Electric Power Transmission and Distribution Solutions of exercise 2 Prof. Göran Andersson ETH Zurich Autumn term 2008 Exercise 1 a) Equivalent circuit diagrams Generator UG a Overhead line ZOL b Load ZL G UG,ph a ROL jXOL b RL jXL R UG S c d T UR IR ROL jXOL RL jXL R c d Figure 1: Generator-Line-Load. Top: Single phase diagram; Middle: Threephase equivalent circuit; Bottom: Single phase equivalent circuit. Figure 1 shows the single phase diagram as well as the three-phase and the single phase equivalent circuits. The points c and d have the same poten1 tial under balanced conditions and can therefore be linked in the one-phase equivalent circuit. b) Phase currents; active, reactive and apparent power; load factor Sense of rotation +w 0° UR -120° UT US Figure 2: Phasor diagram of the phase voltages. We know the absolute value of the generator phase-to-phase voltage. √ The√generator phase voltage (voltage to neutral) is thus UG,ph = UG / 3 = 20/ 3 kV = 11.55 kV . In a balanced three-phase system, all phase voltages have the same amplitude and each phase is shifted by ±120◦ with respect to the other two. The reference angle of the voltage phasors and the sense of rotation can be chosen at will. We put the voltage phasor of phase R in the real axis (θR = 0◦ ) and define the positive sense of rotation ω as shown in figure 2. The voltages of the other two phases S and T are consequently shifted by −120◦ and −240◦ with respect to phase R: U R = UG,ph ∠0◦ = 11.55∠0◦ kV (1) ◦ ◦ (2) ◦ ◦ (3) U S = UG,ph ∠ − 120 = 11.55∠ − 120 kV UT = UG,ph ∠ − 240 = 11.55∠ − 240 kV Generally the phase current is I ph = U ph Z ph (4) That means we also have to calculate the impedance. The total impedance of one phase is Z ph = Z OL + Z L = 2.5 + 110 + j (3.0 + 50) = 112.5 + j53 Ω (5) Since we assume balanced conditions, the impedance has the same value in 2 all phases. According to equation (4), we obtain for the phase currents UR 11.55 kV∠0◦ = 92.85∠ − 25.23◦ A = Z ph 112.5 + j53 Ω = 92.85∠ − 145.23◦ A IR = IS IT ◦ = 92.85∠94.77 A (6) (7) (8) In a balanced system, the phase currents also have the same amplitude and are also shifted by ±120◦ with respect to the other two currents. The total complex power of the load corresponds to the triple value of the complex power in one phase (R): S L = 3 · U L,R I ∗R = 3 · I R Z L I ∗R = 3 · (92.85∠ − 25.23◦ ) (110 + j50) (92.85∠ + 25.23◦ ) MVar} = |2.85{zMW} +j 1.29 | {z PL (9) QL The active and reactive power of the load (PL and QL ) result from the representation of the complex power as real and imaginary part. The values apply to the total three-phase load. The apparent power is the absolute value of the complex power and becomes SL = |S L | = 3.13 MVA. The power factor of the load can be derived from the phasor diagram of the load impedance (see figure 3): cos ϕL = RL 110 = 0.9104 = |Z L | |110 + j50| (10) ZL jXL jL RL Figure 3: Phasor diagram of the load impedance. c) Compensation with capacities To increase the power factor of the load, one can connect capacities in parallel to the load impedances. The reactive power generated by the capacity compensates a part of the inductive reactive power consumed by the load. As shown in figure 4, the capacities can be connected in two ways in parallel to the load, either in Y - or ∆-connection. At first, we consider the Y -connection; that way of connection is easier to deal with because the Y connected capacities are in parallel to the load impedances in the one-phase equivalent circuit (the points d and e have the same potential). 