Part-turn actuators ASO 3 - ASO 6 AS 6 - AS 50 ASR 6 - ASR 50 Operation instructions Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Scope of these instructions: Operation instructions These instructions are only valid for part-turn actuators wired according to wiring diagrams CI V . . . AI . . . (3. digit ”V”), refer to name plate AUMA VARIOMATIC. TABLE OF CONTENTS 1. Safety instructions . . . . . . . . . . . 1.1 Range of application . . . . . . . . . 1.2 Short description . . . . . . . . . . . 1.3 Commissioning (electrical connection) 1.4 Maintenance . . . . . . . . . . . . . 1.5 Warnings and notes. . . . . . . . . . 1.6 Further notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 3 3 3 3 3 2. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3. Transport and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 4. Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 5. Mounting to valve/ gearbox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 6. Test of the mechanical end positions CLOSED and OPEN 6.1 End position CLOSED . . . . . . . . . . . . . . . . . . . 6.2 Limit seating. . . . . . . . . . . . . . . . . . . . . . . . . 6.3 Torque seating . . . . . . . . . . . . . . . . . . . . . . . 6.4 Setting for CLOSED. . . . . . . . . . . . . . . . . . . . . 6.5 End position OPEN . . . . . . . . . . . . . . . . . . . . . 6.6 Setting values for end stops. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 6 6 6 6 7 7 7. Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 8. Setting of the internal end position detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 8.1 Setting for end position OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 8.2 Setting for end position CLOSED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 9. Setting of the torque switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10. Setting of the mechanical position indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 11. Test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 12. Setting of the potentiometer (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 13. Setting of the position feedback 0/4 - 20 mA (option) . . . . . . . . . . . . . . . . . . . . . . . . . 11 14. Programming AUMA VARIOMATIC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 14.1 Programming with BUS board installed (MODBUS, PROFIBUS and INTERBUS S) . . . . . . . . . . 13 15. Electronic positioner (option) . . . . . . . . 15.1 Technical data . . . . . . . . . . . . . . . . 15.2 Setting . . . . . . . . . . . . . . . . . . . . 15.3 Programming of the positioner board . . . . 15.4 Positioner adjustment end position CLOSED 15.5 Positioner adjustment end position OPEN. . 15.6 Setting of the sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 14 14 14 15 16 16 16. Setting of the operating time (output speed) . . . . . . . . . . . . . . . . . . . . . . . 16.1 Setting of the operating time via internal command signal . . . . . . . . . . . . . . . . 16.2 Setting of the operating time via the speed-interface board (option) . . . . . . . . . . . 16.3 Further functions of the speed-interface board in conjunction with the positioner (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 17 18 19 17. Signal board (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 18. Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 19. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 20. Declaration of Conformity and Declaration of Incorporation . . . . . . . . . . . . . . . . . . . . . 22 2 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions 1. Safety instructions 1.1 Range of application AUMA part-turn actuators are designed for the operation of industrial valves, e.g. butterfly valves and ball valves. AUMA is not liable for any possible damages resulting from other applications. Such risk lies entirely with the user. Observance of these operation instructions is considered as part of the actuator’s designated use. 1.2 Short description AUMA part-turn actuators type ASO 3 - ASO 6 and AS(R) 6 - AS(R) 50 have a modular design. Motor and gearing are mounted in a common housing and make up a coaxial unit together with the output drive. Manual operation is possible without change-over. The actuators are driven by an electric motor and controlled with the electronic controls AUMA VARIOMATIC. The controls are included in the scope of delivery. The operating time can be adjusted for 90° swing angle within the range 4 - 60 / 6 - 90 s (dependent on size). 1.3 Commissioning (electrical connection) During electrical operation certain parts inevitably carry lethal voltages. Work on the electrical system or equipment must only be carried out by a skilled electrician himself or by specially instructed personnel under the control and supervision of such an electrician and in accordance with the applicable electrical engineering rules. 1.4 Maintenance The maintenance instructions (refer to page 21) must be observed, otherwise a safe operation of the part-turn actuator is no longer guaranteed. 