Analog display for constant current analysis

www.reinhausen.com
Analog display for constant current analysis
Operating Instructions BA 2220015/01
NOTE
The product may have been modified after this document went to press.
We expressly reserve the right to make changes to the technical data, the design or the scope of
delivery.
In general, the information provided and the arrangements agreed during processing of the relevant offers and orders are binding.
Table of Contents
1
2
3
4
5
Safety ............................................................................................................................................................
5
1.1
1.2
Explanation of safety labels........................................................................................................................
Safety instructions .......................................................................................................................................
5
5
Configuration / Types..................................................................................................................................
6
Principle and configuration........................................................................................................................
7
3.1
3.2
3.3
3.4
Principle .........................................................................................................................................................
Configuration................................................................................................................................................
Connection ....................................................................................................................................................
Settings and adjustment .............................................................................................................................
7
7
7
7
Technical data ..............................................................................................................................................
8
4.1
4.2
4.3
4.4
4.5
Mechanical data ...........................................................................................................................................
Electrical data ...............................................................................................................................................
Accuracy under nominal conditions...........................................................................................................
Ambient characteristics ...............................................................................................................................
Regulations....................................................................................................................................................
8
8
8
9
9
Annex.............................................................................................................................................................
10
5.1
10
Dimensional drawing of tap position indicator device with rectangular front frame (898105:3M)
Operating Instructions BA 2220015/01 Analog display for constant current analysis
The copying, distribution and utilization of this document as well as the communication of its contents to others without expressed authorization is prohibited.
Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or ornamental design registration.
©Maschinenfabrik Reinhausen GmbH 2007
2220015/01 en
3
1
Safety
1
Safety
1.1
Explanation of safety labels
The following safety labels relating to the operation of the
analog signal transfer unit for remote tap position indication
are used in these Operating Instructions.
These labels must be observed at all times!
ATTENTION!
Refers to a potentially hazardous situation that may result in damage to
the product or adjacent equipment.
NOTE
NOTE!
Risk of damage to the motor drive
unit, on-load tap-changer and
transformer!
The signal transfer unit may only be
used with the on-load tap-changer
specified in the order.
It is the responsibility of the user to
make sure that the signal transfer
unit is used for the specified application only.
For safety reasons, any unauthorised
work, i.e. installation, alteration, commissioning or modification of the signal transfer unit is forbidden without
first consulting MR.
Contains important information and
special notes.
1.2
Safety instructions
• All warnings and safety instructions must be observed
at all times!
Failure to follow the safety instructions may lead to
accidents and severe personal injury.
• Please read these operating instructions before
commissioning the equipment!
Read the Operating Instructions before commissioning the
analog tap position indicator. As the operator, you are responsible for ensuring that users of the equipment have
fully understood the operating and safety instructions.
• Train your staff!
Before asking staff to work with the analog tap position
indicator, provide training regarding general and special
safety instructions and accident prevention regulations.
• Only suitably qualified personnel should work with the
analog tap position indicator.
The analog tap position indicator is designed exclusively
for application in electrical or energy systems and facilities
operated by appropriately trained staff,
i.e. staff who are familiar with the installation, assembly,
commissioning and operation of such products.
Operating Instructions BA 2220015/01 Analog display for constant current analysis
Unauthorised copying and distribution of this document and the utilisation and communication of its contents are strictly prohibited unless expressly authorised.
Offenders shall be held liable for damages. All rights conferred by patent grant and registration of a utility model or registered design are reserved.
©Maschinenfabrik Reinhausen GmbH 2007
2220015/01 en
5
2
2
Configuration / Types
Configuration / Types
For transformers where the transformer ratios are modified
through on-load tap-changers with remote-controlled motor
drives, the operating positions of the on-load tap-changer
have to be displayed in the control room.
Tap position indicator instruments with square or rectangular
design for constant current analysis require no additional
power supply unit.
The devices can be mounted with the two screw spindles provided. Insert the screw spindle into the bracket from the rear
of the device (plastic handle facing backwards) and turn it
sideways
• to the first recess (for control panel thickness up to 20 mm)
• to the second recess (for control panel thickness 20 - 40
mm).
Fold in the screw spindle and push the device into the control
panel cutout. Turn the screw spindle until it latches (90° angle
relative to the device) and tighten it manually or with a small
screwdriver.
NOTE
Before tightening the screw spindle
carefully move it back and forth in
order to ensure free movement.
NOTE
In a high-density installation the
screw spindles can be mounted between the devices, since they are diagonally offset.
The power supply unit is designed for top hat rail mounting
according to DIN EN 50022.
Operating Instructions BA 2220015/01 Analog display for constant current analysis
Unauthorised copying and distribution of this document and the utilisation and communication of its contents are strictly prohibited unless expressly authorised.
Offenders shall be held liable for damages. All rights conferred by patent grant and registration of a utility model or registered design are reserved.
©Maschinenfabrik Reinhausen GmbH 2007
2220015/01 en
6
3
3
Principle and configuration
Principle and configuration
The tap position indicator instrument displays the current position of the motor drive or the on-load tap-changer at any
location, usually in the control room.
3.3
3.1
Terminals 17 (+) and 18 (-) (generally terminals X1:211 (-) and
X1:212 (+)) are connected with the output signal of the measuring transducer in the motor drive unit.
Principle
Each motor drive position corresponds to a contact area on the
position transmitter board that is contacted by the slider. The
contact areas are connected with the position transmitter module (resistor type) via the position transmitter cable.
