FIRE ALARM DEVICE LEGEND
SE1.0.0.A
SECURITY ELECTRONICS OVERALL SECURITY CONDUIT SITE PLAN
SE1.0.0.B
SECURITY ELECTRONICS OVERALL TEL/DATA CONDUIT SITE PLAN
SE1.0.1
SECURITY ELECTRONICS OVERALL SITE PLAN - ALTERNATE #3
SE1.0.1.A
SECURITY ELECTRONICS OVERALL SECURITY CONDUIT SITE PLAN - ALTERNATE #3
SE1.0.1.B
SECURITY ELECTRONICS OVERALL TEL/DATA CONDUIT SITE PLAN - ALTERNATE #3
3.
SE1.1A.1
SECURITY ELECTRONICS FLOOR PLAN - STANDARD HOUSING
SE1.1B.1
SECURITY ELECTRONICS FLOOR PLAN - STANDARD HOUSING
SE1.2.1
SECURITY ELECTRONICS FLOOR PLAN - HIGH SECURITY HOUSING
SE1.3.1
SECURITY ELECTRONICS FLOOR PLAN - DORM HOUSING - ALTERNATE #3
SE1.4.1
SECURITY ELECTRONICS FLOOR PLAN - ADMINISTRATION
SE1.5.1
SECURITY ELECTRONICS FLOOR PLAN - SUPPORT
SE1.6.1
SECURITY ELECTRONICS FLOOR PLAN - GYM & SCHOOL
SE1.7.1
SECURITY ELECTRONICS FLOOR PLAN - EXISTING DORM HOUSING REMODEL
SE2.1A.1
FIRE ALARM FLOOR PLAN - STANDARD HOUSING
SE2.1B.1
FIRE ALARM FLOOR PLAN - STANDARD HOUSING
SE2.2.1
FIRE ALARM FLOOR PLAN - HIGH SECURITY HOUSING
SE2.3.1
FIRE ALARM FLOOR PLAN - DORM HOUSING -ALTERNATE #3
SE2.4.1
FIRE ALARM FLOOR PLAN - ADMINISTRATION
SE2.5.1
FIRE ALARM FLOOR PLAN - SUPPORT
SE2.6.1
FIRE ALARM FLOOR PLAN - GYM & SCHOOL
SE2.7.1
FIRE ALARM FLOOR PLAN - EXISTING DORM HOUSING REMODEL
SE3.0.1
SECURITY ELECTRONICS LARGE SCALE SITE GATES
SE4.0.1
SECURITY ELECTRONICS OVERALL SITE PLAN CAMERA SCHEDULE
SE4.0.2
SECURITY ELECTORNICS PERIMETER CAMERA ELEVATIONS
SE4.0.3
SECURITY ELECTORNICS PERIMETER CAMERA ELEVATIONS
SE4.0.4
SECURITY ELECTRONICS BUILDING 1A CAMERA SCHEDULE & VIEWS
SE4.0.5
SECURITY ELECTRONICS BUILDING 1B CAMERA SCHEDULE & VIEWS
SE4.0.6
SECURITY ELECTRONICS BUILDING 2 CAMERA SCHEDULE & VIEWS
SE4.0.7
SECURITY ELECTRONICS BUILDING 2 CAMERA VIEWS
4.
5.
6.
7.
8.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
SE4.0.8
SECURITY ELECTRONICS BUILDING 3 -ALT. #3- CAMERA SCHEDULE & VIEWS
21.
SE4.0.9
SECURITY ELECTRONICS BUILDING 4 CAMERA SCHEDULES & VIEWS
22.
SE4.0.10
SECURITY ELECTRONICS BUILDING 4 CAMERA VIEWS
SE4.0.11
SECURITY ELECTRONICS BUILDING 5 CAMERA SCHEDULE & VIEWS
SE4.0.12
SECURITY ELECTRONICS BUILDING 5 CAMERA VIEWS
SE4.0.13
SECURITY ELECTRONICS BUILDING 6 CAMERA SCHEDULE & VIEWS
SE4.0.14
SECURITY ELECTRONICS BUILDING 6 CAMERA VIEWS
SE4.0.15
SECURITY ELECTRONICS BUILDING 7 CAMERA SCHEDULE & VIEWS
SE5.0.1
SECURITY ELECTRONICS, CONDUIT DETAILS
SE5.0.2
SECUIRTY ELECTRONICS, MISCELLANEOUS DETAILS
SE6.0.1
SECURITY ELECTRONICS, PLC RISER
SE6.0.2
SECURITY ELECTRONICS, CCTV RISER
23.
FIRE ALARM ANNUNCIATOR MOUNTED SO THAT THE TOP OF THE PANEL IS
48" ABOVE FINISHED FLOOR. "MOUNT" REFERS TO THE TYPE OF
MOUNTING AS FOLLOWS:
S = SURFACE WALL MOUNTED 4'-0" AFF.
F = FLUSH WALL MOUNTED 4'-0" AFF.
FAA
MOUNT
ID.#
AUXILIARY POWER SUPPLY PANEL MOUNTED SO THAT THE CENTER OF THE
PANEL IS 48" ABOVE FINISHED FLOOR. "MOUNT" REFERS TO THE TYPE OF
MOUNTING AS FOLLOWS:
S = SURFACE WALL MOUNTED 4'-0" AFF.
F = FLUSH WALL MOUNTED 4'-0" AFF.
MOUNT
AUX
ADDRESS
MOUNT
AUX
ADDRESS
RI
ADDRESS
MOUNT
ADDRESSABLE SPOT SMOKE DETECTOR. "ADDRESS" REFERS TO THE UNIQUE
ADDRESS NUMBER ASSIGNED TO THE DEVICE. CERTAIN DEVICES MAY HAVE AN
AUXILIARY RELAY PROVIDED FOR SPECIAL FUNCTIONS. "AUX" DEFINES THESE
SPECIAL FUNCTIONS. "MOUNT" REFERS TO THE TYPE OF MOUNTING. IF NOT
DESIGNATED, THEN THE DETECTOR MOUNTS ON THE CEILING IN THE LOCATION
INDICATED ON THE PLANS ON A 4" OCTAGONAL BOX. "AUX" AND "MOUNT" CAN
HAVE THE FOLLOWING ALTERNATIVE VALUES:
BT = BEAM DETECTOR TRANSMITTER
BR =BEAM DETECTOR RECIEVER
DH = DOOR HOLDER RELEASE.