1.5 Warnings and notes Non-observance of the warnings and notes may lead to serious injuries or damages. Qualified personnel must be thoroughly familiar with all warnings and notes in these operation instructions. Correct transport, proper storage, mounting and installation, as well as careful commissioning are essential to ensure a trouble-free and safe operation. The following references draw special attention to safety-relevant procedures in these operation instructions. Each is marked by the appropriate pictograph. This pictograph means: Note! ”Note” marks activities or procedures which have major influence on the correct operation. Non-observance of these notes may lead to consequential damage. This pictograph means: Electrostatically endangered parts (ESD)! If this pictograph is attached to a printed circuit board, it contains parts which may be damaged or destroyed by electrostatic discharges. If the boards need to be touched during setting, measurement or for exchange, it must be assured that immediately before a discharge through contact with an earthed metallic surface (e.g. the housing) has taken place. This pictograph means: Warning! ”Warning” marks activities or procedures which, if not carried out correctly, can affect the safety of persons or material. 1.6 Further notes MOV M This pictograph means: Procedure may have been performed by valve manufacturer! If actuators are delivered mounted to a valve, this step has been done in the valve manufacturer’s plant. Setting must be checked during commissioning! 3 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC 2. Operation instructions Technical data Tripping torque both directions max. Nm 321) 631) 63 125 250 500 min. Nm – – 25 50 100 200 AUMA part-turn actuators for OPEN - CLOSE duty Type ASO 3 ASO 6 AS 6 AS 12 AS 25 AS 50 AUMA part-turn actuators for modulating duty Type – – ASR 6 ASR 12 ASR 25 ASR 50 Nm – – 30 60 120 240 Torque for modulating Factor 2) (manual operation) 15 Handwheel turns for 90o 13,5 Swing angle (end stops are adjustable within this range) Operating time for 90o Type of duty 3) VDE 0530 / IEC 34 Standard 90o (82o - 98o) s 4 - 60 6 - 90 OPEN-CLOSE Actuators Short-time duty S2 - 15 min Modulating actuators Intermittent duty S5 -40% ED Number of starts max. 1 800 c/h4) Impulse time (for control signals) min. ms – – 50 Insulation class (motor windings) 50 70 70 2,4 3,2 4,8 6,4 F Current values for single-phase connection 5) Effective values 220 - 240 V; 50 / 60Hz max. A 0,7 1,5 1,5 110 -120 V; 50 / 60Hz max. A 1,5 3,0 3,0 8) Recommended fuses in mains: 6 A , characteristic D according to VDE 0641 and IEC/EN 60 898 Fuses Electrical input power at shortest operating time approx. W 75 160 160 260 360 Weight with controls approx. kg 8 8 11 16 24 Enclosure protection according to EN 60 529 Standard: IP 67 6); Option: Actuator IP 68 7), controls IP 67 for mounting on wall OPEN-CLOSE actuators: – 25 oC to +70 oC / modulating actuators: – 25 oC to +60 oC Ambient temperature Electrical connections with electronic controls AUMA VARIOMATIC directly installed Electrical connections for with electronic controls AUMA VARIOMATIC installed separately Remote control/ signals Mains Controls Motor Plug/socket connector with 48-pole screw cable terminations, max. 2,5 mm2 Option: Crimp connection for flexible cables, 40-pole; 0,75 - 1,0 mm2 on request 0,5 mm2 or 1,5 mm2 are possible Plug/socket connector with screw cable terminations; max.6 mm2 Option: Crimp connection for flexible cables, 0,75 - 1,5 mm2 Plug socket connector with crimp connection for flexible cables, 40-pole; 0,75 -1 mm2, on request 0,5 mm2 or 1,5 mm2 are possible Plug/socket connector with crimp connection for flexible cables, 0,75 - 1,5 mm2 For the electrical operation of the part-turn actuators the electronic controls AUMA VARIOMATIC are necessary. The controls are available for direct fitting or for mounting on wall. A separate installation of the electronic controls requires screened connecting cables. Notes concerning screening and earthing according to wiring diagram and legend must be observed. The max. permissible cable length between part-turn actuator and VARIOMATIC for types AS and ASR is: 100 m, for types ASO: 15 m. 1) Torque sensor not provided. Switching off by motor current monitoring. 2) Conversion factor output torque to input torque at handwheel 3) Adjustable by potentiometer in electronic controls 4) To reach the longest possible maintenance and fault-free operation time, the number of starts during normal operation should be chosen as low as permissible for the process. 4 5) Max. values for shortest operating time. 6) IP 67 means: Protection against short-time immersion into water; max. 1 m head of water for 30 min. 7) IP 68 means: Protection against submersion up to max. 6 m head of water for the duration of 72 hours, up to 10 operations during the submersion. 8) Groups of up to 4 actuators can be protected with a safety cutout 20 A, characteristic according to VDE 0641 and IEC/EN 60 898. Operation instructions 3. Transport and storage .. . .. .. Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Transport to place of installation in sturdy packing. Do not attach ropes or hooks to the handwheel for the purpose of lifting by hoist. If part-turn actuator is mounted on valve, attach ropes or hooks for the purpose of lifting by hoist to valve and not to part-turn actuator. Store in well-ventilated, dry room. Protect against floor dampness by storage on a shelf or on a wooden pallet. Cover to protect against dust and dirt. Apply suitable corrosion protection agent to bright surfaces. If part-turn actuators are to be stored for a long time (more than 6 months), the following points must be observed additionally: . . Prior to storage: Protect unfinished surfaces, especially of output drive parts and mounting surface with long-term corrosion protection agent. Check for corrosion approximately every 6 months. If first signs of corrosion show, apply new corrosion protection. After mounting, connect part-turn actuator immediately to electrical system, so that condensation is prevented by the heater. 