In the position transmitter module a modified resistance value
is transferred to the input of a measuring transducer in the
motor drive unit, depending on the position. This measuring
transducer converts the resistor input signal into a constant
current signal (e.g. 4...20 mA). The input signal of the measuring transducer is generally specified with 10 ohm per step, the
output signal can be variable, usually 4...20 mA. The display
instrument is adapted to the output signal and therefore
indicates the motor drive position, depending on the constant
current signal.
3.2
Configuration
A resistor-type position transmitter position transmitter is
required in the motor drive unit. The resistor contact range (10
ohm per step) must match the number of required positions.
The motor drive unit also features a measuring transducer that
converts the resistor signal into a constant current signal
(4...20 mA).
Connection
Tap position indicator device, square version
Standard connection
Terminal 17 (+)
Terminal 18 (-)
3.4
constant current input +
constant current input -
Settings and adjustment
The tap position indicator instrument are preset and only
require fine-tuning
via the adjusting screw.
Fine-tuning
• Check the connection
• Move the motor drive unit into the minimum switching position
• Set the position indicator to the centre of the minimum
scale value using the adjusting screw
• Move the motor drive unit into the maximum switching
position
• Check the display and readjust if necessary
The output signal of the measuring transducer is connected
with the display instrument via a signal line.
Operating Instructions BA 2220015/01 Analog display for constant current analysis
Unauthorised copying and distribution of this document and the utilisation and communication of its contents are strictly prohibited unless expressly authorised.
Offenders shall be held liable for damages. All rights conferred by patent grant and registration of a utility model or registered design are reserved.
©Maschinenfabrik Reinhausen GmbH 2007
2220015/01 en
7
4
Technical data
4
Technical data
4.1
Mechanical data
Type
Casing material
Front screen
Front frame colour
Mounting position
Fastening
Installation
Control panel thickness
Connection
Wire section
Display dimensions
Square front frame with
bridge circuit
Circuit board section
Drawings
4.2
Casing for installation in control panels or machine
consoles, modular
Polycarbonate, self-extinguishing and non-dripping
according to UL 94 V – 0
Sheet glass
black (similar to RAL 9005)
vertical ± 5°
Screw spindle
High-density installation possible
<= 40 mm
Hex bolts with M4 and bolt clamp strap
max. 2.5 mm²
72 x 72 mm
96 x 96 mm
144 x 144 mm
Installation depth 120 mm (all models)
68 x 68 mm
92 x 92 mm
138 x 138 mm
899030:0M
Electrical data
Measured variable
DC
Overload limit according to DIN EN 60051
Continuous
1.2 x
max. 5 s
10 x
Protection class
II
IP rating
IP20
Insulation group
A according to VDE 0110
Rated insulation voltage
1000 V
Test voltage
3 kV at 50 Hz, 1 min. according to DIN 57410
4.3
Accuracy under nominal conditions
Precision class
Nominal conditions
Ambient temperature
Mounting position
Input variable
Other
Influence factors
Mounting position
Stray magnetic field
1.5 according to DIN EN 60051
23 °C ± 1 K
Nominal mounting position ± 1°
Nominal measuring range
DIN EN 60651
Ambient temperature –10 °C ... +55 °C
Nominal mounting position ± 5°
0.5 mT
Operating Instructions BA 2220015/01 Analog display for constant current analysis
Unauthorised copying and distribution of this document and the utilisation and communication of its contents are strictly prohibited unless expressly authorised.
Offenders shall be held liable for damages. All rights conferred by patent grant and registration of a utility model or registered design are reserved.
©Maschinenfabrik Reinhausen GmbH 2007
2220015/01 en
8
4
4.4
Technical data
Ambient characteristics
Climate suitability
Operating temperature
range
Storage temperature range
Relative humidity
Impact resistance
Vibration resistance
4.5
Climate class 3 according to VDE/VDI 3540
-10 °C ... +55 °C
-25 °C ... +65 °C
<= 75% on average over the year, no condensation
15 g, 11 ms
2.5 g, 5...55 Hz
Regulations
DIN 43700
DIN 43701
DIN 43718
DIN 43802
DIN 16257
DIN 57410/VDE 0410
DIN 60051
VDE 0110
VDE 0411
DIN 40050
VDE/VDI 3540 Sheet 2
Devices for flush mounting, nominal and section
dimensions
Electrical control panel measuring instruments
Front-frames and front panels
Line scales and pointers for electrical measuring
instruments
Nominal positions and position symbols used for
measuring instruments
Safety regulations for measuring instruments with
display and recording function, and accesories
Direct acting indicating analogue electricalmeasuring instruments and their accessories
Regulations for determining clearances and creepage
distances of electrical equipment
Safety requirements for electronic measuring
instruments
Degrees of protection (IP-code); protection against
foreign objects; water and contact; electrical
equipment
Reliability of measuring and control devices (climate
classes for devices and accessories)
Operating Instructions BA 2220015/01 Analog display for constant current analysis
Unauthorised copying and distribution of this document and the utilisation and communication of its contents are strictly prohibited unless expressly authorised.
Offenders shall be held liable for damages. All rights conferred by patent grant and registration of a utility model or registered design are reserved.
©Maschinenfabrik Reinhausen GmbH 2007
2220015/01 en
9
5
Annex
5
Annex
5.1
Dimensional drawing of tap position indicator device with rectangular front frame (898105:3M)
Operating Instructions BA 2220015/01 Analog display for constant current analysis
Unauthorised copying and distribution of this document and the utilisation and communication of its contents are strictly prohibited unless expressly authorised.
Offenders shall be held liable for damages. All rights conferred by patent grant and registration of a utility model or registered design are reserved.
©Maschinenfabrik Reinhausen GmbH 2007