EEL303: Power Engineering I - Tutorial 9 1. For the given power system shown in Figure 1, draw the positive, negative and zero sequence networks. Figure 1: Given Power System Figure 2: Positive Sequence Network Figure 3: Negative Sequence Network Figure 4: Zero Sequence Network 2. Two synchronous machines are connected through three-phase transformers to the transmission line shown in Figure. 5(a). The ratings and reactances of the machines and transformers are ′′ Machines 1 and 2: 100MVA, 20kV; Xd = X1 = X2 = 20%, X0 =4%, Xn = 5% Electrical Engineering Dept - IIT Delhi EEL303: Power Engineering I - Tutorial 9 Transformers T1 and T2 : 100MVA, 20Star/345Star kV; X = 8% Both transformers are solidly grounded on two sides. On a chosen base of 100MVA, 345kV in the transmission line circuit the line reactances are X1 = X2 = 15% and X0 = 50%. The system is operating at nominal voltage without prefault currents when a bolted (Zf = 0) single line to ground fault occurs on phase A at bus 3. Using the bus impedance matrix for each of the three sequence networks, determine the subtransient current to ground at the fault, the line-to-ground voltages at the faulted bus and at the terminals of machine 2. [Ans: I(f A) = 9316 270 A;V3a = 0kV ; V3b = 11.8856 − 122.71kV ; V3c = 11.8856 122.71kV ; V4a = 3.3466 0kV ; V4b = 11.7636 − 121.8kV ; V4c = 11.7636 121.8kV ] Figure 5: Figure 6: Electrical Engineering Dept - IIT Delhi EEL303: Power Engineering I - Tutorial 9 Solution: The transformers are solidly grounded on both sides, the zero-sequence network is fully connected, as shown in Figure. 5(d). Since fault takes place on bus 3, third column of ZBus of every sequence network is required. These can be obtained from the respective YBus . Third column of each of the sequence network is given as follows: 0 ZBus−3 = j0.0493 j0.0789 j0.0789 j0.1104 j0.1104 j0.0701 1 2 ; ZBus−3 = ; ZBus−3 = j0.1696 j0.1696 j0.1999 j0.1407 j0.1211 j0.1211 Since, the LG fault is at bus 3, we must connect the Thevenin equivalent circuits of the sequence networks in series, as shown in Figure. 6. From the figure we can calculate the symmetrical components of the current If A out of the system and into the fault using prefault voltage Vf as I(f A)(0) = I(f A)(1) = I(f A)(2) = Vf (1) Z33 + (2) Z33 + (0) Z33 = 16 0 = −j1.8549p.u j(0.1696 + 0.1696 + 0.1999) The total current in the fault is (0) I(f A) = 3I(f A) = −j5.5648p.u √ and since the base current in the HV transmission line is 100000/ 3×345 = 167.35A, we have The total current in the fault is I(f A) = −j5.5648 × 167.35 = 9316 270A The phase-a sequence voltages at bus 3 are (0) (0) (0) V3a = 0 − Z33 If A = −(j0.1999)(−j1.8549) = −0.3708p.u (1) (1) (1) V3a = Vf − Z33 If A = 1 − (j0.1696)(−j1.8549) = 0.6854p.u (2) (2) (2) V3a = 0 − Z33 If A = −(j0.1696)(−j1.8549) = −0.3146p.u From the above symmetrical components we can calculate a − b − c LG voltages at bus 3 as follows: 0 0 −0.3708 1 1 1 V3a V3b 1 a2 a 0.6854 −0.5562 − j0.8660 1.02936 − 122.71 = = = −0.5562 + j0.8660 1 a a2 −0.3146 V3c 1.02936 122.71 Electrical Engineering Dept - IIT Delhi EEL303: Power Engineering I - Tutorial 9 The phase-a sequence voltages at bus 4, the terminals of machine 2, are (0) (0) (0) V4a = −Z43 If A = −(j0.1407)(−j1.8549) = −0.2610p.u (1) (1) (1) V4a = Vf − Z43 If A = 1 − (j0.1211)(−j1.8549) = 0.7754p.u (2) (2) (2) V4a = −Z43 If A = −(j0.1211)(−j1.8549) = −0.2246p.u Note that subscripts A and a denote voltages and currents in the high voltage and low voltage circuits respectively, of the Star-Star connected transformer. No phase shift is involved. From the above symmetrical components we can calculate a − b − c LG voltages at bus 4 as follows: 0.28986 0 1 1 1 0.2898 + j0.0 −0.2610 V4b 1 a2 a 0.7754 −0.5364 − j0.8660 1.01876 − 121.8 = = = 2 1.01876 121.8 −0.5364 + j0.8660 1 a a −0.2246 V4c V4a To express the line-to-ground voltages at faulted bus √ and at terminals of machine 2 in kV, we multiply the respective p.u values by 20/ 3, which gives V3a = 0; V3b = 11.8856 − 122.71kV ; V3c = 11.8856 122.71kV ; V4a = 3.3466 0kV ; V4b = 11.7636 − 121.8kV ; V4c = 11.7636 121.8kV ; 3. The system shown in Figure 7. is operating at nominal system voltage without prefault currents when a bolted LL fault occurs at bus 3 on lines B and C. Using the bus impedance matrices of the sequence networks for subtransient conditions, determine the currents in the fault, the line-to-line voltages at the fault bus, and the line-to-line voltages at the terminals of machine 2. Figure 7: Solution: From Figure 8 the sequence currents are calculated as follows: Vf 16 90 (1) (2) I(f A) = −I(f A) = (1) = −j2.9481p.u = (2) j(0.1696 + 0.1696) Z33 + Z33 Electrical Engineering Dept - IIT Delhi EEL303: Power Engineering I - Tutorial 9 Figure 8: Uppercase A is used here because the fault is in the high voltage transmission line circuit. Since, I(f A)(0) = 0, the components of currents in the fault are calculated from (1) (2) I(f A) = I(f A) + I(f A) = −j2.9481 + j2.9481 = 0 (1) (2) I(f B) = a2 I(f A) + aI(f A) = −j2.9481(−0.5 − j0.866) + j2.9481(−0.5 + j0.866) = −5.1061 + j0p.u I(f C) = −I(f B) = 5.1061 + j0p.u The base current in the transmission line is 167.35A, and so I(f A) = 0 I(f B) = −5.1061 × 167.35 = 8556 180A I(f C) = −5.1061 × 167.35 = 8556 0A Symmetrical components of phase-A voltage to ground at bus 3 are 0 V3A =0 1 2 1 1 V3A = V3A = 1 − Zkk If A = 1 − (j0.1696)(−j2.9481) = 0.5 + j0p.u Line-to-ground voltages at fault bus 3 are (0) (1) (2) V(3A) = V(3A) + V(3A) + V(3A) = 0 + 0.5 + 0.5 = 16 0p.u (0) (1) (2) V(3B) = V(3A) + a2 V(3A) + aV(3A) = 0 + a2 0.5 + a0.5 = 0.56 180p.u V(3C) = V(3B) = 0.56 180p.u Line-to-line voltages at fault bus 3 are V(3,AB) = V(3A) − V(3B) = (1 + j0) − (−0.5 + j0) = 1.56 0p.u V(3,BC) = V(3B) − V(3C) = (−0.5 + j0) − (−0.5 + j0) = 0 V(3,CA) = V(3C) − V(3A) = (−0.5 + j0) − (−1.0 + j0) = 1.56 180p.u Electrical Engineering Dept - IIT Delhi In volts, the line-to-line voltages are 345 V(3,AB) = 1.56 0 × √ = 2996 0kV 3 EEL303: Power Engineering I - Tutorial 9 V(3,BC) = 0 345 V(3,CA) = 1.56 0 × √ = 2996 180kV 3 The sequence voltages of phase A at bus 4 are (0) (0) 0 V4A = −Z43 If A = 0 (1) (1) 1 V4A = Vf − Z43 If A = 1 − (j0.1211)(−j2.9481) = 0.643p.u (2) (2) 2 V4A = −Z43 If A = −(j0.1211)(−j2.9481) = 0.357p.u At machine 2 terminals, indicated by lower case a, the voltages are 0 V4a =0 1 1 6 V4a = V4A − 30 = 0.6436 − 30 = 0.5569 − j0.3215p.u 2 2 6 30 = 0.3576 30 = 0.3092 + j0.1785p.u V4a = V4A This is according to ASA where HT side positive sequence voltage leads corresponding LT side voltage by 30o . The opposite holds good for negative sequence voltage. 