TRANSFORMER BASICS FECA Clearwater FL June 11, 2009 1 Transformer Applications – FECA Agenda June 11, 2009 08:30-10:00 Transformer Overview - Basic Construction - Lightning / LV Surges - Voltage Regulation / Flicker - Life Cycle Costing / DOE Efficiency Ruling 10:00-10:15 Break 10:15-12:15 Insulation Life (C57.91) + TAP Simulations - The “Meaning of Life”the C57.91 Loading Guide - Over Head – Residential + flicker - Padmount – Residential + fusing + Short Circuit - Padmount 3Φ + harmonics - Vault 3Φ + vault restrictions - Substation/Power Transformers - Ratings/Cooling Modes – Settings - Contingency Modeling 1:00 – 2:45 Power Transformer Maintenance, Monitoring & DGA 2:45 – 3:00 Exams/Discussions/wrap-up Revised June 2009 dad Generation Step Up - GSU Generation… Transmission… Substation… Distribution - Outdoors Distribution - Downtown Distribution - Indoors Transformer Function • Converts electricity from high voltage and low current to low voltage and high current … or … vice versa • Electricity is better generated and used at low voltage, and better transported at high voltage… • Transformers are the basic links of a T&D system… • Electricity and Magnetism work together to produce “transformer action”… • Thin Electrical Grade Steel provides an excellent path for magnetic flux… Distribution – Wound Core Basic Distribution Transformer Core Loop Distribution – ‘Stacking a Core’ Wound Coil - Note “LV Crossovers” Core and Coil (LV Side) Shell Type … Note ‘Core Grounding’ Core and Coil (HV Side) Distribution – Shell Type - Interlaced LV windings core & coil - excellent Short Circuit strength... SS P SS SS P - natural impedance's typically 1.5-2.0% for SPS construction... Interlaced SPS Shell Type C&C Cross-section SS Distribution – Non-Interlaced LV windings core & coil - excellent Short Circuit strength... S P S S P S - natural impedance's typically 1.5-2.0% for SPS construction... Non-Interlaced SPS Shell Type C&C Cross-section Distribution – Core Type core & coil P S - good dielectric strength... S P P S - typically good on thermal performance... - natural impedance's typically 2.5-3.5%... - MUST be interlaced... Core Type C&C Cross-section S P Distribution - 3Φ 5 Legged Construction 3 Φ core & coil P S S P P S S P P S S P 3 Phase 5-Legged C&C Cross-section Power – Stacked Core Form Power – Stacked Core Form Stacked Core – Core Cutting Power – Disk Windings Disk Windings Power Transformer – Disk Winding Power – Disk Windings Power – Disk Windings Power Transformer – Clean Room Power Transformer – 667MVA 1Φ Power – Pan-Cake Windings Pan-Cake Windings Power – Shell Form Construction Transformer Function • Converts electricity from high current and low voltage to low current and high voltage … or … vice versa • Electricity is better generated at low voltage, and better transported at high voltage… • Transformers are the basic links of a T&D system… • Electricity and Magnetism work together to produce “transformer action”… Transformers – Basic Equations Maxwell’s Equations Differential form - General Case δD x H = J + δt δβ x E = - δt Ampere’s Law Faraday’s Law of Induction ·D=ρ Gauss’s Law for Electricity ·β=0 Gauss’s Law for Magnetism ∆ ∆ ∆ ∆ where, H = Magnetic Field Strength E = Electric Field D = Electric Displacement J = current density β = Magnetic Field ρ = Charge Density Transformers – Electric and Magnetic Fields When a wire is connected to an AC power source, current flows through it and a magnetic field is created around the wire… Transformer – Ratings • Transformers are rated in Volt-Amperes @ a specified Maximum Average Winding Temperature Rise in degrees Centigrade. For example, a 25 kVA 65 Deg C rise transformer is rated to transform 25,000 Volt Amperes from one voltage/current level to another voltage/current level WITHOUT exceeding an Average Winding Rise of 65 