FD = FIRE DOOR RELEASE.
SS = SINGLE STATION SMOKE DETECTOR.
WG = UNIT IS PROVIDED WITH A PROTECTIVE METAL GUARD.
P = PHOTOELECTRIC.
I = IONIZATION.
R = RELAY BASE.
ID = IN DUCT (INSIDE CELL CHASE).
DPR = SMOKE DAMPER ACTIVATION.
DUCT SMOKE DETECTOR. "ADDRESS" REFERS TO THE UNIQUE ADDRESS
NUMBER ASSIGNED TO THE DEVICE. CERTAIN DEVICES MAY HAVE AN
AUXILIARY RELAY PROVIDED FOR SPECIAL FUNCTIONS. "AUX" DEFINES
THESE SPECIAL FUNCTIONS AS FOLLOWS:
AHU = AIR HANDLING UNIT SHUTDOWN.
DPR = SMOKE DAMPER ACTIVATION.
ALARM LED THAT ILLUMINATES WHENEVER THE CONNECTED DUCT SMOKE
DETECTOR IS ACTIVATED. MOUNT ON CEILING BELOW CONCEALED DUCT
SMOKE DETECTORS.
HEAT DETECTOR "ADDRESS" REFERS TO THE UNIQUE ADDRESS NUMBER
ASSIGNED TO THE DEVICE. "MOUNT" REFERS TO OPTIONAL MOUNTING
ARRANGEMENTS. IF NOT DESIGNATED, THEN THE DETECTOR MOUNTS ON A
4" OCTAGONAL CEILING BOX IN THE LOCATION INDICATED ON THE PLANS.
OPTIONAL MOUNTING ARRANGEMENTS ARE AS FOLLOWS:
EX = MOUNTED BEHIND EXHAUST GRILL IN CELL.
WG = PROTECTIVE GUARD.
WF
ADDRESS
FIRE SPRINKLER WATER FLOW SWITCH FURNISHED AND INSTALLED BY
SPRINKLER CONTRACTOR AND MONITORED BY THE FIRE ALARM SYSTEM.
"ADDRESS" REFERS TO THE UNIQUE ADDRESS OR ZONE NUMBER ASSIGNED TO
THE DEVICE.
VS
FIRE SPRINKLER VALVE TAMPER (SUPERVISORY) SWITCH FURNISHED AND
INSTALLED BY SPRINKLER CONTRACTOR AND MONITORED BY THE FIRE ALARM
SYSTEM. "ADDRESS" REFERS TO THE UNIQUE ADDRESS OR ZONE NUMBER
ASSIGNED TO THE DEVICE.
ADDRESS
PTZ
ID
MOUNT
G
ID
m
ID
ADDRESS
SE6.0.3
SECURITY ELECTRONICS, CATV RISER
SE6.0.4
SECURITY ELECTRONICS, POWER RISER
SE6.0.5
SECURITY ELECTRONICS, POWER RISER CONTINUED
SE6.0.6
SECURITY ELECTRONICS, CARD ACCESS RISER
SE6.0.7
SECURITY ELECTRONICS, INTERCOM RISER
SE6.0.8
FIRE ALARM - SECURITY ELECTRONICS, FIRE RISER
WIRE SCHEDULE
SYSTEM NAME
MANUFACTURER
PART NUMBER
WET PART NUMBER
DESCRIPTION
COLOR
CARD ACCESS SYSTEM PROXIMITY CARD READER
EQUAL TO WEST PENN
D441
AQC3186
3 PAIR, SHIELDED, TWISTED, 18 AWG
GRAY
REQUEST TO EXIT MOTION DETECTOR
EQUAL TO WEST PENN
222
AQC292
1 PAIR, UNSHIELDED, STRANDED, OVERALL JACKET, 20 AWG
GRAY
REQUEST TO EXIT HARDWARE
EQUAL TO WEST PENN
222
AQC292
1 PAIR, UNSHIELDED, STRANDED, OVERALL JACKET, 20 AWG
GRAY
CCTV IP CAMERA
EQUAL TO COMMSCOPE
874010204/10 10G4
J2R CABLING 10692-C6A/CMXT
4 PAIR CAT6A UTP
GREEN (DRY)/BLACK WITH GREEN TAPE
(WET)
COUNTY DATA JACKS
EQUAL TO COMMSCOPE
874010204/10 10G4
J2R CABLING 10692-C6A/CMXT
4 PAIR CAT6A UTP
ORANGE (DRY)/ BLACK WITH ORANGE TAPE
(WET)
5
ADDENDUM
F
ADDRESS
MOUNT
CANDELA
HEIGHT
CIRCUIT
FIRE SPRINKLER POST INDICATOR VALVE SWITCH FURNISHED AND
INSTALLED BY SPRINKLER CONTRACTOR AND MONITORED BY THE FIRE
ALARM SYSTEM. "ADDRESS" REFERS TO THE UNIQUE ADDRESS OR ZONE
NUMBER ASSIGNED TO THE DEVICE.
MANUAL PULL STATION. "ADDRESS" REFERS TO THE UNIQUE ADDRESS OR ZONE
NUMBER ASSIGNED TO THE DEVICE. INSTALL DEVICE 4'-0" AFF. "MOUNT"
REFERS TO OPTIONAL MOUNTING CONFIGURATIONS AS FOLLOWS:
WG = PROTECTIVE GUARD.
K = KEY REQUIRED TO ACTIVATE STATION.
