to 10HP) 8. HMI - Human Machine Interface: blank = standard (with HMI of LED´S + LCD) SI = Without HMI IL = Optional only with LED HM 9. Dynamic Braking: blank = Standard DB = With Built-in Dynamic Braking Transistor RB = Regenative rectifying unit (models from 105A at 220V, and from 86A at 380-480V) G = German S = Spanish 220-230V 380-480V 500-600V 500-690V 0006 = 6.0A 0007 = 7.0A 0010 = 10A 0013 = 13A 0016 = 16A 0024 = 24A 0028 = 28A 0045 = 45A 0054 = 54A 0070 = 70A 0086 = 86A 0105 = 105A 0130 = 130A 0142 = 142A 0180 = 180A 0240 = 240A 0003 = 3.6A 0004 = 4.0A 0005 = 5.5A 0009 = 9.0A 0013 = 13A 0016 = 16A 0024 = 24A 0030 = 30A 0038 = 38A 0045 = 45A 0060 = 60A 0070 = 70A 0086 = 86A 0105 = 105A 0142 = 142A 0180 = 180A 0211 = 211A 0240 = 240A 0312 = 312A 0361 = 361A 0450 = 450A 0515 = 515A 0600 = 600A 0002 = 2.9A 0004 = 4.2A 0007 = 7.0A 0010 = 10A 0012 = 12A 0014 = 14A 0022 = 22A 0027 = 27A 0032 = 32A 0044 = 44A 0053 = 53A 0063 = 63A 0079 = 79A 0107 = 107A 0147 = 147A 0211 = 211A 0247 = 247A 0315 = 315A 0418 = 418A 0472 = 472A 0107 = 107A 0147 = 147A 0211 = 211A 0247 = 247A 0315 = 315A 0343 = 343A 0418 = 418A 0472 = 472A * Selection Table for 2 10. Expansion Boards: blank = Standard A1 = EBA.01-CFW09 optional A2 = EBA.02-CFW09 optional A3 = EBA.03-CFW09 optional B1 = EBB.01-CFW09 optional B2 = EBB.02-CFW09 optional B3 = EBB.03-CFW09 optional B4 = EBB.04-CFW09 optional B5 = EBB.05-CFW09 optional C1 = EBC1.01-CFW09 optional C2 = EBC1.02-CFW09 optional C3 = EBC1.03-CFW09 optional E1 = Optional with EBE1.00 - CFW09 P1 = PLC1.01-CFW09 optional P2 = PLC2.00-CFW09 optional 11. FieldBus Communications cards: blank = Standard (not provided) PD = KFB-PD optional (Profibus DP) DN = KFB-DN optional (Device Net) DD = Optional with KFB – DD (Device Net Drive Profile / Special software) EN = EtherNet / IP standard 12. Special Hardware: blank = not provided H1...Hn = Special Hardware version-Optional HD = Models from 105A at 220V, and from 86A at 380-480V are power supplied via DC link HC/HV = The CFW09 VSDs mechanics from 2 to 8 have and inductor line for the DC link built into the product. To request the VSD with the inductor in place just add the code “HC” (for drives operating on Variable Torque). 13. Special Software: blank = Standard Spftware Version S1...Sn = Optional with version a special software SF = Protocol Metasys N2 End of Part Number: Z Example: CFW090013T2223ESZ 14. Variable Frequency Drives SC = Hoist functions SN = Winder I with power calculation SQ = Special version for Kit Device Net Drive Profile 1.9 www.pamensky.com 101 CFW 09 - Table of Products 220-230V Electrical Data Current (A) CT VT 6 7 10 13 16 24 28 45 54 68 70 86 86 105 105 130 130 150 142 174 180 240 Built-In Dynamic Braking Yes Yes Yes Yes Yes Yes Yes Yes Optional Optional Optional Optional Optional Optional External DB External DB Mechanical Data Maximum Applicable Motor Constant Torque Variable Torque HP KW HP KW 1.5 2 3 3 5 7.5 10 15 20 25 30 40 50 50 60 75 1.1 1.5 2.2 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 37 45 55 1.5 2 3 3 5 5.5 10 15 25 30 40 50 50 60 60 75 1.1 1.5 2.2 2.2 3.7 5.5 7.5 11 18.5 22 30 37 37 45 45 55 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price 1 1 1 1 2 2 2 3 4 5 5 6 6 7 8 8 8 8 8 8 13 13 13 42 50 90 90 121 121 154 221 221 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 8.27 x 5.63 x 7.72 8.27 x 5.63 x 7.72 8.27 x 5.63 x 7.72 8.27 x 5.63 x 7.72 11.42 x 7.16 x 7.72 11.42 x 7.16 x 7.72 11.42 x 7.16 x 7.72 15.35 x 8.78 x 10.79 18.70 x 9.84 x 10.79 21.65 x 13.19 x 10.79 21.65 x 13.19 x 10.79 26.57 x 13.19 x 11.77 26.57 x 13.19 x 11.77 32.87 x 13.19 x 12.20 38.38 x 16.14 x 14.57 38.38 x 16.14 x 14.57 CFW090006T2223ESZ CFW090007T2223ESZ CFW090010T2223ESZ CFW090013T2223ESZ CFW090016T2223ESZ CFW090024T2223ESZ CFW090028T2223ESZ CFW090045T2223ESZ CFW090054T2223ESZ CFW090070T2223ESZ CFW090086T2223ESZ CFW090105T2223ESZ CFW090130T2223ESZ CFW090142T2223ESZ CFW090180T2223ESZ CFW090240T2223ESZ $1,468 1,486 1,563 1,605 1,731 2,274 2,517 3,837 5,339 7,716 8,124 9,788 10,488 12,178 16,863 24,057 220-230V - With Optional Dynamic Braking Electrical Data Current (A) CT 54 70 86 105 130 142 VT 68 86 105 130 150 174 Built-In Dynamic Braking Yes Yes Yes Yes Yes Yes Mechanical Data Maximum Applicable Motor Constant Torque HP 20 25 30 40 50 50 KW 15 18.5 22 30 37 37 Purchasing Data Variable Torque HP 25 30 40 50 50 60 KW 18.5 22 30 37 37 45 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price 4 5 5 6 6 7 50 90 90 121 121 154 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 18.70 x 9.84 x 10.79 21.65 x 13.19 x 10.79 21.65 x 13.19 x 10.79 26.57 x 13.19 x 11.77 26.57 x 13.19 x 11.77 32.87 x 13.19 x 12.20 CFW090054T2223EODBZ CFW090070T2223EODBZ CFW090086T2223EODBZ CFW090105T2223EODBZ CFW090130T2223EODBZ CFW090142T2223EODBZ $6,377 9,109 9,589 11,447 12,266 15,132 380-480V Electrical Data Current (A) CT VT 3.6 4 5.5 9 13 16 24 30 36 38 45 45 54 60 70 70 86 86 105 105 130 142 174 180 211 240 312 361 450 515 600 Notes: 1.10 Built-In Dynamic Braking Yes Yes Yes Yes Yes Yes Yes Yes Optional Optional Optional Optional Optional Optional Optional External DB External DB External DB External DB External DB External DB External DB External DB Mechanical Data Maximum Applicable Motor Constant Torque HP 2 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 150 150 200 250 300 350 400 500 KW 1.5 1.5 2 4 6 8 11 15 18.5 22 30 37 45 55 75 110 110 150 185 220 260 300 370 Variable Torque HP 2 2 3 5 7.5 10 15 25 30 40 50 60 75 100 125 150 150 200 250 300 350 400 500 KW 1.5 1.5 2.2 4 5.5 7.5 11 18.5 22 30 37 45 55 75 90 110 110 150 185 220 260 300 370 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price 1 1 1 1 2 2 2 3 4 4 5 5 6 6 7 8 8 8 9 9 10 10 10 8 8 8 8 13 13 13 42 50 50 90 90 121 121 154 221 221 221 476 476 571 571 571 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 IP20 IP20 IP20 IP20 IP20 8.27 x 5.63 x 7.72 8.27 x 5.63 x 7.72 8.27 x 5.63 x 7.72 8.27 x 5.63 x 7.72 11.42 x 7.16 x 7.72 11.42 x 7.16 x 7.72 11.42 x 7.16 x 7.72 15.35 x 8.78 x 10.79 18.70 x 9.84 x 10.79 18.70 x 9.84 x 10.79 21.65 x 13.19 x 10.79 21.65 x 13.19 x 10.79 26.57 x 13.19 x 11.77 26.57 x 13.19 x 11.77 32.87 x 13.19 x 12.20 38.38 x 16.14 x 14.57 38.38 x 16.14 x 14.57 38.38 x 16.14 x 14.57 39.37 x 27.56 x 19.33 39.37 x 27.56 x 19.33 46.65 x 27.56 x 19.33 46.65 x 27.56 x 19.33 46.65 x 27.56 x 19.33 CFW090003T3848ESZ CFW090004T3848ESZ CFW090005T3848ESZ CFW090009T3848ESZ CFW090013T3848ESZ CFW090016T3848ESZ CFW090024T3848ESZ CFW090030T3848ESZ CFW090038T3848ESZ CFW090045T3848ESZ CFW090060T3848ESZ CFW090070T3848ESZ CFW090086T3848ESZ CFW090105T3848ESZ CFW090142T3848ESZ CFW090180T3848ESZ CFW090211T3848ESZ CFW090240T3848ESZ CFW090312T3848ESZ CFW090361T3848ESZ CFW090450T3848ESZ CFW090515T3848ESZ CFW090600T3848ESZ $1,646 1,685 1,744 1,884 1,980 2,464 2,654 3,780 4,502 5,628 6,976 7,430 9,110 9,956 11,862 18,778 21,410 22,280 26,396 27,584 35,964 41,636 47,492 The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 101 www.pamensky.com CFW 09 - Table of Products 380-480V - With Optional Dynamic Braking Electrical Data Current (A) CT 38 45 60 70 86 105 142 VT 45 54 70 86 105 130 174 Built-In Dynamic Braking Yes Yes Yes Yes Yes Yes Yes Mechanical Data Maximum Applicable Motor Constant Torque HP 25 30 40 50 60 75 100 KW 19 22 30 37 45 55 75 Variable Torque HP 30 40 50 60 75 100 125 KW 22 30 37 45 55 55 90 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price 4 4 5 5 6 6 7 50 50 90 90 121 121 154 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 18.70 x 9.84 x 10.79 18.70 x 9.84 x 10.79 21.65 x 13.19 x 10.79 21.65 x 13.19 x 10.79 26.57 x 13.19 x 11.77 26.57 x 13.19 x 11.77 32.87 x 13.19 x 12.20 CFW090038T3848EODBZ CFW090045T3848EODBZ CFW090060T3848EODBZ CFW090070T3848EODBZ CFW090086T3848EODBZ CFW090105T3848EODBZ CFW090142T3848EODBZ $5,790 7,884 9,984 10,832 13,457 15,678 18,515 500-600V Electrical Data Current (A) CT 2.9 4.2 7 10 12 14 22 27 32 44 53 63 79 VT 4.2 7 10 12 14 14 27 32 32 53 63 79 99 Built-In Dynamic Braking Yes Yes Yes Yes Yes Yes Optional Optional Optional Optional Optional Optional Optional Mechanical Data Maximum Applicable Motor Constant Torque HP 2 3 5 7.5 10 15 20 25 30 40 50 60 75 KW 1.5 2.2 3.7 5.5 7.5 9.2 15 18.5 22 30 37 45 55 Variable Torque HP 3 5 7.5 10 15 15 25 30 30 50 60 75 100 KW 2.2 4 5.5 7.5 9.2 9.2 18.5 22 22 37 45 55 75 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price 2 2 2 2 2 2 4 4 4 7 7 7 7 13 13 13 13 13 13 50 50 50 154 154 154 154 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 11.4 x 7.2 x 7.7 11.4 x 7.2 x 7.7 11.4 x 7.2 x 7.7 11.4 x 7.2 x 7.7 11.4 x 7.2 x 7.7 11.4 x 7.2 x 7.7 18.7 x 9.8 x 10.8 18.7 x 9.8 x 10.8 18.7 x 9.8 x 10.8 32.9 x 13.2 x 11.8 32.9 x 13.2 x 11.8 32.9 x 13.2 x 11.8 32.9 x 13.2 x 11.8 CFW090002T5060ESZ CFW090004T5060ESZ CFW090007T5060ESZ CFW090010T5060ESZ CFW090012T5060ESZ CFW090014T5060ESZ CFW090022T5060ESZ CFW090027T5060ESZ CFW090032T5060ESZ CFW090044T5060ESZ CFW090053T5060ESZ CFW090063T5060ESZ CFW090079T5060ESZ $1,742 1,801 2,305 2,413 2,935 3,271 4,194 4,928 6,708 8,941 10,550 12,558 14,928 500-600V - With Optional Dynamic Braking Electrical Data Current (A) CT 22 27 32 44 53 63 79 VT 27 32 32 53 63 79 99 Built-In Dynamic Braking Yes Yes Yes Yes Yes Yes Yes Mechanical Data Maximum Applicable Motor Constant Torque HP 20 25 30 40 50 60 75 KW 15 18.5 22 30 37 45 55 Purchasing Data Variable Torque HP 25 30 30 50 60 75 100 KW 18.5 22 22 37 45 55 75 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price 4 4 4 7 7 7 7 50 50 50 154 154 154 154 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 18.7 x 9.8 x 10.8 18.7 x 9.8 x 10.8 18.7 x 9.8 x 10.8 32.9 x 13.2 x 11.8 32.9 x 13.2 x 11.8 32.9 x 13.2 x 11.8 32.9 x 13.2 x 11.8 CFW090022T5060EODBZ CFW090027T5060EODBZ CFW090032T5060EODBZ CFW090044T5060EODBZ CFW090053T5060EODBZ CFW090063T5060EODBZ CFW090079T5060EODBZ $5,526 6,516 8,833 11,490 13,454 16,120 18,968 500-690V Electrical Data Current (A) CT 107 147 211 247 315 343 418 472 Notes: VT 147 196 211 315 343 418 472 555 Built-In Dynamic Braking External DB External DB External DB External DB External DB External DB External DB External DB Mechanical Data Maximum Applicable Motor Constant Torque HP 100 150 200 250 300 350 400 500 KW 75 110 150 185 220 250 300 370 Variable Torque HP 150 200 200 300 350 400 500 600 KW 110 150 150 220 250 300 370 450(370) Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD 8E 8E 8E 10E 10E 10E 10E 10E 253 253 253 682 682 682 682 682 NEMA 1 NEMA 1 NEMA 1 IP20 IP20 IP20 IP20 IP20 45.1 x 16.1 x 14.6 45.1 x 16.1 x 14.6 45.1 x 16.1 x 14.6 46.6 x 27.5 x 22.9 46.6 x 27.5 x 22.9 46.6 x 27.5 x 22.9 46.6 x 27.5 x 22.9 46.6 x 27.5 x 22.9 WEG Part Number List Price CFW090107T5069ESZ CFW090147T5069ESZ CFW090211T5069ESZ CFW090247T5069ESZ CFW090315T5069ESZ CFW090343T5069ESZ CFW090418T5069ESZ CFW090472T5069ESZ 18,119 27,295 36,995 39,018 42,264 56,796 61,225 65,161 The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 1.11 www.pamensky.com 101 CFW 09 Shark - Variable Frequency Drive CFW 09 Drives with a NEMA 4X (IP 56) enclosure, designed for highly aggressive environments including: • Chemical industry • Petrochemical • Food industry • Other applications requiring full protection Standard Features Standard Features - cont. • • • • • • • • • • • • • • • • V/Hz or Sensorless Vector Control Self Tuning to motor parameters NEMA 4X (IP56) Stainless Steel Enclosure 200-240V up to 5HP, 380-480V up to 10HP Single or Three-phase input voltage up to 3HP/230V 150% current overload capacity DC bus connections accessible Detachable Smart Keypad with dual display and Copy Function 32 bit RISC microprocessor controlled PWM output 1.25 / 2.5 / 5 / 10 kHz adjustable switching frequency Six isolated programmable digital inputs Three programmable relay outputs (250Vac/1A) Two isolated programmable analog inputs Two programmable analog outputs (0 - 10 Vdc) Protective features: Over current, motor overload, drive over temperature, output phase-to-phase and phase-to-ground short circuit, DC bus over and under voltage, power supply under voltage and phase loss and external fault • • Optional Features • • • • • • • 1.12 Control features: Linear and “S” amp acceleration and deceleration, local/remote control, DC braking, torque boost, motor slip compensation, electronic pot, preset speeds, adjustable V/Hz profile, maximum and minimum adjustable motor speed limits, three skip frequencies, adjustable output current limit, JOG, ride-thru, flying start and PID regulator Display readings: Motor speed, frequency, voltage, current and torque, output power (kW), last four faults, drive status, digital and analog I/O status, hours powered and hours running Ambient: 32ºF (0ºC) to 104ºF (40ºC), 3300 ft (1000m) altitude, 90% humidity, noncondensing Closed loop vector control RS-485 Serial Interface On/Off line PC programming with SUPERDRIVE Fieldbus Comm: Profibus DP, DeviceNet or Modbus RTU (Requires optional RS-232 or RS-485 Interface), Ethernet TCP/IP Encoder buffered output Additional digital and analog I/O Dynamic Braking capabilities for all models Variable Frequency Drives 101 www.pamensky.com CFW 09 Shark - Table of Products 220-230V Electrical Data Current (A) CT VT 6 7 10 16 Built-In Dynamic Braking Yes Yes Yes Yes Mechanical Data Maximum Applicable Motor Constant Torque Variable Torque HP KW HP KW 1.5 2 3 5 1.1 1.5 2.2 3.7 1.5 2 3 5 1.1 1.5 2.2 3.7 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price 1 1 1 2 10 10 10 15 NEMA 4X NEMA 4X NEMA 4X NEMA 4X 14.2 x 9.2 x 8.5 14.2 x 9.2 x 8.5 14.2 x 9.2 x 8.5 16.2 x 10.2 x 8.5 CFW090006T2223EON4Z CFW090007T2223EON4Z CFW090010T2223EON4Z CFW090016T2223EON4Z $2,660 2,782 2,906 3,276 380-480V Electrical Data Current (A) CT VT 3.6 4 5.5 9 13 16 Notes: Built-In Dynamic Braking Yes Yes Yes Yes Yes Yes Mechanical Data Maximum Applicable Motor Constant Torque Variable Torque HP KW HP KW 2 2 3 5 7.5 10 1.5 1.5 2.2 3.7 5.5 7.5 2 2 3 5 7.5 10 1.5 1.5 2.2 3.7 5.5 7.5 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD WEG Part Number List Price 1 1 1 2 2 2 10 10 10 15 15 15 NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X 14.2 x 9.2 x 8.5 14.2 x 9.2 x 8.5 14.2 x 9.2 x 8.5 16.2 x 10.2 x 8.5 16.2 x 10.2 x 8.5 16.2 x 10.2 x 8.5 CFW090003T3848EON4Z CFW090004T3848EON4Z CFW090005T3848EON4Z CFW090009T3848EON4Z CFW090013T3848EON4Z CFW090016T3848EON4Z $2,782 2,854 2,980 3,114 3,300 3,980 The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 1.13 www.pamensky.com 101 CFW 09 - Accessories Dynamic Braking Description External Dynamic Braking Module for 180A Model (16 X 9 X 10 NEMA 1 Enclosure) External Dynamic Braking Module for 211 & 240A Models (16 X 9 X 10 NEMA 1 Enclosure) External Dynamic Braking Module for 312, 361,450,515, & 600A Models (16 X 9 X 10 NEMA 1 Enclosure) External Dynamic Braking Module for 107,147,211,& 247A Models at 575V (16 X 9 X 10 NEMA 1 Enclosure) External Dynamic Braking Module for 315 & 343A Models at 575V (16 X 9 X 10 NEMA 1 Enclosure) External Dynamic Braking Module for 418 & 472 Amp Models at 575V (16 X 9 X 10 NEMA 1 Enclosure) Part Number List Price DBW01.0165D21801SZ DBW01.0240D21801SZ DBW01.0300D21801SZ DBW02.0210D50691SZ DBW02.0300D50691SZ DBW02.0380D50691SZ $2,120 2,590 3,159 3,893 5,133 6,363 Part Number List Price HMI-CFW09LCD HMI-CFW09LCD N4 KMR CFW09 TCL CFW09 $207 268 91 29 Part Number List Price CFW09HMI091 CFW09HMI092 CFW09HMI093 CFW09HMI095 CFW09HMI097 CFW09HMI0910 $31 39 50 75 88 108 Part Number List Price KSD CFW09 KCS CFW09 KFB-PD KFB DN KFB EN $161 86 1,045 897 1,562 Part Number List Price CFW09CAP1500 CFW09CAP4700 $240 280 Keypads Description Standard Keypad with LED & LCD NEMA 4/IP56 Remote Keypad with LED & LCD Remote Keypad FRAME KIT Blank Keypad with Power & Error LED’s Keypad Cables Description 1m (3.3 ft) Remote Keypad Cable 2m (6.6 ft) Remote Keypad Cable 3m (10 ft) Remote Keypad Cable 5m (16 ft) Remote Keypad Cable 7.5m (25 ft) Remote Keypad Cable (Requires CFW09KMR09) 10m (33 ft) Remote Keypad Cable (Requires CFW09KMR09) Communication Description SUPERDRIVE PC Communication Kit (includes software & hardware accessories) RS-232 Serial Interface Profibus DP Communication Kit DeviceNet Communication Kit Ethernet IP Communication Kit (V3.70 or higher) * Modbus RTU –requires optional RS-232 or RS-485 interface. Caps Description External DC Bus Cap Kit 1500uF (includes bleeder resistor, mounting bracket, & screws) External DC Bus Cap Kit 4700uF (includes bleeder resistor, mounting bracket, & screws) 1.14 Variable Frequency Drives 101 www.pamensky.com CFW 09 - Accessories I/O Expansion Boards Description I/O Exp. Board A with Encoder Input, Encoder Output, RS-485 Serial Interface, I4 bit A/D, I4 bit D/A’s, Digital Inputs and Outputs + Thermistor (PTC) Input I/O Exp. Board A with RS-485 Serial Interface, Digital Inputs and Outputs + Thermistor (PTC) Input I/O Exp. Board A with I4 bit A/D, I4 bit D/A’s, Digital Inputs and Outputs + Thermistor (PTC) Input I/O Exp. Board B with Encoder Input, Encoder Output, RS-485 Serial Interface, Isolated Analog Input, Isolated Analog Outputs, Digital Inputs and Outputs + Thermistor (PTC) Input I/O Exp. Board B with Encoder Input with internal Power Supply - 12VDC, Digital Inputs and Outputs + Thermistor (PTC) Input I/O Exp. Board B with Isolated Analog Input, Isolated Analog Outputs, Digital Inputs and Outputs + Thermistor (PTC) Input I/O Exp. Board B with Encoder Input, 5V Power Supply for Encoder, Buffered Outputs for Encoder Signals, RS485 Serial Port, 24V Digital Input, 2 X 24V DC Digital Outputs, 0…10V/4-20mA Analog Input, 2 X 4-20mA Analog Outputs and PTC Thermistor Input I/O Exp. Board B with 2 X 4-20mA Analog Outputs I/O Exp. Board C with Encoder Input, 5-15VDC External Power Supply I/O Exp. Board C with Encoder Input with internal Power Supply - 12VDC I/O Exp. Board E with RS-485 Serial Interface, Digital or Thermistor (PTC) Input PLC/Motion Control Board PLC/Motion Control Board with Communication Capabilities Part Number List Price EBA.01 CFW09 $1,414 EBA.02 CFW09 EBA.03 CFW09 334 654 EBB.01-CFW09 1,192 EBB.02-CFW09 561 EBB.03-CFW09 667 EBB.04-CFW09 1,487 EBB.05-CFW09 EBC1.01 CFW09 EBC1.02 CFW09 EBC1.03 CFW09 EBE.01 CFW09 PLC1.01 PLC2.00 435 194 504 523 192 957 1,148 Part Number List Price CFW09KMFM3 CFW09KMFM4 CFW09KMFM5 CFW09KMFM6 CFW09KMFM7 CFW09KMFM8 $16 20 22 22 22 28 Through Surface Mounting Description Kit for Through Surface Mounting - Size 3 Kit for Through Surface Mounting - Size 4 Kit for Through Surface Mounting - Size 5 Kit for Through Surface Mounting - Size 6 Kit for Through Surface Mounting - Size 7 Kit for Through Surface Mounting - Size 8 Variable Frequency Drives 1.15 www.pamensky.com 101 CFW 09 - Technical Data Three-phase: Frequency Phase Unbalance Cos (Displacement Power Factor) 50 / 60 Hz +/- 2 Hz (48 ... 62 Hz) Up to 3% Greater Ihan 0.98 at full load NEMA 1/IP20 (sizes 1...8 and 8E), IP20 (sizes 9,10 and 10E) NEMA 4X / IP56 (modules up to 10HP) Plastic Cover - Light Gray PANTONE 413 C (sizes 1 and 2) Metallic Cover and Sides - Light Gray RAL 7032 (sizes 3 to 10) Base - Dark Gray RAL 7022 (sizes 3 to 10) Switched Mode Power Supply Fed from the DC Link 32 bit RISC Technology SVM Sine wave PWM (Space Vector Modulation) Software Implemented Current flux and Speed Regulators (Full DigitaI) V/F Sensorless Vector (without encoder) Vector with Encoder 1.25 / 2.5 / 5.0 / 10 kHz 0...1020 Hz for V / Hz Control 0...408 Hz for Vector Control 150% for 60 seconds every 10 minutes 180% for 1 second every 10 minutes Greater than 97% at full load Regulation (with Slip Compensation) : 1% 01 Motor Rated Speed V / F Mode Resolution: 1 rpm (Keypad Reference) Speed Regulation Range: 1: 20 Regulation: 0.5% of Motor Rated Speed Sensorless Resolution: 1 rpm (Keypad Reference) Vector Mode Speed Regulation Range: 1:100 Regulation with: 10 bit Analogy Reference: +1- 0.1% 01 Motor Rated Speed Encoder Vector 14 bit Analogy Reference: +- 0.01% 01 Motor Rated Speed Mode Digital Reference (Ex: Keypad): + / - 0.01 % of Motor Rated Speed Speed Regulation Range: Down to 0 rpm Regulation: + - 10% of Motor Rated Torque Vector Modes Range: O ... 150% 01 Motor Rated Torque 2 Programmable Differential Input (10 bit) : 0...10 V 0...20 mA or 4...20 mA 1 Programmable Bipolar Input (14 bit): -10 ... + 10 V 0...20 mA or 4...20 mA 1 Programmable Isolated Input (10 bit) : O ... 10 V 0...20 mA or 4...20 mA 6 Programmable Isolated Input: 24 Vdc 1 Programmable Isolated Input: 24 Vdc 1 Programmable Isolated Input: 24 Vdc (for Motor PTC Thermistor) 1 Isolated Differencial Encoder Signals Output: 5 ...15 Vdc External Power Supply RS-232 with KCS-GFW09 Kn - RS-485 Isolated with EBA or EBB Board Johnson Contols-N2 (optional) Modbus RTU Standard, Profibus DP, DeviceNet, EtherNet / IP, DeviceNet Drive Profile with KFB kits. DC Link Under Voltage Output Short Circuit DC Link Over Voltage Output Ground Fault Drive Over Temperature External Fault Motor Over Temperature SeIf -diagnosis Fault Output Over Current Programming Error Motor Overload (i x t) Serial Communication Fault Dynamic Braking Resistor Overload Motor or Encoder Connection Fault CPU / EPROM Error ( watchdog) Power Supply Ohase Fault (30 A and above models) Encoder Fault Keypad Connection Fault 0ºC (32ºF)...40ºC (104ºF), up to 50ºC (122ºF) with 2% / ºC (1,1% / ºF) output current derating 5...90% Non Condensing 0...1000m (3300ft), up to 4000m (13100ft) with 10% / 1000m (3% / 1000ft) output current derating Electromagnetie Compatible - Industrial Environment - EMC - Emission and Immunity Low Voltage Directive Semiconductor drive Power Conversion Enuinment Electronic Equipment for Use in Power Installations Safety Requirements for Electrical Equipament for Measurement Control and laboratory Use Underwriters laboratories Ine. USA Phoenix Test-Lab GmbH – Germany (Competent Body) Instituto Argentino de Normalización Australian Communications Aulhority Power Supply Degree of Protection Enclosure Finishing Color Power Supply Microprocessor PWM Technique Control Modes Control Switching Frequency Frequency Range Overload Capacity Efficiency Speed Control Performance Torque Control Analog Control Inputs Digital Encorder Communication Serial Fieldbus Safety Ambient Conformities Certifications 1.16 220-230 V: 220/230 V (+10% -15%) 380-480 V: 380/400/415/440/460/480 V (+10% - 15%) 500-600 V: 525/575/600 V (+10% - 15%) 500-690 V: 525/575/600 (+10% - 15%) /690 V Voltage Protections Temperature Humidity Altitude EMC Directive 89 / 336 / EEC - EM 61800-3 LVD 73 / 23 / EEC IEC 146 UL 508C EN 50178 EN 61010 UL (USA) and cUL (CANADA) CE (EUROPE) IRAM (ARGENTINA) C-Tiek (AUSTRALIA) 2250/1132383 Variable Frequency Drives 101 www.pamensky.com CFW 09 - Technical Data Programming Controls Keypad Monitoring Control Features Standard General Drive Functions Programming Start/Stop , Increase/Decrease Speed, JOG, FWD/REV and Local/Remote Speed Reference (rpm) Oulput Current (A) Motor Speed (rpm) Oulput Voltage (Vac) Speed Proportional Value (Ex: ft/min) Drive Status Output Frequency (Hz) Digital Inputs Status DC Link Voftage (Vdc) Transistor Outputs Status Motor Torque (%) Relay Outputs Status Outout Power (kW) Analog Inputs Value Hours Powered Up (h) Four Last Faults Hours Enabled (h) Fault Messages Keypad wilh LCD + LED displays (HMI-CFW09-LCD) Password to protect drive programming LCD display language selection: English, Spanish and Portuguese Control mode selection (via parameter}: V / F. Sensorless Vector or Vector with Encoder Fault auto-diagnosis and auto-reset Parameters reset to factory or user default Drive Self-tuning to motor and load (Vector Modes) Specific unit indication ( Ex: l/s, t/h, %, etc. ) Motor slip compensation (V / F Mode) Manual and automatic Torque Boost (V / F Mode) Adjustable V / F Curve (V / F Mode) Minimum and maximum speed limits Output current limit Adjustable motor overload protection Digital gain and offset adjustments for the analog inputs Digital gain adjustment for the analog outputs JOG function JOG + I JOG - Function (momentary speed increase/decrease) COPY Function (Drive to Keypad or Keypad to Drive) Comparison functions for lhe digital outputs: N* > Nx; N > Nx; N < Nx; N = O; N = N*; Is > Ix ; Is < Ix; T > Tx and T < Tx Where: N = Motor speed; N* = Speed reference; Is = Output Current and T = Motor torque Linear and S independent acceleration and deceleration ramps, two sets of ramps DC Braking Optimal Braking (Vector Modes) Built-in dynamic braking transistor – Models up to 45A/220-230V and up to 30A/380-480V and up to 14A/500-600V Multi-speed function (up to 8 preset speeds) Speed Profiling function Hour meter and Wattrneter Overlapping PID Regulator (for automatic control of level, pressure, flow, etc. ) FWD I REV selection Local I Remate operation selection Flying Start function (restart with the motor spinning) Skip Speed (critical speed rejection) Ride-Through (operation during momentary power loss) Built-in dynamic braking transistor: Models: 6 ... 45 A / 220 - 230 V and 36 ... 30 A / 380 - 480 V FieldBus communication: Modbus RTU built-in Variable Frequency Drives 1.17 www.pamensky.com 101 CFW 10 - Variable Frequency Drive The WEG CFW 10 VFD provides a robust drive solution in a compact, easily mounted package. A simplified keypad and bright LED readout, complete diagnostics and fully programmable I/O makes the CFW 10 an ideal control device when requiring an economical drive solution for small motors. Standard Features Applications • • • • • • • • • • • • • • • • • • • V/Hz control IP20 finger safe enclosure Single Phase 110-127V input voltage up to 1 HP Single Phase 200–240V input voltage up to 3 HP 150% current overload capacity DSP controlled PWM output 2.5-15 kHz adjustable switching frequency Four isolated programmable digital inputs Programmable relay output One isolated programmable analog input Diagnostic features: Over current, motor overload, drive over temperature, output short circuit, DC bus over and under voltage and external fault Control features: Linear and S-Ramp acceleration and deceleration, local / remote control, DC braking, torque boost, motor slip compensation, electronic pot, preset speeds, minimum and maximum adjustable frequency limits, adjustable output current limit, JOG Display readings: Motor speed, frequency, voltage, current, last 3 faults, heatsink temperature and drive status, DC link voltage Ambient: 122°F (50°C), 3300 ft (1000 m) altitude, 90% humidity, non-condensing 1.18 Pumps Fans/Blowers Blowers Conveyors Rollout tables Variable Frequency Drives 101 www.pamensky.com CFW-10 - Part Number Specification CFW10 0040 S 2024 E O -- -- -- -- Z 1 2 3 4 5 6 7 8 9 10 11 1. CFW-10 Variable Frequency Drive 2. Output Rated Current 3. Power Supply: S = single-phase 4. Power Supply Voltage: 1112 = 110-127 V (Single-phase only) 2024 = 200-240 V 5. Language: P = Portuguese E = English S = Spanish 110-127V 200-240V 0016 = 1.6 A 0026 = 2.6 A 0040 = 4.0 A 0016 = 1.6A 0026 = 2.6A 0040 = 4.0A 0073 = 7.3A 0100 = 10.0A * Selection Table for 2 6. Product Version: S = Standard O = With options 7. Control Card: blank = Standard CL = clean PL = plus (with potentiometer) 8. EMC Built-in Filter: blank = (not avaliable) FA = with EMC filter (class A) – Only for single-phase models (200-240V) models 9. Special Hardware: Blank = not provided Hx = special hardware in version X CP = Cold Plate heatsink version 10. Special Software: Blank = not provided Sx = special software in version X 11. End of Part Number: Z Example: CFW100040S2024ESZ Variable Frequency Drives 1.19 www.pamensky.com 101 CFW 10 - Table of Products 110-127V - Single Phase Electrical Data Current (A) Motor (HP) 1.6 2.6 4.0 0.25 0.5 1 Mechanical Data Frame Weight (lb) 1 1 2 2.0 2.0 3.3 200-240V - Single Phase Electrical Data Degree of Protection WEG Part Number List Price IP20 IP20 IP20 5.20 x 3.74 x 4.76 5.20 x 3.74 x 4.76 6.34 x 4.53 x 4.80 CFW100016S1112ESZ CFW100026S1112ESZ CFW100040S1112ESZ $401 432 656 Mechanical Data Current (A) Motor (HP) Frame Weight (lb) 1.6 2.6 4 7.3 10 0.25 0.5 1 2 3 1 1 1 2 3 2.0 2.0 2.0 3.3 4.0 Notes: Purchasing Data Dimensions H x W xD (in) Purchasing Data Degree of Protection Dimensions (in) WEG Part Number List Price IP20 IP20 IP20 IP20 IP20 5.20 x 3.74 x 4.76 5.20 x 3.74 x 4.76 5.20 x 3.74 x 4.76 6.34 x 4.53 x 4.80 7.46 x 4.53 x 4.80 CFW100016S2024ESZ CFW100026S2024ESZ CFW100040S2024ESZ CFW100073S2024ESZ CFW100100S2024ESZ $349 375 385 571 680 The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify the VFD through the motor rated current. CFW 10 - Technical Data Single phase Single phase 50 / 60Hz +/- 2Hz Greater than 0.98 IP20 Linear or Quadratic V/Hz 16 bit DSP Voltage Power Supply Enclosure Control Control Inputs Control Ouput Safety Ambient Frequency Cos (Displacement Power Factor) Degree of Protection Control Mode Power Output Sinusoidal PWM (Space Vector Modulation) Switching Frequency IGBT Transistors 2.5, 5, 10 or 15kHz Frequency Range 2.5…15kHz Switching Frequency Overload Capacity 0-300 Hz 4 programmable isolated digital 150% during 60 sec. every 10 min. outputs 1 programmable differential analog input: 0-10V, 0-20mA or 4-20mA 1 programmable realy outputs, one reversing (Form C) contact: 250V / 0.5A Motor over current DC link over voltage Motor overload DC link under voltage output phase-to-phase short circuit Drive over temperature Protections output phase-to-ground short circuit external fault programming error Temperature 0…104F (40ºC), up to 122ºF (50ºC) with 2% / 1.8ºF (1ºC) output current derating Humidity 5…90% Non Condensing 0…3300 ft (1000m), up to 13,200 ft (4000m) with 10% / 3300ft (1000m) output Altitude current derating EMC Directive 89 / 336 / EEC Conformities Special Functions Keypad Mounting 1.20 110…127V (+10%, -15%) 200…240V (+10%, -15%) Electromagnetic compatibility – Industrial Environment EMC – Emission and Immunity ENC61800-3 LVD 73/23/EEC Low Voltage Directive UL 508 C Power Conversion Equipment Linear and “S” ramp accel and decel, local/remote control, FWD/REV selection, DC braking, manual and auto torque boost, motor slip compensation, electronic pot, two skip frequencies, maximum and minimum adjustable frequency limits, adjustable output current limit, 8 present speeds and JOG. 3 digit display, 2 indication LEDs and 4 keys Readouts for: output freqency (Hz), output current (A), output voltage (V), value proportional to frequency (Ex: RPM), heatsink temperature, fault and status messages. Surface with screws Variable Frequency Drives 101 www.pamensky.com CFW 11 - System Variable Frequency ency Driv Drive The WEG CFW 11 inverters use Plug and Play technology to recognize and configure accessories providing easy and safe operation. Programming is simpler using the standard USB port. Soft PLC lets the user create functions without the need for an external PLC. Standard Features Standard Features - cont. • • • • • • • • • • • Plug and play philosophy (connect and use) enables quick and easy installation of accessories and options USB for computer connection for using SUPERDRIVE G2 programming and monitoring software Human-Machine Interface (HMI) with backlit graphic display and soft-keys, greatly facilitates inverter programming and operation DC link inductors (symetrically connected to positive and negative DC link terminals) enable compliance with IEC61000-3-12 standard requirements regarding harmonics, (no need for external line reactance) Intelligent thermal management enables full protection of IGBTs, monitoring of heatsink and internal air temperature Automatic control of the heatsink fan with speed sensor (additional protection) and