4. Manual operation Manual operation is activated by turning the handwheel. A change-over is not required. The handwheel does not rotate during motor operation. Turning the handwheel during motor operation results in an extension or reduction of the operating time, depending on the direction of rotation. 5. . . Mounting to valve/ gearbox MOV M Prior to mounting the part-turn actuator must be checked for any damage. Damaged parts must be replaced by original spare parts. The easiest position for mounting is when the valve shaft points upright. But mounting is also possible in any other position. The part-turn actuator is delivered ex works in position CLOSED. For butterfly valves the mounting position is end position OPEN. For ball valves the mounting position is end position OPEN. Prior to mounting, the part-turn actuator must be driven to the mechanical end stop OPEN by turning the handwheel counter-clockwise. Thoroughly degrease mounting faces of part-turn actuator and valve. Put coupling sleeve on valve shaft and secure it (figure A). Ensure that dimensions X and Y are observed. .. .. Figure A 5 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions Table 1 ASO 3 X max. mm Y max. mm Z max. mm 6. 3 5 28 ASO 6 AS 12 AS 25 AS 50 AS 6 ASR 12 ASR 25 ASR 50 ASR 6 3 2,5 2,5 3,5 5 6 6 10 28 38 48 48 .. . . Fastening torques Strength class Threads Fastening torques Nm M6 10 8.8 M8 M 10 25 50 Apply non-acidic grease at toothing of coupling. Fit actuator so that fixing holes in actuator and valve mounting flange align. If necessary, move actuator upward one tooth on the coupling. If required, turn handwheel a little in direction OPEN or CLOSE until holes align. Ensure that spigot mates uniformly in the recess and that the mounting faces are in complete contact. Fasten actuator with bolts. Fasten bolts crosswise with torque wrench (fastening torques see table 1). Test of the mechanical end positions CLOSED and OPEN MOV 6.1 End position CLOSED 6.2 Limit seating 6.3 Torque seating 6.4 Setting for CLOSED M This test can only be performed on valves which have not been mounted into a pipeline. . . . . Check if mechanical end position of the valve corresponds to mechanical end stop of actuator by turning at handwheel (clockwise for end position CLOSED) For limit seating, the actuator always runs up to the mechanical end stop. For torque seating in end position CLOSED the mechanical end stop of the actuator must be set to a swing angle larger than actually required by the valve. Remove screw plug (22.1, figure B1) and adjust mechanical end position at hex. socket head cap screw (21.1, figure B2). Turning clockwise results in smaller, turning counter-clockwise results in larger swing angle. Never remove the screws (21.1 and 21.2, figure B2) completely, because this will cause oil leakage. . Replace and fasten screw plug (22.2, figure B1). Figure B1 22.2 6 M 12 85 22.1 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions Figure B2 (top view) CLOSED 6.5 End position OPEN Figure B3 (top view) OPEN The swing angle has been set in the factory to approx. 90° or to the swing angle stated in the order. An adjustment might be necessary if an adjustment of the end position CLOSED has been performed. . . . Check if mechanical end position of the valve corresponds to mechanical end stop of actuator by turning at handwheel (counter-clockwise for end position OPEN) Remove screw plug (22.2) and adjust mechanical end position at hex. socket head cap screw (21.1, figure B3). Replace and fasten screw plug (22.2). 6.6 Setting values for end stops Figure B4 (top view) Figure B5 (top view) OPEN CLOSED Swing angle 1) Basic factory setting for 90° swing angle ASO 3 / ASO 6 AS 6 / ASR 6 13,5 Dimension T in mm AS 12 AS 25 ASR 12 ASR 25 13 16 AS 50 ASR 50 19 For each turn of the hex. socket head cap screw, the setting of the end position changes by: ASO 3 / ASO 6 AS 12 AS 25 AS 50 AS 6 / ASR 6 ASR 12 ASR 25 ASR 50 for clockwise turn appr.: 3,3° 2,4° 3° 2,4° for counter-clockwise 2,4° 1,9° 2,1° 1,8° turn appr.: 1) By turning at the hex. socket head cap screw for end stop CLOSED or OPEN the end position changes accordingly. The swing angle can be checked and set by using the dimension T. 7 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC 7. Electrical connection Operation instructions Work on the electrical system or equipment must only be carried out by a skilled electrician himself or by specially instructed personnel under the control and supervision of such an electrician and in accordance with the applicable electrical engineering rules. AUMA part-turn actuators are operated via the electronic controls AUMA VARIOMATIC. The controls may either be mounted directly to the actuator or to a separate wall bracket. The electrical connection to the power supply is made at a plug / socket connector with screw cable terminations as standard. When mounting the AUMA VARIOMATIC separately to a wall bracket, suitable flexible and screened connecting cables are additionally required. The max. permissible cable length between part-turn actuator and VARIOMATIC for types AS and ASR is: 100 m, for types ASO: 15 m. On request, complete cable sets may also be purchased subsequently from our factory. Check whether power supply (type of current, voltage and frequency) suits the motor (see name plate on controls AUMA VARIOMATIC). Remove plug cover. Install suitable cable glands with enclosure protection IP 67 (option IP 68) which suit the cable diameters. Ensure professional connection of the screening for the connecting cables for AUMA VARIOMATIC (on wall bracket) and/or when continuous position indication signal (option) is provided. Connect cables according to wiring diagram CI V... AI...