MV Vacuum circuit-breaker 24 KV - Schneider Electric

MV Vacuum circuit-breaker
24 KV
Catalogue
2004
Evolis circuit-breaker
A safe, easy to integrate
and comprehensive range
for demanding installations.
PE60040
b Evolis is a vacuum circuit-breaker that meets current and future standards in terms
of electrical installation dependability, in compliance with standards and
environmental protection.
It is the quintessential expression of Merlin Gerin’s know-how.
b Evolis is intended for all network applications, either new or renovation
installations, for utilities companies, infrastructures, process industry and
tertiary building.
PE60052
Evolis 24 kV frontal fixed
Evolis 24 kV frontal withdrawable
1
The very best of
vacuum technology
DE60163
As a specialist in breaking technologies,
Merlin Gerin took naturally an interest in
vacuum breaking techniques.
A major R&D investment was made to
develop and engineer Evolis, providing
customers with the very best of vacuum
technology.
Ceramic chamber
Shield
Fixed contact
Mobile contact
Make-up of a vacuum interrupter
b Vacuum interrupters basically have two electrical contacts, one fixed and the other
mobile, and a sealed enclosure. The latter enables a high level of vacuum to be
maintained inside the interrupter (less than 10-2 Pa) to provide insulation between
the open contacts.
b The dielectric strength of the vacuum allows the contact-to-contact distance to be
reduced. This short distance together with the low opening speed allow the use of a
low energy control mechanism. A metal bellows provides the link between the mobile
contact and the enclosure.
b In order to keep the vacuum level required for the correct operation of the
interrupter for 30 years, the enclosure must be perfectly sealed, and the various
components have to be fully degased. This is achieved by:
v choosing materials that are specifically selected for this application
(metals and ceramics),
v choosing an appropriate assembly process (vacuum, high temperature brazing),
v the use of a "getter" material to absorb the residual gas.
Current breaking in a vacuum interrupter
Metal bellows
b At low values of current, these vapors very quickly condense on the shield and
contacts when the arc disappears, thus allowing:
v the vacuum to be re-established,
v a contact-to-contact dielectric strength to be restored that is greater than
the recovery voltage: breaking is then complete.
Fig. 1: vacuum interrupter components
DE60164
Current
Electrode
AMF coil
Contact disk
Arc plasma
Axial magnetic field
PE60042
Fig. 2: cross-section of AMF contact
Fig. 3: diffuse vacuum arc AMF technology
2
b In vacuum breaking, the electrical arc generated on separation of the contacts is
made up of a plasma of metal vapors produced by the vaporization of the contact
material.
b At high currents, the electrical arc in the vacuum switches to a concentrated mode
which causes high, localized temperature rises on the contacts. The existence of
these hot spots is detrimental to the quick restoring of the dielectric strength.
Two techniques can be used in order to avoid this stagnation of the static
concentrated arc:
v the so called RMF (Radial Magnetic Field) technique, involves rotating the arc
thanks to an electromagnetic effect generated by a radial magnetic field; this
therefore limits contact erosion.
v a more recent technique called AMF (Axial Magnetic Field) involves applying an
axial magnetic field parallel to the axis of the two contacts (fig. 2) which allows a
diffuse arc to be maintained (fig. 3) even at high current values. The arc energy is
spread over the whole contact surface area, therefore causing very low levels of
erosion.
v Merlin Gerin has chosen this last technique for the Evolis range.
200110
Merlin Gerin’s choices for Evolis
combined with its industrial expertise
provides customer with a highly reliable
range of circuit-breakers. These products
are suitable for the most demanding
conditions with the guarantee of full
compliance with international standards.
AMF technology
b Evolis circuit-breakers use AMF type vacuum interrupters.
According to technical and economic optimization considerations, the axial magnetic
field is generated:
v either by a coil outside of the interrupter (fig. 4), for rated voltages up to 17.5 kV,
v or by a coil integrated in the interrupter contact structure (fig. 5), for the 24 kV
voltage level.
b In both cases the AMF vacuum interrupters feature low arc voltages (Uarc of
around 50 V) and maximum usage of the contact surface for very low contact erosion.
The advantages provided
b The above choices provide customers with the following advantages in
MV circuit-breaker applications:
v simple and compact vacuum interrupters,
v high electrical endurance meaning that there is no need for contact wear
inspection in normal network protection applications including highly disturbed
overhead line feeders.
DE60162
Fig 4: 17.5 kV external coil type interrupter
Fig 5: 24 kV internal coil type interrupter
3
The very best of
vacuum technology
PE60062
Systematic advanced control
The main components of the circuit-breaker, such as vacuum interrupter and
operating mechanism, are produced by Schneider Electric. The vacuum interrupters
are manufactured in an ultra-modern production unit in France.
During manufacture, each circuit-breaker is subjected to systematic advanced
testing.
Vacuum interrupter testing
b The level of vacuum in each interrupter is tested using the "magnetron discharge
method".
PE60061
Vacuum interrupter
b Using this sophisticated procedure, measurement is very precise and does not
require access to the inside of the interrupter, thus not affecting the airtight seal.
Circuit-breaker testing
b A rigorous set of tests and measurements is carried out on each circuit-breaker.
b The results are reported and signed off by the quality control department on each
device's test certificate to ensure product traceability.
Compliance with standards
b Evolis complies with IEC 62271-100.
b Design and production are certified to ISO 9000 (version 2000).
b Production sites are certified to ISO 14001 (environmental standard).
Certification
Industrial process expertise
b The certificate of conformity provides guarantees that the circuit-breaker:
v has been subject to type tests according to EN 45001 standards procedures in
accredited laboratories by independent organizations,
v is in conformity with recognized international standards
b Evolis is currently being certified by external EN 45011 accredited organizations,
members of the STL (Short circuit Testing Liaison)
v EN 45001: general requirements for the competence of testing and calibration
laboratories,
v EN 45011: general requirements for bodies of operating product certification
systems.
Environmental care
b Product design takes account of the environmental constraints described in a
"Product Environment Profile" dossier (PEP).
b An end-of-service-life manual details procedures for dismantling and processing
components.