easily detachable from the unit for cleaning and maintenance Normal Duty and Heavy Duty ratings to adapt optimally to all kinds of loads Protection with failure and alarm warnings Motor overload protection in compliance with IEC 60947-4-2/UL 508 C On board memory allows user to create functions without the need to use an external PLC (soft-PLC via IEC61131-3 programming software) • • Guided start-up simplifies initial user programming. Real time clock TRACE / SCOPE function to assist with the start-up and system diagnostics via SUPERDRIVE G2 Optional Features • • • • • • • • • • • • • Interface for incremental encoder 5 to 12Vdc Interface for RS-485 serial communication (modbus) Interface for RS-232C serial communication CAN interface Profibus DP interface PLC functions; IEC programming Devicenet 4 interface Ethernet IP interface Blind cover for slot HMI Frame for remote HMI Conduit kit Optimal Braking® IP20 Factory Options • • • Safety Stop RFI Filter 24 VDC power input option for control section Variable Frequency Drives 1.21 www.pamensky.com 101 CFW-11 - Part Number Specification CFW11 - 0016 T 4 S -- -- -- -- -- -- -- -- Z 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1. CFW-11 Variable Frequency Drive 2. Type of Construction: Blank = Inverter in cabinet M = Inverter with modular construction to meet elevated powers, “modular drive” line 3. Output Rated Current 4. Power Supply: S = single-phase T = three-phase B = single-phase or three-phase 5. Power Supply Voltage: 2 = 200-240 V 4 = 380-480 V 5 = 500-600 V 6 = 660-690 V 6. Product Version: S = Standard O = With options 7. Enclosure: Blank = factory standard Sizes A, B and C: IP21 D: Nema 1/IP20 N1 = Nema 1 21 = IP21 220-240V * Selection Table for 2 8. HMI - Human Machine Interface: blank = standard (with HMI of LED´S + LCD) IC = Without HMI 9. Braking: blank = standard (Sizes A, B, C and D: built-in braking IGBT) F = Standard product including Brake Chopper DB = Dynamic Braking (Factory Option) 10. RFI Filter (Not Applicable to CFW-11M Models): Blank = standard FA = Category C3 internal RFI filter 11. Safety Stop: Blank = standard (without safety stop function) Y = with safety stop function according to EN-954-1 category 3 12. External Electronic 4 Vdc Supply 24 icable to (not applicable models CFW-11M): Blank = factory standard: model CFW-11 (without) ; model CFW-11M (with) 12. Special Hardware: Blank = factory standard (without) H1 = special hardware nr. 1 13. Special Software: Blank = factory standard (without) S1 = special software nr. 1 14. art Number: End of Part Z Example:: CFW110016T4SZ 1.22 380-480V 0007 = 7 A 0003 = 3 A 0005 = 5 A 0010 = 10 A 0013 = 13 A 0007 = 7 A 0016 = 16 A 0010 = 10 A 0013 = 13 A 0024 = 24 A 0028 = 28 A 0017 = 17 A 0033 = 33 A 0024 = 24 A 0045 = 45 A 0031 = 31 A 0054 = 54 A 0038 = 38 A 0070 = 70 A 0045 = 45 A 0086 = 86 A 0058 = 58 A 0105 = 105 A 0070 = 70 A 0142 =142 A 0088 = 88 A 0180 = 180 A 0105 = 105 A 0211 = 211 A 0142 = 142 A Variable Frequency Drives 0180 = 180 A 0211 = 211 A 0242 = 242 A 0312 = 312 A 0370 = 370 A 0477 = 477 A 0515 = 515 A 0601 = 601 A 0720 = 720 A 500-690V 0002 = 2.9 A 0150 = 150 A 0004 = 4.2 A 0170 = 170 A 0007 = 7 A 0216 = 216 A 0010 = 10 A 0289 = 289 A 0012 = 12 A 0315 = 315 A 0017 = 17 A 0365 = 365 A 0022 = 22 A 0435 = 435 A 0027 = 27 A 0032 = 32 A 0044 = 44 A 0053 = 53 A 0063 = 63 A 0080 = 80 A 0107 = 107 A 0125 = 125 A 101 www.pamensky.com CFW 11 - Table of Products 200-240V - Single Phase Electrical Data Current (A) ND* HD* 6 7 10 5 7 10 Built-In Dynamic Braking Yes Yes Yes Mechanical Data Maximum Applicable Motor ND* HD* HP HP 1.5 2 3 1 2 3 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price A A A 12.6 12.6 13.4 NEMA 1 NEMA 1 NEMA 1 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 CFW110006B2ON1Z CFW110007B2ON1Z CFW110010S2ON1Z $1,936 1,996 2,117 200-240V - Three Phase Electrical Data Current (A) ND* HD* 6 7 7 10 13 16 24 28 33.5 45 54 70 86 105 142 180 211 5 7 5.5 8 11 13 20 24 28 36 45 56 70 86 115 142 180 Built-In Dynamic Braking Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No Mechanical Data Maximum Applicable Motor ND* HD* HP HP 1.5 2 2 3 4 5 7.5 10 12.5 15 20 25 30 40 50 60 75 1 2 1.5 2 3 4 6 7.5 10 12.5 15 20 25 30 40 50 60 ND* HD* 3.6 5 7 10 13.5 17 24 31 38 45 58.5 70.5 88 105 142 180 211 242 312 370 477 515 601 720 3.6 5 5.5 10 11 13.5 19 25 33 38 47 61 73 88 115 142 180 211 242 312 370 477 515 560 Built-In Dynamic Braking Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price A A A A A A B B B C C C D D E E E 12.6 12.6 12.6 12.6 13.4 13.9 20.1 20.1 20.1 41.7 41.7 41.7 71.7 71.7 143.3 143.3 143.3 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 13.82 x 7.45 x 8.94 13.82 x 7.45 x 8.94 13.82 x 7.45 x 8.94 17.64 x 8.66 x 11.51 17.64 x 8.66 x 11.51 17.64 x 8.66 x 11.51 19.82 x 11.81 x 12.00 19.82 x 11.81 x 12.00 26.60 x 13.20 x 14.10 26.60 x 13.20 x 14.10 26.60 x 13.20 x 14.10 CFW110006B2ON1Z CFW110007B2ON1Z CFW110007T2ON1Z CFW110010T2ON1Z CFW110013T2ON1Z CFW110016T2ON1Z CFW110024T2ON1Z CFW110028T2ON1Z CFW110033T2ON1Z CFW110045T2ON1Z CFW110054T2ON1Z CFW110070T2ON1Z CFW110086T2SZ CFW110105T2SZ CFW110142T2ON1Z CFW110180T2ON1Z CFW110211T2ON1Z $1,936 1,996 1,851 1,967 2,047 2,203 2,740 2,794 3,182 3,583 4,410 5,139 6,514 8,369 12,249 17,051 21,840 Notes: Mechanical Data Maximum Applicable Motor ND* HD* HP HP 2 3 4 6 7.5 10 15 20 25 30 40 50 60 75 100 150 150 200 250 300 400 450 500 600 2 3 3 6 6 7.5 12.5 15 20 25 30 40 50 60 75 100 150 150 200 250 300 400 450 450 * ND - Normal Duty • 110% during 60 seconds every 10 minutes • 150% during 3 seconds every 10 minutes Purchasing Data Frame 380-480V - Three Phase Electrical Data Current (A) Purchasing Data Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price A A A A A B B B C C C D D E E E E F F F F G G G 5.7 5.9 5.9 6.1 6.3 9.1 9.7 10.4 18.9 18.9 18.9 32.5 32.5 143.3 143.3 143.3 143.3 308.6 308.6 308.6 308.6 474.0 474.0 474.0 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 IP20 IP20 IP20 IP20 IP20 IP20 IP20 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 12.04 x 5.71 x 8.94 13.82 x 7.45 x 8.94 13.82 x 7.45 x 8.94 13.82 x 7.45 x 8.94 17.64 x 8.66 x 11.51 17.64 x 8.66 x 11.51 17.64 x 8.66 x 11.51 19.82 x 11.81 x 12.00 19.82 x 11.81 x 12.00 26.60 x 13.20 x 14.10 26.60 x 13.20 x 14.10 26.60 x 13.20 x 14.10 26.60 x 13.20 x 14.10 48.58 x 16.93 x 14.17 48.58 x 16.93 x 14.17 48.58 x 16.93 x 14.17 48.58 x 16.93 x 14.17 49.76 x 21.06 x 16.77 49.76 x 21.06 x 16.77 49.76 x 21.06 x 16.77 CFW110003T4ON1Z CFW110005T4ON1Z CFW110007T4ON1Z CFW110010T4ON1Z CFW110013T4ON1Z CFW110017T4ON1Z CFW110024T4ON1Z CFW110031T4ON1Z CFW110038T4ON1Z CFW110045T4ON1Z CFW110058T4ON1Z CFW110070T4SZ CFW110088T4SZ CFW110105T4ON1Z CFW110142T4ON1Z CFW110180T4ON1Z CFW110211T4ON1Z CFW110242T4SZ CFW110312T4SZ CFW110370T4SZ CFW110477T4SZ CFW110515T4SZ CFW110601T4SZ CFW110720T4SZ $1,903 2,024 2,091 2,161 2,265 2,745 3,324 4,120 4,542 5,725 7,093 7,723 9,302 10,388 12,218 17,914 20,837 21,719 25,735 26,893 33,217 38,456 43,866 48,740 * HD - Heavy Duty • 150% during 60 seconds every 10 minutes • 200% during 3 seconds every 10 minutes The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 1.23 www.pamensky.com 101 CFW 11 - Table of Products 500-600V - Three Phase Electrical Data Current (A) ND* HD* 2.9 4.2 7.0 10 12 17 2.7 3.8 6.5 9.0 10 17 Built-In Dynamic Braking Standard Standard Standard Standard Standard Standard Mechanical Data Maximum Applicable Motor ND* HD* HP HP 2 3 5 7.5 10 15 2 3 5 7.5 10 15 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price B B B B B B 20.1 20.1 20.1 20.1 20.1 20.1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 12.4 x 7.5 x 8.9 12.4 x 7.5 x 8.9 12.4 x 7.5 x 8.9 12.4 x 7.5 x 8.9 12.4 x 7.5 x 8.9 12.4 x 7.5 x 8.9 CFW110002T5ON1NFZ CFW110004T5ON1NFZ CFW110007T5ON1NFZ CFW110010T5ON1NFZ CFW110012T5ON1NFZ CFW110017T5ON1NFZ $2,818 2,895 3,074 3,128 3,283 3,412 500-690V - Three Phase Electrical Data Current (A) ND* HD* 22 27 32 44 53 63 80 107 125 150 170 216 289 315 365 435 19 22 27 36 44 53 66 90 107 122 150 180 240 289 315 357 Built-In Dynamic Braking Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Standard Standard Standard Standard Standard Standard Notes: 1.24 Mechanical Data Maximum Applicable Motor ND* HD* HP HP 20 25 30 40 50 60 75 100 125 150 150 200 300 300 350 450 15 20 25 30 40 50 60 75 100 125 150 200 250 300 300 350 * ND - Normal Duty • 110% during 60 seconds every 10 minutes • 150% during 3 seconds every 10 minutes Purchasing Data Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price D D D D E E E E E E F F F G G G 75 75 75 75 141 141 141 141 141 141 370 370 370 569 569 569 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 IP20 IP20 IP20 IP20 IP20 IP20 21.7 x 11.8 x 12.0 21.7 x 11.8 x 12.0 21.7 x 11.8 x 12.0 21.7 x 11.8 x 12.0 26.6 x 13.2 x 14.1 26.6 x 13.2 x 14.1 26.6 x 13.2 x 14.1 26.6 x 13.2 x 14.1 26.6 x 13.2 x 14.1 26.6 x 13.2 x 14.1 48.6 x 16.9 x 14.2 48.6 x 16.9 x 14.2 48.6 x 16.9 x 14.2 49.8 x 21.1 x 16.8 49.8 x 21.1 x 16.8 49.8 x 21.1 x 16.8 CFW110022T6ONBZ CFW110027T6ONBZ CFW110032T6ONBZ CFW110044T6ONBZ CFW110053T6ON1NBYZ CFW110063T6ON1NBYZ CFW110080T6ON1NBYZ CFW110107T6ON1NBYZ CFW110125T6ON1NBYZ CFW110150T6ON1NBYZ CFW110170T6ONBYZ CFW110216T6ONBYZ CFW110289T6ONBYZ CFW110315T6ONBYZ CFW110365T6ONBYZ CFW110435T6ONBYZ $5,072 5,410 6,672 7,894 10,572 10,823 11,872 14,863 18,128 24,863 25,820 31,612 38,746 43,846 57,147 61,689 * HD - Heavy Duty • 150% during 60 seconds every 10 minutes • 200% during 3 seconds every 10 minutes The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 101 www.pamensky.com CFW 11 - Table of Products - Dynamic Braking 200-240V - Three Phase - with Dynamic Braking Electrical Data Current (A) ND* HD* 142 180 211 115 142 180 Built-In Dynamic Braking Yes Yes Yes Mechanical Data Maximum Applicable Motor ND* HD* HP HP 50 60 75 40 50 60 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price E E E 143.3 143.3 143.3 NEMA 1 NEMA 1 NEMA 1 26.60 x 13.20 x 14.10 26.60 x 13.20 x 14.10 26.60 x 13.20 x 14.10 CFW110142T2ON1DBZ CFW110180T2ON1DBZ CFW110211T2ON1DBZ $13,102 18,232 23,357 380-480V - Three Phase - with Dynamic Braking Electrical Data Current (A) ND* HD* 105 142 180 211 88 115 142 180 Built-In Dynamic Braking Yes Yes Yes Yes Mechanical Data Maximum Applicable Motor ND* HD* HP HP 75 100 150 150 60 75 100 150 ND* HD* 22 27 32 44 53 63 80 107 125 150 19 22 27 36 44 53 66 90 107 122 Built-In Dynamic Braking Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price E E E E 143.3 143.3 143.3 143.3 NEMA 1 NEMA 1 NEMA 1 NEMA 1 26.60 x 13.20 x 14.10 26.60 x 13.20 x 14.10 26.60 x 13.20 x 14.10 26.60 x 13.20 x 14.10 CFW110105T4ON1DBZ CFW110142T4ON1DBZ CFW110180T4ON1DBZ CFW110211T4ON1DBZ $11,109 13,068 19,155 22,282 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes HD* HP HP 20 25 30 40 50 60 75 100 125 150 15 20 25 30 40 50 60 75 100 125 * ND - Normal Duty • 110% during 60 seconds every 10 minutes • 150% during 3 seconds every 10 minutes Notes: Mechanical Data Maximum Applicable Motor ND* Purchasing Data Frame 500-690V - Three Phase - with RFI Filter, Safety Stop and Dynamic Braking Electrical Data Current (A) Purchasing Data Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price D D D D E E E E E E 75 75 75 75 141 141 141 141 141 141 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 21.7 x 11.8 x 12.0 21.7 x 11.8 x 12.0 21.7 x 11.8 x 12.0 21.7 x 11.8 x 12.0 26.6 x 13.2 x 14.1 26.6 x 13.2 x 14.1 26.6 x 13.2 x 14.1 26.6 x 13.2 x 14.1 26.6 x 13.2 x 14.1 26.6 x 13.2 x 14.1 CFW110022T6OYZ CFW110027T6OYZ CFW110032T6OYZ CFW110044T6OYZ CFW110053T6OYZ CFW110063T6OYZ CFW110080T6OYZ CFW110107T6OYZ CFW110125T6OYZ CFW110150T6OYZ $6,248 6,667 8,220 9,727 12,943 13,250 14,545 18,229 22,250 25,541 * HD - Heavy Duty • 150% during 60 seconds every 10 minutes • 200% during 3 seconds every 10 minutes The maximum motor p power ratings g listed above are based on WEG 2 and 4 p pole motors. For motors with different numbers of p poles ((ie. 6 and 8 p poles), ), other voltages g and/ or from m other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 1.25 www.pamensky.com 101 CFW 11 - Accessories I/O Expansion Description Slot Part Number List Price 1 IOA-01 $1,052 1 IOB-01 561 8 Digital Inputs 4 Digital Outputs (Use with Soft PLC) 1 IOC-01 419 8 Digital Inputs 8 Open Collector Digital Outputs (Use with Soft PLC) 1 IOC-02 386 5 PTC type temperature sensor Input 5 PT100 type temperature sensor Input 5 KTY84 type temperature sensor Input 1 1 1 IOE-01 IOE-02 IOE-03 626 1,631 809 Slot Part Number List Price Incremental encoder module 5 to 12 Vdc 100 kHz With encoder signal repeater 2 ENC-01 $461 Incremental encoder module 5 to 12 Vdc 100 kHz 2 ENC-02 404 Slot Part Number List Price 3 3 3 3 3 3 4 4 4 4 4 4 4 RS485-01 RS232-01 RS232-02 CAN/RS485-01 CAN-01 PROFIBUS DP-01 PROFDP-05 DEVICENET-05 ETHERNET/IP-05 RS232-05 RS485-05 MODBUSTCP-05 PROFINETIO-05 $212 161 179 453 378 512 1,138 1,138 1,138 277 333 1,680 1,939 Slot Part Number List Price 2 14-bit analog inputs in voltage or current 2 digital inputs 2 14-bit analog outputs in voltage or current 2 open collector type digital outputs 2 isolated 12-bit analog inputs 2 digital inputs 2 isolated 11-bit analog outputs in voltage or current 2 open collector type digital outputs Interface with Encoder Description Communication Description RS-485 Serial Communication Module (Modbus-RTU) RS-232C Serial Communication Module (Modbus-RTU) RS-232C Serial Communication Module (Modbus-RTU) with DIP switch for flash memory prog. CAN/RS-485 Interface Module (CANopen, DeviceNet and Modbus) CAN Interface Module (CANopen and DeviceNet) Profibus DP-V1 Interface Module Profibus DP Interface Module DeviceNet Interface Module EtherNet/IP Interface Module RS-232 Interface Module (passive) (Modbus-RTU) RS-485 Interface Module (passive) (Modbus-RTU) Modbus - TCP/IP interface module Profinet interface module PLC Module Description PLC functions; Ladder programming; electronic ggearbox; 9 digital inputs; 3 dry-contact digital outputs; 3 open-collector digital ouputs; 1 analog input (14 bits); 2 analog outputs (14 bits); 2 encoder interfaces; RS-485 Modbus-RTU interface; CAN interface (CANopen, CANopen master/ slave). 1,2,3 PLC11-01 $1,960 PLC functions; Ladder programming; electronic ggearbox; 4 digital inputs; 1 dry-contact digital outputs; 3 open-collector digital ouputs; 2 encoder interfaces; RS-485 Modbus-RTU interface; CAN interface (CANopen, CANopen master/slave). 1,2,3 PLC11-02 1,215 1.26 Variable Frequency Drives 101 www.pamensky.com CFW 11 - Accessories Keypad Accessories and Cable for HMI Description CFW 11 Keypad Frame for keypad remote assembly, IP56 Blank cover for keypad slot 1m (3.3ft) Remote Keypad Cable 2m (6.6ft) Remote Keypad Cable 3m (10ft) Remote Keypad Cable 5m (16ft) Remote Keypad Cable 7.5m (25ft) Remote Keypad Cable 10m (33ft) Remote Keypad Cable Part Number List Price HMI-01 RHMIF-01 HMID-01 IHM CAB-RS-1M IHM CAB-RS-2M IHM CAB-RS-3M IHM CAB-RS-5M IHM CAB-RS-7.5M IHM CAB-RS-10M $318 60 47 47 52 57 65 78 88 Part Number List Price PCSA-01 PCSB-01 PCSC-01 $42 44 47 Part Number List Price DBW03 $5,904 Part Number List Price KN1A-01 KN1B-01 KN1C-01 $73 86 99 Shielding Kits and Exctractable Mounting Kits Description Power cable shielding kit for frame A Power cable shielding kit for frame B Power cable shielding kit for frame C Dynamic Braking Description External Dynamic Braking Module NEMA 1 Kits Description NEMA 1 - conduit kit kit for frame A NEMA 1 - conduit kit kit for frame B NEMA 1 - conduit kit kit for frame C Variable Frequency Drives 1.27 www.pamensky.com 101 CFW 11 - Technical Data Single-Phase 200-240 V: 200/220/230/240 V (+10%/-15%) 200-240 V: 200/220/230/240 V (+10%/-15%) Voltage and power range Three-Phase Frequency 50 / 60 Hz +-2% (48 to 63 Hz) Power Supply and Power Range 380-480 V: 380/400/415/440/460/480 V (+10%/-15%) 500-690 V: 525/575/600/690 V (+10%/-15%) Displacement factor Greater than 0.98 Efficiency Greater than 0.97 Voltage Three Phase, 0 up to power supply voltage Frequency 0 to 400 Hz Switching Frequency Standard: 5kHz Options available: 2.5 / 5 / 10 kHz Normal Duty Cycle Motor Overload Heavy Duty Cycle Time (ramps) Acceleration Deceleration 150% for 1 min every 10min 200% for 3 sec every 10min 0 to 999 seconds 0 to 999 seconds Speed variation range: 1:20 Regulation: 1% of rated speed Voltage Vector (VVW) Performance 150% for 3 sec every 10min Regulation: 1% of rated speed Scalar (V/f) Sensorless Vector 110% for 1 min every 10min Speed variation range: 1:30 Speed Control Regulation: 0.5% of rated speed Speed variation range: 1:100 Regulation: +/- 0.01% of rated speed with 14-bit analog input (IOA) Vector with Encoder (with accessory ENC-01 or ENC02) Regulation: +/- 0.01% of rated speed with digital reference (keyboard, serial fieldbus, electronic potentiometer, multispeed) Regulation: +/- 0.05% of rated speed with 12-bit analog input Range: 10 to 180% Torque Control Sensorless Vector Regulation: +/- 5% of rated torque Range: 20 to 180% Regulation: +/-10% of rated torque (above 3 Hz) Digital 6 isolated inputs, 24 Vdc, programmable functions 2 differential inputs isolated by differential amplifier, programmable functions Inputs Inputs and Outputs (I/Os) in the Standard Product Analog Resolution: - AI1: 12 bits - AI2: 11 bits + signal Signals: (0 to 10) V, (0 to 20) mA or (4 to 20) mA Impedance: - 400 kΩ for signal (0 to 10) V - 500 Ω for signal (0 to 20) mA or (4 to 20) mA Relay 3 relays with NA/NF (NO/NC) contacts, 240 Vac / 1A, programmable functions 2 isolated outputs, programmable functions Outputs Environment Degree of Protection Braking Methods 1.28 Resolution: 11 bits Analog Load: 0 to 10 V: RL >= 10 kΩ 0 to 20 mA or 4 to 20 mA: RL < 500Ω Available supply to user 24 Vdc + -20%, 500 mA -10 to 50°C for frame Size A,B,C and D; -10 to 45°C for frame Size E and F; -10 to 40°C for frame Size G with 720A Temperature of Operation Up to 60°C with current derating (2% for each 1°C above 50°C) Humidity 5 to 90% without condensation Altitude 0 to 1000 meters Up to 4000 meters with current reduction (1% for every 100 meters above 1000 meters) IP21 Standard for frame sizes A, B, C. For frame size D the top cover kit has to be added. Frame Sizes E, F and G option not available IP20 Standard for frame sizes D, E, F and G. Frame Sizes A, B and C the top cover has to be removed. NEMA1 Standard for frame Size D. Optinal for frame sizes A, B, C, E, F and G IP54 Frame Sizes 1, 2 and 3 Supply available to user Rheostatic Braking External braking resistor (not provided) Optimal Braking Does not need braking resistor DC Braking Direct current applied to the motor Variable Frequency Drives 101 www.pamensky.com CFW 11 - Technical Data Profibus DP DeviceNet PROFIBUS DP-01 (slot 3) PROFDP-05 (slot 4) CAN/RS485-01 (slot 3) CAN-01 (slot 3) DEVICENET-05 (slot4) CANopen CANopen Master/Slave Communication EtherNet TCP/IP CAN/RS485-01 (slot 3) CAN-01 (slot 3) PLC11-01 (slot 1/2/3) ETHERNET/IP-05 (slot 4) RS485-01 RS485 - ModBus RTU CAN/RS485-01 RS485-05 RS232 - ModBus RTU RS232-01 RS232-05 Built-into the standard product USB Protections Safety Standards Communication with SUPERDRIVE G2 Software Communication with WLP Software used for programming and monitoring the Soft PLC function and the PLC11-01 accessory Overcurrent / short circuit Under / overvoltage in the power circuit Phase loss Overtemperature in the inverter (IGBTs, rectifier and internal air in the electronic cards) Overtemperature in the motor Overload in the braking resistor Overload in the IGBTs Overload in the motor Fault / external alarm Fault in the CPU or memory Phase-to-ground short circuit at the output Fault in the heatsink fan Overspeed of motor Incorrect connection of encoder UL 508C Power conversion equipment UL 840 Insulation coordination including clearances and creepage distances for electrical equipment EN 61800-5-1 Safety requirements electrical, thermal and energy EN 50178 Electronic equipment for use in power installations EN 60204-1 Safety of machinery. Electrical equipment of machines. Part 1: General requirements. Note: In order to have a machine in conformity with this norm, the machine manufacturer is responsible for the installation of an emergency shutdown device and an equipment for network sectioning EN 60146 (IEC 146) Semiconductor converters EN 61800-2 Adjustable speed electrical power drive systems Part 2: General requirements – rating specifications for low voltage adjustable frequency a.c. power drive systems EN 60529 - Degrees of protection provided by enclosures (IP Code) Mechanical Construction Stds. UL 50 - Enclosures for electrical equipment Electromagnetic Compatibility Standards EN 61800-3 - Adjustable speed electrical power drive systems Part 3: EMC product standard including specific test methods EN 55011 - Limits and methods of measurement of radio disturbance characteristics of industrial, scientific and medical (ISM) radio-frequency equipment CISPR 11 - Industrial, scientific and medical (ISM)radio-frequency equipment Electromagnetic disturbance characteristics. Limits and methods of measurement EN 61000-4-2 - Electromagnetic Compatibility Standards (EMC) Part 4: Testing and measurement techniques Section 2: Electrostatic discharge immunity test EN 61000-4-3 - Electromagnetic Compatibility Standards (EMC) Part 4: Testing and measurement techniques Section 3:Radiated, radiofrequency, electromagnetic field immunity test EN 61000-4-4 - Electromagnetic Compatibility Standards (EMC) Part 4: Testing and measurement techniques Section 4: Electrical fast transient / burst immunity test EN 61000-4-5 - Electromagnetic Compatibility Standards (EMC) Part 4: Testing and measurement techniques Section 5: Surge immunity test EN 61000-4-6 - Electromagnetic Compatibility Standards (EMC) Part 4: Testing and measurement techniques Section 6: Immunity to conducted disturbances, induced by radio-frequency fields Variable Frequency Drives 1.29 www.pamensky.com 101 CFW 11M - Modular Variable Frequency Drive The CFW 11M is the new generation of WEG frequency inverters for large power ranges. It ranges from 350 to 2500HP rated at 380-480V / 500-600V / 660-690V with the option for 6 or 12 pulses. Standard Features Optional Features • • • • • • • • • • • • • • Plug and play philosophy (connect and use) enables quick and easy installation of accessories and options USB for computer connection for using SUPERDRIVE G2 programming and monitoring software Human-Machine Interface (HMI) with backlit graphic display and soft-keys, greatly facilitates inverter programming and operation Intelligent thermal management enables full protection of IGBTs, monitoring of heatsink and internal air temperature Automatic control of the heatsink fan with speed sensor (additional protection) and easily detachable from the unit for cleaning and maintenance Normal Duty and Heavy Duty ratings to adapt optimally to all kinds of loads Protection with failure and alarm warnings Motor overload protection in compliance with IEC 60947-4-2/UL 508 C On board memory allows user to create functions without the need to use an external PLC (soft-PLC via IEC61131-3 programming software) Guided start-up simplifies initial user programming Real time clock TRACE / SCOPE function to assist with the start-up and system diagnostics with SUPERDRIVE G2 1.30 • • • • • • • • • Interface for incremental encoder 5 to 12Vdc Interface for RS-485 serial communication (modbus) Interface for RS-232C serial communication CAN interface Profibus DP interface PLC functions; IEC programming Devicenet 4 interface Ethernet IP interface Blind cover for slot HMI Frame for remote HMI Conduit kit Variable Frequency Drives 101 www.pamensky.com CFW 11M - Specification Table 380-480V - Three Phase Electrical Data Current (A) Mechanical Data Maximum Applicable Motor Normal Duty (ND) Heavy Duty (HD) ND* HD* HP KW HP KW 600 1140 1710 2280 2850 515 979 1468 1957 2446 500 900 1400 1800 2300 370 700 1050 1400 1750 450 800 1200 1600 2000 330 590 900 1200 1500 Degree of Protection IP41 IP41 IP41 IP41 IP41 500-600V - Three Phase Electrical Data Current (A) Heavy Duty (HD) ND* HD* HP KW HP KW 470 893 1339 1786 2232 418 794 1191 1588 1985 500 900 1400 1800 2300 370 700 1050 1400 1750 400 800 1250 1600 2000 300 590 900 1200 1500 Degree of Protection IP41 IP41 IP41 IP41 IP41 660-690V - Three Phase *CE certification only Electrical Data Current (A) Dimensions (in) HxWxD Dimensions (in) HxWxD Part Number 90.55 x 55.12 x 31.50 90.55 x 55.12 x 31.50 90.55 x 70.87 x 31.50 90.55 x 78.74 x 31.50 90.55 x 102.36 x 31.50 90.55 x 86.61 x 31.50 90.55 x 86.61 x 31.50 90.55 x 102.36 x 31.50 90.55 x 110.24 x 31.50 90.55 x 125.98 x 31.50 AFW11M0600T4Z AFW11M1140T4Z AFW11M1710T4Z AFW11M2280T4Z AFW11M2850T4Z Purchasing Data 6 Pulse 12 Pulse Dimensions (in) HxWxD Dimensions (in) HxWxD Part Number 90.55 x 55.12 x 31.50 90.55 x 55.12 x 31.50 90.55 x 70.87 x 31.50 90.55 x 78.74 x 31.50 90.55 x 102.36 x 31.50 90.55 x 86.61 x 31.50 90.55 x 86.61 x 31.50 90.55 x 102.36 x 31.50 90.55 x 110.24 x 31.50 90.55 x 125.98 x 31.50 AFW11M0470T5Z AFW11M0893T5Z AFW11M1340T5Z AFW11M1786T5Z AFW11M2232T5Z Mechanical Data Maximum Applicable Motor Normal Duty (ND) 12 Pulse Mechanical Data Maximum Applicable Motor Normal Duty (ND) Purchasing Data 6 Pulse Heavy Duty (HD) ND* HD* HP KW HP KW 427 811 1216 1622 2028 340 646 969 1292 1615 500 1000 1500 2000 2500 370 750 1100 1500 1850 400 800 1250 1600 2000 300 590 900 1200 1500 Degree of Protection IP41 IP41 IP41 IP41 IP41 Purchasing Data 6 Pulse 12 Pulse Dimensions (in) HxWxD Dimensions (in) HxWxD Part Number 90.55 x 55.12 x 31.50 90.55 x 55.12 x 31.50 90.55 x 62.99 x 31.50 90.55 x 78.74 x 31.50 90.55 x 94.49 x 31.50 90.55 x 55.12 x 31.50 90.55 x 62.99 x 31.50 90.55 x 102.36 x 31.50 90.55 x 110.24 x 31.50 90.55 x 125.98 x 31.50 AFW11M0427T6Z AFW11M0811T6Z AFW11M1217T6Z AFW11M1622T6Z AFW11M2028T6Z Variable Frequency Drives 1.31 www.pamensky.com 101 CFW 11M - Accessories I/O Expansion Description Slot Part Number List Price 1 IOA-01 $1,052 1 IOB-01 561 8 Digital Inputs 4 Digital Outputs (Use with Soft PLC) 1 IOC-01 419 8 Digital Inputs 8 Open Collector Digital Outputs (Use with Soft PLC) 1 IOC-02 386 5 PTC type temperature sensor Input 5 PT100 type temperature sensor Input 5 KTY84 type temperature sensor Input 1 1 1 IOE-01 IOE-02 IOE-03 626 1,631 809 Slot Part Number List Price Incremental encoder module 5 to 12 Vdc 100 kHz With encoder signal repeater 2 ENC-01 $461 Incremental encoder module 5 to 12 Vdc 100 kHz 2 ENC-02 404 Slot Part Number List Price 3 3 3 3 3 3 4 4 4 4 4 4 4 RS485-01 RS232-01 RS232-02 CAN/RS485-01 CAN-01 PROFIBUS DP-01 PROFDP-05 DEVICENET-05 ETHERNET/IP-05 RS232-05 RS485-05 MODBUSTCP-05 PROFINETIO-05 $212 161 179 453 378 512 1,138 1,138 1,138 277 333 1,680 1,939 Slot Part Number List Price 2 14-bit analog inputs in voltage or current 2 digital inputs 2 14-bit analog outputs in voltage or current 2 open collector type digital outputs 2 isolated 12-bit analog inputs 2 digital inputs 2 isolated 11-bit analog outputs in voltage or current 2 open collector type digital outputs Interface with Encoder Description Communication Description RS-485 Serial Communication Module (Modbus-RTU) RS-232C Serial Communication Module (Modbus-RTU) RS-232C Serial Communication Module (Modbus-RTU) with DIP switch for flash memory prog. CAN/RS-485 Interface Module (CANopen, DeviceNet and Modbus) CAN Interface Module (CANopen and DeviceNet) Profibus DP-V1 Interface Module Profibus DP Interface Module DeviceNet Interface Module EtherNet/IP Interface Module RS-232 Interface Module (passive) (Modbus-RTU) RS-485 Interface Module (passive) (Modbus-RTU) Modbus - TCP/IP interface module Profinet interface module PLC Module Description PLC functions; Ladder programming; electronic ggearbox; 9 digital inputs; 3 dry-contact digital outputs; 3 open-collector digital ouputs; 1 analog input (14 bits); 2 analog outputs (14 bits); 2 encoder interfaces; RS-485 Modbus-RTU interface; CAN interface (CANopen, CANopen master/ slave). 1,2,3 PLC11-01 $1,960 PLC functions; Ladder programming; electronic ggearbox; 4 digital inputs; 1 dry-contact digital outputs; 3 open-collector digital ouputs; 2 encoder interfaces; RS-485 Modbus-RTU interface; CAN interface (CANopen, CANopen master/slave). 