(refer to name plate). 2 Cross sections: control cables max. 2,5 mm , 2 power supply max. 6 mm . . .. . . Connection in Crimp version (figure C): For AUMA VARIOMATIC on wall bracket the connection for the cables between actuator and controls is always realised in Crimp version (controls max. 40 poles). Crimp socket carriers are supplied loose in sufficient numbers in the plug cover. For crimping a suitable tool, e.g. the BUCHANAN four indent crimp tool, must be used. 2 2 Cross sections: for flexible cables, 0,75 - 1,0 mm , or (if ordered) 0,5 mm or 2 1,5 mm . Optionally the power supply connection can also be realised in Crimp version (number of poles and cable cross sections see above). Figure C Pole diagram for: a) Customer connection for Crimp version (option) b) Connection between actuator and controls VARIOMATIC 8 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions 8. Setting of the internal end position detection MOV M For the setting of the end position detection the actuator must be mounted to the valve. The internal end position detection is set to a swing angle of 90° in the factory. A subsequent change is only necessary if another swing angle is required. Prior to the setting of the electrical swing angle the end stops must be set to the appropriate value according to clause 6, page 6. 8.1 Setting for end position OPEN Figure D .. .. .. . . .. .. .. . Take off cover at switch compartment (figure K, page 12). Turn handwheel firmly in direction OPEN until valve is closed or mechanical end stop OPEN is reached Set selector switch to position LOCAL. Switch on power supply. Loosen both screws (4.06) (figure E). Rotate control disc Figure E (4.2) clockwise, until green LED lights up to indicate switching point OPEN. In case of having turned too far, the green LED goes out again. The control disc should be positioned in such a way that it is situated midway between the green LED lighting up and going out. Hold control disc in position and tighten screws (4.06). Check setting by approaching the switching point under electrical operation in direction OPEN anew. 8.2 Setting for end position CLOSED Turn handwheel up to mechanical end stop CLOSED. Check if switching point is reached (yellow LED CLOSED is illuminated). If not, correct setting value on dial as follows: Loosen screw (4.8) (figure E). Remove control disc (4.2) (figure E). Loosen screw (4.01) at lower side of control disc (figure D). Fit control disc (4.2) (figure E). Rotate control disc (4.2) clockwise, until yellow LED lights up to indicate switching point CLOSED. In case of having turned too far, the yellow LED goes out again. The control disc should be positioned in such a way that it is situated midway, between the yellow LED lighting up and going out. Pull off control disc (4.2) again and fasten screw (4.01) (figure E). Ensure that the graduated control disc (4.02) is not moved. Fit control disc (4.2) and secure with screw (4.8). Check setting: Move valve manually to intermediate position. Approach switching point in direction CLOSE electrically with push-button CLOSE. . .. 9 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC 9. Operation instructions Setting of the torque switching .. . MOV M Figure G 5.2 4.3 . .. (not possible for types ASO 3 and ASO 6) Set torque must suit the valve! When part-turn actuators were delivered by a valve manufacturer, setting was made during testing. This setting should only be changed with the consent of the valve manufacturer. Determine the required setting values for opening and closing direction on scale (5.0) of board (4.3) (figure G). Set the value determined for direction CLOSE (0 - 9) at rotary switch (5.1). Set the value determined for direction OPEN (0 - 9) at rotary switch (5.2). Example (scale for part-turn actuator AS 12) Setting values at 0 1 2 3 4 rotary switch Torque Nm 50 60 65 75 85 5 6 7 8 9 90 100 110 115 125 10. Setting of the mechanical position indicator The mechanical position indicator is realised with the white clamping pointer (4.4, figure H) below the sight glass (of the switch compartment cover). The clamping pointer (4.4) shows only the position CLOSED or OPEN with respect to the pipeline. With the sight glass removed the symbols on the board (4.3) show the electrically set end position points. Run part-turn actuator manually to end position CLOSED. Lift clamping pointer (4.4) at indentation slightly and turn it so that it points crosswise to the pipeline. .. When changing the mounting position of the actuator, the mechanical position indication may have to be re-set! Figure H CLOSED OPEN 4.4 4.4 Switch compartment 11. Test run 10 . . .. Approach end position CLOSED and end position OPEN electrically and check seating. Clean sealing faces at cover and housing; check whether O-ring is in good condition. Apply a thin film of non-acidic grease to the sealing faces. Replace cover and fasten hex. bolts evenly crosswise. Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions 12. Setting of the potentiometer (option) .. . Take off cover at switch compartment (figure K, page 12). Run part-turn actuator to end position CLOSED. Turn potentiometer R11 (figure J) counter-clockwise until the mechanical stop is reached. Afterwards turn minimally in clockwise direction. Figure J Rmax Rmin R11 13. Setting of the position feedback 0/4 - 20 mA (option) .. . . .. .. Take off cover at switch compartment (figure K, page 12). Run part-turn actuator to end position CLOSED. Turn potentiometer R11 (figure J) counter-clockwise until the mechanical stop is reached. Afterwards turn minimally in clockwise direction. Set to 0 or 4 mA with setting potentiometer Rmin. For 2-wire systems the minimum current is always 4 mA (see wiring diagram). Run part-turn actuator to end position OPEN. Set to 20 mA with setting potentiometer Rmax. Check setting by running valve to end positions again. Replace cover and fasten 4 bolts evenly crosswise. 