Deg C above the Ambient. • Liquid Filled (Mineral Oil or Natural Esters) Distribution Transformers are rated in kVA at 65 Deg C. Typically 10-167 kVA 1Φ or 15-2500 kVA 3Φ. • Power Transformers are usually specified in MVA (million volt amperes). Multiple ratings can be specified at either or both 55 and/or 65 Degree C Rise. Power Transformers can have multiple ratings based on optional cooling systems such as Fans or Pumps. For example OA/FA/FA (or under the new EIC definitions ONAN/ONAF/ONAF) for the ratings based on ‘Natural Air/Oil Cooling/Forced Air Cooling/and a second stage of Fans’. kVA/MVA is a ‘Thermal’ Statement!!! Transformers – Turns Relationships Vpri Npri = Vsec Nsec = volts per turn N = turns ratio = Vpri = Vsec x N and Npri Nsec Isec = Ipri x N Transformer - Turns/Volts/Current 25 kVA 120 7200 240 120 3240 turns N = Isec = Ipri = 108 turns 3240 108 = 30 : 1 25,000 VA 240 V 25,000 VA 7200 V = 104.7 Amps = 3.47 Amps Transformer - Core Loss & Exciting Current Iex A Vrated w v NL Watts %Iex = Iex Irated x 100 Rated Voltage is put across the LV terminals with the Primary Open... the No Load Loss and Exciting Current are measured... Transformer - Core Losses No Load Loss = Hysteresis Loss + Eddy Current Losses Hysteresis Loss is caused by the energy used in lining up the magnetic domains in the core... β flux density = kl/in2 H Hysteresis Loss is a function of the area enclosed by the Hysteresis Loop... = magnetic field intensity = mmf = Ampere Turns Eddy Currents are circulating currents in the core due to induction. The thicker the core lamination, the more Eddy Current losses... Transformer – Winding Measurements Irated A VIZ w v low impedance bolted short... LL Watts %IZ = VIZ Vrated x 100 Rated Current is put into the HV terminals with the LV Shorted... the Load Loss and Impedance Voltage (IZ) are measured... Transformer – Winding Measurements Load Loss = Ip2Rp + Is2Rs + Stray Losses Stray Losses = Eddy (skin effect) Losses + Circulating Current Losses + Non-current carrying parts being influenced by leakage flux Load Losses produce heating within the windings and resistance losses increase with temperature... In order to cool the windings, oil ducts are inserted within the windings to allow the oil to circulate and transfer the heat to the tank walls and cooling fins... Transformer – Eddy Current Losses “No-Mag” plates (304L) are used in larger kVA transformers to reduce Eddy Current Losses due to High Current Flow… Transformers - Voltage Regulation LL %IR = kVA x 10 pf = power factor %Reg = pf x IR + q x IX + where, K = p.u. load %IX = IZ2 q = 1 IR2 pf2 ( pf x IX - q x IR)2 200 xK Transformers – Resistance & Reactance in Ohms Ft = [ kV2 / kVA ] x 10 Rt = Ft x %IR = ohms resistance Xt = Ft x %IX = ohms reactance Ztvector = Rt + j Xt (vector form) Ztscalar = √ Rt2 + Xt 2 then, ISC AMPS = kV x 1000 Zt scalar θtscalar = tan-1(Xt/Rt ) (scalar form) (scalar form) …which of course is “Ohms Law” In addition to the TRANSFORMER, the LV Fault Current is also limited by the Impedances of the SYSTEM to/from the Transformer, the LV circuit to/from the Fault, and the impedance of the FAULT… complexity is added with Line-Line and/or Line to Neutral Faults and the connections (Y-Y or Y-D)... And of course the transformation base levels… Transformers - Efficiency Efficiency = Power OUT Power IN OR % Eff = 100 x K x kVA / (kVA x K + (NL + LL x K2)) where K = per unit Load… Transformers – Distribution Polarity H1 H2 H1 H2 > 200kVA > 8,660kV X3 X2 ADDITIVE X1 X1 X2 X3 SUBTRACTIVE Transformer Polarity indicates the direction of current flow through the HV windings with respect to the direction of the current flow through the LV windings… Polarity is either “ADDITIVE” or “SUBTRACTIVE” Lightning Surges and Protection 40 Lightning – Stroke Density Map Lightning – Stroke Current