Surge Protection Made Simple ™
IEC Applications
High Performance
Lightning & Surge Protection
Products for All IEC
Applications
• Vibration and shock resistant according to
EN 60068-2 standards.
• easyID™ Visual indication and optional remote
contact signaling make status monitoring simple.
• High surge discharge capacity due to heavy-duty zinc
oxide varistor and spark-gap technology.
• Wide range of IEC Class l and Class ll SPD
covering all the major markets around the world.
• Modular DIN-rail design with color-coding and
rejection feature makes it easy to identify, install and
maintain.
The Need for Surge Protection
Today’s world is full of electronic products and devices
that are susceptible to damage from overvoltage
surges.
Whether the cause is static discharge or lightning,
overvoltage surges can quickly destroy consumer
electronics or sophisticated electronic packages used
in industrial and commercial applications.
Surge protection products from Bussmann help
assure power quality that’s free from damaging surges
and overvoltage conditions.
Safe and Simple
・IP20 Finger-safe construction.
・Suppressor rejection feature make it easy to know the
suppressor system is installed and properly operating
to protect your IEC system investment.
・Simple selection of system voltage and remote
contact signaling option.
・Five year limited warranty.*
Complete Line of Surge Protection Solutions
Bussmann offers surge protection products for
PV, wind power, telecom and UL, applications.
Base & Module Number System
BSP X X
XXX XXX
X
BSP = Product Series
Technology Type
M = MOV
H = Hybrid
S = Spark-Gap
G = GDT
Poles
1 = 1-pole
2 = 2-pole
3 = 3-pole
4 = 4-pole
System Voltage
230 = 230Vac
320 - 320Vac - Specific to India
400 = 400Vac - Specific to China
440 = 440Vac
System Type
IT = IT system
TN = TN system
TNC = TNC system
TNS = TNS system
TT = TT system
Optional Remote Contact Signaling
R = Optional contact signaling
Blank = No remote switch option
Replacement Module Number System
BP
X
XXX
BP = Product Series
Technology
M = MOV
S = Spark-Gap
XXX
H = Hybrid
G = GDT
MCOV
50NPE*, 100NPE*, 255, 275, 320, 385, 440
*NPE = Neutral to Earth
System Type
IEC = All IEC System Types
PV
Wind
Telecom
UL
IEC
Ordering Information
Power
System Poles
TN
2
Volts
230
Bussmann
Part Number
BSPS2255TN(R)
Lightning Arrestors - IEC Class l
Description
230V Combined lightning current and surge arrestor for 2-pole TN systems (remote)
TNC
TNS
TT
3
4
2
230
230
230
BSPS3255TNC(R)
BSPS4255TNS(R)
BSPS2255TT(R)
TT
4
230
BSPS4255TT(R)
TN
TN
TN
TN
TN
TN
TNC
TNS
TT
1
1
1
1
1
2
3
4
2
230
230
320
400
440
230
230
230
230
BSPM1275TN(R)
BSPG1255NPE(R)
BSPM1320TN(R)
BSPM1385TN(R)
BSPM1440TN(R)
BSPM2275TN(R)
BSPM3275TNC(R)
BSPM4275TNS(R)
BSPH2275TT(R)
230V Combined lightning current and surge arrestor for 3-pole TN-C systems (remote)
230V Combined lightning current and surge arrestor for 4-pole TN-S systems (remote)
230V Combined lightning current and surge arrestor for
single-pole 1+1 TT and TN systems (remote)
230/400V Combined lightning current and surge arrestor for
3+1 TT and TN-S systems (remote)
Surge Arrestors - IEC Class ll
230V Surge arrestor for single-pole TN systems (remote)
240V 1-Pole GDT DIN rail SPD for N-PE (remote)
320V Surge arrestor for single-pole TN systems (remote) (India Market 230/400V)
400V Surge arrestor for single-pole TN systems (remote) (Chinese Market 230/400)
440V Surge arrestor for single-pole TNC systems (400/690V) (remote)
230V Surge arrestor for 2-pole TN systems (remote)
230/400V Surge arrestor for 3-pole TNC systems (remote)
230/400V Surge arrestor for 3-pole TNS systems (remote)
230V Surge arrestor for 2-pole phase TT systems (remote)
TT
4
230
BSPH4275TT(R)
230/400V Surge arrestor for 3+1 TT and TN-S systems (remote)
* See Bussmann SPD Limited Warranty Statement (3A1502) for details at www.bussmannasia.com/surge.