WALL MOUNTED VISUAL ONLY NOTIFICATION APPLIANCE. "CIRCUIT" REFERS TO
THE UNIQUE IDENTITY ASSIGNED TO THE DEVICE. INSTALL DEVICE FLUSH AT
6'-8" UNLESS INDICATED DIFFERENTLY BY "HEIGHT". "WG" INDICATES A UL
LISTED PROTECTIVE GUARD. "CANDELA" REFERS TO THE DIFFERENT
INTENSITIES AS FOLLOWS:
15 CANDELA
30 CANDELA
75 CANDELA
110 CANDELA
MONITORED DOOR. "ID" IS THE ARCHITECTURAL DOOR NUMBER . THE LOWER
CASE m INDICATES A SENTROL SWITCH INSTEAD OF A DETENTION DOOR
POSITION SWITCH.
E
CONTROLLED DOOR WITH SECURITY LOCK. TERMINATE CONDUIT IN DOOR
FRAME LOCK POCKET OR DOOR POSITION SWITCH POCKET. "ID" IS THE
ARCHITECTURAL DOOR NUMBER.
es
COMMERCIAL DOOR ELECTRIC STRIKE. "ID" IS THE ARCHITECTURAL DOOR
NUMBER.
ID
ID
ID
CONTROLLED COMMERCIAL PEDESTRIAN GATE LOCK. "ID" IS THE ARCHITECTURAL
GATE NUMBER.
e
ID
MUSHROOM BUTTON DURESS SWITCH WITH KEY RESET. "G" INDICATES THAT
THE BUTTON IS TO BE PROVIDED WITH A CIRCULAR GUARD TO PREVENT
ACCIDENTAL ACTIVATION. "ID" IS FOR IDENTIFICATION ONLY AND DOES NOT
REPRESENT A COUNT. MOUNT IN SINGLE GANG BOX MOUNTED 4'-0" AFF
UNLESS STATED OTHERWISE.
ID
D
G
INTERCOM STATION, THREE GANG BOX, WALL MOUNTED 4'-0" AFF AND A MAXIMUM OF
IC ID
8" FROM DOOR. "FR" FRAME MOUNTED. "ID" IS FOR IDENTIFICATION ONLY AND DOES
NOT REPRESENT A COUNT.
INTERCOM STATION ON PEDESTAL. FURNISH AND INSTALL INTERCOM,
PEDESTAL, AND WEATHER RESISTANT HOUSING. PROVIDE TEMPLATE AND
BOLTS TO GENERAL CONTRACTOR FOR INSTALLATION IN BASE. "ID" IS FOR
IDENTIFICATION ONLY AND DOES NOT REPRESENT A COUNT.
ID
TOUCHSCREEN CONTROL STATION. A COMPUTER STATION COMPLETE WITH A
TOUCHSCREEN MONITOR FOR OPERATING THE LOCKING CONTROL SYSTEM. REFER
TO SPECIFICATION SECTION 284600.
TCS
IP VIDEO VIEWING WORKSTATION. A COMPUTER STATION FOR CONTROLLING TWO
MONITORS. REFER TO SPECIFICATION SECTION 282300.
CARD ACCESS ENROLLMENT STATION. REFER TO SPECIFICATION SECTION
281300.
IP VIDEO VIEWING MONITOR CONTROLLED BY AN IP WORKSTATION COMPUTER.
REFER TO SPECIFICATION SECTION 282300.
IP.#
CAE
MON
ERC
PRINT
EDUCATION DATA JACKS
EQUAL TO COMMSCOPE
874010204/10 10G4
J2R CABLING 10692-C6A/CMXT
4 PAIR CAT6A UTP
BLUE (DRY)/ BLACK WITH BLUE TAPE (WET)
PLC DATA JACKS
EQUAL TO COMMSCOPE
874010204/10 10G4
J2R CABLING 10692-C6A/CMXT
4 PAIR CAT6A UTP
YELLOW (DRY)/ BLACK WITH YELLOW TAPE
(WET)
DOOR CONTROL
EQUAL TO BELDEN
27084A
DOOR POSITION SWITCH
EQUAL TO WEST PENN
224
27084A
AQC293
6 CONDUCTORS - STRANDED, THWN, 14 AWG
BLACK
2 CONDUCTORS - UNSHIELDED WITH OVERALL JACKET, 18 AWG
GRAY
CIRCUIT
CANDELA
HEIGHT
CIRCUIT
DURESS STATION
222
EQUAL TO WEST PENN
AQC292
2 CONDUCTORS - UNSHIELDED WITH OVERALL JACKET, 20 AWG
GRAY
DOOR CHIME
EQUAL TO WEST PENN
222
AQC292
2 CONDUCTORS - UNSHIELDED WITH OVERALL JACKET, 20 AWG
GRAY
INTERCOM STATION
EQUAL TO WEST PENN
357
AQC357
4 CONDUCTORS - 2 SHIELD, 2 UNSHIELDED, TWISTED, 22 AWG
GRAY
AUX AOM
ADDRESS
CALL STATION
EQUAL TO WEST PENN
222
AQC292
2 CONDUCTORS - UNSHIELDED WITH OVERALL JACKET, 20 AWG
GRAY
NURSE CALL - DOME LAMP
EQUAL TO WEST PENN
222
AQC292
2 CONDUCTORS - UNSHIELDED WITH OVERALL JACKET, 20 AWG
GRAY
AUX
AIM
ADDRESS
NURSE CALL - RESET STATION
EQUAL TO WEST PENN
222
AQC292
2 CONDUCTORS - UNSHIELDED WITH OVERALL JACKET, 20 AWG
GRAY
VISITATION PHONE
EQUAL TO WEST PENN
292
AQC292
1 PAIR, UNSHIELDED, STRANDED, OVERALL JACKET, 20 AWG
GRAY
NOTE: CONDUIT IS TO BE INSTALLED BY ELECTRICAL CONTRACTOR. PROVIDE WET RATED CABLE FOR UNDERGROUND INSTALLATION AS REQUIRED BY NEC.