1,2,3 PLC11-02 1,215 1.32 Variable Frequency Drives 101 www.pamensky.com CFW 11M - Accessories Keypad Accessories and Cable for HMI Description CFW 11 Keypad Frame for keypad remote assembly, IP56 Blank cover for keypad slot 1m (3.3ft) Remote Keypad Cable 2m (6.6ft) Remote Keypad Cable 3m (10ft) Remote Keypad Cable 5m (16ft) Remote Keypad Cable 7.5m (25ft) Remote Keypad Cable 10m (33ft) Remote Keypad Cable Part Number List Price HMI-01 RHMIF-01 HMID-01 IHM CAB-RS-1M IHM CAB-RS-2M IHM CAB-RS-3M IHM CAB-RS-5M IHM CAB-RS-7.5M IHM CAB-RS-10M $318 60 47 47 52 57 65 78 88 Part Number List Price DBW03 $5,904 Dynamic Braking Description External Dynamic Braking Module Variable Frequency Drives 1.33 www.pamensky.com 101 CFW 11M - Technical Data 380-480V: 380/400/415/440/480 V (+10%/-15%) Voltage and power range Power Supply and Power Range Frequency Three-Phase 500-600V: 525/575/600 V (+10%/-15%) 660-690V: 660 (+10%/-15%) /690 V 50 / 60 Hz +-2% (48 to 63 Hz) Displacement factor Greater than 0.98 Efficiency Greater than 0.97 Voltage Three Phase, 0 up to power supply voltage Frequency Switching Frequency 0 to 400 Hz Standard: 5kHz Options available: 2.5 / 5 / 10 kHz 110% for 1 min every 10min Normal Duty Cycle 150% for 3 sec every 10min Motor Overload Heavy Duty Cycle Time (ramps) Acceleration Deceleration Speed variation range: 1:30 Speed Control Regulation: 0.5% of rated speed Speed variation range: 1:100 Regulation: +/- 0.01% of rated speed with 14-bit analog input (IOA) Regulation: +/- 0.01% of rated speed with digital reference (keyboard, serial fieldbus, electronic potentiometer, multispeed) Regulation: +/- 0.05% of rated speed with 12-bit analog input Range: 10 to 180% Torque Control Sensorless Vector Regulation: +/- 5% of rated torque Range: 20 to 180% Regulation: +/-10% of rated torque (above 3 Hz) Digital Inputs and Outputs (I/Os) in the Standard Product 0 to 999 seconds Regulation: 1% of rated speed Vector with Encoder (with accessory ENC-01 or ENC02) Inputs 0 to 999 seconds Speed variation range: 1:20 Voltage Vector (VVW) Performance 200% for 3 sec every 10min Regulation: 1% of rated speed Scalar (V/f) Sensorless Vector 150% for 1 min every 10min Analog Relay 6 isolated inputs, 24 Vdc, programmable functions 2 differential inputs isolated by differential amplifier, programmable functions Resolution: - AI1: 12 bits - AI2: 11 bits + signal Signals: (0 to 10) V, (0 to 20) mA or (4 to 20) mA Impedance: - 400 kΩ for signal (0 to 10) V - 500 Ω for signal (0 to 20) mA or (4 to 20) mA 3 relays with NO/NC contacts, 240 Vac / 1A, programmable functions 2 isolated outputs, programmable functions Outputs Analog Available supply to user Environment Resolution: 11 bits Load: 0 to 10 V: RL >= 10 kΩ 0 to 20 mA or 4 to 20 mA: RL < 500Ω 24 Vdc + -20%, 500 mA Temperature of Operation - 10ºC to 50ºC Humidity 5 to 90% without condensation Altitude 0 to 1000 meters Up to 60°C with current derating (2% for each 1°C above 50°C) Up to 4000 meters with current reduction (1% for every 100 meters above 1000 meters) Degree of Protection IP41 Rheostatic Braking Braking Methods 1.34 Supply available to user External braking resistor (not provided) Optimal Braking Does not need braking resistor DC Braking Direct current applied to the motor Variable Frequency Drives 101 www.pamensky.com CFW 11M - Technical Data Profibus DP DeviceNet CANopen CANopen Master/Slave EtherNet TCP/IP Communication RS485 - ModBus RTU RS232 - ModBus RTU USB Protections Safety Standards Mechanical Construction Standards Electromagnetic Compatibility Standards (EMC) PROFIBUS DP (slot 4) CAN/RS485-01 (slot 3) CAN-01 (slot 3) DEVICENET-05 (slot4) CAN/RS485-01 (slot 3) CAN-01 (slot 3) PLC11-01 (slot 1/2/3) ETHERNET/IP-05 (slot 4) RS485-01 CAN/RS485-01 RS485-05 RS232-01 RS232-05 Built-into the standard product Communication with SUPERDRIVE G2 Software Communication with WLP Software used for programming and monitoring the Soft PLC function and the PLC11-01 accessory Overcurrent / short circuit Under / overvoltage in the power circuit Phase loss Overtemperature in the inverter (IGBTs, rectifier and internal air in the electronic cards) Overtemperature in the motor Overload in the braking resistor Overload in the IGBTs Overload in the motor Fault / external alarm Fault in the CPU or memory Phase-to-ground short circuit at the output Fault in the heatsink fan Overspeed of motor Incorrect connection of encoder UL 508C Power conversion equipment UL 840 Insulation coordination including clearances and creepage distances for electrical equipment EN 61800-5-1 Safety requirements electrical, thermal and energy EN 50178 Electronic equipment for use in power installations EN 60204-1 Safety of machinery. Electrical equipment of machines. Part 1: General requirements. Note: In order to have a machine in conformity with this norm, the machine manufacturer is responsible for the installation of an emergency shutdown device and an equipment for network sectioning EN 60146 (IEC 146) Semiconductor converters EN 61800-2 Adjustable speed electrical power drive systems Part 2: General requirements – rating specifications for low voltage adjustable frequency a.c. power drive systems EN 60529 - Degrees of protection provided by enclosures (IP Code) UL 50 - Enclosures for electrical equipment EN 61800-3 - Adjustable speed electrical power drive systems Part 3: EMC product standard including specific test methods EN 55011 - Limits and methods of measurement of radio disturbance characteristics of industrial, scientific and medical (ISM) radio-frequency equipment CISPR 11 - Industrial, scientific and medical (ISM)radio-frequency equipment Electromagnetic disturbance characteristics. Limits and methods of measurement EN 61000-4-2 - Electromagnetic Compatibility Standards (EMC) Part 4: Testing and measurement techniques Section 2: Electrostatic discharge immunity test EN 61000-4-3 - Electromagnetic Compatibility Standards (EMC) Part 4: Testing and measurement techniques Section 3:Radiated, radiofrequency, electromagnetic field immunity test EN 61000-4-4 - Electromagnetic Compatibility Standards (EMC) Part 4: Testing and measurement techniques Section 4: Electrical fast transient / burst immunity test EN 61000-4-5 - Electromagnetic Compatibility Standards (EMC) Part 4: Testing and measurement techniques Section 5: Surge immunity test EN 61000-4-6 - Electromagnetic Compatibility Standards (EMC) Part 4: Testing and measurement techniques Section 6: Immunity to conducted disturbances, induced by radio-frequency fields Variable Frequency Drives 1.35 www.pamensky.com 101 CFW 700 - Variable Frequency Drive Designed for controlling squirrel cage threephase induction motors the new CFW700 is a general purpose drive that gives costumers the flexibility needed for the control of applications ranging from simple speed control to more demanding ones including torque control. Standard Features • • • • • • • • • • • • Built-in DC Link Reactor Encoder Interface RS485 Port for Modbus-RTU communication 8 Digital Inputs / 5 Digital Outputs. 2 Analog Inputs / 2 Analog Outputs. Common DC bus Connection Multi-speed: up to 8 preset speeds can be programmed. PID regulation: eliminates the use of an external controller for closed loop control, thus great performance of speed and torque can be achieved. Ride through: embedded in the CFW700 control this function avoids the drive from tripping during a power outage. Speed/Torque regulation: open and closed loop (encoder feedback required). Flying start: it is able to start smoothly a motor connected to a rotating load regardless rotation direction. Control options for DC bus regulation: prevents the drive from tripping when short deceleration time is required, in demanding applications with high inertia loads. 1.36 • • • • • • S ramp: in applications requiring smooth start-up (e.g. beverage industry) this function can avoid production losses traditional start-up incurs. Three-wire Start/Stop control: retentive contact can command the drive to start/ stop the motor. (Soft PLC) Electronic potentiometer: increase and decrease motor speed using pushbutton control Skip frequency: for some applications specific frequencies must be avoided to protect against resonance effects. Motor thermal curve adjustment: separate adjustment between the motor and drive allows for more effective protection for overload cycles. Copy function: by using the flash memory card MMF-02 parameter settings can be easily stored ensuring integrity and safety in case replacement of the drive is required. Factory Options • • • Safety Stop RFI Filter 24 VDC power input option for control section Variable Frequency Drives 101 www.pamensky.com CFW 700 - Part Number Specification CFW700 A 03P6 T 4 DB 20 -- Y1 W1 1 2 3 4 5 6 7 8 9 10 1. CFW-700 Variable Frequency Drive 2. Frame Size: 3. Output Rated Current: 4. Power Supply: 5. 6. 7. Power Supply Voltage: Braking Module: Enclosure: 8. RFI Filter: 9. Safety Stop: 10. A, B, C, D or E S = single-phase T = three-phase B = single-phase or three-phase 2 = 200-240 V (Frames A, B, C, D) 220-230 V (Frame E) 4 = 380-480 V 5 = 500-600 V NB = no built-in IGBT DB = with built-in braking IGBT (standard for frames A, B, C, D) 20 = IP 20 (standard for frames A, B, C and E) N1 = Nema 1 (standard for frame D) 21 = IP21 Blank = standard Blank = standard (without safety stop function) Y1 = with safety stop function according to EN-954-1 category 3 200-240V 380-480V 500-600V 06P0 = 6.0 A 03P6 = 3.6 A 02P9 = 2.9 A 07P0 = 7.0 A 05P0 = 5.0 A 04P2 = 4.2 A 10P0 = 10 A 06P0 = 6 A 07P0 = 7 A 13P0 = 13 A 07P0 = 7.0 A 10P0 = 10 A 16P0 = 16 A 10P0 = 10 A 12P0 = 12 A 24P0 = 24 A 13P5 = 13.5 A 17P0 = 17 A 28P0 = 28 A 17P0 = 17 A 22P0 = 22 A 33P5 = 33.5 A 24P0 = 24 A 27P0 = 27 A 45P0 = 45 A 31P0 = 31 A 32P0 = 32 A 54P0 = 54 A 38P0 = 38 A 44P0 = 44 A 70P0 = 70 A 45P0 = 45 A 53P0 = 53 A 86P0 = 86 A 58P5 = 58.5 A 63P0 = 63 A 0105 = 105 A 70P5 = 70.5 A 80P0 = 80 A 0107 = 107 A 0142 = 142 A 88P0 = 88 A 0180 = 180 A 0105 = 105 A 0125 = 125 A 0211 = 211 A 0142 = 142 A 0150 = 150 A 0180 = 180 A 0211 = 211 A * Selection Table for 2 External Electronic Supply for Control: Blank = Control circuit is fed by the inverter SMPS W1 = Control circuit is supplied from an external +24Vdc Example: CFW700B28POT2DB20 Variable Frequency Drives 1.37 www.pamensky.com 101 CFW 700 - Table of Products 200-240V - Single Phase Electrical Data Current (A) ND* HD* 6 7 10 5 7 10 Built-In Dynamic Braking Standard Standard Standard Mechanical Data Maximum Applicable Motor ND* HD* HP HP 1.5 2 3 1 2 3 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price A A A 13.9 13.9 13.9 NEMA 1 NEMA 1 NEMA 1 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 CFW700A06POB2DBN1 CFW700A07POB2DBN1 CFW700A10POS2DBN1 $1,699 1,748 1,854 200-240V - Three Phase Electrical Data Current (A) ND* HD* 6 7 7 10 13 16 24 28 33.5 45 54 70 86 105 5 7 5.5 8 11 13 20 24 28 36 45 56 70 86 Built-In Dynamic Braking Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Mechanical Data Maximum Applicable Motor ND* HD* HP HP 1.5 2 2 3 3 5 7.5 10 10 15 20 25 30 40 1 2 1 2 3 3 5 7.5 10 10 15 20 25 30 ND* HD* 142 180 211 115 142 180 Built-In Dynamic Braking Optional Optional Optional Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price A A A A A A B B B C C C D D 13.9 13.9 13.9 13.9 13.9 13.9 22.9 22.9 22.9 45.2 45.2 45.2 120.2 120.2 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 17.64 x 8.67 x 11.52 17.64 x 8.67 x 11.52 17.64 x 8.67 x 11.52 21.63 x 11.81 x 12.00 21.63 x 11.81 x 12.00 CFW700A06POB2DBN1 CFW700A07POB2DBN1 CFW700A07POT2DBN1 CFW700A10POT2DBN1 CFW700A13POT2DBN1 CFW700A16POT2DBN1 CFW700B24POT2DBN1 CFW700B28POT2DBN1 CFW700B33POT2DBN1 CFW700C45POT2DBN1 CFW700C54POT2DBN1 CFW700C70POT2DBN1 CFW700D86POT2DBN1 CFW700D0105T2DBN1 $1,699 1,748 1,626 1,724 1,794 1,923 2,371 2,417 2,748 3,270 4,014 4,676 5,880 7,555 Notes: 1.38 Mechanical Data Maximum Applicable Motor ND* HD* HP HP 50 60 75 40 50 60 * ND - Normal Duty • 110% during 60 seconds every 10 minutes utes • 150% during 3 seconds every 10 minutes es Purchasing Data Frame 220-230V - Three Phase Electrical Data Current (A) Purchasing Data Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price E E E 143.3 143.3 143.3 NEMA 1 NEMA 1 NEMA 1 28.94 x 13.20 x 14.10 32.63 x 13.20 x 14.10 32.63 x 13.20 x 14.10 CFW700E0142T2NBN1C3 CFW700E0180T2NBN1C3 CFW700E0211T2NBN1C3 $10,796 15,125 19,767 * HD - Heavy Duty • 150% during 60 seconds every 10 minutes • 200% during 3 seconds every 10 minutes The maximum motor power ratings gs listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify ecify the VFD through the motor rated current. Variable Frequency Drives 101 www.pamensky.com CFW 700 - Table of Products 380-480V - Three Phase Electrical Data Current (A) ND* HD* 3.6 5 7 10 13.5 17 24 31 38 45 58.5 70.5 88 105 142 180 211 3.6 5 5.5 10 11 13.5 19 25 33 38 47 61 73 88 115 142 180 Built-In Dynamic Braking Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Optional Optional Optional Optional Mechanical Data Maximum Applicable Motor ND* HD* HP HP 2 3 3 5 7.5 10 15 20 25 30 40 50 60 75 100 150 150 2 3 3 5 7.5 7.5 10 15 20 25 30 40 50 60 75 100 150 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price A A A A A B B B C C C D D E E E E 13.9 13.9 13.9 13.9 13.9 22.9 22.9 22.9 45.2 45.2 45.2 120.2 120.2 143.3 143.3 143.3 143.3 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 17.64 x 8.67 x 11.52 17.64 x 8.67 x 11.52 17.64 x 8.67 x 11.52 21.63 x 11.81 x 12.00 21.63 x 11.81 x 12.00 28.94 x 13.20 x 14.10 28.94 x 13.20 x 14.10 32.63 x 13.20 x 14.10 32.63 x 13.20 x 14.10 CFW700A03P6T4DBN1 CFW700A05P0T4DBN1 CFW700A07P0T4DBN1 CFW700A10P0T4DBN1 CFW700A13P5T4DBN1 CFW700B17P0T4DBN1 CFW700B24P0T4DBN1 CFW700B31P0T4DBN1 CFW700C38P0T4DBN1 CFW700C45P0T4DBN1 CFW700C58P5T4DBN1 CFW700D70P5T4DBN1 CFW700D88P0T4DBN1 CFW700E0105T4NBN1C3 CFW700E0142T4NBN1C3 CFW700E0180T4NBN1C3 CFW700E0211T4NBN1C3 $1,670 1,771 1,833 1,887 1,978 2,334 2,820 3,549 4,224 5,317 6,576 7,129 8,524 9,902 11,647 17,079 19,863 500-600V - Three Phase Electrical Data Current (A) ND* HD* 2.9 4.2 7 10 12 17 22 27 32 44 53 63 80 107 125 150 2.7 3.8 6.5 9 10 17 19 22 27 36 44 53 66 90 107 122 Built-In Dynamic Braking Standard Standard Standard Standard Standard Standard Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Mechanical Data Maximum Applicable Motor ND* HD* HP HP 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 2 2 5 7.5 7.5 15 15 20 25 30 40 50 60 75 100 100 * ND - Normal Duty • 110% during 60 seconds every 10 minutes • 150% during 3 seconds every 10 minutes Purchasing Data Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price B B B B B B D D D D E E E E E E 22.9 22.9 22.9 22.9 22.9 22.9 120.2 120.2 120.2 120.2 143.3 143.3 143.3 143.3 143.3 143.3 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 21.63 x 11.81 x 12.00 21.63 x 11.81 x 12.00 21.63 x 11.81 x 12.00 21.63 x 11.81 x 12.00 28.94 x 13.20 x 14.10 28.94 x 13.20 x 14.10 28.94 x 13.20 x 14.10 28.94 x 13.20 x 14.10 28.94 x 13.20 x 14.10 28.94 x 13.20 x 14.10 CFW700B02P9T5DBN1 CFW700B04P2T5DBN1 CFW700B07P0T5DBN1 CFW700B10P0T5DBN1 CFW700B12P0T5DBN1 CFW700B17P0T5DBN1 CFW700D22P0T5NBN1 CFW700D27P0T5NBN1 CFW700D32P0T5NBN1 CFW700D44P0T5NBN1 CFW700E53P0T5NBN1C3 CFW700E63P0T5NBN1C3 CFW700E80P0T5NBN1C3 CFW700E0107T5NBN1C3 CFW700E0125T5NBN1C3 CFW700E0150T5NBN1C3 $2,089 2,169 2,283 2,464 2,603 3,035 4,552 4,847 6,261 7,408 9,365 10,676 11,306 13,604 16,742 21,506 * HD - Heavy Duty • 150% during 60 seconds every 10 minutes • 200% during 3 seconds every 10 minutes Notes: The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/or from other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 1.39 www.pamensky.com 101 CFW 700 - Accessories Communication Description CAN Interface Module (CANopen and DeviceNet) Profibus DP-V1 Interface modul Part Number List Price CAN-01 PROFIBUS DP-01 $378 512 Part Number List Price HMI-02 RHMIF-02 HMID-01 IHM CAB-RS-1M IHM CAB-RS-2M IHM CAB-RS-3M IHM CAB-RS-5M IHM CAB-RS-7.5M IHM CAB-RS-10M $233 52 47 47 52 57 65 78 88 Part Number List Price PCSA-01 PCSB-01 PCSC-01 $42 44 47 Part Number List Price KN1A-02 KN1B-02 KN1C-02 $109 109 124 Keypad Accessories and Cable for HMI Description CFW 700 Keypad Frame for keypad remote assembly, IP56 Blank cover for keypad slot 1m (3.3ft) Remote Keypad Cable 2m (6.6ft) Remote Keypad Cable 3m (10ft) Remote Keypad Cable 5m (16ft) Remote Keypad Cable 7.5m (25ft) Remote Keypad Cable 10m (33ft) Remote Keypad Cable Shielding Kits Description Power cable shielding kit for frame A Power cable shielding kit for frame B Power cable shielding kit for frame C NEMA 1 Kits Description NEMA 1 - conduit kit kit for frame A + Power cable shielding NEMA 1 - conduit kit kit for frame B + Power cable shielding NEMA 1 - conduit kit kit for frame C + Power cable shielding 1.40 Variable Frequency Drives 101 www.pamensky.com CFW 700 - Technical Data Single-phase Voltage 200-220 V ac (+10%-15%) 200-220 V ac (+10%-15%) Three-phase 380-480 V ac (+10%-15%) 500-600 V ac (+10%-15%) Single-phase Voltage and rating Power features 1.5 to 3 HP (1.1 to 2.2 kW) 1.5 to 75 HP (1.1 to 55 kW) Three-phase 2 to 150 HP (1.5 to 110 kW) 2 to 175 HP (1.5 to 110 kW) Frequency 50...60 Hz (+/-2%_48 to 63 Hz) Displacement factor Greater than 0.98 Efficiency Power factor Frequency range Greater than 0.97 0.94 for Three-phase input at nominal conditional 0.70 for Single-phase input at nominal conditional 0 to 3.4x motor rated frequency (P0403). The rated frequency is programable up to 300Hz (V/Hz) and 120Hz (vector mode). Switching Frequency data must be observed for speed limits. Standard: 5 kHz (A, B, C e D frames) 2.5 kHz for all 380 V models frame E Switching frequency 2.5 kHz for frame E 220 V models 142/180 Amps (ND) 2.5 kHz for frame E 220 V model 211 Amps (ND/HD) 5 kHz for frame E 220 V models 142/180 Amps (HD) Control Overload Aceleration Deceleration Temperature Environment Humidity Altitude Dynamic braking Braking Methods Optimal braking DC braking Available options for 2.5/5/10 kHz (check for derating) 110% for 1 min every 10 min Normal Duty (ND) 150% for 3 s every 10 min 150% for 1 min every 10 min Heavy Duty (HD) 200% for 3 s every 10 min 0 to 999 s 0 to 999 s -10 to 50 °C (14 to 122 °F) for most of models. For operating temperature of each model the table "Dimensions, Weight and Temperature”shall be checked. -10...60ºC for frames A, B, C and D (up to 45 °C without derating for models 13 A and 24 A/200...240 V, 7 and 10 A/380...480 V and up to 50 °C without derating for the other models) and-10...55 °C for frame E (up to 45 °C without derating). If derating has to be considered have 2% current reduction for each °C above the specific operating temperature. 5 to 90% with no condensation 0 to 1000 meters with no derating Up to 4000 meters with current reduction of 1% for each 100 meters above 1000 meters Available as standard for frame sizes A, B, C and D for 460 V and D for 600 V. For frame size E "DB”models has to be used. An extra resistor must be fitted in for dynamic braking capability. There is no need for braking resistor DC current applied to motor Regulation: 1% of rated speed V/f Speed Variation range 1:20 Regulation: 1% of rated speed Voltage vector VVW Speed control Sensorless vector Regulation: 0.5% of rated speed Speed Variation range 1:100 Regulation:+/- 0.1% of rated speed with digital reference (keypad, serial fieldbus, multispeed) Regulation:+/- 0.2% of rated speed with 12 bits analog input Range: 10 to 180% Performance Vector with encoder (Encoder interface built-in) Torque control Sensorless Vector I/Os Output Analog Relay Analog 24 V power supply capacity Regulation: +/-5% of rated torque Range: 20 to 180% Regulation: +/-10% of rated torque (above 3 Hz)% Digital Inputs Speed Variation range 1:30 8 x isolated bidirectional 24 V 2 x +/-10 V, 11 bits + signal (differencial) or 0/4...20 mA, 11 bits (differencial) Impedance: 400 kΩ for voltage signal / 500 Ω for current signal 1 x relay NO/NC contact (240 V ac/1 A) 4 x open drain (24 V/200 mA) 2 x 0...10 V or 0/4...20 mA, 11 bits 500 mA (available for the user, including I/Os) Variable Frequency Drives 1.41 www.pamensky.com 101 CFW 700 - Technical Data Modbus-RTU Communication DeviceNet RS485 built-in (available at the control terminals) RS485 built-in / Superdrive and WLP communication CAN-01 (slot 3) CANopen CAN-01 (slot 3) Profibus DP PROFIBUS DP-01 (slot 3) UL 508C Power conversion equipment UL 840 Insulation coordination including clearences and creepage distances for electrical equipment EN61800-5-1 - Safety requirements electrical, thermal and energy. Safety standards EN 50178 - Electronic equipment for use in power installations. EN 60204-1 - Safety of machinery. Electrical equipment of machines. Part 1: General requirements. In order to have a machine in conformity with this regulation, the machine builder is resposible forthe installation of na emergency shutdown device and na equipment for power disconnection. EN 60146 (IEC 146) - Semiconductor converters. EN 61800-2 - Adjustable speed electrical power drive systems - Part 2: General requirements - Rating specifications for low voltage adjustable frequency A.C. power drive systems EN 60529 - Degrees of protection provided by enclosures (IP code). UL 50 - Enclosures for electrical equipment EN 61800-3 - Adjustable speed electrical power drive systems - Part 3: EMC product standard including specifc test methods. EN 55011 - Limits and methods of measurement of radio disturbance characteristics of undustrial, scientific and medical (ISM) radio-frequency equipment. CISPR 11 - Industrial, scientifc and medical (ISM) radio-frequency equipment - Eletromagnetic disturbance characteristics Mechanical construction standards eletromagnetic compatibility standards (EMC) - Limits and methods of measurement. EN 61000-4-2 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 2: Eletrostatic discharge immunity test. EN 61000-4-3 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 3: Radiated, radiofrequency, electromagnetic feld immunity test. EN 61000-4-4 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 4: Electrical fast transient/burst immunity test. EN 61000-4-5 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 5: Surge immunity test. EN 61000-4-6 - Electromagnetic compatibility (EMC)- Part 4: Testing and measurement techniques - Section 6: Immunity to conducted disturbances, induced by radio-frequency fields. Overcurrent / Short Circuit Under / Overvoltage in the power section Phase Loss VSD thermal Overload (IGBTs, rectifier and in the eletronics) Motor thermal overload Braking resistor overload Protections IGBTs overload Motor overload Fault / external alarm CPU failure Phase-to ground short circuit at the output Failure at the heatsink fan Motor overspeed Wrong connection of encoder wiring 1.42 Variable Frequency Drives 101 www.pamensky.com CFW 701 - HVAC Variable Frequency Drive The CFW701 HVAC is a variable-speed drive intended for use with asynchronous motors when heating, ventilation, air conditioning and refrigeration applications are to be met. Offering excellent cost-effectiveness, the CFW701 HVAC follows the CFW700 with plug and play technology, accessories incorporated in the standard version and simple operation. Standard Features • • • • • • • • • • • 230 V single-phase Rated output current 6 to 10 A (1,5 to 3 HP - 1.5 to 3 kW) 220 V three-phase Rated output current of 7 to 211 A (0.5 to 75 HP - 0.18 to 55 kW) 380-480 V three-phase Rated output current of 3.6 to 211 A (0.5 to 150 HP - 0.58 to 110 kW) Compact structure, ideal for installation in confined spaces High accuracy and reliability in speed control Robust hardware Degree of protection IP20 - standard (IP21 and NEMA1 optional) RFI filter( for electromagnetic interference mitigation) LCD Operating interface with backlight Inductors in the DC Link Inputs and outputs (I/O): 8 Isolated digital inputs 3 Differential analog inputs (0-10V/4-20 mA (2) and 4-20 mA (1)) 5 Digital outputs (2 relays with NA contacts, 3 isolated transistors) 2 Non-isolated analog outputs 1 Dedicated input for PTC • • • Special varnish protects electronic boards from dust, moisture, high temperatures and chemicals According to DIN EN 60068-2-60 RS-485 interface: BACnet MS/TP, Metasys N2 and Modbus RTU Intelligent cooling system Optional Features • • • Operator interface for remote assembly (up to 10 meters) Flash memory module (storage capacity of 1 MB) Safety stop module – Guarantees the blocking of firing circuit and therefore power to the motor. Meets EN 954-1 / EN 13849-1, category 3 standards. This VFD complies with the following standards: • EN 61800-5-2:2007, EN ISO 138491:2008 + AC:2009, IEC 62061:2005, IEC 61508 Parts 1-7:2010, EN 50178:1997, IEC 60204-1:2005 (in extracts) Variable Frequency Drives 1.43 www.pamensky.com 101 CFW 701 - Part Number Specification CFW701 A 03P6 T 4 DB 20 -- Y1 W1 1 2 3 4 5 6 7 8 9 10 1. CFW-701 HVAC Variable Frequency Drive 2. Frame Size: 3. Output Rated Current: 4. Power Supply: 5. 6. 7. Power Supply Voltage: Braking Module: Enclosure: A, B, C, D or E S = single-phase T = three-phase B = single-phase or three-phase 2 = 200-240 V (Frames A, B, C, D) 220-230 V (Frame E) 4 = 380-480 V NB = no built-in IGBT DB = with built-in braking IGBT (standard for frames A, B, C, D) 20 = IP 20 (standard for frames A, B, C and E) N1 = Nema 1 (standard for frame D) 21 = IP21 (not available for frame E) 8. RFI Filter: Blank = standard 9. Safety Stop: Blank = standard (without safety stop function) Y1 = with safety stop function according to EN-954-1 category 3 200-240V 380-480V 06P0 = 6.0 A 03P6 = 3.6 A 07P0 = 7.0 A 05P0 = 5.0 A 10P0 = 10 A 06P0 = 6 A 13P0 = 13 A 07P0 = 7.0 A 16P0 = 16 A 10P0 = 10 A 24P0 = 24 A 13P5 = 13.5 A 28P0 = 28 A 17P0 = 17 A 33P5 = 33.5 A 24P0 = 24 A 45P0 = 45 A 31P0 = 31 A 54P0 = 54 A 38P0 = 38 A 70P0 = 70 A 45P0 = 45 A 86P0 = 86 A 58P5 = 58.5 A 0105 = 105 A 70P5 = 70.5 A 0142 = 142 A 88P0 = 88 A 0180 = 180 A 0105 = 105 A 0211 = 211 A 0211 = 211 A * Selection Table for 2 10. 1.44 0142 = 142 A 0180 = 180 A External Electronic Supply for Control: Blank = Control circuit is fed by the inverter SMPS W1 = Control circuit is supplied from an external +24Vdc Example: CFW701B28POT2DB20 Variable Frequency Drives 101 www.pamensky.com CFW 701 - Table of Products 200-240V - Single Phase Electrical Data Current (A) Built-In Dynamic Braking Mechanical Data Maximum Applicable Motor Frame Weight (lb) Degree of Protection A A A 13.9 13.9 13.9 NEMA 1 NEMA 1 NEMA 1 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 HP 6 7 10 Standard Standard Standard 1.5 2 3 200-240V - Single and Three Phase Electrical Data Current (A) Built-In Dynamic Braking Mechanical Data Maximum Applicable Motor Standard Standard 1.5 2 Current (A) Built-In Dynamic Braking Dimensions (in) HxWxD Part Number A A 13.9 13.9 NEMA 1 NEMA 1 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 CFW701A06POB2DB20 CFW701A07POB2DB20 Mechanical Data Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard 2 3 3 5 7.5 10 10 15 20 25 30 40 Built-In Dynamic Braking Frame Weight (lb) Degree of Protection A A A A B B B C C C D D 13.9 13.9 13.9 13.9 22.9 22.9 22.9 45.2 45.2 45.2 71.8 71.8 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 17.64 x 8.67 x 11.52 17.64 x 8.67 x 11.52 17.64 x 8.67 x 11.52 21.63 x 11.81 x 12.00 21.63 x 11.81 x 12.00 Mechanical Data Maximum Applicable Motor Optional Optional Optional 50 60 75 Part Number CFW701A07POT2DB20 CFW701A10POT2DB20 CFW701A13POT2DB20 CFW701A16POT2DB20 CFW701B24POT2DB20 CFW701B28POT2DB20 CFW701B33POT2DB20 CFW701C45POT2DB20 CFW701C54POT2DB20 CFW701C70POT2DB20 CFW701D86POT2DB20 CFW701D0105POT2DB20 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number E E E 143.3 143.3 143.3 NEMA 1 NEMA 1 NEMA 1 28.94 x 13.20 x 14.10 32.63 x 13.20 x 14.10 32.63 x 13.20 x 14.10 CFW701E0142POT2NB20 CFW701E0180POT2NB20 CFW701E0211POT2NB20 HP 142 180 211 Purchasing Data Dimensions (in) HxWxD 220-230V - Three Phase Electrical Data Current (A) Purchasing Data Degree of Protection HP 7 10 13 16 24 28 33.5 45 54 70 86 105 CFW701A06POS2DB20 CFW701A07POS2DB20 CFW701A10POS2DB20 Weight (lb) 200-240V - Three Phase Electrical Data Maximum Applicable Motor Part Number Frame HP 6 7 Purchasing Data Dimensions (in) HxWxD * ND - Normal Duty • 110% during 60 seconds every 10 minutes Notes: The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 1.45 www.pamensky.com 101 CFW 701 - Table of Products 380-480V - Three Phase Electrical Data Current (A) Built-In Dynamic Braking Mechanical Data Maximum Applicable Motor Frame Weight (lb) Degree of Protection A A A A A B B B C C C D D E E E E 13.9 13.9 13.9 13.9 13.9 22.9 22.9 22.9 45.2 45.2 45.2 71.8 71.8 143.3 143.3 143.3 143.3 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 12.02 x 5.71 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 17.64 x 8.67 x 11.52 17.64 x 8.67 x 11.52 17.64 x 8.67 x 11.52 21.63 x 11.81 x 12.00 21.63 x 11.81 x 12.00 28.94 x 13.20 x 14.10 28.94 x 13.20 x 14.10 32.63 x 13.20 x 14.10 32.63 x 13.20 x 14.10 HP 3.6 5 7 10 13.5 17 24 31 38 45 58.5 70.5 88 105 142 180 211 Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Optional Optional Optional Optional 2 3 3 5 7.5 10 15 20 25 30 40 50 60 75 100 150 150 500-600V - Three Phase Electrical Data Current (A) Built-In Dynamic Braking Mechanical Data Maximum Applicable Motor Standard Standard Standard Standard Standard Standard Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 150 Part Number CFW701A03P6T4DB20 CFW701A05P0T4DB20 CFW701A07P0T4DB20 CFW701A10P0T4DB20 CFW701A13P5T4DB20 CFW701B17P0T4DB20 CFW701B24P0T4DB20 CFW701B31P0T4DB20 CFW701C38P0T4DB20 CFW701C45P0T4DB20 CFW701C58P5T4DB20 CFW701D70P5T4DB20 CFW701D88P0T4DB20 CFW701E0105T4NB20 CFW701E0142T4NB20 CFW701E0180T4NB20 CFW701E0211T4NB20 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number B B B B B B D D D D E E E E E E E 22.9 22.9 22.9 22.9 22.9 22.9 71.8 71.8 71.8 71.8 143.3 143.3 143.3 143.3 143.3 143.3 143.3 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 13.82 x 7.46 x 8.94 21.63 x 11.81 x 12.00 21.63 x 11.81 x 12.00 21.63 x 11.81 x 12.00 21.63 x 11.81 x 12.00 32.63 x 13.20 x 14.10 32.63 x 13.20 x 14.10 32.63 x 13.20 x 14.10 32.63 x 13.20 x 14.10 32.63 x 13.20 x 14.10 32.63 x 13.20 x 14.10 32.63 x 13.20 x 14.10 CFW701B02P9T5DB20 CFW701B04P2T5DB20 CFW701B07P0T5DB20 CFW701B10P0T5DB20 CFW701B12P0T5DB20 CFW701B17P0T5DB20 CFW701D22P0T5NB20 CFW701D27P0T5NB20 CFW701D32P0T5NB20 CFW701D44P0T5NB20 CFW701E53P0T5NB20 CFW701E63P0T5NB20 CFW701E80P0T5NB20 CFW701E0107T5NB20 CFW701E0125T5NB20 CFW701E0150T5NB20 CFW701E0211T4NB20 HP 2.9 4.2 7 10 12 17 22 27 32 44 53 63 80 107 125 150 211 Purchasing Data Dimensions (in) HxWxD * ND - Normal Duty • 110% during 60 seconds every 10 minutes Notes: 1.46 The maximum motor power ratings listed above are based on WEG 2 and 4 pole motors. For motors with different numbers of poles (ie. 6 and 8 poles), other voltages and/ or from other manufacturers, specify the VFD through the motor rated current. Variable Frequency Drives 101 www.pamensky.com CFW 701 - Accessories Communication Description CAN Interface Module (CANopen and DeviceNet) Profibus DP-V1 Interface modul Part Number CAN-01 PROFIBUS DP-01 Keypad Accessories and Cable for HMI Description CFW 700 Keypad Frame for keypad remote assembly, IP56 Blank cover for keypad slot 1m (3.3ft) Remote Keypad Cable 2m (6.6ft) Remote Keypad Cable 3m (10ft) Remote Keypad Cable 5m (16ft) Remote Keypad Cable 7.5m (25ft) Remote Keypad Cable 10m (33ft) Remote Keypad Cable Part Number HMI-03 RHMIF-03 HMID-01 IHM CAB-RS-1M IHM CAB-RS-2M IHM CAB-RS-3M IHM CAB-RS-5M IHM CAB-RS-7.5M IHM CAB-RS-10M Shielding Kits Description Power cable shielding kit for frame A Power cable shielding kit for frame B Power cable shielding kit for frame C Part Number PCSA-01 PCSB-01 PCSC-01 NEMA 1 Kits Description NEMA 1 - conduit kit kit for frame A + Power cable shielding NEMA 1 - conduit kit kit for frame B + Power cable shielding NEMA 1 - conduit kit kit for frame C + Power cable shielding Part Number KN1A-02 KN1B-02 KN1C-02 Variable Frequency Drives 1.47 www.pamensky.com 101 CFW 701 - Technical Data Single phase Voltage Voltage and rating Power features Frequency Displacement factor Efficiency 200-220 V ac (+10 %-15 %) 200-220 V ac (+10 %-15 %) Three phase 380-480 V ac (+10 %-15 %) 500-600 V ac (+10%-15%) Single phase 1.5 to 3 HP (1.1 to 2.2 kW) 1.5 to 75 HP (1.1 to 55 kW) Three phase 2 to 150 HP (1.5 to 110 kW) 50...60 Hz (+/-2%_48 to 63 Hz) Greater than 0.98 Greater than 0.97 0.94 for three phase input at nominal conditional 0.70 for single phase input at nominal conditional 0 to 3.4x motor rated frequency (P0403). The rated frequency is programable up to 300 Hz (V/Hz) and Frequency range 120 Hz (vector mode). Switching Frequency data must be observed for speed limits. Standard: 5 kHz ( A, B, C D frames) 2.5 kHz for all 380 V models frame E 2.5 kHz for frame E 220 V models 142/180 Amps (ND) Switching frequency 2.5 kHz for frame E 220 V model 211 Amps (ND/HD) Control 5 kHz for frame E 220 V models 142/180 Amps (HD) Available options for 2.5 / 5 / 10 kHz ( check for derating) Normal Duty 110% for 1min every 10 min (ND) Overload Aceleration 0 to 999 s Deceleration 0 to 999 s -10 to 50 °C (14 to 122 °F) for most of models. For operating temperature of each model the table " Dimensions, Weight and Temperature" shall be checked. -10...60ºC for frames A, B, C and D (up to 45 °C without derating for models 13 A and 24 A/200...240 V, 7 and Temperature 10 A/380...480 V and up to 50 °C without derating for the other models) and-10...55 °C for frame E (up to 45 °C without derating). If derating has to be considered have 2% current reduction for each °C above the specific operating Environment temperature. Humidity 5 to 90% with no condensation 0 to 1000 meters with no derating Altitude Up to 4000 meters with current reduction of 1% for each 100 meters above 1000 meters Available as standard for frame sizes A, B, C and D for 460 V and D for 600 V. For frame size E "DB" models has to be Dynamic braking used. An extra resistor must be fitted in for dynamic braking capability. Braking methods Optimal braking There is no need for braking resistor DC braking DC Current applied to motor Regulation: 1% of rated speed V/f Speed Variation range 1:20 Performance Speed control Regulation: 1% of rated speed Voltage Vector VVW Speed Variation range 1:30 Digital 8 x isolated bidirectional 24 V Inputs 2 x +/-10V, 11 bits + signal (differencial) or 0/4...20 mA, 11 bits (differencial) Analog Impedance: 400 kΩ for voltage signal / 500Ω for current signal 2 x relay NO/NC contact (240 V ac/1 A) Relay 4 x open drain (24 V/200 mA) I/Os Output 1 x 0/4 - 20 mA 11bits Analog 2 x 0...10 V or 0/4...20 mA, 11 bits (not isolated from inverter ground) 24 V power 500 mA (available for the user, including I/Os) supply capacity Modbus RTU RS485 