For more information visit our website at www.bussmannasia.com
Modules
BPS255IEC,
BPS50NPE
BPS255IEC
BPS255IEC
BPS255IEC,
BPS50NPE
BPS255IEC,
BPS100NPE
BPM275IEC
BPG255NPE
BPM320IEC
BPM385IEC
BPM440IEC
BPM275IEC
BPM275IEC
BPM275IEC
BPM275IEC,
BPSNPE
BPM275IEC,
BPSNPE
Surge Protection Made Simple ™ for IEC Applications
IEC Class I Combined Lightning, Current and Surge Arresters for
230 Volt, 2-Pole TN & TT Systems
Description
The Bussmann ® IEC Class I 230 Volt, two-pole, modular combined
lightning, current and surge arresters feature local, easy ID™ visual indication
and optional remote contact signaling. The unique module locking system
fixes the protection module to the base part. Modules can be easily replaced
without tools by simply depressing the release buttons. Integrated mechanical
coding between the base and protection module ensures against installing an
incorrect replacement module.
BSPS2255TN(R)
BSPS2255TT(R)
230 Volt models are offered with MCOV rating of 255 volts.
TN System Arresters
The features of these two-pole devices are for use as a modular combined
lightning and current arrester and surge arrester for use in single TN- systems
(“2-0” circuit).
TT System Arrester
Provides a current arresting means for use in single TT- systems
(“1-1” circuit).
Visual Status Indication
Remote Signal
Contact Available
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating
changeover contact for use as a break or make contact, according to circuit
concept.
Creepage Discharge Spark Gap
Dimensions - mm
Circuit Diagrams
Shown with optional
remote contact signaling
Spark Gap Trigger
BSPS2255TNR
BSPS2255TTR
Shown with optional
remote contact signaling
Shown with optional
remote contact signaling
For more information visit our website at www.bussmannasia.com
Ordering Information
System Voltage/Poles
Max. Continuous operating AC voltage (MCOV) [UC]
Catalog Numbers:
Without Remote Signaling
With Remote Signaling
Replacement Modules:
MOV technology
Spark Gap technology
230V/2
255V
BSPS2255TN
BSPS2255TNR
(2X) BPS255IEC
--
230V/2
255V
BSPS2255TT
BSPS2255TTR
(1X) BPS255IEC
(1X) BPS50NPEIEC*
Specific energy [L+N-PE] [W/R]
Lightning impulse current (10/350 µs) [L, N-PE] [Iimp]
625.00 kJ/ohms
25kA
Specific energy [L,N-PE] [W/R]
156.25 kJ/ohms
Voltage protection level [L-PE]/[N-PE] [UP]
Voltage protection level [L-N]/[N-PE] [UP]
Follow current extinguishing capability AC [Ifi]
Follow current extinguishing capability [L-N]/[N-PE] [Ifi]
Temporary overvoltage (TOV) [N-PE] [UT]
SPD according to EN 61643-11/... IEC 61643-1
Energy-coordinated protection effect with regard to the terminal equipment
Energy-coordinated protection effect with regard to the terminal equipment (<
_ 5m)
Nominal AC voltage [UN]
Lightning impulse current (10/350 µs) [L+N-PE] [Itotal]
Nominal discharge current (8/20 µs) [In]
Follow current limitation/Selectivity
Response time [tA]
Max. Backup fuse (L) up to IK <
_ 50kA rms
Max. Backup fuse (L) for IK > 50kA rms
Max. Backup fuse (L-L´)
Temporary overvoltage (TOV) [L-N] [UT]
TOV characteristics
Operating temperature range (parallel connection) [TUP]
Operating temperature range (series connection) [TUS]
Operating temperature range [parallel]/[continuity] [TU]
Operating state/fault indication
Number of ports
<
_ 1.5 kV/<
_ 1.5 kV
-50kA rms
---
-25/50kA Is [L-N]/[N-PE]
156.25kJ/ohms/
625.00 kJ/ohms
-<
_ 1.5kV/<
_ 1.5kV
-50kA rms/100A rms
1200V/200 ms
Specifications
Cross-sectional area (L, L´, N, N´, PE,
Cross-sectional area (L, N, PE) [max.]
Cross-sectional area (L´, N´,
For mounting on
Enclosure material
Location category
Degree of protection
Capacity
Standards Information
Product Warranty
Type 1/Class I
Type 1 + Type 2
Type 1 + Type 2 + Type 3
230V
50kA
25/50kA
no tripping of a 20A gL/gG fuse up to 50kA rms (prosp.)
<
_ 100 ns
315A gL/gG
200A gL/gG
125A gL/gG
440V/5 sec.
withstand
-40°C to +80°C
-40°C to +60°C
-40°C to +80°C/-40°C to +60°C
green (good)/red (replace)
1
) [min.]
10mm2 solid/flexible
50mm2/1AWG stranded-35mm2/2AWG flexible
) [max.]