0 1 2 V4a = V4a + V4a + V4a = 0.8661 − j0.1430 = 0.87786 − 9.4p.u For phase-b of machine 2, 0 V4b0 = V4a =0 1 V4b1 = a2 V4a = −0.5569 − j0.3215p.u 2 2 V4a = aV4a = −0.3092 + j0.1785p.u V4b = V4b0 + V4b1 + V4b2 = −0.8661 − j0.143 = 0.87786 − 170.6p.u and, for phase c of machine 2 0 V4c0 = V4a =0 1 V4c1 = aV4a = 0.6436 90p.u 2 V4c2 = a2 V4a = 0.3576 − 90p.u V4c = V4c0 + V4c1 + V4c2 = j0.286p.u Line-to-line voltages at the terminals of machine 2 are V4,ab = V4,a − V4,b = 1.7322 + j0p.u V4,bc = V4,b − V4,c = −0.8661 − j0.429 = 0.96656 − 153.65p.u V4,ca = V4,c − V4,a = −0.8661 + j0.429 = 0.96656 153.65p.u Electrical Engineering Dept - IIT Delhi EEL303: Power Engineering I - Tutorial 9 Line-to-line voltages at machine 2 terminals are 20 V4,ab = 1.73226 0 × √ = 206 0kV 3 20 V4,bc = 0.96656 − 153.65 × √ = 11.26 − 153.65kV 3 20 V4,ca = 0.96656 153.65 × √ = 11.26 153.65kV 3 4. Find the sub-transient currents and the line-to-line voltages at the fault under subtransient conditions when a double line-to-ground fault, with phases B and C involved and Zf = 0 occurs at the terminals of machine 2 in the system of Figure 9.Assume that the (0) system is unloaded and operating at rated voltage when the fault occurs. [Z44 = j0.19, (1) (2) Z44 = Z44 = j0.1437.] [Ans:If a = 0; If b = 19, 2626 154.6o A; If c = 19, 2626 25.4o A;If = 16, 5386 90o A; V4,ab = 12.5686 0o kV ; V4,bc = 0; V4,ca = 12.5686 180okV ] Figure 9: Figure 10: Solution: To simulate the double line-to-ground fault at bus 4, we connect the Thevenin equivalents of all three sequence networks in parallel as shown in Figure 10, from which we obtain Vf 1 + j0 (1) If a = = −j4.4342p.u = (2) (0) (j0.1437)(j0.19) Z44 Z44 (1) j0.1437 + Z44 + (2) (0) (j0.1437 + j0.19) Z44 + Z44 Electrical Engineering Dept - IIT Delhi EEL303: Power Engineering I - Tutorial 9 Therefore, the sequence voltages at the fault are (1) (2) (0) (1) (1) V4a = V4a = V4a = Vf − If a Z44 = 1 − (−j4.4342)(j0.1437) = 0.3628p.u Current injections into the negative- and zero-sequence networks at the fault bus are calculated by current division as follows: (0) (2) If a = (1) −If a = (1) −If a Z44 (2) Z44 + (0) Z44 = j4.4342 × j0.19 = j2.5247p.u j(0.1437 + 0.19) = j4.4342 × j0.1437 = j1.9095p.u j(0.1437 + 0.19) (2) (0) If a Z44 (2) Z44 (0) Z44 + The currents out of the system at the fault point are (0) (1) (2) If a = If a + If a + If a = j1.9095 − j4.4342 + j2.5247 = 0 (0) (1) (2) If b = If a +a2 If a +aIf a = 1.90956 90o +(16 240o)(4.43426 −90o )+(16 120o)(2.52476 90o ) = −6.0266 + j2.8642 = 6.67266 154.6op.u (0) (1) (2) If c = If a +aIf a +a2 If a = 1.90956 90o +(16 120o )(4.43426 −90o )+(16 240o )(2.52476 90o ) = 6.0266 + j2.8642 = 6.67266 25.4o p.u and the current If into the ground is (0) If = If b + If c = 3If a = j5.7285p.u Calculating a-b-c voltages at the fault bus, we find that (0) (1) (2) (1) V4a = V4a + V4a + V4a = 3V4a = 3 × 0.3628 = 1.0884p.u V4b = V4c = 0 V4,ab = V4a − V4b = 1.0884p.u V4,bc = V4b − V4c = 0 V4,ca = V4c − V4a = −1.0884p.u √ Base current equals 100 × 103 /( 3 × 20) = 2887 A in the circuit of machine 2, and so we find that If a = 0 If b = 2887 × 6.67266 154.6o = 19, 2626 154.6o A If b = 2887 × 6.67266 25.4o = 19, 2626 25.4o A If c = 2887 × 5.72856 90o = 16, 5386 90o A √ The base line-to-neutral voltage in machine 2 is 20/ 3 kV, and so √ V4,ab = 1.0884 × 20/ 3 = 12.5686 0o kV V4,ca V4,bc = 0 √ = −1.0884 × 20/ 3 = 12.5686 180o kV Electrical Engineering Dept - IIT Delhi