4
General contents
Evolis presentation
p.6
Panorama
p.8
Evolis 24 kV frontal fixed
p.10
Evolis 24 kV frontal withdrawable
p.24
Evolis Pilot monitoring device
p.43
5
Evolis presentation
6
DE60129
Extended products offer
LV cubicle
components
b Mcb
b protection relay
b lamp
b push button
b terminal blocks
connector
Protection
and control
b UMI
Circuit-breaker
b pilot
b cradle
Metering
b VPIS
b PM500
DV2
(kA)
Icu
Ue
(V)
100
100
220/440
85
525
690
Icw
85kA/1s
cat.B
Ics =
100%
Icu
50/60Hz
IEC
947-2
EN 60947-2
AS
NEMA
UNE
BS
CEI
VDE
UTE
Instrument
transformer
MV cubicle
components
b capacitor insulator
b earthing switch
b heating resistor
b voltage presence
indicator
b crank
b extraction table
7
Panorama
Evolis 7.2… 17.5 kV frontal
DV2
Ue (V)
220/440
525
690
Icu (kA)
100
100
85
DV2
Icu
Icw 85kA/1s
cat.B
Ics =
100%
Ue
(V)
(kA)
100
100
220/440
Icu
85
525
690
Icw
50/60Hz
85kA/1s
cat.B
947-2
IEC
EN 60947-2
BS CEI
UTE
UNE
AS NEMA
Ics =
100%
Icu
VDE
50/60Hz
947-2
IEC
EN 60947-2
AS
UNE
BS
CEI
VDE
UTE
Withdrawable
Fixed
RATED VOLTAGE
kV
kV
kV
PHASE DISTANCE
from 145 to 240 mm
RATED SHORT CIRCUIT CURRENT
from 25 to 40 kA
RATED CURRENT
from 630 to 2500 A
separate catalogue
8
NEMA
Evolis 24 kV frontal
Protection
and control
MERLIN GERIN
Sepam
on
1 > 51
1 > >51 1o > 51 1o > >51
I1 =
I2 =
I3 =
Fixed
Withdrawable
Pilot option checks that the
circuit-breaker is in a good
working order
Pilot option checks that the
circuit-breaker is in a good
working order
ext
0 off
I on
Metering
Instrument
Cubicle
transformers components
Trip
165A RMS
166A RMS
167A RMS
v SEPAM series 20 v PM450,
for common
PM500 for
applications
basic metering
v LPCT
compatible with
Sepam relay
v SEPAM series 40 v PM800 Series v CT
for advanced
compatible with
for demanding
applications
metering
Sepam relay
v
v
v
v
Earthing switch
Insulators
Potential tester
Bus section truck
v Bus section
v Circuit-breaker
extraction table
v Crank
Web accessible
Web accessible
RATED VOLTAGE
kV
v SEPAM series 80 v CM3000,
for complete
CM4000 Series
applications
for
comprehensive
v Voltage
v VT
compatible with
indication
Sepam relay
v Transparent
metering and
screen
v Insulator support
power quality
analysis
PHASE DISTANCE
from 230 to 250 mm
RATED SHORT CIRCUIT CURRENT
from 16 to 31.5 kA
RATED CURRENT
from 630 to 2500 A
separate catalogues
9
Evolis 24 kV frontal
fixed
10
PE60040
Contents
Main characteristics presentation
p.12
Function description
p.13
MV connections
p.13
LV connections
p.14
Opening circuit
p.15
Remote control
p.16
Indication and locking / interlocking
p.17
Auxiliary wiring diagram
p.18
Dimensions
p.19
Offer structure
p.20
Order form
p.21
Separate components
p.22
Services
p.23
Fixed version
11
Evolis 24 kV frontal
fixed
Main characteristics presentation
A fully assembled and tested unit
b Evolis circuit-breakers are actuated by a spring operated mechanism that ensures
operating speeds independent of operator action and can be operated without any
auxiliary supply.
When the operating mechanism is motorized, the circuit-breaker can take on remote
control functions and perform re-closing cycles.
b This unit is easy to integrate in a cubicle environment. An Installation Guide
explains the necessary operations in detail.
DE60047
Electrical characteristics according to IEC 62271-100
Phase distance (mm)
230
Rated voltage 24 kV
Isc
16 kA
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
H
25 kA
D
W
250
250
In
31.5 kA
b
b
v
v
v
v
b
b
v
v
v
v
v
v
v
v
v available end of 2004
Dimensions (mm)
D
H
W
593
712.5
655
593
712.5
730
593
712.5
745
97
97
135
Weight (kg)
Additional characteristics according to IEC 62271-100
Rated values
Voltage
Insulation voltage:
power frequency withstand voltage
lightning impulse withstand voltage
Frequency
Short time withstand current
Peak withstand current
Short circuit making current
Other characteristics
Operating sequences
Mechanical endurance
Electrical endurance
Number of operations at full Isc value
Capacitive current breaking
Service conditions
Humidity:
average relative humidity
12
Ur
kV rms
24
Ud
Up
fr
Ik/tk
Ip
kV rms
kV peak
Hz
kA
kA peak
kA peak
50
125
50-60
Isc/3s
2.5 & 2.6 Isc
2.5 & 2.6 Isc
class
number of operations
class
16 kA
25 kA
31.5 kA
class
24-hours period
1 month
O-3min-CO-3min-CO
O-0.3s-CO-3min-CO
O-0.3s-CO-15s-CO
M2
10 000
E2
50
50
50
C1-C2 (for some applications)
-25°C to 40°C
< 95%
< 90%
Function description
MV connections
Connection
DE60126
b The basic circuit-breaker is fitted with drilled copper terminal pads.
Customer connection is easily achieved outside the circuit-breaker on these vertical
terminal pads.
Type tested configurations of connections are shown in the Installation Guide.
13
Evolis 24 kV frontal
fixed
Function description
LV connections
DE60143
Two solutions for connections
without LV Plug
with LV plug
b The basic fixed circuit-breaker LV wiring can be connected directly to the terminal
block of the operating mechanism, through a cable protection duct.
b An LV plug can be fitted as an option. It includes:
v the fixed part (male) fitted on the circuit-breaker and fully wired to the terminal
block of the operating mechanism,
v the mobile part (female) compatible with the male part.
Two versions of LV plug are available
DE60149
Low voltage connections
b A 21-pin LV plug, allowing connection of:
v a shunt opening release YO1,
v a remote control mechanism (electrical motor, shunt closing release YF,
antipumping relay),
v the monitoring device Pilot,
v maximum number of auxiliary contacts: 3 NC - 3 NO - 1 CHG,
(see details in chapter "Open/closed auxiliary contacts").
b A 42-pin LV plug, allowing connection of:
v an opening release (shunt opening release or undervoltage release),
v a second opening release (shunt opening release YO2 or undervoltage release YN
or low energy release MITOP),
v a remote control mechanism (electrical motor, shunt closing release, antipumping
relay),
v the monitoring device Pilot,
v maximum number of auxiliary contacts: 5 NC - 6 NO - 1 CHG,
(see details in chapter "Open/closed auxiliary contacts").
LV wiring kit
A kit including 21 wires (2 meters long) fitted with pin suitable for the plug can be
supplied for connection to the LV compartment of the cubicle.