built-in ( Available in control terminals) Communication BACnet MS/TP RS485 built-in / Superdrive and WLP communication Metasys N2 Power factor 1.48 Variable Frequency Drives 101 www.pamensky.com CFW 701 - Technical Data UL 508C Power conversion equipment UL 840 Insulation coordination including clearences and creepage distances for electrical equipment EN61800-5-1 - Safety requirements electrical, thermal and energy. EN 50178 - Electronic equipment for use in power installations. Safety standards EN 60204-1 - Safety of machinery. Electrical equipment of machines. Part 1: General requirements. In order to have a machine in conformity with this regulation, the machine builder is resposible forthe installation of na emergency shutdown device and na equipment for power disconnection. EN 60146 (IEC 146) - Semiconductor converters. EN 61800-2 - Adjustable speed electrical power drive systems - Part 2: General requirements - Rating specifications for low voltage adjustable frequency A.C. power drive systems EN 60529 - Degrees of protection provided by enclosures (IP code). UL 50 - Enclosures for electrical equipment EN 61800-3 - Adjustable speed electrical power drive systems - Part 3: EMC product standard including specifc test methods. EN 55011 - Limits and methods of measurement of radio disturbance characteristics of undustrial, scientific and medical (ISM) radiofrequency equipment. Mechanical CISPR 11 - Industrial, scientifc and medical (ISM) radio-frequency equipment - Eletromagnetic disturbance characteristics - Limits and Construccion methods of measurement. Standards EN 61000-4-2 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 2: Eletrostatic discharge Eletromagnetic immunity test. Compatibility EN 61000-4-3 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 3: Radiated, radio-frequency, Standards (EMC) electromagnetic feld immunity test. EN 61000-4-4 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 4: Electrical fast transient/ burst immunity test. EN 61000-4-5 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 5: Surge immunity test. EN 61000-4-6 - Electromagnetic compatibility (EMC)- Part 4: Testing and measurement techniques - Section 6: Immunity to conducted disturbances, induced by radio-frequency fields. Overcurrent / Short circuit Under / Overvoltage in the power section Phase loss VSD thermal overload ( IGBTs, rectifier and in the eletronics) Motor thermal overload Braking resistor overload IGBTs overload Protections Motor overload Fault / external alarm CPU failure Phase-to ground short circuit at the output Failure at the heatsink fan Motor overspeed Wrong connection of encoder coder wiring Variable Frequency Drives 1.49 www.pamensky.com 101 MVW 01- Medium Voltage VFD WEG is a traditional supplier of solutions in speed variation, manufacturing all the parts of a system: Input switchgear, transformer(dry-type or oil-type), frequency inverter and electric motor. The MVW01 is designed to control medium voltage induction motors. It features unique innovations, combining hardware robustness with simplicity, reliability and safety in a compact solution with few components and state-of-the-art technology. MVW01 follows the same programming philosophy of the WEG low voltage inverter line, simplifying its application. Standard Features It has a multilevel topology with high-voltage IGBTs (3.3 or 6.5 kV) and optimal switching reducing the motor harmonic currents to extremely low levels. By reducing the number of components in the drive WEG has made the MVW-01 more efficient and reliables. • • The multipulse diode configuration of the input rectifier gives a high power factor in the power supply meeting IEEE 519 requirements. In the control stage, it has a multiprocessing architecture using 32-bit processors (64-bit bus) with floating point capability and high performance, ensuring high efficiency in motor control. • • • • • • • • • • • • • • • Motor voltage: 2.3 kV, 3.3 kV, 4.16 kV or up to 6.0 kV - 6.9 kV Power ratings up to 8,000 hp (6,000 kW) 12-pulse diode input rectifier (18 or 24 pulses are also available) Reduced number of components, which results in high efficiency and reliability Assembled in IP41/NEMA1 panel Multilevel power topology: Neutral Point Clamped (NPC) 3/5 level up to 4160 V 5/9 level above 6000 V Power and control sections isolated by fiber optic cable or optics Network communication Dry-type plastic film power capacitors of high reliability and long useful life Voltage Source Inverter (VSI) Air-cooled High efficiency (> 99%) High power factor (> 95%) Low noise level (< 75 dBa) Low heat dissipation 3300 & 4160V: 2300, 6600 & 6900V: 1.50 Variable Frequency Drives 101 www.pamensky.com MVW 01 - Specification Table 2300V - Three Phase Electrical Data Mechanical Data Purchasing Data Maximum Applicable Motor Current (A) Constant Torque Variable Torque CT VT HP KW HP KW 120 140 165 175 210 250 280 386 450 490 560 730 855 930 1064 137 160 175 200 240 280 320 440 490 560 640 835 930 1064 1216 500 600 700 750 900 1000 1250 1750 2000 2250 2500 3000 3700 4000 4500 400 450 500 560 710 800 900 1250 1400 1600 1800 2200 2800 3000 3400 600 700 750 900 1000 1250 1500 2000 2250 2500 3000 3500 4000 4500 5000 450 500 560 710 750 900 1120 1400 1600 1600 2200 2500 3000 3400 3700 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number A A A A A A B B B B B C C C C 3,432 3,432 3,432 3,432 3,432 3,432 3,740 3,740 3,740 3,740 3,740 5,940 5,940 5,940 5,940 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 102.36 x 37.80 86.22 x 102.36 x 37.80 86.22 x 102.36 x 37.80 86.22 x 102.36 x 37.80 86.22 x 102.36 x 37.80 86.22 x 157.48 x 37.80 86.22 x 157.48 x 37.80 86.22 x 157.48 x 37.80 86.22 x 157.48 x 37.80 MVW010120T2300ESZ MVW010140T2300ESZ MVW010165T2300ESZ MVW010175T2300ESZ MVW010210T2300ESZ MVW010250T2300ESZ MVW010280T2300ESZ MVW010386T2300ESZ MVW010450T2300ESZ MVW010490T2300ESZ MVW010560T2300ESZ MVW010730T2300ESZ MVW010855T2300ESZ MVW010930T2300ESZ MVW011064T2300ESZ 3300V - Three Phase Electrical Data Mechanical Data Purchasing Data Maximum Applicable Motor Current (A) Constant Torque Variable Torque CT VT HP KW HP KW 85 100 112 138 150 160 186 235 265 310 375 500 580 670 880 1178 97 112 128 150 160 182 212 265 312 354 428 571 650 755 1008 1235 500 600 700 800 900 1000 1250 1500 1750 2000 2500 3000 3750 4000 5500 7000 400 450 500 630 710 800 900 1120 1250 1400 1800 2200 2800 3000 4100 5225 600 700 800 900 1000 1250 1500 1750 2000 2250 2750 3750 4000 4500 6000 8000 450 500 630 710 800 900 1120 1250 1400 1600 2000 2800 3000 3300 4500 6000 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number A A A A A A A A A A C C C D D E 3,432 3,432 3,432 3,432 3,432 3,432 3,432 3,432 3,432 3,432 5,940 5,940 5,940 9,900 9,900 11,000 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 157.48 x 37.80 86.22 x 157.48 x 37.80 86.22 x 157.48 x 37.80 87.52 x 233.07 x 39.57 87.52 x 233.07 x 39.57 87.52 x 283.46 x 39.57 MVW010085T3300ESZ MVW010100T3300ESZ MVW010112T3300ESZ MVW010138T3300ESZ MVW010150T3300ESZ MVW010160T3300ESZ MVW010186T3300ESZ MVW010235T3300ESZ MVW010265T3300ESZ MVW010310T3300ESZ MVW010375T3300ESZ MVW010500T3300ESZ MVW010580T3300ESZ MVW010670T3300ESZ MVW010880T3300ESZ MVW011178T3300ESZ 4160V - Three Phase Electrical Data Mechanical Data Purchasing Data Maximum Applicable Motor Current (A) Constant Torque Variable Torque CT VT HP KW HP KW 70 80 94 110 120 130 162 170 188 250 300 357 475 536 712 950 80 91 107 120 130 148 170 188 214 286 342 403 542 610 815 1086 500 600 700 800 900 1000 1250 1350 1500 2000 2250 3000 4000 4000 5500 7000 400 450 500 630 710 800 900 1000 1120 1400 1600 2250 2900 2900 4100 5225 600 700 800 900 1000 1250 1350 1500 1750 2250 2750 3900 4500 5000 6000 8000 450 500 630 710 800 900 1000 1120 1300 1600 2000 2600 3300 3700 4500 6000 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number A A A A A A A A A A C C C D D E 3,432 3,432 3,432 3,432 3,432 3,432 3,432 3,432 3,432 3,432 5,940 5,940 5,940 9,900 9,900 11,000 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 94.49 x 37.80 86.22 x 157.48 x 37.80 86.22 x 157.48 x 37.80 86.22 x 157.48 x 37.80 87.52 x 233.07 x 39.57 87.52 x 233.07 x 39.57 87.52 x 283.46 x 39.57 MVW010070T4160ESZ MVW010080T4160ESZ MVW010094T4160ESZ MVW010110T4160ESZ MVW010120T4160ESZ MVW010130T4160ESZ MVW010162T4160ESZ MVW010170T4160ESZ MVW010188T4160ESZ MVW010250T4160ESZ MVW010300T4160ESZ MVW010357T4160ESZ MVW010475T4160ESZ MVW010536T3300ESZ MVW010712T4160ESZ MVW010950T4160ESZ Variable Frequency Drives 1.51 www.pamensky.com 101 MVW 01 - Specification Table 6000 to 6300V - Three Phase Electrical Data Mechanical Data Constant Torque Variable Torque CT VT HP KW HP KW 44 59 79 95 107 127 144 164 199 220 253 322 379 440 58 78 104 124 140 166 188 214 260 288 330 420 495 575 500 600 800 900 1000 1350 1500 1750 2250 2500 3000 3700 4500 5000 370 450 600 675 750 1000 1120 1300 1680 1865 2240 2760 3350 3700 600 800 1000 1350 1500 1750 2250 2500 3000 3500 4000 5000 6000 7000 450 600 750 1000 1120 1300 1680 1865 2240 2600 3000 3700 4475 5225 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number C1 C1 C1 C1 C1 C2 C2 C2 C2 C2 C3 C3 C3 C3 3,740 3,740 3,740 3,740 3,740 6,820 6,820 6,820 6,820 6,820 11,000 11,000 11,000 11,000 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 90.79 x 70.87 x 47.24 90.79 x 70.87 x 47.24 90.79 x 70.87 x 47.24 90.79 x 70.87 x 47.24 90.79 x 70.87 x 47.24 87.64 x 137.87 x 39.57 87.64 x 137.87 x 39.57 87.64 x 137.87 x 39.57 87.64 x 137.87 x 39.57 87.64 x 137.87 x 39.57 87.52 x 182.68 x 39.57 87.52 x 182.68 x 39.57 87.52 x 182.68 x 39.57 87.52 x 182.68 x 39.57 MVW010058T6300ESZ MVW010078T6300ESZ MVW010104T6300ESZ MVW010124T6300ESZ MVW010140T6300ESZ MVW010166T6300ESZ MVW010188T6300ESZ MVW010214T6300ESZ MVW010260T6300ESZ MVW010288T6300ESZ MVW010330T6300ESZ MVW010420T6300ESZ MVW010495T6300ESZ MVW010575T6300ESZ 6600 to 6900V - Three Phase Electrical Data Mechanical Data Purchasing Data Maximum Applicable Motor Current (A) Constant Torque Variable Torque CT VT HP KW HP KW 40 53 72 85 99 115 130 144 180 203 230 287 345 398 53 70 94 112 130 150 170 188 235 265 300 375 450 520 500 600 800 1000 1250 1350 1500 1750 2250 2500 3000 3700 4500 5000 370 450 600 750 900 1000 1120 1300 1680 1865 2240 2760 3350 3700 600 800 1000 1350 1500 2000 2250 2500 3000 3500 4000 5000 6000 7000 450 600 750 1000 1120 1500 1680 1865 2240 2600 3000 3730 4475 5225 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number C1 C1 C1 C1 C1 C2 C2 C2 C2 C2 C3 C3 C3 C3 3,740 3,740 3,740 3,740 3,740 6,820 6,820 6,820 6,820 6,820 11,000 11,000 11,000 11,000 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 90.79 x 70.87 x 47.24 90.79 x 70.87 x 47.24 90.79 x 70.87 x 47.24 90.79 x 70.87 x 47.24 90.79 x 70.87 x 47.24 87.64 x 137.87 x 39.57 87.64 x 137.87 x 39.57 87.64 x 137.87 x 39.57 87.64 x 137.87 x 39.57 87.64 x 137.87 x 39.57 87.52 x 182.68 x 39.57 87.52 x 182.68 x 39.57 87.52 x 182.68 x 39.57 87.52 x 182.68 x 39.57 MVW01C0053T6900ESZ MVW01C0070T6900ESZ MVW01C0094T6900ESZ MVW01C0112T6900ESZ MVW01C0123T6900ESZ MVW010150T6900ESZ MVW010170T6900ESZ MVW010188T6900ESZ MVW010235T6900ESZ MVW010265T6900ESZ MVW010300T6900ESZ MVW010375T6900ESZ MVW010450T6900ESZ MVW010520T6900ESZ Notes • Power rating guide, specify the MVW01 through the inverter output rated current • VT= Variable torque – allowable overload of 115% for 60s, every 10 min 1.52 Purchasing Data Maximum Applicable Motor Current (A) Variable Frequency Drives 101 www.pamensky.com MVW 01- Compact Medium Voltage VFD WEG is a traditional supplier of solutions in speed variation, manufacturing all the parts of a system: Input switchgear, transformer(dry-type or oil-type), frequency inverter and electric motor. The MVW01 is designed to control medium voltage induction motors. It features unique innovations, combining hardware robustness with simplicity, reliability and safety in a compact solution with few components and state-of-the-art generation technology. MVW01 follows the same programming philosophy of the WEG low voltage inverter line, simplifying its application. Standard Features It has a multilevel topology with high-voltage IGBTs (3.3 or 6.5 kV) and optimal switching reducing the motor harmonic currents to extremely low levels. By reducing the number of components in the drive WEG has made the MVW-01 more efficient and reliables. • • The multipulse diode configuration of the input rectifier gives a high power factor in the power supply meeting IEEE 519 requirements. In the control stage, it has a multiprocessing architecture using 32-bit processors (64-bit bus) with floating point capability and high performance, ensuring high efficiency in motor control. • • • • • • • • • • • • • • • Motor voltage: 2.3 kV, 3.3 kV, 4.16 kV or up to 6.0 kV - 6.9 kV Power ratings up to 8,000 hp (6,000 kW) 18-pulse diode input rectifier standard (12 pulse is also available) Reduced number of components, which results in high efficiency and reliability Assembled in IP41/NEMA1 panel Multilevel power topology: Neutral Point Clamped (NPC) 3/5 level up to 4160 V 5/9 level above 6000 V Power and control sections isolated by fiber optic cable or optics Network communication Dry-type plastic film power capacitors of high reliability and long useful life Voltage Source Inverter (VSI) Air-cooled High efficiency (> 99%) High power factor (> 95%) Low noise level (< 75 dBa) Low heat dissipation Variable Frequency Drives 1.53 www.pamensky.com 101 MVW 01 Compact - Specification Table 3300V - Three Phase Electrical Data Mechanical Data Purchasing Data Maximum Applicable Motor Current (A) Constant Torque Variable Torque CT VT HP KW HP KW 85 100 112 125 97 112 128 138 500 600 700 800 375 450 525 600 600 700 800 900 450 525 600 675 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number A0 A0 A0 AO 1,980 1,980 1,980 1,980 IP41 IP41 IP41 IP41 91.18 x 39.37 x 39.45 91.18 x 39.37 x 39.45 91.18 x 39.37 x 39.45 91.18 x 39.37 x 39.45 MVW01C0085T3300ESZ MVW01C0100T3300ESZ MVW01C0112T3300ESZ MVW01C0125T3300ESZ 4160V - Three Phase Electrical Data Mechanical Data Current (A) Constant Torque Variable Torque CT VT HP KW HP KW 70 80 94 110 120 80 91 107 120 130 500 600 700 800 900 375 450 525 600 675 600 700 800 900 1000 450 525 600 675 750 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number A0 A0 A0 A0 A0 1,980 1,980 1,980 1,980 1,980 IP41 IP41 IP41 IP41 IP41 91.18 x 39.37 x 39.45 91.18 x 39.37 x 39.45 91.18 x 39.37 x 39.45 91.18 x 39.37 x 39.45 91.18 x 39.37 x 39.45 MVW01C0070T4160ESZ MVW01C0080T4160ESZ MVW01C0094T4160ESZ MVW01C0110T4160ESZ MVW01C0120T4160ESZ Notes • Power rating guide, specify the MVW01 through the inverter output rated current • CT= Constant torque – allowable overload of 150% for¨60s, every 10 min • VT= Variable torque – allowable overload of 115% for 60s, every 10 min 1.54 Purchasing Data Maximum Applicable Motor Variable Frequency Drives 101 www.pamensky.com MVW 01 - Technical Data Voltage Main Power Supply Auxiliary supply Protection degree Dimensions Environmental Conditions Finishing Control 2300, 3300, 4160, 6300 or 6900 V (± 10%, -20% with reduced output power) Frequency 50 or 60 Hz (specify)± 3% Phase Unbalance <3% Cos >0,97 Overvoltage category Category III Voltages 220, 380, 400, 415, 440, 460 , 480, 525, 575, 660 or 690 V Frequency 50 or 60 Hz, )±3 % Phase Unbalance <3% Standard IP41 Width / Height / Depth (mm) 7 different mechanics (see item 9.4) Temperature 0 to 40o C (up to 50o C with reduction of 2.5% / oC on the output current) Humidity 5 to 90% noncondensing Altitude 0 to 1000 m (up to 4000 m with reduction of 10% / 1000 m) Pollution degree 2 Color (Standard) Light Blue cod. 14040 (Doors) Dark Blue cod 42350 (Base, roof, shutters) Microprocessor 32 bits Control Method PWM sinusoidal SVM (Space Vector Modulation) and optimal pulse patterns (OPP) Control Types Scalar (Imposed voltage - V/F), sensorless vector and closed loop vector Switching Device High voltage IGBT (HV – IGBT) Frequency variation 0 to 100 Hz Overload capacity Efficiency 150 % for 60 seconds, every 10 min. (1.5 x I rated. – CT) 115 % for 60 seconds, every 10 min. (1.15 x I rated – VT) 99% V/F Sensorless Performance Speed Control With Encoder (Use EBA or EBB card) Regulation 1 % of rated speed with slip compensation Resolution: 1 rpm (keypad reference) Speed regulation: 0.5% of rated speed Speed variation range:1:100 Regulation: ± 0.1% of rated speed with analog input of 14 bits (EBA); ± 0.1% of rated spedd wth digital reference (keyboard, serial, Fieldbus, Electronic Potetionmeter, multispeed); ± 0.1% of rated speed with analog input of 10 bits (CC9) 2 Programmable differential inputs ( 10 bits ): 0 to 10 V, 0 to 20 mA ou 4 to 20 mA Analog Inputs 1 Programmable bipolar input ( 14 bits ): -10 to + 10 V, 0 to 20 mA or 4...20 mA 1) 1 Programmable isolated input ( 10 bits ): 0 to 10 V, 0 a 20 mA or 4 to 20 mA 1) 1 Programmable isolated input ( 10 bits ): 0 to 10 V, 0 a 20 mA or 4 to 20 mA 8 Programmable isolated inputs: 24 Vdc Digital 1 Programmable isolated input: 24 Vdc 1) 1 Programmable isolated input: 24 Vdc ( for motor PTC thermistor) 1) 2 Programmable outputs ( 11 bits ) : 0 to 10 V Analog Outputs 2 Programmable isolated outputs ( 11 bits ) : 0 to 20 mA or 4 to 20 mA 1) 2 Programmable isolated outputs ( 11 bits ) : 0 to 20 mA or 4 to 20 mA Relay 5 Programmable outputs, contacts NA/NF ( NO/NC ) : 240 Vac, 1 A Transistor 2 DC Programmable isolated outputs: 24 Vdc, 50 mA 1) Serial Interface Communication FieldBus Networks Safety 2 Programmable bipolar outputs ( 14 bits ) : (-10 to + 10) V1) Protections (memories of the last 100 faults/ alarms with date and time) RS-232 (point to point) RS-485, isolated via EBA or EBB cards (multi-point up to 30 inverters) 1) Modbus RTU (embedded software) via serial interface RS-485 Ethernet, Profibus DP or DeviceNet via additional kits KFB 1) Overvoltage in the circuit: intermediate Output short-circuit Undervoltage in the circuit: intermediate Output ground-short-circuit Overtemperature in the inverter and the motor External fault Overcurrent in the output Failed self-test and programming Motor overload (I x t) Failed self-test and programming Overload in braking resistor Phase fault in power supply Failed CPU (Watchdog) / EPROM Interface MMI-MVW-01 connection fault Incremental Encoder fault 1) Optional Variable Frequency Drives 1.55 www.pamensky.com 101 MVW 01 - Technical Data Electromagnetic compatibility Compliances / Standards EMC directive 89 / 336 / EEC – industrial environment CEI Standard - IEC 61800-3 (EMC – Emisson and Immunity) Adjustable Speed Electrical Power Drive System CEI - IEC 61800 Part 4 – General Requirements Part 5 – Safety Requirements Start / Stop, General Functions Programming Commands Increase / Decrease Speed JOG, FWD/VER and Local/Remote Speed Reference (rpm) Keypad Monitoring Output Current (A) Motor Speed (rpm) Output Voltage (V) Speed Proportional Value (Ex: ft/min) Drive Status Output Frequency (Hz) Status of Digital Inputs DC Link Voltage (V) Status of Digital Outputs Motor Torque (%) Status of Relay Outputs Output Power (kW) Analog Inputs Value Hours Powered Up (h) 100 Last Faults with Date and Time Hours Enabled (h) Fault / Alert Messages Keypad with LCD + LED displays Password to protect drive programming LCD display language selection: English, Spanish and Portuguese Fault auto-diagnosis and auto-reset Parameters reset to factory or user default Inverter Self-tuning to motor and load (Vector Modes) Specific unit indication (Ex: l/s, t/h, %, etc.) Slip compensation (V / Hz Mode) Manual and Automatic Torque Boost – I x R (V / Hz Mode) Adjustable V / Hz Curve (V / Hz Mode) Minimum and maximum speed limits Maximum current limit Adjustable motor overload protection Adjustable digital gain and offset for the analog inputs Adjustable digital gain for the analog outputs Standard JOG function JOG + / JOG – Function (momentary speed increase/decrease) COPY Function (Drive Keypad or Keypad Drive) Comparison functions for the digital outputs: N* > Nx; N > Nx; N < Nx ; N = 0; N = N*; Is > Ix ; Is < Ix; T > Tx and T < Tx Where: N = Motor speed; N* = Speed reference; Is = Output Current and T = Motor torque Linear and “S type” ramps / double ramp Control features Independent acceleration and deceleration ramps Multi-speed function (up to 8 preset speeds) Special resources (Hour meter and Wattmeter) Overlapped PID Regulator (for automatic level, flow, pressure, and weight control) Direction of Rotation selection (FWD/REV) Local / Remote Operation selection Flying Start function (restart with a spinning load) Critical Speed Avoidance (Skip Speed) Ride-Through function (operation during momentary power loss) Built-in Modbus RTU (needs the RS-232 or RS-485 interface) NEMA 4 Remote Keypad (LCD display) Remote Keypad cable (3.3, 6.6, 10, 16, 25 and 35 ft) Remote Keypad frame kit Options Expansion Boards with special functions Profibus-DP DeviceNet SUPERDRIVE G2 Kit with RS-232 Serial Interface Communication (Drive - PC) 1.56 Variable Frequency Drives 101 www.pamensky.com SSW 05 Plus - Soft Starter The SSW-05 Plus Micro Soft-Starters, with DSP control (Digital Signal Processor) have been designed to supply excellent performance during starting and stopping of electric motors with an excellent cost effectiveness ratio. The Operator Interface allows easy parameter setting, simplifying the start-up and operation activities. The SSW-05 Plus Micro Soft-Starters are compact, optimizating space in electrical panels. The SSW-05 Plus already incorporates protection for the driven motor. Standard Features Optional Features • • • • • • • • • • • • • • • 208 - 460V, 460-575V 50/60Hz input power supply Duty cycle: 300% rated current during 10 seconds, 4 starts per hour Built-in bypass contacts One digital input for Start/Stop (90 - 250 Vac) One digital input for Fault Reset (90 - 250 Vac) One relay output for Run indication (1 Amp - 250V) One relay output for Full Voltage indication (1 Amp - 250V) RS-232 serial port Adjustable acceleration and deceleration ramps (1 - 20 seconds) Adjustable pedestal voltage (30 - 80% of line voltage) Protective features: Motor overload, over current and locked rotor, SCR overload, phase loss and phase sequence DIN rail or direct mount Ambient: 32ºF (0ºC) to 131ºF (55ºC), 3300ft (1000m) altitude, 90% non-condensing humidity Remote Keypad PC Programming Software Soft Starters 2.1 www.pamensky.com 101 SSW-05 - Part Number Specification SSW05 0010 T 2246 E P -- -- Z 1 2 3 4 5 6 7 8 9 1. Soft-Starter line SSW-05 2. Output Rated Current 3. Power Supply: T = Three-phase 4. Power Supply Voltage: 2246 = 220 ... 460 V 4657 = 460 ... 575 V 5. Language: P = Portuguese E = English G = German S = Spanish 0003 = 3 A 0010 = 10 A 0016 = 16 A 0023 = 23 A 0030 = 30 A 0045 = 45 A 0060 = 60 A 0085 = 85 A * Selection Table for 2 6. Product Version: P = Plus 7. Special Hardware: Blank = Standard (not available) Hx = Optional version x (H1 ... Hn) 8. Special Software: Blank = Standard (not available) Sx = Optional version x (S1 ... Sn) 9. End of Part Number: Z Example: SSW050060T4657PPZ 2.2 Soft Starters 101 www.pamensky.com SSW 05 Plus - Table of Products 230-460V - Three Phase Electrical Data Mechanical Data Maximum Applicable Motor Current (A) HP Kw Voltage 3 10 16 23 30 45 60 85 0.75 3 5 7.5 10 15 20 30 0.55 2.2 3.7 5.5 7.5 11 15 22 230 230 230 230 230 230 230 230 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price 1 1 1 1 1 2 2 2 1.63 1.63 1.63 1.63 1.63 3.68 3.68 3.68 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 7.3 x 3.1 x 6.8 7.3 x 3.1 x 6.8 7.3 x 3.1 x 6.8 SSW050003T2246EPZ SSW050010T2246EPZ SSW050016T2246EPZ SSW050023T2246EPZ SSW050030T2246EPZ SSW050045T2246EPZ SSW050060T2246EPZ SSW050085T2246EPZ $ 581 594 654 705 757 974 1,191 1,432 230-460V - Three Phase Electrical Data Mechanical Data Maximum Applicable Motor Current (A) HP Kw Voltage 3 10 16 23 30 45 60 85 1.5 5 10 15 20 30 40 60 1.1 307 7.5 11 15 22 30 45 460 460 460 460 460 460 460 460 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price 1 1 1 1 1 2 2 2 1.63 1.63 1.63 1.63 1.63 3.68 3.68 3.68 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 7.3 x 3.1 x 6.8 7.3 x 3.1 x 6.8 7.3 x 3.1 x 6.8 SSW050003T2246EPZ SSW050010T2246EPZ SSW050016T2246EPZ SSW050023T2246EPZ SSW050030T2246EPZ SSW050045T2246EPZ SSW050060T2246EPZ SSW050085T2246EPZ $ 581 594 654 705 757 974 1,191 1,432 460-575V - Three Phase Electrical Data Mechanical Data Maximum Applicable Motor Current (A) HP Kw Voltage 3 10 16 23 30 45 60 85 2 7.5 10 20 25 40 50 75 1.5 5.5 7.5 15 18.5 30 37 55 575 575 575 575 575 575 575 575 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price 1 1 1 1 1 2 2 2 1.63 1.63 1.63 1.63 1.63 3.68 3.68 3.68 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 5.1 x 2.3 x 5.7 7.3 x 3.1 x 6.8 7.3 x 3.1 x 6.8 7.3 x 3.1 x 6.8 SSW050003T4657EPZ SSW050010T4657EPZ SSW050016T4657EPZ SSW050023T4657EPZ SSW050030T4657EPZ SSW050045T4657EPZ SSW050060T4657EPZ SSW050085T4657EPZ $ 581 594 654 705 757 974 1,191 1,432 Soft Starters 2.3 www.pamensky.com 101 SSW 05 - Accessories Accessories Keypad and Keypad Cables Description Remote Keypad with LED Display 1m (3.3 ft.) Remote Keypad Cable 2m (6.6 ft.) Remote Keypad Cable 3m (10 ft.) Remote Keypad Cable 5m (15 ft.) Remote Keypad Cable 7.5m (25 ft.) Remote Keypad Cable 10m (33 ft.) Remote Keypad Cable Part Number List Price SSW05HMIRS CAB-RS-1 CAB-RS-2 CAB-RS-3 CAB-RS-5 CAB-RS-7.5 CAB-RS-10 $130 23 31 42 52 62 73 SSW 05 - Technical Data Voltage Power Supply Enclosure Control Starting Duty Cycle Inputs Outputs Communication Safety Functions Resources Ambient Frequency Electronic Supply Injected Plastic Case Method CPU Standard Digital Digital Serial Interface Protections Starting Voltage Programmable Acceleration Ramp Programmable Deceleration Ramp Motor Rated Current and SoftStarter Rated Current Ratio Temperature Humidity Altitude Finishing Installation Conformities / Standards 2.4 Color Fixing Safety Low Voltage EMC 220 - 460 Vac (+10%, -15%) 460 - 575 Vac (+10%, -15%) 50 / 60 Hz Switched mode power supply (90 – 250 Vac ) IP00 Motor Voltage Variation DSP type microprocessor 300% ( 3 x Inom. ) during 10 s, 4 starts per hour 1 input for starting and stopping 1 input for error reset 1 relay output for full voltage indication (By-Pass) 1 relay output for operation indication RS-232C Motor overload Phase sequence Phase loss Locked rotor SCRs overload Overcurrent Internal fault (watchdog) 30 - 80% of the rated voltage 1 – 20 s Off – 20 s 30 - 100% 0 ... 55ºC - standard operation at rated current 0 ... 90% non condensing 0 ... 1000 m (3,300 ft) - standard operation at rated current 1000...4000m - with current derating (1%/ 100 m (328 ft) above 1000m (13.300ft) Ultra mat gray (cover) and ultra mat blue (base) WEG standard Fixing by bolts or assembly on DIN 35 mm rail UL 508 Standard – Industrial Control Equipment / IRAM IEC 60947-4-2 EMC Directive 89 / 336 / EEC - Industrial Environment Soft Starters 101 www.pamensky.com SSW 06 - Soft Starter WEG SSW-06 series soft-starters are microprocessor controlled and designed to start and stop induction motors. Excellent acceleration and deceleration control is achieved with an optimized cost to benefit ratio. Standard Features • • • • • • • • • • • • • • • • • 220 - 575V, 50/60Hz input power supply (-15/+10%) Built-in run rated (AC1) bypass contactor Duty cycle: 300% full load amps for 30 seconds, 10 starts per hour Voltage ramp or current limit start modes Detachable keypad with dual display (LCD and LED) and copy function 90 - 250Vac auxiliary control voltage Single 32 bit RISC processor based control board IP00 protected chassis enclosure Six isolated 24Vdc programmable digital inputs Three programmable relay outputs (2 Amp 250V) One 0 - 10Vdc programmable analog output One 4 - 20mA programmable analog output Motor PTC thermistor input RS-232 serial interface Adjustable acceleration (1-999 seconds) and deceleration ramps (0 - 299 seconds) Adjustable pedestal voltage (25 - 90% of line voltage) Current limitation from 150-500% torque control • • • • • Diagnostic features: Motor overload, over current and phase loss, motor immediate over and under current, SCR over temperature and fault, line phase loss and phase sequence, line over and under voltage Display readings: Motor current, voltage, kW and power factor, line voltage and frequency, four last fault trips, run and power-up timers Ambient: 32ºF (0ºC) to 131ºF (55ºC), 3300 ft (1000m) altitude, 90% non-condensing humidity Braking capabilities: Reverse Braking, Optimal Braking, DC Braking ModBUS ( Built-in) Optional Features • • • • • • • RS-485 serial interface Remote keypad cables and mounting frame PC programming software Profibus Expansion Board DeviceNet Expansion Board Ethernet TCP/IP USB Communication Kit Soft Starters 2.5 www.pamensky.com 101 SSW-06 - Part Number Specification SSW06 0085 T 2223 P O -- -- -- S1 Z 1 2 3 4 5 6 7 8 9 10 11 1. SSW-06 Soft Starter 2. Output Rated Current 3. Power Supply: T = Three-phase 4. Power Supply Voltage: 2257 = 220… 575 V 5769 = 575... 690V 5. Language: P = Portuguese E = English S = Spanish 0010 = 10A 0016 = 16A 0023 = 23A 0030 = 30A 0045 = 45A 0060 = 60A 0085 = 85A 0130 = 130A 0170 = 170A 0205 = 205A 0255 = 255A 0312 = 312A 0365 = 365A 0412 = 412A * Selection Table for 2 6. Product Version: S = Standard O = With options 7. Degree of Protection (IP): blank = Standard (see technical specifications table) 8. HMI - Human Machine Interface: Blank = Standard (with LED + LCD HMI) SI = Without HMI 9. Special Hardware: Blank = Standard H1 = Fan 115V (950A model) H2 = Fan 220V (950A up to 1400A model) 10. Special Software: Blank = Standard S1 = optional with special sofware version 11. End of Part Number: Z Note: 1 - Communication kits are optional 2 - From 950A up to 1400A models the ventilation voltage must be defined (H1 or H2) 3 - 575... 