35mm2/2AWG stranded-25mm2/4AWG flexible
35mm DIN Rail per EN 60715
Thermoplastic, UL 94V0
Indoor
IP20
4 mods., DIN 43880
KEMA
Five Years**
Remote Contact Signaling
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals
Ordering Information
Recommended Bussmann NH DIN Size Back Up Fuses
Size NH Fuse Part Number
Size NH Fuse Part Number
00
125NHG00B (max L-L)
02
125NHG02B (max L-L)
0
125NHG0B (max L-L)
02
200NHG02B (max L Ik >50kA)
01
125NHG01B (max L-L)
2
315NHG2B (max L <
_50kA)
1
200NHG1B (max L Ik >50kA)
03
315NHG03B (max L <
_ 50kA)
Changeover Contact
250V/0.1A
250V/0.1A; 125V/0.2A; 75V/0.5A
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Order from Catalog Numbers Above
* N-PE Surge arrester for location between neutral conductor and protective conductor
in TT systems.
** See Bussmann SPD Limited Warranty Statement (3A1502) for details at
www.cooperbussmann.com/surge.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
For more information visit our website at www.bussmannasia.com
Surge Protection Made Simple ™ for IEC Applications
IEC Class I Combined Lightning, Current and Surge Arrester for
230/400 Volt, 3-Pole TNC Systems
Description
The Bussmann® IEC Class I 230 Volt, three-pole, modular combined
lightning, current and surge arresters feature local, easy ID™ visual indication
and optional remote contact signaling. The unique module locking system
fixes the protection module to the base part. Modules can be easily replaced
without tools by simply depressing the release buttons. Integrated mechanical
coding between the base and protection module ensures against installing an
incorrect replacement module.
BSPS3255TNC(R)
230 Volt models are offered with a MCOV rating of 255 volts.
TNC System Arrester
The features of these three-pole devices are for use in TN-C 230/400 Volt
systems (“3-0” circuit) against surges.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating
changeover contact for use as a break or make contact, according to circuit
concept.
Remote Signal
Contact Available
Visual Status Indication
Creepage Discharge Spark Gap
Circuit Diagrams
Dimensions - mm
Spark Gap Trigger
Shown with optional
remote contact signaling
BSPS3255TNC(R)
Shown with optional
remote contact signaling
For more information visit our website at www.bussmannasia.com
Ordering Information
System Voltage/Poles
Max. Continuous operating AC voltage (MCOV) [UC]
Catalog Numbers:
Without Remote Signaling
With Remote Signaling
Replacement Module
MOV technology
230/400V/3
255V
BSPS3255TNC
BSPS3255TNCR
BPS255IEC
Specifications
SPD according to EN 61643-11/... IEC 61643-1
Energy-coordinated protection effect with regard to the terminal equipment
Energy-coordinated protection effect with regard to the terminal equipment (<
_ 5m)
Nominal AC voltage [UN]
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] [Itotal]
Specific energy [L1+L2+L3-PEN] [W/R]
Lightning impulse current (10/350 µs) [L-PEN] [Iimp]
Specific energy [L-PEN] [W/R]
Nominal discharge current (8/20 µs) [In]
Voltage protection level [UP]
Follow current extinguishing capability AC [Ifi]
Follow current limitation/Selectivity
Response time [tA]
Max. Backup fuse (L) up to IK = 50kA rms
Max. Backup fuse (L) for IK > 50kA rms
Max. Backup fuse (L-L´)
Temporary overvoltage (TOV) [UT]
TOV characteristics
Operating temperature range [parallel]/[continuity] [TU]
Operating state/fault indication
Number of ports
Type 1/Class I
Type 1 + Type 2
Type 1 + Type 2 + Type 3
230/400V
75kA
1.40 MJ/ohms
25kA
156.25kJ/ohms
25/75kA
<
_ 1.5kV
50kA rms
no tripping of a 20A gL/gG fuse up to 50kA rms (prosp.)
<
_ 100 ns
315A gL/gG
200A gL/gG
125A gL/gG
440V/5 sec.
withstand
-40°C to +80°C/-40°C to +60°C
green (good)/red (replace)
1
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, PEN,
Cross-sectional area (L1, L2, L3, PEN) [max.]
10mm2 solid/flexible
50mm2/1AWG stranded-35mm2/2AWG flexible
Cross-sectional area (L1´, L2´, L3´,
Mounting
Enclosure material
Location category
Degree of protection
Capacity
Standards Information
Product Warranty
) [min.]
) [max.]