LV plug connections
Interlocking kit
For withdrawble applications, an interlocking kit is available. This kit facilitates
the interlocking between the LV plug (connected/disconnected) and the open/closed
position of the circuit-breaker (as required by the IEC standard 62271-200).
This arrangement provides an auxiliary supply connection with a high level of
electrical safety.
14
Function description
opening circuit
DE60161
Composition
b
v
v
v
v
(2)
(1) or (3)
The opening circuit can be produced using the followings units:
shunt opening release (YO1),
second shunt opening release (YO2),
undervoltage release (YN),
low energy release (MITOP).
Please check in the combination table the right associations of different releases.
Note: this table is present in order form at the end of this catalogue.
Shunt opening release (YO1 and YO2)
b This causes instant opening of the circuit-breaker when energised.
Characteristics
Supply
Threshold
VAC
VDC
VAC
VDC
Consumption
see order form
0.7 to 1.1 Un
0.85 to 1.1 Un
160 VA
50 W
DE60094
Undervoltage release (YN)
(1) Shunt opening release
b An Undervoltage release operates to open the circuit-breaker when the voltage at
the terminals of the release falls below 35% of its rated voltage, even if the fall is slow
and gradual.
On the other hand, it does not operate the circuit-breaker when the voltage at its
terminals exceeds 70% of its rated supply voltages.
Circuit-breaker closing is possible when the values of the voltage at the terminals of
the release are greater than or equal to 85% of its rated voltage.
Closing is impossible when the voltage at the terminals is lower than 35% of its
rated supply voltage.
Characteristics
DE60089
Supply
Threshold
Consumption
pick-up
hold
(2) Undervoltage release
opening
closing
VAC
VDC
VAC
VDC
see order form
0.35 to 0.7 Un
0.85 Un
400 VA
100 W
100 VA
10 W
Low energy release (MITOP)
DE60091
b This specific release comprises a low energy consumption unit and is used
specifically with self-powered relay SEPAM 100LA ("REFLEX MODULE"), or VIP
relay.
Characteristics
(3) Low energy release
Supply
Threshold
direct current
0.6 A < I < 3 A
Any tripping caused by the Mitop release is indicated momentarily by an SDE type
changeover contact.
15
Function description
remote control
Evolis 24 kV frontal
fixed
Function
DE60160
(6)
(5)
b The remote control enables remote opening and closing of the circuit-breaker.
Composition
(8)
b
v
v
v
v
The remote control comprises:
electrical motor and gear reducer,
a shunt closing release (YF),
an antipumping relay,
an operation counter.
(7)
(9)
(4)
Operating mechanism
DE60093
Electric motor and gear reducer
Ì
(4) Electric motor and gear reducer
b The electrical motor arms and rearms the energy storage springs as soon as the
circuit-breaker is closed. This enables instant reclosing of the device after opening.
The arming lever is only used as back up control in the absence of an auxiliary
voltage.
M3 contact indicates end of charging.
Characteristics
Supply
Consumption
VAC
VDC
VAC
VDC
50/60
see order form
see order form
380 VA
380 W
DE60094
Shunt closing release (YF)
b This causes the remote closing of the circuit-breaker when the operating
mechanism is armed.
Characteristics
Supply
(5) Shunt closing release
Threshold
Consumption
YF
VAC 50/60 Hz
VDC
VAC
VDC
see order form
see order form
0.85 to 1.1 Un
160 VA
50 W
DE60095
Antipumping relay
b The antipumping relay avoids unwanted closing and tripping within a short interval.
This function gives absolute priority to the opening order and blocks closing.
This prevents the device from being locked in an indefinite opening-closing cycle.
(6) Antipumping relay
16
Function description
indication and locking / interlocking
DE60087
Operation counter
b The operation counter is visible from the front face.
It displays the number of operating cycles that the device has performed.
(7) Operation counter
DE60152
Open/closed auxiliary contacts
b The number of available contacts depends on the fitted options on the operating
mechanism.
(8) Auxiliary contacts
b In its basic configuration, the operating mechanism of the circuit-breaker
comprises a total of:
v 5 normally closed contacts (NC),
v 6 normally open contacts (NO),
v 1 changeover contact (CHG).
b Use of auxiliary contacts is given in the following table:
Option
Remote control
Shunt opening release (each)
Undervoltage release
Low energy release MITOP
Trip circuit supervision
NC contact
1
0
0
0
1
NO contact
1
1
0
0
0
To find out the final number of contacts available, the above quantity must be
deducted from the total quantity (5 NC + 6 NO + 1 CHG) included in the circuitbreaker.
(Example: a circuit-breaker equipped with a remote control and a shunt opening release
has 4 NC + 4 NO + 1 CHG available contacts. With an undervoltage release instead of
a shunt release, this circuit-breaker has 4 NC + 5 NO + 1CHG available contacts).
b When the 21-pin LV plug is used (for withdrawable applications), the maximum
number of available contacts is:
v 3 NC,
v 3 NO,
v 1 changeover.
(Instead of 5NC-6NO-1CHG with the 42-pin LV plug).
Contact characteristics
Rated current
Breaking capacity
AC
DC
220 V (cos ϕ ≥ 0.3)
110/220 V (L/R ≤ 0.02 s)
10 A
1A
0.3 A
DE60124
Locking of the circuit-breaker
in the open position
b This key lock allows the locking of the circuit-breaker in the "open" position by the
means of a key.
b The circuit-breaker is locked in the "open" position by blocking the opening
pushbutton in the "pushed-in position".
b The key lock is of Profalux or Ronis captive key type.
(9) Locking kit
17
Function description
auxiliary wiring diagram
Evolis 24 kV frontal
fixed
DE60123
Auxiliary wiring diagram (principle)
CLOSE CB
OPEN CB
M
YF +
anti-pumping
motor
shunt closing
+ anti-pumping
system
remote control
18
PILOT
YO1
or
YO2
YM
monitoring
device pilot
shunt
opening
release
undervoltage
release
MITOP
low energy
release
(MITOP)
changeover
contact
NO
NC
contacts contacts
Dimensions
D
97.5
DE60062
D
DE60060
3 sizes of width
712.5
W
593
Dimensions (mm)
Phase distance
230
D
16 kA
25 kA
31.5 kA
W
250
D
W
630 A
b
655
b
734
1250 A
b
655
b
734
250
D
W
2000 A
b
745
2500 A
b
745
2000 A
b
745
2500 A
b
745
630 A
b
745
1250 A
b
745
2000 A
b
745
2500 A
b
745
630 A
b
655
b
734
1250 A
b
655
b
734
19
Evolis 24 kV frontal
fixed
Offer structure
The basic frontal fixed circuit-breaker includes:
b
b
b
b
b
b
b
a manual operating mechanism (spring type),
closing and opening pushbuttons,
a mechanical "open/closed" position indicator,
a mechanical "charged/discharged" closing spring indicator,
a shunt opening release,
an "end of charging" contact,
a block of auxiliary contacts.