CEILING MOUNTED VISUAL ONLY NOTIFICATION APPLIANCE. "CIRCUIT" REFERS
TO THE UNIQUE IDENTITY ASSIGNED TO THE DEVICE. INSTALL DEVICE FLUSH
AT CEILING. "WG" INDICATES A UL LISTED PROTECTIVE GUARD. "CANDELA"
REFERS TO THE DIFFERENT INTENSITIES AS FOLLOWS:
15 CANDELA
30 CANDELA
75 CANDELA
110 CANDELA
COMBINATION AUDIBLE AND VISUAL NOTIFICATION APPLIANCE. "CIRCUIT"
REFERS TO THE UNIQUE IDENTITY ASSIGNED TO THE DEVICE. INSTALL DEVICE
FLUSH AT 6'-8" UNLESS INDICATED DIFFERENTLY BY "HEIGHT". "C" INDICATES
CEILING MOUNTED. "WG" INDICATES A UL LISTED PROTECTIVE GUARD.
"CANDELA" REFERS TO THE DIFFERENT INTENSITIES AS FOLLOWS:
15 CANDELA
30 CANDELA
75 CANDELA
110 CANDELA
ADDRESSABLE OUTPUT MODULE. PROVIDES UNIQUE ADDRESS FOR CONTROL.
"AUX" DEFINES THE FOLLOWING FUNCTIONS:
DH = DOOR HOLDER RELEASE.
FD = FIRE DOOR RELEASE.
DPR = SMOKE DAMPER ACTIVATION.
TRANSIENT VOLTAGE SURGE SUPPRESSOR COMPATIBLE WITH FIRE ALARM SYSTEM.
LOCATE WHERE WIRING LEAVES THE BUILDING.
XS
EXTERIOR FIRE STROBE.
B
EXTERIOR FIRE BELL.
ESC
SECURITY SYSTEM INTEGRATOR.
RB
RESET BUTTON FOR DIRECT SUPERVISION DOME LAMPS AND DOME LAMPS.
SINGLE GANG BOX MOUNTED 4'-0" ABOVE FINISHED FLOOR.
DL
DOME LAMP. DIRECT SUPERVISOIN DOME LAMP. SINGLE GANG BOX CENTERED
ABOVE FLOOR.
C
CALL BUTTON, SINGLE GANG BOX, WALL MOUNTED 18" AFF NEAR SHOWER STALL.
"ID" IS FOR IDENTIFICATION ONLY AND DOES NOT REPRESENT A COUNT.
RDR
PROXIMITY CARD READER MOUNTED ON SINGLE GANG BOX 4'-0" AFF. "ID" IS FOR
IDENTIFICATION ONLY AND DOES NOT REPRESENT A COUNT.
REX
REQUEST TO EXIT BUTTON MOUNTED ON SINGLE GANG BOX 4'-0" AFF. "ID" IS FOR
IDENTIFICATION ONLY AND DOES NOT REPRESENT A COUNT.
M = MOTION DETECTOR CENTERED ABOVE DOOR LOCATED IN THE ALUMINUM
PANEL ABOVE THE FRAME.
COMMUNICATIONS OUTLET MOUNTED 18" ABOVE FINISHED FLOOR (UNLESS NOTED OTHERWISE) AND SIX
INCHES FROM POWER RECEPTACLE. FURNISH AND INSTALL A SEPARATE CAT6 OR CAT6A CABLE FOR
2TD
EACH OUTLET. FURNISH AND INSTALL A SEPARATE 1" CONDUIT FROM EACH OUTLET BACK TO LOCAL IT
RACK FOR OUTLETS WITH MORE THAN TWO JACKS. CABLING CANNOT BE EXPOSED. WHITE DATA JACKS
DENOTE THOSE OWNED BY THE COUNTY SHERIFF AND GO BACK TO THEIR IDF ROOM. ALTERNATE
NOTATIONS AS FOLLOWED:
C = COUNTER MOUNTED OUTLET 4" ABOVE COUNTER BACKSPLASH. COORDINATE WITH MILLWORK
PROVIDER.
CL = CEILING MOUNTED BACKBOX.
F = FLOOR MOUNTED BACKBOX.
Y = YOUTH TELEPHONE RJ45 CAT 6 TELEPHONE JACK
W = WALL MOUNTED OUTLET 48" AFF TO TOP OF BACKBOX.
#X = RJ45 CAT 6A DATA JACK MOUNTED 12' AFF FOR WIRELESS. "#" INDICATES QUANTITY.
#T = RJ45 CAT 6 TELEPHONE JACK. "#" INDICATES QUANTITY OTHER THAN ONE.
#D = RJ45 CAT 6 DATA JACK. "#" INDICATES QUANTITY OTHER THAN ONE.
#V= RJ45 CAT 6 DATA JACK FOR VIDEO VISITIATION
SO= SPECIALTY OUTLET THAT CONECTS AN HDMI AND VGA CABLE TO A TELEVISION OR PROJECTOR.
SECURITY CONTRACTOR SHALL CONFIRM ALL CABLE/CONDUIT REQUIREMENTS WITH ELECTRICAL CONTRACTOR BEFORE INSTALLATION.
DH
No.P1
No.P5
No.P2
240/120 VAC EMERGENCY
BUILDING
PANEL
L1
240/120 VAC
UPS DISTRIBUTION
PANEL
EXTERNAL BYPASS SWITCH
WITH AC DISCONNECT
(MBB)
L2
UPS NOTES FOR DETAIL 1/SE0.0:
P1. DIVISION 26 TO FURNISH AND INSTALL OVERCURRENT PROTECTION AS
REQUIRED BY NATIONAL ELECTRIC CODE.
P2. DIVISION 28 TO FURNISH AND DIVISION 26 TO INSTALL MAKE BEFORE BREAK
BYPASS SWITCH (MBB).
EMT CONDUIT
EMT CONDUIT
P3. DIVISION 28 TO FURNISH AND DIVISION 26 TO INSTALL UPS SYSTEM.
AC TO UPS
INPUT
AC FROM
UPS OUTPUT
GR N L1 L2
GR N L1 L2
L2
GR N L1 L2
GR N L1 L2
AC LINE INPUT
AC LINE LOADS
L1
TO
LOADS
No.P11
FC
GR
GR
P5. DIVISION 26 TO USE EMERGENCY POWER SOURCE. REFER TO ELECTRICAL E5.02.
