Chiller Replacement Contractor`s Guide

advertisement
CHILLER REPLACEMENT
CONTRACTORS GUIDE
YCAL – 15 to 65 TONS
AIR COOLED SCROLL CHILLER
YLAA – 70 to 175 TONS
AIR COOLED SCROLL CHILLER
YVAA – 150 to 500 TONS
AIR COOLED SCREW CHILLER
YCWL – 50 to 200 TONS
WATER COOLED SCROLL CHILLER
AIR-COOLED
YCAL
15 TO 40
Pages 12-23
YCAL
41 TO 65
Pages 24-29
CHILLER REPLACEMENT
CONTRACTORS GUIDE
YLAA
70 TO 90
Pages 36-43
YLAA
91 TO 130
YCAL – 15 to 65 TONS
AIR COOLED SCROLL CHILLER
YLAA – 70 to 175 TONS
AIR COOLED SCROLL CHILLER
Pages 44-53
YLAA
131 TO 175
Pages 54-63
YVAA
150 TO 200
Pages 68-73
YVAA
201 TO 500
Pages 74-85
YVAA – 150 to 500 TONS
AIR COOLED SCREW CHILLER
YCWL – 50 to 200 TONS
WATER COOLED SCROLL CHILLER
WATER COOLED
YCWL
50 TO 90
Pages 92-109
YCWL
91 TO 130
Pages 110-117
YCWL
131 TO 200
Pages 118-125
In-stock Chillers Ready for Quick Shipment
When You Need Cooling Fast!
Complete packages for quick ‘Plug & Play’ installation
Unit Benefits
Air-cooled Scroll Chillers
Air-cooled Screw Chillers
Air-cooled chillers using scroll-compressor technology ranging from 15 to 175 tons. Standard feature include:
Air-cooled chillers using YORK® VSD Screw technology ranging from 150 to 500 tons. Standard features include:
• Voltages: 200V, 230V, 380V, 460V, 380-415V/50Hz, 575V
• Chilled-water supply range: 40 - 55°F; brine supply to 10°F
• Ambient operation between 0 - 115°F
• Single-point power connection reduces wiring costs
• Non-fused disconnect switch simplifies installation and
servicing
• Control transformer eliminates separate control wiring
• Micro-computer control panel is very user-friendly
• Low-noise fans reduce radiated sound
• Victaulic-grooved water connections reduce installation
costs
• Complies with ASHRAE Standard 90.1 on energy efficiency
• Options are available upon request
• Voltages: 200V, 230V, 380V, 400V, 460V, 380-415V/50Hz,
575V
• Chilled-water supply range: 40 - 55°F; brine supply to 15°F
• Ambient operation between 0 - 125°F
• Single-point power connection reduces wiring costs
• Non-fused disconnect switch simplifies installation and
servicing
• Control transformer eliminates separate control wiring
• VSD increases reliability at start-up and shut-down
• Micro-computer control panel is very user-friendly
• Low-noise fans reduce radiated sound
• Victaulic-grooved water connections reduce installation
costs
• Complies with ASHRAE Standard 90.1 on energy efficiency
• Options are available upon request
2
JOHNSON CONTROLS
Water-cooled Scroll Chillers
Water-cooled chillers using scroll-compressor technology
ranging from 50 to 200 tons. Standard features include:
• Voltages: 200V, 230V, 380V, 460V, 380-415V/50Hz, 575V
• Chilled-water supply range: 40 - 55°F; brine supply to 15°F
• Single-point power connection reduces wiring costs
• Non-fused disconnect switch simplifies installation and
servicing
• Control transformer eliminates separate control wiring
• Micro-computer control panel is very user-friendly
• Complies with ASHRAE Standard 90.1 on energy
efficiency
• Non-reversing heat pump function (leaving condenser
temperature control)
• Options are available upon request
Need temporary cooling?
If you need cooling while we are customizing your unit,
Johnson Controls can provide a rental unit. We make
available a wide range of products including chillers,
rooftop units, air handlers, towers and peripheral
equipment. Our service includes delivery, installation,
start-up, maintenance, and financing. If interested in
this option please contact the JCI Rental Department at:
1-800-JCI-RNTL (1800-524-7685)
www.johnsoncontrols.com/rental
Need more than the standard unit?
Need Replacement Parts?
If you need a chiller quickly but need some customization
of features, Johnson Controls can make it happen.
Customization features include:
• Suction-pressure readouts
• Service-Isolation valves
• Hot gas by-pass
• Brine cooling as low as 10°F
• Functional witness testing
• Hydronics package
• Epoxy Coated Cond. Coils
• Options are available upon request
Your brand HVAC parts source for air cooled, water cooled,
and absorption chillers. We are able to ship out the HVAC
parts that you need as soon as possible. If you need items
urgently (for a hospital, school or other critical application) we
can prioritize this requirement and work with our supplier for
expediting. If you have a need for replacement parts please
contact the JCI Parts Department at :
jOHNSON CONTROLS
1-800-932-1701
3
Ways to Reduce Your Risk, Expand Your Business and
Increase Your Profits
OPTION I
Use Variable Speed Technology to Create Chiller Replacement Opportunities
Compressor motor control via a variable frequency drive allows you as the installing contractor to give your
customer more tonnage without changing the electrical power supply. Also, emergency generator size can be
reduced when feeding chillers with variable speed compressors.
For Example: Your customer has an existing chiller that produces 165 tons at ARI conditions. The MCA for this
chiller is 374 amps and the existing wire and breaker size was installed to meet this MCA. Your customer is short
on capacity during peak hours of the day. YORK has an YVAA0248CEV that produces 225 tons with an MCA of
374. This will give you an extra 61 tons without changing out the wires or breakers.
On the other hand, if your customer doesn’t have a need for additional capacity, and the installation requires electrical power component upgrades, the first cost savings when using smaller breakers, wire and conduit is substantial.
$310 Average Wire Savings
Potential For a Smaller Circuit
Breaker Frame Size
$2,100
$3,500
OPTION II
Use Energy Performance to Differentiate Your Replacement Offering
The YORK Latitude variable speed air-cooled chiller allows you as the installing contractor to offer your customers
a replacement alternative that is as much as 25% more efficient than existing chillers.
For Example: Your customer wants to replace an existing 350-ton chiller. You as the installing contractor can
offer either a standard efficiency chiller or the YORK optimized variable speed chiller. The optimized offering will
save the customer over $17,000/year*. With this level of annual savings, you can offer your customer a $21,250
additive alternate with a 1.25 year simple payback. The price premium for the optimized offering is $7,000, which
allows you to capture $14,250 of additional gross profit.
*see the next page for the Average Energy Cost (AEC) calculation
4
JOHNSON CONTROLS
Annual Savings / Average Energy Cost (AEC) Calculation
Input Variables:
IPLV = Integrated Part Load Value (kW/TON) = (12) / (IPLV EER)
FLT = Full Load Tons (tons)
ACL = Average Chiller Load (tons) = (FLT) x (0.58)
RATE = Commercial Energy Cost ($/kWh)
OH – Average Chiller Operating Hours (hrs)
Output Functions:
AEC = (IPLV) x (ACL) x (RATE) x (OH)
Annual Savings = AEC Existing or Base Bid – AEC New
Example
Input Variables:
IPLV Existing or Base Bid = 15.4 EER
IPLV New = 19.0 EER
FLT Existing or Base Bid = 350 tons
FLT New = 350 tons
RATE = $0.1016/kWh
OH = 5000 hrs
Calculations:
AEC Existing or Base Bid = (IPLV) x (ACL) x (RATE) x (OH)
AEC Existing or Base Bid = (12 / (IPLV EER)) x ((FLT) x (0.58)) x (RATE) x (OH)
AEC Existing or Base Bid = (12 / 15.4 EER) x (350 tons x 0.58) x ($0.1016/kWh) x (5000 hrs)
AEC Existing or Base Bid = $80,356.36
AEC New = (IPLV) x (ACL) x (RATE) x (OH)
AEC New = (12 / (IPLV EER)) x ((FLT) x (0.58)) x (RATE) x (OH)
AEC New = (12 / 19.0 EER) x (350 tons x 0.58) x ($0.1016/kWh) x (5000 hrs)
AEC New = $65,130.95
Annual Savings = AEC Existing or Base Bid – AEC New
Annual Savings = $80,356.36 - $65,130.95
Annual Savings = $15,225.41 / year
jOHNSON CONTROLS
5
6
JOHNSON CONTROLS
YCAL
15 to 65 Tons
Air Cooled Scroll Chiller
jOHNSON CONTROLS
7
8
JOHNSON CONTROLS
YCAL Rigging
WARNING ­— To ensure warranty coverage, this equipment must be commissioned and serviced
by an authorized Johnson Controls Service Mechanic or a qualified service person experienced in
chiller installation. Installation must comply with all applicable codes, particularly in regard to electrical wiring and other safety elements such as relief valves, HP cutout settings, design working
pressures, and ventilation requirements consistent with the amount and type of refrigerant charge.
Lethal voltages exist within the control panels. Before servicing, open and tag all disconnect
switches.
Installation Check List
The following items must be checked before placing the units in operation.
1. Inspect the unit for shipping damage.
2. Rig Unit using spreader bars.
3. Open the unit only to install water piping system. Do not remove protective covers from water connections
until piping is ready for attachment. Check water piping to ensure cleanliness.
4. Pipe unit using good piping practice (see ASHRAE handbook section 215 and 195).
5. Check to see that the unit is installed and operated within limitations (Refer to Operational and Voltage
Limitations located in Section 1 of the YCAL Operations and Maintenance Guide [Form 150.62-NM8]).
The following pages outline detailed procedures to be followed to install and startup the chiller.
Handling
These units are shipped as completely assembled units containing full operating charge, and care should be taken to
avoid damage due to rough handling.
WARNING —The unit should be lifted by inserting hooks through the holes provided in the unit
base rails. Spreader bars should be used to avoid crushing the unit frame rails with lifting chains.
Inspection
EXAMPLE OF PROPER LIFTING
Immediately upon receiving the unit, it should be inspected for possible damage which may have occurred during transit. If damage is
evident, it should be noted in the carrier’s freight bill. A written request
for inspection by the carrier’s agent should be made at once. See
Instruction manual, Form 50.15-NM for more information and details.
Location and Clearances
These units are designed for outdoor installations on ground level,
rooftop, or beside a building. Location should be selected for minimum sun exposure and to insure adequate supply of fresh air for the
condenser. The units must be installed with sufficient clearances for
air entrance to the condenser coil, for air discharge away from the
condenser, and for servicing access.
In installations where winter operation is intended and show accumulations are expected, additional height must be provided to ensure
normal condenser air flow.
Clearances are listed under Dimensions in Section 1 of the YCAL
Operations and Maintenance Guide form 150.62-NM8.
jOHNSON CONTROLS
9
AIR COOLED SCROLL CHILLER
YCAL Style E - 15 to 65 TONS (R-410A)
BENEFITS
• Maintenance free, hermetic scroll compressor utilizes fewer moving parts to minimize breakdown
•Components and circuitry designed for lower minimum circuit ampacities (MCA) to allow use of smaller
wire for reduced power wiring costs
• Electronic, digital-based controls ensure reliable, solid-state monitoring and control
•Units ship with full ref. charge and undergo factory pressure and operational testing to minimize field setup
time
• Two refrigerant circuits on units over 35 tons allows redundant operation
• Industry’s only 18-month air cooled warranty that covers all parts
• Wide range of options to fit any design requirement. (Acoustical treatments, Hydrokit packages etc)
UPGRADE OPTIONS
•Remote Cooler
• Power Options --> 200, 230, 380, 460, 575 (Not available on all models, refer to Engineering Guide):
• Single Point Terminal Block, Non-fused Disconnect Switch, Circuit Breaker, Control Transformer
• Control Options:
• Low Ambient Kit extends operating range to 0 deg. F from +25 deg. F
•Discharge Pressure Transducers and Readout Capability (standard) allows unit to sense and display
discharge pressure
• Low Temperature Brine for chilling below 30 deg. F
•Motor Current Module allows monitoring of compressor motor current, provides extra protection against
compressor reverse rotation, phase-loss and phase imbalance
• Hot Gas Bypass for continuous, stable operation at capacities as low as 5% capacity
•Service Isolation Valve - suction and discharge (ball type) isolation valves are added to unit per system;
includes a system high pressure relief valve in compliance with ASHRAE 15
• Pre-coated, Post-coated Epoxy Dipped or Copper Fin condenser coils
• Unit Enclosure Options:
•Wire Panels (full unit-standard): coated, heavy gauge welded wire mesh mounted on exterior of unit to
prevent unauthorized access
•Louvered Panels (full unit): to protect condenser coils, visually screen internal components and prevent
unauthorized access
• Sound Attenuation:
• Compressor Acoustic Sound Blanket
• Ultra Quiet fans
• Vibration Isolators - 1" spring, 2" spring or neoprene pad isolators for mounting under unit base rails
10
JOHNSON CONTROLS
AIR COOLED SCROLL CHILLER
YCAL Style E - 15 to 65 TONS
PACKAGE DESCRIPTION:
Cooler:
•Shipped complete from the factory ready for field
installation and use
• Fully charged with HFC-410A and initial oil charge
• Baked on powder paint
• Heavy gauge, formed galvanized steel base
• Operational and Pressure Tested
•Equipped with a heater controlled by separate
thermostat for freeze protection to –20 deg. F
• Covered by closed cell foam insulation
•Inlet and outlet are grooved for compatibility with
field supplied victaulic connections
Controls:
Compressors:
• Suction-gas cooled, hermetic scroll compressors
•Large internal volume and oil reservoir provides
greater liquid tolerance
•Crankcase heaters for extra protection against
liquid migration
•All controls housed in a NEMA 3R/12 cabinet with
gasket sealed, hinged & latched door
• LCD, 40-character display with backlight
• Color coded, sealed keypad
•Standard controls permit operation from 25 to
125 deg F.
Condenser:
•Low noise, direct drive, maximum efficiency fans
with corrosion resistant aluminum hub and composite blades; statically and dynamically balanced
•Totally enclosed air over (TEAO) type fan motors,
current protected and permanently sealed
•Seamless, internally enhanced copper fin & tube
coils arranged in staggered rows; mechanically
expanded to full-height aluminum fins
• Design Working Pressure 650 PSIG
• Integral subcooling included
jOHNSON CONTROLS
11
Air Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0019EE46
15.4
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
37.0
6.3
Water
0.00010
3.3
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
Min. Ambient Temp. (°F)
Max. Ambient Temp. (°F)
95.0
0
25.0
115.0
Electrical Data
2
1
18.6/18.6
114.0/114.0
2/1.3
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.0 / 2.9
14.6 / 4.3
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
3
1454
1481
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
44.9
60
50
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type
60
50
60
1
(1)#14 - #2/0
39.8
114.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
17.6
1.0
18.6
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.
Load %
100.0
50.0
12
Operating Condition Electrical Data
Ambient (°F)
95.0
70.2
Part Load Rating Data
Capacity (Tons)
15.4
9.1
Compressor kW
17.6
6.3
Unit Efficiency
10.0 / 2.9
16.0 / 4.7
JOHNSON CONTROLS
jOHNSON CONTROLS
LEFT END
44 5/16"
BASE WIDTH
B
8 5/16"
18 3/4"
11"
(2) 3.0 X 1.50
RIGGING HOLES
BOTH ENDS
2" VICTAULIC CONN (TYP)
LIQUID IN
BOTTOM OF PANEL
VIEW B-B
7/8" TYP.
AIR-COOLED SCROLL CHILLER
MODEL: YCAL0019EE46
NOT FOR CONSTRUCTION
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT
TO ACCESS PANEL 16 1/4"
11 5/8"
B
PRODUCT DRAWING
2 1/4"
46 1/16"
45 1/4"
3 15/16"
3 1/4"
6 3/4"
X
13 3/4"
38 3/16"
2 1/4"
3 3/8"
CONTROL
PANEL
R-410A CHILLER
C
G
Y
ORIGIN
6 1/8"
CONTROL
PANEL
44 3/8"
END
END CAP
WIDTH
32 1/8"
1 1/16"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,454, OPERATING - 1,481.
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.6", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
44 1/2"
15 5/8"
9 1/16"
374
FRONT VIEW
109 3/16"
74 1/2"
97 1/8"
5"
1 1/16"
COMPR
END
(2) 3.0 X 1.50
RIGGING HOLES
BOTH SIDES
340
365
A JOHNSON CONTROLS COMPANY
(2) 7.0 X 2.25
FORKLIFT HOLES
BOTH SIDES
TOP VIEW
5/8" DIA MOUNTING HOLES(TYP)
Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS
1"
17"
2 1/4"
402
MODEL: YCAL0019EE46
AHRI CAPACITY 15.4 TONS
YCAL
15 TO 40
13
Air Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0022EE46
18.7
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
44.8
4.9
Water
0.00010
3.6
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
Min. Ambient Temp. (°F)
Max. Ambient Temp. (°F)
95.0
0
25.0
115.0
Electrical Data
2
1
20.0/20.0
125.0/125.0
2/1.3
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.0 / 2.9
15.5 / 4.5
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
3
1567
1597
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
48.1
60
60
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type
60
60
60
1
(1)#14 - #2/0
42.6
125.0
Across the Line
48.1
Notes:
Compressor kW
Total Fan kW
Total kW
21.5
1.0
22.5
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.
