installation and wiring instructions, operation and

advertisement
INSTALLATION AND WIRING INSTRUCTIONS,
OPERATION AND MAINTENANCE PROCEDURES
INSTALLATION AND WIRING INSTRUCTIONS:
1. INSTALLATION :
Date
Lamp Size
4
Initials
FOR: FLUORESCENT SELF CONTAINED EMERGENCY
LIGHTING LUMINAIRES, WITH AUTOTEST FACILITY
Important Notes:
Date
Mode
3
Initials
a) Check product labels for correct input voltage and frequency before installation.
b) If separate switched and unswitched supplies are to be connected to this luminaire they must originate from the same phase.
c) If testing distribution wiring by meggering, luminaires must be disconnected or damage may occur.
d) During installation do not position installation cables under electronic ballast.
1.1
Installation should be carried out by a qualified electrician in accordance with IEE regulations.
1.2
Carefully unpack the luminaire and remove the diffuser/ceiling panel, as appropriate.
1.3
Remove the geartray assembly from the housing where necessary.
1.4
Fix the luminaire to the ceiling or wall. Position the luminaire to ensure that the LED will be visible when installed. If vertically
mounted, ensure that the battery will be at the bottom of the luminaire.
Initials
CARD
Important Note: To retain the weatherproof integrity of an IP65 rated luminaire, the fixings should be sealed using mastic or
similar sealing compound to preserve the IP65 rating.
1.5
Date
Type
2
Self contained emergency lighting luminaires must be supplied with an unswitched supply. Maintained and Combined
(Sustained) luminaires may also be supplied with a switched supply to control the use of the luminaires as a part of the normal
lighting.
The battery pack label should be marked with installation date for self-contained luminaires.
1.7
Reassemble the luminaire and check operation by restoring the mains supply, checking that the LED is operating in self-contained
luminaires. The Autotest LED (Tricolour LED) should flash Red/Green for 6 seconds and then extinguish.
1.8
After being connected for 1 hour, depress the Autotest push button. This will initiate an 18-second self-test cycle where the unit will
check correct functioning of the product, both in a mains present situation and an emergency situation. Any failure will be indicated by
the buzzer sounding (if fitted) and the Autotest tricolour LED (see specification 2.6).
1.9
If there are no failures recorded, the product is correctly installed and the product will carry out all further tests required in
accordance with the test programme below.
Date
1
Initials
1.6
1.10 If the status indicator registers a fail, allow the product to charge for 24 hours and carry out the self-test sequence again by
depressing the push button. If the luminaire then continues to fail contact the company for advice.
Month 12 Full rated Duration Test
Month 11 Functional Test
Month 10 Functional Test
Month 9 Functional Test -See
requirement
Month 8 Functional Test
Month 7 Functional Test
Month 6 Duration Test
-See requirement
Month 5 Functional Test
Month 4 Functional Test
Month 3 Functional Test -See
requirement
Month 2 Functional Test
Month 1 Functional Test
Year
Note: Remove protective film from finished surfaces where indicated.
Location
RECORD
Ensure that the mains supply is isolated. Connect the luminaire to the supply (or supplies) as marked using cable of at least 1.5 mm2
cross sectional area.
CONNECTION DIAGRAM:
•
NON – MAINTAINED LUMINARIES
P/N 40395
Page 1 of 2
Doc. No. ENG-099-03
•
MAINTAINED AND SUSTAINED LUMINARIES
3.
Alternatively Permanent Live (L) and Switched Live (Ls) may be linked together with only the Line (Phase) Unswitched Live Feed
provided for continuous (unswitched) maintained or sustained operation.
2. SPECIFICATION :
2.1
The purpose of edge lit and exit luminaires (with directional legends) is to provide either exit instruction or information, and not to
illuminate the surrounding area. Therefore the light output value of said luminaire types must be assumed to be zero and correct operation
determined by legend panel legibility.
The rated total light output of emergency lighting luminaires used to illuminate surrounding areas will be affected by normal production
tolerances of electronic circuitry and by the performance of any fluorescent lamp utilised. The figures quoted are therefore subject to a
tolerance of +/- 20%.
Figures quoted are the minimum values expected during the period from 1 minute after supply failure to the end of rated duration.
Nominal values will exceed those quoted.
Rated Total Emergency Light Output
Mode of Operation – Autotest Luminaires are available in the following modes of operation:2.1.1 Self-contained Luminaires:
2.1.1.1 Non Maintained - the lamp(s) are normally off and illuminated only in case of failure of the mains supply.
2.1.1.2 Maintained - the lamp(s) always illuminate in case of failure of the mains supply but are also able to be used to
provide normal lighting when the Switched Live connection is powered.