Magnitude Lightning Stroke Current Magnitude Probability < Abcissa 1.2 1 0.8 0.6 0.4 0.2 0 1 10 100 1000 Stroke Curre nt (KA) Lightning Stroke Current magnitude is a probability distribution. Lightning - Transformer Failures 16.00% 14.00% 12.00% 10.00% 8.00% 6.00% 4.00% 2.00% 0.00% 120.00% 80.00% 60.00% 40.00% 20.00% Cumulative Pct 100.00% R/W Emerg FPC Const Equip Emerg- Cust Dig-In Human Error- FPC Vehicle Misc Human Error- Pub UG PRI UG Sec OH Sec Overload Connector Storm Unknown Tree Lightning Defective Equip 0.00% Animal Pct Transformer Outages 1995-1996 Cause Code Lightning is the most common cause of Transformer Failures... Wildlife is the most common cause of Transformer Outages... Lightning Lightning acts as a current source which deposits a large charge of electrons on the power line. This charge appears as a current wave propagating along the power line. The current wave has a very steep wave front, i.e., high di/dt. The power system is highly inductive. The voltage produced is V=L di/dt. This can result in voltages approaching 1 million volts. Such voltages will fail the insulation system of transformers and other equipment. Lightning – Arrester Discharge Voltage Lightning Arresters act to limit the voltage between conductors. This is accomplished by transferring charge (current) between conductors. The arrester is modeled electrically as a non-linear resistor. MOV Arrester Typical MOV Arrester characteristics 10 kA = 30 kV Voltage Silicon Carbide Arrester L ar e in to s i s Re r Current Lightning – Arrester Lead Lengths kV Voltage Arrester Voltage Across = + Transformer Lead Voltage Transformer Voltage = 30 kV + 48 kV = 78 kV for a 10 kA stroke with a 20 kA/usec rise time. The Transformer BIL for 12470 GRDY/7200 is 95 kV... The probability of a stroke > 10 kA is 95%... 30kV MOV Arrester #6 Copper Lead Length +/- 6 feet Current - The Lead Inductance of #6 Copper is typically 4 microhenerys per foot (uh/ft)... - The di/dt for Florida Lightning averages 20 kA per microsecond... - Lead Length voltage is V = L di/dt = 4 uh x 20 kA/usec = 8 kV per Foot. Lead Length Voltage = 6 feet x 8 kV/ft = 48 kV Arrester – Lead Length Reduction Reduction of lead length voltage is accomplished by use of either Tank Mounted or Internal Under Oil Arresters. Voltage = Arrester Voltage Across Transformer MOV Arrester Tank mounted or under oil arresters cannot be used on wye-delta banks due to single phase switching over voltages. Under Oil arresters are used only on single bushing transformers. Low Side / Secondary Surges 48 Lightning – Transformer Winding Failures Lightning on the High Voltage winding can produce 2 failure modes - Layer to Ground (anywhere in the winding) - Layer to Layer at the H1 end of winding Lightning on the Low Voltage winding can produce layer-to-layer failures at either end of the High voltage winding or layer-to-ground in the Low Voltage winding. Lightning – Poletype Winding Failures TRANSFORMER FAILURE CAUSES POLE TYPE (167 UNITS) OVRLOAD 5% SEC 10% NONE 4% HVPROB 43% LVPROB 19% LVPOS 17% LEAD 2% Lightning – Padmount Winding Failures TRANSFORMER FAILURE CAUSES PAD-MOUNTED (84 UNITS) HVPROB 12% SEC 21% LEAD 1% OVRLOAD 1% LVPOS 18% NONE 11% LVPROB 36% Low Side Surges • 5% of Stroke Currents Exceed 85 kA • 50% Exceed 35 kA • 35-50% of Surges enter on the LV side • The Average LV Surge is 1500 amps/transformer/year? • The Majority do not exceed 5000 amps? Distribution – Core Type core & coil P S - good dielectric strength... S P P S - typically good on thermal performance... - natural impedance's typically 2.5-3.5%... - MUST be interlaced... Core Type C&C Cross-section S P Distribution – Non-Interlaced LV windings core & coil - excellent Short Circuit strength... S P S S P S - natural impedance's typically 1.5-2.0% for SPS construction... Non-Interlaced SPS Shell