Load %
100.0
50.0
14
Operating Condition Electrical Data
Ambient (°F)
95.0
72.1
Part Load Rating Data
Capacity (Tons)
18.7
11.5
Compressor kW
21.5
7.2
Unit Efficiency
10.0 / 2.9
16.9 / 5.0
JOHNSON CONTROLS
jOHNSON CONTROLS
LEFT END
44 5/16"
BASE WIDTH
B
8 5/16"
18 3/4"
11"
(2) 3.0 X 1.50
RIGGING HOLES
BOTH ENDS
2" VICTAULIC CONN (TYP)
LIQUID IN
BOTTOM OF PANEL
VIEW B-B
7/8" TYP.
AIR-COOLED SCROLL CHILLER
MODEL: YCAL0022EE46
NOT FOR CONSTRUCTION
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT
TO ACCESS PANEL 16 1/4"
11 5/8"
B
PRODUCT DRAWING
2 1/4"
46 1/16"
45 1/4"
3 15/16"
3 1/4"
6 3/4"
X
13 3/4"
38 3/16"
2 1/4"
3 3/8"
CONTROL
PANEL
R-410A CHILLER
C
G
Y
ORIGIN
6 1/8"
CONTROL
PANEL
44 3/8"
END
END CAP
WIDTH
32 1/8"
1 1/16"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,567, OPERATING - 1,597.
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.5", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
44 1/2"
15 5/8"
9 1/16"
403
FRONT VIEW
109 3/16"
74 1/2"
97 1/8"
5"
1 1/16"
COMPR
END
(2) 3.0 X 1.50
RIGGING HOLES
BOTH SIDES
366
394
A JOHNSON CONTROLS COMPANY
(2) 7.0 X 2.25
FORKLIFT HOLES
BOTH SIDES
TOP VIEW
5/8" DIA MOUNTING HOLES(TYP)
Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS
1"
17"
2 1/4"
434
MODEL: YCAL0022EE46
AHRI CAPACITY 18.7 TONS
YCAL
15 TO 40
15
Air Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0028EE46
25.6
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
61.3
8.9
Water
0.00010
2.5
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
Min. Ambient Temp. (°F)
Max. Ambient Temp. (°F)
95.0
0
25.0
115.0
Electrical Data
2
1
23.1/26.9
150.0/187.0
2/4.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.1 / 3.0
13.4 / 3.9
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
3
1798
1835
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
64.7
100
80
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type
90
80
90
1
(1)#14 - #2/0
58.0
187.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
27.5
3.0
30.5
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.
Load %
100.0
50.8
16
Operating Condition Electrical Data
Ambient (°F)
95.0
71.9
Part Load Rating Data
Capacity (Tons)
25.6
15.7
Compressor kW
27.5
11.7
Unit Efficiency
10.1 / 3.0
14.3 / 4.2
JOHNSON CONTROLS
jOHNSON CONTROLS
15 1/2"
49 1/4"
B
LEFT END
44 5/16"
BASE WIDTH
19"
B
8 5/16"
10 3/4"
8 1/2"
AIR-COOLED SCROLL CHILLER
MODEL: YCAL0028EE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
(2) 3.0 X 1.50
RIGGING HOLES
BOTH ENDS
2" VICTAULIC CONN (TYP)
LIQUID IN
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT
TO ACCESS PANEL 13 3/8"
2 1/4"
50 1/16"
3 15/16"
3 1/4"
6 3/4"
2 1/4"
3 3/8"
CONTROL
PANEL
X
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
17 3/4"
42 1/8"
C
G
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
1 1/16"
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
CONTROL
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
PANEL
44 3/8"
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
END CAP
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
WIDTH
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
32 1/8"
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
6 1/8"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,798, OPERATING - 1,835.
3. CENTER OF GRAVITY FROM ORIGIN: X= 63.1", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
ORIGIN
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
Y
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1"
17"
TOP VIEW
50 1/2"
15 5/8"
9"
Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS
FRONT VIEW
118 5/16"
105 1/16"
80 1/2"
(2) 7.0 X 2.25
FORKLIFT HOLES
BOTH SIDES
5"
1 1/16"
COMPR
END
(2) 3.0 X 1.50
RIGGING HOLES
BOTH SIDES
423
456
A JOHNSON CONTROLS COMPANY
5/8" DIA MOUNTING HOLES(TYP)
R-410A CHILLER
460
1 7/8"
495
MODEL: YCAL0028EE46
AHRI CAPACITY 25.6 TONS
YCAL
15 TO 40
17
Air Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0033EE46
28.6
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
68.4
11.0
Water
0.00010
5.2
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
Min. Ambient Temp. (°F)
Max. Ambient Temp. (°F)
95.0
0
25.0
115.0
Electrical Data
2
1
26.9/26.9
187.0/187.0
2/4.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.5 / 3.1
14.5 / 4.2
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
3
2034
2077
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
66.7
100
80
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type
90
80
90
1
(1)#14 - #2/0
61.8
187.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
29.6
3.0
32.6
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.
Load %
100.0
50.0
18
Operating Condition Electrical Data
Ambient (°F)
95.0
70.0
Part Load Rating Data
Capacity (Tons)
28.6
16.6
Compressor kW
29.6
11.2
Unit Efficiency
10.5 / 3.1
15.7 / 4.6
JOHNSON CONTROLS
jOHNSON CONTROLS
15 1/2"
49 1/4"
B
LEFT END
44 5/16"
BASE WIDTH
19"
B
8 5/16"
10 3/4"
8 1/2"
AIR-COOLED SCROLL CHILLER
MODEL: YCAL0033EE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
(2) 3.0 X 1.50
RIGGING HOLES
BOTH ENDS
2" VICTAULIC CONN (TYP)
LIQUID IN
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT
TO ACCESS PANEL 13 3/8"
2 1/4"
50 1/16"
3 15/16"
3 1/4"
6 3/4"
2 1/4"
3 3/8"
CONTROL
PANEL
X
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
17 3/4"
42 1/8"
C
G
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
1 1/16"
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
CONTROL
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
PANEL
44 3/8"
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
END CAP
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
WIDTH
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
32 1/8"
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
6 1/8"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,034, OPERATING - 2,077.
3. CENTER OF GRAVITY FROM ORIGIN: X= 67.1", Y= 23.1" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
ORIGIN
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
Y
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1"
17"
TOP VIEW
50 1/2"
15 5/8"
9"
Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS
FRONT VIEW
118 5/16"
105 1/16"
80 1/2"
(2) 7.0 X 2.25
FORKLIFT HOLES
BOTH SIDES
5"
1 1/16"
COMPR
END
(2) 3.0 X 1.50
RIGGING HOLES
BOTH SIDES
516
565
A JOHNSON CONTROLS COMPANY
5/8" DIA MOUNTING HOLES(TYP)
R-410A CHILLER
475
1 7/8"
520
MODEL: YCAL0033EE46
AHRI CAPACITY 28.6 TONS
YCAL
15 TO 40
19
Air Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0043EE46
37.2
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
89.2
6.1
Water
0.00010
2.7
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
Min. Ambient Temp. (°F)
Max. Ambient Temp. (°F)
95.0
0
25.0
115.0
Electrical Data
2
20.0/20.0
125.0/125.0
2/3.4
1
20.0/20.0
125.0/125.0
2/3.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.1 / 3.0
14.5 / 4.2
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
3
2942
2967
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
99.2
150
110
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type
110
110
110
1
(1)#14 - #2/0
93.7
125.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
38.8
5.6
44.4
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.
Load %
100.0
75.0
50.0
25.0
20
Operating Condition Electrical Data
Ambient (°F)
95.0
83.3
69.0
55.0
Part Load Rating Data
Capacity (Tons)
37.2
30.0
21.1
11.5
Compressor kW
38.8
24.4
14.2
6.6
Unit Efficiency
10.1 / 3.0
12.0 / 3.5
14.9 / 4.4
17.3 / 5.1
JOHNSON CONTROLS
jOHNSON CONTROLS
46 15/16"
LIQUID IN
LEFT END
45 1/8"
90 1/4" BASE WIDTH
LIQUID OUT
3" VICTAULIC (TYP)
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
12 5/8"
25 3/16"
9 7/8"
15 3/4"
ELECTRICAL ACCESS
PANEL
AIR-COOLED SCROLL CHILLER
MODEL: YCAL0043EE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
47 3/4"
3 15/16"
6 3/4"
3 1/4"
C
G
X
15 1/16"
13 5/8"
25 3/8"
5 5/16"
Y
18 1/2"
ORIGIN
45 1/8"
B
COOLER
END
1 1/16"
90 9/16"
END CAP
WIDTH
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,942, OPERATING - 2,967.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.6", Y= 43.6" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
925
862
B
CONTROLPANEL
TOP VIEW
Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS
13 15/16"
611
569
9 13/16"
1 1/16"
COIL
END
A JOHNSON CONTROLS COMPANY
FRONT VIEW
144 13/16"
TWO LIFTING HOLES
BOTH SIDES
38"
9 13/16"
5/8" DIA MOUNTING HOLES(TYP)
MODEL: YCAL0043EE46
AHRI CAPACITY 37.2 TONS
YCAL
15 TO 40
21
Air Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0046EE46
39.4
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
94.5
5.1
Water
0.00010
3.5
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
Min. Ambient Temp. (°F)
Max. Ambient Temp. (°F)
95.0
0
25.0
115.0
Electrical Data
2
20.0/20.0
125.0/125.0
2/3.4
1
20.7/20.7
125.0/125.0
2/3.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.2 / 3.0
14.7 / 4.3
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
3
2968
3000
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
100.8
150
110
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type
110
110
110
1
(1)#14 - #2/0
95.1
125.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
41.0
5.6
46.6
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.
Load %
100.0
73.2
50.0
23.2
22
Operating Condition Electrical Data
Ambient (°F)
95.0
82.9
69.1
55.0
Part Load Rating Data
Capacity (Tons)
39.4
31.5
22.4
11.6
Compressor kW
41.0
25.2
14.9
6.5
Unit Efficiency
10.2 / 3.0
12.3 / 3.6
15.2 / 4.5
17.5 / 5.1
JOHNSON CONTROLS
jOHNSON CONTROLS
46 15/16"
45 1/8"
LEFT END
12 5/8"
AIR-COOLED SCROLL CHILLER
MODEL: YCAL0046EE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
15 3/4" 25 3/16"
ELECTRICAL ACCESS
PANEL
9 7/8"
LIQUID IN
90 1/4" BASE WIDTH
LIQUID OUT
3" VICTAULIC (TYP)
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
47 3/4"
3 15/16"
6 3/4"
3 1/4"
X
15 1/16"
13 5/8"
25 3/8"
5 5/16"
C
G
Y
16 11/16"
ORIGIN
45 1/8"
B
COOLER
END
1 1/16"
90 9/16"
END CAP
WIDTH
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,968, OPERATING - 3,000.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.2", Y= 43.5" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
941
875
B
CONTROLPANEL
TOP VIEW
Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS
13 15/16"
613
570
9 13/16"
1 1/16"
COIL
END
A JOHNSON CONTROLS COMPANY
FRONT VIEW
144 13/16"
TWO LIFTING HOLES
BOTH SIDES
38"
9 13/16"
5/8" DIA MOUNTING HOLES(TYP)
MODEL: YCAL0046EE46
AHRI CAPACITY 39.4 TONS
YCAL
15 TO 40
23
Air Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0052EE46
46.2
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
110.8
9.2
Water
0.00010
3.5
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
Min. Ambient Temp. (°F)
Max. Ambient Temp. (°F)
95.0
0
25.0
115.0
Electrical Data
2
23.1/23.1
150.0/150.0
2/4.0
1
23.1/23.1
150.0/150.0
2/4.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.2 / 3.0
15.1 / 4.4
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
3
3170
3208
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
114.2
150
125
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type
125
125
125
1
(1)#14 - #2/0
108.4
150.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
47.9
6.7
54.6
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.
Load %
100.0
75.0
50.0
25.0
24
Operating Condition Electrical Data
Ambient (°F)
95.0
83.4
69.5
55.0
Part Load Rating Data
Capacity (Tons)
46.2
37.3
26.6
15.1
Compressor kW
47.9
30.7
17.6
7.8
Unit Efficiency
10.2 / 3.0
12.0 / 3.5
15.2 / 4.5
19.1 / 5.6
JOHNSON CONTROLS
jOHNSON CONTROLS
61 7/8"
45 1/8"
90 1/4" BASE WIDTH
LEFT END
LIQUID OUT
3" VICTAULIC (TYP)
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
12 5/8"
25 3/16"
9 13/16"
15 3/4"
ELECTRICAL ACCESS
PANEL
LIQUID IN
AIR-COOLED SCROLL CHILLER
MODEL: YCAL0052EE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
62 5/8"
3 15/16"
6 3/4"
3 1/4"
X
15 1/16"
13 5/8"
25 3/8" B
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
C
G
Y
18 1/2"
ORIGIN
9 13/16"
B
TOP VIEW
Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS
FRONT VIEW
144 13/16"
713
623
1 1/16"
COIL
END
A JOHNSON CONTROLS COMPANY
13 15/16"
9 13/16"
5/8" DIA MOUNTING HOLES(TYP)
TWO LIFTING HOLES
BOTH SIDES
CONTROL
PANEL
5 5/16"
38"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
873
1 1/16"
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
WIDTH
2. WEIGHTS (LB):SHIPPING - 3,170, OPERATING - 3,208.
3. CENTER OF GRAVITY FROM ORIGIN: X= 61.9", Y= 42.2" .
45 1/8"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
999
MODEL: YCAL0052EE46
AHRI CAPACITY 46.2 TONS
YCAL
41 TO 65
25
Air Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0056EE46
56.2
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
134.7
9.9
Water
0.00010
4.1
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
Min. Ambient Temp. (°F)
Max. Ambient Temp. (°F)
95.0
0
25.0
115.0
Electrical Data
2
26.9/26.9
187.0/187.0
2/4.0
1
26.9/26.9
187.0/187.0
2/4.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.1 / 3.0
14.7 / 4.3
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
3
3206
3244
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
130.3
150
150
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type
150
150
150
1
(1)#14 - #2/0
123.6
187.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
60.3
6.7
67.0
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.
Load %
100.0
75.0
50.0
25.0
26
Operating Condition Electrical Data
Ambient (°F)
95.0
83.6
69.4
55.0
Part Load Rating Data
Capacity (Tons)
56.2
45.5
32.2
18.0
Compressor kW
60.3
38.8
22.6
10.2
Unit Efficiency
10.1 / 3.0
12.0 / 3.5
14.9 / 4.4
18.1 / 5.3
JOHNSON CONTROLS
jOHNSON CONTROLS
61 7/8"
45 1/8"
90 1/4" BASE WIDTH
LEFT END
LIQUID OUT
3" VICTAULIC (TYP)
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
AIR-COOLED SCROLL CHILLER
MODEL: YCAL0056EE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
15 3/4"
12 5/8"
9 7/8"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
25 3/16"
ELECTRICAL ACCESS
PANEL
LIQUID IN
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
62 5/8"
3 15/16"
6 3/4"
3 1/4"
X
15 1/16"
28 9/16"
25 3/8" B
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
C
G
Y
16 11/16"
ORIGIN
9 13/16"
B
TOP VIEW
Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS
FRONT VIEW
144 13/16"
715
625
1 1/16"
COIL
END
A JOHNSON CONTROLS COMPANY
14"
9 13/16"
5/8" DIA MOUNTING HOLES(TYP)
TWO LIFTING HOLES
BOTH SIDES
CONTROL
PANEL
5 3/16"
38"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
889
1 1/16"
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
WIDTH
2. WEIGHTS (LB):SHIPPING - 3,206, OPERATING - 3,244.
3. CENTER OF GRAVITY FROM ORIGIN: X= 61.5", Y= 42.2" .
45 1/8"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1,015
MODEL: YCAL0056EE46
AHRI CAPACITY 56.2 TONS
YCAL
41 TO 65
27
Air Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0066EE46
66.1
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
158.4
8.3
Water
0.00010
4.9
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
Min. Ambient Temp. (°F)
Max. Ambient Temp. (°F)
95.0
0
25.0
115.0
Electrical Data
2
26.9/26.9
187.0/187.0
2/1.3
1
33.9/33.9
250.0/250.0
2/4.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.1 / 3.0
15.1 / 4.4
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
3
4097
4142
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
146.0
200
175
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type
175
175
175
1
(1)#6 - 350
137.6
250.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
72.1
6.7
78.8
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.
Load %
100.0
71.5
50.0
21.5
28
Operating Condition Electrical Data
Ambient (°F)
95.0
82.6
69.3
55.0
Part Load Rating Data
Capacity (Tons)
66.1
52.5
37.8
18.5
Compressor kW
72.1
42.2
26.6
10.3
Unit Efficiency
10.1 / 3.0
12.9 / 3.8
15.2 / 4.5
18.5 / 5.4
JOHNSON CONTROLS
jOHNSON CONTROLS
61 7/8"
43 1/8"
90 1/4" BASE WIDTH
LEFT END
LIQUID OUT
3" VICTAULIC (TYP)
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
AIR-COOLED SCROLL CHILLER
MODEL: YCAL0066EE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
15 3/4"
12 5/8"
9 3/4"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
25 1/16"
ELECTRICAL ACCESS
PANEL
LIQUID IN
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
62 5/8"
3 15/16"
6 3/4"
3 1/4"
X
15 1/16"
28 9/16"
25 3/8" B
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
C
G
Y
12 13/16"
ORIGIN
9 13/16"
B
TOP VIEW
Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS
FRONT VIEW
153 5/8"
776
768
1 1/16"
COIL
END
A JOHNSON CONTROLS COMPANY
16"
9 13/16"
5/8" DIA MOUNTING HOLES(TYP)
TWO LIFTING HOLES
BOTH SIDES
CONTROL
PANEL
5 3/16"
38"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
1,292
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
1 1/16"
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
WIDTH
2. WEIGHTS (LB):SHIPPING - 4,097, OPERATING - 4,142.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.7", Y= 44.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
43 1/8"
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1,306
MODEL: YCAL0066EE46
AHRI CAPACITY 66.1 TONS
YCAL
41 TO 65
29
30
JOHNSON CONTROLS
YLAA
70 to 175 Tons
Air Cooled Scroll Chiller
jOHNSON CONTROLS
31
32
JOHNSON CONTROLS
YLAA RIGGING
Typical Lifting Arrangement - 8 Fan Models
Use spreader bars to avoid lifting chains hitting
the chiller.