35mm2/2AWG stranded-25mm2/4AWG flexible
35mm DIN rail per to EN 60715
Thermoplastic, UL 94V0
Indoor
IP20
6 mods., DIN 43880
KEMA
Five Years*
Remote Contact Signaling
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals
Ordering Information
Changeover Contact
250V/0.1A
250V/0.1A; 125V/0.2A; 75V/0.5A
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Order from Catalog Numbers Above
* See Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Size
00
0
01
1
Recommended Bussmann NH DIN Size Back Up Fuses
NH Fuse Part Number
Size NH Fuse Part Number
125NHG00B (max L-L)
02
125NHG02B (max L-L)
125NHG0B (max L-L)
02
200NHG02B (max L Ik >50kA)
125NHG01B (max L-L)
2
315NHG2B (max L <
_50kA)
200NHG1B (max L Ik >50kA)
03
315NHG03B (max L <
_ 50kA)
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
For more information visit our website at www.bussmannasia.com
Surge Protection Made Simple ™ for IEC Applications
IEC Class I Combined Lightning, Current and Surge Arresters for
230/400 Volt, 4-Pole TNS & TT Systems
Description
The Bussmann ® IEC Class I 230 volt, four-pole, modular combined
lightning, current and surge arresters feature local, easy ID™ visual indication
and optional remote contact signaling. The unique module locking system
fixes the protection module to the base part. Modules can be easily replaced
without tools by simply depressing the release buttons. Integrated mechanical
coding between the base and protection module ensures against installing an
incorrect replacement module.
BSPS4255TNS(R)
BSPS4255TT(R)
230 Volt models are offered with MCOV ratings of 255 volts.
TNS System Arresters
The features of these four-pole devices are for use in TNS 230/400 volt
systems (“4-0” circuit) against surges.
TT System Arrester
Provides a current arresting means between neutral conductor and protective
conductor in TT 230/400 volt systems (“3+1” circuit) against surges.
Visual Status Indication
Remote Signaling Contact
Remote Signal
Contact Available
The three-pole terminal remote signaling contact versions have a floating
changeover contact for use as a break or make contact, according to circuit
concept.
Creepage Discharge Spark Gap
Dimensions - mm
Circuit Diagrams
Spark Gap Trigger
BSPS4255TNS(R)
Shown with
optional remote
contact signaling
Shown with optional remote contact signaling
BSPS4255TT(R)
Shown with
optional remote
contact signaling
For more information visit our website at www.bussmannasia.com
Ordering Information
System Voltage/Poles
Max. Continuous operating AC voltage (MCOV) [UC]
Catalog Numbers:
Without Remote Signaling
With Remote Signaling
Replacement Modules:
MOV technology
Spark Gap technology
230/400V/4
255V
BSPS4255TNS
BSPS4255TNSR
BPS255IEC
--
230/400V/4
255V
BSPS4255TT
BSPS4255TTR
BPS255IEC
BPS100NPEIEC*
Specifications
SPD according to EN 61643-11/... IEC 61643-1
Energy-coordinated protection effect with regard to the terminal equipment
Energy-coordinated protection effect with regard to the terminal equipment (<
_ 5m)
Nominal AC voltage [UN]
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] [Itotal]
Specific energy [L1+L2+L3+N-PE] [W/R]
Lightning impulse current (10/350 µs) [L, N-PE] [Iimp]
TNS system specific energy [L,N-PE] [W/R]
TT system specific energy [L-N]/[N-PE] [W/R]
Nominal discharge current (8/20 µs) [In]
Voltage protection level [L-PE]/[N-PE] [UP]
TNS system follow current extinguishing capability AC [Ifi]
TT system follow current extinguishing capability AC [Ifi]
Follow current limitation/Selectivity
Response time [tA]
Max. Backup fuse (L) up to IK <
_ 50kA rms
Max. Backup fuse (L) for IK > 50kA rms
Max. Backup fuse (L-L´)
Temporary overvoltage (TOV) [L-N] [UT]
Temporary overvoltage (TOV) [N-PE] [UT]
TOV characteristics
Operating temperature range [parallel]/[continuity] [TU]
Operating state/fault indication
Number of ports
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, N, N´, PE,
Cross-sectional area (L1, L2, L3, N, PE) [max.]
Cross-sectional area (L1´, L2´, L3´, N´,
Mounting
Enclosure material
Location category
Degree of protection
Capacity
Agency Information
Product Warranty
Type 1/Class I
Type 1 + Type 2
Type 1 + Type 2 + Type 3
230/400V
100kA
2.50MJ/ohms
25kA
156.25kJ/ohms
156.25kJ/ohms/2.50kJ/ohms
25/100kA
<
_ 1.5kV/<
_ 1.5kV
50kA rms
50kA rms/100A rms
No tripping of a 20A gL/gG fuse up to 50kA rms (prosp.)
<
_ 100 ns
315A gL/gG
200A gL/gG
125A gL/gG
440V/5 sec.
1200V/200mS
Withstand
-40°C to +80°C/-40°C to +60°C
green (good)/red (replace)
1
) [min.]
) [max.]
10mm2 solid/flexible
50mm2/1AWG stranded-35mm2/2AWG flexible
35mm2/2AWG stranded-25mm2/4AWG flexible
35mm DIN Rail per EN 60715
Thermoplastic, UL 94V0
Indoor
IP20
8 mods., DIN 43880
KEMA
Five Years**
Remote Contact Signaling
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals
Ordering Information
Changeover Contact
250V/0.1A
250V/0.1A; 125V/0.2A; 75V/0.5A
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Order from Catalog Numbers Above
* N-PE Surge arrester for location between neutral conductor and protective conductor in TT systems.