VP
VISITATION PHONES. REFER TO SPECIFICATION 275123.
P6. DIVISION 26 TO FURNISH AND INSTALL CONDUIT AND PULL STRING TO BE
CONNECTED TO DIVISION 28 PLC EQUIPMENT RACK.
P
PULL BOX MOUNTED IN CHASE, ON WALL, OR ABOVE LAY-IN CEILING. SIZE AS
REQUIRED. PROVIDE EXTENSION RINGS IF REQUIRED.
P7. DIVISION 28 TO FURNISH AND INSTALL CABLE AND PROGRAM PLC POINTS TO
ANNUNCIATE AND LOG UPS ALARMS.
TV
CATV OUTLET. FURNISH SINGLE GANG BACKBOX. COORDINATE HEIGHT WITH
DIVISION 26.
P8. LIQUID TIGHT FLEXIBLE STEEL CONDUIT.
VR
EQUIPMENT TO POWER VISITATION PHONES AND RECORD THE AUDIO FROM THE
VISITATION PHONES. REFER TO SPECIFICATION 275123 FOR DETAILS.
CB
P9. DIVISION 26 TO PROVIDE CONDITIONED POWER.
P10. REFER TO 1/SE6.04 & 1/SE6.05 AND ELECTRICAL DRAWINGS FOR PANEL NAMES
AND VOLTAGES.
P11. DIVISION 26 TO PROVIDE THE TVSS FOR THE INPUT VOLTAGE TO THE UPS SYSTEM.
3 2 1
LINE INPUT
No.P3
+DC X3X2X1
BUILDING GROUNDING
ELECTRODE OR
PROTECTIVE EARTH SYSTEM
N
-DC
OUTPUT POWER
COMM
PLC
No.P6
UPS
No.P7
BUILDING GROUNDING
ELECTRODE OR
PROTECTIVE EARTH SYSTEM
5
ADDENDUM
DOOR ALARM CHIME TO NOTIFY ANYONE IN THE LOCAL BUILDING IF A DOOR HAS
BEEN OPENED.
CH
No.P9
No.P4
FIELD CABINET TO BRING LOCAL ELECTRONICS BACK TO THE SECURITY ROOM.
P4. DIVISION 26 TO FURNISH AND INSTALL UPS POWER DISTRIBUTION PANEL,
CONDUIT AND WIRING.
No.P1
No.P8
2TD SOLID FILLED DATA JACKS DENOTE THOSE PROVIDED BY THE MONTEREY COUNTY OFFICE OF
EDUCATION(MCOE) FOR THEIR PROGRAMS AND GO BACK TO THEIR IDF ROOM. COMMUNICATIONS OUTLET
MOUNTED 18" ABOVE FINISHED FLOOR (UNLESS NOTED OTHERWISE) AND SIX INCHES FROM POWER
RECEPTACLE. FURNISH AND INSTALL A SEPARATE CAT6A CABLE FOR EACH OUTLET SHOWN. FURNISH AND
INSTALL A SEPARATE 1" CONDUIT FROM EACH OUTLET BACK TO LOCAL IT RACK FOR OUTLETS WITH MORE
THAN TWO JACKS. CABLING CANNOT BE EXPOSED. ALTERNATE NOTATIONS AS FOLLOWED:
C = COUNTER MOUNTED OUTLET 4" ABOVE COUNTER BACKSPLASH. COORDINATE WITH MILLWORK PROVIDER.
CL = CEILING MOUNTED BACKBOX.
F = FLOOR MOUNTED BACKBOX.
W = WALL MOUNTED OUTLET 48" AFF TO TOP OF BACKBOX.
#X = RJ45 CAT 6A DATA JACK MOUNTED 12' AFF FOR WIRELESS. "#" INDICATES QUANTITY.
#T = RJ45 CAT 6A TELEPHONE JACK. "#" INDICATES QUANTITY OTHER THAN ONE.
#D = RJ45 CAT 6A DATA JACK. "#" INDICATES QUANTITY OTHER THAN ONE.
PH
ALEPH MY 40 PHOTOELECTRIC BEAM ON A PEDESTAL USED AT GATES TO ENSURE
GATES DO NOT SHUT ON VEHICLES.
N
TVSS
5/11/2016 10:01:07 AM
C:\Users\dustinb\Documents\Revit MEP 2015\Monterey County\75-14126-00_0_SS_2015_Central.dustinBrown.rvt
N
MAGNETIC DOOR HOLDER DEVICE TO KEEP DOORS OPEN. DEVICE WILL
RELEASE AND CLOSE UPON ACTIVATION OF THE SMOKE DETECTORS OR LOSS
OF POWER.
ID WATCH TOUR STATION MOUNTED 48" ABOVE FINISHED FLOOR. DEVICE IS TO
CONSIST OF A SWITCH AND LED AS SPECIFIED IN SECTION 284619 AND
281300. ID IS FOR IDENTIFICATION ONLY AND DOES NOT REPRESENT A
COUNT. PROVIDE A BACKBOX COMPATIBLE WITH THE DEVICE PROVIDED.
PERIMETER WATCH TOUR STATIONS MOUNTED 60" ABOVE FINISHED GRADE.
W
ADDRESSABLE INPUT MODULE. PROVIDES UNIQUE ADDRESS FOR MONITORING.
"AUX" DEFINES THE FOLLOWING FUNCTIONS:
HOOD = KITCHEN HOOD ACTIVATION.
AP = AIR PRESSURE.
WL = WATER LEVEL.
FPR = FIRE PUMP RUNNING.
FPP = FIR PUMP PHASE REVERSAL.
TVSS
EVENT RECORDING COMPUTER. A COMPUTER STATION THAT RECORDS THE
EVENTS OF THE LOCKING CONTROL SYSTEM. REFER TO SPECIFICATION
SECTION 284600.2.
EVENT RECORDING PRINTER. A COMPUTER PRINTER THAT GENERATES HARD
COPIES OF THE ERC REPORTS. REFER TO SPECIFICATION SECTION 284600.2.