CAUTION — Never lift the chiller using
a forklift or by hooking to the top rails.
Use only the lifting holes provided.
Lifting instructions are placed on a label on the
chiller and on the shipping bag.
Typical Lifting Arrangement - 4 Fan Models
jOHNSON CONTROLS
33
AIR COOLED SCROLL CHILLER
YLAA - 70 to 175 TONS
BENEFITS
• Optimized design for R-410A refrigerant (No EPA Phase out date)
•Available in 2-tiers of efficiency:
•Standard Efficiency: 9.6 – 10.0 EER
•High Efficiency: 10.1 an above EER
•Best Part Load Efficiency with an IPLV as high as 15.9.
•The YLAA always qualifies for LEED credit through Enhanced Refrigerant Management.
•This chiller utilizes 30-50% less refrigerant than conventional scroll chiller design.
•Standard ambient operation from 30 to 115-deg F
•Maintenance free, hermetic scroll compressor utilizes fewer moving parts to minimize breakdown
•Components and circuitry designed for lower minimum circuit ampacities (MCA) to allow use of smaller
wire for reduced power wiring costs
•Electronic, digital-based controls ensure reliable, solid-state monitoring and control
•Units ship evacuated with initial oil charge and undergo factory pressure and operational testing to
minimize field setup time
•Two refrigerant circuits allows redundant operation.
•Industry’s only 18-month air cooled warranty that covers all parts
•Wide range of options to fit any design requirement. (Acoustical treatments, Hydrokit packages etc)
UPGRADE OPTIONS
•Remote Cooler
•Power Options --> 200, 230, 380, 460, 575 (Not available on all models, refer to Engineering Guide):
•Single Point Terminal Block, Terminal Block with Individual Circuit Breakers, Circuit Breaker, Non-fused
Disconnect Switch or Non-fused Disconnect Switch with Individual System Circuit Breakers
•Control Options: Low Ambient Kit extends operating range to 0 deg. F from +30 deg. F
•Discharge Pressure Transducers and Readout Capability allows unit to sense and display discharge
pressure
•Low Temperature Brine for chilling below 30 deg. F (which includes Electronic Expansion Valve)
•Motor Current Module allows monitoring of compressor motor current, provides extra protection against
compressor reverse rotation, phase-loss and phase imbalance
•Hot Gas Bypass for continuous, stable operation at capacities as low as 5% capacity
•Service Isolation Valve - suction and discharge (ball type) isolation valves are added to unit per system;
includes a system high pressure relief valve in compliance with ASHRAE 15
•Post-coated Epoxy Dipped
•Unit Enclosure Options:
•Wire Panels (full unit): coated, heavy gauge welded wire mesh mounted on exterior of unit to prevent
unauthorized access
•Louvered Panels (condenser coils only): louvered panels mounted over exterior condenser coil faces to
protect coils
•Louvered Panels (full unit): to protect condenser coils, visually screen internal components and prevent
unauthorized access
•Louvered (condensers)/Wire Panels (mechanicals): Louvered steel panels on external condenser coil
faces, heavy-gauge welded-wire mesh around base
•Sound Attenuation:
•Compressor Acoustic Sound Blanket
•Ultra Quiet fans
•Vibration Isolators - 1" spring, 2" spring or neoprene pad isolators for mounting under unit base rails
34
JOHNSON CONTROLS
AIR COOLED SCROLL CHILLER
YLAA - 70 to 175 TONS
PACKAGE DESCRIPTION:
Evaporator:
•Shipped complete from the factory ready for field
installation and use
• Fully charged with HFC-410A and initial oil charge
• Baked on powder paint
• Heavy gauge, formed galvanized steel base
• Operational and Pressure Tested
•Equipped with a heater controlled by separate
thermostat for freeze protection to –20 deg. F
•Covered by closed cell foam insulation
•Inlet and outlet are grooved for compatibility with
field supplied victaulic connections
Refrigerant Circuit:
Compressors:
•Suction-gas cooled, hermetic scroll compressors
•Large internal volume and oil reservoir provides
greater liquid tolerance
•Crankcase heaters for extra protection against
liquid migration
•Independent circuits per compressor
•Each refrigerant circuit includes: liquid line shutoff
valve with charging port, low side pressure relief
device, filter-drier, solenoid valve, sight glass with
moisture indicator, thermostatic expansion valves,
and flexible, closed-cell foam insulated suction
line and suction pressure transducer.
Condenser:
•Low noise, direct drive, maximum efficiency fans
with corrosion resistant aluminum hub and composite blades; statically and dynamically balanced
•The fan motors are Totally Enclosed Air-Over,
current protected. They feature ball bearings that
are double-sealed and permanently lubricated.
•Condenser coils are made of a single material to
avoid galvanic corrosion due to dissimilar metals.
Coils and headers are brazed as one piece.
•Design Working Pressure 650 PSIG
•Integral subcooling included
jOHNSON CONTROLS
Controls:
•All controls housed in a NEMA 3R/12 cabinet
with gasket sealed, hinged & latched door
• LCD, 40-character display with backlight
• Color coded, sealed keypad
•Standard controls permit operation from 30 to
115 deg F.
35
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
36
YLAA-B0070SE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
°F
°F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
71.8
84.8
10.2
16
16
87
3.3
Plate Heat Exchanger
5.4
Water
54
44
38.7 / 38.7
171.2
11.4
0.0001
3"
95
122.5 / 122.5
4
0
59329
6.7
460-3-60 / 414-506
160
175
175
1
#4 - 500 kcmil
3578
3623
101
116.1
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0070SE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
88 5/16" - FRAME WIDTH
88 13/16" - OVERALL WIDTH
PRODUCT DRAWING
94 3/8" - OVERALL HEIGHT
88 5/8" - FRAME HEIGHT
81 13/16"
ORIGIN
3 1/4"
C
G
Y
X
76 5/8"
23 3/16"
UNIT0
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
732
5 5/8"
1,030
114 11/16" - FRAME LENGTH
121 11/16" - OVERALL LENGTH
23 3/16"
19 5/8"
1,087
774
46 3/8"
Date : 12/18/2012 11:37:46
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 1/2"
A JOHNSON CONTROLS COMPANY
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 3,578, OPERATING - 3,622.
3. CENTER OF GRAVITY FROM ORIGIN: X= 56.8", Y= 51.3" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
10"
jOHNSON CONTROLS
42 11/16"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0070SE
AHRI CAPACITY 71.8 TONS
YLAA
70 TO 90
37
1 1/16"
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
38
YLAA-B0080SE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
°F
°F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
77.7
94.4
9.9
15.4
15.4
88
3.3
Plate Heat Exchanger
6.7
Water
54
44
38.7 / 39
185.4
9
0.0001
3"
95
126.1 / 122.9
4
0
59329
6.7
460-3-60 / 414-506
173
200
200
1
#4 - 500 kcmil
3898
3954
106
116.1
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0080SE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
88 5/16" - FRAME WIDTH
88 13/16" - OVERALL WIDTH
PRODUCT DRAWING
94 3/8" - OVERALL HEIGHT
88 5/8" - FRAME HEIGHT
81 13/16"
ORIGIN
3 1/4"
C
G
Y
X
76 5/8"
23 3/16"
UNIT0
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
750
5 5/8"
1,135
114 11/16" - FRAME LENGTH
121 11/16" - OVERALL LENGTH
23 3/16"
19 5/8"
1,246
822
46 3/8"
Date : 12/18/2012 11:39:31
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 1/2"
A JOHNSON CONTROLS COMPANY
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 3,898, OPERATING - 3,953.
3. CENTER OF GRAVITY FROM ORIGIN: X= 56.1", Y= 52.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
10"
jOHNSON CONTROLS
42 11/16"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0080SE
AHRI CAPACITY 77.7 TONS
YLAA
70 TO 90
39
1 1/4"
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
40
YLAA-B0090SE
5
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
°F
°F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
83.9
103.4
9.7
15.5
15.5
88
3.3
Plate Heat Exchanger
8.8
Water
54
44
39.4 / 39.4
199.7
7
0.0001
3"
95
126.1 / 127.2
4
0
59329
6.7
460-3-60 / 414-506
192
225
225
1
#4 - 500 kcmil
4169
4241
115
116.1
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0090SE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
88 5/16" - FRAME WIDTH
88 13/16" - OVERALL WIDTH
PRODUCT DRAWING
94 3/8" - OVERALL HEIGHT
88 5/8" - FRAME HEIGHT
81 13/16"
3" INLET
3" OUTLET
ORIGIN
3 1/4"
C
G
Y
X
76 5/8"
23 3/16"
UNIT0
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
831
5 5/8"
1,310
114 11/16" - FRAME LENGTH
121 11/16" - OVERALL LENGTH
23 3/16"
19 5/8"
1,285
816
46 3/8"
Date : 12/18/2012 11:52:29
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 1/2"
A JOHNSON CONTROLS COMPANY
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,169, OPERATING - 4,242.
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.1", Y= 53.7" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
10"
jOHNSON CONTROLS
42 11/16"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0090SE
AHRI CAPACITY 83.9 TONS
YLAA
70 TO 90
41
1 1/16"
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
42
YLAA-B0091HE
4
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
°F
°F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
88.2
98.3
10.8
15
14.9
88
3.3
Plate Heat Exchanger
8.8
Water
54
44
39.2 / 39.2
210.8
7.7
0.0001
3"
95
117.7 / 117.7
6
0
88993
10.1
460-3-60 / 414-506
200
250
225
1
#4 - 500 kcmil
4718
4791
115
142.7
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0091HE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
88 5/16" - FRAME WIDTH
88 13/16" - OVERALL WIDTH
PRODUCT DRAWING
94 3/8" - OVERALL HEIGHT
88 5/8" - FRAME HEIGHT
81 13/16"
42 11/16"
ORIGIN
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,718, OPERATING - 4,791.
3. CENTER OF GRAVITY FROM ORIGIN: X= 67.8", Y= 52.1" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
3 1/4"
C
G
Y
884
571
X
23 5/16"
47 3/8"
UNIT1
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
142 1/4" - FRAME LENGTH
149 5/16" - OVERALL LENGTH
69 3/4"
23 1/8"
7 11/16"
1,290
840
5 5/8"
672
534
46 3/8"
Date : 12/18/2012 11:54:27
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 1/2"
A JOHNSON CONTROLS COMPANY
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
jOHNSON CONTROLS
10"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0091HE
AHRI CAPACITY 88.2 TONS
YLAA
91 TO 130
43
1 1/16"
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
44
YLAA-B0100SE
5
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
°F
°F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
95.8
119.1
9.7
14.3
14.3
88
3.3
Plate Heat Exchanger
8.8
Water
54
44
39.6 / 38.5
228.2
9
0.0001
3"
95
122.7 / 123.6
5
0
74161
8.4
460-3-60 / 414-506
223
250
250
1
#4 - 500 kcmil
4791
4864
112
142.7
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0100SE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
88 5/16" - FRAME WIDTH
88 13/16" - OVERALL WIDTH
PRODUCT DRAWING
94 3/8" - OVERALL HEIGHT
88 5/8" - FRAME HEIGHT
81 13/16"
42 11/16"
ORIGIN
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,791, OPERATING - 4,863.
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.6", Y= 53.5" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
3 1/4"
C
G
Y
800
542
X
23 5/16"
47 3/8"
UNIT1
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
142 1/4" - FRAME LENGTH
149 5/16" - OVERALL LENGTH
69 3/4"
23 1/8"
7 11/16"
1,459
836
5 5/8"
703
520
46 3/8"
Date : 12/18/2012 12:55:43
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 1/2"
A JOHNSON CONTROLS COMPANY
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
jOHNSON CONTROLS
10"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0100SE
AHRI CAPACITY 95.8 TONS
YLAA
91 TO 130
45
1 1/16"
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
46
YLAA-B0101HE
5
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
°F
°F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
98.5
116.1
10.2
15.4
15.4
89
3.3
Plate Heat Exchanger
8.8
Water
54
44
39.6 / 38.1
234.6
9.4
0.0001
3"
95
125.2 / 117.7
6
0
88993
10.1
460-3-60 / 414-506
227
250
250
1
#4 - 500 kcmil
4954
5026
126
142.7
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0101HE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
88 5/16" - FRAME WIDTH
88 13/16" - OVERALL WIDTH
PRODUCT DRAWING
94 3/8" - OVERALL HEIGHT
88 5/8" - FRAME HEIGHT
81 13/16"
42 11/16"
ORIGIN
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,954, OPERATING - 5,027.
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.8", Y= 53.2" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
3 1/4"
C
G
Y
818
560
X
23 5/16"
47 3/8"
UNIT1
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
142 1/4" - FRAME LENGTH
149 5/16" - OVERALL LENGTH
69 3/4"
23 1/8"
7 11/16"
1,501
875
5 5/8"
728
545
46 3/8"
Date : 12/18/2012 12:58:34
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 1/2"
A JOHNSON CONTROLS COMPANY
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
jOHNSON CONTROLS
10"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0101HE
AHRI CAPACITY 98.5 TONS
YLAA
91 TO 130
47
1 1/16"
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
48
YLAA-B0115SE
4
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
°F
°F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
113.9
140.9
9.7
14.6
14.6
88
3.3
Plate Heat Exchanger
8.8
Water
54
44
38.3 / 38.3
272.6
12.4
0.0001
3"
95
124 / 124
6
0
88993
10.1
460-3-60 / 414-506
256
300
300
1
#4 - 500 kcmil
5029
5101
119
142.7
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0115SE46
NOT FOR CONSTRUCTION
ORIGIN
81 13/16"
42 11/16"
Project Name : New Project
Location :
Engineer :
Contractor :
For :
88 5/16" - FRAME WIDTH
88 13/16" - OVERALL WIDTH
PRODUCT DRAWING
94 3/8" - OVERALL HEIGHT
88 5/8" - FRAME HEIGHT
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 5,029, OPERATING - 5,102.
3. CENTER OF GRAVITY FROM ORIGIN: X= 68", Y= 53.5" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
3 1/4"
C
G
Y
941
582
X
23 5/16"
47 3/8"
UNIT0
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
142 1/4" - FRAME LENGTH
149 5/16" - OVERALL LENGTH
69 3/4"
23 1/8"
7 11/16"
1,442
866
5 5/8"
728
545
46 1/2"
Date : 12/11/2012 8:18:19
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 3/8"
A JOHNSON CONTROLS COMPANY
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
jOHNSON CONTROLS
10"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0115SE
AHRI CAPACITY 113.9 TONS
YLAA
91 TO 130
49
1 1/16"
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
50
YLAA-B0120SE
4
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
°F
°F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
119.6
143.3
10
14.8
14.8
88
3.3
Plate Heat Exchanger
13.2
Water
54
44
40.6 / 40.6
285.3
8.4
0.0001
3"
95
125.1 / 125.1
6
0
88993
10.1
460-3-60 / 414-506
256
300
300
1
#4 - 500 kcmil
5183
5293
128
142.7
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0120SE46
NOT FOR CONSTRUCTION
ORIGIN
81 13/16"
42 11/16"
Project Name : New Project
Location :
Engineer :
Contractor :
For :
88 5/16" - FRAME WIDTH
88 13/16" - OVERALL WIDTH
PRODUCT DRAWING
94 3/8" - OVERALL HEIGHT
88 5/8" - FRAME HEIGHT
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 5,183, OPERATING - 5,293.
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.5", Y= 53.2" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
3 1/4"
C
G
Y
937
578
X
23 5/16"
47 3/8"
UNIT0
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
142 1/4" - FRAME LENGTH
149 5/16" - OVERALL LENGTH
69 3/4"
23 1/8"
7 11/16"
1,486
906
5 5/8"
789
600
46 1/2"
Date : 12/11/2012 8:21:24
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 3/8"
A JOHNSON CONTROLS COMPANY
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
jOHNSON CONTROLS
10"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0120SE
AHRI CAPACITY 119.6 TONS
YLAA
91 TO 130
51
1 1/16"
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Net Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Power
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Min Fluid Flow Rate
Max Fluid Flow Rate
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
YLAA-B0136SE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
USGPM
USGPM
°F
°F
ft
cfm
kW
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)
A
A
A
[kA]
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
Software Version
lb
lb
lb
in
in
in
R410A
129.9
154.3
10.1
15.5
16.5
93
Plate Heat Exchanger
10
Water
54
44
37.2 / 39.6
310.7
13.4
0.0001
4"
120
625
95
126.9 / 113.2
8
0
120776
13.4
460-3-60 / 414-506
285
300
300
5
1
#4 - 500 kcmil
6103
6187
146
187.7
88.3
94.2
YW13.02a
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
52
JOHNSON CONTROLS
MODEL: YLAA0136SE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
88 1/4" - FRAME WIDTH
88 3/4" - OVERALL WIDTH
Y
C
G
23 3/16"
ORIGIN
3 5/16"
Project Name : cg ylaa
Location :
Engineer :
Contractor :
For :
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN
ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.
