Low voltage power cables halogen free, flame retardant NHXMH-0 NHXMH-J Uo/U - 300/500V Standard: DIN VDE 0250 part 214 Cu conductors • XLPE insulation • LSF sheaths Application The power insulated conductors flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for Uo/U 300/500 V in: important objects - power stations (nuclear, thermal), transformer substations, metro, airport, public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, places with great concentration of people and material values whose safety in case of fire should be guaranteed. The conductors are designed for laying over, in and under plasters in dry and wet premises as well as in brickwork”s and concrete. They are also suitable for outdoor use. The conductors should not be laid directly in vibro concrete or rammed concrete and directly under ground. Cable construction Construction Conductor Core identification According to VDE 0250-214 Сu wires according to VDE 0295 (HD 383) cl.1 or 2 (IEC 60228) XLPE compound 2XI1 (DIX8) to VDE 0276-604 according to VDE 0250 and VDE 0293 Inner sheath halogen free compound Insulation Technical data Conductor resistance at o 20 C according to VDE 0295 (IEC60228) class 1 or 2 Operating temperature о 70 С Short circuit temperature Nominal voltage Uo/U: Test voltage Bending radius, min Tests 160 С / 5 s max./ 300/500 V АС - 2kV 4xD cable DIN VDE 0250-214 VDE 0472 ч804/ С( IEC 3323/СandВ) flame retardancy Sheath Color halogen free compound, flame retardant type LTS 1 grey RAL 7035 -corrosivity of combustion gases pH - min 4.3; σ-max100µS/cm -density of smoke gases о VDE 0472ч813 (IEC 607541и2) VDE 0472ч816 (IEC 610341и2) Color coding Single core - black or yellow/green Double core - black ; blue or yellow/green; black 3 - core 4 - core black; blue; brown black; blue; brown; black; or or yellow/green; black; blue yellow/green; black; blue brown ; 5 - core black; blue; brown; black; black or yellow/green; black; blue ; brown; black; multiple cores black with number mark on cores or black with number mark on cores and yellow/green core in the outer cover Construction data MHXMH-0, MHXMH-J 300/500V Number of conductors and nominal cross section Thickness of insulation Thickness of inner sheath Thickness of sheath N х mm2 mm mm mm min/mm 1x1,5re 1x2,5re 1x4,0re 1x6,0re 1x10re 1x16rm 2x1,5re 2x2,5re 2x4,0re 3x1,5re 3x2,5re 3x4,0re 3x6,0re 3x10re 3x16rm 3x25rm 3x35rm 4x1,5re 4x2,5re 4x4,0re 4x6,0re 4x10re 4x16rm 4x25rm 4x35rm 5x1,5re 5x2,5re 5x4,0re 5x6,0re 5x10re 5x16rm 5x25rm 5x35rm 7x1,5re 7x2,5re 0,5 0,5 0,6 0,6 0,7 0,7 0,5 0,5 0,6 0,5 0,5 0,6 0,6 0,7 0,7 0,9 0,9 0,5 0,5 0,6 0,6 0,7 0,7 0,9 0,9 0,5 0,5 0,6 0,6 0,7 0,7 0,9 0,9 0,5 0,5 1,4 1,4 1,4 1,4 1,4 1,4 0,4 0,4 0,4 0,4 0,4 0,4 0,4 0,6 0,8 0,8 1,0 0,4 0,4 0,6 0,6 0,6 0,8 1,0 1,0 0,4 0,4 0,6 0,6 0,6 0,8 1,0 1,2 0,4 0,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,6 1,6 1,6 1,8 1,8 1,4 1,4 1,6 1,6 1,6 1,6 1,8 1,8 1,4 1,4 1,6 1,6 1,6 1,8 1,8 1,8 1,4 1,6 5,0 5,4 6,0 6,4 7,4 8,6 8,0 8,8 10,0 8,4 9,3 10,5 12,0 14,5 17,0 21,0 23,5 9,0 10,0 12,0 13,0 15,5 19,0 23,5 26,5 9,6 10,5 13,0 14,5 17,0 21,0 25,5 28,5 10,0 12,0 Mass of Cu approx. Mass of cable approx. max/mm kg/km kg/km 8,8 9,4 10,0 10,5 12,0 13,5 9,4 10,5 12,0 9,8 11,0 12,5 14,0 16,5 20,5 25,5 28,5 10,5 11,5 14,0 15,5 18,0 22,5 28,0 31,0 11,5 12,5 15,5 16,5 19,5 25,0 30,5 34,5 12,0 14,0 14 29 37 55 94 149 28 46 75 43 70 112 168 282 460 728 1010 57 93 149 223 376 614 970 1346 71 116 187 279 470 767 1213 1683 100 163 48 61 79 112 160 230 108 140 205 131 178 239 325 503 769 1164 1542 150 211 309 242 630 969 1490 1935 178 240 380 480 730 1145 1798 2495 210 302 Cable diameter approx.