11 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions 14. Programming AUMA VARIOMATIC . Remove 4 screws at VARIOMATIC (figure K / 8.1) and take off cover. Figure K: Part-turn actuator ASO/ AS(R) with controls AUMA VARIOMATIC 8.1 AUMA VARIOMATIC Switch compartment cover Local controls MOV M . . . In the factory push-to-run operation REMOTE and push-to-run operation LOCAL are programmed (refer to table 2, page 13). The type of seating - limit or torque seating - (DIP switch S1 pos. 5 and pos. 6) must be determined by the valve manufacturer. Set desired programming according to table 2 at DIP switch S1 (figure L). If no positioner (figure N, page 14) or speed-interface board (figure R, page 18) is fitted, the DIP switch S1 pos. 7 must always be in position ”ON”. Figure L: VARIOMATIC Standard Diagnosis LED (green): Potentiometer Illuminated when for setting of OPERATING TIME ready Diagnosis LED (red): Motor protection tripped Diagnosis LED (green): Enable REMOTE (option) always installed, illuminated during normal operation DIP switch S1 for programming ON 1234 56 7 Diagnosis LEDs for active REMOTE control commands: run command STOP (red) run command OPEN (green) run command CLOSE (yellow) Logic board Cover plate standard . 12 Replace cover and fasten 4 bolts (figure K / 8.1) evenly crosswise. Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions Table 2 DIP switch S1 (on logic board) Programming Direction CLOSE ON OFF Self-retaining REMOTE ON OFF Push-to-run operation REMOTE ON OFF Self-retaining LOCAL Push-to-run operation LOCAL Type of seating limit seating ON OFF ON OFF 1234 56 7 1234 56 7 ON OFF 1234 56 7 1234 56 7 ON OFF 1234 56 7 1234 56 7 ON OFF 1234 56 7 1234 56 7 for end position CLOSED for end position OPEN ON OFF ON OFF ON OFF torque seating Direction OPEN With positioner installed: Speed dependent on error variable Speed not dependent on error variable 1234 56 7 1234 56 7 ON OFF ON OFF 1234 56 7 ON OFF 1234 56 7 1234 56 7 1234 56 7 Self-retaining REMOTE must be switched off when used in conjunction with the positioner (clause 15, page 14). 14.1 Programming with BUS board installed (MODBUS, PROFIBUS and INTERBUS S) Refer to separate instructions for appropriate bus system. Table 3 DIP switch S1 (on logic board) Self-retaining REMOTE Push-to-run operation REMOTE Programming (not applicable for BUS systems) ON OFF ON OFF Self-retaining LOCAL ON OFF Push-to-run operation LOCAL Type of seating 1234 56 7 1234 56 7 1234 56 7 for end position CLOSED see insert at appendix ON limit seating torque seating OFF ON OFF 1234 56 7 1234 56 7 externally (via BUS) Nominal output speed 1) 1) PROFIBUS-FMS and MODBUS Profibus DP and INTERBUS-S ON OFF 1234 56 7 for end position OPEN ON OFF ON OFF 1234 56 7 1234 56 7 internally ON OFF 1234 56 7 switch position S1 pos. 7 to ”ON”. (no nominal output speed possbible via bus) switch position S1 pos. 7 to ”OFF”. 13 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions 15. Electronic positioner (option) 15.1 Technical data Command signal (input signal E1, nom. value) Feedback (input signal E2, actual value) Sensitivity (dead band) ∆E (R35) Fine adjustment ”Sens” (R31) Time delay ”toff ”(R88) Input resistance 15.2 Setting MOV . .. M 0/4 - 20 mA (option 0 - 5 V) 0/4 - 20 mA (option 0 - 5 V) 0,5 % - 2,5 % min 0,25 % 0,5 - 10 s 250 Ohm Remove 4 screws at cover of AUMA VARIOMATIC (8.1, figure K, page 12) and take off cover. For the functions of the LEDs installed on positioner board: refer to figure N. Check programming of the logic board according to pages 12/13, clause 14: Pos. 1 and Pos. 3 must be in Pos. ”OFF” (figure N). If no speed variation is desired, the DIP switch S1 pos. 7 must be in position ”ON”. If an error-dependent speed variation is required (figure M), set DIP switch S1 pos. 7 to ”OFF”. Figure M: Speed dependent on error variable Figure N: VARIOMATIC with positioner Potentiometer for setting of OPERATING TIME Diagnosis LED (green): Illuminated when ready DIP switch S1 for programming Diagnosis LED (red): Motor protection tripped Diagnosis LED (green) 1) Enable REMOTE (option) always installed, illuminated during normal operation V24: Run command OPEN (green) 1234567 V23: Run command CLOSE (yellow) V35: Permissible number of starts exceeded (red) V37: Signals E1 or E2 not available (red) Logic board R88: Delay time Cover plate positioner 1) Enable REMOTE (option) refer to appropriate wiring diagram: Analogue command signal or run command via local controls are not accepted without external enable signal (24V DC). .. . 15.3 Programming of the positioner board Remove cover plate (figure N). Set switch S2 pos. 5 (figure O1, page 16) according to input signal (nominal value) E1: 0 - 20 mA: Position ”OFF” 4 - 20 mA: Position ”ON” Set switch S2 pos. 6 for E2 (actual value) = 4 mA to position ”ON”. (for E2 position feedback via potentiometer 0 - 5 V in position ”OFF”) 14 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions In standard version switch S3 (figure O1, page 16) for command signal E1 = 0/4 - 20 mA, i.e. end position ”OPEN” = 20 mA, must be in position 1. Version for inverse operation (i.e. end position ”OPEN” = 0/4 mA) must be ordered accordingly from the factory. Programming for faults: Behaviour on loss of input signal E1 and / or on loss of feedback signal E2 Pre-condition: Signals 4 - 20 mA . Process related (desired) behaviour: Programming: (figure O1, page 16) fail as is, i.e. part-turn actuator stops immediately and remains in this position fail close, i.e. part-turn actuator moves the valve to the end position CLOSED fail open, i.e. part-turn actuator moves the valve to the end position OPEN Before beginning the positioner setting it has to be ensured that the internal end position recognition (clause 8), the torque switching of the actuator (clause 9) as well as the position feedback (clauses 12 and 13) have been set. .. . 