3. CENTER OF GRAVITY FROM ORIGIN: X= 82.6"; Y= 51.9" .
2. WEIGHTS (LB): SHIPPING - 6,102; OPERATING - 6,186.
RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY
BE HIGHER THAN THE UNIT.
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION.
94 3/8" - OVERALL HEIGHT
88 1/2" - FRAME HEIGHT
81 5/8"
jOHNSON CONTROLS
X
6 1/2"
69"
58"
59 13/16"
75 1/2"
UNIT1
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
186 1/4" - FRAME LENGTH
5/8" DIA
MOUNTING
HOLES (TYP)
1 3/16"
4" OUTLET
4" INLET
Date : 5/21/2013 15:16:15
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
5 3/8"
46 3/8"
A JOHNSON CONTROLS COMPANY
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
10"
NOTES:
MODEL: YLAAB0136SE
AHRI CAPACITY 129.9 TONS
YLAA
91 TO 130
53
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Net Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Power
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Min Fluid Flow Rate
Max Fluid Flow Rate
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
YLAA-B0142HE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
USGPM
USGPM
°F
°F
ft
cfm
kW
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)
A
A
A
[kA]
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
Software Version
lb
lb
lb
in
in
in
R410A
132.1
152.3
10.4
14.4
16.2
96
Plate Heat Exchanger
13.2
Water
54
44
39.2 / 41.5
315.4
10
0.0001
4"
150
625
95
123.1 / 116.4
8
0
120776
13.4
460-3-60 / 414-506
285
300
300
5
1
#4 - 500 kcmil
6333
6444
157
187.7
88.3
94.2
YW13.02a
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
54
JOHNSON CONTROLS
MODEL: YLAA0142HE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
88 1/4" - FRAME WIDTH
88 3/4" - OVERALL WIDTH
Y
C
G
23 3/16"
ORIGIN
3 5/16"
Project Name : cg ylaa
Location :
Engineer :
Contractor :
For :
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN
ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.
3. CENTER OF GRAVITY FROM ORIGIN: X= 83"; Y= 52.1" .
2. WEIGHTS (LB): SHIPPING - 6,334; OPERATING - 6,444.
RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY
BE HIGHER THAN THE UNIT.
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION.
94 3/8" - OVERALL HEIGHT
88 1/2" - FRAME HEIGHT
81 5/8"
jOHNSON CONTROLS
X
6 1/2"
69"
58"
59 13/16"
75 1/2"
UNIT2
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
186 1/4" - FRAME LENGTH
5/8" DIA
MOUNTING
HOLES (TYP)
1 3/16"
4" OUTLET
4" INLET
Date : 5/21/2013 15:16:37
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
5 3/8"
46 3/8"
A JOHNSON CONTROLS COMPANY
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
10"
NOTES:
MODEL: YLAAB0142HE
AHRI CAPACITY 132.1 TONS
YLAA
131 TO 175
55
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Net Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Power
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Min Fluid Flow Rate
Max Fluid Flow Rate
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
YLAA-B0156HE
5
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
USGPM
USGPM
°F
°F
ft
cfm
kW
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)
A
A
A
[kA]
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
Software Version
lb
lb
lb
in
in
in
R410A
147.3
173.2
10.2
15.5
15.8
97
Plate Heat Exchanger
10
Water
54
44
36.9 / 38.7
351.9
16.7
0.0001
4"
120
625
95
118.8 / 117.1
10
0
150440
16.8
460-3-60 / 414-506
319
350
350
5
1
#4 - 500 kcmil
7269
7353
172
232.7
88.3
94.2
YW13.02a
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
56
JOHNSON CONTROLS
MODEL: YLAA0156HE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
88 1/4" - FRAME WIDTH
88 3/4" - OVERALL WIDTH
23 3/16"
ORIGIN
81 5/8"
C
G
Y
Project Name : cg ylaa
Location :
Engineer :
Contractor :
For :
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN
ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.
3. CENTER OF GRAVITY FROM ORIGIN: X= 95.8"; Y= 51.2" .
2. WEIGHTS (LB): SHIPPING - 7,269; OPERATING - 7,352.
RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY
BE HIGHER THAN THE UNIT.
3 5/16"
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION.
94 3/8" - OVERALL HEIGHT
88 1/2" - FRAME HEIGHT
jOHNSON CONTROLS
X
7 11/16"
69"
58"
UNIT3
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
230 1/4" - FRAME LENGTH
43"
42 1/2"
5/8" DIA
MOUNTING
HOLES (TYP)
82 7/8"
93 5/8"
1 3/8"
4" OUTLET
4" INLET
13/16"
Date : 5/21/2013 15:16:58
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 3/8"
A JOHNSON CONTROLS COMPANY
5 3/8"
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
32 3/8"
10"
NOTES:
MODEL: YLAAB0156SE
AHRI CAPACITY 147.3 TONS
YLAA
131 TO 175
57
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Net Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Power
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Min Fluid Flow Rate
Max Fluid Flow Rate
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
YLAA-B0170SE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
USGPM
USGPM
°F
°F
ft
cfm
kW
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)
A
A
A
[kA]
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
Software Version
lb
lb
lb
in
in
in
R410A
170.5
208.6
9.8
15.1
15.9
97
Plate Heat Exchanger
10
Water
54
44
37 / 37
407.4
22.1
0.0001
4"
120
625
95
121.3 / 121.3
10
0
150440
16.8
460-3-60 / 414-506
372
400
400
5
2
#4 - 500 kcmil
7624
7708
179
232.7
88.3
94.2
YW13.02a
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
58
JOHNSON CONTROLS
MODEL: YLAA0170SE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
88 1/4" - FRAME WIDTH
88 3/4" - OVERALL WIDTH
23 3/16"
ORIGIN
81 5/8"
C
G
Y
Project Name : cg ylaa
Location :
Engineer :
Contractor :
For :
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN
ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.
3. CENTER OF GRAVITY FROM ORIGIN: X= 97.1"; Y= 52.2" .
2. WEIGHTS (LB): SHIPPING - 7,624; OPERATING - 7,707.
RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY
BE HIGHER THAN THE UNIT.
3 5/16"
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION.
94 3/8" - OVERALL HEIGHT
88 1/2" - FRAME HEIGHT
jOHNSON CONTROLS
X
7 11/16"
69"
58"
UNIT4
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
230 1/4" - FRAME LENGTH
43"
42 1/2"
5/8" DIA
MOUNTING
HOLES (TYP)
82 7/8"
93 5/8"
1 3/8"
4" OUTLET
4" INLET
13/16"
Date : 5/21/2013 15:17:18
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 3/8"
A JOHNSON CONTROLS COMPANY
5 3/8"
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
32 3/8"
10"
NOTES:
MODEL: YLAAB0170SE
AHRI CAPACITY 170.5 TONS
YLAA
131 TO 175
59
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Net Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Power
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Min Fluid Flow Rate
Max Fluid Flow Rate
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
YLAA-B0175HE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
USGAL
°F
°F
°F
USGPM
ft H2O
h.ft².F/Btu
in
USGPM
USGPM
°F
°F
ft
cfm
kW
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)
A
A
A
[kA]
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
Software Version
lb
lb
lb
in
in
in
R410A
176
211.1
10
15.1
16
97
Plate Heat Exchanger
14.3
Water
54
44
39.6 / 39.6
420
16.4
0.0001
4"
180
650
95
122 / 122
10
0
150440
16.8
460-3-60 / 414-506
372
400
400
5
2
#4 - 500 kcmil
7772
7891
187
232.7
88.3
94.2
YW13.02a
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
60
JOHNSON CONTROLS
MODEL: YLAA0175HE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
88 1/4" - FRAME WIDTH
88 3/4" - OVERALL WIDTH
23 3/16"
ORIGIN
81 5/8"
C
G
Y
Project Name : cg ylaa
Location :
Engineer :
Contractor :
For :
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN
ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.
3. CENTER OF GRAVITY FROM ORIGIN: X= 97.4"; Y= 52" .
2. WEIGHTS (LB): SHIPPING - 7,771; OPERATING - 7,890.
RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY
BE HIGHER THAN THE UNIT.
3 5/16"
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION.
94 3/8" - OVERALL HEIGHT
88 1/2" - FRAME HEIGHT
jOHNSON CONTROLS
X
7 11/16"
69"
58"
UNIT5
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
230 1/4" - FRAME LENGTH
43"
42 1/2"
5/8" DIA
MOUNTING
HOLES (TYP)
82 7/8"
93 5/8"
1 3/8"
4" OUTLET
4" INLET
13/16"
Date : 5/21/2013 15:17:39
Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS
46 3/8"
A JOHNSON CONTROLS COMPANY
5 3/8"
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
32 3/8"
10"
NOTES:
MODEL: YLAAB0175HE
AHRI CAPACITY 176 TONS
YLAA
131 TO 175
61
62
JOHNSON CONTROLS
YVAA
150 to 500 Tons
Air Cooled Screw Chiller
jOHNSON CONTROLS
63
YVAA RIGGING
Lifting Unit
Container lugs should be inserted into the holes provided in the bottom of the frame rail.
Use spreader bars to avoid lifting chains hitting the chiller. Various methods of spreader bar arrangements may
be used; keeping in mind the intent is to keep the unit stable and to keep the chains from hitting the chiller and
causing damage.
WARNING — Never lift the chiller using a forklift or by hooking the top rails. Use only the lifting
holes provided.
Lifting instructions are placed on a label on the chiller and on the shipping bag.
64
JOHNSON CONTROLS
Delivery and Storage
To ensure consistent quality and maximum reliability, all units are tested and inspected before leaving the factory.
Units are shipped completely assembled and containing refrigerant under pressure. Units are shipped without
export crating unless crating has been specified on the Sales Order.
If the unit is to be put into storage, prior to installation, the following precautions should be observed.
• The chiller must be “blocked” so that the base is not permitted to sag or bow.
• Ensure that all openings, such as water connections, are securely capped.
• Do not store where exposed to ambient air temperatures exceeding 43°C (110°F).
• The condensers should be covered to protect the coils and fins from potential damage and corrosion,
particularly where building work is in progress.
• The unit should be stored in a location where there is minimal activity in order to limit the risk of accidental
physical damage.
• To prevent inadvertent operation of the pressure relief devices the unit must not be steam cleaned.
• It is recommended that the unit is periodically inspected during storage.
Inspection
Remove any transit packing and inspect the unit to ensure that all components have been delivered and that no
damage has occurred during transit. If any damage is evident, it should be noted on the carrier’s freight bill and a
claim entered in accordance with the instructions given on the advice note.
Major damage must be reported immediately to your local Johnson Controls representative.
Moving the Chiller
Prior to moving the unit, ensure that the installation site is suitable for installing the unit and is easily capable of supporting the weight of the unit and all associated services.
The units are designed to be lifted using shackles or safety hooks. A spreader bar or frame should be used in
order to prevent damage to the unit from the lifting chains. (Refer to Figure 4 on Page 20 of the Operations and
Maintenance Guide [Form 201.28-NM1.1 (812)] for hooks.)
Units are provided with lifting eyes in the sites of the base frame, which can be attached directly using container
lugs, shackles or safety hooks (Refer to Figure 4 on Page 20 of the Operations and Maintenance Guide [Form
201.28-NM1.1 (812)] for proper lifting illustration).
WARNING — The unit must only be lifted by the base frame at the points provided. Never move the
unit on rollers, or lift the unit using a forklift truck.
Care should be taken to avoid damaging the condenser cooling fins when moving the unit.
Lifting Weights
For details of weights and weight distribution, refer to the data shipped in the chiller information packet and unit
nameplate.
jOHNSON CONTROLS
65
AIR COOLED SCREW CHILLER
YVAA - 150 to 500 TONS (R-134A)
BENEFITS
•Continuous function, microprocessor controlled Variable Speed Drive (VSD) for valve less, smooth capacity
control to 10% of chiller capacity
• Chiller speed matched to system requirements at off-peak conditions resulting in lower energy usage
• Use of VSD reduces compressor moving parts by 50%
• Soft motor start with no electrical inrush reduces components stress, heat buildup
• Operating efficiencies at off-design conditions results in IPLVs as high as 19.8 EER
•Standard full load power factor of 95%, maintained throughout operating range resulting in improved
energy savings
• Superior acoustic operation at off-design conditions
• HFC-R134a standard for long term availability and zero ODP
• Wide range of options to fit any design requirement
• Competitors MCA is an average of 10% higher than YORK’s
• Lower MCA allows for smaller wiring and smaller circuit breakers therefore lower costs
• Allows for replacing chiller and increasing tonnage without replacing electrical components
• Industry’s only 18-month air cooled warranty that covers all parts.
UPGRADE OPTIONS
• Remote Cooler
• Factory mounted non-fused disconnect switch or circuit breaker
• Epoxy Post Coated, Pre Coated or Post Coated for tube and fin
•Seamless internally enhanced copper fin & tube coils arranged in staggered rows; mechanically bonded to
full eight aluminum fins
• Evaporator Options:
• 1-1/2" Insulation (double thickness)
• Raised Face Flange Accessory for cooler nozzles
• Flow Switch Accessory: Vapor proof, SPDT, NEMA 3R switch, 150psig
• Suction service isolation valve per circuit (discharge valve standard)
• Unit Enclosure Options:
•Wire Panels (full unit): coated, heavy gauge welded wire mesh mounted on exterior of unit to prevent
unauthorized access to refrigerant components
•Louvered Panels (condenser coils only): Painted to match unit; louvered panels mounted over exterior
condenser coils faces to visually screen unit, protects coils
•Louvered Panels (full unit): Painted to match unit; to protect condenser coils, visually screen internal
components and prevent unauthorized access
•Louvered (condensers)/Wire Panels (mechanicals): Louvered steel panels on external condenser coil
faces, heavy-gauge welded-wire mesh around base to prevent unauthorized access
• Sound Attenuation:
•SilentNightTM controls to force lower sound levels on demand or per user schedule
• Ultra quiet fans, compressor sound blankets and/or acoustical enclosures
• Vibration Isolation: Neoprene, 1" spring isolators or 2" spring isolators
66
JOHNSON CONTROLS
AIR COOLED SCREW CHILLER
YVAA - 150 to 500 TONS
PACKAGE DESCRIPTION:
Evaporator:
• Self contained, designed for outdoor installation
• Baked on powder paint
• Heavy gauge, formed galvanized steel base
• Factory mounted control transformer
• ARI-Standard 550/590-11 Rated & Certified
•All exposed wiring routed through liquid-tight,
non-metallic conduit
•High efficiency Hybrid falling film cooler;
refrigerant in shell and water in tubes
• Removable heads to access copper tubes
• Air vent and water drain connections
• Heater protection to -20 deg. F ambient
• Insulated with ¾" closed cell foam
•Design working pressure 150 PSIG water side
and 235 PSIG on refrigerant side
Compressors:
• Reliable VSD driven semi-hermetic twin screw
•High efficiency, accessible hermetic motor with
redundant overload protection
• Temperature actuated body cartridge heater
• Acoustically tuned discharge gas muffler
• Design pressure of compressor 450 PSIG
Condenser:
•Low noise, full airflow cross section fans for
maximum efficiency; statically & dynamically balanced for low vibration operation; positioned in
extended orifices for low sound
•High efficiency, direct drive, 3-phase totally
enclosed fan motors with double sealed, permanently lubricated ball bearings
•Condenser coils are made of a single material to
avoid galvanic corrosion due to dissimilar metals.
Coils and headers are brazed as one piece
• Design Working Pressure 450 PSIG
Electrical:
•Competitors MCA is an average of 10% higher
than YORK’s
•Lower MCA allows for smaller wiring and smaller
circuit breakers therefore lower costs
•Allows for replacing chiller and increasing tonnage without replacing electrical components
jOHNSON CONTROLS
Refrigerant circuit:
• Independent circuits per compressor
•Computer controlled bending of refrigerant pipe
reduces over 60% of pipe brazed joints
•Liquid line components include: manual shutoff
valve with charging port, removable core filterdrier, solenoid valve, sight glass with moisture
indicator, electronic expansion valves
•Discharge line proided with manual compressor
shutoff service valve
•External Oil separators with no moving parts, 450
PSIG design working pressure
Controls:
•All controls housed in a NEMA 3R cabinet with
gasket sealed, hinged & latched door
•VSD section includes dedicated inverter for each
compressor
•Control display accessible without opening main
cabinet doors
• LCD, 80-character display with backlight
• Color coded, sealed keypad
•Standard controls permit operation from 0 to
125 deg F ambient temperature
67
Air Cooled Screw Chiller
Performance Specification
Unit Tag
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
1
YVAA0153BAF46
150.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0153BAF46BA VSXX XTAXLXXXX60 44XOXXX S189W 1SXXA2B MXF PXXXX XXXX BXSX
5
10
15 Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
359.6
5.6
Water
0.00010
58.0
25
30
35
40
45
Evaporator Data (Cont.)
Min. Flow Rate (gpm)
Max. Flow Rate (gpm)
250.0
950.0
Condenser Data
Ambient Temp. Design (°F)
Altitude (ft.)