690V are not UL certified 4 - Up to 820A standard built-in bypass 2.6 Soft Starters 0480 = 480A 0604 = 604A 0670 = 670A 0820 = 820A 0950 = 950A 1100 = 1100A 1400 = 1400A 101 www.pamensky.com SSW 06 - Table of Products 230V - Three Phase Electrical Data Mechanical Data Maximum Applicable Motor Current (A) 10 16 23 30 45 60 85 130 170 205 255 312 365 412 480 604 670 820 950 1100 1400 3 Leads 6 Leads Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price 1 1 1 1 2 2 2 2 3 3 4 4 4 5 5 5 6 6 7 8 8 7.3 7.3 7.3 7.3 18.7 18.7 18.7 18.7 40.8 40.8 91.5 91.5 91.5 121 121 121 265 265 236 480 480 IP20 IP20 IP20 IP20 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 10.08 x 5.20 x 7.16 10.08 x 5.20 x 7.16 10.08 x 5.20 x 7.16 10.08 x 5.20 x 7.16 14.57 x 5.20 x 9.61 14.57 x 5.20 x 9.61 14.57 x 5.20 x 9.61 14.57 x 5.20 x 9.61 17.32 x 8.78 x 10.94 17.32 x 8.78 x 10.94 21.65 x 14.57 x 12.24 21.65 x 14.57 x 12.24 21.65 x 14.57 x 12.24 25.59 x 14.57 x 13.66 25.59 x 14.57 x 13.66 25.59 x 14.57 x 13.66 31.30 x 21.26 x 14.05 31.30 x 21.26 x 14.05 33.27 x 22.44 x 13.66 45.16 x 26.97 x 17.01 45.16 x 26.97 x 17.01 SSW060010T2257ESZ SSW060016T2257ESZ SSW060023T2257ESZ SSW060030T2257ESZ SSW060045T2257ESZ SSW060060T2257ESZ SSW060085T2257ESZ SSW060130T2257ESZ SSW060170T2257ESZ SSW060205T2257ESZ SSW060255T2257ESZ SSW060312T2257ESZ SSW060365T2257ESZ SSW060412T2257ESZ SSW060480T2257ESZ SSW060604T2257ESZ SSW060670T2257ESZ SSW060820T2257ESZ SSW060950T2257ESZ SSW061100T2257ESZ SSW061400T2257ESZ $1,559 1,608 1,768 1,915 2,223 2,453 3,008 3,760 4,605 5,791 8,021 8,509 8,643 10,142 12,556 14,005 15,936 18,832 28,491 35,737 45,876 Voltage HP Kw HP Kw 3 5 7.5 10 15 20 30 50 60 75 100 125 150 150 200 250 250 300 350 450 500 2.2 3.7 5.5 7.5 11 15 22 37 45 55 75 90 110 110 150 185 185 225 260 330 370 25 30 50 75 100 125 150 200 250 - 18.5 22 37 55 75 90 110 150 185 - 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 460V - Three Phase Electrical Data Mechanical Data Maximum Applicable Motor Current (A) 10 16 23 30 45 60 85 130 170 205 255 312 365 412 480 604 670 820 950 1100 1400 Notes: 3 Leads Purchasing Data 6 Leads Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price 1 1 1 1 2 2 2 2 3 3 4 4 4 5 5 5 6 6 7 8 8 7.3 7.3 7.3 7.3 18.7 18.7 19 19 41 41 91 91 91 121 121 121 265 265 236 480 480 IP20 IP20 IP20 IP20 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 10.08 x 5.20 x 7.16 10.08 x 5.20 x 7.16 10.08 x 5.20 x 7.16 10.08 x 5.20 x 7.16 14.57 x 5.20 x 9.61 14.57 x 5.20 x 9.61 14.57 x 5.20 x 9.61 14.57 x 5.20 x 9.61 17.32 x 8.78 x 10.94 17.32 x 8.78 x 10.94 21.65 x 14.57 x 12.24 21.65 x 14.57 x 12.24 21.65 x 14.57 x 12.24 25.59 x 14.57 x 13.66 25.59 x 14.57 x 13.66 25.59 x 14.57 x 13.66 31.30 x 21.26 x 14.05 31.30 x 21.26 x 14.05 33.27 x 22.44 x 13.66 45.16 x 26.97 x 17.01 45.16 x 26.97 x 17.01 SSW060010T2257ESZ SSW060016T2257ESZ SSW060023T2257ESZ SSW060030T2257ESZ SSW060045T2257ESZ SSW060060T2257ESZ SSW060085T2257ESZ SSW060130T2257ESZ SSW060170T2257ESZ SSW060205T2257ESZ SSW060255T2257ESZ SSW060312T2257ESZ SSW060365T2257ESZ SSW060412T2257ESZ SSW060480T2257ESZ SSW060604T2257ESZ SSW060670T2257ESZ SSW060820T2257ESZ SSW060950T2257ESZ SSW061100T2257ESZ SSW061400T2257ESZ $1,559 1,608 1,768 1,915 2,223 2,453 3,008 3,760 4,605 5,791 8,021 8,509 8,643 10,142 12,556 14,005 15,936 18,832 28,491 35,737 45,876 Voltage HP Kw HP Kw 5 10 15 20 30 40 60 100 125 150 200 250 300 350 400 500 550 600 700 800 1050 3.7 7.5 11 15 22 30 45 75 90 110 150 185 225 260 300 370 410 450 525 600 775 60 75 100 150 200 250 350 450 500 550 650 800 900 1150 1350 1600 2000 45 55 75 110 150 185 260 330 370 410 485 600 670 820 1000 1175 1475 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460 Purchasing Data 3 Leads - Inline Connection 6 Leads - Inside Delta Connection Soft Starters 2.7 www.pamensky.com 101 SSW 06 - Table of Products 575V - Three Phase Electrical Data Mechanical Data Maximum Applicable Motor Current (A) 10 16 23 30 45 60 85 130 170 205 255 312 365 412 480 604 670 820 950 1100 1400 Notes: 2.8 3 Leads 6 Leads Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price 1 1 1 1 2 2 2 2 3 3 4 4 4 5 5 5 6 6 7 8 8 7.3 7.3 7.3 7.3 18.7 18.7 19 19 41 41 91 91 91 121 121 121 265 265 236 480 480 IP20 IP20 IP20 IP20 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 10.08 x 5.20 x 7.16 10.08 x 5.20 x 7.16 10.08 x 5.20 x 7.16 10.08 x 5.20 x 7.16 14.57 x 5.20 x 9.61 14.57 x 5.20 x 9.61 14.57 x 5.20 x 9.61 14.57 x 5.20 x 9.61 17.32 x 8.78 x 10.94 17.32 x 8.78 x 10.94 21.65 x 14.57 x 12.24 21.65 x 14.57 x 12.24 21.65 x 14.57 x 12.24 25.59 x 14.57 x 13.66 25.59 x 14.57 x 13.66 25.59 x 14.57 x 13.66 31.30 x 21.26 x 14.05 31.30 x 21.26 x 14.05 33.27 x 22.44 x 13.66 45.16 x 26.97 x 17.01 45.16 x 26.97 x 17.01 SSW060010T5257ESZ SSW060016T5257ESZ SSW060023T5257ESZ SSW060030T5257ESZ SSW060045T5257ESZ SSW060060T5257ESZ SSW060085T5257ESZ SSW060130T5257ESZ SSW060170T5257ESZ SSW060205T5257ESZ SSW060255T5257ESZ SSW060312T5257ESZ SSW060365T5257ESZ SSW060412T5257ESZ SSW060480T5257ESZ SSW060604T5257ESZ SSW060670T5257ESZ SSW060820T5257ESZ SSW060950T5257ESZ SSW061100T5257ESZ SSW061400T5257ESZ $1,559 1,608 1,768 1,915 2,223 2,453 3,008 3,760 4,605 5,791 8,021 8,509 8,643 10,142 12,556 14,005 15,936 18,832 28,491 35,737 45,876 Voltage HP Kw HP Kw 7.5 10 20 25 40 50 75 125 150 200 250 300 350 450 500 600 650 750 850 1000 1300 5.5 7.5 15 18.5 30 37 55 90 110 150 185 225 260 330 370 450 485 550 630 750 1000 75 100 150 200 300 350 450 550 650 750 850 1100 1200 1500 1750 2000 2500 55 75 110 150 220 260 330 410 485 550 630 800 900 1200 1290 1475 1850 575 575 575 575 575 575 575 575 575 575 575 575 575 575 575 575 575 575 575 575 575 Purchasing Data 3 Leads - Inline Connection 6 Leads - Inside Delta Connection Soft Starters 101 www.pamensky.com SSW 06 - Accessories Keypad and Keypad Cables Description Local Keypad with LED and LCD Remote Keypad Frame Kit 1m (3.3 ft) Remote Keypad Cable 2m (6.6 ft) Remote Keypad Cable 3m (10 ft) Remote Keypad Cable 5m (16 ft) Remote Keypad Cable 7.5m (25 ft) Remote Keypad Cable (Requires CFW09KMR09) 10m (33 ft) Remote Keypad Cable (Requires CFW09KMR09) Part Number List Price SSW06HMILCD KMR-SSW-06 CFW09HMI091 CFW09HMI092 CFW09HMI093 CFW09HMI095 CFW09HMI097 CFW09HMI0910 $230 31 31 39 50 75 88 108 Part Number List Price KFB PD SSW06 KFB DN SSW06 KRS 485 KFB ENIP SSW06 $1,045 897 183 2,070 Part Number List Price KIT IP20 SSW06 M2 KIT IP20 SSW06 M3 KIT IP20 SSW06 M4/M5 KIT IP20 SSW06 M6 $210 236 254 517 Part Number List Price SSW06 KEIO $758 Communication Description Profibus DP Communication Kit DeviceNet Communication Kit Interface for RS-485 Communication Ethernet/IP Communication Kit IP20 Kits Description SSW06 IP20 Kit - Frame Size 2 SSW06 IP20 Kit - Frame Size 3 SSW06 IP20 Kit - Frame Size 4 & 5 SSW06 IP20 Kit - Frame Size 6 I/O Expansion Description I/Os Expansion Module for SoftPLC applications Soft Starters 2.9 www.pamensky.com 101 SSW 06 - Technical Data Power Control Power Supply Degree of protection Fan Frequency Metallic cabinet Control method CPU Control Types of control Starting Duty cycles (10 starts / hour) Inputs Rated Heavy Digital Relay Outputs Safety Functions/resources 2.10 Analog Protections Standard 220 to 575 Vac -15% to +10%, or 198 to 632 Vac 110 to 230 Vac -15% to +10%, or 94 to 253 Vac Models from 255 to 820 A: 115 Vac (104 to 127) Vac / 230 vac (207 to 253) Vac Model 950 A: 115 Vac (103,5 to 122) Vac / 230 Vac (207 to 243,8) Vac Models from 1100 to 1400 A: 230 vac (207 to 243,8) Vac 50 to 60 Hz (+/- 10%), or 45 to 66 Hz IP00 Motor voltage variation (Three phase induction motor) 32-Bit RISC microcontroller Voltage ramp Current limitation Current limitation ramp Pump control Torque control 1, 2 or 3 points 300% (3 x I nom.) during 30 s for 3-cable connection and during 25 s for 6-cable connection 450% (4,5 x I nom.) during 30 s with 33% rated current reduction; 450 % ( 4,5 x I nom.) during 25 s for 6-cable connection 5 x 24 Vdc isolated programmable inputs 1 x 24 Vdc insolated programmable input for motor PTC 3 programmable outputs 250 Vac / 2 A: (2 x NA) + (1 x NO + NC – Fault) 1 Programmable output (11 bits) 0…10 Vdc 1 programmable output (11 bits) 0...20 mA or 4...20 mA Overvoltage Power supply phase loss Undervoltage Output phase loss (motor) Voltage imbalance Thyristor failure Undercurrent CPU failure (watch dog) Overcurrent Programming error Current imbalance Serial communication error Overload (motor) – i²t Self-check error Thyristors over temperature HMI-SSW06 communication error Motor over temperature / PTC Starting time expired Phase sequence failure Fieldbus communication error External fault Serial communication error Open by-pass contact failure (1) Undervoltage in the electronic board Closed by-pass contact failure (1) Frequency out of range Overcurrent in the by-pass (1) Undercurrent before by-pass closing (1) Removable human-machine interface with double display LED + LCD Programming access password HMI language selection: Portuguese, English, Spanish and German Control type selection: Voltage ramp, current limitation, current Limitation ramp, pump control and torque control Local/ Remote operation selection Self-checking and automatic fault reset Oriented start-up according to the control type Standard or within-the-delta (6 leads) connection All protections and functions available in both types of connection to the motor PUMP CONTROL function (protection against “water hammer” in pumps) COPY function (Soft-starter to HMI or HMI to soft-starter) Built-in by-pass for the models 85 to 820 A Serial interface RS-232 with Modbus RTU protocol. RS-485 optional Insolated input for motor PTC Standard or user parameters reset (Brings back the standard or user values) Special features: Running hours Programmable over and undervoltage and voltage imbalance between phases Programmable over and undercurrent and current imbalance between phases Under and overcurrent before by-pass Programmable immediate overcurrent Programmable time for immediate overcurrent Programmable immediate undercurrent Programmable time for immediate undercurrent Programmable line nominal voltage Fully programmable voltage ramp Programmable current limitation Programmable current ramp Programmable pump control Fully flexible torque control Auto reset of the programmable thermal memory Thermal class protection (motor overload) programmable from class 5 to 45. Soft Starters 101 www.pamensky.com SSW 06 - Technical Data Functions/resources Optional Frame for remote HMI Controls Human-Machine Interface (HMI-SSW06-LCD) Supervision Temperature Enviroment Conditions Humdity Altitude Finishing Painting Standards Color Safety Low voltage EMC UL (USA) / cUL (Canadá) CE (Europe) IRAM (Argentina) C-Tick (Australia) Cable to interconnect the soft-starter with the remote HMI 1, 2, 3 and 5 m Rs-485 communication kit PROFIBUS-DP communication kit Device Net communication kit IP20 protection for the models from 85 up to 820 A Start, stop, reset and parameterization (main functions programming) Increase and decrease parameters and their values Motor current (% Soft-starter In) Motor current (% Motor In) Motor current (A) Line frequency (0…99.9 Hz) Line voltage (0…999 V) Output voltage (0…999 V) Motor torque (% motor I n) Load active power – (kW) Load apparent power – (kVA) Soft-starter status Digital and analog inputs and outputs status Load Cos φ (0.00 – 0.99) Energized hours Enabled hours Last six error codes memory Soft-starter software version 0 to 55ºC (Models from 85 to 820 A) standard operation at rated current 0 to 40ºC (Models from 950 to 1400 A) standard operation at rated current 5...90 %, non-condensing 0... 1000 m: standard operation at rated current 1000... 4000 m; with output current reduction of 1%/100 m, over 1000 m Cover: ultra mat gray Cabinet: ultra mat blue UL 508 Standard – Industrial control equipment (2) EN 60947-4-2 Standard; LVD 73/23/EEC – Low voltage directive EMC directive 89 / 336 / EEC – Industrial environment Underwritters Laboratories Inc. – USA (2) Certified by EPCOS Instituto Argentino de Normalización (2) Australian Communications Authority Notes: (1) Models from 10A to 820A (2) Models from 85A to 1400A approved Soft Starters 2.11 www.pamensky.com 101 SSW 07 - Soft Starter The SSW-07 Soft Starter from WEG was designed for high performance starting and stopping while providing an excellent cost-benefit ratio. The Starter is designed to be easily set-up and makes start up and daily activities simpler. Excellent for applications with heavy loads, the SSW-07 is suitable for Crusher applications as well as conveyors, hammer mills, centrifuges and many others. Standard Features Optional Features • • • • • • • • • • • • • • • • • • • Strong reduction on mechanical stresses over the coupling and transmission devices (gearboxes, pulleys, gears, conveyors, etc.) during the start Eliminates mechanical shock Increases motor and machine mechanical equipment lifetime due to the elimination of mechanical shock Easy operation, setup, maintenance & installation Simple electric installation Operates in environments up to 55ºC (without current reduction for all models) Integral, electronic motor protection Built-in electronic thermal relay Avoids the “Water Hammer” in pump applications Limitation of voltage drop during start Universal voltage (220 to 575 Vac) Switched type power supply with EMC filter for the control electronics (110 to 240 Vac) Voltage monitoring of the electronics to backup l2t values (thermal image) Local Keypad 2.12 RS 485 Serial Interface RS 232 Serial Interface Remote keypad PTC Kit IP20 Kit for M3 Soft Starters 101 www.pamensky.com SSW-07 - Part Number Specification SSW07 0017 T 5 S -- -- -- Z 1 2 3 4 5 6 7 8 9 1. SSW-07 Soft Starter 2. Output Rated Current 3. Power Supply: T = Three-phase 4. Power Supply Voltage: 5 = 220 to 575 V 5. Product Version: S = Standard O = With options 6. Enclosure: blank = Standard (see technical specifications table) IP = IP20 for models from 130 A to 412 A 7. Special Hardware: Blank = Standard 8. Special Software: Blank = Standard 9. End of Part Number: Z 0017 = 17A 0024 = 24A 0030 = 30A 0045 = 45A 0061 = 61A 0085 = 85A 0130 = 130A Soft Starters 0171 = 171A 0200 = 200A 0255 = 255A 0312 = 312A 0365 = 365A 0412 = 412A * Selection Table for 2 2.13 www.pamensky.com 101 SSW 07 - Table of Products 230V - Three Phase Electrical Data Mechanical Data Maximum Applicable Motor Current (A) HP Kw Voltage 17 24 30 45 61 85 130 171 200 255 312 365 412 5 7,5 10 15 20 30 50 60 75 100 125 150 150 3.7 5.5 7.5 11 15 22 37 45 55 75 90 110 110 230 230 230 230 230 230 230 230 230 230 230 230 230 Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price 1 1 1 2 2 2 3 3 3 4 4 4 4 2.90 2.90 2.90 7.28 7.28 7.28 16.80 16.80 16.80 20.32 20.32 20.32 20.32 iP20 iP20 iP20 iP20 iP20 iP20 IP00 IP00 IP00 IP00 IP00 IP00 IP00 6.38 x 3.74 x 6.18 6.38 x 3.74 x 6.18 6.38 x 3.74 x 6.18 8.19 x 5.67 x 7.99 8.19 x 5.67 x 7.99 8.19 x 5.67 x 7.99 10.90 x 8.78 x 8.66 10.90 x 8.78 x 8.66 10.90 x 8.78 x 8.66 13.00 x 8.94 x 9.53 13.00 x 8.94 x 9.53 13.00 x 8.94 x 9.53 13.00 x 8.94 x 9.53 SSW070017T5SZ SSW070024T5SZ SSW070030T5SZ SSW070045T5SZ SSW070061T5SZ SSW070085T5SZ SSW070130T5SZ SSW070171T5SZ SSW070200T5SZ SSW070255T5SH1Z SSW070312T5SH1Z SSW070365T5SH1Z SSW070412T5SH1Z $1,266 1,346 1,386 1,558 1,736 2,070 2,560 3,210 3,778 5,026 5,457 5,671 6,655 460V - Three Phase Electrical Data Mechanical Data Maximum Applicable Motor Current (A) HP Kw Voltage 17 24 30 45 61 85 130 171 200 255 312 365 412 10 15 20 30 40 60 100 125 150 200 250 300 350 7.5 11 15 22 30 45 75 90 110 160 185 220 260 460 460 460 460 460 460 460 460 460 460 460 460 460 Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price 1 1 1 2 2 2 3 3 3 4 4 4 4 2.90 2.90 2.90 7.28 7.28 7.28 16.80 16.80 16.80 20.32 20.32 20.32 20.32 iP20 iP20 iP20 iP20 iP20 iP20 IP00 IP00 IP00 IP00 IP00 IP00 IP00 6.38 x 3.74 x 6.18 6.38 x 3.74 x 6.18 6.38 x 3.74 x 6.18 8.19 x 5.67 x 7.99 8.19 x 5.67 x 7.99 8.19 x 5.67 x 7.99 10.90 x 8.78 x 8.66 10.90 x 8.78 x 8.66 10.90 x 8.78 x 8.66 13.00 x 8.94 x 9.53 13.00 x 8.94 x 9.53 13.00 x 8.94 x 9.53 13.00 x 8.94 x 9.53 SSW070017T5SZ SSW070024T5SZ SSW070030T5SZ SSW070045T5SZ SSW070061T5SZ SSW070085T5SZ SSW070130T5SZ SSW070171T5SZ SSW070200T5SZ SSW070255T5SH1Z SSW070312T5SH1Z SSW070365T5SH1Z SSW070412T5SH1Z $1,266 1,346 1,386 1,558 1,736 2,070 2,560 3,210 3,778 5,026 5,457 5,671 6,655 575V - Three Phase Electrical Data Mechanical Data Maximum Applicable Motor Current (A) HP Kw Voltage 17 24 30 45 61 85 130 171 200 255 312 365 412 15 20 25 40 50 75 125 150 200 250 300 350 400 11 15 18.5 30 37 55 90 110 150 185 220 260 330 575 575 575 575 575 575 575 575 575 575 575 575 575 2.14 Purchasing Data Purchasing Data Frame Weight (lb) Degree of Protection Dimensions (in) HxWxD Part Number List Price 1 1 1 2 2 2 3 3 3 4 4 4 4 2.90 2.90 2.90 7.28 7.28 7.28 16.80 16.80 16.80 20.32 20.32 20.32 20.32 iP20 iP20 iP20 iP20 iP20 iP20 IP00 IP00 IP00 IP00 IP00 IP00 IP00 6.38 x 3.74 x 6.18 6.38 x 3.74 x 6.18 6.38 x 3.74 x 6.18 8.19 x 5.67 x 7.99 8.19 x 5.67 x 7.99 8.19 x 5.67 x 7.99 10.90 x 8.78 x 8.66 10.90 x 8.78 x 8.66 10.90 x 8.78 x 8.66 13.00 x 8.94 x 9.53 13.00 x 8.94 x 9.53 13.00 x 8.94 x 9.53 13.00 x 8.94 x 9.53 SSW070017T5SZ SSW070024T5SZ SSW070030T5SZ SSW070045T5SZ SSW070061T5SZ SSW070085T5SZ SSW070130T5SZ SSW070171T5SZ SSW070200T5SZ SSW070255T5SH1Z SSW070312T5SH1Z SSW070365T5SH1Z SSW070412T5SH1Z $1,266 1,346 1,386 1,558 1,736 2,070 2,560 3,210 3,778 5,026 5,457 5,671 6,655 Soft Starters 101 www.pamensky.com SSW 07 - Accessories Keypad and Keypad Cables Description Local Keypad Remote Keypad Kit 1m (3.3 ft.) Remote Keypad Cable 2m (6.6 ft.) Remote Keypad Cable 3m (10 ft.) Remote Keypad Cable 5m (15 ft.) Remote Keypad Cable 7.5m (25 ft.) Remote Keypad Cable 10m (33 ft.) Remote Keypad Cable Part Number List Price HMI-LOCAL-SSW07/08 HMI-REMOTE-SSW07 CAB-RS-1 CAB-RS-2 CAB-RS-3 CAB-RS-5 CAB-RS-7.5 CAB-RS-10 $160 312 23 31 42 52 62 73 Part Number List Price KRS-232-SSW07/08 KRS-485-SSW07/08 $128 150 Part Number List Price SSW07M2V.K SSW07M3V.K KITPTCSSW07/08 KITIP20SIZE3 KITIP20SIZE4 $70 101 118 60 115 Communication Description RS-232 Communication Kit RS-485 Communication Kit Kits Description Ventilation Kit M2 (Frame Size 2, 45 to 85A) Ventilation Kit M3 (Frame Size 3, 130 to 200A) PTC Kit for motor IP20 Kit for M3 (Frame Size 3, 130 to 200A) IP20 Kit for M4 (Frame Size 4, 255 to 412A) Soft Starters 2.15 www.pamensky.com 101 SSW 07 - Technical Data Power Supply Degree of protection Control Power Control Frequency Injected plastic case Control Method CPU Types of Control Starting Cycle (1) Inputs Outputs Normal Digital Relay Normal 17 - 30A Starting Duty Cycle Normal 45 - 200A With optional ventilation kit 45-200A Protections (Standard) Safety Protections (with Accessory) Functions / Resources Standard Command Additional Functions/Resources Programming Accessory (HMI or Serial communication) Supervision Accessories and Options Finishing Conformities / Standards 2.16 Options Color Safety Low voltage EMC UL (USA) / cUL (Canada) CE (Europe) C-Tick (Australia) 220 to 575 Vac 110 to 240 Vac (-15% to +10%), or 94 to 264 Vac 50 to 60 Hz (+/- 10%), or 45 to 66 Hz IP20 in models from 17 to 85 A IP00 in models from 130 to 200 A (IP20 as option) Motor Voltage Variation DSP type microprocessor (Digital Signal Processor) Voltage ramp Current limit 300% (3 x Inom.) during 30 s, 10 starts per hour ( every 6 minutes) 3 isolated programmable inputs 2 relays with NO contacts, 240Vac, 1A, programmable functions 300% 3 starts 10 starts Overcurrent Locked rotor Overcurrent before By-pass Excess starting time Phase loss Frequency outside tolerance Inverted phase sequence By-pass contact open Overtemperature in power heatsink Undervoltage in control supply Motor overload (class 5 to 30) Undercurrent Programming error Current imbalance Serial communication error Undercurrent before by-pass HMI communication error External fault Overtemperature in motor PTC Voltage ramp (Initial voltage: 30% to 90%) Current limitation (150% to 450% of SSW-07 rated current) Starting time (1 to 40s) Kick Start (Off - 0.2 to 2s) Deceleration ramp ( 0 to 40s) Motor and SSW-07 current relation (50% to 100%) Faults automatic-reset Thermal memory automatic-reset Factory standard reset Soft-starter built-in By-pass On, Off / Reset and Parameterization (function programming) Starting time up to 999s Deceleration time up to 999s Program enabling password Selection for Local / Remote operation COPY function (SSW-07 >>> HMI and HMI >>> SSW-07) Programmable rated voltage Motor current (%Soft-Starter In) Motor current (%motor In) Motor current (A) Current indication in each phase R-S-T Supply network frequency Apparent power supplied to load (kVA) Soft-Starter status Digital input and output status Last 4 faults Soft-Starter Software Version Heatsink temperature Motor thermal protection status Plug-in type local HMI HMI remote Kit 5 and 10m cable for remote HMI interconnection RS-232 communication kit SSW-07 interconnection leads >>> PC Serial (RS-232) 3 and 10m RS-485 communication kit Motor PTC kit Ventilation kit for size 2 (45 to 85 A) Ventilation kit for size 3 (130 to 200 A) IP20 kit for size 3 (130 to 200 A) Lid: Ultra mat gray Cabinet: Ultra mat blue UL 508 Standard- Industrial Control Equipment EN60947-4-2; LVD 2006/95/EC Standard – Low voltage Directive EMC 89/336/EEC Directive – Industrial Environment Underwriters Laboratories Inc. – USA Conformity test conducted by EPCOS Australian Communication Authority Soft Starters 101 www.pamensky.com EDP - Enclosed Drive Panel The Enclosed Drive Panel is an industrial general purpose AC motor control and protection package. It is designed for simple and quick installation and start-up, requiring only input power and output motor connections. The Enclosed Drive Panel is built to complement the ruggedness and reliability of WEG electric motors, providing a complete, simple, and cost effective AC motor control, monitor and protection solution. Standard Features Optional Features • • • • • • • • • • V/Hz and Sensorless Vector Control 230V, 460V or 575V Input Voltage 2 Isolated Analog Inputs 6 Programmable Digital Inputs 3 Programmable Relay Outputs 2 Analog Outputs 150% Overload 1min Line Reactor Load Reactor Panel Control Option • Start/Stop Pushbuttons • Run/Stop/Fault Pilot Lights • Local/Remote Selector Switch Applications Standard Panel Includes • • • • • • Variable Frequency Drive CFW09 Keypad Mounted to Panel Door Through Door Disconnect Control Power Transformer NEMA 12 Ventilated Enclosure Canadian Certification • • • • • • • Pumps Fans Blowers Conveyors Rollout tables Agitators Mixers Wall Mounted 230V: 30 - 50HP: 86 - 130A 460V: 30 - 75HP: 45 - 105A 575V: 30HP: 32A Free Standing 230V: 60 - 75HP: 180 - 240A 460V: 100 - 500HP: 142 - 600A 575V: 40 - 500HP: 44 - 472A Panels 3.1 www.pamensky.com 101 EDP - Table of Products 230V Standard Product Current (A) Optional Features HP* Panel Control Part Number List Price Dimensions Line Reactor Load Reactor CT VT CT VT Part Number List Price Part Number List Price Part Number 86 105 30 40 EDP09.86/230 $18,129 60 x 36 x 16 EDP-PNLCTRL $681 EDP-KDRF24LI $741 EDP-KDRF24LO List Price $741 105 130 40 50 EDP09105/230 $22,048 72 x 36 x 16 EDP-PNLCTRL $681 EDP-KDRF25LI $1,036 EDP-KDRF25LO $1,036 130 150 50 50 EDP09130/230 $23,032 72 x 36 x 16 EDP-PNLCTRL $681 EDP-KDRF26LI $1,194 EDP-KDRF26LO $1,194 142 174 50 60 EDP09142/230 $25,300 72 x 36 x 18 EDP-PNLCTRL $681 EDP-KDRF26LI $1,212 EDP-KDRF26LO $1,212 180 60 EDP09180/230 $30,104 72 x 36 x 18 EDP-PNLCTRL $681 EDP-KDRI22LI $1,390 EDP-KDRI22LO $1,390 240 75 EDP09240/230 $36,985 72 x 36 x 18 EDP-PNLCTRL $681 EDP-KDRI23LI $1,415 EDP-KDRI23LO $1,415 460V Standard Product Current (A) Optional Features HP* Panel Control Part Number List Price CT VT CT VT 45 54 30 40 EDP09.45/460 $14,204 60 70 40 50 EDP09.60/460 $15,959 70 86 50 60 EDP09.70/460 86 105 60 75 105 130 75 100 174 100 142 125 Line Reactor Load Reactor Dimensions Part Number List Price Part Number List Price Part Number List Price 48 x 36 x 16 EDP-PNLCTRL 60 x 36 x 16 EDP-PNLCTRL $681 EDP-KDRD2LI $681 EDP-KDRC1LI $644 EDP-KDRD2LO $644 $697 EDP-KDRC1LO $16,605 60 x 36 x 16 EDP-PNLCTRL $681 $697 EDP-KDRF2LI $792 EDP-KDRF2LO EDP09.86/460 $19,785 72 x 36 x 16 EDP-PNLCTRL $792 $681 EDP-KDRF4LI $810 EDP-KDRF4LO EDP09105/460 $22,499 72 x 36 x 16 EDP-PNLCTRL $810 $681 EDP-KDRF3LI $1,058 EDP-KDRF3LO $1,058 EDP09142/460 $25,270 72 x 36 x 18 EDP-PNLCTRL $681 EDP-KDRH3LI $1,201 EDP-KDRH3LO $1,201 180 150 EDP09180/460 $32,953 72 x 36 x 18 EDP-PNLCTRL $681 EDP-KDRH1LI $1,673 EDP-KDRH1LO $1,673 211 150 EDP09211/460 $36,339 72 x 36 x 18 EDP-PNLCTRL $681 EDP-KDRG3LI $2,084 EDP-KDRG3LO $2,084 240 200 EDP09240/460 $37,187 72 x 36 x 18 EDP-PNLCTRL $681 EDP-KDRG3LI $2,084 EDP-KDRG3LO $2,084 312 250 EDP09312/460 $50,888 72 x 72 x 24 EDP-PNLCTRL $681 EDP-KDRG1LI $2,280 EDP-KDRG1LO $2,280 361 300 EDP09361/460 $52,144 72 x 72 x 24 EDP-PNLCTRL $681 EDP-KDRG2LI $2,328 EDP-KDRG2LO $2,328 450 350 EDP09450/460 $64,021 72 x 72 x 24 EDP-PNLCTRL $681 EDP-KDRJ2LI $2,673 EDP-KDRJ2LO $2,673 515 400 EDP09515/460 $73,451 72 x 72 x 24 EDP-PNLCTRL $681 EDP-KDRJ1LI $2,935 EDP-KDRJ1LO $2,935 600 500 EDP09600/460 $83,399 72 x 72 x 24 EDP-PNLCTRL $681 EDP-KDRL2LI $5,055 EDP-KDRL2LO $5,055 575V Standard Product Current (A) Optional Features HP* Panel Control Part Number List Price CT VT CT VT 32 32 30 30 EDP09.32/575 $13,790 44 53 40 50 EDP09.44/575 $17,278 53 63 50 60 EDP09.53/575 63 79 60 75 79 99 75 107 147 147 211 Line Reactor Load Reactor Dimensions Part Number List Price Part Number List Price Part Number List Price 48 x 36 x 16 EDP-PNLCTRL 72 x 36 x 18 EDP-PNLCTRL $681 EDP-KDRD42LI $681 EDP-KDRC43LI $535 EDP-KDRD42LO $535 $570 EDP-KDRC43LO $19,023 72 x 36 x 18 EDP-PNLCTRL $681 $570 EDP-KDRC44LI $605 EDP-KDRC44LO EDP09.63/575 $20,753 72 x 36 x 18 EDP-PNLCTRL $605 $681 EDP-KDRF46LI $761 EDP-KDRF46LO 100 EDP09.79/575 $23,280 72 x 36 x 18 $761 EDP-PNLCTRL $681 EDP-KDRF47LI $786 EDP-KDRF47LO 100 150 EDP09107/575 $35,071 $786 72 x 72 x 18 EDP-PNLCTRL $681 EDP-KDRF47LI $1,058 EDP-KDRF47LO $1,058 196 150 211 200 200 EDP09147/575 200 EDP09211/575 $42,721 72 x 72 x 18 EDP-PNLCTRL $681 EDP-KDRH44LI $1,433 EDP-KDRH44LO $1,433 $48,646 72 x 72 x 18 EDP-PNLCTRL $681 EDP-KDRI42LI $1,517 EDP-KDRI42LO 247 315 250 300 $1,517 EDP09247/575 $63,850 90 x 72 x 36 EDP-PNLCTRL $681 EDP-KDRG47LI $1,675 EDP-KDRG47LO 315 343 300 $1,675 350 EDP09315/575 $68,011 90 x 72 x 36 EDP-PNLCTRL $681 EDP-KDRG45LI $1,938 EDP-KDRG45LO 343 418 $1,938 350 400 EDP09343/575 $84,040 90 x 72 x 36 EDP-PNLCTRL $681 EDP-KDRJ45LI $2,150 EDP-KDRJ45LO 418 $2,150 472 400 500 EDP09418/575 $89,672 90 x 72 x 36 EDP-PNLCTRL $681 EDP-KDRJ43LI $2,254 EDP-KDRJ43LO 472 $2,254 555 500 600 EDP09472/575 $98,022 90 x 72 x 36 EDP-PNLCTRL $681 EDP-KDRL45LI $2,675 EDP-KDRL45LO $2,675 * Please note that HP reference is for 4 pole motors (1800 RPM). To size the drive correctly please confirm the Current (A). Sizing table is used for approximation only, final sizing subject to review of application/load details. Standard Panel includes drive, fuse disconnect, control transformer, door mounted keypad and filtered fan mounted in a NEMA 12 ventilated enclosure. Panel Control Option Includes Start/Stop Pushbuttons, Run/Stop/Fault Pilot Lights and Local/Remote Selector Switch. 3.2 Panels 101 www.pamensky.com EDP - Sample Wiring Diagram This wiring diagram is reprinted for illustrative purposes only and may be subject to change. Panels 3.3 www.pamensky.com 101 GPH - Combination Soft Starter The GPH Series of WEG Combination Soft Starters is an industrial general purpose AC motor Soft Starter package designed for simple and quick installation and start-up, requiring only input power and output motor connections. The NEMA 4/12 enclosure is ideal for dusty or wet environments. The GPH starters are built to complement the ruggedness and reliability of WEG motors, providing a complete and cost effective AC motor starting and protection solution. Standard Features Applications • • • • • • • • • • • • • • • • • Rated 500% 5 - 250HP at 230V, 10 -500HP at 460V and 15 - 500HP at 575V NEMA 4/12 wall mount enclosure suitable for dusty, wet, or outdoor applications Circuit breaker with door mounted operator provides built-in short circuit protection and input power disconnect Automatic run rated bypass contactor Fused Control Power Transformer (CPT) Start and Stop Pushbuttons and Run and Fault Pilot Lights on the front cover Keypad with protective cover mounted on enclosure door, all parameter changes are through the cover-mounted keypad. Dust and water stay out of the enclosure. Monitoring of current, voltage, kVA and kW can be done from the outside Standard Panel Includes • • • • 3.4 Soft Starter SSW 07 Through Door Disconnect Control Power Transformer NEMA 4/12 Enclosure Panels Pumps Fans Blowers Compressors Conveyors Mixers Crushers Saws 101 www.pamensky.com GPH - Table of Products 230V HP Current (A) Part Number List Price Dimensions 5 17 GPH070017230 7.5 24 GPH070024230 10 30 GPH070030230 15 45 GPH070045230 20 61 GPH070061230 30 85 GPH070085230 50 130 GPH070130230 60 171 GPH070171230 75 200 GPH070200230 100 255 GPH070255230 125 312 GPH070312230 150 365 GPH070365230 150 412 GPH070412230 $5,084 $5,445 $5,478 $5,440 $6,897 $7,182 $9,584 $11,511 $11,997 $13,356 $13,680 $13,841 $17,210 24x24x12 24x24x12 24x24x12 24x24x12 24x24x12 24x24x12 42x30x12 42x30x12 42x30x12 60x36x16 60x36x16 60x36x16 60x36x16 460V HP Current (A) Part Number List Price Dimensions 10 17 GPH070017460 15 24 GPH070024460 20 30 GPH070030460 30 45 GPH070045460 40 61 GPH070061460 60 85 GPH070085460 100 130 GPH070130460 125 171 GPH070171460 150 200 GPH070200460 200 255 GPH070255460 250 312 GPH070312460 300 365 GPH070365460 350 412 GPH070412460 $5,084 $5,445 $5,478 $5,440 $6,897 $7,182 $9,584 $11,511 $11,997 $13,356 $13,680 $13,841 $17,210 24x24x12 24x24x12 24x24x12 24x24x12 24x24x12 24x24x12 42x30x12 42x30x12 42x30x12 60x36x16 60x36x16 60x36x16 60x36x16 575V HP Current (A) Part Number List Price Dimensions 15 17 GPH070017575 20 24 GPH070024575 25 30 GPH070030575 40 45 GPH070045575 50 61 GPH070061575 75 85 GPH070085575 125 130 GPH070130575 150 171 GPH070171575 200 200 GPH070200575 250 255 GPH070255575 300 312 GPH070312575 350 365 GPH070365575 400 412 GPH070412575 $5,084 $5,445 $5,478 $5,440 $6,897 $7,182 $9,584 $11,511 $11,997 $13,356 $13,680 $13,841 $17,210 24x24x12 24x24x12 24x24x12 24x24x12 24x24x12 24x24x12 42x30x12 42x30x12 42x30x12 60x36x16 60x36x16 60x36x16 60x36x16 Panels 3.5 www.pamensky.com 101 GPH - Sample Wiring Diagram Fused Disconnect Motor R U S T V W Door Mounted Keypad Fuse Fuse Fuse Control Transformer 120V Secondary A1 Start DI1 Stop DI2 DI3 Run 13 Fault 24 14/23 A2 3.6 Panels 102 www.pamensky.com PESW - Enclosed Motor Starter WEG offers non-reversing and non-combination NEMA-4X magnetic starter up to 75HP at 460V. Featuring components that meet IEC design standards and UL horsepower ratings, including WEG contactors and overload relays, the PESW magnetic starters are ideal to help protect motors and ensure smooth operation year-after-year. Assembled together in a NEMA 4X enclosure with two options. WEG PESW starters are recommended for all single and three phase applications where across-the-line starters can be applied. Standard Features • • • • • • • • • High horsepower ratings in four compact sizes Bimetallic Overload Relays Adjustable trip current Direct heated bimetallic elements – class 10 Ambient temperature compensated Phase-loss sensitivity protection Selectable Manual or Automatic RESET Electrically isolated NO-NC auxiliary contacts NEMA 4X polymeric enclosure with knockouts Industrial Control Products Start/Stop contacts independent from main contactor and from thermal overload relay Ground and Neutral (supplied as standard) Thermal overload relay reset integrated to the stop button up to 25-30HP - 460V, 25HP - 575V 4.1 www.pamensky.com 102 PESW - Part Number Specification PESW S 1 2 - 105 V24 A X 3 4 5 6 1. PESW Enclosed Starter, Non-Combination, Non-Reversing 2. Number of Phases: 3. CWM (Contactor) Type: 4. RM38 7 S = Single Phase Blank = Three Phase Control Voltage: Code Contactor Part Number Description 9 CWM9 - 10 - 30 Contactor 9 A, 1NO 12 CWM12 - 10 - 30 Contactor 12 A, 1NO 18 CWM18 - 10 - 30 Contactor 18 A, 1NO 25 CWM25 - 11 - 30 Contactor 25 A, 1NO/1NC 32 CWM32 - 11 - 30 Contactor 32 A, 1NO/1NC 40 CWM40 - 11 - 30 Contactor 40 A, 1NO/1NC 50 CWM50 - 11 - 30V Contactor 50 A, 1NO/1NC 65 CWM65 - 11 - 30 Contactor 65 A, 1NO/1NC 80 CWM80 - 11 - 30 Contactor 80 A, 1NO/1NC 95 CWM95 - 11 - 30 Contactor 95 A, 1NO/1NC 105 CWM105 - 11 - 30 Contactor 105 A, 1NO/1NC Code Coil Voltage Coil Part Number Description V18 120 V BCA4 - 25V-18 AC coil contactor 9 -25 A V24 208-240 V BCA4 - 25V-24 AC coil contactor 9 -25 A V47 480 V BCA4 - 25V-47 AC coil contactor 9 -25 A V56 575 V BCA4 - 25V-56 AC coil contactor 9 -25 A V18 120 V BCA4 - 40V-18 AC coil contactor 32 - 40 A V24 208-240 V BCA4 - 40V-24 AC coil contactor 32 - 40 A V47 480 V BCA4 - 40V-47 AC coil contactor 32 - 40 A V56 575 V BCA4 - 40V-56 AC coil contactor 32 - 40 A V18 120 V BCA - 105V-18 AC coil contactor 50 - 105 A V24 208-240 V BCA - 105V-24 AC coil contactor 50 - 105 A V47 480 V BCA - 105V-47 AC coil contactor 50 - 105 A V56 575 V