MORSEMAN KEYWATCH CABINET. REFER TO SPECIFICATION SECTION 281300
KEY
CANDELA
CCTV CAMERA. PTZ DENOTES A PAN-TILT ZOOM CAMERA. OTHER CAMERAS ARE FIXED WITH
FIELDS OF VIEW AS INDICATED ON THE PLANS. "ID" IS FOR CAMERA IDENTIFICATION ONLY AND
DOES NOT REPRESENT A COUNT. PROVIDE A 4" SQUARE BOX WITH FLEXIBLE CONDUIT TO
HOUSING. REFER TO EACH BUILDING'S CAMERA SCHEDULE IN THE SE4.## SHEETS FOR
CAMERA MOUNTING HEIGHTS. "MOUNT" REFERS TO THE TYPE OF MOUNTING AS FOLLOWS:
C = INTERIOR CEILING MOUNTED TO 4" SQUARE 2 1/8" DEEP BOX.
P = POLE MOUNTED SEE DETAIL. REFER TO SHEET SE5.0.2.
W = INTERIOR WALL MOUNTED TO 4" SQUARE 2 1/8" DEEP BOX.
CRNR = INTERIOR CORNER MOUNTED.
XCRNR = EXTERIOR CORNER MOUNTED.
XC = EXTERIOR CEILING WITH HOOK MOUNT.
XW = EXTERIOR WALL MOUNTED.
FP = FENCE POST MOUNTED. REFER TO SHEET SE5.0.2.
.
VEHICLE GATE OPERATOR WITH LOCAL POWER BY DIVISION 26. COORDINATE
CONTROLS INTERFACE WITH GATE CONTROLLER SUPPLIER. "ID" IS THE
ARCHITECTURAL DOOR NUMBER.
M
IC
VS PIV
LOCATIONS OF CONTROL PANELS, RACKS AND SPECIAL PULL BOXES. REFER TO RISERS AND THE SPECIFICATION
FOR SPECIFIC EQUIPMENT. "ID" IDENTIFIES THE PANEL AND IS NOT A COUNT OF PANELS. PANELS ARE
IDENTIFIED AS FOLLOWS:
CP.# = CONTROL PANEL FOR OPERATING DOORS. MOUNTED IN TURRET ON THE COUNTER.
SEC = SECURITY ELECTRONICS RACK WITH MULTIPLE SYSTEMS.
IC.# = INTERCOM EQUIPMENT RACK.
LR.# = FREE STANDING LOCKING RACK OR PULL CABINET.
PLC.# = PLC CONTROL RACK.
VID = IP VIDEO EQUIPMENT RACK.
TELE = WALL MOUNTED TELEPHONE PUNCHDOWN BLOCKS FOR OWNER FURNISHED YOUTH
TELEPHONE EQUIPMENT.
TD = RACK FOR MOUNTING TELEPHONE/DATA NETWORK EQUIPMENT.
TVSS = TRANSIENT VOLTAGE SURGE SUPPRESSION CABINET.
MBB = MAKE BEFORE BREAK BYPASS SWITCH FOR UPS
UPS = UNINTERRUPTIBLE POWER SUPPLY.
CATV = PLYWOOD MOUNTED CABLE TELEVISION EQUIPMENT.
VID-VIS = WALL MOUNTED VIDEO VISITATION EQUIPMENT FURNISHED BY OWNER.
VAULT
CODE ANALYSIS ROADMAP
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
COUNTY OF MONTEREY NEW JUVENILE HALL
SECURITY ELECTRONICS OVERALL SITE PLAN
.
ARROWS INDICATE A CONDUIT HOME RUN TO THE CABINET OR PULL BOX
INDICATED. HOME RUNS THAT ARE SUPPRESSED ARE ROUTED FIRST TO THE
APPROPRIATE SURGE SUPPRESSION CABINET AND THEN TO THE TERMINATING
EQUIPMENT (I.E. "TVSS1, LR" INDICATES THAT THE RUN IS ROUTED TO THE TVSS1
SUPPRESSION CABINET AND THEN TO THE APPROPRIATE LOCKING RACK.)
CONCRETE CHRISTY BOX FOR SITE CONDUIT. SIZE AS REQUIRED.
IT VAULT FOR SITE CONDUIT. SIZE AS REQUIRED.
5
ADDENDUM
FOR SCOPE OF WORK DEPICTION AND GROSS BUILDING AREAS, REFER TO CP0.01 - CODE ANALYSIS.
FOR OCCUPANT LOADS, AND BASIC DESCRIPTIONS OF REFUGE SCHEMES, REFER TO CP1.1A.1
FOR CODE ANALYSIS, RATED WALLS, AND INTERIOR EXITING SCHEMES, REFER TO CODE PLANS CP1.1A.1 TO CP1.7.1
(IF APPLICABLE) FOR CODE ANALYSIS OF EXISTING BUILDING, REFER TO SHEETS CP0.05 (FOR REFERENCE ONLY)
FOR LOCATIONS OF RATED ENCLOSURES INCLUDING WALLS, DOORS, AND WINDOWS, SEE CODE PLANS CP1.1A.1 TO CP1.7.1
FOR SCHEDULES OF RATED SECURITY DOORS, SEE A9.1. FOR SCHEDULE OF RATED STANDARD DOORS, SEE A9.5
FOR LIST OF WALL TYPES AND WALL DETAILS DESCRIBING RATED ASSEMBLIES SEE WALL TYPE SHEET CP3.1 - CP4.2
FOR UL LISTINGS RATED WALLS, HEAD OF WALL DETAILS, PENETRATIONS, AND ASSEMBLIES REFER TO WALL DETAIL SHEETS
BEGINNING AT CP4.1
FOR WALL TYPE CALLOUTS AND WALL TAGS, REFER TO FLOOR PLANS A1 SERIES & ENLARGED FLOOR PLANS A2 SERIES.
FOR LOCATIONS OF CODE-REQUIRED SIGNAGE REFER TO CODE PLANS CP4.4
(IF APPLICABLE FOR ADDITION WORK) FOR EXITING PATHS DURING CONSTRUCTION REFER TO SHEET CP0.05
FOR EXITING PATHS EXTERIOR TO THE FACILITY REFER TO CP0.04 LIFE SAFETY SITE PLAN.
