Low voltage power cables halogen free, flame retardant NHXMH

advertisement
Low voltage power cables
halogen free, flame retardant
NHXMH-0
NHXMH-J
Uo/U - 300/500V
Standard: DIN VDE 0250 part 214
Cu conductors • XLPE insulation • LSF sheaths
Application
The power insulated conductors flame retardant, with low halogen free smoke emission and corrosion at fire
conditions are suitable for use in electrical installations for Uo/U 300/500 V in:
important objects - power stations (nuclear, thermal), transformer substations, metro, airport,
public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers,
places with great concentration of people and material values whose safety in case of fire should be
guaranteed.
The conductors are designed for laying over, in and under plasters in dry and wet premises as well as in
brickwork”s and concrete. They are also suitable for outdoor use.
The conductors should not be laid directly in vibro concrete or rammed concrete and directly under ground.
Cable construction
Construction
Conductor
Core
identification
According to VDE 0250-214
Сu wires according to
VDE 0295 (HD 383) cl.1 or 2
(IEC 60228)
XLPE compound
2XI1 (DIX8) to VDE 0276-604
according to VDE 0250
and VDE 0293
Inner sheath
halogen free compound
Insulation
Technical data
Conductor resistance at
o
20 C
according to VDE 0295
(IEC60228) class 1 or 2
Operating temperature
о
70 С
Short circuit temperature
Nominal voltage Uo/U:
Test voltage
Bending radius, min
Tests
160 С / 5 s max./
300/500 V
АС - 2kV
4xD cable
DIN VDE 0250-214
VDE 0472 ч804/ С( IEC 3323/СandВ)
flame retardancy
Sheath
Color
halogen free compound, flame
retardant type LTS 1
grey RAL 7035
-corrosivity of combustion
gases
pH - min 4.3;
σ-max100µS/cm
-density of smoke gases
о
VDE 0472ч813 (IEC 607541и2)
VDE 0472ч816 (IEC 610341и2)
Color coding
Single core - black or yellow/green
Double core - black ; blue or yellow/green; black
3 - core
4 - core
black; blue; brown
black; blue; brown; black;
or
or
yellow/green; black; blue
yellow/green; black; blue
brown ;
5 - core
black; blue; brown; black;
black
or
yellow/green; black; blue ;
brown; black;
multiple cores
black with number mark on
cores
or
black with number mark on
cores and yellow/green
core in the outer cover
Construction data
MHXMH-0, MHXMH-J 300/500V
Number of
conductors and
nominal cross
section
Thickness of
insulation
Thickness
of inner
sheath
Thickness of
sheath
N х mm2
mm
mm
mm
min/mm
1x1,5re
1x2,5re
1x4,0re
1x6,0re
1x10re
1x16rm
2x1,5re
2x2,5re
2x4,0re
3x1,5re
3x2,5re
3x4,0re
3x6,0re
3x10re
3x16rm
3x25rm
3x35rm
4x1,5re
4x2,5re
4x4,0re
4x6,0re
4x10re
4x16rm
4x25rm
4x35rm
5x1,5re
5x2,5re
5x4,0re
5x6,0re
5x10re
5x16rm
5x25rm
5x35rm
7x1,5re
7x2,5re
0,5
0,5
0,6
0,6
0,7
0,7
0,5
0,5
0,6
0,5
0,5
0,6
0,6
0,7
0,7
0,9
0,9
0,5
0,5
0,6
0,6
0,7
0,7
0,9
0,9
0,5
0,5
0,6
0,6
0,7
0,7
0,9
0,9
0,5
0,5
1,4
1,4
1,4
1,4
1,4
1,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,6
0,8
0,8
1,0
0,4
0,4
0,6
0,6
0,6
0,8
1,0
1,0
0,4
0,4
0,6
0,6
0,6
0,8
1,0
1,2
0,4
0,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,4
1,6
1,6
1,6
1,8
1,8
1,4
1,4
1,6
1,6
1,6
1,6
1,8
1,8
1,4
1,4
1,6
1,6
1,6
1,8
1,8
1,8
1,4
1,6
5,0
5,4
6,0
6,4
7,4
8,6
8,0
8,8
10,0
8,4
9,3
10,5
12,0
14,5
17,0
21,0
23,5
9,0
10,0
12,0
13,0
15,5
19,0
23,5
26,5
9,6
10,5
13,0
14,5
17,0
21,0
25,5
28,5
10,0
12,0
Mass of
Cu
approx.
Mass of cable
approx.
max/mm
kg/km
kg/km
8,8
9,4
10,0
10,5
12,0
13,5
9,4
10,5
12,0
9,8
11,0
12,5
14,0
16,5
20,5
25,5
28,5
10,5
11,5
14,0
15,5
18,0
22,5
28,0
31,0
11,5
12,5
15,5
16,5
19,5
25,0
30,5
34,5
12,0
14,0
14
29
37
55
94
149
28
46
75
43
70
112
168
282
460
728
1010
57
93
149
223
376
614
970
1346
71
116
187
279
470
767
1213
1683
100
163
48
61
79
112
160
230
108
140
205
131
178
239
325
503
769
1164
1542
150
211
309
242
630
969
1490
1935
178
240
380
480
730
1145
1798
2495
210
302
Cable diameter
approx.
Download