Basic frontal fixed circuit-breaker
Phase distance (mm)
230
250
DE60080
24 kV
16 kA
25 kA
31.5 kA
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
-
-
Extra value for:
DE60132
undervoltage release
(instead of shunt opening release)
Circuit-breaker fitted options
LV connection
DE60153
21-pin LV plug
42-pin LV plug
Monitoring device
DE60135
Pilot module
diagnosis by Schneider Electric expert
Remote control
DE60101
remote control
(electrical motor, gear reducer, shunt closing release, antipumping relay, operation counter)
Fig. 1
shunt opening release (YO2) (fig. 1)
undervoltage release (YN) (fig. 2)
low energy release (MITOP) (fig. 3)
DE60081
DE60102
DE60132
Second opening release
Fig. 2
Fig. 3
Locking / interlocking
DE60136
open position circuit-breaker locking without lock
Ronis or Profalux lock
Indication
DE60092
operation counter
20
Order form
Basic frontal fixed circuit-breaker
Only one box (ticked
or filled in
by
the needed value) have to be considered between
each horizontal line.
A blue box
corresponds to a non priced function.
Quantity
Rated voltage Ur
Rated short-circuit breaking current Isc
Rated normal current Ir
Phase distance (mm)
230
Indicators
IEC standard
labels and push button colours
red-black
ANSI standard
red-black
1st opening release (see possible choice in combination table below)
shunt opening
24 Vdc
110 Vdc
110 Vac (50 Hz)
release (YO1)
48 Vdc
125-127 Vdc
220-230 Vac (50 Hz)
220 Vdc
undervoltage
24 Vdc
110 Vdc
110 Vac (50 Hz)
release (YN)
48 Vdc
125-127 Vdc
220-230 Vac (50 Hz)
220 Vdc
kV
24
kA
A
250
red-green
red-green
120 Vac (60 Hz)
120 Vac (60 Hz)
Circuit-breaker fitted options
LV connection
21 pin LV plug
42 pin LV plug
Pilot monitoring device
Pilot with connecting kit
with LV plug
without LV plug
diagnosis by Schneider Electric expert (separate order)
Remote control
Electrical motor
24… 32 Vdc
110… 127 Vdc/ac
48… 60 Vdc/ac
220… 250 Vdc/ac
Shunt closing release
(YF)
110 Vdc
110 Vac (50 Hz)
120 Vac (60 Hz)
24 Vdc
48 Vdc
125-127 Vdc
220-230 Vac (50 Hz)
220 Vdc
2nd opening release (see possible choice in combination table below)
shunt opening
24 Vdc
110 Vdc
110 Vac (50 Hz)
120 Vac (60 Hz)
release (YO2)
48 Vdc
125-127 Vdc
220-230 Vac (50 Hz)
220 Vdc
undervoltage
24 Vdc
110 Vdc
110 Vac (50 Hz)
120 Vac (60 Hz)
release (YN)
48 Vdc
125-127 Vdc
220-230 Vac (50 Hz)
220 Vdc
low energy release (MITOP)
Locking / interlocking
open position CB locking
Ronis
Profalux
Indication
operation counter (already included if remote control supplied)
Combination table
Shunt opening release YO1
Shunt opening release YO2
undervoltage YN
Mitop
No LV plug or
42-pin LV plug
1
1 1 1
1
1
1
1
21-pin
LV plug
1
1
1
21
Evolis 24 kV frontal
fixed
Separate components
The following components can be
ordered separately and can be adapted
or replaced by the customer
Accessories incorporated in the operating mechanism
Shunt opening release
DE60102
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
50 Hz
50 Hz
60 Hz
AAA10 115
AAA10 116
AAA10 117
AAA10 118
AAA10 119
AAA10 120
AAA10 121
AAA10 122
50 Hz
50 Hz
60 Hz
AAA10 106
AAA10 107
AAA10 108
AAA10 109
AAA10 110
AAA10 111
AAA10 112
AAA10 113
50 Hz
50 Hz
60 Hz
AAA10 124
AAA10 125
AAA10 126
AAA10 127
AAA10 128
AAA10 129
AAA10 130
AAA10 131
Shunt closing release
DE60154
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
Undervoltage release
DE60132
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
DE60133
Electrical motor
24… 32 Vdc
48… 60 Vac/dc
100… 127 Vac/dc
220… 250 Vac/dc
AAA10 027
AAA10 028
AAA10 029
AAA10 030
gear reducer
open position circuit-breaker locking
AAA10 065
AAA10 092
DE60101
DE60136
Other accessories of the operating mechanism
MV and LV connection accessories
200190
200188
MV connection accessories
clusters set (including fingers)
arms set
630-1250 A
2500 A
630-1250 A
2500 A
AAA10 025
AAA10 026
AAA10 022
AAA10 023
LV connection
DE60153
21-pin LV plug
42-pin LV plug
LV connection kit (21 wires)
22
AAA10 031
AAA10 032
59117
Services
The following components can only be adapted or replaced on
site by personnel trained by Schneider Electric:
b Pilot monitoring device,
b remote control (incl.: motor, gear train, shunt closing release, antipumping relay,
operation counter),
b operation counter,
b low energy release (MITOP),
b interlocking kit between circuit-breaker position and LV plug,
b racking device,
b operating mechanism auto-discharge,
b frontal circuit-breaker front cover.
23
Evolis 24 kV frontal
withdrawable
24
PE60041
Contents
Withdrawable version
Main characteristics presentation
p.26
Function description
p.27
Racking in
p.27
LPCT sensors
p.28
MV connections
p.29
LV connections
p.30
Opening circuit
p.31
Remote control
p.32
Indication and locking / interlocking
p.33
Auxiliary wiring diagram
p.34
Dimensions
p.35
Offer structure
p.36
Order form
p.39
Separate components
p.40
Services
p.42
25
Evolis 24 kV frontal
withdrawable
Main characteristics presentation
A fully assembled and tested unit
b Evolis circuit-breakers are actuated by a spring operated mechanism that ensures
operating speed independent of operator action and can be operated without any
auxiliary supply.
When the operating mechanism is motorized, the circuit-breaker can take on remote
control functions and perform re-closing cycles.
b This unit is easy to integrate in a cubicle environment. An Installation Guide
explains the necessary operations in detail.
b This withdrawable unit comprises the circuit-breaker, arms and clusters, racking
truck and its cradle. The cradle and the circuit-breaker can be ordered and delivered
separately.