FOR SITE ACCESSIBILITY AND PATH OF TRAVEL TO PUBLIC WAY, REFER TO CP0.04
(IF APPLICABLE) FOR GENERATOR DATA, REFER TO E5 DRAWINGS
FOR FIRE ALARM DESIGN, REFER TO SPECIFICATION SECTION 28 3111 AND SHEETS SE2.1.1A.1 TO SE2.7.1
FOR MECHANICAL FIRE/ SMOKE DAMPERS LOCATIONS SEE M1.1A.1 TO M1.7.1. FOR DAMPER DETAILS SEE M4.1 FOR
DETAILS OF SECURITY BAR AT DAMPERS SEE SP2.5
OFFICE OF THE STATE FIRE MARSHAL
APPROVED FIRE AND PANIC ONLY
Reviewed by:________________________________________
Fire & Life Safety Division-North
DATE:
Approval of this plan does not authorize or approve any
omission or deviation from applicable regulations. Final
approval is subject to field inspection. One set of approved
plans shall be available on the project site at all times.
SFM FILE #
© 2015 , DLR Group inc. of California, a California corporation, ALL RIGHTS RESERVED
SE1.0.0
2.
3.
MOUNT
TVSS1, SEC
5-12-2016
SECURITY ELECTRONICS, LEGEND & GENERAL NOTES
FIRE ALARM CONTROL PANEL WITH BUILT IN ANNUNCIATOR MOUNTED SO THAT THE CENTER
OF THE PANEL IS 48" ABOVE FINISHED FLOOR. "MOUNT" REFERS TO THE TYPE OF MOUNTING
AS FOLLOWS:
S = SURFACE WALL MOUNTED 4'-0" AFF.
F = FLUSH WALL MOUNTED 4'-0" AFF.
FACP
DEVICE AND CONDUIT LAYOUT ON FLOOR PLANS IS DIAGRAMMATIC AND IS PROVIDED TO INDICATE
HOW SYSTEMS ARE INSTALLED, INTERCONNECTED, AND ROUTED. REFER TO ARCHITECTURAL
DRAWINGS FOR EXACT BUILDING DIMENSIONS AND CONFIGURATION.
DIVISION 26 TO FURNISH AND INSTALL ALL 120 VAC POWER FOR THE DIVISION 27/28 EQUIPMENT.
DIVISION 26 TO PROVIDE CIRCUIT BREAKERS IN POWER PANELS TO SERVE EQUIPMENT RACKS,
CCTV MONITORS, AND COMPUTER STATIONS AS INDICATED ON THE DRAWINGS.
THE DIVISION 27/28 EQUIPMENT SHALL BE CONNECTED TO A UNIFIED GROUND SYSTEM PROVIDED
BY DIVISION 26. ALL TRANSIENT VOLTAGE SURGE SUPPRESSION GROUND CONNECTIONS MUST BE
NO GREATER THAN 1 OHM.
ALL DIVISION 27/28 SECURITY ELECTRONICS CONTROL EQUIPMENT IS TO BE POWERED FROM UPS
CIRCUITS.
DIVISION 26 TO PROVIDE ALL CONDUIT. CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED. ESC
TO COORDINATE CONDUIT, BACK BOX, AND LOCATION WITH DIVISION 26.
ANY MODIFICATION TO CONDUIT ROUTINGS FROM THAT SHOWN ON THESE PLANS MUST BE
SUBMITTED AND APPROVED PRIOR TO INSTALLATION. ALL CONDUIT INSTALLATION SHALL BE
SUPERVISED BY A MASTER LICENSED ELECTRICIAN.
ALL CONDUIT INSTALLED IN OTHER THAN EQUIPMENT ROOMS SHALL BE CONCEALED.
FULLY COORDINATE THE MOUNTING LOCATIONS OF ALL PULL BOXES AND CONDUIT ROUTING WITH
ALL TRADES. ALL DEVICES SHALL BE FIELD LOCATED TO AVOID DAMAGE FROM DOORS OPENING
AND CONTACTING WALLS.
INSTALL ALL PULL BOXES BEHIND ACCESS PANELS OR IN ACCESSIBLE AREAS.
DIVISION 26 SHALL FURNISH AND INSTALL A 2 AMP 120 VAC POWER CIRCUIT FROM THE SECURITY
SYSTEM UPS TO EACH EXTERIOR MOUNTED CAMERA USING FIBER. CIRCUIT IS USED TO POWER
CAMERA AND MEDIA CONVERTERS AT EACH CAMERA LOCATION.
LOW VOLTAGE WIRING SHALL BE INSTALLED IN A SEPARATE RACEWAY FROM ALL 120 VAC
CONDUCTORS.
CONDUITS ROUTED INTO CONTROL ROOMS AND BEHIND COUNTERS SHALL STUB UP INTO
CONSOLE OR WIRE CHASE PROVIDED BEHIND MILLWORK.
CONDUIT IN YOUTH AREAS, AND WHERE FEASIBLE IN THE REMAINDER OF THE FACILITY SHALL BE
ROUTED UNDER SLAB.
JUNCTION BOXES SHALL BE SIZED TO ACCEPT THE NUMBER OF TERMINATING CONDUITS.
FURNISH A HOME RUN CONDUIT FOR EACH DEVICE OR GROUP OF DEVICES AS INDICATED ON THE
PLANS. NO MORE THAN TWO DEVICES OF THE SAME SYSTEM CAN BE CONNECTED TOGETHER
AND THEN HOME RUN BACK TO THE MAIN EQUIPMENT ROOM.
DEVICES AND PANELS ARE NUMBERED BY BUILDING. FOR EXAMPLE A COMPUTER CONTROL
STATION IN BUILDING 1A IS LABELED "TCS.1A". MULTIPLE OCCURRENCES OF THE SAME PANEL ARE
DESIGNATED WITH AN ADDITIONAL LETTER.
ALL DIVISION 27 & 28 SYSTEMS COMMUNICATION BETWEEN AREAS SHALL BE OVER OPTIC FIBERS.