15.4 Positioner adjustment end position CLOSED Set selector switch (local controls) to position I (LOCAL). Run part-turn actuator with push-button to end position CLOSED . Supply nominal value E1 of 0 or 4 mA (see wiring diagram). . . Connect voltmeter to measuring points M1 and M2 (0 - 5 V) for measuring of the nominal value (figure O1, page 16). For a nominal value E1 of 0 mA the Voltmeter shows 0 V. For a nominal value E1 of 4 mA the Voltmeter shows 1 V. Connect Voltmeter to measuring points M3 and M4 for measuring the actual value signal. For an actual value E2 of 0 mA the Voltmeter shows 0 V. For an actual value E2 of 4 mA the Voltmeter shows 1 V. If measured value is not correct: Adjust position feedback signal according to page 11, clause 12 or 13. Set potentiometer R35 (∆E) and R31 (sens) to minimal value by turning counter-clockwise. Possible LED indication: (refer to figures O1 and O2) LEDs are not illuminated Required setting in end position CLOSED: (refer to figures O1 and O2) Turn potentiometer ”0” (R25) slightly clockwise until LED (V23 yellow) lights up. LED (V24 green) is illuminated Turn potentiometer ”0” (R25) slightly clockwise until LED (V24) goes out and LED (V23 yellow) lights up. LED (V23 yellow) is illuminated Then If . Missing signal E1 and / or E2 is indicated by ”LED E1/E2 < 4 mA” (figures O1+O2 / V37). Turn potentiometer ”0” (R25) counter-clockwise until LED (V23 yellow) goes out. Then turn potentiometer ”0” (R25) slightly clockwise until LED (V 23 yellow) lights up again. 15 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions . . 15.5 Positioner adjustment end position OPEN Run part-turn actuator by depressing push-button (local controls) to end position OPEN. Connect Voltmeter to measuring points M3 and M4 (figure O1) for measuring of the actual value E2. When position feedback is set correctly the Voltmeter shows 5 V. If measured value is not correct: Perform feedback adjustment according to page 11, clause 12 or clause 13 and continue with page 15 subclause 15.4. Connect max. command signal (nominal value E1) = 20 mA. Connect Voltmeter to measuring points M1 and M2 (figure O1) for measuring of the nominal value E1. For a measured value of 20 mA the Voltmeter shows 5 V. If measured value is not correct: Check the externally supplied command signal E1. .. Required setting in end position OPEN: (refer to figures O1 und O2) Turn potentiometer ”max” (R28) slightly counter-clockwise until LED (V24 green) lights up. LED (V24 green) is illuminated Turn potentiometer ”max” (R28) clockwise until LED (V24 green) goes out. Then turn potentiometer ”max” (R28) slightly counter-clockwise until LED (V24) lights up again. Turn potentiometer ”max” (R28) slightly counter-clockwise until LED (V23) goes out and LED (V24 green) lights up. If Then LED indication: (refer to figures O1 and O2) LEDs are not illuminated LED (V23 yellow) is illuminated 15.6 Setting of the sensitivity . .. . Set selector switch to position II (REMOTE) at local controls (figure P, page 17). Set command signal E1 according to sticker on cover plate (see figure O2). Set dead band with potentiometer ∆E (R35) so that part-turn actuator does not readjust after a single control operation: - turning clockwise results in reduced sensitivity (dead band increased) When setting E the following must be observed by all means: If the number of starts is too high, this will lead to unnecessary wear at the valve and actuator. Therefore the maximum possible sensitivity (dead band) acceptable for the process must be set. To prevent an exceeding of the max. permissible number of starts (1 500 c/h) in extreme cases, a time delay between 0,5 s (left stop) and 10s (right stop) may be set with potentiometer ”t-off” (R88). Figure O2: Cover plate positioner R28 R25 R31 R35 R28 R25 R31 R35 Figure O1: Positioner board S3 ENABLE FREIGABE 1 Meas. points M1 E1 M2 M3 E2 M4 { { S2 V24 V23 V35 V37 STELLZEIT OPERATING TIME - + READY BEREIT E sens 0 max J R88 E1 E2 4-20mA 4-20mA X7 auma variomatic X8 Sticker with signal details (example: E1 = 4-20 mA, E2 = 4-20 mA) 16 X9 t-off E1/E2 <4 mA t-off V24 V23 V35 V37 R88 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions 16. Setting of the operating time (output speed) 16.1 Setting of the operating time via internal command signal Figure P: Actuator ASO/AS(R) with controls AUMA VARIOMATIC 8.1 AUMA VARIOMATIC Switch compartment cover Local controls .. . Loosen 4 screws (8.1) and remove cover (figure P). Set required operating time at potentiometer OPERATING TIME (figure Q). Short operating time: turn counter-clockwise. Long operating time: turn clockwise. Speed ranges see technical data sheet Replace cover and fasten 4 bolts (8.1) evenly crosswise. Figure Q: VARIOMATIC Standard Diagnosis LED (green): Potentiometer Illuminated when for setting of OPERATING TIME ready Diagnosis LED (red): Motor protection tripped Diagnosis LED (green): Enable REMOTE (option) always installed, illuminated during