Series ELC-P2.cdr

advertisement

Emergency Lighting Control

For Use With Series CBS Central Battery System for Emergency Lighting

Series ELC-P2

ELCP2.05.15.00

GENERAL DESCRIPTION

ELC converts any LED luminaire to emergency lighting operation, powered from a Signtex central battery system.

Constant power output is factory adjustable to optimize emergency illumination level and fixtures may be on, off, switched or dimmed in normal mode without affecting emergency operation. General lighting fixtures with ELC may be combined with MOONLITE LED™ emergency luminaires and exits in the central battery system, as required.

AC

ELC ELC

ELC ELC

Typical applications for Type P2 may include 2 x 2 or 2 x 4 LED flat panel or other lay-in designs, with normal power ranging from 10W to 70 watts or more.

Building Utility

Supply (CBS)

120/ 277 VAC

Central

Battery

100-1000

Watts for 90 mins.

for 90 mins.

for 90 mins.

Watts Watts

100-1000 100-1000

Battery Battery

Central Central

Up To (8)

24V Emergency

Lighting Circuits

AC

Low Voltage Emergency Circuits

All Signtex central battery systems Series CBS and CBM include fully automatic self-test, self-diagnostics. Series CBM includes the MARS™ Monitoring and Reporting System which provides cloud-based internet communication and fault reports delivered automatically via email for all components of the emergency system.

10-12 FT CEILING

ELC ELC

CONSTRUCTION & OPERATION

• Package size 2.9” x 1.55” x 1.0”.

• Factory or field installable in the Fire and Electrical Enclosure of UL listed fixtures.

• Normal lighting operation is not affected by ELC operation.

Compatible with all types of dimming and lighting controls.

• UL Conditions of Acceptability requires installation in a Fire and Electrical Enclosure, with power level set to produce minimum required emergency illumination.

ELC

CBS

ELC

Office

ELECTRICAL

• Input 24 VDC.

• Constant emergency power output is factory adjustable from

5W to 17W.

• Output voltage auto sensing range from 24V to 48V.

• Adjustable emergency lumen output allows optimum settings for any fixture to equal or exceed requirements of NEC and

NFPA 101 codes for varying mounting heights and other conditions.

• Available for LED fixtures operating from 10W to 70W or higher in normal mode.

CODES

• Component Recognized in compliance with UL Standard

924, for field or factory installation in the Fire and Electrical

Enclosure of any LED fixture. All Signtex Central Battery

Systems and MOONLITE LED emergency fixtures are UL

Listed to Standard 924.

ELC

ELC

ELC

ELC

ELC

ELC ELC ELC

30-40 FT CEILING

Warehouse

EMERGENCY LIGHTING CIRCUIT: LOW VOLTAGE 24 VDC

NORMAL LIGHTING BRANCH CIRCUIT 120/ 277 VAC

D E S I G N E D &

M A N U F A C T U R E D

FIXTURE SCHEDULE

MODEL CATALOG NO

APPROVAL JOB INFORMATION

I N T H E U S A

Signtex Inc

LIGHTING

SPECIFIED EMERGENCY LIGHTING

Emergency Lighting Control

For Use With Series CBS Central Battery System for Emergency Lighting

Series ELC

Type P2

ELCP2.05.15.00

SUGGESTED SPECIFICATIONS:

Supply and install Signtex Emergency Lighting Control Series ELC which shall be capable of operating a LED general lighting fixture in emergency mode for a minimum of 90 minutes following failure of the normal power supply to the fixture, when connected to a Signtex

Central Battery System, Series CBM or CBS, with luminance level to equal or exceed the minimums required by the current NEC codes.

See Signtex SPECIFICATION GUIDE to develop exact specifications for your specific application

2.9”

EMERGENCY

INPUT 24 VDC

1.55”

NORMAL

INPUT

120/277 VAC

OUTPUT

VOLTAGE

CURRENT

POWER

EMERGENCY OPERATION

MAX RATINGS

48 VDC

350 mA

17W

FROM CBS + 24V

BUILDING SUPPLY

120/ 277 VAC

2.5” EMERGENCY

OUTPUT

1.0”

NORMAL DRIVER

ELC

NORMAL DRIVER

EMERGENCY & GENERAL

LIGHTING FIXTURE

SIGNTEX

EXIT

GENERAL LIGHTING

FIXTURE

SIGNTEX

EMERGENCY

LIGHTING

FIXTURE

ORDERING INFORMATION: Example: ELC8P2-32W36-CHX

ELC

MODEL

SERIES

ELC X = X Watts ¹

8

EMERGENCY

POWER

WATTS

P2

PACKAGE

TYPE

P2

-32W

FIXTURE

NORMAL

POWER WATTS

FW= F Watts

36

NORMAL DRIVER

MAX OUTPUT

VOLTS

-CHX

OPTIONS

X= X Volts DC

CHX = X Channel²

RCP= Reverse Current

Protection³

Notes: ¹ Based on lumen output required

² Contact factory for wiring multiple normal drivers

³ Required for normal drivers with output protection

Signtex Inc

LIGHTING

220 VFW Avenue, Grasonville, MD 21638

TEL: (410) 827-8300 Fax:(410)827- 8866 sales@signtexinc.com www.signtexinc.com