DE60049
Electrical characteristics according to IEC 62271-100
Phase distance (mm)
Rated voltage 24 kV
230
Isc
250
In
16 kA
25 kA
H
31.5 kA
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
b
b
v
v
b
b
v
v
v
v
v
v
v available end of 2004
Dimensions (mm)
D
H
W
D
W
1309
1188
786
1309
1188
886
145
136
206
148
Weight (Kg)
Circuit-breaker
Cradle
Additional characteristics according to IEC 62271-100
Rated values
Voltage
Insulation voltage:
power frequency withstand voltage
lightning impulse withstand voltage
Frequency
Short time withstand current
Peak withstand current
Short circuit making current
Other characteristics
Operating sequences
Mechanical endurance
Electrical endurance
Number of operations at full Isc value
Capacitive current breaking
Service conditions
Humidity:
average relative humidity
26
Ur
kV rms
24
Ud
Up
fr
Ik/tk
Ip
kV rms
kV peak
Hz
kA
kA peak
kA peak
50
125
50-60
Isc/3s
2.5 & 2.6 Isc
2.5 & 2.6 Isc
class
number of operations
class
16 kA
25 kA
31.5 kA
class
24-hours period
1 month
O-3min-CO-3min-CO
O-0.3s-CO-3min-CO
O-0.3s-CO-15s-CO
M2
10 000
E2
50
50
50
C1-C2 (for some applications)
-25°C to 40°C
< 95%
< 90%
Function description
racking in
200128
Composition
b
v
v
v
The "racking in" function is provided by:
the racking truck supporting the circuit-breaker (mobile part),
the cradle including the bushings (fixed part),
the LV plug.
Operating procedure
Service position
200149
b The circuit-breaker moves through 3 stable positions:
v service position:
circuit-breaker racked in and locked in place; low voltage plug connected,
v test position:
circuit-breaker racked out and locked in place; low voltage plug connected,
v extracted position:
the circuit-breaker can be unlocked and extracted from the cubicle,
with no interlocking.
Test position
2000148
Safety functions
A propulsive system combined with a screw-shaft makes racking in and racking out
easier.
b Interlocking
In accordance with IEC standards 62271-100 and 62271-200, the following
interlockings are provided:
v racking in or out are impossible unless the circuit-breaker is in the open position,
v racking in the circuit-breaker is impossible unless the LV plug is connected,
v disconnecting the LV plug is impossible unless the circuit-breaker is racked out.
DE60114
Extracted position
In addition the truck is equipped with a device that allows circuit-breaker racking in
to be interlocked with the cubicle door (which must be specially designed):
v It is only possible to rack in the circuit-breaker if the door is closed,
v the door can only be opened with the circuit-breaker racked out.
b Earthing is achieved throughout the whole racking in operation by the mean of the
wheels of the racking truck. Additional earthing device can be supplied as an option.
b Protective shutters on the cradle prevent access to the racking fingers when the
device is extracted (protection index: IP2X).
b For maintenance or test purposes, it is possible to:
v padlock the shutters in the closed position,
v unlock the shutters mechanism to access the fixed contacts, and insert a screen
to prevent the lived set of fixed contacts being exposed.
DE60138
b A fool-proof protection enables cradle and circuit-breaker to be matched up.
This system is mounted on the circuit-breaker. Part of it has to be assembled by
the panel builder on the cradle side.
b Earthing switch
It can be fixed on the cradle, allowing proper interlocking between the circuit-breaker
and the earthing switch, (see detailed description in "Earthing switch and cubicle
components" catalogue).
b Anti-drop function
This function ensures the safety of the operator during the extraction of the
circuit-breaker.
Accessories
DE55137
MT66049
Auto-discharge function
Racked in/out position
Earthing sliding device
b 4 racked in/racked out position contacts.
b Additional earthing device (copper brush).
b Core sensors LPCT type, directly fitted on the bushings of the cradle.
b Auto-discharge function:
the spring of the circuit-breaker operating mechanism is automatically discharged
when the circuit-breaker is extracted from the cubicle. This feature avoids
unexpected closing of the circuit-breaker.
27
Evolis 24 kV frontal
withdrawable
Function description
LPCT sensors
The LPCT’s are the best way to increase
the effectiveness of the protection chain
and simplify the selection.
Function
b These Low Power Current Transducers (LPCT) provide accurate current
measurement to the protection function when an Evolis circuit-breaker is associated
with the Sepam relay range.
DE60099
b They comply with IEC 60044-8 standard.
Composition
b Two types of LPCT are available:
v LPCT for bushings,
v LPCT for cubicles.
LPCT for bushings (TLP Type)
b The sensor is delivered with 5m of cable and connector that allows direct
connection to the Sepam unit.
DE60097
Mechanical characteristics
(LPCT for bushings)
b Mounted directly on the Evolis withdrawable circuit-breaker cradle.
The sensors are simply located on the bushings and fixed using three screws.
Each sensor covers the full operating range of the corresponding circuit-breaker.
b Connection to the Sepam is achieved using an shielded cable which is attached to
each sensor.
LPCT for cubicle (CLP Type)
Electrical characteristics
b In compliance with IEC 60044-8 standard, defining Low Power current Transducer
with voltage output.
b Usable for nominal currents of 25 A to 2500 A.
b Class 0.5 throughout the range.
b Current sensors deliver a voltage output at a ratio of 100 A/22.5 mV.
Common features
Rated primary current
Rated secondary output (at 100A)
Accuracy class for measuring
Accuracy class for protection
Burden
Frequency
100 A
22.5 mV
0.5
5P
2 kΩ
50 / 60 Hz
TLP190
On the bushings
On the bushings
Rated extended primary current
Accuracy limit factor
Rated short time thermal current
Highest voltage for equipment
Rated power frequency withstand volt.
Rated lighting inpulse withstand voltage
28
1250 A
250
25 kA / 3s
24 kV
50 kV
125 kV
2500 A
315
31.5 kA / 3s
24 kV
50 kV
125 kV
DE60100
TLP160
In the cubicle
DE60099
CLP3
In the cubicle
DE60098
CLP2
DE60097
Specific features
Assembly
1250 A
250
25 kA / 3s
0.72 kV
3 kV
2500 A
315
31.5 kA / 3s
0.72 kV
3 kV
Function description
MV connections
Connection
DE60134
b Customer connection is easily achieved outside the cradle:
v on vertical copper terminals integrated in the bushing.
DE60158
Type tested connection configuration are shown in the Installation Guide.
Field deflectors
The field deflectors are to be fitted at the end of the bushings. They are necessary in
case of installation of the cradle within a compartmented cubicle.
For other applications, tested configurations are described in the Installation Guide.