Type C&C Cross-section Distribution – Shell Type - Interlaced LV windings core & coil - excellent Short Circuit strength... SS P SS SS P - natural impedance's typically 1.5-2.0% for SPS construction... Interlaced SPS Shell Type C&C Cross-section SS Lightning – ‘Anonymous’ Winding Failures H1 HV LV “The Anonymous Failure Mode” LV H2 Lightning – ‘Anonymous’ Winding Failures During the 1960’s, the Transformer Manufacturers switched from Conductor wound Copper LV windings to Aluminum Sheet wound construction… COST $$$ Driven by COST, the practice of NONINTERLACED Construction found favor with those Manufacturers who could make this change… S P S S P S During the 1970’s, the installed failure rate of distribution transformers began to rise dramatically!!! Teardown analysis began to show a special failure signature which became known as “The Anonymous Failure”… this is a “turn-turn” or “layer-layer” dielectric failure near the grounded end of a single bushing transformer… And this seemed to be associated with the Non-Interlaced Shell Type Construction… Lightning – ‘Anonymous’ Winding Failures H1 HV LV “The Anonymous Failure Mode” LV H2 • Layer to Layer failures near the grounded end of the HV winding is a “signature” of a low side surge occurrence... Lightning – ‘Anonymous’ Winding Failures Arrester E=L di dt = the voltage developed across the ground leads... • The majority of LV surges probably enter the Transformer through the LV ground connections... either due to Primary Arrester operation or from the ground following direct or nearby strokes... Lightning – ‘Anonymous’ Winding Failures HV LV LV • Surge currents flowing through the LV windings of a Non-Interlaced LV winding produce a high magnetic field across the primary coil... Lightning – ‘Anonymous’ Winding Failures 290 kV winding voltage to ground... kV 10 kVA 95kV BIL H2 HV winding layers H1 • The rapidly changing magnetic field induces a very high voltage in the primary winding... • The lightning arrester connected across H1 to H2 does not see any voltage... Lightning – ‘Anonymous’ Winding Failures Layer to Layer Voltage Peak 80 kV kV 10 kVA 95kV BIL H2 HV winding layers H1 • The high layer to layer stress in the HV winding will cause coil failure near either end of the coil... but usually at or near the grounded end of the winding... Lightning – Low Side Surges HV LV LV LV LV • Surge currents flowing through the LV windings of an Interlaced LV winding cancel and produce a weak magnetic field across the primary coil... Lightning – Low Side Surges Non-Interlaced 290 kV winding voltage to ground... kV Interlaced 3 kV to ground... H2 HV winding layers H1 • Interlacing the LV winding balances the winding and significantly reduces the stress due to LV Surges... Lightning – Low Side Surges Layer to Layer Voltage kV Non-Interlaced Peak 80 kV Interlaced Peak 1 kV 10 kVA 95kV BIL H2 HV winding layers H1 • Interlacing the LV winding balances the winding and significantly reduces the stress due to LV Surges... Lightning – Low Side Surges • Non-Interlaced LV windings are the major cause of Distribution Transformer (DT) Lightning Failures... • Small kVA’s are MORE susceptible because of more turns... • Primary Arresters DO NOT Protect the HV against LV Surges... • Interlacing or LV Arresters reduces DT Failure Rate... 1.0 % 0.5 % Failure Rate interlaced types non-interlaced types Lightning - Summary • The proper application and choice of Arresters can reduce the failure rate significantly… especially in the Southeastern USA… • Arrester Lead length can be very important… • About 50% of lightning surges come from the low side… on the smaller kVA transformers, Interlaced windings and/or LV Arresters can reduce winding failures… Starting Transformers and Motors 68 Motor Starting Issues • The current required to start equipment such as