normal operation DIP switch S1 for programming Logic board Cover plate standard Diagnosis LEDs for active REMOTE control commands: run command STOP (red) run command OPEN (green) run command CLOSE (yellow) 17 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions 16.2 Setting of the operating time via the speed-interface board (option) (refer to order-related wiring diagram CI V... AI...) With the speed-interface board the operating time (speed) can also be pre-determined through an external signal, either analogue (command signal E3 = 0 - 20 mA or 4 - 20 mA) or binary (command signal n1, n2). .. The simultaneous use of the analogue and the digital nominal operating time is not possible! Loosen 4 screws (8.1) and remove cover (figure P, page 17). The speed-interface board (figure R) is situated directly above the logic board. Depending on version (with or without positioner), remove the boards above (cover plate, positioner board and additional board). Figure R: Speed-interface board Potentiometer R9: for setting of the binary nominal operating time n1 Range switch S1-2.2 (component A2.2) for analogue nominal operating time E3 Dot visible: 4 - 20 mA Potentiometer R10: for setting of the binary nominal operating time n2 LED’s: V4: nominal operating time n1 V6: nominal operating time n2 Dot not visible: 0 - 20 mA Range switch S2-2.2 (component A2.2) for analogue nominal operating time E3 DIP switch S1 for programming ON Dot visible: positioner Logic board Dot not visible: interface board Speed-interface board Measuring point MP2 Measuring point MP1 Potentiometer R16: adjustment analogue nominal operating time E3 Setting on logic board: Setting on speed-interface board: 18 . . Check on the logic board whether the DIP switch S1, pos. 7 (nominal output speed) is in position ”OFF”. If necessary, correct the switch position (see clause 14, pages 12/13). Set the potentiometer ”OPERATING TIME” (figure Q, page 17) on the logic board to the fully clockwise position (max. speed) to make use of the entire range of operating time. If the minimal operating time (max. speed) has to be limited to a higher value as the operating time possible by the actuator (see technical data sheet), set potentiometer to this value (e.g. to avoid water hammer). When using the option positioner (see clause 15, page 14) set the selector switch S2-2.2 (figure R) on the speed-interface board to position ‘positioner’. For all other versions the switch S2-2.2 has to be set to position ‘speed-interface board’. Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions Analogue nominal operating time E3: The analogue operating time range E3 (refer to wiring diagram CI V... AI...) can be set with the switch S1-2.2 (figure R) to either 0 - 20 mA or 4 - 20 mA. After a change, adjustment of the max. value (20 mA) is necessary. The adjustment is performed as follows: Connection of 24 V DC +/- 10 % to the analogue input of the speed-interface board (see wiring diagram CI V... AI...) max. current input ≤30mA Connection of 20 mA at nominal operating time E3 of the speed-interface board (see wiring diagram CI V... AI...) Measure voltage between MP1 and MP2 (figure R). Adjust the voltage to 10,00 V +/- 0,01 V by using the potentiometer R16 (figure R). . . .. Binary nominal operating time n1, n2 Two inputs are available for the setting of the operating time via binary signals. The adjustment of the two operating times is performed as follows: Control of the binary nominal operating time n1 by connection of 24 V DC to the binary input n1 of the speed-interface board (see wiring diagram CI V... AI...) A visual check of the connected signal with LED V4 is possible (figure R). The setting of the operating time is done via potentiometer R9 (figure R), clockwise rotation equals higher speed = shorter operating time. . . . . Control of the binary nominal operating time n2 by connection of 24 V DC to the binary input n2 of the speed-interface board (see wiring diagram CI V... AI...) A visual check of the connected signal with LED V6 is possible (figure R). The setting of the operating time is done via potentiometer R10 (figure R), clockwise rotation equals higher speed = shorter operating time. . . . . . During simultaneous control of n1 and n2, the shortest operating time has priority. Without control of n1 and n2, the max. operating time is available. When operated via local controls, the actuator always runs with max. speed (shortest operating time). Control of the set speed (operating time) is only possible via REMOTE commands. 16.3 Further functions of the speed-interface board in conjunction with the positioner (option) Remote change-over of the nominal operating time This function is only possible in combination with the analogue or binary nominal operating time (selector switch S2-2.2 in position ‘positioner’, figure R). From Remote, the nominal operating time can be changed over with a + 24 V DC signal between the operating time determined by the positioner and the operating time set by the customer via the speed-interface board. 19 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC for connection at AUMA plug/socket connector XK see wiring diagram CI V... AI... . Operation instructions Voltage Function 0 V DC internal nominal operating time by positioner (operating time dependent on error variable) 24 V DC external nominal operating time by speed interface board 3) (analogue or binary nominal operating time) Change-over AUTO/REMOTE The positioner can be completely switched off from Remote with a + 24 V DC signal. This permits the use of the binary control signals (OPEN, STOP, CLOSE) in conjunction with the analogue or digital nominal operating time. Voltage for connection at AUMA plug/socket connector XK see wiring diagram CI V... AI... 0 V DC 24 V DC Function Run commands by positioner1) (operating time dependent on error variable) Run commands by binary REMOTE commands 2) 3) (OPEN, STOP, CLOSE and analogue or binary nominal operating time) 1) The binary control signals must be externally deactivated (customer) as long as the positioner is active. 