BCA - 105V-56 AC coil contactor 50 - 105 A 5. Pilot Device: A = Start & Stop/Reset Pushbutton E = Reset Pushbutton 6. Enclosure Type: X = NEMA 4X 7. Overload Ampere Range: 4.2 - Single Phase Class 10 Three Phase Class 10 Code Part Number Description Code Part Number Description Code RM26 RW27-1D2-U004 2.8 - 4A R23 RW27-1D3-D012 0.8 - 1.2A R36 RW67-2D3-U040 Part Number Description 25 - 40A RM27 RW27-1D2-D063 4 - 6.3A R24 RW27-1D3-D018 1.2 - 1.8A R37 RW67-1D3-U050 32 - 50A 32 - 50A RM28 RW27-1D2-U008 5.6 - 8A R25 RW27-1D3-D028 1.8 - 2.8A R38 RW67-2D3-U050 RM29 RW27-1D2-U010 7 - 10A R26 RW27-1D3-U004 2.8 - 4.0A R39 RW67-2D3-U057 40 - 57A RM30 RW27-1D2-D125 8 - 12.5A R27 RW27-1D3-D063 4.0 - 6.3A R40 RW67-2D3-U063 50 - 63A RM31 RW27-1D2-U015 10 - 15A R28 RW27-1D3-U008 5.6 - 8.0A R41 RW67-2D3-U070 57 - 70A RM32 RW27-1D2-U017 11 - 17A R29 RW27-1D3-U010 7.0 - 10A R42 RW67-2D3-U080 63 - 80A 63 - 80A RM33 RW27-1D2-U023 15 - 23A R30 RW27-1D3-D125 8.0 - 12.5A R43 RW117-1D3-U080 RM34 RW27-1D2-U032 22 - 32A R31 RW27-1D3-U015 10 - 15A R44 RW117-1D3-U097 75 - 97A RM35 RW67-1D2-U040 25 - 40A R32 RW27-1D3-U017 11 - 17A R45 RW117-1D3-U112 90 - 112A RM36 RW67-2D2-U040 25 - 40A R33 RW27-1D3-U023 15 - 23A RM37 RW67-1D2-U050 32 - 50A R34 RW27-1D3-U032 22 - 32A RM38 RW67-2D2-U050 32 - 50A R35 RW67-1D3-U040 25 - 40A Industrial Control Products 102 www.pamensky.com PESW - Table of Products 115V - Single Phase Electrical Data Mechanical Data Purchasing Data Overload Range (A) Max. Motor (HP) Coil Voltage Frame Degree of Protection Dimensions H x W xD (in) WEG Part Number List Price 7 - 10 10 - 15 11 - 17 15 - 23 25 - 40 25 - 40 40 - 57 0.5 0.75 1 2 3 3 5 120 V 120 V 120 V 120 V 120 V 120 V 120 V 04 04 04 04 06 08 08 NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 8.3 x 4.7 x 5.0 11.0 x 7.1 x 5.6 11.0 x 7.1 x 5.6 PESWS-9V18AX-RM29 PESWS-12V18AX-RM31 PESWS-18V18AX-RM32 PESWS-25V18AX-RM33 PESWS-40V18AX-RM35 PESWS-50V18AX-RM36 PESWS-50V18AX-RM39 $123 135 141 148 289 504 539 208-230V - Single Phase Electrical Data Mechanical Data Purchasing Data Overload Range (A) Max. Motor (HP) Coil Voltage Frame Degree of Protection Dimensions H x W xD (in) WEG Part Number List Price 5.6 - 8 8 - 12.5 10 - 15 11 - 17 15 - 23 25 - 40 32 - 50 1 1.5 2 3 5 7.5 10 230 V 230 V 230 V 230 V 230 V 230 V 230 V 04 04 04 04 04 08 08 NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 11.0 x 7.1 x 5.6 11.0 x 7.1 x 5.6 PESWS-9V24AX-RM28 PESWS-9V24AX-RM30 PESWS-12V24AX-RM31 PESWS-18V24AX-RM32 PESWS-25V24AX-RM33 PESWS-50V24AX-RM36 PESWS-65V24AX-RM38 $123 123 135 141 148 504 539 208-230V - Three Phase Electrical Data Mechanical Data Purchasing Data Overload Range (A) Max. Motor (HP) Coil Voltage Frame Degree of Protection Dimensions H x W xD (in) WEG Part Number List Price 1.8 - 2.8 2.8 - 4 4 - 6.3 5.6 - 8 7 - 10 11 - 17 15 - 23 15 - 23 22 - 32 25 - 40 25 - 40 32 - 50 40 - 57 57 - 70 63 - 80 90 - 112 0.75 1 1.5 2 3 5 7.5 7.5 10 15 15 15 20 25 30 40 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 04 04 04 04 04 04 04 06 06 06 08 08 08 08 10 10 NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 8.3 x 4.7 x 5.0 8.3 x 4.7 x 5.0 8.3 x 4.7 x 5.0 11.0 x 7.1 x 5.6 11.0 x 7.1 x 5.6 11.0 x 7.1 x 5.6 11.0 x 7.1 x 5.6 14.2 x 9.9 x 6.6 14.2 x 9.9 x 6.6 PESW-9V24AX-R25 PESW-9V24AX-R26 PESW-9V24AX-R27 PESW-9V24AX-R28 PESW-9V24AX-R29 PESW-18V24AX-R32 PESW-25V24AX-R33 PESW-32V24AX-R33 PESW-32V24AX-R34 PESW-40V24AX-R35 PESW-50V24AX-R36 PESW-50V24AX-R38 PESW-65V24AX-R39 PESW-80V24AX-R41 PESW-95V24AX-R43 PESW-105V24AX-R45 $139 139 139 139 139 161 169 226 226 340 622 622 637 691 836 871 Industrial Control Products 4.3 www.pamensky.com 102 PESW - Table of Products 460V - Three Phase Electrical Data Mechanical Data Purchasing Data Overload Range (A) Max. Motor (HP) Coil Voltage Frame Degree of Protection Dimensions H x W xD (in) WEG Part Number List Price 1.2 - 1.8 1.8 - 2.8 2.8 - 4 4 - 6.3 5.6 - 8 8 - 12.5 11 - 17 15 - 23 15 - 23 22 - 32 25 - 40 32 - 50 40 - 57 57 - 70 63 - 80 75 - 97 1 1.5 2 3 5 7.5 10 15 15 20 25 30 40 50 60 75 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 04 04 04 04 04 04 04 04 06 06 06 08 08 08 10 10 NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 8.3 x 4.7 x 5.0 8.3 x 4.7 x 5.0 8.3 x 4.7 x 5.0 11.0 x 7.1 x 5.6 11.0 x 7.1 x 5.6 11.0 x 7.1 x 5.6 14.2 x 9.9 x 6.6 14.2 x 9.9 x 6.6 PESW-9V47AX-R24 PESW-9V47AX-R25 PESW-9V47AX-R26 PESW-9V47AX-R27 PESW-9V47AX-R28 PESW-12V47AX-R30 PESW-18V47AX-R32 PESW-25V47AX-R33 PESW-32V47AX-R33 PESW-32V47AX-R34 PESW-40V47AX-R35 PESW-50V47AX-R38 PESW-65V47AX-R39 PESW-80V47AX-R41 PESW-95V47AX-R43 PESW-105V47AX-R44 $139 139 139 139 139 145 161 169 226 226 340 622 637 691 836 871 575V - Three Phase Electrical Data Mechanical Data Purchasing Data Overload Range (A) Max. Motor (HP) Coil Voltage Frame Degree of Protection Dimensions H x W xD (in) WEG Part Number List Price 1.2 - 1.8 1.8 - 2.8 2.8 - 4 4 - 6.3 7 - 10 8 - 12.5 11 - 17 15 - 23 22 - 32 25 - 40 32 - 50 40 - 57 57 - 70 63 - 80 1 1.5 3 5 7.5 10 15 20 25 30 40 50 60 75 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 04 04 04 04 04 04 04 06 06 08 08 08 08 10 NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 7.3 x 4.1 x 4.4 8.3 x 4.7 x 5.0 8.3 x 4.7 x 5.0 11.0 x 7.1 x 5.6 11.0 x 7.1 x 5.6 11.0 x 7.1 x 5.6 11.0 x 7.1 x 5.6 14.2 x 9.9 x 6.6 PESW-9V56AX-R24 PESW-9V56AX-R25 PESW-9V56AX-R26 PESW-9V56AX-R27 PESW-9V56AX-R29 PESW-12V56AX-R30 PESW-18V56AX-R32 PESW-32V56AX-R33 PESW-32V56AX-R34 PESW-50V56AX-R36 PESW-50V56AX-R38 PESW-65V56AX-R39 PESW-80V56AX-R41 PESW-95V56AX-R43 $139 139 139 139 139 145 161 226 226 622 622 637 691 836 4.4 Industrial Control Products 102 www.pamensky.com PESW - Wiring Diagrams Three phase D.O.L. Starter - - - - - / - * - , * % , , % , '5 '5 '5 '5 6 7 8 6 " , 8 " , " . _ 7 . _ Figure 1 " Figure 2 Control circuit with phase to phase coil supply Control circuit with separate coil supply When using 230V, 400V, 500V, and 690V on the Part Number, WEG D.O.L. starters (DLW) will be factory-connected, as per wiring diagrams of figure 1, that is, with phase to phase coil suplly. For the voltages with phase to phase coil supply, contact WEG. When using 24V, 48V, 110V, etc. on the Part Number, WEG D.O.L. starters (DLW) will be factory-connected, as per wiring diagrams of figure 2, that is, with control circuit to be connected through a separate coil supply. Single-phase D.O.L Starter - Pilot Devices - * , % , '5 '5 6 6 " , " . _ Note: When using remote control, disconnect the circuit at the points marked with the “x” in figures 1 and 2 and connect the external devices (Thermostat, pushbutton, etc), as indicated with dotted lines. Industrial Control Products 4.5 www.pamensky.com 102 PESW - Dimensions Provision for cable gland fitting Frame øA B C D E Top Bottom Back Size 04 0.2 7.1 4.4 4.1 7.3 2 x 1/2” 2 x 1/2” ø0.7 Size 06 0.3 8.1 5.0 4.7 8.3 2 x 1/2” and 3/4” 2 x 1/2” and 3/4” ø0.9 Size 08 0.2 10.8 5.6 7.1 11.0 2 x 3/4” and 1” 2 x 3/4” and 1” N/A * Size 10 0.3 14.0 6.6 9.9 14.2 1 x 1” and 1 1/4” 1 x 1” and 1 1/4” N/A * Dimensions in inches. * For wall mounting on starters size 08 and 10, four screws with the following characteristics should be used: • Pan, dome or rounded shaped head; • Starter size 08: • Screws size 1/4 (or M6 – ISO Standard); • Dimensions: diameter thread shall be maximum 1/4 in. and diameter head shall be maximum 15/64 in. • Starter size 10: • Screws size 12 (or M5 – ISO Standard); • Dimensions: diameter thread shall be maximum 0.236 in. and diameter head shall be maximum 0.394 in. 4.6 Industrial Control Products 102 www.pamensky.com Other Starter Options ESW Series NEMA 1 Non-Combination Starters • • • • • High horsepower ratings in three compact sizes NEMA type 1 metallic lift-off enclosure with knockouts Bimetallic ambient compensated overload relays Easy addition of pilot devices for field modification Manual RESET plunger is provided as standard feature on all models Customized Starter Solution V.J. Pamensky Canada Inc. has a Toronto based panel shop to design and build custom solutions for motor control applications. Customized NEMA 4 starters with Emergency Stop, Start-Stop and control options can be built quickly and to fit the demands of different applications. Explosion Proof Manual Motor Starters • • • • • • Suitable for Hazardous Areas: Class I, Groups C & D - Class II, Groups E, F, G Motor Control Circuit Disconnect Short Circuit Protection up to 10 kA @ 600 VAC Thermal Overload Protection Class 10 Control Devices: Start & Stop / Reset Industrial Control Products 4.7 www.pamensky.com 102 CWC Miniature Contactors The CWC Series miniature contactor features more horsepower for its size than any other miniature contactor on the market. The CWC’s compact dimensions for its current rating, up to 25A, AC-3 utilization category, allows it to take up less space inside electrical enclosures while still running motors up to 10HP @ 575V. The dimensions remain the same whether the coil voltage is AC or DC making panel design and assembly easier. DC models feature low consumption coils allowing the CWC to be operated directly from a PLC without interface relays. The following configurations are available “off-the-shelf.” • • • • 3 Pole Normally Open Power Contacts with one built-in Auxiliary Contact (Can be Normally Open or Normally Closed) 3 Pole Normally Open Reversing Contactors rated AC-4 Utilization Category 4 Pole Power Contacts (four Normally Open, or two Normally Open and two Normally Closed) Control Relay An extensive lineup of modular and tool-free accessories makes the CWC Series the most flexible and easy-to-use miniature contactor available today. Features • • • • • • 4.8 Rated up to 10 HP @ 575V Direct mounting to the WEG RW17D overload relay and MPW25 manual motor protector with ECCMP-C0 accessory Frame size remains the same for AC and DC coil contactors Heavy-duty operation Tool-free DIN rail mounting Complete line of snap-on accessories Industrial Control Products 102 www.pamensky.com CWC - Part Number Specification CWC 16 1 2 - 1. CWC Miniature Contactor 2. Frame Rating: Blank: Control Relay (Ith = 10Amps) 07: 7Amps 09: 9Amps 12: 12Amps 16: 16Amps 25: 25Amps 3. Auxiliary Contacts: 00: None 10: 1 NO 01: 1 NC 4. Power Pole: 00: Control Relay (4 auxiliary terminals) 30: CWC0 with 3 NO Power Poles 22: CWC0 with 2 NO + 2 NC Power Poles 40: CWC0 with 4 NO Power Poles 5. Coil Voltage: VAC Coil 10 30 V18 3 4 5 VDC Coil (Standard Consumption) VDC Coil (Low Consumption) Description Code Description Code Description Code 24Vac 60Hz V04 24Vdc C03 24Vdc L03 120Vac 60Hz V18 110Vdc C12 208-240Vac 60Hz V24 480Vac 60Hz V47 600Vac 60Hz V56 Industrial Control Products 4.9 www.pamensky.com 102 CWC Miniature Contactors - Table of Products Three Pole Miniature Contactors with AC Coil Electrical Data Mechanical Data Purchasing Data Maximum Applicable Motor (HP) Auxiliary Contacts Current (A) Single Phase 7 7 9 9 12 12 16 16 25 Three Phase 115V 230V 200V 230V 460V 575V NO NC 1/3 1/3 1/3 1/3 1/2 1/2 1 1 1 1/2 3/4 3/4 1 1 2 2 2 2 3 1 1/2 1 1/2 2 2 3 3 3 3 5 1 1/2 1 1/2 3 3 3 3 5 5 7 1/2 5 5 5 5 7 1/2 7 1/2 10 10 15 5 5 7 1/2 7 1/2 7 1/2 7 1/2 10 10 15 1 0 1 0 1 0 1 0 0 0 1 0 1 0 1 0 1 0 Weight (lb) Part Number List Price 0.43 0.43 0.43 0.43 0.43 0.43 0.43 0.43 0.44 CWC07-10-30* CWC07-01-30* CWC09-10-30* CWC09-01-30* CWC12-10-30* CWC12-01-30* CWC16-10-30* CWC16-01-30* CWC25-00-30* $29 29 31 31 32 32 33 33 42 Replace ‘X’ with code for AC Coil Voltage Code Selection 60 Hz 120V 208-240V CODE V18 V24 50 Hz 110V - Miniature Control Relay with AC Coils Electrical Data Purchasing Data Auxiliary Contacts Current (A) Rating 10 10 10 10 10 A600, Q600 A600, Q600 A600, Q600 A600, Q600 A600, Q600 N.O. N.C. 2 3 1 4 0 2 1 3 0 4 Replace ‘X’ with code for AC Coil Voltage Code Selection 60 Hz 120V 208-240V 480V 600V CODE V18 V24 V47 V56 50 Hz 110V - 400-415V - 4.10 Industrial Control Products Part Number List Price CAW04R422X CAW04R431X CAW04R413X CAW04R440X CAW04R404X $30 30 30 30 30 102 www.pamensky.com CWC Miniature Contactors - Technical Data Part number CWC07 CWC09 Standards CWC012 CWC016 CWC025 CWCA0 IEC/EN 60 947. DIN VDE 0660. UL. CSA Rated insulation voltage Ui IEC/EN 60 947. DIN VDE 0660 690 V 600 V UL. CSA Rated impuse withstand voltage Uimp 4kV Rated operational frequency 25 - 400 Hz Degree of protection Main circuits IP20 IP20 Control circuits and auxiliary contacts Ambient temperature Operating temperature Storage temperature -25oC to +55oC -55oC to +80oC Altitude Normal values 90 % Ie / 80 % Ue 80 % Ie / 75 % Ue to 3000 m 3000 to 4000 m 4000 to 5000 m Overvoltage category / Pollution degree III / 3 Climatic proofing IEC 60 680-2 Pole number of main circuits 3 4 Rated operational voltage Ue 690V 690 V Conv. thermal current Ith at < 55oC rated operational current Ie / AC-1 18 A 20 A 22 A 22 A 32 A 10 A Rated operational current Ie AC-4 (Ue ≤ 440V) 2.8 3.5 4.5 5 9 - 1.5 / 2 3/4 3/4 3.7 / 5 3.7 / 5 3.7 / 5 2.2 / 3 4/5 4.5 / 6 4.5 / 6 4.5 / 6 5.5 / 7.5 3/4 5.5 / 7.5 5.5 / 7.5 5.5 / 7.5 5.5 / 7.5 7.5 / 10 4/5 7.5 / 10 7.5 / 10 7.5 / 10 7.5 / 10 7.5 / 10 5.5 / 7.5 11 / 15 11 / 15 11 / 15 11 / 15 11 / 15 - 2 4 20 20 25 25 35 10 AC-3 Utilization Category Rated operational power 220/230 V kW / hp 380 V kW / hp 400/415 V kW / hp 440 V kW / hp 500 V kW / hp 690 V kW / hp Maximum numbers of auxiliary contacts Short circuit rating max. fuse gL-gG Maximum electrical operations per hour AC-1 AC-3 AC-4 no load 5 (A) Ops/h Ops/h Ops/h Ops/h Mechanical lifespan Ops x 106 Electrical lifespan (AC-3) Ops x 106 2500 300 600 300 2500 3 10 1.4 1.3 10 1.2 1.1 0.6 - Rated operational current Ie AC-15 DC-13 220-230 V A - - - - - 10 380-400 V A - - - - - 6 415 V A - - - - - 5 500 V A - - - - - 4 24 V A - - - - - 6 48 V A - - - - - 4 110 V A - - - - - 2 220 V A - - - - - 0.7 Control circuit reliability Ue min=17 V Ie min= 5 mA - Terminal capacity 1 or 2 x (1...2.5) 1 or 2 x (0.5...2.5) 1 or 2 x (0.5...2.5) 1 or 2 x (2.5...6.0) Tightening torque N.m 1...1.5 Industrial Control Products 1.8 1...1.5 4.11 www.pamensky.com 102 Control circuit CWC Miniature Contactors - Technical Data Part number CWC07 Pick-up Coil consumption CWC09 Sealing Coils rated voltage V 30 0.8 0.8 2...3 4.5...5.8 2...3 0.27 0.27 0.27 8...20 / 6...13 13...16 / 13.5...17 8...20 / 6...13 12-660VAC 12-660VAC / 12-440VDC 12-660VAC / 12-440VDC Coil operational limits Bifrequency coils CWCA0 0.8 VA Closing / Opening (AC) ms CWC025 58 Cos j Operation time CWC016 30 Cos j AC CWC012 VA 0.85...1.1 Pick-up xUs 0.5...0.8 Drop-out xUs 0.2...0.6 Auxiliary contact block BFC Terminal capacity Number of conductors and Cross section (min. and max.) Flexible without cable lug (mm2) 2x (0.5...2.5) Flexible without cable lug (mm2) 2x (0.75...1.5) AWG Cables (12...22) Tightening torque Nm 08...1.5Nm Conventional thermal current (lth) A Rated operational current (Ie) AC - 15 10 6/4(220/240V). 3/2(380/440V). 2(500V) A Rated operational current (Ie) DC - 13 1.5(24V). 0.5(60V). 0.2(220-240V) Timing Relay Rated insulation voltage (Ui ) V 300 24...240 VDC/VAC 50/60 Hz (TEC0) 24...60 VDC/VAC 50/60 Hz (TDC0) Supply voltage (Ue ) 1–2 terminals 100...240 VDC/VAC 50/60 Hz (TDC0) 220-240 VAC 50/60Hz (TETC0) 110-130 VAC 50/60Hz (TETC0) 24-28 VAC 50/60Hz (TETC0) Control Voltage (Uc ) only TDC0 - pg 18 2 – B1 terminals 24...60 VDC/VAC 50/60 Hz (TDC0) 100...240 VDC/VAC 50/60 Hz (TDC0) 0.85...1.1 x Uc (VAC) Voltage operational limits 0.8...1.25 x Uc (VDC) 4.12 Consumption mA ≤5 Minimum time for Reset (Recovery time) ms 650 Minimum control time (only TDC0) ms 50 Setting accuracy (% of the full scale value) % +/-5 Repeat Accuracy % +/-1 Changeover time Y - Δ ms 50 Industrial Control Products 102 www.pamensky.com CWM Standard Contactors The CWM general-purpose contactor line has been designed to take into consideration industrial duty and reliability. Rated for inductive loads up to 800A or 440kW @380/400V, WEG can offer the suitable contactor for your application. CWM contactors allow total panel space optimization, with only a few compact frame sizes from 4 to 440kW @ 400/415V. Reducing inventory is a “snap” with CWM’s common accessories. For example, side-mounted auxiliary contact blocks are the same from 9 to 300A (AC-3) @ 440V. Designed for extended mechanical and electrical life, dependable switching in even the most heavy-duty applications can be achieved. No matter how demanding the application, all WEG contactors are tested and approved to be used under Type 1 and Type 2 short circuit coordination. Ensuring global acceptance, all components conform to UL508 (USA and Canada), IEC60947 and CE. Features • • • • • • • • • • General purpose motor applications Fractional power through 600HP @ 460V Compact frame sizes Panel mountable or 35mm DIN rail up to 75HP @ 460V Built-in auxiliary contacts up to 10HP @ 460V Front and side mountable auxiliary contact blocks IP20 Finger-touch protection Wide coil voltage selection AC or DC AC/DC coils with electronic modules available from 100HP and up Replaceable main contacts for entire line Industrial Control Products 4.13 www.pamensky.com 102 CWM - Part Number Specification CWM 18 1 2 - 1. CWM Contactor CWM: Contactor up to 300A CWME: Contactor 400A and above 2. Frame Rating: 9: 9Amps 12: 12Amps 18: 18Amps 25: 25Amps 32: 32Amps 40: 40Amps 50: 50Amps 65: 65Amps 80: 80Amps 95: 95Amps 3. Auxiliary Contacts: 00: None 10: 1 NO 01: 1 NC 11: 1 NO + 1 NC 22: 2 NO + 2 NC 4. Power Pole: 30: 3 NO Power Poles 20: 2 NO Power Poles 5. Coil Voltage: 4.14 10 30 V18 3 4 5 105: 105Amps 112: 112Amps 150: 150Amps 180: 180Amps 250: 250Amps 300: 300Amps 400: 400Amps 600: 630Amps 800: 800Amps VAC Coil (CWM9 to CWM105) VDC Coil (CWM9 to CWM105) VAC / VDC Coil (CWM112 to CWME800) Description Code Description Code Description Code 24Vac 60Hz V04 24Vdc (CWM9…CWM25) C03 24-28Vac/Vdc (CWM112…CWM300) E02 E10 120Vac 60Hz V18 24-28Vdc (CWM32…CWM105) C34 110-130Vac/Vdc (CWM112…CWM300) 208-240Vac 60Hz V24 110Vdc (CWM9…CWM25) C12 208-250Vac/Vdc (CWM112…CWM300) E13 480Vac 60Hz V47 110-130Vdc (CWM32…CWM105) C40 430-500Vac/Vdc (CWM112…CWM300) E42 600Vac 60Hz V56 100-127Vac/Vdc (CWME630…CWME800) E35 100-240Vac/Vdc (CWME400) E36 200-240Vac/Vdc (CWME630…CWME800) E39 440-575Vac (CWME400…CWME800) D82 Industrial Control Products 102 www.pamensky.com CWM Standard Contactors - Table of Products Three Pole Contactors with AC Coil Electrical Data Mechanical Data Purchasing Data Maximum Applicable Motor (HP) Auxiliary Contacts Current (A) Single Phase 9 9 12 12 18 18 25 25 32 32 40 40 50 50 65 65 80 80 95 95 105 105 150 180 250 300 400 630 800 Three Phase 115V 230V 200V 230V 460V 575V NO NC 1/2 1/2 3/4 3/4 1 1 2 2 3 3 3 3 3 3 5 5 7 1/2 7 1/2 7 1/2 7 1/2 10 10 - 1.5 1.5 2 2 3 3 5 5 5 5 7.5 7.5 10 10 10 10 15 15 15 15 20 20 - 3 3 3 3 5 5 7 1/2 7 1/2 10 10 10 10 15 15 20 20 20 20 25 25 30 30 50 60 75 100 125 150 200 3 3 3 3 5 5 7 1/2 7 1/2 10 10 15 15 15 15 20 20 25 25 30 30 40 40 60 75 100 125 150 200 300 5 5 7 1/2 7 1/2 10 10 15 15 20 20 30 30 40 40 50 50 50 50 60 60 75 75 125 150 200 250 300 400 600 7 1/2 7 1/2 10 10 15 15 15 15 25 25 25 25 40 40 50 50 60 60 75 75 75 75 150 200 250 350 300 400 600 1 0 1 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 2 2 2 2 2 2 2 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 2 2 2 2 2 2 2 Weight (lb) Part Number List Price 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 1.15 1.15 1.19 1.19 2.44 2.44 2.47 2.47 2.49 2.49 3.20 3.20 3.24 3.24 5.60 8.91 13.54 13.54 call call call CWM9-10-30* CWM9-01-30* CWM12-10-30* CWM12-01-30* CWM18-10-30* CWM18-01-30* CWM25-00-30* CWM25-11-30* CWM32-00-30* CWM32-11-30* CWM40-00-30* CWM40-11-30* CWM50-00-30* CWM50-11-30* CWM65-00-30* CWM65-11-30* CWM80-00-30* CWM80-11-30* CWM95-00-30* CWM95-11-30* CWM105-00-30* CWM105-11-30* CWM150L322X CWM180L322X CWM250L322X CWM300L322X CWME400L322X CWME630L322X CWME800L322X $42 42 55 55 60 60 71 71 101 101 143 143 163 163 182 182 233 233 284 284 331 331 658 909 1,321 1,514 2,082 3,158 4,620 Replace ‘X’ with code for AC Coil Voltage Code Selection for Contactors CWM9 to CWM105 60 Hz 24V 48V 120V 208-240V 480V CODE V04 V10 V18 V24 V47 600V V56 50 Hz - 42V 110V - 400-415V 500V Replace ‘X’ with AC/DC Coil voltage code selection for Contactors CWM150, 180, 250, 300 Voltage 110-130Vac/Vdc 208-250Vac/Vdc CODE E10 E13 Mounting on CWM112-300 CWM112-300 Replace ‘X’ with AC/DC Coil voltage code selection for Contactors CWM400, 630, 800 Voltage 100-240Vac/100-220Vdc 100-127Vac/100-110Vdc 200-240Vac/200-220Vdc CODE E36 E35 E39 D82 Mounting on CWME400 CWME630-800 CWME630-800 CWME400-800 Industrial Control Products 440-575Vac 4.15 www.pamensky.com 102 CWM Standard Contactors - Accessories Auxiliary contact blocks for CWM9 to CWME800 • Terminal markings to EN 50 005 and EN 50 012 • Positive driven contacts in accordance with IEC/EN 60947-4-1 resp. IEC/EN60947-5-1 Auxiliary Description Front Mounting Front Mounting Side Mounting Side Mounting Side Mounting Side Mounting, Second Block For Contactor CWM9…105 CWM9…105 CWM9…300 CWM9…300 CWM400…CWM800 CWM400…CWM800 NO NC 1 0 1 2 1 1 0 1 1 0 1 1 Part Number List Price BCXMF10 BCXMF01 BCXML11 BCXML20 BCXML11 CWME800 BCXMRL11 CWME800 $5 5 15 15 44 44 Maximum # of added auxiliary contacts per contactor frame size: Note that side mountable version has 2 aux. contacts per block. CWM9…25 = 4 aux. contacts; CWM32…40 = 6 aux. contacts; CWM50…300E = 8 aux. contacts. Mechanical Interlock Auxiliary Description Side mounted between two contactors Side mounted between two contactors Side mounted between two contactors Bottom mounted between two contactors For Contactor CWM9…105 CWM112…CWM300 CWM400 CWM630…CWM800 NO NC 0 0 0 0 0 0 0 0 Part Number List Price BLIM 9-105 BLIM 112-300 BLIM CWME400 BLIM CWME800 $30 54 44 1424 For CWM9…CWM105 the mechanical interlock can be used to interlock different frame sizes. For CWM112…CWM300, the mechanical interlock has to be used with contactors that have the same mechanical frame size. For BLIM CWME800, a metal mount base is provided with this accessory for an accurate assembling of the contactors. Surge Suppressors Description Limits switching transients from contactor pick-up Limits switching transients from contactor pick-up 4.16 For Contactor Voltage Range Part Number List Price CWM9...40 CWM50...105 130...250V 130...250V CWMBAMRC6 CWMBAMRC9 $23 23 Industrial Control Products 102 www.pamensky.com CWM Standard Contactors - Accessories Individual spare coils Description AC Coil AC Coil AC Coil AC Coil AC Coil AC Coil Dual-Voltage Coils AC/DC (contactors with electronic module) Dual-Voltage Coils AC/DC (contactors with electronic module) Dual-Voltage Coils AC/DC (contactors with electronic module) Dual-Voltage Coils AC/DC (contactors with electronic module) Dual-Voltage Coils AC/DC (contactors with electronic module) CWM9....25. CWMC25 CWM32...40. CWMC32 CWM50...105. CWMC50...65 CWM112 CWM180 CWM250 CWM112...150 CWM180 CWM250...300 CWME400 CWME630...800 Part Number List Price CWMBCA425X CWMBCA440X CWMBCA105X CWMBCA112X CWMBCA180X CWMBCA250X CWMBCE-150X CWMBCE-180X CWMBCE-300X CWMEBCE-400X CWMEBCE-800X $10 16 22 24 44 60 28 44 74 492 600 Replace ‘X’ with code for AC Coil Voltage Code Selection for Contactors CWM9 to CWM105 60 Hz 24V 48V 120V 208-240V 480V CODE V04 V10 V18 V24 V47 600V V56 50 Hz - 42V 110V - 400-415V 500V Replace ‘X’ with AC/DC Coil voltage code selection for Contactors CWM150, 180, 250, 300 Voltage 110-130Vac/Vdc 208-250Vac/Vdc CODE E10 E13 Mounting on CWM112-300 CWM112-300 Replace ‘X’ with AC/DC Coil voltage code selection for Contactors CWM400, 630, 800 Voltage 100-240Vac/100-220Vdc 100-127Vac/100-110Vdc 200-240Vac/200-220Vdc 440-575Vac CODE E36 E35 E39 D82 Mounting on CWME400 CWME630-800 CWME630-800 CWME400-800 Industrial Control Products 4.17 www.pamensky.com 102 CWM Standard Contactors - Technical Data General Ratings - CWM9 to CWM105 Type CWM9 Standards Rated Insulation Voltage Ui Acc. IEC; VDE 0660 Acc. UL; CSA Rated Impulse Voltage Uimp Acc. IEC60947-1 Rated Operating Frequency Degree of Protection Main terminals Coil terminals Auxiliary terminals Ambient Temperature Storage Operating Altitude Up to 1,500m Other altitudes Pollution Degree Climatic Withstand Mounting Vibration Resistance (5 to 200 Hz) Contactor open Contactor closed at Uc Mechanical Endurance AC Coil Electrical Endurance AC-3 Shock Resistance (1/2 sin wave = 11ms) Contactor open Contactor closed at Uc Weight AC Coil Terminal Capacity Fine - Stranded with sleeve Coarse - Stranded / Solid Stranded / Solid (UL / CSA) CWM12 Operating Position 4.18 CWM25 CWM32 [V] [V] CWM40 CWM50 CWM65 CWM80 CWM95 CWM105 1000 600 [kV] 6 8 [Hz] 25…400 Protection against direct contact Acc. VDE 0160 - Part. 100 IP10 IP20 IP20 IP20 -55 to +80oC (-67 to +176oF) -25 to +55oC (-13 to +131oF) Nominal values See graphic on page 94 3 According to IEC 68-2 35mm rail Acc. DIN EN 50 022 [g] [g] Million ops. Million ops. [g] [g] [kg] [lb] Top [mm2] Bottom [mm2] Top [mm2] Bottom [mm2] Top [AWG] Bottom [AWG] 3 6 3 6 lb-in (Nm) 3 6 7.5 8 8 12 8 12 4.5 9 4.5 9 4.5 9 5 7 5 7 10 1.8 1.6 1.2 1.2 1.1 1.3 1.1 1.1 1 8 12 0.30 0.65 8 12 0.30 0.65 7 12 0.52 1.15 7 12 0.54 1.19 6 10 1.11 2.44 6 10 1.12 2.47 6 10 1.13 2.49 Allen Head 6 10 1.45 3.20 6 10 1.47 3.24 2x0.5-2.5 2x0.5-2.5 2x0.5-2.5 2x1-2.5 0.75-16 0.75-16 1-35 1-35 1-35 1.5-50 1.5-50 or 2x2.5-6 or 2x2.5-6 or 2x2.5-6 or 2x2.5-10 1.0-16 1.0-16 2.5-35 2.5-35 2.5-35 4-35 4-35 2x1-2.5 2x1-2.5 2x1-2.5 2x1-2.5 1-16 1-16 1.5-35 1.5-35 1.5-35 2.5-50 2.5-50 or 2x2.5-6 or 2x2.5-6 or 2x2.5-6 or 2x2.5-10 1.5-16 1.5-16 6-35 6-35 6-35 6-35 6-35 2x20-12 2x20-12 2x20-12 2x18-12 18-6 18-6 16-2 16-2 16-2 16-1 16-1 or 2x12-10 or 2x12-10 or 2x12-10 or 2x12-8 16-6 16-6 14-2 14-2 14-2 10-2 10-2 8.9...15 (1...1.7) 8.9...15 (1...1.7) Drive Size Tightening Torque CWM18 Devices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN 60947-1 / 60947-4-1, Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102 1.2 1.3 8 8 12 12 0.30 0.30 0.65 0.65 Cross / Slotted Combination Philips #2 8.9...15 14.2...26.6 (1...1.7) (1.6...3) 22.1...35..4 (2.5...4) 22.1...35..4 35.4...53.1 (2.5...4) (4...6) see next page Industrial Control Products 35.4...53.1 (4...6) 5/32” (4mm.) 35.4...53.1 44.3...57.5 (4...6) (5...6.5) 44.3...57.5 (5...6.5) 102 www.pamensky.com CWM Standard Contactors - Technical Data General Ratings - CWM112 to CWME800 Type CWM112 Standards Rated Insulation Voltage Ui Acc. IEC; VDE 0660 Acc. UL; CSA Rated Impulse Voltage Uimp Acc. IEC60947-1 Rated Operating Frequency Degree of protection Main terminals Coil terminals Auxiliary terminals Ambient Temperature Storage Operating Altitude Up to 1,500m Other altitudes Pollution Degree Climatic withstand Mounting Vibration Resistance (5 to 200 Hz) Contactor open Contactor closed at Uc Mechanical Endurance AC Coil Electrical Endurance AC-3 Shock Resistance (1/2 sin wave = 11ms) Contactor open Contactor closed at Uc Weight AC/DC Coil - CWM_E Series only Terminal Capacity Fine - Stranded with sleeve AWG wires with end sleeve Busbars Tightening Torque CWM150 CWM180 CWM250 CWM300 CWME400 CWME630 CWME800 Devices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN 60947-1 / 60947-4-1, Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102 [V] [V] 1000 600 [kV] [Hz] 8 25…400 Protection against direct contact acc. VDE 0160 - Part. 100 IP00 IP20 IP20 -55 to +80oC (-67 to +176oF) -25 to +55oC (-13 to +131oF) Nominal values See graphic on page __ up to 2000m 3 According to IEC 68-2 Screw to panel [g] [g] Million ops. Million ops. 4 4 10 1.1 1.1 1.0 5 1.0 [g] [g] 1.0 0.5 3 3 [kg] [lb] 2.54 5.60 2.54 5.60 4.04 8.91 6.14 13.54 6.14 13.54 - - - [mm2] 2 x (25-70) 2 x (25-70) 2 x (50-120) 2 x (50-150) 2 x (50-150) 1 x 150 1 x 240 1 x 240 1 x 300 or 2 x 107 2 x (15 x 3) 47.8-53.1 (5.4-6) 1 x 300 or 2 x 107 2 x (20 x 3) 123.9-141.6 (14-16) 1 x 500 1 x 500 or 2 x 300 or 2 x 300 2 x (30 x 5) 2 x (30 x 5) 203.6-230.1 203.6-230.1 (23-26) (23-26) see below Nº2 30×5 Nº2 50×5 Nº2 60×5 [mm] lb-in (Nm) 1 x 300 or 2 x 107 2 x (15 x 3) 47.8-53.1 (5.4-6) 203.6 (23) 504.5 (57) 504.5 (57) Operating Position Operating Position CWM9 to CWM105 CWM112 to CWM800 Industrial Control Products 4.19 www.pamensky.com 102 CWM Standard Contactors - Technical Data Power Contacts - CWM9 to CWM105 Type Standard UL/CSA Ratings Rated Operating Voltage General Purpose Rating Switching Motor Loads Full Voltage - 60Hz 1-phase 115V 230V 115V 230V 3-phase 200V 230V 460V 575V 200V 230V 460V 575V Standard IEC Ratings Rated Operating Voltage Rated Thermal Current Ith Switching Motor Loads AC-2; AC-3; AC-4 - 50Hz 3-phase 220-240V 380-400V 415-440V 500V 660-690V 220-240V 380-400V 415-440V 500V 660-690V Maximum Switching Rate AC-1 AC-3 no load AC-4 200,000 operations <= 690V 50/60Hz 220-230V 380-400V 415-440V 500V 660-690V Maximum Switching Rate Making Capacity Breaking Capacity Ue=400V Ue<=400V Ue=500V Ue=690V Impedance per Pole Power Dissipation per Pole AC-1 AC-3 Short Time Current Icw 1 sec. 5 sec. 10 sec. 30 sec. 1 min. 3 min. Rec. time Short Circuit Coordination Coordination Type “1” gL/gG Coordination Type “2” gL/gG 4.20 CWM9 CWM12 CWM18 CWM25 CWM32 CWM40 CWM50 CWM65 CWM80 CWM95 CWM105 [V] [A] 25 25 32 32 60 600 60 90 110 110 140 140 [A] [A] [HP] [HP] [A] [A] [A] [A] [HP] [HP] [HP] [HP] 9.8 10 1/2 1-1/2 11 9.6 7.6 9 3 3 5 7-1/2 13.8 12 3/4 2 11 9.6 11 11 3 3 7-1/2 10 16 17 1 3 17.5 15.2 14 17 5 5 10 15 24 28 2 5 25 22 21 17 7-1/2 7-1/2 15 15 34 28 3 5 32.2 28 27 27 10 10 20 25 34 28 3 5 32.2 42 40 27 10 15 30 25 56 40 5 7-1/2 48.3 42 52 41 15 15 40 40 56 50 5 10 62.1 54 65 52 20 20 50 50 80 68 7-1/2 15 62.1 68 65 62 20 25 50 60 80 68 7-1/2 15 78.2 80 77 77 25 30 60 75 100 88 10 20 92 104 96 77 30 40 75 75 [V] [A] 25 25 32 45 60 60 90 110 1000 110 140 140 [A] [A] [A] [A] [A] [kW] [kW] [kW] [kW] [kW] 9 9 9 7.5 7 2.2 4 4 5.5 5.5 12 12 12 10.5 9 3 5.5 5.5 7.5 7.5 18 18 18 14 13 4 7.5 7.5 10 10 25 25 25 19 15 7.5 11 11 15 15 32 32 32 24 22 9 15 15 18.5 18.5 40 40 40 32 25 11 18.5 22 25 30 50 50 50 38 34 15 22 25 30 35 65 65 65 55 44 18.5 30 37 40 45 80 80 80 63 48 22 37 45 45 45 95 95 95 79 60 25 45 50 55 55 105 105 105 85 80 30 55 55 65 65 [ops/hr] [ops/hr] [ops/hr] 1,200 1,200 9,000 1,200 1,200 9,000 1,200 1,200 9,000 1,200 1,200 9,000 1,200 1,200 9,000 1,200 1,200 9,000 1,200 1,200 5,000 1,200 1,200 5,000 1,200 1,200 5,000 1,200 600 5,000 1,200 600 5,000 [A] [kW] [HP] [kW] [HP] [kW] [HP] [kW] [HP] [kW] [HP] [ops/hr] [A] 5 1.1 1.5 2.2 3 2.2 3 3 4 3 4 360 450 7 1.5 2 3 4 3.7 5 4 5.4 4.5 6 360 450 8 1.5 2 3.7 5 4.5 6 5.5 7.5 5.5 7.5 360 450 12 3 4 5.5 7.5 5.5 7.5 7.5 10 7.5 10 360 450 16 4 5.4 7.5 10 9.2 12.5 10 13 11 15 360 550 18.5 4.5 6 9.2 12.5 11 15 11 15 12.5 17 200 1000 23 5.5 7.5 11 15 11 15 15 20 15 20 200 1000 30 7.5 10 15 20 15 20 18.5 25 20 27 200 1000 37 9.2 12.5 18.5 25 22 30 22 30 25 33 200 1000 44 11 15 22 30 22 30 25 33 30 40 200 1280 50 12.5 17 22 30 30 40 30 40 33 45 200 1280 690 [A] 250 250 250 450 450 920 920 920 920 1050 1050 [A] [A] [mW] 250 130 2.41 250 130 2.41 250 130 2.35 320 170 1.65 450 205 1.28 920 780 0.95 920 780 0.85 920 780 0.86 920 780 0.86 1050 950 0.76 1050 950 0.76 [W] [W] 1.47 0.19 1.47 0.34 2.46 0.78 3.34 1.03 4.6 1.31 3.42 1.52 6.86 2.12 10.4 3.63 10.4 5.5 14.89 6.86 14.89 8.37 [A] [A] [A] [A] [A] [A] [min.] 455 205 144 85 60 35 10 455 205 144 85 60 35 10 570 254 180 104 74 46 10 630 280 200 115 80 50 10 1010 450 320 185 130 90 10 1265 450 400 230 165 100 10 1580 710 500 290 205 120 10 2530 1130 800 460 325 185 10 2530 1130 800 460 325 185 10 3300 1485 1050 600 430 250 10 3300 1485 1050 600 430 250 10 [A] [A] 50 25 50 35 63 35 63 50 100 63 125 80 200 100 200 125 200 125 250 160 250 200 Industrial Control Products 102 www.pamensky.com CWM Standard