Ambient Temp. Min (°F)
95.0
0
0.0
Circuit
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
109
4/3.3
1
109
4/3.3
Compressor RLA
Fan QTY/FLA (each)
50
3
10.1 / 3.0
15.1 / 4.4
10 %
11518
11979
4
Single Point
Min. Circuit Ampacity
275
Recommended Fuse/CB Rating
Max. Inverse Time CB Rating
350
350
Max. Dual Element Fuse Size (Amps)
Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type
Notes:
350
30kA
2
#2 - 600 KCM
0.95
2.0
VSD
Operating Condition Electrical Data
Compressor kW
162.6
Total Fan kW
14.8
Total kW
177.4
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
Part Load Rating Data
Capacity (Tons)
150.0
112.5
75.0
37.5
Ambient (°F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.1 / 3.0
13.3 / 3.9
16.3 / 4.8
17.6 / 5.2
Compressor kW
162.6
86.2
43.0
18.2
SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0153BAF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (°F)
95.0
80.0
65.0
55.0
63
95.0
95.0
94.0
91.0
125
95.0
95.0
94.0
91.0
250
96.0
96.0
95.0
92.0
500
98.0
95.0
94.0
91.0
1K
95.0
92.0
91.0
88.0
2K
87.0
86.0
85.0
82.0
4K
83.0
82.0
81.0
78.0
8K
78.0
78.0
77.0
73.0
LWA
99.0
97.0
96.0
92.0
2K
60.0
59.0
58.0
55.0
4K
56.0
55.0
54.0
51.0
8K
51.0
51.0
50.0
46.0
dBA
72.0
70.0
69.0
65.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **
YVAA0153BAF46 ( Equipped with Low Sound Fans )
Load %
Ambient (°F)
63
125
250
500
100.0
95.0
68.0
68.0
69.0
71.0
75.0
80.0
68.0
68.0
69.0
68.0
50.0
65.0
67.0
67.0
68.0
67.0
25.0
55.0
64.0
64.0
65.0
64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)
1K
68.0
65.0
64.0
61.0
Performance at AHRI Conditions
YVAA0153BAF46
Evaporator Data
EWT (°F)
54.0
LWT (°F)
44.0
Flow Rate (gpm)
359.6
Pressure Drop (ft.)
5.6
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
58.0
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.1 / 3.0
EER IPLV/COP IPLV
15.1 / 4.4
Capacity (Tons)
150.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
68
JOHNSON CONTROLS
15 1/8"
AIR-COOLED SCREW CHILLER
MODEL: YVAA0153BAF46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
POWER: SINGLE POINT WITH TERMINAL BLOCK
88 3/16"
44 1/8"
Project Name : stp
Location :
Engineer :
Contractor :
For :
26 9/16"
6" (WATER INLET)
C
G
Y
X
780
644
2,116
2,147
75 15/16"
(4) RIGGING HOLES
EACH SIDE 3 X 2
48 11/16"
6 15/16"
56 1/8"
A
41 1/4"
62 9/16"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
203 1/4"
71 1/4"
2,116
2,147
3/4" MOUNTING HOLES (TYP)
1,052
978
VSD / POWER PANEL
jOHNSON CONTROLS
6" (WATER OUTLET)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 11,518, OPERATING - 11,980.
3. CENTER OF GRAVITY FROM ORIGIN: X= 101.8", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
14 1/8"
18 1/4"
47 5/16"
10 3/8"
A
60"
94 1/2"
4"
VIEW B-B
12"
B
VIEW A-A
2 15/16"
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
POWER ENTRY IS ON BOTTOM OF PANEL
1 1/2"
POWER ENTRY
10" WIDE X 13" HIGH
B
Date : 12/6/2012 11:43:34
Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS
A JOHNSON CONTROLS COMPANY
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
1 3/8" (TYP)
MODEL: YVAA0153BAF46
AHRI CAPACITY 150.0 TONS
YVAA
150 TO 200
69
Air Cooled Screw Chiller
Performance Specification
Unit Tag
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
1
YVAA0183ABF46
175.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0183ABF46BAVSXXXTAXLXXXX6044XOXXXS192W1SXXA2BMXFPXXXXXXXXBXSX
5
10
15 Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
419.5
11.4
Water
0.00010
48.0
25
30
35
40
45
Evaporator Data (Cont.)
Min. Flow Rate (gpm)
Max. Flow Rate (gpm)
200.0
750.0
Condenser Data
Ambient Temp. Design (°F)
Altitude (ft.)
Ambient Temp. Min (°F)
95.0
0
0.0
Circuit
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
111
4/3.3
1
139
6/3.3
Compressor RLA
Fan QTY/FLA (each)
50
3
10.4 / 3.0
15.4 / 4.5
10 %
12019
12460
4
Single Point
Min. Circuit Ampacity
322
Recommended Fuse/CB Rating
Max. Inverse Time CB Rating
450
450
Max. Dual Element Fuse Size (Amps)
Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type
Notes:
450
30kA
2
#2 - 600 KCM
0.95
2.0
VSD
Operating Condition Electrical Data
Compressor kW
184.4
Total Fan kW
17.9
Total kW
202.4
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
Part Load Rating Data
Capacity (Tons)
175.0
131.3
87.5
43.7
Ambient (°F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.4 / 3.0
13.5 / 4.0
16.5 / 4.8
17.9 / 5.2
Compressor kW
184.4
97.8
49.4
22.0
SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0183ABF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (°F)
95.0
80.0
65.0
55.0
63
96.0
96.0
94.0
91.0
125
96.0
96.0
95.0
91.0
250
97.0
97.0
95.0
92.0
500
98.0
96.0
95.0
91.0
1K
94.0
94.0
91.0
88.0
2K
88.0
87.0
86.0
82.0
4K
84.0
83.0
82.0
78.0
8K
80.0
79.0
78.0
73.0
LWA
99.0
98.0
96.0
93.0
2K
61.0
60.0
59.0
55.0
4K
57.0
56.0
55.0
51.0
8K
53.0
52.0
51.0
46.0
dBA
72.0
71.0
69.0
66.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **
YVAA0183ABF46 ( Equipped with Low Sound Fans )
Load %
Ambient (°F)
63
125
250
500
100.0
95.0
69.0
69.0
70.0
71.0
75.0
80.0
69.0
69.0
70.0
69.0
50.0
65.0
67.0
68.0
68.0
68.0
25.0
55.0
64.0
64.0
65.0
64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)
1K
67.0
67.0
64.0
61.0
Performance at AHRI Conditions
YVAA0183ABF46
Evaporator Data
EWT (°F)
54.0
LWT (°F)
44.0
Flow Rate (gpm)
419.5
Pressure Drop (ft.)
11.4
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
48.0
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.4 / 3.0
EER IPLV/COP IPLV
15.4 / 4.5
Capacity (Tons)
175.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
70
JOHNSON CONTROLS
14 1/8"
AIR-COOLED SCREW CHILLER
MODEL: YVAA0183ABF46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
POWER: SINGLE POINT WITH TERMINAL BLOCK
88 3/16"
44 1/8"
Project Name : stp
Location :
Engineer :
Contractor :
For :
25 9/16"
6" (WATER INLET)
C
G
Y
X
38 3/4"
47 5/8"
1,654
1,659
247"
82 13/16"
(4) RIGGING HOLES
EACH SIDE 3 X 2
1,084
1,088
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
77 1/4"
1,084
1,729
46 3/4"
1,088
17 11/16"
1,660
3/4" MOUNTING HOLES (TYP)
42 1/16"
66 1/8"
A
711
704
VSD / POWER PANEL
jOHNSON CONTROLS
6" (WATER OUTLET)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 12,019, OPERATING - 12,460.
3. CENTER OF GRAVITY FROM ORIGIN: X= 128.4", Y= 44.2".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
14 1/8"
94 1/2"
4"
VIEW B-B
12"
B
VIEW A-A
2 15/16"
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
POWER ENTRY IS ON BOTTOM OF PANEL
1 1/2"
POWER ENTRY
10" WIDE X 13" HIGH
B
Date : 12/6/2012 11:51:6
Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS
A JOHNSON CONTROLS COMPANY
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
18 1/4"
47 5/16"
10 3/8"
A
60"
1 1/4" (TYP)
MODEL: YVAA0183ABF46
AHRI CAPACITY 175.0 TONS
YVAA
150 TO 200
71
Air Cooled Screw Chiller
Performance Specification
Unit Tag
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
1
YVAA0233BEF46
200.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0233BEF46BAVSXXXTAXLXXXX6044XOXXXS176W1SXXA2BMXFPXXXXXXXXBXSX
5
10
15 Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
479.4
9.2
Water
0.00010
58.0
25
30
35
40
45
Evaporator Data (Cont.)
Min. Flow Rate (gpm)
Max. Flow Rate (gpm)
250.0
950.0
Condenser Data
Ambient Temp. Design (°F)
Altitude (ft.)
Ambient Temp. Min (°F)
95.0
0
0.0
Circuit
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
135
5/3.3
1
158
7/3.3
Compressor RLA
Fan QTY/FLA (each)
50
3
10.5 / 3.1
15.2 / 4.5
10 %
13288
13750
4
Single Point
Min. Circuit Ampacity
375
Recommended Fuse/CB Rating
Max. Inverse Time CB Rating
500
500
Max. Dual Element Fuse Size (Amps)
Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type
Notes:
500
30kA
2
#2 - 600 KCM
0.95
2.0
VSD
Operating Condition Electrical Data
Compressor kW
208.4
Total Fan kW
21.1
Total kW
229.4
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
Part Load Rating Data
Capacity (Tons)
200.0
150.0
100.0
50.0
Ambient (°F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.5 / 3.1
13.5 / 4.0
16.2 / 4.7
17.3 / 5.1
Compressor kW
208.4
111.2
56.5
23.9
SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0213ADF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (°F)
95.0
80.0
65.0
55.0
63
97.0
97.0
96.0
93.0
125
97.0
97.0
96.0
93.0
250
98.0
98.0
97.0
94.0
500
97.0
97.0
96.0
94.0
1K
94.0
93.0
93.0
90.0
2K
88.0
88.0
87.0
84.0
4K
84.0
84.0
83.0
80.0
8K
80.0
80.0
78.0
76.0
LWA
99.0
99.0
97.0
95.0
2K
61.0
61.0
60.0
57.0
4K
57.0
57.0
56.0
53.0
8K
53.0
53.0
51.0
49.0
dBA
72.0
72.0
70.0
68.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **
YVAA0213ADF46 ( Equipped with Low Sound Fans )
Load %
Ambient (°F)
63
125
250
500
100.0
95.0
70.0
70.0
71.0
70.0
75.0
80.0
70.0
70.0
71.0
70.0
50.0
65.0
69.0
69.0
70.0
69.0
25.0
55.0
66.0
66.0
67.0
67.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)
1K
67.0
66.0
66.0
63.0
Performance at AHRI Conditions
YVAA0213ADF46
Evaporator Data
EWT (°F)
54.0
LWT (°F)
44.0
Flow Rate (gpm)
479.4
Pressure Drop (ft.)
9.2
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
58.0
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.5 / 3.1
EER IPLV/COP IPLV
15.2 / 4.5
Capacity (Tons)
200.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
72
JOHNSON CONTROLS
15 1/8"
AIR-COOLED SCREW CHILLER
MODEL: YVAA0233BEF46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
POWER: SINGLE POINT WITH TERMINAL BLOCK
88 3/16"
44 1/8"
Project Name : stp
Location :
Engineer :
Contractor :
For :
26 9/16"
6" (WATER INLET)
C
G
Y
X
670
659
57 5/8"
72 5/16"
73 5/16"
670
659
38 3/4"
933
1,430
291 3/16"
76 13/16"
41 5/8"
947
1,423
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
77 5/8"
(5) RIGGING HOLES
EACH SIDE 3 X 2
51 3/4"
2,247
2,230
3/4" MOUNTING HOLES (TYP)
42 1/16"
66 1/8"
A
947
933
VSD / POWER PANEL
jOHNSON CONTROLS
6" (WATER OUTLET)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 13,288, OPERATING - 13,750.
3. CENTER OF GRAVITY FROM ORIGIN: X= 134.7", Y= 44.1".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
14 1/8"
94 1/2"
4"
VIEW B-B
12"
B
VIEW A-A
2 15/16"
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
POWER ENTRY IS ON BOTTOM OF PANEL
1 1/2"
POWER ENTRY
10" WIDE X 13" HIGH
B
Date : 12/6/2012 12:52:26
Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS
A JOHNSON CONTROLS COMPANY
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
18 1/4"
47 5/16"
10 3/8"
A
60"
1 1/4" (TYP)
MODEL: YVAA0233BEF46
AHRI CAPACITY 200.0 TONS
YVAA
150 TO 200
73
Air Cooled Screw Chiller
Performance Specification
Unit Tag
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
1
YVAA0273DGF46
250.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0273DGF46BAVSXXXTAXLXXXX6044XOXXXS188W1SXXA2BMXFXXXXXXXXXBXSX
5
10
15 Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
598.3
15.2
Water
0.00010
82.0
25
30
35
40
45
Evaporator Data (Cont.)
Min. Flow Rate (gpm)
300.0
Max. Flow Rate (gpm)
1150.0
Condenser Data
Ambient Temp. Design (°F)
Altitude (ft.)
Ambient Temp. Min (°F)
Circuit
55
60
65
Performance Data
EER / COP
NPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
175
7/3.3
1
175
7/3.3
Compressor RLA
Fan QTY/FLA (each)
95.0
0
0.0
50
3
10.8 / 3.2
16.0 / 4.7
10 %
16275
17103
4
Single Point
Min. Circuit Ampacity
444
Recommended Fuse/CB Rating
Max. Inverse Time CB Rating
600
600
Max. Dual Element Fuse Size (Amps)
Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type
Notes:
600
30kA
2
#2 - 600 KCM
0.95
2.0
VSD
Operating Condition Electrical Data
Compressor kW
253.5
Total Fan kW
24.2
Total kW
277.7
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
Part Load Rating Data
Capacity (Tons)
250.0
187.5
125.0
62.5
Ambient (°F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.8 / 3.2
14.0 / 4.1
17.2 / 5.0
18.9 / 5.5
Compressor kW
253.5
135.2
68.3
29.0
SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0273DGF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (°F)
95.0
80.0
65.0
55.0
63
97.0
97.0
96.0
93.0
125
97.0
97.0
96.0
93.0
250
98.0
98.0
97.0
94.0
500
97.0
97.0
96.0
94.0
1K
94.0
93.0
93.0
90.0
2K
88.0
88.0
87.0
84.0
4K
84.0
84.0
83.0
80.0
8K
80.0
80.0
78.0
76.0
LWA
99.0
99.0
97.0
95.0
2K
63.0
62.0
61.0
58.0
4K
59.0
58.0
57.0
54.0
8K
54.0
53.0
52.0
49.0
dBA
74.0
72.0
71.0
68.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **
YVAA0213ADF46 ( Equipped with Low Sound Fans )
Load %
Ambient (°F)
63
125
250
500
100.0
95.0
71.0
71.0
72.0
73.0
75.0
80.0
71.0
71.0
72.0
71.0
50.0
65.0
69.0
69.0
70.0
70.0
25.0
55.0
66.0
67.0
67.0
67.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)
1K
70.0
67.0
66.0
63.0
Performance at AHRI Conditions
YVAA0273DGF46
Evaporator Data
EWT (°F)
54.0
LWT (°F)
44.0
Flow Rate (gpm)
599.8
Pressure Drop (ft.)
15.3
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
82.0
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.8 / 3.2
EER IPLV/COP IPLV
16.0 / 4.7
Capacity (Tons)
249.9
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
74
JOHNSON CONTROLS
44 1/8"
15 5/16"
AIR-COOLED SCREW CHILLER
MODEL: YVAA0273DGF46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
POWER: SINGLE POINT WITH TERMINAL BLOCK
88 3/16"
26 3/4"
X
59 1/8"
Project Name : adsfasdfa
Location :
Engineer :
Contractor :
For :
6" (WATER INLET)
C
G
Y
1,518
1,389
1,946
2,135
83 1/4"
(6) RIGGING HOLES
EACH SIDE 3 X 2
100 5/16"
42 7/8"
60 3/16"
335 3/16"
79 13/16"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
40 3/16"
3,036
2,778
48 5/16"
1,372
1,539
3/4" MOUNTING HOLES (TYP)
60 1/4"
70 5/8"
A
710
14 1/8"
12 3/8"
47 1/2"
10 3/8"
A
60"
4"
VIEW B-B
POWER ENTRY
10" WIDE X 13" HIGH
12"
B
VIEW A-A
2 15/16"
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
POWER ENTRY IS ON BOTTOM OF PANEL
1 1/2"
94 11/16"
1 5/16" (TYP)
B
Date : 3/6/2013 8:56:2
Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS
A JOHNSON CONTROLS COMPANY
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
681
VSD / POWER PANEL
jOHNSON CONTROLS
6" (WATER OUTLET)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 16,275, OPERATING - 17,103.
3. CENTER OF GRAVITY FROM ORIGIN: X= 168.3", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
MODEL: YVAA0273DGF46
AHRI CAPACITY 250.0 TONS
YVAA
201 TO 500
75
Air Cooled Screw Chiller
Performance Specification
Unit Tag
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
1
YVAA0343EKF46
300.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0343EKF46BA VSXX XTAXLXXXX60 44XOXXX S179W 1SXXA2B MXF PXXXX XXXX BXSX
5
10
15 20
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
719.1
11.8
Water
0.00010
113.0
25
30
35
40
45
Evaporator Data (Cont.)
