HURO/0901/028/2.3.1

advertisement
Two countries, one goal, joint success!
PROJECT
HURO/0901/028/2.3.1
UNIVERSITY OF DEBRECEN
2011
Two countries, one goal, joint success!
PROJECT
HURO/0901/028/2.3.1
UNIVERSITY OF DEBRECEN
2011
Two countries, one goal, joint success!
FOREWORD The project E-Laboratory Practical Teaching for Applied Engineering Sciences
(Acronym EPRAS) is implemented under the Hungary-Romania Cross-Border Co-operation
Programme 2007-2013 (www.huro-cbc.eu), and is part-financed by the European Union through
the European Regional Development Fund, Hungary and Romania. The programme aims to
bring the different actors – people, economic actors and communities – closer to each other, in
order to better exploit opportunities offered by the joint development of the border area.
This material contains the documentation associated to the e-laboratories designed by the
project team from University of Debrecen in the frame of this project.
2
www.huro-cbc.eu
Two countries, one goal, joint success!
CONTENTS E‐LABORATORY 4. Industrial process control with Twido PLC. Theoretical background................. 4 E‐LABORATORY 4. Industrial process control with Twido PLC. Grid test......................................... 8 E‐LABORATORY 4. Industrial process control with Twido PLC. Experiment description .............. 10 E‐LABORATORY 4. Industrial process control with Twido PLC. Final report.................................. 12 E‐LABORATORY 5. Amplifier testing with NI ELVIS II test station. Theoretical background ......... 14 E‐LABORATORY 5. Amplifier testing with NI ELVIS II test station. Grid test................................... 16 E‐LABORATORY 5. Amplifier testing with NI ELVIS II test station. Experiment description........... 17 E‐LABORATORY 5. Amplifier testing with NI ELVIS II test station. Final report ............................. 26 E‐LABORATORY 6. Remote flow control. Theoretical background ............................................... 28 E‐LABORATORY 6. Remote flow control. Grid test ....................................................................... 29 E‐LABORATORY 6. Remote flow control. Experiment description ................................................ 31 E‐LABORATORY 6. Remote flow control. Final report .................................................................. 35 3
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 4
Industrial process control with Twido PLC
Theoretical background
1. Bases of the program:
The ladder programming language most commonly used PLC programming tool. The
electrical model developed road plans, they are regarded as equivalent to the software, but
today's PLC systems developer traditional relay logic corresponding elements already too
many complex organizational functions and program analysis techniques allow the use of
ladder programs within
1.1 Basic elements
The Ladder of the following basic elements:
line
contact
coils
function blocks
1.1.1Wires
The graphical representation of the left hand side is positive tápsín vertically on the right side
and negative power supply rails. Between the two horizontal and one below the other current
paths. Each current path on the left are the contacts, the right-hand side of the coils. A current
path (Rung, Network) is a Boolean function implements. The serial or parallel connection
contacts of the AND and OR logic elements to deliver on our relationship. The coil is stored
in the logical result of a function. The Twido PLC in today's PLCs, like most of the logical
functions from top to bottom, a function (ladder line) and within calculates from left to right.
Figure 1 logical function
The (Fig. 1) is: Q = ((A and B) or C) and (not (D)) to implement logic functions. The "A",
"B", "C", "D" may be the binary inputs of the PLC, the "Q" is one of the two-state output, but
there may be internal memory variables. (The above statement, the parentheses in the not (D)
exception is not necessary.)
1.1.2 Function Blocks
This brief summary of today's PLC is located in a number of function blocks, only
measurement is required and the Twido PLC can be used in the main function blocks
shows.timers
The Twido PLC units, operating in three different timer can be used:
4
www.huro-cbc.eu
Two countries, one goal, joint success!
_ Turn on delay TON
_ TOF Off Delay
_ TP Pulse
Figure 2 Timers
Counters.
CU in the counter input rising edge of the counter is increased by 1, the CD input is in a rising
edge is reduced. The R input in logic clears the counter value is TRUE, TRUE value in the S
input and set the value of Preset Value. The counter block compares the current value is
always known. Value preset value, and consistency, the D (Done) logic output is set to TRUE.