Electric Motors or Transformers requires a starting current, typically known as ‘Inrush’ or ‘locked rotor current’… • For fusing, the typical ‘inrush’ rule is to keep the fuse melt beyond 812 times rated current at 0.1 second (about 6 cycles)… • The short term voltage drop or ‘Flicker’ is a function of the required ‘Locked Rotor’ current required to start the equipment… a number of papers and information is available to the user on this issue… • In addition to the impact on the local low voltage circuits, starting equipment such as large motors can cause voltage quality issues on the primary circuits of the distribution feeders… which can affect associated equipment… • Some electronic systems may be sensitive to these changes! Transformers – Resistance & Reactance in Ohms Ft = [ kV2 / kVA ] x 10 Rt = Ft x %IR = ohms resistance Xt = Ft x %IX = ohms reactance Ztvector = Rt + j Xt (vector form) Ztscalar = √ Rt2 + Xt 2 then, ISC AMPS = kV x 1000 Zt scalar θtscalar = tan-1(Xt/Rt ) (scalar form) (scalar form) …which of course is “Ohms Law” In addition to the TRANSFORMER, the LV Fault Current is also limited by the Impedances of the SYSTEM to/from the Transformer, the LV circuit to/from the Fault, and the impedance of the FAULT… complexity is added with Line-Line and/or Line to Neutral Faults and the connections (Y-Y or Y-D)... And of course the transformation base levels… Motor Start – calculations The voltage drop across the transformer: %T = [1-Zm/sqrt((Rm+Rt)^2 + (Xm+Xt)^2))] x100 where, Zm is the motor impedance is calculated as, Zm = (line-line voltage rating of the motor) / LRA LRA = locked rotor amps PF = motor starting power factor Rm = Zm x PF ohms Xm = sqrt( 1-PF^2) ohms To translate the %Impedance ( %IZ ) into Real and Reactive components, we use the transformer impedance factor, Ft. Ft = [ [(Secondary voltage in kV)^2] / kVA rating of Transformer ] x 10 Rt = Ft x %IR ohms Xt = Ft x %IX ohms %IR and %IX are calculated from the Load Loss watts (LL) and Impedance (%IZ) of the specific transformer. %IR = LL / (kVA x 10) %IX = sqrt[ %IZ^2 - %IR^2 ] The voltage drop across the secondary conductor is: %C = [ [ Rc x LRA x PF ] + [ Xc x LRA x sqrt(1-PF^2) ] ] x 100 / LV where LV is the line-line secondary voltage, typically 240 volts and, Rc = conductor resistance in ohms per 100 feet x [ 2 x length /100 ] Xc = conductor reactance in ohms per 100 feet x [ 2 x length /100 ] The conductor length is multiplied by 2 as the current must have a return path. If the return path conductor is not the same size and characteristics as the line conductor the calculation must be adjusted accordingly. Flicker Flicker is typically the voltage drop caused by the Locked Rotor Current required to start a air-conditioner compressor motor. The duration of this current for residential air conditioners varies from 4 to 20 cycles. A voltage drop occurs in each component of the system, i.e., Transformer and Conductors, based on the magnitude of the current and the impedance of the components. The most common occurrence is during the startup of residential air conditioners. Customers see this as a dimming of the lights or, under extreme conditions, as a shrinking of the TV picture. Customer sensitivity varies based on individual perception, the magnitude and duration of the voltage dip, and the type of light source. Flicker – Motor Starting Current 15-20 cycles RAYSAC Y1 Volts 400 Y2 Amps 300 300 200 200 100 100 0 0 -100 -100 -200 -200 -300 -400 0.00 0.05 0.10 0.15 0.20 Channel A (V) 0.25 0.30 Channel A (I) Measured : 02/14/97 11:47:57 0.35 0.40 -300 0.45 Sec. Motor Start – Single Phase Capacitor Start motors utilize a capacitor in series with the start winding to provide phase shift in the current through the start winding. This phase shift causes an angular displacement in the magnetic fields between