Contactors - Technical Data Power Contact - CWM112 to CWME800 Type UL/CSA Applications Rated Operating Voltage General Purpose Rating Switching Motor Loads Full Voltage - 60Hz 1-phase 115V 230V 115V 230V 200V 230V 460V 575V 200V 230V 460V 575V 3-phase Standard IEC Ratings Rated Operating Voltage Rated Thermal Current Ith Switching Motor Loads AC-3 - 60Hz 3-phase 220-240V 380-400V 415-440V 500V 660-690V 220-240V 380-400V 415-440V 500V 660-690V Maximum Switching Rate AC-1 AC-3 no load AC-4 200,000 operations <= 690V 50/60Hz 220-230V 380-400V 415-440V 500V 660-690V Maximum Switching Rate Making Capacity Breaking Capacity CWM112 CWM150 CWM180 CWM250 CWM300 CWME400 CWME630 CWME800 [V] [A] 170 170 200 300 400 450 660 900 [A] [A] [HP] [HP] [A] [A] [A] [A] [HP] [HP] [HP] [HP] 120 130 124 99 40 50 100 100 150 154 156 144 50 60 125 150 177 192 180 192 60 75 150 200 221 248 240 242 75 100 200 250 285 312 302 336 100 125 250 350 359 360 361 289 125 150 300 300 414 480 477 382 150 200 400 400 552 772 200 300 600 600 [V] [A] 180 225 225 350 350 450 660 900 [A] [A] [A] [A] [A] [kW] [kW] [kW] [kW] [kW] 112 112 112 95 82 30 55 55 55 75 150 150 150 130 110 45 75 90 90 110 180 180 180 155 135 55 90 110 110 110 250 250 250 220 185 75 132 150 160 160 300 300 300 265 220 90 160 185 200 200 400 400 400 350 300 110 220 220 220 260 630 630 630 500 420 185 330 370 330 400 800 800 800 720 630 220 450 500 500 560 [ops/hr] [ops/hr] [ops/hr] 600 600 1,000 600 600 1,000 600 600 1,000 600 600 1,000 600 600 1,000 500 500 1,000 500 500 1,000 500 500 1,000 [A] [kW] [HP] [kW] [HP] [kW] [HP] [kW] [HP] [kW] [HP] 50 18.5 25 30 40 37 50 40 54 45 600 55 20 27 33 44 40 54 45 60 50 67 58 22 30 37 50 45 60 50 67 55 75 100 37 50 55 75 63 84 75 100 90 121 130 45 60 75 100 80 107 90 121 100 133 90 125 150 200 185 250 - 110 150 220 300 220 300 - 185 250 330 450 370 500 - - - - 600 1000 [ops/hr] 150 150 150 150 150 [A] 1430 1820 2100 2600 3000 [A] [A] [mW] 1290 1290 0.5 1350 1350 0.5 1400 1400 0.45 2000 2000 0.3 0.3 4000 4000 - 6300 6300 - 8000 8000 - AC-1 AC-3 [W] [W] 16 6.2 25 11.1 21.6 13.8 35 17.9 45.7 25.7 - - - 1 sec. 5 sec. 10 sec. 30 sec. 1 min. 3 min. [A] [A] [A] [A] [A] [A] [min.] 3165 1820 1430 826 584 337 10 3763 2164 1700 980 694 401 10 4649 2673 2100 1212 857 495 10 4427 2546 2000 1155 816 471 10 10 - - - gL/gG gL/gG [A] [A] 315 224 355 250 355 250 500 400 630 500 630 - 800 - 1000 - Ue<=400V Ue=500V Impedance per pole Power Dissipation per Pole Short Time Current Icw Recovery time Short Circuit Coordination Coordination type “1” Coordination type “2” Industrial Control Products 4.21 www.pamensky.com 102 CWM Standard Contactors - Technical Data Built-in Auxiliary Contacts - CWM9 to CWM18 Type CWM9 Rated Insulation Voltage Ui Acc. IEC; VDE 0660 Acc. UL; CSA Rated Operating Voltage Ue Acc. IEC; VDE 0660 Acc. UL; CSA Rated Thermal Current Ith <=55oC Rated Operating Current Ie CWM12 [V] [V] 1000 600 [V] [V] [A] 690 600 20 110-127V 220-240V 380-400V 415-450V 500V 660-690V [A] [A] [A] [A] [A] [A] 10 10 6 5 4 2 A600 24V 48V 110V 220V 440V [A] [A] [A] [A] [A] 6 4 2 0.7 0.7 P600 Ue <= 690V 50/60Hz Ue <= 440Vdc [A] [A] 250 250 Ue <= 400V 50/60Hz Ue <=220Vdc [A] [A] 250 2 [A] [V/mA] Million ops. Million ops. [ms] [MOhm] 10 17/5 1 10 1.5 >10 Acc. IEC 60947-5-1 / AC-15 Acc. UL; CSA Rated Operating Current Ie Acc. IEC 60947-5-1 / DC-13 Acc. UL; CSA Making Capacity Im AC-15 / AC-11 DC-13 / DC-11 Breaking Capacity Ic AC-15 / AC-11 DC-13 / DC-11 Short Circuit Protection with Fuses Acc. IEC 60947-5-1 - gL/gG Minimum Switching Capacity Electrical Endurance Mechanical Endurance Guaranteed Non-Overlap Time Insulation Resistance CWM18 Control Circuit Ratings - AC Coil - CWM9 to CWM105 Type Rated Insulation Voltage Ui Acc. IEC; VDE 0660 Acc. UL; CSA Rated Operating Voltage Ue Acc. IEC; VDE 0660 Acc. UL; CSA Standard Voltages 60Hz Coil Operating limits Monofrequency coils xUc Pick-up xUc Drop-out xUc Reinforced coils xUc Pick-up xUc Drop-out xUc Operating Time Coil energization - N.O. Coil de-energization - N.O. Coil Consumption Monofrequency coils Sealed Inrush Thermal Power Dissipation 60Hz Power Factor Closed Opened 4.22 CWM9 CWM12 CWM18 CWM25 CWM32 CWM40 [V] [V] 1000 600 [V] [V] [V] 690 600 24...600 [V] [V] 0.4...0.76 0.25...0.65 CWM50 CWM65 0.85…1.1 0.5...0.76 0.3...0.65 CWM80 CWM95 CWM105 0.5...0.76 0.25...0.6 [V] [V] 0.4...0.7 0.3...0.6 [ms] [ms] 8...20 6...13 10...19 5...25 [VA] [VA] 5.5...9.3 70 9.5...12.5 115 [W] 2.6 4.3 8.0 Cos phi Cos phi 0.28 0.85 0.34 0.69 0.32 0.54 Industrial Control Products 15...30 9...15 16.8...25 295 16.8...25 295 102 www.pamensky.com CWM Standard Contactors - Technical Data Control Circuit Ratings - DC Coil - CWM9 to CWM105 Type Rated Insulation Voltage Ui Acc. IEC; VDE 0660 Acc. UL; CSA Standard Voltages Coil Operating limits Pick-up xUc Drop-out xUc Operating Time Coil energization - N.O. Coil de-energization - N.O. Coil Consumption Closed Magnetic circuit opened CWM9 CWM12 CWM18 CWM25 CWM32 CWM40 CWM50 CWM65 1000 600 24...240 0.85...1.1 0.45...0.75 0.15...0.45 CWM80 [V] [V] [V] 12...440 [V] [V] 0.4...0.7 0.15...0.4 [ms] [ms] 35...45 7...12 40...55 30...65 50...60 55...60 [W] [W] 3.8...7.5 3.8...7.5 6 240 6.5 340 CWM95 CWM105 24...240 0.7...0.8 0.4...0.6 Electronic Module Control Circuit - CWM112 to CWME800 Type Rated Insulation Voltage Ui Acc. IEC; VDE 0660 Acc. UL; CSA Rated Operating Voltage Ue Acc. IEC; VDE 0660 Acc. UL; CSA Standard Voltages 50Hz; 60Hz; DC Coil Operating limits xUc Pick-up xUc Drop-out xUc Operating Time Coil energization - N.O. Coil de-energization - N.O. Coil Consumption Closed AC Opened AC Closed DC Opened DC Thermal Power Dissipation AC DC CWM112 CWM150 CWM180 CWM250 CWM300 [V] [V] 1000 600 [V] [V] [V] 690 600 24…600 [V] [V] [V] 0.65…1.1 0.70...0.85 0.40...0.60 CWME400 CWME630 CWME800 [ms] [ms] 60…70 13…17 60…70 13…17 60…70 13…17 60…70 13…17 60…70 13…17 64…68 43…47 66…70 45…49 66…70 45…49 [VA] [VA] [VA] [VA] 14.8 213 2.4 166 14.8 213 2.4 166 14.1 214 2.4 154 14.1 229 2.5 171 14.1 229 2.5 171 14 571 14 571 17 1000 17 1000 29 1000 17 1000 [W] [W] 3.9 2.4 3.9 2.4 3.8 2.4 3.7 2.5 3.7 2.5 4.7 5.0 4.9 6.3 5.3 7.8 Industrial Control Products 4.23 www.pamensky.com 102 CWM Standard Contactors - Technical Data Auxiliary Contact Block Ratings Type Rated Insulation Voltage Ui Acc. IEC; VDE 0660 Acc. UL; CSA Rated Operating Voltage Ue Acc. IEC; VDE 0660 Acc. UL; CSA Rated Thermal Current Ith <=55oC Rated Operating Current Ie Acc. IEC 60947-5-1 / AC-15 Acc. UL; CSA Rated Operating Current Ie Acc. IEC 60947-5-1 / DC-13 Acc. UL; CSA Making Capacity Im AC-15 / AC-11 DC-13 / DC-11 Breaking Capacity Ic AC-15 / AC-11 DC-13 / DC-11 Short Circuit Protection with Fuses Acc. IEC 60947-5-1 - gL/gG Minimum Switching Capacity Electrical Endurance Mechanical Endurance Guaranteed Non-Overlap Time Insulation Resistance 4.24 BCXMF BCXML BCXMRL [V] [V] 1000 600 [V] [V] [A] 690 600 10 110-127V 220-240V 380-400V 415-450V 500V 660-690V [A] [A] [A] [A] [A] [A] 6 6 4 3.5 2.5 1.5 A600 24V 48V 110V 220V 440V [A] [A] [A] [A] [A] 4 2 0.7 0.3 0.15 Q600 Ue <= 400V 50/60Hz Ue <= 220Vdc [A] [A] 90 90 Ue <= 400V 50/60Hz Ue <= 220Vdc [A] [A] 60 0.95 [A] [V/mA] Million ops. Million ops. [ms] [MOhm] 10 17/5 1 10 1.5 >10 Industrial Control Products BLIM.02 102 www.pamensky.com RW Thermal Overload Relays RW overload relays are important equipment within the WEG Controls range of products. As usual for WEG products, an extended operational service life is one of the main features you will find in RW overload relays. WEG’s RW Class 10 Thermal Overload Relays are designed to work with, and compliment WEG’s minicontactors and contactors. Effectively, RW overload relays can be mounted directly to WEG minicontactors and contactors, assuring electrical and mechanical operation as an open across-the-line starter. Features Dial FLC Setting The trip-current is set via an infinitely adjustable dial designed for the motor’s full load current. Temperature Compensation Because RW overload relays include a fourth bimetallic strip in addition to the three that are directly heated by the motor current, ambient temperature variations in the range of -20ºC to +60ºC are no obstacle for accurate protection of your motors under even the toughest conditions. Phase Failure Sensitivity WEG overload relays include phase failure sensitivity protection as standard. This feature ensures fast tripping in case of phase loss, protecting your motor and avoiding expensive repairs or corrective maintenance services. Multi Function Button The programmable RESET button can be selected to operate in a Manual or Automatic mode, with or without TEST capabilities of the isolated “trip” NC and “alarm” NO auxiliary contacts. The multifunction RESET / TEST button can be set in four different positions; H (manual RESET only), HAND (manual RESET/TEST), AUTO (automatic RESET/ TEST) and A (automatic RESET only). In HAND and AUTO positions, when RESET button is pushed, both NO (97-98) and NC (95-96) contacts change states. Industrial Control Products 4.25 www.pamensky.com 102 RW - Part Number Specification RW 27-1D 3 1 2 3 1. RW Thermal Overload Relay 2. Frame Size and Terminal Type: 17-1D: to use with CWC07…016 17-2D: to use with CWC025 27-1D: to use with CWM9…25 67-1D: to use with CWM32…40 67-2D: to use with CWM50…80 117-1D: to use with CWM95…105 117-2D: to use with CWM112…150 317-1D: to use with CWM112…300 407-1D: to use with CWME400…800 3. Power Pole: 3: 3 NO Power Poles 2: 2 NO Power Poles 4. Overload Setting Current: 4.26 RW17 RW27 - D004 4 RW67 RW117 RW317 RW407 Description Code Description Code Description Code Description Code Description Code Description Code 0.28 ... 0.40A D004 0.28 ... 0.40A D004 25 ... 40A U040 63 … 80A U080 100 … 150A U150 400 … 600A U600 11 … 32A U032 11 … 32A U032 63 … 80A U080 90 ... 112A U112 275 ... 420A U420 560 ... 840A U840 Industrial Control Products 102 www.pamensky.com RW Thermal Overload Relays - Table of Products Three Pole Contactors with AC Coil Electrical Data Purchasing Data Setting Range (A) List Price Max. Max. Fuse (A) Part Number Min. 0.28 0.40 0.56 0.80 1.20 1.80 2.80 4.00 5.60 7.00 8.00 10.0 11.0 15.0 22.0 0.28 0.40 0.56 0.80 1.20 1.80 2.80 4.00 5.60 7.00 8.00 10.0 11.0 15.0 22.0 25.0 32.0 25.0 32.0 40.0 50.0 57.0 63.0 63.0 75.0 90.0 75.0 90.0 100 140 200 275 400 560 0.40 0.63 0.80 1.20 1.80 2.80 4.00 6.30 8.00 10.0 12.5 15.0 17.0 23.0 32.0 0.40 0.63 0.80 1.20 1.80 2.80 4.00 6.30 8.00 10.0 12.5 15.0 17.0 23.0 32.0 40.0 50.0 40.0 50.0 57.0 63.0 70.0 80.0 80.0 97.0 112 97 112 150 215 310 420 600 840 15 15 15 15 15 15 15 25 30 40 50 60 60 90 100 15 15 15 15 15 15 15 25 30 40 50 60 60 90 90 90 125 90 125 150 150 175 175 200 225 250 225 250 300 350 500 700 1000 1250 RW17-1D3-D004 RW17-1D3-C063 RW17-1D3-D008 RW17-1D3-D012 RW17-1D3-D018 RW17-1D3-D028 RW17-1D3-U004 RW17-1D3-D063 RW17-1D3-U008 RW17-1D3-U010 RW17-1D3-D125 RW17-1D3-U015 RW17-1D3-U017 RW17-2D3-U023 RW17-2D3-U032 RW27-1D3-D004 RW27-1D3-C063 RW27-1D3-D008 RW27-1D3-D012 RW27-1D3-D018 RW27-1D3-D028 RW27-1D3-U004 RW27-1D3-D063 RW27-1D3-U008 RW27-1D3-U010 RW27-1D3-D125 RW27-1D3-U015 RW27-1D3-U017 RW27-1D3-U023 RW27-1D3-U032 RW67-1D3-U040 RW67-1D3-U050 RW67-2D3-U040 RW67-2D3-U050 RW67-2D3-U057 RW67-2D3-U063 RW67-2D3-U070 RW67-2D3-U080 RW117-1D3-U080 RW117-1D3-U097 RW117-1D3-U112 RW117-2D3-U097 RW117-2D3-U112 RW317-1D3-U150 RW317-1D3-U215 RW317-1D3-U310 RW317-1D3-U420 RW407-1D3-U600 RW407-1D3-U840 $44 44 44 44 44 44 44 44 44 44 44 44 44 45 45 48 48 48 48 48 48 48 48 54 54 54 54 54 54 54 92 100 100 100 100 152 152 152 152 152 152 154 154 215 215 269 269 632 692 For Contactor CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC07…CWC016 & CWCA0 (Mini-Contactor) CWC025 (Mini-Contactor) CWC025 (Mini-Contactor) CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM9...CWM40 CWM32...CWM40 CWM32...CWM40 CWM50...CWM80 CWM50...CWM80 CWM50...CWM80 CWM50...CWM80 CWM50...CWM80 CWM50...CWM80 CWM95...CWM105 CWM95...CWM105 CWM95...CWM105 CWM112E...CWM150E CWM112E...CWM150E CWM112E…CWM300E CWM112E…CWM300E CWM112E…CWM300E CWME400...CWME800 CWME400...CWME800 CWME400...CWME800 RW Thermal Overload Relays - Accessories Mounting Brackets Description Enables overload to be mounted directly to a panel via screws or DIN rail Enables overload to be mounted directly to a panel via screws or DIN rail Enables overload to be mounted directly to a panel via screws or DIN rail Enables overload to be mounted directly to a panel via screws or DIN rail RW27-1D RW67-1D RW67-2D RW117-1D Industrial Control Products Part Number List Price BF27D BF67.1D BF67.2D BF117D $14 24 24 30 4.27 www.pamensky.com 102 RW Thermal Overload Relays - Technical Data General Ratings Type Standards Number of poles Tripping Class Phase failure sensitivity Temperature Compensation Multi function button R Rated Insulation Voltage Ui acc. IEC 60947-4-1 acc. UL; CSA Rated Operation Voltage Ue acc. IEC 60947-4-1 acc. UL; CSA Rated Impulse Voltage Uimp Current direct alternating Degree of protection Temperature Compensation Storage Operating Pollution Degree Mounting Power Dissipation per pole Weight Dimensions height width lenght Shock Resistance IEC 60 068 part 2-27 Front auxiliary contact Rated auxiliary contacts 24V 60V 125V AC (AC-14/15), 230V 400V 500V 690V DC (DC-13/14), 24V 60V 110V 220V Rated thermal current Short Circuit protection Fuses type D or NH RW17D RW27D RW67D RW117D RW317D Devices according to International Standards, IEC 60947-4-1 and Underwriters Laboratories, UL 3 10 Yes Yes Yes [V] [V] 690 [V] [V] 690 1000 600 1000 600 kV 6 Hz W Kgs. Lbs. 0.15 0.33 up to 3 mm mm mm 45 79.5 92 yes up to 400 Hz Protection against direct contact acc. VDE 0160 - Part 100 - IP20 -20 to +60oC (-4 to 140oF) -50 to +80oC (-58 to 176oF) -20 to +70oC (-4 to 158oF) 3 Direct on contactor or separately with the accessory up to 5.5 0.147 0.31 0.52 0.323 0.683 1.15 79.5 45 92 73 50 106 100 75 99 g/ms 8/10 1 NO + 1 NC A A A A A A A A A A A A 4 3.5 3 2 1.5 0.5 0.3 1 0.5 0.25 0.1 6 gL/gG 6 no 50/60 Hz 2.3 5.06 155 115 166 Terminal Capacity Type Terminal Description Fine - Stranded with Sleeve Coarse - Stranded / Solid Slide Bars max. Tightening Torque Stranded / Solid (UL / CSA) Tightening Torque 4.28 (mm2) (mm2) (mm2) Nm AWG - min and max. Lb-in RW17D RW27D 1.5 - 10 1.5 - 6.0 1.4 - 2.3 14 - 6 20 Cross / Slotted Combination 1.5 - 10 1.5 - 6.0 1.4 - 2.3 14 - 6 20 Industrial Control Products RW67D RW117D RW317D 6.0 - 35 6.0 - 35 4.0 - 6.0 18 - 2 20 Allen Head 6.0 - 35 25 - 35 4.0 - 6.0 8 – 1/0 40 Slide bar 2x(25x5) 14 - 26 8 – 1/0 40 102 www.pamensky.com RW Thermal Overload Relays - Technical Data Operating Positions RW17D, RW27D, RW67D, RW117D, RW317D, RW407D Mounting without contactor The relays can be mounted at any position. RW27D, RW67D, RW117D, RW317D, RW407D Mounting without contactor The mounting position showed in the left-hand figure is equivalent to 0° - not requiring a correction factor on the dial of the relay. The assembly can work with mounting variations of 0° to 180°. However, the mounting with the relay above the contactor, position between 135° and 225°, requires a correction factor of +10% on the dial of the relay. Laterally, as shown in the right-hand figure, the inclination can not exceed ±30° for perfect functioning of the contactor. RW17D with CWC07 As shown in the left-hand figure, the inclination can not exceed ±30° for perfect functioning of the contactor. Laterally, as shown in the right-hand figure, the mounting position is equivalent to 0° - not requiring a correction factor on the dial of the relay. The assembly can work with mounting variations of 0° to 180°. Industrial Control Products 4.29 www.pamensky.com 102 MPW Manual Motor Protector WEG Manual Motor Protectors are the state-of-the-art products available for the worldwide market. With the latest technology and design, you’ll find how easy is to save panel space and to face almost any application in motor control. Built in a very compact frame size, WEG’s Manual Motor Protectors combine, motor control, disconnect means short-circuit and motor overload protections in just one component. These devices include pushbutton operators or a three-position rotary ON-TRIP-OFF handle, which can be padlocked in the OFF position. WEG Manual Motor Protectors are designed for DIN rail mounting, while lugs for direct panel mounting are also available as an accessory. Features • • • • • • • • • • • • • • • • • • High short-circuit interrupting rating – up to 50kA @ 480V Current limiting short-circuit protection Thermal overload protection Class 10 Phase loss sensitivity protection Ambient temperature compensation -4ºF +140ºF (-20ºC +60ºC) Lockable rotary handle mechanism for disconnect Visual indication of ON-TRIP-OFF status 35mm DIN-rail mounting Snap-in accessories Finger safe protected terminals Rated for DC applications Test trip feature Coordination type 2 per IEC60947-4-1 and UL508E, with WEG’s CWM contactors Manual Motor Starters Group motor installations (per NEC Article 430) Multi-motor starter applications Suitable for motor disconnect applications UL Type-E self protected combination starter 4.30 Industrial Control Products 102 www.pamensky.com MPW - Part Number Specification MPW 25 1 2 - 1. MPW Manual Motor Protector 2. Frame Size: 25: to use with CWC07…025 & CWM9…40 65: to use with CWM32…80 100: to use with CWM95…105 3. Power Pole: 3: 3 NO Power Poles 4. Overload Setting Current: 3 - 3 MPW25 U016 4 MPW65 MPW100 Description Code Description Code Description Code 0.10 ... 0.16A C016 10 … 16A U016 55 … 75A U075 25 … 32A U032 50 ... 65A U065 80 ... 100A U100 Industrial Control Products 4.31 www.pamensky.com 102 MPW Manual Motor Protector - Table of Products Manual Motor Protector MPW25 Electrical Data Purchasing Data Maximum UL Horsepower Single Phase Thermal Setting Three Phase Short-Circuit interruption capacity 115V 230V 200V 230V 460V 575V [A] 480V 600V 1/8 1/4 1/2 1 1 1/2 2 - 1/10 1/6 1/3 3/4 1 1/2 3 3 3 5 1/4 1/2 3/4 1 1/2 3 5 5 7 1/2 10 1/3 1/2 1 1 1/2 3 5 7 1/2 7 1/2 10 3/4 1 1/2 2 3 5 10 15 15 20 1 1 1/2 3 5 7 1/2 15 15 20 25 1.0 - 1.6 1.6 - 2.5 2.5 - 4.0 4.0 - 6.3 6.3 - 10 10 - 16 16 - 20 20 - 25 25 - 32 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 42kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA Part Number List Price MPW25-3-D016 MPW25-3-D025 MPW25-3-U004 MPW25-3-D063 MPW25-3-U010 MPW25-3-U016 MPW25-3-U020 MPW25-3-U025 MPW25-3-U032 $100 100 100 100 110 110 124 146 158 Manual Motor Protector MPW65 Electrical Data Purchasing Data Maximum UL Horsepower Single Phase Thermal Setting Three Phase Short-Circuit interruption capacity 115V 230V 200V 230V 460V 575V [A] 480V 600V 3 5 7 1/2 10 10 15 20 15 15 20 25 30 50 30 40 60 32 ... 40 40 ... 50 50 ... 65 35kA 35kA 35kA 10kA 10kA 10kA Part Number List Price MPW65-3-U040 MPW65-3-U050 MPW65-3-U065 $300 300 300 Manual Motor Protector MPW100 Electrical Data Purchasing Data Maximum UL Horsepower Single Phase Thermal Setting Three Phase Short-Circuit interruption capacity 115V 230V 200V 230V 460V 575V [A] 480V 600V 5 7 1/2 10 15 20 20 20 25 30 25 30 30 50 60 75 60 75 100 55 ... 75 70 ... 90 80 ... 100 50kA 50kA 50kA 10kA 10kA 10kA 4.32 Industrial Control Products Part Number List Price MPW100-3-U075 MPW100-3-U090 MPW100-3-U100 $500 534 534 102 www.pamensky.com MPW Manual Motor Protector - Accessories Auxiliary Contact Blocks Description 1NO&1NC auxiliary contact block front mounting - 250Vmax. 1NO&1NC auxiliary contact block left side mounting - 600Vmax. 2NO Auxiliary contact block left side mounting - 600Vmax. 2NC Auxiliary contact block left side mounting - 600Vmax. 1NO&1NC auxiliary contact block front mounting - 250Vmax. 1NO&1NC auxiliary contact block left side mounting - 600Vmax. 2NO Auxiliary contact block left side mounting - 600Vmax. 2NC Auxiliary contact block left side mounting - 600Vmax. For Protector Part Number List Price MPW25 & MPW65 MPW25 & MPW65 MPW25 & MPW65 MPW25 & MPW65 MPW100 MPW100 MPW100 MPW100 ACBF-11 ACBS-11 ACBS-20 ACBS-02 ACBF-11 MPW100 ACBS-11 MPW100 ACBS-20 MPW100 ACBS-02 MPW100 $14 14 14 14 28 40 40 40 For Protector Part Number List Price MPW25 LST25 $31 MPW25 & MPW65 TSB-22 33 MPW65 MPW100 MPW100 LST65 IB MPW100 TSB-11 MPW100 68 15 40 For Protector Part Number List Price MPW25 ECCMP-07 $11 MPW25 ECCMP-25 11 For Protector Part Number List Price MPW25 MPW25 MPW25 MPW25 MPW25 MPW25 MPW25 MPW25 MPW25 FTBBS BBS45-2 BBS45-3 BBS45-4 BBS45-5 BBS54-2 BBS54-3 BBS54-4 BBS54-5 $23 24 28 36 38 28 32 38 39 Accessories for Combination Type-E Construction Description Line power terminal Trip Signaling and Alarm Contact Block (1NO&1NC for Short-circuit and 1NO&1NC for Overload) Line power terminal Insulators Trip Signaling and Alarm Contact Block (1NO&1NC for Short-circuit and Overload) Link Modules Description Mechanical and electrical link module for CWC07 to CWC016 miniature contactor series Mechanical and electrical link module for CWM9…CWM25 contactor series Accessories for Group Motor Installation Description Income power terminal for bus bar system Bus bar system 45mm (for 2 MPW without side mounting auxiliary contacts) Bus bar system 45mm (for 3 MPW without side mounting auxiliary contacts) Bus bar system 45mm (for 4 MPW without side mounting auxiliary contacts) Bus bar system 45mm (for 5 MPW without side mounting auxiliary contacts) Bus bar system 54mm (for 2 MPW with side mounting auxiliary contacts) Bus bar system 54mm (for 3 MPW with side mounting auxiliary contacts) Bus bar system 54mm (for 4 MPW with side mounting auxiliary contacts) Bus bar system 54mm (for 5 MPW with side mounting auxiliary contacts) Industrial Control Products 4.33 www.pamensky.com 102 MPW Manual Motor Protector - Accessories Through-the-door Rotary Mechanisms NEMA 1 Description Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 130mm shaft Rotary NEMA 1 Through the Door Mechanism - yellow/red handle with 130mm shaft Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 330mm shaft Rotary NEMA 1 Through the Door Mechanism - yellow/red handle with 330mm shaft Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 130mm shaft Rotary NEMA 1 Through the Door Mechanism - yellow/red handle with 130mm shaft Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 330mm shaft Rotary NEMA 1 Through the Door Mechanism - yellow/red handle with 330mm shaft Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 115 mm shaft Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 315mm shaft For Protector Part Number List Price MPW25 MPW25 MPW25 MPW25 MPW65 MPW65 MPW65 MPW65 MPW100 MPW100 RMMP-130 RMMP-130-E RMMP-330 RMMP-330-E RMMP65-130 RMMP65-130-E RMMP65-330 RMMP65-330-E MR MPW100-115 MR MPW100-315 $58 58 69 69 58 58 69 69 80 80 For Protector Part Number List Price MPW25 MPW25 MPW25 MPW25 MPW65 MPW65 MPW65 MPW65 MPW100 MPW100 MRX-130 MRX-130-E MRX-330 MRX-330-E MRX65-130 MRX65-130-E MRX65-330 MRX65-330-E MRX100-130 MRX100-130E 62 62 72 72 63 63 72 72 86 86 Through-the-door Rotary Mechanisms NEMA 4X Description Rotary NEMA 4X Through the Door Mechanism - gray/black handle with 130mm shaft Rotary NEMA 4X Through the Door Mechanism - yellow/red handle with 130mm shaft Rotary NEMA 4X Through the Door Mechanism - gray/black handle with 330mm shaft Rotary NEMA 4X Through the Door Mechanism - yellow/red handle with 330mm shaft Rotary NEMA 4X Through the Door Mechanism - black/red handle with 130mm shaft Rotary NEMA 4X Through the Door Mechanism - yellow/red handle with 130mm shaft Rotary NEMA 4X Through the Door Mechanism - black/red handle with 330mm shaft Rotary NEMA 4X Through the Door Mechanism - yellow/red handle with 330mm shaft Rotary NEMA 4X Through the Door Mechanism - gray/black handle with 130mm shaft Rotary NEMA 4X Through the Door Mechanism - yellow/red handle with 130mm shaft 4.34 Industrial Control Products 102 www.pamensky.com MPW Manual Motor Protector - Technical Data General Ratings Part Number Maximum Rated Current Imax(Iu) Number of poles Instantaneous short-circuit Rated operational voltage Ue Rated operational frequency 2) Insulation Voltage Ui Rated impulse withstand voltage Uimp IEC 60 947-2 (Circuit breaker) Utilization category IEC 60 947-4-1 (Motor starter) Tripping Test Overload Protection Phase failure sensitivity Tripping indication Tripping Class Maximum operation per hour Operations/hour Altitude (m) Degree of protection Mechanical life span Number of operations Electrical life span Number of operations Ambient temperatures allowed Transport and storage Operation 3) Temperature compensation Resistance to Impact (g) Standards IEC/EN 60 947-1. DIN VDE 0660 (part 100) IEC/EN 60 947-2. DIN VDE 0660 (part 101) IEC/EN 60 947-4-1. DIN VDE 0660 (part 102) Terminal capacity Type of terminal N.m Tightening torque lb.in Type of screws Dimensions Width (mm) Height (mm) Depth (mm) MPW25 32A 3 13 x Iemax. 690V 1) 50/60Hz 690V 6kV A AC-3 Yes Yes Yes Yes 10 15 2000 IP20 100,000 100,000 MPW65 65A 3 13 x Iemax. 690V 50/60Hz 690V 6kV A AC-3 Yes Yes Yes Yes 10 15 2000 IP20 50,000 25,000 MPW100 100A 3 13 x Iemax. 690V 50/60Hz 1000V 8kV A AC-3 Yes Yes Yes Yes 10 25 2000 IP20 50,000 25,000 -50...+80ºC -20...+70ºC -20...+60ºC 15 -50...+80ºC -20...+70ºC -20...+60ºC 15 -50...+80ºC -20...+60ºC -20...+60ºC 25 Yes Yes Yes Yes Yes Yes Yes Yes Yes Flat 2...2.5 18...22 Philips (Nº2) Box 4...6 35...55 Allen (4mm) Box 4...6 35...53 Allen (4mm) 45 97 98 54 125 157 70 165 171 Altitude Correction Factor Altitude (above sea level) - h Rated operational voltage Ue Current correction factor Iu h ≤ 2000 m 690 V 1 x Iu 2000 < h ≤ 3000 m 550 V 0,96 x Iu 3000 < h ≤ 4000 m 480 V 0,93 x Iu 4000 < h ≤ 5000 m 420 V 0,90 x Iu The MPW motor protective circuit breakers do not undergo any change to their specified performance when applied at an altitude of up to 2000 meters above sea level. However, as the altitude increases, the atmospheric properties vary in terms of dielectric rigidness and pressure. Therefore, current and voltage correction factors must be applied for altitudes exceeding 2000 meters, as shown in the table on the left: Notes: 1) 500V with plastic box; 2) On request: 0 to 400Hz 3) Reduce current for temperatures exceeding +60°C (87% to 70°C) Industrial Control Products 4.35 www.pamensky.com 102 MPW Manual Motor Protector - Technical Data Auxiliary Contact Block - ACB - MPW25 & MPW65 Part Number ACBF-11 ACBS-11. ACBS-20. ACBS-02. TSB For use with MPW16/16i. MPW25/25i/25t. MPW65/65i Utilization Category 24 VAC 220-230 VAC 24 VAC 230 VAC 400 VAC AC-15 2A 0.5 A 6A 6A 3A 1A AC-12 2.5 A 2.5 A 10 A 10 A 10 A 10 A DC-13 690 VAC 24 VDC 48 VDC 60 VDC 24 VDC 110 VDC 220 VDC 440 VDC 1A 0.3 A 0.15 A 2A 0.5 A 0.25 A 0.1 A Type of terminal Flat Type of screw Philips (Nº2) Tightening torque 0.8…1.2 N.m (7…10 lb.in) Rigid cable 1 or 2 x (0.5...1.5 mm2). 1 or 2 x (0.75…2.5 mm2). 2 x (18…14 AWG) Flexible cable Backup fuses gL/gG 10 A Auxiliary Contact Block - ACB - MPW100 Part Number ACBF-11 MPW100 ACBS-11/ACBS-20/ACBS-02/TSB AT-11 MPW100 For use with MPW100 Utilization Category AC-15 DC-13 240 VAC 24 VAC 3A 6A 4A 24 VDC 220VDC 2A 0.25 A 24 VDC 220VDC 1A 0.1 A Type of screw Philips (Nº2) Tightening torque 0.8…1.2 N.m (7…10 lb.in) 1 (0.5…2.5mm2 / 20…14 AWG) Rigid cable Flexible cable 240 VAC 1 or 2 x (0.5…2.5mm2 / 20…14 AWG) 1(0.5...4mm2 / 20...10 AWG) or 2(0.75...2.5mm2 / 18...14 AWG) Back-up fuses gL/gG 16 A Undervoltage Release - URMP Part Number For use with URMP URMP V_ _ MPW100 MPW16/16i. MPW25/25i/25t. MPW65/65i MPW100 Operating voltage (Enables cir. breaker switch ON) Non-operating voltage (guarantees circuit breaker switch OFF) 0.85...1.1xUs 0.7...0.35xUs Energization Consumption 20.2 VA / 13 W Consumption 7.2 VA / 2.4 W 8.5 VA / 6 W 3 VA / 1.2 W Max. opening time 20 ms Type of terminal Flat Type of screws Philips (Nº2) Tightening torque Rigid cable Flexible cable 0.8…1.2 N.m (7…10 lb.in) 1 or 2 x (0.5...2.5 mm2 / 20...14 AWG) 1 or 2 x (0.5...1.5 mm2). 1 or 2 x (0.75…2.5 mm2). 2 x (18…14 AWG) Back-up fuses gL/gG 1 (0.5...4 mm2 / 20...10 AWG) or 2 x (0.75...2.5 mm2 / 18...14 AWG) 10 A Shunt Release - SRMP Part Number For use with SRMP SRMP-K_ _ MPW100 MPW16/16i. MPW25/25i/25t. MPW65/65i MPW100 Operating Voltage (guarantee circuit breaker switch OFF) Consumption - Energization Maximum opening time 0.7...1.1xUs 20.2 VA / 13 W 8.5 VA / 6 W 20 ms Type of terminal Flat Type of screw Tightening torque Rigid cable Flexible cable Back-up fuses gL/gG 4.36 Philips (Nº2) 0.8…1.2 N.m (7…10 lb.in) 1 ou 2 x (0.5...2.5 mm2 / 20...14 AWG) 1 or 2 x (0.5...1.5 mm2). 1 or 2 x (0.75…2.5 mm2) 2 x (18…14 AWG) 1 (0.5...4 mm2 / 20...10 AWG) or 2 x (0.75...2.5 mm2 / 18...14 AWG) 10 A Industrial Control Products 102 www.pamensky.com Pushbuttons and Pilot Lights WEG has used its leading-edge technology & development capability to design the CSW series of pushbuttons, pilot lights, selector switches and accessories. These user friendly and durable Ø22mm pilot devices are used in many industrial applications and environments. Besides the brightness, the BIDL blocks have many other valuable characteristics, such as: • Long life expectancy • Great performance on shock and vibration applications • Extremely low power consumption and thermal dissipation • High luminosity and color definition (independant of the lens) Fast and easy assembling system The Mounting of the contact blocks to the operator (pushbutton, selector switch or indicator) is done via a snap on flange which ensures a fast tight fit. This system can also be removed quickly, without tools. Each block can be mounted or removed individually: to assemble, just snap the components together and a common screwdriver is all that is necessary for disassembly. The ergonomic design of the new locking ring allows hand tightening, without the need for a screwdriver. Contact blocks – safety and reliability High efficiency self-cleaning contact blocks; Pure Silver Contacts (Ag100), ensures maximum reliability in every condition even at low energy levels (5mA/12V). NC Contacts with “Positive Break” system, ensures circuit interruption. Industrial Control Products 4.37 www.pamensky.com 102 Pushbuttons and Pilot Lights - Table of Products Flush 4.38 Color White Part Number CSW-BF0 List Price $6.80 Red CSW-BF1 6.80 Green CSW-BF2 6.80 Yellow CSW-BF3 6.80 Blue CSW-BF4 6.80 Black CSW-BF5 6.80 Double Color N/A Part Number CSW-BD List Price $14.30 Illuminated Flush Color White Part Number CSW-BFI0 List Price $11.40 Red CSW-BFI1 11.40 Green CSW-BFI2 11.40 Yellow CSW-BFI3 11.40 Blue CSW-BFI4 11.40 Emergency Stop - Twist Release Color Red Part Number CSW-BEG List Price $15.10 Pilot Lights Color White Part Number CSW-SD0 List Price $10.10 Red CSW-SD1 10.10 Green CSW-SD2 10.10 Yellow CSW-SD3 10.10 Blue CSW-SD4 10.10 Industrial Control Products 102 www.pamensky.com Pushbuttons and Pilot Lights - Table of Products KNOB with KEY(1) LEVER ILLUMINATED substitute # for colour code (see right) Part Number List Price Colour Code Clear/White 0 Red 1 Green 2 Yellow 3 Blue 4 POSITION DIAGRAM Part Number List Price Part Number List Price Part Number List Price CSW-CK2F45 $16 CSW-CA2F45 $17 CSW-CY2F45 $45 CSW-CK2R45 18 CSW-CA2R45 19 CSW-CK2F90 16 CSW-CA2F90 17 CSW-CK2R90 18 CSW-CA2R90 19 CSW-CK3F45 16 CSW-CA3F45 17 CSW-CK3R45 18 CSW-CA3R45 19 3 CSW-CK3RE45 18 CSW-CA3RE45 19 3 CSW-CK3RD45 18 CSW-CA3RD45 19 3 1 1 CSW-CKI2F90* 2 $10 2 CSW-CY3F45 45 CSW-CKI3F45* 3 10 (1) Key is released in any position Substitute CY for CYD for key release on the right only Substitute CY for CYE for key release on the left only Substitute CY for CYC for key release in the center only DIAGRAM 1 DIAGRAM 2 Contact Status Handle Position 2 3 Contact Status Handle Position Contact Status Handle Position 1 DIAGRAM 3 2 2 3 3 1 1 0 0 I - I I II II Contacts in rest position Contacts actuated Mounting position for the LED or lamp blocks only Industrial Control Products 4.39 www.pamensky.com 102 Pushbuttons and Pilot Lights - Assembled Units Pushbuttons Description Stop pushbutton, 1NC, red Start pushbutton, 1NO, green pushbutton, 1NO, black Emergency stop pushbutton w/1NC twist release Double pushbutton Start/Stop 1NO/1NC Parts CSW-BF1, CSW-BC01 CSW-BF2, CSW-BC10 CSW-BF5, CSW-BC10 CSW-BEG-01, CSW-BC01 CSW-BD, CSW-BC11 Part Number CSW-BF1-01 CSW-BF2-10 CSW-BF5-10 CSW-BEG-01 CSW-BD-11 List Price $12.70 12.70 12.70 22.00 26.00 Parts CSW-CK2F45, CSW-BC10 CSW-CK3F45, CSW-BC20 Part Number CSW-CK2F45-10 CSW-CK3F45-20 List Price $23.00 29.00 Parts CSW-SD1, BIDL110-130VAC1 CSW-SD2, BIDL110-130VAC2 Part Number CSW-SD1-D61 CSW-SD2-D61 List Price $30.00 30.00 Parts CSW-BFI1, CSW-BC01, BIDL110-130VAC1 CSW-BFI2, CSW-BC10, BIDL110-130VAC2 Part Number CSW-BFI1-01 CSW-BFI2-10 List Price $37.00 37.00 Selector Switches Description 2 position selector switch with 1 NO 3 position selector switch with 2 NO Pilot Lights Description Pilot light colour red, with LED 110 V Pilot light colour green, with LED 110 V Illuminated Pushbutton Description Illuminated pushbutton LED red, 1 NC, 110 V Illuminated pushbutton LED green, 1 NO, 110 V 4.40 Industrial Control Products 102 www.pamensky.com Pushbuttons and Pilot Lights - Accessories Single Contact Block Double Contact Block 1NC 1NO-1NC Part Number: CSW-BC01 Part Number: CSW-BC11 1NO 2NO Part Number: CSW-BC10 Part Number: CSW-BC20 List Price: $5.10 List Price: $9.20 Push-on / Push-off Block Part Number: CSW-BR Full Voltage AC/DC Lamp Block Part Number: CSW-BR - Device for flush, extended and mushroom pushbuttons List Price: $8.50 List Price: $8.50 Note: Use only with single contact blocks. 