The Twido PLC counters can count the 0th .9999 range. Greater numbers of two or more
counters count kaszkádosításával solved. E and F of this output can be used in the bottom
(Empty) or overflow (Full) show (Figure 3)
Figure 3 Counters
Comparator block
The "C" coil is activated when the "A" and "B" contacts are closed, as well as in the previous
example of the counter value is less than 5. The comparator block the usual relational signals
can be used: >> = << == <> Analog input signals when processing the operands can be such a
comparator.: IW0.0%,% MW0
Figure 4 Comparator block
5
www.huro-cbc.eu
Two countries, one goal, joint success!
Arithmetic block
The physical address% MW1000 select the maximum amount of memory. The arithmetic
blocks on the right side of assignment expressions consist of the usual arithmetic operation
symbols + - * /
Analog output signal produced at the left for example, in QW1.0%, +10% MW1.
Figure 5 Arithmetic block
2. Addresses used in programs
The Twido SUITE in the variables (input, output, memory, ...) to address we have. The form
of the following addresses:
Ix.y%:% IWx.y Two state input:
Analog Input
QWx.y%:% Qx.y Analog Output:
Two state output
TMX%:% Mx Timer:
Memory Bit
% Cx: Counter% MWx:
Memory word
3. Symbolic variables
The variables and objects used by the program (timers, counters, etc) should be given
symbolic names and physical addresses instead of the Ladder of contact for them to use. The
program is so readable, easier to understand. The symbols and the physical address mappings
of the Twido Suite-_ Configure menu item can be done. Symbolic names can not contain a
space character, not start with numbers, but you can use accented characters.
4. Subrutin calling
If the programming you want to create junctions, the main program must be taken in the
program. The main program can be selected which do it contains logical and / or function
block instructions. A (Fig. 6) (Figure 7) in the sample program.
Figure 6 Main program
6
www.huro-cbc.eu
Two countries, one goal, joint success!
7. ábra Subrutin
http://www.schneider-electric.hu/hungary/hu/termekek-szolgaltatasok/ipariautomatizalas/termekek/rangepresentation.page?p_function_id=18&p_family_id=234&p_range_id=533#
http://sirkan.iit.bme.hu/dokeos/courses/BMEVIIIA3522551/document/5._m%E9r%E9s_doku
mentumai/TwidoSuite.pdf?cidReq=BMEVIIIA352932b
7
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 4
Industrial process control with Twido PLC
Grid test
Which item does not include the Twido Ladder diagram programming language?
 Switching
 Roll
 Cord
 Cycle
Which logical analysis of this signal corresponds to | | ?
 Switcher
 Keypad
 Timer
 Counter
When to define the physical layout?
 Before Writing Program
 Simulation before
 At any time
How should the plc in the memory area, refer to?
 With ~
 With *
 With @
 With%
Which parameter specifies the current value of the counter function block?
 %C0.d
 %C0.p
 %C0.v
 %C0.e
What kind of logic replaces this circuit?




Q:= A or B or C
Q:=A and B or C and not D
Q:=A and B or C and D
Q:=C and not D
What is the title of a 1.0 analog input?%MW1.0
 %I1.0
 %IW1.0
 %Q1.0
8
www.huro-cbc.eu
Two countries, one goal, joint success!
Which is not Twido Suite, function block?
 TON
 TOF
 TP
 FPGA
Which statement is true for Twido Suite?
 CU input on rising edge of the counter is incremented by one
 CU input on rising edge of the counter is decremented by one
 CU input of the counter is reset on the rising edge
 CU input on falling edge of the counter is incremented by one
Which of the following may be an arithmetic assignment statement?
 %MW=12
 %M:=true
 %MW:=%I0.5
 %MW:=%IW0.1
9
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 4
Industrial process control with Twido PLC
Experiment description
Abstract: The industrial process control systems implemented in software simulation and the
real industrial process control system linking is very important in modern manufacturing
management. These programs to acquire skills necessary for educational level modeling is
extremely important for the development of modern educational methods. A virtual model
visualization will enable the students 24 hours a day for exercise programming task, and
measurement tasks.