the Run and Start windings resulting in a torque on the rotor. Run Winding Start Winding Rotor Start Winding Run Winding The larger the Capacitor - the larger the phase shift - the larger the starting torque - the shorter the starting cycle Motor Start – Permanent Split Capacitor Motor Run Capacitor Start Run Line The Start winding and Run Capacitor remain energized at all times Motor Start – Conventional 3 wire Hard Start Run Capacitor Potential Relay Start Capacitor Start Run Line The Potential Relay removes capacitor with Start Winding back E.M.F. Residential Air Conditioners Residential Air Conditioners use one of two types of Motors - Permanent Split Capacitor - Capacitor Start / Capacitor Run Residential Air Conditioners use one of two types of Compressors - Reciprocating (Piston) - Scroll (new High Efficency units) Motor Sizing rules are Different for Different Compressors Motor Start Flicker – Field Test Data AC Starting Characteristics 250.0 200.0 150.0 LRA RECIP Test Data Recip Regression Scroll Test DAta Scroll Regression 100.0 50.0 0.0 2.0 2.5 3.0 3.5 4.0 Tons 4.5 5.0 5.5 Motor Start Flicker – Kickstart TO-5 Motor Start Flicker – Kickstart TO-5 Run Capacitor Potential Relay Start Capacitor Start Run Line The Potential Relay removes capacitor with Start and Run Winding back E.M.F. Flicker – Kickstart Motor Starting Current 4-6 cycles RAYG4KS Y1 Volts 400 Y2 Amps 400 300 300 200 200 100 100 0 0 -100 -100 -200 -200 -300 -300 -400 0.00 0.05 0.10 Channel A (V) 0.15 Channel A (I) M easured : 02/25/97 16:39:47 0.20 -400 0.25 Sec. Compressor/Motor Start Flicker – Summary • Compressor Flicker is a momentary (5-30 cycle) voltage drop caused by Motor Start… such as a Residential Air Conditioner… • Compressor Flicker is ‘as perceived by the user’… Not everyone can notice it… once seen, the mind can ‘tune-in’ to it… • Flicker is a function of the required ‘Locked Rotor’ Starting Amperes… the High Efficiency ‘Scroll Type’ Compressors require Higher Starting Amps… thus going to Higher Efficiencies can cause other issues! • Adding extra Capacitive Reactance will not reduce the magnitue of the required starting current, but can reduce the amount of time required to get the compressor started… thus reducing the ‘perception of Flicker’… Transformer Costs and Efficiencies 83 Quantifying Transformer Costs • Capital Vs. Expense Dollars • Financial Math Relationships • Cost of Losses – the A and B Factors • Band of Equivalence • DOE Efficiency Rules Capital Dollars The purchase cost of a transformer is amortized over the expected life. This is done by applying a Fixed Charge Rate (FCR) to the purchase price... Price x FCR = Annualize Fixed Cost The result is an annual cost which is uniform for the life of the unit... FCR (%) = Fixed Charge Rate - The cost of carrying a capital investment made up of: - The weighted cost of capital (stocks, bonds) - Depreciation on the investment - Taxes (Income, Ad valorem, Gross Receipts) - Insurance Expense Dollars Expense costs such as Cost of Losses or future Change-Out are levelized to an annual form with the Capital Recovery Factor which considers only the cost of money and time… Change Out Cost x CRF = Annualize Change Out Cost The result is an annual cost which is uniform for the life of the unit... CRF (%) = A/P = i(1+i)n /((1+i)n-1) Note: In ANNUAL form Expense and Capital are equal! Basic Financial Math Capital Recovery Factor A/P = i(1+i)n /((1+i)n-1) Annuity Compound Amount Factor F/A = (1+i)n-1/i Present Worth Factor P/A = ((1+i)n-1)/i(1+i)n Present Value Sinking Fund Factor A/F = i/((1+i)n-1) Compound Interest Factor F/P = (1+i)n Future Value Present Value Factor P/F = 1/(1+i)n Moving Money (Value) through Time Cost of Transformer Losses The cost to operate a Transformer over it’s life is affected by the Cost to Supply the capacity, or