ELCP2.05.15.00
GENERAL DESCRIPTION
ELC converts any LED luminaire to emergency lighting operation, powered from a Signtex central battery system.
Constant power output is factory adjustable to optimize emergency illumination level and fixtures may be on, off, switched or dimmed in normal mode without affecting emergency operation. General lighting fixtures with ELC may be combined with MOONLITE LED™ emergency luminaires and exits in the central battery system, as required.
AC
ELC ELC
ELC ELC
Typical applications for Type P2 may include 2 x 2 or 2 x 4 LED flat panel or other lay-in designs, with normal power ranging from 10W to 70 watts or more.
Building Utility
Supply (CBS)
120/ 277 VAC
Central
Battery
100-1000
Watts for 90 mins.
for 90 mins.
for 90 mins.
Watts Watts
100-1000 100-1000
Battery Battery
Central Central
Up To (8)
24V Emergency
Lighting Circuits
AC
Low Voltage Emergency Circuits
All Signtex central battery systems Series CBS and CBM include fully automatic self-test, self-diagnostics. Series CBM includes the MARS™ Monitoring and Reporting System which provides cloud-based internet communication and fault reports delivered automatically via email for all components of the emergency system.
10-12 FT CEILING
ELC ELC
CONSTRUCTION & OPERATION
• Package size 2.9” x 1.55” x 1.0”.
• Factory or field installable in the Fire and Electrical Enclosure of UL listed fixtures.
• Normal lighting operation is not affected by ELC operation.
Compatible with all types of dimming and lighting controls.
• UL Conditions of Acceptability requires installation in a Fire and Electrical Enclosure, with power level set to produce minimum required emergency illumination.
ELC
CBS
ELC
Office
ELECTRICAL
• Input 24 VDC.
• Constant emergency power output is factory adjustable from
5W to 17W.
• Output voltage auto sensing range from 24V to 48V.
• Adjustable emergency lumen output allows optimum settings for any fixture to equal or exceed requirements of NEC and
NFPA 101 codes for varying mounting heights and other conditions.
• Available for LED fixtures operating from 10W to 70W or higher in normal mode.
CODES
• Component Recognized in compliance with UL Standard
924, for field or factory installation in the Fire and Electrical
Enclosure of any LED fixture. All Signtex Central Battery
Systems and MOONLITE LED emergency fixtures are UL
Listed to Standard 924.
ELC
ELC
ELC
ELC
ELC
ELC ELC ELC
30-40 FT CEILING
Warehouse
EMERGENCY LIGHTING CIRCUIT: LOW VOLTAGE 24 VDC
NORMAL LIGHTING BRANCH CIRCUIT 120/ 277 VAC
D E S I G N E D &
M A N U F A C T U R E D
FIXTURE SCHEDULE
MODEL CATALOG NO
APPROVAL JOB INFORMATION
I N T H E U S A
SPECIFIED EMERGENCY LIGHTING
ELCP2.05.15.00
Supply and install Signtex Emergency Lighting Control Series ELC which shall be capable of operating a LED general lighting fixture in emergency mode for a minimum of 90 minutes following failure of the normal power supply to the fixture, when connected to a Signtex
Central Battery System, Series CBM or CBS, with luminance level to equal or exceed the minimums required by the current NEC codes.
See Signtex SPECIFICATION GUIDE to develop exact specifications for your specific application
2.9”
EMERGENCY
INPUT 24 VDC
1.55”
NORMAL
INPUT
120/277 VAC
OUTPUT
VOLTAGE
CURRENT
POWER
EMERGENCY OPERATION
MAX RATINGS
48 VDC
350 mA
17W
FROM CBS + 24V
BUILDING SUPPLY
120/ 277 VAC
2.5” EMERGENCY
OUTPUT
1.0”
NORMAL DRIVER
ELC
NORMAL DRIVER
EMERGENCY & GENERAL
LIGHTING FIXTURE
SIGNTEX
EXIT
GENERAL LIGHTING
FIXTURE
SIGNTEX
EMERGENCY
LIGHTING
FIXTURE
ELC
MODEL
SERIES
ELC X = X Watts ¹
8
EMERGENCY
POWER
WATTS
P2
PACKAGE
TYPE
P2
-32W
FIXTURE
NORMAL
POWER WATTS
FW= F Watts
36
NORMAL DRIVER
MAX OUTPUT
VOLTS
-CHX
OPTIONS
X= X Volts DC
CHX = X Channel²
RCP= Reverse Current
Protection³
Notes: ¹ Based on lumen output required
² Contact factory for wiring multiple normal drivers
³ Required for normal drivers with output protection