1. Tools, softwares
The Vijeo Citect by Schneider Electric's own SCADA system. The program to display and
simulate different production processes used, the Windows XP-style buttons, rounded
rectangles and gradient fills, high-quality user interfaces allow the creation. The Vijeo Citect
by Schneider Electric to other similar software, they sell the hardware components to
communicate via multiple protocols.
2. Measurement task
The visualization interface implemented XYZ scrolling arms are realizing that the movement
can be positioned with PLC programming and different routes of the prepared PLC program
correctness can be checked. In this way students can exercise programming for industrial
control equipment, as well as the written test accuracy of the task may also be checked.
The SCADA software built-in sub-Cicode control can be achieved by performing the task
model, visual information is thus available for detailed understanding of the task (Fig. 1).
Fig. 1
10
www.huro-cbc.eu
Two countries, one goal, joint success!
The PLC program has to be written in the Ladder Diagram language. The problem
can receive multiple difficulty levels, or it may be required to fully design the control program
may, or, for obtaining a correct functionning, it may be necessary to modifiy some values of
the control program in accordance with the preset parameters.
Z axis counter
The value %CO.P may establish the envisaged target, obviously together with the
actual values %CXY.P of parameters (X-Y).
1.
Problems
1) Write a PLC program which cannot be further deleted or modified, but can be
executed again!
2) Write a PLC program which can be modified and executed again!
3) Realize the measurement instructions!
4) Realize a theoretical abstract!
5) Formulate control questions!
11
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 4
Industrial process control with Twido PLC
Final report
Subject of the measurement: ELAB- PLC laboratory programming task
Name: Eszes Elemér, ITM34X
Place of the measurement: University of Debrecen, Faculty of ENgineering
Time:
Tools for the measurement (Apparatus):
 Personal Computer
 Vijeo Designer Demo verzió
 TwidoPLC
 Twido Suite program
Theoretical description:
Engine handling tasks has many conditions in the industry sector..The PLC is the most
suitable hardware for this. Highly complex technical task can be achieved especially with the
use of some programs
Preparation processes of the lab. program:
1. Allocate the space memory
2.
Zle Zfel exclusive-or relationship3.
call is to bring driving axle Subrutin
4.
Subrutin reset call is to bring
5.
Z-axis down - Create a counter
6.
Z-axis stepping algorithm to bring up (3 points)
7.
zero position programming (4 points)
8.
Making the built-in report editor.
In Figure 1. you should see the finished diagram
The completed program was tested in accordance with the specifications of the Vijeo Cictect
Program. All the buttons functions well..
12
www.huro-cbc.eu
Two countries, one goal, joint success!
Figure 1 : Eszes Elemér example.
13
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 5
Amplifier testing with NI ELVIS II test station
Theoretical background
Measure’s concept:
With the help of NI ELVIS II electronic test station we examined different electronic circuits.
Through internet users can make measures at home, they can study the operation of various
circuits through simple test. The control of the measure is done by distance measurement. The
ELVIS system implements tests with real elements and virtual instruments. The virtual and
real-world spectacular assist by connecting youth to the attention of those who wish to learn
electronics. The measurement practices using the NI ELVIS system presents the circuit
operation. Thus, students will gain full knowledge of design of the measuring systems as well.
With the NI ELVIS we can reduce the cost of laboratory equipment, while it contains such lab
tools you may need (eg. digital multimeter, oscilloscope, function generator, etc.). The test
station provides great help in electronics, education for electrical engineering student
especially in circuit construction, but also fo mechanical engineering students and for other
specialized engineering students can be useful.
Measure’s task:
Examination of bipolar transistor circuit analysis
The measurement is in the main circuit switching among the most common used operation,
the most important measurement for determining the characteristics of the Internet. The
amplifier basic characteristics of static and dynamic calculation methods for measuring
learning. Device management exercise.
The object of the measure:
The main circuit switching among the most common used operation, the most important
measurement for determining the characteristics of the Internet. The amplifier basic
characteristics of static and dynamic calculation methods for measuring learning.