Demand (SC $/kW-yr), and the Cost incurred to supply the Energy (EC $/kW-Hour). The No Load losses are continuous as long as the transformer is connected to the system, typically 8760 hours/year. The Load Losses vary with transformer load and are affected by the annual load factor and the timing of the system peak. The Annual cost of ownership (AOC) is: AOC = Price x FCR + A x NL + B x LL NOTE: draft C57.12.33 Loss Evaluation methodology currently under development by the IEEE… The ‘A’ Factor A = $ per No Load (excitation) Loss Watt A = SC + 8760 x EC 1000 $/watt where, SC = Avoided Cost of System Capacity ($/kW-yr) - - The levelized avoided (incremental) cost of generation, transmission, and primary distribution capacity required to supply the next kW of load to the distribution transformer coincident with the peak load. EC = Avoided Cost of Energy ($/kWh-yr) - - The levelized avoided (incremental) cost for supplying the next kWh, which may be produced by the utility’s generating units or purchased from an energy supplier. The ‘B’ Factor B = $ per Load (winding) Loss Watt B = ( SC x RF + 8760 x LsF x EC) x PL2 $/watt 1000 where, RF = Peak Loss Responsibility Factor - Defines the relationship between the transformer peak load and the transformer load at the time of system peak load. LsF = Loss Factor - A ratio of the annual average load losses to the peak value of load losses on the transformer. LsF = [Σ(K2n*tn)/t]/K2peak NOTE: An empirical relationship for loss factor for RESIDENTIAL transformers is the Propst/Ganger relationship: LsF = 0.15 (Load Factor) + 0.85 (Load Factor)2 PL = Equivalent Annual Peak Load “ON THE TRANSFORMER” Evaluation Forms The Transformer Evaluation Equation may be written as: Total Owning Cost (TOC) = F x Price + A x NL + B x LL Where the factor F is a multiplier against the Price and is used to express the owning cost equation in three forms: Type description F form . - EFC Equivalent First Cost 1.0 Capital form - PW Present Worth FCR/CRF Expense form - AC Annual FCR Annuity form Band of Equivalence • The BOE was described by the Shincovich and Stephens (EEI 1981) as a way to address the uncertainty of the future estimates on factors such as Energy Costs, Loading, etc… 1% was suggested! • “Uncertainty” of course can result in HIGHER or LOWER future costs! • However, this idea has been expanded as a tool to force lower first prices at the expense of future costs… 3-10% BOE is not uncommon! • BOE reduces the actual value of the Loss Evaluation Factors… Typically, a 3% BOE effectively reduces the A&B Factors by ½ or more! Variances would be better addressed with tools such as Crystal Ball… or the Economics Variance module in TAP… A & B Variance LCC – Mild Steel Tank vs. Stainless DOE Transformer Efficiencies – 2010 Rule 95 Energy Policy and Conservation Act The Energy Policy and Conservation Act (EPCA) of 1975 established an energy conservation program for major household appliances. The National Energy Conservation Policy Act of 1978 amended EPCA to add Part C of Title III, which established an energy conservation program for certain industrial equipment. The Energy Policy Act of 1992 amended EPCA to add certain commercial equipment, including distribution transformers. The Department of Energy, Office of Energy Efficiency and Renewable Energy, Building Technologies Program conducts the program that develops equipment energy conservation standards and has overall responsibility for rulemaking activities for distribution transformers in fulfillment of the law. http://www.eere.energy.gov/buildings/appliance_standards/ Energy Policy and Conservation Act Distribution Transformers The first step in developing energy conservation standards was the Secretarial determination in 1997 that, "Based on its analysis of the information now available, the Department