Min. Flow Rate (gpm)
400.0
Max. Flow Rate (gpm)
1500.0
Condenser Data
Ambient Temp. Design (°F)
Altitude (ft.)
Ambient Temp. Min (°F)
Circuit
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
209
9/3.3
1
209
9/3.3
Compressor RLA
Fan QTY/FLA (each)
95.0
0
0.0
50
3
10.9 / 3.2
15.5 / 4.5
10 %
19315
20175
4
Single Point
Min. Circuit Ampacity
533
Recommended Fuse/CB Rating
Max. Inverse Time CB Rating
700
700
Max. Dual Element Fuse Size (Amps)
Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type
Notes:
700
30kA
3
#2 - 600 KCM
0.95
2.0
VSD
Operating Condition Electrical Data
Compressor kW
300.3
Total Fan kW
30.5
Total kW
330.8
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
Part Load Rating Data
Capacity (Tons)
300.0
225.0
150.0
75.0
Ambient (°F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.9 / 3.2
13.9 / 4.1
16.5 / 4.8
17.8 / 5.2
Compressor kW
300.3
162.5
85.1
38.1
SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0343EKF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (°F)
95.0
80.0
65.0
55.0
63
99.0
99.0
97.0
94.0
125
99.0
99.0
97.0
94.0
250
100.0
100.0
98.0
95.0
500
99.0
100.0
98.0
94.0
1K
98.0
98.0
95.0
92.0
2K
92.0
91.0
89.0
87.0
4K
87.0
88.0
85.0
83.0
8K
83.0
84.0
81.0
79.0
LWA
102.0
102.0
100.0
96.0
2K
65.0
64.0
62.0
60.0
4K
60.0
61.0
58.0
56.0
8K
56.0
57.0
54.0
52.0
dBA
75.0
75.0
73.0
69.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **
YVAA0343EKF46 ( Equipped with Low Sound Fans )
Load %
Ambient (°F)
63
125
250
500
100.0
95.0
72.0
72.0
73.0
72.0
75.0
80.0
72.0
72.0
73.0
73.0
50.0
65.0
70.0
70.0
71.0
71.0
25.0
55.0
67.0
67.0
68.0
67.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)
1K
71.0
71.0
68.0
65.0
Performance at AHRI Conditions
YVAA0343EKF46
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
719.1
11.8
Water
0.00010
113.0
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.9 / 3.2
EER IPLV/COP IPLV
15.5 / 4.5
Capacity (Tons)
300.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
76
JOHNSON CONTROLS
44 1/8"
15 1/2"
AIR-COOLED SCREW CHILLER
MODEL: YVAA0343EKF46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
POWER: SINGLE POINT WITH TERMINAL BLOCK
88 3/16"
29 1/2"
Project Name : stp
Location :
Engineer :
Contractor :
For :
8" (WATER INLET)
X
1000"
(7) RIGGING HOLES
EACH SIDE 3 X 2
C
G
Y
423 1/8"
40 3/16"
79 13/16"
48 5/16"
1,966
1,995
3/4" MOUNTING HOLES (TYP)
60 3/16"
2,259
2,260
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
61 3/4"
2,259
97 1/2"
1,951
863
84 7/16"
2,260
1,910
863
132 3/16"
790
14 1/8"
12 3/8"
47 1/2"
10 1/4"
A
60"
4"
VIEW B-B
POWER ENTRY
10" WIDE X 13" HIGH
12"
B
VIEW A-A
2 15/16"
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
POWER ENTRY IS ON BOTTOM OF PANEL
1 1/2"
94 11/16"
1 3/8" (TYP)
B
Date : 12/6/2012 13:34:33
Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS
A JOHNSON CONTROLS COMPANY
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
60 1/4"
70 5/8"
A
801
VSD / POWER PANEL
jOHNSON CONTROLS
8" (WATER OUTLET)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 19,316, OPERATING - 20,175.
3. CENTER OF GRAVITY FROM ORIGIN: X= 187.5", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
MODEL: YVAA0343EKF46
AHRI CAPACITY 300.0 TONS
YVAA
201 TO 500
77
Air Cooled Screw Chiller
Performance Specification
Unit Tag
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
1
YVAA0373FJF46
350.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
YVAA0373FJF46BA
VSXX XTAXLXXXX60 44XOXXX S196W 1SXXA2B MXF XXXXX XXXX BXSX
5
10
CONTROLS
15 Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
837.7
11.2
Water
0.00010
96.0
PIPING
25
30
COMP
35
EVAPORATOR
40
45
Evaporator Data (Cont.)
Min. Flow Rate (gpm)
460.0
Max. Flow Rate (gpm)
1540.0
Condenser Data
Ambient Temp. Design (°F)
Altitude (ft.)
Ambient Temp. Min (°F)
Circuit
CABINET
50
MISC
55
WARR
60
65
Performance Data
EER / COP
NPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
178
7/3.3
1
327
7/3.3
Compressor RLA
Fan QTY/FLA (each)
95.0
0
0.0
COND
3
10.4 / 3.0
15.0 / 4.4
10 %
22346
23405
4
Single Point
Min. Circuit Ampacity
658
Recommended Fuse/CB Rating
Max. Inverse Time CB Rating
800
800
Max. Dual Element Fuse Size (Amps)
Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type
Notes:
800
30kA
2
#2 - 600 KCM
0.95
3.0
VSD
Operating Condition Electrical Data
Compressor kW
372.6
Total Fan kW
31.8
Total kW
404.4
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
Part Load Rating Data
Capacity (Tons)
350.0
262.5
175.0
87.5
Ambient (°F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.4 / 3.0
13.3 / 3.9
16.1 / 4.7
17.4 / 5.1
Compressor kW
372.6
203.4
105.5
44.4
SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0373FJF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (°F)
95.0
80.0
65.0
55.0
63
99.0
99.0
98.0
96.0
125
99.0
100.0
98.0
96.0
250
100.0
100.0
99.0
97.0
500
103.0
100.0
98.0
97.0
1K
100.0
97.0
95.0
92.0
2K
97.0
91.0
89.0
87.0
4K
96.0
88.0
86.0
84.0
8K
85.0
83.0
83.0
81.0
LWA
105.0
102.0
100.0
98.0
2K
70.0
64.0
62.0
60.0
4K
69.0
61.0
59.0
57.0
8K
58.0
56.0
56.0
54.0
dBA
78.0
75.0
73.0
71.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **
YVAA0373FJF46 ( Equipped with Low Sound Fans )
Load %
Ambient (°F)
63
125
250
500
100.0
95.0
72.0
72.0
73.0
76.0
75.0
80.0
72.0
73.0
73.0
73.0
50.0
65.0
71.0
71.0
72.0
71.0
25.0
55.0
69.0
69.0
70.0
70.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)
1K
73.0
70.0
68.0
65.0
Performance at AHRI Conditions
YVAA0373FJF46
Evaporator Data
EWT (°F)
54.0
LWT (°F)
44.0
Flow Rate (gpm)
839.7
Pressure Drop (ft.)
11.3
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
96.0
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.4 / 3.0
EER IPLV/COP IPLV
15.0 / 4.4
Capacity (Tons)
349.9
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
78
JOHNSON CONTROLS
jOHNSON CONTROLS
88
5/16"
44 1/8"
15
13/16"
28
13/16"
94
11/16"
8" WATER INLET
AIR-COOLED SCREW CHILLER
MODEL: YVAA0373FJF46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
8" WATER OUTLET
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 22,346, OPERATING - 23,405.
3. CENTER OF GRAVITY FROM ORIGIN: X= 200.3", Y= 46.6".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
Project Name : adsfasdfa
Location :
Engineer :
Contractor :
For :
(6) RIGGING HOLES EACH SIDE 3 X 2
133
11/16"
142
11/16"
467 1/8"
56 5/8"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
63 7/8"
78
11/16"
60 5/8"
108 1/2"
63 7/8"
10
5/16"
12
5/16"
A
42 1/8"
B
END VIEW
SECTION
12"
2 15/16"
A-A
B-B
POWER ENTRY
10" WIDE X 13" HIGH
SECTION
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
2 1/2"
2 1/2"
B
Date : 3/5/2013 14:21:26
Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS
A JOHNSON CONTROLS COMPANY
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
60
5/16"
70
11/16"
A
3/4" MOUNTING HOLES (TYP)
MODEL: YVAA0373EKF46
AHRI CAPACITY 350.0 TONS
YVAA
201 TO 500
79
Air Cooled Screw Chiller
Performance Specification
Unit Tag
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
1
YVAA0443FMF46
400.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0443FMF46BA VDXX XTAXLXXXX60 44XOXXX S172W 1SXXA2B MXF PXXXX XXXX BXSX
5
10
15 Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
958.8
14.3
Water
0.00010
96.0
Circuit
25
30
35
45
Evaporator Data (Cont.)
Min. Flow Rate (gpm)
460.0
Max. Flow Rate (gpm)
1540.0
Condenser Data
Ambient Temp. Design (°F)
Altitude (ft.)
Ambient Temp. Min (°F)
95.0
0
0.0
50
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
287
12/3.3
1
287
12/3.3
Compressor RLA
Fan QTY/FLA (each)
40
3
10.6 / 3.1
14.8 / 4.3
10 %
25942
27001
4
Single Point
Min. Circuit Ampacity
398
398
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
600
600
600
600
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Unit Power Factor
Control KVA
Starter Type
600
600
600
#2 - 600 KCM
0.95
3.0
VSD
600
600
600
#2 - 600 KCM
0.95
Notes:
Operating Condition Electrical Data
Compressor kW
414.4
Total Fan kW
38.0
Total kW
452.4
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
Part Load Rating Data
Capacity (Tons)
400.0
300.0
200.0
100.0
Ambient (°F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.6 / 3.1
13.2 / 3.9
15.8 / 4.6
17.3 / 5.1
Compressor kW
414.4
231.7
120.9
53.3
SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0443FMF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (°F)
95.0
80.0
65.0
55.0
63
100.0
100.0
99.0
96.0
125
100.0
100.0
99.0
96.0
250
101.0
101.0
100.0
97.0
500
102.0
102.0
100.0
98.0
1K
99.0
100.0
96.0
93.0
2K
95.0
92.0
90.0
87.0
4K
93.0
90.0
87.0
84.0
8K
88.0
85.0
85.0
82.0
LWA
104.0
104.0
101.0
98.0
2K
68.0
65.0
63.0
60.0
4K
66.0
63.0
60.0
57.0
8K
61.0
58.0
58.0
55.0
dBA
77.0
77.0
74.0
71.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **
YVAA0443FMF46 ( Equipped with Low Sound Fans )
Load %
Ambient (°F)
63
125
250
500
100.0
95.0
73.0
73.0
74.0
75.0
75.0
80.0
73.0
73.0
74.0
75.0
50.0
65.0
72.0
72.0
73.0
73.0
25.0
55.0
69.0
69.0
70.0
71.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)
1K
72.0
73.0
69.0
66.0
Performance at AHRI Conditions
YVAA0443FMF46
Evaporator Data
EWT (°F)
54.0
LWT (°F)
44.0
Flow Rate (gpm)
958.8
Pressure Drop (ft.)
14.3
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
96.0
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.6 / 3.1
EER IPLV/COP IPLV
14.8 / 4.3
Capacity (Tons)
400.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
80
JOHNSON CONTROLS
jOHNSON CONTROLS
88"
44 1/8"
16"
29"
95"
8" WATER INLET
AIR-COOLED SCREW CHILLER
MODEL: YVAA0443FMF46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
8" WATER OUTLET
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 25,942, OPERATING - 27,001.
3. CENTER OF GRAVITY FROM ORIGIN: X= 213.7", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
42"
56"
Project Name : stp
Location :
Engineer :
Contractor :
For :
67"
88"
56"
143"
146"
(8) RIGGING HOLES EACH SIDE 3 X 2
287"
52"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
555"
79"
57"
51"
109"
60"
71"
12"
10"
A
SECTION
42"
B
12"
3"
END
VIEW
SECTION
A-A
B-B
POWER ENTRY
10" WIDE X 13" HIGH
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
2 1/2"
2 1/2"
B
Date : 12/6/2012 13:47:41
Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS
A JOHNSON CONTROLS COMPANY
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
73"
A
3/4" MOUNTING HOLES (TYP)
MODEL: YVAA0443FMF46
AHRI CAPACITY 400.0 TONS
YVAA
201 TO 500
81
Air Cooled Screw Chiller
Performance Specification
Unit Tag
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
1
YVAA0523HMF46
450.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0523HMF46BA VDXX XTAXLXXXX60 44XOXXX S183W 1SXXA2B MXF PXXXX XXXX BXSX
5
10
15 20
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
1078.7
14.8
Water
0.00010
147.0
Circuit
25
30
35
45
Evaporator Data (Cont.)
Min. Flow Rate (gpm)
550.0
Max. Flow Rate (gpm)
1880.0
Condenser Data
Ambient Temp. Design (°F)
Altitude (ft.)
Ambient Temp. Min (°F)
95.0
0
0.0
50
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
312
13/3.3
1
312
13/3.3
Compressor RLA
Fan QTY/FLA (each)
40
3
10.9 / 3.2
15.4 / 4.5
10 %
28427
29784
4
Single Point
Min. Circuit Ampacity
423
423
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
700
700
700
700
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Unit Power Factor
Control KVA
Starter Type
700
700
700
#2 - 600 KCM
0.95
3.0
VSD
700
700
700
#2 - 600 KCM
0.95
Notes:
Operating Condition Electrical Data
Compressor kW
452.4
Total Fan kW
41.1
Total kW
493.6
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
Part Load Rating Data
Capacity (Tons)
450.0
337.5
225.0
112.5
Ambient (°F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.9 / 3.2
13.7 / 4.0
16.4 / 4.8
18.2 / 5.3
Compressor kW
452.4
251.2
131.9
58.2
SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0523HMF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (°F)
95.0
80.0
65.0
55.0
63
101.0
100.0
99.0
96.0
125
101.0
101.0
99.0
96.0
250
102.0
102.0
100.0
97.0
500
102.0
103.0
100.0
97.0
1K
101.0
100.0
96.0
93.0
2K
96.0
93.0
91.0
87.0
4K
92.0
92.0
87.0
84.0
8K
87.0
86.0
85.0
81.0
LWA
104.0
104.0
101.0
98.0
2K
69.0
66.0
64.0
60.0
4K
65.0
65.0
60.0
57.0
8K
60.0
59.0
58.0
54.0
dBA
77.0
77.0
74.0
71.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **
YVAA0523HMF46 ( Equipped with Low Sound Fans )
Load %
Ambient (°F)
63
125
250
500
100.0
95.0
74.0
74.0
75.0
75.0
75.0
80.0
73.0
74.0
75.0
76.0
50.0
65.0
72.0
72.0
73.0
73.0
25.0
55.0
69.0
69.0
70.0
70.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)
1K
74.0
73.0
69.0
66.0
Performance at AHRI Conditions
YVAA0523HMF46
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
1078.6
14.8
Water
0.00010
147.0
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.9 / 3.2
EER IPLV/COP IPLV
15.4 / 4.5
Capacity (Tons)
450.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
82
JOHNSON CONTROLS
jOHNSON CONTROLS
88"
44 1/8"
16"
30"
95"
8" WATER INLET
AIR-COOLED SCREW CHILLER
MODEL: YVAA0523HMF46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
8" WATER OUTLET
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 28,427, OPERATING - 29,784.
3. CENTER OF GRAVITY FROM ORIGIN: X= 222.4", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
Project Name : stp
Location :
Engineer :
Contractor :
For :
79"
132"
57"
59"
78"
309"
146"
599"
52"
79"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
(8) RIGGHING HOLES EACH SIDE 3 X 2
143"
57"
51"
109"
60"
71"
12"
10"
A
B
42"
SECTION
END
END
VIEW
VIEW
SECTION
12"
3"
B-B
A-A
POWER ENTRY
10" WIDE X 13" HIGH
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
2 1/2"
2 1/2"
B
Date : 12/6/2012 13:57:16
Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS
A JOHNSON CONTROLS COMPANY
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
73"
A
3/4" MOUNTING HOLES (TYP)
MODEL: YVAA0523HMF46
AHRI CAPACITY 450.0 TONS
YVAA
201 TO 500
83
Air Cooled Screw Chiller
Performance Specification
Unit Tag
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
1
YVAA0523HMG46
500.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0523HMG46BA VDXX XTAXLXXXX60 44XOXXX S200W 1SXXA3B MXG XXXXX XXXX BXSX
5
10
15 20
Evaporator Data
EWT (°F)
LWT (°F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
1199.9
51.4
Water
0.00010
147.0
Circuit
25
30
35
45
Evaporator Data (Cont.)
Min. Flow Rate (gpm)
400.0
Max. Flow Rate (gpm)
1400.0
Condenser Data
Ambient Temp. Design (°F)
Altitude (ft.)