29
Evolis 24 kV frontal
withdrawable
Function description
LV connections
DE60155
Main functions
b With the basic withdrawable circuit-breaker, LV wiring is produced via an
LV plug.
b The LV plug includes:
v the fixed part (male) fitted on the circuit-breaker and fully wired to the terminal
block of the operating mechanism,
v the mobile part (female) compatible with the male part.
Two versions of LV plug are available
b A 21-pin LV plug, allowing to connection of
v a shunt opening release YO1,
v a remote control mechanism (electrical motor, shunt closing release YF,
antipumping relay),
v the Pilot monitoring device,
v maximum number of auxiliary contacts: 3 NC - 3 NO - 1 CHG
(see details in chapter "Open/closed auxiliary contacts").
b A 42-pin LV plug, allowing to connect
v an opening release (shunt opening release or under-voltage release),
v a second opening release (shunt opening release YO2, under-voltage release YN
or low energy release MITOP),
v a remote control mechanism (electrical motor, shunt closing release,
antipumping relay)
v the Pilot monitoring device,
v maximum number of auxiliary contacts: 5 NC - 6 NO - 1 CHG
(see details in chapter "Open/closed auxiliary contacts").
b Interlocking function
In order to comply with IEC standard 62271-200, an interlocking feature prevents:
v racking in when the LV plug is not connected.
v disconnection of the LV plug when the circuit-breaker is in racking in position.
LV wiring kit
b A kit including 21 wires (2 meters long) fitted with pin suitable for the plug can be
supplied for connection to the LV compartment of the cubicle.
This arrangement provides an auxiliary supply connection with a high level of
electrical safety.
30
Function description
opening circuit
DE60161
Composition
b
v
v
v
v
(2)
(1) or (3)
The opening circuit can be achieved by the followings units:
shunt opening release (YO1),
second shunt opening release (YO2),
under voltage release (YN),
low energy release (MITOP).
Please check in the combination table the right associations of different releases.
Note: this table is present in order form at the end of this catalogue.
Shunt opening release (YO1 et YO2)
b This causes the instant opening of the circuit-breaker when energised.
Characteristics
Supply
Threshold
VAC
VDC
VAC
VDC
Consumption
Operating mechanism
see order form
0.7 to 1.1 Un
0.85 to 1.1 Un
160 VA
50 W
DE60094
Under voltage release (YN)
(1) Shunt opening release
b An under voltage release operates to open the circuit-breaker when the voltage at
the terminals of the release falls below 35% of its rated voltage, even if the fall is slow
and gradual.
On the other hand, it does not operate the circuit-breaker when the voltage at its
terminals exceeds 70% of its rated supply voltage.
Circuit-breaker closing is possible when the values of the voltage at the terminals of
the release are greater than or equal to 85% of its rated voltage.
Closing is impossible when the voltage at the terminals is lower than 35% of its
rated supply voltage.
DE60089
Characteristics
Supply
Threshold
Consumption
(2) Under voltage release
pick-up
hold
opening
closing
VAC
VDC
VAC
VDC
see order form
0.35 to 0.7 Un
0.85 Un
400 VA
100 W
100 VA
10 W
DE60091
Low energy release (MITOP)
b This specific release comprises a low energy consumption unit and is used
specifically with self-powered relay SEPAM 100LA ("REFLEX MODULE"), or VIP
relay.
(3) Low energy release
Characteristics
Supply
Threshold
direct current
0.6 A < I < 3 A
Any tripping caused by the Mitop release is indicated momentarily by an SDE type
changeover contact.
31
Function description
remote control
Evolis 24 kV frontal
withdrawable
Function
DE60160
(6)
(5)
b The remote control enables remote opening and closing of the circuit-breaker.
Composition
(8)
b
v
v
v
v
The remote control comprises:
electrical motor and gear reducer,
a shunt closing release (YF),
an antipumping relay,
an operation counter.
(7)
(9)
(4)
Operating mechanism
Electric motor and gear reducer
DE60093
b The electrical motor arms and rearms the energy storage springs as soon as the
circuit-breaker is closed. This enables instant reclosing of the device after opening.
The arming lever is only used as back up control in the absence of an auxiliary
voltage.
M3 contact indicates end of charging.
(4) Electric motor and gear reducer
Characteristics
Supply
Consumption
V AC
V DC
V AC
V DC
50/60
see order form
see order form
380 VA
380 W
DE60151
Shunt closing release (YF)
b This causes the remote closing of the circuit-breaker when the operating
mechanism is armed.
Characteristics
Supply
(5) Shunt closing release
Threshold
Consumption
YF
VAC 50/60 Hz
VDC
VAC
VDC
see order form
see order form
0.85 to 1.1 Un
160 VA
50 W
DE60095
Antipumping relay
b The antipumping relay avoids unwanted closing and tripping within a short interval.
This function gives absolute priority to the opening order and blocks closing.
This prevents the device from being locked in an indefinite opening-closing cycle.
(6) Antipumping relay
32
Function description
indication and locking / interlocking
DE60087
Operation counter
b The operation counter is visible from the front face.
It displays the number of operating cycles that the device has performed.
(7) Operation counter
DE60152
Open/closed auxiliary contacts
b The number of available contacts depends on the fitted options on the operating
mechanism.
(8) Auxiliary contacts
b In its basic configuration, the operating mechanism of the circuit-breaker
comprises a total of:
v 5 normally closed contacts (NC),
v 6 normally open contacts (NO),
v 1 changeover contact (CHG).
b Use of auxiliary contacts is given in the following table:
Option
Remote control
Shunt opening release (each)
Undervoltage release
Low energy release MITOP
Trip circuit supervision
NC contact
1
0
0
0
1
NO contact
1
1
0
0
0
To find out the final number of contacts available, the above quantity
must be deducted from the total quantity (5 NC + 6 NO + 1 CHG) included in the
circuit-breaker.
(Example: a circuit-breaker equipped with a remote control and a shunt opening release
has 4 NC + 4 NO + 1 CHG available contacts. With an under-voltage release instead of
a shunt release, this circuit-breaker has 4 NC + 5 NO + 1CHG available contacts).
b
v
v
v
When the 21-pin LV plug is used, the maximum number of available contacts is:
3 NC,
3 NO,
1 changeover.
(Instead of 5NC-6NO-1CHG with the 42-pin LV plug).
Contact characteristics
Rated current
Breaking capacity
AC
DC
220 V (cos ϕ ≥ 0.3)
110/220 V (L/R ≤ 0.02 s)
10 A
1A
0.3 A
DE60124
Locking of the circuit-breaker
in the open position
b This key lock allows the locking of the circuit-breaker in the "open" position by
the means of a key.
b The circuit-breaker is locked in the "open" position by blocking the opening
pushbutton in the "pushed-in position".
b The key lock is of Profalux or Ronis captive key type.