The measure’s linking:
14
www.huro-cbc.eu
Two countries, one goal, joint success!
Photos about the linked measurement:
15
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 5
Amplifier testing with NI ELVIS II test station
Grid test
Form the followings which is the alternating current
a.
AC
b.
DC
c.
PC
How to calculate the rms value of sine wave?
a. half the peak value
b. twice the peak value
c. the peak value of √ 2-fold
What is a sinusoidal alternating voltage frequency?
a. the period length of √ 2-fold
b. the number of periods per second
c. phase position of the same length of time between points
How many V is 1234 mV?
a.
1,234V
b.
12,34V
c.
0,1234V
How does works a central base-emitter voltage can be measured in a silicon bipolar
tranzistor?
a.
0,3V
b.
1,5V
c.
0,6V
Which gives the most basic circuit voltage gain?
a.
Joint based
b.
Joint Emitter
c.
Joint collector
How to calculate the experimental results in the strengthening of the stage?
a.
uki/ube
b.
ube/uki
c.
ube*2
Changes in the sinking-load output voltage of the amplifier when load resistance we make it?
a. Yes, it will grow
b. yes, will decrease
c. no change
16
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 5
Amplifier testing with NI ELVIS II test station
Experiment description
Measurement tasks:
1. DC working point measurement data
• Power setting, measurement (UT)
• Base Voltage Measurement (UB)
• emmitter voltage measurement (UE)
• collector voltge measurement (UC)
2. AC measurements
• measuring the output level (p-ubemaxp, ukimaxp-p)
• Gain measurement (Au)
• The gain frequency and phase sequence of determination (Au (f), φ (f))
• Bandwidth and phase shift control Bode analyzer
The measured values in table, create charts, calculations can check the results! Protocol
form documenting the measurement!
The inputs and outputs are defined as:
Characteristics:
connection to the test station:
Power supply (UT):
Amplifier input (Ube):
Amplifier output (UKI):
Base voltage (UB):
Emitter voltage (UE):
Collector voltage (UC):
DMM (COM, V)
SCOPE CH0 (CH0)
SCOPE CH1 (CH1)
SCOPE AI5 (AI5)
SCOPE AI6 (AI6)
SCOPE AI7 (AI7)
Measurement circiut diagram
17
www.huro-cbc.eu
Two countries, one goal, joint success!
Launch the desktop EVISmx NI Instrument Launcher is (Figure 1)!
Figure 1. Program start icon
The next menu screen (Figure 2):
Figure 2. Main menu
DC measurements:
Power Set (UT).
On the Main Menu (Figure 2) VPS icon!
A screen will appear next to the virtual instrument (Figure 3):
Figure 3
Set the positive supply voltage (Voltage), +12 V, and run (Run) button on the screen marked!
Measure the voltage value of the digital multimeter!
The voltage meter to measure the supply voltage is physically connected to COM and V
points.
18
www.huro-cbc.eu
Two countries, one goal, joint success!
On the second Figure DMM icon! Then the following device appears (Figure 4).
Figure 4.
Click on the V button, and then click the button Zero Offset (ON-OFF indication), and run the
Run button (Figure 4)! Record the measured value!
Second Base voltage (UB) is measured (Fig. 5).
Since the DMM connected to only one physical measurement point, so the measurements
were done using an oscilloscope (more selectable measuring points).
The base voltage of the input point is connected to an oscilloscope AI5.
The measurement is carried out without the function generator (the amplifier input is empty),
or the function generator must be set to stop, that does not interfere with the DC
measurements. The oscilloscope "Trigger Type" set to "Immediate" to be in position. On the
second Figure Scope icon!
- The oscilloscope "Channel 0 Source Settings" "SCOPE CH0" value set from AI5!
- The "Run" button to press!
- Check the "Curzor on" setting! The screen shows the C1, C2 cursor line to the on-screen "+"
sign and holding the left mouse button to move. The exact value of the screen under the label
of C1 series can be read. Record the voltage value!
Emitter voltage (UE) measurement (Figure 5).