** See Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Size
00
0
01
1
Recommended Bussmann NH DIN Size Back Up Fuses
NH Fuse Part Number
Size NH Fuse Part Number
125NHG00B (max L-L)
02
125NHG02B (max L-L)
125NHG0B (max L-L)
02
200NHG02B (max L Ik >50kA)
125NHG01B (max L-L)
2
315NHG2B (max L <
_50kA)
200NHG1B (max L Ik >50kA)
03
315NHG03B (max L <
_ 50kA)
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
For more information visit our website at www.bussmannasia.com
Surge Protection Made Simple ™ for IEC Applications
IEC Class II Surge Arresters for 230-600 Volt, 1-Pole TN & TT Systems
Description
The Bussmann IEC Class II 275, 320, 385, 440 and 600 volt, onepole, modular surge arresters feature local, easy ID™ visual indication and
optional remote contact signaling. The unique module locking system fixes the
protection module to the base part. Modules can be easily replaced without
tools by simply depressing the release buttons. Integrated mechanical coding
between the base and protection module ensures against installing an
incorrect replacement module.
BSPM1275TN(R)
BSPM1320TN(R)
BSPM1385TN(R)
BSPM1440TN(R)
BSPM1600TN(R)
BSPG1255NPE(R)
Class II single-pole surge arrester models are offered with MCOV ratings of
255, 275, 320, 385, 440 and 600 volts.
TN System Arresters
The features of these single-pole devices are for use as a single device or in
combination with other devices.
TT System Arrester
Provides a current arresting means between neutral conductor and protective
conductor in TT systems, this device helps ensure fulfilling the requirements
for protection of personnel and equipment in “3+1” and “1+1” circuits.
Visual Status Indication
Remote Signal
Contact Available
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating
changeover contact for use as a break or make contact, according to circuit
concept.
Module Circuit Diagrams - Shown with optional remote contact signaling
Dimensions - mm
MOV
Thermal Disconnector
Gas Discharge Tube (single)
Shown with optional remote contact signaling
BSPM1275TN(R)
BSPM1320TN(R)
BSPM1385TN(R)
BSPM1440TN(R)
BSPM1600TN(R)
BSPG1255NPE(R)
For more information visit our website at www.bussmannasia.com
Ordering Information
System Voltage/Poles
230V/1
Max. Continuous operating AC voltage (MCOV) [UC]
275V
Catalog Numbers:
Without Remote Signaling BSPM1275TN
(Base + Modules)
With Remote Signaling
BSPM1275TNR
Replacement Modules
BPM275IEC
230V/1
230V/1
400V/1
600V/1
230V/1*
320V
385V
440V
600V
255V
BSPM1320TN BSPM1385TN BSPM1440TN BSPM1600TN BSPG1255NPE
BSPM1320TNR BSPM1385TNR BSPM1440TNR BSPM1600TNR BSPG1255NPER
BPM320IEC
BPM385IEC
BPM440IEC
BPM600IEC
BPG255NPE
Specifications
Line system type
Max. Continuous operating DC voltage [UC]
Voltage protection level [UP]
Voltage protection level at 5kA [UP]
Max. mains-side overcurrent protection
Short-circuit withstand capability for max.
mains-side overcurrent protection
Temporary overvoltage (TOV) [UT]
Response time [tA]
Follow current extinguishing capability [Ifi]
Lightning impulse current (10/350 µs) [Iimp]
Nominal discharge current (8/20 µs) [In]
Max. Discharge current (8/20 µs) [Imax]
Standards Information
Capacity
SPD according to EN 61643-11
SPD according to IEC 61643-1
TOV characteristics
Operating temperature range [TU]
Operating state/fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
Mounting
Enclosure material
Location category
Degree of protection
Product Warranty
TN / TT
350V
<
_ 1.25kV
<
_ 1kV
125A gL/gG
TN / TT
420V
<
_ 1.5kV
<
_ 1.2kV
125A gL/gG
TN / TT
500V
<
_ 1.75kV
<
_ 1.35kV
125A gL/gG
TN
585V
<
_ 2kV
<
_ 1.7kV
125A gL/gG
TN
600V
<
_ 2.5kV
<
_ 2kV
100A gL-gG
TT
-<
_ 1.5kV
---
50kArms
25kArms
25kArms
25kArms
25kA rms
--
335V/5 sec.
<
_ 25 ns
--20kA
40kA
KEMA
335V/5 sec.
<
_ 25 ns
--20kA
40kA
KEMA, CSA
600V/5 sec.
<
_ 25 ns
--15kA
30kA
KEMA
1200V/200 ms
<
_ 100 ns
100Arms
12kA
20kA
40kA
KEMA
385V/5 sec.