2) This function is only possible in combination with the analogue or binary nominal operating time (selector switch S2-2.2 in position ‘positioner’, figure R, page 18). 3) If no external signal is present, the actuator runs with its slowest speed (or longest operating time). 17. Signal board (option) Signal boards with the option ”Running indication” (blinker transmitter) offer the possibility to switch over from impulse to continuous signal by way of a sliding switch (see wiring diagram). The signal board (figure S) is accessible after taking off the green cover plate (figure L, page 12, or figure N, page 14). Figure S: Signal board Switch for running indication (blinker transmitter) ON OFF 20 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC Operation instructions 18. Fuses Fuses (figure T) are accessible after removing the local controls (figure P, page 17) Figure T: Fuses Fuses: (figure T) F1 F2 20 x 5 20 x 5 F2 F1 10 A T; 250 V 1 A T; 250 V Observe recommended fuses in mains: See ”Technical data”, page 4. Disconnect actuator from the mains before changing the fuses. 19. Maintenance After commissioning, check for damages on paint of part-turn actuator. Do a thorough touch-up to prevent corrosion. Original paint in small quantities can be supplied by AUMA. AUMA part-turn actuators require very little maintenance. Precondition for reliable service is correct commissioning. Seals made of elastomers are subject to aging and must therefore regularly be checked and, if necessary, exchanged. It is also very important that the O-rings at the covers are placed correctly and cable glands fastened firmly to prevent ingress of dirt or water. . . We recommend: If operated seldom, perform a test run about every 6 months. This ensures that the actuator is always ready to operate. Approximately six months after commissioning and then every year check bolts between part-turn actuator and valve/gearbox for tightness. If required, re-tighten applying the torques given in table 1, page 6. The gear housing is filled with lubricant in the factory. This filling lasts for several years of service. The described actuators are high-precision electro mechanical devices. Defective actuators can therefore only be repaired in the factory or in an authorised workshop. 21 Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC 20. Declaration of Conformity and Declaration of Incorporation 22 Operation instructions Operation instructions Part-turn actuators ASO 3 - ASO 6 / AS 6 - AS 50 / ASR 6 - ASR 50 AUMA VARIOMATIC 23 Multi-turn actuators SA 07.1 – SA 16.1 / SA 25.1 – SA 48.1 Torques from 10 to 32 000 Nm Speeds from 4 to 180 min-1 Controls AUMA MATIC with multi-turn actuators SA/ SAR Torques from 10 to 1 000 Nm Speeds from 4 to 180 min-1 Part-turn actuators SG 05.1 – SG 12.1 Torques from 100 to 1 200 Nm Speeds for 90° from 4 to 180 s Linear thrust units LE with multi-turn actuators SA Thrusts from 4 kN to 217 kN Strokes up to 400 mm Running speeds from 20 to 360 mm/min Part-turn actuators AS 6 – AS 50 Torques from 25 to 500 Nm Speeds for 90° from 4 to 90 s Bevel gearboxes GK 10.2 – GK 40.2 Torques up to 16 000 Nm Worm gearboxes GS 40.3 – GS 125.3 GS 160 – GS 500 Torques up to 360 000 Nm Lever gearboxes GF 50.3 – GF 125.3 GF 160 – GF 250 Torques up to 32 000 Nm WERNER RIESTER GmbH & Co. KG Armaturen- und Maschinenantriebe P.O.Box 1362 D - 79373 Müllheim Tel 07631/809-0 Fax 07631/13218 e-mail riester@auma.com http://www.auma.com Spur gearboxes GST 10.1 – GST 40.1 Torques up to 16 000 Nm WERNER RIESTER GmbH & Co. KG Armaturen- und Maschinenantriebe P.O. Box 1151 D - 73747 Ostfildern Tel 0711/34803-0 Fax 0711/34803-34 e-mail riester@wof.auma.com Y000.237/003/en/1.00 Insert to operation instructions ASO 3 - ASO 6/ AS 6 - AS 50/ ASR 6 - ASR 50 Issue 1.00 AUMA VARIOMATIC Bus The following changes in the operation instructions must be observed: Page 13, subclause 14.1, programming with bus board installed (MODBUS, PROFIBUS and INTERBUS-S): Table 3 Programming (ON = switch pressed) (not applicable for bus systems) DIP switch S1 (on logic board) Self-retaining REMOTE ON OFF Push-to-run operation REMOTE ON OFF Self-retaining LOCAL ON OFF Push-to-run operation LOCAL Type of seating 1234 5 1234 5 for end position CLOSED for end position OPEN set DIP switch on logic board always to torque seating, refer to operation instructions, subclause 6.2, page 6 Limit seating ON OFF Torque seating ON OFF 1234 5 external (setting via bus possible) ON OFF Nominal output speed 1) 1) 1234 5 1234 5 internal (fixed setting via potentiometer ‘operating time’) ON OFF 1234 5 1234 5 Profibus FMS and MODBUS Set switch position S1 pos. 5 to ”ON” (no nominal output speed possbible via bus) Profibus DP and INTERBUS-S Set switch position S1 pos. 5 to ”OFF” Figure: Logic board for AUMA VARIOMATIC Bus Potentiometer operating time S1 The setting for the type of seating - limit or torque seating - must be identical on the PROFIBUS DP board (switch S4, ð already set in the factory, refer to operation instructions AUMA VARIOMATIC PROFIBUS DP) and on the logic board (DIP switch S1/ DIP 3). R Issue 1.00 Y000.584/003/en