The AI6 emitter voltage the oscilloscope input point is connected.
- The oscilloscope "Channel 0 Source Settings" to set the value to AI6!
- A measurement equal to the rest of the fourth as described above.
Kollector voltage UC) is measured (Fig. 5).
The AI7 kollector voltage the oscilloscope input point is connected.
19
www.huro-cbc.eu
Two countries, one goal, joint success!
- The oscilloscope "Channel 0 Source Settings" to set the value from AI7!
- If necessary, the "Scale Volts / Div" value to be worth more!
The rest of the measurement corresponds to the fourth as described above.
Figure 5
The measurements of the "Scale Volts / Div" value is set to the measured value is clearly
visible on the screen (eg: 2 V) (Fig. 6)!
Figure 6
AC measurements:
1. Measuring the output level.
On the Main Menu (Figure 2) FGEN icon!
20
www.huro-cbc.eu
Two countries, one goal, joint success!
Figure 7
The function generator to the input of the amplifier is turned on.
Set the waveform (Waveform) Sine (default), frequency (Frequency) from 1kHz, and the
"RUN" key to start, with the function generator signal is input to the amplifier (Figure 7)!
The oscilloscope settings (Figure 8):
- "Channel 0 Source Settings" to set the value on CH0 Source (shows the input signal from the
amplifier)!
- "Channel 1 Source Settings" to set the value of CH1 for Source (the amplifier output signal
shows)!
- Channel 1 Enabled box in stoppage!
- Set the channel mode is attached to C (Coupling)!
- The time base (Time Base), the value set to 1ms, and visibility can also choose a different
value!
- The "Trigger Type" value to "Edge" to the "Trigger Source" to "Chan1 Source" link!
- The signal amplitude of the "Scale Volts / Div" button can be sufficiently large so that the
signal does not hang over the screen, but the maximum size should be!
- In the "Settings Cursors" C2 value of "CH1" to adjust, so the cursor to the C2 channel CH1
(output, UKI) value of the measure. The C1 is the default channel CH0 (input, Ube) shows the
value (8, 9, 10).
21
www.huro-cbc.eu
Two countries, one goal, joint success!
Figure 8
Measure the output level!
The function generator amplitude (Amplitude) of the adjustment knob will increase, while
the oscilloscope "CH1" and channel (output) of the waveform is not distorted (Fig. 9)!
The scale of the pitch much to the extent necessary to adjust so that the signal does not
hang over the screen, but to the largest possible (Figure 9)!
Figure 9
Jegyezze fel a be-és kimeneti jelek értékét (10. ábra) (ubemaxp-p, ukimaxp-p)!
2. Measurement of gain
The function generator amplitude button to set the size of the input signal ubemaxp-p up to
70% of the output signal is free from distortion for sure! Read and record the
22
www.huro-cbc.eu
Two countries, one goal, joint success!
oszcilloszkópról the input and output values (the oscilloscope Vp-p values) using the C1
and C2 kurzorvonalak (Figure 10)! The gain is the ratio of two values.
Au[dB]=20*log(Au)
Figure 10
3. Determination of the frequency response of the gain
The function generator input signal size kept constant, changing the frequency (10Hz, 20Hz,
50Hz, 100Hz, 200Hz, 500Hz, 1kHz, 2kHz, 5kHz, 10kHz, 20kHz, 50kHz, 100kHz) to measure
the gain as described above! Au [dB] and f values in tables and charts make it (Au-log (f))!
The scale of the oscilloscope time base and set the correct value (Figure 11)!
Figure 11
23
www.huro-cbc.eu
Two countries, one goal, joint success!
4. The amplifier stage sequence of defining
The output and the input signal between the time difference (dT) C2 C1és the cursor can be
measured. The phase angle of the "dT" value and the time period can be calculated (Fig. 12).
Calculate the individual frequencies the phase shift (φ), and represents them in the thread with
a frequency diagram (φ-log (f))! Determine the receiver bandwidth (-3dB from points)!
Figure 12
5. The gain bandwidth and phase sequence of control Bode analyzer.
The measurement of "VPS" exception should be stopped any open and close!