has determined that energy conservation standards for transformers appear to be technologically feasible and economically justified, and are likely to result in significant savings" 62 FR 54809 (October 22, 1997). The Department of Energy (DOE) conducted two rulemakings for Distribution Transformers: • an energy conservation standard • a test procedure http://www.eere.energy.gov/buildings/appliance_standards/ Energy Policy and Conservation Act • In response, NEMA developed the TP-1 Minimum Efficiency Guidelines in the early 1990’s… note: basically a 3 year payback! • In August 2006, the DOE published the Notice of Proposed Rulemaking with a recommendation for to the Trial Standard Level 2 (TSL-2)… • Mixed responses… some opposed mostly based on increased cost and material availability… some saying it doesn’t go far enough… http://www.eere.energy.gov/buildings/appliance_standards/ Trial Standard Levels Efficiency = Power OUT / Power IN %E = 100 x kVA x 0.5 / [ kVA x 0.5 + ((NL + LL x 0.9 x 0.52)/1000)] Where NL and LL are in watts… Note: 0.9 = Load Loss Temp correction from 85 to 55 deg C… •TSL-1 = NemaTP1 •TSL-2 = 1/3 between TP1 and TSL-4 •TSL-3 = 2/3 between TP1 and TSL-4 •TSL-4 = minimum Life Cycle Cost •TSL-5 = max Energy Savings with no change in LCC •TSL-6 = max Energy Savings KVA NEMA TP1 10.0 98.40% 15.0 98.60% 25.0 98.70% 37.5 98.80% 50.0 98.40% 75.0 99.00% 100.0 99.00% 167.0 99.10% 75.0 112.5 150.0 225.0 300.0 500.0 750.0 1000.0 1500.0 2000.0 2500.0 98.70% 98.80% 98.90% 99.00% 99.00% 99.10% 99.20% 99.20% 99.30% 99.40% 99.40% TSL-2 98.40% 98.56% 98.73% 98.85% 98.90% 99.04% 99.10% 99.21% TSL-3 98.43% 98.59% 98.76% 98.99% 99.04% 99.18% 99.24% 99.35% TSL-4 98.46% 98.62% 98.79% 99.14% 99.19% 99.33% 99.39% 99.50% 98.91% 99.01% 99.08% 99.17% 99.23% 99.32% 99.24% 99.29% 99.36% 99.40% 99.44% 99.09% 99.19% 99.26% 99.35% 99.41% 99.50% 99.42% 99.47% 99.42% 99.46% 99.50% 99.27% 99.37% 99.44% 99.53% 99.59% 99.68% 99.60% 99.65% 99.48% 99.50% 99.55% Final Rule – October 12, 2007 “Effective January 1, 2010, Liquid Filled Distribution Transformers manufactured for sale in the United States MUST meet or exceed the following Efficiency levels…” Efficiency = Power OUT / Power IN @ 50% Load %Eff = 100 x kVA x 0.5 / [ kVA x 0.5 + ((NL + LL x 0.9 x 0.52)/1000)] where NL and LL are in watts… Note: 0.9 = Load Loss Temp correction from 85 to 55 deg C… DOE Final Rule • Similar rules are in place for Medium Voltage Dry type Transformers… • The DOE rule resolves the issue between Single and Three Phase designs by using the same Efficiency Value for the Single Phase design for the equivalent 3 Phase kVA… For example, the required efficiency value for a 3Φ 150 kVA transformer is the same as a 50 kVA 1Φ unit…. (3 x 50 = 150 kVA)… • Pre-Existing Distributor Stock, Re-manufactured units, and Transformers intended for Mining Operations are excluded from the rule… • For Liquid Filled Transformers, the relationships to the Trial Standard Levels are… • 1Φ 10-167 kVA • 1Φ 250-833 kVA slightly above TSL-4 between TSL2 and TSL3 • 3Φ • 3Φ • 3Φ • 3Φ TSL-2 between NEMA TP-1 & TSL-2 slightly greater than TSL-3 TSL-3 45-300 kVA 500 kVA 750 kVA 1000-2500 kVA For the final rule, DOE set average A & B values of A=3.85 and B=1.16 $/watt 1Φ and B=1.93 $/watt 3Φ DOE Projected Benefits TSL-1 TSL-2 TSL-3 TSL-4 TSL-5 TSL-6 Energy Saved Quads = 1.77 2.39 3.15 3.63 6.9 9.77 CO2 (Mt) reductions = 123.1 167.3 218.5 252.7 483.1 679.5 NOX (kt) reductions = 34.1 46.4 60.9 71 134.9 188 Hg (t) reductions 3 3.7 4.3 4.9 6.4 6.5 = NOTE: The QUAD is used by the U.S. Department of Energy in discussing world and national energy budgets. One Quad = 1015 BTU. The global primary energy production in 2004 was 446 quads… Conclusion Q/A? Don A. Duckett, P.E. Technical Sales Engineer HD Supply Utilities (407) 402-0944 Don.Duckett@ieee.org