(9) Locking kit
33
Function description
auxiliary wiring diagram
Evolis 24 kV frontal
withdrawable
DE60123
Auxiliary wiring diagram (principle)
CLOSE CB
OPEN CB
M
YF +
anti-pumping
motor
shunt closing
+ anti-pumping
system
remote control
34
PILOT
YO1
or
YO2
YM
monitoring
device pilot
shunt
opening
release
undervoltage
release
MITOP
low energy
release
(MITOP)
changeover
contact
NO
NC
contacts contacts
230
230 163
DE60065
230 mm phase distance
DE60063
Dimensions
1188
400
473.5
250
288
1309
1400
250
193
DE60065
250 mm phase distance
DE60064
786
1188
400
473.5
886
288
1309
1400
35
Evolis 24 kV frontal
withdrawable
Offer structure
The basic frontal withdrawable circuit-breaker includes:
b
b
b
b
b
b
b
b
b
b
b
b
6 power connections including arms and clusters
a racking truck
a manual operating mechanism (spring type)
closing and opening pushbuttons
a mechanical "open/closed" position indicator
a mechanical "charged/discharged" closing spring indicator
a shunt opening release
an "end of charging" contact
a block of auxiliary contacts
a 21-pin LV plug
an interlocking kit between the LV plug and the circuit-breaker position
antidrop function.
Basic frontal withdrawable circuit-breaker
Phase distance (mm)
230
250
DE60165
24 kV
16 kA
25 kA
31.5 kA
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
-
Extra value for:
DE60132
DE60153
undervoltage release (fig. 1) (instead of shunt opening release)
LV plug 42-pin (fig. 2) (instead of 21 pin)
Fig. 1
Circuit-breaker fitted options
Monitoring device
DE60135
Pilot module
diagnosis by Schneider Electric expert
Remote control
DE60101
remote control
(electrical motor, gear reducer, shunt closing release, antipumping relay, operation counter)
Fig. 1
Fig. 2
DE60081
DE60132
DE60102
Second opening release
shunt opening release (YO2) (fig. 1)
undervoltage release (YN) (fig. 2)
low energy release (MITOP) (fig. 3)
Fig. 3
Locking / interlocking
DE60136
open position circuit-breaker locking without lock
Ronis or Profalux lock
Indication
DE60092
operation counter
36
Circuit-breaker fitted options (cond’t)
Safety device
DE60142
operating mechanism auto discharge *
230 mm phase distance circuit-breaker
250 mm phase distance circuit-breaker
* available end of 2004
Rack-in / rack-out operation
200295
operating crank
Cradle
Phase distance
DE60084
phase distance
230 mm
250 mm
Cradle accessories
DE55137
MT66049
racked in/out position contacts (fig. 1)
earthing sliding device (fig. 2)
Fig. 2
LPCT tore sensor for 230 mm phase distance cradle (TLP 160)
LPCT tore sensor for 250 mm phase distance cradle (TLP 190)
DE60107
DE60108
Fig. 1
TLP 160
TLP 190
37
Evolis 24 kV frontal
withdrawable
38
Order form
Basic frontal withdrawable circuit-breaker
Only one box (ticked
or filled in
by
the needed value) have to be considered between
each horizontal line.
A blue box
corresponds to a non priced function.
Quantity
kV
Rated voltage Ur
24
kA
Rated short-circuit breaking current Isc
A
Rated normal current Ir
Indicators
red-black
IEC standard
labels and push button colours
red-green
ANSI standard
red-black
red-green
1st opening release (see possible choice in combination table below, 21-pin or 42-pin)
shunt opening
24 Vdc
110 Vdc
110 Vac (50 Hz)
120 Vac (60 Hz)
release (YO1)
48 Vdc
125-127 Vdc
220-230 Vac (50 Hz)
220 Vdc
undervoltage
24 Vdc
110 Vdc
110 Vac (50 Hz)
120 Vac (60 Hz)
release (YN)
48 Vdc
125 Vdc
220-230 Vac (50 Hz)
220 Vdc
Circuit-breaker fitted options
LV connection
42 pin LV plug (instead of 21)
Pilot monitoring device
Pilot with connecting kit
with LV plug
diagnosis by Schneider Electric expert (separate order)
Remote control
Electrical motor
24… 32 Vdc
48… 60 Vdc/ac
Shunt closing release
110 Vdc
110 Vac (50 Hz)
(YF)
24 Vdc
48 Vdc
125-127 Vdc
220-230 Vac (50 Hz)
220 Vdc
2nd opening release (see possible choice in combination table below)
shunt opening
24 Vdc
110 Vdc
110 Vac (50 Hz)
release (YO2)
48 Vdc
125-127 Vdc
220-230 Vac (50 Hz)
220 Vdc
undervoltage
24 Vdc
110 Vdc
110 Vac (50 Hz)
release (YN)
48 Vdc
125-127 Vdc
220-230 Vac (50 Hz)
220 Vdc
low energy release (MITOP)
Locking / interlocking
open position CB locking
Ronis
Indication
operation counter (already included if remote control supplied)
Safety device function
auto discharge (available end of 2004)
Earthing
earth sliding device
Operation
operating crank
without LV plug
110… 127 Vdc/ac
220… 250 Vdc/ac
120 Vac (60 Hz)
120 Vac (60 Hz)
120 Vac (60 Hz)
Profalux
Cradle
Quantity
Rated current
Cradle accessories
Rack in/rack out position contact
LPCT-TLP
up to 1250 A
and 25 kA
above
up to 1250 A
and 25 kA
above
Combination table
Shunt opening release YO1
Shunt opening release YO2
undervoltage YN
Mitop
No LV plug or
42-pin LV plug
1
1 1 1
1
1
1
1
21-pin
LV plug
1
1
1
39
Evolis 24 kV frontal
withdrawable
Separate components
The following components can be
ordered separately and can
be adapted or replaced
by the customer
MV and LV connection accessories
MV connection accessories
200190
200188
clusers set (including fingers)
630-1250 A
2500 A
630-1250 A
2500 A
AAA10 025
AAA10 026
AAA10 022
AAA10 023
21 pin LV plug
42 pin LV plug
630-1250 A
2500 A
AAA10 031
AAA10 032
bus section truck
1250 A / 230 mm
2500 A / 250 mm
230 mm
250 mm
AAA10 061
AAA10 062
AAA10 063
AAA10 064
AAA10 089
59449
630 - 1250 A
2500 A
630-1250 A
2500 A
AAA10 016
AAA10 018
AAA10 020
AAA10 021
59173
LPCT toroidal sensor
TLP 160 (up to 1250 A)
TLP 190 (above)
AAA10 094
AAA10 095
phase distance
230 mm
250 mm
AAA10 015
AAA10 017
arms set
DE60153
LV connection
200295
200354
Other circuit-breaker accessories
busbar earthing truck
circuit-breaker insertion slope
operating crank for racking in/out
Fig. 2
DE60107
DE60108
Fig. 1
TLP 160
1 bushing kit for cradle (fig.1)
DE55137
DE60145
MT66055
Accessories fitted on the cradle
Fig. 3
6 field deflectors for cradle bushings
(fig.2)
4 racked in/out position contacts (fig.3)
(to be installed in the cradle)
TLP 190
DE60141
Cradle without bushings
40
The following components can be