3 RL b jXL d CY e CD RL jXL CY d e Figure 4: Top: Capacities for compensation of inductive reactive power in Y - or ∆-connection. Bottom: One-phase equivalent circuit with capacities in Y -connection. The power factor shall be increased to 0.98. The corresponding phase angle ϕ′L can be calculated from the compensated load impedance (load k capacity): ¶ µ ℑ{Z ′L } ′ = arccos(0.98) (11) ϕL = arctan ℜ{Z ′L } where Z ′L = jXCY k Z L (12) Z ′L is the compensated load impedance, XCY = −1/(ωCY ) is the reactance of the capacity. We can determine the value of the capacity by calculating 4 the real and imaginary part of Z ′L : Z ′L = jXCY Z L jXCY (RL + jXL ) = · jXCY + Z L RL + j(XL + XCY ) | {z } X RL XCY (X − XL ) + jXCY (XXL + 2 + X2 RL RL XCY (X − XL ) ⇒ ℜ{Z ′L } = 2 + X2 RL = ⇒ ℑ{Z ′L } = RL − jX R − jX | L {z } conj. compl. expansion 2) RL 2) XCY (XXL + RL 2 + X2 RL (13) (14) (15) From equation (11) we obtain tan(ϕ′L ) = tan(arccos(0.98)) = 2) XCY (XXL + RL RL XCY (X − XL ) (16) We solve this equation for XCY and obtain 2 + X2 RL 1102 + 502 L = = −527.86 Ω RL · tan(ϕ′L ) − XL 110 · tan(arccos(0.98)) − 50 (17) Eventually, the capacity becomes XC Y = CY = − 1 1 = = 6.03 µF ωXCY 2π50 · 527.86 (18) As one can see in figure 2.10 on p. 34 in the lecture notes, the value of the capacity in ∆-connection is C∆ = CY = 2.01 µF 3 (19) We again consider figure 4. The phase-to-phase voltage is applied to the capacities C∆ , whereas the voltage to neutral is applied to CY . The capacities are smaller in the case of the ∆-connection. In that way, the 1 reactance becomes bigger (XC = − ωC ). Due to the higher phase-to-phase voltage, the smaller capacities C∆ generate the same reactive power in ∆connection as the bigger capacities CY in Y -connection. d) Comparison of the line losses To determine the line losses, at first we have to calculate the current in the balanced state. For that we need the impedance of the compensated load: Z ′L = −j527.86(110 + j50) jXCY Z L = = 127.47 + j25.89 Ω jXCY + Z L 110 + j(50 − 527.86) 5 (20) The absolute value of the phase current then results as UR 11.55 kV = 127.47 + 2.5 + j(25.89 + 3.0) Ω + Z OL = 84.68 − j18.82 A I ′R = ′ IR = Z ′L |I ′R | = 86.75 A (21) (22) The active and reactive power losses on the overhead line are then ′ ′ 2 POL = 3 · (IR ) R = 3 · 86.752 · 2.5 = 56.44 kW | {z OL} Q′OL = 3· per phase ′ 2 (IR ) XOL | {z per phase } = 3 · 86.752 · 3.0 = 67.73 kVar (23) (24) In the uncompensated state, i.e. without capacities, the losses are higher: 2 = 3 · 92.852 · 2.5 = 64.66 kW POL = 3 · IR R | {zOL} QOL = 3 · per phase 2 IR XOL | {z } = 3 · 92.852 · 3.0 = 77.59 kVar (25) (26) per phase e) Comparison of the load voltages The load phase-to-phase voltage in the compensated state results from √ √ U ′L = 3 · I ′R Z ′L = 3 · (84.68 − j18.82 A)(127.47 + j25.89 Ω) | {z } phase voltage ◦ = 19.54∠ − 1.05 kV (27) And without compensation: √ √ 3 · I R Z L = 3 · (92.85∠ − 25.23◦ A)(110 + j50 Ω) UL = | {z } phase voltage ◦ = 19.43∠ − 0.79 kV (28) f) Effects of the compensation • The phase current is reduced, by that • line losses are reduced and • the amplitude and phase angle of the load voltage increase Exercise 2 We consider the transmission system from figure 5 consisting of a generator, transformer-line-transformer and a load. 6 Generator Transformer 1 UG Overhead line ZOL Transformer 2 Load ZL G 1 2 3 Figure 5: Power transmission with transformer-load-transformer. a) Impedances in p.u. As demanded, we choose one single base power SB = 10 MVA for the entire system. Then we choose a base voltage for section 2: UB2 = 138 kV. According to the transformation ratios of the transformers, we define UB1 = 13.8 kV and UB3 = 69 kV. The base values for the impedances now result from the base values for power and voltages: ZB3 = ZB2 = 2 UB3 690002 = 476 Ω ⇒ z L = 0.63 p.u. = (29) SB 107 2 UB2 1380002 = 1904 Ω ⇒ z OL = 0.00525 + j0.0525 p.u.