580V/5 sec.
<
_ 25 ns
<
_ 25 ns
----20kA
20kA
40kA
40kA
KEMA, CSA
KEMA, CSA
1 mod., DIN 43880
Type 2
Class II
Withstand
-40°C to +80°C
Green (good) / Red (replace)
1
1.5mm2/14AWG solid/flexible
35mm2/2AWG stranded-25mm2/4AWG flexible
35mm DIN Rail per EN 60715
Thermoplastic, UL 94V0
Indoor
IP20
Five Years**
Remote Contact Signaling
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Conductor Ratings and Cross-Sectional Area for
Remote Contact Signal Terminals
Ordering Information
Changeover Contact
250V/0.1A
250V/0.1A; 125V/0.2A; 75V/0.5A
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Order from Catalog Numbers Above
* N-PE Surge arrester for location between neutral conductor and protective conductor in TT systems.
** See Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Bussmann Back Up Fuses
DIN
TT / TN System NH Fuse Part Numbers
Fuse Size
275, 320, 385, 440V
600V
00
125NHG00B
100NHG00B-690
0
125NHG0B
100NHG0B-690
01
125NHG01B
-1
-100NHG1B-690
02
125NHG02B
-2
-100NHG2B-690
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
For more information visit our website at www.bussmannasia.com
Surge Protection Made Simple ™ for IEC Applications
IEC Class II Surge Arresters for 230 Volt, 2-Pole TN & TT Systems
Description
The Bussmann ® IEC Class II 230 volt, two-pole, modular surge
arresters feature local, easy ID™ visual indication and optional remote contact
signaling. The unique module locking system fixes the protection module to
the base part. Modules can be easily replaced without tools by simply
depressing the release buttons. Integrated mechanical coding between the
base and protection module ensures against installing an incorrect
replacement module.
BSPM2275TN(R)
BSPH2275TT(R)
230 Volt models are offered with MCOV ratings of 255 and 275 volts.
TN System Arresters
The features of these single-pole devices are for use in single-phase 230 volt
TN systems (“2-0” circuit).
TT System Arrester
The features of these single-pole devices are for use in single-phase 230 volt
TT and TNS systems (“1-1” circuit).
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating
changeover contact for use as a break or make contact, according to circuit
concept.
Visual Status Indication
Remote Signal
Contact Available
MOV
Thermal Disconnector
Circuit Diagrams
Dimensions - mm
Gas Discharge Tube (single)
BSPM2275TN(R)
BSPH2275TT(R)
Shown with optional remote
contact signaling
Shown with optional remote
contact signaling
Shown with optional remote contact signaling
For more information visit our website at www.bussmannasia.com
Ordering Information
System Voltage/Poles
Max. continuous operating AC voltage (MCOV) [UC]
Max. Continuous operating AC voltage (MCOV) [L-N] [UC]
Max. Continuous operating AC voltage (MCOV) [N-PE] [UC]
Catalog Numbers:
Without Remote Signaling
With Remote Signaling
Replacement Modules:
MOV Technology
Spark Gap technology
230V/2
275V
--BSPM2275TN
BSPM2275TNR
BPM275IEC
--
230V/2
-275V
255V
BSPH2275TT
BSPH2275TTR
BPM275IEC
BPSNPEIEC*
-<
_ 1.25kV
<
_ 1kV
----<
_ 25 ns
--335V/5 sec.
---
12kA
--<
_ 1.25kV
<
_ 1kV
<
_ 1.5kV
100A rms
-<
_ 25 ns
<
_ 100 ns
-335V/5 sec.
1200V/200 ms
Specifications
Lightning impulse current (10/350 µs) [N-PE] [Iimp]
Voltage protection level [UP]
Voltage protection level at 5kA [UP]
Voltage protection level [L-N] [UP]
Voltage protection level [L-N] at 5kA [UP]
Voltage protection level [N-PE] [UP]
Follow current extinguishing capability [N-PE] [Ifi]
Response time [tA]
Response time [L-N] [tA]
Response time [N-PE] [tA]
Temporary overvoltage (TOV) [UT]
Temporary overvoltage (TOV) [L-N] [UT]
Temporary overvoltage (TOV) [N-PE] [UT]
SPD according to EN 61643-11
SPD according to IEC 61643-1
Nominal discharge current (8/20 µs) [In]
Max. discharge current (8/20 µs) [Imax]
Max. mains-side overcurrent protection
Short-circuit withstand capability for max. mains-side overcurrent protection
Nominal AC voltage [UN]
TOV characteristics
Operating temperature range [TU]
Operating state/fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
Mounting
Enclosure material
Location category
Degree of protection
Capacity
Standards Information
Product Warranty
Type 2
Class II
20kA
40kA
125A gL/gG
50kA rms
230V
withstand
-40°C to +80°C
green (good)/red (replace)
1
1.5mm2/14AWG solid/flexible
35mm2/2AWG stranded-25mm2/4AWG flexible
35mm DIN rail per EN 60715
Thermoplastic, UL 94V0
Indoor
IP20
2 mods., DIN 43880
KEMA
Five Years**
Remote Contact Signaling
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals
Ordering Information
Changeover Contact
250V/0.1A
250V/0.1A; 125V/0.2A; 75V/0.5A
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Order from Catalog Numbers Above
* N-PE Surge arrester for location between neutral conductor and protective conductor in TT systems.