Ambient Temp. Min (°F)
95.0
0
0.0
50
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
341
13/5.1
1
341
13/5.1
Compressor RLA
Fan QTY/FLA (each)
40
3
10.5 / 3.1
14.4 / 4.2
10 %
29365
30722
4
Single Point
Min. Circuit Ampacity
478
478
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
800
800
800
800
Max. Dual Element Fuse Size (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Unit Power Factor
Control KVA
Starter Type
800
800
800
#2 - 600 KCM
0.95
3.0
VSD
800
800
800
#2 - 600 KCM
0.95
Notes:
Operating Condition Electrical Data
Compressor kW
495.3
Total Fan kW
74.7
Total kW
570.0
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
Part Load Rating Data
Capacity (Tons)
500.0
375.0
250.0
125.0
Ambient (°F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.5 / 3.1
12.8 / 3.8
15.5 / 4.5
16.2 / 4.7
Compressor kW
495.3
272.8
151.9
63.4
SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0523HMG46 ( Equipped with High Airflow Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (°F)
95.0
80.0
65.0
55.0
63
103.0
103.0
101.0
99.0
125
117.0
117.0
115.0
113.0
250
116.0
116.0
114.0
112.0
500
110.0
110.0
107.0
105.0
1K
107.0
106.0
103.0
101.0
2K
103.0
102.0
99.0
97.0
4K
96.0
94.0
91.0
90.0
8K
90.0
89.0
87.0
85.0
LWA
113.0
112.0
110.0
108.0
2K
76.0
75.0
72.0
70.0
4K
69.0
67.0
64.0
63.0
8K
63.0
62.0
60.0
58.0
dBA
86.0
85.0
83.0
81.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **
YVAA0523HMG46 ( Equipped with High Airflow Fans )
Load %
Ambient (°F)
63
125
250
500
100.0
95.0
76.0
90.0
89.0
83.0
75.0
80.0
76.0
90.0
89.0
83.0
50.0
65.0
74.0
88.0
87.0
80.0
25.0
55.0
72.0
86.0
85.0
78.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)
1K
80.0
79.0
76.0
74.0
Performance at AHRI Conditions
YVAA0523HMG46
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
1199.9
51.4
Water
0.00010
147.0
Condenser Data
Ambient Temp. (°F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.5 / 3.1
EER IPLV/COP IPLV
14.4 / 4.2
Capacity (Tons)
500.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
84
JOHNSON CONTROLS
jOHNSON CONTROLS
16"
AIR-COOLED SCREW CHILLER
MODEL: YVAA0523HMG46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
88"
44 1/8"
95"
8" WATER INLET
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 29,365, OPERATING - 30,722.
3. CENTER OF GRAVITY FROM ORIGIN: X= 225.1", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
59"
78"
146"
599"
52"
79"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
(8) RIGGHING HOLES EACH SIDE 3 X 2
143"
Project Name : examples - Small tonnage BOM
Location :
Engineer :
Contractor :
For :
79"
132"
57"
309"
528 5/16"
57"
51"
109"
73"
Date : 4/26/2013 9:55:8
Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS
60"
71"
A
12"
10"
A
3/4" MOUNTING HOLES (TYP)
END
END
VIEW
VIEW
A-A
B
30"
A JOHNSON CONTROLS COMPANY
42"
B
8" WATER OUTLET
SECTION
12"
3"
B-B
POWER ENTRY
10" WIDE X 13" HIGH
SECTION
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
2 1/2"
2 1/2"
MODEL: YVAA0523HMG46
AHRI CAPACITY 500.0 TONS
YVAA
201 TO 500
85
86
JOHNSON CONTROLS
YCWL
50 to 200 Tons
Water Cooled Scroll Chiller
jOHNSON CONTROLS
87
88
JOHNSON CONTROLS
YCWL RIGGING
Delivery and Storage
To ensure consistent quality and maximum reliability, all units are
tested and inspected before leaving the factory. Units are shipped
completely assembled and containing refrigerant under pressure.
Units are shipped without export crating unless this has been
specified on the Sales Order.
If the unit is to be put into storage, before installation, the following
precautions should be observed:
Ensure that all openings, such as water connections, are securely
capped.
Do not store where exposed to ambient air temperatures exceeding
107°F (42°C).
The unit should be stored in a location where there is minimal activity
to limit the risk of accidental physical damage.
To prevent inadvertent operation of the pressure relief devices the
unit must not be steam cleaned.
It is recommended that the unit is periodically inspected during
storage.
Inspection
Immediately upon receiving the unit, it should be inspected for possible damage which may have occurred during transit. If damage
is evident, it should be noted in the carrier’s freight bill. A written
request for inspection by the carrier’s agent should be made at once.
See “Instruction Manual”, Form 50.15-NM for more information and details.
Major damage must be reported immediately to your local Johnson Controls representative.
Moving the Unit
Before moving the unit, ensure that the installation site is suitable for installing the unit and is capable of supporting
the weight of the unit and all associated services.
The units are designed to be lifted using either lifting chains or a fork lift.
Lifting by Crane / Hoist
A spreader frame should be used to prevent damage to the unit from the lifting chains (Refer to page 34 of the
Operations and Maintenance Guide [Form 201.26-NM1]).
NOTE: The unit must only be lifted a the points provided.
jOHNSON CONTROLS
89
WATER COOLED SCROLL CHILLER
YCWL - 50 to 200 TONS
BENEFITS
• •
•
•
•
•
IPLV as high as 25.4 EER provide cost effective operation
Designed for low acoustics without additional sound treatment
Wide range of options to fit any design requirement
HFC-410A Standard for zero ODP and low global warming potential; long service life
Multiple scroll compressors offer redundancy and accurate capacity matching
Native BACnet MSTP & Modbus communications for BAS integration
UPGRADE OPTIONS
•Low temperature brine chilling to 15°F
• Power Options:
• Single Point Power Connection to Terminal Block, Non-fused Disconnect or Circuit Breaker
• Multiple Point Power Connection to Circuit Breakers for retrofit projects
• Compressor Overloads to limit MCA (ideal for retrofit applications)
• Heat Pump (non-reversing) option to 130°F leaving condenser water temperature for energy conservation
• Remote Condenser YCRL variant for remote condenser applications
• Evaporator Options:
• Victaulic Flange Accessory for cooler nozzles
• Flow switch: Vapor proof, SPDT, NEMA 4X switch, 150 psig
• Vibration Isolators - Neoprene isolators, 1" spring isolators or 2" spring isolators
90
JOHNSON CONTROLS
WATER COOLED SCROLL CHILLER
YCWL - 50 to 200 TONS
PACKAGE DESCRIPTION:
Evaporator:
•Completely assembled with all piping and wiring
ready for field installation
• Pressure and operational tested
•Provided with HFC-410A charge and initial oil
charge
•Can be provided with optional overspray coat of
Caribbean Blue enamel paint
•High efficiency DX cooler, refrigerant in tubes and
chilled liquid through baffled shell
• Two independent circuits per chiller
• Removable heads to access copper tubes
• Water vent and drain connections
• Insulated with 3/4" closed cell foam
•Design working pressure 150 PSIG waterside and
400 PSIG on refrigerant side
Compressors:
• Reliable suction-gas cooled hermetic scrolls
•High efficiency motors with redundant overload
protection
•Microprocessor controlled compressor staging
regulates chiller capacity to 15% of maximum
• Design Working Pressure 560 PSIG
Condenser:
•
•
•
•
Cleanable, thru-tube type with removable heads
Integral subcooling standard
Equipped with relief valves
Steel shell and copper tubes
Refrigerant Circuit:
• Tandem or trio compressors per circuit
•Liquid line components include: shut-off valve
with charging port, high-absorption removable
core filter-drier, solenoid valve, sight glass with
moisture indicator, thermal or electronic expansion valves (depending on options)
•Entire suction line and liquid line between expansion valve and cooler insulated with flexible
closed-cell foam insulation
Controls:
•All controls housed in a NEMA 1 cabinet with
gasket sealed, hinged & latched door
• LCD, 40-character display with backlight
• Color coded, 32-button sealed keypad
jOHNSON CONTROLS
91
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0056SE46
52.4
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
125.6
12.2
Water
0.00010
22.4
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
23.1/23.1
150.0/150.0
85.0
95.0
153.2
10.6
Water 0.0
0.00025
19.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.1 / 4.7
21.3 / 6.2
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
23.1/23.1
150.0/150.0
3
3515
3648
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
110.0
(1)#12 - #1
92.4
150.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
39.2
39.2
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
92
98.0
150.0
110.0
Capacity (Tons)
52.4
41.1
29.0
14.2
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.4
84.0
67.1
72.4
65.0
67.6
Compressor kW
39.2
26.3
15.4
7.3
Unit Efficiency
16.1 / 4.7
18.8 / 5.5
22.6 / 6.6
23.3 / 6.8
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0056SE46
NOT FOR CONSTRUCTION
8 15/16" TO RIGGING HOLES
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
15 1/2" TO COOLER CONN
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
64 1/2"
WATER OUTLET
VICTAULIC
CONNECTION
1 1/2" RIGGING HOLES
PRODUCT DRAWING
14 1/2"
35 1/2"
29"
17 11/16"
34 5/8"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 3,515, OPERATING - 3,648.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 9.8"
9 1/16"
34"
9"
5/8" MOUNTING HOLES (TYP)
50"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
84 1/2"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
25 7/8"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
5 1/2"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
909 (LB)
915 (LB)
15 1/16"
119 5/8"
101 13/16"
9 7/8"
9 7/8"
ORIGIN
Y
A JOHNSON CONTROLS COMPANY
8 5/8"
30 3/8"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
909 (LB)
915 (LB)
X
MODEL: YCWL0056SE46
AHRI CAPACITY 52.4 TONS
YCWL
50 TO 90
93
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0064SE46
59.9
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
143.6
15.7
Water
0.00010
22.4
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
26.9/26.9
187.0/187.0
85.0
95.0
175.8
13.4
Water 0.0
0.00025
19.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
15.7 / 4.6
19.9 / 5.8
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
26.9/26.9
187.0/187.0
3
3883
4016
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
125.0
(1)#10 - 300
107.6
187.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
45.7
45.7
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
94
114.0
150.0
125.0
Capacity (Tons)
59.9
47.1
33.3
16.3
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.4
84.1
67.2
72.5
65.0
67.6
Compressor kW
45.7
31.1
19.1
9.2
Unit Efficiency
15.7 / 4.6
18.2 / 5.3
20.9 / 6.1
21.2 / 6.2
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0064SE46
NOT FOR CONSTRUCTION
8 15/16" TO RIGGING HOLES
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
15 1/2" TO COOLER CONN
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
64 1/2"
WATER OUTLET
VICTAULIC
CONNECTION
1 1/2" RIGGING HOLES
PRODUCT DRAWING
14 1/2"
35 1/2"
29"
17 11/16"
34 5/8"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 3,883, OPERATING - 4,016.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.3"
9 1/16"
50"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
5 1/2"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
9"
5/8" MOUNTING HOLES (TYP)
50"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
84 1/2"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
25 7/8"
1,042 (LB)
966 (LB)
15 1/16"
119 5/8"
101 13/16"
9 7/8"
9 7/8"
ORIGIN
Y
A JOHNSON CONTROLS COMPANY
8 5/8"
30 3/8"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,042 (LB)
966 (LB)
X
MODEL: YCWL0064SE46
AHRI CAPACITY 59.9 TONS
YCWL
50 TO 90
95
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0064HE46
62.4
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
149.6
7.4
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
26.9/26.9
187.0/187.0
85.0
95.0
181.7
6.6
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.5 / 4.8
20.2 / 5.9
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
26.9/26.9
187.0/187.0
3
4533
4848
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
125.0
(1)#10 - 300
107.6
187.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
45.5
45.5
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
96
114.0
150.0
125.0
Capacity (Tons)
62.4
48.5
33.4
16.3
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.0
83.6
66.4
71.5
65.0
67.5
Compressor kW
45.5
31.0
18.9
9.2
Unit Efficiency
16.5 / 4.8
18.8 / 5.5
21.2 / 6.2
21.3 / 6.2
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0064HE46
NOT FOR CONSTRUCTION
67 5/8"
1"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
11 3/4" TO COOLER CONN
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
1 1/2" RIGGING HOLES
12 1/4" TO RIGGING HOLES
PRODUCT DRAWING
14 1/2"
35 1/2"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
23 1/2"
8 1/4"
50"
25 7/8"
34"
9"
124 3/8"
5/8" MOUNTING HOLES (TYP)
50"
101 13/16"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
85"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
1,250 (LB)
1,174 (LB)
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
7 1/8"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,533, OPERATING - 4,848.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.2"
19 13/16"
9 7/8"
9 7/8"
ORIGIN
Y
A JOHNSON CONTROLS COMPANY
8 3/8"
32"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,250 (LB)
1,174 (LB)
X
MODEL: YCWL0064HE46
AHRI CAPACITY 62.4 TONS
YCWL
50 TO 90
97
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0074SE46
67.8
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
162.5
19.9
Water
0.00010
22.4
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
30.4/30.4
225.0/225.0
85.0
95.0
200.2
16.8
Water 0.0
0.00025
19.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
15.2 / 4.5
20.2 / 5.9
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
26.9/26.9
187.0/187.0
3
4061
4194
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
150.0
(1)#10 - 300
114.6
225.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
53.6
53.6
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
72.2
50.0
22.2
98
122.0
150.0
150.0
Capacity (Tons)
67.8
52.5
38.7
16.2
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.0
83.5
67.8
73.2
65.0
67.3
Compressor kW
53.6
34.1
21.8
9.2
Unit Efficiency
15.2 / 4.5
18.5 / 5.4
21.2 / 6.2
21.2 / 6.2
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0074SE46
NOT FOR CONSTRUCTION
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
15 1/2" TO COOLER CONN
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER 68 7/8"
WATER OUTLET
VICTAULIC
CONNECTION
1 1/2" RIGGING HOLES
8 15/16" TO RIGGING HOLES
PRODUCT DRAWING
14 1/2"
35 1/2"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,061, OPERATING - 4,194.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.4"
23 1/2"
9 1/16"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
5 1/2"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
1"
50"
34"
9"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
84 1/2"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
Y
9 7/8"
9 7/8"
ORIGIN
X
A JOHNSON CONTROLS COMPANY
8 5/8"
30 3/8"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
5/8" MOUNTING HOLES (TYP) 1,106 (LB)
1,106 (LB)
50"
990 (LB)
25 7/8"
101 13/16"
125 15/16"
990 (LB)
21 3/8"
MODEL: YCWL0074SE46
AHRI CAPACITY 67.8 TONS
YCWL
50 TO 90
99
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0074HE46
72.7
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
174.4
6.0
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
30.4/30.4
225.0/225.0
85.0
95.0
212.0
8.6
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.3 / 4.8
20.7 / 6.1
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
26.9/26.9
187.0/187.0
3
4911
5406
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
150.0
(1)#10 - 300
114.6
225.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
53.4
53.4
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
72.2
50.0
22.2
100
122.0
150.0
150.0
Capacity (Tons)
72.7
54.6
38.9
16.2
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
75.0
82.3
66.4
71.5
65.0
67.1
Compressor kW
53.4
33.7
21.4
9.1
Unit Efficiency
16.3 / 4.8
19.4 / 5.7
21.9 / 6.4
21.3 / 6.2
JOHNSON CONTROLS
jOHNSON CONTROLS
14 1/2"
29"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0074HE46
NOT FOR CONSTRUCTION
74 5/8"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
16" TO COOLER CONN
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
1 1/2" RIGGING HOLES
12 3/4" TO RIGGING HOLES
PRODUCT DRAWING
40"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,911, OPERATING - 5,406.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.3"
1"
5 1/8"
7 1/8"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
8 1/4"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
29"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
83"
ORIGIN
Y
9 3/8"
33 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
1,409 (LB)
1,294 (LB)
X
A JOHNSON CONTROLS COMPANY
5/8" MOUNTING HOLES (TYP)
50"
101 13/16"
123 5/16"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
9"
1,409 (LB)
1,294 (LB)
18 3/4"
MODEL: YCWL0074HE46
AHRI CAPACITY 72.7 TONS
YCWL
50 TO 90
101
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0084SE46
76.6
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
183.5
24.9
Water
0.00010
22.4
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
30.4/30.4
225.0/225.0
85.0
95.0
224.6
9.5
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
15.8 / 4.6
21.4 / 6.3
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
30.4/30.4
225.0/225.0
3
4489
4684
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
150.0
(1)#10 - 300
121.6
225.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
58.3
58.3
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
102
129.0
150.0
150.0
Capacity (Tons)
76.6
61.0
44.3
21.9
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.9
84.6
68.2
73.6
65.0
67.7
Compressor kW
58.3
39.7
23.5
11.1
Unit Efficiency
15.8 / 4.6
18.4 / 5.4
22.7 / 6.7
23.8 / 7.0
JOHNSON CONTROLS
jOHNSON CONTROLS
14 1/2"
29"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0084SE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
35 1/2"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
68 7/8"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
15 1/2" TO COOLER CONN
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
1 1/2" RIGGING HOLES
8 15/16" TO RIGGING HOLES
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,489, OPERATING - 4,684.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.6"
1"
5 1/8"
7 1/8"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
8 1/4"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
84 1/2"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
X
Y
9 7/8"
A JOHNSON CONTROLS COMPANY
8 5/8"
30 3/8"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,249 (LB)
1,093 (LB) ORIGIN
9 7/8"
5/8" MOUNTING HOLES (TYP)
50"
101 13/16"
125 15/16"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
1,249 (LB)
9"
25 7/8"
1,093 (LB)
21 3/8"
MODEL: YCWL0084SE46
AHRI CAPACITY 76.6 TONS
YCWL
50 TO 90
103
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0084HE46
82.6
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
198.0
7.6
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
30.4/30.4
225.0/225.0
85.0
95.0