(30) = SB 107 Transformer 1 has a nominal voltage of 13.2 kV (in section 1) and a nominal power of 5 MVA; we now want to calculate its impedance in p.u. related to UB1 = 13.8 kV and SB = 10 MVA: µ ¶ µ ¶ µ ¶ µ ¶ 13.2 kV 2 SB 13.2 2 10 xT 1 = XT 1 = 0.1 = 0.183 p.u. UB1 5 MVA 13.8 5 (31) The inductivity of transformer 2 does not have to be recalculated because the chosen base values for voltage and power correspond to the nominal quantities: xT 2 = 0.08 p.u. (32) Eventually, we have to relate the generator voltage to the base voltage: 13.2 = 0.96 p.u. (33) 13.8 The angle of uG can be chosen arbitrarily; for the sake of simplicity we choose 0◦ : uG = 0.96∠0◦ p.u. |uG | = b) Single phase equivalent circuit The deduction of the single phase equivalent circuit of a balanced threephase system is discussed on p.33 of the lecture notes. Figure 6 shows the single phase equivalent circuit of the system from figure 5. The points k, l, m and n correspond in both figures to the transformer primary and secondary. 7 Generator iph uph Transformer 1 jxT1 k Overhead line zOL Transformer 2 jxT2 m l Load n zL Figure 6: Single phase equivalent circuit with p.u. values. c) Phase currents With the help of figure 6, we can now calculate the phase current in p.u.: iph = uph 0.96 = 1.35∠ − 26.4◦ p.u. = jxT 1 + z F + jxT 2 + z L 0.709∠26.4◦ (34) To obtain the actual phase currents (in A) in the sections 1, 2 and 3, we have to multiply with the respective base value; this base value is the quotient of the base power and the base voltage. However, we have to take into consideration that we now calculate per phase. This means we have to take phase values for the base power and the base voltage: IBi = SB /3 S √ =√ B UBi / 3 3UBi (i = 1, 2, 3) (35) We obtain for the phase currents in sections 1, 2 and 3: ¯ ¯ 107 · 1.35 = 564.4 A Iph1 = IB1 ¯iph ¯ = √ 3 · 13800 ¯ ¯ 107 Iph2 = IB2 ¯iph ¯ = √ · 1.35 = 56.4 A 3 · 138000 ¯ ¯ 107 Iph3 = IB3 ¯iph ¯ = √ · 1.35 = 112.9 A 3 · 69000 (36) (37) (38) d) Complex power The complex load power in p.u. is calculated as follows: sL = iph i∗ph · z L = 1.352 · 0.63 = 1.147 p.u. (39) By multiplication with the base value, we obtain S L = sL · SB = 1.147 · 107 = 11.47 MW (40) As the load impedance is a purely ohmic resistance, ℑ (S L ) = 0, i.e. only active power is consumed. 8 Exercise 3 How can the electric field strength on the conductor surface be reduced? Conductor voltage: The higher the voltage, the higher the electric field strength on the conductor surface. To reduce the electric field strength, one would have to reduce the voltage. Geometry of the line towers, arrangement of the conductors: The longer the distance between the conductors and between earth and conductors, the smaller the electric field strength. Cross section and form of the conductors: The smoother and the cleaner the conductor surface, locally high electric field strengths will occur to a lesser extent. Sharp edges stemming from the production process and dirt on the conductor surface (e.g. metal cuttings) can lead to locally high electric field strengths and can thus favor corona discharges. The distribution of the whole conductor cross section on several bundle conductors leads to an increase of the equivalent conductor radius and thus to a reduction of the electric field strength. A further possibility is to treat the conductor with a special coating that accelerates the draining of water; with that, local rises of the electric field strength can be prevented. See also: http://www.eeh.ee.ethz.ch/hvl/forschung/conor.html. 9