2.1.1.3 Combined or Sustained - at least one of the lamps is normally off and illuminated only in case of failure of the
mains supply. Separate lamp(s) may be used to provide normal lighting when the Switched Live connection is
powered.
2.2
RATED LIGHT OUTPUT:
Emergency Lighting Inverter - High frequency inverter modules for emergency lighting complying with the requirements of
EN60924 and EN60925.
2.3
Battery - High Temperature Sealed Nickel Cadmium, voltage and capacity as marked.
2.4
Lamp(s) - Fluorescent (See specification on product label)
2.5
Charge Indicator - High Intensity Light Emitting Diode (L.E.D.) indicating correct functioning of charger and connection of battery.
2.6
Status Indicator - Buzzer (if fitted), sounds for 10 seconds every hour under any fault condition, detailed below.
Tricolour, High Intensity Light Emitting Diode (L.E.D.) indicating health status of the luminaire as per the
legend below:
(Lumens)
Luminaire Type
Diffuser Type
General Purpose 8W Luminaire 2 cell
General Purpose 8W Luminaire 2 cell
Opal Diffuser
Clear Diffuser
60 Lumens
76 Lumens
General Purpose 8W Luminaire 3 cell
General Purpose 8W Luminaire 3 cell
Opal Diffuser
Clear Diffuser
100 Lumens
128 Lumens
Weatherproof 8W Luminaire 2 cell
Weatherproof 8W Luminaire 2 cell
Opal Diffuser
Clear Diffuser
76 Lumens
80 Lumens
Weatherproof 8W Luminaire 3 cell
Weatherproof 8W Luminaire 3 cell
Opal Diffuser
Clear Diffuser
128 Lumens
160 Lumens
Interior 16W Luminaire 4 cell
Interior 28W Luminaire 4 cell
Opal Diffuser
Opal Diffuser
149.5 Lumens
328 Lumens
These values do not reflect readings on all luminaires. Full photometric data for individual luminaires is available upon request from the
company.
4. OPERATION AND MAINTENANCE
Page 2 of 2
4.1
On completion of the installation a copy of these instructions together with the test record card(s) should be handed over to the
authority responsible for maintenance.
4.2
Cleaning and relamping of emergency lighting luminaires should be regularly carried out to ensure optimum photometric
performance.
4.3
Isolate supply to luminaire before attempting any form of servicing. Be aware that the emergency lighting inverter circuit will
continue to function after isolation of the mains supply and there is an Electric Shock Risk from fluorescent lamp tube pins etc.
4.4
It is recommended that sealed rechargeable nickel cadmium batteries are replaced after each 4 years of operation in accordance
with their design life. Batteries should be replaced when the luminaire no longer meets its’ declared duration performance. Consult
the company for details of correct replacement battery packs.
4.5
Important Note - When replacing components:
This publication is provided to outline recommended installation and maintenance practices
and is not deemed to form any part of any offer or contract.
We adopt a policy of continuous product and services improvement and we reserve the right to vary details without prior notice.
Fluorescent lamps should be disposed of carefully taking precautions against glass fragments.
Rechargeable batteries should not be disposed of with normal waste. Seek advice from the company.
5. TESTING RECOMMENDATIONS
For Self Contained Luminaires the following test schedule is adopted and any failures indicated via the Status LED indicator (see specification
2.6)
Daily:
Monthly:
Six Monthly:
Annually
Manual:
The unit is checked for mains present and correct battery charge operation.
The daily test is carried out. The Autotest module interrupts the mains supply to the luminaire and the luminaire
switches into emergency operation. The unit is allowed to operate for 60 seconds in emergency during which time
correct operation is checked.
The daily test is carried out. The Autotest module interrupts the mains supply to the luminaire and the luminaire
switches into emergency operation. The unit is allowed to operate for 1 hour in emergency (20 minutes for a one
hour system) during which time correct operation is checked.
The daily test is carried out. The Autotest module interrupts the mains supply to the luminaire and the luminaire
switches into emergency operation. The unit is allowed to operate for a full rated duration in emergency during
which time correct operation is checked.
Any time the push button is depressed, the Autotest module indicates how many monthly tests have been carried
out in an annual schedule. Buzzer (if fitted) is turned on/off and Tricolour LED flashes Amber every second
indicating the number of tests passed, then it goes into self-test sequence where the module will check the correct
functioning of the product.
Page 2 of 2
This publication is provided to outline recommended installation and maintenance practices
and is not deemed to form any part of any offer or contract.
We adopt a policy of continuous product and services improvement and we reserve the right to vary details without prior notice.
Download