On the Main Menu (Figure 2), "Bode" icon!
The Bode analyzer settings (Figure 13):
- The "Stimulus Channel" default "SCOPE CH0".
- The "Response Channel" default "SCOPE CH1".
- The "Steps" default "5".
- "Start Frequency" value to "10" Hz!
- The "Stop Frequency" value to "200k" Hz!
- The "Peak Amplitude" value to "1"!
- The "Op-Amp Signal Polarity" value to "inverted" to!
24
www.huro-cbc.eu
Two countries, one goal, joint success!
Figure 13
The minutes for each frequency compare Kulu, separately measured and calculated results
are shown by the Bode Analyzer charts! Note that the program features (inverted
configuration) due to the f is 0 ˚ 180 ˚ true value!
Photos about switching:
25
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 5
Amplifier testing with NI ELVIS II test station
Final report
The measurements have been done: ....................................................................
The gauge group number: .............................
The measurement date of completion: .................
The measurement is:
Common emitter amplifier of gain, frequency and phase sequence of measurements.
The test subject: PA amplifier ELVIS II n
Measurement tasks:
Frequency datas
measured data
Ut (V)
Ub (V)
Ue (V)
Uc (V)
Ic (mA)
Ie (mA)
value
---------
-----
AC data:
Output level is measured as:
f = 1kHz
Ukimaxp p = ......................
Ubemaxp p = .....................
Ube = (-p * Ubemaxp 0.7) ....................
Gain (Au) and phase angle (φ) measurements of the frequencies given in Table.
f (kHz)
0,01
Ube(Vp-p)
0,02
0,05
0,1
0,2
0,5
1
2
5
10
20
50
100
200
Uki(Vp-p)
Au
##### ##### ##### ##### ##### ##### ##### ##### ##### ##### ##### ##### ##### #####
Au(dB)
##### ##### ##### ##### ##### ##### ##### ##### ##### ##### ##### ##### ##### #####
∆T(ms)
φ(°)
-360
-360
-360
-360
-360
-360
-360
26
-360
-360
-360
-360
-360
-360
-360
www.huro-cbc.eu
Two countries, one goal, joint success!
Represents the gain (Au (dB)) is a function of frequency.
Represents the phase angle is a function of frequency.
27
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 6
Remote flow control
Theoretical background
The measurement name: FluidLab
The test site: University of Debrecen, Faculty of Engineering, Department of Electrical
Engineering and Mechatronics
Measurement Objective: Flow Control and control remotely
Measuring accessibility: http://epras.webhost.uoradea.ro/
Description of the measurement:
To carry out this exercise the knowledge of computer's basic handling is essential. By
performing the measurement trainees could implement control technique and regulate
processes under real conditions. The results of interventions remotely can be traced on an
operating model that appears on the user's own computer (Figure 2) and by the help of the
image of a web camera.
In case of remote operation the fluid flow could be controlled by a mixer and two pumps.
During the control it is possible to measure, monitor the heating and cooling temperature
curve of the water in the tank. The control loop time constants could be calculated from the
resulting characteristics. Using the specified time constants one can set the classic PID control
parameters. The effect of the calculated control parameters can be tested using the station.
If necessary, the results can be further refined.
Figure 1. Reactor station
Figure 2. Functional block diagram of Reactor
station
The list of measuring instruments used:
 Temperature sensor (3B1),
 Capacitive proximity sensor (3B2),
 Capacitive proximity sensor (3B3),
 Float switch (3B10),
 Reactor tank (B301),
 Heating element (3M1),
 Cooling pump (3M2),
 Pump to drain liquid (3M3),
 Stirring motor (3M4)
28
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 6
Remote flow control
Grid test
1. What kind of sensors are used at the reactor station:
a.
Temperature sensor, electric heater, limit switch, capacitive proximity sensor
b.
Temperature sensor, capacitive proximity sensor, flow meter
c.
Temperature sensor, float switch, capacitive proximity sensor
d.