239.5
10.6
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.8 / 4.9
21.9 / 6.4
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
30.4/30.4
225.0/225.0
3
5089
5584
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
150.0
(1)#10 - 300
121.6
225.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
58.9
58.9
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
104
129.0
150.0
150.0
Capacity (Tons)
82.6
64.4
44.7
21.9
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.2
83.8
66.6
71.8
65.0
67.5
Compressor kW
58.9
39.7
23.0
11.0
Unit Efficiency
16.8 / 4.9
19.5 / 5.7
23.3 / 6.8
23.8 / 7.0
JOHNSON CONTROLS
jOHNSON CONTROLS
14 1/2"
29"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0084HE46
NOT FOR CONSTRUCTION
74 5/8"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
16" TO COOLER CONN
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
1 1/2" RIGGING HOLES
12 3/4" TO RIGGING HOLES
PRODUCT DRAWING
40"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,089, OPERATING - 5,584.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.5"
1"
5 1/8"
7 1/8"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
8 1/4"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
29"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
83"
ORIGIN
Y
9 3/8"
33 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
1,474 (LB)
1,318 (LB)
X
A JOHNSON CONTROLS COMPANY
5/8" MOUNTING HOLES (TYP)
50"
101 13/16"
125 11/16"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
9"
1,474 (LB)
1,318 (LB)
21 1/8"
MODEL: YCWL0084HE46
AHRI CAPACITY 82.6 TONS
YCWL
50 TO 90
105
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0094SE46
85.9
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
205.8
13.2
Water
0.00010
37.3
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
42.9/42.9
250.0/250.0
85.0
95.0
250.8
11.5
Water 0.0
0.00025
85.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.2 / 4.7
21.5 / 6.3
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
30.4/30.4
225.0/225.0
3
5023
5338
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
200.0
(1)#10 - 300
146.6
250.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
63.8
63.8
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
72.6
50.0
22.6
106
157.0
200.0
175.0
Capacity (Tons)
85.9
66.6
47.8
21.9
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.0
83.6
67.2
72.5
65.0
67.4
Compressor kW
63.8
41.6
25.4
11.0
Unit Efficiency
16.2 / 4.7
19.2 / 5.6
22.5 / 6.6
23.8 / 7.0
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
33 13/16"
OVERALL WIDTH
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0094SE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
14 1/2"
35 1/2"
29"
17 11/16"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
11 3/4" TO COOLER CONN
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
72 1/4"
1 1/2" RIGGING HOLES
12 1/4" TO RIGGING HOLES
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,023, OPERATING - 5,338.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.7"
8 1/4"
23 1/2"
50"
34"
9"
125 15/16"
85"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
Y
A JOHNSON CONTROLS COMPANY
8 3/8"
32"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
1,242 (LB) ORIGIN
X
5/8" MOUNTING HOLES (TYP) 1,427 (LB)
50"
101 13/16"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
1,427 (LB)
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
7 1/8"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
1"
25 7/8"
1,242 (LB)
21 3/8"
MODEL: YCWL0094SE46
AHRI CAPACITY 85.9 TONS
YCWL
50 TO 90
107
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0094HE46
89.4
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
214.3
8.7
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
42.9/42.9
250.0/250.0
85.0
95.0
258.5
5.4
Water 0.0
0.00025
44.1
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.9 / 5.0
21.9 / 6.4
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
30.4/30.4
225.0/225.0
3
5773
6412
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
200.0
(1)#10 - 300
146.6
250.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
63.5
63.5
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
72.6
50.0
22.6
108
157.0
200.0
175.0
Capacity (Tons)
89.4
68.5
47.9
21.9
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
75.6
83.1
66.4
71.6
65.0
67.3
Compressor kW
63.5
41.1
25.1
10.9
Unit Efficiency
16.9 / 5.0
20.0 / 5.9
23.0 / 6.7
24.1 / 7.1
JOHNSON CONTROLS
jOHNSON CONTROLS
15"
30"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0094HE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
42"
29"
33 7/8"
OVERALL WIDTH
17 11/16"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
16" TO COOLER CONN
5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
76 5/8"
1 1/2" RIGGING HOLES
12 3/4" TO RIGGING HOLES
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,773, OPERATING - 6,412.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.6"
5 3/16"
8 5/8"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
8 1/2"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
83"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
108 3/4"
Y
9 7/8"
9 3/8"
35 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,696 (LB)
1,510 (LB) ORIGIN
9 7/8"
X
A JOHNSON CONTROLS COMPANY
5/8" MOUNTING HOLES (TYP)
50"
101 13/16"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
1,696 (LB)
9"
27 1/2"
1,510 (LB)
17 3/16"
121 3/4"
MODEL: YCWL0094HE46
AHRI CAPACITY 89.4 TONS
YCWL
50 TO 90
109
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0104SE46
92.8
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
222.5
11.0
Water
0.00010
37.3
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
42.9/42.9
250.0/250.0
85.0
95.0
271.0
13.1
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.2 / 4.7
20.9 / 6.1
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
42.9/42.9
250.0/250.0
3
5157
5472
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
225.0
(1)#4 - 500
171.6
250.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
68.9
68.9
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
110
182.0
200.0
200.0
Capacity (Tons)
92.8
72.6
50.9
24.9
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.3
83.9
66.9
72.2
65.0
67.5
Compressor kW
68.9
46.5
27.6
13.2
Unit Efficiency
16.2 / 4.7
18.7 / 5.5
22.2 / 6.5
22.6 / 6.6
JOHNSON CONTROLS
jOHNSON CONTROLS
14 1/2"
29"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0104SE46
NOT FOR CONSTRUCTION
71 3/4"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
15 1/2" TO COOLER CONN
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
1 1/2" RIGGING HOLES
12 1/4" TO RIGGING HOLES
PRODUCT DRAWING
38 1/2"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,157, OPERATING - 5,472.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.8"
8 1/4"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
7 1/8"
23 1/2"
50"
9"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
85"
Y
32"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
ORIGIN
8 3/8"
1,476 (LB)
1,260 (LB)
X
A JOHNSON CONTROLS COMPANY
5/8" MOUNTING HOLES (TYP)
50"
124 1/8"
101 13/16"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
1,476 (LB)
25 7/8"
1,260 (LB)
19 9/16"
MODEL: YCWL0104SE46
AHRI CAPACITY 92.8 TONS
YCWL
91 TO 130
111
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0118SE46
110.5
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
264.8
15.1
Water
0.00010
37.3
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
54.5/54.5
310.0/310.0
85.0
95.0
324.5
17.8
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
15.6 / 4.6
23.5 / 6.9
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
42.9/42.9
250.0/250.0
3
4983
5298
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
310.0
(1)#4 - 500
194.8
310.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
84.9
84.9
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
71.8
50.0
21.8
112
208.4
250.0
225.0
Capacity (Tons)
117.2
89.7
64.4
27.7
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
75.6
83.0
67.0
72.1
65.0
67.2
Compressor kW
83.1
49.7
29.4
11.9
Unit Efficiency
16.9 / 5.0
21.7 / 6.4
26.3 / 7.7
27.9 / 8.2
JOHNSON CONTROLS
jOHNSON CONTROLS
14 1/2"
29"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0118SE46
NOT FOR CONSTRUCTION
71 3/4"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
15 1/2" TO COOLER CONN
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
1 1/2" RIGGING HOLES
12 1/4" TO RIGGING HOLES
PRODUCT DRAWING
38 1/2"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,983, OPERATING - 5,298.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.8"
8 1/4"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
7 1/8"
23 1/2"
50"
9"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
85"
Y
32"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
ORIGIN
8 3/8"
1,413 (LB)
1,236 (LB)
X
A JOHNSON CONTROLS COMPANY
5/8" MOUNTING HOLES (TYP)
50"
124 1/8"
101 13/16"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
1,413 (LB)
25 7/8"
1,236 (LB)
19 9/16"
MODEL: YCWL0118SE46
AHRI CAPACITY 110.5 TONS
YCWL
91 TO 130
113
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0118HE46
117.2
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
280.8
14.1
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
54.5/54.5
310.0/310.0
85.0
95.0
334.0
8.4
Water 0.0
0.00025
44.1
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.9 / 5.0
24.7 / 7.2
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
42.9/42.9
250.0/250.0
3
5733
6372
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
310.0
(1)#4 - 500
194.8
310.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
83.1
83.1
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
71.8
50.0
21.8
114
208.4
250.0
225.0
Capacity (Tons)
117.2
89.7
64.4
27.7
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
75.6
83.0
67.0
72.1
65.0
67.2
Compressor kW
83.1
49.7
29.4
11.9
Unit Efficiency
16.9 / 5.0
21.7 / 6.4
26.3 / 7.7
27.9 / 8.2
JOHNSON CONTROLS
jOHNSON CONTROLS
15"
30"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0118HE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
42"
29"
33 7/8"
OVERALL WIDTH
17 11/16"
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
16" TO COOLER CONN
5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
76 5/8"
1 1/2" RIGGING HOLES
12 3/4" TO RIGGING HOLES
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,733, OPERATING - 6,372.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.7"
5 3/16"
8 5/8"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
8 1/2"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
83"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
108 3/4"
Y
9 7/8"
9 3/8"
35 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,681 (LB)
1,505 (LB) ORIGIN
9 7/8"
X
A JOHNSON CONTROLS COMPANY
5/8" MOUNTING HOLES (TYP)
50"
101 13/16"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
1,681 (LB)
9"
25 7/8"
1,505 (LB)
18 3/4"
123 5/16"
MODEL: YCWL0118HE46
AHRI CAPACITY 117.2 TONS
YCWL
91 TO 130
115
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0132SE46
127.4
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
305.3
16.5
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
54.5/54.5
310.0/310.0
85.0
95.0
372.0
14.8
Water 0.0
0.00025
35.2
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.1 / 4.7
23.4 / 6.9
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
54.5/54.5
310.0/310.0
3
5463
6027
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
310.0
(1)#4 - 500
218.0
310.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
94.7
94.7
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
116
231.6
400.0
310.0
Capacity (Tons)
127.4
100.2
70.8
34.7
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.5
84.1
67.2
72.4
65.0
67.5
Compressor kW
94.7
61.0
33.7
15.9
Unit Efficiency
16.1 / 4.7
19.7 / 5.8
25.2 / 7.4
26.2 / 7.7
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0132SE46
NOT FOR CONSTRUCTION
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
16" TO COOLER CONN
5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
74 1/2"
1 1/2" RIGGING HOLES
12 3/4" TO RIGGING HOLES
PRODUCT DRAWING
14 1/2"
40"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,463, OPERATING - 6,027.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.7"
7 3/4"
8 1/8"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
34"
9"
123 5/16"
101 13/16"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
108 1/4"
83"
X
Y
A JOHNSON CONTROLS COMPANY
9 3/8"
33 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
1,415 (LB) ORIGIN
1,598 (LB)
5/8" MOUNTING HOLES (TYP)
50"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
1,598 (LB)
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/4"
23 1/2"
50"
25 7/8"
1,415 (LB)
18 3/4"
MODEL: YCWL0132SE46
AHRI CAPACITY 127.4 TONS
YCWL
91 TO 130
117
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0157SE46
144.0
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
345.1
17.3
Water
0.00010
57.6
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
54.5/54.5
310.0/310.0
85.0
95.0
419.0
15.3
Water 0.0
0.00025
52.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.5 / 4.8
23.5 / 6.9
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
54.5/54.5
310.0/310.0
3
6163
6891
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
231.6
400.0
250.0
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
250.0
() -
Notes:
Operating Condition Electrical Data
Compressor kW
Total kW
104.7
104.7
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
118
218.0
310.0
Across the Line
Capacity (Tons)
144.0
113.5
80.2
39.3
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.5
84.2
67.3
72.5
65.0
67.5
Compressor kW
104.7
68.1
38.0
17.9
Unit Efficiency
16.5 / 4.8
20.0 / 5.9
25.3 / 7.4
26.3 / 7.7
JOHNSON CONTROLS
MODEL: YCWL0157SE46
AHRI CAPACITY 144.0 TONS
YCWL
131 TO 200
jOHNSON CONTROLS
119
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0157HE46
148.5
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
355.9
11.6
Water
0.00010
77.0
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
54.5/54.5
310.0/310.0
85.0
95.0
422.4
12.4
Water 0.0
0.00025
59.1
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
17.1 / 5.0
24.2 / 7.1
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
54.5/54.5
310.0/310.0
3
6863
7807
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
231.6
400.0
250.0
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
250.0
() -
Notes:
Operating Condition Electrical Data
Compressor kW
Total kW
104.3
104.3
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0
120
218.0
310.0
Across the Line
Capacity (Tons)
148.5
116.8
81.4
39.9
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
76.5
84.1
66.9
72.1
65.0
67.5
Compressor kW
104.3
67.2
37.7
17.8
Unit Efficiency
17.1 / 5.0
20.9 / 6.1
25.9 / 7.6
26.9 / 7.9
JOHNSON CONTROLS
MODEL: YCWL0157HE46
AHRI CAPACITY 148.5 TONS
YCWL
131 TO 200
jOHNSON CONTROLS
121
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0177SE46
166.6
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
399.3
14.2
Water
0.00010
77.0
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
49.2/49.2/49.2
242.0/242.0/242.0
85.0
95.0
477.9
15.3
Water 0.0
0.00025
59.1
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
17.1 / 5.0
25.4 / 7.4
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
49.2/49.2
242.0/242.0
3
7318
8262
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
300.0
(1)#4 - 500
246.0
242.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
117.1
117.1
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
80.0
60.0
40.0
20.0
122
258.0
400.0
300.0
Capacity (Tons)
166.6
141.0
108.3
73.3
35.6
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
78.8
87.1
71.0
77.2
65.0
69.1
65.0
67.0
Compressor kW
117.1
80.8
52.8
31.0
15.2
Unit Efficiency
17.1 / 5.0
20.9 / 6.1
24.6 / 7.2
28.4 / 8.3
28.2 / 8.3
JOHNSON CONTROLS
jOHNSON CONTROLS
15"
30"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0177SE46
NOT FOR CONSTRUCTION
23 1/2"
9"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
16" TO COOLER CONN
5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
77 1/2"
CONNECTION
1 1/2" RIGGING HOLES
17 3/4" TO RIGGING HOLES
PRODUCT DRAWING
41"
29"
17 11/16"
34 13/16"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 7,318, OPERATING - 8,262.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 62.9", Y= 11.7"
34"
9"
50"
132 3/4"
102"
5/8" MOUNTING HOLES (TYP)
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
37 5/8"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 3/16"
7 1/8"
50"
2,229 (LB)
1,902 (LB)
14 7/8"
143 7/16"
125 13/16"
Y
11 7/8"
36 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
10 3/8"
A JOHNSON CONTROLS COMPANY
2,229 (LB)
1,902 (LB) ORIGIN
10 3/8"
X
MODEL: YCWL0177SE46
AHRI CAPACITY 166.6 TONS
YCWL
131 TO 200
123
Water Cooled Scroll Chiller
Performance Specification
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0198SE46
198.4
460/3/60
R410A
Evaporator Data
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
475.6
19.6
Water
0.00010
77.0
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (°F)
LWT (°F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
49.2/49.2/49.2
242.0/242.0/242.0
85.0
95.0
566.2
20.4
Water 0.0
0.00025
59.1
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.8 / 4.9
24.8 / 7.3
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
49.2/49.2/49.2
242.0/242.0/242.0
3
7673
8617
4
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
350.0
(1)#4 - 500
295.2
242.0
Across the Line
Operating Condition Electrical Data
Compressor kW
Total kW
141.9
141.9
RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.
* Use Copper Conductors only
Load %
100.0
83.3
66.7
50.0
33.3
16.7
124
308.0
400.0
350.0
Capacity (Tons)
198.4
172.0
144.2
110.2
73.0
35.8
Part Load Rating Data
Cond. EWT (°F)
Cond. LWT (°F)
85.0
95.0
79.7
88.1
74.1
81.0
67.2
72.4
65.0
68.4
65.0
66.7
Compressor kW
141.9
106.6
76.0
50.6
31.5
15.5
Unit Efficiency
16.8 / 4.9
19.4 / 5.7
22.8 / 6.7
26.1 / 7.6
27.8 / 8.1
27.7 / 8.1
JOHNSON CONTROLS
jOHNSON CONTROLS
15"
30"
WATER-COOLED SCROLL CHILLER
MODEL: YCWL0198SE46
NOT FOR CONSTRUCTION
23 1/2"
9"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
Project Name : Contractors Guide
Location :
Engineer :
Contractor :
For :
16" TO COOLER CONN
5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
77 1/2"
CONNECTION
1 1/2" RIGGING HOLES
17 3/4" TO RIGGING HOLES
PRODUCT DRAWING
41"
29"
17 11/16"
34 13/16"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 7,673, OPERATING - 8,617.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 62.9", Y= 11.7"
34"
9"
143 7/16"
50"
102"
5/8" MOUNTING HOLES (TYP)
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
132 3/4"
125 13/16"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
37 5/8"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 3/16"
7 1/8"
50"
2,371 (LB)
1,938 (LB)
14 7/8"
Y
11 7/8"
36 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
10 3/8"
A JOHNSON CONTROLS COMPANY
2,371 (LB)
1,938 (LB) ORIGIN
10 3/8"
X
MODEL: YCWL0198SE46
AHRI CAPACITY 198.4 TONS
YCWL
131 TO 200
125
126
JOHNSON CONTROLS
Printed on recycled paper
Form: 050.05-TD1 (313) Supersedes: 050.05-TD1 (309)
© 2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA
www.johnsoncontrols.com
Download