Static Transfer Switch Power Panel

advertisement
B U L L E T I N
Static Transfer Switch Power Panel
6415
Standard Features
 Continuous monitoring of sources
 Automatic transfer operation
 Manual transfer capability
 Automatic retransfer
 Remote control and monitoring
 Additional RS-485 port
 Digitally adjustable parameters
 Redundant logic power
 CE marking
Applications
 Communication/Data Centers
 Hospitals
 Airports and military bases
 Industrial plants
 Commercial buildings
Options
 Site testing and maintenance
 Installation and start-up
 Spare parts
 Training programs
This Static Transfer Switch Power Panel (STS-PP) automatically transfers
critical loads from a primary power source to an alternate power source in
the event of interruption or abnormal conditions. Designed using siliconcontrolled rectifier (SCR) power-switching elements, the STS-PP transfers
the critical load between power sources in less than 1/4 cycle upon loss
of source – more than 10 times shorter than traditional electromechanical
switches – appearing seamless to even the most sophisticated loads.
Accomplishing rapid transfer without cross-connecting power sources, the
STS-PP ensures that no damage can occur to either power source. This
also allows for transfer between two dissimilar power sources – a feature
far superior to mechanical open-or closed-transition automatic transfer
switches.
The STS-PP has precision digital sense and control circuits that do not
require calibration or adjustments (no potentiometers). The sensed analog
signals are converted to digital format before being interpreted. All operational parameters are set digitally.
The STS-PP has dedicated logic for the critical interpretation and switching operations. This dedicated logic ensures fast and predictable operation at all times. A microcontroller performs the system level functions
such as operator interface (control panel), operating parameter setup, and
remote monitoring and control.
The STS-PP is designed to mount in a switchgear panel or power
distribution unit that has the necessary circuit breakers for bypass and
isolation.
STS-PP
Bulletin 6415
Electrical Characteristics:
Voltage/Frequency ..... 120 to 400 VAC, 3-phase
50 or 60Hz (selectable)
3 or 4-pole
Current Rating ............ 100A, 150A, 200A, 250A,
400A , 600A, 800A
Efficiency .................... 99% nominal
Environmental Specifications:
Temperature ............... 0°C to 40°C
Humidity ..................... 95%, noncondensing
Panel Indicators: ............. Summary Alarm
Source 1 active
Sense Time ............ <2ms upon loss of source
Source 2 active
Sense/Transfer ....... 1/4 cycle upon loss of source
Source 1 preferred
RS-485 Port ............ Remote status & operation
Source 2 preferred
Auto retransfer on/off
User Adjustable Settings: Overvoltage
Load power on
Undervoltage
Breaker status
Retransfer delay time
Panel Controls: ............... Fault reset
Phase angle error
Lamp test
Transfer delay (optional)
Auto retransfer on
Transfer Inhibit (optional)
Auto retransfer off
Select source 1
Select source 2
Control enable
Operational Characteristics:
Physical Characteristics:
Rating
Dimensions (mm)
HxWxD
100A, 3-pole
150A, 3-pole
200A, 3-pole
250A, 3-pole
400A, 3-pole
600A, 3-pole
800A, 3-pole
800 x 555 x420
800 x 555 x420
800 x 555 x420
800 x 555 x420
1200 x 820 x520
1200 x 920 x520
1200 x 920 x520
Weight
(kg)
91
91
91
91
135
220
220
Rating
Dimensions (mm)
HxWxD
100A, 4-pole
150A, 4-pole
200A, 4-pole
250A, 4-pole
400A, 4-pole
600A, 4-pole
800A, 4-pole
800 x 555 x420
800 x 555 x420
800 x 555 x420
800 x 555 x420
1200 x 820 x520
1200 x 920 x520
1200 x 920 x520
Weight
(kg)
95
95
95
95
143
245
245
Specification subject to change without notice
EUROATLAS GmbH
Zum Panrepel 2
28307 Bremen
Germany
Phone +49-421-486930
Fax +49-421-4869341
info@euroatlas.de
www.euroatlas.de
Download