THE DIVISION 28 CONDUIT SHOWN ON THESE DRAWINGS SHALL BE
REVIEWED/APPROVED/COORDINATED BY THE SECURITY ELECTRONICS
CONTRACTOR/INTEGRATOR.
PROVIDE A BACKBOX SCHEDULE FOR ALL DIVISION 27/28 EQUIPMENT PRIOR TO CONDUIT
INSTALLATION. CONDUIT AND BACKBOXES SHALL BE SIZED TO ACCEPT THE NUMBER OF WIRES TO
BE INSTALLED. PROVIDE CONDUIT AND WIRING SCHEDULE INDICATING CONDUIT AND FILL RATIO
COMPLIES WITH CEC.
DIVISION 28 CONTRACTOR SHALL FULLY COORDINATE THE FINAL LOCATION OF ALL CAMERAS TO
PREVENT CAMERA VIEWS BEING BLOCKED BY LIGHT FIXTURES, HVAC FIXTURES, AND ALL OTHER
OBSTRUCTIONS. DIVISION 28 CONTRACTOR SHALL INCLUDE IN THE BID, COST TO RELOCATE 10%
OF THE CCTV CAMERAS.
FULLY COORDINATE ALL DEVICES AND INSTALLATION WITH APPROVED HVAC AND SPRINKLER
PLANS AND SHOP DRAWINGS.
DIVISION 26 TO FURNISH AND INSTALL CONDUIT AND WIRE FOR POWER DISTRIBUTION AS REQUIRED
BY CEC AND LOCAL CODES. DIVISION 26 TO PROVIDE CONDUIT AND WIRE FROM BREAKER PANEL
TO TVSS CABINET, FROM TVSS CABINET TO RACK TERMINATION POINTS, AND FROM BREAKER TO
CONTROL ROOM RECEPTACLE. FULLY COORDINATE EQUIPMENT INSTALLATION WITH DIVISION 26.
THE SECURITY SYSTEM OPERATION AND MAINTENANCE MANUALS ARE TO BE SUPPLIED AT THE
FINAL INSPECTION.
Revisions
5 ADDENDUM
SE0.0
1.
Architecture Engineering Planning Interiors
2.
SPECIAL SYSTEMS
FURNISH AND INSTALL A CODE COMPLIANT FIRE ALARM SYSTEM. PROVIDE FIRE ANNUNCIATORS IN EACH CONTROL
STATION, CENTRAL CONTROL, AND FOR FIRE DEPARTMENT ACCESS.
FURNISH AND INSTALL A UUKL LISTED FIRE FIGHTER'S CONTROL PANEL WHERE INDICATED ON THE PLANS AS PART
OF THIS SYSTEM. SYSTEM SHALL PROVIDE FUNCTIONS AS REQUIRED FOR THE PROPER OPERATION OF THE
EXHAUST SYSTEM.
THE FIRE ALARM SYSTEM SHALL CONFORM TO THE 2013 CALIFORNIA ELECTRICAL CODE (CEC) ARTICLE 760 AND THE
2013 CALIFORNIA FIRE CODE (CFC) 15.7 AND 907.
INSTALLATION OF THE FIRE ALARM SYSTEM SHALL NOT START UNTIL DETAILED PLANS AND SPECIFICATIONS,
INCLUDING CALIFORNIA STATE FIRE MARSHALL (CSFM) LISTING NUMBERS FOR EACH COMPONENT OF THE SYSTEM
HAVE BEEN APPROVED BY THE CALIFORNIA STATE FIRE MARSHALL.
FIRE ALARM WILL BE A DEFFERED SUBMITTAL TO THE AHJ. THE INSTALLING CONTRACTOR SHALL SUBMIT SHOP
DRAWINGS WITH THE FOLLOWING INFORMATION:
a. BUILDING DATA INFORMATION
b. SCOPE OF PROJECT
c. MANUFACTURE'S SPECIFICATION SHEET ON ALL FIRE ALARM EQUIPMENT
d. SYMBOL FOR ALL FIRE ALARM DEVICES BEING INSTALLED
e. FLOOR PLANS SHOWING FIRE ALARM DEVICES
f. LOCATION OF ALL FIRE RATED WALLS
g. SEQUENCE OF OPERATION MATRIX TABLE
h. SINGLE LINE RISER DIAGRAM
i. POINT TO POINT WIRING DIAGRAM
j. BATTERY CALCULATIONS
k. VOLTAGE DROP CALCULATIONS
l. IDENTIFICATION OF WIRE TYPE TYPE TOP BE USED FOR THE FIRE ALARM SYSTEM
m. ELEVATION DETAILS OF MANUAL FIRE BOXES AND VISUAL DEVICES
n. DESIGN NUMBER AND DETAIL OF THROUGH PENETRATION FIRE STOP SYSTEM
o. CURRENT CFSM LISTING SHEETS FOR ALL COMPONENTS
p. SYMBOLS SHALL BE COMPLIANT WITH NFPA 70
q. ADDITIONAL INFORMATION AS REQUIRED FOR APPROVAL BY THE CALIFORNIA STATE FIRE MARSHALL
THE FIRE ALARM SYSTEM SHALL BE EQUIPPED WITH AN OCCUPANT NOTIFICATION SYSTEM IN ACCORDANCE
WITH THE SECTION 907.5 OF THE CALIFORNIA BUILDING CODE.
THE FIRE ALARM OPERATION AND MAINTENANCE MANUALS ARE TO BE SUPPLIED AT THE FINAL INSPECTION.
DIVISION 26 TO FURNISH AND INSTALL ALL FIRE CONDUIT.
75-14126-00
9-01-15
1.
Sheet Name
SECURITY ELECTRONICS, LEGEND & GENERAL NOTES
Sheet Number
SE0.0
SECURITY ELECTRONICS-SHEET INDEX
100%
CONSTRUCTION
DOCUMENTS
SPECIAL SYSTEMS DEVICE LEGEND
1414 Natividad Road
Salinas CA
GENERAL NOTICES:
FIRE ALARM GENERAL NOTES