** See Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Bussmann Back Up Fuses
DIN Fuse Size
NH Fuse Part Number
00
125NHG00B
0
125NHG0B
01
125NHG01B
02
125NHG02B
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
For more information visit our website at www.bussmannasia.com
Surge Protection Made Simple ™ for IEC Applications
IEC Class II Surge Arrester for 120/240 and 230/400 Volt, 3-Pole TNC Systems
Description
The Bussmann ® IEC Class II 120/240 volt and 230/400 volt, threepole, modular surge arresters feature local, easy ID™ visual indication and
optional remote contact signaling. The unique module locking system fixes the
protection module to the base part. Modules can be easily replaced without
tools by simply depressing the release buttons. Integrated mechanical coding
between the base and protection module ensures against installing an
incorrect replacement module.
BSPM3150TNC(R)
BSPM3275TNC(R)
BSPM3385TNC(R)
120 Volt models are offered with a MCOV rating of 150 volts.
230 Volt models are offered with a MCOV rating of 275 or 385 volts.
TNC System Arresters
The features of these three-pole devices are for use in TN-C 120/240 volt or
230/400 volt systems (“3-0” circuit) against surges.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating
changeover contact for use as a break or make contact, according to circuit
concept.
Visual Status Indication
Remote Signal
Contact Available
MOV
Circuit Diagrams
Dimensions - mm
Thermal Disconnector
BSPM3150TNC(R), BSPM3275TNC(R), BSPM3385TNC(R)
Shown with optional remote contact signaling
Shown with optional remote contact signaling
For more information visit our website at www.bussmannasia.com
ORDERING INFORMATION
System Voltage/Poles
Max. Continuous operating AC voltage (MCOV) [UC]
Catalog Numbers:
Without Remote Signaling
With Remote Signaling
Replacement Module
MOV technology
120V/3
150V
BSPM3150TNC
BSPM3150TNCR
BPM150IEC
230V/3
275V
BSPM3275TNC
BSPM3275TNCR
BPM275IEC
230V/3
385V
BSPM3385TNC
BSPM3385TNCR
BPM385IEC
SPECIFICATIONS
Nominal AC voltage [UN]
Voltage protection level [UP]
Voltage protection level at 5kA [UP]
Short-circuit withstand capability for max. mains-side overcurrent protection
Temporary overvoltage (TOV) [UT]
Standards Information
Nominal discharge current (8/20 µs) [In]
Max. Discharge current (8/20 µs) [Imax]
SPD according to EN 61643-11
SPD according to IEC 61643-1
Response time [tA]
Max. mains-side overcurrent protection
TOV characteristics
Operating temperature range [TU]
Operating state/fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
Mounting
Enclosure material
Location category
Degree of protection
Capacity
Product Warranty
120/240V
<
_ 0.7kV
<
_ 0.55kV
50kArms
175V/5 sec
-15kA
230/400V
230/400V
<
_ 1.25kV
<
_ 1.75kV
<
_ 1kV
<
_ 1.35kV
50kArms
25kArms
335V/5 sec.
385V/5 sec
KEMA
-20kA
20kA
40kA
Type 2
Class II
<
_ 25 ns
125A gL/gG
withstand
-40°C to +80°C
Green (good)/Red (replace)
1
1.5mm2/14AWG solid/flexible
35mm2/2AWG stranded-25mm2/4AWG flexible
35mm DIN rail per EN 60715
Thermoplastic, UL 94V0
Indoor
IP20
3 mods., DIN 43880
Five Years*
REMOTE CONTACT SIGNALING
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals
Ordering Information
Changeover Contact
250V/0.1A
250V/0.1A; 125V/0.2A; 75V/0.5A
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Order from Catalog Numbers Above
* See Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Bussmann Back Up Fuses
DIN Fuse Size
NH Fuse Part Number
00
125NHG00B
0
125NHG0B
01
125NHG01B
02
125NHG02B
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
For more information visit our website at www.bussmannasia.com
Surge Protection Made Simple ™ for IEC Applications
IEC Class II Surge Arresters for 230/400 Volt, 4-Pole TNS & TT Systems
Description
The Bussmann ® IEC Class II 230/400 volt, four-pole, modular surge
arresters feature local, easy ID™ visual indication and optional remote contact
signaling. The unique module locking system fixes the protection module to
the base part. Modules can be easily replaced without tools by simply
depressing the release buttons. Integrated mechanical coding between the
base and protection module ensures against installing an incorrect
replacement module.