Float switch, limit switch, capacitive proximity sensor
2. Contactless detection of the liquid in the container:
3. Capacitive proximity sensors are used to sense the liquid level in the container. They
are used to detect both the lower and upper liquid levels through the wall of the
container. What is the working philosophy of this sensor?
a.
The liquid changes the distance of a capacitor integrated in the proximity
sensor.
b.
The liquid changes the capacity of a capacitor integrated in the proximity
sensor.
c.
The proximity sensor changes the distance of the liquid in the tank.
d.
The proximity sensor changes the capacity of the liquid in the tank.
4. What kind of actuators are used at the reactor station:
a.
pump, heating element, stirring module, valve
b.
pump, heating element, stirring module, ultrasonic sensor
c.
filter, valve, temperature sensor
d.
pump, heating element, stirring module
5. How can you control the heating power of the heating element?
a.
By PWM pulse width modulation
b.
By AM amplitude modulation
c.
By FM frequency modulation
d.
By switching on-off
6. The process temperature of a liquid in the tank is to be controlled. To set the controller
properly, we should determine the time constant of the controlled system.
a.
We can find its value in the manual
b.
We can measure it
c.
We can calculate it
d.
We can ask an expert
7. What kind of controller is used at this station?
a.
PID
b.
PI
c.
PD
d.
Smith predictor
29
www.huro-cbc.eu
Two countries, one goal, joint success!
8. What is this controller used for?
a.
To control the speed of the stirring module.
b.
To control the flow of the liquid.
c.
To control the level of the liquid.
d.
To control the power of the heating element.
9. What kind of processes could be performed by this station?
a.
Heating, stirring and circulating a liquid.
b.
Mixing together different type of liquids.
c.
Cooling liquid.
d.
Filtering, heating and stirring a liquid.
10. What is the maximum temperature of the container must not be exceeded.
a.
+25° C
b.
+5° C
c.
+65° C
d.
+55° C
11. System supply requirements:
a.
230 V AC mains
b.
230 V AC mains and 24 V DC power pack
c.
compressed air, 230 V AC mains
d.
24 V AC mains and 230 V DC power pack
30
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 6
Remote flow control
Experiment description
1. To start the measurement please press this button
FluidLab-PA V3.0 for MPS-PA.lnk
2. In the next page please select the Reactor station.
3. In 3.1.0 you can see the demo of the process. In 3.2.0 you can measure with the
station, in 3.3.0 you can control the station.
31
www.huro-cbc.eu
Two countries, one goal, joint success!
4. In 3.1.0 point, on the right corner, youcan see the automatic operation of the station.
Such as 1. Charge, 2. Heating, 3. Mixing, 4.Heating, 5. discharge.
32
www.huro-cbc.eu
Two countries, one goal, joint success!
5. In point 3.2.1 You can try the operation from A0 to A3.
33
www.huro-cbc.eu
Two countries, one goal, joint success!
6. A 3.3.2 Under continuous control you can set the parameters
34
www.huro-cbc.eu
Two countries, one goal, joint success!
E-Laboratory 6
Remote flow control
Final report
Measure: ELAB- Fluid measure
Name: Proba Elek, KóD123
Place of the measure: University of Debrcen, Faculty of Engineering
Date:
Tools used for the measure (Apparatus):






Personal Computer
Elab remote operation and testing environment
MPS-PA Reactor Workstation
FESTO PLC
FESTO PID controller
PC Ethernet Communication
Background:
Many applications require a heating element to accurately control system or process
temperature. This lab investigates the use of proportional integral derivative (PID)
temperature control for heating tracking as shown in next Figure.
PID Temperature Controller
EP (s)
D (s)
Electric Heating Element
SKV
+
+
KP
VA (s)
+
Heater
S
(s)
(s)
1
S
+
_
KI
S
35
www.huro-cbc.eu
Two countries, one goal, joint success!
Elek PROBA
36
www.huro-cbc.eu
University of Debrecen
Debrecen, Egyetem tér 1 sz.
Tel. 0036 52 415 155
www.unideb.hu
The content of this material does not necessarily represent the official position of the
European Union.
www.huro-cbc.eu
Download