ordered separately and can
be adapted or replaced
by the customer
Accessories incorporated in the operating mechanism
Shunt opening release
DE60102
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
50 Hz
50 Hz
60 Hz
AAA10 115
AAA10 116
AAA10 117
AAA10 118
AAA10 119
AAA10 120
AAA10 121
AAA10 122
50 Hz
50 Hz
60 Hz
AAA10 106
AAA10 107
AAA10 108
AAA10 109
AAA10 110
AAA10 111
AAA10 112
AAA10 113
50 Hz
50 Hz
60 Hz
AAA10 124
AAA10 125
AAA10 126
AAA10 127
AAA10 128
AAA10 129
AAA10 130
AAA10 131
Shunt closing release
DE60154
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
Undervoltage release
DE60132
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
DE60133
Electrical motor
24… 32 Vdc
48… 60 Vac/dc
100… 127 Vac/dc
220… 250 Vac/dc
AAA10 027
AAA10 028
AAA10 029
AAA10 030
gear reducer
open position circuit-breaker locking
AAA10 065
AAA10 092
DE60101
Other accessories of the operating mechanism
41
Evolis 24 kV frontal
withdrawable
Services
The following components can only be adapted or replaced on
site by personnel trained by Schneider Electric:
b Pilot monitoring device,
b remote control (incl.: motor, gear reducer, shunt closing release, antipumping
relay, operation counter),
b operation counter,
b low energy release (MITOP),
b interlocking kit between circuit-breaker position and LV plug,
b racking device,
b operating mechanism auto-discharge,
b frontal circuit-breaker front cover.
42
PE60053
Evolis Pilot monitoring
device
Contents
Function description
p.44
Two specific features
p.44
Pilot main characteristics
p.44
Detailed features
p.44
Local or remote data collection
p.45
Easy to install module
p.45
Added at any time
p.45
Operation and service
p.45
Pilot
43
Evolis Pilot monitoring
device
Function description
Fitted on the circuit-breaker,
the Pilot monitors its operating
conditions.
The Pilot circuit-breaker monitoring device
has two specific features
Monitoring operating conditions
DE60053
The device monitors external conditions and provides alarms if they are out of the
specified range.
Recording circuit-breaker operating data
Similarly to an aircraft black box the monitor device logs the circuit-breaker’s key data
over time, allowing a diagnosis on its mechanical conditions.
Pilot main characteristics
Characteristics
DE60058
Energy
supply
Supply
Service temperature
Consumption
Measurement inputs
YM
V AC 50/60 Hz
V DC
°C
VA or W
V AC 50/60 Hz
V DC
Events recording capacity
Conditions record capability
Maintenance notes record capacity
YL
100/250
24/250
100/250
24/250
1000
1000
256 (x 256 characters)
-15% to +10%
-30% to +10%
-25°C to +70°C
>3
-15% to +10%
-30% to +10%
M
Communication
Detailed features
DE60055
Monitoring operating conditions
Pilot
ON
Reset alarm
Aux. voltage
θ °C
OK
45°C
50°C
40°C
55°C
N > 20000
Operating
I > 360j
b The module continuously monitors
v opening auxiliary voltage,
v circuit-breaker ambient temperature,
v number of operations,
v time between operations,
v and sends alarms if the set points are exceeded.
b Alarms are visible on the front of the device and can also be transferred to
the LV compartment, or supervision system.
b Operating conditions are recorded: minimum and maximum values of auxiliary
voltage and ambient temperature are time-tagged and stored every 24h.
Recording circuit-breaker data
b All circuit-breaker events are time-tagged and stored (opening, closing, motor
charging, energizing, voltage set point, temperature set point, number of operations,
time between operations).
b A circuit-breaker expert can analyse the stored data in order to check the correct
mechanical functioning of the circuit-breaker, 1000 events are stored in the
module.
Servicing note-pad
b The device incorporates this useful feature to record any information related to
servicing the circuit-breaker (250x250 - character note-pad).
44
PE60037
Local or remote data collection
DE60056
Local use
4
We
bs
er
r
ve
RS
E th
85
ernet network
Alarms are displayed on the device itself.
A dry contact relay collates the faults and can be wired to the low voltage
compartment.
A laptop user-machine Interface can be used to set parameters and to display
and upload data.
Pilot
ON
θ °C
OK
Reset alarm
Aux. voltage
45°C
50°C
40°C
55°C
N > 20000
Operating
I > 360j
Remote use
The monitoring device can be connected to a supervisor or concentrator
for connection to the Web via a local RS485 Modbus network.
The supervisor can display, process and acknowledge alarms.
Data is then either processed in the supervision system or in the remote
web-enabled system.
DE60057
Easy to install module
b The module is inserted in the special housing reserved for it on the front of the
circuit-breaker.
This module may be added at any time
during the circuit-breaker's service life
b The module may be factory-mounted within the circuit-breaker: connection and
parameter setting, are done by Schneider Electric.
b The module may be added after circuit-breaker commissioning: connection,
parameter setting and testing, are done by a specialized service provider (Schneider
Electric or other).
The customer is provided with the product manual and the CDrom containing the
computerized manual and UMI PC software.
Operation and service
The "Pilot" monitoring device can be used on two levels:
b Information on operating conditions.
b Diagnosis of mechanical circuit-breaker conditions: performed by a circuit-breaker
expert (from Schneider Electric), by analyzing the recorded data.
45
Note
46
Note
47
Note
48
Postal address
MV department
F-38050 Grenoble cedex 9
Tel: +33 (0)4 76 57 60 60
As standards, specifications and designs change from time to time, please ask for confirmation of
the information given in this publication.
http://www.schneider-electric.com
RSC Nanterre B 954 503 439
ART 41172
Publishing: Schneider Electric SA
Technical writing: P. Andréani
Design, production: HeadLines
Printing: Imprimerie du Pont de Claix
02-04
AMTED302014EN © 2004 Schneider Electric - All rights reserved