1NO-contacts must be CSW-BCA10 (early make) type. Note: For BA9S lamps 380V / 2W max. LED Block Part Numbers: 24Vac/Vdc: BIDL24VAC/VDC# Colour Code Clear/White 0 Red 1 Green 2 Yellow 3 Blue 4 110-130Vac: BIDL110-130VAC# 220-240Vac: BIDL220-240VAC# List Price: $17.60 Note: Replace # with desired colour code (see right) Industrial Control Products 4.41 www.pamensky.com 102 Pushbuttons and Pilot Lights - Technical Data Standards Rated insulation voltage Degree of protection Degree of protection - Terminals UL ratings Electrical ratings Conventional thermal current Utilization category AC-15 Utilization category DC-13 UL / CSA ratings Contacts resistance Short circuit protection Electrical shock protection Rated impulse voltage Terminal capacity Temperature range Shock resitance Vibration resistance IEC/EN 6068-2-6 Mechanical endurance Pushbuttons Selector Switches Emergency-Stop Maximum number of contacts Pushbuttons (BF) 4.42 IEC/EN 60947-5-1, VDE 0660, NFC63140, UL 508, UL 50, CENELEC EN50007 660 Vac / Vdc IP66 (IEC/EN 60529) IP2X (IEC/EN 60529) Type 1, 2, 3, 3R, 35, 4, 4X, 5, 12, 12K e 13 Ith = 10A (IEC 947-5-1) (V) 24 48 60 110 230 400 500 600 (V) 24 48 60 110 230 400 600 (A) 10 10 10 6 3 2 1.5 1.2 (A) 2.5 1.4 1 0.55 0.27 0.2 0.1 AC / Heavy Duty (A600) DC / Standard Duty (Q600) ≤ 25mΩ (IEC/EN 60255) 16A gL/gG fuse or MPW25-10 Class II 2.5 kV (IEC 947-5-1) 1 or 2 x (0.5 - 2.5mm2) / 1 or 2 x 14-20AWG -25ºC to 70ºC (-13ºF to 158ºF) No damage or disassembling at 100g for all devices according to MIL 202 Bmethod 202A ≤ ½ sinusoid 11ms 16g with frequency range from 40 to 500Hz and max shifting 0.75mm (peak-to-peak) 3 x 106 1 x 106 3 x 105 AF3 Flange AF5 Flange Max. 6 Max 10 Industrial Control Products 101 www.pamensky.com Variable Frequency Drive Sizing Guide CFW 08 Plus Motor HP 1 1.5 2 3 5 7.5 10 15 20 Notes: CFW-08 Plus Variable Frequency Drive Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 143T 143T 145T 182T 143T 145T 182T 184T 145T 145T 184T 213T W182T W182T 213T 215T 184T 184T 215T 254T 213T 213T 254T 256T 215T 215T 256T 284T 254T 254T 284T 286T 256T 256T 286T 324T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V CFW080040B2024EON1A1 CFW080040B2024EON1A1 CFW080040B2024EON1A1 CFW080040B2024EON1A1 CFW080073B2024EON1A1 CFW080073B2024EON1A1 CFW080073B2024EON1A1 CFW080073B2024EON1A1 CFW080073B2024EON1A1 CFW080073B2024EON1A1 CFW080073B2024EON1A1 CFW080073B2024EON1A1 CFW080100B2024EON1A1 CFW080100B2024EON1A1 CFW080100B2024EON1A1 CFW080100B2024EON1A1 CFW080160T2024EON1A1 CFW080160T2024EON1A1 CFW080160T2024EON1A1 CFW080160T2024EON1A1 CFW080220T2024EON1A1 CFW080220T2024EON1A1 CFW080220T2024EON1A1 CFW080220T2024EON1A1 CFW080280T2024EON1A1 CFW080280T2024EON1A1 CFW080280T2024EON1A1 CFW080280T2024EON1A1 CFW080026T3848EON1A1 CFW080026T3848EON1A1 CFW080026T3848EON1A1 CFW080026T3848EON1A1 CFW080040T3848EON1A1 CFW080040T3848EON1A1 CFW080040T3848EON1A1 CFW080040T3848EON1A1 CFW080043T3848EON1A1 CFW080043T3848EON1A1 CFW080043T3848EON1A1 CFW080043T3848EON1A1 CFW080065T3848EON1A1 CFW080065T3848EON1A1 CFW080065T3848EON1A1 CFW080065T3848EON1A1 CFW080100T3848EON1A1 CFW080100T3848EON1A1 CFW080100T3848EON1A1 CFW080100T3848EON1A1 CFW080130T3848EON1A1 CFW080130T3848EON1A1 CFW080130T3848EON1A1 CFW080130T3848EON1A1 CFW080160T3848EON1A1 CFW080160T3848EON1A1 CFW080160T3848EON1A1 CFW080160T3848EON1A1 CFW080240T3848EON1A1 CFW080240T3848EON1A1 CFW080240T3848EON1A1 CFW080240T3848EON1A1 CFW080300T3848EON1A1 CFW080300T3848EON1A1 CFW080300T3848EON1A1 CFW080300T3848EON1A1 CFW080017T5060EON1A1 CFW080017T5060EON1A1 CFW080017T5060EON1A1 CFW080017T5060EON1A1 CFW080030T5060EON1A1 CFW080030T5060EON1A1 CFW080030T5060EON1A1 CFW080030T5060EON1A1 CFW080030T5060EON1A1 CFW080030T5060EON1A1 CFW080030T5060EON1A1 CFW080030T5060EON1A1 CFW080042T5060EON1A1 CFW080042T5060EON1A1 CFW080042T5060EON1A1 CFW080042T5060EON1A1 CFW080070T5060EON1A1 CFW080070T5060EON1A1 CFW080070T5060EON1A1 CFW080070T5060EON1A1 CFW080100T5060EON1A1 CFW080100T5060EON1A1 CFW080100T5060EON1A1 CFW080100T5060EON1A1 CFW080120T5060EON1A1 CFW080120T5060EON1A1 CFW080120T5060EON1A1 CFW080120T5060EON1A1 This chart is designed as a guide only. For specific sizing please contact V.J. Pamensky Canada Inc. Reference 5.1 www.pamensky.com 101 Variable Frequency Drive Sizing Guide CFW 09 Motor HP 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 5.2 CFW-09 Variable Frequency Drive Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 143T 143T 145T 182T 143T 145T 182T 184T 145T 145T 184T 213T W182T W182T 213T 215T 184T 184T 215T 254T 213T 213T 254T 256T 215T 215T 256T 284T 254T 254T 284T 286T 256T 256T 286T 324T 284TS 284T 324T 326T 286TS 286T 326T 364/5T 324TS 324T 364/5T 364/5T 326TS 326T 364/5T 404/5T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V CFW090006T2223ESZ CFW090006T2223ESZ CFW090006T2223ESZ CFW090006T2223ESZ CFW090006T2223ESZ CFW090006T2223ESZ CFW090006T2223ESZ CFW090006T2223ESZ CFW090007T2223ESZ CFW090007T2223ESZ CFW090007T2223ESZ CFW090007T2223ESZ CFW090010T2223ESZ CFW090010T2223ESZ CFW090010T2223ESZ CFW090010T2223ESZ CFW090016T2223ESZ CFW090016T2223ESZ CFW090016T2223ESZ CFW090016T2223ESZ CFW090024T2223ESZ CFW090024T2223ESZ CFW090024T2223ESZ CFW090024T2223ESZ CFW090028T2223ESZ CFW090028T2223ESZ CFW090028T2223ESZ CFW090028T2223ESZ CFW090045T2223ESZ CFW090045T2223ESZ CFW090045T2223ESZ CFW090045T2223ESZ CFW090054T2223ESZ CFW090054T2223ESZ CFW090054T2223ESZ CFW090054T2223ESZ CFW090070T2223ESZ CFW090070T2223ESZ CFW090070T2223ESZ CFW090070T2223ESZ CFW090086T2223ESZ CFW090086T2223ESZ CFW090086T2223ESZ CFW090086T2223ESZ CFW090105T2223ESZ CFW090105T2223ESZ CFW090105T2223ESZ CFW090105T2223ESZ CFW090130T2223ESZ CFW090130T2223ESZ CFW090130T2223ESZ CFW090130T2223ESZ CFW090003T3848ESZ CFW090003T3848ESZ CFW090003T3848ESZ CFW090003T3848ESZ CFW090003T3848ESZ CFW090003T3848ESZ CFW090003T3848ESZ CFW090003T3848ESZ CFW090004T3848ESZ CFW090004T3848ESZ CFW090004T3848ESZ CFW090004T3848ESZ CFW090005T3848ESZ CFW090005T3848ESZ CFW090005T3848ESZ CFW090005T3848ESZ CFW090009T3848ESZ CFW090009T3848ESZ CFW090009T3848ESZ CFW090009T3848ESZ CFW090013T3848ESZ CFW090013T3848ESZ CFW090013T3848ESZ CFW090013T3848ESZ CFW090016T3848ESZ CFW090016T3848ESZ CFW090016T3848ESZ CFW090016T3848ESZ CFW090024T3848ESZ CFW090024T3848ESZ CFW090024T3848ESZ CFW090024T3848ESZ CFW090030T3848ESZ CFW090030T3848ESZ CFW090030T3848ESZ CFW090030T3848ESZ CFW090038T3848ESZ CFW090038T3848ESZ CFW090038T3848ESZ CFW090038T3848ESZ CFW090045T3848ESZ CFW090045T3848ESZ CFW090045T3848ESZ CFW090045T3848ESZ CFW090060T3848ESZ CFW090060T3848ESZ CFW090060T3848ESZ CFW090060T3848ESZ CFW090070T3848ESZ CFW090070T3848ESZ CFW090070T3848ESZ CFW090070T3848ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090002T5060ESZ CFW090004T5060ESZ CFW090004T5060ESZ CFW090004T5060ESZ CFW090004T5060ESZ CFW090007T5060ESZ CFW090007T5060ESZ CFW090007T5060ESZ CFW090007T5060ESZ CFW090010T5060ESZ CFW090010T5060ESZ CFW090010T5060ESZ CFW090010T5060ESZ CFW090012T5060ESZ CFW090012T5060ESZ CFW090012T5060ESZ CFW090012T5060ESZ CFW090014T5060ESZ CFW090014T5060ESZ CFW090014T5060ESZ CFW090014T5060ESZ CFW090022T5060ESZ CFW090022T5060ESZ CFW090022T5060ESZ CFW090022T5060ESZ CFW090027T5060ESZ CFW090027T5060ESZ CFW090027T5060ESZ CFW090027T5060ESZ CFW090032T5060ESZ CFW090032T5060ESZ CFW090032T5060ESZ CFW090032T5060ESZ CFW090044T5060ESZ CFW090044T5060ESZ CFW090044T5060ESZ CFW090044T5060ESZ CFW090053T5060ESZ CFW090053T5060ESZ CFW090053T5060ESZ CFW090053T5060ESZ Reference 101 www.pamensky.com Variable Frequency Drive Sizing Guide CFW 09 Motor HP 60 75 100 125 150 200 250 300 Notes: CFW-09 Variable Frequency Drive Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 364/5TS 364/5T 404/5T 404/5T 364/5TS 364/5T 404/5T 444/5T 404/5TS 404/5T 444/5T 444/5T 444/5TS 444/5T 444/5T 504/5T 445TS 445T 447T 504/5T 447TS 447T 447T 449T 447TS 447T 586/7T 586/7T 586/7TS 586/7T 586/7T 586/7T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V CFW090180T2223ESZ CFW090180T2223ESZ CFW090180T2223ESZ CFW090180T2223ESZ CFW090240T2223ESZ CFW090240T2223ESZ CFW090240T2223ESZ CFW090240T2223ESZ CFW090086T3848ESZ CFW090086T3848ESZ CFW090086T3848ESZ CFW090086T3848ESZ CFW090105T3848ESZ CFW090105T3848ESZ CFW090105T3848ESZ CFW090105T3848ESZ CFW090142T3848ESZ CFW090142T3848ESZ CFW090142T3848ESZ CFW090142T3848ESZ CFW090180T3848ESZ CFW090180T3848ESZ CFW090180T3848ESZ CFW090180T3848ESZ CFW090180T3848ESZ CFW090180T3848ESZ CFW090180T3848ESZ CFW090180T3848ESZ CFW090240T3848ESZ CFW090240T3848ESZ CFW090240T3848ESZ CFW090240T3848ESZ CFW090312T3848ESZ CFW090312T3848ESZ CFW090312T3848ESZ CFW090312T3848ESZ CFW090361T3848ESZ CFW090361T3848ESZ CFW090361T3848ESZ CFW090361T3848ESZ CFW090063T5060ESZ CFW090063T5060ESZ CFW090063T5060ESZ CFW090063T5060ESZ CFW090079T5060ESZ CFW090079T5060ESZ CFW090079T5060ESZ CFW090079T5060ESZ CFW090107T5069ESZ CFW090107T5069ESZ CFW090107T5069ESZ CFW090107T5069ESZ CFW090147T5069ESZ CFW090147T5069ESZ CFW090147T5069ESZ CFW090147T5069ESZ CFW090147T5069ESZ CFW090147T5069ESZ CFW090147T5069ESZ CFW090147T5069ESZ CFW090211T5069ESZ CFW090211T5069ESZ CFW090211T5069ESZ CFW090211T5069ESZ CFW090247T5069ESZ CFW090247T5069ESZ CFW090247T5069ESZ CFW090247T5069ESZ CFW090315T5069ESZ CFW090315T5069ESZ CFW090315T5069ESZ CFW090315T5069ESZ This chart is designed as a guide only. For specific sizing or sizing for larger motors please contact V.J. Pamensky Canada Inc. Reference 5.3 www.pamensky.com 101 Variable Frequency Drive Sizing Guide CFW 11 Motor HP 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 5.4 CFW-11 Variable Frequency Drive Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 143T 143T 145T 182T 143T 145T 182T 184T 145T 145T 184T 213T W182T W182T 213T 215T 184T 184T 215T 254T 213T 213T 254T 256T 215T 215T 256T 284T 254T 254T 284T 286T 256T 256T 286T 324T 284TS 284T 324T 326T 286TS 286T 326T 364/5T 324TS 324T 364/5T 364/5T 326TS 326T 364/5T 404/5T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V CFW110006B2ON1Z CFW110006B2ON1Z CFW110006B2ON1Z CFW110006B2ON1Z CFW110006B2ON1Z CFW110006B2ON1Z CFW110006B2ON1Z CFW110006B2ON1Z CFW110007B2ON1Z CFW110007B2ON1Z CFW110007B2ON1Z CFW110007B2ON1Z CFW110010T2ON1Z CFW110010T2ON1Z CFW110010T2ON1Z CFW110010T2ON1Z CFW110024T2ON1Z CFW110024T2ON1Z CFW110024T2ON1Z CFW110024T2ON1Z CFW110028T2ON1Z CFW110028T2ON1Z CFW110028T2ON1Z CFW110028T2ON1Z CFW110033T2ON1Z CFW110033T2ON1Z CFW110033T2ON1Z CFW110033T2ON1Z CFW110054T2ON1Z CFW110054T2ON1Z CFW110054T2ON1Z CFW110054T2ON1Z CFW110070T2ON1Z CFW110070T2ON1Z CFW110070T2ON1Z CFW110070T2ON1Z CFW110086T2SZ CFW110086T2SZ CFW110086T2SZ CFW110086T2SZ CFW110105T2SZ CFW110105T2SZ CFW110105T2SZ CFW110105T2SZ CFW110142T2SZ CFW110142T2SZ CFW110142T2SZ CFW110142T2SZ CFW110180T2ON1Z CFW110180T2ON1Z CFW110180T2ON1Z CFW110180T2ON1Z CFW110003T40N1Z CFW110003T40N1Z CFW110003T40N1Z CFW110003T40N1Z CFW110003T40N1Z CFW110003T40N1Z CFW110003T40N1Z CFW110003T40N1Z CFW110003T40N1Z CFW110003T40N1Z CFW110003T40N1Z CFW110003T40N1Z CFW110005T40N1Z CFW110005T40N1Z CFW110005T40N1Z CFW110005T40N1Z CFW110010T40N1Z CFW110010T40N1Z CFW110010T40N1Z CFW110010T40N1Z CFW110017T40N1Z CFW110017T40N1Z CFW110017T40N1Z CFW110017T40N1Z CFW110024T40N1Z CFW110024T40N1Z CFW110024T40N1Z CFW110024T40N1Z CFW110031T40N1Z CFW110031T40N1Z CFW110031T40N1Z CFW110031T40N1Z CFW110038T40N1Z CFW110038T40N1Z CFW110038T40N1Z CFW110038T40N1Z CFW110045T40N1Z CFW110045T40N1Z CFW110045T40N1Z CFW110045T40N1Z CFW110058T40N1Z CFW110058T40N1Z CFW110058T40N1Z CFW110058T40N1Z CFW110070T4SZ CFW110070T4SZ CFW110070T4SZ CFW110070T4SZ CFW110088T4SZ CFW110088T4SZ CFW110088T4SZ CFW110088T4SZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110002T5ON1NFZ CFW110004T5ON1NFZ CFW110004T5ON1NFZ CFW110004T5ON1NFZ CFW110004T5ON1NFZ CFW110007T5ON1NFZ CFW110007T5ON1NFZ CFW110007T5ON1NFZ CFW110007T5ON1NFZ CFW110010T5ON1NFZ CFW110010T5ON1NFZ CFW110010T5ON1NFZ CFW110010T5ON1NFZ CFW110012T5ON1NFZ CFW110012T5ON1NFZ CFW110012T5ON1NFZ CFW110012T5ON1NFZ CFW110017T5ON1NFZ CFW110017T5ON1NFZ CFW110017T5ON1NFZ CFW110017T5ON1NFZ CFW110022T6SZ CFW110022T6SZ CFW110022T6SZ CFW110022T6SZ CFW110027T6SZ CFW110027T6SZ CFW110027T6SZ CFW110027T6SZ CFW110032T6SZ CFW110032T6SZ CFW110032T6SZ CFW110032T6SZ CFW110044T6SZ CFW110044T6SZ CFW110044T6SZ CFW110044T6SZ CFW110053T6ON1NBYZ CFW110053T6ON1NBYZ CFW110053T6ON1NBYZ CFW110053T6ON1NBYZ Reference 101 www.pamensky.com Variable Frequency Drive Sizing Guide CFW 11 Motor HP 60 75 100 125 150 200 250 300 Notes: CFW-11 Variable Frequency Drive Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 364/5TS 364/5T 404/5T 404/5T 364/5TS 364/5T 404/5T 444/5T 404/5TS 404/5T 444/5T 444/5T 444/5TS 444/5T 444/5T 504/5T 445TS 445T 447T 504/5T 447TS 447T 447T 449T 447TS 447T 586/7T 586/7T 586/7TS 586/7T 586/7T 586/7T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V CFW110211T2ON1Z CFW110211T2ON1Z CFW110211T2ON1Z CFW110211T2ON1Z CFW110105T40N1Z CFW110105T40N1Z CFW110105T40N1Z CFW110105T40N1Z CFW110142T40N1Z CFW110142T40N1Z CFW110142T40N1Z CFW110142T40N1Z CFW110180T40N1Z CFW110180T40N1Z CFW110180T40N1Z CFW110180T40N1Z CFW110211T40N1Z CFW110211T40N1Z CFW110211T40N1Z CFW110211T40N1Z CFW110242T4SZ CFW110242T4SZ CFW110242T4SZ CFW110242T4SZ CFW110312T4SZ CFW110312T4SZ CFW110312T4SZ CFW110312T4SZ CFW110370T4SZ CFW110370T4SZ CFW110370T4SZ CFW110370T4SZ CFW110477T4SZ CFW110477T4SZ CFW110477T4SZ CFW110477T4SZ CFW110063T6ON1NBYZ CFW110063T6ON1NBYZ CFW110063T6ON1NBYZ CFW110063T6ON1NBYZ CFW110080T6ON1NBYZ CFW110080T6ON1NBYZ CFW110080T6ON1NBYZ CFW110080T6ON1NBYZ CFW110107T6ON1NBYZ CFW110107T6ON1NBYZ CFW110107T6ON1NBYZ CFW110107T6ON1NBYZ CFW110125T6ON1NBYZ CFW110125T6ON1NBYZ CFW110125T6ON1NBYZ CFW110125T6ON1NBYZ CFW110150T6ON1NBYZ CFW110150T6ON1NBYZ CFW110150T6ON1NBYZ CFW110150T6ON1NBYZ CFW110216T6ONBYZ CFW110216T6ONBYZ CFW110216T6ONBYZ CFW110216T6ONBYZ CFW110289T6ONBYZ CFW110289T6ONBYZ CFW110289T6ONBYZ CFW110289T6ONBYZ CFW110315T6ONBYZ CFW110315T6ONBYZ CFW110315T6ONBYZ CFW110315T6ONBYZ This chart uses Normal Duty (ND) ratings for sizing. See CFW-11 product table for more information. This chart is designed as a guide only. For specific sizing or sizing for larger motors please contact V.J. Pamensky Canada Inc. Reference 5.5 www.pamensky.com 101 Variable Frequency Drive Sizing Guide CFW 700 Motor HP 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 5.6 CFW-700 Variable Frequency Drive Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 143T 143T 145T 182T 143T 145T 182T 184T 145T 145T 184T 213T W182T W182T 213T 215T 184T 184T 215T 254T 213T 213T 254T 256T 215T 215T 256T 284T 254T 254T 284T 286T 256T 256T 286T 324T 284TS 284T 324T 326T 286TS 286T 326T 364/5T 324TS 324T 364/5T 364/5T 326TS 326T 364/5T 404/5T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V CFW700A06POB2DBN1 CFW700A06POB2DBN1 CFW700A06POB2DBN1 CFW700A06POB2DBN1 CFW700A06POB2DBN1 CFW700A06POB2DBN1 CFW700A06POB2DBN1 CFW700A06POB2DBN1 CFW700A07POB2DBN1 CFW700A07POB2DBN1 CFW700A07POB2DBN1 CFW700A07POB2DBN1 CFW700A10POT2DBN1 CFW700A10POT2DBN1 CFW700A10POT2DBN1 CFW700A10POT2DBN1 CFW700B24POT2DBN1 CFW700B24POT2DBN1 CFW700B24POT2DBN1 CFW700B24POT2DBN1 CFW700B28POT2DBN1 CFW700B28POT2DBN1 CFW700B28POT2DBN1 CFW700B28POT2DBN1 CFW700B33POT2DBN1 CFW700B33POT2DBN1 CFW700B33POT2DBN1 CFW700B33POT2DBN1 CFW700C54POT2DBN1 CFW700C54POT2DBN1 CFW700C54POT2DBN1 CFW700C54POT2DBN1 CFW700C70POT2DBN1 CFW700C70POT2DBN1 CFW700C70POT2DBN1 CFW700C70POT2DBN1 CFW700D86POT2DBN1 CFW700D86POT2DBN1 CFW700D86POT2DBN1 CFW700D86POT2DBN1 CFW700D0105T2DBN1 CFW700D0105T2DBN1 CFW700D0105T2DBN1 CFW700D0105T2DBN1 CFW700E0142T2NBN1C3 CFW700E0142T2NBN1C3 CFW700E0142T2NBN1C3 CFW700E0142T2NBN1C3 CFW700E0180T2NBN1C3 CFW700E0180T2NBN1C3 CFW700E0180T2NBN1C3 CFW700E0180T2NBN1C3 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A03P6T4DBN1 CFW700A05P0T4DBN1 CFW700A05P0T4DBN1 CFW700A05P0T4DBN1 CFW700A05P0T4DBN1 CFW700A10P0T4DBN1 CFW700A10P0T4DBN1 CFW700A10P0T4DBN1 CFW700A10P0T4DBN1 CFW700B17P0T4DBN1 CFW700B17P0T4DBN1 CFW700B17P0T4DBN1 CFW700B17P0T4DBN1 CFW700B24P0T4DBN1 CFW700B24P0T4DBN1 CFW700B24P0T4DBN1 CFW700B24P0T4DBN1 CFW700B31P0T4DBN1 CFW700B31P0T4DBN1 CFW700B31P0T4DBN1 CFW700B31P0T4DBN1 CFW700C38P0T4DBN1 CFW700C38P0T4DBN1 CFW700C38P0T4DBN1 CFW700C38P0T4DBN1 CFW700C45P0T4DBN1 CFW700C45P0T4DBN1 CFW700C45P0T4DBN1 CFW700C45P0T4DBN1 CFW700C58P5T4DBN1 CFW700C58P5T4DBN1 CFW700C58P5T4DBN1 CFW700C58P5T4DBN1 CFW700D70P5T4DBN1 CFW700D70P5T4DBN1 CFW700D70P5T4DBN1 CFW700D70P5T4DBN1 CFW700D88P0T4DBN1 CFW700D88P0T4DBN1 CFW700D88P0T4DBN1 CFW700D88P0T4DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B02P9T5DBN1 CFW700B04P2T5DBN1 CFW700B04P2T5DBN1 CFW700B04P2T5DBN1 CFW700B04P2T5DBN1 CFW700B07P0T5DBN1 CFW700B07P0T5DBN1 CFW700B07P0T5DBN1 CFW700B07P0T5DBN1 CFW700B10P0T5DBN1 CFW700B10P0T5DBN1 CFW700B10P0T5DBN1 CFW700B10P0T5DBN1 CFW700B12P0T5DBN1 CFW700B12P0T5DBN1 CFW700B12P0T5DBN1 CFW700B12P0T5DBN1 CFW700B17P0T5DBN1 CFW700B17P0T5DBN1 CFW700B17P0T5DBN1 CFW700B17P0T5DBN1 CFW700D22P0T5NBN1 CFW700D22P0T5NBN1 CFW700D22P0T5NBN1 CFW700D22P0T5NBN1 CFW700D27P0T5NBN1 CFW700D27P0T5NBN1 CFW700D27P0T5NBN1 CFW700D27P0T5NBN1 CFW700D32P0T5NBN1 CFW700D32P0T5NBN1 CFW700D32P0T5NBN1 CFW700D32P0T5NBN1 CFW700D44P0T5NBN1 CFW700D44P0T5NBN1 CFW700D44P0T5NBN1 CFW700D44P0T5NBN1 CFW700E53P0T5NBN1C3 CFW700E53P0T5NBN1C3 CFW700E53P0T5NBN1C3 CFW700E53P0T5NBN1C3 Reference 101 www.pamensky.com Variable Frequency Drive Sizing Guide CFW 700 Motor HP 60 75 100 125 150 Notes: CFW-700 Variable Frequency Drive Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 364/5TS 364/5T 404/5T 404/5T 364/5TS 364/5T 404/5T 444/5T 404/5TS 404/5T 444/5T 444/5T 444/5TS 444/5T 444/5T 504/5T 445TS 445T 447T 504/5T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V CFW700E0211T2NBN1C3 CFW700E0211T2NBN1C3 CFW700E0211T2NBN1C3 CFW700E0211T2NBN1C3 CFW700E0105T4NBN1C3 CFW700E0105T4NBN1C3 CFW700E0105T4NBN1C3 CFW700E0105T4NBN1C3 CFW700E0142T4NBN1C3 CFW700E0142T4NBN1C3 CFW700E0142T4NBN1C3 CFW700E0142T4NBN1C3 CFW700E0180T4NBN1C3 CFW700E0180T4NBN1C3 CFW700E0180T4NBN1C3 CFW700E0180T4NBN1C3 CFW700E0211T4NBN1C3 CFW700E0211T4NBN1C3 CFW700E0211T4NBN1C3 CFW700E0211T4NBN1C3 CFW700E63P0T5NBN1C3 CFW700E63P0T5NBN1C3 CFW700E63P0T5NBN1C3 CFW700E63P0T5NBN1C3 CFW700E80P0T5NBN1C3 CFW700E80P0T5NBN1C3 CFW700E80P0T5NBN1C3 CFW700E80P0T5NBN1C3 CFW700E0107T5NBN1C3 CFW700E0107T5NBN1C3 CFW700E0107T5NBN1C3 CFW700E0107T5NBN1C3 CFW700E0125T5NBN1C3 CFW700E0125T5NBN1C3 CFW700E0125T5NBN1C3 CFW700E0125T5NBN1C3 CFW700E0150T5NBN1C3 CFW700E0150T5NBN1C3 CFW700E0150T5NBN1C3 CFW700E0150T5NBN1C3 This chart uses Normal Duty (ND) ratings for sizing. See CFW-700 product table for more information. This chart is designed as a guide only. For specific sizing please contact V.J. Pamensky Canada Inc. Reference 5.7 www.pamensky.com 101 Direct On-Line Starter Sizing Guide PESW Motor HP 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 5.8 PESW Direct On-Line Starter Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 143T 143T 145T 182T 143T 145T 182T 184T 145T 145T 184T 213T W182T W182T 213T 215T 184T 184T 215T 254T 213T 213T 254T 256T 215T 215T 256T 284T 254T 254T 284T 286T 256T 256T 286T 324T 284TS 284T 324T 326T 286TS 286T 326T 364/5T 324TS 324T 364/5T 364/5T 326TS 326T 364/5T 404/5T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V PESW-9V24AX-R26 PESW-9V24AX-R26 PESW-9V24AX-R26 PESW-9V24AX-R26 PESW-9V24AX-R27 PESW-9V24AX-R27 PESW-9V24AX-R27 PESW-9V24AX-R27 PESW-9V24AX-R28 PESW-9V24AX-R28 PESW-9V24AX-R28 PESW-9V24AX-R28 PESW-9V24AX-R29 PESW-9V24AX-R29 PESW-9V24AX-R29 PESW-9V24AX-R29 PESW-18V24AX-R32 PESW-18V24AX-R32 PESW-18V24AX-R32 PESW-18V24AX-R32 PESW-25V24AX-R33 PESW-25V24AX-R33 PESW-25V24AX-R33 PESW-32V24AX-R33 PESW-32V24AX-R34 PESW-32V24AX-R34 PESW-32V24AX-R34 PESW-32V24AX-R34 PESW-40V24AX-R35 PESW-40V24AX-R35 PESW-40V24AX-R35 PESW-50V24AX-R36 PESW-65V24AX-R39 PESW-65V24AX-R39 PESW-65V24AX-R39 PESW-65V24AX-R39 PESW-80V24AX-R41 PESW-80V24AX-R41 PESW-80V24AX-R41 PESW-80V24AX-R41 PESW-95V24AX-R43 PESW-95V24AX-R43 PESW-95V24AX-R43 PESW-95V24AX-R43 PESW-105V24AX-R45 PESW-105V24AX-R45 PESW-105V24AX-R45 PESW-105V24AX-R45 PESW-9V47AX-R24 PESW-9V47AX-R24 PESW-9V47AX-R24 PESW-9V47AX-R24 PESW-9V47AX-R25 PESW-9V47AX-R25 PESW-9V47AX-R25 PESW-9V47AX-R25 PESW-9V47AX-R26 PESW-9V47AX-R26 PESW-9V47AX-R26 PESW-9V47AX-R26 PESW-9V47AX-R27 PESW-9V47AX-R27 PESW-9V47AX-R27 PESW-9V47AX-R27 PESW-9V47AX-R28 PESW-9V47AX-R28 PESW-9V47AX-R28 PESW-9V47AX-R28 PESW-12V47AX-R30 PESW-12V47AX-R30 PESW-12V47AX-R30 PESW-12V47AX-R30 PESW-18V47AX-R32 PESW-18V47AX-R32 PESW-18V47AX-R32 PESW-18V47AX-R32 PESW-25V47AX-R33 PESW-25V47AX-R33 PESW-25V47AX-R33 PESW-32V47AX-R33 PESW-32V47AX-R34 PESW-32V47AX-R34 PESW-32V47AX-R34 PESW-32V47AX-R34 PESW-40V47AX-R35 PESW-40V47AX-R35 PESW-40V47AX-R35 PESW-50V47AX-R36 PESW-50V47AX-R36 PESW-50V47AX-R38 PESW-50V47AX-R38 PESW-50V47AX-R38 PESW-65V47AX-R39 PESW-65V47AX-R39 PESW-65V47AX-R39 PESW-65V47AX-R39 PESW-80V47AX-R41 PESW-80V47AX-R41 PESW-80V47AX-R41 PESW-80V47AX-R41 PESW-9V56AX-R24 PESW-9V56AX-R24 PESW-9V56AX-R24 PESW-9V56AX-R24 PESW-9V56AX-R25 PESW-9V56AX-R25 PESW-9V56AX-R25 PESW-9V56AX-R25 PESW-9V56AX-R25 PESW-9V56AX-R25 PESW-9V56AX-R25 PESW-9V56AX-R25 PESW-9V56AX-R26 PESW-9V56AX-R26 PESW-9V56AX-R26 PESW-9V56AX-R26 PESW-9V56AX-R27 PESW-9V56AX-R27 PESW-9V56AX-R27 PESW-9V56AX-R27 PESW-9V56AX-R29 PESW-9V56AX-R29 PESW-9V56AX-R29 PESW-9V56AX-R29 PESW-12V56AX-R30 PESW-12V56AX-R30 PESW-12V56AX-R30 PESW-12V56AX-R30 PESW-18V56AX-R32 PESW-18V56AX-R32 PESW-18V56AX-R32 PESW-18V56AX-R32 PESW-32V56AX-R33 PESW-32V56AX-R33 PESW-32V56AX-R33 PESW-32V56AX-R33 PESW-32V56AX-R34 PESW-32V56AX-R34 PESW-32V56AX-R34 PESW-32V56AX-R34 PESW-50V56AX-R36 PESW-50V56AX-R36 PESW-50V56AX-R36 PESW-50V56AX-R36 PESW-50V56AX-R38 PESW-50V56AX-R38 PESW-50V56AX-R38 PESW-50V56AX-R38 PESW-65V56AX-R39 PESW-65V56AX-R39 PESW-65V56AX-R39 PESW-65V56AX-R39 Reference 101 www.pamensky.com Direct On-Line Starter Sizing Guide PESW Motor HP 60 75 Notes: PESW Direct On-Line Starter Part Number RPM Frame Voltage 3600 1800 1200 900 3600 1800 1200 900 364/5TS 364/5T 404/5T 404/5T 364/5TS 364/5T 404/5T 444/5T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 230V 460V 575V PESW-95V47AX-R43 PESW-95V47AX-R43 PESW-95V47AX-R43 PESW-95V47AX-R43 PESW-105V47AX-R44 PESW-105V47AX-R44 PESW-105V47AX-R44 PESW-105V47AX-R44 PESW-80V56AX-R41 PESW-80V56AX-R41 PESW-80V56AX-R41 PESW-80V56AX-R41 PESW-95V56AX-R43 PESW-95V56AX-R43 PESW-95V56AX-R43 PESW-95V56AX-R43 This chart is designed as a guide only. For specific sizing please contact V.J. Pamensky Canada Inc. Reference 5.9 www.pamensky.com 101 Soft Starter Sizing Guide SSW 06 Motor HP 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 5.10 SSW 06 Soft Starter Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 143T 143T 145T 182T 143T 145T 182T 184T 145T 145T 184T 213T W182T W182T 213T 215T 184T 184T 215T 254T 213T 213T 254T 256T 215T 215T 256T 284T 254T 254T 284T 286T 256T 256T 286T 324T 284TS 284T 324T 326T 286TS 286T 326T 364/5T 324TS 324T 364/5T 364/5T 326TS 326T 364/5T 404/5T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060016T2257ESZ SSW060016T2257ESZ SSW060016T2257ESZ SSW060016T2257ESZ SSW060023T2257ESZ SSW060023T2257ESZ SSW060023T2257ESZ SSW060023T2257ESZ SSW060030T2257ESZ SSW060030T2257ESZ SSW060030T2257ESZ SSW060030T2257ESZ SSW060045T2257ESZ SSW060045T2257ESZ SSW060045T2257ESZ SSW060045T2257ESZ SSW060060T2257ESZ SSW060060T2257ESZ SSW060060T2257ESZ SSW060060T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060010T2257ESZ SSW060016T2257ESZ SSW060016T2257ESZ SSW060016T2257ESZ SSW060016T2257ESZ SSW060016T2257ESZ SSW060016T2257ESZ SSW060016T2257ESZ SSW060016T2257ESZ SSW060023T2257ESZ SSW060023T2257ESZ SSW060023T2257ESZ SSW060023T2257ESZ SSW060030T2257ESZ SSW060030T2257ESZ SSW060030T2257ESZ SSW060030T2257ESZ SSW060045T2257ESZ SSW060045T2257ESZ SSW060045T2257ESZ SSW060045T2257ESZ SSW060045T2257ESZ SSW060045T2257ESZ SSW060045T2257ESZ SSW060045T2257ESZ SSW060060T2257ESZ SSW060060T2257ESZ SSW060060T2257ESZ SSW060060T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060010T5257ESZ SSW060016T5257ESZ SSW060016T5257ESZ SSW060016T5257ESZ SSW060016T5257ESZ SSW060016T5257ESZ SSW060016T5257ESZ SSW060016T5257ESZ SSW060016T5257ESZ SSW060023T5257ESZ SSW060023T5257ESZ SSW060023T5257ESZ SSW060023T5257ESZ SSW060030T5257ESZ SSW060030T5257ESZ SSW060030T5257ESZ SSW060030T5257ESZ SSW060030T5257ESZ SSW060030T5257ESZ SSW060030T5257ESZ SSW060030T5257ESZ SSW060045T5257ESZ SSW060045T5257ESZ SSW060045T5257ESZ SSW060045T5257ESZ SSW060060T5257ESZ SSW060060T5257ESZ SSW060060T5257ESZ SSW060060T5257ESZ Reference 101 www.pamensky.com Soft Starter Sizing Guide SSW 06 Motor HP 60 75 100 125 150 200 250 300 Notes: SSW 06 Soft Starter Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 364/5TS 364/5T 404/5T 404/5T 364/5TS 364/5T 404/5T 444/5T 404/5TS 404/5T 444/5T 444/5T 444/5TS 444/5T 444/5T 504/5T 445TS 445T 447T 504/5T 447TS 447T 447T 449T 447TS 447T 586/7T 586/7T 586/7TS 586/7T 586/7T 586/7T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V SSW060170T2257ESZ SSW060170T2257ESZ SSW060170T2257ESZ SSW060170T2257ESZ SSW060205T2257ESZ SSW060205T2257ESZ SSW060205T2257ESZ SSW060205T2257ESZ SSW060255T2257ESZ SSW060255T2257ESZ SSW060255T2257ESZ SSW060255T2257ESZ SSW060312T2257ESZ SSW060312T2257ESZ SSW060312T2257ESZ SSW060312T2257ESZ SSW060365T2257ESZ SSW060365T2257ESZ SSW060365T2257ESZ SSW060365T2257ESZ SSW060480T2257ESZ SSW060480T2257ESZ SSW060480T2257ESZ SSW060480T2257ESZ SSW060604T2257ESZ SSW060604T2257ESZ SSW060604T2257ESZ SSW060604T2257ESZ SSW060820T2257ESZ SSW060820T2257ESZ SSW060820T2257ESZ SSW060820T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060085T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060130T2257ESZ SSW060170T2257ESZ SSW060170T2257ESZ SSW060170T2257ESZ SSW060170T2257ESZ SSW060205T2257ESZ SSW060205T2257ESZ SSW060205T2257ESZ SSW060205T2257ESZ SSW060255T2257ESZ SSW060255T2257ESZ SSW060255T2257ESZ SSW060255T2257ESZ SSW060312T2257ESZ SSW060312T2257ESZ SSW060312T2257ESZ SSW060312T2257ESZ SSW060365T2257ESZ SSW060365T2257ESZ SSW060365T2257ESZ SSW060365T2257ESZ SSW060060T5257ESZ SSW060060T5257ESZ SSW060060T5257ESZ SSW060060T5257ESZ SSW060085T5257ESZ SSW060085T5257ESZ SSW060085T5257ESZ SSW060085T5257ESZ SSW060130T5257ESZ SSW060130T5257ESZ SSW060130T5257ESZ SSW060130T5257ESZ SSW060130T5257ESZ SSW060130T5257ESZ SSW060130T5257ESZ SSW060130T5257ESZ SSW060170T5257ESZ SSW060170T5257ESZ SSW060170T5257ESZ SSW060170T5257ESZ SSW060205T5257ESZ SSW060205T5257ESZ SSW060205T5257ESZ SSW060205T5257ESZ SSW060255T5257ESZ SSW060255T5257ESZ SSW060255T5257ESZ SSW060255T5257ESZ SSW060312T5257ESZ SSW060312T5257ESZ SSW060312T5257ESZ SSW060312T5257ESZ This chart is designed as a guide only. For specific sizing or sizing for larger motors please contact V.J. Pamensky Canada Inc. Reference 5.11 www.pamensky.com 101 Soft Starter Sizing Guide SSW 07 Motor HP 3 5 7.5 10 15 20 25 30 40 50 60 75 100 5.12 SSW 07 Soft Starter Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 W182T W182T 213T 215T 184T 184T 215T 254T 213T 213T 254T 256T 215T 215T 256T 284T 254T 254T 284T 286T 256T 256T 286T 324T 284TS 284T 324T 326T 286TS 286T 326T 364/5T 324TS 324T 364/5T 364/5T 326TS 326T 364/5T 404/5T 364/5TS 364/5T 404/5T 404/5T 364/5TS 364/5T 404/5T 444/5T 404/5TS 404/5T 444/5T 444/5T 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V 208-230/460 & 575V SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070024T5SZ SSW070024T5SZ SSW070024T5SZ SSW070024T5SZ SSW070030T5SZ SSW070030T5SZ SSW070030T5SZ SSW070030T5SZ SSW070045T5SZ SSW070045T5SZ SSW070045T5SZ SSW070045T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070085T5SZ SSW070085T5SZ SSW070085T5SZ SSW070085T5SZ SSW070085T5SZ SSW070085T5SZ SSW070085T5SZ SSW070085T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070171T5SZ SSW070171T5SZ SSW070171T5SZ SSW070171T5SZ SSW070200T5SZ SSW070200T5SZ SSW070200T5SZ SSW070200T5SZ SSW070255T5SH1Z SSW070255T5SH1Z SSW070255T5SH1Z SSW070255T5SH1Z SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070024T5SZ SSW070024T5SZ SSW070024T5SZ SSW070024T5SZ SSW070030T5SZ SSW070030T5SZ SSW070030T5SZ SSW070030T5SZ SSW070045T5SZ SSW070045T5SZ SSW070045T5SZ SSW070045T5SZ SSW070045T5SZ SSW070045T5SZ SSW070045T5SZ SSW070045T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070085T5SZ SSW070085T5SZ SSW070085T5SZ SSW070085T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070017T5SZ SSW070024T5SZ SSW070024T5SZ SSW070024T5SZ SSW070024T5SZ SSW070030T5SZ SSW070030T5SZ SSW070030T5SZ SSW070030T5SZ SSW070030T5SZ SSW070030T5SZ SSW070030T5SZ SSW070030T5SZ SSW070045T5SZ SSW070045T5SZ SSW070045T5SZ SSW070045T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070061T5SZ SSW070085T5SZ SSW070085T5SZ SSW070085T5SZ SSW070085T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ Reference 101 www.pamensky.com Soft Starter Sizing Guide SSW 07 Motor HP 125 150 200 250 300 Notes: SSW 07 Soft Starter Part Number RPM Frame Voltage 230V 460V 575V 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 3600 1800 1200 900 444/5TS 444/5T 444/5T 504/5T 445TS 445T 447T 504/5T 447TS 447T 447T 449T 447TS 447T 586/7T 586/7T 586/7TS 586/7T 586/7T 586/7T 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V 460 & 575V SSW070312T5SH1Z SSW070312T5SH1Z SSW070312T5SH1Z SSW070312T5SH1Z SSW070365T5SH1Z SSW070365T5SH1Z SSW070412T5SH1Z SSW070412T5SH1Z SSW070171T5SZ SSW070171T5SZ SSW070171T5SZ SSW070171T5SZ SSW070200T5SZ SSW070200T5SZ SSW070200T5SZ SSW070200T5SZ SSW070255T5SH1Z SSW070255T5SH1Z SSW070255T5SH1Z SSW070255T5SH1Z SSW070312T5SH1Z SSW070312T5SH1Z SSW070312T5SH1Z SSW070312T5SH1Z SSW070365T5SH1Z SSW070365T5SH1Z SSW070365T5SH1Z SSW070365T5SH1Z SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070130T5SZ SSW070171T5SZ SSW070171T5SZ SSW070171T5SZ SSW070171T5SZ SSW070200T5SZ SSW070200T5SZ SSW070200T5SZ SSW070200T5SZ SSW070255T5SH1Z SSW070255T5SH1Z SSW070255T5SH1Z SSW070255T5SH1Z SSW070312T5SH1Z SSW070312T5SH1Z SSW070312T5SH1Z SSW070312T5SH1Z This chart is designed as a guide only. For specific sizing or sizing for larger motors please contact V.J. Pamensky Canada Inc. Reference 5.13