BSPM4275TNS(R)
BSPH4275TT(R)
BSPH4320TT(R)
BSPH4385TT(R)
These 230 Volt models are offered with MCOV ratings of 275, 320 or 385
volts.
TNS System Arrester
The features of these four-pole devices are for use in TNS 230/400 volt
systems (“4-0” circuit) against surges.
TT System Arrester
The features of these four-pole devices are for use in TT and TN-S 230/400
volt systems (“3+1” circuit) against surges.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating
changeover contact for use as a break or make contact, according to circuit
concept.
Dimensions - mm
Visual Status Indication
Remote Signal
Contact Available
Circuit Diagrams
BSPM4275TNS(R)
Shown with optional
remote contact
signaling
MOV
Thermal Disconnector
Gas Discharge Tube (single)
BSPH4275TT(R)
BSPH4320TT(R)
BSPH4385TT(R)
Shown with optional remote contact signaling
For more information visit our website at www.bussmannasia.com
Shown with optional
remote contact
signaling
ORDERING INFORMATION
System Voltage/Poles
Max. continuous operating AC voltage (MCOV) [UC]
Max. continuous operating AC voltage (MCOV) [L-N] [UC]
Max. continuous operating AC voltage [N-PE] [UC]
Catalog Numbers:
Without Remote Signaling
With Remote Signaling
Replacement Modules:
MOV technology
Spark Gap technology
230V/4
275V
--BSPM4275TNS
BSPM4275TNSR
BPM275IEC
--
230V/4
230V/4
230V/4
---275V
320V
385V
255V
255V
255V
BSPH4275TT BSPH4320TT BSPH4385TT
BSPH4275TTR BSPH4320TTR BSPH4385TTR
BPM275IEC
BPM320IEC
BPM385IEC
BPSNPEIEC*
BPSNPEIEC*
BPSNPEIEC*
-<
_ 1.25kV
<
_ 1kV
----<
_ 25 ns
--335V/5 sec.
---
12kA
12kA
12kA
------<
_ 1.25kV
<
_ 1.5kV
<
_ 1.75kV
<
_ 1kV
<
_ 1.2kV
<
_ 1.35kV
<
_ 1.5kV
<
_ 1.5kV
<
_ 1.5kV
100Arms
100Arms
100Arms
---<
_ 25 ns
<
_ 25 ns
<
_ 25 ns
<
_ 100 ns
<
_ 100 ns
<
_ 100 ns
---335V/5 sec.
335V/5 sec.
385V/5 sec.
1200V/200 ms 1200V/200 ms 1200V/200 ms
SPECIFICATIONS
Lightning impulse current (10/350 µs) [N-PE] [Iimp]
Voltage protection level [UP]
Voltage protection level at 5kA [UP]
Voltage protection level [L-N] [UP]
Voltage protection level [L-N] at 5kA [UP]
Voltage protection level [N-PE] [UP]
Follow current extinguishing capability [N-PE] [Ifi]
Response time [tA]
Response time [L-N] [tA]
Response time [N-PE] [tA]
Temporary overvoltage (TOV) [UT]
Temporary overvoltage (TOV) [L-N] [UT]
Temporary overvoltage (TOV) [N-PE] [UT]
Short-circuit withstand capability for max.
mains-side overcurrent protection
SPD according to EN 61643-11
SPD according to IEC 61643-1
Nominal AC voltage [UN]
Nominal discharge current (8/20 µs) [In]
Max. discharge current (8/20 µs) [Imax]
Max. mains-side overcurrent protection
TOV characteristics
Operating temperature range [TU]
Operating state/fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
Mounting
Enclosure material
Location category
Degree of protection
Capacity
Standards Information
Product Warranty
50kArms
50kArms
25kArms
25kArms
Type 2
Class II
230/400V
20kA
40kA
125A gL/gG
withstand
-40°C to +80°C
green (good)/red (replace)
1
1.5mm2/14AWG solid/flexible
35mm2/2AWG stranded-25mm2/4AWG flexible
35mm DIN rail per EN 60715
Thermoplastic, UL 94V0
Indoor
IP20
4 mods., DIN 43880
KEMA
Five Years**
REMOTE CONTACT SIGNALING
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals
Ordering Information
Changeover Contact
250V/0.1A
250V/0.1A; 125V/0.2A; 75V/0.5A
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Order from Catalog Numbers Above
* N-PE Surge arrester module for location between neutral conductor and protective conductor in TT systems.
** See Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Bussmann Back Up Fuses
DIN Fuse Size
NH Fuse Part Number
00
125NHG00B
0
125NHG0B
01
125NHG01B
02
125NHG02B
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
For more information visit our website at www.bussmannasia.com
Download